J-1502000.1-03 DHA ASSET DATA INDEX, SYSTEM DESCRIPTIONS AND ASSET DATA BY SYSTEM.xlsx
XLSX spreadsheet 430 KB Posted
- Attached to
- Base Operations Support Services For NSA Annapolis and US Naval Academy, Annapolis, Maryland
- Solicitation number
- N6247026R0017
About this file
This file is a data index and system asset inventory spreadsheet that catalogs Defense Health Agency (DHA) assets and their associated system descriptions. The document serves as a reference tool mapping various DHA systems, their classifications, and related asset data, organized in a structured tabular format for asset management and tracking purposes. While the specific asset categories and system details are contained within the spreadsheet, this file functions as a supporting reference document rather than as a primary solicitation requirement specification. The index appears designed to support asset inventory management and system documentation for the Defense Health Agency's operational infrastructure.
This file is supplementary reference material related to the Base Operations Support Services presolicitation for NSA Annapolis and US Naval Academy in Annapolis, Maryland (Solicitation N6247026R0017). The actual solicitation and final requirements documents are expected to be posted by the Naval Facilities Engineering Command on or after November 30, 2026, with potential revisions to occur prior to final posting. Contractors interested in this opportunity should monitor the official solicitation release for definitive scope of work, performance requirements, evaluation criteria, and submission deadlines.
View the file
Other files
Show 40 more
Latest 50 of 86 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
J-1502000.1-03-01 INDEX
ATTACHMENT J-1502000.1-03-01
INDEX
| SPEC ITEM | ATTACHMENT NUMBER AND TITLE |
| RECURRING WORK | |
| 3 | J-1502000.1-03-02 SYSTEM DESCRIPTIONS |
| INTEGRATED MAINTENANCE PROGRAM | |
| 3.3.1 | J-1502000.1-03-03 (IMP) LIGHTING SYSTEMS ASSET DATA |
| 3.3.2 | J-1502000.1-03-04 (IMP) PHOTOVOLTAIC ENERGY SYATEMS ASSET DATA |
| 3.3.3 | J-1502000.1-03-05 (IMP) SOLAR WATER HEATING SYSTEMS ASSET DATA |
| 3.3.4 | J-1502000.1-03-06 (IMP) LIGHTNING PROTECTION SYSTEMS ASSET DATA |
| 3.3.5 | J-1502000.1-03-07 (IMP) FIRE PROTECTION SYSTEMS ASSET DATA |
| 3.3.6 | J-1502000.1-03-08 (IMP) VERTICAL TRANSPORTATION EQUIPMENT (VTE) ASSET DATA |
| 3.3.7 | J-1502000.1-03-09 (IMP) COMPRESSED AIR, MEDICAL AIR, GAS, AND VACUUM SYSTEMS ASSET DATA |
| 3.3.8 | J-1502000.1-03-10 (IMP) AUXILIARY GENERATOR SYSTEMS ASSET DATA |
| 3.3.9 | J-1502000.1-03-11 (IMP) UNINTERRUPTED POWER SYSTEMS (UPS) ASSET DATA |
| 3.3.10 | J-1502000.1-03-12 (IMP) PUMP SYSTEMS ASSET DATA |
| 3.3.11 | J-1502000.1-03-13 (IMP) PUBLIC ANNOUNCEMENT (PA) SYSTEMS ASSET DATA |
| 3.3.12 | J-1502000.1-03-14 (IMP) ROOF AND DRAINAGE SYSTEMS ASSET DATA |
| 3.3.13 | J-1502000.1-03-15 (IMP) MANUAL AND AUTOMATED DOOR SYSTEMS ASSET DATA |
| 3.3.14 | J-1502000.1-03-16 (IMP) ROLL-UP DOOR AND WINDOW SYSTEMS ASSET DATA |
| 3.3.15 | J-1502000.1-03-17 (IMP) HVAC AND REFRIGERATOR SYSTEMS ASSET DATA |
| 3.3.16 | J-1502000.1-03-18 (IMP) CONTROL SYSTEMS ASSET DATA |
| 3.3.17 | J-1502000.1-03-19 (IMP) CYBERSECURITY SYSTEMS INVENTORY |
| 3.3.18 | J-1502000.1-03-20 (IMP) BOILER AND UNFIRED PRESSURE VESSEL (UPV) SYSTEMS ASSET DATA |
| 3.3.19 | J-1502000.1-03-21 (IMP) CHILLER AND DISTRIBUTION SYSTEMS ASSET DATA |
| INSPECTION, TESTING, AND CERTIFICATION | |
| 3.4.1 | SEE ATTACHMENT J-1502000.1-03-05 TJC ENVIRONMENT OF CARE INSPECTION, TESTING, AND DOCUMENTATION REQUIREMENTS |
| 3.4.2 | J-1502000.1-03-22 (ITCP) BOILER AND UNFIRED PRESSURE VESSEL (UPV) SYSTEMS ASSET DATA |
| 3.4.3 | J-1502000.1-03-23 (ITCP) BACKFLOW PREVENTION DEVICE SYSTEMS ASSET DATA |
| 3.4.4 | J-1502000.1-03-24 (ITCP) VERTICAL TRANSPORTATION EQUIPMENT (VTE) ASSET DATA |
| OTHER RECURRING SERVICES | |
| 3.5.1 | J-1502000.1-03-25 (ORS) NAVAL HEALTH CLINIC AUXILIARY GENERATOR SYSTEMS ASSET DATA |
| 3.5.2 | J-1502000.1-03-26 (ORS) PLASTER TRAP SERVICES ASSET DATA |
| 3.5.3 | J-1502000.1-03-27 (ORS) EXHAUST HOOD AND DUCT SYSTEMS ASSET DATA |
| 3.5.4 | J-1502000.1-03-28 (ORS) MECHANICAL ROOM ASSET DATA |
| 3.5.5 (1) | J-1502000.1-03-29 (ORS) HVAC SYSTEMS SEASONAL STARTUP AND SHUTDOWN ASSET DATA |
| 3.5.5 (2) | J-1502000.1-03-30 (ORS) HVAC GLYCOL SYSTEMS ASSET DATA |
| 3.5.6 | J-1502000.1-03-31 (ORS) HVAC WATER TESTING AND TREATMENT SYSTEMS ASSET DATA |
| 3.5.7 | J-1502000.1-03-32 (ORS) BOILER & STEAM EQUIPMENT SYSTEMS SEASONAL START-UP AND SHUTDOWN ASSET DATA |
| 3.5.8 | J-1502000.1-03-33 (ORS) IRRIGATION SYSTEMS SEASONAL START-UP AND SHUTDOWN ASSET DATA |
| 3.5.9 | J-1502000.1-03-34 (ORS) NAVAL HEALTH CLINIC SEWER LINE SERVICES ASSET DATA |
| 3.5.10 | SEE ATTACHMENT J-1502000.1-04 DHA FACILITY DATA |
J-1502000.1-03-02
ATTACHMENT J-1502000.1-03-02
SYSTEM DESCRIPTIONS
| SPEC ITEM | SYSTEM DESCRIPTION |
| INTEGRATED MAINTENANCE PROGRAM | |
| 3.3.1 | Lighting Systems commence at and include the utility isolation point of connection. Lighting Systems include, but are not limited to all mechanically and electrically interlocked ancillary parts, equipment, and components of the Lighting Systems, such as: bulbs, batteries, lamps, tubes, ballasts, fuses, starters, switches, diffusers, covers, lenses, globes, domes, trims, poles, reflectors, photocells, controls, etc. Lighting System fixture types include, but are not limited to area lighting, architectural lighting, security lighting, exit and emergency lighting, athletic lighting, high-bay lighting, street lighting, parking lot lighting, field lighting, safety/security lighting, landscape lighting, and traffic signals. |
| 3.3.2 | Photovoltaic Energy Systems commence at and include the utility isolation point of connection. Photovoltaic Energy systems include, but are not limited to circulation pumps, PV modules and panels, thermostats, valves, limit control devices, all interconnection wirings, mounting systems, transformers, and energy storage units such as batteries and charge controllers, monitoring units, and all ancillary infrastructure, etc. |
| 3.3.3 | Solar Water Heating Systems commence at and include the utility isolation point of connection. Solar Water Heating Systems include, but are not limited to circulation pumps, PV modules and panels, thermostats, valves, limit control devices, all interconnection wirings, mounting systems, transformers, and energy storage units such as batteries and charge controllers, monitoring units, and all ancillary infrastructure, etc. |
| 3.3.4 | Lightning Protection Systems commence at and include the utility isolation point of connection and terminate at foundation. Lightning Protection Systems include, but are not limited to all mechanically and electrically interlocked ancillary parts, equipment, and components to include: grounding system, cabling, fasteners, air terminals (lightning rods), conductors, plates, bonding, interconnection, surge protection devices, etc. |
| 3.3.5 | Fire Protection Systems commence at and include the utility isolation point of connection. Fire Protection Systems include, but are not limited to all mechanically and electrically interlocked ancillary parts, equipment and components such as: non-PFAS containing foam concentrates, air compressors, alarm devices, antennas, backflow prevention devices, batteries, connections, detectors, diesel engines, electric motors, fuses, gauges, initiating devices, meters, nozzles, pumps, receivers, sensors, tanks, transmitters, voice communication devices, monitoring, reporting and controls systems, detectors, sensors, notification appliances (horns, strobes, speakers, voice communication devices), control panels (fire alarm, releasing, booster, annunciating), mag locks, fuses, gauges, meters, connections, nozzles, sprinkler heads, piping (main and branch lines), pipe fittings, valves (check, alarm, post indicator, wet, dry, pre-action, etc.), test and drain assemblies, fire department connections (FDCs), dry chemical and wet chemical systems, switches, and related equipment, etc. |
| 3.3.6 | Vertical Transportation Equipment Systems commence at and include the utility isolation point of connection. Vertical Transportation Equipment Systems include, but are not limited to all mechanically and electrically interlocked ancillary parts, equipment, and components of the Vertical Transportation Equipment Systems, such as: doors, cars, tracks, lighting, rails, guides, governors, motors, cables, pulleys, switches, hydraulic cylinders, piping, pumps, tanks, weights, monitoring, communication, control systems, electrical disconnects, etc. |
| 3.3.7 | Compressed Air, Medical Air, Gas, and Vacuum Systems commence at and include the utility isolation point of connection and terminate at the compressed air point of delivery. Compressed Air Systems include, but are not limited to all mechanically and electrically interlocked ancillary parts, equipment, and components of the Compressed Air Systems, such as: compressors, regulators, unfired pressure vessels, air drying systems, distribution systems, air supply connectors, monitoring and control systems, electrical disconnects, etc. |
| 3.3.8 | Auxiliary Generator Systems commence at and include the utility isolation point of connection. Auxiliary Generator Systems to include, but are not limited to all mechanically and electrically interlocked ancillary parts, equipment, and components of the Auxiliary Generator Systems, such as: batteries, fuel tanks, engines, inverters, rectifiers, regulators, prime mover, pumps, piping, transfer switches, switchgear, meters, monitoring and control systems, cooling, exhaust, displays, doors, seals, uninterruptible power supply, wiring, connections, etc. |
| 3.3.9 | UPS Systems include but are not limited to all mechanically and electrically interlocked ancillary parts, equipment, and components of the systems, such as: inverters, static switches, bypass switches, transformers, batteries, battery management systems, chargers, control panels, monitoring devices, wiring, conduit, cooling, filters, protective relays, and enclosures. |
| 3.3.10 | Pump Systems commence at and include the utility isolation point of connection. Pump Systems include but are not limited to all mechanically and electrically interlocked ancillary parts, equipment, and components of the systems, such as: pump casings, impellers, bearings, seals, shafts, couplings, motors, drives, bases, strainers, suction and discharge piping, valves, gauges, flow meters, vibration isolators, controls, starters, variable frequency drives (VFDs), wiring, etc. |
| 3.3.11 | Public Announcement (PA) Systems commence at, and include, the utility isolation point of connection. PA Systems include but are not limited to: microphones, amplifiers, mixers, paging controllers, speakers, horns, cabling, junction boxes, racks, mounts, brackets, power supplies, batteries, network interfaces, etc. |
| 3.3.12 | Roof and Drainage Systems consist of all integrated components that protect a building from the elements to include the primary roof covering, underlayments, ventilation, flashng and drainage components. The roof drainage system includes, but is not limited to grates, gutters, internal and external downspouts, piping, splash blocks, and drainage pathways. |
| 3.3.13 | Manual and Automated Door Systems include but are not limited to all mechanically and electrically interlocked ancillary parts, equipment, and components of the systems, such as: door leaves, frames, hinges, pivots, closers, operators, sensors, push plates, actuators, locks, keys, latches, strikes, thresholds, seals, glazing to include transoms and sidelites, weather-stripping, control panels, power supplies, wiring, safety devices, alarms, and monitoring systems. |
| 3.3.14 | Roll-Up Door and Window Systems include but are not limited to all mechanically and electrically interlocked ancillary parts, equipment, and components of the Roll-Up Doors and Windows, such as: motors, gears, bearings, springs, hinges, guides, tracks, rollers, seals, weather-stripping, operators, control panels, limit switches, sensors, emergency release mechanisms, screens, panels, covers, fasteners, glazing, handles, locks, keys, etc. |
| 3.3.15 | HVAC and Refrigeration Systems commence at, and include, the utility isolation point of connection and terminate at the point of air delivery. HVAC and Refrigeration Systems include, but are not limited to all mechanically and electrically interlocked ancillary parts, equipment, and components of the HVAC and Refrigeration Systems such as: air handling units, blowers, boilers, chillers, compressors, condensers, controls, cooling towers, dehumidifiers, diffusers, driers, ducts, electrical disconnects, evaporators, fans, fan coil units, filters, fire dampers, fresh air dampers, heaters, heat exchangers, heat pumps, hoods, humidification systems, insulation, intakes, package units, piping, pumps, refrigeration boxes, registers, returns, strainers, ultraviolet lighting, valves, VAV boxes, variable frequency drives, water treatment systems, monitoring and pneumatic and electronic control systems including the EMCS. |
| 3.3.16 | Control Systems may be pneumatic or electronic and commence at, and include, the utility isolation point of connection. Control Systems include, but are not limited to controllers, sensors, actuators, relays, control panels, user interfaces, servers, monitoring devices, network switches, communication cabling, software, graphics, databases, trend logs, alarms, power supplies, UPS units, etc. |
| 3.3.17 | Boiler and UPV Systems commence at, and include, the utility isolation point of connection and terminate at the steam/hot water point of delivery. Boiler and UPV System include, but are not limited to all mechanically and electrically interlocked ancillary parts, equipment, and components of the Boiler and UPV Systems, such as: burners, heat exchangers, flash tanks, meters, pressure vessel, pumps, piping, valves, steam regulating valves, steam traps, distribution lines, insulation, chemical feed system, condensation return lines, condensate meters, monitoring and controls systems, etc. |
| 3.3.18 | Chiller and Distribution Systems commence at, and include, the utility isolation point of connection and terminate at the delivery point. Chiller and Distribution Systems include, but are not limited to all ancillary parts, equipment, and components; chillers, compressors, condensers, evaporators, pumps, motors, bearings, couplings, seals, strainers, valves, expansion tanks, piping, insulation, gauges, sensors, flow meters, controls, variable frequency drives, cooling towers, fans, belts, gearboxes, water treatment systems, etc. |
| INSPECTION, TESTING, AND CERTIFICATION | |
| 3.4.1 | NOT APPLICABLE |
| 3.4.2 | Boiler and UPV Systems commence at, and include, the utility isolation point of connection and terminate at the steam/hot water point of delivery. Boiler and UPV System include, but are not limited to all mechanically and electrically interlocked ancillary parts, equipment, and components of the Boiler and UPV Systems, such as: burners, heat exchangers, flash tanks, meters, pressure vessel, pumps, piping, valves, steam regulating valves, steam traps, distribution lines, insulation, chemical feed system, condensation return lines, condensate meters, monitoring and controls systems, etc. |
| 3.4.3 | Backflow Prevention Devices commence at, and include, the utility isolation point of connection. Backflow Prevention Systems include, but are not limited to all ancillary components, double check valve assemblies, reduced pressure zone devices, pressure vacuum breakers, check valves, relief valves, shutoff valves, strainers, test cocks, gauges, piping, enclosures, drains, etc. |
| 3.4.4 | Vertical Transportation Equipment Systems commence at and include the utility isolation point of connection. Vertical Transportation Equipment Systems include, but are not limited to all mechanically and electrically interlocked ancillary parts, equipment, and components of the Vertical Transportation Equipment Systems, such as: doors, cars, tracks, lighting, rails, guides, governors, motors, cables, pulleys, switches, hydraulic cylinders, piping, pumps, tanks, weights, monitoring, communication, control systems, electrical disconnects, etc. |
| OTHER RECURRING SERVICES | |
| 3.5.1 | Auxiliary Generator Systems commence at and include the utility isolation point of connection. Auxiliary Generator Systems to include, but are not limited to all mechanically and electrically interlocked ancillary parts, equipment, and components of the Auxiliary Generator Systems, such as: batteries, fuel tanks, engines, inverters, rectifiers, regulators, prime mover, pumps, piping, transfer switches, switchgear, meters, monitoring and control systems, cooling, exhaust, displays, doors, seals, uninterruptible power supply, wiring, connections, etc. |
| 3.5.2 | Plaster Trap Systems include, but are not limited to trap bodies, inlet and outlet piping, baffles, flow control devices, strainers, seals, gaskets, covers, manways, drains, vents, sensors, and monitoring devices, etc. |
| 3.5.3 | Exhaust Hoods and Duct Systems commence at, and include, the points of intake and exhaust. Exhaust Hoods and Duct Systems include, but are not limited to hoods, ductwork, grease filters, fans, belts, motors, bearings, dampers, sensors, controls, access panels, fire suppression and monitoring, seals, insulation, and drains, etc. |
| 3.5.4 | Mechanical Room Systems commence at the point of entry. Mechanical Room Systems include, but are not limited to all pathways, points of ingress/egress, flooring, ceiling, piping (steam, condensate, chilled water, domestic water, sewer, gas, etc.), valves, pumps, expansion joints, insulation, conduit, cabling, junction boxes, lighting, ventilation systems, ductwork, thermostats, drains, sumps, structural supports, access hatches, ladders, fire stopping, leak detection systems, and monitoring devices, etc. |
| 3.5.5 | HVAC and Refrigeration Systems commence at, and include, the utility isolation point of connection and terminate at the point of air delivery. HVAC and Refrigeration Systems include, but are not limited to all mechanically and electrically interlocked ancillary parts, equipment, and components of the HVAC and Refrigeration Systems such as: air handling units, blowers, boilers, chillers, compressors, condensers, controls, cooling towers, dehumidifiers, diffusers, driers, ducts, electrical disconnects, evaporators, fans, fan coil units, filters, fire dampers, fresh air dampers, heaters, heat exchangers, heat pumps, hoods, humidification systems, insulation, intakes, package units, piping, pumps, refrigeration boxes, registers, returns, strainers, ultraviolet lighting, valves, VAV boxes, variable frequency drives, water treatment systems, monitoring and pneumatic and electronic control systems including the EMCS. |
| 3.5.6 | HVAC Equipment Systems receiving water treament include heat exchangers, chillers and boilers, colling towers, piping, valves, pumps, etc. Water Treatment programs may include closed loops, open/condenser loops, Glycol systems, etc. Water Testing Equipment includes colorimeters / photmeters for testing, pH and conductivity meters for testing, dip slides, corrosion coupons, etc. Water Treatment components include chemical feed pumps, chemical mix tanks, water meters (contact head), controllers, probes, blowdown solenoid valves. etc. |
| 3.5.7 | Facility Boiler Steam Equipment Systems receiving seasonal start-up and shutdown include waterfeed devices, level controls, vents and drains, fuel train components, draft fans, safety valves, circulation pumps, thermostats, power, fuel valves, main steam stop/crown valves, blowdown valves, draft dampers, layup (wet vs. dry strategy) for shut-down period. |
| 3.5.8 | Irrigation Systems commence at, and include, the utility isolation point of connection. The Irrigation System includes, but is not limited to pumps, piping, valves, controllers, sensors, backflow preventers, filters, heads, nozzles, drip lines, manifolds, wiring, and monitoring devices, etc. |
| 3.5.9 | NOT APPLICABLE |
| 3.5.10 | NOT APPLICABLE |
J-1502000.1-03-03
ATTACHMENT J-1502000.1-03-03
LIGHTING SYSTEMS ASSET DATA
| MUIC | Location | Asset Number | Description | Master System | System | Sub-System | Quantity | UOM | Additional Location Info |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | SV695NS-LGTEX-01-A | EXTERIOR LIGHTING SYSTEM | D50 - ELECTRICAL | D5020 - LIGHTING & BRANCH WIRING | D5020903 - EXTERIOR LIGHTING | 1 | EA | INCLUDING BUT NOT LIMITED TO: WALL PACK FLOOD |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | SV695NS-LGTI-01-A | INT LIGHTING SYSTEM - APPROX 10,000 SF BASEMENT, APPROX 7'-12' CEILING HEIGHTS | D50 - ELECTRICAL | D5020 - LIGHTING & BRANCH WIRING | D5020903 - EXTERIOR LIGHTING | 1 | EA | INCLUDING BUT NOT LIMITED TO: OFFICES, MECHANICAL ROOM, ELECTRICAL ROOM, COMMUNICATION ROOM, LABS, RESTROOMS, LOADING DOCK. INCLUDING BUT NOT LIMITED TO: CIRCULAR LEDs, 2X2 TUBE LED, 2X4 TUBE LED, RECESSED LIGHTS, PERIMETER LIGHTS, DOME LIGHTS |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | SV695NS-LGTI-02-A | INT LIGHTING SYSTEM - APPROX 50,800 SF FIRST FLOOR, APPROX 8'-40' CEILING HEIGHTS | D50 - ELECTRICAL | D5020 - LIGHTING & BRANCH WIRING | D5020903 - EXTERIOR LIGHTING | 1 | EA | INCLUDING BUT NOT LIMITED TO: EXAM ROOMS, LABS, RESTROOMS, LOUNGES, STORAGE. INCLUDING BUT NOT LIMITED TO: CIRCULAR LEDs, 2X2 TUBE LED, RECESSED LIGHTS, PERIMETER LIGHTS, DOME LIGHTS |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | SV695NS-LGTI-03-A | INT LIGHTING SYSTEM - APPROX 40,798 SF SECOND FLOOR, APPROX 7'-10' CEILING HEIGHTS | D50 - ELECTRICAL | D5020 - LIGHTING & BRANCH WIRING | D5020903 - EXTERIOR LIGHTING | 1 | EA | INCLUDING BUT NOT LIMITED TO: EXAM ROOMS, LABS, RESTROOMS, LOUNGES, STORAGE. INCLUDING BUT NOT LIMITED TO: CIRCULAR LEDs, 2X2 TUBE LED, RECESSED LIGHTS |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | SV695NS-LGTM-01-A | EMERGENCY & EXIT LIGHTING SYSTEM - APPROX 10,000 SF BASEMENT, APPROX 7'-12' CEILING HEIGHTS | D50 - ELECTRICAL | D5020 - LIGHTING & BRANCH WIRING | D5020903 - EXTERIOR LIGHTING | 1 | EA | INCLUDING BUT NOT LIMITED TO: OFFICES, MECHANICAL ROOM, ELECTRICAL ROOM, COMMUNICATION ROOM, LABS, RESTROOMS, LOADING DOCK. INCLUDING BUT NOT LIMITED TO: LIGHTED EXIT SIGNS AND FLOOD LIGHTS |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | SV695NS-LGTM-02-A | EMERGENCY & EXIT LIGHTING SYSTEM - APPROX 50,800 SF FIRST FLOOR, APPROX 8'-40' CEILING HEIGHTS | D50 - ELECTRICAL | D5020 - LIGHTING & BRANCH WIRING | D5020903 - EXTERIOR LIGHTING | 1 | EA | INCLUDING BUT NOT LIMITED TO: EXAM ROOMS, LABS, RESTROOMS, LOUNGES, STORAGE. INCLUDING BUT NOT LIMITED TO: LIGHTED EXIT SIGNS AND FLOOD LIGHTS |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | SV695NS-LGTM-03-A | EMERGENCY & EXIT LIGHTING SYSTEM - APPROX 40,798 SF SECOND FLOOR, APPROX 7'-10' CEILING HEIGHTS | D50 - ELECTRICAL | D5020 - LIGHTING & BRANCH WIRING | D5020903 - EXTERIOR LIGHTING | 1 | EA | INCLUDING BUT NOT LIMITED TO: EXAM ROOMS, LABS, RESTROOMS, LOUNGES, STORAGE. INCLUDING BUT NOT LIMITED TO: LIGHTED EXIT SIGNS AND FLOOD LIGHTS |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695A | SV695ANS-LGTEX-01-A | EXTERIOR LIGHTING SYSTEM | D50 - ELECTRICAL | D5020 - LIGHTING & BRANCH WIRING | D5020903 - EXTERIOR LIGHTING | 1 | EA | INCLUDING BUT NOT LIMITED TO: WALL PACK FLOOD |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695A | SV695ANS-LGTI-01-A | INT LIGHTING SYSTEM - APPROX 240 SF APPROX 7'-12' CEILING HEIGHTS | D50 - ELECTRICAL | D5020 - LIGHTING & BRANCH WIRING | D5020903 - EXTERIOR LIGHTING | 1 | EA | INCLUDING BUT NOT LIMITED TO: HEALTH CLINIC FIRE PUMP HOUSE. INCLUDING BUT NOT LIMITED TO: CIRCULAR LEDs, 2X2 TUBE LED |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695A | SV695ANS-LGTM-01-A | EMERGENCY & EXIT LIGHTING SYSTEM - APPROX 240 SF APPROX 7'-12' CEILING HEIGHTS | D50 - ELECTRICAL | D5020 - LIGHTING & BRANCH WIRING | D5020903 - EXTERIOR LIGHTING | 1 | EA | INCLUDING BUT NOT LIMITED TO: HEALTH CLINIC FIRE PUMP HOUSE. INCLUDING BUT NOT LIMITED TO: LIGHTED EXIT SIGNS AND FLOOD LIGHTS |
J-1502000.1-03-04
ATTACHMENT J-1502000.1-03-04
PHOTOVOLTAIC ENERGY SYSTEMS ASSET DATA
| MUIC | Location | Asset Number | Description | Master System | System | Sub-System | Quantity | UOM | Additional Location Info |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NA695-SOL-01-A | PHOTOVOLTAIC ENERGY SYSTEM | D50 - ELECTRICAL | D5090 - OTHER ELECTRICAL SYSTEMS | D5090999 - OTHER | 1 | EA | ROOFTOP |
J-1502000.1-03-05
ATTACHMENT J-1502000.1-03-05
SOLAR WATER HEATING SYSTEMS ASSET DATA
| MUIC | Location | Asset Number | Description | Master System | System | Sub-System | Quantity | UOM | Additional Location Info |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-SOL-02-A | SOLAR WATER HEATING ARRAY - 15 PANEL | D30 - HVAC | D3020 - HEAT GENERATING SYSTEMS | D3020999 - OTHER | 1 | EA | ROOF OF NS HEALTH CLINIC |
J-1502000.1-03-06
ATTACHMENT J-1502000.1-03-06
LIGHTNING PROTECTION SYSTEMS ASSET DATA
| MUIC | Location | Asset Number | Description | Master System | System | Sub-System | Quantity | UOM | Additional Location Info |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | SVNA695-LAR-01 | LIGHTNING PROTECTION & GROUNDING SYSTEM | D50 - ELECTRICAL | D5090 - OTHER ELECTRICAL SYSTEMS | D5090902 - LIGHTNING PROTECTION (ARRESTERS) | 1 | EA | HEALTH CLINIG LIGHTNING PROTECTION & GROUNDING SYSTEM |
J-1502000.1-03-07
ATTACHMENT J-1502000.1-03-07
FIRE PROTECTION SYSTEMS ASSET DATA
| MUIC | Location | Asset Number | Description | Master System | System | Sub-System | Quantity | UOM | Additional Location Info |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-FIRE-01-A | FIRE ALARM SYSTEM 101,598SF | D50 - ELECTRICAL | D5030 - COMMUNICATION AND SECURITY | D5030911 - FIRE ALARM CONTROL PANEL & ALARM SYSTEM | 1 | EA | THROUGHOUT BUILDING |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-FPS-01-A | FIRE PROTECTION SYSTEM WET 101,598SF | D40 - FIRE PROTECTION | D4010 - SPRINKLERS | D4010410 - WET PIPE SYSTEMS | 1 | EA | THROUGHOUT BUILDING |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695A | NANA695A-FP-01-A | FIRE PROTECTION PACKAGED PUMP SYSTEM | D40 - FIRE PROTECTION | D4010 - SPRINKLERS | D4010905 - FIRE PUMP, ELECTRIC MOTOR DRIVEN | 1 | EA | FIRE PUMP HOUSE |
J-1502000.1-03-08
ATTACHMENT J-1502000.1-03-08
VERTICAL TRANSPORTATION EQUIPMENT (VTE) ASSET DATA
| MUIC | Location | Asset Number | Description | Master System | System | Sub-System | Quantity | UOM | Additional Location Info |
| N00162 - NMRTC ANNAPOLIS MD | USNA-695 | NA695-PASS-01-A | PASSENGER ELEVATOR HYDRAULIC 3,500 LBS P-1 | D10 - CONVEYING | D1010 - ELEVATORS AND LIFTS | D1010110 - HYDRAULIC ELEVATORS | 1 | EA | ELEVATOR NA695 NAVAL HEALTH CLINIC |
| N00162 - NMRTC ANNAPOLIS MD | USNA-695 | NA695-PASS-02-A | PASSENGER ELEVATOR HYDRAULIC 3,500 LBS P-2 | D10 - CONVEYING | D1010 - ELEVATORS AND LIFTS | D1010110 - HYDRAULIC ELEVATORS | 1 | EA | ELEVATOR NA695 NAVAL HEALTH CLINIC |
| N00162 - NMRTC ANNAPOLIS MD | USNA-695 | NA695-PASS-03-A | PASSENGER ELEVATOR HYDRAULIC 4,500 LBS S-3 | D10 - CONVEYING | D1010 - ELEVATORS AND LIFTS | D1010110 - HYDRAULIC ELEVATORS | 1 | EA | ELEVATOR NA695 NAVAL HEALTH CLINIC |
| N00162 - NMRTC ANNAPOLIS MD | USNA-695 | NA695-PASS-04-A | PASSENGER ELEVATOR HYDRAULIC 4,500 LBS S-4 | D10 - CONVEYING | D1010 - ELEVATORS AND LIFTS | D1010110 - HYDRAULIC ELEVATORS | 1 | EA | ELEVATOR NA695 NAVAL HEALTH CLINIC |
| N00162 - NMRTC ANNAPOLIS MD | USNA-695 | NANA695-DKLV-01-A | SCISSOR LIFT VTE5 | D10 - CONVEYING | D1010 - ELEVATORS AND LIFTS | D1010901 - LIFTS | 1 | EA | LOADING DOCK NA695 NAVAL HEALTH CLINIC |
J-1502000.1-03-09
ATTACHMENT J-1502000.1-03-09
COMPRESSED AIR, MEDICAL AIR, GAS, AND VACUUM SYSTEMS ASSET DATA
| MUIC | Location | Asset Number | Description | Master System | System | Sub-System | Quantity | UOM | Additional Location Info |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | SV695-AIR-01-A | DENTAL AIR COMPRESSOR DA/G.1 | E10 - EQUIPMENT | E1040 - INDUSTRIAL PROCESS EQUIPMENT | E1040999 - OTHER INDUSTRIAL PROCESS EQUIPMENT | 1 | EA | NEW CLINIC 1W148 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | SV695-AIR-02-A | DENTAL VACUUM PUMP VP/G.1 & VP/G.2 | E10 - EQUIPMENT | E1040 - INDUSTRIAL PROCESS EQUIPMENT | E1040999 - OTHER INDUSTRIAL PROCESS EQUIPMENT | 2 | EA | NEW CLINIC 1W148 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | SV695-AIR-03-A | ORAL EVACUATION TANK T/G.1 | E10 - EQUIPMENT | E1040 - INDUSTRIAL PROCESS EQUIPMENT | E1040999 - OTHER INDUSTRIAL PROCESS EQUIPMENT | 1 | EA | NEW CLINIC 1W148 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | SV695-AIR-04-A | AMALGAM SEPARATOR AS/G.1 | E10 - EQUIPMENT | E1040 - INDUSTRIAL PROCESS EQUIPMENT | E1040999 - OTHER INDUSTRIAL PROCESS EQUIPMENT | 1 | EA | NEW CLINIC 1W148 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | SV695-AIR-05-A | PRESSURE REGULATOR .5" | E10 - EQUIPMENT | E1040 - INDUSTRIAL PROCESS EQUIPMENT | E1040999 - OTHER INDUSTRIAL PROCESS EQUIPMENT | 1 | EA | NEW CLINIC 1W128 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | SV695-AIR-CIMU | CLINIC COMPRESSED AIR, MEDICAL GAS, AND VACUUM SYSTEM | E10 - EQUIPMENT | E1040 - INDUSTRIAL PROCESS EQUIPMENT | E1040999 - OTHER INDUSTRIAL PROCESS EQUIPMENT | 1 | EA | NEW CLINIC PRIMARILY 1W & 2W |
J-1502000.1-03-10
ATTACHMENT J-1502000.1-03-10
AUXILIARY GENERATOR SYSTEMS ASSET DATA
| MUIC | Location | Asset Number | Description | Master System | System | Sub-System | Quantity | UOM | Additional Location Info |
| N61152 - NAVSUPPACT ANNAPOLIS | USNA-1014 | NA1014-EG-1 | EMERGENCY GENERATOR GENERAC 97A06868 80KW DIESEL | D50 - ELECTRICAL | D5090 - OTHER ELECTRICAL SYSTEMS | D5090210 - GENERATORS | 1 | EA | 4B14 |
| N61152 - NAVSUPPACT ANNAPOLIS | USNA-1018 | NA1018-EG-3 | EMERGENCY GENERATOR GENERAC 96A00558-S 80KW DIESEL | D50 - ELECTRICAL | D5090 - OTHER ELECTRICAL SYSTEMS | D5090210 - GENERATORS | 1 | EA | 8B22 - EMERGENCY GENER RM |
J-1502000.1-03-11
ATTACHMENT J-1502000.1-03-11
UNINTERRUPTED POWER SYSTEMS (UPS) ASSET DATA
| MUIC | Location | Asset Number | Description | Master System | System | Sub-System | Quantity | UOM | Additional Location Info |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | SVNA695-UPS-01-A | UPS BATTERY BACKUPS - 14 WALL PACKS | D50 - ELECTRICAL | D5090 - OTHER ELECTRICAL SYSTEMS | D5090904 - UNINTERUPTIBLE POWER SUPPLY | 14 | EA | INCLUDES REFRIGERATION, SECURITY, AND COMMUNICATION |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | SVNA695-UPS-02-A | UPS - LIGHTING BACKUP | D50 - ELECTRICAL | D5090 - OTHER ELECTRICAL SYSTEMS | D5090904 - UNINTERUPTIBLE POWER SUPPLY | 1 | EA | ELECTRONIC SECURITY SYSTEM |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | SVNA695-UPS-03-A | UPS - SERVER ROOM SECURITY BACKUP | D50 - ELECTRICAL | D5090 - OTHER ELECTRICAL SYSTEMS | D5090904 - UNINTERUPTIBLE POWER SUPPLY | 1 | EA | ELECTRONIC SECURITY SYSTEM |
J-1502000.1-03-12
ATTACHMENT J-1502000.1-03-12
PUMP SYSTEMS ASSET DATA
| MUIC | Location | Asset Number | Description | Master System | System | Sub-System | Quantity | UOM | Additional Location Info |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-CP-09-A | PUMP P-9 5HP 3PH 1750RPM 9.50IMP | D20 - PLUMBING | D2020 - DOMESTIC WATER DISTRIBUTION | D2020906 - CIRCULATING PUMP | 1 | EA | BASEMENT-BW152 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-CP-10-A | PUMP P-10 5HP 3PH 1750RPM 9.50IMP | D20 - PLUMBING | D2020 - DOMESTIC WATER DISTRIBUTION | D2020906 - CIRCULATING PUMP | 1 | EA | BASEMENT-BW152 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-CWP-01-A | PUMP P-1 20HP 3PH 208-230/460V | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040330 - CIRCULATING PUMP, END SUCTION | 1 | EA | BASEMENT-BW151 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-CWP-02-A | PUMP P-2 20HP 3PH 208-230/460V | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040330 - CIRCULATING PUMP, END SUCTION | 1 | EA | BASEMENT-BW151 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-CWP-03-A | PUMP P-3 20HP 3PH 208-230/460V | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040330 - CIRCULATING PUMP, END SUCTION | 1 | EA | BASEMENT-BW151 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-HWP-01-A | BOILER PUMP BP/B.1 7.5HP 3PH 208-230/460V 206FT 96GPM TRIPLE PUMPS | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040330 - CIRCULATING PUMP, END SUCTION | 1 | EA | BASEMENT-BW152 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-PUMP-04-A | PUMP P-4 20HP 3PH 208-230/460V | D20 - PLUMBING | D2020 - DOMESTIC WATER DISTRIBUTION | D2020906 - CIRCULATING PUMP | 1 | EA | BASEMENT-BW151 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-PUMP-05-A | PUMP P-5 20HP 3PH 230/460V 610 GPM 1755RPM | D20 - PLUMBING | D2020 - DOMESTIC WATER DISTRIBUTION | D2020906 - CIRCULATING PUMP | 1 | EA | BASEMENT-BW151 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-PUMP-06-A | PUMP P-6 20HP 3PH 230/460V 610 GPM 1755RPM | D20 - PLUMBING | D2020 - DOMESTIC WATER DISTRIBUTION | D2020906 - CIRCULATING PUMP | 1 | EA | BASEMENT-BW151 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-PUMP-07-A | PUMP P-7 15HP 3PH 230/460V 1765RPM 300GPM 100FT | D20 - PLUMBING | D2020 - DOMESTIC WATER DISTRIBUTION | D2020906 - CIRCULATING PUMP | 1 | EA | BASEMENT-BW152 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-PUMP-08-A | PUMP P-8 15HP 3PH 230/460V 1765RPM 300GPM 100FT | D20 - PLUMBING | D2020 - DOMESTIC WATER DISTRIBUTION | D2020906 - CIRCULATING PUMP | 1 | EA | BASEMENT-BW152 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-PUMP-11-A | PUMP P-11 3/4HP 115/208V 1725RPM | D20 - PLUMBING | D2020 - DOMESTIC WATER DISTRIBUTION | D2020906 - CIRCULATING PUMP | 1 | EA | GROUND-1E135 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-PUMP-12-A | PUMP P-12 3/4HP 115/208V 1725RPM | D20 - PLUMBING | D2020 - DOMESTIC WATER DISTRIBUTION | D2020906 - CIRCULATING PUMP | 1 | EA | GROUND-1E136 |
J-1502000.1-03-13
ATTACHMENT J-1502000.1-03-13
PUBLIC ADDRESS (PA) SYSTEMS ASSET DATA
| MUIC | Location | Asset Number | Description | Master System | System | Sub-System | Quantity | UOM | Additional Location Info |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NA695-ALM-CIMU | NEW CLINIC PA SYSTEM | D50 - ELECTRICAL | D5030 - COMMUNICATION AND SECURITY | D5030910 - COMMUNICATION/ALARM SYSTEMS | 1 | EA | INDOOR/OUTDOOR PA SYSTEM |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NA695-ALM-01-A | PA SPEAKER COOPER WHEELOCK E60-W | D50 - ELECTRICAL | D5030 - COMMUNICATION AND SECURITY | D5030910 - COMMUNICATION/ALARM SYSTEMS | 119 | EA | CEILING MOUNTED |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NA695-ALM-02-A | PA SPEAKER COOPER WHEELOCK ET-1010-R | D50 - ELECTRICAL | D5030 - COMMUNICATION AND SECURITY | D5030910 - COMMUNICATION/ALARM SYSTEMS | 11 | EA | OUTDOOR SPEAKER |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NA695-ALM-03-A | SIGCOM AUDIO POWER BOOSTER | D50 - ELECTRICAL | D5030 - COMMUNICATION AND SECURITY | D5030910 - COMMUNICATION/ALARM SYSTEMS | 11 | EA | OUTDOOR |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NA695-ALM-04-A | MASS NOTIFICATION OPERATOR CONSOLE W/REMOTE MIC | D50 - ELECTRICAL | D5030 - COMMUNICATION AND SECURITY | D5030910 - COMMUNICATION/ALARM SYSTEMS | 1 | EA | NEW CLINIC CONTROL ROOM |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NA695-ALM-05-A | NAC OUPUT EXPANSION BOARD | D50 - ELECTRICAL | D5030 - COMMUNICATION AND SECURITY | D5030910 - COMMUNICATION/ALARM SYSTEMS | 1 | EA | NEW CLINIC CONTROL ROOM |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NA695-ALM-06-A | 16 ZONE TRANSMITTER | D50 - ELECTRICAL | D5030 - COMMUNICATION AND SECURITY | D5030910 - COMMUNICATION/ALARM SYSTEMS | 1 | EA | NEW CLINIC CONTROL ROOM |
J-1502000.1-03-14
ATTACHMENT J-1502000.1-03-14
ROOF AND DRAINAGE SYSTEMS ASSET DATA
| MUIC | Location | Location Description | Roof Area in SQFT |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NAVAL HEALTH CLINIC - ANNAPOLIS | UNKNOWN |
J-1502000.1-03-15
ATTACHMENT J-1502000.1-03-15
MANUAL AND AUTOMATED DOOR SYSTEMS ASSET DATA
| MUIC | Location | Asset Number | Description | Master System | System | Sub-System | Quantity | UOM | Additional Location Info |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NA695-AD-01-A | AUTOMATED SLIDING DOOR | B20 - EXTERIOR ENCLOSURE | B2030 - EXTERIOR DOORS | B2030110 - GLAZED DOORS | 1 | EA | FRONT ENTRANCE |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NA695-AD-02-A | DOOR AUTOMATED | B20 - EXTERIOR ENCLOSURE | B2030 - EXTERIOR DOORS | B2030110 - GLAZED DOORS | 1 | EA | FRONT ENTRANCE |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NA695-ID-01-A | ELECTRIC DOOR (CARD ENTRY) | D50 - ELECTRICAL | D5030 - COMMUNICATION AND SECURITY | D5030910 - COMMUNICATION/ALARM SYSTEMS | 31 | EA | 2ND DECK |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NA695-ID-02-A | ELECTRIC DOOR (CARD ENTRY) | D50 - ELECTRICAL | D5030 - COMMUNICATION AND SECURITY | D5030910 - COMMUNICATION/ALARM SYSTEMS | 25 | EA | GROUND |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NA695-ID-03-A | ELECTRIC DOOR (CARD ENTRY) | D50 - ELECTRICAL | D5030 - COMMUNICATION AND SECURITY | D5030910 - COMMUNICATION/ALARM SYSTEMS | 2 | EA | GROUND |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NA695-ID-04-A | ELECTRIC DOOR (CARD ENTRY) | D50 - ELECTRICAL | D5030 - COMMUNICATION AND SECURITY | D5030910 - COMMUNICATION/ALARM SYSTEMS | 11 | EA | BASEMENT |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NA695-ID-05-A | ELECTRIC DOOR (CARD ENTRY) | D50 - ELECTRICAL | D5030 - COMMUNICATION AND SECURITY | D5030910 - COMMUNICATION/ALARM SYSTEMS | 7 | EA | BASEMENT |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-FD-01-A | FIRE DOOR - FIRE RATED NARROW LITE DOOR | C10 - INTERIOR CONSTRUCTION | C1020 - INTERIOR DOORS | C1020113 - FIRE DOOR, ROLLING SERVICE/ROLL-UP | 1 | EA | BASEMENT, GROUND, 2ND |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-FD-02-A | FIRE DOOR - FIRE RATED NARROW LITE DOOR | C10 - INTERIOR CONSTRUCTION | C1020 - INTERIOR DOORS | C1020113 - FIRE DOOR, ROLLING SERVICE/ROLL-UP | 1 | EA | BASEMENT, GROUND, 2ND |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-FD-03-A | FIRE DOOR - FIRE RATED NARROW LITE DOOR | C10 - INTERIOR CONSTRUCTION | C1020 - INTERIOR DOORS | C1020113 - FIRE DOOR, ROLLING SERVICE/ROLL-UP | 1 | EA | BASEMENT, GROUND, 2ND |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-FD-04-A | FIRE DOOR - FIRE RATED NARROW LITE DOOR | C10 - INTERIOR CONSTRUCTION | C1020 - INTERIOR DOORS | C1020113 - FIRE DOOR, ROLLING SERVICE/ROLL-UP | 1 | EA | BASEMENT, GROUND, 2ND |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-FD-05-A | FIRE DOOR - FIRE RATED NARROW LITE DOOR | C10 - INTERIOR CONSTRUCTION | C1020 - INTERIOR DOORS | C1020113 - FIRE DOOR, ROLLING SERVICE/ROLL-UP | 1 | EA | BASEMENT, GROUND, 2ND |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-FD-06-A | FIRE DOOR - FIRE RATED NARROW LITE DOOR | C10 - INTERIOR CONSTRUCTION | C1020 - INTERIOR DOORS | C1020113 - FIRE DOOR, ROLLING SERVICE/ROLL-UP | 1 | EA | BASEMENT, GROUND, 2ND |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-FD-07-A | FIRE DOOR - FIRE RATED NARROW LITE DOOR | C10 - INTERIOR CONSTRUCTION | C1020 - INTERIOR DOORS | C1020113 - FIRE DOOR, ROLLING SERVICE/ROLL-UP | 1 | EA | BASEMENT, GROUND, 2ND |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-FD-08-A | FIRE DOOR - FIRE RATED NARROW LITE DOOR | C10 - INTERIOR CONSTRUCTION | C1020 - INTERIOR DOORS | C1020113 - FIRE DOOR, ROLLING SERVICE/ROLL-UP | 1 | EA | BASEMENT, GROUND, 2ND |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-FD-09-A | FIRE DOOR - FIRE RATED NARROW LITE DOOR | C10 - INTERIOR CONSTRUCTION | C1020 - INTERIOR DOORS | C1020113 - FIRE DOOR, ROLLING SERVICE/ROLL-UP | 1 | EA | BASEMENT, GROUND, 2ND |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-FD-10-A | FIRE DOOR - FIRE RATED NARROW LITE DOOR | C10 - INTERIOR CONSTRUCTION | C1020 - INTERIOR DOORS | C1020113 - FIRE DOOR, ROLLING SERVICE/ROLL-UP | 1 | EA | BASEMENT, GROUND, 2ND |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-FD-11-A | FIRE DOOR - FIRE RATED NARROW LITE DOOR | C10 - INTERIOR CONSTRUCTION | C1020 - INTERIOR DOORS | C1020113 - FIRE DOOR, ROLLING SERVICE/ROLL-UP | 1 | EA | BASEMENT, GROUND, 2ND |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-FD-12-A | FIRE DOOR - FIRE RATED NARROW LITE DOOR | C10 - INTERIOR CONSTRUCTION | C1020 - INTERIOR DOORS | C1020113 - FIRE DOOR, ROLLING SERVICE/ROLL-UP | 1 | EA | BASEMENT, GROUND, 2ND |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-FD-13-A | FIRE DOOR - FIRE RATED COILING COUNTER DOOR | C10 - INTERIOR CONSTRUCTION | C1020 - INTERIOR DOORS | C1020113 - FIRE DOOR, ROLLING SERVICE/ROLL-UP | 1 | EA | BASEMENT, GROUND, 2ND |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-FD-14-A | FIRE DOOR - FIRE RATED COILING COUNTER DOOR | C10 - INTERIOR CONSTRUCTION | C1020 - INTERIOR DOORS | C1020113 - FIRE DOOR, ROLLING SERVICE/ROLL-UP | 1 | EA | BASEMENT, GROUND, 2ND |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-FD-15-A | FIRE DOOR - FIRE RATED COILING COUNTER DOOR | C10 - INTERIOR CONSTRUCTION | C1020 - INTERIOR DOORS | C1020113 - FIRE DOOR, ROLLING SERVICE/ROLL-UP | 1 | EA | BASEMENT, GROUND, 2ND |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-FD-16-A | FIRE DOOR - FIRE RATED COILING COUNTER DOOR | C10 - INTERIOR CONSTRUCTION | C1020 - INTERIOR DOORS | C1020113 - FIRE DOOR, ROLLING SERVICE/ROLL-UP | 1 | EA | BASEMENT, GROUND, 2ND |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-FD-17-A | FIRE DOOR - FIRE RATED COILING COUNTER DOOR | C10 - INTERIOR CONSTRUCTION | C1020 - INTERIOR DOORS | C1020113 - FIRE DOOR, ROLLING SERVICE/ROLL-UP | 1 | EA | BASEMENT, GROUND, 2ND |
J-1502000.1-03-16
ATTACHMENT J-1502000.1-03-16
ROLL UP DOOR AND WINDOW SYSTEMS ASSET DATA
| MUIC | Location | Asset Number | Description | Master System | System | Sub-System | Quantity | UOM | Additional Location Info |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NA695-MOD-01-A | OVERHEAD ROLL UP DOOR | B20 - EXTERIOR ENCLOSURE | B2030 - EXTERIOR DOORS | B2030410 - OVERHEAD DOORS | 1 | EA | LOADING DOCK |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NA695-MOD-02-A | ROLL UP DOOR | C10 - INTERIOR CONSTRUCTION | C1020 - INTERIOR DOORS | C1020113 - FIRE DOOR, ROLLING SERVICE/ROLL-UP | 1 | EA | PHARMACY |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NA695-MOD-03-A | ROLL UP DOOR | C10 - INTERIOR CONSTRUCTION | C1020 - INTERIOR DOORS | C1020113 - FIRE DOOR, ROLLING SERVICE/ROLL-UP | 1 | EA | PHARMACY |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NA695-MOD-04-A | ROLL UP DOOR | C10 - INTERIOR CONSTRUCTION | C1020 - INTERIOR DOORS | C1020113 - FIRE DOOR, ROLLING SERVICE/ROLL-UP | 1 | EA | PHARMACY |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NA695-MOD-05-A | ROLL UP DOOR | C10 - INTERIOR CONSTRUCTION | C1020 - INTERIOR DOORS | C1020113 - FIRE DOOR, ROLLING SERVICE/ROLL-UP | 1 | EA | PHARMACY |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NA695-MOD-06-A | ROLL UP DOOR | C10 - INTERIOR CONSTRUCTION | C1020 - INTERIOR DOORS | C1020113 - FIRE DOOR, ROLLING SERVICE/ROLL-UP | 1 | EA | PHARMACY |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NA695-MOD-07-A | ROLL UP DOOR | C10 - INTERIOR CONSTRUCTION | C1020 - INTERIOR DOORS | C1020113 - FIRE DOOR, ROLLING SERVICE/ROLL-UP | 1 | EA | LABORATORY |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NA695-MOD-08-A | ROLL UP DOOR | C10 - INTERIOR CONSTRUCTION | C1020 - INTERIOR DOORS | C1020113 - FIRE DOOR, ROLLING SERVICE/ROLL-UP | 1 | EA | RADIOLOGY |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NA695-MOD-09-A | ROLL UP DOOR | C10 - INTERIOR CONSTRUCTION | C1020 - INTERIOR DOORS | C1020113 - FIRE DOOR, ROLLING SERVICE/ROLL-UP | 1 | EA | MS CARE |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NA695-MOD-10-A | ROLL UP DOOR | C10 - INTERIOR CONSTRUCTION | C1020 - INTERIOR DOORS | C1020113 - FIRE DOOR, ROLLING SERVICE/ROLL-UP | 1 | EA | OCC MED |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NA695-MOD-11-A | ROLL UP DOOR | C10 - INTERIOR CONSTRUCTION | C1020 - INTERIOR DOORS | C1020113 - FIRE DOOR, ROLLING SERVICE/ROLL-UP | 1 | EA | HOME PORT |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NA695-MOD-12-A | ROLL UP DOOR | C10 - INTERIOR CONSTRUCTION | C1020 - INTERIOR DOORS | C1020113 - FIRE DOOR, ROLLING SERVICE/ROLL-UP | 1 | EA | HOME PORT |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NA695-MOD-13-A | ROLL UP DOOR | C10 - INTERIOR CONSTRUCTION | C1020 - INTERIOR DOORS | C1020113 - FIRE DOOR, ROLLING SERVICE/ROLL-UP | 1 | EA | HOME PORT |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NA695-MOD-14-A | ROLL UP DOOR | C10 - INTERIOR CONSTRUCTION | C1020 - INTERIOR DOORS | C1020113 - FIRE DOOR, ROLLING SERVICE/ROLL-UP | 1 | EA | PEDS |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NA695-MOD-15-A | ROLL UP DOOR | C10 - INTERIOR CONSTRUCTION | C1020 - INTERIOR DOORS | C1020113 - FIRE DOOR, ROLLING SERVICE/ROLL-UP | 1 | EA | PEDS |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NA695-MOD-16-A | ROLL UP DOOR | C10 - INTERIOR CONSTRUCTION | C1020 - INTERIOR DOORS | C1020113 - FIRE DOOR, ROLLING SERVICE/ROLL-UP | 1 | EA | DENTAL |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NA695-MOD-17-A | ROLL UP DOOR | C10 - INTERIOR CONSTRUCTION | C1020 - INTERIOR DOORS | C1020113 - FIRE DOOR, ROLLING SERVICE/ROLL-UP | 1 | EA | OPTOMETRY |
J-1502000.1-03-17
ATTACHMENT J-1502000.1-03-17
HEATING, VENTILATION & AIR CONDITIONING (HVAC) & REFRIGERATION SYSTEMS ASSET DATA
| MUIC | Location | Asset Number | Description | Master System | System | Sub-System | Quantity | UOM | Additional Location Info |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-AC-01-A | MEDICAL GAS COMPRESSOR | D30 - HVAC | D3060 - CONTROLS & INSTRUMENTATION | D3060903 - AIR COMPRESSOR | 1 | EA | DENTAL MECH ROOM |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-AHU-01-A | AIR HANDLER UNIT AHU-1.1, (2) 20 HP, 23,130 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040106 - AIR HANDLING UNIT, FIELD FAB | 1 | EA | 2F-2E183 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-AHU-02-A | AIR HANDLER UNIT AHU-1.2, 25 HP, 13,680 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040106 - AIR HANDLING UNIT, FIELD FAB | 1 | EA | 2F-2W152 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-AHU-03-A | AIR HANDLER UNIT AHU-2.1, (2) 20 HP, 19,020 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040106 - AIR HANDLING UNIT, FIELD FAB | 1 | EA | 2F-2E183 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-AHU-04-A | AIR HANDLER UNIT AHU-2.2, 20 HP, 12,440 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040106 - AIR HANDLING UNIT, FIELD FAB | 1 | EA | 2F-2W152 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-AHU-05-A | AIR HANDLER UNIT AHU-2.3, 20 HP, 12,440 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040106 - AIR HANDLING UNIT, FIELD FAB | 1 | EA | 2F-2E183 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-AHU-06-A | AIR HANDLER UNIT AHU-B.1, 25 HP, 13,460 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040106 - AIR HANDLING UNIT, FIELD FAB | 1 | EA | BASEMENT-BW153 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-AHU-CIMU-01A | AIR HANDLER UNITS | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040106 - AIR HANDLING UNIT, FIELD FAB | 6 | EA | |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-AIRS-01-A | AIR SEPARATOR AS-1, 8-INCH, 650 GPM | D30 - HVAC | D3020 - HEAT GENERATING SYSTEMS | D3020999 - OTHER | 1 | EA | BASEMENT-BW151 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-AIRS-02-A | AIR SEPARATOR AS-2, 6-INCH, 250 GPM | D30 - HVAC | D3020 - HEAT GENERATING SYSTEMS | D3020999 - OTHER | 1 | EA | BASEMENT-BW152 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-AIRS-03-A | AIR SEPARATOR AS-3, 3-INCH, 65 GPM | D30 - HVAC | D3020 - HEAT GENERATING SYSTEMS | D3020999 - OTHER | 1 | EA | BASEMENT-BW152 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-AIRS-04-A | PACKAGED SOLIDS SEPARATOR SS-1, 3-INCH, 75 GPM | D30 - HVAC | D3030 - COOLING GENERATING SYSTEMS | D3030999 - OTHER | 1 | EA | BASEMENT-BW151 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-AIRS-05-A | PACKAGED SOLIDS SEPARATOR SS-2, 3-INCH, 75 GPM | D30 - HVAC | D3030 - COOLING GENERATING SYSTEMS | D3030999 - OTHER | 1 | EA | BASEMENT-BW151 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-AIRS-CIMU-01A | AIR SEPARATORS | D30 - HVAC | D3020 - HEAT GENERATING SYSTEMS | D3020999 - OTHER | 3 | EA | |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-AIRS-CIMU-02A | PACKAGED SOLIDS SEPARATORS | D30 - HVAC | D3030 - COOLING GENERATING SYSTEMS | D3030999 - OTHER | 2 | EA | |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-ATU-01-A | AIR TERMINAL UNIT VAV-B.1.1, REHEAT, UP TO 2,500 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040132 - VAV TERMINAL | 1 | EA | BASEMENT-BW142 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-ATU-02-A | AIR TERMINAL UNIT VAV-B.1.2, REHEAT, UP TO 2,500 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040132 - VAV TERMINAL | 1 | EA | BASEMENT-BWC04 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-ATU-03-A | AIR TERMINAL UNIT VAV-B.1.3, REHEAT, UP TO 2,500 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040132 - VAV TERMINAL | 1 | EA | BASEMENT-BW129 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-ATU-04-A | AIR TERMINAL UNIT VAV-B.1.4, REHEAT, UP TO 2,500 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040132 - VAV TERMINAL | 1 | EA | BASEMENT-BW138 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-ATU-05-A | AIR TERMINAL UNIT VAV-B.1.5, REHEAT, UP TO 2,500 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040132 - VAV TERMINAL | 1 | EA | BASEMENT-BW131 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-ATU-06-A | AIR TERMINAL UNIT VAV-B.1.6, REHEAT, UP TO 2,500 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040132 - VAV TERMINAL | 1 | EA | BASEMENT-BW313 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-ATU-07-A | AIR TERMINAL UNIT VAV-B.1.7, REHEAT, UP TO 2,500 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040132 - VAV TERMINAL | 1 | EA | BASEMENT-BW117 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-ATU-08-A | AIR TERMINAL UNIT VAV-B.1.8, REHEAT, UP TO 2,500 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040132 - VAV TERMINAL | 1 | EA | BASEMENT-BEC01 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-ATU-09-A | AIR TERMINAL UNIT VAV-B.1.9, REHEAT, UP TO 2,500 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040132 - VAV TERMINAL | 1 | EA | BASEMENT-BW124 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-ATU-100-A | AIR TERMINAL UNIT VAV-2.1.11, REHEAT, UP TO 2,500 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040132 - VAV TERMINAL | 1 | EA | 2F-2E127 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-ATU-101-A | AIR TERMINAL UNIT VAV-2.1.12, REHEAT, UP TO 2,500 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040132 - VAV TERMINAL | 1 | EA | 2F-2EC01 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-ATU-102-A | AIR TERMINAL UNIT VAV-2.1.13, REHEAT, UP TO 2,500 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040132 - VAV TERMINAL | 1 | EA | 2F-2E136 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-ATU-103-A | AIR TERMINAL UNIT VAV-2.1.14, REHEAT, UP TO 2,500 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040132 - VAV TERMINAL | 1 | EA | 2F-2E131 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-ATU-104-A | AIR TERMINAL UNIT VAV-2.1.15, REHEAT, UP TO 2,500 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040132 - VAV TERMINAL | 1 | EA | 2F-2EC01 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-ATU-105-A | AIR TERMINAL UNIT VAV-2.1.16, REHEAT, UP TO 2,500 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040132 - VAV TERMINAL | 1 | EA | 2F-2EC01 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-ATU-106-A | AIR TERMINAL UNIT VAV-2.1.17, REHEAT, UP TO 2,500 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040132 - VAV TERMINAL | 1 | EA | 2F-2E121 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-ATU-107-A | AIR TERMINAL UNIT VAV-2.1.18, REHEAT, UP TO 2,500 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040132 - VAV TERMINAL | 1 | EA | 2F-2E112 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-ATU-108-A | AIR TERMINAL UNIT VAV-2.1.19, REHEAT, UP TO 2,500 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040132 - VAV TERMINAL | 1 | EA | 2F-2EC02 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-ATU-109-A | AIR TERMINAL UNIT VAV-2.1.20, REHEAT, UP TO 2,500 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040132 - VAV TERMINAL | 1 | EA | 2F-2E111 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-ATU-10-A | AIR TERMINAL UNIT VAV-B.1.10, REHEAT, UP TO 2,500 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040132 - VAV TERMINAL | 1 | EA | BASEMENT-BW124 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-ATU-110-A | AIR TERMINAL UNIT VAV-2.1.21, REHEAT, UP TO 2,500 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040132 - VAV TERMINAL | 1 | EA | 2F-2EC01 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-ATU-111-A | AIR TERMINAL UNIT VAV-2.1.22, REHEAT, UP TO 2,500 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040132 - VAV TERMINAL | 1 | EA | 2F-2E183 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-ATU-112-A | AIR TERMINAL UNIT VAV-2.1.23, REHEAT, UP TO 2,500 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040132 - VAV TERMINAL | 1 | EA | 2F-2E179 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-ATU-113-A | AIR TERMINAL UNIT VAV-2.1.24, REHEAT, UP TO 2,500 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040132 - VAV TERMINAL | 1 | EA | 2F-2E179 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-ATU-114-A | AIR TERMINAL UNIT VAV-2.1.25, REHEAT, UP TO 2,500 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040132 - VAV TERMINAL | 1 | EA | 2F-2E182 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-ATU-115-A | AIR TERMINAL UNIT VAV-2.1.26, REHEAT, UP TO 2,500 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040132 - VAV TERMINAL | 1 | EA | 2F-2E179 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-ATU-116-A | AIR TERMINAL UNIT VAV-2.1.27, REHEAT, UP TO 2,500 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040132 - VAV TERMINAL | 1 | EA | 2F-2E162 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-ATU-117-A | AIR TERMINAL UNIT VAV-2.1.28, REHEAT, UP TO 2,500 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040132 - VAV TERMINAL | 1 | EA | 2F-2E163 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-ATU-118-A | AIR TERMINAL UNIT VAV-2.1.29, REHEAT, UP TO 2,500 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040132 - VAV TERMINAL | 1 | EA | 2F-2E149 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-ATU-119-A | AIR TERMINAL UNIT VAV-2.1.30, REHEAT, UP TO 2,500 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040132 - VAV TERMINAL | 1 | EA | 2F-2E146 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-ATU-11-A | AIR TERMINAL UNIT VAV-B.1.11, REHEAT, UP TO 2,500 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040132 - VAV TERMINAL | 1 | EA | BASEMENT-BW124 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-ATU-120-A | AIR TERMINAL UNIT VAV-2.1.31, REHEAT, UP TO 2,500 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040132 - VAV TERMINAL | 1 | EA | 2F-2E134 |
| N00162 - NMRTC ANNAPOLIS MD | USNA-NA695 | NANA695-ATU-121-A | AIR TERMINAL UNIT VAV-2.1.32, REHEAT, UP TO 2,500 CFM | D30 - HVAC | D3040 - DISTRIBUTION SYSTEMS | D3040132 - VAV TERMINAL | 1 | EA | 2F-2EC07 |