This solicitation seeks proposals for construction services at two sites for Crane Army Ammunition Activity in Crane, Indiana. At the Railcar Site, the scope of work includes demolishing existing buildings and structures, constructing a new rail holding yard, and conducting surveys to identify materials that require special handling. The new Defense Logistics Agency Disposition site will include building a new operations building, storage building with loading dock, and various site works. The contractor will relocate an existing radiation detection system. The solicitation was issued by the Naval Facilities Engineering Command on behalf of the Department of the Navy. Offerors should submit proposals in accordance with the instructions and deadlines provided in the solicitation.
View the file
Other files
Show 40 more
Latest 50 of 53 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
(15)
ELECTRICAL SYMBOLS
S L 1 A
LIGHTING FIXTURES
SUBSCRIPTS: A = LIGHT FIXTURE TYPE
L1B:1b =PANELBOARD NAME, CIRCUIT 1, CONTROL ZONE b
RECESSED, CEILING OR PENDANT MOUNTED FIXTURE
WALL MOUNTED LIGHT FIXTURE
EMERGENCY FIXTURE
WALL WASHER
LINEAR WALL WASHER
SURFACE OR PENDANT STRIP FIXTURE
RECESSED OR SURFACE 2 x 2 FIXTURE
RECESSED OR SURFACE 2 X 4 FIXTURE
RECESSED OR SURFACE 1 X 4 FIXTURE
WALL MOUNTED FIXTURE
PENDANT LINEAR FIXTURE
BATTERY PACK WITH HEADS
ILLUMINATED BOLLARD
ROADWAY OR PARKING LOT STANDARD
BUILDING MOUNTED WALLPACK
CEILING OR PENDANT MOUNTED EXIT SIGN
WALL MOUNTED EXIT SIGN
SHADING INDICATES ILLUMINATED FACE OF EXIT SIGN
ARROW INDICATES EXIT SIGN DIRECTIONAL ARROW
RECEPTACLES
SUBSCRIPTS: 1b = CIRCUIT 1, CONTROL ZONE b, K=K RATED POWER, P=PROJECTOR, WP =
WEATHERPROOF WHILE IN USE COVER, S = SWITCHED, F = FLUSH FLOOR, SM = SURFACE
MOUNT FLOOR
DUPLEX RECEPTACLE, (CT = COUNTER TOP HEIGHT, GFI = GROUND-FAUL INTERRUPTER,
S=SWITCHED)
QUADRUPLEX RECEPTACLE
SPECIAL RECEPTACLE, NEMA DESIGNATION AS INDICATED
DUPLEX CEILING RECEPTACLE
QUADRUPLEX CEILING RECEPTACLE
SPECIAL CEILING RECEPTACLE, NEMA DESIGNATION AS INDICATED
DUPLEX FLOOR RECEPTACLE
QUADRUPLEX FLOOR RECEPTACLE
SPECIAL FLOOR RECEPTACLE, NEMA DESIGNATION AS INDICATED
SWITCHES AND CONTROLS
SINGLE POLE TOGGLE SWITCH
SUBSCRIPTS: 3b = TYPE 3, CONTROL ZONE b
3 = 3-WAY, 2 = DOUBLE POLE, 4 = 4 WAY,
D = DIMMER, K = KEY OPERATED, XP = EXPLOSION PROOF,
T = TIMER OPERATED, LV = LOW VOLTAGE,
OS = OCCUPANCY SENSOR, F = FUSED, P = PILOT LIGHT,
M = MANUAL MOTOR STARTER
DIMMING SYSTEM
OCCUPANCY SENSOR, CEILING MOUNTED, MULTI DIRECTIONAL
OCCUPANCY SENSOR, WALL MOUNTED, DIRECTIONAL
TIME CLOCK
PUSHBUTTON OR CONTROL STATION
PHOTOELECTRIC RELAY
LIGHTING CONTACTOR
FUSED DISCONNECT SWITCH
30 = SWITCH AMPERE RATING
(15) = FUSE AMPERE RATING
NON-FUSED DISCONNECT SWITCH
30 = SWITCH AMPERE RATING
VARIABLE FREQUENCY DRIVE
PRE-WIRED CONTROL PANEL
SITE
POLE MOUNTED TRANSFORMER
PAD MOUNTED TRANSFORMER
UTILITY POLE
NEW MANHOLE, E=ELEC, C=COMM, P=PULLBOX, H=HANDHOLE
ELECTRICAL DUCTBANK (PRIMARY)
ELECTRICAL DIRECT BURIED CONDUITS (SECONDARY)
OVERHEAD WIRES
REFER TO CIVIL PLANS, SHEET C0011, FOR OTHER
UTILITY SYMBOLS AND ABBREVIATIONS.
GENERAL
CIRCUIT HOME RUN
EQUIPMENT
MOTOR
RACEWAYS AND WIRES
JUNCTION BOX, CEILING MOUNTED
JUNCTION BOX WALL MOUNTED
JUNCTION BOX FLOOR MOUNTED
DEPICTION OF EXISTING AND NEW ELECTRICAL WORK
LIGHTWEIGHT SOLID LINE = EXISTING TO REMAIN
HEAVY DASHED LINE = REMOVE OR RELOCATE EXISTING
HEAVY SOLID LINE = NEW WORK
DISTRIBUTION EQUIPMENT (EQUIPMENT PREFIX)
LIGHTING OR RECEPTACLE PANELBOARD
RELAY CABINET (RC)
TRANSFORMER (T)
EQUIPMENT DESIGNATION LOGIC
SPECIAL PREFIX (E=EMERGENCY, S=STANDBY, U=UPS, K=K-RATED) IF
APPLICABLE
VOLTAGE (L=208Y/120V, H=480Y/277V)
AREA DESIGNATOR, BUILDING, LEVEL OR FLOOR NO.
SEQUENCE (A, B, C...), IF APPLICABLE
ONE-LINE DIAGRAMS
FUSED CUTOUT
TRANSFORMER
CURRENT TRANSFORMER
PANELBOARD
DISCONNECT SWITCH, 30 = AMPERE RATING
FUSE, (20) = AMPERE RATING
MOLDED CASE CIRCUIT BREAKER, 20 = TRIP RATING
SURGE PROTECTIVE DEVICE
ELECTRICAL UTILITY METER: M=UTILITY METER
V=VOLT METER
W=WATT METER
GROUND
ES
PE
T
M
J
J
J
3b
VFD
PWCP
(20)
(XX)
M
SPD
ELECTRICAL GENERAL NOTES
1. ALL SYMBOLS, ABBREVIATIONS AND GENERAL NOTES SHOWN ARE NOT NECESSARILY USED ON THIS
PROJECT.
2. LIGHTING CONTROL ZONE DESIGNATIONS INDICATE WHICH DEVICES CONTROL WHICH GROUPS OF
FIXTURES. WHERE LOCAL SWITCHES AND DIMMERS ARE SHOWN, OR WHERE NO CONTROL ZONE
DESIGNATION IS INDICATED, LOCAL CONTROL DEVICES SHALL ONLY CONTROL FIXTURES IN THEIR
RESPECTIVE ROOMS.
3. COORDINATE INSTALLATION OF LIGHTING FIXTURES WITH LOCATION OF EQUIPMENT, PIPING AND
DUCTWORK.
4. SEE ONE-LINE DIAGRAM AND EQUIPMENT DATA SCHEDULE FOR WIRE SIZES, CONDUIT SIZES, AND
DEVICE RATINGS NOT SHOWN ON POWER PLANS.
5. PROVIDE HOUSEKEEPING PADS FOR FLOOR MOUNTED ELECTRICAL EQUIPMENT.
6. VOLTAGE DROP SHALL BE CONSIDERED WHEN DETERMINING THE EXACT ROUTING OF BRANCH WIRING.
INCREASE BRANCH CIRCUIT CONDUCTOR SIZE AS NECESSARY TO MAINTAIN NO MORE THAN 2
PERCENT VOLTAGE DROP BETWEEN THE PANELBOARD AND THE FURTHEST BRANCH DEVICE. BASED
ON THE PANEL BOARD DIRECTORY LOAD AND ACTUAL CIRCUIT ROUTING.
7. UNLESS OTHERWISE NOTED, ALL ELECTRICAL WORK AND MATERIALS ARE NEW AND PROVIDED BY
CONTRACTOR.
8. MOUNTING HEIGHTS ABOVE FINISHED FLOOR, TO CENTERLINE OF DEVICE, ARE AS FOLLOWS, UNLESS
OTHERWISE NOTED:
WALL AND END MOUNTED EXIT SIGNS
LIGHTING SWITCHES
OCCUPANCY SENSOR SWITCH
WALL MOUNTED OCCUPANCY SENSORS
GENERAL PURPOSE RECEPTACLES
COUNTER TOP RECEPTACLES (CT)
HAND DRIER JUNCTION BOX
CLOCK OUTLET
FURNITURE JUNCTION BOX
96-INCHES
48-INCHES
48-INCHES
120-INCHES
18-INCHES
8 INCHES ABOVE COUNTER
48-INCHES
90-INCHES
18-INCHES
ELECTRICAL ABBREVIATIONS
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
ARCH ARCHITECTURAL
AV AUDIO AND VISUAL
BKR BREAKER
BLDG BUILDING
C CONDUIT
CAB CABINET
CB CIRCUIT BREAKER
CKT CIRCUIT
CLG CEILING
CONST CONSTRUCTION
CONT CONTINUATION
CT COUNTER TOP
DIST DISTRIBUTION
DS DISCONNECT SWITCH
DWG DRAWING
ELEC ELECTRICAL
ELEV ELEVATOR
EMER EMERGENCY
EWC ELECTRIC WATER COOLER
EXIST EXISTING
FACP FIRE ALARM CONTROL PANEL
FDR FEEDER
G GROUND
GEN GENERATOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
GFGI GOVERNMENT FURNISHED, GOVERNMENT
INSTALLED
GFCI GOVERNMENT FURNISHED, CONTRACTOR
INSTALLED
HVAC HEATING, VENTILATION AND AIR CONDITIONING
IDS INTRUSION DETECTION SYSTEM
JB JUNCTION BOX
LTG LIGHTING
MCB MAIN CIRCUIT BREAKER
MECH MECHANICAL
MH MOUNTING HEIGHT
MLO MAIN LUGS ONLY
MTS MANUAL TRANSFER SWITCH
N NEUTRAL
OH OVERHEAD
PC PERSONAL COMPUTER
PWR POWER
QTY QUANTITY
RECP RECEPTACLE
RM ROOM
SECT SECTION
SPEC SPECIFICATION
SURF SURFACE
SW SWITCH
SYM SYMMETRICAL
SPD SURGE PROTECTION DEVICE
TEL TELEPHONE
TELCOM TELECOMMUNICATIONS
TYP TYPICAL
UG UNDERGROUND
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER
SUPPLY
VD VOLTAGE DROP
VFD VARIABLE FREQUENCY DRIVE
WP WEATHERPROOF
XFMR TRANSFORMER
XP DUST IGNITION-PROOF
Y WYE CONNECTED
L1B-1,3
9. ALL UNDERGROUND CONDUITS SHALL BE PVC CONDUITS EXCEPT WHEN TRANSITIONING FROM BELOW
GRADE TO ABOVE WHERE RIGID STEEL CONDUIT SHALL BE USED. RIGID STEEL CONDUIT SHALL ALSO
BE USED WITHIN 6-INCHES PRIOR TO TRANSITION.
501 North Broadway
Saint Louis, MO 63102
(314) 335-4000
LAUREN SHIPMAN
CRANE ARMY AMMO ACTIVITY
11/21/2019
12805272
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
H
I
G
H
W
A
Y
H
I G
H
W
G
G
G
G
G
G
S
S
S
S
W
W
W
W
W
W
W
W
W
W
W W W W
W
W
S
D
W
W
W
W
W
W
W
W
W
W
G
S
DC
C
W
W
F
M
E
S
E
S
E
S
E
S
E
S
E
S
E
S
E
S
E
S
E
S
E
ES ES
E
S
E
S
E
S
E
S
E
S
S1
L1B-2,4
S1
L1B-2,4
S1
L1B-2,4
S2
L1B-1,3
S2
L1B-1,3
S2
L1B-1,3
S2
L1B-1,3
S2
L1B-1,3
L1B-1,3
S1
L1B-1,3
L1B-2,4
S1
S1
L1B-6,8
S1
L1B-6,8
S1
L1B-2,4
S1
L1B-2,4
S1
L1B-2,4
(TYP.)
OPERATIONS
BUILDING
SCALE
CANOPY
LOADING
DOCK
STORAGE
BUILDING
(TYP.)
WETLAND
WETLAND
3F-6
3F-5
3F-4
3F-3
3F-2
3F-1
3F-6-2
3F-6-1
3F-6-3
3F-6-4
3F-6-5
EXISTING HYDRAULIC
RECLOSER MOUNTED
TO THIS POLE
(TYP.)
L1B-6,8
S1
L1B-6,8
S1
S1
L1B-1,3
S1
L1B-6,8
GRAPHIC SCALE
501 North Broadway
Saint Louis, MO 63102
(314) 335-4000
LAUREN SHIPMAN
CRANE ARMY AMMO ACTIVITY
11/21/2019
N
100'25' 50'
1" = 50'
1" = 50'
A1
DLA SITE
OVERALL SITE PLAN
GENERAL NOTES
1. REFER TO CIVIL PLANS, (SHEET C1011) AND ONE LINE DIAGRAM (SHEET
E6011) FOR ELECTRICAL DEMOLITION REQUIREMENTS.
2. REFER TO ONE LINE DIAGRAM FOR CONDUIT AND WIRE SIZES.
3. REFER TO SHEET E1011 FOR EXTERIOR BUILDING LIGHTING AND CANOPY
LIGHTING.
4. COORDINATE POWER CONNECTION REQUIREMENTS WITH WEIGHT SCALE
DRAWINGS AND RADIATION DETECTION UNITS PRIOR TO INSTALLATION.
1. EXISTING OH LINES TO REMAIN.
2. EXISTING UTILITY POLE TO REMAIN.
3. EXISTING UTILITY POLE "3F-6" TO BE MODIFIED. REFER TO ONE LINE
DIAGRAM ON SHEET E-6011 AND POLE DETAILS ON SHEET E5031.
4. NEW GUY WIRE AS NEEDED TO BALANCE EXISTING UTILITY POLE. REFER
TO DETAIL ON SHEET E5031. COORDINATE WITH CIVIL PLANS.
5. PROVIDE (1) 2-INCH CONCRETE ENCASED CONDUITS FOR POWER
SERVICE LINE AND (1) 2-INCH SPARE CONDUIT. CAP SPARE CONDUIT
12-INCHES AFG AT RISER POLE. REFER TO SHEET E6011 AND E5011.
CONDUITS MUST BE A MINIMUM 2-FEET FROM THE EDGE OF THE RAMP
FOUNDATION.
6. POLE MOUNTED TRANSFORMER. REFER TO SHEET E6011 AND MOUNTING
DETAILS ON SHEET E-5031.
7. AMI METER WITH CT ENCLOSURE. FOR MOUNTING OPTIONS REFER TO
DETAILS ON SHEET E5011.
8. LIGHT POLE, REFER TO LIGHT POLE DETAIL ON SHEET E5021.
9. PROVIDE (2) 3/4-INCH, UG, SCHEDULE 40, PVC CONDUITS FOR
RELOCATED RADIATION DETECTION SYSTEM AND NEW SCALE SYSTEM.
REFER TO ONE LINE AND PANEL SCHEDULE FOR WIRING REQUIREMENTS.
10. PROVIDE UG, SCHEDULE 40, PVC CONDUIT BETWEEN PANELBOARD AND
CANOPY COLUMN FOR CANOPY LIGHTING CIRCUIT.
11. REFER TO POWER PLAN FOR LOCATION OF PANELBOARD(S) LOCATED
INSIDE BUILDING(S).
12. PROVIDE SCHEDULE 40 PVC CONCRETE ENCASED, 1-INCH CONDUIT
BETWEEN PANELBOARD AND LOADING DOCK.
13. PROVIDE SCHEDULE 40, DIRECT BURIED, 1-INCH PVC CONDUIT FOR SITE
LIGHTING. CONCRETE ENCASE CONDUITS UNDER DRIVABLE SURFACES.
14. GATES MUST BE BONDED AT THE GATE SUPPORT POSTS. PROVIDE
BONDING JUMPERS AT EACH FENCE CORNER AND 150FT INTERVALS
ALONG THE FENCE. REFER TO DETAILS ON E-5011.
15. RELOCATED AUTO HYDRANT FLUSHING SYSTEM. REFER TO CIVIL
DRAWINGS FOR EXISTING LOCATION AND DEMOLITION NOTES. PROVIDE
DIRECT BURIED, 3/4-INCH, SCHEDULE 40, PVC CONDUIT FROM
PANELBOARD "L1B" LOCATED IN OPERATIONS BUILDING. (VOLTAGE AND
POWER SOURCE OF EXISTING UNIT TO BE VERIFIED PRIOR TO
INSTALLATION).
16. STANDARD ELECTRICAL HANDHOLE, NON-TRAFFIC, TYPE 7, 12-INCHES X
24-INCHES X 24-INCHES.
17. PRIMARY 15KV OHW.
18. PROVIDE J-BOX AT BOTTOM OF WOOD POLE 3F-6-2,3,4, & 5 FOR
PERIMETER LIGHTING. REFER TO DETAIL ON SHEET E5031.
19. NEW 50FT, CLASS 3, WOOD POLE.
20. SHADED AREA DENOTES OPTIONAL SCOPE. SEE G001 FOR ADDITIONAL
INFORMATION ON OPTIONS.
21. COORDINATE UG ELECTRICAL CONNECTIONS WITH SCALE AND
RADIATION DETECTOR LAYOUT PRIOR TO PAVING IN THIS AREA.
22. IF "OPTION" IS TAKEN, PROVIDE LIGHT POLE AT THIS LOCATION AND
ADJUST UG CONDUIT ROUTING ACCORDINGLY.
23. (1) 1-INCH CONCRETE ENCASED CONDUIT FOR POWER TO LIFT STATION
AND ONE 1-INCH EMPTY CONDUIT WITH PULL STRING FOR CONTROLS.
COORDINATE REQUIREMENTS WITH CIVIL AND PLUMBING DRAWINGS.
REFER TO ONE LINE DIAGRAM AND PANEL SCHEDULES.
KEYNOTES
12805273
T V
3 3 3 3 3 3 3
SWITCH ZONE "a" SWITCH ZONE "b" SWITCH ZONE "c" SWITCH ZONE "d" SWITCH ZONE "e"
5 5 5 5
S.1
S.C
S.A
S.2 S.3 S.4 S.5 S.6 S.7 S.8 S.9 S.10 S.11
S.B
STORAGE
S-101
FIRE RISER
S-104
LOCKABLE STOR
S-103
B1 L1A :5
B1 L1A :5
B1 L1A :5
B1 L1A :5
B1 L1A :5
B1 L1A :5
B1 L1A :5
B1 L1A :5
B1 L1A :5
B1 L1A :5
B1 L1A :5
B1 L1A :5
B1 L1A :3
B1 L1A :3
B1 L1A :3
B1 L1A :3
B1 L1A :3
B1 L1A :3
B1 L1A :3
B1 L1A :3
B1 L1A :3
B1 L1A :3
B1 L1A :3
B1 L1A :3
B1 L1A :3
B1 L1A :3
B1 L1A :3
B1 L1A :3
B1 L1A :3
B1 L1A :3
B1 L1A :3
B1 L1A :3
B1 L1A :3
B1 L1A :3
B1 L1A :3
B1 L1A :3
B1 L1A :1
B1 L1A :1
B1 L1A :1
B1 L1A :1
B1 L1A :1
B1 L1A :1
B1 L1A :1
B1 L1A :1
B1 L1A :1
B1 L1A :1
B1 L1A :1
B1 L1A :1
B1 L1A :1
B1 L1A :1
B1 L1A :1
B1 L1A :1
B1 L1A :1
B1 L1A :1
B1 L1A :1
B1 L1A :1
B1 L1A :1
B1 L1A :1
B1 L1A :1
B1 L1A :1
X L1A :9
X L1A :9
X L1A :9
W L1A :7
W L1A :7
W L1A :7
W L1A :7
W L1A :7
W L1A :7
W L1A :7
W L1A :7
W L1A :7
W L1A :7 ba L1A c d e b a e
TIME CLOCK
TC#1
B1
OPTION SCOPE:
SHADED AREA DENOTES OPTION SCOPE AND INCLUDES
ASPECTS OF ARCHITECTURE, STRUCTURE, BUILDING
SYSTEMS, AND FINISHES BETWEEN GRIDLINE S.9 AND S.11.
DRAWINGS SHOW FINAL INTENT IF OPTION SCOPE IS
TAKEN. BASE BID DOES NOT INCLUDE OPTION SCOPE.
O P T I O N S C O P E
0"
X L1A :9
3W L1A :7
C L1A :7
C L1A :7
C L1A :7
X.B
X.A
X.1 X.2 X.3
COVERED STORAGE
S-000 C L1A :7
PE
A1 L1B :7
A1 L1B :7
A1 L1B :7
A1 L1B :7
A1 L1B :7
A1 L1B :7
A1 L1B :7
D1 L1B :9
D1 L1B :9
T1 L1B :9
T1 L1B :9
D L1B :7
D L1B :7
D L1B :7
D L1B :7
D L1B :7
D L1B :7
D1 L1B :7
D1 L1B :7
X L1B :41
X L1B :41
OS OS
D
D
W L1B :5
W L1B :5
W L1B :5
C.B
C.A
C.2C.1
G L1B :9
OPEN OFFICE
O-101
CONFERENCE
O-108
UTILITY
O-106
WOMEN
O-105
MEN
O-104
CORRIDOR
O-103
KITCHENETTE
O-102
TELECOM
O-109
P L1B :7
G L1B :9
B
B
B
B
L1B
L1B: 7
L1B: 41
L1B: 5
L1B: 9
CONTACTOR
TIME CLOCK
TC#2
T L1B:9
T L1B:9
PE
1/8" = 1'-0"
24'4' 8' 16'
C
B
D
N62473-18-D-5801
1596603
N
AV
AL
FA
C
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
C O M M
AN
D
M
ID
AT
LA
N
TI
C
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
PM/DM BHD/PJB
BRANCH MANAGER
CHIEF ENG/ARCH EA
SATISFACTORY TO
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
A/E INFO
D E P A R T M E N T
O F
T H E
N A V Y
N A V A L
F A C
IL
IT
IE
S
E N G
IN
E E R
IN
G
C O M M A N D
N
AV
AL
S
TA
TI
O N
N O R
FO
LK
VA
C R
AN
E, IN
D
IA
N A
LAUREN SHIPMAN
CRANE ARMY AMMO ACTIVITY
S
YM
D E S C R
IP
TI
O N
D
AT
E
AP
P R
C
AA
A
EX
P
LO
S
IV
E R
AI
LC
AR
H O
LD
IN
G
YA
R D
(P
SEAL
501 North Broadway Saint Louis, MO 63102
(314) 335-4000
M
ID
LA
N T C I C O R E
A
C
B
D
A
DATE
N
AV
AL
S U P P O R T
AC
TI
VI
TY
C R
AN
E
FIRE PROTECTION
DRAWFORM REVISION: 31 JANUARY 2017
GRAPHIC SCALE
PW DRAWING NO. PW7534
11/21/2019
As indicated
:0 :0
A M
E1011
EL
EC
TR
IC
AL
12805274
HS HS RK
LI
G H
TI
N G
P
LA
N S
1/8" = 1'-0"C2
STORAGE FACILITY LIGHTING PLAN
1/8" = 1'-0"B3
CANOPY LIGHTING PLAN
1/4" = 1'-0"A1
OPERATIONS LIGHTING PLAN
SCALE: 1/4" = 1'
2' 4' 8' 12'
KEYNOTES
COORDINATE MOUNTING HEIGHT WITH FINAL TELECOMMUNICATIONS
CABLE TRAY AND EQUIPMENT LAYOUT.
MOUNT LIGHT FIXTURES IN THIS ROOM 10'-0" AFF. COORDINATE LIGHT
FIXTURE LOCATIONS WITH MECHANICLA DUCTWORK.
MOUNTED 12-FEET ABOVE FINISHED GRADE.
CANOPY LIGHTING. MOUNT TO BOTTOM OF CANOPY STRUCTURE.
PROVIDE PHOTOCELL AND MANUAL SWITCH IN NEMA 4X ENCLOSURE
MOUNTED ON CANOPY COLUMN. WIRE THROUGH TC#1, PHOTOCELL ON,
TIME CLOCK OFF.
OCCUPANCY SENSOR, CONTROLS LIGHTS IN INDICATED SWITCH ZONE,
UON.
PENDANT MOUNTED TASK LIGHT CENTERED, 48-INCHES ABOVE SINK.
PROVIDE UNISTRUT AND SUPPORTS REQUIRED TO MOUNT PANELBOARD
TO P.E.M.B. WALL TYPE.
TWO CHANNEL TIME CLOCK.
8-POLE CONTACTOR. WIRE SITE LIGHTING THROUGH CONTACTOR AND
TC#2, CHANNEL #1. WIRE BUILDING MOUNTED LIGHTS THROUGH CHANNEL
#2. CONTROLS: PHOTOCELL ON, TIME CLOCK OFF. MOUNT PHOTOCELL ON
ROOF EDGE FACING NORTH SKY.
**OPTION** IF OPTION SCOPE IS TAKEN, PROVIDE EXIT SIGN ABOVE DOOR.
**OPTION** IF OPTION SCOPE IS TAKEN, PROVIDE LIGHT FIXTURES,
OCCUPANCY SENSOR AND LIGHT WITCH IN SHADED AREA AND RELATED
CIRCUITING FOR SWITCHZONE "e".
**OPTION** IF OPTION SCOPE IS TAKEN, PROVIDE THIS EXTERIOR LIGHT
FIXTURE.
N
N GENERAL NOTES
1 AUTOMATICALLY CONTROLLED LIGHT FIXTURES THROUGH OCCUPANCY
SENSOR ALONG PATH OF EGRESS SHOULD BE TIED TO RELAY IN FIRE
ALARM PANELBOARD PER NFPA 101, SECTION 7.8.1.2.2 (5)
REQUIREMENTS. REFER TO DETAIL A4/5011.
A a,b
A a,b
A c,d
A c,d
A e
PE
FACP
MMMMMMMM
J J
J J
DCLMP
DCLMP
J J
J J J
J
J
L1A
GFI, WP
GFI, WP GFI, WP
GFI, WP
GFI, WP
GFI, WPGFI, WPGFI, WPGFI, WPGFI, WP
GFI, WP
TYP.
UH
UH
EF
EUH
S.1
S.C
S.A
S.2 S.3 S.4 S.5 S.6 S.7 S.8 S.9 S.10 S.11
S.B
X.B
X.A
X.3
STORAGE
S-101
FIRE RISER
S-104
LOCKABLE STOR
S-103
METER
LOCATION
SERVICE
DISCONNECT
GROUND
BAR
L1A: 6
L1A: 12
L1A: 13,15,17 L1A: 19,21,23
L1A: 14,16,18
L1A: 20,22,24 L1A: 8
L1A: 4
L1A:4L1A:4L1A:4L1A:4 L1A:4 L1A:4L1A:11
L1A:12 L1A:12
L1A:11 L1A:8 L1A:8
L1A:8
L1A:12 L1A:12 L1A:12
L1A:12
L1A:12
L1A:12L1A:12
L1A:12
L1A:6L1A:6
L1A:6
L1A:6
L1A:6
L1A:12
L1A:6 L1A:8
L1A: 31 L1A: 33
L1A: 37,39,41
L1A: 28,30
L1A:26
OPTION SCOPE:
SHADED AREA DENOTES OPTION SCOPE AND INCLUDES
ASPECTS OF ARCHITECTURE, STRUCTURE, BUILDING
SYSTEMS, AND FINISHES BETWEEN GRIDLINE S.9 AND S.11.
DRAWINGS SHOW FINAL INTENT IF OPTION SCOPE IS
TAKEN. BASE BID DOES NOT INCLUDE OPTION SCOPE.
O P T I O N S C O P E
7 7
81 1
L1A:34 L1A:32
L1B
GFI, WP
GFI, WP
GFI, WP
GFI, WP
CT(GFI)
CT
CT
CT
CTCT
CT(GFI)
42"AFF (GFI) 42"AFF (GFI)
GFI
CU
CU
ACU
IWH
IWH
AHU
C.B
C.A
C.2C.1
CONFERENCE
O-108
OPEN OFFICE
O-101
UTILITY
O-106
WOMEN
O-105MEN
O-104
CORRIDOR
O-103
KITCHENETTE
O-102
TELECOM
O-109
60" AFF
SERVICE
DISCONNECT
GROUND BAR
METER
LOCATION 6
IWH
S
L1B: 43
S S
S
S S
SL1B: 11
L1B: 15
L1B:15
L1B:15
L1B:15L1B:15L1B:15
L1B: 24
L1B:24
L1B: 18
L1B: 13
L1B: 53
L1B:51
L1B:51 L1B:51
L1B:51
L1B: 26
L1B:26L1B:26
L1B: 17 L1B: 19
L1B: 21
L1B:21
L1B: 27,29
L1B: 31,33
L1B: 36,38
L1B: 37,39
L1B: 20,22
L1B: 16 L1B:16
L1B:16
L1B:16
L1B:16
L1B:16
GFI
L1B: 23
L1B:23
L1B:23
L1B:23
L1B:23
L1B: 14
L1B:14L1B:14
L1B: 51
L1B: 40
L1B: 44,46,48
L1B: 45,47 L1B: 10
L1B
L1B:10
L1B:10
L1B:10L1B:10
L1B:10
L1B: 12
L1B: 35
L1B:34
NEMA
L6-30R
22"
AFF
9 9
9 9
MICROWAVE
EF
L1B:50
SPECIFICATION DIVISION NUMBER:
DIVISION 21 - FIRE PROTECTION
DIVISION 22 - PLUMBING
DIVISION 23 - MECHANICAL
DIVISION 26 - ELECTRICAL LOAD:
FULL LOAD AMPERES (FLA) ARE SHOWN. FOR HORSE POWER (HP) AND
KILOWATTS (KW), IF APPLICABLE, SEE MECHANICAL SCHEDULES.
1.
2.
SCHEDULE NOTES
1. ALL MAGNETIC AND SOLID STATE STARTERS ARE TO BE EQUIPPED WITH
AUXILIARY CONTACTS, PILOT LIGHTS AND FUSED CONTROL POWER
TRANSFORMERS. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
2. DISCONNECT SWITCHES AND CONTROLLERS ARE NOT SHOWN ON PLANS FOR
CLARITY. LOCATE DISCONNECT SWITCHES AND CONTROLLERS ADJACENT TO
EQUIPMENT IT IS SERVING AND PER NEC CLEARANCE REQUIREMENTS UNLESS
OTHERWISE NOTED.
SCHEDULE GENERAL NOTES
STARTER TYPE:
COMB - COMBINATION MAGNETIC FVNR WITH FUSIBLE DISCONNECT SWITCH
FVR - FULL VOLTAGE REVERSING MAGNETIC STARTER
FVNR - FULL VOLTAGE NON-REVERSING MAGNETIC STARTER
MAN - MANUAL STARTER
SDS - STAR DELTA STARTER
PWCP - PREWIRED CONTROL PANEL
VFD - VARIABLE FREQUENCY DRIVE
2S2W - 2 SPEED 2 WINDING
2S1W - 2 SPEED SINGLE WINDING
3.
SCHEDULE NOTES (CONT'D)
ACCESSORIES:
HOAP - HOA WITH PILOT LIGHT
PB - START/STOP PUSH BUTTON (MOMENTARY CONTACT)
KEY TO REMARKS:
(1) FIRE ALARM INTERLOCK
(2) INTEGRAL DISCONNECT SWITCH
(3) MOUNT DISCONNECT SWITCH ON EQUIPMENT HOUSING
(4) UNIT IS FED FROM RESPECTIVE CONDENSER UNIT
(5) PUSHBUTTON FURNISHED BY DIV. 23, INSTALLED AND CONNECTED BY DIV. 26
(6) SINGLE POINT POWER CONNECTION PACKAGE UNIT
4.
5.
SCHEDULE NOTES (CONT'D)
1/8" = 1'-0"
24'4' 8' 16'
C
B
D
N62473-18-D-5801
1596603
N
AV
AL
FA
C
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
C O M M
AN
D
M
ID
AT
LA
N
TI
C
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
PM/DM BHD/PJB
BRANCH MANAGER
CHIEF ENG/ARCH EA
SATISFACTORY TO
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
A/E INFO
D E P A R T M E N T
O F
T H E
N A V Y
N A V A L
F A C
IL
IT
IE
S
E N G
IN
E E R
IN
G
C O M M A N D
N
AV
AL
S
TA
TI
O N
N O R
FO
LK
VA
C R
AN
E, IN
D
IA
N A
LAUREN SHIPMAN
CRANE ARMY AMMO ACTIVITY
S
YM
D E S C R
IP
TI
O N
D
AT
E
AP
P R
C
AA
A
EX
P
LO
S
IV
E R
AI
LC
AR
H O
LD
IN
G
YA
R D
(P
SEAL
501 North Broadway Saint Louis, MO 63102
(314) 335-4000
M
ID
LA
N T C I C O R E
A
C
B
D
A
DATE
N
AV
AL
S U P P O R T
AC
TI
VI
TY
C R
AN
E
FIRE PROTECTION
DRAWFORM REVISION: 31 JANUARY 2017
GRAPHIC SCALE
PW DRAWING NO. PW7534
11/21/2019
As indicated
:0 :0
A M
E1021
EL
EC
TR
IC
AL
12805275
HS HS RK
P O W
ER
P
LA
N S
1/8" = 1'-0"C1
STORAGE FACILITY POWER PLAN
1/4" = 1'-0"B1
OPERATIONS POWER PLAN
SCALE: 1/4" = 1'
2' 4' 8' 12'
KEYNOTES
WP J-BOX FOR RADON FAN AND DISCONNECT SWITCH, MOUNTED 5'-0" AFG.
PROVIDE 120V, 20A, WP GFI RECEPTACLE UNDER CANOPY. SURFACE
MOUNT TO STRUCTURAL COLUMN 42-INCHES ABOVE FINISHED GRADE AT
TWO OPPOSITE CORNERS OF CANOPY (ONLY ONE SHOWN).
COMBINATION POWER AND DATA FLOOR BOX. REFER TO
TELECOMMUNICATIONS DETAILS SHEET. PROVIDE UG CONDUIT TO
NEAREST FULL HEIGHT WALL.
COORDINATE OH DOOR MOTOR AND CONTROLS REQUIREMENTS WITH
SPECIFICATION SECTION 08 33 23. BASIS OF DESIGN: 208V, 3-PHASE, 1-HP
MOTOR.
PROVIDE TOGGLE SWITCH 6-INCH ABOVE COUNTER FOR FOOD WASTE
DISPOSAL UNIT.
COORDINATE LOCATIONS AND MOUNTING HEIGHTS OF IWH DISCONNECTS
WITH PLUMBING DRAWINGS.
**OPTION** IF OPTION SCOPE IS TAKEN, PROVIDE POWER TO OVERHEAD
DOORS AND RELATED DOOR CONTROLERS.
**OPTION** IF OPTION SCOPE IS TAKEN, PROVIDE THIS RECEPTACLE.
COORDINATE MOUNTING HEIGHT WITH PLUMBING.
EQUIPMENT DATA SCHEDULE
TYPE MARK EQUIPMENT DESCRIPTION LOCATION VOLTAGE PH HZ FED FROM WIRES FLA
DISCONNECT SWITCH STARTER
REMARKS
NEMA ENCLOSURE
TYPE & (DISC. SIZE)
FURNISHED
BY
INSTALLED
BY
CONNECTED
BY
NEMA
ENCLOSURE
TYPE &
(STARTER
SIZE) TYPE ACCESSORIES
FURNISHED
BY
INSTALLED
BY
CONNECTED
BY
CONTROL
WIRING BY
ACU 1 AIR CONDITIONER UNIT O-109 TELECOM 208 V 1 60 Hz L1B 2#12, 1#12G 0.4 A NEMA 1 (30A) 26 26 26 - PWCP _ 23 23 23 23
AHU 1 AIR HANDLING UNIT O-106 UTILITY 120 V 1 60 Hz L1B 2#12, 1#12G 10.8 A NEMA 1 (30A) 26 26 26 - PWCP _ 23 23 23 23
CU 1 CONDENSING UNIT EXTERIOR 208 V 3 60 Hz L1B 3#12, 1#12G 15 A NEMA 4X (30A) 26 26 26 - PWCP _ 23 23 23 23
CU 2 CONDENSING UNIT EXTERIOR 208 V 1 60 Hz L1B 2#12, 1#12G 10 A NEMA 4X (30A) 26 26 26 - PWCP _ 23 23 23 23
EF 1 EXHAUST FAN O-102 KITCHENETTE 115 V 1 60 Hz L1B 2#12, 1#12G 0.5 A NEMA 1 (30A) 23 26 26 - FVNR _ 23 23 23 23
EF 2 EXHAUST FAN STORAGE 208 V 3 60 Hz L1A 3#12, 1#12G 2.4 A NEMA 1 (30A) 23 26 26 1 (00) FVNR _ 26 26 26 26
EUH 1 ELECTRIC UNIT HEATER STORAGE 208 V 1 60 Hz L1A 2#10, 1#10G 16 A NEMA 1 (30A) 23 26 26 - PWCP _ 23 23 23 23
GD 1 GARBAGE DISPOSAL O-102 KITCHENETTE 120 V 1 60 Hz 9.5 A
IWH 1 INSTANTANEOUS ELECTRIC WATER HEATER KITCHENETTE O-102 208 V 1 60 Hz L1B 2#10, 1#10G 20 A NEMA 3R (30A) 22 26 26 - _ _ 22 22 22 22
IWH 2 INSTANTANEOUS ELECTRIC WATER HEATER MEN O-104 208 V 1 60 Hz L1B 2#10, 1#10G 20 A NEMA 3R (30A) 22 26 26 - _ _ 22 22 22 22
IWH 3 INSTANTANEOUS ELECTRIC WATER HEATER UTILITY O-106 208 V 1 60 Hz L1B 2#8, 1#8G 40 A NEMA 3R (30A) 22 26 26 - _ 22 22 22 22
UH 1 UNIT HEATER STORAGE 115 V 1 60 Hz L1A 2#12, 1#12G 9.4 A NEMA 1 (30A) 26 26 26 - PWCP _ 23 23 23 23
UH 2 UNIT HEATER STORAGE 115 V 1 60 Hz L1A 2#12, 1#12G 9 A NEMA 1 (30A) 26 26 26 - PWCP _ 23 23 23 23
N
3000 PSI CONCRETE
NOTE:
REINFORCED DUCTBANK SHALL BE PROVIDED
UNDER ALL PAVED ROADS OR PARKING AREAS
FLOWABLE FILL UNDER PAVED AREAS
FINISHED GRADE
WARNING TAPE
4.62"
(REF)
T
Y P
M
I N
3.0"
(MIN)
M
I N
19.12"
UNDER ROADWAY ONLY
USE: (2) #4 STEEL
REBAR
(TOP AND BOTTOM)
UNDER ROADWAY ONLY, USE: #4 STEEL
REBAR TIES @12-INCHES
SNAP-LOCK BASE SIZE 2"X2" OR
APPROVED EQUAL (INSTALL AT 8'
INTERVALS)
POLYETHYLENE INSULATED SOLID
COPPER TRACER WIRE
2-INCH PVC CONDUIT
SPARE 2-INCH CONDUIT
4.25"
(REF)
WATER
METER
GAS
METER
ELECTRIC
AMI METER
WITH RADIO
EXISTING
MESH
SYSTEM
ANTENNA MOUNTED
AT APPROVED
LOCATION
PSNET
POP
WHERE APPLICABLE: REFER TO
MECHANICAL AND PLUMBING DRAWINGS.
ION8600, FORM 9S OR
APPROVED EQUAL
TRUSS RODS
PLUNGER BAR
TOP RAIL
3/4"Øx10' COPPER CLAD STEEL GROUND RODS
(TYP) 3/4"Øx10' COPPER CLAD STEEL
GROUND RODS (TYP)
#1/0 BARE COPPER CONDUCTOR (CONNECT
GATE POST TO GATE POST)
BRACE
STRETCHER
BAR
GROUNDING STRAP
FROM FENCE ACROSS
POST TO GATE
EXOTHERMIC
WELD CONNECTION
GATE POST
CONC. FOUNDATION
GROUNDING STRAP FROM
FENCE ACROSS POST TO GATE
EXOTHERMIC
WELD CONNECTION
3/4"Øx10' COPPER CLAD STEEL
GROUND RODS (TYP)
GROUND CLAMP, PLACE AROUND
POST & ONE OR MORE STRANDS
OF WIRE MESH. LOCATE ON
POST AT 24" INTERVALS
COMPRESSION
CONNECTION (TYP.)
EXOTHERMIC
WELD CONNECTION
ILLUSTRATION:
ELECTRIC METER ENCLOSURE WITH REMOTE ANTENNA - OUTDOOR
(MOUNTED ON WALL)
1 5
SERVICE DISCONNECT SWITCH
WATERTIGHT PENETRATION TO
PANELBOARD INSIDE BUILDING.
SPARE 2-INCH PVC CONDUIT
CAPPED 12-INCHES
ABOVE GRADE
GRADE
2-INCH CONDUIT
GROUNDING ELECTRODE
CONDUCTOR IN PVC CONDUIT
CIRCUIT#1
NC
NC
NC
NC
NEUTRAL
HOT
OCCUPANCY
SENSOR "A"
"ON"
LV SWITCH / DIMMER
"ON"
LV SWITCH / DIMMER
NORMAL
LIGHT
NORMAL / EM
LIGHT
POWER
PACK
LIGHTING
CONTACTOR
CIRCUIT #1
CIRCUIT #2
CIRCUIT #3
CIRCUIT #4
NORMAL
LIGHT
NORMAL / EM
LIGHT
OCCUPANCY
SENSOR "B"
MANUAL
"ON"
LV SWITCH / DIMMER
NC
FIRE ALARM
PANEL
NEUTRAL
HOT
120V
120V
NO = NORMALLY OPEN CONTACT. CONTACTS ARE OPEN WHEN NO
CURRENT FLOWS THOUGH THE COIL, BUT CLOSES AS SOON AS THE COIL
IS ENERGIZED
NC = NORMALLY CLOSED CONTACT. CONTACTS ARE CLOSED WHEN NO
CURRENT FLOWS THOUGH THE COIL, BUT OPENS AS SOON AS THE COIL IS
ENERGIZED
NO
POWER
PACK
NO
C
KEYNOTES
1. WATER AND GAS FLOW METERS ARE HARDWIRED TO THE INPUTS OF THE
ELECTRICAL AMI METER. PROVIDE CAT-6 CABLE AND 1-INCH PVC COATED
RIGID STEEL UG CONDUIT FROM AMI METER ENCLOSURE TO WATER AND
GAS METER LOCATION (PROVIDE EXPLOSION PROOF SEALOFFS IF
REQUIRED).
2. PROVIDE OUTDOOR RATED COAX CABLE (LMR400 OR EQUAL) INSIDE 3/4
INCH CONDUIT FROM METER ENCLOSURE TO ANTENNA LOCATION. ALL
COAX TERMINATIONS SHALL BE MADE WITH A SELF HEALING
WEATHERPROOF TAPE. COAX CABLE MUST BE ADEQUATELY GROUNDED
TO A PERMANENT SYSTEM GROUND INSIDE OF ENCLOSURE.
3. INSTALLATION HEIGHT SHALL BE A MINIMUM OF 5-FEET, MAXIMUM 6-FEET.
PREFERRED HEIGHT IS 66-INCHES ABOVE GROUND LEVEL.
ELECTRIC METER LOCATIONS SHALL BE AT LEAST 3-FEET FROM GAS
METER.
4. ALL UNITS SHALL BE EQUIPPED WITH INTEGRATED LIGHTNING
ARRESTORS.
5. FUTURE USE: PROVIDE ONE 1-INCH CONDUIT WITH PULL STRING FOR
COMMUNICATIONS FROM METER LOCATION TO THE
TELECOMMUNICATIONS EQUIPMENT ROOM. COORDINATE WITH BASE.
6. TEST THE SIGNAL STRENGTH PRIOR TO INSTALLATION. IF REQUIRED, AMI
ANTENNA CAN BE MOUNTED AT ROOF EDGE FOR BETTER SIGNAL
TRANSMISSION, OR AT LOCATION INDICATED IN DETAIL "A4". LOCATION
MUST BE APPROVED BY NAVFAC PRIOR TO INSTALLATION.
7. UNDER NORMAL POWER AND NO ALARM CONDITIONS CONTACT IN FIRE
ALARM PANEL IS CLOSED. UNDER ALARM CONDITIONS CONTACT WILL
OPEN. WHEN CONTACT IS OPEN AT FIRE ALARM PANEL LIGHTING
CONTACTOR WILL DE-ENERGIZE AND TURN THE LIGHTS "ON" BYPASSING
CONTACT IN POWER PACK CONTROL DEVICE.
8. LIGHTS ARE NOT POWERED THROUGH FIRE ALARM PANEL. UNDER
NORMAL POWER CONDITIONS AND WITH NO ACTIVE FIRE ALARM LIGHTING
CONTACTOR COIL IS ENERGIZED.
501 North Broadway
Saint Louis, MO 63102
(314) 335-4000
LAUREN SHIPMAN
CRANE ARMY AMMO ACTIVITY
11/21/2019
NOT TO SCALE
C1
TYPICAL FENCE GROUNDING DETAIL
NOT TO SCALE
C2
TYPICAL GATE GROUNDING DETAIL
NOT TO SCALE
B2
AMI METERING CONNECTION DETAIL
NOT TO SCALE
A2
AMI ANTENNA AND METER MOUNTING DETAIL
NOT TO SCALE
A1
DUCTBANK DETAIL
NOT TO SCALE
A4
LIGHTING CONTROL DIAGRAM
CIRCUIT#2
CIRCUIT#3
L1B-7
CIRCUIT#1
L1B-9
SPARE
CIRCUIT#4 SPARE
STORAGE
BUILDING
L1A-1
L1A-3
L1A-5
SPARE
CONTACTOR SCHEDULE
OPERATIONS
BUILDING
12805276
DIRECT/INDIRECT LED TROFFER
REVISED: APRIL 2016
NL-1
LIGHTING PLATE:
LUMINAIRE REQUIREMENTS:
1. HOUSING - DIE-FORMED, COLD ROLLED STEEL, WITH ONE-PIECE LOWER REFLECTOR HAVING
TEXTURED, HIGH REFLECTANCE, WHITE POLYESTER POWDER-COATED FINISH. OPTIONAL SIZES OF
1FT x 4FT, 2FT x 2FT, AND 2FT x 4FT AVAILABLE.
2. LIGHT SOURCE - UPWARD-FACING LEDS WITH DIFFUSE LENS TO ELIMINATE DIRECT VIEW OF LIGHT
SOURCE. 5000K COLOR TEMPERATURE UON, MAXIMUM BINNING TOLERANCE OF A 4-STEP MCADAM
ELLIPSE, MINIMUM EFFICACY OF 90 LUMENS/WATT, WITH A MINIMUM CRI OF 80. INITIAL LUMEN
OUTPUT AS INDICATED IN LUMINAIRE SCHEDULE.
4. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DRIVER WITH MINIMUM 0.9 PF, OPERATING
VOLTAGE OF 120-277V, THERMAL MANAGEMENT, < 20% TOTAL HARMONIC DISTORTION.
STEP-DIMMABLE OR FULLY DIMMABLE AS INDICATED IN LUMINAIRE SCHEDULE.
5. CERTIFICATION - UL 1598, DAMP LOCATION, DLC QUALIFIED, AND ROHS COMPLIANT. COMPLIES WITH
LM79, LM80 AND TM21 TESTING STANDARDS. UL 924 WHEN EQUIPPED WITH EMERGENCY BATTERY
BACK-UP. IC RATED WHEN INDICATED.
6. MOUNTING - RECESSED IN SUSPENDED ACOUSTICAL TILE OR HARD CEILING.
7. THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THAT MAY MEET
THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE A CERTAIN MANUFACTURER
OR PREFERENCE.
HOUSING - DIE-CAST ALUMINUM OR HIGH-IMPACT, UV-STABILIZED, INJECTION-MOLDED
LETTERS/CHEVRONS - MINIMUM 6" HIGH WITH 3/4" STROKE. RED OR GREEN LETTERS
FINISH (ON CAST ALUMINUM HOUSING ONLY) - TEXTURED POWDER COAT FINISH
OPTIONS INCLUDE WHITE, WHITE WITH BRUSHED ALUMINUM FACE, BLACK, OR BLACK
EMERGENCY PACK - SOLID-STATE, CONSTANT-CURRENT TYPE BATTERY CHARGER WITH
MOUNTING - UNIVERSAL MOUNTING KIT FOR CEILING, WALL OR END-OF-FIXTURE
ILLUMINATION - PROVIDED BY RED, GREEN OR WHITE HIGH-OUTPUT LEDS INSIDE
1.
2.
3.
4.
5.
6.
LUMINAIRE REQUIREMENTS:
REVISED: AUGUST 2004
NL-63
MOUNTING.
THERMOPLASTIC. SINGLE OR DOUBLE-FACED AS INDICATED.
AS INDICATED. PROVIDE CHEVRONS AS INDICATED EITHER LEFT, RIGHT OR BOTH
MAINTENANCE-FREE, NICKEL-CADMIUM BATTERY, AC-ON INDICATOR LAMP AND
LIGHTING PLATE:
LED EXIT SIGN
13"
NOMINAL
NOMINAL
9"
WITH BRUSHED ALUMINUM FACE.
DIRECTIONS AS INDICATED. CHEVRONS PUNCHED OUT THROUGH HOUSING AS REQUIRED.
TEST SWITCH.
OF FIXTURE HOUSING. PROVIDE POLYSTYRENE DIFFUSER IN COLOR INDICATED WITH
FREQUENCY-MATCHED SILKSCREEN COATING FOR MAXIMUM LED LIGHT OUTPUT.
CERTIFICATION - UL LISTED AND CERTIFIED FOR DAMP LOCATIONS.7.
TOP VIEW
19 IN
4 IN
POLE AS
INDICATED
36.5 IN
LUMINAIRE REQUIREMENTS:
1. HOUSING - DIE-CAST ALUMINUM OR DIE-CAST AND EXTRUDED ALUMINUM WITH INTEGRAL, SELF-CLEANING
HEAT SINK FINS, RIBS, OR EQUIVALENT PASSIVE COOLING MECHANISM. HEAT SINK SHALL BE INCORPORATED
DIRECTLY INTO HOUSING TO ENSURE MAXIMUM HEAT TRANSFER AND DISSIPATION.
2. FINISH - MULTI-STAGE PRE-TREATMENT, FINISHED WITH BAKED-ON POLYESTER POWDER COAT. FINISH
SHALL PASS 2500 HOUR SALT SPRAY TEST PER ASTM B117. FINISH COLORS INCLUDE DARK BRONZE, SILVER, OR BLACK WITH CUSTOM COLORS AVAILABLE.
3. POWER SUPPLY/LED DRIVER - PROVIDE IN SEPARATE COMPARTMENT ACCESSIBLE WITHOUT THE USE OF
HAND TOOLS. CLASS 1 DRIVER SHALL OPERATE AT 208V, 60 HZ. POWER FACTOR GREATER THAN 0.9 AND THD
LESS THAN 20% AT FULL LOAD. MINIMUM EFFICACY SHALL BE 60 LM/W AT MAXIMUM 600 mA OPERATING
CURRENT.
4. LED OPTICAL ASSEMBLY - NUMBER OF LED ARRAYS SHALL VARY TO ACCOMMODATE DESIRED LUMINAIRE
OUTPUT. PROVIDE WITH EQUIVALENT NEMA TYPE III, IV OR V DISTRIBUTION AS INDICATED. BUG UPLIGHT
RATING OF U0, WITH BACKLIGHT AND GLARE RATINGS AS DETERMINED BY LIGHTING ZONE INSTALLED.
MINIMUM COLOR RENDERING INDEX (CRI) SHALL BE 70 FOR CORRELATED COLOR TEMPERATURE (CCT) OF
5000 DEGREES K.
5. SURGE PROTECTION - 6 kV MINIMUM, COMPLIANT WITH ANSI C62.41.2.
6. CERTIFICATION - UL AND/OR ETL LISTED, MINIMUM IP65 RATED PER ANSI/IEC 60529, AND RoHS COMPLIANT.
7. OPTIONS - BIRD SPIKES, DUAL FUSING (208V).
8. OTHER - THE ABOVE SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THAT MAY
MEET THE SPECIFICATION REQUIREMENTS AND IS NOT INTENDED TO INDICATE A CERTAIN MANUFACTURER'S
PREFERENCE. ALL DIMENSIONS ARE NOMINAL AND VARY PER MANUFACTURER.
REVISED: MARCH 2013
XL-03
LUMINAIRE PLATE:
LED AREA LUMINAIRE
OPTIONAL
PHOTOCELL
LUMINAIRE REQUIREMENTS:
1. HOUSING - DIE-CAST OR EXTRUDED ALUMINUM WITH INTEGRAL PASSIVE COOLING MECHANISM. HEAT SINK
SHALL BE INCORPORATED DIRECTLY INTO HOUSING OR DRIVER COMPARTMENT TO ENSURE MAXIMUM HEAT
TRANSFER AND DISSIPATION.
2. FINISH - MULTI-STAGE PRE-TREATMENT, FINISHED WITH BAKED-ON POLYESTER POWDER COAT. FINISH SHALL
PASS 2500 HOUR SALT SPRAY TEST PER ASTM B117. STANDARD FINISH IS DARK BRONZE, WITH OTHER
CUSTOM COLORS AVAILABLE.
3. POWER SUPPLY/LED DRIVER - CLASS 1 DRIVER SHALL OPERATE AT 120/277 VOLTS, 60 HZ, WITH OTHER
VOLTAGES OPTIONAL; POWER FACTOR GREATER THAN 0.9 AND THD LESS THAN 20% AT FULL LOAD. MINIMUM
EFFICACY SHALL BE 60 LM/W AT MAXIMUM 600mA OPERATING CURRENT.
4. LED OPTICAL ASSEMBLY - PRECISION MOLDED ACRYLIC LENS PROVIDED FOR MULTIPLE HIGH-POWERED
LEDS PRODUCING NEMA TYPE III DISTRIBUTION OR AS OTHERWISE INDICATED. BUG UPLIGHT RATING OF U0, WITH GLARE RATING AS DETERMINED BY LIGHTING ZONE INSTALLED. MINIMUM COLOR RENDERING INDEX
(CRI) SHALL BE 70 FOR CORRELATED COLOR TEMPERATURE (CCT) OF 5000 DEGREES K.
5. CERTIFICATION - UL AND/OR ETL LISTED FOR DAMP OR WET LOCATIONS AS INDICATED, AND RoHS
COMPLIANT.
6. OPTIONS - LUMEN OUTPUT RATING AS INDICATED.
7. OTHER - THE ABOVE SKETCH IS A NON-PROPRIETY GRAPHIC REPRESENTATION OF A LUMINAIRE THAT MAY
MEET THE SPECIFICATION REQUIREMENTS AND IS NOT INTENDED TO INDICATE A CERTAIN MANUFACTURER'S
PREFERENCE. ALL DIMENSIONS ARE NOMINAL AND VARY PER MANUFACTURER.
REVISED: MARCH 2013
XL-17
LUMINAIRE PLATE:
LED WALL PACK
15 IN
10 IN
5 IN
LED INDUSTRIAL STRIP
REVISED: APRIL 2016
NL-7
LIGHTING PLATE:
LUMINAIRE REQUIREMENTS:
1. HOUSING - DIE-FORMED, COLD-ROLLED STEEL, WITH REINFORCEMENT RIBS FOR RIGIDITY AND SPECULAR
ALUMINUM OR HIGHLY-REFLECTIVE PAINTED STEEL REFLECTORS. OPTIONAL LENGTHS OF 4FT OR 8FT.
2. FINISH - MULTI-STAGE PHOSPHATE BONDING TREATMENT FINISHED WITH HIGH-REFLECTANCE, WHITE POLYESTER
POWDER COAT, PAINTED AFTER FABRICATION.
3. LIGHT SOURCE - SOLID STATE LEDS WITH MINIMUM 50K HOURS RATED LIFE AT L70, 3500K CCT UON, MINIMUM 80
CRI, MAXIMUM 4-STEP MCADAM ELLIPSE BINNING TOLERANCE FOR COLOR CONSISTENCY, AND MINIMUM EFFICACY
OF 100 LUMENS/WATT. INITIAL LUMEN OUTPUT AS INDICATED IN LUMINAIRE SCHEDULE.
4. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DRIVER WITH MINIMUM 0.9 PF, OPERATING VOLTAGE OF
120-277V, THERMAL MANAGEMENT, < 20% TOTAL HARMONIC DISTORTION. ON-OFF CONTROL, STEP-DIMMABLE OR
FULLY DIMMABLE AS INDICATED.
5. CERTIFICATION - UL 1598, DAMP LOCATION, DLC QUALIFIED, AND ROHS COMPLIANT. COMPLIES WITH LM79, LM80
AND TM21 TESTING STANDARDS. UL 924 WHEN EQUIPPED WITH EMERGENCY BATTERY BACK-UP.
6. MOUNTING - SURFACE ON CEILING OR SUSPENDED.
7. OPTIONS - CHAIN, STEM OR SWIVEL STEM HANGERS.
8. THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THAT MAY MEET THE
SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE A CERTAIN MANUFACTURER OR PREFERENCE.
501 North Broadway
Saint Louis, MO 63102
(314) 335-4000
LAUREN SHIPMAN
CRANE ARMY AMMO ACTIVITY
11/21/2019
REVISED: MARCH 2013
XL-29
LUMINAIRE PLATE:
ANCHOR BASE POLE FOUNDATION
A
POLE
HEIGHT
B
31'-40' 78" 30"
"A"
4"
"B"
FINISHED GRADE
INSULATED COPPER GROUNDING
CONDUCTOR ATTACHED TO INTERNAL
LUG WELDED TO INTERIOR OF POLE.
USE #6 AWG STRANDED COPPER
GROUND DOWN CONDUCTOR.
CHAMFER ALL EDGES OF CONCRETE
BASE 1/2"
HANDHOLE - SEE POLE SKETCH AND
SPECIFICATION
POLE - SEE POLE SKETCH AND
SPECIFICATION
CONDUIT STUBBED UP ADJACENT TO
HANDHOLE; NUMBER AND SIZE AS
REQUIRED
SET TOP OF CONCRETE
FOUNDATION 4" ABOVE
GRADE
COPPER EQUIPMENT
GROUNDING CONDUCTOR -
ATTACH TO INTERNAL LUG
WELDED TO INTERIOR OF
POLE. CONDUCTOR TO BE
SAME SIZE AND TYPE AS
SUPPLY PHASE
CONDUCTOR.
CIRCUIT CONDUCTORS AND
CONDUIT TO POWER SOURCE
OR NEXT POLE
CONCRETE PER
SPECIFICATION
CIRCUIT CONDUCTORS AND
CONDUIT TO POWER SOURCE
OR NEXT POLE
ANCHOR BOLTS AS
RECOMMENDED BY
MANUFACTURER OF POLE
#4 BARS VERTICAL AT 6"
EACH FACE
#3 BARS AT 12" ON CENTER
HORIZONTALLY
3/4" X 10' GROUND ROD
REVISED: MARCH 2013
XL-27
LUMINAIRE PLATE:
ANCHOR BASE STEEL POLE
TAPERED OR STRAIGHT STEEL OR ALUMINUM POLE. CROSS SECTIONAL
SHAPE AND COLOR AS INDICATED.
NOTES:
COORDINATE TOTAL EPA WITH SPECIFICATIONS.
WIRING HANDHOLE MINIMUM 2 1/2" X 5" CLEAR OPENING WITH COVER
AND STAINLESS STEEL SCREWS.
INTERNAL GROUNDING LUG.
TERMINATE C0NDUITS INTERNALLY, ADJACENT TO HANDHOLE.
FULL BASE COVER - TW0 PIECE GALVANIZED STEEL.
CONCRETE FOUNDATION - SEE PLATE XL-29.
"U"
POLE
TYPE
TENON OPTION - 2-3/8" TENON WITH PROVISION
FOR WIRING. COORDINATE WITH LUMINAIRE.
MAST ARM OPTION - COORDINATE WIRING AND BOLT HOLES
WITH MAST ARM PROVIDED.
DIM
1'-6"
"U"
9"
12"
LUMINAIRE REQUIREMENTS:
1. HOUSING - ONE-PIECE, NON-CORROSIVE STEEL WITH ALUMINUM HEAT SINK. HEAT SINK SHALL BE
INCORPORATED DIRECTLY INTO DRIVER COMPARTMENT TO ENSURE MAXIMUM HEAT TRANSFER AND
DISSIPATION.
2. REFLECTOR - ONE-PIECE, IRIDESCENCE-SUPPRESSED ALUMINUM. PAINTED WHITE SELF-TRIM AND OTHER
REFLECTOR FINISHES AS INDICATED.
LED DRIVER:
TYPE B - CLASS 1, CONSTANT CURRENT, ELECTRONIC DRIVER WITH
0-10 VOLT DIMMING FOR LED LIGHT SOURCE.
3. LIGHT SOURCE:
TYPE B - MULTI-LED ARRAY WITH MINIMUM CRI OF 70 AT A CCT OF
4000-4500 DEGREES K. LUMEN OUTPUT AND WATTAGE AS INDICATED.
4. CERTIFICATION - UL AND/OR ETL LISTED FOR DAMP OR WET LOCATIONS AS INDICATED, AND RoHS
COMPLIANT.
5. OPTIONS - WHERE INDICATED EMERGENCY BATTERY INVERTER. REFLECTOR COLOR AND FINISH, AND
APERTURE OPENING SIZE OF 6 IN OR 8 IN.
6. OTHER - THE ABOVE SKETCH IS A NON-PROPRIETY GRAPHIC REPRESENTATION OF A LUMINAIRE THAT MAY
MEET THE SPECIFICATION REQUIREMENTS AND IS NOT INTENDED TO INDICATE A CERTAIN MANUFACTURER'S
PREFERENCE. ALL DIMENSIONS ARE NOMINAL AND VARY PER MANUFACTURER.
REVISED: MARCH 2013
XL-15
LUMINAIRE PLATE:
EXTERIOR RECESSED DOWNLIGHT
6-8 IN
9 IN
BASIS ON DESIGN
BASIS OF DESIGN: ARM MOUNTED LIGHT FIXTURE
12805277
XL-27
F
40 BASIS OF DESIGN: XL-27F
NOTES:
EXISTING CROSSARM TO REMAIN
LAG BOLT
WITH SQUARE
WASHER
GUY ATTACHMENT
FIBERGLASS STRAIN
INSULATOR
7 STRAND GUY WIRE
DEADEND FOR
GUY STRAND
DEADEND FOR
GUY STRAND
SERVE OR CLIP
MAX AFTER
STRAIN IS
APPLIED
5"
6"
12"
5"
GRADE
SCREW ANCHOR
PROVIDE NEW
ANCHOR ROD
NOTES:
1. ANCHOR AND GUY WIRE SHALL BE AS REQUIRED.
2. IF MORE THAN TWO GUY WIRES ARE REQUIRED INSTALL SECOND ANCHOR
AT LEAST 60-INCHES FROM FIRST.
3. INSTALL FIBERGLASS STRAIN INSULATOR IN GUY AT POLE ATTACHMENT.
MINIMUM LENGTH OF 48-INCHES.
4. INSTALL 8 FOOT GUY GUARD.
5. PROVIDE GUY WIRE
501 North Broadway
Saint Louis, MO 63102
(314) 335-4000
LAUREN SHIPMAN
CRANE ARMY AMMO ACTIVITY
11/21/2019
EXISTING CUT-OUT
TO BE REMOVED
EXISTING STIRRUP AND HOT
LINE CLAMP TO REMAIN. TO
BE DISCONNECTED AND
REMOVED BY BASE
ELECTRICIAN.
LIGHTNING ARRESTOR
TO BE REMOVED
EXISTING TRANSFORMER
TO BE REMOVED
(3)15KV FUSE CUTOUTS
SEE ONE LINE FOR SIZE
TRI MOUNT BRACKET FOR
FUSED CUT-OUTS AND
LIGHTNING ARRESTORS
#4 ACSR PRIMARY
CONDUCTOR
CROSSARM
CROSSARM BRACE
NEW WOOD POLE
SUSPENSION INSULATOR,
SEE DETAIL C2/E5031 FOR
ARRANGEMENT
SCREW LAG 1/2" X 4"
1. NOTES ABOVE LIST THE MAJOR ITEMS OF EQUIPMENT ONLY. ALL OTHER EQUIPMENT
NECESSARY FOR PURPOSE INDICATED SHALL BE PROVIDED UNDER THIS CONTRACT.
2. RISER CONDUIT SHALL BE RIGID STEEL CONDUIT UP TO 9 FEET ABOVE GROUND LEVEL, BUT
MAY BE SCHEDULE 40 PVC THEREAFTER.
3. SIZE SECONDARY UNDERGROUND SERVICE CONDUCTORS AS INDICATED ON ONE-LINE.
EXISTING COMMUNICATIONS
LINES TO REMAIN
NOT TO SCALE
C3
TYPICAL POLE ANCHOR DETAIL
NOT TO SCALE
C1
EXISTING POLE (3F-4) DETAIL
NOT TO SCALE
A3
TYPICAL RISER POLE (3F-6-2 AND 3F-6-5) DETAILS
REMOVE SERVICE DROP
AND SECONDARY CLEVIS
NEW OH #2 ACSR
15KV INSULATORS
NOT TO SCALE
C2
TYPICAL NEW UTILITY POLE DETAIL
NEW GUY
AND ANCHOR
NEW #2 ACSR
PRIMARY CONNECTION,
BY NAVFAC (TYP.)
EXISTING TELECOMMUNICATIONS
LINES BELOW
NEW 15KV SUSPENSION
INSULATORS (TYP. OF 4),
BY EC
NEW 8-FOOT CROSSARM,
BY EC.
NEW 15KV PIN INSULATORS
(TYP. OF 4) , BY EC
EXISTING OHW
TO REMAIN
EXISTING WOODEN
CROSSARM
ANGLE NEW CROSSARM
TOWARDS POLE 3F-6-1
90 DEGREES.
NOT TO SCALE
C4
MODIFIED POLE 3F-6 DETAIL (TOP VIEW)
CONDUIT COUPLING
CONDUIT BEND
FINISHED
GRADE
NOT TO SCALE
A1
GROUNDING & BOTTOM OF POLE DETAILS
8-FOOT CROSSARM
TOP VIEW
PROVIDE CROSSARM
BRACES
POLE MOUNTED EQUIPMENT LOCATIONS
ROAD SIDE
POSITION
RISER
POSITION
RISER
POLE
POSITION
TRANSFORMER
POSITION
FUSED CUTOUTS
LIGHT FIXTURE
POSITION
CONCRETE ENCASED CONDUIT
LIGHT FIXTURE MOUNTING TO WOOD POLE
LED LIGHT FIXTURE
PROVIDE BRACKET FOR
SELECTED LIGHT FIXTURES
TYPICAL FOR TYPE S2
(SEE LIGHT FIXTURE SCHEDULE)
ROUTE WIRE IN 1/2"
NON-CONDUCTIVE CONDUIT TO ARM
TO POLE
GROUND
J-BOX
1/2" FLEXIBLE
NON-METALIC CONDUIT
LIGHT FIXTURE
ADDITIONAL
GROUND RODS
(WHEN REQUIRED)
PLAN
GROUND
WIRE
POLE
BOTTOM OF POLE
GROUND ROD
PLASTIC OR FIBER MOLDING
GALVANIZED STAPLES (TYPICAL)
FINISHED
GRADE
#4 BARE
COPPER
POLE
24"
MIN.
10'-0"
MIN.
10'-0"
MIN.
24"
12"
ALTERNATE GROUND WIRE
POSITION. (USE WHEN
MULTIPLE GROUNDING
SYSTEMS ARE REQUIRED.)
(SEE NOTE 4)
1.
2.
NOTES
USE ADDITIONAL GROUND RODS, WHEN REQUIRED,
TO OBTAIN RESISTANCE VALUE, AS REQUIRED BY
IEEE C2.
MAKE GROUNDING CONNECTIONS TO ALL EQUIPMENT
ON POLE AS REQUIRED BY IEEE C2.
PVC J-BOX
#4 600V INSULATED COPPER GROUNDING
CONDUCTOR REQUIRED ON PRIMARY SYSTEM
WHEN SEPARATE SYSTEMS ARE REQUIRED.
3.
1/2" PVC CONDUIT
1" PVC CONDUITS
SEE DIRECT BURIED
CONDUIT DETAIL
ROAD SIDE
J-BOX
CONNECT TO NEURAL
TOP OF POLE
J-BOX
NOT TO SCALE
A2
LIGHT FIXTURE MOUNTING DETAILS
J-BOX
DIRECT BURIED CONDUIT
FINISHED
GRADE
CONDUIT BEND
CONDUIT COUPLING
18'' AFG
24" BELOW GRADE 24" BELOW GRADE
RIGID STEEL CONDUIT RISER WITH END
FITTING, SIZE AS INDICATED ON ONE LINE
DIAGRAM, WITH LENGTH AS REQD.
PROVIDE STIRRUP, COMPRESSION TYPE AND
HOT LINE CLAMP. CONNECTION TO EXISTING OH
LINES BY BASE ELECTRICIAN
NEW OVERHEAD LINES
REFER TO SHEET E1001
AND SHEET E6011
GROUND ROD
GROUND ROD CLAMP.
REFER TO DETAIL A1/E5031.
BOND CONDUIT TO POLE
GROUND AND SYSTEM NEUTRAL
CONNECTOR
(TYPICAL)
FUSED CUTOUT
(TYPICAL)
TRANSFORMER
GROUNDING
CONNECTION
SURGE
ARRESTER
(TYPICAL)
(3)25kVA
TRANSFORMERS
(ORIENTATION MAY
BE DIFFERENT, SHOW
HERE FOR CLARITY).
12805278
FOR LIGHTING
NOT TO SCALE
A1
DLA
SINGLE LINE DIAGRAM
G
N
GENERAL NOTES
1. REFER TO CIVIL DEMOLITION SITE PLANS FOR ELECTRICAL DEMOLITION
WORK REQUIREMENTS.
2. REFER TO ELECTRICAL SITE PLAN FOR NEW ELECTRICAL WORK
REQUIREMENTS.
3. ALL DEMOLISHED ELECTRICAL EQUIPMENT TO BE DISPOSED BY
CONTRACTOR UNLESS NOTED OTHERWISE.
4. FINAL TERMINATION AT POLE 3F-6 BY NAVFAC ELECTRICIANS.
DEMOLITION KEYNOTES
1. OVERHEAD 15kV CABLES TO REMAIN.
2. OVERHEAD 600V CABLES TO BE DEMOLISHED.
3. EXISTING POLE MOUNTED TRANSFORMER, 12.47kV PRIMARY, TO BE
DEMOLISHED. REMOVED TRANSFORMERS TO BE TURNED IN TO NAVFAC
FOR TESTING. IF TRANSFORMER HAS NON-PCB RESULTS, THE
CONTRACTOR SHALL REMOVE FROM SITE AND PROPERLY DISPOSE
TRANSFORMERS. IF TRANSFORMERS TEST POSITIVE (>50 PPM PCB'S),
THEN CRANE ENVIRONMENTAL WILL ARRANGE DISPOSAL.
4. UG CONDUIT AND CABLES SERVING SITE LIGHTING TO BE DEMOLISHED.
5. EXISTING DISCONNECT TO BE DEMOLISHED.
6. EXISTING 50FT (WOOD) LIGHT POLE TO BE DEMOLISHED.
M
501 North Broadway
Saint Louis, MO 63102
(314) 335-4000
LAUREN SHIPMAN
CRANE ARMY AMMO ACTIVITY
11/21/2019
XFMR T1
(3)15kVA
12,470V -
208Y/120V, 3-PHASE
(3)5A, 15kV FUSED
CUT-OUTS
1. MODIFY EXISTING UTILITY POLE. REFER TO DETAILS ON SHEET E-5031.
2. PROVIDE GUY WIRE TO BALANCE MODIFIED UTILITY POLE. REFER TO
DETAIL ON SHEET E-5031.
3. #2,15kV, 3/C ACSR OHW.
4. UG 600V CONDUCTORS IN CONCRETE ENCASED SCHEDULE 40 PVC 2-INCH
CONDUIT.
5. POLE MOUNTED TRANSFORMER.
6. UG 600V WIRING IN CONCRETE ENCASED SCHEDULE 40 PVC, 1-INCH
CONDUIT, UON.
7. PROVIDE AMI METER AND CT ENCLOSURE. REFER TO DETAILS ON SHEET
E-5011. METER SHOULD BE COMPATIBLE WITH EXISTING SMART GRID, AMI
MESH NETWORK.
8. NEMA1 PANELBOARD LOCATED INSIDE STORAGE BUILDING.
9. SIZE SPD OVERCURRENT PROTECTION PER MANUFACTURER'S
RECOMMENDATION. PROVIDE SPD IN NEMA1 ENCLOSURE EXTERNAL TO
MAIN PANELBOARD. LOCATE SPD ENCLOSURE AS CLOSE AS POSSIBLE TO
ELECTRICAL PANELBOARD.
10. 240VAC MAIN DISCONNECT, NEMA 4X, LOCATED ON EXTERIOR WALL AT
STORAGE BUILING.
11. NEMA1 PANELBOARD LOCATED INSIDE OPERATIONS BUILDING.
12. 240VAC, 30A, NEMA 4X, DISCONNECT FOR RADIATION DETECTION SYSTEM.
13. 240VAC, 30A, NEMA 4X, DISCONNECT FOR DOCK LEVELER.
14. 240VAC, 30A, NEMA 4X, DISCONNECT FOR TRUCK SCALE SYSTEM.
15. 3/4-INCH SCHEDULE 40, CONCRETE ENCASED PVC CONDUIT, UNO.
16. 600V UG WIRE FOR PERIMETER LIGHTING, NORTH SIDE. REFER TO E1001.
17. MAIN BUILDING GROUND BAR LOCATED NEAR PANELBOARD.
18. REFER TO TLECOMMUNICATIONS DRAWINGS FOR CONNECTION TO
GROUND BAR LOCATED IN TELECOM ROOM.
19. (1) 1-INCH, UG, PVC CONDUIT WITH PULL STRING TO PANELBOARD L1A.
20. REFER TO DETAIL A1/5031 AND DETAIL A2/5031.
21. 60A, NEMA 4X DISCONNECT FOR 208/120V, 3-PHASE, LIFT STATION.
MOUNTED ON C-CHANNEL FRAME NEAR LIFT STATION CONTROL PANEL.
REFER TO PLUMBING DRAWINGS FOR DETAILS. COORDINATE POWER
REQUIREMENTS WITH APPROVED LIFT STATION DESIGN.
22. LIFT STATION CONTROL PANEL WITH INTEGRATED OVERCURRENT
PROTECTION FOR PUMPS AND CONTROLS. PROVIDED BY LIFT STATION
MANUFACTURER.
23. PROVIDE POWER CONNECTION BETWEEN CONTROL PANEL AND PUMPS.
CONTROLS BY OTHERS.
(3)9KV, LIGHTNING
ARRESTORS
CT'S
FEEDER SIZE
FEEDER SCHEDULE
3#12, 1#12G20A
20A 4#12, 1#12G
30A
30A
4#10, 1#10G
3#10, 1#10G
50A
50A 3#8, 1#10G
4#8, 1#10G
3#6, 1#10G65A
65A 4#6, 1#10G
3/4"
3/4"
85A
85A
4#4, 1#8G
3#4, 1#8G
100A
100A
4#3, 1#8G
3#3, 1#8G
115A
115A
4#2, 1#6G
3#2, 1#6G
130A
130A
4#1, 1#6G
3#1, 1#6G
150A
150A
3#1/0, 1#6G
4#1/0, 1#6G
175A
175A
4#2/0, 1#6G
3#2/0, 1#6G
200A
200A 3#3/0, 1#6G
4#3/0, 1#6G
230A
230A
4#4/0, 1#4G
3#4/0, 1#4G
255A
255A
3#250KCMIL, 1#4G
4#250KCMIL, 1#4G
4#300KCMIL, 1#4G285A
285A 3#300KCMIL, 1#4G
310A
310A
3#350KCMIL, 1#4G
4#350KCMIL, 1#4G
350A
350A 2-SETS: 3#2/0, 1#3G
2-SETS: 4#2/0, 1#3G
400A
400A
NOTES: 1. WIRE AMPACITY (COPPER) IS BASED ON 75°F. RATING TO COORDINATE
WITH 75°F. MAX TERMINAL RATINGS.
2. FEEDER INSULATION IS THHN/THWN 75° WET AND 90° DRY.
CONDUIT
SIZE
FEEDER
NUMBER
CONDUCTOR
AMPACITY (CU)
620A 2-SETS: 4#350KCMIL, 1#1G
620A 2-SETS: 3#350KCMIL, 1#1G
3/4"
3/4"
3/4"
3/4"
1"
3/4"
1 1/4"
1"
1 1/4"
1 1/4"
1 1/2"
1 1/4"
1 1/2"
1 1/4"
2"
1 1/2"
2"
2"
2"
2"
2 1/2"
2"
3"
2"
3"
2 1/2"
3"
2 1/2"
2"
2"
2-SETS: 3#3/0, 1#3G
2-SETS: 4#3/0, 1#3G
2"
2"
3"
2 1/2"
855A 3-SETS: 4#300KCMIL, 1#1/0G
855A 3-SETS: 3#300KCMIL, 1#1/0G
3"
2 1/2"
NEMA 4x
15KV, (3) 1/C, #2 ACSR OHW
KEYNOTES
3F-6
EXISTING 12.47KV
OVERHEAD LINES
TO REMAIN
3F-5
3F4-1
3F4-2
3F4-3
3F-6-1
3F-6-2
3F-6-3
3F-6-4
3F-6-5
G
N
M
XFMR T2
(3)25kVA
12,470V -
208Y/120V, 3-PHASE
(3)9KV, LIGHTNING
ARRESTORS
4HP
PUMP#2
NEMA 4x
#2, 15KV, (3) 1/C,
ACSR OHW
15KV, (3) 1/C, #2
ACSR OHW
L1A
SPD
L1B
SPD
CANOPY
SEE GENERAL NOTE 4
3 3 3
#1/017
15KV, (3)1/C, #2 ACSR OHW
4#1, 1#6G, 2"C
TO PANEL
L1B
4#8, 1#10G, 1"C
4#8, 1#10G, 1"C 4#8, 1#10G, 1"C 4#8, 1#10G, 1"C 4#8, 1#10G, 1"C
(3)7A, 15kV FUSED
CUT-OUTS
4#8, 1#10G, 1"C
6 16
#2/017
200A
3-PHASE,
4-WIRE Y,
208Y/120V
200A
3-PHASE,
4-WIRE Y,
208Y/120V
12805279
175 125
4#8, 1#10G, 1"C
15A15A
CT'S
4HP
PUMP#1
3P
3P
20 20 20
501 North Broadway
Saint Louis, MO 63102
(314) 335-4000
LAUREN SHIPMAN
CRANE ARMY AMMO ACTIVITY
11/21/2019
SOURCE
EACH
WATTS
LAMPMOUNTINGMARK
LAMP DATA
VOLTS
STYLE NO.
LUMINAIRE SCHEDULE
W WALL MOUNTED 12WLED 120VXL-17
NOTE 1: BoD WOOD TYPE LIGHTING POLES. AS BID OPTION PROVIDE PRICING FOR STEEL POLE XL-27F, ANCHOR BASE XL-29, PROVIDE APPROPRIATE MOUNTING
BRACKET. PROVIDE LOW TEMPERATURE LED DRIVER.
NOTE 2: VERIFY VOLTAGE REQUIREMENTS PRIOR TO ORDERING.
NOTE 3: PROVIDE QUANTITY OF FACES AS INDICATED ON THE PLANS. MOUNT 8'-0" AFF UNLESS NOTED OTHERWISE.
NOTE 4: MOUNT BOTTOM OF FIXTURE 10-FEET ABOVE FINISHED FLOOR UON.
NOTE 5: FIXTURE TO BE SURFACE MOUNTED UNDER CANOPY. PROVIDE LOW TEMPERATURE LED DRIVER AND PHOTOCELL INTEGRAL TO FIXTURE.
NOTE 6: LINEAR LIGHT FIXTURE, RECESSED IN THE CEILING ABOVE SINK IN RESTROOMS.
COLD ROLLED STEEL HOUSING WITH EXTRUDED ALUMINUM TRIM, LOW GLOSS, WHITE, WITH HIGH REFLECTIVE POWDER COATED ACRYLIC FINISH.
NOTE 7: WOOD POLE MOUNTED LIGHT FIXTURE, 35-FEET AFG, PROVIDE BRACKET FOR MOUNTING TO WOOD UTILITY POLE. PROVIDE LOW TEMPERATURE LED
DRIVER. REFER TO SHEET E5031 FOR DETAILS.
NOTE 8: TASK LIGHT FIXTURE CENTERED ABOVE SINK. MINI ONE LIGHT PENDANT, WHITE, ALUMINUM HOUSING, CYLINDRICAL, DOWNROD PENDANT STEM.
NOTE 9: CONTROLLED THROUGH PHOTOCELL. REFER TO E1011.
GENERAL SCHEDULE NOTES:
1. PROVIDE 90MIN EMERGENCY BATTERY PACK FOR ALL EMERGENCY LIGHT FIXTURES. EMERGENCY LIGHT FIXTURES ARE HALF-SHADED OR "EM" IS INDICATED
NEAR FIXTURE.
2. EXTENDED TEMPERATURE RANGE FOR EM PACKS/LED DRIVERS REQUIRED FOR LUMINAIRES LOCATED OUTDOORS.
DISTRIBUTION TYPE
LUMENS
1,6404000K
S1 WOOD POLE MOUNTED 133WLED 208VXL-03 18,5504000K
B1 PENDANT 33WLEDNL-7 50264000K
A1 RECESSED 25WLED 120VNL-1 3,0504000K
120V
120V
X AS INDICATED 0.70WLEDNL-63 N/A4000K
120V
TYPE VS
NOTES
NOTE 1, 2, 9
NOTE 4
NOTE 5
TYPE VS
B.O.D. LIGHT
N/A
TYPE VS
TYPE II
TYPE IV
TECHNOLOGY
SENSOR
COVERAGE
MOUNTINGMARK SENSOR DESCRIPTION
OCCUPANCY SENSOR SCHEDULE
NOTE 1: MOUNT BOTTOM OF SENSOR AT SAME ELEVATION AS ADJACENT LUMINAIRE.
B CEILING DUALADMIN AREA 1,200
A PENDANT PIR 24V DCOPEN CEILING AREA 1,600
OS WALL DUALSWITCH SENSOR 270
NOTES
(SQ. FT.) REQUIREMENTS
POWER
24V DC
24V DC
NOTE 1
C SURFACE 33WLEDNL-7 50264000K
120V TYPE V
D RECESSED 12WLEDXL-15, TYPE B 1,0754000K
120V
G RECESSED 15WLEDN/A 1,5004000K
T PENDANT 35WLEDNL-7 26354000K
120V TYPE V
NOTE 3
120V TYPE V
D1 RECESSED 8WLEDXL-15, TYPE B 6004000K
NOTE 8
NOTE 5
S2 WOOD POLE MOUNTED 133WLED 208VXL-03 18,5504000K NOTE 2, 7, 9TYPE IV
120V
P PENDANT 10WLEDN/A 1,0004000K
NOTE 6
TYPE V
TYPE V
12805280
MOUNT 14FT AFF.
NOTE 4
T1 PENDANT 67WLEDNL-7 4,8304000K
120V TYPE V
I
G
H
W
I G
H
W
F
F
G
G
G
G
G
G
G
G
G
G
G
G
S
S
S
S
S
S
S
S
G
G
C
C
C
C
F
M
T46
T44
T44
T44
T44
T45
T45
T45
T47
OPERATIONS
BUILDING
SCALE
CANOPY
LOADING
DOCK
STORAGE
BUILDING
WETLAND
WETLAND
CHH2
CHH1
A
3F-5
3F-4
3F-3
3F-2
T45
3F-6-5
3F-6-6
3F-6-4 3F-6-3
3F-6-1
3F-6-2
T5021
A2
T
T83
T81
T82
RELOCATED RADIATION
DETECTION SYSTEM PANELS.
SCALE SYSTEM PANELS.
T81
T83
T84
T84
501 North Broadway
Saint Louis, MO 63102
(314) 335-4000
LAUREN SHIPMAN
CRANE ARMY AMMO ACTIVITY
11/21/2019
100'
1" = 50'
1" = 50'
A1
TELECOM OVERALL SITE PLAN
TELECOMMUNICATIONS GENERAL NOTES
1. REFER TO SHEET T6011 FOR CABLE INFORMATION.
2. REFER TO SHEET T5021 FOR TELECOMMUNICATIONS SITE DETAILS.
3. EXISTING UTILITIES SHOWN IN LINE WEIGHT.
4. REFER TO SHEET E1001 FOR ELECTRICAL SITE PLAN.
EXISTING OH LINES TO REMAIN.
EXISTING UTILITY POLE TO REMAIN.
EXISTING UTILITY POLE TO REMAIN. REFER TO ONE-LINE DIAGRAM ON
SHEET T6011 AND POLE DETAILS ON SHEET T5021.
TWO 4-INCH CONDUITS FROM HANDHOLE TO TELECOM O-109. REFERENCE
SHEET T1011. SEE DETAIL B1/T5021.
PROVIDE 2-INCH, UG, SCHEDULE 40 PVC CONDUITS FOR RELOCATED
RADIATION DETECTION SYSTEM. PANELS TO BE RELOCATED BY OTHERS.
PROVIDE 2-INCH, UG, SCHEDULE 40 PVC CONDUITS FOR SCALE SYSTEM
PANELS. PANELS TO BE PROVIDED BY OTHERS.
FOR CONTINUATION SEE OFF-SITE FIBER OPTIC CABLE EXTENSION PLAN,
SHEETS 01001 THROUGH 01131 AND SHEETS 05011 THROUGH 05051 FOR
DETAILS. (TYPICAL)
SHADED AREA DENOTES OPTIONAL SCOPE. SEE G001 FOR ADDITIONAL
INFORMATION ON OPTIONS.
KEYNOTES
T44
T45
T46
T47
TELECOMMUNICATIONS ABBREVIATIONS
OHW OVERHEAD WIRE
TELECOMMUNICATIONS SYMBOLS
UTILITY POLE
NEW UNDERGROUND COMMUNICATIONS DUCTBANK
MANHOLE (CMH) OR HANDHOLE (CHH)
3F-6-3
CU
OVERHEAD WIRING
JDH CAT
JMH
T81
T82
T83
N
GRAPHIC SCALE
T84
DCLMP
DCLMP
T V
CONFERENCE
O-108
OPEN OFFICE
O-101
UTILITY
O-106
WOMEN
O-105
MEN
O-104
CORRIDOR
O-103
KITCHENETTE
O-102
TELECOM
O-109 T1011
C1
T1011
C2
AV
AV
C.B
C.A
C.2C.1
+70-INCHES AFF
AV, CT
AV
T79
T80
A4
T1011
PBB
C1
FRONT
T01
T02
T04
C.B
T21
3'
0"
2' - 7"
FINISH FLOOR
EL: 100' - 0"
C1
1U SPACE
2U WIRE MANAGER
2U BBFPP1
2U WIRE MANAGER
48 PORT HPP1
2U WIRE MANAGER
SWITCH (GFGI)
2U WIRE MANAGER
UPS (GFGI)
NETWORK SERVER
(GFGI)
T03
T06
T07
T08
T09
T10
T04
T11
T12
(TYP)
2U POWER STRIP
1U POWER STRIP
2U SPACE
T07
T10
T55
1U RBB T68
RBB SHALL BE INSTALLED
ON REAR SIDE OF CABINET.
T03
C.B
T03
T05
T05
T69
T70
T71
T71
T71
BBFPP BACKBONE FIBER PATCH PANEL
HCPP HORIZONTAL COPPER PATCH PANEL
PBB PRIMARY BONDING BUSBAR
TBC TELECOM BONDING CONDUCTOR
TR TELECOMMUNICATIONS ROOM
UTP UNSHIELDED TWISTED PAIR
TEBC TELECOMMUNICATIONS BONDING CONDUCTOR
RBB RACK BONDING BUSBAR
TELEPHONE AND DATA COMMUNICATIONS SYMBOLS
DATA WALL OUTLET
AV = AUDIO VISUAL
EQUIPMENT CABINET
TELEVISION OUTLET
PRIMARY BONDING BUSBAR (PBB); SECONDARY BONDING BUSBAR (SBB)
LADDER CABLE TRAY
TV
COMBINATION DATA OUTLET AND AV IN COMMON FLOOR
BOX WITH ELECTRICAL OUTLET
AV
COMBINATION DATA OUTLET IN COMMON FLOOR BOX WITH
ELECTRICAL OUTLET
MANHOLE (CMH) OR HANDHOLE (CHH)
NEW UNDERGROUND COMMUNICATIONS DUCTBANKC
TELEPHONE WALL OUTLET
1/4" = 1'-0"
2' 4' 8' 12'
C
B
D
N62473-18-D-5801
1596603
N
AV
AL
FA
C
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
C O M M
AN
D
M
ID
AT
LA
N
TI
C
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
PM/DM BHD/PJB
BRANCH MANAGER
CHIEF ENG/ARCH EA
SATISFACTORY TO
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
A/E INFO
D E P A R T M E N T
O F
T H E
N A V Y
N A V A L
F A C
IL
IT
IE
S
E N G
IN
E E R
IN
G
C O M M A N D
N
AV
AL
S
TA
TI
O N
N O R
FO
LK
VA
C R
AN
E, IN
D
IA
N A
LAUREN SHIPMAN
CRANE ARMY AMMO ACTIVITY
S
YM
D E S C R
IP
TI
O N
D
AT
E
AP
P R
C
AA
A
EX
P
LO
S
IV
E R
AI
LC
AR
H O
LD
IN
G
YA
R D
(P
SEAL
501 North Broadway Saint Louis, MO 63102
(314) 335-4000
M
ID
LA
N T C I C O R E
A
C
B
D
A
DATE
N
AV
AL
S U P P O R T
AC
TI
VI
TY
C R
AN
E
FIRE PROTECTION
DRAWFORM REVISION: 31 JANUARY 2017
GRAPHIC SCALE
PW DRAWING NO. PW7534
11/21/2019
As indicated
:4 :3
P M
T1011
TE
LE
C O M M U N
IC
AT
IO
N S
12805282
JDH CAT JMH
FL
O O R
P
LA
N S
AN
D
C
AB
IN
ET
EL
EV
AT
IO
N
1/4" = 1'-0"A1
OPERATIONS BUILDING TELECOM PLAN
1/2" = 1'-0"C1
ENLARGED TELECOM ROOM O-109 EQUIPMENT PLAN
NOT TO SCALEA4
CABINET ELEVATION
1/2" = 1'-0"C2
ENLARGED TELECOM ROOM O-109 CABLE TRAY
PLAN
SCALE: 1/2" = 1'
1' 2' 4' 6'
TELECOMMUNICATIONS GENERAL NOTES
KEYNOTES
T01 PROVIDE MULTIPLE 48-INCH WIDE X 96-INCH HIGH X 3/4-INCH DEEP FIRE
RATED PLYWOOD BACKBOARDS ON ENTIRE LENGTH OF THE WALL,
MOUNTED 6-INCHES AFF TO BOTTOM OF PLYWOOD BACKBOARD.
(TYPICAL)
T02 PROVIDE TWO 4-INCH CONDUITS FROM COMM HANDHOLE CHH1 STUBBED
3-INCHES AFF. REFER TO DETAILS A2 AND B1 ON SHEET T5021.
T03 PROVIDE 12-INCH WIDE LADDER RACK MOUNTED AT 7'-6" AFF, BLACK.
T04 PROVIDE 84-INCH HIGH X 24-INCH WIDE X 30-INCH DEEP (45RU) ENCLOSED
EQUIPMENT CABINET WITH LOCKABLE FRONT AND REAR VENTED DOORS.
T05 PROVIDE (1) 4-INCH SLEEVE, REFERENCE DETAIL B1 ON SHEET T5011.
T06 PROVIDE 2RU, UNIVERSAL WIRE MANAGER, SINGLE SIDED WITH SNAP ON
COVER THAT OPENS 180 DEGREES UP OR DOWN, 19-INCHES WIDE BY
5.25-INCHES DEEP.
T07 PROVIDE 2RU FIBER SPLICE ENCLOSURE WITH 12 FIBER SPLICE TRAY, 6
PORT DUPLEX (12-FIBER) LC, SMF ADAPTER PANELS WITH CERAMIC
SLEEVES; 12-FIBER LOOSE TUBE FIBER BREAK OUT KIT; HEAT SHRINK
SLEEVES,…