Electrical Safety Program.pdf

PDF 225 KB Posted

Attached to
Z1DA--642-22-104 | Upgrade Substation Building 2 Phase 1 for Philadelphia VAMC
Solicitation number
36C24426R0088
Issued by

About this file

This document is a Medical Center Policy (MCP 138-12) for the Electrical Safety Program at the Corporal Michael J. Crescenz VA Medical Center in Philadelphia, effective June 21, 2023, with recertification due June 30, 2028. The policy establishes comprehensive safety requirements for all electrical line-operated (AC powered) equipment and systems across the medical center, Community Living Center, and affiliated facilities to comply with NFPA-99 "Health Care Facilities Code" and provide a safe environment for patients, staff, and visitors.

The policy delineates specific responsibilities across multiple departments: Biomedical Engineering must conduct initial and periodic electrical safety inspections, testing for ground resistance and leakage current, and maintain documentation via electronic work orders in the VistA system; the Maintenance and Repair Section tests electrical receptacles after replacement or servicing; the Projects Section tests altered/replaced electrical systems and evaluates grounding effectiveness for new construction; and the Safety Section spot-checks for non-approved extension cords and personally owned equipment. All personnel must receive initial and annual electrical safety training, documented per medical center policy. Equipment testing intervals vary by classification: patient-care-related equipment in the Medical Equipment Management Program requires at least annual preventive maintenance and electrical safety inspections, while equipment excluded from the program receives incoming inspection only. Equipment restrictions include mandatory three-wire power cords and three-pin grounding plugs for patient-care equipment (except double-insulated or transformer-powered devices), prohibition of three-to-two wire adapters throughout the facility, and prohibition of all employee-owned and patient-owned electrical devices in Critical Care Rooms. Extension cords and excessively long power cords are prohibited except in temporary situations requiring written approval from designated personnel, and personally owned power strips and extension cords are entirely prohibited. The policy addresses isolated power systems in Operating Rooms, Cardiac Catheterization laboratories, and Interventional Radiography rooms, requiring monthly line isolation monitor testing by using services and annual evaluation by Engineering. Standard 120-volt receptacles in all patient care rooms must be "hospital grade," polarized, 3-conductor, grounded receptacles, tested after initial installation, replacement, or servicing. Patient-owned electrical devices require written approval from the Chief of Facilities Management and submission of an Electronic Work Request to Biomedical Engineering; approved devices receive a "non-hospital-owned" inspection sticker. Employee-owned devices must be registered via VA Form 90-2235, approved by UL or recognized testing laboratory, maintained in good repair, and are not permitted in Critical Care Rooms. The policy includes three appendices addressing extension cord request procedures, patient-owned device approval requirements, and employee-owned device registration and maintenance standards.

View the file

Other files

File Type Posted
2024-12-03_HAZARDOUS AND UNIVERSAL WASTE POLICY.pdf PDF
2024-12-03_HAZARDOUS MATERIALS AND WASTE MANAGEMENT PLAN.pdf PDF
ALL-31-SINGLE-LINES-ONE-FILE-012325.pdf PDF
FMS 138-54 Hot Work Policy.doc DOC document
Confined Space Entry Program.pdf PDF
7714_D_2017-04-06 ASBESTOS MANAGEMENT PROGRAM.pdf PDF
VHA Dir 7714 Asbestos Management Program.pdf PDF
Fire and Smoke Barrier Pentration Permit.pdf PDF
Safety Coordination Meeting Safety Policies for SOW Project 642-22-104.pdf PDF
B6-SUB-PRIMARY-NORMAL-324-371-DWG-FINAL-070623.pdf PDF
Inspection Final RAC Blank Master.docx DOCX document
SAFE PRACTICES FOR WORKING WITH LIVE ELECTRICAL POWER.pdf PDF
36C24426R0088 0004.pdf PDF
RFI 2 Upgrade Substation 36C24426R0088.docx DOCX document
B02-SUB-3.pdf PDF
FMS SOP 138-44 Fire and Smoke Barrier Penetration Policy.pdf PDF
B02-SUB-2.pdf PDF
B6-SITE-POWER-WITH-MANHOLES-DWG-FINAL-070623.pdf PDF
2024-12-03_Green Procedure Program.pdf PDF
FIRE SYSTEM permit 2021 blank.pdf PDF
MANHOLES 19529-02 VA Hospital of Philedelphia 11.17.22.pdf PDF
VHA ICRA-1.2 Oct 1 2024.pdf PDF
B02-SUB-1.pdf PDF
Blank Above Ceiling Permit.pdf PDF
Asbestos Control Regulation.pdf PDF
Building 2_LS_SB_G_B FOR REFERENCE ONLY.pdf PDF
INFECTION PREVENTION AND CONTROL POLICY BEHAVIORAL HEALTH SERVICES.pdf PDF
Fire Plan.pdf PDF
FMS SOP 138-54 Hot Work Policy.pdf PDF
Safety and Health During Construction.pdf PDF
B02-SUB-4.pdf PDF
36C24426R0088 0003.pdf PDF
36C24426R0088 0003.pdf PDF
Attachment 1 RFI 1 Upgrade Substation 642-22-104.docx DOCX document
Attachment 3 General Decision Number PA20260003 10012026.docx DOCX document
Attachment 1 RFI 1 Upgrade Substation 642-22-104.docx DOCX document
Attachment 2 P09 Final SOW Rev1 Building 2 Substation Phase 1 642-22-104 10202026.docx DOCX document
36C24426R0088 0003.pdf PDF
36C24426R0088 0002.docx DOCX document
36C24426R0088 0001.docx DOCX document
S04 Pre-Bid Sign-In Sheet 36C24426R0088 - 642-22-104 - Upgrade Substation.pdf PDF
Substations Upgrade Building 2-Phase 1_Bid Documents_Specification_10-21-24.pdf PDF
Substations Upgrade Building 2-Phase 1 Combined Drawings.pdf PDF
36C24426R0088_1.docx DOCX document
Show all 44

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ELECTRICAL SAFETY PROGRAM

MCP: 138-12

Corporal Michael J. Crescenz Rescinded Document:

VA Medical Center MCP 138-12 dated, April 2021 Philadelphia, Pennsylvania 19104

Signatory Authority: Effective Date:

Karen Flaherty-Oxler, MSN. R.N. June 21, 2023 Medical Center Director

Responsible Owner: Recertification Date:

Chief, Facilities Management Service June 30, 2028

1. POLICY: To outline policy for safety testing, maintenance, use, and restrictions of electrical line-operated (AC powered) equipment and systems at the Corporal Michael J. Crescenz Department of Veterans Affairs Medical Center (CMCVAMC), Community Living Center (CLC), and all affiliated facilities.

2. JUSTIFICATION: To provide a safe environment, free of electrical hazards, for patients, staff, and visitors. It is the policy of CMCVAMC to comply with NFPA-99 “Health Care Facilities Code,” which defines electrical safety requirements for the patient care environment.

3. RESPONSIBILITIES:

A. The Environment of Care Committee is responsible for overseeing the electrical safety program.

B. All Employees are responsible for adhering to the guidelines and procedures specified in this electrical safety policy, and for completing annual training on electrical safety issues for their work area.

C. All Users of electrical line-operated (AC powered) equipment are responsible for visually inspecting equipment prior to use (e.g., check inspection sticker due date, if applicable, check for any damage to cord or case) and notifying Facilities Management when a hazard is suspected or identified.

D. Users of isolated power systems are responsible for monthly testing and documentation of the line isolation monitors (LIMs). LIMs are located in the Operating Rooms (Surgical Service), Cardiac Cath lab (Medicine), and Interventional Radiography (IR) rooms (Radiology).

E. Chief, Facilities Management Support, through Biomedical Engineering, is responsible for ensuring that this electrical safety policy is monitored and

June 21, 2023 MCP: 138-12 enforced. Biomedical Engineering conducts initial and periodic electrical safety inspections for medical equipment as required and initial testing for electrical receptacles in new/renovated patient care rooms. Biomedical Engineering, along with Safety and FMS, will spot check personally owned electrical equipment during Environmental Rounds.

F. Chief, Facilities Management Support, through Maintenance and Repair Section, is responsible for testing of electrical receptacles after replacement or servicing.

G. Chief, Facilities Management Support, through Projects Section, is responsible for ensuring electrical systems are tested after being altered/replaced and effectiveness of the grounding system is evaluated before acceptance for new construction.

H. Chief, Facilities Management Support, through the Safety Section, is responsible for spot checking for any non-approved extension cords/power strips or personally owned equipment during Environmental Rounds or other safety inspections.

I. Chief, Logistics, through Supervisor, Warehouse is responsible to generate an Electronic Work Request to Biomedical Engineering when new Patient-Care-Related electrical equipment arrives on station so it can be properly tested for electrical safety prior to use as needed.

J. Chief, Logistics, through the Asset Management Section, is responsible to coordinate employee-owned equipment requests submitted via VA form 90-2235 and provide “non-hospital-owned” stickers for approved devices.

K. All ACOS’s/Managers/Supervisors are responsible for ensuring their employees are familiar with and adhere to this electrical safety policy, and that employees receive initial and annual training on electrical safety issues for their work area. All training shall be documented in accordance with medical center policy. They shall ensure that all personally owned equipment in their service meets the requirements of this policy.

L. Nurse Managers of in-patient units are responsible for ensuring that patient-owned electrical equipment has been inspected and approved by Biomedical Engineering, is not used in critical care rooms, and is maintained in good working condition.

M. Chief of Information Technology & Operations Services (ITOPS) is responsible for notifying Biomedical Engineering prior to placing any Information Technology Operations & Services (ITOPS) equipment in the Patient-Care Vicinity so it can be properly inspected and isolated if needed.

4. PROCEDURES:

A. New Equipment

(1) Prior to the purchase of medical electrical line-operated (AC powered) equipment, a review of the requisition shall be conducted by Biomedical Engineering. The requesting service shall include the manufacturer's technical specifications as part of their equipment request submission to the Equipment Review Committee.

(2) All electrical line-operated (AC powered) patient-care-related equipment for use in the patient care vicinity shall be tested by Biomedical Engineering for ground resistance, leakage current, and manufacturer's specifications before it is placed into use.

(3) Non-medical electrical line-operated (AC powered) equipment used in a critical care room or other patient care vicinity will be inspected by Safety prior to use.

(4) ITOPS equipment is generally excluded from the incoming inspection requirement. However initial inspections should be performed if placed in the patient care vicinity.

(5) All electrical line-operated (AC powered) patient-care-related equipment and non-medical equipment for use in the patient care vicinity that is loaned to or rented by the VA will be inspected for compliance with VA safety standards by Biomedical Engineering prior to its use and thereafter at a frequency determined by the risk-based Medical Equipment Management Program and its length of time on station. In some cases, for short-term loans/rentals, verification of the vendor’s inspection will be considered in lieu of testing by Biomedical Engineering. A copy of the vendor’s documentation will be reviewed and maintained by the service requesting the equipment (e.g., wound care nurse).

(6) Equipment formally designated as “double insulated” as defined by NFPA-99 will receive only a visual inspection. Plastic-encased devices are not automatically double-insulated. Refer to section 3 above for definition.

B. Equipment Testing

(1) Biomedical Engineering shall be responsible for inspecting, testing, tagging, and maintaining documentation of all required patient-care-related electrical equipment electrical safety inspections. Documentation shall be maintained via electronic work orders in the VistA computer system.

(2) An electrical safety inspection shall be performed after repairs or modifications to electronic/electrical components of electrical line-operated (AC powered) patient-care-related equipment or non-medical equipment used in the patient care vicinity. Repair/replacement of mechanical components which do not compromise the electrical integrity of the device will not require this testing.

(3) Testing Intervals –

a. Electrical line-operated (AC powered) patient-care-related equipment included in the Medical Equipment Management Program (ref: medical center policy (MCP): 138-23) shall receive at least annual preventive maintenance and/or electrical safety inspections. A longer interval may be justified based on previous experience and the Environment of Care Committee's approval.

b. Patient-care-related electrical equipment excluded from the Medical Equipment Management Program will receive an incoming inspection only and repairs as needed. In some instances, equipment that is excluded from the Program may be scheduled for an annual inspection to include an electrical safety test.

c. Non-medical electrical line-operated (AC powered) equipment not used in a critical care room or other patient vicinity will not be inspected periodically by Biomedical Engineering.

Periodic visual checks of this equipment will be the responsibility of the using service. If a problem is identified or suspected, the using service shall notify Engineering immediately via an electronic work request (ref: MCP: 138-16).

(4) Operators of electrical equipment should inspect all pieces of equipment before each use for the following:

a. inspection sticker (if applicable) – verify “due date” has not passed

b. potential hazards, such as:

i. broken or damaged plugs

ii. frayed line cords

iii. abnormal operation (e.g., abnormal vibrations/noise, smoke)

iv. obvious chassis cracks/damage

v. overheating or tingling sensations

NOTE: If a hazard is identified or suspected, notify Engineering immediately via an electronic work request (ref:

MCP: 138-16). The equipment shall not be used and shall be removed from service. If equipment is critical, users shall follow the medical equipment emergency procedures established for that equipment.

C. Equipment Restrictions

(1) All cord-connected electrically powered patient-care-related equipment and any non-medical equipment used in the Patient Care Vicinity shall be provided with a three-wire power cord and a three-pin grounding-type plug. Exception: equipment formally designated as “double-insulated” or using a transformer shall be permitted to have two-conductor cords/plugs.

(2) Three-to-two wire adapters (cheater plugs) are prohibited from use anywhere in the CMCVAMC.

(3) Non-medical electrical devices not commonly equipped with grounding conductors in their power cords are permitted, provided they are not located within the Patient Care Vicinity. Double-insulated appliances shall be permitted in the Patient Care Vicinity.

(4) Equipment powered through a transformer is inherently isolated and may utilize a 2-wire cord and plug.

(5) Extension cords and excessively long power cords are prohibited from use except in temporary situations (see Appendix A for procedures).

Exceptions: Power strips commonly used with ITOPS equipment shall be permitted and provided by the CMCVAMC. All power strips shall be equipped with surge protection. Power strips shall not be plugged into other power strips (i.e., “daisy-chained”). Also, multiple outlet extension cords, including power strips, may be used in portable applications such as on equipment carts. When used in these applications, the outlet shall be hard mounted to the cart and provisions made to store the cord.

(6) Caution shall be taken to not overload receptacles and power strips.

(7) Unless specifically tested for the purpose, ITOPS equipment to be used in patient care rooms shall be placed away from the Patient Care Vicinity so it is not likely to be in contact with the patient.

(8) ITOPS equipment to be used in critical care rooms shall be reviewed on a case-by-case basis by Biomedical Engineering for placement and need for isolation transformers.

(9) No employee-owned or patient-owned electrical line-operated (AC powered) devices may be used in Critical Care Rooms. In other areas, employee-owned and patient-owned electrical line-operated (AC powered) devices are permitted if they are approved in accordance with Medical Center policy (see Appendix B and Appendix C).

(10) The use of personally owned portable heating devices, such as electric space heaters, is prohibited in the CMCVAMC. Hot plates (with open coils) are also prohibited (see Appendix C).

(11) Approval for use of patient-owned battery-only operated devices is not required, as long as they do not transmit/receive an RF signal (reference MCP: 138-32).

D. Power Systems

(1) Receptacles:

a. Standard (120 volt) receptacles in all patient care rooms in the CMCVAMC will be "hospital grade," polarized, 3-conductor, grounded receptacles.

b. All receptacles in patient care rooms will be tested after initial installation, replacement, or servicing.

(2) For new construction, the effectiveness of the grounding system shall be evaluated before acceptance. Whenever the electrical system has been altered or replaced, that portion of the system shall be tested.

(3) Isolated power centers are located in the Operating Rooms, Cardiac Catheterization laboratories, and Interventional Radiography (IR) rooms. The using service shall test the line isolation monitors (LIM) monthly by activating the LIM test switch. Documentation of monthly testing shall be kept by the using service. An annual evaluation of all LIMs shall be performed and documented by Engineering.

E. Employee Education - All ACOSs/Managers/Supervisors shall ensure that all personnel attend initial and annual in-service training on electrical safety and potential electrical hazards in their area. Training is provided during New Employee Orientation and as part of the Mandatory Review training. This training shall be documented in accordance with standard medical center policy.

5. DEFINITIONS:

A. Patient Care Room - Any room of a health care facility wherein patients are intended to be examined or treated (business offices, corridors, lounges, day rooms, dining rooms, or similar areas typically are not classified as patient care rooms). Includes the following types:

(1) Critical Care Room – Room in which failure of equipment or a system is likely to cause major injury or death of patients or caregivers (Category 1). These rooms are typically where patients are intended to be subjected to invasive procedures and connected to line-operated, patient care-related appliances. Examples include, but are not limited to: MICU, SICU, emergency room, interventional radiography (IR) rooms, cardiac cath/EP labs, operating rooms, PACU, and other special care patient rooms used for critical or intensive care.

(2) General Care Room – Room in which failure of equipment or a system is likely to cause minor injury to patients or caregivers (Category 2). Examples include, but are not limited to inpatient bedrooms, dialysis rooms, procedural rooms, and similar rooms.

(3) Basic Care Room – Room in which the failure of equipment or a system is not likely to cause injury to the patients or caregivers but can cause patient discomfort (Category 3). These rooms are typically where basic medical or dental care, treatment, or examinations are performed.

Examples include, but are not limited to, examination or treatment rooms in clinics, medical and dental offices, nursing homes, and limited care facilities.

(4) Patient Care Vicinity - A space, within a location intended for the examination and treatment of patients, extending 6 ft beyond the normal location of the bed, chair, table, treadmill, or other device that supports the patient during examination and treatment and extending vertically to 7 ft. 6 in above the floor. The dimensions of a patient care vicinity are based on the possible reach of the patient or the reach of an attendant who might be touching the bed with one hand and touching a piece of apparatus with the other.

(5) Wet Procedure Locations – The area in a patient care room where a procedure is performed that is normally subject to wet conditions while patients are present, including standing fluids on the floor or drenching of the work area, either of which condition is intimate to the patient or staff.

Routine housekeeping procedures and incidental spillage of liquids do not define a wet procedure location. Examples include: CLC congregate bath/shower rooms and operating rooms.

B. Support Room – Room in which failure of equipment or a system is not likely to have a physical impact on patients or caregivers (Category 4).

Examples include, but are not limited to nurses’ stations, medication rooms, anesthesia work rooms, sterile supply, clinical laboratories, morgues, waiting rooms, dining rooms, utility rooms, and lounges.

C. Non-patient Care Area - Administrative areas and areas where patients have little or no direct contact with electrically powered equipment. Examples include offices and corridors.

D. Types of Equipment:

(1) Patient-Care-Related Electrical Equipment – Electrical medical equipment that is intended to be used for diagnostic, therapeutic, or monitoring purposes in patient care vicinity.

(2) Non-Medical Electrical Equipment – Electrical line-operated (AC powered) equipment that is not classified as Patient-Care-Related.

Examples include floor buffers, lamps and IT equipment such as personal computers, monitors, and printers.

(3) Double-Insulated Appliances – Appliances where the primary means of protection against electrical shock is not grounding. The primary means is by the use of combinations of insulation and separation spacing’s in accordance with an approved standard. Double-insulated appliances can be identified by a symbol consisting of a square within a square or wording such as “double-insulated” marked on the appliance.

Appliance packaging and documents can also provide identification.

6. REFERENCES:

A. NFPA-99, Health Care Facilities Code Handbook, Latest Edition

B. NFPA-70, National Electric Code, Latest Edition

C. VHA Directive 2008-011, “Electrical Safety Policy for Patient Care Equipment”, dated March 10, 2008.

D. MCP 138-23, “Medical Equipment Management Plan”

E. MCP 90-16 “Equipment Request and Assessment Program”

F. MCP 138-16 “Facility Management Work Requests”

G. MCP 138-32 “Restrictions on Use of Cell Phones and Two-way Wireless

Communication Devices”

H. MCP 00-16 “Environmental Rounds”

7. RESCISSION: Medical Center Policy 138-12 “ELECTRICAL SAFETY PROGRAM” dated, April 2021

8. REVIEW: June 2028

9. RECERTIFICATION: June 30, 2028

10. SIGNATORY AUTHORITY:

KAREN FLAHERTY-OXLER, MSN, R.N.

Medical Center Director

NOTE: The signature remains valid until rescinded by an appropriate administrative action.

DISTRIBUTION: MCPs are available at:

https://dvagov.sharepoint.com/sites/VHAPHIcmcvamc/mcpub

Attachments (A, B, C) https://dvagov.sharepoint.com/sites/VHAPHIcmcvamc/mcpub

Appendix A

USE OF EXTENSION CORDS WITHIN THE CMCVAMC

1. All requests for extension cords must be submitted in writing via a work order submitted via the VA VISTA work order system and can only be approved for use on a temporary basis by one of the following personnel:

A. Chief, Facilities Management - Extension 204251

B. Assistant Chief, Facilities Management – Extension 205811

C. Chief, Biomedical Engineering - Extension 206105

D. Electric Shop Foreman – Extension 205170

E. Safety Manager or designated Specialist - 206109

2. Any extension cord approved for use will be furnished by Facilities Management only until such time as permanent modifications can be made. Unless specifically designed, extension cords will not be used to power refrigerators, microwave ovens, toaster ovens, coffee pots, or other high current-draw equipment.

3. Personally, owned power strips and extension cords are prohibited from use and not permitted to be brought into the Medical Center. All personally owned multiple outlets, power strips, and extension cords shall be removed from the facility immediately.

4. Services are not to request extension cords based on rearrangement of furniture or for use of personally owned equipment. These requests will be denied.

5. The Office of Safety will automatically confiscate any non-approved extension cord or power strip found during inspections.

Appendix B

PATIENT-OWNED ELECTRICAL LINE-OPERATED DEVICES

1. Written permission of the Chief, Facilities Management, or designee must be obtained before patient-owned electrical line-operated devices can be used. To comply with those regulations, the procedure described below shall be followed any time that you are aware of a patient or patient's family that wishes to bring such a device into the

CMCVAMC:

A. No patient-owned electrical line-operated device is permitted in the patient's room or otherwise used, until approval of the Chief, Facilities Management, or designee, has been obtained.

B. No patient-owned electrical line-operated devices may be used in Critical Care Rooms (e.g., MICU, SICU, etc.). Devices used in General Care Rooms shall be placed outside the patient vicinity.

C. The patient's physician, nurse, or other VA representative must submit an Electronic Work Request to Biomedical Engineering (ref: MCP 38-16). This request should state the patient's name, room number, description of the device, a brief statement as to why the device is required, and the name and phone extension of the VA representative.

D. The Chief, Facilities Management, or designee will approve or disapprove the request upon consideration of the justification provided and the recommendations from Biomedical Engineering regarding the safety of the device.

E. If the request is approved, the electrical device will be affixed with a non-hospital-owned equipment inspection sticker and returned to the patient for use.

If the request is not approved, an inspection sticker will NOT be affixed, the device will be returned, and the device must be removed from the CMCVAMC

2. Any patient-owned device currently being used at the medical center that does not have a safety inspection label affixed has NOT been approved for use. Written permission for these devices must be obtained as soon as possible or they should be removed from use.

3. Patient-owned devices shall be inspected initially; however subsequent periodic inspections will not be performed by Biomedical Engineering. The Nurse Manager shall ensure that patient-owned devices are maintained in good operating condition.

4. Approval for use of patient-owned battery-only operated devices is not required, as long as it does not transmit/receive an RF signal (reference MCP 138-32).

Appendix C

EMPLOYEE-OWNED ELECTRICAL LINE-OPERATED DEVICES

1. All employee-owned electrical line-operated (AC powered) devices (radios, coffee pots, etc.) must be registered/reported to the Asset Management Section of Logistics via VA form 90-2235. If approved, a “non-hospital-owned” sticker shall be affixed to the device.

2. The CMCVAMC does not encourage the use of personally owned, line operated devices. However, if an employee brings a personally owned device on station, the employee and supervisor shall ensure the device complies with the requirements below and that it remains in good working condition. Compliance with this policy shall be reviewed during weekly Environmental Rounds inspections (ref: MCP 00-16):

A. Employee-owned electrical devices are not permitted in Critical Care Rooms.

B. Must be approved by UL (Underwriter's Laboratories, Inc.) or another recognized testing laboratory.

C. Device must be in good repair (no frayed cords, broken plugs, cracked housings, missing parts, etc.). Power cords and plug will be visually inspected on a regular basis by the employee owner/user. If the power cord or other parts are found to be defective, the appliance must be removed from service until repaired at the employee owner's expense.

D. Electrical capabilities must be available to accommodate the device.

There will be no building alterations, such as the installation of additional outlets, made to accommodate personally owned equipment.

3. This section removed in lieu of newly proposed MCP 138-11. The new MCP is specific to cooking appliances. See MCP 138-11 Personally Owned Cooking Appliances for information and approval requirements. Approval of this change and acceptance and approval of new MCP is requested.