This document is a Standard Operating Procedure (SOP) for hot work operations at the Corporal Michael J. Crescenz Department of Veterans Affairs Medical Center in Philadelphia, PA, effective September 2019. The policy establishes procedures for cutting, welding, thermal welding, brazing, soldering, grinding, thermal spraying, pipe thawing, and other spark or flame-producing operations conducted in non-designated areas of the medical facility. The policy aims to minimize fire risk during construction, alteration, demolition, and repair operations while protecting patients, staff, and visitors. Designated welding areas where hot work may occur without special permits include the Machine Shop, Pipefitting Shop, Air Conditioning Shop, and Biomedical Engineering Section repair area.

The SOP establishes clear responsibilities and mandatory procedures for all hot work operations. The Chief Engineer of Facilities Management Support oversees all hazardous cutting and welding operations; Contracting Officer's Technical Representatives (COTRs) must instruct employees and contractors on proper procedures and ensure compliance; the Safety Office approves hot work permits and maintains operational records; contractors must instruct their employees on requirements; and employees must secure authorization and permits before work begins. Hot work permits must be requested from the Safety Office between 7:30 a.m. and 8:30 a.m., Monday through Friday, and are valid only for specified areas, dates, and times—requiring daily renewal for ongoing jobs. Additionally, a Fire Alarm Systems Permit is required. Permits will not be issued for odd tour work (4:00 p.m. to 8:00 a.m.) without prior approval from the Chief Engineer. Hot work is prohibited in areas with known explosive atmospheres, in areas not authorized by the Safety Office, and in buildings with impaired sprinkler systems unless special approval is granted. All operations must include a qualified fire watch present with an approved fire extinguisher during work and for 30 minutes after completion, and all work must be completed by 3:00 p.m. daily. The fire watch must inspect the area for hot materials upon completion before the work area is secured. Annual training on the policy is required for all Facilities personnel and other supervisors who work with contractors. The policy references NFPA 241 and NFPA 51B standards and supersedes Medical Center Memorandum No. 138-44 dated February 2013.

View the file

Other files

File Type Posted
2024-12-03_HAZARDOUS AND UNIVERSAL WASTE POLICY.pdf PDF
2024-12-03_HAZARDOUS MATERIALS AND WASTE MANAGEMENT PLAN.pdf PDF
ALL-31-SINGLE-LINES-ONE-FILE-012325.pdf PDF
FMS 138-54 Hot Work Policy.doc DOC document
Confined Space Entry Program.pdf PDF
Electrical Safety Program.pdf PDF
7714_D_2017-04-06 ASBESTOS MANAGEMENT PROGRAM.pdf PDF
VHA Dir 7714 Asbestos Management Program.pdf PDF
Fire and Smoke Barrier Pentration Permit.pdf PDF
Safety Coordination Meeting Safety Policies for SOW Project 642-22-104.pdf PDF
B6-SUB-PRIMARY-NORMAL-324-371-DWG-FINAL-070623.pdf PDF
Inspection Final RAC Blank Master.docx DOCX document
SAFE PRACTICES FOR WORKING WITH LIVE ELECTRICAL POWER.pdf PDF
36C24426R0088 0004.pdf PDF
RFI 2 Upgrade Substation 36C24426R0088.docx DOCX document
B02-SUB-3.pdf PDF
FMS SOP 138-44 Fire and Smoke Barrier Penetration Policy.pdf PDF
B02-SUB-2.pdf PDF
B6-SITE-POWER-WITH-MANHOLES-DWG-FINAL-070623.pdf PDF
2024-12-03_Green Procedure Program.pdf PDF
FIRE SYSTEM permit 2021 blank.pdf PDF
MANHOLES 19529-02 VA Hospital of Philedelphia 11.17.22.pdf PDF
VHA ICRA-1.2 Oct 1 2024.pdf PDF
B02-SUB-1.pdf PDF
Blank Above Ceiling Permit.pdf PDF
Asbestos Control Regulation.pdf PDF
Building 2_LS_SB_G_B FOR REFERENCE ONLY.pdf PDF
INFECTION PREVENTION AND CONTROL POLICY BEHAVIORAL HEALTH SERVICES.pdf PDF
Fire Plan.pdf PDF
Safety and Health During Construction.pdf PDF
B02-SUB-4.pdf PDF
36C24426R0088 0003.pdf PDF
36C24426R0088 0003.pdf PDF
Attachment 1 RFI 1 Upgrade Substation 642-22-104.docx DOCX document
Attachment 3 General Decision Number PA20260003 10012026.docx DOCX document
Attachment 1 RFI 1 Upgrade Substation 642-22-104.docx DOCX document
Attachment 2 P09 Final SOW Rev1 Building 2 Substation Phase 1 642-22-104 10202026.docx DOCX document
36C24426R0088 0003.pdf PDF
36C24426R0088 0002.docx DOCX document
36C24426R0088 0001.docx DOCX document
S04 Pre-Bid Sign-In Sheet 36C24426R0088 - 642-22-104 - Upgrade Substation.pdf PDF
Substations Upgrade Building 2-Phase 1_Bid Documents_Specification_10-21-24.pdf PDF
Substations Upgrade Building 2-Phase 1 Combined Drawings.pdf PDF
36C24426R0088_1.docx DOCX document
Show all 44

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Corporal Michael J. Crescenz Facility Management Support

Dept. of Veterans Affair Medical Center Standard Operating Procedure

Philadelphia, PA 19104 No. 138-54 September 2019

HOT WORK POLICY

1. PURPOSE: To establish policy and procedures for cutting, welding and other hot work operations in non-designated areas and to ensure that all supervisors, employees and contractors take proper precautions when any cutting, welding, or other hot work is to be accomplished, such that all work is done in a safe manner with limited risk to patients, staff and visitors.

2. POLICY:

A. To minimize the risk of fires during construction, alteration, demolition operations, or making repairs while performing hot work such as cutting, welding, thermal welding, brazing, soldering, grinding, thermal spraying, thawing pipe, or any other similar work.

B. Procedures and controls are hereby established to control all cutting and welding operations conducted in areas not specifically designated for this type of operation. Designated welding areas include the Machine Shop, the Pipefitting

Shop, the Air Conditioning Shop and the Biomedical Engineering Section repair area.

3. DEFINITION: Hot work operations include cutting, welding, brazing, soldering, thawing pipe, grinding, or other spark or flame producing operation. Any process which involves an open flame used temporarily for repair or temporary heating is considered a hot work operation. The use of a portable engine for temporary power is also considered a hot work operation.

4. RESPONSIBILTIES:

A. Chief Engineer of Facilities Management Support is responsible for the overall hazardous operation involving cutting and welding operations within the

Medical Center complex.

B. Contracting Officer’s Technical Representatives (COTR) are responsible for:

(1) Instructing employees/contractors on proper procedures for cutting, welding and other hot work in the Medical Center and to ensure that the procedures in this policy are followed.

FMS SOP No 138-54 September 2019

(2) Discussing the possibility of some smoke, dust, noise, etc., with nurse managers or persons responsible for the area in which the work is to be accomplished prior to the starting of any hot work operation. This is done to assure staff that every precaution is being taken to minimize any risks to patients and staff.

(3) Providing this policy requirement to vendors/construction contractors before work begins (i.e., pre-construction meetings) in contracts involving cutting and/or welding.

(4) Ensuring that all contractors follow the procedures in this policy.

C. The Safety Office is responsible for approving cutting, welding and other hot work operations in areas not specifically designed or approved for such processes, signing the hot work permit before work begins and keeping a record of hot work operations at this Medical Center.

D. Contractors are responsible for instructing their employees on the requirements of this policy.

E. Employees will ensure that authorization and permits are secured for cutting, welding and other hot work operations, and that conditions are safe.

5. PROCEDURES:

A. Issuing Hot Work Permits:

(1) For all cutting, welding and other hot work requests, a hot work permit shall be requested from the Safety Office between the hours of 7:30 am and 8:30 am Monday through Friday at extension 6109 or 5909 prior to beginning any hot work operation.

(2) The hot work permit will apply only to the area specified on the permit and only for the date and time specified. Hot work permits must be renewed DAILY for ongoing jobs. Additionally, a Fire Alarm Systems

Permit must be obtained from the Safety Office prior to beginning any work under the scope of this policy. Reference Facilities Management

Memorandum No. 1, Fire Alarm Systems Procedures.

(3) All requirements on the permit must be met prior to the start of any burning, welding, etc. Reference Attachment "A", Hot Work Permit".

(4) Upon issuance of a hot work permit, the permit must be kept on the site of the hot work procedure and be made available to the VA auditing official (COTR or Safety Office) upon request. At the end of the hot work procedure, the permit must be returned to the Safety Office.

B. Hot work permits will not be issued for Odd Tour works (4:00 PM - 8:00

AM) unless each request is approved by the Chief Engineer of Facilities

Management prior to the odd tour.

C. Cutting, welding and other hot work shall not be permitted in the following areas:

(1) In the presence of known explosive atmospheres (mixtures of flammable gases, vapors, liquids, or dust with air).

(2) In areas not authorized by the Safety Office.

(3) In buildings equipped with a sprinkler system while the sprinkler system is impaired, unless a special review has been made by the Safety

Office and approval given for such work. Interim Life Safety Measures would be applied if special approval is given.

D. The Safety Office and COTRs, shall have the authority to stop cutting, welding and other hot work operations that are being accomplished without a permit and such operations that do not meet the standards set forth in NFPA 51B.

E. When work cannot be moved practically, the work area will be made fire safe by removing or covering combustibles within a range of any possible sparks.

F. The area around any operation will be cleared of dust or lint to exceed the possible range of sparks by three feet.

G. A fire watch is required during all hot work operations. The individual from the requesting shop or contractor shall supply an individual or individuals, depending on the scope of the work, for safety operations who is knowledgeable and capable of operating the fire extinguisher in his/her possession. If work is being performed in multiple rooms or floors, more than one individual is required for the fire watch. The fire watch will be designated to be present with an approved fire extinguisher for the duration of the operation and for thirty (30) minutes after the operation is completed. All operations must be completed by

3:00 PM daily so that the appropriate fire watch can be conducted.

H. Upon completion of any operation, an inspection will be made for hot materials by the fire watch individual before securing the area. Occupants in the area will be informed that the operation is complete, and the area is safe. Upon completion of odd tour hot work, inspection will be made for hot materials by the fire watch individual before securing the area and notification of completion of work will be made by the Duty Engineer on duty for permit close out.

6. TRAINING: On an annual basis, the Chief Engineer of Facilities Management will ensure that training on the use of this policy is given to all Facilities personnel by

Engineering Shop supervisors. Other Medical Center supervisors who work with contractors shall also ensure that this policy is reviewed at least annually.

7. REFERENCES: NFPA 241, NFPA 51B, and Facilities Management Policy

138-01, Fire Alarm Systems Procedures.

8. RESCISSIONS: Medical Center Memorandum No. 138-44 “Hot Work Policy” dated February 2013. Replaced by this FMS Memorandum No. 138-54.

9. REVIEW DATE: September 2022.

William England

Chief Engineer, FMS

Attachment

Department of Veterans Affairs Medical Center H O T W O R K P E R M I T

For Cutting and Welding with Portable Gas or ARC Equipment

This permit applies ONLY TO THE AREA AND TIME BELOW

Date________________________

Building________________________________

Floor_______________________________

Work to be done_______________________________________________________________

Special Precautions: ( ) Floors swept clean of combustibles.

Check each as ( ) Flammable liquids removed from work area.

completed ( ) All wall and floor openings covered.

( ) Walls/ceilings protected via wetting or covering.

( ) Proper utilities secured, such as oxygen, LP gas, etc.

( ) Contractor/worker familiar with operation of fire alarm system.

( ) Fire Extinguishing equipment on hand in case of fire.

( ) Personnel familiar with operation of fire extinguishing equipment.

I have been informed and understand the provisions of this permit. I understand this permit can be revoked at any time if my employees or I fail to follow the provisions outlined above.

(Requester)

The location where this work is to be done has been examined, necessary precautions taken, and permission is granted for this work.

Permit expires: ___________________________

(Date/Time) (Safety Office)

Time Started_______________________________ Time

Completed___________________

FINAL CHECK-UP

Work area and all adjacent areas to which sparks and heat might have spread (including floors above and below and on opposite sides of walls) were inspected 30 minutes after the work was completed and were found firesafe.

_______________________________________ (Requester/Contractor/Fire Watch

Inspector) Permit to be returned to Safety Office within 24 hours of date of permit.