This is a Medical Center Policy (MCP) document that serves as a comprehensive Fire Plan for the Corporal Michael J. Crescenz Department of Veterans Affairs Medical Center in Philadelphia, Pennsylvania. The policy, effective April 29, 2021, with recertification required by April 30, 2026, outlines fire protection procedures, emergency response protocols, and fire prevention measures for all facility personnel.

The Fire Protection Plan comprises ten key elements: fire alarm systems (electronic signaling throughout occupied buildings with manual pull stations, smoke/heat detectors, water flow switches, and annunciator panels); built-in building protection (sprinkler systems, fire-rated doors, and stairways); fire evacuation procedures (immediate, horizontal, vertical, and outside evacuation); procedures in case of fire using the RACE protocol (Rescue, Alarm, Confine, Evacuate); assignment of specific duties to Facilities Management, VA Police, and telephone operators; fire drills conducted per Life Safety Code requirements; fire extinguisher classifications (Class A, B, and C); fire prevention measures including storage regulations, housekeeping standards, and flammable liquid controls; interim life safety measures during construction; and fire incident reporting procedures. The policy mandates annual fire training for all employees, establishment of product line-specific fire plans reviewed by the Safety and Fire Protection Committee, and reportable fire incident documentation within 30 days. VISN office notification is required within 24 hours for property damage exceeding $10,000 or any casualties. All personnel must comply with fire safety regulations, with supervisors responsible for ensuring safe work environments and hazard correction. Special provisions address operating rooms (NFPA 99 compliance), MRI areas (nonferrous fire extinguishers), and CLC operations with designated emergency personnel and evacuation procedures for ambulatory and non-ambulatory patients, visitors, and staff with special needs.

View the file

Other files

File Type Posted
2024-12-03_HAZARDOUS AND UNIVERSAL WASTE POLICY.pdf PDF
2024-12-03_HAZARDOUS MATERIALS AND WASTE MANAGEMENT PLAN.pdf PDF
ALL-31-SINGLE-LINES-ONE-FILE-012325.pdf PDF
FMS 138-54 Hot Work Policy.doc DOC document
Confined Space Entry Program.pdf PDF
Electrical Safety Program.pdf PDF
7714_D_2017-04-06 ASBESTOS MANAGEMENT PROGRAM.pdf PDF
VHA Dir 7714 Asbestos Management Program.pdf PDF
Fire and Smoke Barrier Pentration Permit.pdf PDF
Safety Coordination Meeting Safety Policies for SOW Project 642-22-104.pdf PDF
B6-SUB-PRIMARY-NORMAL-324-371-DWG-FINAL-070623.pdf PDF
Inspection Final RAC Blank Master.docx DOCX document
SAFE PRACTICES FOR WORKING WITH LIVE ELECTRICAL POWER.pdf PDF
36C24426R0088 0004.pdf PDF
RFI 2 Upgrade Substation 36C24426R0088.docx DOCX document
B02-SUB-3.pdf PDF
FMS SOP 138-44 Fire and Smoke Barrier Penetration Policy.pdf PDF
B02-SUB-2.pdf PDF
B6-SITE-POWER-WITH-MANHOLES-DWG-FINAL-070623.pdf PDF
2024-12-03_Green Procedure Program.pdf PDF
FIRE SYSTEM permit 2021 blank.pdf PDF
MANHOLES 19529-02 VA Hospital of Philedelphia 11.17.22.pdf PDF
VHA ICRA-1.2 Oct 1 2024.pdf PDF
B02-SUB-1.pdf PDF
Blank Above Ceiling Permit.pdf PDF
Asbestos Control Regulation.pdf PDF
Building 2_LS_SB_G_B FOR REFERENCE ONLY.pdf PDF
INFECTION PREVENTION AND CONTROL POLICY BEHAVIORAL HEALTH SERVICES.pdf PDF
FMS SOP 138-54 Hot Work Policy.pdf PDF
Safety and Health During Construction.pdf PDF
B02-SUB-4.pdf PDF
36C24426R0088 0003.pdf PDF
36C24426R0088 0003.pdf PDF
Attachment 1 RFI 1 Upgrade Substation 642-22-104.docx DOCX document
Attachment 3 General Decision Number PA20260003 10012026.docx DOCX document
Attachment 1 RFI 1 Upgrade Substation 642-22-104.docx DOCX document
Attachment 2 P09 Final SOW Rev1 Building 2 Substation Phase 1 642-22-104 10202026.docx DOCX document
36C24426R0088 0003.pdf PDF
36C24426R0088 0002.docx DOCX document
36C24426R0088 0001.docx DOCX document
S04 Pre-Bid Sign-In Sheet 36C24426R0088 - 642-22-104 - Upgrade Substation.pdf PDF
Substations Upgrade Building 2-Phase 1_Bid Documents_Specification_10-21-24.pdf PDF
Substations Upgrade Building 2-Phase 1 Combined Drawings.pdf PDF
36C24426R0088_1.docx DOCX document
Show all 44

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FIRE PLAN

MCP: 138-05

Corporal Michael J. Crescenz Rescinded Document:

VA Medical Center MCM 138-05 dated, April 2018 Philadelphia, Pennsylvania 19104

Signatory Authority: Effective Date:

Karen Flaherty-Oxler, MSN. R.N. April 29, 2021 Medical Center Director

Responsible Owner: Recertification Date:

Chief of Facilities Management April 30, 2026

1. POLICY: To outline the Fire Protection Plan and procedures to be utilized in case of fire at the Corporal Michael J. Crescenz Department of Veterans Affairs Medical Center (CMCVAMC).

2. JUSTIFICATION: It is the policy of the CMCVAMC to provide for the following:

A. The protection of patients, employees, visitors, and all other personnel on VA property.

B. The removal of valuable records.

C. The protection of property, whether government owned or not.

D. The provision of fire protection training.

3. RESPONSIBILITIES:

A. The Chief Engineer of Facilities Management is designated the Safety Officer and will develop fire programs and specific corrective actions. The Safety Manager is the Assistant Safety Officer and has been delegated the authority to act at such time when a hazardous condition exists, which warrants a decision to alleviate the hazard.

(1) The Safety Office staff will conduct supervisory training, conduct inspections, investigate fires, inform employees of fire and safety regulations, and report fire hazards when encountered.

(2) Supervisors are responsible for providing and enforcing safe work environments in areas under their control, and for correcting hazards as they are detected, and if beyond their scope for corrections, for reporting them to their supervisors. Supervisors are responsible for ensuring that all

April 29, 2021 MCP: 138-05 employees receive the required fire training annually (Reference MCP:

138-09, Fire Response Training).

(3) All employees including Licensed Independent practitioners shall comply with all fire safety regulations, follow safe work practices, report hazards, and keep their work area free of hazards. All employees will participate in the fire safety program as outlined in MCP: 38-09 “Fire Response Training” and MCP: 138-42 “Life Safety/Fire Management.”

B. PLAN: The Fire Protection Plan consists of the following elements:

(1) Fire Alarm System

(2) Built-in Building Protection

(3) Fire Evacuation

(4) Procedures in Case of Fire

(5) Assignment of Specific Duties

(6) Fire Drills/Training

(7) Fire Extinguishers and Classes of Fire

(8) Fire Prevention

(9) Temporary Fire Plans during Construction

(10) Fire Incident Reporting

4. PROCEDURES:

A. FIRE ALARM SYSTEM:

(1) A fire alarm system is an electronic signaling system installed throughout all occupied buildings. The purpose of the fire alarm system is to notify occupants in the immediate fire zone to evacuate and to summon emergency response.

(2) A fire alarm system usually consists of six basic components that are:

a. Fire alarm pulls stations.

b. Indicators such as chimes, bells, and lights.

c. Smoke detectors, heat detectors, and duct detectors.

d. Water flow switches (sprinkler system).

e. Annunciator panel.

f. Fire alarm control panel (F.A.C.P.).

(3) The Medical Center Audio Paging System is also utilized to notify occupants of Building #1 (Main Building), Building #2 (Clinical Addition), Building #21 (Research Building, and Building #30 (CLC/Community Living Center), of a fire emergency, via the code words "CODE RED.”

(4) Fire alarm pull stations are normally located within the building corridors next to each exit. This allows for both quick identification and easy access. Chimes or bells and lights are normally located above the pull station. By activating the manual fire alarm pull station, a signal will immediately be sent to the Fire Alarm Control Panel (F.A.C.P).

(5) Smoke detectors, heat detectors, duct detectors, and water flow switches are automatic devices used to signal that a fire is in progress.

(6) An annunciator panel indicates what fire zone the alarm is in and what type of device sent in the alarm.

(7) Upon receiving a fire alarm signal, the F.A.C.P. will immediately sound the alarm over the bells, flash the fire lights, close corridor smoke barrier doors, and summon the Philadelphia Fire Department via a monitoring company.

(8) All buildings are operating on a computer voice announcement system. Building #1 (Main Building), Building #2 (Clinical Addition), Building #21 (Medical Research), and Building #30 (CLC) are divided into numerous fire zones, and each fire zone has its own computer voice announcement system.

(9) Individuals located in the fire event zone will hear a templar alarm upon activation of an initiating device. Staff member located in fire zones where the event is not occurring will hear a computer voice announcement give the location of the “Code Red”, by building number, floor and wing.

This announcement will repeat 3 times.

a. CODE RED, (Location of fire, e.g. Building 1, 5 West)

NOTE: This is repeated three times. The all clear is repeat three times.

b. CODE RED ALL CLEAR (Location of fire, e.g. Building 1, 5 West)

B. ADDITIONAL BUILT-IN BUILDING PROTECTION:

(1) Fire Protection Systems: The most efficient and widely used fire protection system is the sprinkler system. The sprinkler system is designed to react to heat. When the temperature of a given area rises due to a fire, a fusible support on a sprinkler head will melt and allow water to flow onto a fire. Although sprinkler systems are designed to control fire spread, many times they will completely extinguish the fire before the arrival of responding emergency personnel.

(2) Stairways and Doors: The most effective and quickest method to confine fire and smoke and to evacuate is to make proper use of stairways and doors.

a. Doors leading into patient rooms will resist the passage of smoke for approximately twenty minutes. By closing the door leading into the room of fire origin, both fire and smoke travel will be effectively stopped.

b. Doors in corridors are usually of the same rating as patient room doors. Smoke barrier doors are rated for twenty minutes and will close automatically when the fire alarm system is activated. It is always important to be sure all smoke barrier doors are closed in the emergency fire zone area. If evacuation is beyond the smoke doors, ensure that they are closed when evacuation is complete.

c. Interior stairways are constructed to withstand fire penetration for approximately 1-1/2 to 3 hours. Doors leading into stairways are fire exit doors and must remain closed except when in use.

d. All fire and smoke barrier doors will remain closed unless they are held open by approved means such as an automatic door open/door release device which is tied into the fire alarm system.

e. Fire hydrants will be used only for firefighting. Other purposes (testing, etc.) must be authorized by the Safety Office.

Vehicles will not be parked within twenty feet of any hydrant.

C. FIRE EVACUATION: There are four levels of evacuation to follow during fire emergencies. The type of evacuation will depend upon the severity of the fire and/or the amount of smoke present. Individual Fire Plans for each Product Line/Service Line shall provide guidelines for the evacuation of handicapped employees, visitors, and patients. Information within the plan shall deal with specifics, i.e., blind, hearing impaired, ambulatory, and non-ambulatory staff, patients, and visitors.

(1) IMMEDIATE EVACUATION: This refers to the early stage of a fire in a room where the fire is relatively small. An example would be a trash can fire in a patient room. Evacuate the room of fire origin, and always

CLOSE THE DOOR!

(2) HORIZONTAL EVACUATION: Refers to the lateral movement of persons to another zone or area of refuge of the building, or relocation from one building to another through fire doors, such as from Building #1 to Building #2, Research to Building #1, etc. Included in this relocation is the transport of necessary medical needs (e.g. equipment records, etc.).

Fire zones are normally separated by smoke barrier doors and/or fire doors in the corridors. These doors are designed to close automatically when the fire alarm system is activated.

(3) VERTICAL EVACUATION: Refers to evacuation by use of stairways. Vertical evacuation is used when fire/smoke severity is increased or if horizontal evacuation is not feasible. Elevators are not to be used for fire emergency evacuations. Exceptions would be during transport of non-ambulatory patients in life threatening situations, and only under the direction of the Philadelphia Fire Department.

(4) OUTSIDE THE BUILDING: For outbuildings, (Building 3, 5, 6, 8, 15, 16, 28 and 31) exit directly to the outside of the building and meet at the designated meeting spot. This is the first and only form of evacuation.

For Building #1, 2, 21, and 30 (CLC), evacuation to the outside of the building would probably indicate an internal disaster. A total facility evacuation will only be ordered by the Medical Center Director or the Philadelphia Fire Department. If a total facility evacuation is ordered, the facility Disaster Plan should be activated.

D. PROCEDURES IN CASE OF FIRE: The following key word will provide a step-by-step procedure which is appropriate for most situations: R A C E

(1) R - RESCUE person/persons in immediate danger to a safe area and close the door to the room of fire origin. (See immediate evacuation).

(2) A - Sound the ALARM and call 202633; Go to the nearest manual alarm box (pull station), and after pulling, go to the nearest phone and call 202633. Give the exact location of the fire, type of fire if known, and your name. Stay on the line until the telephone operator hangs up. MAKE

SURE YOU IDENTIFY THE AREA; CLC PERSONNEL MUST IDENTIFY

THEMSELVES AS BEING AT THE COMMUNITY LIVING CENTER. A

telephone should also be used in those areas where alarm boxes are not available or to report an outdoor fire. Reporting a fire summons help! The Philadelphia Fire Department will be contacted by our monitoring company and will respond to all alarms at this Medical Center.

(3) C - CONFINE or contain the fire by closing doors and windows to eliminate drafts and the spread of smoke.

(4) E – EVACUATE. If fire is small, use fire extinguishing equipment until help arrives. Fire extinguishers are located in red fire closets on each floor of the main Medical Center, in white cabinets on each unit of the CLC, throughout the Clinical Addition and outbuildings. Fire extinguishers are also located in high hazard areas such as laboratories. All employees should know the location of fire equipment in their area and how to use it.

Fire hose is provided for Fire Department use only. If extinguishment is not possible, close the door to room of fire origin and back away. Report to the Charge Nurse for evacuation directions.

(5) NOTE: In addition to R A C E, the following actions may also be necessary:

(6) FURTHER EVACUATION: Ready yourself and staff to evacuate either horizontally or vertically out of the affected fire zone. Patient relocation is a team effort under the direction of a charge person.

a. The person in charge of the area is designated in charge until relieved. This person will ensure that the proceeding steps have been followed and will coordinate all the activities of personnel in the fire area.

b. In patient occupied areas, the charge nurse will establish priorities for removal of patients and designate personnel responsible for assisting in the evacuation or other duties. All personnel regardless of service affiliation, in ward areas at the time of an alarm will report to the charge nurse for assignments.

Licensed Independent Practitioners (LIPs) are required to report to the Nurse’s Stations for instructions.

c. The nurse manager/charge nurse and Facilities personnel are responsible for oxygen shutoff in patient care areas. If Facilities personnel are shutting off the oxygen this should be done in direct coordination with nursing staff to ensure proper patient care is maintained.

d. All life sustaining equipment such as oxygen or other respiratory equipment should be moved with the patient, if at all feasible.

NOTE: No attempt should be made to administer oxygen if FLAME is present.

e. Be calm and reassure the patients. DO NOT SHOUT "FIRE.” All lights are to be left on. Fear and panic can do as much damage as any fire.

(7) Efforts may begin immediately to extinguish the fire, but it is most important that planning for further evacuation not be compromised in case the fire cannot be extinguished.

(8) ACTION TO BE TAKEN IN ALL OTHER AREAS OF THE

MEDICAL CENTER DURING AN ALARM:

a. All personnel will determine the location of the alarm by listening to the fire alarm system. Also, in buildings 1, 2 and 21 personnel are to listen to the page system to determine the location of the alarm.

b. Employees designated by the supervisor above, below and adjacent to the fire alarm will respond to the area.

c. All personnel not assigned specified duties will secure their area, remain at their worksite, and await further instructions from their supervisor.

d. At the "All Clear" employees will return to their normal duties.

(9) FIRES ON THE HOSPITAL GROUNDS: Upon discovery of a fire on the grounds, the telephone operator should be notified by dialing ext.

202633 from the nearest in-house phone. The exact nature and location of the fire emergency should be given to the telephone operator (e.g., car fire on C level of the parking garage.) Upon receipt of an alarm, the telephone operator should notify the Philadelphia Fire Department, Safety Office, and the VA Police.

E. ASSIGNMENT OF SPECIFIC DUTIES:

(1) Initial fire alarm response and reporting requirements for specific services are as follows:

a. Facilities Management responds to area of alarm. (See Appendix B for specific duties).

b. VA Police respond to area of alarm and provide necessary manpower to maintain security and guide PFD to proper location.

(See Appendix B for specific duties).

c. Telephone operator reports fire location (overhead page) and notifies key personnel. (See Appendix B for specific duties).

d. For service area in alarm and other areas as applicable, see Appendix C for individual service plans.

(2) All Product Lines/Services must develop and implement a local fire plan unique for their area of responsibility. The fire plan must be reviewed by the Safety and Fire Protection Committee prior to implementation.

Generally, the fire plan should cover the following:

a. Area of concern and fire alarm systems.

b. Responsibilities of all service personnel. (Including designation of individual on each shift to respond to fire alarms adjacent to floors directly above and below their area).

c. Evacuation procedures and routes.

d. Types of fires anticipated in area.

e. Types of firefighting equipment in area.

f. Fire reporting procedures.

g. Response (if applicable) to other service areas.

h. Evacuation of staff/others with special needs.

F. FIRE DRILLS: Fire drills will be held as required by the most current edition of the Life Safety Code, CARF, The Joint Commission, or VA policy.

(1) Fire drills will be conducted in accordance with MCP: 138-09, "FIRE

RESPONSE TRAINING.”

(2) Drills will be made as realistic as possible without endangering patients. All movement or evacuation drills shall be previously arranged with Nursing Service so as not to endanger patients.

(3) The telephone operator will be told the time and place of alarm so that they will not initiate actual fire emergency procedures.

(4) Staff response to fire drills will be evaluated in accordance with

MCP: 138-09.

G. FIRE EXTINGUISHERS AND CLASSES OF FIRE:

(1) Fire is a chemical reaction involving fuel, heat, and oxygen. If any one of these elements is removed the fire will be extinguished.

(2) Classification of fire depends mainly upon the fuel involved.

a. Class “A” fires are ordinary combustible solid materials, such as wood, paper, rags, bedding, etc. This type of fire burns with an ember and leaves an ash. It is best extinguished by reducing the heat. Application of water solutions are the best extinguishing agents. This reduces the heat of the fire below the danger point.

b. Class "B" fires involve flammable liquids, greases, fats, oils, etc. This type of fire involves the surfaces and is best extinguished by a blanketing or smothering action. A fire of this type is a fast spreading fire and could engulf a large area in a very short time.

c. Class "C" fires involve energized electrical equipment.

Blanketing or smothering with a non-conducting extinguishing agent is of prime importance. Water or solutions containing water is never to be used in class C fires. If possible, shut off source of electricity as soon as possible.

(3) Fire extinguishers are labeled as to what class of fires they can be used on.

(4) Most fire extinguishers on Medical Center property are class ABC type fire extinguishers which can be used on all three types of fires. In some areas there may be two types of fire extinguishers:

a. Carbon Dioxide (CO2) can be used on Class B and C fires.

b. Dry Chemical (ABC) can be used on Class A, B and C fires.

(5) Fire Extinguishers in the MRI area are nonferrous type. This means that they will not be affected by the MRI magnet. If it becomes necessary to utilize an extinguisher in the MRI area, the only extinguishers which should be used are the nonferrous extinguishers. These extinguishers are labeled “nonferrous” and are located inside the MRI suite and in the corridor across from the MRI suite.

(6) To help you remember how to use a fire extinguisher, remember the acronym P A S S:

a. P - Pull pin to release handle. (Use a twisting action like turning a key, then pulls the pin).

b. A - Aim the extinguisher at the base of the fire (base of flame).

c. S - Squeeze the handle of the fire extinguisher and continue to squeeze until all extinguishing agent is released.

d. S - Sweep the extinguisher back and forth at the base of the fire as you squeeze the handle.

NOTE: Hands-on fire extinguisher training is offered annually.

H. FIRE PREVENTION:

(1) To safeguard the lives of patients, other beneficiaries, visitors, and employees, and to prevent destruction of property, the following preventive measures will be taken:

a. Safety and fire protection personnel, along with Product Line/Service personnel, will make regularly scheduled inspections of the buildings and grounds for fire hazards and safety hazards.

b. Corridors and exits will be kept free of obstructions.

c. Proper containers will be used for disposal of all combustible waste (e.g., waste containers for cups and candy wrappers, etc.).

d. The use of cloth, paper, or other flammable decorations will not be permitted unless approved by the Safety Office.

e. Paper cartons will not be used as waste receptacles or for the storage of paper, rubbish, or trash.

f. Hoods over kitchen equipment will not be operated without the use of proper filters, which will be cleaned per preventive maintenance guidelines.

g. Cooking equipment in daily or frequent use will be kept clean to avoid accumulation of grease, which is easily ignitable and highly combustible.

h. All equipment will be maintained in accordance with MCP:

138-23 "Equipment Management Program.”

(2) Fire Hazards:

a. A fire hazard is any set of conditions where storage, handling, disposing, location, or use of materials or equipment is likely to cause a fire.

b. Some specific hazards and the appropriate regulations to prevent them from contributing to fire or accidents are outlined in this policy.

(3) Smoking Regulations Policy on smoking within the CMCVAMC is outlined in MCP: 00-08, "Smoke-Free Environment."

(4) Storage:

a. All combustible and flammable items, as well as hazardous noncombustible or nonflammable items, which, because of their hazardous nature, require special storage protection, will be segregated.

b. Hazardous materials that may react with dangerous effects will not be placed near each other.

c. According to the National Fire Protection Association (NFPA), the following clearance regulations will allow a good distribution of water from sprinkler heads in case of fire and will facilitate inspecting supplies:

i. Clear space of 18" will be maintained below and around sprinkler heads, ceiling joists, and electric light fixtures when stacking ordinary supplies.

ii. Aisles will be maintained for access to electrical equipment, firefighting equipment, or sprinklers.

iii. Exit doors will not be blocked or held open by any means unless a special locking arrangement that meets the requirements of the Life Safety Code is utilized.

(5) Flammable and Combustible Liquids: The use and storage of flammable and combustible liquids vary widely throughout the facility. The type of liquid, occupancy, amount, and use is regulated by applicable codes and standards. Contact the Industrial Hygienist for specific regulations at extension 204104.

(6) General Housekeeping:

a. Good housekeeping reduces the possibility of fire starting and facilitates control of fire when it starts.

b. All shops, storerooms, supply closets, basements, and crawl spaces shall be kept free from accumulation of trash, rubbish or unnecessary combustible materials.

c. All rubbish will be removed daily.

d. Clean and used rag containers will be of metal, with fitted metal covers. Used rags will be disposed of daily.

NOTE: Electrical Wiring and Appliances: Electrical equipment, appliances, and wiring systems will be installed, maintained, and used in accordance with the National Electric Code. Equipment, appliances, and wiring will be kept in safe operating condition, and personally owned equipment and appliances will be inspected and approved in accordance with MCP: 138-12 "Electrical Safety".

(7) Special Hazards: Power Hazards- Steam boilers, electric motors, engines, internal combustion machines, fuel oil and refrigeration will be safe-guarded in accordance with the following:

a. The National Fire Code

b. The National Electric Code

c. MP-3, Part III, Safety Occupational Health, and Fire Protection

(8) Occupational Safety and Health Act (OSHA) and OSHA Standards:

a. Operating Rooms: The installation, use, construction, and arrangement of the operating rooms will be in accordance with the recommendations of the National Fire Protection Codes and accepted standards of the Electrical Codes. The provisions of NFPA 99 as well as the Surgical Service Fire and Safety Plan will be followed. Because the OR is an area where there is significant risk of patient injury should a fire occur, the Surgical Service Fire and Safety Plan outlines duties of O.R. staff for responding to a fire emergency safely. Please refer to the Surgical Service Fire and Safety Plan for response to fire emergencies in the O.R.

b. Furnishings: Every precaution must be exercised to limit the use of decorative materials that create hazards and fires. Only flame-resistant materials are to be used wherever decorations are employed in the CMCVAMC. Refer to MCP: 138-42 “LIFE SAFETY/FIRE MANAGEMENT PLAN", and MCP: 138-43 Decorations.

I. INTERIM LIFE SAFETY MEASURES (ILSM) DURING CONSTRUCTION:

Interim Life Safety Measures will be implemented whenever there is a significant Life Safety Deficiency which cannot be immediately corrected. I.e. Fire alarm or sprinkler system failure or other significant life safety deficiency. ILSMs will also be implemented when required during construction.

(1) The Interim Life Safety Measures will be documented, and a record maintained on file. ILSMs will be updated when changes are needed until they are discontinued.

(2) Specific guidelines for Interim Life Safety Measures related to construction can be found in MCP: 138-62 Interim Life Safety Measures

(ILSM)

J. FIRE INCIDENT REPORTING:

(1) A reportable fire incident is defined as an ignition resulting in an uncontrolled flame of any size, or an explosion, in which the flame or explosion results in:

a. Any damage to VA-owned property (whether real or personal property) or any damage to patient, employee or contractor-owned personal property (for example, a small trash can fire or a small cigarette burn of a patient bed linen must be reported).

b. Any casualty, whether an injury or fatality, to any patient, employee, visitor, or contactor, regardless of whether any property damage occurred.

(2) In the absence of a reportable fire, the following are not intended to be reported via these procedures:

a. Activation of a fire alarm and/or detection system

b. Discharge of a portable or fixed fire extinguishing device or system

c. A response by a fire department (including in-house VA fire departments) to a suspected fire incident, rescue, or hazardous condition.

(3) All property damage must be included in any estimated damage total, including real property damage to any structure, building equipment, or building systems, as well as any personal property damage to building contents, including VA property. Fire incidents in leased spaces occupied by VHA employees are included in this policy, even though real property damage (i.e., damage to the lessor’s structure, equipment, or systems) cannot be included in any property damage totals. In addition, for fires on VA property as well as in leased spaces, damage to patient, employee, or contractor-owned personal property cannot be included in any damage totals reported. In determining the estimated property damage costs, replacement costs of the property using like kind and quality are to be included, plus any cost associated with cleanup and repair.

(4) The facility Director will ensure that each reportable fire incident is addressed in accordance with the following procedures:

(5) The VISN office must be notified by email within 24 hours of the incident if property damage is expected to exceed $10,000 in value or the incident results in any casualties to patients, employees, or other individuals. Facilities need to use the “blast up” mail group entitled “VHA Under Secretary” as described in the January 9, 2003, Under Secretary for Health memorandum to report these types of incidents.

a. When a fire incident generates significant media coverage, the VISN office must be notified within 24 hours.

b. Any employee casualties must be reported in accordance with Federal and VA occupational safety and health requirements.

c. Fire incidents involving patients must be handled in accordance with VA patient safety requirements.

d. Local authorities (i.e., local fire department) responding to the incident, must be requested to report the incident in accordance with local protocol via the National Fire Incident Reporting System (NFIRS), if they participate in this national reporting system.

e. An on-line fire incident report form (located at the following VA Intranet address – vaww.ceosh.med.va.gov) for any reportable fire incident must be completed within 30 days of the incident.

NOTE: VA Form 2162, Report of Accident, cannot be used to report fire incidents.

f. A log and all documentation must be maintained of each fire incident at each facility with a specific identifier using sequential calendar and number format (i.e., 2003-001).

g. Each fire incident involving patients must be evaluated as a potential Sentinel Event in accordance with VHA and The Joint Commission protocol.

h. A Root Cause Analysis is to be performed, if needed, in accordance with patient safety requirements.

5. DEFINITIONS: None

6. OTHER PARAGRAPHS: None

7. REFERENCES:

A. VA Directive 7700, latest edition published by VA

B. VA Handbook 7700. latest edition published by VA

C. NFPA Life Safety Code 101, latest edition published by VA

D. The Joint Commission Standards, EC & LS Chapters, VHA Directives 2003-051, Fire Incident Reporting. latest edition published by VA

8. RESCISSION: Medical Center Memorandum No.138-05 dated April 2020

9. REVIEW: April 2026

10. RECERTIFICATION: April 30, 2026

11. SIGNATORY AUTHORITY:

KAREN FLAHERTY-OXLER, MSN, R.N.

Medical Center Director Date Approved: Month Day, Year

NOTE: The signature remains valid until rescinded by an appropriate administrative action.

DISTRIBUTION: MCPs are available at:

https://dvagov.sharepoint.com/sites/VHAPHIcmcvamc/mcpub https://dvagov.sharepoint.com/sites/VHAPHIcmcvamc/mcpub

Attachments (A, B, C)

Attachment (A)

ASSIGNMENT OF SPECIFIC DUTIES

FACILITIES MANAGEMENT SUPPORT

1. In the event the fire alarm is activated at this facility during regular duty hours, designated individuals from each shop will respond to the area of the alarm:

A. Safety

B. Supervisor Electric Shop or Representative

C. Supervisor Plumbing Shop or Representative

D. Supervisor HVAC Shop or Representative

E. M&R Foreman

2. Any Facilities Management personnel located on the floor of the alarm, or a floor above or below, will also respond to the alarm. All other personnel will stand by at their location for further instructions.

3. The Supervisor, Carpenter Shop, will remain in the shop to coordinate if additional personnel are necessary. The decision to utilize additional Facilities Management personnel in the fire alarm area will be made by the Life Safety Manager, Safety Manager or Chief Engineer of Facilities Management Support at the scene of the alarm.

4. Personnel responding to scene of alarm will:

A. Initiate a search of the area to determine cause of alarm if cause is not apparent. Fire Safety Manager, Safety Manager, Chief of Facilities or Duty Engineer has the authority to direct an evaluation of the floor directly involved with the fire alarm.

B. Assist personnel in controlling an incipient fire until PFD arrives.

C. M&R personnel will be equipped and prepared to provide assistance to the Fire Department as well as perform utility control such as electrical shutdown, sprinkler shutoff or open windows/doors with special keys.

D. Take corrective action for any equipment malfunctions at the scene.

E. If utilized, monitor smoke control program and ensure that it is operating properly.

F. If false alarm, the electricians will reset any manual pull box that was activated.

G. The Electricians will reset the F.A.C.P. in the effected Building and then reset the F.A.C.P at the operations station in Building #1.

5. The Chief Engineer of Facilities management, Safety Manager/Fire safety Manager and Duty Engineer are the only personnel authorized to give the “ALL CLEAR” signal to the Telephone Operator.

6. Responsibilities during off tours:

A. In the event a fire alarm is activated at this facility during off tours, (i.e., 1630 hours – 0800) the following procedures will take effect:

(1) Duty Engineer will respond to scene of alarm and initiate a search of the area. In addition to the above mentioned, the Duty Engineer will maintain radio contact with the VA Police and Telephone Operator.

(2) On other than false alarms, the Duty Engineer will secure the activated system by shutting off the suppression system water at the closets zone control valve, replace the activated head with a new head, and recharge the system.

(3) In the event of an actual fire, the fire alarm panel shall not be reset until the Safety Office has been contacted and the Duty Engineer is instructed to do so. In the meantime, Interim Life Safety Measures shall be put into effect as follows:

a. Contact the Telephone Operator and VA Police and notify them that the fire alarm system is not in service for that building/area.

b. Implement a fire watch in the area where the system has been shut down; VA Police can assist in this action.

c. Notify building occupants that the system is not in service and that extension 202633 must be dialed to report a fire incident.

(4) Contact VA Police immediately to secure the scene by having an Officer posted at the scene, and by the use of tape, locks, guards and/or other mechanisms, deemed appropriate by the Officer at the scene.

(5) Contact the Safety Manager/Specialist via the Telephone Operator as soon as the above has been accomplished.

(6) Secure as evidence (in an evidence bag to be provided by the VA Police) any sprinkler head that is replaced as a result of the incident. The evidence bag shall be turned over to the Safety Office upon their arrival. If a smoke detector has activated, the detector should remain in place until the Safety Office has arrived on the scene.

(7) Notify the Operator when the area is secure (CODE RED, LOCATION ALL CLEAR). Additionally alert the following key staff through the Telephone Operator in priority order:

a. Chief Engineer of Facilities Management Support

b. Facilities Manager Coordinator

c. M&R Foreman

(8) For all alarms (false included) during irregular tours, the Duty Engineer shall record date, time, location, device and cause of alarm in duty log book, and on a “Problem Tracking Report,” which should be forwarded to the Safety Office on the next day tour by the Supervisor AC Shop.

Attachment (B)

TELEPHONE OPERATORS

1. PROCEDURES FOR MEDICAL CENTER:

A. Upon receipt of an alarm or report of fire by means of the fire alarm system or phone, the Telephone Operator will follow the procedures as listed.

B. Dial 911 and ask attendant to verify our alarm was received, at the fire department. If alarm has not been received, operator will notify 911 attendant of our alarm location.

C. Immediately notify the VA Police of the location of the fire for initial size up and meeting of the Philadelphia Fire Department to direct them to the fire location.

D. The alarm monitoring company will notify the telephone operator that the fire alarm has been received and that the Philadelphia Fire Department has been notified.

E. If confirmation of the alarm is not received from the alarm monitoring company, telephone (800) 932-3822 and tell the dispatcher, “THIS IS THE

CORPORAL MICHAEL J. CRESCENZ DEPARTMENT VETERANS AFFAIRS

MEDICAL CENTER, 3900 WOODLAND AVENUE” the fire is located at (give location; Main Building, 5th Floor, or Main Building, 9th Floor, etc.).

F. Notify by telephone the following during regular duty hours for an actual fire:

(1) Director’s Suite (extension 6622) (Director, Associate Director

(2) Facilities Management Office (extension 5811)

(3) (Chief Engineer, Facilities Manager Coordinator, Safety Manager/Fire Safety Specialist beeper #402/404)

(4) ACOS PCS/Nurse Exec Patient Care (extension 5854)

(5) Medical Officer of the Day (extension 2364/5902/5199)

G. During off tours contact the following:

(1) VA Police and Duty Engineer via radio

(2) Medical Officer of the Day

(3) Medical Center Director

(4) Associate Director

(5) Chief of Staff

6) ACOS PCS/Nurse Exec

H. Contact only one of the following Facilities Management personnel listed below in priority order:

(1) In the event of an actual fire emergency:

c. M & R Foreman

d. Safety Manager/Specialist

I. Upon receipt of a trouble signal for any building on the Fire alarm Control Panel, the telephone operator will immediately contact the Electric Shop extension 5170 or if on odd tour, the Duty Engineer via radio.

2. PROCEDURES FOR THE COMMUNITY LIVING CENTER (CLC):

A. Upon receipt of an alarm, or report of fire by means of the Fire Alarm System or telephone the Telephone Operator will follow the procedures as listed:

B. Dial 911 and ask attendant to verify our alarm was received, at the fire department. If alarm has not been received, operator will notify 911 attendant of our alarm location.

C. Immediately notify the VA Police of the location of the fire in order that they may meet the Philadelphia Fire Department or direct them to the fire location.

D. The Alarm Monitoring Company will notify the Telephone Operator that the Fire Alarm has been received for the COMMUNITY LIVING CENTER and that the Philadelphia Fire Department has been notified.

E. If confirmation of the alarm is not received from the alarm company, the Telephone Operator will telephone (800) 932-3822 and tell the dispatcher “THIS

IS THE VA COMMUNITY LIVING CENTER, CIVIC CENTER BOULEVARD”.

The fire is located at (give location; Unit 1B, Unit 2C, etc.)

F. Notify by telephone the following during regular duty hours for an actual fire:

(1) Director’s Suite (extension 6622) (Director, Associate Director)

(2) Facilities Management Office (extension 5811)

(3) (Chief Engineer of Facilities Management, Facilities Manager

Coordinator, Safety Manager/Specialist) beeper #402/404

G. During odd tours contact the following:

(1) VA Police and Duty Engineer via radio

(2) Medical Officer of the Day

(3) Medical Center Director

(4) Associate Director

(5) Chief of Staff

(6) Administrator CLC

(7) Contact the following Facilities personnel listed below in priority order:

c. M & R Foreman

d. Safety Manager/Fire Safety Specialist

Attachment (C)

VA POLICE

1. PROCEDURES FOR MEDICAL CENTER AND COMMUNITY LIVING CENTER:

A. The VA Police will provide the necessary manpower to cover the following assignments:

(1) One Officer reports to the scene of the alarm to assist in the search to determine the cause of alarm, and will maintain radio contact with the VA Police Watch Commander on duty who will maintain contact with the Telephone Operator, as appropriate. Facilities Management Support personnel, and other VA Police officers.

(2) One Officer reports to the main lobby to guide the Philadelphia Fire Department to the scene. The VA Police will also provide the Fire Department with access to the fire location through the use of master keys, card access or other appropriate means as necessary. VA Police will provide traffic control in order that the PFD can access the buildings.

B. On other than false alarms:

(1) VA Police will provide security at the fire location.

(2) VA Police will work in conjunction with the Safety Office in the collection of evidence and follow-up investigation of actual fire occurrences.

(3) VA Police will provide assistance to the Duty Engineer (odd tours) for a fire watch if the building fire alarm system is not or cannot be immediately set.

(4) VA Police will provide the Duty Engineer with appropriate evidence containers for the type of evidence being collected and for activated fire alarm devices (sprinkler heads, etc.) and other pertinent evidence that may be required for evaluation by third parties to determine cause of the fire or acceptable performance of the fire systems.