J-1501000 Facility Management.pdf

PDF 886 KB Posted

Attached to
Base Operations Support Services For NSA Annapolis and US Naval Academy, Annapolis, Maryland
Solicitation number
N6247026R0017
Issued by

About this file

This document is Section J-1501000 of a Facility Management specification, containing four attachments that provide guidance for asset management, tagging, and condition assessment procedures.

Attachment J-1501000-03 establishes asset tagging requirements for NAVFAC facilities and utilities. Labels must be 3" x 2", printed with TUFFLABELS or equivalent, using Times New Roman bold uppercase text. Each label includes: the asset classification (NAVFAC Facility Asset or NAVFAC Utility Asset), location formatted in NAVFAC MAXIMO, barcode and text versions of the MAXIMO asset number, asset name and capacity/size description, a QR code containing pipe-delimited MAXIMO attributes (location, asset number, type, installation date, manufacturer, model, serial number, and utilities classification), and the QR code generation date. Handwritten information is not acceptable, and non-compliant existing labels must be replaced.

Attachment J-1501000-04 provides meter group descriptions and direct condition rating guidance for numerous facility asset types. The guidance establishes three-tier condition ratings (GREEN, AMBER, RED) with optional modifiers (+, -) for approximately 30 asset categories including overhead doors, hangar doors, elevators, escalators, cranes and hoists, boilers, chillers, cooling towers, air handling units, fan systems, heat exchangers, packaged HVAC units, switchgear, transformers, capacitor banks, panelboards, communication/alarm systems, generators, emergency lighting, and uninterruptible power supplies. Each asset category specifies discrete meter codes (CR-xxxx) for evaluating specific components, with detailed descriptors defining GREEN (minimal damage, fully operational), AMBER (noticeable degradation but operational, maintenance needed), and RED (significant damage, operationally impaired) conditions. A summary table at the document's conclusion defines SRM (Sustainment, Restoration, and Modernization) needs correlating to each rating level from preventive maintenance through complete component replacement.

View the file

Other files

File Type Posted
J-1604000-09 SAMPLE SLUDGE ANAYLSIS REPORT AND SLUDGE GENERATOR REPORT.pdf PDF
J-1503020-06 ASSET DATA AND FREQUENCIES FOR SCHEDULED WORK.xlsx XLSX spreadsheet
J-1502000.1-03 DHA ASSET DATA INDEX, SYSTEM DESCRIPTIONS AND ASSET DATA BY SYSTEM.xlsx XLSX spreadsheet
0100000 C General Information.pdf PDF
J-1605000-07-04 SAMPLE UTILITY CONSUMPTION REPORTING LOG.xlsx XLSX spreadsheet
J-1502000.1 Facility Investment - DHA.pdf PDF
J-1605000-06 SAMPLE NAVFAC BOILER AND UPV INSPECTION FORM AND INSPECTION CERTIFICATE.pdf PDF
J-0200000-07-07 Contractor Incident Report System (CIRS) Form.pdf PDF
J-1604000-14-01 STORMWATER MANAGEMENT REPORT-ANNAPOLIS JANUARY 2017.pdf PDF
J-1602000 Electrical.pdf PDF
J-1604000 Wastewater.pdf PDF
J-0200000 Management and Administration.pdf PDF
J-1607000 Chiller.pdf PDF
1501000 C Facility Management.pdf PDF
0200000 C Management and Administration.pdf PDF
N6247026R0017 Pre-Sol Notice.pdf PDF
J-1606000 Water.pdf PDF
Attachment F - Section F Deliverables.pdf PDF
J-1601000-04 SERVICE DESK GUIDE FOR UTILITY OUTAGES.pdf PDF
J-1605000-07-02 SAMPLE ROVING PATROL LOG.xlsx XLSX spreadsheet
J-1606000-03-02 WTP AND DISTRIBUTION SYSTEM DESCRIPTION 2.docx DOCX document
J-1601000-05 UTILITY INTERRUPTIONS ROAD AND PARKING LOT CLOSURE AUTHORIZATIONS REQUEST FORM.xlsx XLSX spreadsheet
1502000 C Facility Investment.pdf PDF
J-0200000-20 - ELINS.xlsx XLSX spreadsheet
J-1605000-09 HISTORICAL BOILER HRSG UPV TESTING AND CERTIFICATION SCHEDULE.xlsx XLSX spreadsheet
J-1607000-08 Cooling Tower Water Testing and Treatment Asset Data.xlsx XLSX spreadsheet
J-1502000-04 FACILITY DATA.xlsx XLSX spreadsheet
DRAFT Solicitation - N6247026R0017.pdf PDF
J-1604000-14-03 STORMWATER MANAGEMENT REPORT-ANNAPOLIS JANUARY 2017.pdf PDF
J-4 Pre-Award Inquiry Form.xlsx XLSX spreadsheet
J-1503020 Pest Control.pdf PDF
J-1601000-08 EXCAVATION-UTILITY MARKING AUTHORIZATIONS REQUEST FORM.xlsx XLSX spreadsheet
J-1503070-03 Special Event Project Historical Data.xlsx XLSX spreadsheet
1700000 C BSVE.pdf PDF
J-1604000-04 WASTEWATER SYSTEM ASSET DATA.xlsx XLSX spreadsheet
1503020 C Pest Control.pdf PDF
J-1605000-04 STEAM ASSET DATA.xlsx XLSX spreadsheet
1604000 C Wastewater.pdf PDF
1601000 C Utility Management.pdf PDF
J-1604000-15 PERMEABLE PAVEMENT AREAS.pdf PDF
J-0200000-02-02 DBA WAGE DETERMINATION.pdf PDF
J-1700000-05 HISTORICAL FUEL DELIVERY QUANTITIES.xlsx XLSX spreadsheet
1606000 C Water.pdf PDF
J-1503070 Special Events.pdf PDF
J-1502000 Facility Investment.pdf PDF
J-1607000-04 Chiller Plant and Distribution System Asset Data.xlsx XLSX spreadsheet
1605000 C Steam.pdf PDF
J-1503030 Integrated Solid Waste Management.pdf PDF
J-0200000-02-01 SCA WAGE DETERMINATION.pdf PDF
J-1606000-08 MDE SCHEDULE OF MONITORING REQUIREMENTS EXAMPLE.pdf PDF
Show 40 more

Latest 50 of 86 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SECTION J-1501000

FACILITY MANAGEMENT

TABLE OF CONTENTS

ATTACHMENT

NUMBER

ATTACHMENT TITLE

J-1501000-01 DEFINITIONS AND ACRONYMS

J-1501000-02 REFERENCES AND TECHNICAL DOCUMENTS

J-1501000-03 ASSET TAGGING GUIDANCE

J-1501000-04 METER GROUP DESCRIPTIONS AND DIRECT CONDITION RATING

GUIDANCE

ATTACHMENT J-1501000-01

DEFINITIONS AND ACRONYMS

SEE SEPARATE ATTACHMENT J-0200000-01

ATTACHMENT J-1501000-02

REFERENCES AND TECHNICAL DOCUMENTS

SEE SEPARATE ATTACHMENT J-0200000-03

INSTRUCTIONS:

LABELS SHALL BE 3”x2” AND PRINTED WITH TUFFLABELS OR EQUIVALENT.

HANDWRITTEN INFORMATION IS NOT ACCEPTABLE. TEXT SHALL BE TIMES NEW ROMAN

BOLD ALL UPPER CASE. ANY EXISTING ASSET LABEL NOT MEETNIG ALL REQUIREMENTS

WITHIN THIS ASSET TAGGING GUIDANCE SHALL BE REPLACED. KEY TO DIAGRAM ABOVE

IS AS FOLLOWS:

1. TOP LINE TO BE “NAVFAC FACILITY ASSET” or “NAVFAC UTILITY ASSET” AS

APPLICABLE.

2. LOCATION OF THE ASSET AS FORMATTED IN NAVFAC MAXIMO.

3. BARCODE VERSION OF NAVFAC MAXIMO ASSET NUMBER.

4. TEXT VERSION OF NAVFAC MAXIMO ASSET NUMBER.

5. TEXT DESCRIPTION OF ASSET NAME AND CAPACITY/SIZE

6. QR CODE CONTAINING PIPE DELIMITED MAXIMO ATTRIBUTES INCLUDING:

a. LOCATION

b. ASSET NUMBER

c. ASSET TYPE

d. INSTALLATION DATE

e. MANUFACTURER

f. MODEL

g. SERIAL NUMBER

h. CLASSIFICATION & ATTRIBUTES FOR UTILITIES ASSETS PER J-1601000-10

7. DATE QR CODE IS GENERATED

ATTACHMENT J-1501000-03

ASSET TAGGING GUIDANCE

ATTACHMENT J-1501000-04

METER GROUP DESCRIPTIONS AND DIRECT CONDITION RATING GUIDANCE

B2030410 - Overhead Doors Meter & Description Direct Condition Rating Guidance Condition CR-5200 - Record the condition of the Controls

GREEN: Controls function properly AMBER: Controls need calibrating RED: Controls are damaged and/or not operational

CR-5250 - Record the condition of the Door

GREEN: Door has minimal damage and corrosion, is square and securely fastened AMBER: Door has noticeable damage and corrosion, may be slightly displaced, but does not affect door operation or safety RED: Door has significant damage and/or corrosion, noticeably displaced, and may be structurally unsound or affect door operation

CR-5415 - Record the condition of the Guides

GREEN: Guides/Stops/Rollers/Pulleys show no signs of wear or damage, and are properly secured and aligned AMBER: Guides/Stops/Rollers/Pulleys show slight wear, and/or may be slightly loose or misaligned RED: Guides/Stops/Rollers/Pulleys have noticeable damage or wear, and are insecurely fastened and/or misaligned

CR-5505 - Record the condition of the Motor

GREEN: Motor operates properly, free of excessive noise/vibration, or overheating AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance RED: Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired

B2030901 - Hangar Doors

CR-5050 - Record the condition of the Brakes

GREEN: Brakes have minimal wear AMBER: Brakes have noticeable wear, may exhibit unusual noise, but are still operational RED: Brakes have significant wear, excessive noise, or may not function properly

CR-5200 - Record the condition of the Controls

GREEN: Controls function properly

CR-5250 - Record the condition of the Door

GREEN: Door has minimal damage and corrosion, is square and securely fastened AMBER: Door has noticeable damage and corrosion, may be slightly displaced, but does not affect door operation or safety RED: Door has significant damage and/or corrosion, noticeably displaced, and may be structurally unsound or affect door operation

CR-5415 - Record the condition of the Guides

GREEN: Guides/Stops/Rollers/Pulleys show no signs of wear or damage, and are properly secured and aligned AMBER: Guides/Stops/Rollers/Pulleys show slight wear, and/or may be slightly loose or misaligned RED: Guides/Stops/Rollers/Pulleys have noticeable damage or wear, and are insecurely fastened and/or misaligned

CR-5505 - Record the condition of the Motor

GREEN: Motor operates properly, free of excessive noise/vibration, or overheating AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance

D1010110 - Hydraulic Elevators Description How to Assess & Enter Meter Value for Condition Rating (CR-1000) Condition

Notes to Field Assessor:

*Do not select “Green(+)” unless Condition_Date = Install_Date*

For “GREEN” may assign either G or G(-) For “AMBER” may assign any of A(+), A or A(-) For “RED” may assign any of R(+), R or R(-)

CR-1000 - Record the condition of the Elevator Assembly

GREEN:

Car Supporting Platform/Frame has no damage, is structurally sound Car Operating Panel/Indicator has minimal damage and corrosion, fully operational Car Doors have minimal damage or wear, door operation is smooth Controls function properly Hydraulic Piston Well has minimal damage, deterioration, no cracks or leaks, fully secured

AMBER:

Car Supporting Platform/Frame has noticeable damage or corrosion, but no loss of structural integrity Car Operating Panel/Indicator has noticeable damage and corrosion, still operational Car Doors have noticeable damage or wear, doors are operational but may need adjustments Controls need calibrating Hydraulic Piston Well has noticeable damage, deterioration, but no cracks or leaks, still operational

RED:

Car Supporting Platform/Frame has significant damage and corrosion, structural integrity significantly impaired Car Operating Panel/Indicator has significant damage and corrosion, operationally impaired Car Doors have significant damage or corrosion, doors are operationally impaired Controls are damaged and/or not operational Hydraulic Piston Well has significant damage, deterioration, cracks or leaks, operationally impaired

D1010140 - Traction Geared Elevators

Notes to Field Assessor:

*Do not select “Green(+)” unless Condition_Date = Install_Date*

For “GREEN” may assign either G or G(-) For “AMBER” may assign any of A(+), A or A(-) For “RED” may assign any of R(+), R or R(-)

CR-1000 - Record the condition of the Elevator Assembly

GREEN:

Car Supporting Platform/Frame has no damage, is structurally sound.

Car Operating Panel/Indicator has minimal damage and corrosion, fully operational.

Safety Buffers have minimal deterioration or damage, fully operational.

Motor operates properly, free of excessive noise/vibration, or overheating.

Anchors/Cables/Tie Backs show no damage, deterioration and corrosion, fully secure.

corrosion, but no loss of structural integrity.

Car Operating Panel/Indicator has noticeable damage and corrosion, still operational.

Safety Buffers have noticeable deterioration or damage, still operational

Car Doors have noticeable damage or wear, doors are operational but may need adjustments.

Controls need calibrating.

Motor exhibits unusual noise/vibration, but still operational, may require maintenance.

Anchors/Cables/Tie Backs show minimal wear or deterioration, but are still fully secure and stable.

corrosion, structural integrity significantly impaired.

Car Operating Panel/Indicator has significant damage and corrosion, operationally impaired.

Safety Buffers have significant deterioration or damage, operationally impaired.

Car Doors have significant damage or corrosion, doors are operationally impaired.

Controls are damaged and/or not operational.

Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired.

Anchors/Cables/Tie Backs have noticeable damage, deterioration and/or corrosion, loosely secured or unstable, may jeopardize safety.

D1010150 - Traction Gearless Elevators

Notes to Field Assessor:

*Do not select “Green(+)” unless Condition_Date = Install_Date*

For “GREEN” may assign either G or G(-) For “AMBER” may assign any of A(+), A or A(-) For “RED” may assign any of R(+), R or R(-)

CR-1000 - Record the condition of the Elevator Assembly

GREEN:

Car Supporting Platform/Frame has no damage, is structurally sound.

Car Operating Panel/Indicator has minimal damage and corrosion, fully operational.

Safety Buffers have minimal deterioration or damage, fully operational.

Car Doors have minimal damage or wear, door operation is smooth Controls function properly.

Motor operates properly, free of excessive noise/vibration, or overheating Anchors/Cables/Tie Backs show no damage, deterioration and corrosion, fully secure.

corrosion, but no loss of structural integrity.

Car Operating Panel/Indicator has noticeable damage and corrosion, still operational.

Safety Buffers have noticeable deterioration or damage, still operational

Car Doors have noticeable damage or wear, doors are operational but may need adjustments.

Controls need calibrating.

Motor exhibits unusual noise/vibration, but still operational, may require maintenance.

Anchors/Cables/Tie Backs show minimal wear or deterioration, but are still fully secure and stable.

corrosion, structural integrity significantly impaired.

Car Operating Panel/Indicator has significant damage and corrosion, operationally impaired.

Safety Buffers have significant deterioration or damage, operationally impaired.

Car Doors have significant damage or corrosion, doors are operationally impaired.

Controls are damaged and/or not operational.

Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired.

Anchors/Cables/Tie Backs have noticeable damage, deterioration or corrosion, loosely secured or unstable, may jeopardize safety.

D1010901 – Lifts

Notes to Field Assessor:

*Do not select “Green(+)” unless Condition_Date = Install_Date*

For “GREEN” may assign either G or G(-) For “AMBER” may assign any of A(+), A or A(-) For “RED” may assign any of R(+), R or R(-)

CR-1000 - Record the condition of the Lift Assembly

GREEN:

Controls function properly Motor operates properly, free of excessive noise/vibration, or overheating Platform has little to no damage or deterioration, and is structurally sound

Controls need calibrating Motor exhibits unusual noise/vibration, but still operational, may require maintenance Platform has noticeable damage or deterioration, but still structurally sound

Controls are damaged and/or not operational Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired Platform has significant damage or deterioration, may be loose or unstable

D1020110 – Escalators

Notes to Field Assessor:

*Do not select “Green(+)” unless Condition_Date = Install_Date*

For “GREEN” may assign either G or G(-) For “AMBER” may assign any of A(+), A or A(-) For “RED” may assign any of R(+), R or R(-)

CR-1000 - Record the condition of the Escalator Assembly

GREEN:

Controls function properly Motor operates properly, free of excessive noise/vibration, or overheating Handrails have minimal damage or corrosion, and are fully secured Platform has little to no damage or deterioration, and is structurally sound Step Risers/Tread have minimal damage or deterioration, fully secured and aligned Comb Plates have minimal deterioration and damage, and are not loose or displaced

Controls need calibrating.

Motor exhibits unusual noise/vibration, but still operational, may require maintenance Handrails have noticeable damage or corrosion, slightly loose but still operational Platform has noticeable damage or deterioration, but still structurally sound Step Risers/Tread have noticeable damage or deterioration, are mostly secure and operational Comb Plates have noticeable deterioration and damage, but are not loose or displaced

Controls are damaged and/or not operational Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired Comb Plates have significant deterioration and damage, may be noticeably loose, displaced, or misaligned Handrails have significant damage or corrosion, noticeable loose or missing Platform has significant damage or deterioration, may be loose or unstable Step Risers/Tread have significant deterioration, damage, corrosion, or are loose or misaligned

D1090902 - Cranes and Hoists

Notes to Field Assessor:

*Do not select “Green(+)” unless Condition_Date = Install_Date*

For “GREEN” may assign either G or G(-) For “AMBER” may assign any of A(+), A or A(-) For “RED” may assign any of R(+), R or R(-)

CR-1000 - Record the condition of the Brakes

GREEN:

Brakes have minimal wear. Hook has minimal damage or wear, and is fully secured. Controls function properly.

Crane Unit shows minimal signs of wear, no loose components, structurally sound, fully operational Guide Wheels show little to no wear or damage, are securely fastened, and fully functional Motor operates properly, free of excessive noise/vibration, or overheating Structural Frame has minimal damage and corrosion, is square and securely fastened Trolley Drive has minimal to no damage, operation is smooth, fully functional

CR-1000 - Record the condition of the Chains/Hooks

AMBER:

Brakes have noticeable wear, may exhibit unusual noise, but are still operational. Hook has noticeable damage or wear, but is still securely fastened. Controls need calibrating.

Crane Unit shows noticeable signs of damage or wear, but no loose or missing components, and still operational

Guide Wheels have noticeable wear, may have slight damage, but are secure and still operational

Motor exhibits unusual noise/vibration, but still operational, may require maintenance

Structural Frame has noticeable damage and corrosion, may be slightly displaced, but does not affect door operation or safety

Trolley Drive has noticeable damage, wear, may require adjustments but is fully functional

CR-1000 - Record the

RED:

Brakes have significant wear, excessive noise, or may not function properly Hook has significant damage, connections not secure Controls are damaged and/or not operational Crane Unit shows significant signs of damage or wear, may have missing or loose components, comprised structural integrity, or is operationally impaired

Guide Wheels have significant damage, may be loose, displaced, missing, or operationally impaired

Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired

Structural Frame has significant damage or corrosion, is displaced, and may be structurally unsound or affect door operation

Trolley Drive has significant damage or wear, operation is significantly impaired

D3020130 - Boiler, Cast Iron, Hot Water, Gas

CR-5060 - Record the condition of the Burner Assembly

GREEN: Burners have minimal damage or corrosion, but is fully operational AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound RED: Burners have significant damage or corrosion, may be loose or displaced, improper flame, and is not operationally sound

GREEN: Controls function properly

CR-5365 - Record the

Firebox/Fire Tubes

GREEN: Firebox has minimal damage or corrosion AMBER: Firebox has noticeable damage or corrosion, but no cracks or holes RED: Firebox has significant damage or corrosion, cracks or holes may be present

CR-5370 - Record the condition of the Flue

GREEN: Flue has minimal damage, is secured and aligned properly, and fully operational AMBER: Flue has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational RED: Flue has significant damage and corrosion, noticeably loose, misaligned, or missing, and/or operationally impaired

CR-5380 - Record the condition of the Fuel System

GREEN: Little to no damage or corrosion, secure connections, no leaks, fully operational AMBER: Fuel System has noticeable damage or corrosion, but free of leaks, fully operational RED: Fuel System has significant damage or corrosion, significant leaking, and/or is operationally impaired

CR-5530 - Record the

Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs

CR-5540 - Record the condition of the Pressure Vessel

GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure RED: Tank has noticeable damage, punctures, holes, and leaks, may be unstable or not fully secured

CR-5690 - Record the

Wiring/Connections

GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding RED: Wiring is significantly deteriorated or frayed, connection are loose, or risk of unintentional grounding

D3020134 - Boiler, Cast Iron, Steam, Gas

CR-5060 - Record the condition of the Burner Assembly

GREEN: Burners have minimal damage or corrosion, but is fully operational AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound

GREEN: Controls function properly

Firebox/Fire Tubes

GREEN: Firebox has minimal damage or corrosion AMBER: Firebox has noticeable damage or corrosion, but no cracks or holes

CR-5520 - Record the

Pipes/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

Vessel

GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure

D3020136 - Boiler, Cast Iron, Hot Water, Gas/Oil

CR-5060 - Record the condition of the Burner Assembly

GREEN: Burners have minimal damage or corrosion, but is fully operational AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound

GREEN: Controls function properly

Firebox/Fire Tubes

GREEN: Firebox has minimal damage or corrosion AMBER: Firebox has noticeable damage or corrosion, but no cracks or holes

System

GREEN: Little to no damage or corrosion, secure connections, no leaks, fully operational AMBER: Fuel System has noticeable damage or corrosion, but free of leaks, fully operational

Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

Vessel

GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure

Wiring/Connections

GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding

D3020138 - Boiler, Cast Iron, Steam, Gas/Oil

CR-5060 - Record the condition of the Burner Assembly

GREEN: Burners have minimal damage or corrosion, but is fully operational AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound

GREEN: Controls function properly

CR-5345 - Record the condition of the Feed Water System

GREEN: Feed Water System has no damage or leaks, fully operational AMBER: Feed Water System has noticeable damage or corrosion, may have slight leaks but still operational RED: Feed Water System has significant damage or corrosion, noticeable leaks, and does not function properly

Firebox/Fire Tubes

GREEN: Firebox has minimal damage or corrosion AMBER: Firebox has noticeable damage or corrosion, but no cracks or holes

GREEN: Flue has minimal damage, is secured and aligned properly, and fully operational AMBER: Flue has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational

Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

Vessel

GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure

D3020901 - Boiler, Cast Iron, HW, Oil

CR-5060 - Record the condition of the Burner Assembly

GREEN: Burners have minimal damage or corrosion, but is fully operational AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound

GREEN: Controls function properly

Firebox/Fire Tubes

GREEN: Firebox has minimal damage or corrosion AMBER: Firebox has noticeable damage or corrosion, but no cracks or holes

GREEN: Flue has minimal damage, is secured and aligned properly, and fully operational AMBER: Flue has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational

System

GREEN: Little to no damage or corrosion, secure connections, no leaks, fully operational AMBER: Fuel System has noticeable damage or corrosion, but free of leaks, fully operational

Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

Vessel

GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure

Wiring/Connections

GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding

D3020902 - Boiler, Cast Iron, Steam, Oil

CR-5060 - Record the condition of the Burner Assembly

GREEN: Burners have minimal damage or corrosion, but is fully operational AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound

GREEN: Controls function properly

Firebox/Fire Tubes

GREEN: Firebox has minimal damage or corrosion AMBER: Firebox has noticeable damage or corrosion, but no cracks or holes

Pipes/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

Vessel

GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure

D3030130 - Chiller, Reciprocating, Water Cooled

CR-5140 - Record the condition of the Compressor

GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional RED: Unacceptable Noise, Vibration, or overheating from compressor, significant damage, and/or operationally impaired

CR-5155 - Record the

Condenser

GREEN: Minimal corrosion or fouling of the condenser/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational RED: Significant damage, corrosion or fouling of the condenser/coils, no damage, operationally impaired

GREEN: Controls function properly

CR-5295 - Record the

Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced RED: Significant damage/corrosion to Enclosure, a number of panels are loose, displaced, or missing

CR-5305 - Record the

Evaporator

GREEN: Minimal corrosion or fouling of the evaporator/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational RED: Significant damage, corrosion or fouling of the evaporator/coils, operationally impaired

Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

CR-5565 - Record the condition of the Receiver Tank

GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure

D3030135 - Chiller, Reciprocating, Air Cooled

CR-5140 - Record the condition of the Compressor

GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional

Condenser

GREEN: Minimal corrosion or fouling of the condenser/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational

CR-5175 - Record the

Condenser Fan(s) Assembly

GREEN: Motor operates properly, free of excessive noise/vibration, or overheating AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance

GREEN: Controls function properly

Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced

Evaporator

GREEN: Minimal corrosion or fouling of the evaporator/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational

Pipes/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

Tank

GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure

Wiring/Connections

GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding

D3030140 - Chiller, Centrifugal, Water Cooled

CR-5110 - Record the condition of the Centrifugal Motor

GREEN: Motor operates properly, free of excessive noise/vibration, or overheating AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance

CR-5140 - Record the

Compressor

GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional

Condenser

GREEN: Minimal corrosion or fouling of the condenser/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational

CR-5210 - Record the

Controls/Sensors

GREEN: Controls function properly

Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced

Evaporator

GREEN: Minimal corrosion or fouling of the evaporator/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational

Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

Tank

GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure

D3030145 - Chiller, Gas Absorption, Water Cooled

CR-5000 - Record the condition of the Absorber

GREEN: Absorber has minimal damage and corrosion, but no leaks AMBER: Absorber has noticeable damage and corrosion, but minimal leaks and is still operational RED: Absorber has significant damage and corrosion, and noticeable leaks, operationally impaired

Compressor

GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional

Condenser

GREEN: Minimal corrosion or fouling of the condenser/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational

GREEN: Controls function properly

Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced

Evaporator

GREEN: Minimal corrosion or fouling of the evaporator/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational

CR-5430 - Record the condition of the Heat Generator

GREEN: Heating Element has little to no damage or corrosion, and is fully operational AMBER: Heating Element has noticeable damage or corrosion, but still operational RED: Heating Element has significant damage or corrosion, Pipes/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

CR-5555 - Record the

GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure

D3030150 - Chiller, Steam Absorption, Water Cooled

CR-5000 - Record the condition of the Absorber

GREEN: Absorber has minimal damage and corrosion, but no leaks AMBER: Absorber has noticeable damage and corrosion, but minimal leaks and is still operational RED: Absorber has significant damage and corrosion, and noticeable leaks, operationally impaired

Compressor

GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional

Condenser

GREEN: Minimal corrosion or fouling of the condenser/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational

GREEN: Controls function properly

Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced

Evaporator

GREEN: Minimal corrosion or fouling of the evaporator/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational

CR-5430 - Record the condition of the Heat Generator

GREEN: Heating Element has little to no damage or corrosion, and is fully operational AMBER: Heating Element has noticeable damage or corrosion, but still operational RED: Heating Element has significant damage or corrosion, Pipes/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

CR-5555 - Record the

GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure

D3030310 - Cooling Tower, Galvanized

CR-5025 - Record the condition of the Basin/Sump

GREEN: Sump has minimal damage or corrosion, no leaking AMBER: Sump has noticeable damage or corrosion, but no leaking RED: Sump has significant damage or corrosion, and noticeable leaking, operationally impaired

CR-5280 - Record the

Electrodes

GREEN: Conductivity Electrodes have minimal damage and corrosion, secure connections and fully functional AMBER: Conductivity Electrodes have noticeable damage and corrosion, some loose connections but still functional RED: Conductivity Electrodes have significant damage and corrosion, loose or missing connections, operationally impaired

CR-5325 - Record the condition of the Fan Assembly

GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational RED: Fans blades are out of balance, significantly bent or corroded, or fan is operationally impaired

CR-5350 - Record the condition of the Fill Material

GREEN: Filter has minimal to no dirt and debris, free of damage AMBER: Filter shows noticeable signs of debris, but little to no damage allowing unobstructed flow RED: Air Filter clogged with dirt and debris, or shows signs of damage such as, punctures, tears, rips

Pipes/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

D3030320 - Cooling Tower, Fiberglass

CR-5025 - Record the condition of the Basin/Sump

GREEN: Sump has minimal damage or corrosion, no leaking AMBER: Sump has noticeable damage or corrosion, but no leaking

Electrodes

GREEN: Conductivity Electrodes have minimal damage and corrosion, secure connections and fully functional AMBER: Conductivity Electrodes have noticeable damage and corrosion, some loose connections but still functional

Assembly

GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational

Material

GREEN: Filter has minimal to no dirt and debris, free of damage AMBER: Filter shows noticeable signs of debris, but little to no damage allowing unobstructed flow

Pipes/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

D3030330 - Cooling Tower, Stainless Steel

CR-5025 - Record the condition of the Basin/Sump

GREEN: Sump has minimal damage or corrosion, no leaking AMBER: Sump has noticeable damage or corrosion, but no leaking

Electrodes

GREEN: Conductivity Electrodes have minimal damage and corrosion, secure connections and fully functional AMBER: Conductivity Electrodes have noticeable damage and corrosion, some loose connections but still functional

Assembly

GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational

Material

GREEN: Filter has minimal to no dirt and debris, free of damage AMBER: Filter shows noticeable signs of debris, but little to no damage allowing unobstructed flow

Pipes/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

D3030902 - Condenser, DX, Evaporative

CR-5325 - Record the condition of the Fan Assembly

GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational

CR-5495 - Record the condition of the Louvers

GREEN: Louvers have minimal damage and corrosion, fully secured AMBER: Louvers have noticeable damage and corrosion, may be loose but still operational RED: Louvers have significant damage and corrosion, may be loose, missing, and/or operationally impaired

CR-5515 - Record the condition of the Nozzles

GREEN: Nozzles show no signs of damage, corrosion, or clogging, fully operational AMBER: Nozzles have some damage, corrosion, or clogs, noticeable obstruction of flow, but operational RED: Nozzles have significant damage and corrosion, severely obstructed flow, operationally impaired

CR-5615 - Record the condition of the Sump Pump

GREEN: Pump has minimal damage or corrosion, no unusual noise/vibration, no leaks, and is fully operational AMBER: Pump has noticeable damage or corrosion, slight leaking, unusual noise/vibration, but still operational RED: Pump has significant damage or corrosion, excessive noise/vibration, noticeable leaking, and/or is operationally impaired

Wiring/Connections

GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding

D3030903 - Packaged DX Refrigerant System

CR-5140 - Record the condition of the Compressor

GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional

Condenser Fan(s) Assembly

GREEN: Motor operates properly, free of excessive noise/vibration, or overheating AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance

CR-5185 - Record the

Condensing Coils

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

RED: Coils are clogged, show some signs of damage, or significant scaling and deterioration.

GREEN: Controls function properly

Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

Wiring/Connections

GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding

D3040106 - Air Handling Unit, Field Fabricated

CR-5120 - Record the condition of the Coils (Cooling)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

CR-5125 - Record the condition of the Coils (Heating)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

CR-5145 - Record the

Condensate Piping

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

Controls/Sensors

GREEN: Controls function properly

CR-5235 - Record the condition of the Dampers

GREEN: Damper has minimal damage, is secured and aligned properly, and fully operational AMBER: Damper has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational RED: Damper has significant damage and corrosion, noticeably loose, CR-5260 - Record the condition of the Drain Pan

GREEN: Drain Pan has minimal damage or corrosion AMBER: Drain Pan has noticeable damage or corrosion, but no leaks RED: Drain Pan has significant damage or corrosion, and noticeable leaks

Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced

CR-5330 - Record the

Assy

GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational

Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

D3040110 - Air Handling Unit, Central Station

CR-5120 - Record the condition of the Coils (Cooling)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

(Heating)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

GREEN: Controls function properly

GREEN: Damper has minimal damage, is secured and aligned properly, and fully operational AMBER: Damper has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational

Pan

GREEN: Drain Pan has minimal damage or corrosion AMBER: Drain Pan has noticeable damage or corrosion, but no leaks

Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced

CR-5340 - Record the condition of the Fan(s) Assembly

GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational

GREEN: Louvers have minimal damage and corrosion, fully secured AMBER: Louvers have noticeable damage and corrosion, may be loose but still operational

Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

D3040114 - Air Handling Unit, Rooftop

CR-5120 - Record the condition of the Coils (Cooling)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

(Heating)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

GREEN: Controls function properly

GREEN: Damper has minimal damage, is secured and aligned properly, and fully operational AMBER: Damper has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational

Pan

GREEN: Drain Pan has minimal damage or corrosion AMBER: Drain Pan has noticeable damage or corrosion, but no leaks

Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced

CR-5340 - Record the condition of the Fan(s) Assembly

GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational

GREEN: Louvers have minimal damage and corrosion, fully secured AMBER: Louvers have noticeable damage and corrosion, may be loose but still operational

Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

D3040220 - Fan System, Centrifugal In-Line

CR-5200 - Record the condition of the Controls

GREEN: Controls function properly

GREEN: Damper has minimal damage, is secured and aligned properly, and fully operational AMBER: Damper has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational

Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced

Assy

GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational

Wiring/Connections

GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding

D3040230 - Fan System, Utility Set

CR-5330 - Record the condition of the Fan Assy

GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational

CR-5630 - Record the condition of the Switches Controls

GREEN: Switches function properly AMBER: None RED: Switches do not function properly

Wiring/Connections

GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding

D3040240 - Fan System, Roof Exhaust

CR-5200 - Record the condition of the Controls

GREEN: Controls function properly

GREEN: Damper has minimal damage, is secured and aligned properly, and fully operational AMBER: Damper has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational

Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced

Assy

GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational

Wiring/Connections

GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding

D3040330 - Circulating Pump, End Suction

CR-5045 - Record the condition of the Booster Pump, w/ Oil Reservoir

GREEN: Pump has minimal damage or corrosion, no unusual noise/vibration, no leaks, and is fully operational AMBER: Pump has noticeable damage or corrosion, slight leaking, unusual noise/vibration, but still operational RED: Pump has significant damage or corrosion, excessive noise/vibration, noticeable leaking, and/or is operationally impaired

D3040340 - Circulating Pump, Double Suction

CR-5045 - Record the condition of the Booster Pump, w/ Oil Reservoir

GREEN: Pump has minimal damage or corrosion, no unusual noise/vibration, no leaks, and is fully operational AMBER: Pump has noticeable damage or corrosion, slight leaking, unusual noise/vibration, but still operational RED: Pump has significant damage or corrosion, excessive noise/vibration, noticeable leaking, and/or is operationally impaired

D3040610 - Heat Exchanger, Plate Type

CR-5200 - Record the condition of the Controls

GREEN: Controls function properly

CR-5375 - Record the

Frame/Supports

GREEN: Supports have minimal damage and corrosion, are fully stable and secure AMBER: Supports have noticeable damage and corrosion, but still structurally stable and secure RED: Supports have significant damage and corrosion, and/or unstable or not secured

CR-5465 - Record the

Insulation

GREEN: Insulation has minimal deterioration, and is mostly in place where necessary AMBER: Insulation has noticeable deterioration, portions may be loose or displaced, but mostly intact RED: Insulation is significantly damaged, or large portions are displaced or missing

Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

CR-5570 - Record the condition of the Relief Valve

GREEN: Valve has little to no damage or corrosion, is fully operational AMBER: Valve shows some damage or corrosion, valve functions but may require calibration RED: Valve has significant damage or corrosion, is operationally impaired

CR-5590 - Record the condition of the Steam Modulating Valve

GREEN: Valve has little to no damage or corrosion, is fully operational AMBER: Valve shows some damage or corrosion, valve functions but may require calibration

D3040620 - Heat Exchanger, Shell Tube

CR-5200 - Record the condition of the Controls

GREEN: Controls function properly

CR-5375 - Record the

Frame/Supports

GREEN: Supports have minimal damage and corrosion, are fully stable and secure AMBER: Supports have noticeable damage and corrosion, but still structurally stable and secure RED: Supports have significant damage and corrosion, and/or unstable or not secured

CR-5465 - Record the

Insulation

GREEN: Insulation has minimal deterioration, and is mostly in place where necessary AMBER: Insulation has noticeable deterioration, portions may be loose or displaced, but mostly intact RED: Insulation is significantly damaged, or large portions are displaced or missing

Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

CR-5570 - Record the condition of the Relief Valve

GREEN: Valve has little…