J-1601000-11 SAMPLE ESSENTIAL EQUIPMENT LOG (EEL).pdf
PDF 261 KB Posted
- Attached to
- Base Operations Support Services For NSA Annapolis and US Naval Academy, Annapolis, Maryland
- Solicitation number
- N6247026R0017
About this file
This document is a Facilities and Equipment Status Report for the United States Naval Academy (USNA) in Annapolis, Maryland, dated January 14, 2026. The report provides comprehensive operational status updates for all major building systems, utilities, and equipment across the USNA campus, including heating, cooling, water treatment, wastewater management, electrical infrastructure, emergency generators, and specialized facilities such as pools and irrigation systems.
The report indicates numerous critical systems currently offline or requiring maintenance, including HTHW Generator #2 (oil meter failure), multiple boiler circulating pumps in standby mode, Zone Distribution pump #1 (isolation valve leaks), two portable boilers undergoing NAVFAC inspection awaiting funding, Steam Generator #2 (tube bundle leak), and several backflow preventers at various buildings that have failed pressure relief valve (BFP) testing and present health hazards. Active maintenance issues include condensate leaks in the lower yard, faulty water softeners, multiple chiller units with failed actuators and VFD faults, condenser pumps with leaking seals and failed motors, and numerous fire alarm systems offline requiring full replacement engineering. Scheduled utility outages approved for the near term include electrical power maintenance at substations, steam outages at dormitories, water service work at Brigade Sports Complex, and parking lot closures for construction staging. The document also tracks 36 street and building lights currently out of service across four patrol zones, with several requiring RFP development. Door dams and sandbag inventory for flood mitigation are confirmed ready for deployment, and weather forecasting indicates potential rain and snow showers Thursday through Friday with gusting winds.
View the file
Other files
Show 40 more
Latest 50 of 86 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Production/UEM: NOAA Weather Forecast: 7-Day Forecast 38.97N 76.49W (weather.gov) On Line Safety Manager: AccuWeather Weather Forecast: Annapolis, MD Daily Weather | AccuWeather Stand-By Utilities Manager: NOAA Tides and Currents: Station Home Page - NOAA Tides & Currents Inspection Facilities Manager: WeatherBug Weather Forecast: Annapolis, Maryland | 10-Day Weather Forecasts & Weekend Weather | WeatherBug High Temp Water Shut-down IDIQ Manager: NOAA Operational (Tides): Operational Forecast System - Station Plot Time Series (noaa.gov) Stand-By EV/Energy Manager: NOAA Hurricane Center: National Hurricane Center (noaa.gov) Off-Line for Summer Duty Manager: NOAA Water-Adv. Hydrologic Prediction: NOAA Severn River Tidal Forecast Off-Line for Winter
1/5/2026
BLDG # EQUIPMENT STATUS Action Date ETR Maximo Work Order # Impact if Equipment/System is Out of Service Remarks IDIQ Remarks
HTHW GENERATOR #1
Stand-By
1/14/2026
12/16/2025
HTHW GENERATOR #2
On-line
1/14/2026 01/06/2026 Oil Meter Bad unable to run on oil until replaced
1/14/2026 HTHW Generator #3 On-line 1/14/2026 12/17/2025 Repair
1/14/2026 Boiler Circulating pump #1 Stand-By 1/14/2026 11/17/2025 Boiler Circulating pump #2 On-line 1/14/2026 Boiler Circulating pump #3 On-line 1/14/2026 Monthly Change Over 10/28/2025 Boiler Circulating pump #4 Stand-By 1/14/2026 Placed Back In Service. 11/19/2025 Feed Water Pump #1 On-line 1/14/2026 Monthly Change Over 1/1/2026 Feed Water Pump #2 Stand-By 1/14/2026 Monthly Change Over 1/1/2026 Make-Up Water Pump # 1 On-line 1/14/2026 Monthly Change Over 1/1/2026 Make-Up Water Pump # 2 Stand-By 1/14/2026 Monthly Change Over 1/1/2026 Zone Distribution pump #1 Out-of-Service 12/23/2025 6/26/2024 CM6ZZR LOTO# 2009 HTHW Isolation Valves Not holding, leaking by. pump installed warmed up and online for testing 10/30/2024 Zone Distribution pump #2 On-line 1/14/2026 Monthly Change Over 1/2/2026 Zone Distribution pump #3 Stand-By 1/14/2026 Monthly Change Over 10/1/2025 Zone Distribution pump #4 Stand-By 1/14/2026 Making a knocking noice . Switched to #2. Distribution pump. 1/3/2026.
#1 Control Air Compressor On-line 1/14/2026 #2 Control Air Compressor On-line 1/14/2026 #5 atomizing air compressor Stand-By 1/14/2026 #6 atomizing air compressor Stand-By 1/14/2026 #7 atomizing air compressor Stand-By 1/14/2026 #8 atomizing air compressor Stand-By 1/14/2026 HTHW Generator Safety Valves Stand-By 1/14/2026 Sulfite 100-200 130 1/14/2026 Alkalinity 150-200 150 1/14/2026 Softener (Hard/Soft) Soft 1/14/2026
EMERG. DIESEL GEN RUN HRS. 364.3 1/14/2026 Generator Test Run every Wednesday at 17:00-17:30
Monitored Fuel Level 63% 1/13/2026 579S Portable Boiler #1 Out-of-Service 3/29/2024 620550 Moved to rear of CHP for storage 3/29/2024. Disassembled For NAVFAC inspection. IQ bid to repair submitted, waiting funding
Portable Boiler #2 Out-of-Service 3/29/2024 Moved to rear of CHP for storage 3/29/2024. Disassembled For NAVFAC inspection.
579 HTHW Sump Pump # 1 On-line 1/13/2026 579 HTHW Sump Pump # 2 On-line 1/14/2026 583 #1 Fuel Oil Tank (Full 317,015 gal) -
Suction On-line 1/14/2026 Fuel tank capacity 80 % = (253,612) 12/29/2025 10' 1 3/16" = 136,235 Gal.
617 #2 Fuel Oil Tank (Full 335,000 gal) Out-of-Service
EMPTY 1/14/2026 FY24
Expansion Tank/Dump Tank On-line 1/14/2026 Fuel Oil Transfer Pump #1 Stand-By 1/14/2026 Fuel Oil Transfer Pump #2 Stand-By 1/14/2026 Zone 1 Supply Temp (°F) 360 1/14/2026 Zone 1 ReturnTemp (°F) 285 1/14/2026
Zone 1 Supply PSI 455 1/14/2026 Zone 1 Return PSI 405 1/14/2026
Zone 2 Supply Temp (°F) 360 1/14/2026 Zone 2 ReturnTemp (°F) 318 1/14/2026
Zone 2 Supply PSI 455 1/14/2026 Zone 2 Return PSI 420 1/14/2026
Lower Yard Tunnel (Michelson) Condensate Leak 3/27/2025 1/11/2026 10/27/23 Energy awareness: Loss of condensate will 19OCT23: UEM found the condensate in the Lower Yard leaking leaving Michelson. UEM
Steam Generator #1 On-line 1/13/2026 @ 24psi 10/25/2025 Increasing 5psi each day till 25psi Alkalinity 200 - 600 150 1/11/2026 Sulfite 30 - 150 40 1/11/2026 Conductivity, neutralized (2500 - 3500) 2543 1/11/2026 Steam Generator #2 Out-of-Service 12/20/2025 Tube Bundle Leak LOTO# 1970 Alkalinity 200 - 600 Sulfite 30 - 150 Conductivity, neutralized (2500 - 3500) Softener (Hard/Soft) Hard 1/13/2026 Repair or Replace Faulty Water Softner. Water Softner Has a Faulty Electronic Head
Essential Equipment Log
CENTRAL HEATING PLANT
Oil meter: 745.6 // Hrs. since VE 0 @ 09:00 hrs
Oil meter: 38998.7 // Hrs. since VEO @ 72:00 hrs
Oil meter: 17342.2 // Hrs. since VEO @ 72:00 hrs
Known HTHW / Steam Issues
STEAM PLANT
CHP:
Medium Voltage:
CHWP:
WTP:
WWTP:
Fire Sprinklers:
Pools & Irrigation:
NAVFAC has fuel tank out of service: PWD Annapolis has this for action. LOTO #1033
654U Well #15 Stand-By 1/14/2026 683U Well #16 Stand-By 1/14/2026 587U Well #17 On-line 1/14/2026 IQ: CJXGW9
Control Panel On-line 1/14/2026 #1 Air Compressor On-line 1/14/2026 12/22/2025 IMP WO# 3931484 #2 Air Compressor On-line 1/14/2026 Ingersoll Rand (spare) Air Compressor On-line 1/14/2026 Quincy air compressor 2nd deck On-line 1/14/2026
#1 Aerator Motor On-line 1/14/2026 #2 Aerator Motor Stand-By 1/14/2026 Fluoride pump On-line 1/14/2026 IMP WO# 3782936 #1 Wispro Floc pump Stand-By 1/14/2026 #2 Wispro Floc pump On-line 1/14/2026 #1 Lime Injection System Stand-By 1/14/2026 #2 Lime Injection System On-line 1/14/2026 #1 Coagulation Tank On-line 1/14/2026 #2 Coagulation Tank On-line 1/14/2026 Filter #1 On-line 1/14/2026 Filter #2 Stand-By 1/14/2026 Filter #3 On-line 1/14/2026 Filter #4 On-line 1/14/2026 Filter #5 On-line 1/14/2026 Filter #6 Stand-By 1/14/2026 Filter #7 Stand-By 1/14/2026 Distribution pump #1 On-line 1/14/2026 Distribution pump #2 On-line 1/14/2026 Distribution pump #3 On-line 1/14/2026 Distribution pump #4 Stand-By 1/14/2026 Centrifuge #1 Stand-By 1/14/2026 Centrifuge #2 On-line 1/14/2026 Sludge Holding #A On-line 1/14/2026
Sludge Holding #B On-line 1/14/2026 12/13/2025 Sludge Pump #1 Stand-By 1/14/2026 12/13/2025 Sludge Pump #2 On-line 1/14/2026 12/13/2025 Water Tower Level (Normal:154'-160') 156 1/14/2026 Daily On line System psi 65 to 68 12/13/2025 Storage Tank Levels (Normal: 23'-27') 25.2/25.3 1/14/2026 Daily 12/13/2025 Daily Discharge Flow 412664 1/14/2026 Daily 12/13/2025 Effluent Distribution meter On-line 1/14/2026 12/13/2025 GPM (Avg.) 196 1/14/2026 Daily 12/13/2025 MGD 0.412 1/14/2026 Daily 12/13/2025 Gallon Totalizer Reading: 36614500 1/14/2026 Daily 12/13/2025 Booster pump #1 On-line 1/14/2026 12/13/2025
Booster pump #2 Stand-By 1/14/2026 12/13/2025
Iron 0.02 1/14/2026 Range: 0.03 ppm (0.3 ppm MCL) Daily 12/13/2025
Turbidity 0.07 1/14/2026 Daily 12/13/2025
Free Chlorine Residual (Cl2) 1.36 1/14/2026 Range: 1.2 - 1.8 mg/L (4.0 mg/L MCL) Daily 12/13/2025
PH 8.14 1/14/2026 Range: 6.5 - 8.5 Daily 12/13/2025
Fluoride 0.53 1/14/2026 Target: 0.7 mg/L MCL Daily 12/13/2025
12/13/2025 ivo 907ns Valve F50-p1 Leaking went to make repair on leaking water main at gun range, found valve leaking from thevalve body.reported to UEM greg, BP11/10/2025 12/13/2025
12/13/2025
FH #32 leaks and is hard to Operate In service found during udf BP 12/13/2025 FH #43 leaks form bonnet hard to operate
In service found durring udf BP
FH #6 leaks form bottom when in operatio In service found durring udf BP
FH# 49 leaks when in operation In service found durring udf BP
FH# 54 leaks form bonnet when in operati In service found durring udf BP
FH# 82 hard to open and leaks form bonne In service
Found on UFD BP
FH# 80 has stripped cap In service
Found on UFD BP
FH# 81 has stripped cap In service
Found on UFD BP
FH# 97 hard to open/ leaks from bonnet In service
Found on UFD BP
WATER TREATMENT PLANT
1st 12 hour Tests
Known Water Main Issues
Known Fire Hydrant Issues
FH# 100 hard to open In service
Found on UFD BP
FH# 75 hard to open In service
Found on UFD BP
FH# 65
Out-of-Service CPJVLR
FIRE HYDRANT TAKEN OUT OF SERVICE TO SUPPORT OUTAGE REQUEST #5753 This is to support the Perimeter Wall Project
FH# 212
IN Service CRD4MC fire hydrand dose not seal when off and leask by the valve. also leaks form top screw. BP
FH# 85 hard to open In service
Found on UFD BP
257 POLICE STATION 3" MAIN NA257-BFP-417FAILED
CLJ3VJ
HEALTH HAZARD FAILED BFP TESTING
101-6 WING 6 6" DOMESTIC HOT WATER NA101FAILED
CLJ3VD
HEALTH HAZARD FAILED BFP TESTING
579 CHP MAIN 4" NAUP579-BFP-153-A FAILED
CLJ3VP
HEALTH HAZARD FAILED BFP TESTING
201 FARRAGUT FIELD IRRIGATION 4" NA201-FAILED
CLJ3VP
HEALTH HAZARD FAILED BFP TESTING
693 COMMISSARY MAIN 3" FAILED HEALTH HAZARD FAILED BFP TESTING
571 PERRY CENTER 3/4" COMPRESSOR COOFAILED HEALTH HAZARD FAILED BFP TESTING
101-4 WING 4 3" DHW NA1014-BFP-4251-A FAILED HEALTH HAZARD FAILED BFP TESTING
590 RICKOVER 1 1/4" NA590-BFP-188-A FAILED HEALTH HAZARD FAILED BFP TESTING
87 YP PIER BOAT FILL 2-1/2" NA87NS-BFP-4FAILED HEALTH HAZARD FAILED BFP TESTING
107 SAMPSON 3/4" NO-POT NA107-BFP-5004-FAILED HEALTH HAZARD FAILED BFP TESTING
2 O' CLUB HUMIDIFIER 3/4" NA2-BFP-5013- FAILED HEALTH HAZARD FAILED BFP TESTING
101-8 WING 8 FIRE NA1018-BFP-35-A FAILED HEALTH HAZARD FAILED BFP TESTING
101-7 WING 7 6" DOMESTIC HOT WATER NA101FAILED HEALTH HAZARD FAILED BFP TESTING
291 BEACH HALL MAKE UP 1" NA291-BFP-17 FAILED HEALTH HAZARD FAILED BFP TESTING
101-L LEAVY FIRE NA101L-BFP-4216-A FAILED HEALTH HAZARD FAILED BFP TESTING
101-2 WING 2 WTR SOFTNER 2" 1012-BFP-1994FAILED HEALTH HAZARD FAILED BFP TESTING
101-3 WING 3 FIRE 6" 1013-BFP-251-A FAILED HEALTH HAZARD FAILED BFP TESTING
234NS HANGER 1" WTR SOFTNER NA234NS-BFPFAILED HEALTH HAZARD FAILED BFP TESTING
NA265 NATURE CENTER 1" MAIN NANA265-BFP FAILED HEALTH HAZARD FAILED BFP TESTING
82NS OUTBOARD MAKE UP 3/4" NA82NS-BFP-5FAILED HEALTH HAZARD FAILED BFP TESTING
181 HALLIGAN HALL 6" FIRE SYSTEM NA181-FAILED
2/23/2024 NEEDS RFP
HEALTH HAZARD FAILED BFP TESTING
47NS BEQ FIRE 6" NA47NS-BFP-157-A FAILED
NEEDS RFP
HEALTH HAZARD FAILED BFP TESTING
274 OLD NHC 3" MAIN NA274-BFP-228-A FAILED
NEEDS RFP
HEALTH HAZARD FAILED BFP TESTING
597U Chiller #1 2500 Ton Stand-By 1/14/2026 CRXLYK CDW actuator failed. (WS) Chiller #2 2500 Ton Stand-By 1/14/2026 CRXLYK CDW actuator failed. (WS) Chiller #3 2500 Ton Stand-By 1/14/2026 CRXLYK VGD fault work started, discussing project needs with inspector
Primary CHW Pump #1 Stand-By 1/14/2026 Primary CHW Pump #2 Stand-By 1/14/2026 Primary CHW Pump #3 Stand-By 1/14/2026 Primary CHW Pump #4 Stand-By 1/14/2026
Cndenser Pump #1 Out-of-Service 1/14/2026 IMP Imp for leaking seal (dh), motor bad 10-8- Condenser Pump #2 Stand-By 1/14/2026 CRL9FR Leaking seal. (WS) in comp os Condenser Pump #3 Out-of-Service 1/14/2026 Imp bad motor Condenser Pump # 4 Stand-By 1/14/2026 Secondary Pump #1 Stand-By 1/14/2026 Secondary Pump #2 Stand-By 1/14/2026 Secondayr Pump #3 Out-of-Service 1/14/2026 Offline needs new VFD (DH) Conductivity Range 1000 1/14/2026
Nitrate 520 1/14/2026
LEJEUNE (597U)
Known Backflow Preventer Issues
CHILLED WATER PLANTS
Cooling Tower #1A Stand-By 1/14/2026 bad motor Cooling Tower #1B Stand-By 1/14/2026 Cooling Tower #2A Stand-By 1/14/2026 VFD cooling fan needs replaced (WS) Cooling Tower #2B Stand-By 1/14/2026 Cooling Tower #3A Stand-By 1/14/2026 Cooling Tower #3B Stand-By 1/14/2026 COMPOS for replacement. (WS)
City Water-Make Up Meter 81567 1/14/2026 Chilled Water Make Up Meter 0 1/14/2026
Condenser Make Up Meter 97490 1/14/2026 " " SystemPSI 63 1/14/2026 " "
SUPV Controllers 1/14/2026 " "
JCI Metasys On-Line 1/14/2026 JCI PMI On-Line 1/14/2026 Siemens On-Line 1/14/2026
Chiller 1 2500 Ton Stand-By 1/14/2026 1/5/2026 Chiller 2 2500 Ton Stand-By 1/14/2026 1/5/2026 Chiller 3 2500 Ton On Line 1/14/2026 1/5/2026
Primary CHW pump 1 Stand-By 1/14/2026 1/5/2026 Primary CHW pump 2 Stand-By 1/14/2026 1/5/2026 Primary CHW pump 3 Out-of-Service 1/14/2026 1/5/2026 Primary CHW pump 4 On Line 1/14/2026 1/5/2026 Primary CHW pump 5 Stand-By 1/14/2026 1/5/2026 Condenser Pump 1 Stand-By 1/14/2026 1/5/2026 Condenser Pump 2 Stand-By 1/14/2026 1/5/2026 Condenser Pump 3 On Line 1/14/2026 1/5/2026 Condenser Pump 4 Out-of-Service 1/14/2026 1/5/2026 Condenser Pump 5 Stand-By 1/14/2026 1/5/2026
Secondary CHW Pump 1 Stand-By 1/14/2026 1/5/2026 Secondary CHW Pump 2 On Line 1/14/2026 1/5/2026 Secondary CHW Pump 3 On Line 1/14/2026 1/5/2026
Conductivity (range 900-1100) 600 1/14/2026 1/5/2026 Nitrate 520 1/14/2026 1/5/2026
Cooling Tower 1A Stand-By 1/14/2026 1/5/2026 Cooling Tower 1B Stand-By 1/14/2026 1/5/2026 Cooling Tower 2A Stand-By 1/14/2026 1/5/2026 Cooling Tower 2B Stand-By 1/14/2026 1/5/2026 Cooling Tower 3A On Line 1/14/2026 1/5/2026 Cooling Tower 3B On Line 1/14/2026 1/5/2026 Cooling Tower 4A On Line 1/14/2026 1/5/2026 Cooling Tower 4B On Line 1/14/2026 1/5/2026
Tower PM ststus Complete = Green 1/5/2026 1/14/2026 1/5/2026
Tertiary Pump 1 Stand-By 1/14/2026 1/5/2026 Teritary Pump 2 Stand-By 1/14/2026 1/5/2026 Teritary Pump 3 Stand-By 1/14/2026 1/5/2026
City make-Up Water Meter 2,598,852 1/14/2026 1/5/2026 Chill Water Meter 211 1/14/2026 1/5/2026
Comndenser Water 1,006,969 1/14/2026 1/5/2026 Pressure 64 1/14/2026 1/5/2026
Ward Hall Geo System valve 7/8/9 Closed = Campus Open 1/14/2026 1/5/2026
Valve 10 (open = Canpus/Close Geo Close 1/14/2026 1/5/2026 Geo-Pump 1(P-1) Out-of-Service 1/14/2026 1/5/2026
Geo-Pump #2 (P-2) On 1/14/2026 Condenser Pump #3 (P-3) On 1/14/2026 Condenser Pump #4 (P-4) Off 1/14/2026 Chilled Water Pump #5 (P-5) On 1/14/2026 Chilled Water Pump #6 (P-6) Off 1/14/2026
EVAP-FM(Geo-Chiller Evaporator Flow) 119.9 1/14/2026 COND-FM(Geo-Chiller Condenser Flow) 76.9 1/14/2026
Data Rack Leaving Temp. (Setpoint is 55°F) 44.70 1/14/2026 Chiller Evaporator Leaving Water Temp 41,0 1/14/2026 Chiller Evaporator Entering Water Temp 44.40 1/14/2026 `
CHLR1-FAIL-IN(Normal or Alarm) On-Line 1/14/2026 CHLR2-FAIL-IN(Normal or Alarm) On-Line 1/14/2026 CHLR3-FAIL-IN(Normal or Alarm) On-Line 1/14/2026
TRANS-SW-S(Off=Normal Power, On=EmergencOff 1/14/2026 MAN-SW-S(Off=Geo-Chiller, On-Campus) Off 1/14/2026
Effluent Flow Rate 50,475 1/14/2026 7-15-25 Old surge basin surface aerator INOP - Waiting on price for a new motor - IMP Surge Basin Level 2.57 1/14/2026 7-9-25 New surge basin #2 pump not running as effeciently as #1 pump - Pinch Valve Adjusted To 231 1/14/2026 Need to drain the surge tank and check for trash buld up where pump connects to.
Sludge Pump On-line 1/14/2026 #1 Digester On-line 1/14/2026 #2 Digester On-line 1/14/2026
108 #1 Primary Clarifier Stand-By 1/14/2026 109 #2 Primary Clarifier On-line 1/14/2026 7/24/2023 Placed Online
EMCS-BAS Servers/System 597U
RICKOVER (590A)
590A
WasteWater Treatment Plant
Pump Station #1 On-line 1/14/2026 7-14-25 - Installed new submerisible level trasnducer IMP: 3304379 Pump #1 On-line 1/14/2026 Pump #2 On-line 1/14/2026 08AUG24: Pumps #2 and #3 online with a pump around in place-RM Pump #3 On-line 1/14/2026
Pump Station #2 On-line 1/14/2026 4-24-2024 Beall cleaned out wet well #1 pump On-line 1/14/2026 #2 pump On-line 1/14/2026
Overflow Tank 5.9 @ 43.9 1/14/2026 Aux. Equipment On-line 1/14/2026 Sludge Holding Tank 1/14/2026 Sludge Holding Tank Level 4.31 1/14/2026 How many Gallons was Pumped Out 1/14/2026 Beall hauled 5200 gls from SHT 1/12/2026 How many Gallons was Decanted 0 1/14/2026 Level Pre / Post Decant 0 1/14/2026
323 #2 Air Compressor On-line 1/14/2026 MBR #1 On-line 1/14/2026
Influent Flow 20.7 1/14/2026 Wasted 1,200 1/14/2026
Aeration Zone Results: 350 1/14/2026
PH 7.1 1/14/2026
DO 2.2 1/14/2026
ATC 5,600 1/14/2026
Micro C Pump Speed 7% 1/14/2026 TMPs -1.7 1/14/2026
MBR #2 On-line 1/14/2026
Influent Flow 18.5 1/14/2026 Wasted 1,200 1/14/2026
Aeration Zone Results: 7.1 1/14/2026
PH 7 1/14/2026
DO 2 1/14/2026
ATC 5,500 1/14/2026
Micro C Pump Speed 7% 1/14/2026 TMPs -1.7 1/14/2026
Combined Effluent 1&2 7% 1/14/2026 PH 7.6 1/14/2026 PH range 6.5 - 8.5
PO4 (Phosphate) 2.5 12/30/2025 NO2+NO3 (Nitrates) N/D 12/30/2025
NH3 (Ammonia) 22 12/30/2025 DO 9.1 1/14/2026 DO greater than 5.0 PPM
PO4 (Phosphate) 0.06 1/14/2026 PO4 range less than 0.30 NO3 (Nitrates) 0.8 1/14/2026 NO3 range under 1.0
NH3 (Ammonia) 0 1/14/2026 NH3 under 1.0 Temperature 52 Deg F 1/14/2026 Effluent Water Temperature F
Monthly Effluent (gallons) - Running Total 0.75461 1/14/2026
579 Main Vision 21 System (Main SCADA On-line
370 Hubbard Hall On-line 326 50 Rogers Road On-line 3/15/2024 tbd IMP 1662809 bearings on both pumps sound bad and causing a vibration in pumps. wrote up compos to have rebuilt or replaced.
287 Hospital Point Bathhouse On-line
105 Carter Hall On-line 9/4/2025 PM 3234510 RFP TO BE SENT 1/6 DG 04SEPT25: Lift Sttaion can't run in auto-RM; 14JUL25: Found failed starter for pump #1, new started was ordered by DJ on 14JUL25. BP. found most of the wires underground have failed and one of the pumps failed. have statoin running on 1 foat and 1 pump. BP
572 Michelson/Chauvenet Hall On-line 572 Michelson/Chauvenet Hall On-line 572 Michelson/Chauvenet Hall On-line 572 Michelson/Chauvenet Hall On-line 590 Rickover Hall On-line 5/9/2023 Sewage alarm radio is offline 5.9 compos submitted, radio requires rebuild 601 Robert Crown Sailing Center (SSP-8) On-line 601 Robert Crown Sailing Center (SSP-8A) On-line 150 Glenn Warnter Soccer Center On-line 145 Cutter Shed On-line 685 Farragut Field On-line 614 Ingram Field On-line 250 Old Medical Clinic On-line
640 Hopper Hall On-line
880 Larson Hall On-line 2976428/sr33678476 found pump #2 motor has failed will need to pull and order new one. pump #1 is RFP TO BE SENT 1/6 DG
645 Bishop Stadium On-line
North Severn Sanitary Lift Stations
NA103 Hooper Highland Road (by Marina) On-line 5/16/2023 WO: 605844
Sewage alarm radio failed to send signals to CHP during monthly inspection, requires rebuild compos sent 5/12/23
106NS Railway (near 82NS) On-line 5/16/2024 NA695APS Navy Medical Health Clinic On-line
234NS Hangar On-line 66NS Small Craft On-line 131NS Hobby Shops On-line
Sanitary Lift Stations USNA Sanitary Lift Stations
MBR #1
MBR #2
114NS Influent
MBR #1 & 2
297NS CBU 403 (behind 297NS) On-line 336NS Flammable Liquid Storage On-line 89NS Rec Bldg. On-line 12/3/2025 WO: CSJSJN FOUND PUMP LOCKED UP DG 334NS YP Bilge Pump On-line NA686 Restroom 12th Tee On-line NA140 Mill Creek Marina On-line 803NS Recycling Bldg. On-line 114NS WWTP-Pump House 1 On-line 289NS WWTP-Pump House 2 On-line 235NS MAREXP SECRON 12 DET C On-Line
326NS WWTP-Surge Basin On-line 1/17/2024 PM: 1373662 communication with T-rex restored, LOCAL ALARM NOT FUNCTIONAL,ordering parts to repair
330NS Campground On-line Sanitary Manholes - ALARM ONLY - NO PUMPS Badger Road (AH9.1S) On-line Badger Road (AG11.1S) On-line
NA76 Golf Course On-line 11/28/2023 Not communicating with T-rex, under investigation
36 upsher sewer main has root intrusion on-line 8/4/2025 3417389 /CSCD7M 3AUG25 after hours call was put in for sewer 3 porter sewer main has root intrusion on-line 12/18/2024 2564351/CP73JX/3207977 18DEC24 cabled and ran camera down sewer 354NS Youth Center On-line 6/1/2024 062624: Greg Currence has the SOW for action- Line has two holes. Needs to be repaired-BP;
USNA-320 MWR BATH HOUSE SOUTH POOL On-line 6/1/2024 vjfs 1952577 gov sr# 24197883 062624: Greg Currence has the SOW for action- found drop man hole IVO of md 450 has root intrusion. the man hole can not be located with USNA- IVO carter hall 6" sewer main has root intrusion on-line 8/14/2024 vjfs#2157810 GOV# CNH7YT 14AUG24: found 6" terracotta sewer line has
4/2 porter road root intrusion on-line 11/19/2024 VJFS# 2496728 19NOV24 found root intrustion 20'-30' from clean 44 upsher root intrusion on-line 11/120/2024 VJFS# 2516961 20NOV24 found root intrustion from new clean USNA-SS 31/32 UPSHUR On-line 6/12/2024 VJFS 1952221 GOV CMYH63 062624: Greg Currence has the SOW for action- found about 30-40 feet of terracotta drain line had root intrustion at every joint. at about 80-90 feet
Medium Voltage Main Substations/Feeders Main Feeder - 64 Normal - Closed 1/13/2026 Main Feeder - 67 Normal - Closed 1/13/2026 Tie Breaker Normal - Open 1/13/2026 W20A Normal - Closed 1/13/2026 18MAR24: W20A is LOTO'd for W20B repairs-RM.
D5 Normal - Closed 1/13/2026 W13A Normal - Closed 1/13/2026 W10 Normal - Closed 1/13/2026 W20B Out of Service 6/16/2023 No redundancy at CHWP 597U 20JUN23: Feeder W4A loop could be used if needed to support CHWP 597U. Urgent SC W13B Normal - Closed 1/13/2026 W9 Normal - Closed 1/13/2026
Main Feeder - 35 Normal - Closed 1/13/2026 AC unit # 3 found not working, HVAC is submitting FWO (GC 6/24) Main Feeder - 36 Normal - Closed 1/13/2026 Tie Breaker Normal - Open 1/13/2026 W64A Normal - Closed 1/13/2026 W64B Normal - Closed 1/13/2026 W64C Normal - Closed 1/13/2026 W64D Stand-By 1/13/2026 W68A Normal - Closed 1/13/2026 W69B Normal - Closed 1/13/2026 W68C Normal - Closed 1/13/2026 W68D Stand-By 1/13/2026 W68E Normal - Closed 1/13/2026 SPARE Stand-By 1/13/2026 SPARE Stand-By 1/13/2026
Main Feeder - W13A Normal - Closed 1/13/2026 Main Feeder - W13B Normal - Closed 1/13/2026 Tie Breaker Normal - Open 1/13/2026 W1 Normal - Closed 1/13/2026 W3 Normal - Closed 1/13/2026 W5 Normal - Closed 1/13/2026 W7A Normal - Closed 1/13/2026 W11 Normal - Closed 1/13/2026 FL1 Normal - Closed 1/13/2026 HH1 Normal - Closed 1/13/2026 TS-103 Normal - Closed 1/13/2026 SPARE Stand-By 1/13/2026 W2 Normal - Closed 1/13/2026 W4 Normal - Closed 1/13/2026 W6 Normal - Closed 1/13/2026 W8A Normal - Closed 1/13/2026 FL2 Normal - Closed 1/13/2026 HH2 Normal - Closed 1/13/2026 SPARE Stand-By 1/13/2026
CHWP 597U Feeder W20B Out of Service 6/16/2023 5/31/24 No redundancy at CHWP 597U 20JUN23: Feeder W4A loop could be used if needed to support CHWP 597U. Urgent SC
W20B Main Breaker Abnormal - In Operation 3/18/2024 FY24
Known Sanitary Main and/or Sanitary Lateral Issues
13C-1
KINKAID
13C-2
Feeders that are OOC or have known issues:
Medium Voltage Equipment (Transformers-TS and Switches-PS) that are OOC or have known issues:
Preble TS-139 Abnormal - In Operation 5/14/2025 FY25
11APR25: Awaiting proposal for testing and minor repairs, Preble is being powered by a portable generator--RM;
105 Building 105, Maury Hall Ready for Operation 1/13/2026 PM completed 7/30/24 106 Building 106, Mahan Hall/Telephone
Office Ready for Operation 1/13/2026 PM Complete 7/30/24 187 Printing Plant Ready for Operation 1/13/2026 PM complete 7/31/24 257 Building 257, Safety Ready for Operation 1/13/2026 Unit smokes when starting, Need WO and need to call cummings PM COMPLETE 8/1/24 274 Building #274, Hospital Clinic Ready for Operation 1/13/2026 PM COMPLETE 8/1/24 275 Building #275, Hospital (Server Room) Ready for Operation 1/13/2026 PM COMPLETE 7/8/24 290 Building 290, Ward hall Ready for Operation 1/13/2026 Fuel Level: 20%
PM COMPLETE 10/25/23326 Building 326, Sewage Pump, Dorsey Creek Ready for Operation 1/13/2026 PM COMPLETE 10/17/23
370 Building 370, Hubbard Hall Ready for Operation 1/13/2026 PM COMPLETE 10/16/23 446 Building 446, USNA Fire Station Ready for Operation 1/13/2026 Small coolant leak on reserve bottle. Looking PM COMPLETE 7/24/24 579 Building 579, Central Heating Plant Ready for Operation 1/13/2026 PM COMPLETE 10/18/23 590 Substation 13C-2 (Hopper, Rickover &
Nimitz) Ready for Operation 1/13/2026 Kelly Generator completed the May generator PMs 591 Building 591, Water Treatment Plant Ready for Operation 1/13/2026 PM COMPLETE 10/19/23 591 Building 591, Water Treatment Plant
(Centrifuge System) Ready for Operation 1/13/2026 PM COMPLETE 10/19/23 628 Building 628, LeJeune Hall Ready for Operation 1/13/2026 Fuel Level 65% 675 Building 675, Alumni Hall Ready for Operation 1/13/2026 PM COMPLETE 10/20/23 1013 Building 1013, Bancroft Hall, Wing 3 Ready for Operation 1/13/2026 PM COMPLETE 7/29/24 1014 Building 1014, Bancroft hall, Wing 4 Ready for Operation 1/13/2026 PM COMPLETE 7/29/24 1017 Building 1017, 7th Wing Ready for Operation 1/13/2026 PM COMPLETE 10/27/23 1018 Building 1018 Bancroft Hall, Wing 8 Ready for Operation 1/13/2026 PM COMPLETE 7/29/24
1014K King Hall, 1014K, Bancroft Hall Ready for Operation 1/13/2026 Kelly Generator completed the May generator PMs 7/31/24 58NS NSA Annapolis ADMIN 58NS Ready for Operation 1/13/2026 Kelly Generator completed the May generator PMs 8/2/24 106NS Building 106NS, Railway Sewage Pump Ready for Operation 1/13/2026 PM COMPLETE 10/3/23 107NS Building 107NS @ WWTP Ready for Operation 1/13/2026 PM COMPLETE 10/2/23 130RL 130RL, NS Water Tower Ready for Operation 1/13/2026 PM COMPLETE 7/31/24 167RL Building 167RL, David Taylor, Telephone
Equipment Ready for Operation 1/13/2026 PM COMPLETE 10/3/23 297NS New CDC Out of Service 1/13/2026 12JAN26: This genertaor is making a mechanical noise that needs to be Fuel Level: 48% PM COMPLETE 10/4/23298NS CDC Ready for Operation 1/13/2026 PM COMPLETE 10/5/23
46NS Building 46NS, BEQ Ready for Operation 1/13/2026 Kelly Generator completed the May generator PMs 572A Building 572A, Chauvenet Hall Ready for Operation 1/13/2026 PM COMPLETE 10/18/23 572B Building 572B, Michelson Hall Ready for Operation 1/13/2026 PM COMPLETE 10/25/23
NA103 NA103, Greenbury Point, Sewage Lift Station Ready for Operation 1/13/2026 Kelly Generator completed the May generator PMs
NA687 Brigade Sports Complex Ready for Operation 1/13/2026 Fuel Level: 90%
PM COMPLETE 10/31/23
NA342 NA342 Naval Station Fire Station Ready for Operation 1/13/2026 Ryan changed the spring in the oil pump, CuKelly Generator completed the May generator PMs NA908 New Hospital (NHCL) Lift Station Ready for Operation 1/13/2026 PM COMPLETE 10/24/23
# Portable Generators: Portable Generator Status: Action Date ETR Maximo # Current Location: Remarks IDIQ Remarks
P-4 Portable Generator: 125KW Ready for Operation 1/13/2026 Perry Center Kelly Generator completed the May generator PMs 7/24/24 14MAY25: Repairs went COMPOS-RM P-5 Portable Generator: 147KW Out of Service 1/8/2026 Perry Center Kelly Generator completed the May generator PM 7/24/24 14MAY25: Repairs went COMPOS-RM P-6 Portable Generator: 45KW Ready for Operation 1/13/2026 Perry Center Kelly Generator completed the May generator PMs 7/19/24 P-7 Portable Generator: 70KW Ready for Operation 1/13/2026 Perry Center Kelly Generator completed the May generator PMs 7/22/24
Badgers and Sellers Gas Meter On-line 1/13/2026 Gate 4 Gas Meter On-line 1/13/2026 Gate 2 Gas Meter On-line 1/13/2026 6 Porter Gas Meter On-line 1/13/2026 Kinkaid Road Gas Meter On-line 1/13/2026
NA 11/12/2025
GWSF Propane Farm: 65% 01/05/2026 Recycling Center: 40% 01/08/2026
Boiler 1 On-line 1/13/2026
Boiler 2 On-line 1/13/2026 Domestic Hot Water Heater #1 On-line 1/13/2026 Domestic Hot Water Heater #2 On-line 1/13/2026
AUX Equipment On-line 1/13/2026
Domestic Hot Water Heater #1 On-line 1/13/2026 Domestic Hot Water Heater #2 On-line 1/13/2026 Hot Water Boiler On-line 1/13/2026 Running just waiting for JCI & Boiler OP's Chiller, 1st Stage Off-Line for Winter 10/20/2025 Compressor replaced in 8/2023 Chiller, 2nd Stage Off-Line for Winter 10/20/2025
Condenser Pump #10 for cooling towers On-line 10/12/2025 currently LOTO valve P10 reported leaking, IMP created, VJFS investigating Chiller #1 repairs 8/4/2023
Natural Gas System
Known Natural Gas Issues
Propane Readings (Taken Biweekly: Beau Nickerson/Dan Garner)
NORTH SEVERN ANNEX FACILITIES
46NS B.E.Q.
Emergency Electrical Generators
NA695
46 NS
47NS B.E.Q.
47 NS
NAVAL STATION HOSPITAL CLINIC - Building NA695
234 NS Steam Boiler #1 On-line 1/13/2026
234 NS Steam Boiler #2 On-line 1/13/2026 Blower motor capacitor bad, put a temporary capacitor on the blower motor Waiting Boiler OP's test, combustion linkage needs to be adjusted.
234 NS Hot Water Boiler #3 On-line 1/13/2026
339 NS Steam Boiler #1 On-line 1/13/2026 12/24/2025
339 NS Steam Boiler #2 On-line 1/13/2026
BANCROFT HALL
DHW #1 (Dual Operations) On-line HTHW 1/13/2026 Monthly Change Over 12/24/2025 DHW #2 (Dual Operations) On-line HTHW 1/13/2026 Monthly Change Over 12/24/2025 DHW #3 (Dual Operations) Stand-By 1/13/2026 Monthly Change Over 12/24/2025 Converter #1 (Dual Operations) Stand-By 1/13/2026 Monthly Change Over 12/24/2025 Converter #2 (Dual Operations) On-line 1/13/2026 Monthly Change Over 12/24/2025 Steam Generator # 8 Stand-By 1/13/2026 P8000-2 Steam Controller is calibrated; Generator 8 to be used only in emergency, bundle leaks 2/27/2024 Sulfite (range 30-60) Stand-By 1/13/2026 Conductivity, neutralized Stand-By 1/13/2026 Softener (Hard/Soft) Stand-By 1/13/2026 Heating Water Pump #1 Stand-By 1/13/2026 Heating Water Pump #2 On-line 1/13/2026 Dual Temp Pump #1 On-line 1/13/2026 Dual Temp Pump #2 Stand-By 1/13/2026
DHWH #1 (Dual Operations) Stand-By 1/13/2026 Monthly Change Over 12/24/2025
DHWH #2 (Dual Operations) Stand-By 1/13/2026 DHWH #3 (Dual Operations) On-line HTHW 1/13/2026 Monthly Change Over 12/24/2025 Converter #1 Stand-By 1/13/2026 Monthly Change Over 12/24/2025 Converter #2 On-line 1/13/2026 Monthly Change Over 12/24/2025 Steam Generator #9 On-line 1/13/2026 EASI scheduling install, tentative week of jan 22, 2023 Sulfite (range 30_60) 40 1/13/2026 Conductivity, neutralized 2632 1/13/2026 Steam Generator #10 On-line 1/13/2026 IQ: CL6NF6 EASI scheduling install, tentative week of jan 22, 2023 Sulfite (range 20-60) 40 1/13/2026 Conductivity, neutralized 2313 1/13/2026 Softener (Hard/Soft) Soft 1/13/2026 Operating normal on new softner Aux. Equipment On-line 1/13/2026 Dual Temp Pump #1 On-line 1/13/2026 Dual Temp Pump #2 Stand-By 1/13/2026
DHWH #1 Out of Service 1/12/2026 For Service 1/8/2026 DHWH #2 On-line 1/13/2026 6/15/2024 DHWH #3 (Dual Operations) On-line 1/13/2026 DHWH #4 (Dual Operations) Out of Service 12/24/2025 CJJX49 Converter #1 Out of Service 12/24/2025 FWO submitted 12/24/2025 Converter #2 On-line / HTHW 1/13/2026 Aux. Equipment: Chilled Water Pump On-line 1/13/2026 3/5/2024 Dual Temp Pump #1 On-line 1/13/2026 Dual Temp Pump #2 Stand-By 1/13/2026
Steam Converter #1 On-line 1/13/2026 TBD
DHWH #4 (Dual Operations) On-line 1/13/2026 DHWH #5 (Dual Operations) Stand-By 1/13/2026 Monthly Change Over 2/13/2025 - 3/28/2025 Secured Supply,Return HTHW Valves Converter #1 (Dual Operations) On-line 1/13/2026 Converter #2 (Dual Operations) Out of Service 3/25/2025 3/25/2025 Secured , unit hads head leak.
Condensate Recovery Tank Stand-By 1/13/2026 Softener (Hard/Soft) Stand-By 1/13/2026
101-1
101-2
SMALLCRAFT REPAIR FACILITY
WING 1
WING 2
WING 3
101-3
KING HALL
101-K
CENTER SECTION
101-C
AUX EQUIPMENT On-line 1/13/2026
Converter On-line 1/13/2026 Aux. Equipment Stand-By 1/13/2026
DHWH #1 (Dual Operations) Stand-By 1/13/2026 Control Valve Repair LOTO# 1959 DHWH #2 (Dual Operations) On-line 1/13/2026 Repair Outage 11/27/2025 DHWH #3 (Dual Operations) Out of Service 12/20/2025 Monthly Change Over 5/15//2024 , Placed OOS tube bundle leak, tube bundle send back Converter #1 (Dual Operations) Stand-By 1/13/2026 Monthly Change Over 12/24/2025 Converter #2 (Dual Operations) On-line 1/13/2026 Monthly Change Over 12/24/2025 Dual Temp Pump #1 Stand-By 1/13/2026 5/17/2024 Dual Temp Pump #2 On-line 1/13/2026 Chilled Water Pumps On-line 1/13/2026 Heating Water Pump # 3 On Line 1/13/2026 3/5/2024
HTG Pump #4 Stand-By 1/13/2026 TBD 23463535 Needs new starter motor. WC 11/7/23. 8/27/2024 Need New Transformer. Transformer On Order
Key Equipment that is OOC:
AHU #3 On-line 4/4/2025 TBD Unit is running Mod hub is down.
DHWH #1 (Dual Operations) On-line HTHW 1/13/2026 DHWH #2 (Dual Operations) On-line HTHW
1/13/2026
12/9/2025. Placed On-line. HTHW Operation.
DHWH #3 (Dual Operations) Out of Service 1/12/2026 12/22/2025
3/28/2025 Secured Suppy and Return HTHW, suspect tube leak. removed head in preperation for tube inspection LO/TO #1875
Converter #1 (Dual Operations) On-line 1/13/2026 Monthly Change Over 12/23/2025 Converter #2 (Dual Operations) Stand-By 1/13/2026 Monthly Change Over 12/23/2025 Dual Temp Pump #1 Stand-By 1/13/2026 Dual Temp Pump #2 On-line 1/13/2026 Aux. Equipment: Chilled Water Pump On-line 1/13/2026 P-5 is now on year round per. PWD 4/6/22
DHWH #1 (Dual Operations) Stand-By 1/13/2026 Monthly Change Over 12/24/2025 DHWH #2 (Dual Operations) On-line 1/13/2026 Monthly Change Over 12/24/2025 Converter #1 (Dual Operations) Stand-By 1/13/2026 Monthly Change Over 12/24/2025 Converter #2 (Dual Operations) On-line 1/13/2026 Monthly Change Over 12/24/2025 Dual Temp Pump #1 On-line 1/13/2026 Dual Temp Pump #2 Stand-By 1/13/2026 Aux. Equipment: On-line 1/13/2026
DHWH #1 Out of Service 11/17/2025 VJFS2828466/GOVU1321FEB2025 VJFS2832030/ GOV30491687DHWH #2 On-line HTHW 1/13/2026 Monthly Change Over 9/30/2025
DHWH #3 (Dual Operations) On-line 1/13/2026 DHWH #4 (Dual Operations) Out of Service 11/17/2025 Swich From Steam To HTHW 11/17/2025 Converter #1 On-line 1/13/2026 Converter #2 Stand-By 1/13/2026 Aux. Equipment On-line 1/13/2026 Dual Temp Pump 1 On-line 1/13/2026 3/1/24 IQ: CLKHJF 1.22 work funded for in house, ordering material Dual Temp Pump 2 Stand-By 1/13/2026 7/5/24 IQ: CLLNFB 1.22 work funded for in house, ordering material
DHWH #1 Out of Service 12/26/2025 FWO Submitted 12/26/2025 DHWH #2 On-line HTHW 1/13/2026 Monthly Change Over 11/14/2025 DHWH #3 (Dual Operations) Stand-By 1/13/2026 Monthly Change Over 11/14/2025 DHWH #4 (Dual Operations) Out of Service 12/24/2025 12/16/2024 1/9/2024 Major- No redundancy for hthw or steam 05OCT21: Repair was funded to IAP at the end of their contract, but they turned the IQ RFP to replace #4 moved to FY24/Q1 and will need to be revisited Converter #1 Out of Service 12/24/2025 9/24/2025 1/8/2024 Impacts heating in Wing 8 12/9 #1 converter HTHW strainer leak LOTO W.O. Submitted.
Converter #2 On-line HTHW 1/13/2026 Online 11/14/2025
Aux. Equipment On-line 1/13/2026 Dual Temp Pump 1 Stand-By 1/13/2026 Dual Temp Pump 2 On-line 1/13/2026 9/5/23
Converter #1 Stand-By 1/13/2026 Monthly Change Over 12/26/2025 Converter #2 On-line 1/13/2026 Monthly Change Over 12/26/2025 Electric Reheat Boiler Off-Line for Summer 1/7/2026 Feeder W-6 On-line 1/13/2026 AHU 1 Out of Service 7/19/2025 WO1546624 Bad drive
102 Pool Converter Out of Service 5/8/2025 Removed during construction (LOTO #1506 HTHW)
DHWH # 1A Stand-By 1/13/2026 DHWH # 1B On-line 1/13/2026
MACDONOUGH
NORMAN SCOTT
MITCHER HALL - LEVY CENTER
WING 4
WING 5
WING 6
WING 7
WING 8
ACADEMIC / SUPPORT FACILITIES
MAHAN HALL
101-M
101-4
101-5
101-6
101-7
101-8
Heating Converter # 1A Stand-By 1/13/2026 Monthly Change Over 12/23/2025 Heating Converter # 1B On-line 1/13/2026 Monthly Change Over 12/23/2025 Pool Converter # 2A Stand-By 1/13/2026 Monthly Change Over 12/23/2025 Pool Converter # 2B On-line 1/13/2026 Monthly Change Over 12/23/2025
12/14/2025
12/14/2025
12/14/2025
Steam humidifier On-line 1/13/2026 Online for season 11/14/025 Softener PH 8.2 1/13/2026 Online for season 11/14/025 Softener conductivity 186.1 1/13/2026 Online for season 11/14/025 Softener (Hard/Soft) Soft 1/13/2026 Online for season 11/14/025 Converter #1 On-line 1/13/2026 SR23310659 proposal being sent 9.29 Converter #2 Out of Service 4/7/2025 LOTO #1812. Out Of Service For Repair. 9/4/2024 ESV bad packing leak, not rotating Converter #3 On-line 1/13/2026 Online for season 11/14/025 Electric Reheat boiler Out of Service 7/21/2025 Out Of Service For Inspection 7/21/2025 Gas Fired Reheat Boiler off -line 5/29/2025 Vcc 1 Chiller (Circuit A) Out-of-Service 5/5/2025 Waiting on RFP Moderate - With temps at lower levels Vcc 2 will be able to handle cooling requirements Vcc 1 chiller circuit A down known leak went compos for repair. Waiting on RFP
DHWH G-1 (Natural Gas Fired) On-line 1/13/2026 Inspection DHWH G-2 (Natural Gas Fired) On-line 1/13/2026 Recirc Pump And Flow switch Replaced 7/24/2025 Emergency DHWH (HTHW)
Out-of-Service 5/5/2025
Minimal - Unit is isolated from DHW system
- Unit removed 3161 lock are in place
Converter On-line 1/13/2026 Online for winter 11/10/2025
(2) Electric DHW Heaters Stand-by 1/13/2026 Aux. Equipment On-line 1/13/2026 Dual Temp Pump 1 Stand-by 1/13/2026 Dual Temp Pump 2 Stand-By 1/13/2026
DHW #1 On-line 1/13/2026 DHW #2 Non-Potable On-line 1/13/2026 2559790/ CP6KWV Converter #1 (Dual Operations) Out-of-Service 9/25/2025 CJNVWD SR23445565 Head Gasket Leak - LOTO #1653 RFP rcvd IDIQ to replace head gaskets sent 11/8, waiting funding Converter #2 (Dual Operations) On-line HTHW 1/13/2026 Laboratory Steam Generator Out-of-Service 2/28/2025 LO/TO #1853 for inspection Aux. Equipment On-line 1/13/2026 Motor Control Centers (MCC) On-line 1/13/2026
Converter On-line 1/13/2026 Electric water heater Stand-by 1/13/2026 Electric Reheat Boiler off -line 11/3/2025 AHU #7 Out-of-Service Bad shaft. Ordering parts from Trane
Converter #1 Stand-By 1/13/2026
Monthly Change Over 12/26/2025
Converter #2 On-line 1/13/2026 Monthly Change Over 12/26/2025 Gas Re-Heat Boiler 3rd Floor M.R. Stand-By 1/13/2026 New temperature sensors need to be Air Compressor #1 Out-of-Service 5/8/2025 18MAR24: Oil Leak, we are checking into the PM records-RM Air Compressor #2 On-line 1/13/2026 18MAR24: Mechanically limping along, we are checking into the PM records-RM
Converter On-line 1/13/2026 Electric Boiler Stand-By 1/13/2026 Aux. Equipment Stand-By 1/13/2026
DHWH #1 Stand-By 1/13/2026 Monthly Change Over 12/23/2025 HTHW control vlave work funded, ordering material DHWH #2 On-line
1/13/2026
Monthly Change Over 12/23/2025 HTHW control vlave work funded, ordering material
Electric Domestic Water Heater On-line 1/13/2026 Converter #1 Stand-By 1/13/2026 Monthly Change Over 12/30/2025 Converter #2 On-line 1/13/2026 Monthly Change Over 12/30/2025 Electric Boiler Stand-By 1/13/2026
#1 Converter On-line 1/13/2026 Online for Season.
#2 Converter Stand-By 1/13/2026 Off for Summer 4/4/25
Steam Reducing Station On-line 1/13/2026
Condensation line On-line 1/13/2026 11/3/23 23454827
A 12' section of pipe was removed and replaced due to Deterioration. This was replaced on 11/3/23.
RICKOVER HALL G49
ALUMNI HALL
WESLEY BROWN FIELD HOUSE
HOSPITAL CLINIC - Building 253
LEJEUNE HALL
PREBLE HALL
HALSEY FIELD HOUSE
RICKETTS HALL
MICHELSON HALL
NIMITZ LIBRARY
Chiller #4 Stand-By
12/28/2025 Per cooling transition meeting, 1 circuit needs repair. (WS)
LEJEUNE HALL HEATING EQUIP. Stand-By 1/13/2026 Domestic Hot Water #1 Stand-By 1/13/2026 Monthly Change Over 12/30/2025
Domestic Hot Water #2 On-Line 1/13/2026 Monthly Change Over 12/30/2025
Electric DHWH #1 Stand-By 1/13/2026 Electric DHWH #2 Stand-By 1/13/2026 Converter #1 On-line 1/13/2026 10/19/2025 Online 10/15/2025
Converter #2 On-line 1/13/2026 Online for Season
Converter #3 On-line 1/13/2026 Converter #4 Lap Pool On-line
1/13/2026
Converter #5 Dive Pool On-line 1/13/2026 IQ: CKRKDJ
Electric Boiler B-1 Dive Pool Stand-By 1/13/2026 Electric Boiler B-2 Lap Pool Stand-By 1/13/2026
Converter Out-of-Service 4/18/2024 O/S Bldg. Rehab / Equipment LO/TO #1765
Boiler #1 On-line 1/13/2026 SR23438334 Boiler #2 On-line 1/13/2026 Boiler #3 On-line 1/13/2026 Auxillary Equipment On-line 1/13/2026
Gas DHWH #1 On-line 1/13/2026 Gas DHWH #2 On-line 1/13/2026 Storage Tank #1 On-line 1/13/2026 Storage Tank #2 On-line 1/13/2026 Placed back in service. RH
Converter Stand-By 1/13/2026
Chiller: On-line 8/15/2024 System 1, Compressor 1 On-line 8/15/2024 System 1, Compressor 2 On-line 8/15/2024 System 1, Compressor 3 On-line 8/15/2024 System 2, Compressor 1 On-line 8/15/2024 System 2, Compressor 2 Out-of-Service TBD System 2, Compressor 3 Out-of-Service TBD
101-1 Bancroft Hall, exterior lift Out-of-Service 1/3/2024 1/15/24 IQ: CKZ9N3 work starting approx 1.8, one week to complete 101-3 Bancroft Hall, Wing 3: Passenger Out-of-Service 8/4/2023 10/31/23 IQ: CKLDH4 Elevator Upgrade Modification mod funded, vendor notified 101-7 Bancroft Hall, Wing 7: Handicap Lift Out-of-Service 4/5/2021 TBD Replacement to be scheduled 101-8 Bancroft Hall, Wing 8: Handicap Lift Out-of-Service 4/5/2021 TBD Replacement to be scheduled 105 Maury Hall: Passenger Out-of-Service 4/5/2021 TBD Construction Contractor Use Only 589 Nimitz Library: Passenger #1 Out-of-Service 4/5/2021 TBD Construction Contractor Use Only 590 Rickover Hall: Passenger #2 On-line 7/6/2023 6/30/23 Temp cert issued elevator in service, waiting final material to complete 675 Alumni Hall: Freight Out-of-Service 4/5/2021 06/04/21 Elevator Upgrade Modification 181 Halligan Hall: Handicap Lift Out-of-Service 5/17/2021 TBD WO# CFM6CC Lift requires the control board to be replaced. FWO requested 5/07/2021
675 Alumni Hall On-line 3/2/2025 3/2/25 04MAR245: Power supply failed-RM;
NA140 Mill Creek Pier (Possum Point) Out-of-Service 10/2/2024 12/31/24 10.2.24 project starting 10.4.24; Elliott H/Dexter managing 339NS Paint & Blasting Shop Out-of-Service 6/30/2023 TBD compOS: 550790 fire panel OOS, needs full replacement engineered as old system is no longer supported COMPOS sent PWD
276 PHYSICAL EDUCATION BUILDING Out-of-Service 1/24/2023 TBD fire panel OOS, needs full replacement engineered as old system is no longer supported needs to be re-engineered by PWD, system is not up to code
250 Old Naval Health Clinic Out-of-Service
4/5/2023 TBD 4.4.23 per LT Hunter, PMEB has commissioned new system--work to start in June 2023
Went down years ago-needs replacement building being rehabed by Navy subk starting 2023
NA298 Bachelors Enlisted Quarters Out-of-Service
4/5/2023 FY26
Went down years ago - directed to turn off by PWD: 17SEPT24: Demo slated in FY26-RM
101-K (rm C118) Galley Cook and Chill Hood System Out-of-Service
10/17/2023 11/17/23 SR22879540 Hoods 1, 2 3 & 4 did not pass PM inspection RFP rcvd IDIQ, Fireline to be here Nov 7-8/2023
321NS Old NEX Out-of-Service 4/5/2023 04/21/23 SR22649485 Fire panel needs replacement compos sent 3.31, pending IQ proposal
HOPPER HALL
HUBBARD HALL
LEAHY HALL
Ward Hall
BEACH HALL / USNI
VTE OUTAGES
Fire Alarm System Outages (systems that are OOC)
329NS NEX/Retail Out-of-Service
3/6/2023
3.2.23 per ACQ, will be part of larger project
FA failing, needs replacement
260 HUBBARD HALL: Row tank on-line 12/6/2024 151 WESLEY BROWN FIELDHOUSE cold plunge p on-line 9/9/2021 628 Lejeune Hall: Lap Pool On-line 9/9/2021 628 Lejeune Hall: Dive Pool on-line 12/27/2024
114 Norm Scott Pool: Polo Pool
On-line
8/29/2024
320A South Seven: Main Pool Off-line 8/8/2024 winterized 15OCT25 320B South Severn; Kidney Pool Off-line 8/8/2024 winterized 15OCT25 321 South Severn: Wading Pool Off-line 8/8/2024 3419806/ SR-080425-10:32-BH winterized 15OCT25, still waitng on new board for pool pump
160NS North Severn: Main Pool Off-line 8/8/2024 . winterized 15OCT25 160ANS North Severn: Wading Pool Off-line 8/8/2024 winterized 15OCT25
739 Radford Terrace Fountaim Off-line 8/8/2024 tbd CN4CYW/CN3VH6 taken off line to pressure test overflows and inspect for leaks,found both will overflows Alumni Fountain Off-line 8/8/2024 TBD 1763629/ CMHMXJ 22APR24: working on tempoarry solution for graduation and special events along with a permanent Lejeune Fountain Off-line 10/18/2024 winterized AK 11/12/25 Mitcher/Levy Fountian Off-line 8/8/2024 winterized BP 11/26/25
Worden Field Off-line 9/4/2025 Winterized 11/10/25 BP Stribling Off-line 9/4/2025 winterized BP 11/26/25 BP Lejeune Off-line 9/4/2025 winterized 11/12/25 BP Leahy Off-line 9/4/2025 vjfs# 3783107 SR# SR-111025-13:24-BH Placed in operation BP 4/2/25, isolation valve handel bent and will not turn off, will need to dig up and Farragut Field (Rip Miller Side) off-line 9/4/2025 winterized 11/26/25 BP Farragut Field (RCSC Side) Off-line 9/4/2025 winterized BP 11/12/25 Ingram Track Off-line 9/4/2025 winterized 11/12/25 BP Dewey (GWSF) Off-line 9/4/2025 winterized 11/12/25 BP Dewey (Practice 1) Off-line 9/4/2025 winterized 11/12/25 BP Dewey (Practice 2, IVO 13C-2) Off-line 9/4/2025 winterized 11/25/25 Sherman Field Off-line 9/4/2025 winterized 11/12/25 BP Halsey FH Off-line 9/4/2025 winterized 11/12/25 BP Old NHC right of circle Off-line 9/4/2025 winterized 11/12/25 BP Old NHC left of circle Off-line 9/4/2025 winterized 11/12/25 BP Larson Off-line 9/4/2025 winterized 11/12/25 BP Nimitz terrace deck Off-line 9/4/2025 winterized 11/12/25 BP Rickover terrace deck Off-line 9/4/2025 winterized 11/12/25 BP carter terrace deck Off-line 9/4/2025 winterized 11/12/25 BP Chapel Off-line 9/4/2025 winterized 11/10/25 BP sampson Off-line 9/4/2025 winterized 11/10/25 BP alumni Off-line 9/4/2025 winterized 11/10/25 BP smoke park wing 5 Off-line 9/4/2025 winterized 11/12/25 BP smoke park wing 6 Off-line 9/4/2025 winterized 11/12/25 BP Rickets off-line 9/4/2025 winterized 11/12/25 BP Hopper 1 lower off-line 9/4/2025 winterized 11/12/25 BP Hopper 2 upper off-line 9/4/2025 winterized 11/12/25 BP Gate 1 Off-line 9/4/2025 winterized 11/12/25 BP alumni drinking fountian college ceek side off-line 9/4/2025 winterized 11/12/25 BP worden field drinking fountian Off-line 9/4/2025 winterized 11/10/25 BP ward hall Off-line 9/4/2025 winterized 11/26/25 BP soft ball field Off-line 9/4/2025 winterized 11/10/25 BP drinking fountion by prebel Off-line 9/4/2025 winterized 11/10/25 BP
Navy Lodge Off-line 9/4/2025 winterized 11/24/25 NHC Off-line 9/4/2025 winterized 11/24/25 Golf Shop at BSC Off-line 9/4/2025 winterized 11/14/25 BP Rugby Field BSC Off-line 9/4/2025 winterized 11/14/25 BP rugby field driving range Off-line 9/4/2025 winterized 11/14/25 BP MWR soft ball field by pool Off-line 9/4/2025 winterized 11/14/25 BP NEX Off-line 9/4/2025 Winterized 11/24/25 MWR soft ball field retelle room Off-line 9/4/2025 winterized 11/14/25 BP
Bishop stadium Off-line 9/4/2025 winterized 11/26/25 BP Worden field bath house Off-line 9/4/2025 winterized 11/26/25 BP Ingram Track bath house Off-line 9/4/2025 winterized 11/26/25 BP South Serven Pool Bath Hosue Off-line 9/4/2025 winterized 11/24/25 Drinking Fountians between Alumni and CarterOff-line 9/4/2025 wintrerized BP 11/10/25 Santee Basin Off-line 9/4/2025 3867473/CSJMXN 11/28/25 drained system, need to wait for antifreeze to come in to fill cht system.
Drinking Fountian Worden field off-line 9/4/2025 wintrerized BP 11/10/25
North ServernPpool Bath House Off-line 9/4/2025 Winterized 11/24/25 Retelle Room Off-line 9/4/2025 Winterized 11/24/25 YP Seawall Dock Off-line 9/4/2025 Winterized 11/24/25 Carr Creek Marina Off-line 9/4/2025 winterized 11/24/25 Mill Creek Pier (Possum Point) off-line 9/4/2025 winterized 12/1/25
USNA Irrigation Systems (UEM)
USNS Irrigation Systems
USNA Seasonal Buildings
USNS Seasonal Buildings
NSAA Pools
USNA Outdoor Fountains
Scheduled Utility Outages Approved:
Wednesday 14 January
* There are no utility outages scheduled for today.
Thursday 15 January
Wednesday 21 January
Thursday 22 January
New * Request 5993- Steam Outage for Bldg.114 Norm Scott Natatorium and Bldg. 102 Macdonough Hall USNA-102 from 0600-0900. Outage is to install a new steam pressure sensor.
Road/Parking Spaces Closures Approved:
Tuesday 3 November
Monday 5 January
* Request 760- Bldg. 275 Loading Dock Area and the Parking Spaces Closure from 0700 - 1600 on Friday, March 6, 2026. This is to place dumpsters in the loading dock area for the carpet removal at Bldg. 291 USNI Beach Hall.
Monday 12 January
New * Request 5980- Electrical Power Outage for Bldg. 46NS Marine Barracks, Bldg. 58NS Admin with the building generator providing backup emergency power to 58NS, Bldg. 2NS Armory, Bldg. 89NS Recreation/Gym from 2300-0500. Outage is to perform preventative maintenance on the transformers and associated equipment in Substation TS-28 & TS-28A.
* Request 5981- Electrical Power Outage for Bldg. 103 Dahlgren Hall the permanently installed generator will provide backup power to the emergency circuits from 2200-0500. Outage is to perform preventative maintenance on the transformers and associated equipment in Substation TS-76.
New * Request 5997- Water Outage Hot and Cold for Bldg. NA687 Brigade Sprots Complex from 0001-0500. Outage is for the contractor to tie-in the water supply to the building water main. Work Order #CTVSML issued to VJFS to provide the assistance as requested to secure the water and to provide access to the sprinkler room and restore the water once this work is complete.
* Request 752- Parking Lot between Wing 8 Parking Lot and Bldg. 628 Lejeune Hall, known as the Stone Lot from 0730 - 1600 on Friday, January 30, 2026. This is for the contractor working the Bldg. 628 Lejeune Roof Project staging the materials, equipment, scaffolding, stair tower to complete the roof overlay.
* Request 762- Parking Spaces four to be blocked for a laydown area to store the new pavers from 0700 - 1600 on Monday, January 26, 2026. This is for the new pavers that are being replaced at Bldg. 572 Michelson, Chauvenet, Bldg. 590 Rickover Hall and Bldg. 589 Nimtz. This work is under VJFS W/O #CS3Y3M.
Pending Approval Utility Outages:
Thursday 22 January
Tuesday 27 January
VJFS W/O #CSHWX9, VJFS #3763697.
Pending Approval Road/Parking Spaces Closures:
* There is no scheduled Pending Approval Road/Parking Spaces Closures at this time.
* Request 5979- Electrical Power Outage for Bldg. 336NS Storage, Shore Power, Reach A Contractor's Construction Trailers from 0100-0400. Outage is to perform preventative maintenance on the transformers and associated equipment in Substation TS-24 & PS-24.
New * Request 5995- Heating Hot Water Outage for Bldgs. 252, 250, 251, 276, 275 all of the 250 complex. Note this will only be performed based on the weather/outside temperature from 0600-1600. Outage is to replace a isolation valve, check valve and to move the pump. This work is under
* Request 5996- Electrical Power Outage for Smoke Hall at Bancroft Hall and Rotunda at Bancroft Hall from 0500-0900. The outage is to remove temporary power for lights. Work Order #CTT364 issued to VJFS to provide the assistance as requested to open the high voltage room TS- 9 in the Center Section for the contractor. PDCB contractor will be turning the power off and performing LOTO to Electrical Panels C1A (LS) & C1A (RS) in the Rotunda.
Forecast Discussion:
Interested parties are advised to check back on Wednesday for the next regular forecast and monitor updates from the National Weather Service at https://www.weather.gov/lwx.
Weather Forecast:
Monday: Sunny and seasonable. West wind 10-15 mph. High near 45 oF.
Tuesday: Sunny and seasonable. South wind 5-10 mph. Low: 28-32 oF. High: 44-48 oF.
Wednesday: Sunny and mild with a chance for rain showers in the evening and overnight (50% chance). Light snow showers could mix-in late overnight. Southwest wind 5-10 mph. Low: 34-38 oF. High: 46-50 oF.
Thursday: Overcast and breezy with rain and/or…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .