MIDDLE SCHOOL MS-T101-MS-T101A.pdf
PDF 561 KB Posted
- Attached to
- 2025 E-Rate Network Cabling Additions
- Solicitation number
- RFP-SCC-250000001194-3
- Issued by
- Genesee County, Michigan
About this file
This is a structured cabling design drawing for Swartz Creek Community Schools' Swartz Creek Middle School, created by Convergent Technology Partners in December 2024/January 2025. The drawing shows a floor plan layout for Unit A of the middle school building with detailed specifications for Category 6A UTP cable installations. The plan includes locations for wall and ceiling UTP locations, telecom cabinets, telecom bus-bars, and firesafe cabinets throughout various rooms including classrooms, offices, band room, practice rooms, kitchen areas, and cafeteria.
The technical specifications require all UTP cable to meet ANSI/TIA Category 6A standards, with wall locations to be installed in surface-mounted single-gang back boxes with white two-port faceplates. The installation includes specific requirements for cable concealment in contractor-provided raceways below ceiling, service loops for ceiling locations, white 8P/8C (RJ45) jack terminations, and grounding for all cabinets. The drawing provides detailed general notes for installation standards, including placement instructions relative to whiteboards and standard mounting heights.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UNIT A
UNIT B
0' 5' 10' 20' 30' 40' 50'
NOT TO SCALE - BAR SCALE APPROXIMATE. FIELD VERIFY ALL DIMENSIONS
1 1
1 1
B
A
C D
E
FF
GENERAL NOTES
1. ALL UTP CABLE SHALL BE ANSI/TIA CATEGORY 6A.
PLACE WALL LOCATIONS IN A SURFACE MOUNTED
SINGLE-GANG BACK BOX WITH A WHITE TWO
PORT FACEPLATE.
2. THE UNUSED TOP PORT OF THE FACEPLATE IS TO
BE FILLED WITH A BLANK KEYSTONE JACK
INSERT.
3. PLACE WALL LOCATIONS CENTERED BELOW
WHITEBOARD AT STANDARD HEIGHT.
4. LOCATIONS WITHOUT WHITEBOARDS, CENTER
THE INSTALLATION ON THE WALL AT STANDARD
HEIGHT.
5. ALL CABLE BELOW CEILING SHALL BE
CONCEALED IN RACEWAY PROVIDED BY
CONTRACTOR.
6. PROVIDE CEILING LOCATION WITH SERVICE LOOP
LONG ENOUGH TO REACH THE FARTHEST
LOCATION IN THE ASSOCIATED ROOM. SECURELY
FASTEN SERVICE LOOP TO STRUCTURE.
7. TERMINATE ALL CATEGORY 6A CABLES ON WHITE
8P/8C (RJ45) JACKS.
8. LOCATION OF BUS BLOCKS ARE ESTIMATED, USE
BEST PRACTICES FOR INSTALLATION LOCATION.
9. FOR ESTIMATES ASSUME ALL CABINETS NEED
GROUNDING.
TGB
SYMBOL LEGEND
WALL UTP LOCATION, QTY AS
NOTED
CEILING UTP LOCATION, QTY AS
NOTED
TELECOM CABINET
TELECOM BUS-BAR
REPLACE CABINETR
C O N V E R G E N T 6197 Miller Road Suite 4 Swartz Creek, MI 48473
Phone: 810.720.3820 www.ctpartners.net
T E C H N O L O G Y P A R T N E R S
TECHNOLOGY DESIGN I CONSULTING I PLANNING
1/27/2025 DESIGN DLF
12/17/2024 DESIGN EGH
DATE ISSUE AUTHOR
SWARTZ CREEK
COMMUNITY SCHOOLS
STRUCTURED CABLING
SWARTZ CREEK
MIDDLE SCHOOL
MS-T101A
KEYMAP
101A
NTS
M.S. UNIT A