MIDDLE SCHOOL MS-T101-MS-T101A.pdf

PDF 561 KB Posted

Attached to
2025 E-Rate Network Cabling Additions
Solicitation number
RFP-SCC-250000001194-3
Issued by
Genesee County, Michigan

About this file

This is a structured cabling design drawing for Swartz Creek Community Schools' Swartz Creek Middle School, created by Convergent Technology Partners in December 2024/January 2025. The drawing shows a floor plan layout for Unit A of the middle school building with detailed specifications for Category 6A UTP cable installations. The plan includes locations for wall and ceiling UTP locations, telecom cabinets, telecom bus-bars, and firesafe cabinets throughout various rooms including classrooms, offices, band room, practice rooms, kitchen areas, and cafeteria.

The technical specifications require all UTP cable to meet ANSI/TIA Category 6A standards, with wall locations to be installed in surface-mounted single-gang back boxes with white two-port faceplates. The installation includes specific requirements for cable concealment in contractor-provided raceways below ceiling, service loops for ceiling locations, white 8P/8C (RJ45) jack terminations, and grounding for all cabinets. The drawing provides detailed general notes for installation standards, including placement instructions relative to whiteboards and standard mounting heights.

View the file

Other files

Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

UNIT A

UNIT B

0' 5' 10' 20' 30' 40' 50'

NOT TO SCALE - BAR SCALE APPROXIMATE. FIELD VERIFY ALL DIMENSIONS

1 1

1 1

B

A

C D

E

FF

GENERAL NOTES

1. ALL UTP CABLE SHALL BE ANSI/TIA CATEGORY 6A.

PLACE WALL LOCATIONS IN A SURFACE MOUNTED

SINGLE-GANG BACK BOX WITH A WHITE TWO

PORT FACEPLATE.

2. THE UNUSED TOP PORT OF THE FACEPLATE IS TO

BE FILLED WITH A BLANK KEYSTONE JACK

INSERT.

3. PLACE WALL LOCATIONS CENTERED BELOW

WHITEBOARD AT STANDARD HEIGHT.

4. LOCATIONS WITHOUT WHITEBOARDS, CENTER

THE INSTALLATION ON THE WALL AT STANDARD

HEIGHT.

5. ALL CABLE BELOW CEILING SHALL BE

CONCEALED IN RACEWAY PROVIDED BY

CONTRACTOR.

6. PROVIDE CEILING LOCATION WITH SERVICE LOOP

LONG ENOUGH TO REACH THE FARTHEST

LOCATION IN THE ASSOCIATED ROOM. SECURELY

FASTEN SERVICE LOOP TO STRUCTURE.

7. TERMINATE ALL CATEGORY 6A CABLES ON WHITE

8P/8C (RJ45) JACKS.

8. LOCATION OF BUS BLOCKS ARE ESTIMATED, USE

BEST PRACTICES FOR INSTALLATION LOCATION.

9. FOR ESTIMATES ASSUME ALL CABINETS NEED

GROUNDING.

TGB

SYMBOL LEGEND

WALL UTP LOCATION, QTY AS

NOTED

CEILING UTP LOCATION, QTY AS

NOTED

TELECOM CABINET

TELECOM BUS-BAR

REPLACE CABINETR

C O N V E R G E N T 6197 Miller Road Suite 4 Swartz Creek, MI 48473

Phone: 810.720.3820 www.ctpartners.net

T E C H N O L O G Y P A R T N E R S

TECHNOLOGY DESIGN I CONSULTING I PLANNING

1/27/2025 DESIGN DLF

12/17/2024 DESIGN EGH

DATE ISSUE AUTHOR

SWARTZ CREEK

COMMUNITY SCHOOLS

STRUCTURED CABLING

SWARTZ CREEK

MIDDLE SCHOOL

MS-T101A

KEYMAP

101A

NTS

M.S. UNIT A

Sheets and Views
MS-T101A

File details come from the government source that posted it. Updated .