Confined Space Entry Program Policy

This is a Medical Center Policy (MCP 138-45) establishing procedures for safe confined space entry at the Corporal Michael J. Crescenz Department of Veterans Affairs Medical Center in Philadelphia, Pennsylvania, effective January 22, 2024, with recertification required by January 31, 2029. The policy establishes comprehensive requirements for identifying, assessing, and safely entering permit-required confined spaces (PRCS) in compliance with OSHA regulation 29CFR 1910.146.

The policy defines three classifications of confined spaces based on atmospheric hazard levels: low, moderate, and high hazard atmospheres. Key procedural requirements include initial and pre-entry hazard assessments, atmospheric testing (monitoring oxygen, carbon monoxide, hydrogen sulfide, and flammable gas concentrations), lockout/tagout procedures, isolation of harmful substances through blanking, blinding, or double block-and-bleed systems, and continuous ventilation while workers occupy spaces. The policy mandates Entry Supervisors, Attendants, and Entrants complete confined space training and establishes specific communication, atmospheric monitoring, and rescue protocols varying by hazard level. For high-hazard atmosphere spaces, rescue personnel must be stationed at the entrance with continuous monitoring capability; moderate-hazard spaces require standby personnel at or near the entrance with checks at least every 20 minutes; low-hazard spaces require continuous means of summoning assistance. All entries require completion of a Confined Space Entry Permit documenting atmospheric test results, precautions, PPE requirements, rescue procedures, and worker names. The policy specifies that CMCVAMC has contracted with the Philadelphia Fire Rescue Department for 24-hour rescue services and maintains an inventory of confined spaces throughout its facilities including manholes, crawl spaces, boilers, and air handlers listed in Appendix F.

View the file

Other files

File Type Posted
2024-12-03_HAZARDOUS AND UNIVERSAL WASTE POLICY.pdf PDF
2024-12-03_HAZARDOUS MATERIALS AND WASTE MANAGEMENT PLAN.pdf PDF
ALL-31-SINGLE-LINES-ONE-FILE-012325.pdf PDF
FMS 138-54 Hot Work Policy.doc DOC document
Electrical Safety Program.pdf PDF
7714_D_2017-04-06 ASBESTOS MANAGEMENT PROGRAM.pdf PDF
VHA Dir 7714 Asbestos Management Program.pdf PDF
Fire and Smoke Barrier Pentration Permit.pdf PDF
Safety Coordination Meeting Safety Policies for SOW Project 642-22-104.pdf PDF
B6-SUB-PRIMARY-NORMAL-324-371-DWG-FINAL-070623.pdf PDF
Inspection Final RAC Blank Master.docx DOCX document
SAFE PRACTICES FOR WORKING WITH LIVE ELECTRICAL POWER.pdf PDF
36C24426R0088 0004.pdf PDF
RFI 2 Upgrade Substation 36C24426R0088.docx DOCX document
B02-SUB-3.pdf PDF
FMS SOP 138-44 Fire and Smoke Barrier Penetration Policy.pdf PDF
B02-SUB-2.pdf PDF
B6-SITE-POWER-WITH-MANHOLES-DWG-FINAL-070623.pdf PDF
2024-12-03_Green Procedure Program.pdf PDF
FIRE SYSTEM permit 2021 blank.pdf PDF
MANHOLES 19529-02 VA Hospital of Philedelphia 11.17.22.pdf PDF
VHA ICRA-1.2 Oct 1 2024.pdf PDF
B02-SUB-1.pdf PDF
Blank Above Ceiling Permit.pdf PDF
Asbestos Control Regulation.pdf PDF
Building 2_LS_SB_G_B FOR REFERENCE ONLY.pdf PDF
INFECTION PREVENTION AND CONTROL POLICY BEHAVIORAL HEALTH SERVICES.pdf PDF
Fire Plan.pdf PDF
FMS SOP 138-54 Hot Work Policy.pdf PDF
Safety and Health During Construction.pdf PDF
B02-SUB-4.pdf PDF
36C24426R0088 0003.pdf PDF
36C24426R0088 0003.pdf PDF
Attachment 1 RFI 1 Upgrade Substation 642-22-104.docx DOCX document
Attachment 3 General Decision Number PA20260003 10012026.docx DOCX document
Attachment 1 RFI 1 Upgrade Substation 642-22-104.docx DOCX document
Attachment 2 P09 Final SOW Rev1 Building 2 Substation Phase 1 642-22-104 10202026.docx DOCX document
36C24426R0088 0003.pdf PDF
36C24426R0088 0002.docx DOCX document
36C24426R0088 0001.docx DOCX document
S04 Pre-Bid Sign-In Sheet 36C24426R0088 - 642-22-104 - Upgrade Substation.pdf PDF
Substations Upgrade Building 2-Phase 1_Bid Documents_Specification_10-21-24.pdf PDF
Substations Upgrade Building 2-Phase 1 Combined Drawings.pdf PDF
36C24426R0088_1.docx DOCX document
Show all 44

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CONFINED SPACE ENTRY PROGRAM

MCP: 138-45

Corporal Michael J. Crescenz Rescinded Document:

VA Medical Center NONE Philadelphia, Pennsylvania 19104

Signatory Authority: Effective Date:

Karen Flaherty-Oxler, MSN, RN January 22, 2024 Medical Center Director

Responsible Owner: Recertification Date:

Susan McCaffrey January 31, 2029 Facility Chief Engineer

1. POLICY: To establish policy and procedures to eliminate or minimize the risk to workers who enter or work in confined spaces in compliance with federal regulations at the Corporal Michael J. Crescenz Department of Veterans Affairs Medical Center (CMCVAMC).

2. DEFINITIONS:

A. Attendant- means an individual stationed outside one or more permit spaces who monitors the activities inside and outside of a permit required confined space during an entry. See Responsibilities (Section 3) for a list of Attendant duties.

B. Confined Space - A confined space is any space that has all three of the following characteristics:

1. Is large enough and so configured that an employee can bodily enter and perform assigned work; and

2. Has limited or restricted means for entry or exit (for examples are tanks, storage bins, manholes and vaults); and

3. Is not designed for continuous employee occupancy.

C. Confined Space List - A consolidated list of all confined spaces by site. This list provides a location, description, classification, hazards, and Entry Procedures for all known confined spaces on CMCVAMC property.

D. Emergency Service- means the personnel designated to enter a PRCS and conduct rescue an incapacitated Entrants in the event self rescue or non-entry rescue methods are not possible.

January 24, 2024 MCP 138-45

E. Entrant -means an employee who is authorized by the employer to enter a permit space and shall be referred to as the Entrant. See Responsibilities (Section 3) for a detailed list of Entrant duties.

F. Entry Permit- means the written or printed document that is provided by the

Entry Supervisor to authorized entry and control activities in a Permit Required Confined Space (See Appendix C).

G. Entry Procedures- means the steps, actions, and conditions that must be taken and exist in a PRCS to allow entry and to ensure that employees involved with a PRCS Entry can safely enter into and work within the space.

H. Entry Supervisor- means the person responsible for developing Entry

Procedures, authorizing, and overseeing PRCS Entry operations to ensure all PRCS entries are conducted in accordance with this policy and specific Entry Procedures as listed on the Confined Space List. See Responsibilities (Section 3) for a detailed list of Entry Supervisor duties.

1. The following positions may serve as Entry Supervisor as long as they are trained in confined space procedures and Entry Supervisor duties.

a. Industrial Hygienist

b. Safety Specialists and Manager

c. Facilities Management Supervisors

d. Contractor with relevant training

I. Immediately Dangerous to Life and Health (IDLH) - means any condition that poses an immediate or delayed threat to life or that would cause irreversible adverse health effects or that would interfere with an individual's ability to escape unaided from a permit space. This may include an atmosphere with:

1. An oxygen deficiency (less than 19.5%) or an oxygen enriched (more than 23.5%) atmosphere

2. A concentration of flammable gas, vapors, or mist in excess of 10% of its lower flammable limit (LEL);

3. Atmospheric concentration of any hazardous substance identified in

29CFR 1910 subpart G or Subpart Z which could result in employee exposure in excess of its dose or permissible exposure limit;

J. Isolated - means the process by which a PRCS is removed from service and completely protected against the release of energy or material into the space by such means as: blanking or blinding; misaligning or removing sections of lines, pipes, or ducts; a double block and bleed system;

Lockout/Tagout of all sources of energy; or blocking or disconnecting all mechanical linkages.

K. Non-Entry Rescue- means the extraction of an incapacitated Entrant from a PRCS, by the Attendant, with the use of a retrieval system; without the Attendant making physical entry into the PRCS.

L. Non-permit confined space (NPCS) - means a confined space that does not contain or, with respect to atmospheric hazards, have the potential to contain any hazard capable of causing death or serious physical harm.

M. Permit Required Confined Space (PRCS): is a confined space that has one or more of the following characteristics:

1 Contains a hazardous atmosphere or has a potential hazardous atmosphere;

2. Contains a material that has the potential for engulfing an Entrant;

3. Has an internal configuration such that an Entrant could be trapped or asphyxiated by inwardly converging walls or by a floor which slopes downward and tapers to a smaller cross-section; or

4. Contains any other recognized serious safety or health hazard

N. Permit Required Confined Space (PRCS) Entry: means the action by which a person passes through an opening into a PRCS. Entry includes ensuing work activities in that space and is considered to have occurred as soon as any part of the Entrant's body breaks the plane of an opening into the space.

O. Retrieval system - means the equipment (including a retrieval line, full-body harness, wristlets - if appropriate, and a lifting hoist, and anchor) used for Non-Entry Rescue of persons from permit spaces.

3. RESPONSIBILITIES:

A. FMS

1. Shall maintain the written Confined Space Program and associated documentation to include:

a. Confined Space Evaluation Forms

b. PRCS Entry Reclassification Forms

c. Completed Entry Permits

d. Copies of Contractor Entry Permits for entries made on CMCVAMC property

e. Confined Space Training Documents

2. May serve as an Entry Supervisor, Attendant, or Entrant as long as he/she is trained in the duties of each position.

3. Shall maintain and inspect retrieval equipment annually in accordance with manufactures instructions.

4. Shall maintain atmospheric testing equipment and supply calibration gas to perform bump and calibration tests in accordance with manufactures instructions.

5. Shall conduct Confined Space Training.

6. Conduct an annual review of this confined space program in accordance with 29CFR 1910.146.

B. Entry Supervisor:

1. Shall complete confined space training as required by the confined space program.

2. Shall know the hazards that may be faced during entry, including information on the mode, signs or symptoms, and consequences of the exposure.

3. Shall verify that PRCS entries are conducted in accordance with this policy and the specific the Entry Procedures listed on the Confined Space List.

4. Shall perform a bump check/calibration check of atmospheric testers prior to each day’s use.

a. Shall perform calibration of atmospheric testers as necessary based on results of bump check.

5. Shall issue the Entry Permit only after verifying that:

a. The Entrant and Attendant are trained in PRCS entry

b. The Entry Procedures listed on the Confined Space List have been taken and are document on the Entry Permit

c. All known hazards inside the PRCS have been eliminated, Isolated or effectively controlled.

d. The authorized tasks and duration of the PRCS Entry are clearly defined and documented on the Entry Permit.

e. The Attendant has a means of communication to summon Emergency Services.

f. The Attendant and Entrant have an effectively method to communicate during the Entry.

g. A Retrieval System is set up and functionally checked at the PRCS location prior to entry as required by Section of this policy.

6. Shall evaluate PRCS if conditions change within the space during a PRCS entry or a Reclassified Entry.

7. Shall forwards all completed PRCS Entry Reclassification Forms and Entry Permits to Industrial Hygienist.

8. May serve as an Attendant or Entrant as long as he/she is trained in the duties of each position.

9. May reclassify an entry as a non-permit entry under the conditions listed in Section IV paragraph D.

C. Attendants shall:

1. Complete confined space training as required by the training section of this policy.

2. Comply with this policy, the specific PRCS Entry Procedures, and limited tasks and entry duration as authorized by the Entry Permit.

3. Know the hazards that may be faced during entry, including information on the mode, signs or symptoms, and consequences of the exposure.

4. Ensure that prior to Entry:

a. The Entry Supervisor has signed the Entry Permit

b. The Entrant reviews and signs a the Entry permit

c. The Emergency Services contact information is documented on the Entry Permit

d. A reliable method of communication is available and documented on the Entry Permit.

e. A reliable method means of communication is available to summon Emergency Services.

f. Atmospheric testing has been accomplished and document on the Entry Permit as required by the Entry Procedures.

5. Perform functional test of atmospheric monitoring equipment at the PRCS location to ensure it has not been damage during transportation.

6. Monitor activities inside and outside the space to determine if it is safe for Entrant to remain in the space.

a. Prevent unauthorized personnel from entering a PRCS.

b. Perform atmospheric testing as required by the Entry Procedures or as indicated on the Entry Permit.

7. Remain outside the permit space during entry operations until relieved by another Attendant.

8. Performs no duties that might interfere with the Attendant's primary duty to monitor and protect the entrants.

9. Continuously maintain an accurate count of all Entrants in the PRCS.

10. Communicate with Entrants as necessary to monitor the Entrant’s status and to alert Entrants of the need to evacuate the space.

a. Be aware of possible behavioral effects of hazard exposure in Entrants.

11. Orders the Entrants to evacuate the permit space immediately if:

a. The Attendant detects a prohibited condition or conditions within the PRCS change during a Permit Entry

b. The Attendant detects the behavioral effects of a hazard exposure in an Entrant;

c. The Attendant detects a situation outside the space that could endanger the Entrant; or

d. The Attendant cannot effectively and safely perform all the duties required under this section;

12. Summon the Emergency Service if the Entrant becomes unresponsive or is in need of emergency medical services

13. Use the Retrieval System to perform Non-Entry Rescue in the event an Entrant is incapable of self rescue or unresponsive

D. Entrants shall:

1. Complete confined space training as required.

2. Ensure PRCS entries are conducted in accordance with the specific Entry Procedures for the PRCS and as authorized by the Entry Permit.

3. Comply with PRCS reclassification procedures and sign/date the

Reclassification Form to certify that the associated hazards have been eliminated or isolated in accordance with the entry procedures listed on the Confined Space List prior to entry in accordance with Section IV paragraph D.

4. Review and Sign the Entry Permit to acknowledge:

a. The know hazards that may be faced during entry

b. The current conditions of the PRCS

c. The entry duration and tasks authorized to be performed during the entry.

5. Properly use retrieval system equipment and any PPE required by

PRCS Entry Procedures and Entry Permit.

6. Communicate with the Attendant as necessary to ensure the

Attendant is able to monitor Entrant’s status and alert Entrants of the need to evacuate the space as required;

7. Know the mode, signs or symptoms and consequences of the exposure any known or potential hazards in the PRCS.

8. Alert the Attendant whenever the Entrant recognizes any warning sign or symptom of exposure to a dangerous situation, or the Entrant detects a prohibited condition;

9. Exit the PRCS as quickly as possible whenever:

a. An order to evacuate is given by the Attendant or the Entry Supervisor,

b. The Entrant recognized any warning sign or symptom of exposure to a dangerous situation,

c. The Entrant detects a prohibited condition,

d. An atmospheric monitor alarm is activated.

E. Contractors Responsibilities

1. Contractors are responsible to fully comply with the OSHA 1910.146 Permit-Required Confined Spaces standard.

2. CMCVAMC Contracting Officer Technical Representative (COTR) will ensure that the contractor’s Entry Supervisor Review the confined space hazards and Entry Procedures listed on the Confined Space List.

3. CMCVAMC employees will not enter into PRCS under a contractor’s

Entry Permit.

4. COTR will obtain and forward a copy of the contractor’s closed Entry

Permits to the CMCVAMC Safety Office.

4. PROGRAM DETAILS:

Identification of Confined Spaces

Each confined space that requires special precautions is identified on an inventory.

This inventory is maintained by the Safety Department

Each confined space that does not require entry has a warning sign posted at the entry stating that it is a confined space and that entry is not allowed. A confined space identification chart is provided in Appendix A.

Hazard Identification and Risk Assessments

Hazard identification and risk assessments must be conducted and documented for each confined space or group of similar confined spaces. There are two types of risk assessment that must be completed: Initial and Pre-Entry Assessments.

Initial Hazard Identification, Risk Assessment, and Classification

Use the Risk Assessment and Classification Form in Appendix B. This form must be completed by a qualified person as part of the initial identification and classification process. It must be done for all confined spaces or groups of similar spaces in CMCVAMC.

This initial assessment is done in order to identify confined spaces, provide an initial classification of the spaces, and to aid in maintaining the confined space inventory. Use the Confined Space Risk Assessment and Classification Form for this purpose. The completed forms will be reviewed, and the space classification confirmed by the Confined Space Administrator and/or by the Manager responsible for the space. The hazard identification and initial risk assessment must include the following information:

1. Location of the space.

2. The conditions that may exist prior to entry due to the confined space’s design, location. or use, and those which may develop during work activity inside the space.

3. Atmospheric hazards including the potential for oxygen enrichment and deficiency, flammable gas, vapor or mist, combustible dust, and other hazardous atmospheres.

4. Physical hazards such as noise, electric shock, deteriorating structural components, slick, wet surfaces, etc.

5. Lockout and isolation requirements.

6. The potential for engulfment and entrapment.

7. Layout of the space, which may include a floor plan/schematic drawing.

Hazard identification will be redone (and the risk assessments will be revalidated) whenever a significant change in the risk is likely to result from any of the following:

1. installation or modification of a space.

2. a change in equipment operating conditions.

3. a change in the atmosphere or working environment.

4. a change in working arrangements or procedures.

Pre-Entry Assessment

The second hazard identification and risk assessment are done by workers just prior to entering the space using the Confined Space Entry Permit found in Appendix C. This assessment is done to identify any changes that may have taken place in the confined space since the initial assessment and since the last entry. It takes into account the type of work to be done and any equipment or materials that will be used in the space during the entry. The Confined Space Entry Permit / Form will be used for this purpose.

The information on the form must include, but not necessarily be limited to, the following:

a. The nature of the confined space, e.g., manhole, pump station, chamber, box culvert, water,

b. sewer or storm main, etc.

c. The work required to be done, e.g., maintenance, valve shut-off.

d. Any potentially harmful substances that may be used in the work process and procedures

e. to eliminate or minimize the risk to workers.

f. The hazards involved and the associated risks, e.g., hazardous atmosphere present.

g. Emergency and rescue procedures.

h. Gas detector readings.

Lockout

Lockout is used to eliminate or minimize hazardous energy in confined spaces.

Lockout procedures have been established for all work being performed in confined spaces. CMCVAMC uses locks to render machinery or equipment inoperable and to isolate energy sources in accordance with the organization’s written lockout program and procedures. The lockout procedures and all lockout points are identified and documented as part of the hazard identification and risk assessment process.

Isolation and Control of Harmful Substances

If there is piping entering and/or exiting the space that contains or has contained a harmful substance as described in CMCVAMC Regulation 9.18(1), it must be controlled by either disconnecting the adjacent piping or isolating it using blanks or blinds that are either certified by a professional engineer or have been manufactured in accordance with ANSI standards (see CMCVAMC Regulation Part 9.20).

If the harmful substance in the piping is not a gas or vaper or a volatile liquid, then in addition to either disconnecting the adjacent piping or isolating it using blanks or blinds, a double block and bleed system may be used as per CMCVAMC Regulation 9.21. (Double block and bleed involves closing two valves in the line, and opening a drain valve between them.)

Opening piping to install blanks and blinds is dangerous if the piping contains harmful materials. Workers must follow written safe work procedures when installing blanks and blinds. The written procedures include the procedure to depressurize the line and drain the system. Proper personal protective equipment including respirators, if required, must be part of the written procedures, as well as lockout procedures and monitoring for air contaminants.

Municipal Water Systems

If a substance in the piping is harmful only because of the temperature, pressure or quantity of the substance, e.g., a municipal water system, then the harmful substance must be controlled by either:

• disconnecting the adjacent piping, or

• isolating it using blanks or blinds as per Regulation 9.20, or

• using a double block and bleed system as per Regulation 9.21, or

• by isolating the adjacent piping in a manner that a professional engineer has certified will make the confined space safe for a worker to carry out the intended work, or

• if there is no head pressure in the adjacent piping, by de-energizing and locking out each pressure source for the adjacent piping and depressurizing the adjacent piping.

The Alternative Measures section below also applies to this section with regards to controlling the flow of non-hazardous fluid by closing a valve or using inflatable rubber bladders. See CMCVAMC Guideline regarding Regulation 9(18)(3)(b) for more information.

Municipal Sanitary Sewers

Where the gases from a gravity-flow municipal or domestic sanitary sewer system or storm sewer system may enter the space, a worker may enter if:

• The space is protected from the ingress of gases by use of a p-trap.

• The atmosphere in the space has been tested immediately before entry and the testing confirms clean, respirable air.

• The integrity of the p-trap has been confirmed immediately prior to entry.

• The atmosphere is continuously monitored while the worker is in the space and confirms the space contains clean, respirable air.

Alternative Measures

Where normal isolation practices are not practicable in a municipal sewage system (including storm drains systems) an evaluation will be conducted by a qualified person to determine the alternate measures required in order to safely enter the space without isolating the liquid flow. Alternate measures may include simply closing a valve instead of blanking, blinding or double block and bleed. The alternate measures, including occupational hygiene and safety precautions other than or in addition to isolation, will be submitted to the Safety Department to determine acceptability prior to entering the space.

Alternate measures for fluid control may include inserting inflatable rubber bladders into pipes, or simply closing valves or gates. If possible to lockout the device, then a lockout system must be implemented, e.g. for closing valves.

Communication

One of the most important components of any Confined Space Entry Program is communication. Workers can be placed at significant risk if:

• A confined space is improperly identified due to poor communication,

• The procedures are improperly followed, or

• Help is delayed.

There are several pieces of information that must be communicated to the workers involved in the entry. Each worker involved in the entry must know or be aware of:

1. whether the space is on the inventory.

2. the results of the hazard identification.

3. the results of the risk assessment on the work that they are going to perform in the confined space.

4. the precautions that are required for this confined space.

5. his/her responsibilities and who else in the organization is responsible for confined spaces, and what those responsibilities are.

6. the requirement for a permit, the whereabouts of the permit, and that their name is on the permit.

7. the requirements for lockout and where the lockout points are.

8. who the standby person is and the method of communication with that person.

Each class of confined space has different requirements for communication between the standby person and the worker(s) in the space:

1. Low Hazard Atmosphere Communication:

In a confined space with a low hazard atmosphere, there must be continuous means of summoning the standby person. Also, the standby person must:

• check on the wellbeing of workers inside the space at least every 20 minutes, and

• have a means to immediately summon rescue personnel.

2. Moderate Hazard Atmosphere Communication:

In a confined space with a moderate hazard atmosphere, there must be a continuous means of summoning the standby person. Also, the standby person must:

• be stationed at or near the entrance to the space,

• visually observe or otherwise check the wellbeing of the workers inside the space at least every 20 minutes or more often if required,

• have a means to immediately summon rescue personnel.

3. High Hazard Atmosphere Communication:

In a confined space with a high hazard atmosphere, or potential for engulfment or entrapment, there must be a continuous means of summoning the standby person.

Also, the standby person must:

• be stationed at the entrance to the space,

• continuously monitor the wellbeing of the workers in the space,

• be equipped and capable of immediately commencing the rescue of the workers in the space.

Atmospheric Testing and Monitoring

All confined spaces must be continuously monitored for the presence of contaminants and safe oxygen levels prior to and during entry. This must be done by a trained worker using calibrated equipment and in accordance with written procedures. A record of the tests must be kept using the Confined Space Entry Permit / Form.

Atmospheric testing will ensure that:

a. the confined space contains a safe oxygen level - between 19.5% and

23.5%.

b. the atmospheric contaminants in the confined space are reduced to below the relevant CMCVAMC permissible exposure levels, e.g., Hydrogen sulfide less than 10 ppm, Carbon Monoxide less than 25 ppm.

c. the concentration of flammable contaminant in the atmosphere is below 10% of its LEL.

In addition to regular atmospheric testing for contaminants such as hydrogen sulfide and carbon monoxide, testing for other contaminants should be done based on the information recorded in the confined space risk assessment for the specific confined space that is to be entered. Some possible contaminants include, but are not limited to:

Gas or Contaminant Possible Locations

Hydrogen Sulfide (H2S) Sewers/Crawl Spaces

Carbon Monoxide (CO) Sewers

Ammonia (NH3) Arenas

Chlorine (Cl) Pools

Methane (CH4) (Explosives) Sewers

Ozone (O3) Pools

Petroleum Hydrocarbons Various

The worker doing the testing must always assume that the space has a dangerous atmosphere until it is proven otherwise. Testing must be done in the following order:

1. At the opening of the space – Where possible, test above a manhole cover or access hatch prior to opening.

2. Before ventilating - After removing the cover to the space test at various levels of the space, i.e., at least every 5 feet, and record.

3. Testing after ventilation can give false security to the workers because they will not know if a hazard existed prior to the ventilation and therefore may not look for the source of the contaminants.

4. Monitor continuously - while workers are in the space.

Record the results of the monitoring at least every 20 minutes, more when a contaminant is known to be or could possibly be in the space.

Pre-entry atmospheric testing is not required in a confined space with a low hazard atmosphere if:

1. the location and control of the space ensures a more hazardous atmosphere could not inadvertently develop,

2. such testing is not required to verify the effectiveness of an isolation or other pre-entry control,

3. prior documented representative sampling shows the space contains clean respirable air, and

4. the written procedures do not require such testing.

Atmospheric testing will be completed within 20 minutes before workers enter the space and prior to each re-entry if all workers leave the space for more than 20 minutes.

Atmospheric Hazards

Oxygen Hazards

Hazards due to oxygen can occur as a result of oxygen enrichment or oxygen deficiency. Oxygen naturally occurs in the atmosphere at approximately 20.8 percent of the total volume of air.

Oxygen enrichment can occur as a result of chemical processes or as a result of leakage from a tanked source such as welding equipment. When the percentage of oxygen in the air is greater than 23 percent, it significantly increases the rate of chemical reactions and can cause an explosive atmosphere.

Oxygen deficiency can occur as a result of:

• rusting of metal consumes oxygen.

• bacterial action such as found in sewage systems consumes oxygen.

• chemical processes in the space.

• displacement by other gases such as Carbon Dioxide and some fire extinguishing agents. operation of open flame heaters or internal combustion engines, as well as any other burning activities that use oxygen.

Oxygen can also be displaced by acetylene, methane, propane and natural gas.

When the percentage of oxygen in the air is less than 19.5 percent, it can result in disorientation and unconsciousness. At oxygen levels less than 6 percent, unconsciousness occurs in a matter of minutes, followed by death.

Flammable Hazards

Flammable gases and vapors can result in explosions. Decaying organic matter can produce methane gas. Natural gas can be present due to leaks in the building or home heating gas distribution system. Gasoline can be found in storm drains as a result of inadvertent or intentional disposal. Acetylene can leak from tank or piping systems for welding. Flammable gases and vapors can become explosive when they are mixed with air in concentrations over a certain range. In some circumstances airborne dust can create an explosive atmosphere, e.g., fine wood dust, coal dust.

Where workers must enter a confined space, the concentration of flammable gases and vapors in the space will be maintained below 10 percent of the lower explosive limit. If any flammable or explosive gas, vapors or liquids are present, all sources of ignition will be eliminated prior to entry, including cutting, grinding and burning activities.

Non-sparking tools will be used, and equipment will be grounded to prevent static electricity.

Only intrinsically safe electrical equipment will be used in confined spaces where there is a possibility of a flammable atmosphere.

Note: LEL concentrations vary between chemicals, and the meter measuring them.

Contact the site Industrial Hygienist if your LEL concentration is increasing.

Carbon Monoxide Hazards

Carbon monoxide is a colorless, odorless, tasteless gas that results from the incomplete combustion of hydrocarbon fuels, e.g., gasoline, diesel. It is commonly produced by internal combustion engines and may be produced by the decomposition of organic matter. It can cause workers to become disoriented and can cause death. Carbon monoxide is the same weight as air and therefore can be found in the breathing zone. It has an 8-hour exposure limit of 25 ppm and a 15-minute ceiling exposure limit of 100 ppm.

Hydrogen Sulfide (H2S) Hazards

Hydrogen sulfide is a gas that is produced by the decomposition of organic matter.

It can be found in sewage systems, but also in stagnant areas in storm drains. It smells like rotten eggs, but even low levels of hydrogen sulfide can paralyze the sense of smell. Hydrogen sulfide can be fatal at very low levels. This gas is heavier than air and will collect in low areas, but it can be moved by strong air currents and so may be at the top of the space as well. Hydrogen sulfide has a ceiling permissible concentration of 10 ppm.

Permits

There are certain situations, as outlined below, in which a confined space entry permit is required. If a permit is required, no worker is allowed to enter the space until the permit has been filled out and signed by the supervisor.

A permit is required:

• If the hazard assessment shows that the confined space has the potential for a high hazard atmosphere. A high hazard atmosphere means an atmosphere that may expose a worker to risk of death, incapacitation, injury, acute illness or otherwise impair the ability of the worker to escape unaided from a confined space, in the event of a failure of the ventilation system or respirator.

• If there is a potential for entrapment. Entrapment can be caused by structural failure, such as rusting of the floor of a culvert, or hazardous adjacent activities such as a location next to a chlorine plant that might require evacuation. It can also be caused by the design of the space.

• If there is a potential for engulfment. This refers to being buried by loose materials or being drowned by fluids. This risk occurs whenever free flowing solid or liquid materials are present in enclosures.

• If lockout is required either prior to entering the space or while work is being done in the space.

• If isolation is required, for example:

o If piping into the space must be disconnected o If blanks, or blinds must be installed, or o If a double block and bleed system is used

The confined space entry permit:

• Describes the type of the work being done in the space.

• Describes the ventilation system being used.

• Records the results of the atmospheric testing.

• Lists the precautions that must be taken to minimize the risk to workers entering and working in the space.

• Names each worker that is in the space.

• Outlines the provision for rescue.

• Identifies the expiry time of the permit.

• Must be re-authorized and signed by the supervisor if there is a change in the work crew or supervisor.

An example of a Confined Space Entry Permit is included in Appendix C.

Completed permits are kept by Safety Department for a minimum period of one year.

Cleaning and Purging

Whenever possible, CMCVAMC will ensure that a confined space contains clean respirable air. If the confined space does not contain clean respirable air, cleaning, purging or venting will be used to control the hazardous atmosphere.

Purging residual gases in the space may precede cleaning of residual materials within the space. Purging is the removal of a dangerous atmosphere in a confined space by a fluid such as water or non-flammable gas such as nitrogen or carbon dioxide. Prior to entry, the purge gas will be displaced with ventilation, and the atmosphere will be tested to ensure that clean respirable air exists.

Ventilation

All confined spaces will be continuously ventilated while workers are inside the space except in:

• an atmosphere intentionally inert or

• a low hazard atmosphere where the following conditions are met:

o the atmosphere is continuously monitored and shown to contain clean respirable air, and o the space has an internal volume greater than 1.8m3 (64 cu ft) per occupant, is occupied for less than 15 minutes, and the work inside the space generates no contaminants other than exhaled air.

The ventilation blower is to be situated up wind of the entry point so as to draw clean air, free of dust, exhaust fumes, etc. The standby worker must be aware of changes in wind direction, etc., and adjust the air intake as required. The discharge end of the hose is to be located such that incoming air movement is obtained at the waist level of the worker at the lowest level in the confined space. In the event of a failure of the ventilation system, the space must be vacated immediately.

The ventilation system will adequately ventilate every occupied area within the space.

Be aware of:

• Obstructions within the space that could result in pockets of dead air or affect airflow.

• Short-circuiting of the airflow that can occur when air intakes are too close to air outlets on the ventilation system.

The ventilation system will push air into the space rather than pull it out, except for the use of local exhaust systems. The ventilation system will be able to maintain any contaminants below their exposure limits.

Contaminants produced by the work will be controlled at the source by a local exhaust ventilation system if practicable. This includes internal combustion engines as well as activities such as welding. The exhaust will be positioned well away from the intake for the ventilation air. Typical airflow for welding is 100 to 200 cubic feet per minute with the hood less than six inches away from the arc. Air arc gouging will require up to 2000 cubic feet per minute.

When spray painting, the ventilation rate must be high enough to ensure that the permissible concentration of the chemicals listed in the Safety Data Sheet, is not exceeded. Also, the ventilation system must be high enough to ensure that flammability limits are not exceeded if there is a flammable component to the paint or chemical.

Other processes, which may require local exhaust may include but are not limited to:

• Painting

• Applying epoxy

• Grinding, or burning galvanized metal

Natural Ventilation

If natural ventilation is used, the rate of air flow through the space must be monitored and must be sufficient to maintain the concentration of any contaminants below their exposure levels. Natural ventilation will not be used if there is a high hazard atmosphere, or if the natural ventilation could draw other contaminants into the space. Natural ventilation typically would be used in low hazard atmospheres such as air plenum intakes, attic crawl spaces, etc.

Equipment

Air Monitoring (Gas Detectors)

The portable gas detector is one of the most important tools used by personnel required to enter confined spaces or areas where contaminated atmospheres may exist or may develop.

All gas detectors must be certified, calibrated according to the manufacturer’s instructions, and bump-tested prior to use.

Everyone involved in confined space entry, i.e., the entry worker, the standby worker and the supervisor must know how to operate the gas detector used in any confined space entry they are involved in. It is imperative that the worker using the portable gas detector be trained, familiar with, and practiced in the use, functions and operating procedures of the gas detector he/she may use.

Testing

Before a gas detector is used, it must be bump tested. This must be done by a worker who has been trained in the procedure.

Most gas detectors are equipped to self-diagnose automatically when the power is turned on. The user should observe this diagnosis with particular attention paid to the battery condition. The battery voltage must be within certain limits for the instrument to function properly.

Ventilation Equipment

Ventilation equipment includes blowers, hoses and saddle vents where applicable.

Blowers are required to be used unless the natural ventilation in the space has been measured and found to be adequate as described above. Each blower must be identified as to its capacity (cubic feet per minutes - cfm) and must be able to provide at least 50 cfm for each worker in the space.

Rescue and Retrieval Equipment

When entering any type or classification of confined space workers must wear a full body harness. In spaces with moderate or high hazard atmospheres, or those where there is a risk of entrapment, engulfment or any other recognized serious health or safety hazard, the harness must be connected to a lifeline that is connected to the winch. The standby worker must be trained in how to use the rescue equipment to remove a person from the space in an emergency.

Lifelines must have an ultimate strength of 6,000 pounds and be kept free of knots or splices except at the ends. Only stainless-steel lines will be used where hot work is being done.

Personal Protective Equipment

The conditions in the confined space will dictate the requirements for personal protective equipment. PPE may include safety headgear, safety goggles, face shield, gloves, safety footwear, disposable suits, respirators and earplugs or muffs.

Intrinsically safe flashlights and tools must also be required if a flammable atmosphere is, or could be, present.

Electrical Tools and Equipment

Electrical tools and equipment used in the confined space will be grounded or double insulated. Generators located outside the confined space must be equipped with ground fault circuit interrupters (GFCI).

Other Tools and Equipment

Torches and hoses used for welding, brazing or cutting will be removed from the confined space when not in use. No welding, brazing or cutting will be allowed if flammable or explosive gases, vapors or liquids are present.

Communications Equipment

It is essential to have an appropriate means of communication between the person working inside a confined space (the entry worker) and the person stationed outside (the standby worker).

It should be noted that radio frequency and wireless devices do not work effectively in confined spaces such as tanks or sewers where there is metal or concrete shielding between the interior of the space and the outside. When visual monitoring of the worker is not possible because of the design of the confined space or location of the entry hatch, a voice or alarm-activated explosion proof type of communication system may be necessary, particularly for rescue operations.

Another consideration is that, in some instances, electrical communication may introduce an ignition source in a flammable atmosphere.

Basic equipment includes a mobile or portable radio and/or a cell phone in order to provide:

• a system of communication between the standby person and entry person.

• a system of communication between the standby person and an outside source such as Yard Dispatch and/or 911.

All communications equipment must be tested prior to entry to ensure proper operation and that a contact person is available.

Rescue

Rescue plans will be in place before workers enter a confined space. The rescue plan will consider:

• The specific hazards of the confined space

• Any obstacles to rescue

• The type of rescue equipment that must be in place before the confined space entry

• Communication, and

• First aid

For spaces with a high hazard atmosphere rescue personnel will be stationed at or near the entrance to the confined space whenever a worker is in the space.

Rescue personnel will be confined space entry and rescue trained, or outside rescue services will be contracted. For all other situations the standby person will have the means to summon emergency rescue personnel and/or conduct an outside rescue using the lifeline and lifting device that is in place. A sample Confined Space Rescue Guideline is provided in Appendix D.

The following paragraphs are provided as examples of possible rescue situations.

The organization utilizing this document must determine which of the following paragraphs best suits their circumstances and remove the rest of the paragraphs as necessary.

CMCVAMC will ensure that rescue services are available when a worker enters a confined space. Prior to entering the space, rescue personnel will be notified that work is taking place in a confined space. Rescue personnel will monitor the incoming line to ensure that they receive the signal if rescue is required.

CMCVAMC has entered into an agreement with the Philadelphia Fire Rescue Department to provide rescue services from confined spaces on a 24-hour a day basis. In the event that there is a requirement for rescue, the standby person will call 911 to activate the rescue service.

A sample of a Confined Space Entry and Rescue Checklist is provided in Appendix E.

TRAINING REQUIREMENTS

Goal

To train workers in the hazards of confined spaces and inform them of procedures to eliminate or minimize the risks associated with confined space entries.

Objectives

Workers involved in confined space entry will:

• be familiar with the CMCVAMC Regulations regarding confined spaces

• understand the criteria for a confined space

• have received confined space entry and rescue training

• be able to identify confined spaces

• understand how to perform hazard identification and risk assessments

• know how to conduct pre-entry testing based on written procedures

• understand the typical air contaminants found in municipal confined spaces

• understand the hazards associated with the space

• know how to complete the confined space entry form / permit

• understand ventilation requirements and be able to properly set up the ventilation system

• understand and be able to follow the safety precautions required by the written procedures

Summary of Training

• Confined space policy

• CMCVAMC Regulations and definitions

• Hazard identification and risk assessment

• Pre-entry atmospheric testing

• Communication required for confined space entry

• Use of the confined space entry forms / permits

• Equipment required for confined space

• Rescue procedures for confined space

PROGRAM MAINTENANCE

CMCVAMC will ensure that the inventory of confined spaces is kept current, and that hazard and risk assessment information provided to contractors is correct and current.

All hazard identifications and risk assessments are maintained as part of the inventory.

Maintenance of the inventory is the responsibility of Safety Department.

DOCUMENTATION

Documentation for the confined space entry program includes:

• Completed inventory of confined spaces

• Completed hazard identifications and risk assessments for each space or group of similar confined spaces

• Records of pre-entry testing

• Completed entry permits – must be kept for at least one year

• Rescue procedures

5. RESCISSION: None

6. REVIEW: January 31, 2029

7. RECERTIFICATION:

This MCP is scheduled for recertification on or before the last working day of [January 2029 – 5 years from effective date]. This MCP will continue to serve as local policy until it is recertified or rescinded. In the event of contradiction with national policy, the national policy supersedes and controls.

8. SIGNATORY AUTHORITY:

KAREN FLAHERTY, MSN, RN

Medical Center Director

NOTE: The signature remains valid until rescinded by an appropriate administrative action.

DISTRIBUTION: MCPs are available at:

https://dvagov.sharepoint.com/sites/VHAPHIcmcvamc/mcpub

APPENDICES

https://dvagov.sharepoint.com/sites/VHAPHIcmcvamc/mcpub

Appendix A: Confined Space Identification Chart

Is the space enclosed or partially enclosed?

YES NO

Is the space large enough to enter?

YES

Not a confined space

Is the space designed for occupancy:

▪ 20 air exchanges per hour

▪ Permanent lighting

▪ Air intake above grade

▪ Ventilation throughout the space?

YES

Not a confined space

NO

Not a confined space

Does the space have access restrictions that would complicate first aid or evacuation of an injured worker? (ladder access, crawl in, manhole access, opening blocked or partially blocked by equipment or materials, worker lowered into the space on a line)

NO

YES NO

This is a confined space Not a confined space

Appendix B: Risk Assessment and Classification Form

CONFINED SPACE ENTRY PROGRAM

Risk Assessment & Classification Form

Classification

Type A - Low o

Type B - Moderate o

Type C - High o

Date of assessment:

Name of person(s) doing assessment:

Space I.D. #

Location of space (address and/or description of physical location):

Description of Space

Description of space:

Wet Well ............ o Dry Well ............... o Valve Chamber ... o Outlet/Inlet ............ o Tank ..................... o

PRV Chamber .... o Manhole ............... o Box culverts ........ o Pump station ......... o Pipe Line .............. o

Pool filtration ..... o Chemical storage .. o

Other .................. o Specify: ____________________________________________________________________

Type of Access: Door o .......................... Regular Hatch .......................... o Large Hatch .......... o Manhole cover o

Ladder ................ o Stairs ........................ o

Possible Content Hazards:

Possible atmospheric hazards:

Who usually enters the confined space?

Sewers/Sanitation ............. o Waterworks ............... o Contractor ................ o

Other - Specify:

Frequency of entry:

Daily ... o Weekly .... o Monthly ... o Yearly .... o

Other ... o Specify: __________________________________________________________________________

Typical reasons for entering the space:

Inspection ....... o Clearing Blockage .... o Minor Repair ........... o Cleaning ... o Meter Reading ...... o

Removal ......... o Electrical repair ........ o Mechanical repair ... o Painting .... o Debris removal ..... o

Other ............... o Specify: ______________________________________________________________________

External or internal connections to the space:

Operations/businesses nearby that may affect the space:

How will nearby operations/businesses affect the space?

Hazards

Potential Hazards Specific Hazards for

This Space

Hazard Control as Part of Entry Procedures

PPE

Required

1. Isolation & Lockout

▪ Piping coming into the space may have to be isolated, block and bleed…

▪ Equipment, e.g., electrical must be isolated & locked out

2. Ventilation - Limited or no ventilation

3. Toxic materials - Ensure MSDS available on site; Ventilation and/or respiratory eqpt to be used

4. Toxic Gases - Gases in the space may be toxic, irritating, asphyxiating, or flammable.

5. Oxygen Deficiency – e.g., rusting construction components, new concrete, excessive organic growth.

6. Outside Contaminant Sources - Nearby sources may affect workers in the space

7. Limited or restricted entry/egress

▪ small access point,

▪ equipment placement

▪ Material placement

8. Internal configuration hazards - Specific rescue procedures may be required

9. Below grade heavier than air contaminants may settle

10. Fall Hazard – Excessive height or depth

11. Slipping Hazards

▪ wet floor- risk of slip

▪ sloping floor – risk of slip

12. Electrical Hazards – e.g., Near power lines

13. Deteriorating construction components:

▪ Concrete - spalling or cracking

▪ Wood - rotting

14. Entrapment/Engulfment

▪ Rotting materials, e.g. wood.

▪ Upstream fluids - risk of drowning

▪ Internal baffles - may also restrict ventilation

15. Internal pinch points - risk of crushing

16. Dust - may be flammable or irritating, or restrict vision

17. Temperature - may be too hot or too cold

18. Noise – Hearing protection may be required

19. Other

Isolation and Lockout

Describe any internal mechanical and electrical equipment:

Is Isolation/Lockout and/or Blanking/Blinding/Bleeding required and reasonably possible to do? Explain:

List of lockout points (for more space use Comments section on Page 4):

Size and Configuration of Space

No. of Levels of Space: _______ Depth of space: to 1st level: ___________ Total depth: _____________

Entry/Exit:

Number of entry points:

Number of exit points:

Size & Type of opening:

Location of opening:

Rescue Considerations

Horizontal ... o Entrapment ..... o Piping ....... o Multi-level ...... o Other .... o

Comments:

Photo or Drawing of Confined Space

Preliminary Assessment Flow Chart

Appendix C: Confined Space Entry Permit

CMCVAMC CONFINED SPACE ENTRY PERMIT

(Permit expires at end of shift)

Date of Entry: Time of Entry: Name of Standby Person:

Location/Designation of

Space:

Describe Space:

Describe Work To Be Done:

Confined Space Entry Permit must be completed, signed and posted at the entrance when any of the following occur:

• Lockout is required prior to entry

• Blanking or blinding is required to isolate the space prior to entry

• The space has piping coming into it which cannot be blanked or blinded

• There is risk of entrapment or of being buried/drowned

• Air quality would prevent self-rescue if ventilation or other equipment failed

• Ventilation is not provided or is not measured

• Ventilation cannot keep contaminants below permissible concentrations

Ventilation Method: Mechanical ventilation □ Natural ventilation □

Capacity of air mover or measured natural ventilation ________ c.f.m. or m3

Gas Test Monitor Calibrated _____________________________________

Pre-Entry Air Testing Results: Name of tester ______________________ Signature of tester: _____-

Contaminant Time Time Time Time

Oxygen (%)

Carbon Monoxide

(ppm)

Hydrogen Sulfide

(ppm)

Flammables (%)

High Hazard Precautions:

No entry allowed if:

• Flammables greater than 10% of lower explosive limit (LEL)

No entry without high hazard precautions if:

• Oxygen greater than 23.5 or less than 19.5 %

• Hydrogen Sulfide greater than 5 ppm

• Carbon monoxide greater than 25 ppm

• Flammables greater than 10% of LEL

• Ventilation not supplied or not measured

• Risk of entrapment or being buried/drowned (see back of form for high hazard precautions)

Workers Entering Space:

Note: No worker to enter space until permit completed and signed. (Supervisor Signature)

Legend: Write an X in the boxes under Status each time the named worker has EXITED the Confined Space (X) i.e. for coffee, lunch and each break. Write an / each time the named worker had ENTERED the Confined Space (/).

Name…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .