J-1501000 Facility Management.pdf
PDF 886 KB Posted
- Attached to
- Base Operations Support Services For NSA Annapolis and US Naval Academy, Annapolis, Maryland
- Solicitation number
- N6247026R0017
About this file
This document is Section J-1501000 of a Facility Management specification, containing four attachments that provide guidance for asset management, tagging, and condition assessment procedures.
Attachment J-1501000-03 establishes asset tagging requirements for NAVFAC facilities and utilities. Labels must be 3" x 2", printed with TUFFLABELS or equivalent, using Times New Roman bold uppercase text. Each label includes: the asset classification (NAVFAC Facility Asset or NAVFAC Utility Asset), location formatted in NAVFAC MAXIMO, barcode and text versions of the MAXIMO asset number, asset name and capacity/size description, a QR code containing pipe-delimited MAXIMO attributes (location, asset number, type, installation date, manufacturer, model, serial number, and utilities classification), and the QR code generation date. Handwritten information is not acceptable, and non-compliant existing labels must be replaced.
Attachment J-1501000-04 provides meter group descriptions and direct condition rating guidance for numerous facility asset types. The guidance establishes three-tier condition ratings (GREEN, AMBER, RED) with optional modifiers (+, -) for approximately 30 asset categories including overhead doors, hangar doors, elevators, escalators, cranes and hoists, boilers, chillers, cooling towers, air handling units, fan systems, heat exchangers, packaged HVAC units, switchgear, transformers, capacitor banks, panelboards, communication/alarm systems, generators, emergency lighting, and uninterruptible power supplies. Each asset category specifies discrete meter codes (CR-xxxx) for evaluating specific components, with detailed descriptors defining GREEN (minimal damage, fully operational), AMBER (noticeable degradation but operational, maintenance needed), and RED (significant damage, operationally impaired) conditions. A summary table at the document's conclusion defines SRM (Sustainment, Restoration, and Modernization) needs correlating to each rating level from preventive maintenance through complete component replacement.
View the file
Other files
Show 40 more
Latest 50 of 86 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SECTION J-1501000
FACILITY MANAGEMENT
TABLE OF CONTENTS
ATTACHMENT
NUMBER
ATTACHMENT TITLE
J-1501000-01 DEFINITIONS AND ACRONYMS
J-1501000-02 REFERENCES AND TECHNICAL DOCUMENTS
J-1501000-03 ASSET TAGGING GUIDANCE
J-1501000-04 METER GROUP DESCRIPTIONS AND DIRECT CONDITION RATING
GUIDANCE
ATTACHMENT J-1501000-01
DEFINITIONS AND ACRONYMS
SEE SEPARATE ATTACHMENT J-0200000-01
ATTACHMENT J-1501000-02
REFERENCES AND TECHNICAL DOCUMENTS
SEE SEPARATE ATTACHMENT J-0200000-03
INSTRUCTIONS:
LABELS SHALL BE 3”x2” AND PRINTED WITH TUFFLABELS OR EQUIVALENT.
HANDWRITTEN INFORMATION IS NOT ACCEPTABLE. TEXT SHALL BE TIMES NEW ROMAN
BOLD ALL UPPER CASE. ANY EXISTING ASSET LABEL NOT MEETNIG ALL REQUIREMENTS
WITHIN THIS ASSET TAGGING GUIDANCE SHALL BE REPLACED. KEY TO DIAGRAM ABOVE
IS AS FOLLOWS:
1. TOP LINE TO BE “NAVFAC FACILITY ASSET” or “NAVFAC UTILITY ASSET” AS
APPLICABLE.
2. LOCATION OF THE ASSET AS FORMATTED IN NAVFAC MAXIMO.
3. BARCODE VERSION OF NAVFAC MAXIMO ASSET NUMBER.
4. TEXT VERSION OF NAVFAC MAXIMO ASSET NUMBER.
5. TEXT DESCRIPTION OF ASSET NAME AND CAPACITY/SIZE
6. QR CODE CONTAINING PIPE DELIMITED MAXIMO ATTRIBUTES INCLUDING:
a. LOCATION
b. ASSET NUMBER
c. ASSET TYPE
d. INSTALLATION DATE
e. MANUFACTURER
f. MODEL
g. SERIAL NUMBER
h. CLASSIFICATION & ATTRIBUTES FOR UTILITIES ASSETS PER J-1601000-10
7. DATE QR CODE IS GENERATED
ATTACHMENT J-1501000-03
ASSET TAGGING GUIDANCE
ATTACHMENT J-1501000-04
METER GROUP DESCRIPTIONS AND DIRECT CONDITION RATING GUIDANCE
B2030410 - Overhead Doors Meter & Description Direct Condition Rating Guidance Condition CR-5200 - Record the condition of the Controls
GREEN: Controls function properly AMBER: Controls need calibrating RED: Controls are damaged and/or not operational
CR-5250 - Record the condition of the Door
GREEN: Door has minimal damage and corrosion, is square and securely fastened AMBER: Door has noticeable damage and corrosion, may be slightly displaced, but does not affect door operation or safety RED: Door has significant damage and/or corrosion, noticeably displaced, and may be structurally unsound or affect door operation
CR-5415 - Record the condition of the Guides
GREEN: Guides/Stops/Rollers/Pulleys show no signs of wear or damage, and are properly secured and aligned AMBER: Guides/Stops/Rollers/Pulleys show slight wear, and/or may be slightly loose or misaligned RED: Guides/Stops/Rollers/Pulleys have noticeable damage or wear, and are insecurely fastened and/or misaligned
CR-5505 - Record the condition of the Motor
GREEN: Motor operates properly, free of excessive noise/vibration, or overheating AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance RED: Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired
B2030901 - Hangar Doors
CR-5050 - Record the condition of the Brakes
GREEN: Brakes have minimal wear AMBER: Brakes have noticeable wear, may exhibit unusual noise, but are still operational RED: Brakes have significant wear, excessive noise, or may not function properly
CR-5200 - Record the condition of the Controls
GREEN: Controls function properly
CR-5250 - Record the condition of the Door
GREEN: Door has minimal damage and corrosion, is square and securely fastened AMBER: Door has noticeable damage and corrosion, may be slightly displaced, but does not affect door operation or safety RED: Door has significant damage and/or corrosion, noticeably displaced, and may be structurally unsound or affect door operation
CR-5415 - Record the condition of the Guides
GREEN: Guides/Stops/Rollers/Pulleys show no signs of wear or damage, and are properly secured and aligned AMBER: Guides/Stops/Rollers/Pulleys show slight wear, and/or may be slightly loose or misaligned RED: Guides/Stops/Rollers/Pulleys have noticeable damage or wear, and are insecurely fastened and/or misaligned
CR-5505 - Record the condition of the Motor
GREEN: Motor operates properly, free of excessive noise/vibration, or overheating AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance
D1010110 - Hydraulic Elevators Description How to Assess & Enter Meter Value for Condition Rating (CR-1000) Condition
Notes to Field Assessor:
*Do not select “Green(+)” unless Condition_Date = Install_Date*
For “GREEN” may assign either G or G(-) For “AMBER” may assign any of A(+), A or A(-) For “RED” may assign any of R(+), R or R(-)
CR-1000 - Record the condition of the Elevator Assembly
GREEN:
Car Supporting Platform/Frame has no damage, is structurally sound Car Operating Panel/Indicator has minimal damage and corrosion, fully operational Car Doors have minimal damage or wear, door operation is smooth Controls function properly Hydraulic Piston Well has minimal damage, deterioration, no cracks or leaks, fully secured
AMBER:
Car Supporting Platform/Frame has noticeable damage or corrosion, but no loss of structural integrity Car Operating Panel/Indicator has noticeable damage and corrosion, still operational Car Doors have noticeable damage or wear, doors are operational but may need adjustments Controls need calibrating Hydraulic Piston Well has noticeable damage, deterioration, but no cracks or leaks, still operational
RED:
Car Supporting Platform/Frame has significant damage and corrosion, structural integrity significantly impaired Car Operating Panel/Indicator has significant damage and corrosion, operationally impaired Car Doors have significant damage or corrosion, doors are operationally impaired Controls are damaged and/or not operational Hydraulic Piston Well has significant damage, deterioration, cracks or leaks, operationally impaired
D1010140 - Traction Geared Elevators
Notes to Field Assessor:
*Do not select “Green(+)” unless Condition_Date = Install_Date*
For “GREEN” may assign either G or G(-) For “AMBER” may assign any of A(+), A or A(-) For “RED” may assign any of R(+), R or R(-)
CR-1000 - Record the condition of the Elevator Assembly
GREEN:
Car Supporting Platform/Frame has no damage, is structurally sound.
Car Operating Panel/Indicator has minimal damage and corrosion, fully operational.
Safety Buffers have minimal deterioration or damage, fully operational.
Motor operates properly, free of excessive noise/vibration, or overheating.
Anchors/Cables/Tie Backs show no damage, deterioration and corrosion, fully secure.
corrosion, but no loss of structural integrity.
Car Operating Panel/Indicator has noticeable damage and corrosion, still operational.
Safety Buffers have noticeable deterioration or damage, still operational
Car Doors have noticeable damage or wear, doors are operational but may need adjustments.
Controls need calibrating.
Motor exhibits unusual noise/vibration, but still operational, may require maintenance.
Anchors/Cables/Tie Backs show minimal wear or deterioration, but are still fully secure and stable.
corrosion, structural integrity significantly impaired.
Car Operating Panel/Indicator has significant damage and corrosion, operationally impaired.
Safety Buffers have significant deterioration or damage, operationally impaired.
Car Doors have significant damage or corrosion, doors are operationally impaired.
Controls are damaged and/or not operational.
Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired.
Anchors/Cables/Tie Backs have noticeable damage, deterioration and/or corrosion, loosely secured or unstable, may jeopardize safety.
D1010150 - Traction Gearless Elevators
Notes to Field Assessor:
*Do not select “Green(+)” unless Condition_Date = Install_Date*
For “GREEN” may assign either G or G(-) For “AMBER” may assign any of A(+), A or A(-) For “RED” may assign any of R(+), R or R(-)
CR-1000 - Record the condition of the Elevator Assembly
GREEN:
Car Supporting Platform/Frame has no damage, is structurally sound.
Car Operating Panel/Indicator has minimal damage and corrosion, fully operational.
Safety Buffers have minimal deterioration or damage, fully operational.
Car Doors have minimal damage or wear, door operation is smooth Controls function properly.
Motor operates properly, free of excessive noise/vibration, or overheating Anchors/Cables/Tie Backs show no damage, deterioration and corrosion, fully secure.
corrosion, but no loss of structural integrity.
Car Operating Panel/Indicator has noticeable damage and corrosion, still operational.
Safety Buffers have noticeable deterioration or damage, still operational
Car Doors have noticeable damage or wear, doors are operational but may need adjustments.
Controls need calibrating.
Motor exhibits unusual noise/vibration, but still operational, may require maintenance.
Anchors/Cables/Tie Backs show minimal wear or deterioration, but are still fully secure and stable.
corrosion, structural integrity significantly impaired.
Car Operating Panel/Indicator has significant damage and corrosion, operationally impaired.
Safety Buffers have significant deterioration or damage, operationally impaired.
Car Doors have significant damage or corrosion, doors are operationally impaired.
Controls are damaged and/or not operational.
Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired.
Anchors/Cables/Tie Backs have noticeable damage, deterioration or corrosion, loosely secured or unstable, may jeopardize safety.
D1010901 – Lifts
Notes to Field Assessor:
*Do not select “Green(+)” unless Condition_Date = Install_Date*
For “GREEN” may assign either G or G(-) For “AMBER” may assign any of A(+), A or A(-) For “RED” may assign any of R(+), R or R(-)
CR-1000 - Record the condition of the Lift Assembly
GREEN:
Controls function properly Motor operates properly, free of excessive noise/vibration, or overheating Platform has little to no damage or deterioration, and is structurally sound
Controls need calibrating Motor exhibits unusual noise/vibration, but still operational, may require maintenance Platform has noticeable damage or deterioration, but still structurally sound
Controls are damaged and/or not operational Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired Platform has significant damage or deterioration, may be loose or unstable
D1020110 – Escalators
Notes to Field Assessor:
*Do not select “Green(+)” unless Condition_Date = Install_Date*
For “GREEN” may assign either G or G(-) For “AMBER” may assign any of A(+), A or A(-) For “RED” may assign any of R(+), R or R(-)
CR-1000 - Record the condition of the Escalator Assembly
GREEN:
Controls function properly Motor operates properly, free of excessive noise/vibration, or overheating Handrails have minimal damage or corrosion, and are fully secured Platform has little to no damage or deterioration, and is structurally sound Step Risers/Tread have minimal damage or deterioration, fully secured and aligned Comb Plates have minimal deterioration and damage, and are not loose or displaced
Controls need calibrating.
Motor exhibits unusual noise/vibration, but still operational, may require maintenance Handrails have noticeable damage or corrosion, slightly loose but still operational Platform has noticeable damage or deterioration, but still structurally sound Step Risers/Tread have noticeable damage or deterioration, are mostly secure and operational Comb Plates have noticeable deterioration and damage, but are not loose or displaced
Controls are damaged and/or not operational Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired Comb Plates have significant deterioration and damage, may be noticeably loose, displaced, or misaligned Handrails have significant damage or corrosion, noticeable loose or missing Platform has significant damage or deterioration, may be loose or unstable Step Risers/Tread have significant deterioration, damage, corrosion, or are loose or misaligned
D1090902 - Cranes and Hoists
Notes to Field Assessor:
*Do not select “Green(+)” unless Condition_Date = Install_Date*
For “GREEN” may assign either G or G(-) For “AMBER” may assign any of A(+), A or A(-) For “RED” may assign any of R(+), R or R(-)
CR-1000 - Record the condition of the Brakes
GREEN:
Brakes have minimal wear. Hook has minimal damage or wear, and is fully secured. Controls function properly.
Crane Unit shows minimal signs of wear, no loose components, structurally sound, fully operational Guide Wheels show little to no wear or damage, are securely fastened, and fully functional Motor operates properly, free of excessive noise/vibration, or overheating Structural Frame has minimal damage and corrosion, is square and securely fastened Trolley Drive has minimal to no damage, operation is smooth, fully functional
CR-1000 - Record the condition of the Chains/Hooks
AMBER:
Brakes have noticeable wear, may exhibit unusual noise, but are still operational. Hook has noticeable damage or wear, but is still securely fastened. Controls need calibrating.
Crane Unit shows noticeable signs of damage or wear, but no loose or missing components, and still operational
Guide Wheels have noticeable wear, may have slight damage, but are secure and still operational
Motor exhibits unusual noise/vibration, but still operational, may require maintenance
Structural Frame has noticeable damage and corrosion, may be slightly displaced, but does not affect door operation or safety
Trolley Drive has noticeable damage, wear, may require adjustments but is fully functional
CR-1000 - Record the
RED:
Brakes have significant wear, excessive noise, or may not function properly Hook has significant damage, connections not secure Controls are damaged and/or not operational Crane Unit shows significant signs of damage or wear, may have missing or loose components, comprised structural integrity, or is operationally impaired
Guide Wheels have significant damage, may be loose, displaced, missing, or operationally impaired
Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired
Structural Frame has significant damage or corrosion, is displaced, and may be structurally unsound or affect door operation
Trolley Drive has significant damage or wear, operation is significantly impaired
D3020130 - Boiler, Cast Iron, Hot Water, Gas
CR-5060 - Record the condition of the Burner Assembly
GREEN: Burners have minimal damage or corrosion, but is fully operational AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound RED: Burners have significant damage or corrosion, may be loose or displaced, improper flame, and is not operationally sound
GREEN: Controls function properly
CR-5365 - Record the
Firebox/Fire Tubes
GREEN: Firebox has minimal damage or corrosion AMBER: Firebox has noticeable damage or corrosion, but no cracks or holes RED: Firebox has significant damage or corrosion, cracks or holes may be present
CR-5370 - Record the condition of the Flue
GREEN: Flue has minimal damage, is secured and aligned properly, and fully operational AMBER: Flue has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational RED: Flue has significant damage and corrosion, noticeably loose, misaligned, or missing, and/or operationally impaired
CR-5380 - Record the condition of the Fuel System
GREEN: Little to no damage or corrosion, secure connections, no leaks, fully operational AMBER: Fuel System has noticeable damage or corrosion, but free of leaks, fully operational RED: Fuel System has significant damage or corrosion, significant leaking, and/or is operationally impaired
CR-5530 - Record the
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs
CR-5540 - Record the condition of the Pressure Vessel
GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure RED: Tank has noticeable damage, punctures, holes, and leaks, may be unstable or not fully secured
CR-5690 - Record the
Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding RED: Wiring is significantly deteriorated or frayed, connection are loose, or risk of unintentional grounding
D3020134 - Boiler, Cast Iron, Steam, Gas
CR-5060 - Record the condition of the Burner Assembly
GREEN: Burners have minimal damage or corrosion, but is fully operational AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound
GREEN: Controls function properly
Firebox/Fire Tubes
GREEN: Firebox has minimal damage or corrosion AMBER: Firebox has noticeable damage or corrosion, but no cracks or holes
CR-5520 - Record the
Pipes/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
Vessel
GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure
D3020136 - Boiler, Cast Iron, Hot Water, Gas/Oil
CR-5060 - Record the condition of the Burner Assembly
GREEN: Burners have minimal damage or corrosion, but is fully operational AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound
GREEN: Controls function properly
Firebox/Fire Tubes
GREEN: Firebox has minimal damage or corrosion AMBER: Firebox has noticeable damage or corrosion, but no cracks or holes
System
GREEN: Little to no damage or corrosion, secure connections, no leaks, fully operational AMBER: Fuel System has noticeable damage or corrosion, but free of leaks, fully operational
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
Vessel
GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure
Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding
D3020138 - Boiler, Cast Iron, Steam, Gas/Oil
CR-5060 - Record the condition of the Burner Assembly
GREEN: Burners have minimal damage or corrosion, but is fully operational AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound
GREEN: Controls function properly
CR-5345 - Record the condition of the Feed Water System
GREEN: Feed Water System has no damage or leaks, fully operational AMBER: Feed Water System has noticeable damage or corrosion, may have slight leaks but still operational RED: Feed Water System has significant damage or corrosion, noticeable leaks, and does not function properly
Firebox/Fire Tubes
GREEN: Firebox has minimal damage or corrosion AMBER: Firebox has noticeable damage or corrosion, but no cracks or holes
GREEN: Flue has minimal damage, is secured and aligned properly, and fully operational AMBER: Flue has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
Vessel
GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure
D3020901 - Boiler, Cast Iron, HW, Oil
CR-5060 - Record the condition of the Burner Assembly
GREEN: Burners have minimal damage or corrosion, but is fully operational AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound
GREEN: Controls function properly
Firebox/Fire Tubes
GREEN: Firebox has minimal damage or corrosion AMBER: Firebox has noticeable damage or corrosion, but no cracks or holes
GREEN: Flue has minimal damage, is secured and aligned properly, and fully operational AMBER: Flue has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational
System
GREEN: Little to no damage or corrosion, secure connections, no leaks, fully operational AMBER: Fuel System has noticeable damage or corrosion, but free of leaks, fully operational
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
Vessel
GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure
Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding
D3020902 - Boiler, Cast Iron, Steam, Oil
CR-5060 - Record the condition of the Burner Assembly
GREEN: Burners have minimal damage or corrosion, but is fully operational AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound
GREEN: Controls function properly
Firebox/Fire Tubes
GREEN: Firebox has minimal damage or corrosion AMBER: Firebox has noticeable damage or corrosion, but no cracks or holes
Pipes/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
Vessel
GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure
D3030130 - Chiller, Reciprocating, Water Cooled
CR-5140 - Record the condition of the Compressor
GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional RED: Unacceptable Noise, Vibration, or overheating from compressor, significant damage, and/or operationally impaired
CR-5155 - Record the
Condenser
GREEN: Minimal corrosion or fouling of the condenser/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational RED: Significant damage, corrosion or fouling of the condenser/coils, no damage, operationally impaired
GREEN: Controls function properly
CR-5295 - Record the
Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced RED: Significant damage/corrosion to Enclosure, a number of panels are loose, displaced, or missing
CR-5305 - Record the
Evaporator
GREEN: Minimal corrosion or fouling of the evaporator/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational RED: Significant damage, corrosion or fouling of the evaporator/coils, operationally impaired
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
CR-5565 - Record the condition of the Receiver Tank
GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure
D3030135 - Chiller, Reciprocating, Air Cooled
CR-5140 - Record the condition of the Compressor
GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional
Condenser
GREEN: Minimal corrosion or fouling of the condenser/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational
CR-5175 - Record the
Condenser Fan(s) Assembly
GREEN: Motor operates properly, free of excessive noise/vibration, or overheating AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance
GREEN: Controls function properly
Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced
Evaporator
GREEN: Minimal corrosion or fouling of the evaporator/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational
Pipes/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
Tank
GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure
Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding
D3030140 - Chiller, Centrifugal, Water Cooled
CR-5110 - Record the condition of the Centrifugal Motor
GREEN: Motor operates properly, free of excessive noise/vibration, or overheating AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance
CR-5140 - Record the
Compressor
GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional
Condenser
GREEN: Minimal corrosion or fouling of the condenser/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational
CR-5210 - Record the
Controls/Sensors
GREEN: Controls function properly
Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced
Evaporator
GREEN: Minimal corrosion or fouling of the evaporator/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
Tank
GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure
D3030145 - Chiller, Gas Absorption, Water Cooled
CR-5000 - Record the condition of the Absorber
GREEN: Absorber has minimal damage and corrosion, but no leaks AMBER: Absorber has noticeable damage and corrosion, but minimal leaks and is still operational RED: Absorber has significant damage and corrosion, and noticeable leaks, operationally impaired
Compressor
GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional
Condenser
GREEN: Minimal corrosion or fouling of the condenser/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational
GREEN: Controls function properly
Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced
Evaporator
GREEN: Minimal corrosion or fouling of the evaporator/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational
CR-5430 - Record the condition of the Heat Generator
GREEN: Heating Element has little to no damage or corrosion, and is fully operational AMBER: Heating Element has noticeable damage or corrosion, but still operational RED: Heating Element has significant damage or corrosion, Pipes/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
CR-5555 - Record the
GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure
D3030150 - Chiller, Steam Absorption, Water Cooled
CR-5000 - Record the condition of the Absorber
GREEN: Absorber has minimal damage and corrosion, but no leaks AMBER: Absorber has noticeable damage and corrosion, but minimal leaks and is still operational RED: Absorber has significant damage and corrosion, and noticeable leaks, operationally impaired
Compressor
GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional
Condenser
GREEN: Minimal corrosion or fouling of the condenser/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational
GREEN: Controls function properly
Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced
Evaporator
GREEN: Minimal corrosion or fouling of the evaporator/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational
CR-5430 - Record the condition of the Heat Generator
GREEN: Heating Element has little to no damage or corrosion, and is fully operational AMBER: Heating Element has noticeable damage or corrosion, but still operational RED: Heating Element has significant damage or corrosion, Pipes/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
CR-5555 - Record the
GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure
D3030310 - Cooling Tower, Galvanized
CR-5025 - Record the condition of the Basin/Sump
GREEN: Sump has minimal damage or corrosion, no leaking AMBER: Sump has noticeable damage or corrosion, but no leaking RED: Sump has significant damage or corrosion, and noticeable leaking, operationally impaired
CR-5280 - Record the
Electrodes
GREEN: Conductivity Electrodes have minimal damage and corrosion, secure connections and fully functional AMBER: Conductivity Electrodes have noticeable damage and corrosion, some loose connections but still functional RED: Conductivity Electrodes have significant damage and corrosion, loose or missing connections, operationally impaired
CR-5325 - Record the condition of the Fan Assembly
GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational RED: Fans blades are out of balance, significantly bent or corroded, or fan is operationally impaired
CR-5350 - Record the condition of the Fill Material
GREEN: Filter has minimal to no dirt and debris, free of damage AMBER: Filter shows noticeable signs of debris, but little to no damage allowing unobstructed flow RED: Air Filter clogged with dirt and debris, or shows signs of damage such as, punctures, tears, rips
Pipes/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
D3030320 - Cooling Tower, Fiberglass
CR-5025 - Record the condition of the Basin/Sump
GREEN: Sump has minimal damage or corrosion, no leaking AMBER: Sump has noticeable damage or corrosion, but no leaking
Electrodes
GREEN: Conductivity Electrodes have minimal damage and corrosion, secure connections and fully functional AMBER: Conductivity Electrodes have noticeable damage and corrosion, some loose connections but still functional
Assembly
GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational
Material
GREEN: Filter has minimal to no dirt and debris, free of damage AMBER: Filter shows noticeable signs of debris, but little to no damage allowing unobstructed flow
Pipes/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
D3030330 - Cooling Tower, Stainless Steel
CR-5025 - Record the condition of the Basin/Sump
GREEN: Sump has minimal damage or corrosion, no leaking AMBER: Sump has noticeable damage or corrosion, but no leaking
Electrodes
GREEN: Conductivity Electrodes have minimal damage and corrosion, secure connections and fully functional AMBER: Conductivity Electrodes have noticeable damage and corrosion, some loose connections but still functional
Assembly
GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational
Material
GREEN: Filter has minimal to no dirt and debris, free of damage AMBER: Filter shows noticeable signs of debris, but little to no damage allowing unobstructed flow
Pipes/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
D3030902 - Condenser, DX, Evaporative
CR-5325 - Record the condition of the Fan Assembly
GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational
CR-5495 - Record the condition of the Louvers
GREEN: Louvers have minimal damage and corrosion, fully secured AMBER: Louvers have noticeable damage and corrosion, may be loose but still operational RED: Louvers have significant damage and corrosion, may be loose, missing, and/or operationally impaired
CR-5515 - Record the condition of the Nozzles
GREEN: Nozzles show no signs of damage, corrosion, or clogging, fully operational AMBER: Nozzles have some damage, corrosion, or clogs, noticeable obstruction of flow, but operational RED: Nozzles have significant damage and corrosion, severely obstructed flow, operationally impaired
CR-5615 - Record the condition of the Sump Pump
GREEN: Pump has minimal damage or corrosion, no unusual noise/vibration, no leaks, and is fully operational AMBER: Pump has noticeable damage or corrosion, slight leaking, unusual noise/vibration, but still operational RED: Pump has significant damage or corrosion, excessive noise/vibration, noticeable leaking, and/or is operationally impaired
Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding
D3030903 - Packaged DX Refrigerant System
CR-5140 - Record the condition of the Compressor
GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional
Condenser Fan(s) Assembly
GREEN: Motor operates properly, free of excessive noise/vibration, or overheating AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance
CR-5185 - Record the
Condensing Coils
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
RED: Coils are clogged, show some signs of damage, or significant scaling and deterioration.
GREEN: Controls function properly
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding
D3040106 - Air Handling Unit, Field Fabricated
CR-5120 - Record the condition of the Coils (Cooling)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
CR-5125 - Record the condition of the Coils (Heating)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
CR-5145 - Record the
Condensate Piping
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
Controls/Sensors
GREEN: Controls function properly
CR-5235 - Record the condition of the Dampers
GREEN: Damper has minimal damage, is secured and aligned properly, and fully operational AMBER: Damper has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational RED: Damper has significant damage and corrosion, noticeably loose, CR-5260 - Record the condition of the Drain Pan
GREEN: Drain Pan has minimal damage or corrosion AMBER: Drain Pan has noticeable damage or corrosion, but no leaks RED: Drain Pan has significant damage or corrosion, and noticeable leaks
Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced
CR-5330 - Record the
Assy
GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
D3040110 - Air Handling Unit, Central Station
CR-5120 - Record the condition of the Coils (Cooling)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
(Heating)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
GREEN: Controls function properly
GREEN: Damper has minimal damage, is secured and aligned properly, and fully operational AMBER: Damper has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational
Pan
GREEN: Drain Pan has minimal damage or corrosion AMBER: Drain Pan has noticeable damage or corrosion, but no leaks
Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced
CR-5340 - Record the condition of the Fan(s) Assembly
GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational
GREEN: Louvers have minimal damage and corrosion, fully secured AMBER: Louvers have noticeable damage and corrosion, may be loose but still operational
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
D3040114 - Air Handling Unit, Rooftop
CR-5120 - Record the condition of the Coils (Cooling)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
(Heating)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
GREEN: Controls function properly
GREEN: Damper has minimal damage, is secured and aligned properly, and fully operational AMBER: Damper has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational
Pan
GREEN: Drain Pan has minimal damage or corrosion AMBER: Drain Pan has noticeable damage or corrosion, but no leaks
Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced
CR-5340 - Record the condition of the Fan(s) Assembly
GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational
GREEN: Louvers have minimal damage and corrosion, fully secured AMBER: Louvers have noticeable damage and corrosion, may be loose but still operational
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
D3040220 - Fan System, Centrifugal In-Line
CR-5200 - Record the condition of the Controls
GREEN: Controls function properly
GREEN: Damper has minimal damage, is secured and aligned properly, and fully operational AMBER: Damper has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational
Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced
Assy
GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational
Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding
D3040230 - Fan System, Utility Set
CR-5330 - Record the condition of the Fan Assy
GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational
CR-5630 - Record the condition of the Switches Controls
GREEN: Switches function properly AMBER: None RED: Switches do not function properly
Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding
D3040240 - Fan System, Roof Exhaust
CR-5200 - Record the condition of the Controls
GREEN: Controls function properly
GREEN: Damper has minimal damage, is secured and aligned properly, and fully operational AMBER: Damper has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational
Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced
Assy
GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational
Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding
D3040330 - Circulating Pump, End Suction
CR-5045 - Record the condition of the Booster Pump, w/ Oil Reservoir
GREEN: Pump has minimal damage or corrosion, no unusual noise/vibration, no leaks, and is fully operational AMBER: Pump has noticeable damage or corrosion, slight leaking, unusual noise/vibration, but still operational RED: Pump has significant damage or corrosion, excessive noise/vibration, noticeable leaking, and/or is operationally impaired
D3040340 - Circulating Pump, Double Suction
CR-5045 - Record the condition of the Booster Pump, w/ Oil Reservoir
GREEN: Pump has minimal damage or corrosion, no unusual noise/vibration, no leaks, and is fully operational AMBER: Pump has noticeable damage or corrosion, slight leaking, unusual noise/vibration, but still operational RED: Pump has significant damage or corrosion, excessive noise/vibration, noticeable leaking, and/or is operationally impaired
D3040610 - Heat Exchanger, Plate Type
CR-5200 - Record the condition of the Controls
GREEN: Controls function properly
CR-5375 - Record the
Frame/Supports
GREEN: Supports have minimal damage and corrosion, are fully stable and secure AMBER: Supports have noticeable damage and corrosion, but still structurally stable and secure RED: Supports have significant damage and corrosion, and/or unstable or not secured
CR-5465 - Record the
Insulation
GREEN: Insulation has minimal deterioration, and is mostly in place where necessary AMBER: Insulation has noticeable deterioration, portions may be loose or displaced, but mostly intact RED: Insulation is significantly damaged, or large portions are displaced or missing
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
CR-5570 - Record the condition of the Relief Valve
GREEN: Valve has little to no damage or corrosion, is fully operational AMBER: Valve shows some damage or corrosion, valve functions but may require calibration RED: Valve has significant damage or corrosion, is operationally impaired
CR-5590 - Record the condition of the Steam Modulating Valve
GREEN: Valve has little to no damage or corrosion, is fully operational AMBER: Valve shows some damage or corrosion, valve functions but may require calibration
D3040620 - Heat Exchanger, Shell Tube
CR-5200 - Record the condition of the Controls
GREEN: Controls function properly
CR-5375 - Record the
Frame/Supports
GREEN: Supports have minimal damage and corrosion, are fully stable and secure AMBER: Supports have noticeable damage and corrosion, but still structurally stable and secure RED: Supports have significant damage and corrosion, and/or unstable or not secured
CR-5465 - Record the
Insulation
GREEN: Insulation has minimal deterioration, and is mostly in place where necessary AMBER: Insulation has noticeable deterioration, portions may be loose or displaced, but mostly intact RED: Insulation is significantly damaged, or large portions are displaced or missing
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
CR-5570 - Record the condition of the Relief Valve
GREEN: Valve has little…