Confidential and Proprietary Information Contract #2
JEFF - 181202 26 56 00-1
031814 EXTERIOR LIGHTING
SECTION 26 56 00 – EXTERIOR LIGHTING
GENERAL PART 1
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes
1. Exterior luminaires with associated light sources and electric components.
2. Poles and accessories
B. Related Sections
1. Division 26 Sections
2. Division 26 09 43 Networked Lighting Controls
1.3 DEFINITIONS
A. Luminaire: Complete lighting fixture, including housings, drivers, ballasts where required
B. Pole: Luminaire support structure provided by designated lighting product’s manufacturer
C. CCT: Correlated Color Temperature
D. CRI: Color Rendering Index
E. LER: Luminaire Efficacy Rating
F. LED: Light Emitting Diode
G. HID: High-Intensity Discharge
H. Lamp: Source within luminaire producing visible light (may be fluorescent, HID, or LED)
1.4 LIGHTING CONSULTANT
A. There is an independent lighting consultant and designer for this project, Randy Burkett Lighting Design, Inc., St. Louis, Missouri.
B. The consultant or contracting officer will review all final light fixture shop drawings.
JEFF - 181202 26 56 00-2
1.5 ACTION SUBMITTALS
A. Product Data: For each luminaire, lamp, pole, and support component, arranged in order of lighting unit designation as indicated on E-300 Lighting Fixture Schedule and herein, submit prior to order and installation. Include data on features, accessories, finishes, and the following:
1. Physical description of luminaire, including materials, dimensions, effective projected area, and verification of indicated parameters.
2. Details of attaching luminaires and accessories.
3. Details of installation and construction.
4. Luminaire materials.
5. Photometric data based on laboratory tests of each luminaire type, complete with indicated lamp, driver or ballast, and accessories as specified.
a. Testing Agent Certified Data: For indicated luminaires, photometric data shall be certified by a qualified independent testing agency. Photometric data for remaining luminaires shall be certified by manufacturer.
b. Manufacturer Certified Data: Photometric data shall be certified by manufacturer’s laboratory with a current accreditation under the National Voluntary Laboratory Accreditation Program for Energy Efficient Lighting Products.
6. Drivers, including energy-efficiency data.
7. Lamp including rated life, output, CCT, CRI, lumen output, center beam candlepower and beam angle where indicated, and energy-efficiency data.
8. Materials, dimensions, and finishes of poles and their mounting hardware.
9. Means of attaching luminaires to supports, and indication that attachment is suitable for components involved.
10. Base plates and anchor bolts for poles.
B. Shop Drawings: Include plans, elevations, sections, details, and attachments to other work.
1. Detail equipment assemblies and indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection.
2. Anchor-bolt templates keyed to specific poles and structurally certified by manufacturer.
3. Where indicated, provide scaled composite drawing indicating pole, luminaire, pole base, and any other specified components such as receptacles.
4. For any luminaire utilizing a pole, manufacturer shall provide anchor bolt size, embedment length, and embedment calculations for each foundation type (see S111) required on project.
5. Wiring diagrams: for power, signal, and control wiring.
C. Mock-Ups: For products that are designated for mock-up sample review within the lighting fixture schedule and submittal schedule for Contract 2:
1. Contractor shall prepare and conduct an exterior nighttime lighting mock-up temporary in set-up, and available for viewing by the Contracting Owner for up to five (5) consecutive business days. Scope of work includes procurement and temporary installation of
JEFF - 181202 26 56 00-3
specified equipment as well as all ancillary materials necessary for a complete mockup of luminaire, exactly as specified.
2. Contractor shall coordinate mockup with landscape architecture details to provide accurate mounting and installation condition.
3. Contractor shall make modifications in mock-up installation as deemed necessary by Contracting Owner, to asses possible alterations in final mounting disposition.
1.6 INFORMATIONAL SUBMITTALS
A. Where indicated provide source quality-control test reports.
B. Where indicated provide field quality-control test reports.
1.7 CLOSEOUT SUBMITTALS
A. Operation and Maintenance Data: For luminaires and their various components and accessories, to include in emergency, operation, and maintenance manuals.
1. Manufacturers recommended installation and maintenance documents.
2. Any quality-control test results.
3. Copy of returned final, approved shop drawings.
4. Field condition wiring diagrams of control system.
5. Warranty documents, including certification of commencement date
6. List of manufacturer contact addresses and telephone numbers for each specified fixture.
1.8 COORDINATION
A. Coordinate exterior luminaires and their mounting with all applicable Contract Document details.
B. Refer to drawings for dimensions and details. Check and verify dimensions before proceeding with the Work. Clarify any discrepancies with the Contracting Officer. Should it appear that the Work intended to be described, is not sufficiently detailed or explained on the drawings or in these specifications, refer to Contracting Officer for further explanations.
C. Fixture locations as indicated on the electrical drawings are generalized and approximate.
Carefully verify locations with Contracting Officer plans and details and other reference data prior to installation.
D. Check for adequacy of headroom and non-interference with other equipment, such as pipes, conduit, or openings.
E. Bring non-standard modifications necessary to comply with the Contract Documents, and construction conflicts, to Contracting Officer’s attention before proceeding with Work.
F. Coordinate with other exterior trades with regard to mounting fixtures on project structures and bring any variance to Contracting Officer’s attention before proceeding with Work.
JEFF - 181202 26 56 00-4
1.9 DELIVERY, STORAGE, AND HANDLING
A. Package aluminum poles for shipping according to ASTM B 660.
B. Poles shall be supported to prevent any distortion.
C. Store all luminaires on decay-resistant-treated skids at least 12 inches above grade and vegetation.
D. Arrange to provide free air circulation ensuring fixtures are not stored in conditions outside of manufacturer’s recommendations.
1.10 WARRANTY
A. Special Warranty: Manufacturer’s standard form, which manufacturer agrees to repair or replace luminaire and or components of luminaires and lamps that fail in materials or workmanship;
corrode; or fade, stain, or chalk due to effects of weather or solar radiation within specified warranty period. Manufacturer may exclude lightning damage, hail damage, vandalism, abuse, or unauthorized repairs or alterations from special warrant coverage.
1. Warranty period for Luminaires: Three years from date of Substantial Completion
a. Warranty Period for Metal Corrosion: Five years from date of Substantial Completion
b. Warranty Period for Color Retention: Five years from date of Substantial Completion
c. Warranty Period for Poles: Repair or replace lighting poles and standards that fail in finish, materials, and workmanship within manufacturer’s standard warranty period, but not less than three years from date of Substantial completion.
d. Warranty Period for Lamps:
1) Replace any non-LED lamp and fuses that fail within 12 months from date of Substantial Completion; furnish replacement lamps and fuses that fail within the second 12 months from date of Substantial Completion.
2) Replace any LED lamp and its associated driver and electrical components that fail within five years from Substantial Completion.
3) Luminaires shall not be operated, other than to confirm operation for a period not to exceed 96 hours, prior to substantial completion point without acceptance from Owner.
2. Contractor responsible for notifying manufacturer of following:
a. Installation date
b. Date energized
c. Agree date of Substantial Completion with Owner.
PRODUCTS PART 2
2.1 GENERAL
JEFF - 181202 26 56 00-5
A. Luminaires must be the type designated as drawings and specifications herein indicate. Fixtures of the same type must be provided by one manufacturer.
B. Luminaire must be of the types and manufacturers described in the REQUIREMENTS FOR LUMINAIRES below, with light source, wattage, and voltage as indicated. With approval from the Contracting Officer, other manufacturers may be supplied if the submitted product meets or exceeds the specifications.
C. Substitution Limitations:
1. Listed equal manufacturers must provide a product that nominally matches physical dimensions while maintaining industrial design and equaling or bettering all performance aspects of luminaire specified including, but not limited to:
a. Distribution
b. Intensity
c. Efficacy
d. Color Rendering Index
e. CCT
f. Controllability attributes
2.2 REQUIREMENTS FOR LUMINAIRES
A. Luminaires shall comply with UL 1598 and be listed and labeled for installation in wet locations by an NRTL acceptable to authorities having jurisdiction.
B. Light Distribution Patterns: Comply with IESNA RP-8 for parameters of light distribution patterns indicated for luminaires, unless otherwise noted or specified for specific luminaire.
C. Metal Parts: free of burrs and sharp corners and edges.
D. Sheet Metal Components: Corrosion-resistant aluminum unless otherwise indicated. Form and support to prevent warping and sagging.
E. Housings: Rigidly formed, weather- and light-tight enclosures that will not warp, sag, or deform in use. Provide filter/breather for enclosed luminaires.
F. Doors, Frames, and Other Internal Access: Smooth operating, free of light leakage under operation conditions, and designed to permit access to purpose with use of tamper-resistant hardware. Designed to prevent doors, frames, lenses, diffusers, and other components from falling accidentally during relamping and when secured in operating position. Doors shall be removable for cleaning or replacing lenses. Designed to disconnect ballast/driver when door opens.
G. Exposed Hardware Material: Stainless steel fasteners with matching stainless steel receiver to avoid galvanic corrosion.
H. Plastic Parts: High resistance to yellowing and other changes due to aging, exposure to heat, and UV radiation.
1. Where used in optical elements, plastic shall be UV stabilized and pure acrylics.
JEFF - 181202 26 56 00-6
I. Reflecting surfaces shall have minimum reflectance as follows unless otherwise indicated:
1. White: 85 percent
2. Specular: 83 percent
3. Diffusing Specular: 75 percent
J. Lens and Refractor Gaskets: Use single piece heat- and aging-resistant gaskets to seal and cushion lenses and refractors in luminaire doors.
K. Luminaire finish: Manufacturer’s standard paint applied to factory assembled and tested luminaire before shipping. Where indicated, match finish process and color of pole or support materials
L. Factory-Applied Finish for Aluminum Luminaires: Comply with NAAMM’s “Metal Finishes Manual for Contracting Officer and Metal Products” for recommendations for applying and designating finishes.
1. Finish designations prefixed by AA comply with the system established by the Aluminum Association for designating aluminum finishes.
2. Natural Satin Finish: Provide fine, directional, medium satin polish (AA-M32); buff complying with AA-M20; and seal aluminum surfaces with clear, hard-coat wax.
M. Factory-Applied Labels: Comply with UL 1598. Include recommended lamps and drivers/ballasts. Labels shall be located where they will be readily visible to service personnel, but not seen from normal viewing angles when lamps are in place.
1. Label shall include the following characteristics:
a. “USES ONLY” and include specific lamp type.
b. Lamp type, wattage, color temperature
1) For LEDs: provide unique identifier used to track diode manufacturer, chip style, efficacy, and manufacture date.
2) CCT and CRI for all luminaires.
N. All recessed fixtures shall be provided with appropriate housing for its mounting condition.
Check the fixture types against the approved Contracting Officer detail prior to submittal of Action Submittals.
O. Where light fixtures are specified to be furnished with aimable, adjustable or directional components, the exact location shall be obtained from the Contracting Officer/Engineer in writing prior to roughing in.
P. 80% of luminaire material by weight shall be recyclable at end of life.
Q. LED sources must be integrally designed elements to the luminaire meeting the following requirements:
1. Rated for operation within luminaire between -40°C to +35°C
2. Where indicated in fixture specifications, CCT values shall meet the following criteria:
a. 3000K (3045 ± 175)
b. 4000K (3985 ± 275)
JEFF - 181202 26 56 00-7
3. CRI shall be greater than 75
4. Where indicated or for any substitution, luminaire manufacturer must submit reliability reports from the manufacturer of the LED (chip, diode, or package) has performed JEDEC (Joint Electron Devices Engineering Council) tests of the following aspects:
a. High Temperature Operating Life
b. Room Temperature Operating Life
c. Low Temperature Operating Life
d. Powered Temperature Cycle
e. Non-Operating Thermal Shock
f. Variable Vibration Frequency
R. Driver Requirements
1. Minimum efficiency: 85%
2. Must be rated to operate between -40°C to +35°C
3. Input Voltage: 277V unless indicated
4. Operating frequency must be 50/60 Hz
5. Power Factor of: ≥0.90
6. Total Harmonic Distortion (THD): ≤20%
7. Comply with FCC 47 CFR part 15 Non-Consumer RFI/EMI standards
2.3 GENERAL REQUIREMENTS FOR POLES AND SUPPORT COMPONENTS
A. Structural Characteristics: Comply with AASHTO LTS-4-M
1. Wind-Load Strength of Poles: Adequate at indicated heights above grade without failure, permanent deflection, or whipping with a wind speed zone of 90 MPH.
B. Luminaire Attachment Provisions: Comply with luminaire manufacturers’ mounting requirements. Use stainless-steel fasteners and mounting bolts that match manufacturer’s recommendations, unless otherwise indicated.
C. Mounting, Fasteners, and Appurtenances for Pole: Corrosion-resistant items compatible with support components:
1. Materials: Shall not cause galvanic action at contact points.
2. Anchor bolts, Leveling Nuts, Bolt Caps, and Washers: Hot-dip galvanized after fabrication unless otherwise indicated.
3. Anchor-Bolt Template: Plywood or steel
D. Handhole: Cast aluminum oval-shaped reinforcement frame, with minimum clear opening of 2- 1/2 by 4 inches, with cover secured by stainless-steel captive screws.
2.4 POLE ACCESSORIES
JEFF - 181202 26 56 00-8
A. Base Covers: Manufacturers’ standard metal units, arranged to cover pole’s mounting bolts and nuts. Finish same as pole.
B. Collar: Provide where specified and detailed in cutsheets or shop drawings.
2.5 FIXTURES
A. F1 – Glass globe with guard for general illumination located within equipment vaults. (Contractor Procured and Installed)
1. Construction: Luminaire shall be designed to support a LED source as a wet location listed fixture. Housing shall be a non-metallic body supporting a glass globe with a guard.
All elements shall be enclosed within luminaire guard and globe with molded ‘U-channel’ silicone gaskets as required.
2. Electrical: Provide with driver rated for a minimum of 50,000 hours operation at 277V.
15 watt maximum.
3. Certification: UL listed for wet locations.
4. Mounting: Provide installation details and equipment to match electrical details 5/E201 and 6/E201.
5. Source and Optics: Minimum of 40 lumens/watt at 80 CRI or better. Provide at 4000K.
6. Distribution: N/A
7. Light Source Rating: LM70/B50 of 60,000
8. Minimum Dimensions
a. H: 8.5”
b. DIA: 5.0”
9. Product:
a. DAC D8012-LED8-277-MG-WET Lithonia Lighting OLVTCM-4000K-MVOLT- Grey
b. Hubbell Lighting VNGL-1
c. Or approved equal by Lithonia Lighting, Cooper Lighting DAC D8012-LED8-
277-MG-WET
B. RC – Single ‘cobra-head’ styled luminaire mounted to steel davit arm and granitiod pole for illumination of municipal streets adjacent to park boundary. Pole to utilize a direct embedment mounting in lieu of base. All construction and procurement of this type shall conform to City of St. Louis Lighting standards (Contractor Procured and Installed)
1. Construction:
a. Fixture – Luminaire housing shall be constructed of die-cast aluminum with an optical reflector/refractor assembly with adjustable porcelain socket. The housing shall have a power module door that does not require tools for access. A slip-fitter shall be incorporated into the housing that is internally accessible and capable of mounting to a pole, davit arm, or bracket diameter of 1” to 2” while being adjustable to +/- five degrees horizontally. Luminaire shall use a medium mogul size lamp base high pressure sodium lamp rated at 250W. Socket adjustability shall
JEFF - 181202 26 56 00-9
allow for ANSI/IES medium cutoff Type II and Type III distribution without exchange of optic assembly.
b. Ballast - Ballast shall be a three coil magnetic regulator, with isolated primary and secondary. When operated at nominal like and lamp rated voltage, ballast shall deliver lamp wattage within +/- 7% of rating. Operating voltage shall be within a design range of +/- 10% from nominal with lamp wattage regulation not to except +/- 9%. At nominal line voltage and frequency when operating at nominal lamp voltage, the ballast shall be capable of sustaining a 50% input line voltage dip without extinguishing lamp. Ballast shall operate lamp in an open or short circuit state for a period of six (6) months without significant loss to ballast life.
c. Pole – Manufacturer shall be of pre-stressed concrete, machine made in steel molds by centrifugal process. Standard shall be octagonal shape and have a uniform taper of approximately 0.1 to .125 inch per foot with natural, light grey finish of spun concrete with construction to include 5/16” pre-stressed cables and four inch diameter steel rebar rods along entire length. Wiring hole shall be concentric and uniform throughout length of pole and free of rough edges capable of supporting minimum of one 1” inch but not more than two (2) inches. The cement in the standard shall conform to ASTM specification number C 150. The concrete shall produce a minimum 24 hour compressive strength of 3900 psi, under radiant heat, prior to pre-stressing release. The steel in the standard shall have a minimum ultimate tensile strength of 240,000 psi and shall be pre-stressed to at least 60% but not more than 70% of ultimate tensile strength. The standard's steel reinforcement materials shall conform to ASTM A-416-59T and ASTM A- 421-58T. The standard shall have a handhole slot centered 16” above grade and a cable entrance slot below grade level. These two slots shall be on the side of standard opposite to the street. The luminaire arm shall consist of galvanized black steel schedule 40 pipe, conforming to ASTM-A-501 and ASTM A-12207T, or aluminum pipe conforming to ASTM B-241-6063-T6. The arm shall be welded to the octagon shaped mounting bracket, specifically designed for use with octagon shaped concrete lighting poles. The arm length shall be 6’ and have a single curvilinear rise of approximately 3'- 6", from the bracket to the luminaire's slip fitter. The arm shall have a 3E rise, as measured to the end.
2. Electrical – Luminaire shall incorporate ballast operating at 480VAC, 1φ with a correlated power factor of a minimum 90%. Maximum lamp wattage of 250W.
3. Certification: UL listed for wet locations.
4. Mounting: Provide as direct embed pole meeting necessary structural requirements for soil conditions. Provide embedment details for review as part of shop drawing submittal.
5. Source and Optics: Luminaire shall use a medium mogul size lamp base high pressure sodium lamp rated at 250W. Socket adjustability shall allow for ANSI/IES medium cutoff Type II and Type III distribution without exchange of optic assembly.
6. Distribution: Factory setting shall be medium semi-cutoff Type III.
7. Light Source Life Rating: 24,000 hours average rated life
8. Dimensions:
a. H: 30’-0” above grade (pole height)
b. L: 6’-0” davit arm
JEFF - 181202 26 56 00-10
C. SA – Single head, pole mounted full cutoff pedestrian LED area light for use in illumination of pathways and plazas. (Following fixture will be provided by the Government, FOB Job Site)
1. Construction: Luminaire shall be designed as an integral design element within same shape and profile as pole. Housing shall be fabricated from aluminum with no visible welds. Wall thickness shall be no less than 3/16” treated to produce a T6 temper. Provide with flush hand-hole and include tamper-resistant locking device. All hardware shall be stainless steel with matching inserts to prevent galvanizing components. Two piece fabricated aluminum base cover. Luminaire design shall be in the shape of inverted ‘L’ with the projecting arm to be installed perpendicular to the path.
2. Electrical: Provide with driver rated for a minimum of 50,000 hours operation capable of supporting DALI control protocol. Luminaire shall operate as a single device within control loop. 60 watt maximum.
3. Certification: UL listed for wet locations.
4. Mounting: Provide wood anchor bolt template. Anchor bolts shall be sized by manufacturer to meet necessary requirements of pole design and structural foundation details on drawing S111. Anchor bolt plate shall be no larger than 11.81” square with a nominal bolt circle of 7.87”. Anchor bolts shall be at 90° increments located in corners of bolt plate. Two piece fabricated aluminum base cover to encapsulate anchor bolt plate with minimal spacing possible.
5. Source and Optics: Minimum of 40 system lumens/watt at 75 CRI or better. Provide with 4000K field replaceable aluminum core LED module. Prismatic lens shall be of molded optical quality US stabilized acrylic single piece prismatic lens.
6. Distribution: ANSI Type III
7. Light Source Life Rating: LM70/B50 of 60,000
8. Dimensions:
a. H: 177.6”
b. L: 43.7”
c. W: 7.5”
d. D: 4.1”
9. Product:
a. Hess America LN450/2LV-2/N-ME-UNVMOD/A/15SRA/xx(FINISH)
b. Bega 8977LED
c. Or approved equal from Schreder Lighting, Louis Poulsen
D. SA-R – Single head, pole mounted full cutoff pedestrian LED area light for use in illumination of pathways and plazas with integral convenience receptacle. Fixtures identified per E300 lighting fixture schedule; only responsible for quantity within contract boundary per L100 layout series and E100 series drawings. (Following fixture will be provided by the Government, FOB Job Site)
1. Construction: Luminaire shall be designed as an integral design element within same shape and profile as pole. Housing shall be fabricated from aluminum with no visible welds. Wall thickness shall be no less than 3/16” treated to produce a T6 temper. Provide with flush hand-hole and include tamper-resistant locking device. All hardware shall be stainless steel with matching inserts to prevent galvanizing components. Two piece
JEFF - 181202 26 56 00-11
fabricated aluminum base cover. Luminaire design shall be in the shape of inverted ‘L’ with the projecting arm to be installed perpendicular to the path.
2. Electrical: Provide with driver rated for a minimum of 50,000 hours operation capable of supporting DALI control protocol. Luminaire shall operate as a single device within control loop. 60 watt maximum. Provide with integral 120V duplex convenience receptacle.
3. Certification: UL listed for wet locations.
4. Mounting: Provide wood anchor bolt template. Anchor bolts shall be sized by manufacturer to meet necessary requirements of pole design and structural foundation details on drawing S111. Anchor bolt plate shall be no larger than 11.81” square with a nominal bolt circle of 7.87”. Anchor bolts shall be at 90° increments located in corners of bolt plate. Two piece fabricated aluminum base cover to encapsulate anchor bolt plate with minimal spacing possible.
5. Source and Optics: Minimum of 40 system lumens/watt at 75 CRI or better. Provide with 4000K field replaceable aluminum core LED module. Prismatic lens shall be of molded optical quality US stabilized acrylic single piece prismatic lens.
6. Distribution: ANSI Type III
7. Light Source Life Rating: LM70/B50 of 60,000
8. Dimensions:
a. H: 177.6”
b. L: 43.7”
c. W: 7.5”
d. D: 4.1”
9. Product:
a. Hess America LN450/2LV-2/N-ME-UNVMOD/A/15SRA/xx(FINISH)/MODREC
b. Bega 8977LED-MODREC
c. Or approved equal from Schreder Lighting, Louis Poulsen
E. SG – Straight aluminum pole with mounting collar for attachment of (3) adjustable LED floodlights. (Following fixture will be provided by the Government, FOB Job Site)
1. Construction:
a. Fixture – Main exterior components including housing, hinge, cover, and mounting bracket shall be corrosion-resistant, cast aluminum with a two layer powder-coat finish selected from manufacturer’s standard finishes or a RAL color during submittals. Hinge shall provide 130° tilt at a minimum with a stainless steel graduated disc. Cover glass shall be optically clear safety glass and cover shall be secured by screw without spill light. All hardware shall be stainless steel with matching inserts to prevent galvanizing components. Finish shall be selected from manufacturer’s standard finishes or a RAL color during submittals.
b. Pole – Shaft shall be 5” in diameter, extruded from seamless aluminum and heat treated to a T6 tamper. Anchor base shall be cast from aluminum and welded to shaft with similar heat treatment to T6 temper. Provide with flush hand-hole and include tamper-resistant locking device. Luminaire collar shall be of same material and construction as shaft, 7” in diameter and 8” tall secured by weld prior to
JEFF - 181202 26 56 00-12
finishing allowing. Provide 4” from top of collar to top of pole. Anchor base shall be cast aluminum and welded to shaft. Collar shall be spun aluminum no larger than 11” in diameter and 5” tall. Finish shall be selected from manufacturer’s standard finishes or a RAL color during submittals to match fixture finish. Pole manufacturer shall be responsible for coordinating final collar and fixture fit prior to delivery.
2. Electrical: Luminaire shall be supplied with driver operating at 277V and support through-wiring. All wiring shall be internal to the luminaire – no visible wiring.
3. Certification:
a. Fixture - UL listed for wet locations. Minimum IP65 rating.
4. Mounting:
a. Fixtures - (3) luminaires to be mounted at 90° of each other on pole collar.
Luminaires shall be provided with mounting sleeve of same construction and finish as luminaire designed for purpose and detailed as integral element. Mounting sleeve shall allow for 360° of rotation by luminaire.
b. Pole: Provide wood anchor bolt template. Anchor bolts shall be sized by manufacturer to meet necessary requirements of pole design and structural foundation details on drawing S111. Anchor bolt plate shall be triangular in shape allowing nominal bolt circle of 7-3/8” minimum and 8-1/2” maximum. Anchor bolts shall be at 120° increments. Two piece fabricated aluminum base cover to encapsulate anchor bolt plate with minimal spacing possible.
5. Source and Optics: Minimum of 90 lumens/watt at 4000K with a CRI of 80 or better.
Diodes shall be mounted to metal-core PCB with surge protection. Luminaire shall utilize a projection based optical system including collimating and separate distribution lenses made of optical polymer. Distribution lens shall be installed recessed within luminaire housing from outer safety glass in such a manner to allow 360° rotation and be field interchangeable. In addition to base specification, luminaire shall be provided with following distribution lenses: Wide Flood, Oval Flood.
6. Distribution: Flood, 29°; Center Beam Candlepower minimum of 2800 candela.
7. Light Source Life Rating: LM70/B10 of 50,000
8. Dimensions (Fixture):
a. H: 7.6”
b. L: 8.3”
c. DIA: 5.3”
d. Weight: 8.5lbs maximum
e. EPA maximum: 0.4ft²
9. Dimensions (Pole):
a. H: 108.0” 144.0”
b. DIA: 5.0”
c. Collar DIA: 7.0”
d. Collar H: 8.0”
10. Product:
a. Fixture
JEFF - 181202 26 56 00-13
1) ERCO 34475.099/34957.023 (.099-provide FL, WF and OF lenses)
b. Pole
1) Valmont 1000-50-50-5-S-3-MODCollar-xx(FINISH)
F. SN – Wall recessed, low wattage LED pathway light at sloped pathways. (Contractor procured, and Installed)
1. Construction: Luminaire housing shall be die-cast of marine grade and copper free aluminum. Faceplate shall be constructed of stainless steel with a tempered safety glass with optical texture. Any gasket required for weather tight operation shall be a molded ‘U-channel’ in shape made of silicone. All hardware shall be stainless steel with matching inserts to prevent galvanizing components.
2. Electrical: Luminaire shall be supplied with driver operating at 277V and support through-wiring.
3. Certification: UL listed for wet locations. Minimum IP65 rating.
4. Mounting: Manufacturer shall provide matching housing if necessary to support pour in-place concrete installation. Refer to architectural details for installation details and clearances.
5. Source and Optics: Minimum of 50 lumens/watt at 4000K with CRI of 85 or better. LEDs shall be mounted to metal-core PCB with surge protection. Any lens shall be of optically neutral material with acrylics being UV stabilized.
6. Distribution: Asymmetric, forward throw
7. Operation: LM70/B50 of 50,000
8. Dimensions:
a. D: 4.75”
b. DIA: 6.0”
9. Product:
a. BEGA 3020LED/BB3020LED
b. ERCO 33300.099/MODLED
c. Or approved equal by Winona
G. SP – Semi-cutoff, pole mounted pedestrian LED area light for use in illumination of pathways and plaza. (Contracting Officer Procured, Contractor Installed)
1. Construction: Luminaire head and pole shall be considered as integral design elements from the same manufacturer. Luminaire head shall be constructed of two elements – the source module comprised of all electronics and optical elements necessary for operation, and the reflector shade. Luminaire head and reflector shade shall be designed to be separable units for future maintenance, but appear as a singular element. The combination of head and shade shall be supported from the pole top by total of (3) arms. Arms shall be mounted at the same point at the top of the pole, angled to meet the reflector at similar distances, 120° from each other around the reflector. Lighting distribution produced by the luminaire shall be set to pass through two of the arms, with installation notations providing installing contractor with correct orientation for appropriate illumination of the pathways.
JEFF - 181202 26 56 00-14
a. Luminaire head: Shall comprise an upper, die-cast element made from marine grade aluminum free of copper. The lower element shall utilize translucent, UV stabilized acrylic allowing no greater than 10% total visible light transmission and optically neutral safety glass for weather seal. Upper and lower elements shall be manufactured to match with minimal seam and all required seals to ensure watertight operation. Molded ‘U-Channel’ silicone gaskets to be used where necessary.
b. Reflector Shade: Shade shall be constructed of two pieces to create desired architectural shape while allowing required electrical and data cables to pass from the pole to the luminaire head. Outer shade element shall be die-cast marine-grade, copper free aluminum. Inner shade shall be spun aluminum.
c. Pole: Shaft shall be tapered from 4” O.D. at base to 3” O.D. at head mount, extruded from seamless aluminum. Shaft shall attach to a cast aluminum base with a circumferential weld. Provide with flush hand-hole and include tamper-resistant locking device. Spun aluminum base cover shall be no larger than 12” in diameter and 5” tall. Finish shall be selected from manufacturer’s standard finishes or a RAL color during submittals.
2. Electrical: Provide with driver rated for a minimum of 50,000 hours operation capable of supporting DALI control protocol. Luminaire shall operate as a single device address within a DALI control loop. 75 watt maximum.
3. Certification: UL listed for wet locations. Minimum IP65 rating.
4. Mounting: Provide wood anchor bolt template. Anchor bolts shall be sized by manufacturer to meet necessary requirements of pole design and structural foundations details on drawing S111. Anchor bolt plate shall be no larger than 8.8” square with a nominal bolt circle of 6.5” minimum and 8.3” maximum. Anchor bolts shall be at 90° increments located in corners of bolt plate. Two piece fabricated aluminum base cover to encapsulate anchor bolt plate with minimal spacing possible.
5. Source and Optics: Minimum of 65 lumens/watt at 4000K with a CRI of 85 or better.
6. Distribution: ANSI Type III
7. Operation: LM70/B50 of 50,000
8. Dimensions:
a. H: 192.0” total, 29.3” for head
b. DIA Shade: 39.0”
c. DIA Pole: taper 4.0” OD to 3.0” OD
9. Product:
a. Louis Poulsen 131-17120
b. Custom luminaire, no substitutions allowed.
EXECUTION PART 3
3.1 LUMINAIRE INSTALLATION
A. Fasten luminaire to indicated structural supports.
JEFF - 181202 26 56 00-15
1. Use fastening methods and materials selected to resist seismic forces defined for the application and approved for by manufacturer.
B. Where Work of this section is to be flush or concealed, install so that it does not project beyond the finished lines of the surface into which the fixture is installed, unless otherwise designated.
C. Where indicated for fixtures installed recessed flush within wall construction, Contractor shall verify and supply all necessary mounting and installation hardware required to ensure a safe, secure, code compliant application.
1. If necessary, Contractor shall pre-order back boxes for fixture to be installed prior to arrival of optical/lamp assembly, in order to avoid compromises in schedule or damage to finished luminaire surfaces.
D. Lenses, Louvers, and Reflectors:
1. Wear special gloves, as approved by the fixture manufacturer, to preclude smudging or damaging the reflector surface when installing fixtures and lamps in fixtures with specular reflector material.
2. Install louvers and glare shields in place after the project is complete and dust free or provide with protective cover over louvers, UL listed for temporary lighting. Upon completion of Work, remove cover with special gloves indicated above.
E. Accessibility
1. Install equipment such as junction and pull boxes, fixture housing, transformers, ballasts, drivers, controls, and other apparatus that requires occasional maintenance, to be accessible and appropriate for mounting.
3.2 POLE INSTALLATION
A. Alignment: Align pole foundations and poles for optimum directional alignment of luminaires and their mounting provisions of the pole.
1. See Landscape Detail Drawings for additional direction and guidance.
B. Foundation-Mounted Poles: Mount pole with leveling nuts, and tighten top nuts to torque level recommended by pole manufacturer.
1. Use anchor bolts and nut selected to resist seismic forces defined for the application and approved by manufacturer.
2. Grout void between pole base and foundation. Use no-shrink or expanding concrete grout firmly packed to fill space.
3. Install base covers unless otherwise indicated.
4. Use a short length of ½ inch-diameter pipe to make a drain hole through grout. Arrange to drain condensation from interior of pole.
5. Refer to structural drawings for specifications for further installation requirements.
3.3 CORROSION PREVENTION
JEFF - 181202 26 56 00-16
A. Aluminum: Do not use in contact with earth or concrete. When in direct contact with a dissimilar metal or material, protect aluminum by insulation fittings or treatment.
B. Steel Conduits: Comply with applicable Division 26 section. In concrete foundations, wrap conduit with 0.010 inch thick, pipe wrapping plastic tape applied with a 50 percent overlap.
3.4 GROUNDING
A. Ground metal poles and support structures according to applicable Division 26 Section.
1. Install grounding electrode for each pole unless otherwise indicated.
2. Install grounding conductor pigtail in the base for connecting luminaire to grounding system.
B. Ground nonmetallic poles and support structures according to applicable Division 26 Section.
1. Install grounding electrode for each pole.
2. Install grounding conductor and conductor protector.
3. Ground metallic components of pole accessories and foundations.
3.5 FIELD QUALITY CONTROL
A. Execution requirements: Testing, Adjusting, and Focusing: refer to Projects General Conditions and Lighting Fixture Schedule.
B. Inspect each installed fixture for damage. Replace damaged fixtures and components to the satisfaction of the Contracting Officer.
C. Operate each luminaire after installation and connection for a period not to exceed 96 hours.
Inspect connections after operation.
D. If luminaires are believed to be underperforming in early life, the Site Owner may choose to take field measurements between 2,000 and 3,000 operating hours of the completion of installation to confirm that lighting levels are in accordance with the projected levels. If average light levels are more than 15% below the Day 1 submittal, and the luminaire locations in the field are as designed, the luminaire manufacturer must provide replacement luminaires for those tested.
3.6 AIMING AND FOCUSING
A. Contractor shall be responsible for final targeting/focusing of adjustable light fixtures under the observation of, and according to, the recommendations of the Contracting Officer or Lighting Designer. Aiming shall take place after dark at a mutually agreed upon time, after all relevant amenities’ have been installed.
B. All necessary equipment to complete aiming and focusing work including ladders, lifts, and personnel shall be supplied by the Contractor.
JEFF - 181202 26 56 00-17
C. Where made necessary by site conditions, Contractor shall provide surface protection for surrounding materials to protect from potential damage caused by the use of any lifts and related equipment used during the final lighting adjustments.
3.7 CLEANING
A. Execution Requirements: Final Cleaning (Refer to Project’s General Conditions)
B. Remove dirt and debris from enclosures.
3.8 PROTECTION OF FINISHED WORK
A. Execution Requirements: Protecting Finished Work (Refer to Project’s General Conditions).
END OF SECTION
JEFF - 181202 26 56 00-18
THIS PAGE IS INTENTIONALLY BLACK