J-1601000-11 SAMPLE ESSENTIAL EQUIPMENT LOG (EEL).pdf

PDF 261 KB Posted

Attached to
Base Operations Support Services For NSA Annapolis and US Naval Academy, Annapolis, Maryland
Solicitation number
N6247026R0017
Issued by

About this file

This document is a Facilities and Equipment Status Report for the United States Naval Academy (USNA) in Annapolis, Maryland, dated January 14, 2026. The report provides comprehensive operational status updates for all major building systems, utilities, and equipment across the USNA campus, including heating, cooling, water treatment, wastewater management, electrical infrastructure, emergency generators, and specialized facilities such as pools and irrigation systems.

The report indicates numerous critical systems currently offline or requiring maintenance, including HTHW Generator #2 (oil meter failure), multiple boiler circulating pumps in standby mode, Zone Distribution pump #1 (isolation valve leaks), two portable boilers undergoing NAVFAC inspection awaiting funding, Steam Generator #2 (tube bundle leak), and several backflow preventers at various buildings that have failed pressure relief valve (BFP) testing and present health hazards. Active maintenance issues include condensate leaks in the lower yard, faulty water softeners, multiple chiller units with failed actuators and VFD faults, condenser pumps with leaking seals and failed motors, and numerous fire alarm systems offline requiring full replacement engineering. Scheduled utility outages approved for the near term include electrical power maintenance at substations, steam outages at dormitories, water service work at Brigade Sports Complex, and parking lot closures for construction staging. The document also tracks 36 street and building lights currently out of service across four patrol zones, with several requiring RFP development. Door dams and sandbag inventory for flood mitigation are confirmed ready for deployment, and weather forecasting indicates potential rain and snow showers Thursday through Friday with gusting winds.

View the file

Other files

File Type Posted
J-1604000-09 SAMPLE SLUDGE ANAYLSIS REPORT AND SLUDGE GENERATOR REPORT.pdf PDF
J-1503020-06 ASSET DATA AND FREQUENCIES FOR SCHEDULED WORK.xlsx XLSX spreadsheet
J-1502000.1-03 DHA ASSET DATA INDEX, SYSTEM DESCRIPTIONS AND ASSET DATA BY SYSTEM.xlsx XLSX spreadsheet
0100000 C General Information.pdf PDF
J-1605000-07-04 SAMPLE UTILITY CONSUMPTION REPORTING LOG.xlsx XLSX spreadsheet
J-1502000.1 Facility Investment - DHA.pdf PDF
J-1605000-06 SAMPLE NAVFAC BOILER AND UPV INSPECTION FORM AND INSPECTION CERTIFICATE.pdf PDF
J-0200000-07-07 Contractor Incident Report System (CIRS) Form.pdf PDF
J-1604000-14-01 STORMWATER MANAGEMENT REPORT-ANNAPOLIS JANUARY 2017.pdf PDF
J-1602000 Electrical.pdf PDF
J-1604000 Wastewater.pdf PDF
J-0200000 Management and Administration.pdf PDF
J-1607000 Chiller.pdf PDF
1501000 C Facility Management.pdf PDF
0200000 C Management and Administration.pdf PDF
N6247026R0017 Pre-Sol Notice.pdf PDF
J-1606000 Water.pdf PDF
Attachment F - Section F Deliverables.pdf PDF
J-1601000-04 SERVICE DESK GUIDE FOR UTILITY OUTAGES.pdf PDF
J-1605000-07-02 SAMPLE ROVING PATROL LOG.xlsx XLSX spreadsheet
J-1606000-03-02 WTP AND DISTRIBUTION SYSTEM DESCRIPTION 2.docx DOCX document
J-1601000-05 UTILITY INTERRUPTIONS ROAD AND PARKING LOT CLOSURE AUTHORIZATIONS REQUEST FORM.xlsx XLSX spreadsheet
1502000 C Facility Investment.pdf PDF
J-0200000-20 - ELINS.xlsx XLSX spreadsheet
J-1605000-09 HISTORICAL BOILER HRSG UPV TESTING AND CERTIFICATION SCHEDULE.xlsx XLSX spreadsheet
J-1607000-08 Cooling Tower Water Testing and Treatment Asset Data.xlsx XLSX spreadsheet
J-1502000-04 FACILITY DATA.xlsx XLSX spreadsheet
DRAFT Solicitation - N6247026R0017.pdf PDF
J-1604000-14-03 STORMWATER MANAGEMENT REPORT-ANNAPOLIS JANUARY 2017.pdf PDF
J-4 Pre-Award Inquiry Form.xlsx XLSX spreadsheet
J-1503020 Pest Control.pdf PDF
J-1601000-08 EXCAVATION-UTILITY MARKING AUTHORIZATIONS REQUEST FORM.xlsx XLSX spreadsheet
J-1503070-03 Special Event Project Historical Data.xlsx XLSX spreadsheet
1700000 C BSVE.pdf PDF
J-1604000-04 WASTEWATER SYSTEM ASSET DATA.xlsx XLSX spreadsheet
1503020 C Pest Control.pdf PDF
J-1605000-04 STEAM ASSET DATA.xlsx XLSX spreadsheet
1604000 C Wastewater.pdf PDF
1601000 C Utility Management.pdf PDF
J-1604000-15 PERMEABLE PAVEMENT AREAS.pdf PDF
J-0200000-02-02 DBA WAGE DETERMINATION.pdf PDF
J-1700000-05 HISTORICAL FUEL DELIVERY QUANTITIES.xlsx XLSX spreadsheet
1606000 C Water.pdf PDF
J-1503070 Special Events.pdf PDF
J-1502000 Facility Investment.pdf PDF
J-1607000-04 Chiller Plant and Distribution System Asset Data.xlsx XLSX spreadsheet
1605000 C Steam.pdf PDF
J-1503030 Integrated Solid Waste Management.pdf PDF
J-0200000-02-01 SCA WAGE DETERMINATION.pdf PDF
J-1606000-08 MDE SCHEDULE OF MONITORING REQUIREMENTS EXAMPLE.pdf PDF
Show 40 more

Latest 50 of 86 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Production/UEM: NOAA Weather Forecast: 7-Day Forecast 38.97N 76.49W (weather.gov) On Line Safety Manager: AccuWeather Weather Forecast: Annapolis, MD Daily Weather | AccuWeather Stand-By Utilities Manager: NOAA Tides and Currents: Station Home Page - NOAA Tides & Currents Inspection Facilities Manager: WeatherBug Weather Forecast: Annapolis, Maryland | 10-Day Weather Forecasts & Weekend Weather | WeatherBug High Temp Water Shut-down IDIQ Manager: NOAA Operational (Tides): Operational Forecast System - Station Plot Time Series (noaa.gov) Stand-By EV/Energy Manager: NOAA Hurricane Center: National Hurricane Center (noaa.gov) Off-Line for Summer Duty Manager: NOAA Water-Adv. Hydrologic Prediction: NOAA Severn River Tidal Forecast Off-Line for Winter

1/5/2026

BLDG # EQUIPMENT STATUS Action Date ETR Maximo Work Order # Impact if Equipment/System is Out of Service Remarks IDIQ Remarks

HTHW GENERATOR #1

Stand-By

1/14/2026

12/16/2025

HTHW GENERATOR #2

On-line

1/14/2026 01/06/2026 Oil Meter Bad unable to run on oil until replaced

1/14/2026 HTHW Generator #3 On-line 1/14/2026 12/17/2025 Repair

1/14/2026 Boiler Circulating pump #1 Stand-By 1/14/2026 11/17/2025 Boiler Circulating pump #2 On-line 1/14/2026 Boiler Circulating pump #3 On-line 1/14/2026 Monthly Change Over 10/28/2025 Boiler Circulating pump #4 Stand-By 1/14/2026 Placed Back In Service. 11/19/2025 Feed Water Pump #1 On-line 1/14/2026 Monthly Change Over 1/1/2026 Feed Water Pump #2 Stand-By 1/14/2026 Monthly Change Over 1/1/2026 Make-Up Water Pump # 1 On-line 1/14/2026 Monthly Change Over 1/1/2026 Make-Up Water Pump # 2 Stand-By 1/14/2026 Monthly Change Over 1/1/2026 Zone Distribution pump #1 Out-of-Service 12/23/2025 6/26/2024 CM6ZZR LOTO# 2009 HTHW Isolation Valves Not holding, leaking by. pump installed warmed up and online for testing 10/30/2024 Zone Distribution pump #2 On-line 1/14/2026 Monthly Change Over 1/2/2026 Zone Distribution pump #3 Stand-By 1/14/2026 Monthly Change Over 10/1/2025 Zone Distribution pump #4 Stand-By 1/14/2026 Making a knocking noice . Switched to #2. Distribution pump. 1/3/2026.

#1 Control Air Compressor On-line 1/14/2026 #2 Control Air Compressor On-line 1/14/2026 #5 atomizing air compressor Stand-By 1/14/2026 #6 atomizing air compressor Stand-By 1/14/2026 #7 atomizing air compressor Stand-By 1/14/2026 #8 atomizing air compressor Stand-By 1/14/2026 HTHW Generator Safety Valves Stand-By 1/14/2026 Sulfite 100-200 130 1/14/2026 Alkalinity 150-200 150 1/14/2026 Softener (Hard/Soft) Soft 1/14/2026

EMERG. DIESEL GEN RUN HRS. 364.3 1/14/2026 Generator Test Run every Wednesday at 17:00-17:30

Monitored Fuel Level 63% 1/13/2026 579S Portable Boiler #1 Out-of-Service 3/29/2024 620550 Moved to rear of CHP for storage 3/29/2024. Disassembled For NAVFAC inspection. IQ bid to repair submitted, waiting funding

Portable Boiler #2 Out-of-Service 3/29/2024 Moved to rear of CHP for storage 3/29/2024. Disassembled For NAVFAC inspection.

579 HTHW Sump Pump # 1 On-line 1/13/2026 579 HTHW Sump Pump # 2 On-line 1/14/2026 583 #1 Fuel Oil Tank (Full 317,015 gal) -

Suction On-line 1/14/2026 Fuel tank capacity 80 % = (253,612) 12/29/2025 10' 1 3/16" = 136,235 Gal.

617 #2 Fuel Oil Tank (Full 335,000 gal) Out-of-Service

EMPTY 1/14/2026 FY24

Expansion Tank/Dump Tank On-line 1/14/2026 Fuel Oil Transfer Pump #1 Stand-By 1/14/2026 Fuel Oil Transfer Pump #2 Stand-By 1/14/2026 Zone 1 Supply Temp (°F) 360 1/14/2026 Zone 1 ReturnTemp (°F) 285 1/14/2026

Zone 1 Supply PSI 455 1/14/2026 Zone 1 Return PSI 405 1/14/2026

Zone 2 Supply Temp (°F) 360 1/14/2026 Zone 2 ReturnTemp (°F) 318 1/14/2026

Zone 2 Supply PSI 455 1/14/2026 Zone 2 Return PSI 420 1/14/2026

Lower Yard Tunnel (Michelson) Condensate Leak 3/27/2025 1/11/2026 10/27/23 Energy awareness: Loss of condensate will 19OCT23: UEM found the condensate in the Lower Yard leaking leaving Michelson. UEM

Steam Generator #1 On-line 1/13/2026 @ 24psi 10/25/2025 Increasing 5psi each day till 25psi Alkalinity 200 - 600 150 1/11/2026 Sulfite 30 - 150 40 1/11/2026 Conductivity, neutralized (2500 - 3500) 2543 1/11/2026 Steam Generator #2 Out-of-Service 12/20/2025 Tube Bundle Leak LOTO# 1970 Alkalinity 200 - 600 Sulfite 30 - 150 Conductivity, neutralized (2500 - 3500) Softener (Hard/Soft) Hard 1/13/2026 Repair or Replace Faulty Water Softner. Water Softner Has a Faulty Electronic Head

Essential Equipment Log

CENTRAL HEATING PLANT

Oil meter: 745.6 // Hrs. since VE 0 @ 09:00 hrs

Oil meter: 38998.7 // Hrs. since VEO @ 72:00 hrs

Oil meter: 17342.2 // Hrs. since VEO @ 72:00 hrs

Known HTHW / Steam Issues

STEAM PLANT

CHP:

Medium Voltage:

CHWP:

WTP:

WWTP:

Fire Sprinklers:

Pools & Irrigation:

NAVFAC has fuel tank out of service: PWD Annapolis has this for action. LOTO #1033

654U Well #15 Stand-By 1/14/2026 683U Well #16 Stand-By 1/14/2026 587U Well #17 On-line 1/14/2026 IQ: CJXGW9

Control Panel On-line 1/14/2026 #1 Air Compressor On-line 1/14/2026 12/22/2025 IMP WO# 3931484 #2 Air Compressor On-line 1/14/2026 Ingersoll Rand (spare) Air Compressor On-line 1/14/2026 Quincy air compressor 2nd deck On-line 1/14/2026

#1 Aerator Motor On-line 1/14/2026 #2 Aerator Motor Stand-By 1/14/2026 Fluoride pump On-line 1/14/2026 IMP WO# 3782936 #1 Wispro Floc pump Stand-By 1/14/2026 #2 Wispro Floc pump On-line 1/14/2026 #1 Lime Injection System Stand-By 1/14/2026 #2 Lime Injection System On-line 1/14/2026 #1 Coagulation Tank On-line 1/14/2026 #2 Coagulation Tank On-line 1/14/2026 Filter #1 On-line 1/14/2026 Filter #2 Stand-By 1/14/2026 Filter #3 On-line 1/14/2026 Filter #4 On-line 1/14/2026 Filter #5 On-line 1/14/2026 Filter #6 Stand-By 1/14/2026 Filter #7 Stand-By 1/14/2026 Distribution pump #1 On-line 1/14/2026 Distribution pump #2 On-line 1/14/2026 Distribution pump #3 On-line 1/14/2026 Distribution pump #4 Stand-By 1/14/2026 Centrifuge #1 Stand-By 1/14/2026 Centrifuge #2 On-line 1/14/2026 Sludge Holding #A On-line 1/14/2026

Sludge Holding #B On-line 1/14/2026 12/13/2025 Sludge Pump #1 Stand-By 1/14/2026 12/13/2025 Sludge Pump #2 On-line 1/14/2026 12/13/2025 Water Tower Level (Normal:154'-160') 156 1/14/2026 Daily On line System psi 65 to 68 12/13/2025 Storage Tank Levels (Normal: 23'-27') 25.2/25.3 1/14/2026 Daily 12/13/2025 Daily Discharge Flow 412664 1/14/2026 Daily 12/13/2025 Effluent Distribution meter On-line 1/14/2026 12/13/2025 GPM (Avg.) 196 1/14/2026 Daily 12/13/2025 MGD 0.412 1/14/2026 Daily 12/13/2025 Gallon Totalizer Reading: 36614500 1/14/2026 Daily 12/13/2025 Booster pump #1 On-line 1/14/2026 12/13/2025

Booster pump #2 Stand-By 1/14/2026 12/13/2025

Iron 0.02 1/14/2026 Range: 0.03 ppm (0.3 ppm MCL) Daily 12/13/2025

Turbidity 0.07 1/14/2026 Daily 12/13/2025

Free Chlorine Residual (Cl2) 1.36 1/14/2026 Range: 1.2 - 1.8 mg/L (4.0 mg/L MCL) Daily 12/13/2025

PH 8.14 1/14/2026 Range: 6.5 - 8.5 Daily 12/13/2025

Fluoride 0.53 1/14/2026 Target: 0.7 mg/L MCL Daily 12/13/2025

12/13/2025 ivo 907ns Valve F50-p1 Leaking went to make repair on leaking water main at gun range, found valve leaking from thevalve body.reported to UEM greg, BP11/10/2025 12/13/2025

12/13/2025

FH #32 leaks and is hard to Operate In service found during udf BP 12/13/2025 FH #43 leaks form bonnet hard to operate

In service found durring udf BP

FH #6 leaks form bottom when in operatio In service found durring udf BP

FH# 49 leaks when in operation In service found durring udf BP

FH# 54 leaks form bonnet when in operati In service found durring udf BP

FH# 82 hard to open and leaks form bonne In service

Found on UFD BP

FH# 80 has stripped cap In service

Found on UFD BP

FH# 81 has stripped cap In service

Found on UFD BP

FH# 97 hard to open/ leaks from bonnet In service

Found on UFD BP

WATER TREATMENT PLANT

1st 12 hour Tests

Known Water Main Issues

Known Fire Hydrant Issues

FH# 100 hard to open In service

Found on UFD BP

FH# 75 hard to open In service

Found on UFD BP

FH# 65

Out-of-Service CPJVLR

FIRE HYDRANT TAKEN OUT OF SERVICE TO SUPPORT OUTAGE REQUEST #5753 This is to support the Perimeter Wall Project

FH# 212

IN Service CRD4MC fire hydrand dose not seal when off and leask by the valve. also leaks form top screw. BP

FH# 85 hard to open In service

Found on UFD BP

257 POLICE STATION 3" MAIN NA257-BFP-417FAILED

CLJ3VJ

HEALTH HAZARD FAILED BFP TESTING

101-6 WING 6 6" DOMESTIC HOT WATER NA101FAILED

CLJ3VD

HEALTH HAZARD FAILED BFP TESTING

579 CHP MAIN 4" NAUP579-BFP-153-A FAILED

CLJ3VP

HEALTH HAZARD FAILED BFP TESTING

201 FARRAGUT FIELD IRRIGATION 4" NA201-FAILED

CLJ3VP

HEALTH HAZARD FAILED BFP TESTING

693 COMMISSARY MAIN 3" FAILED HEALTH HAZARD FAILED BFP TESTING

571 PERRY CENTER 3/4" COMPRESSOR COOFAILED HEALTH HAZARD FAILED BFP TESTING

101-4 WING 4 3" DHW NA1014-BFP-4251-A FAILED HEALTH HAZARD FAILED BFP TESTING

590 RICKOVER 1 1/4" NA590-BFP-188-A FAILED HEALTH HAZARD FAILED BFP TESTING

87 YP PIER BOAT FILL 2-1/2" NA87NS-BFP-4FAILED HEALTH HAZARD FAILED BFP TESTING

107 SAMPSON 3/4" NO-POT NA107-BFP-5004-FAILED HEALTH HAZARD FAILED BFP TESTING

2 O' CLUB HUMIDIFIER 3/4" NA2-BFP-5013- FAILED HEALTH HAZARD FAILED BFP TESTING

101-8 WING 8 FIRE NA1018-BFP-35-A FAILED HEALTH HAZARD FAILED BFP TESTING

101-7 WING 7 6" DOMESTIC HOT WATER NA101FAILED HEALTH HAZARD FAILED BFP TESTING

291 BEACH HALL MAKE UP 1" NA291-BFP-17 FAILED HEALTH HAZARD FAILED BFP TESTING

101-L LEAVY FIRE NA101L-BFP-4216-A FAILED HEALTH HAZARD FAILED BFP TESTING

101-2 WING 2 WTR SOFTNER 2" 1012-BFP-1994FAILED HEALTH HAZARD FAILED BFP TESTING

101-3 WING 3 FIRE 6" 1013-BFP-251-A FAILED HEALTH HAZARD FAILED BFP TESTING

234NS HANGER 1" WTR SOFTNER NA234NS-BFPFAILED HEALTH HAZARD FAILED BFP TESTING

NA265 NATURE CENTER 1" MAIN NANA265-BFP FAILED HEALTH HAZARD FAILED BFP TESTING

82NS OUTBOARD MAKE UP 3/4" NA82NS-BFP-5FAILED HEALTH HAZARD FAILED BFP TESTING

181 HALLIGAN HALL 6" FIRE SYSTEM NA181-FAILED

2/23/2024 NEEDS RFP

HEALTH HAZARD FAILED BFP TESTING

47NS BEQ FIRE 6" NA47NS-BFP-157-A FAILED

NEEDS RFP

HEALTH HAZARD FAILED BFP TESTING

274 OLD NHC 3" MAIN NA274-BFP-228-A FAILED

NEEDS RFP

HEALTH HAZARD FAILED BFP TESTING

597U Chiller #1 2500 Ton Stand-By 1/14/2026 CRXLYK CDW actuator failed. (WS) Chiller #2 2500 Ton Stand-By 1/14/2026 CRXLYK CDW actuator failed. (WS) Chiller #3 2500 Ton Stand-By 1/14/2026 CRXLYK VGD fault work started, discussing project needs with inspector

Primary CHW Pump #1 Stand-By 1/14/2026 Primary CHW Pump #2 Stand-By 1/14/2026 Primary CHW Pump #3 Stand-By 1/14/2026 Primary CHW Pump #4 Stand-By 1/14/2026

Cndenser Pump #1 Out-of-Service 1/14/2026 IMP Imp for leaking seal (dh), motor bad 10-8- Condenser Pump #2 Stand-By 1/14/2026 CRL9FR Leaking seal. (WS) in comp os Condenser Pump #3 Out-of-Service 1/14/2026 Imp bad motor Condenser Pump # 4 Stand-By 1/14/2026 Secondary Pump #1 Stand-By 1/14/2026 Secondary Pump #2 Stand-By 1/14/2026 Secondayr Pump #3 Out-of-Service 1/14/2026 Offline needs new VFD (DH) Conductivity Range 1000 1/14/2026

Nitrate 520 1/14/2026

LEJEUNE (597U)

Known Backflow Preventer Issues

CHILLED WATER PLANTS

Cooling Tower #1A Stand-By 1/14/2026 bad motor Cooling Tower #1B Stand-By 1/14/2026 Cooling Tower #2A Stand-By 1/14/2026 VFD cooling fan needs replaced (WS) Cooling Tower #2B Stand-By 1/14/2026 Cooling Tower #3A Stand-By 1/14/2026 Cooling Tower #3B Stand-By 1/14/2026 COMPOS for replacement. (WS)

City Water-Make Up Meter 81567 1/14/2026 Chilled Water Make Up Meter 0 1/14/2026

Condenser Make Up Meter 97490 1/14/2026 " " SystemPSI 63 1/14/2026 " "

SUPV Controllers 1/14/2026 " "

JCI Metasys On-Line 1/14/2026 JCI PMI On-Line 1/14/2026 Siemens On-Line 1/14/2026

Chiller 1 2500 Ton Stand-By 1/14/2026 1/5/2026 Chiller 2 2500 Ton Stand-By 1/14/2026 1/5/2026 Chiller 3 2500 Ton On Line 1/14/2026 1/5/2026

Primary CHW pump 1 Stand-By 1/14/2026 1/5/2026 Primary CHW pump 2 Stand-By 1/14/2026 1/5/2026 Primary CHW pump 3 Out-of-Service 1/14/2026 1/5/2026 Primary CHW pump 4 On Line 1/14/2026 1/5/2026 Primary CHW pump 5 Stand-By 1/14/2026 1/5/2026 Condenser Pump 1 Stand-By 1/14/2026 1/5/2026 Condenser Pump 2 Stand-By 1/14/2026 1/5/2026 Condenser Pump 3 On Line 1/14/2026 1/5/2026 Condenser Pump 4 Out-of-Service 1/14/2026 1/5/2026 Condenser Pump 5 Stand-By 1/14/2026 1/5/2026

Secondary CHW Pump 1 Stand-By 1/14/2026 1/5/2026 Secondary CHW Pump 2 On Line 1/14/2026 1/5/2026 Secondary CHW Pump 3 On Line 1/14/2026 1/5/2026

Conductivity (range 900-1100) 600 1/14/2026 1/5/2026 Nitrate 520 1/14/2026 1/5/2026

Cooling Tower 1A Stand-By 1/14/2026 1/5/2026 Cooling Tower 1B Stand-By 1/14/2026 1/5/2026 Cooling Tower 2A Stand-By 1/14/2026 1/5/2026 Cooling Tower 2B Stand-By 1/14/2026 1/5/2026 Cooling Tower 3A On Line 1/14/2026 1/5/2026 Cooling Tower 3B On Line 1/14/2026 1/5/2026 Cooling Tower 4A On Line 1/14/2026 1/5/2026 Cooling Tower 4B On Line 1/14/2026 1/5/2026

Tower PM ststus Complete = Green 1/5/2026 1/14/2026 1/5/2026

Tertiary Pump 1 Stand-By 1/14/2026 1/5/2026 Teritary Pump 2 Stand-By 1/14/2026 1/5/2026 Teritary Pump 3 Stand-By 1/14/2026 1/5/2026

City make-Up Water Meter 2,598,852 1/14/2026 1/5/2026 Chill Water Meter 211 1/14/2026 1/5/2026

Comndenser Water 1,006,969 1/14/2026 1/5/2026 Pressure 64 1/14/2026 1/5/2026

Ward Hall Geo System valve 7/8/9 Closed = Campus Open 1/14/2026 1/5/2026

Valve 10 (open = Canpus/Close Geo Close 1/14/2026 1/5/2026 Geo-Pump 1(P-1) Out-of-Service 1/14/2026 1/5/2026

Geo-Pump #2 (P-2) On 1/14/2026 Condenser Pump #3 (P-3) On 1/14/2026 Condenser Pump #4 (P-4) Off 1/14/2026 Chilled Water Pump #5 (P-5) On 1/14/2026 Chilled Water Pump #6 (P-6) Off 1/14/2026

EVAP-FM(Geo-Chiller Evaporator Flow) 119.9 1/14/2026 COND-FM(Geo-Chiller Condenser Flow) 76.9 1/14/2026

Data Rack Leaving Temp. (Setpoint is 55°F) 44.70 1/14/2026 Chiller Evaporator Leaving Water Temp 41,0 1/14/2026 Chiller Evaporator Entering Water Temp 44.40 1/14/2026 `

CHLR1-FAIL-IN(Normal or Alarm) On-Line 1/14/2026 CHLR2-FAIL-IN(Normal or Alarm) On-Line 1/14/2026 CHLR3-FAIL-IN(Normal or Alarm) On-Line 1/14/2026

TRANS-SW-S(Off=Normal Power, On=EmergencOff 1/14/2026 MAN-SW-S(Off=Geo-Chiller, On-Campus) Off 1/14/2026

Effluent Flow Rate 50,475 1/14/2026 7-15-25 Old surge basin surface aerator INOP - Waiting on price for a new motor - IMP Surge Basin Level 2.57 1/14/2026 7-9-25 New surge basin #2 pump not running as effeciently as #1 pump - Pinch Valve Adjusted To 231 1/14/2026 Need to drain the surge tank and check for trash buld up where pump connects to.

Sludge Pump On-line 1/14/2026 #1 Digester On-line 1/14/2026 #2 Digester On-line 1/14/2026

108 #1 Primary Clarifier Stand-By 1/14/2026 109 #2 Primary Clarifier On-line 1/14/2026 7/24/2023 Placed Online

EMCS-BAS Servers/System 597U

RICKOVER (590A)

590A

WasteWater Treatment Plant

Pump Station #1 On-line 1/14/2026 7-14-25 - Installed new submerisible level trasnducer IMP: 3304379 Pump #1 On-line 1/14/2026 Pump #2 On-line 1/14/2026 08AUG24: Pumps #2 and #3 online with a pump around in place-RM Pump #3 On-line 1/14/2026

Pump Station #2 On-line 1/14/2026 4-24-2024 Beall cleaned out wet well #1 pump On-line 1/14/2026 #2 pump On-line 1/14/2026

Overflow Tank 5.9 @ 43.9 1/14/2026 Aux. Equipment On-line 1/14/2026 Sludge Holding Tank 1/14/2026 Sludge Holding Tank Level 4.31 1/14/2026 How many Gallons was Pumped Out 1/14/2026 Beall hauled 5200 gls from SHT 1/12/2026 How many Gallons was Decanted 0 1/14/2026 Level Pre / Post Decant 0 1/14/2026

323 #2 Air Compressor On-line 1/14/2026 MBR #1 On-line 1/14/2026

Influent Flow 20.7 1/14/2026 Wasted 1,200 1/14/2026

Aeration Zone Results: 350 1/14/2026

PH 7.1 1/14/2026

DO 2.2 1/14/2026

ATC 5,600 1/14/2026

Micro C Pump Speed 7% 1/14/2026 TMPs -1.7 1/14/2026

MBR #2 On-line 1/14/2026

Influent Flow 18.5 1/14/2026 Wasted 1,200 1/14/2026

Aeration Zone Results: 7.1 1/14/2026

PH 7 1/14/2026

DO 2 1/14/2026

ATC 5,500 1/14/2026

Micro C Pump Speed 7% 1/14/2026 TMPs -1.7 1/14/2026

Combined Effluent 1&2 7% 1/14/2026 PH 7.6 1/14/2026 PH range 6.5 - 8.5

PO4 (Phosphate) 2.5 12/30/2025 NO2+NO3 (Nitrates) N/D 12/30/2025

NH3 (Ammonia) 22 12/30/2025 DO 9.1 1/14/2026 DO greater than 5.0 PPM

PO4 (Phosphate) 0.06 1/14/2026 PO4 range less than 0.30 NO3 (Nitrates) 0.8 1/14/2026 NO3 range under 1.0

NH3 (Ammonia) 0 1/14/2026 NH3 under 1.0 Temperature 52 Deg F 1/14/2026 Effluent Water Temperature F

Monthly Effluent (gallons) - Running Total 0.75461 1/14/2026

579 Main Vision 21 System (Main SCADA On-line

370 Hubbard Hall On-line 326 50 Rogers Road On-line 3/15/2024 tbd IMP 1662809 bearings on both pumps sound bad and causing a vibration in pumps. wrote up compos to have rebuilt or replaced.

287 Hospital Point Bathhouse On-line

105 Carter Hall On-line 9/4/2025 PM 3234510 RFP TO BE SENT 1/6 DG 04SEPT25: Lift Sttaion can't run in auto-RM; 14JUL25: Found failed starter for pump #1, new started was ordered by DJ on 14JUL25. BP. found most of the wires underground have failed and one of the pumps failed. have statoin running on 1 foat and 1 pump. BP

572 Michelson/Chauvenet Hall On-line 572 Michelson/Chauvenet Hall On-line 572 Michelson/Chauvenet Hall On-line 572 Michelson/Chauvenet Hall On-line 590 Rickover Hall On-line 5/9/2023 Sewage alarm radio is offline 5.9 compos submitted, radio requires rebuild 601 Robert Crown Sailing Center (SSP-8) On-line 601 Robert Crown Sailing Center (SSP-8A) On-line 150 Glenn Warnter Soccer Center On-line 145 Cutter Shed On-line 685 Farragut Field On-line 614 Ingram Field On-line 250 Old Medical Clinic On-line

640 Hopper Hall On-line

880 Larson Hall On-line 2976428/sr33678476 found pump #2 motor has failed will need to pull and order new one. pump #1 is RFP TO BE SENT 1/6 DG

645 Bishop Stadium On-line

North Severn Sanitary Lift Stations

NA103 Hooper Highland Road (by Marina) On-line 5/16/2023 WO: 605844

Sewage alarm radio failed to send signals to CHP during monthly inspection, requires rebuild compos sent 5/12/23

106NS Railway (near 82NS) On-line 5/16/2024 NA695APS Navy Medical Health Clinic On-line

234NS Hangar On-line 66NS Small Craft On-line 131NS Hobby Shops On-line

Sanitary Lift Stations USNA Sanitary Lift Stations

MBR #1

MBR #2

114NS Influent

MBR #1 & 2

297NS CBU 403 (behind 297NS) On-line 336NS Flammable Liquid Storage On-line 89NS Rec Bldg. On-line 12/3/2025 WO: CSJSJN FOUND PUMP LOCKED UP DG 334NS YP Bilge Pump On-line NA686 Restroom 12th Tee On-line NA140 Mill Creek Marina On-line 803NS Recycling Bldg. On-line 114NS WWTP-Pump House 1 On-line 289NS WWTP-Pump House 2 On-line 235NS MAREXP SECRON 12 DET C On-Line

326NS WWTP-Surge Basin On-line 1/17/2024 PM: 1373662 communication with T-rex restored, LOCAL ALARM NOT FUNCTIONAL,ordering parts to repair

330NS Campground On-line Sanitary Manholes - ALARM ONLY - NO PUMPS Badger Road (AH9.1S) On-line Badger Road (AG11.1S) On-line

NA76 Golf Course On-line 11/28/2023 Not communicating with T-rex, under investigation

36 upsher sewer main has root intrusion on-line 8/4/2025 3417389 /CSCD7M 3AUG25 after hours call was put in for sewer 3 porter sewer main has root intrusion on-line 12/18/2024 2564351/CP73JX/3207977 18DEC24 cabled and ran camera down sewer 354NS Youth Center On-line 6/1/2024 062624: Greg Currence has the SOW for action- Line has two holes. Needs to be repaired-BP;

USNA-320 MWR BATH HOUSE SOUTH POOL On-line 6/1/2024 vjfs 1952577 gov sr# 24197883 062624: Greg Currence has the SOW for action- found drop man hole IVO of md 450 has root intrusion. the man hole can not be located with USNA- IVO carter hall 6" sewer main has root intrusion on-line 8/14/2024 vjfs#2157810 GOV# CNH7YT 14AUG24: found 6" terracotta sewer line has

4/2 porter road root intrusion on-line 11/19/2024 VJFS# 2496728 19NOV24 found root intrustion 20'-30' from clean 44 upsher root intrusion on-line 11/120/2024 VJFS# 2516961 20NOV24 found root intrustion from new clean USNA-SS 31/32 UPSHUR On-line 6/12/2024 VJFS 1952221 GOV CMYH63 062624: Greg Currence has the SOW for action- found about 30-40 feet of terracotta drain line had root intrustion at every joint. at about 80-90 feet

Medium Voltage Main Substations/Feeders Main Feeder - 64 Normal - Closed 1/13/2026 Main Feeder - 67 Normal - Closed 1/13/2026 Tie Breaker Normal - Open 1/13/2026 W20A Normal - Closed 1/13/2026 18MAR24: W20A is LOTO'd for W20B repairs-RM.

D5 Normal - Closed 1/13/2026 W13A Normal - Closed 1/13/2026 W10 Normal - Closed 1/13/2026 W20B Out of Service 6/16/2023 No redundancy at CHWP 597U 20JUN23: Feeder W4A loop could be used if needed to support CHWP 597U. Urgent SC W13B Normal - Closed 1/13/2026 W9 Normal - Closed 1/13/2026

Main Feeder - 35 Normal - Closed 1/13/2026 AC unit # 3 found not working, HVAC is submitting FWO (GC 6/24) Main Feeder - 36 Normal - Closed 1/13/2026 Tie Breaker Normal - Open 1/13/2026 W64A Normal - Closed 1/13/2026 W64B Normal - Closed 1/13/2026 W64C Normal - Closed 1/13/2026 W64D Stand-By 1/13/2026 W68A Normal - Closed 1/13/2026 W69B Normal - Closed 1/13/2026 W68C Normal - Closed 1/13/2026 W68D Stand-By 1/13/2026 W68E Normal - Closed 1/13/2026 SPARE Stand-By 1/13/2026 SPARE Stand-By 1/13/2026

Main Feeder - W13A Normal - Closed 1/13/2026 Main Feeder - W13B Normal - Closed 1/13/2026 Tie Breaker Normal - Open 1/13/2026 W1 Normal - Closed 1/13/2026 W3 Normal - Closed 1/13/2026 W5 Normal - Closed 1/13/2026 W7A Normal - Closed 1/13/2026 W11 Normal - Closed 1/13/2026 FL1 Normal - Closed 1/13/2026 HH1 Normal - Closed 1/13/2026 TS-103 Normal - Closed 1/13/2026 SPARE Stand-By 1/13/2026 W2 Normal - Closed 1/13/2026 W4 Normal - Closed 1/13/2026 W6 Normal - Closed 1/13/2026 W8A Normal - Closed 1/13/2026 FL2 Normal - Closed 1/13/2026 HH2 Normal - Closed 1/13/2026 SPARE Stand-By 1/13/2026

CHWP 597U Feeder W20B Out of Service 6/16/2023 5/31/24 No redundancy at CHWP 597U 20JUN23: Feeder W4A loop could be used if needed to support CHWP 597U. Urgent SC

W20B Main Breaker Abnormal - In Operation 3/18/2024 FY24

Known Sanitary Main and/or Sanitary Lateral Issues

13C-1

KINKAID

13C-2

Feeders that are OOC or have known issues:

Medium Voltage Equipment (Transformers-TS and Switches-PS) that are OOC or have known issues:

Preble TS-139 Abnormal - In Operation 5/14/2025 FY25

11APR25: Awaiting proposal for testing and minor repairs, Preble is being powered by a portable generator--RM;

105 Building 105, Maury Hall Ready for Operation 1/13/2026 PM completed 7/30/24 106 Building 106, Mahan Hall/Telephone

Office Ready for Operation 1/13/2026 PM Complete 7/30/24 187 Printing Plant Ready for Operation 1/13/2026 PM complete 7/31/24 257 Building 257, Safety Ready for Operation 1/13/2026 Unit smokes when starting, Need WO and need to call cummings PM COMPLETE 8/1/24 274 Building #274, Hospital Clinic Ready for Operation 1/13/2026 PM COMPLETE 8/1/24 275 Building #275, Hospital (Server Room) Ready for Operation 1/13/2026 PM COMPLETE 7/8/24 290 Building 290, Ward hall Ready for Operation 1/13/2026 Fuel Level: 20%

PM COMPLETE 10/25/23326 Building 326, Sewage Pump, Dorsey Creek Ready for Operation 1/13/2026 PM COMPLETE 10/17/23

370 Building 370, Hubbard Hall Ready for Operation 1/13/2026 PM COMPLETE 10/16/23 446 Building 446, USNA Fire Station Ready for Operation 1/13/2026 Small coolant leak on reserve bottle. Looking PM COMPLETE 7/24/24 579 Building 579, Central Heating Plant Ready for Operation 1/13/2026 PM COMPLETE 10/18/23 590 Substation 13C-2 (Hopper, Rickover &

Nimitz) Ready for Operation 1/13/2026 Kelly Generator completed the May generator PMs 591 Building 591, Water Treatment Plant Ready for Operation 1/13/2026 PM COMPLETE 10/19/23 591 Building 591, Water Treatment Plant

(Centrifuge System) Ready for Operation 1/13/2026 PM COMPLETE 10/19/23 628 Building 628, LeJeune Hall Ready for Operation 1/13/2026 Fuel Level 65% 675 Building 675, Alumni Hall Ready for Operation 1/13/2026 PM COMPLETE 10/20/23 1013 Building 1013, Bancroft Hall, Wing 3 Ready for Operation 1/13/2026 PM COMPLETE 7/29/24 1014 Building 1014, Bancroft hall, Wing 4 Ready for Operation 1/13/2026 PM COMPLETE 7/29/24 1017 Building 1017, 7th Wing Ready for Operation 1/13/2026 PM COMPLETE 10/27/23 1018 Building 1018 Bancroft Hall, Wing 8 Ready for Operation 1/13/2026 PM COMPLETE 7/29/24

1014K King Hall, 1014K, Bancroft Hall Ready for Operation 1/13/2026 Kelly Generator completed the May generator PMs 7/31/24 58NS NSA Annapolis ADMIN 58NS Ready for Operation 1/13/2026 Kelly Generator completed the May generator PMs 8/2/24 106NS Building 106NS, Railway Sewage Pump Ready for Operation 1/13/2026 PM COMPLETE 10/3/23 107NS Building 107NS @ WWTP Ready for Operation 1/13/2026 PM COMPLETE 10/2/23 130RL 130RL, NS Water Tower Ready for Operation 1/13/2026 PM COMPLETE 7/31/24 167RL Building 167RL, David Taylor, Telephone

Equipment Ready for Operation 1/13/2026 PM COMPLETE 10/3/23 297NS New CDC Out of Service 1/13/2026 12JAN26: This genertaor is making a mechanical noise that needs to be Fuel Level: 48% PM COMPLETE 10/4/23298NS CDC Ready for Operation 1/13/2026 PM COMPLETE 10/5/23

46NS Building 46NS, BEQ Ready for Operation 1/13/2026 Kelly Generator completed the May generator PMs 572A Building 572A, Chauvenet Hall Ready for Operation 1/13/2026 PM COMPLETE 10/18/23 572B Building 572B, Michelson Hall Ready for Operation 1/13/2026 PM COMPLETE 10/25/23

NA103 NA103, Greenbury Point, Sewage Lift Station Ready for Operation 1/13/2026 Kelly Generator completed the May generator PMs

NA687 Brigade Sports Complex Ready for Operation 1/13/2026 Fuel Level: 90%

PM COMPLETE 10/31/23

NA342 NA342 Naval Station Fire Station Ready for Operation 1/13/2026 Ryan changed the spring in the oil pump, CuKelly Generator completed the May generator PMs NA908 New Hospital (NHCL) Lift Station Ready for Operation 1/13/2026 PM COMPLETE 10/24/23

# Portable Generators: Portable Generator Status: Action Date ETR Maximo # Current Location: Remarks IDIQ Remarks

P-4 Portable Generator: 125KW Ready for Operation 1/13/2026 Perry Center Kelly Generator completed the May generator PMs 7/24/24 14MAY25: Repairs went COMPOS-RM P-5 Portable Generator: 147KW Out of Service 1/8/2026 Perry Center Kelly Generator completed the May generator PM 7/24/24 14MAY25: Repairs went COMPOS-RM P-6 Portable Generator: 45KW Ready for Operation 1/13/2026 Perry Center Kelly Generator completed the May generator PMs 7/19/24 P-7 Portable Generator: 70KW Ready for Operation 1/13/2026 Perry Center Kelly Generator completed the May generator PMs 7/22/24

Badgers and Sellers Gas Meter On-line 1/13/2026 Gate 4 Gas Meter On-line 1/13/2026 Gate 2 Gas Meter On-line 1/13/2026 6 Porter Gas Meter On-line 1/13/2026 Kinkaid Road Gas Meter On-line 1/13/2026

NA 11/12/2025

GWSF Propane Farm: 65% 01/05/2026 Recycling Center: 40% 01/08/2026

Boiler 1 On-line 1/13/2026

Boiler 2 On-line 1/13/2026 Domestic Hot Water Heater #1 On-line 1/13/2026 Domestic Hot Water Heater #2 On-line 1/13/2026

AUX Equipment On-line 1/13/2026

Domestic Hot Water Heater #1 On-line 1/13/2026 Domestic Hot Water Heater #2 On-line 1/13/2026 Hot Water Boiler On-line 1/13/2026 Running just waiting for JCI & Boiler OP's Chiller, 1st Stage Off-Line for Winter 10/20/2025 Compressor replaced in 8/2023 Chiller, 2nd Stage Off-Line for Winter 10/20/2025

Condenser Pump #10 for cooling towers On-line 10/12/2025 currently LOTO valve P10 reported leaking, IMP created, VJFS investigating Chiller #1 repairs 8/4/2023

Natural Gas System

Known Natural Gas Issues

Propane Readings (Taken Biweekly: Beau Nickerson/Dan Garner)

NORTH SEVERN ANNEX FACILITIES

46NS B.E.Q.

Emergency Electrical Generators

NA695

46 NS

47NS B.E.Q.

47 NS

NAVAL STATION HOSPITAL CLINIC - Building NA695

234 NS Steam Boiler #1 On-line 1/13/2026

234 NS Steam Boiler #2 On-line 1/13/2026 Blower motor capacitor bad, put a temporary capacitor on the blower motor Waiting Boiler OP's test, combustion linkage needs to be adjusted.

234 NS Hot Water Boiler #3 On-line 1/13/2026

339 NS Steam Boiler #1 On-line 1/13/2026 12/24/2025

339 NS Steam Boiler #2 On-line 1/13/2026

BANCROFT HALL

DHW #1 (Dual Operations) On-line HTHW 1/13/2026 Monthly Change Over 12/24/2025 DHW #2 (Dual Operations) On-line HTHW 1/13/2026 Monthly Change Over 12/24/2025 DHW #3 (Dual Operations) Stand-By 1/13/2026 Monthly Change Over 12/24/2025 Converter #1 (Dual Operations) Stand-By 1/13/2026 Monthly Change Over 12/24/2025 Converter #2 (Dual Operations) On-line 1/13/2026 Monthly Change Over 12/24/2025 Steam Generator # 8 Stand-By 1/13/2026 P8000-2 Steam Controller is calibrated; Generator 8 to be used only in emergency, bundle leaks 2/27/2024 Sulfite (range 30-60) Stand-By 1/13/2026 Conductivity, neutralized Stand-By 1/13/2026 Softener (Hard/Soft) Stand-By 1/13/2026 Heating Water Pump #1 Stand-By 1/13/2026 Heating Water Pump #2 On-line 1/13/2026 Dual Temp Pump #1 On-line 1/13/2026 Dual Temp Pump #2 Stand-By 1/13/2026

DHWH #1 (Dual Operations) Stand-By 1/13/2026 Monthly Change Over 12/24/2025

DHWH #2 (Dual Operations) Stand-By 1/13/2026 DHWH #3 (Dual Operations) On-line HTHW 1/13/2026 Monthly Change Over 12/24/2025 Converter #1 Stand-By 1/13/2026 Monthly Change Over 12/24/2025 Converter #2 On-line 1/13/2026 Monthly Change Over 12/24/2025 Steam Generator #9 On-line 1/13/2026 EASI scheduling install, tentative week of jan 22, 2023 Sulfite (range 30_60) 40 1/13/2026 Conductivity, neutralized 2632 1/13/2026 Steam Generator #10 On-line 1/13/2026 IQ: CL6NF6 EASI scheduling install, tentative week of jan 22, 2023 Sulfite (range 20-60) 40 1/13/2026 Conductivity, neutralized 2313 1/13/2026 Softener (Hard/Soft) Soft 1/13/2026 Operating normal on new softner Aux. Equipment On-line 1/13/2026 Dual Temp Pump #1 On-line 1/13/2026 Dual Temp Pump #2 Stand-By 1/13/2026

DHWH #1 Out of Service 1/12/2026 For Service 1/8/2026 DHWH #2 On-line 1/13/2026 6/15/2024 DHWH #3 (Dual Operations) On-line 1/13/2026 DHWH #4 (Dual Operations) Out of Service 12/24/2025 CJJX49 Converter #1 Out of Service 12/24/2025 FWO submitted 12/24/2025 Converter #2 On-line / HTHW 1/13/2026 Aux. Equipment: Chilled Water Pump On-line 1/13/2026 3/5/2024 Dual Temp Pump #1 On-line 1/13/2026 Dual Temp Pump #2 Stand-By 1/13/2026

Steam Converter #1 On-line 1/13/2026 TBD

DHWH #4 (Dual Operations) On-line 1/13/2026 DHWH #5 (Dual Operations) Stand-By 1/13/2026 Monthly Change Over 2/13/2025 - 3/28/2025 Secured Supply,Return HTHW Valves Converter #1 (Dual Operations) On-line 1/13/2026 Converter #2 (Dual Operations) Out of Service 3/25/2025 3/25/2025 Secured , unit hads head leak.

Condensate Recovery Tank Stand-By 1/13/2026 Softener (Hard/Soft) Stand-By 1/13/2026

101-1

101-2

SMALLCRAFT REPAIR FACILITY

WING 1

WING 2

WING 3

101-3

KING HALL

101-K

CENTER SECTION

101-C

AUX EQUIPMENT On-line 1/13/2026

Converter On-line 1/13/2026 Aux. Equipment Stand-By 1/13/2026

DHWH #1 (Dual Operations) Stand-By 1/13/2026 Control Valve Repair LOTO# 1959 DHWH #2 (Dual Operations) On-line 1/13/2026 Repair Outage 11/27/2025 DHWH #3 (Dual Operations) Out of Service 12/20/2025 Monthly Change Over 5/15//2024 , Placed OOS tube bundle leak, tube bundle send back Converter #1 (Dual Operations) Stand-By 1/13/2026 Monthly Change Over 12/24/2025 Converter #2 (Dual Operations) On-line 1/13/2026 Monthly Change Over 12/24/2025 Dual Temp Pump #1 Stand-By 1/13/2026 5/17/2024 Dual Temp Pump #2 On-line 1/13/2026 Chilled Water Pumps On-line 1/13/2026 Heating Water Pump # 3 On Line 1/13/2026 3/5/2024

HTG Pump #4 Stand-By 1/13/2026 TBD 23463535 Needs new starter motor. WC 11/7/23. 8/27/2024 Need New Transformer. Transformer On Order

Key Equipment that is OOC:

AHU #3 On-line 4/4/2025 TBD Unit is running Mod hub is down.

DHWH #1 (Dual Operations) On-line HTHW 1/13/2026 DHWH #2 (Dual Operations) On-line HTHW

1/13/2026

12/9/2025. Placed On-line. HTHW Operation.

DHWH #3 (Dual Operations) Out of Service 1/12/2026 12/22/2025

3/28/2025 Secured Suppy and Return HTHW, suspect tube leak. removed head in preperation for tube inspection LO/TO #1875

Converter #1 (Dual Operations) On-line 1/13/2026 Monthly Change Over 12/23/2025 Converter #2 (Dual Operations) Stand-By 1/13/2026 Monthly Change Over 12/23/2025 Dual Temp Pump #1 Stand-By 1/13/2026 Dual Temp Pump #2 On-line 1/13/2026 Aux. Equipment: Chilled Water Pump On-line 1/13/2026 P-5 is now on year round per. PWD 4/6/22

DHWH #1 (Dual Operations) Stand-By 1/13/2026 Monthly Change Over 12/24/2025 DHWH #2 (Dual Operations) On-line 1/13/2026 Monthly Change Over 12/24/2025 Converter #1 (Dual Operations) Stand-By 1/13/2026 Monthly Change Over 12/24/2025 Converter #2 (Dual Operations) On-line 1/13/2026 Monthly Change Over 12/24/2025 Dual Temp Pump #1 On-line 1/13/2026 Dual Temp Pump #2 Stand-By 1/13/2026 Aux. Equipment: On-line 1/13/2026

DHWH #1 Out of Service 11/17/2025 VJFS2828466/GOVU1321FEB2025 VJFS2832030/ GOV30491687DHWH #2 On-line HTHW 1/13/2026 Monthly Change Over 9/30/2025

DHWH #3 (Dual Operations) On-line 1/13/2026 DHWH #4 (Dual Operations) Out of Service 11/17/2025 Swich From Steam To HTHW 11/17/2025 Converter #1 On-line 1/13/2026 Converter #2 Stand-By 1/13/2026 Aux. Equipment On-line 1/13/2026 Dual Temp Pump 1 On-line 1/13/2026 3/1/24 IQ: CLKHJF 1.22 work funded for in house, ordering material Dual Temp Pump 2 Stand-By 1/13/2026 7/5/24 IQ: CLLNFB 1.22 work funded for in house, ordering material

DHWH #1 Out of Service 12/26/2025 FWO Submitted 12/26/2025 DHWH #2 On-line HTHW 1/13/2026 Monthly Change Over 11/14/2025 DHWH #3 (Dual Operations) Stand-By 1/13/2026 Monthly Change Over 11/14/2025 DHWH #4 (Dual Operations) Out of Service 12/24/2025 12/16/2024 1/9/2024 Major- No redundancy for hthw or steam 05OCT21: Repair was funded to IAP at the end of their contract, but they turned the IQ RFP to replace #4 moved to FY24/Q1 and will need to be revisited Converter #1 Out of Service 12/24/2025 9/24/2025 1/8/2024 Impacts heating in Wing 8 12/9 #1 converter HTHW strainer leak LOTO W.O. Submitted.

Converter #2 On-line HTHW 1/13/2026 Online 11/14/2025

Aux. Equipment On-line 1/13/2026 Dual Temp Pump 1 Stand-By 1/13/2026 Dual Temp Pump 2 On-line 1/13/2026 9/5/23

Converter #1 Stand-By 1/13/2026 Monthly Change Over 12/26/2025 Converter #2 On-line 1/13/2026 Monthly Change Over 12/26/2025 Electric Reheat Boiler Off-Line for Summer 1/7/2026 Feeder W-6 On-line 1/13/2026 AHU 1 Out of Service 7/19/2025 WO1546624 Bad drive

102 Pool Converter Out of Service 5/8/2025 Removed during construction (LOTO #1506 HTHW)

DHWH # 1A Stand-By 1/13/2026 DHWH # 1B On-line 1/13/2026

MACDONOUGH

NORMAN SCOTT

MITCHER HALL - LEVY CENTER

WING 4

WING 5

WING 6

WING 7

WING 8

ACADEMIC / SUPPORT FACILITIES

MAHAN HALL

101-M

101-4

101-5

101-6

101-7

101-8

Heating Converter # 1A Stand-By 1/13/2026 Monthly Change Over 12/23/2025 Heating Converter # 1B On-line 1/13/2026 Monthly Change Over 12/23/2025 Pool Converter # 2A Stand-By 1/13/2026 Monthly Change Over 12/23/2025 Pool Converter # 2B On-line 1/13/2026 Monthly Change Over 12/23/2025

12/14/2025

12/14/2025

12/14/2025

Steam humidifier On-line 1/13/2026 Online for season 11/14/025 Softener PH 8.2 1/13/2026 Online for season 11/14/025 Softener conductivity 186.1 1/13/2026 Online for season 11/14/025 Softener (Hard/Soft) Soft 1/13/2026 Online for season 11/14/025 Converter #1 On-line 1/13/2026 SR23310659 proposal being sent 9.29 Converter #2 Out of Service 4/7/2025 LOTO #1812. Out Of Service For Repair. 9/4/2024 ESV bad packing leak, not rotating Converter #3 On-line 1/13/2026 Online for season 11/14/025 Electric Reheat boiler Out of Service 7/21/2025 Out Of Service For Inspection 7/21/2025 Gas Fired Reheat Boiler off -line 5/29/2025 Vcc 1 Chiller (Circuit A) Out-of-Service 5/5/2025 Waiting on RFP Moderate - With temps at lower levels Vcc 2 will be able to handle cooling requirements Vcc 1 chiller circuit A down known leak went compos for repair. Waiting on RFP

DHWH G-1 (Natural Gas Fired) On-line 1/13/2026 Inspection DHWH G-2 (Natural Gas Fired) On-line 1/13/2026 Recirc Pump And Flow switch Replaced 7/24/2025 Emergency DHWH (HTHW)

Out-of-Service 5/5/2025

Minimal - Unit is isolated from DHW system

- Unit removed 3161 lock are in place

Converter On-line 1/13/2026 Online for winter 11/10/2025

(2) Electric DHW Heaters Stand-by 1/13/2026 Aux. Equipment On-line 1/13/2026 Dual Temp Pump 1 Stand-by 1/13/2026 Dual Temp Pump 2 Stand-By 1/13/2026

DHW #1 On-line 1/13/2026 DHW #2 Non-Potable On-line 1/13/2026 2559790/ CP6KWV Converter #1 (Dual Operations) Out-of-Service 9/25/2025 CJNVWD SR23445565 Head Gasket Leak - LOTO #1653 RFP rcvd IDIQ to replace head gaskets sent 11/8, waiting funding Converter #2 (Dual Operations) On-line HTHW 1/13/2026 Laboratory Steam Generator Out-of-Service 2/28/2025 LO/TO #1853 for inspection Aux. Equipment On-line 1/13/2026 Motor Control Centers (MCC) On-line 1/13/2026

Converter On-line 1/13/2026 Electric water heater Stand-by 1/13/2026 Electric Reheat Boiler off -line 11/3/2025 AHU #7 Out-of-Service Bad shaft. Ordering parts from Trane

Converter #1 Stand-By 1/13/2026

Monthly Change Over 12/26/2025

Converter #2 On-line 1/13/2026 Monthly Change Over 12/26/2025 Gas Re-Heat Boiler 3rd Floor M.R. Stand-By 1/13/2026 New temperature sensors need to be Air Compressor #1 Out-of-Service 5/8/2025 18MAR24: Oil Leak, we are checking into the PM records-RM Air Compressor #2 On-line 1/13/2026 18MAR24: Mechanically limping along, we are checking into the PM records-RM

Converter On-line 1/13/2026 Electric Boiler Stand-By 1/13/2026 Aux. Equipment Stand-By 1/13/2026

DHWH #1 Stand-By 1/13/2026 Monthly Change Over 12/23/2025 HTHW control vlave work funded, ordering material DHWH #2 On-line

1/13/2026

Monthly Change Over 12/23/2025 HTHW control vlave work funded, ordering material

Electric Domestic Water Heater On-line 1/13/2026 Converter #1 Stand-By 1/13/2026 Monthly Change Over 12/30/2025 Converter #2 On-line 1/13/2026 Monthly Change Over 12/30/2025 Electric Boiler Stand-By 1/13/2026

#1 Converter On-line 1/13/2026 Online for Season.

#2 Converter Stand-By 1/13/2026 Off for Summer 4/4/25

Steam Reducing Station On-line 1/13/2026

Condensation line On-line 1/13/2026 11/3/23 23454827

A 12' section of pipe was removed and replaced due to Deterioration. This was replaced on 11/3/23.

RICKOVER HALL G49

ALUMNI HALL

WESLEY BROWN FIELD HOUSE

HOSPITAL CLINIC - Building 253

LEJEUNE HALL

PREBLE HALL

HALSEY FIELD HOUSE

RICKETTS HALL

MICHELSON HALL

NIMITZ LIBRARY

Chiller #4 Stand-By

12/28/2025 Per cooling transition meeting, 1 circuit needs repair. (WS)

LEJEUNE HALL HEATING EQUIP. Stand-By 1/13/2026 Domestic Hot Water #1 Stand-By 1/13/2026 Monthly Change Over 12/30/2025

Domestic Hot Water #2 On-Line 1/13/2026 Monthly Change Over 12/30/2025

Electric DHWH #1 Stand-By 1/13/2026 Electric DHWH #2 Stand-By 1/13/2026 Converter #1 On-line 1/13/2026 10/19/2025 Online 10/15/2025

Converter #2 On-line 1/13/2026 Online for Season

Converter #3 On-line 1/13/2026 Converter #4 Lap Pool On-line

1/13/2026

Converter #5 Dive Pool On-line 1/13/2026 IQ: CKRKDJ

Electric Boiler B-1 Dive Pool Stand-By 1/13/2026 Electric Boiler B-2 Lap Pool Stand-By 1/13/2026

Converter Out-of-Service 4/18/2024 O/S Bldg. Rehab / Equipment LO/TO #1765

Boiler #1 On-line 1/13/2026 SR23438334 Boiler #2 On-line 1/13/2026 Boiler #3 On-line 1/13/2026 Auxillary Equipment On-line 1/13/2026

Gas DHWH #1 On-line 1/13/2026 Gas DHWH #2 On-line 1/13/2026 Storage Tank #1 On-line 1/13/2026 Storage Tank #2 On-line 1/13/2026 Placed back in service. RH

Converter Stand-By 1/13/2026

Chiller: On-line 8/15/2024 System 1, Compressor 1 On-line 8/15/2024 System 1, Compressor 2 On-line 8/15/2024 System 1, Compressor 3 On-line 8/15/2024 System 2, Compressor 1 On-line 8/15/2024 System 2, Compressor 2 Out-of-Service TBD System 2, Compressor 3 Out-of-Service TBD

101-1 Bancroft Hall, exterior lift Out-of-Service 1/3/2024 1/15/24 IQ: CKZ9N3 work starting approx 1.8, one week to complete 101-3 Bancroft Hall, Wing 3: Passenger Out-of-Service 8/4/2023 10/31/23 IQ: CKLDH4 Elevator Upgrade Modification mod funded, vendor notified 101-7 Bancroft Hall, Wing 7: Handicap Lift Out-of-Service 4/5/2021 TBD Replacement to be scheduled 101-8 Bancroft Hall, Wing 8: Handicap Lift Out-of-Service 4/5/2021 TBD Replacement to be scheduled 105 Maury Hall: Passenger Out-of-Service 4/5/2021 TBD Construction Contractor Use Only 589 Nimitz Library: Passenger #1 Out-of-Service 4/5/2021 TBD Construction Contractor Use Only 590 Rickover Hall: Passenger #2 On-line 7/6/2023 6/30/23 Temp cert issued elevator in service, waiting final material to complete 675 Alumni Hall: Freight Out-of-Service 4/5/2021 06/04/21 Elevator Upgrade Modification 181 Halligan Hall: Handicap Lift Out-of-Service 5/17/2021 TBD WO# CFM6CC Lift requires the control board to be replaced. FWO requested 5/07/2021

675 Alumni Hall On-line 3/2/2025 3/2/25 04MAR245: Power supply failed-RM;

NA140 Mill Creek Pier (Possum Point) Out-of-Service 10/2/2024 12/31/24 10.2.24 project starting 10.4.24; Elliott H/Dexter managing 339NS Paint & Blasting Shop Out-of-Service 6/30/2023 TBD compOS: 550790 fire panel OOS, needs full replacement engineered as old system is no longer supported COMPOS sent PWD

276 PHYSICAL EDUCATION BUILDING Out-of-Service 1/24/2023 TBD fire panel OOS, needs full replacement engineered as old system is no longer supported needs to be re-engineered by PWD, system is not up to code

250 Old Naval Health Clinic Out-of-Service

4/5/2023 TBD 4.4.23 per LT Hunter, PMEB has commissioned new system--work to start in June 2023

Went down years ago-needs replacement building being rehabed by Navy subk starting 2023

NA298 Bachelors Enlisted Quarters Out-of-Service

4/5/2023 FY26

Went down years ago - directed to turn off by PWD: 17SEPT24: Demo slated in FY26-RM

101-K (rm C118) Galley Cook and Chill Hood System Out-of-Service

10/17/2023 11/17/23 SR22879540 Hoods 1, 2 3 & 4 did not pass PM inspection RFP rcvd IDIQ, Fireline to be here Nov 7-8/2023

321NS Old NEX Out-of-Service 4/5/2023 04/21/23 SR22649485 Fire panel needs replacement compos sent 3.31, pending IQ proposal

HOPPER HALL

HUBBARD HALL

LEAHY HALL

Ward Hall

BEACH HALL / USNI

VTE OUTAGES

Fire Alarm System Outages (systems that are OOC)

329NS NEX/Retail Out-of-Service

3/6/2023

3.2.23 per ACQ, will be part of larger project

FA failing, needs replacement

260 HUBBARD HALL: Row tank on-line 12/6/2024 151 WESLEY BROWN FIELDHOUSE cold plunge p on-line 9/9/2021 628 Lejeune Hall: Lap Pool On-line 9/9/2021 628 Lejeune Hall: Dive Pool on-line 12/27/2024

114 Norm Scott Pool: Polo Pool

On-line

8/29/2024

320A South Seven: Main Pool Off-line 8/8/2024 winterized 15OCT25 320B South Severn; Kidney Pool Off-line 8/8/2024 winterized 15OCT25 321 South Severn: Wading Pool Off-line 8/8/2024 3419806/ SR-080425-10:32-BH winterized 15OCT25, still waitng on new board for pool pump

160NS North Severn: Main Pool Off-line 8/8/2024 . winterized 15OCT25 160ANS North Severn: Wading Pool Off-line 8/8/2024 winterized 15OCT25

739 Radford Terrace Fountaim Off-line 8/8/2024 tbd CN4CYW/CN3VH6 taken off line to pressure test overflows and inspect for leaks,found both will overflows Alumni Fountain Off-line 8/8/2024 TBD 1763629/ CMHMXJ 22APR24: working on tempoarry solution for graduation and special events along with a permanent Lejeune Fountain Off-line 10/18/2024 winterized AK 11/12/25 Mitcher/Levy Fountian Off-line 8/8/2024 winterized BP 11/26/25

Worden Field Off-line 9/4/2025 Winterized 11/10/25 BP Stribling Off-line 9/4/2025 winterized BP 11/26/25 BP Lejeune Off-line 9/4/2025 winterized 11/12/25 BP Leahy Off-line 9/4/2025 vjfs# 3783107 SR# SR-111025-13:24-BH Placed in operation BP 4/2/25, isolation valve handel bent and will not turn off, will need to dig up and Farragut Field (Rip Miller Side) off-line 9/4/2025 winterized 11/26/25 BP Farragut Field (RCSC Side) Off-line 9/4/2025 winterized BP 11/12/25 Ingram Track Off-line 9/4/2025 winterized 11/12/25 BP Dewey (GWSF) Off-line 9/4/2025 winterized 11/12/25 BP Dewey (Practice 1) Off-line 9/4/2025 winterized 11/12/25 BP Dewey (Practice 2, IVO 13C-2) Off-line 9/4/2025 winterized 11/25/25 Sherman Field Off-line 9/4/2025 winterized 11/12/25 BP Halsey FH Off-line 9/4/2025 winterized 11/12/25 BP Old NHC right of circle Off-line 9/4/2025 winterized 11/12/25 BP Old NHC left of circle Off-line 9/4/2025 winterized 11/12/25 BP Larson Off-line 9/4/2025 winterized 11/12/25 BP Nimitz terrace deck Off-line 9/4/2025 winterized 11/12/25 BP Rickover terrace deck Off-line 9/4/2025 winterized 11/12/25 BP carter terrace deck Off-line 9/4/2025 winterized 11/12/25 BP Chapel Off-line 9/4/2025 winterized 11/10/25 BP sampson Off-line 9/4/2025 winterized 11/10/25 BP alumni Off-line 9/4/2025 winterized 11/10/25 BP smoke park wing 5 Off-line 9/4/2025 winterized 11/12/25 BP smoke park wing 6 Off-line 9/4/2025 winterized 11/12/25 BP Rickets off-line 9/4/2025 winterized 11/12/25 BP Hopper 1 lower off-line 9/4/2025 winterized 11/12/25 BP Hopper 2 upper off-line 9/4/2025 winterized 11/12/25 BP Gate 1 Off-line 9/4/2025 winterized 11/12/25 BP alumni drinking fountian college ceek side off-line 9/4/2025 winterized 11/12/25 BP worden field drinking fountian Off-line 9/4/2025 winterized 11/10/25 BP ward hall Off-line 9/4/2025 winterized 11/26/25 BP soft ball field Off-line 9/4/2025 winterized 11/10/25 BP drinking fountion by prebel Off-line 9/4/2025 winterized 11/10/25 BP

Navy Lodge Off-line 9/4/2025 winterized 11/24/25 NHC Off-line 9/4/2025 winterized 11/24/25 Golf Shop at BSC Off-line 9/4/2025 winterized 11/14/25 BP Rugby Field BSC Off-line 9/4/2025 winterized 11/14/25 BP rugby field driving range Off-line 9/4/2025 winterized 11/14/25 BP MWR soft ball field by pool Off-line 9/4/2025 winterized 11/14/25 BP NEX Off-line 9/4/2025 Winterized 11/24/25 MWR soft ball field retelle room Off-line 9/4/2025 winterized 11/14/25 BP

Bishop stadium Off-line 9/4/2025 winterized 11/26/25 BP Worden field bath house Off-line 9/4/2025 winterized 11/26/25 BP Ingram Track bath house Off-line 9/4/2025 winterized 11/26/25 BP South Serven Pool Bath Hosue Off-line 9/4/2025 winterized 11/24/25 Drinking Fountians between Alumni and CarterOff-line 9/4/2025 wintrerized BP 11/10/25 Santee Basin Off-line 9/4/2025 3867473/CSJMXN 11/28/25 drained system, need to wait for antifreeze to come in to fill cht system.

Drinking Fountian Worden field off-line 9/4/2025 wintrerized BP 11/10/25

North ServernPpool Bath House Off-line 9/4/2025 Winterized 11/24/25 Retelle Room Off-line 9/4/2025 Winterized 11/24/25 YP Seawall Dock Off-line 9/4/2025 Winterized 11/24/25 Carr Creek Marina Off-line 9/4/2025 winterized 11/24/25 Mill Creek Pier (Possum Point) off-line 9/4/2025 winterized 12/1/25

USNA Irrigation Systems (UEM)

USNS Irrigation Systems

USNA Seasonal Buildings

USNS Seasonal Buildings

NSAA Pools

USNA Outdoor Fountains

Scheduled Utility Outages Approved:

Wednesday 14 January

* There are no utility outages scheduled for today.

Thursday 15 January

Wednesday 21 January

Thursday 22 January

New * Request 5993- Steam Outage for Bldg.114 Norm Scott Natatorium and Bldg. 102 Macdonough Hall USNA-102 from 0600-0900. Outage is to install a new steam pressure sensor.

Road/Parking Spaces Closures Approved:

Tuesday 3 November

Monday 5 January

* Request 760- Bldg. 275 Loading Dock Area and the Parking Spaces Closure from 0700 - 1600 on Friday, March 6, 2026. This is to place dumpsters in the loading dock area for the carpet removal at Bldg. 291 USNI Beach Hall.

Monday 12 January

New * Request 5980- Electrical Power Outage for Bldg. 46NS Marine Barracks, Bldg. 58NS Admin with the building generator providing backup emergency power to 58NS, Bldg. 2NS Armory, Bldg. 89NS Recreation/Gym from 2300-0500. Outage is to perform preventative maintenance on the transformers and associated equipment in Substation TS-28 & TS-28A.

* Request 5981- Electrical Power Outage for Bldg. 103 Dahlgren Hall the permanently installed generator will provide backup power to the emergency circuits from 2200-0500. Outage is to perform preventative maintenance on the transformers and associated equipment in Substation TS-76.

New * Request 5997- Water Outage Hot and Cold for Bldg. NA687 Brigade Sprots Complex from 0001-0500. Outage is for the contractor to tie-in the water supply to the building water main. Work Order #CTVSML issued to VJFS to provide the assistance as requested to secure the water and to provide access to the sprinkler room and restore the water once this work is complete.

* Request 752- Parking Lot between Wing 8 Parking Lot and Bldg. 628 Lejeune Hall, known as the Stone Lot from 0730 - 1600 on Friday, January 30, 2026. This is for the contractor working the Bldg. 628 Lejeune Roof Project staging the materials, equipment, scaffolding, stair tower to complete the roof overlay.

* Request 762- Parking Spaces four to be blocked for a laydown area to store the new pavers from 0700 - 1600 on Monday, January 26, 2026. This is for the new pavers that are being replaced at Bldg. 572 Michelson, Chauvenet, Bldg. 590 Rickover Hall and Bldg. 589 Nimtz. This work is under VJFS W/O #CS3Y3M.

Pending Approval Utility Outages:

Thursday 22 January

Tuesday 27 January

VJFS W/O #CSHWX9, VJFS #3763697.

Pending Approval Road/Parking Spaces Closures:

* There is no scheduled Pending Approval Road/Parking Spaces Closures at this time.

* Request 5979- Electrical Power Outage for Bldg. 336NS Storage, Shore Power, Reach A Contractor's Construction Trailers from 0100-0400. Outage is to perform preventative maintenance on the transformers and associated equipment in Substation TS-24 & PS-24.

New * Request 5995- Heating Hot Water Outage for Bldgs. 252, 250, 251, 276, 275 all of the 250 complex. Note this will only be performed based on the weather/outside temperature from 0600-1600. Outage is to replace a isolation valve, check valve and to move the pump. This work is under

* Request 5996- Electrical Power Outage for Smoke Hall at Bancroft Hall and Rotunda at Bancroft Hall from 0500-0900. The outage is to remove temporary power for lights. Work Order #CTT364 issued to VJFS to provide the assistance as requested to open the high voltage room TS- 9 in the Center Section for the contractor. PDCB contractor will be turning the power off and performing LOTO to Electrical Panels C1A (LS) & C1A (RS) in the Rotunda.

Forecast Discussion:

Interested parties are advised to check back on Wednesday for the next regular forecast and monitor updates from the National Weather Service at https://www.weather.gov/lwx.

Weather Forecast:

Monday: Sunny and seasonable. West wind 10-15 mph. High near 45 oF.

Tuesday: Sunny and seasonable. South wind 5-10 mph. Low: 28-32 oF. High: 44-48 oF.

Wednesday: Sunny and mild with a chance for rain showers in the evening and overnight (50% chance). Light snow showers could mix-in late overnight. Southwest wind 5-10 mph. Low: 34-38 oF. High: 46-50 oF.