About this file

This document is an electrical riser diagram for the Veterans Affairs Medical Center in Philadelphia, Pennsylvania. The drawing, numbered ER-B02-SUB-1 and titled "Substation: B02-SUB #1," illustrates the single-line electrical distribution system serving Building B02 (Building Number 36C24423N0708) across multiple floors from the sub-basement through the eleventh floor. The diagram depicts the primary substation infrastructure including the main transformer (T-SUB-1, 750 KVA, 13.2KV to 480Y/277V), distribution sections, tie breaker to Sub #2, and main metering equipment with a 1200-ampere main circuit breaker. The riser diagram details the electrical panels, transformers, and circuit breakers distributed throughout each floor level, including dedicated systems for critical loads such as operating rooms, imaging equipment (MRI, CT scan), and emergency power systems with automatic transfer switches (ATS-1, ATS-2, ATS-14, ATS-15, ATS-16).

The document was prepared by ThinkForm Design Architect LLC (38 East Broad Street, Hopewell, NJ 08525) with electrical engineering by Watson Engineering (1112 State Route 434, Owego, NY 13827) under Project Number 36C24421D0043. The drawing is dated 11 February 2025 and was drawn by GJP with approval from the Project Director. The facility address is 3900 Woodland Avenue, Philadelphia, PA 19104. The diagram includes both standard electrical distribution components and emergency power infrastructure, with detailed amperage ratings, voltage specifications (480/277V, 208/120V), and equipment designations for each floor level serving various hospital functional areas including patient care units, laboratories, pharmacy, and imaging departments.

View the file

Other files

File Type Posted
2024-12-03_HAZARDOUS AND UNIVERSAL WASTE POLICY.pdf PDF
2024-12-03_HAZARDOUS MATERIALS AND WASTE MANAGEMENT PLAN.pdf PDF
ALL-31-SINGLE-LINES-ONE-FILE-012325.pdf PDF
FMS 138-54 Hot Work Policy.doc DOC document
Confined Space Entry Program.pdf PDF
Electrical Safety Program.pdf PDF
7714_D_2017-04-06 ASBESTOS MANAGEMENT PROGRAM.pdf PDF
VHA Dir 7714 Asbestos Management Program.pdf PDF
Fire and Smoke Barrier Pentration Permit.pdf PDF
Safety Coordination Meeting Safety Policies for SOW Project 642-22-104.pdf PDF
B6-SUB-PRIMARY-NORMAL-324-371-DWG-FINAL-070623.pdf PDF
Inspection Final RAC Blank Master.docx DOCX document
SAFE PRACTICES FOR WORKING WITH LIVE ELECTRICAL POWER.pdf PDF
36C24426R0088 0004.pdf PDF
RFI 2 Upgrade Substation 36C24426R0088.docx DOCX document
B02-SUB-3.pdf PDF
FMS SOP 138-44 Fire and Smoke Barrier Penetration Policy.pdf PDF
B02-SUB-2.pdf PDF
B6-SITE-POWER-WITH-MANHOLES-DWG-FINAL-070623.pdf PDF
2024-12-03_Green Procedure Program.pdf PDF
FIRE SYSTEM permit 2021 blank.pdf PDF
MANHOLES 19529-02 VA Hospital of Philedelphia 11.17.22.pdf PDF
VHA ICRA-1.2 Oct 1 2024.pdf PDF
Blank Above Ceiling Permit.pdf PDF
Asbestos Control Regulation.pdf PDF
Building 2_LS_SB_G_B FOR REFERENCE ONLY.pdf PDF
INFECTION PREVENTION AND CONTROL POLICY BEHAVIORAL HEALTH SERVICES.pdf PDF
Fire Plan.pdf PDF
FMS SOP 138-54 Hot Work Policy.pdf PDF
Safety and Health During Construction.pdf PDF
B02-SUB-4.pdf PDF
36C24426R0088 0003.pdf PDF
36C24426R0088 0003.pdf PDF
Attachment 1 RFI 1 Upgrade Substation 642-22-104.docx DOCX document
Attachment 3 General Decision Number PA20260003 10012026.docx DOCX document
Attachment 1 RFI 1 Upgrade Substation 642-22-104.docx DOCX document
Attachment 2 P09 Final SOW Rev1 Building 2 Substation Phase 1 642-22-104 10202026.docx DOCX document
36C24426R0088 0003.pdf PDF
36C24426R0088 0002.docx DOCX document
36C24426R0088 0001.docx DOCX document
S04 Pre-Bid Sign-In Sheet 36C24426R0088 - 642-22-104 - Upgrade Substation.pdf PDF
Substations Upgrade Building 2-Phase 1_Bid Documents_Specification_10-21-24.pdf PDF
Substations Upgrade Building 2-Phase 1 Combined Drawings.pdf PDF
36C24426R0088_1.docx DOCX document
Show all 44

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ELEVENTH FLOOR

TENTH FLOOR

NINTH FLOOR

EIGHT FLOOR

SEVENTH FLOOR

SIXTH FLOOR

EC5H

480/277V

125A

MCB

60A

FOURTH FLOOR

EC3A

208/120V

EC4H

480V/277V

400A

MCB

400A

WITH (2)

SUB-FEED

BKR'S.

SECOND FLOOR

FIRST FLOOR

GROUND FLOOR

SUB-BASEMENT

T-EC3K

480/208

45 KVA

EC3K

120/208V

AVANTO

CB

MRI

T-EC3L

480/208

45 KVA

EC3L

208/120V

150A

MCBEC3L-SW

100A/3P

SS

EC1A

208/120V

225A

MCB

200A

EC1D

208/120V

150A

MCB

100A

ECSB

208/120V

250A

MCB

100A

DEC-2

208/120V

1200A

MCB

800A

APFCU

T-1ELA

480/208

225 KVA

DEC-1

480/277V

600A

MCB

400AN E

NE

ATS 1

400A

CRITICAL

TRANSFER

SWITCH OWNER

METERING

MAIN

50A

15KV FUSE

T-SUB-1

XFMR

13.2KV-

480Y/277V

750KVA

MCB

1200AF

1200AT

DIST.

SECTION

DIST.

SECTION

TIE

BREAKER

TO

SUB #2

1200AF

1200AT

SUBSTATION #1

M

ELEV S-20

50HP - 480V

DEC-7

480/277V

800A

MCB

800A N E

ATS 14

NE

PBHA

480/277V

400A

MCB

225A

PBLA

208/120V

225A

MCB

100A

T-PBLA

480/208

30 KVA

ELB

480/277V

100A

MCB

60A

DEL-1

480/277V

225A

MCB

225AN E

NE

ATS 2

260A

LIFE SAFETY

B2A104

ROOM NUMBER

AMP-F / AMP-T

FEEDER CKT BKR

LEGEND

B2A102

225AF / 225AT

PBHA

400AF / 250AT

75 kVAR PFU

B2A105 B2A104

400AF / 400AT

ATS-1

B2B105E

225AF / 100AT

ELEV.S-20

PHARMACY

B3A134

B2A105

800AF / 800AT

ATS-14

225AF / 225AT

ATS-2

400AF / 400AT

ATS-1(B02)

PNL: ELSDP-2-1

B02 - EPSS 250AF / 250AT

ATS-2(B02)

PNL: ELSDP-2-1

B02 - EPSS

800AF / 800AT

ATS-14(B02)

PNL: B2-EPSS

B02 - EPSS

PANEL (IF OTHER Substation)

BLDG (IF OTHER Substation)

THIRD FLOOR

FIFTH FLOOR

1A176 1A123

5A143E

3A147 3A1033A180 3A151A

PETH

CT

3A109A

EC4X

600A

MCB

T-EC3J

480/208

112.5 KVA

T-EC3J-PRI

225A/3P

2B104

EC3J - LAB

3B139

HYBIRD

UPS

FEEDER

250A

T-EC5H2

480/208

45 KVA

EC5D

208/120V

150A

MCB EC5H2

250A

MCB

5A180 5A179F

T-ECSPD2

480/208

45 KVA

ECSPD2

208/120V

250A

MCB ECSPD1

250A

MCB

SEC #1

B2A116

T-EC5H2

480/208

45 KVA

EC5D

208/120V

150A

MCB EC5H2

250A

MCB

5A180 5A179F

T-EC5H2

480/208

45 KVA

EC5D

208/120V

150A

MCB EC5H2

250A

MCB

5A180 5A179F

T-EC5H2

480/208

45 KVA

EC5D

208/120V

150A

MCB EC5H2

250A

MCB

5A180 5A179F

T-EC5H2

480/208

45 KVA

EC5D

208/120V

150A

MCB EC5H2

250A

MCB

5A180 5A179F

T-EC5H2

480/208

45 KVA

EC5D

208/120V

150A

MCB EC5H2

250A

MCB

5A180 5A179F

T-EC5H2

480/208

45 KVA

EC5D

208/120V

150A

MCB EC5H2

250A

MCB

5A180 5A179F

T-EC5H2

480/208

45 KVA

EC5D

208/120V

150A

MCB EC5H2

250A

MCB

5A180 5A179F

T-EC5H2

480/208

45 KVA

EC5D

208/120V

150A

MCB EC5H2

250A

MCB

5A180 5A179F

T-EC5H2

480/208

45 KVA

EC5D

208/120V

150A

MCB EC5H2

250A

MCB

5A180 5A179F

T-EC5H2

480/208

45 KVA

EC5D

208/120V

150A

MCB EC5H2

250A

MCB

5A180 5A179F

T-EC5H2

480/208

45 KVA

EC5D

208/120V

150A

MCB EC5H2

250A

MCB

5A180 5A179F

T-EC5H2

480/208

45 KVA

EC5D

208/120V

150A

MCB EC5H2

250A

MCB

5A180 5A179F

T-EC5H2

480/208

45 KVA

EC5D

208/120V

150A

MCB EC5H2

250A

MCB

5A180 5A179F

T-EC5H2

480/208

45 KVA

EC5D

208/120V

150A

MCB EC5H2

250A

MCB

5A180 5A179F

T-EC5H2

480/208

45 KVA

EC5D

208/120V

150A

MCB EC5H2

250A

MCB

5A180 5A179F

T-EC5H2

480/208

45 KVA

EC5D

208/120V

150A

MCB EC5H2

250A

MCB

5A180 5A179F

T-EC5H2

480/208

45 KVA

EC5D

208/120V

150A

MCB EC5H2

250A

MCB

5A180 5A179F

T-EC5H2

480/208

45 KVA

EC5D

208/120V

150A

MCB EC5H2

250A

MCB

5A180 5A179F

T-EC5H2

480/208

45 KVA

EC5D

208/120V

150A

MCB EC5H2

250A

MCB

5A180 5A179F

T-EC5H2

480/208

45 KVA

EC5D

208/120V

150A

MCB EC5H2

250A

MCB

5A180 5A179F

T-EC5H2

480/208

45 KVA

EC5D

208/120V

150A

MCB EC5H2

250A

MCB

5A180 5A179F

T-EC5H2

480/208

45 KVA

EC5D

208/120V

150A

MCB EC5H2

250A

MCB

5A180 5A179F

T-EC5H2

480/208

45 KVA

EC5D

208/120V

150A

MCB EC5H2

250A

MCB

5A180 5A179F5A151

T-51 PU

480/208

75 KVA

51 PU

208/120V

150A

MCB

VARIOUS

OPERATING

ROOMS

EC5H3

400A

MCB

OP ROOMS

T-EL1L

480/208

15 KVA

EL1L

208/120V

60A

MCB EL1A

60A

MCB

1A176

4A1024A102

CT SCAN

CT

400A

MCB

3A177

T-1ELA

480/208

75 KVA

1EHA

400A

1A103

1ELA

400A

T-1ELB

480/208

75 KVA

1A176

1ELB

400A

3ELA

208/120V

150A

MCB

3ELC

208/120V

150A

MCB

3A180

3ELB

208/120V

225A

MCB

3EHA

480/277V

60A

MCB

SP

208/120V

225A

MCB

3A1473A180

400AF / 400AT

RISER - 1EHA

EC5A

208/120V

225A

MCB

200A

EC5S

208/120V

300A

MCB

300A

WITH SUB

BKR-125A

(X.I.P.U.)

X.I.P.U.

208/120V

VARIOUS

OPERATING

ROOMS

I.P.U. 15 208/120V

VARIOUS

OPERATING

ROOMS

51PU

208/120V

600A

MCB

600A

S1C1 208/120V

S1C2 208/120V

I.P.U. 1 208/120V

VARIOUS

OPERATING

ROOMS

EC8A

208/120V

250A

MCB

100A

TO EC5C

5A151 5A143E 5A143F 5A135 5A143E 5A127 5A137 5A168

8A127

7EHA

480/277V

600A

MCB

600A

8EHA

480/277V

100A

MCB

100A

7EHB

480/277V

125A

MLO

7EL

208/120V

400A

MCB

300A

8ELA

208/120V

225A

MCB

100A

7ELA

208/120V

225A

MLO

7ELB

208/120V

225A

MCB

175A

8ELB

208/120V

100A

MCB

100A

T-7EL

480/208

75 KVA

T-7ELB

480/208

45 KVA

7EHC

208/120VV

7A156 7A124 7A141C

8A1278A1508A150

800AF / 600AT

RISER - 7EHA

5ELA

208/120V

100A

MCB

100A

5A143C

5ELB

208/120V

100A

MCB

100A

5A151

5EHA

480/277V

225A

MCB

200A

5A143

DG

480V

250A MCB

T-LB

480/208

54 KVA

225AF / 225AT

GARAGE - DG HC

480V

150A MCB

HB

480V

100A MCB

LB

208/120V

MCB

LL

480V

100A MCB

B - LEVELC - LEVEL

GARAGE

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

ARCHITECT/ENGINEER OF RECORDCONSULTANT

THINKFORM DESIGN ARCHITECT LLC

38 EAST BROAD STREET

HOPEWELL, NJ 08525

T:855.821.0274 F:609.644.4397 Russell DiNardo, AIA NY 031521-1

A/E: GABRIEL PAOLETTI, P.E.

WATSON ENGINEERING

1112 STATE ROUTE 434

OWEGO, NY 13827

PHONE: (607) 223-4334

CELL: (609) 970-3875

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

11 FEB 2025 C. ROGERS GJP

B02-REV-0

3900 WOODLAND AVE.

PHILADELPHIA, PA 19104

36C24421D0043 36C24423N0708

SINGLE-LINE / RISER

DIAGRAMS

Drawing Title VA-PHILADELPHIA

ELECTRICAL

RISER DIAGRAMS

Approved: Project Director

RISER DIAGRAM

SUBSTATION: B02-SUB #1

642-23-113

ER-B02-SUB-1

DIFFERENT BLDG

EMERGENCY PWR

PANEL ALSO FED

BY ATS (EMERG)

3A152

EC3K-SW

100A/3P

SS

ECSPD1

250A

MCB

SEC #2

B02-SUB #1

EC3K - LAB

EECRA

ATS-15

ROOM

480V 400A

B3A138C

400AF / 400AT

ATS-15 EQ RM

N E

NE

ATS 15

400A

CRITICAL

400AF / 400AT

ATS-15 (B02)

B16 - EPSS-R

B02-EEDP1-B2

PNL: EEDP1-B2

UPS-A

480V

120 KVA

PDU-A

BYPASS

EECRB

ATS-16

ROOM

480V 400A

EC8A-2

208/120V

250A

MCB

200A

SIEMENS

IR-UPS

PHILLIPS

IR-UPS

ESPREE

MRI

3A1843A152C

Sheets and Views
Model

File details come from the government source that posted it. Updated .