Substations Upgrade Building 2-Phase 1 Combined Drawings.pdf

PDF 36 MB Posted

Attached to
Z1DA--642-22-104 | Upgrade Substation Building 2 Phase 1 | Kevin Rodgers | NCO 4 Construction East (VA-26-00030476)
Solicitation number
36C24426R0088
Issued by

About this file

This file is a combined drawings document for the Substations Upgrade Building 2-Phase 1 project. The drawings provide architectural and engineering specifications for the upgrade of Substation Building 2, Phase 1, at the Philadelphia VA Medical Center (PHL CMCVAMC) under solicitation number 36C24426R0088. The project is being executed through the Department of Veterans Affairs Veterans Health Administration, Veterans Integrated Service Network 4.

The combined drawings document contains the technical specifications, architectural plans, and engineering schematics necessary for contractors to understand the scope of work for the substation building upgrade. As a drawing set rather than a standalone specification document, it serves as a visual and technical reference that establishes the physical requirements, layout modifications, and construction standards for Phase 1 of the upgrade project. Contractors responding to solicitation 36C24426R0088 should reference these drawings in conjunction with the Statement of Work, Performance Work Statement, and other contract documents to develop accurate bids and project execution plans for the substation building renovation work.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

S S S S

S S S

S S S S

S S

S S S S S

S S S

S S

S S

S S

S S

S S

S

S S

S S

S S

S S S S

S S

SS

SSSSS

SSSSS

S S

S

HZ

LINEN/TRASH CHUTE

WITH 2 HR FIRE BARRIER

COMPARTMENT ID

SUITE ID

EXIT

HAZARDOUS AREA

HAZARDOUS AREA

(MULTIPLE ROOMS)

HZ

X-X-X1

DISTANCE SMOKE BARRIER

1 HOUR FIRE SMOKE BARRIER

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

DISTANCE TO EXIT

CONSTRUCTION AREA

EXIT STAIRWELL

2 HOUR FIRE SMOKE BARRIER

1 HOUR SMOKE BARRIER

PB.1

HZ

HZ

HZ

HZHZ

CRAWL SPACE

LOADING DOCK

HZ

HZ

HZ

FEMALE

TOILET

B2B117

MALE

TOILET

B2B118

MECHANICAL

EQUIPMENT

B2A105

ELECTRIC

ROOM

B2A104

MECHANICAL

EQUIPMENT

B2A103

WAREHOUSE

B2A117A

STERILE

STORAGE

B2A116

H.A.C.

B2A118B

TEL. CLO.

B2A117

E.C.

B2A116

MEN'S

LOCKER

B2A115A

HALLWAY

B2A115

WOMEN'S

LOCKER

B2A115D

CLERICAL

OFFICE

B2A114

SPD

OFFICE

B2A114C

E.C.

B2A102

TEL. CLO.

B2A101

STO.

B2A100

GARAGE

PASSENGER

ELEVATOR

LOBBY

CB2-1STAIR

No. 11

SPS

LOUNGE

B2A107

VEST

B2A108

MALE

LOCKERS

B2A108

H.A.C.

B2A109C

STORAGE

B2A109D

E.C.

B2A109F

STAIR

No. 12

CART LIFT

B2A140

MECH.

EQUIP.

B2A109H

LOBBY

CB2-5

ELEVATOR

MACHINE

ROOM

B2B105e

ROOM

B2A144

FEMALE

LOCKERS

B2A110A

VEST

B2A110

STORAGE

B2B119

OFFICE

B2B131a

SUPERVISORS,

TECHS &

CLERKS

B2B131

PRODUCT

& SERV.

CHIEF

B2B131b

INGREDIENT

CONTROL

B2B125

FOOD

STORAGE

B2B121 H.A.C.

B2B120

B2B115

NUTRITION

THERAPY

CHIEF

B2B136

SEC./

WAITING

B2B137

PROG.

MGT. &

PLANNING

CHIEF

B2B138

CLEAN

DISH

STORAGE

B2B139

DISHWASHING

B2B139b

SANITATION

SUPPLY

STORAGE

B2B139a

CHIEF

B2B104

SUBSTANCE

STORAGE

REFRIGERATOR

B2B105b

MECH.

EQUIP.

SHAFT

BREAK

DOWN

ROOM

B2A118A

HALL

B2A119

CORRIDOR

CB2-3

RECEIVING

& ISSUE

AREA

B2B105

VESTIBULE

B2B113

OFFICE

B2B114

FOOD

SERVICE

COORD.

CENTER

B2B135STORAGE

B2B135a TEL. CLO.

B2B134

ELEC. CLO.

B2B133

CLEAN

EQUIP.

FACIL.

B2B140

STORAGE/

FUTURE

MECH.

SHAFT

B2B132b

STORAGE/

FUTURE

MECH.

SHAFT

B2B132a

H.A.C.

B2B130

DAIRY

REFRIGERATOR

B2B126

VEG.

REFRIGERATOR

B2B124

ELECTRICAL

ROOM

B2B127

MEAT

REFRIGERATOR

B2B123

VEG.

FREEZER

B2B124a

MEAT

FREEZER

B2B123a

NON-FOOD

STORAGE

B2B122

UNPOSTED

STOCK

HOLDING

AREA

B2B113a

TEL. CLO.

B2B105g

E.C.

B2B105h

TOILET

ROOM

B2B105f

ELEV.

F-19

POT WASH

CENTER

B2B129

TRAY

MAKE-UP

B2B132

CORRIDOR

CB2-17

CORRIDOR

CB2-15

CORRIDOR

CB2-16

FOOD

PROCESSING

PREPARATION

B2B128

FLAMMABLE

STORAGE

VAULT

B2B110

GAS

STORAGE

B2B111

GAS

STORAGE

B2B112

W/C STAFF

TOILET

B2B102

W/C STAFF

TOILET

B2B101

H.A.C.

B2B103

SPD

OFFICE

B2B100

SOUTH

PASSENGER

ELEVATOR

LOBBY

CB2-6

SOUTH

SERVICE

ELEVATOR

LOBBY

CB2-10

CORRIDOR

CB2-12

CORRIDOR

CB2-11

CORRIDOR

CB2-7

CORRIDOR

CB2-8

CORRIDOR

CB2-9

FOOD

SERVICE

ELEV.

LOBBY

B2B141

STAIR

NO. 10

MECH.

SHAFT

B2B143

MECH.

SHAFT

B2B144

NARCOTICS

VAULT

B2B105d

DRUG

REFRIGERATOR

B2B105c

FORMS

ROOM

B2A118A

MANUAL

EQUIP

WASH

B2A109B

DECONTAMINATION

ROOM

B2A109

SHOWER

AUTO CAR

WASH

B2A109A

CART LIFT

B2A109G

SPD

STORAGE

B2A111

CORRIDOR

CB2-4

EXIT

CORRIDOR

CB2-13

VEST.

B2B107

VEST.

B2B108

ELECTRIC

ROOM

B2B106

MECHANICAL

EQUIPMENT

B2B109

STAIR

No. 8

CORRIDOR

CB2-8

PREP.

STERILIZATION

B2A112

MECH.

EQUIP.

SHAFT

OI & T

WAREHOUSE

B2A117

MAIL

ROOM

B2A118

CRAWL SPACE

CRAWL SPACE

BATTERY

CHARGING

B2B105I

BREAK

ROOM

2BB105A

DISTANCE EXIT:

262' - 0"

DISTANCE EXIT:

196' - 0"

DISTANCE EXIT:

124' - 0"

HZ

STAIR

.3"/OCC

CODE MIN:

PROVIDED:

(E)

36" * 36.5"

24"

DOOR

.2"/OCC

CODE MIN:

PROVIDED:

(E)

32" 44"

16"

CORRIDOR

.2"/OCC

CODE MIN:

PROVIDED:

(E)

44" 73"

16"

DOOR

.2"/OCC

CODE MIN:

PROVIDED:

(E)

32" 70"

16"

DOOR

.2"/OCC

CODE MIN:

PROVIDED:

(E)

32"

39.5"

16"

CORRIDOR

.2"/OCC

CODE MIN:

PROVIDED:

(E)

44" 96"

16"

OFFICE

B2A119B

CLERICAL

OFFICE

B2A119C

CONFERENCE

ROOM

B2A119A

SCOPE

PROCESSING

B2A113

SCOPE

DRY

B2A113A

ROOM

B2B105J

PANDEMIC

STORAGE

B2B105K

PB.1

2 HOURS BUILDING

OCCUPANCY SEPARATION

STAIR

No. 9

2 HOURS BUILDING

OCCUPANCY SEPARATION

CORRIDOR

CB2-2

CORRIDOR

CB2-8a

CORRIDOR

CB2-7

CORRIDOR

CB2-12

SERVICE

ELEVATOR

S-9

SERVICE

ELEVATOR

S-10

SERVICE

ELEVATOR

S-11

SERVICE

ELEVATOR

S-12

PASSENGER

ELEVATOR

P-15

PASSENGER

ELEVATOR

P-16

PASSENGER

ELEVATOR

P-13

PASSENGER

ELEVATOR

P-14

OFFICE

B2A114A

OFFICE

B2A114B

CORRIDOR

CB2-13

CORRIDOR

CB2-12

CORRIDOR

CB2-4

CORRIDOR

CB2-4

CORRIDOR

CB2-4

ANTE-ZONE

CB2-4A

N

P N

KEYPLAN: PIPE BASEMENT

BUILDING 2

BUILDING 1

BUILDING 21

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

ACELAJLH

C:

\U se rs\

AA

hm ed \D oc um en ts\

PH

ILA

V A

MA

ST

ER

F

ILE

_k sc hn ec kE

VB

MP

.rv t

9/1 1/2

3 3

:16 :25

P M

2-LS-00.2

BUILDING 2 PIPE BASEMENT/ GROUND FLOOR- LIFE

SAFETY PLAN

10-21-2024

Corporal Michael J. Crescenz VA Medical Center Philadelphia

642-22-124LIFE SAFETY ASSESSMENT

22-USDVA-09

LIFE SAFETY LEGEND

COMPARTMENT KEY PLAN

BUILDING 2- PIPE BASEMENT EXISTING INDUSTRIAL OCCUPANCY

COMPARTMENT

ID

COMPARTMENT

SQ. FT.

OCCUPANCY

LOAD

AREA USE DISTANCE

TO SMOKE

DISTANCE

TO EXIT

SPRINKLER

SYSTEM

BUILDING 2

PB.1 62840 SF 418 BUSINESS - VARIES Yes Grand total 62840 SF

COMPARTMENT SCHEDULE

DISCLAIMER:

LIFE SAFETY PLANS DEPICT INFORMATION

PERTAINING TO NFPA 101-2021 EDITION ONLY.

THIS PLAN IS SOLELY FOR THE

REPRESENTATION OF THOSE FIRE

PROTECTION / LIFE SAFETY FEATURES

NECESSARY FOR A STATEMENT OF

CONDITIONS LIFE SAFETY ASSESSMENT AS

REQUIRED BY THE JOINT COMMISSION (TJC). IT

SHOULD NOT BE CONSIDERED AN ACCURATE

PLAN FOR ARCHITECTURE OR ANY OTHER

DESIGN OR CONSTRUCTION DISCIPLINE.

Revisions: Date:

AJE25

Text Box

REFERENCE DRAWING ONLY

Drawing Title

Chief Engineer Approval

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. of

CONSULTANT FIRM: ARCHITECTS/ENGINEERS:

Office of Facility Management Service on e e igh th inc h = on e f oo t

IF

T

H

IS

S H

EE

T

IS

N

O T

" X

2"

FU

LL

S

IZ

E, U

SE

G

R

AP

H

IC

S C

AL

ES

on e i nc h = on e f oo t

6" 6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Name, Title Prevention Coordinator

Name Title

Name Title

Name Title

Name Title

DESIGN CHANGE APPROVED

DESCRIPTION DATE

SEAL: SEAL:

BID DOCUMENTS October-21-2024

ART - ARCHITECTURE - ENGINEERING

2787 HILL ROAD

VIENNA, VA 22181

FRANK V. STURGEON, AIA

AMBRISH RASTOGI, PE

703.938.5226

FRANK@ADG10.COM

A DESIGN GROUP, LLC

AutoCAD SHX Text

ABBREVIATIONS

AutoCAD SHX Text

AD

AutoCAD SHX Text

AHU

AutoCAD SHX Text

AP

AutoCAD SHX Text

BIW

AutoCAD SHX Text

CC

AutoCAD SHX Text Db

AutoCAD SHX Text dB

AutoCAD SHX Text Dp

AutoCAD SHX Text

ACCESS DOOR

AutoCAD SHX Text

AIR HANDLING UNIT

AutoCAD SHX Text

ACCESS PANEL

AutoCAD SHX Text

BACKWARD INCLINED WHEEL

AutoCAD SHX Text

COOLING COIL

AutoCAD SHX Text

DRY BULB TEMPERATURE

AutoCAD SHX Text

DECIBELS

AutoCAD SHX Text

DEWPOINT TEMPERATURE

AutoCAD SHX Text E/A

AutoCAD SHX Text

ECC

AutoCAD SHX Text

EER

AutoCAD SHX Text

EF

AutoCAD SHX Text

EX.

AutoCAD SHX Text

FLR.

AutoCAD SHX Text

F.DPR.

AutoCAD SHX Text

HC

AutoCAD SHX Text

HP

AutoCAD SHX Text

EXHAUST AIR

AutoCAD SHX Text

ENGINEERING CONTROL CENTER

AutoCAD SHX Text

ENERGY EFFICIENCY RATIO

AutoCAD SHX Text

EXHAUST FAN

AutoCAD SHX Text

EXISTING

AutoCAD SHX Text

FLOOR

AutoCAD SHX Text

FIRE DAMPER

AutoCAD SHX Text

HEATING COIL

AutoCAD SHX Text

HORSEPOWER

AutoCAD SHX Text

MER

AutoCAD SHX Text

MAX.

AutoCAD SHX Text

MIN.

AutoCAD SHX Text

NOM.

AutoCAD SHX Text O/A

AutoCAD SHX Text P

AutoCAD SHX Text

PD

AutoCAD SHX Text R/A

AutoCAD SHX Text Rh

AutoCAD SHX Text S/A

AutoCAD SHX Text

SP

AutoCAD SHX Text

MECHANICAL ROOM

AutoCAD SHX Text

MAXIMUM

AutoCAD SHX Text

MINIMUM

AutoCAD SHX Text

NOMINAL

AutoCAD SHX Text

OUTDOOR AIR

AutoCAD SHX Text

PUMP

AutoCAD SHX Text

PRESSURE DROP

AutoCAD SHX Text

RETURN AIR

AutoCAD SHX Text

RELATIVE HUMIDITY

AutoCAD SHX Text

SUPPLY AIR

AutoCAD SHX Text

STATIC PRESSURE

AutoCAD SHX Text V

AutoCAD SHX Text

VD

AutoCAD SHX Text Wb

AutoCAD SHX Text

VALVE

AutoCAD SHX Text

VOLUME DAMPER (MANUAL

AutoCAD SHX Text

OPPOSED BLADE)

AutoCAD SHX Text

WET BULB TEMPERATURE

AutoCAD SHX Text

%%UDRAWING SYMBOLS

AutoCAD SHX Text

AutoCAD SHX Text H4

AutoCAD SHX Text H7

AutoCAD SHX Text A

AutoCAD SHX Text

26-SF 3

AutoCAD SHX Text

DETAIL NUMBER

AutoCAD SHX Text

DRAWING NUMBER WHERE SHOWN

AutoCAD SHX Text

SECTION LETTER

AutoCAD SHX Text

TYPICAL UNIT NO.

AutoCAD SHX Text

BUILDING NO. WHERE EQUIPMENT IS LOCATED.

AutoCAD SHX Text

SUPPLY FAN NO.3 IN BUILDING NO.26

AutoCAD SHX Text

EQUIPMENT ABBREVIATION (SUPPLY FAN)

AutoCAD SHX Text

DRAWING NUMBER WHERE DRAWN

AutoCAD SHX Text

%%UDUCTWORK SYMBOLS

AutoCAD SHX Text

LIMIT OF DEMOLITION

AutoCAD SHX Text

(WALL TYPE)

AutoCAD SHX Text

DN

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

SUPPLY DUCT (UP & DOWN)

AutoCAD SHX Text

EXHAUST DUCT (UP & DOWN)

AutoCAD SHX Text

SUPPLY TOP REGISTER OR GRILLE (WALL TYPE)

AutoCAD SHX Text

EXHAUST OR RETURN CEILING REGISTER OR GRILLE

AutoCAD SHX Text

EXHAUST OR RETURN REGISTER OR TOP GRILLE

AutoCAD SHX Text

VANED ELBOW & AIR SPLIT TYPE DUCT TAKE-OFF

AutoCAD SHX Text

CONNECT NEW DUCT TO EXISTING DUCT

AutoCAD SHX Text D

AutoCAD SHX Text

INCLINED RISE, IN DIRECTION OF AIR FLOW

AutoCAD SHX Text

INCLINED DROP, IN DIRECTION OF AIR FLOW

AutoCAD SHX Text R

AutoCAD SHX Text 10x8

AutoCAD SHX Text

VANED ELBOW (PROVIDE ALL SQUARE OR

AutoCAD SHX Text

RECTANGULAR ELBOWS WITH VANES EVEN IF

AutoCAD SHX Text

SYMBOL IS MISSING)

AutoCAD SHX Text

VANED ELBOW (SHORT RADIUS)

AutoCAD SHX Text

STANDARD RADIUS ELBOW

AutoCAD SHX Text NEW DUCT (WIDTH x DEPTH)

AutoCAD SHX Text

FIRE DAMPER

AutoCAD SHX Text

F. DPR

AutoCAD SHX Text

VD

AutoCAD SHX Text

DUCT WITH SOUND LINING

AutoCAD SHX Text

MANUAL VOLUME DAMPER

AutoCAD SHX Text

EXISTING EQUIPMENT/PIPING/DUCT

AutoCAD SHX Text

SUPPLY

AutoCAD SHX Text

RETURN

AutoCAD SHX Text 45%%d

AutoCAD SHX Text RETURN, NO SPLITTER (45%%d TAP)

AutoCAD SHX Text

STANDARD BRANCH SUPPLY OR

AutoCAD SHX Text

MANUAL SPLITTER DAMPER

AutoCAD SHX Text 45%%d

AutoCAD SHX Text

%%UAIR CONDITIONING

AutoCAD SHX Text

CHILLED WATER SUPPLY

AutoCAD SHX Text

CHILLED WATER RETURN

AutoCAD SHX Text

DRAIN LINE

AutoCAD SHX Text

CH

AutoCAD SHX Text

CHR

AutoCAD SHX Text

%%UGENERAL SYMBOLS

AutoCAD SHX Text

LIMIT OF DEMOLITION

AutoCAD SHX Text

DIRECTION OF FLOW

AutoCAD SHX Text

SIDE CONNECTION

AutoCAD SHX Text BOTTOM CONNECTION, 45%%d OR 90%%d

AutoCAD SHX Text TOP CONNECTION, 45%%d OR 90%%d

AutoCAD SHX Text

DIRECTION OF PIPE PITCH (DOWN)

AutoCAD SHX Text

UNION

AutoCAD SHX Text

RISE OR DROP IN PIPE

AutoCAD SHX Text

CAPPED OUTLET

AutoCAD SHX Text

AND EXISTING WORK

AutoCAD SHX Text

ORIFICE UNION

AutoCAD SHX Text

POINT OF CONNECTION BETWEEN NEW

AutoCAD SHX Text

PRESSURE GAGE

AutoCAD SHX Text

THERMOMETER

AutoCAD SHX Text

STRAINER

AutoCAD SHX Text

%%UVALVE SYMBOLS

AutoCAD SHX Text

BALL VALVE

AutoCAD SHX Text

GLOBE VALVE

AutoCAD SHX Text

GATE VALVE WITH 3/4 " HOSE ADAPTER

AutoCAD SHX Text

CHECK VALVE

AutoCAD SHX Text

ANGLE GLOBE VALVE

AutoCAD SHX Text

BUTTERFLY VALVE

AutoCAD SHX Text

BALANCING VALVE

AutoCAD SHX Text

STRAIGHT-THRU MODULATING CONTROL VALVE

AutoCAD SHX Text

STRAIGHT-THRU TWO POSITION CONTROL VALVE

AutoCAD SHX Text

THREE-WAY MODULATING CONTROL VALVE

AutoCAD SHX Text

GATE VALVE

AutoCAD SHX Text

MANUAL AIR VENT

AutoCAD SHX Text

TEST PLUG (PRESSURE/TEMPERATURE)

AutoCAD SHX Text

%%UCONTROLS SYMBOLS

AutoCAD SHX Text T

AutoCAD SHX Text

GENERAL NOTES

AutoCAD SHX Text /(E)

AutoCAD SHX Text THE CONTRACTOR SHALL FURNISH AND INSTALL ALL SUPPORTS, HANGERS, EQUIPMENT, DUCT WORK, PIPING, WIRING, PANELS ETC., AS REQUIRED BY TRADE, AND SHALL PERFORM DEMOLITION AND MODIFICATION WORK, AS REQUIRED FOR COMPLETE AND OPERABLE SYSTEMS WITHOUT ADDITIONAL COST TO THE OWNER. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CERTIFICATES, INSPECTIONS, ETC., FOR ALL WORK DONE UNDER THIS CONTRACT. ALL WORK SHALL BE DONE IN COMPLIANCE WITH ALL LAWS, ORDINANCES, CODES, ETC. OF ANY GOVERNING BODY HAVING JURISDICTION AND IN FULL COMPLIANCE WITH VAMC REGULATIONS AND REQUIREMENTS. ALL APPLICABLE ITEMS SHALL BEAR THE UNDERWRITERS LABORATORIES (UL) LABEL AND SHALL BE FACTORY MUTUAL APPROVED. ALL EQUIPMENT SHALL BE NEW UNLESS SPECIFICALLY NOTED OTHERWISE ON THE DRAWINGS. ALL WORK SHALL BE CAREFULLY COORDINATED WITH ALL TRADES INVOLVED, AND THE CONTRACTOR SHALL PROVIDE PROPER CONNECTIONS, FITTINGS, VALVES, PIPING, ETC., FOR ALL EQUIPMENT FURNISHED BY THE OWNER OR THE TRADES INVOLVED IN THIS CONTRACT. DRAWINGS ARE TO BE CONSIDERED DIAGRAMMATIC AND DO NOT NECESSARILY INDICATE THE ACTUAL LOCATION OR ROUTING OF EQUIPMENT, PIPING, OR DUCTWORK. DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS CONDITIONS ALLOW TO COMPLETE THE INTENT OF THE CONTRACT. CONTRACTOR SHALL MAKE MINOR ADJUSTMENTS, OFFSETS, ELBOWS OR RESIZING OF DUCTS (WHILE MAINTAINING EQUIVALENT FREE AREA) AS REQUIRED BY ACTUAL FIELD CONDITIONS. THE RIGHT IS RESERVED BY THE ENGINEER TO MAKE MINOR CHANGES IN LOCATIONS AND ARRANGEMENTS, WHEN REQUIRED BY JOB DEVELOPMENT, WITHOUT ADDITIONAL COMPENSATION TO THE CONTRACTOR. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR THE LOCATION OF LIGHT FIXTURES AND OTHER CEILING MOUNTED ITEMS. THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS OF MANUFACTURED ITEMS REQUIRED ON THIS PROJECT, AS REQUIRED BY THE SPECIFICATION. A MINIMUM OF 8 COPIES SHALL BE SUBMITTED. SHEET METAL SHOP DRAWINGS SHALL BE SUBMITTED AT MINIMUM 1/4" SCALE. SHEET METAL SHOP DRAWINGS SHALL INCLUDE ONE ELECTRONIC COPY (CD), AND TWO HARD COPIES (REPRODUCIBLE BLACKLINE PRINTS). ENGINEER'S APPROVAL OF SHOP OR SETTING DRAWINGS SHALL ONLY BE CONSTRUED TO APPLY TO GENERAL LAYOUT AND CONFORMANCE TO THE DESIGN CONCEPT OF THE PROJECT AND FOR COMPLIANCE WITH THE GENERAL REQUIREMENTS OF THE CONTRACT DOCUMENTS. THE RESPONSIBILITY OF ANY DEVIATIONS FROM THE REQUIREMENTS OF THE CONTRACT DOCUMENTS SHALL REMAIN THE CONTRACTOR'S, UNLESS CONTRACTOR HAS, IN WRITING, SPECIFICALLY CALLED THE ENGINEER'S ATTENTION TO SUCH DEVIATIONS AT THE TIME OF SUBMISSION AND HAS RECEIVED THE ENGINEER'S WRITTEN APPROVAL OF SUCH DEVIATIONS. GENERAL CONTRACTOR TO PROVIDE ALL REQUIRED TEMPORARY UTILITIES AND PAY FOR ALL TEMPORARY AND PERMANENT UTILITIES UP TO SUBSTANTIAL COMPLETION, WHEN INSTALLED WORK IS READY FOR START-UP AND PRE- FUNCTIONAL TESTS. THE HVAC CONTRACTOR SHALL PERFORM ALL CUTTING AND PATCHING AS REQUIRED FOR THEIR RESPECTIVE WORK, EXCEPT THAT STRUCTURALLY FRAMED OPENINGS SHALL BE CUT AND FRAMED BY THE GENERAL CONTRACTOR. ALL HOLES IN MASONRY, FLOORS, AND WALLS SHALL BE CORE DRILLED. EDGES OF TRENCHES IN EXISTING CONCRETE FLOORS SHALL BE SAW CUT. MAINTAIN FIRE RATING OF FLOORS AND WALLS. MANUFACTURER'S NAMES GIVEN FOR EQUIPMENT ARE USED FOR THE BASIS OF SELECTION, NOT WITH INTENT TO LIMIT COMPETITION, UNLESS NOTED OTHERWISE. EQUIVALENT EQUIPMENT OF OTHER MANUFACTURERS WILL BE CONSIDERED FOR ACCEPTANCE AND INSTALLATION. LOCATE AND IDENTIFY ALL CONCEALED BUILDING SYSTEMS PRIOR TO EXECUTION OF THIS WORK INCLUDING CUTTING, EXCAVATING, AND/OR REMOVING ANY PART OF THE SYSTEM COMPONENTS FOR THE BUILDING CONSTRUCTION. CAREFULLY PERFORM ALL WORK TO PREVENT DAMAGE TO THE CONCEALED SYSTEMS OR STRUCTURE. ANY SUCH DAMAGE OR INJURIES RESULTING FROM PERFORMANCE OF THE WORK OF THIS CONTRACT IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR. DEMONSTRATE SYSTEM OPERATION TO COR. ALL PIPING AND DUCTS IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN A FURRED CHASE OR ABOVE THE SUSPENDED CEILING. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN OR INDICATED. TOTAL STATIC PRESSURE NOTED IN THE SCHEDULES INCLUDES DUCT SYSTEM, UNITS, FILTERS, COILS, ETC. FOR TYPICAL WATER AND HYDRONIC PIPING CONNECTIONS TO EQUIPMENT SEE STANDARD EQUIPMENT DETAILS. DIFFUSER, REGISTER AND GRILLE SIZES SHOWN ON FLOOR PLANS ARE NECK SIZES. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING COILS SHALL BE MADE TO PROVIDE COUNTER FLOW BETWEEN WATER AND AIR. PROVIDE SEISMIC-RESTRAINT HANGERS AND SUPPORT FOR ALL HVAC SYSTEMS, DUCT WORK, EQUIPMENT, PIPING, ETC. AS PER SEISMIC DESIGN OF BUILDINGS, VA DESIGN GUIDES LINES AND UNIFIED FACILITIES CRITERIA (UFC), UFC 3-310-04, 1 JUNE 2013 (OR) LATEST EDITION.

AutoCAD SHX Text 15.

AutoCAD SHX Text 14.

AutoCAD SHX Text 12.

AutoCAD SHX Text 13.

AutoCAD SHX Text 11.

AutoCAD SHX Text 10.

AutoCAD SHX Text 9.

AutoCAD SHX Text 8.

AutoCAD SHX Text 7.

AutoCAD SHX Text 5.

AutoCAD SHX Text 6.

AutoCAD SHX Text 4.

AutoCAD SHX Text 3.

AutoCAD SHX Text 2.

AutoCAD SHX Text 1.

AutoCAD SHX Text

THERMOSTAT

AutoCAD SHX Text M

AutoCAD SHX Text

MOTORIZED DAMPER

AutoCAD SHX Text

(TYP.)

AutoCAD SHX Text

TYPICAL

AutoCAD SHX Text

VIF

AutoCAD SHX Text

VERIFY IN FIELD

AutoCAD SHX Text

TO BE REMOVED

AutoCAD SHX Text COMMISSIONING EFFORTS SHOULD BE COORDINATED BY THE GENERAL CONTRACTOR WITH COR, SHALL INCLUDE (AT A MINIMUM) THE CONTROLS CONTRACTOR, BALANCING CONTRACTOR, FACTORY REPRESENTATIVES FOR THE EQUIPMENT MANUFACTURERS, AND THE MECHANICAL CONTRACTOR. COMMISSIONING SHALL BE IN ACCORDANCE WITH ASHRAE "GUIDELINE 1", LATEST VERSION. COMMISSIONING EFFORTS SHALL BE COORDINATED WITH VAMC COR AND BUILDING OPERATING PERSONNEL WHO SHALL BE FULL PARTICIPANTS IN ALL OPERATIONS. AS PART OF THIS PROCESS, PROVIDE INSTRUCTION PERIOD TO OWNER DESIGNATED PERSONNEL, DEMONSTRATING TYPICAL SERVICE, MAINTENANCE AND TROUBLE-SHOOTING PROCEDURES FOR THE VARIOUS SYSTEMS. INSTRUCTION PERIOD SHALL BE NO LESS THAN EIGHT (8) HOURS, SCHEDULED AT OWNER'S CONVENIENCE. COMMISSIONING SHALL INCLUDE BUT NOT BE LIMITED TO AIR HANDLING UNITS, CONTROLS, AIR & WATER DISTRIBUTION SYSTEMS, ETC.

AutoCAD SHX Text

NOTE-COMMISSIONING WORK:

AutoCAD SHX Text 2.

AutoCAD SHX Text 3.

AutoCAD SHX Text 1.

AutoCAD SHX Text 4.

AutoCAD SHX Text

20. COORDINATION DRAWINGS: A. SUBMIT COORDINATION DRAWINGS, AT A MINIMUM OF 1/4'' SCALE, OF ALL TRADES INCLUDING BUT NOT LIMITED TO EQUIPMENT, SUBMIT COORDINATION DRAWINGS, AT A MINIMUM OF 1/4'' SCALE, OF ALL TRADES INCLUDING BUT NOT LIMITED TO EQUIPMENT, ARCHITECTURAL ITEMS, STRUCTURAL MEMBERS, SHEET METAL DUCTWORK, PIPING, LIGHT FIXTURES, CONDUITS, CABLE TRAYS, FIRE PROTECTION AND ALARM SYSTEMS, SECURITY DEVICES, ETC. B. THE COORDINATION DRAWINGS SHALL BE BASED ON THE ACTUAL FIELD CONDITIONS. CONTRACTOR SHALL ENSURE THAT WORK IN EACH PHASE THE COORDINATION DRAWINGS SHALL BE BASED ON THE ACTUAL FIELD CONDITIONS. CONTRACTOR SHALL ENSURE THAT WORK IN EACH PHASE IS CARRIED OUT WITHOUT ANY DISRUPTION OF UTILITIES TO AREA IN OTHER PHASES. C. CONTRACTOR SHALL FIELD COORDINATE TO PROVIDE TEMPORARY ALTERNATIVE FEED OF UTILITIES TO AREAS THAT ARE IN OPERATION BEFORE CONTRACTOR SHALL FIELD COORDINATE TO PROVIDE TEMPORARY ALTERNATIVE FEED OF UTILITIES TO AREAS THAT ARE IN OPERATION BEFORE PERFORMING THE DEMOLITION/RELOCATION/ RAISING OF UTILITIES. D. THIS WORK SHALL BE CARRIED OUT WITH MINIMUM DISRUPTION OF SERVICES. ALL WORK MUST BE COORDINATED WITH BUILDING THIS WORK SHALL BE CARRIED OUT WITH MINIMUM DISRUPTION OF SERVICES. ALL WORK MUST BE COORDINATED WITH BUILDING MAINTENANCE GROUP AND USERS.

AutoCAD SHX Text

VAMC

AutoCAD SHX Text

VA MEDICAL CENTER

AutoCAD SHX Text

CDP

AutoCAD SHX Text

CONDENSATE PUMP

AutoCAD SHX Text (N)

AutoCAD SHX Text

NEW

AutoCAD SHX Text

EXISTING EQUIPMENT/DUCT WORK/PIPING

AutoCAD SHX Text

(ER)

AutoCAD SHX Text

EXISTING TO BE RELOCATED

AutoCAD SHX Text (R)

AutoCAD SHX Text

REMOVE

AutoCAD SHX Text

(RE)

AutoCAD SHX Text

RELOCATED EXISTING

AutoCAD SHX Text (NOTE: THESE ABBREVIATIONS ARE STANDARD AND ALL MAY NOT BE APPLICABLE TO THIS PROJECT)

AutoCAD SHX Text

(NOTE: THESE SYMBOLS ARE STANDARD AND ALL MAY NOT BE APPLICABLE TO THIS PROJECT)

AutoCAD SHX Text

(NOTE: THESE SYMBOLS ARE STANDARD AND ALL MAY NOT BE APPLICABLE TO THIS PROJECT)

AutoCAD SHX Text

(NOTE: THESE SYMBOLS ARE STANDARD AND ALL MAY NOT BE APPLICABLE TO THIS PROJECT)

AutoCAD SHX Text

(NOTE: THESE SYMBOLS ARE STANDARD AND ALL MAY NOT BE APPLICABLE TO THIS PROJECT)

AutoCAD SHX Text

(NOTE: THESE SYMBOLS ARE STANDARD AND ALL MAY NOT BE APPLICABLE TO THIS PROJECT)

AutoCAD SHX Text 16.

AutoCAD SHX Text 17.

AutoCAD SHX Text 18.

AutoCAD SHX Text 1.

AutoCAD SHX Text 2.

AutoCAD SHX Text 3.

AutoCAD SHX Text 4.

AutoCAD SHX Text UNDER NO CIRCUMSTANCE SHALL THE WORK PERFORMED UNDER THIS CONTRACT ADVERSELY AFFECT ADJACENT AREAS, WHICH ARE NOT PART OF THIS CONTRACT. ALL DEMOLISHED EQUIPMENT AND RUBBISH SHALL BE CLEARED, TRANSPORTED AND DISPOSED OF IN A LAWFUL AND RESPONSIBLE MANNER DAILY. THE PREMISES-INTERIOR AND EXTERIOR SHALL BE MAINTAINED IN A REASONABLY CLEAN AND ORDERED STATE FOLLOWING EACH DAY'S CONSTRUCTION PROCESS. UNDER NO CIRCUMSTANCES SHALL CONSTRUCTION DEBRIS BE LEFT EXPOSED TO ACCESS BY THE PUBLIC. ALL OPENINGS IN WALLS REMAINING AFTER THE REMOVAL OF EXISTING PIPING, DUCTWORK, EQUIPMENT ETC. SHALL BE SEALED AND PATCHED TO MATCH EXISTING CONSTRUCTION CONDITIONS, AND SHALL MAINTAIN FIRE RATING REQUIREMENTS. CAP OR PLUG ALL ACTIVE REMAINING SYSTEMS WHERE RECONNECTIONS ARE NOT PLANNED AT POINTS WHERE EXISTING SYSTEM IS RETAINED. MAINTAIN EXISTING SYSTEMS AS NECESSARY TO CONTINUE NORMAL OPERATIONS. ALL SERVICE INTERRUPTIONS SHALL BE AT OWNER'S CONVENIENCE. DURING THE CONSTRUCTION PHASE, IT IS REQUIRED TO MAINTAIN UNINTERRUPTED SERVICE TO OTHER AREA. CONTRACTOR SHALL ENSURE THAT THE OTHER PHASES ARE NOT AFFECTED AND PROVIDE TEMPORARY DUCT, CONDUITS, PIPES ETC. AS NECESSARY TO MAINTAIN CONTINUITY. ALL THIS SHALL BE PART OF THE INITIAL BID COST. ANY CHANGE ORDER ADDITIONAL CHARGES FROM THE CONTRACTOR DURING CONSTRUCTION WILL STRICTLY NOT BE ENTERTAINED. CONTRACTOR IS FULLY RESPONSIBLE TO PRODUCE COORDINATION DRAWINGS BASED ON THE ACTUAL FIELD CONDITIONS. CONTRACTOR SHALL ENSURE THAT WORK CARRIED OUT WITHOUT ANY DISRUPTION OF UTILITIES TO OTHER AREAS WHICH ARE NOT IN CONTRACT. CONTRACTOR SHALL FIELD COORDINATE TO PROVIDE TEMPORARY/PERMANENT ALTERNATIVE FEED OF UTILITIES TO AREAS THAT ARE IN OPERATION BEFORE PERFORMING THE DEMOLITION/RELOCATION/RAISING OF UTILITIES (INCLUDING BUT NOT LIMITED TO DUCTWORK, MECHANICAL AND PLUMBING PIPING, CONDUITS, LIGHTS, CABLES, CABLE TRAY, EQUIPMENT ETC.). THIS WORK SHALL BE CARRIED OUT WITH MINIMUM DISRUPTION OF SERVICES. ALL WORK MUST BE COORDINATED WITH COR.

AutoCAD SHX Text 5.

AutoCAD SHX Text 6.

AutoCAD SHX Text 7.

AutoCAD SHX Text 8.

AutoCAD SHX Text

GENERAL NOTES-DEMOLITION AND NEW WORK:

AutoCAD SHX Text

COR

AutoCAD SHX Text

CONTRACTING OFFICER REPRESENTATIVE

AutoCAD SHX Text 19.

AutoCAD SHX Text D

AutoCAD SHX Text M-001

AutoCAD SHX Text

AutoCAD SHX Text

MECHANICAL COVER SHEET

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

CORPORAL MICHAEL J. CRESCENZ

AutoCAD SHX Text

VA MEDICAL CENTER

AutoCAD SHX Text 642-22-104

AutoCAD SHX Text 10-21-2024

AutoCAD SHX Text

SUBSTATION UPGRADE BUILDING 2 - PHASE 1

AutoCAD SHX Text

AR

AutoCAD SHX Text

AM

B2A105

EQUIPMENT

MECHANICAL

ELECTRICAL

ROOM

GENERAL NOTES - DEMOLITION WORK

KEYED NOTES - DEMOLITION WORK

1/4" = 1'-0" PARTIAL GROUND FLOOR - ELECTRICAL ROOM - DEMOLITION WORK - MECHANICAL1 KEY PLAN-GROUND FLOOR

EXISTING EMERGENCY

SWITCHGEAR ROOM

XXXX

HALL

XXXX

TYPICAL DEMOLITION NOTES

AREA OF

WORK

C B2

-1

C O

R R

ID

O

R

CB2-5

LOBBY

C B2

-1

C O

R R

ID

O

R

STAIR #9

#F-19

ELEV.

B2B105h E. C.

B2B105g

TEL. CLO.

B2B113a Warehouse Supervisor

B2B113

VESTIBULEB2B112

GAS STO.

B2B111

GAS STO.FLAMMABLE

B2B110

STOR. VAULT

MECHANICAL

B2B109

EQUIP.

B2B108

VEST.

B2B107

VEST.

EXIT

CB2-13

CORRIDOR

ELECTRIC

B2B106

ROOM

B2B105a

STORAGE

SUBSTANCE STO.

B2B105b

REFRIGERATOR

B2B103 H. A. C.

SHAFT

MECH.

C B2

-8 C

O R

R

ID

O R

CB2-7

CORRIDOR

PASSENGER

CB2-6

ELEV. LOBBY

B2B100 SPD Office

W/C.

STAFF

B2B101

TLT.

B2B102

TLT.

B2B126

REFRIGERATOR

SHAFT

MECH.

C B2

-1

C O

R R

ID

O

R

CB2-17

CORRIDOR

CB2-9

CORRIDOR

SANITATION

SUPPLY

B2B139b

STO.

B2B139b

DISHWASHING

B2B139

CLEAN DISH STO.

B2B140 Office

B2B132

TRAY MAKE-UP

B2B131b Office

B2B135

CENTER

FOOD SERVICE

B2B131 Conference Room

B2B134

TEL. CLO.

B2B133 E. C.

B2B131a

OFFICE

B2B135a

STORAGE

B2B119

STORAGE

FOOD PROCESSING

B2B128

& PREPARATION

INGREDIENT

B2B125

CONTROL

B2B121

FOOD STORAGE

B2B104

CHIEF

PROG. MGT.

& PLAN'G.

B2B138

CHIEF

SEC./

B2B137

WAITING

B2B118

M. TLT.

B2B117

F. TLT.

B2B120 H. A. C.

NUTRITION

THERAPY

B2B136

CHIEF

CAN WASH

B2B115

& CRUSH

FOOD SERVICE

B2B141

ELEV. LOBBYPATIENT SERVICE

CB2-10

ELEV. LOBBY

W/C.

STAFF

STAIR #8

CB2-16

CORRIDOR

DAIRY

B2B124

VEG. REFRIGERATOR

B2B123

MEAT REFRIGERATOR

B2B122

NON-FOOD STO.

B2B124a

VEG. FREEZER

B2B123a

MEAT FREEZER

STORAGE/

B2B132a

FUTURE MECH. SHAFT

B2B130 H. A. C.

POT WASH

B2B129

CENTER

MECHANICAL

B2B143

ROOM

ELECTRIC

B2B127

ROOM

LOADING DOCK

B2B132b Storage

NUTRITION & FOOD SERVICE

CB2-1

ELEVATOR LOBBY

ST

AI

R #1

TEL.

MECH.

EQUIP.

SHAFT

SPS

LOGISTICS

MECHANICAL

EQUIPMENT

B2A105

B2A102 E.C.

CLO.

B2A101 B2A100

STOR.

ELECTRICAL

EXISTING

MECHANICAL

EXISTING

CORRIDOR

CB2-3

NEW

ELECTRICAL ROOM

XXXX

EXISTING EMERGENCY

SWITCHGEAR ROOM

XXXX

NEW

STORAGE ROOM

XXXX

HALL

XXXX

ELECTRICAL

EXISTING

MECHANICAL

EXISTING

CORRIDOR

CB2-3

Drawing Title

Chief Engineer Approval

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. of

CONSULTANT FIRM: ARCHITECTS/ENGINEERS:

Office of Facility Management Service on e e igh th inc h = on e f oo t

IF

T

H

IS

S H

EE

T

IS

N

O T

" X

2"

FU

LL

S

IZ

E, U

SE

G

R

AP

H

IC

S C

AL

ES

on e i nc h = on e f oo t

6" 6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Name, Title Prevention Coordinator

Name Title

Name Title

Name Title

Name Title

DESIGN CHANGE APPROVED

DESCRIPTION DATE

SEAL: SEAL:

BID DOCUMENTS October-21-2024

ART - ARCHITECTURE - ENGINEERING

2787 HILL ROAD

VIENNA, VA 22181

FRANK V. STURGEON, AIA

AMBRISH RASTOGI, PE

703.938.5226

FRANK@ADG10.COM

A DESIGN GROUP, LLC

SEE KEY PLAN BELOW FOR AREA OF WORK

0 4 8 scale: 14"= 1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

EXISTING MAIL ROOM AND WALL

AutoCAD SHX Text

ICRA WALL

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text M

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

(R) EF

AutoCAD SHX Text

1. REMOVE EXISTING EXHAUST FAN, ACCESSORIES, SUPPORTS, CONTROL WIRING, REMOVE EXISTING EXHAUST FAN, ACCESSORIES, SUPPORTS, CONTROL WIRING, MOTORIZED DAMPER, ETC. 2. EXISTING LOUVER TO REMAIN. EXISTING LOUVER TO REMAIN. 3. EXISTING CHILLED WATER SUPPLY AND RETURN PIPING RISER TO REMAIN (TYPICAL). EXISTING CHILLED WATER SUPPLY AND RETURN PIPING RISER TO REMAIN (TYPICAL). 4. REMOVE EXISTING MOTORIZED DAMPER. MODIFY EXISTING DUCT PLENUM. REMOVE EXISTING MOTORIZED DAMPER. MODIFY EXISTING DUCT PLENUM. 5. EXISTING OUTDOOR AIR INTAKE LOUVER TO REMAIN. EXISTING OUTDOOR AIR INTAKE LOUVER TO REMAIN.

AutoCAD SHX Text CONTRACTOR SHALL PROVIDE COORDINATION DRAWINGS AFTER THE DEMOLITION WORK. PROVIDE ALL SYSTEMS IN COORDINATION WITH THE SITE CONDITIONS AS PART OF THIS CONTRACT. MAINTAIN CONTINUITY OF HVAC, PLUMBING AND ELECTRICAL SYSTEMS ETC. UNDER NO CIRCUMSTANCE SHALL THE WORK PERFORMED UNDER THIS CONTRACT ADVERSELY AFFECT ADJACENT AREAS, NOT PART OF THIS CONTRACT. MAINTAIN EXISTING SYSTEMS AS NECESSARY TO CONTINUE NORMAL OPERATIONS. ALL SERVICE INTERRUPTIONS SHALL BE AT OWNER'S CONVENIENCE. REQUESTS FOR SERVICE INTERRUPTIONS SHALL BE MADE A MINIMUM OF 14 DAYS PRIOR TO ANTICIPATED DATE. IF SUSPECTED ASBESTOS-CONTAINING MATERIALS ARE ENCOUNTERED IN THE COURSE OF THE WORK, THE CONTRACTOR SHALL CEASE WORK WITH THE SUSPECT MATERIAL AND AWAIT DIRECTION FROM THE COR. ALL DEMOLISHED EQUIPMENT AND RUBBISH SHALL BE CLEARED, TRANSPORTED AND DISPOSED OF IN A LAWFUL AND RESPONSIBLE MANNER.

AutoCAD SHX Text 1.

AutoCAD SHX Text 2.

AutoCAD SHX Text 3.

AutoCAD SHX Text 4.

AutoCAD SHX Text 5.

AutoCAD SHX Text

%%UFOR ALL ITEMS SCHEDULED FOR DEMOLITION:

AutoCAD SHX Text

%%USCHEDULING & SEQUENCING OF THE WORK:

AutoCAD SHX Text

%%UELECTRICAL COMPONENTS:

AutoCAD SHX Text

%%UMECHANICAL COMPONENTS:

AutoCAD SHX Text COORDINATE WITH COR REGARDING WHICH ITEMS ARE TO BE PROTECTED, SALVAGED, AND/OR DISCARDED.

AutoCAD SHX Text PRIOR TO COMMENCEMENT OF ANY WORK ON THE PROJECT, THE CONTRACTOR SHALL MEET WITH THE COR & A REPRESENTATIVE OF THE "END USER" TO DISCUSS & FORMULATE A SCHEDULING & SEQUENCING OF THE WORK PLAN IN AN EFFORT TO MINIMIZE THE DISRUPTION OF ONGOING SERVICES & ACTIVITIES WITHIN THE AREAS OF THE WORK. BEFORE COMMENCEMENT OF THE WORK THE CONTRACTOR SHALL DEVELOP A WRITTEN PLAN OF SCHEDULING & SEQUENCING INDICATING TARGET DATES FOR CERTAIN PHASES ON THE WORK & ASSOCIATED SELECTIVE DEMOLITION PROVIDE COPIES TO COR.

AutoCAD SHX Text COORDINATE REMOVAL OF ELECTRICAL SYSTEMS AND COMPONENTS WITH ELECTRICAL DRAWINGS.

AutoCAD SHX Text COORDINATE REMOVAL OF MECHANICAL SYSTEMS AND COMPONENTS WITH MECHANICAL DRAWINGS.

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text

NO SCALE

AutoCAD SHX Text

WASHERS

AutoCAD SHX Text

STERILIZERS

AutoCAD SHX Text

ULTRASONIC

AutoCAD SHX Text

TD100

AutoCAD SHX Text

TD100

AutoCAD SHX Text Reliance

AutoCAD SHX Text Reliance

AutoCAD SHX Text Reliance

AutoCAD SHX Text Future Reliance

AutoCAD SHX Text Reliance

AutoCAD SHX Text Reliance

AutoCAD SHX Text Reliance

AutoCAD SHX Text

DRY CABS

AutoCAD SHX Text

STORAGE CABS

AutoCAD SHX Text

DRY CABS

AutoCAD SHX Text Future Reliance

AutoCAD SHX Text

STAIR #2

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text B2A121

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SF

AutoCAD SHX Text B2A122

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SF

AutoCAD SHX Text B2A120

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SF

AutoCAD SHX Text

EXISTING MAIL ROOM AND WALL

AutoCAD SHX Text

ICRA WALL

AutoCAD SHX Text

MD-101

AutoCAD SHX Text

AutoCAD SHX Text

ELECTRICAL ROOM-DEMOLITION WORK - MECHANICALMECHANICAL

AutoCAD SHX Text

AM

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

CORPORAL MICHAEL J. CRESCENZ

AutoCAD SHX Text

VA MEDICAL CENTER

AutoCAD SHX Text 642-22-104

AutoCAD SHX Text 10-21-2024

AutoCAD SHX Text

SUBSTATION UPGRADE BUILDING 2 - PHASE 1

AR

B2A105

EQUIPMENT

MECHANICAL

KEYED NOTES - NEW WORK

GENERAL - NEW WORK

KEY PLAN-GROUND FLOOR

WARE HOUSE

XXXX

EXISTING EMERGENCY

SWITCHGEAR ROOM

XXXX

ELECTRICAL

EXISTING

HALL

XXXX

AREA OF

WORK

NUTRITION & FOOD SERVICE

SPS

LOGISTICS

NEW

ELECTRICAL ROOM

XXXX

EXISTING EMERGENCY

SWITCHGEAR ROOM

XXXX

NEW

STORAGE ROOM

XXXX

HALL

XXXX

MECHANICAL

EXISTING

CORRIDOR

CB2-3

SUBSTATION ROOM

NEW TEMPORARY

Drawing Title

Chief Engineer Approval

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. of

CONSULTANT FIRM: ARCHITECTS/ENGINEERS:

Office of Facility Management Service on e e igh th inc h = on e f oo t

IF

T

H

IS

S H

EE

T

IS

N

O T

" X

2"

FU

LL

S

IZ

E, U

SE

G

R

AP

H

IC

S C

AL

ES

on e i nc h = on e f oo t

6" 6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Name, Title Prevention Coordinator

Name Title

Name Title

Name Title

Name Title

DESIGN CHANGE APPROVED

DESCRIPTION DATE

SEAL: SEAL:

BID DOCUMENTS October-21-2024

ART - ARCHITECTURE - ENGINEERING

2787 HILL ROAD

VIENNA, VA 22181

FRANK V. STURGEON, AIA

AMBRISH RASTOGI, PE

703.938.5226

FRANK@ADG10.COM

A DESIGN GROUP, LLC

1/4" = 1'-0"

PARTIAL GROUND FLOOR - ELECTRICAL ROOM - NEW WORK - MECHANICAL1

SEE KEY PLAN BELOW FOR AREA OF WORK

0 4 8 scale: 14"= 1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

ICRA WALL

AutoCAD SHX Text

EXISTING MAIL ROOM AND WALL

AutoCAD SHX Text

2-AH2

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

(E) FD

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text T

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 8"X4"

AutoCAD SHX Text 2-1/2"

AutoCAD SHX Text 1-1/4"

AutoCAD SHX Text T

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 2-1/2"

AutoCAD SHX Text M

AutoCAD SHX Text T

AutoCAD SHX Text PROVIDE COORDINATION DRAWINGS AFTER THE DEMOLITION WORK. PROVIDE ALL SYSTEMS IN COORDINATION WITH THE SITE CONDITIONS AS PART OF THIS CONTRACT. MAINTAIN CONTINUITY OF HVAC AND ELECTRICAL SYSTEMS ETC. WHICH IS NOT PART OF SCOPE OF WORK. ALL EXISTING, NEW WALL PENETRATIONS WILL BE COMPLETELY SEALED WITH APPROVED U/L LISTED FIRE STOPPING MATERIALS. CONTRACTOR SHALL PROVIDE FIRE STOPPING SUBMITTALS FOR APPROVAL. CONTRACTOR SHALL PERFORM AIR BALANCE. ALL NEW HVAC SYSTEM SHALL BE INTERLOCKED WITH EXISTING BUILDING AUTOMATION SYSTEMS. PROVIDE A DDC SENSOR TO MONITOR THE SPACE TEMPERATURE AND INITIATE LOCAL AND REMOTE ALARMS IN THE EVENT SPACE TEMPERATURE EXCEEDS 95° F (ADJUSTABLE). PROVIDE A DDCSENSOR FOR MONITORING AND ALARM LOCAL CONTROL LOOP.

AutoCAD SHX Text 1.

AutoCAD SHX Text 2.

AutoCAD SHX Text 3.

AutoCAD SHX Text 4.

AutoCAD SHX Text

1. NEW AIR HANDLING UNIT, 2-AH2, CEILING MOUNTED UNIT, NEW AIR HANDLING UNIT, 2-AH2, CEILING MOUNTED UNIT, PROVIDE UNIT SUPPORTS. INSTALL DRAIN PAN BELOW AIR HANDLING UNIT. INSTALL WATER DETECTION SENSOR IN THE DRAIN PAN. INSTALL THE UNIT IN FULL COMPLIANCE WITH MANUFACTURER RECOMMENDATIONS. PROVIDE ADEQUATE SERVICE CLEARANCE AROUND THE UNIT. 2. EXISTING LOUVER. THE CONTRACTOR SHALL REUSE THE EXISTING EXISTING LOUVER. THE CONTRACTOR SHALL REUSE THE EXISTING LOUVER FOR OUTDOOR AIR INTAKE AND COORDINATE WITH MANUFACTURER FOR PROPER OPERATION. MODIFY EXISTING DUCT PLENUM AS REQUIRED. VERIFY IN FIELD. 3. EXISTING CHILLED WATER SUPPLY AND RETURN PIPING RISERS. EXISTING CHILLED WATER SUPPLY AND RETURN PIPING RISERS. THE CONTRACTOR SHALL PERFORM BALANCING OF EXISTING CHILLED WATER PUMPS TO PROVIDE ADDITIONAL 65.5 GPM FOR NEW AHU UNITS (2-AH1 & 2-AH2). VERIFY IN FIELD (TYPICAL). 4. COVER EXISTING LOUVER WITH SHEET METAL, SEAL OPENING AIR COVER EXISTING LOUVER WITH SHEET METAL, SEAL OPENING AIR AND WATER TIGHT. 5. EXISTING LOUVER. EXISTING LOUVER. 6. NEW AIR HANDLING UNIT, 2-AH1, CEILING MOUNTED UNIT, NEW AIR HANDLING UNIT, 2-AH1, CEILING MOUNTED UNIT, PROVIDE UNIT SUPPORTS. INSTALL DRAIN PAN BELOW AIR HANDLING UNIT. INSTALL WATER DETECTION SENSOR IN THE DRAIN PAN. INSTALL THE UNIT IN FULL COMPLIANCE WITH MANUFACTURER RECOMMENDATIONS. PROVIDE ADEQUATE SERVICE CLEARANCE AROUND THE UNIT. 7. SUPPLY AIR GRILLE (TYPICAL). SUPPLY AIR GRILLE (TYPICAL). 8. RETURN AIR GRILLE (TYPICAL). RETURN AIR GRILLE (TYPICAL). 9. SUPPLY AIR DUCT. PROVIDE DUCT SUPPORTS. COORDINATE WITH SUPPLY AIR DUCT. PROVIDE DUCT SUPPORTS. COORDINATE WITH ELECTRICAL CONDUITS (TYPICAL). 10. RETURN AIR DUCT. PROVIDE DUCT SUPPORTS. COORDINATE WITH RETURN AIR DUCT. PROVIDE DUCT SUPPORTS. COORDINATE WITH ELECTRICAL CONDUITS (TYPICAL). 11. CONDENSATE DRAIN PIPING. PROVIDE PIPING SUPPORTS. PROVIDE CONDENSATE DRAIN PIPING. PROVIDE PIPING SUPPORTS. PROVIDE PIPING INSULATIONS. MAINTAIN PROPER PIPING SLOPE (TYPICAL). 12. CHILLED WATER SUPPLY AND RETURN PIPING. PROVIDE PIPING CHILLED WATER SUPPLY AND RETURN PIPING. PROVIDE PIPING INSULATIONS. PROVIDE PIPING SUPPORTS. THE CONTRACTOR SHALL COORDINATE WITH EXISTING PIPING (TYPICAL). 13. ROOM TEMPERATURE SENSOR. ROOM TEMPERATURE SENSOR. 14. OUTDOOR AIR DUCT. PROVIDE DUCT SUPPORTS (TYPICAL). OUTDOOR AIR DUCT. PROVIDE DUCT SUPPORTS (TYPICAL). 15. NEW CONDENSATE DRAIN PUMP, 1-CP1, CEILING MOUNTED UNIT, NEW CONDENSATE DRAIN PUMP, 1-CP1, CEILING MOUNTED UNIT, PROVIDE PUMP SUPPORTS. INSTALL THE PUMP IN FULL COMPLIANCE WITH MANUFACTURER RECOMMENDATIONS.

AutoCAD SHX Text 5.

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text 22"X20"

AutoCAD SHX Text 18"X16"

AutoCAD SHX Text

NO SCALE

AutoCAD SHX Text U

AutoCAD SHX Text

2-AH1

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

2-CP1

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 32"X24"

AutoCAD SHX Text 16"X18"

AutoCAD SHX Text

AutoCAD SHX Text 8"X4"

AutoCAD SHX Text 8"X4"

AutoCAD SHX Text

AutoCAD SHX Text 24"X32"

AutoCAD SHX Text 24"X32"

AutoCAD SHX Text 26"X24"

AutoCAD SHX Text 16"X22"

AutoCAD SHX Text 20"X18"

AutoCAD SHX Text M

AutoCAD SHX Text

AutoCAD SHX Text 8"X6"

AutoCAD SHX Text 1-1/4"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 1-1/2"

AutoCAD SHX Text

AutoCAD SHX Text 1-1/2"

AutoCAD SHX Text

AutoCAD SHX Text 1-1/2"

AutoCAD SHX Text 1-1/4"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 20"X18"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 1-1/4"

AutoCAD SHX Text

WASHERS

AutoCAD SHX Text

STERILIZERS

AutoCAD SHX Text

ULTRASONIC

AutoCAD SHX Text

TD100

AutoCAD SHX Text

TD100

AutoCAD SHX Text Reliance

AutoCAD SHX Text Reliance

AutoCAD SHX Text Reliance

AutoCAD SHX Text Future Reliance

AutoCAD SHX Text Reliance

AutoCAD SHX Text Reliance

AutoCAD SHX Text Reliance

AutoCAD SHX Text

DRY CABS

AutoCAD SHX Text

STORAGE CABS

AutoCAD SHX Text

DRY CABS

AutoCAD SHX Text Future Reliance

AutoCAD SHX Text

STAIR #2

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text B2A121

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SF

AutoCAD SHX Text B2A122

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SF

AutoCAD SHX Text B2A120

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SF

AutoCAD SHX Text

ICRA WALL

AutoCAD SHX Text

EXISTING MAIL ROOM AND WALL

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

MH-101

AutoCAD SHX Text

AutoCAD SHX Text

ELECTRICAL ROOM-NEW WORK -MECHANICAL

AutoCAD SHX Text

AM

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

CORPORAL MICHAEL J. CRESCENZ

AutoCAD SHX Text

VA MEDICAL CENTER

AutoCAD SHX Text 642-22-104

AutoCAD SHX Text 10-21-2024

AutoCAD SHX Text

SUBSTATION UPGRADE BUILDING 2 - PHASE 1

AR

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. of

CONSULTANT FIRM: ARCHITECTS/ENGINEERS:

Office of Facility Management Service on e e igh th inc h = on e f oo t

IF

T

H

IS

S H

EE

T

IS

N

O T

" X

2"

FU

LL

S

IZ

E, U

SE

G

R

AP

H

IC

S C

AL

ES

on e i nc h = on e f oo t

6" 6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Name, Title Prevention Coordinator

Name Title

Name Title

Name Title

Name Title

DESIGN CHANGE APPROVED

DESCRIPTION DATE

SEAL: SEAL:

BID DOCUMENTS October-21-2024

ART - ARCHITECTURE - ENGINEERING

2787 HILL ROAD

VIENNA, VA 22181

FRANK V. STURGEON, AIA

AMBRISH RASTOGI, PE

703.938.5226

FRANK@ADG10.COM

A DESIGN GROUP, LLC

AutoCAD SHX Text

CHILLED WATER COOLING COIL SCHEDULE

AutoCAD SHX Text

TEMP. IN °F

AutoCAD SHX Text

TEMP. OUT °F

AutoCAD SHX Text

MAX. LOSS FT. FLUID

AutoCAD SHX Text

COIL NO.

AutoCAD SHX Text

SYSTEM

AutoCAD SHX Text

CFM

AutoCAD SHX Text

AutoCAD SHX Text 90.9

AutoCAD SHX Text Db

AutoCAD SHX Text

ENT. AIR °F

AutoCAD SHX Text Wb

AutoCAD SHX Text 62.2

AutoCAD SHX Text 54.3

AutoCAD SHX Text Db

AutoCAD SHX Text

LVG. AIR °F

AutoCAD SHX Text Wb

AutoCAD SHX Text 48.0

AutoCAD SHX Text

GPM

AutoCAD SHX Text 18.2

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 5.9

AutoCAD SHX Text 90,973

AutoCAD SHX Text

MIN. BTUH

AutoCAD SHX Text

CIRCULATING FLUID

AutoCAD SHX Text

AIR HANDLING UNIT SCHEDULE

AutoCAD SHX Text

%%UNOTES:

AutoCAD SHX Text 1.

AutoCAD SHX Text 2.

AutoCAD SHX Text 3.

AutoCAD SHX Text 4.

AutoCAD SHX Text EXTERNAL STATIC PRESSURE REQUIRED AT DUCT CONNECTIONS TO INLET & OUTLET OF AHU. MEASUREMENTS SHALL BE TAKEN WITHIN 3 FT. OF INLET AND OUTLET AT A POINT OF MAX. ACCURACY. TOTAL OF MAX. PRESSURE DROPS OF COMPONENTS WHICH ARE SPECIFIED SEPARATELY, IE., FILTER, COOLING COIL. INTERNAL LOSS ALLOWANCE SHALL INCLUDE LOSSES DUE TO ENTRANCE & EXIT OF AHU, INCLUDING LOSSES DUE TO FAILURE TO PROPERLY CONVERT FAN DISCHARGE VELOCITY PRESSURE TO STATIC PRESSURE, FAN INLET CONDITIONS, CASINGS, DAMPERS, ETC. TOTAL FAN S.P. = EXTERNAL STATIC PRESSURE + SPECIFIED INTERNAL LOSSES + UNSPECIFIED INTERNAL LOSSES. MANUFACTURER SHALL PROVIDE SUBMITTAL SHOWING ACTUAL LOSSES OF ALL EQUIPMENT PROVIDED. REFER TO FAN SCHEDULE FOR ADDITIONAL FAN SELECTION INFORMATION.

AutoCAD SHX Text

UNIT NO.

AutoCAD SHX Text

2-AH1

AutoCAD SHX Text

LOCATION

AutoCAD SHX Text

ELECTRICAL ROOM

AutoCAD SHX Text

SUPPLY FAN NO.

AutoCAD SHX Text

2-SF1

AutoCAD SHX Text

AREA SERVED

AutoCAD SHX Text

CFM

AutoCAD SHX Text

SUPPLY

AutoCAD SHX Text

AutoCAD SHX Text O.A.

AutoCAD SHX Text

EXTERNAL STATIC PRESSURE (NOTE 1) IN

AutoCAD SHX Text 1.0

AutoCAD SHX Text

FAN TOTAL S.P. (NOTE 4) IN

AutoCAD SHX Text

AutoCAD SHX Text

CAV

AutoCAD SHX Text

TYPE SYSTEM

AutoCAD SHX Text

AutoCAD SHX Text

FILTER NO.

AutoCAD SHX Text

CFM

AutoCAD SHX Text

SYSTEM

AutoCAD SHX Text

VA GRADE

AutoCAD SHX Text

FINAL

AutoCAD SHX Text

IN

AutoCAD SHX Text

HOUSING TYPE

AutoCAD SHX Text

NO.

AutoCAD SHX Text

AutoCAD SHX Text

ARRANGEMENT

AutoCAD SHX Text 0.56

AutoCAD SHX Text

AutoCAD SHX Text D

AutoCAD SHX Text

DROP

AutoCAD SHX Text

MAX. S.P.

AutoCAD SHX Text

RATED EFF %

AutoCAD SHX Text

DEPTH IN

AutoCAD SHX Text

TYPE

AutoCAD SHX Text

PLEATED

AutoCAD SHX Text 85%

AutoCAD SHX Text

SUPPLY FAN SCHEDULE

AutoCAD SHX Text

FAN NO

AutoCAD SHX Text

2-SF1

AutoCAD SHX Text

LOCATION

AutoCAD SHX Text

BUILT-IN 2-AH1

AutoCAD SHX Text

CFM

AutoCAD SHX Text

AutoCAD SHX Text E.S.P.

AutoCAD SHX Text

IN

AutoCAD SHX Text 1.0

AutoCAD SHX Text

FAN TYPE

AutoCAD SHX Text

CF

AutoCAD SHX Text

TYPE

AutoCAD SHX Text

PLN

AutoCAD SHX Text

AutoCAD SHX Text

MIN.

AutoCAD SHX Text

IN

AutoCAD SHX Text

WHEEL

AutoCAD SHX Text

MAX. RPM

AutoCAD SHX Text

BELT

AutoCAD SHX Text

DRIVE

AutoCAD SHX Text

MAX. BHP

AutoCAD SHX Text

NOM.

AutoCAD SHX Text

HP

AutoCAD SHX Text 1.2

AutoCAD SHX Text

PHASE VOLT.

AutoCAD SHX Text 3/460

AutoCAD SHX Text

MOTOR

AutoCAD SHX Text

AutoCAD SHX Text

DIA.

AutoCAD SHX Text

%%UNOTE:

AutoCAD SHX Text

1. COOLING COIL DATA SHOWN IN THE SCHEDULE REPRESENT THE VALVE SETTINGS.

AutoCAD SHX Text

SIDE SERVICE

AutoCAD SHX Text

PROVIDE CONTROLS SYSTEMS TO INTERLOCK BUILDING AUTOMATION SYSTEMS.

AutoCAD SHX Text 1.

AutoCAD SHX Text

SIZE AND ARRANGEMENT SHALL BE DETERMINED BY AHU MANUFACTURER

AutoCAD SHX Text

AF-

AutoCAD SHX Text 1751-2300

AutoCAD SHX Text 1501-1750

AutoCAD SHX Text

RANGE

AutoCAD SHX Text

AutoCAD SHX Text 0.04

AutoCAD SHX Text 0.05

AutoCAD SHX Text 0.05

AutoCAD SHX Text

(IN WG)

AutoCAD SHX Text

DROP

AutoCAD SHX Text

PRESSURE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 2000-2500

AutoCAD SHX Text

RETURN AIR GRILLE

AutoCAD SHX Text

SYMBOL

AutoCAD SHX Text

NOISE

AutoCAD SHX Text

CRITERIA

AutoCAD SHX Text

(INCH)

AutoCAD SHX Text

FACE SIZE

AutoCAD SHX Text

CFM

AutoCAD SHX Text

TYPE

AutoCAD SHX Text

%%UGENERAL NOTES:

AutoCAD SHX Text

1. ALL FINISH SELECTIONS SHALL BE BY ARCHITECT.

AutoCAD SHX Text

AIR DEVICE SCHEDULE

AutoCAD SHX Text

THE AIR DEVICE PERFORMANCE DATA INDICATED BASIS OF DESIGN:

AutoCAD SHX Text

TITUS MFR'S CO-MODEL NO. 301RS SERIES (OR) APPROVED EQUAL

AutoCAD SHX Text

DUCT LEAKAGE CLASSIFICATION AND ALLOWABLE LEAKAGE TABLE

AutoCAD SHX Text

DUCT PRESSURE

AutoCAD SHX Text

CLASS, W.G.

AutoCAD SHX Text IN[mm]

AutoCAD SHX Text 1/2", 1", 2"

AutoCAD SHX Text 3"

AutoCAD SHX Text 4", 6"

AutoCAD SHX Text

SEAL CLASS

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

APPLICABLE SEALING

AutoCAD SHX Text

TRAVERSE JOINTS ONLY

AutoCAD SHX Text

TRAVERSE JOINTS AND SEAMS

AutoCAD SHX Text

JOINTS, SEAMS AND ALL WALL PENETRATIONS

AutoCAD SHX Text

SMACNA LEAKAGE CLASS

AutoCAD SHX Text

RECTANGULAR DUCT

AutoCAD SHX Text

ROUND DUCT

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 88.5

AutoCAD SHX Text 87.5

AutoCAD SHX Text 86.5

AutoCAD SHX Text 84.0

AutoCAD SHX Text 84.0

AutoCAD SHX Text 7.5

AutoCAD SHX Text 5.0

AutoCAD SHX Text 3.0

AutoCAD SHX Text 2.0

AutoCAD SHX Text 1.5

AutoCAD SHX Text

NOM. EFF.

AutoCAD SHX Text 82.5

AutoCAD SHX Text

HP

AutoCAD SHX Text 1.0

AutoCAD SHX Text

NOTE: REFER TO SECTION 16150, MOTORS SECTION OF THE SPECIFICATIONS.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

HP

AutoCAD SHX Text

AutoCAD SHX Text

NOM. EFF.

AutoCAD SHX Text 93.0

AutoCAD SHX Text 92.4

AutoCAD SHX Text 91.7

AutoCAD SHX Text 91.0

AutoCAD SHX Text 91.0

AutoCAD SHX Text 89.5

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

HP

AutoCAD SHX Text

AutoCAD SHX Text

NOM. EFF.

AutoCAD SHX Text 95.0

AutoCAD SHX Text 94.5

AutoCAD SHX Text 94.1

AutoCAD SHX Text 94.1

AutoCAD SHX Text 93.6

AutoCAD SHX Text 93.0

AutoCAD SHX Text

ENERGY EFFICIENT MOTOR SCHEDULE

AutoCAD SHX Text

AIR HANDLING UNIT PERFORMANCE DATA INDICATED BASIS OF DESIGN:

AutoCAD SHX Text

AutoCAD SHX Text

SUPPLY AIR GRILLE

AutoCAD SHX Text

SUPPLY AIR GRILLE

AutoCAD SHX Text

SUPPLY AIR GRILLE

AutoCAD SHX Text

2-CC1

AutoCAD SHX Text

2-AH1

AutoCAD SHX Text

AutoCAD SHX Text

2-AF1

AutoCAD SHX Text

2-AH1

AutoCAD SHX Text

AutoCAD SHX Text

AIR FILTER SCHEDULE

AutoCAD SHX Text

2-AH1: DAIKIN MFR'S CO-MODEL NO. BCHD0301 (OR) APPROVED EQUAL

AutoCAD SHX Text

MAX. FACE VEL. FPM

AutoCAD SHX Text

ELECTRICAL ROOM

AutoCAD SHX Text

NTS

AutoCAD SHX Text

AIR HANDLING UNIT (2-AH1 AND 2-AH2)-SCHEMATIC CONTROL DIAGRAM

AutoCAD SHX Text

AutoCAD SHX Text

MJ101

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

%%UAIR HANDLING UNIT, 2-AH1 AND 2-AH2 (CONSTANT AIR VOLUME)

AutoCAD SHX Text

FILTER

AutoCAD SHX Text

OUTSIDE AIR

AutoCAD SHX Text D-1

AutoCAD SHX Text

COOLING COIL

AutoCAD SHX Text

LOCATE SENSOR OUTSIDE UNDER SHIELD

AutoCAD SHX Text V-1

AutoCAD SHX Text

CHR

AutoCAD SHX Text

CH

AutoCAD SHX Text

SUPPLY AIR

AutoCAD SHX Text

TT

AutoCAD SHX Text

TT

AutoCAD SHX Text

TT

AutoCAD SHX Text

HS

AutoCAD SHX Text

IT

AutoCAD SHX Text

MOTOR

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

ZC

AutoCAD SHX Text

PDS

AutoCAD SHX Text

TT

AutoCAD SHX Text

AutoCAD SHX Text

SST

AutoCAD SHX Text

NO

AutoCAD SHX Text

ECC

AutoCAD SHX Text

RETURN AIR

AutoCAD SHX Text D-2

AutoCAD SHX Text

ZC

AutoCAD SHX Text

SUPPLY AIR FAN, 1-SF1 FAN

AutoCAD SHX Text

1. GENERALGENERAL

AutoCAD SHX Text UNIT IS NORMALLY STARTED AND STOPPED REMOTELY AT THE ECC. H-O-A SWITCH SHALL BE KEPT IN THE "AUTO" POSITION. "HAND" AND "OFF" POSITIONS SHALL BE USED ONLY FOR MAINTENANCE.

AutoCAD SHX Text

SEQUENCE OF OPERATION:

AutoCAD SHX Text

2. TEMPERATURE CONTROL TEMPERATURE CONTROL FAN SHALL RUN CONTINUOUSLY IN OCCUPIED MODE. FAN STATUS FAN SHALL RUN CONTINUOUSLY IN OCCUPIED MODE. FAN STATUS SHALL BE MONITORED AND AN ALARM MESSAGE SHALL BE GENERATED IN THE EVENT THE UNIT FAILS TO RUN BETWEEN THE RANGE OF 70°-80° SPACE TEMPERATURE V-1 SHALL BE CLOSED. UPON RISE IN TEMPERATURE ABOVE 80° (ADJUSTABLE) V-1SHALL MODULATE OPEN TO MAINTAIN 80° F (ADJUSTABLE).OUTDOOR AIR DAMPER, (D-1), (MOTORIZED) SHALL OPEN TO MINIMUM DURING OCCUPIED MODE.

AutoCAD SHX Text

3. FREEZE PROTECTION FREEZE PROTECTION FREEZE PROTECTION

AutoCAD SHX Text IF THE AIR TEMPERATURE AS SENSED BY TT-3 FALLS BELOW 45°F [7°C], AN ALARM SIGNAL SHALL INDICATE AT THE DCP AND ECC. IF THIS TEMPERATURE FALLS BELOW 40°F [4.4°C], AS SENSED BY THE TSL THE SUPPLY SHALL SHUT DOWN AND A CRITICAL ALARM SHALL INDICATE AT THE DIGITAL CONTROL PANEL AND ECC. TSL SHALL BE HARDWIRED TO THE SUPPLY FAN AND UNIT SHALL BE SHUTDOWN IN HAND, AUTO. TSL WILL REQUIRE MANUAL RESET AT THE DEVICE.

AutoCAD SHX Text

SYSTEM COMPONENT

AutoCAD SHX Text

POINT ID

AutoCAD SHX Text

SUPPLY FANS (2-SF1 & 1-SF-2)

AutoCAD SHX Text

ON/OFF

AutoCAD SHX Text

ELECTRIC

AutoCAD SHX Text

PNEUMATIC

AutoCAD SHX Text

ELECTRIC

AutoCAD SHX Text

STATUS

AutoCAD SHX Text

TEMPERATURE

AutoCAD SHX Text

PRESSURE

AutoCAD SHX Text

LEVEL

AutoCAD SHX Text

HUMDITIY

AutoCAD SHX Text

FLOW

AutoCAD SHX Text

CURRENT

AutoCAD SHX Text

PERCENT

AutoCAD SHX Text

DATA

AutoCAD SHX Text

LOW LIMIT

AutoCAD SHX Text

HIGH LIMIT

AutoCAD SHX Text

LEAD/LAG

AutoCAD SHX Text

START/STOP

AutoCAD SHX Text

PNEUMATIC

AutoCAD SHX Text

DIFFERENTIAL

AutoCAD SHX Text

PRESSURE

AutoCAD SHX Text

EQUIPMENT

AutoCAD SHX Text

STATUS

AutoCAD SHX Text

SYSTEM OUTPUTS

AutoCAD SHX Text

SYSTEM INPUTS

AutoCAD SHX Text

SYSTEM SOFTWARE/CONTROL

AutoCAD SHX Text

BINARY

AutoCAD SHX Text

ANALOG

AutoCAD SHX Text

BINARY

AutoCAD SHX Text

ANALOG

AutoCAD SHX Text

ALARM

AutoCAD SHX Text

PROCESSING

AutoCAD SHX Text

APPLICATION/

AutoCAD SHX Text

FUNCTION

AutoCAD SHX Text

START/STOP

AutoCAD SHX Text

AIR HANDLING SYSTEMS (2-AH1) & (2-AH2)

AutoCAD SHX Text

MIXED AIR TEMPERATURE

AutoCAD SHX Text

CHILLED WATER COIL TEMPERATURE

AutoCAD SHX Text

SUPPLY AIR TEMPERATURE

AutoCAD SHX Text

SPACE TEMPERATURE

AutoCAD SHX Text

FILTER STATUS

AutoCAD SHX Text

FREEZSTAT STATUS

AutoCAD SHX Text

RETURN AIR DAMPER POSITION

AutoCAD SHX Text

OUTSIDE AIR DAMPER POSITION

AutoCAD SHX Text

OUTSIDE AIR TEMPERATURE

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text

DAMPER END SWITCH

AutoCAD SHX Text X

AutoCAD SHX Text

%%UCONTROL SYMBOLS

AutoCAD SHX Text T

AutoCAD SHX Text

ROOM THERMOSTAT/TEMPERATURE SENSOR/TRANSMITTER-WALL MOUNT

AutoCAD SHX Text

TT

AutoCAD SHX Text

TEMPERATURE TRANSMITTER

AutoCAD SHX Text

TT

AutoCAD SHX Text

TEMPERATURE TRANSMITTER, AVERAGING ELEMENT

AutoCAD SHX Text

SD

AutoCAD SHX Text

SMOKE DETECTOR

AutoCAD SHX Text

HS

AutoCAD SHX Text

HAND SWITCH (HAND-OFF-AUTO SWITCH)

AutoCAD SHX Text

ZC

AutoCAD SHX Text

VALVE OR DAMPER POSITION CONTROLLER

AutoCAD SHX Text

HVAC

AutoCAD SHX Text

HVAC CONTROL PANEL

AutoCAD SHX Text

ECC

AutoCAD SHX Text

INTEGRATE CONTROL POINT ON REMOTE GRAPHICS WORKSTATION AT ENERGY CONTROL CENTER

AutoCAD SHX Text

TC

AutoCAD SHX Text

TEMPERATURE CONTROLLER. SEE SEQUENCE OF OPERATION

AutoCAD SHX Text M

AutoCAD SHX Text M

AutoCAD SHX Text

%%UDDC POINT SCHEDULE

AutoCAD SHX Text TEMPERATURE SENSING ELEMENT FOR TRANSMITTING TEMPERATURE TO EMCS (PROVIDE 12 INCHES [200mm] MINIMUM LENGTH IN DUCT WHEN SPACE PERMITS.)

AutoCAD SHX Text

ELECTRIC OPERATED CONTROL DAMPER/OR VALVE

AutoCAD SHX Text NOTES: 1. ALL POINTS SHALL BE TRENDED. TRENDING TYPE SHALL BE EITHER INTERVAL OR CHANGE-OF-VALUE AS APPROPRIATE FOR THE POINT TYPE. DATA SHALL BE PERIODICALLY UPLOADED TO A CENTRAL SERVER AND MAINTAINED FOR A MINIMUM OF 180 DAYS BEFORE BEING DELETED. 2. ALL ANALOG INPUTS AND DIGITAL INPUTS SHALL BE CONFIGURED TO BE ALARMABLE. OPERATORS SHALL HAVE THE OPTION TO SELECT AND CONFIGURE THE POINTS THEY WANT TO ALARM. 3. THE CONTRACTOR SHALL PROVIDE ENTIRE CONTROL COMPONENTS AND DDC CONTROL POINTS FOR A FULLY OPERATIONAL SYSTEM. 4. THE CONTRACTOR SHALL COORDINATE WITH EXISTING BUILDING CENTRAL MONITORING DDC SYSTEMS. THE NEW DDC SYSTEMS SHALL BE COMPATIBLE AND FULLY OPERATIONAL WITH EXISTING CENTRAL DDC SYSTEMS. 4. ALL LOW VOLTAGE WIRING SHALL BE FURNISHED BY CONTROL CONTRACTOR AND MEDIUM VOLTAGE WIRING SHALL BE FURNISHED BY ELECTRICAL CONTRACTOR.ALL LOW VOLTAGE WIRING SHALL BE FURNISHED BY CONTROL CONTRACTOR AND MEDIUM VOLTAGE WIRING SHALL BE FURNISHED BY ELECTRICAL CONTRACTOR.

AutoCAD SHX Text

AUXILIARY DRAIN PAN SENSOR

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text

2-AH2

AutoCAD SHX Text

ELECTRICAL ROOM

AutoCAD SHX Text

2-SF2

AutoCAD SHX Text

AutoCAD SHX Text 1.0

AutoCAD SHX Text

AutoCAD SHX Text

CAV

AutoCAD SHX Text

AutoCAD SHX Text

ELECTRICAL ROOM

AutoCAD SHX Text

2-SF2

AutoCAD SHX Text

BUILT-IN 2-AH2

AutoCAD SHX Text

AutoCAD SHX Text 1.0

AutoCAD SHX Text

CF

AutoCAD SHX Text

PLN

AutoCAD SHX Text

AutoCAD SHX Text

BELT

AutoCAD SHX Text 4.5

AutoCAD SHX Text 3/460

AutoCAD SHX Text

AutoCAD SHX Text

AF-

AutoCAD SHX Text 2X6.63

AutoCAD SHX Text

2-CC1

AutoCAD SHX Text

2-AH2

AutoCAD SHX Text

AutoCAD SHX Text 90.9

AutoCAD SHX Text 66.4

AutoCAD SHX Text 57.3

AutoCAD SHX Text 54.8

AutoCAD SHX Text 47.3

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 9.33

AutoCAD SHX Text 238,862

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 0.56

AutoCAD…