Attachment G-1596603dwg03of11_C.pdf
PDF 13 MB Posted
- Attached to
- Construction of P447 Explosive Railcar Yard
- Solicitation number
- N40085-20-R-0048
About this file
This is a solicitation for a construction project at Crane Army Ammunition Activity in Crane, Indiana. The project includes demolition and new construction work at two sites. At the Railcar Site, the work involves demolishing existing buildings and constructing a new rail holding yard with approximately 11,000 linear feet of rail track, along with associated site work. The new Defense Logistics Agency Disposition Site will include constructing a new operations building, storage building with loading ramp, and associated site work such as aggregate and concrete storage areas and off-site fiber/support structures. The solicitation also involves relocating an existing radiation detector and DLA facilities from the Railcar Site to the new DLA Disposition Site. The solicitation is being conducted by the Naval Facilities Engineering Command on behalf of the Department of the Navy.
View the file
Other files
Show 40 more
Latest 50 of 53 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
W
W
W x
W x
W x
W x
W x
H
I
G
H
W
A
Y
HYMAX TYPE COUPLER,
EXACT LOCATION TO BE
DETERMINED IN FIELD
HYMAX TYPE COUPLER,
EXACT LOCATION TO BE
DETERMINED IN FIELD
8"X8"X8" TEE
8" GATE VALVE WITH VALVE SIGN,
SEE C4/C5051 AND A4/C5081
EXISTING 8" DI
WATER LINE
CASING PIPE, SEE
PROFILE FOR DETAILS
8" C900 PVC
(WATERLINE "A")
W
W
W
W
W
W
W
G
G
8"X8"X8" TEE
8" GATE VALVE
WITH VALVE SIGN,
SEE C4/C5051
AND A4/C5081
8" GATE VALVE WITH VALVE SIGN,
SEE C4/C5051 AND A4/C5081
8" C900 PVC
(WATERLINE "B") OR
(WATERLINE "B" **OPTION**)
8" C900 PVC
(WATERLINE "A")
W
W
W
W
W
W
W
G
G
F
O
F
O
8" C900 PVC
(WATERLINE "A")
6" C900 PVC
(WATERLINE "C")
8"X8"X6" TEE
W
W
W
W
W x
W x
W x
W x
W
W x
W x
W x
W x
S
S
S
S
S
S
S
S
H I G
H W
Y
HYMAX TYPE COUPLER,
EXACT LOCATION TO BE
DETERMINED IN FIELD
CASING PIPE, SEE
PROFILE FOR DETAILS
8" C900 PVC
(WATERLINE "A")
HYMAX TYPE COUPLER,
EXACT LOCATION TO BE
DETERMINED IN FIELD
8"X8"X8" TEE
8" GATE VALVE WITH VALVE SIGN,
SEE C4/C5051 AND A4/C5081
EXISTING 8" DI
WATER LINE
W W
W W
W
W
8"X8"X8" TEE
8" C900 PVC
(WATERLINE "A")
8" GATE VALVE WITH VALVE SIGN,
SEE C4/C5051 AND A4/C5081
8" GATE VALVE WITH VALVE SIGN,
SEE C4/C5051 AND A4/C5081
8" C900 PVC
(WATERLINE "B")
F F
W W
W W W W
8" C900 PVC
(WATERLINE "A")
8" GATE VALVE WITH VALVE SIGN,
SEE C4/C5051 AND A4/C5081
1-1/4" COPPER
8" C900 PVC
FIRELINE
8"X8"X8" TEE
TAPPING SADDLE, SEE C2/C5091
CENTERLINE OF SWALE
1-1/4" VALVE WITH VALVE SIGN,
SEE A4/C5081
501 North Broadway
Saint Louis, MO 63102
(314) 335-4000
LAUREN SHIPMAN
CRANE ARMY AMMO ACTIVITY
11/21/2019
1" = 10'
A1
WATERLINE CONNECTION DETAILS
1" = 10'
C1
WATERLINE CONNECTION DETAILS
1" = 10'
C3
WATERLINE CONNECTION DETAILS
1" = 10'
C4
WATERLINE CONNECTION DETAILS
1" = 10'
A3
WATERLINE CONNECTION DETAILS
1" = 10'
A4
WATERLINE CONNECTION DETAILS
G
G
G
S
S
S
S
S
S
W
W W W W
W
W
S
D
S
D
C
C
C
R10'10.0'
C5021 C3
C5021 A1
BOTTOM OF BASIN = 581.00
5.0'
10.0'
R5'
R5'
R5'
ST-6
OUTLET STRUCTURE
A1/C5041
ST-7
FES
167' OF 4"Ø
UNDERDRAIN
6" PVC CLEANOUT
WITH PLUG (TYP)
22' OF 4"Ø
UNDERDRAIN
84' OF 4"Ø
UNDERDRAIN
56' OF 4"Ø
UNDERDRAIN
29' OF 4"Ø
UNDERDRAIN
SEE A3/C5041 FOR BIORETENTION
BASIN DETAILS
A-A
B B
STATION
0+00 0+50 1+00 1+50 2+00
5' BERM
TOP OF BERM
EL = 583.80
EXISTING
GROUND
PROPOSED GRADE
3:1 MAX (TYP)
BIORETENTION MEDIA
SEE A3/C5041
BOTTOM OF BASIN
EL = 581.00
WIDTH VARIES
SEE PLAN VIEW
STATION
0+00 0+50 1+00 1+50 2+00 2+50 3+00
BIORETENTION MEDIA
SEE A3/C5041
EXISTING
GROUNDPROPOSED GRADE
3:1 MAX (TYP)
BOTTOM OF BASIN
EL = 581.00
WIDTH VARIES
SEE PLAN VIEW
POINT TABLE
POINT #
NORTHING
1326266.1174
1326286.3939
1326337.9679
1326262.1575
1326282.4108
1326359.8886
1326258.1975
1326278.4739
1326430.7778
1326261.5262
1326268.0974
1326253.6062
1326256.2175
1326342.3522
1326372.6498
1326345.5346
1326374.7525
1326403.1714
1326405.6016
1326432.1429
1326429.7669
EASTING
3010696.8050
3010705.5492
3010727.7907
3010705.9875
3010714.7851
3010748.1343
3010715.1700
3010723.9142
3010791.6836
3010694.8250
3010692.2137
3010713.1900
3010719.7612
3010724.2363
3010754.0897
3010726.4197
3010755.8929
3010776.2752
3010777.6494
3010789.0955
3010794.6050
DESCRIPTION
CLEANOUT
CLEANOUT
CLEANOUT
CLEANOUT
CLEANOUT
CLEANOUT
CLEANOUT
CLEANOUT
CLEANOUT
TOP OF BIORETENTION BASIN
TOP OF BIORETENTION BASIN
TOP OF BIORETENTION BASIN
TOP OF BIORETENTION BASIN
TOP OF BIORETENTION BASIN
TOP OF BIORETENTION BASIN
TOP OF BIORETENTION BASIN
TOP OF BIORETENTION BASIN
TOP OF BIORETENTION BASIN
TOP OF BIORETENTION BASIN
TOP OF BIORETENTION BASIN
TOP OF BIORETENTION BASIN
501 North Broadway
Saint Louis, MO 63102
(314) 335-4000
LAUREN SHIPMAN
CRANE ARMY AMMO ACTIVITY
11/21/2019
1" = 20'
C1
BIORETENTION BASIN DETAILS
H: 1" = 20' V: 1" = 5'
C3
BIORETENTION BASIN SECTION A-A
H: 1" = 20' V: 1" = 5'
A1
BIORETENTION BASIN SECTION B-B
S
D
S
D
S
D
C5031 C3
C5
A1
R5'
R10'
R5' R10'
GRADE BOTTOM
OF BASIN
@ 1% MIN.
ST-4
OUTLET STRUCTURE
C1/C5041
EXISTING WETLAND
DO NOT DISTURB
A A
B-B
0 58
STATION
0+00 0+50 1+00 1+50 2+00
EXISTING
GROUND
PROPOSED GRADE
3:1 MAX (TYP)
1 % M
IN
STATION
0+00 0+50 1+00 1+50 2+00
EXISTING
GROUND
PROPOSED GRADE
3:1 MAX (TYP)
1 % MIN
POINT TABLE
POINT #
NORTHING
1326522.4060
1326522.4060
1326512.4060
1326463.2444
1326458.2444
1326458.2444
1326460.2604
1326513.1897
EASTING
3010867.7758
3010947.7313
3010957.7313
3010957.7313
3010952.7313
3010915.6110
3010909.5898
3010863.8783
DESCRIPTION
ELEV. 580
ELEV. 580
ELEV. 580
ELEV. 580
ELEV. 580
ELEV. 580
ELEV. 580
ELEV. 580
501 North Broadway
Saint Louis, MO 63102
(314) 335-4000
LAUREN SHIPMAN
CRANE ARMY AMMO ACTIVITY
11/21/2019
1" = 20'
C1
DETENTION BASIN DETAILS
H: 1" = 20' V: 1" = 5'
C3
DETENTION BASIN SECTION A-A
H: 1" = 20' V: 1" = 5'
A1
DETENTION BASIN SECTION B-B
4'-0"
NOTES:
1. TRASH RACK TO BE CONSTRUCTED OF GLASS-REINFORCED
HDPE AS MANUFACTURED BY PLASTIC SOLUTIONS INC. OR
APPROVED EQUAL.
2. GRID MATERIAL MUST NOT EXCEED 6" ON CENTER.
3. UV PROTECTION MUST MEET OR EXCEED ASTM D 2565-99.
4. LOAD RATING: 2030 LBS./SF
5. ANCHOR BOLTS MUST BE STAINLESS STEEL AND LOCATED
PER MANUFACTURER'S PRE-DRILLED HOLES.
PLAN VIEW
FRONT ELEVATION
BOTTOM OF BASIN = 579.00
OVERFLOW WEIR
ELEV. 582.70
TOP OF BERM = 584.50
P
R
O
P
R
A
D
E
OVERFLOW WEIR
ELEV. 582.70
TRASH RACK
ASSEMBLY - ROOF
MOUNT
SECTION A-A
BOTTOM OF BASIN = 579.00
4'
2.7' 4'
OUTLET PIPE
TRASH RACK
PROP. CONC.
FOOTING
11" ORIFICE IN
CONTROL STRUCTURE
INV. 579.00
CONTROL STRUCTURE:
INDOT CATCH BASIN - TYPE "A"
TOP OF BOX
TRASH RACK
TOP OF BOX
TRASH RACK
COMPACTED SUBGRADE
OUTFLOW PIPE SIZE
AND ORIENTATION
SEE PLAN
INV. 579.00
CONTROL STRUCTURE:
INDOT CATCH BASIN - TYPE "A"
11" ORIFICE
INV. 579.00
PCC INFILLPCC INFILL
TRASH RACK ASSEMBLY
TRASH RACK
ASSEMBLY SIDE
MOUNT
NOTES:
1. TRASH RACK TO BE CONSTRUCTED OF GLASS-REINFORCED
HDPE AS MANUFACTURED BY PLASTIC SOLUTIONS INC. OR
APPROVED EQUAL.
2. GRID MATERIAL MUST NOT EXCEED 6" ON CENTER.
3. UV PROTECTION MUST MEET OR EXCEED ASTM D 2565-99.
4. LOAD RATING: 2030 LBS./SF
5. ANCHOR BOLTS MUST BE STAINLESS STEEL AND LOCATED
PER MANUFACTURER'S PRE-DRILLED HOLES.
PLAN VIEW
FRONT ELEVATION
BOTTOM OF BASIN = 581.00
OVERFLOW WEIR
ELEV. 582.55
TOP OF BERM = 583.50
P
R
O
R
A
D
E
OVERFLOW WEIR
ELEV. 582.55
TRASH RACK
ASSEMBLY - ROOF
MOUNT
SECTION A-A
BOTTOM OF BASIN = 581.00
4'
1.55'
4'
OUTLET PIPE
TRASH RACK
PROP. CONC.
FOOTING
4" UNDERDRAIN
INV. 578.84
4" UNDERDRAIN
INV. 577.50
CONTROL STRUCTURE:
INDOT CATCH BASIN - TYPE "A"
TOP OF BOX
TRASH RACK
TOP OF BOX
TRASH RACK
COMPACTED SUBGRADE
OUTFLOW PIPE SIZE
AND ORIENTATION
SEE PLAN
INV. 577.47
CONTROL STRUCTURE:
INDOT CATCH BASIN - TYPE "A"
THREADED PLUG
INV. 577.50
4" Ø UNDERDRAIN
(SCHEDULE 40 PVC OR SDR 35)
CLEANOUT/OBSERVATION WELL
INV. 578.84
6" ORIFICE
INV. EL. 581.40
6" ORIFICE
INV. EL. 581.40
TRASH RACK ASSEMBLY
TRASH RACK
ASSEMBLY SIDE
MOUNT
24" (MIN.) THICK
BIORETENTION
SOIL MEDIA
EXISTING SOIL SUBGRADE,
TILLED OR "RIPPED" 12"
DEEP BEFORE BACKFILLING
4" Ø SCHEDULE 40 PVC OR SDR 35
PERFORATED PIPE, 3/8" Ø HOLES, TWO
SIDES, FACING DOWN, 2" OFF BOTTOM
FILTER FABRIC
(SIDES ONLY)
2" THICK MULCH
SLOPE VARIES, SEE
GRADING PLAN (TYP.)
6" THICK SAND (ASTM C-33
FINE AGGREGATE)
6" THICK 3/8" Ø GRAVEL
(ASTM C-33 NO. 8)
6" THICK 3/4" Ø GRAVEL
(ASTM C-33 NO. 6 OR 67)
NOTE:
ALL SAND AND GRAVEL TO BE NATURAL, UNCRUSHED.
VEGETATION NOT SHOWN FOR CLARITY. BOTTOM OF BASIN TO BE PLANTED WITH SWAMP MILKWEED (ASCLEPIAS INCARNATE) AT 2' CENTERS
(#1 CONTAINER).
THE PLANTING SOIL MUST BE A SANDY LOAM OR LOAMY SAND CONTAINING A MINIMUM OF 60 PERCENT SAND, BY VOLUME. THE CLAY
CONTENT MUST BE LESS THAN 10 PERCENT BY VOLUME. A SATURATED HYDRAULIC CONDUCTIVITY OF AT LEAST 2.0 FEET PER DAY (1.0 INCHES
PER HOUR) IS REQUIRED. THE SOIL MUST BE FREE OF STONES, STUMPS, ROOTS, OR OTHER WOODY MATERIAL OVER 1 INCH IN DIAMETER AND
MUST BE FREE OF BRUSH OR SEEDS FROM NOXIOUS WEEDS, SUCH AS JOHNSON GRASS, MUGWORT, NUTSEDGE AND CANADIAN THISTLE.
PLACEMENT OF THE PLANTING SOIL MUST BE IN LIFTS OF 12 TO 18 INCHES, LOOSELY COMPACTED (RUBBER WHEELED HEAVY EQUIPMENT AND
MECHANICAL TAMPING DEVICES ARE NOT RECOMMENDED FOR COMPACTION). THE PH RANGE MUST BE BETWEEN 5.2 AND 8.0. ORGANIC
MATTER MUST BE BETWEEN 1.5 AND 5%. MAGNESIUM, PHOSPHORUS AND POTASSIUM MUST BE APPLIED AT MINIMUM RATES OF 35, 75 AND 85
LBS. PER ACRE.
THE MULCH LAYER MUST BE STANDARD LANDSCAPE STYLE, SINGLE OR DOUBLE SHREDDED HARDWOOD MULCH. THE MULCH LAYER MUST BE
FREE OF OTHER MATERIALS, SUCH AS WEED SEEDS, SOIL, ROOTS, ETC.
WIDTH VARIES, SEE PLAN VIEW
501 North Broadway
Saint Louis, MO 63102
(314) 335-4000
LAUREN SHIPMAN
CRANE ARMY AMMO ACTIVITY
11/21/2019
1" = 20'
A1
BIORETENTION BASIN OUTLET STRUCTURE
1" = 20'
C1
DETENTION BASIN OUTLET STRUCTURE
1" = 20'
A3
BIORETENTION TYPICAL
M I N
V A
R I E
S
M
I N
#3 BAR ALL AROUND (W/ 6"
OVERLAP)
DUCTILE IRON (TO MAIN)
WITH TRACE WIRE
NTS
A2
THRUST BLOCK
NTS
C2
POST INDICATOR VALVE
NTS
C4
VALVE AND VALVE BOX
NTS
A1
TYPICAL UTILITY TRENCHING - UNPAVED
NTS
C1
TYPICAL UTILITY TRENCHING - PAVED
1"
ROUND CONCRETE COLLAR
(4000 PSI CONCRETE)
6" TYP.
6"
THERMITE WELD
GATE VALVE
WATER LINE
WITH TRACE WIRE
THRUST BLOCK
REFER TO DETAIL ON THIS SHEET
POST INDICATOR
GROUND LINE
DUCTILE IRON (TO BUILDING)
3'-0" MIN.
3'-6" MIN.
FINISH GRADE
FINAL BACKFILL
COMPACT TO 95% ASTM 1557
UTILITY MARKING TAPE
TRACE WIRE (TAPE TO PIPE)
UTILITY BEDDING MATERIAL
- SEE SPECIFICATION
VARIES
MIN. WIDTH REQUIRED FOR SAFE UTILITY
INSTALLATION PER OSHA REQUIREMENTS
PIPE O.D. + 18"
MINIMUM
PIPE O.D. + 18"
MINIMUM
6"
SEE DETAIL ON
SHEET C-5071
UTILITY BEDDING
MATERIAL - SEE
SPECIFICATION
TRACE WIRE (TAPE
TO PIPE)
PAVEMENT
FINISHED PAVED AREA
VARIES
COVER, LABELED "WATER"
UTILITY MARKING TAPE
VARIES
MIN. WIDTH REQUIRED FOR SAFE UTILITY
INSTALLATION PER OSHA REQUIREMENTS
PLUS 1' ON EACH SIDE
12"
BACKFILL MATERIAL
6"
THRUST BLOCK,
REFER TO DETAIL
ON THIS SHEET
EXTEND TRACER WIRE FROM SPLICE ALONG
VALVE BOX AND EXTEND 3 FEET OF EXTRA
TRACER WIRE INSIDE OF VALVE BOX
SPLICE VALVE TRACER WIRE TO PIPE
TRACER WIRE WITH BRASS OR
ALUMINUM WIRE CLAMP
PROVIDE
" X 12" LONG SCH. 40 PVC PIPE BURIED WITH
CAP JUST ABOVE GROUND LEVEL. EXTEND TRACER
WIRE FROM SPLICE ALONG VALVE BOX AND EXTEND TO
GROUND SURFACE, LOOP AT TOP AND DRAPE BACK TO
BOTTOM OF PVC PIPE. CONNECT LOOP TO CAP.
SPLICE VALVE TRACER WIRE TO
PIPE TRACER WIRE WITH BRASS
OR ALUMINUM WIRE CLAMP
REMOVABLE FLOWABLE FILL
PER INDOT STANDARD
SPECIFICATION, SECTION 213
8"
NOTES:
1. THRUST BLOCK BUILT AGAINST UNDISTURBED SOIL WITH ADEQUATE BACKING TO PREVENT MOVEMENT OF FITTING.
2. BEARING TABLE BASED ON 150 PSI STATIC PRESSURE PLUS 50 PSI WATER HAMMER AND 3000 PSF SOIL BEARING.
3. PIPE JOINTS AND BOLTS MUST BE ACCESSIBLE.
4. FELT WRAP AND TAPE FITTING FASTENER AREAS PRIOR TO THE CONCRETE THRUST BLOCK POUR TO ALLOW
FUTURE ACCESS TO THE FASTENERS AT THE JOINTS.
5. THRUST BLOCKING ON VALVE SHALL HAVE THE SAME SOIL BEARING AREA AS A 45° ELBOW .
6. THRUST BLOCKING DETAILS ARE SHOWN FOR TYPICAL INSTALLATIONS. IN SOME CASES ADDITIONAL RESTRAINT MAY BE REQUIRED.
FOR UNSTABLE SOIL CONDITIONS, SUBMIT RFI TO CONTRACTING OFFICER FOR THRUST BLOCK DIMENSIONS.
7. USE 2500 PSI PORTLAND CEMENT CONCRETE FOR THRUST BLOCKS.
8. WHERE PIPES ARE INSTALLED PARALLEL TO EACH OTHER, USE RESTRAINED JOINTS WHERE THRUST BLOCKS CANNOT BE USED.
9. ALL WATERLINES MUST BE RESTRAINED USING MECHANICAL JOINTS.
B
BA
1'-3"
1'-0"
8"
6" dxe
C B
6"
6"
8"
5"
ACB
6"
6"
1'-0"
7"
8"
6"x4"
4"x2" e
A
B
8" 1'-1"
A
A d
A
B
8" 1'-6" d
B
1'-1"
C
R E
D U
C E
R S
AC
B
6"
6"
1'-4"
10"
ACB
6"
6"
1'-1" 1'-4"
Ad
4"
2"-2.5"
1'-1"
B
E N
D S
8"
A
2'-0" d
B
B
E N
D S
8"
B
A
1'-8" d d
B
2'-0"
C
B
6"
B
A C d
1'-8" 1'-6"
1'-0"
T E
E
N D
C
P
S
B E
N D
S
MINIMUM SIZE OF 2500 PSI CONCRETE THRUST BLOCKS FOR WATER MAINS
CB
3'-7" 2'-3"
A
2'-3"
V
E R
T I C
A L
B
E N
D
10" 1'-5"
10" 2'-0" 1'-5"10" 2'-2"10"
2'-3" 3'-4"8" 2'-3"
2'-0" 1'-6"
10" 8"x6"
C
A
B
C
V
E R
T I C
A L
B
E N
D
5" 8"
10" 7"
5'-6" 3'-7"
3'-7"
#4
REIN.
BAR
12" 2'-7"12" 2'-7"12"
2'-4" 4'-4"
3'-5" 4'-4"
12" 1'-9"
1'-9"10"
CB
Ad
4"
2"-2.5"
6"
C R
O S
S E
S
8"
10"
10" 8"
10" d
B
A
A
B
B
B
A
A
C
C
1'-0" 6"
4"x2
501 North Broadway
Saint Louis, MO 63102
(314) 335-4000
LAUREN SHIPMAN
CRANE ARMY AMMO ACTIVITY
11/21/2019
NTS
C2
TYPICAL FIRE HYDRANT SETTING
E D
O
F
P
A V
E M
E N
T
ROUND CONCRETE COLLAR
1'-0" x 1'-0" x 1'-0"
CONCRETE BLOCK
2'-0" SQ. X 6"
CONCRETE BLOCK
1'-3" MIN. SQ.
CONCRETE BLOCK
3'-0" MIN. 7'-0" MAX.
3'-6" (TYP.)
2'-0" MAX. (LOW PROFILE)
4'-0"MAX. (STANDARD HT.)
1'-6" MIN.
FINISHED GRADE
SEE VALVE BOX DETAIL
FOR CONCRETE COLLAR
EXTEND TRACER WIRE
FROM SPLICE ALONG
VALVE BOX AND
EXTEND 3 FEET OF
EXTRA TRACER WIRE
INSIDE OF VALVE BOX
SPLICE VALVE TRACER WIRE
TO PIPE TRACER WIRE WITH
BRASS OR ALUMINUM WIRE
CLAMP
COMBINATION AIR VALVE
8" PIPE
CONCRETE BASE
1'-0" X 2'-0" X 5'-0"
WITH #5 REBAR ON
12" CENTERS
GRADE
CAST IRON FRAME AND COVER,
SET TOP 3" ABOVE
SURROUNDING GRADE
GRADE
SUPPORT PIPE WITH UNISTRUT
CHANNEL AND U-BOLT
PROVIDE ASPHALT
WATERPROOF COATING
2" BRASS NIPPLE
48" I.D. PRECAST
CONCRETE MANHOLE
" SQUARE JOINT SEALANT
(KENT-SEAL NO.2 OR EQUAL)
" DIAMETER PRESSURE
GAGE (0-300 PSI) (SEE NOTE 1)
" BALL VALVE
8" PIPE
2" COMBINATION AIR VALVE
2" BRASS UNION
2" BALL VALVE
2" THEADED TAP
FILL TO TOP OF PIPE WITH
GRANULAR BACKFILL
NOTE:
1. FACE OF PRESSURE GAGE MUST BE VIEWABLE THROUGH THE AIR RELEASE
VALVE VAULT HATCH WITHOUT ENTERING THE VAULT.
STEP 16" O.C. (TYP.)
SECTION "A-A"
PLAN
NTS
A4
AIR RELEASE VALVE
48" I.D. PRECAST
CONCRETE MANHOLE
PROVIDE MECHANICAL JOINT
RESTRAINTS BETWEEN TEE
AND VALVE
ITEM ITEM / DESCRIPTION
NOTES:
1. AUTOMATIC FLUSHING DEVICE MUST HAVE A 2" STAINLESS STEEL FIP INLET THAT WILL LEAD
VERTICALLY TO THE BOTTOM OF A 2” AUTOMATIC FLUSHING VALVE.
2. THE FLUSHING VALVE MUST CONTROL THE FLOW OF WATER THROUGH THE HYDRANT AND ITS
DIAPHRAGM WITH THE EXTENSION AND RETRACTION OF A DC LATCHING SOLENOID AND HAVE A 220 PSI
RATING.
3. EACH UNIT MUST BE FURNISHED WITH A STAND-ALONE VALVE CONTROLLER. THE VALVE CONTROLLER
WILL NOT REQUIRE A SECOND HAND-HELD DEVICE FOR PROGRAMMING. CONTROLLER MUST HAVE
MINIMUM OF 12 POSSIBLE FLUSHING CYCLES PER DAY. CONTROLLER MUST BE SUBMERSIBLE TO 12
FEET, OPERATE WITH A 9 VOLT BATTERY, AND HAVE RESIN-SEALED ELECTRICAL COMPONENTS. THE
SOLENOID MUST HAVE NO LOOSE PARTS WHEN REMOVED FROM THE VALVE. EACH UNIT MUST HAVE A
ALL STAINLESS STEEL SAMPLING POINT. REMOVAL OF THE 2" VALVE SHALL BE POSSIBLE VIA AN O-RING
CONNECTOR LOCATED BENEATH THE VALVE AFTER THE ABOVE GROUND DISCONNECTION OF THE
STAINLESS STEEL ACCESS PLATE. VALVE ASSEMBLY MUST BE HOUSED IN A PVC ENCLOSURE AND
EACH UNIT MUST BE SELF-DRAINING, NON-FREEZING. ALL ABOVE-GROUND COMPONENTS MUST BE
CONTAINED WITHIN A UV-RESISTANT LOCKING COVER.
4. WATER LINES MUST BE FREE OF DEBRIS PRIOR TO INSTALLATION.
5. UNIT MODEL # MUST BE ECLIPSE 9800, OR APPROVED EQUAL.
42"
MIN.
R
4" AIR GAP
NTS
A1
FLUSH HYDRANT
NTS
A2
FIRE HYDRANT BOLLARD LOCATION DETAIL
UV RESISTANT LOCKABLE LID
DIFFUSER / TRAP
2" PVC BALL VALVE
SAMPLING POINT
2" STAINLESS STEEL QUICK DISCONNECT
REMOVABLE ACCESS PLATE
DECHLOR BASKET
6" 45° PVC ELBOW
CONTROLLER
SDR 35 PVC PIPE
AUTOMATIC DRAIN
2" AUTOMATIC VALVE
O-RING CONNECTOR
1" CLEAN ROCK
2" BRASS FIP INLET
2" MIP x COMPRESSION ADAPTER
DEBRIS PLATE
6" PVC PIPE
SCHEDULE 80 PVC PIPE
6" PVC P TRAP
DEPTH AS REQUIRED
SEE WATER
LINE PROFILES
T
Y
P
EDGE OF TRAVELWAY
NOTES:
1. USE WHERE SHOWN ON PLANS.
2. REFER TO FIRE HYDRANT DETAIL FOR HYDRANT INSTALLATION AND CONNECTION TO
FIRE MAIN.
3. REFER TO BOLLARD DETAIL FOR CONSTRUCTION.
3'-0"
FENCE
HYDRANT OR PIV
WATER MAIN WITH
TRACE WIRE
6" DIA. D.I.
AS REQUIRED
VALVE
VALVE BOX
GRAVEL
#3 BAR ALL AROUND
(W/6" OVERLAP)
PAINT HYDRANT TOP AND NOZZLE CAP AS
REQUIRED BY NFPA 291
PAINT HYDRANT BARREL YELLOW IN
ACCORDANCE WITH UFC 3-600-01
501 North Broadway
Saint Louis, MO 63102
(314) 335-4000
LAUREN SHIPMAN
C1
SIDEWALK
PREMOLDED STRIP OR JOINT
SEALER WHEN SAWED
FLUSH WITH SURFACE
T/3 MIN.
1/8"
T
T
LUBRICATE ONE END
1"Ø SMOOTH DOWEL
BAR 18"LG. @ 12" CTRS.
NTS
D2
HEAVY DUTY CONCRETE PAVEMENT
NTS
C2
CONCRETE PAVEMENT
TRANSVERSE CONTRACTION JOINT
NTS
B1
CONCRETE MOW STRIP
NTS
A1
ASPHALT PAVEMENT
W
4" PCC SIDEWALK
DUMMY JOINT (MADE
WITH 3/4" CENTER GROVER)
4" AGGREGATE BASE
COURSE
UNDISTURBED EARTH OR
COMPACTED FILL
PREPARED SUBGRADE
1/2" PREMOLDED EXPANSION
JOINT FILLER WITH JOINT
SEALER.
NOTES:
1. W = WIDTH OF SIDEWALK
2. SPACE DUMMY JOINTS AT W. PLACE EXPANSION JOINTS AT 3 x W.
3. EXPANSION JOINT MUST BE PLACED THROUGH THE FULL DEPTH OF THE SIDEWALK.
1.5" HMA, PG 64-22, 9.5 MM SURFACE
2.5" HMA, PG 64-22, 19.0 MM INTERMEDIATE
6" NO. 53 AGGREGATE BASE COURSE
PREPARED SUBGRADE
TACK COAT
8" P.C. CONCRETE (NON-REINFORCED)
PREPARED SUBGRADE
4" AGGREGATE BASE COURSE, EXTEND 4" MIN. BEYOND
PAVEMENT EDGE
PREPARED SUBGRADE
2' WIDE CAST IN PLACE CONCRETE (4" THICK) SLOPE 1%
AWAY FROM BUILDING
FACE OF BUILDING
FINISHED GRADE, TOPSOIL AND SEED
4"
6" NO. 53 AGGREGATE BASE COURSE
1/2" PREMOLDED EXPANSION JOINT
FILLER WITH JOINT SEALER.
1-1/4" ROLLER CUT
DOWEL SLEEVE
NOTE: 12' MAXIMUM JOINT SPACING
NOTES:
1. CONCRETE MATERIAL TO
MATCH SIDEWALK
2. PLACE JOINTS TO MATCH
SIDEWALK DETAIL (C1,
THIS SHEET)
NTS
A2
AGGREGATE PAVEMENT
6" INDOT #2 CRUSHED AGGREGATE
PREPARED SUBGRADE
NTS
B2
AGGREGATE FILTER STRIP
PREPARED SUBGRADE
6" INDOT #2 CRUSHED STONE
NTS
C4
CONCRETE DUMPSTER PAD
8" P.C. CONCRETE
PREPARED SUBGRADE
4" AGGREGATE BASE COURSE
6" INDOT #53 CRUSHED AGGREGATE
NOTES:
1. PORTLAND CEMENT CONCRETE MUST BE MIN. 4500 PSI COMPRESSIVE STRENGTH.
2. PRIOR TO PLACING BASE MATERIALS, THE SUBGRADE SOIL MUST BE PREPARED PER
GEOTECHNICAL REPORT. FILL MATERIALS WITHIN PAVEMENT AREAS MUST BE PLACED IN
LIFTS NOT EXCEEDING 8 INCHES AND COMPACTED TO A MIN. 95% OF THE SOIL'S
MODIFIED PROCTOR (ASTM D 1557) MAXIMUM DRY DENSITY.
3. AGGREGATE BASE MUST BE COMPACED TO A MIN. 95% OF MODIFIED PROCTOR MAXIMUM
DRY DENSITY (ASTM D 1557).
4. CONCRETE PAVEMENT IN THE TRASH ENCLOSURE AREA MUST BE REINFORCED WITH #4
@ 12" EACH DIRECTION.
NTS
A4
CONCRETE PARKING BLOCK
2'-8" MIN. TO
8"
EDGE OF PARKING
LOT
3" NO. 8 AGGREGATE BASE COURSE
2-#4 BARS THRU WHEEL STOP &
PARKING SURFACE, MIN 18" LONG.
PARKING SURFACE
6' LONG PRECAST CONC. WHEEL STOP
W/2-#4 BARS CONT. 5'-9" LONG
UNDISTURBED SOIL/COMPACTED FILL
PER PROJECT SPECIFICATIONS
BIAXIAL GEOGRID
501 North Broadway
Saint Louis, MO 63102
(314) 335-4000
LAUREN SHIPMAN
C1
MUTCD SIGNAGE
NTS
C2
SIGN MOUNTING
NTS
C4
CROSSWALK
NTS
A1
BOLLARD
WASHER
M
I N
M
A X
3"
FINISH GRADE
CONCRETE
SLOPE TO DRAIN
3/8" DIA. PAN HEAD
MACHINE SCREW
W/HEX NUT &
WASHERS
3LB U-CHANNEL
GALVANIZED
STEEL (12 GAUGE)
NOT TO SCALE
NOT TO SCALE
SIGN MOUNTING POST
SIGN PANEL ATTACHMENT
3.4"
1.3"
MUTCD STANDARD SIGN DESIGNATION SHOW AS (X-1)
MOUNTING HEIGHT - 60" FROM BOTTOM OF SIGN TO
PAVEMENT IN NON-PEDISTRIAN AREAS AND 84" IN
PEDISTRIAN AREAS.
ALL SIGNS MUST BE MOUNTED TO 3LB "U-CHANNEL" POST.
ALL ROAD WAY SIGNAGE MUST BE HIGH INTENSITY
SHEETING
SIGNS MUST MEET THE REQUIREMENTS OF THE MANUAL
ON UNIFORM TRAFFIC CONTROL DEVICES (MUTCD).
SIGNS MUST BE FABRICATED FROM ALUMINUM ALLOY
SHEETS.
ALL MOUNTING HARDWARE MUST BE GALVANIZED.
NOTES:
FLOW OF TRAFFIC
6" D
C
L
NOTES:
1. POSTS MUST BE PAINTED CATERPILLAR YELLOW.
1.
2.
3.
4.
5.
6.
7.
ACCESSIBLE PARKING (R7-8 AND R7-8A)
NOT TO SCALE
1.9"
2' TYP.
PIANO KEY MARKING, WHITE
8'
2'
18"
6"
4'
4'
2"
PAVEMENT OR SIDEWALK
6" Ø SCHEDULE 80 STEEL PIPE FILLED WITH
CONCRETE AND PAINTED SAFETY YELLOW
SLOPE TO DRAIN (TYP)
FINISHED GRADE
CONCRETE
PEDESTRIAN CROSSING
SIGN
20'
VAN
ACCESSIBLE
RESERVED
PARKING
NTS
A2
ACCESSIBLE STALL MARKING
PEDESTRIAN CROSSING (W11-2)
NOT TO SCALE
DO NOT ENTER (R5-1)
NOT TO SCALE
SIGN PANEL ATTACHMENT
WASHER
3/8" DIA. PAN HEAD
MACHINE SCREW W/HEX
NUT & WASHERS
SIGN MOUNTING POST
FINISHED GRADE
PAINTED 3-LB
B-CHANNEL
GALVANIZED STEEL
(12 GAUGE)
4" x 8" ALUMINUM METAL PLATE AT TOP OF POST, SIGN TO
BE MOUNTED PARALLEL TO THE LINE THE VALVE/HYDRANT
IS ASSOCIATED WITH. VALVE/HYDRANT NUMBER SHOWN ON
PLATE TO BE COORDINATED WITH CONTRACTING OFFICER.
NTS
A4
VALVE/HYDRANT LOCATION SIGN
KEYED NOTES:
9"(TYP.)
4"(TYP.)
T
Y P
T
Y P
4" (TYP.)
1. TYPICAL VAN ACCESSIBLE SPACE.
2. TYPICAL STANDARD ACCESSIBLE SPACE.
3. RESERVED PARKING SYMBOL
4. 4" WIDE WHITE STRIPING (TYP.)
5. RESERVED PARKING SIGN
6. CONC. SIDEWALK
7. CONCRETE WHEEL STOP
TYPICAL STANDARD ACCESSIBLE LAYOUT
TYP. PARKING LOT STRIPING
9'
9'9'9'
6" Ø CONCRETE BOLLARD CAP
PAINTED SAFETY YELLOW
501 North Broadway
Saint Louis, MO 63102
(314) 335-4000
LAUREN SHIPMAN
A3
ROOF DRAIN CONNECTION
6" DIA. PVC
PIPE
4"X6" PVC ENLARGER
6" 90° PVC ELBOW
PLAN
PROFILE
SEE PLAN
12" DIA. PVC PIPE
6" DIA. PVC PIPE
12"x6" 45° PVC WYE
SIDEWALK / DOCK / MOW STRIP / GRASS, SEE PLANS
4" DIA. PVC PIPE
NOTES:
1. ALL CONNECTIONS MUST BE WATER TIGHT
12"x6" 45°
PVC WYE
6" 45° PVC ELBOW
6" 45° PVC
BEND
12" DIA. PVC PIPE
PROPOSED
BUILDING
CAST IRON DOWNSPOUT ADAPTER
NEW DOWNSPOUT,
SEE ARCHITECTURE FOR DETAILS
1%
MANUFACTURER'S STANDARD TRANSITIONAL
COUPLING
NTS
C4
PRECAST CONCRETE END SECTION
DIA. WALL
A
(+/-1")
B
(+/-1")
C
(+/-1")
E
12" 2" 5" 4'-3" 6'-2" 2'-0"
15"
18"
7"
11"
4'-0"
4'-1"
2-1/4"
2-1/2 "
6'-3"
6'-2"
2'-6"
3'-0"
24"
DIMENSIONS
B
C
A
E
PLAN VIEW
SECTION A-A
END VIEW
8"
WALL
DIA.
A A
DIA.
WALL
6"
D
WALL +6"
D
DIA.
E
WALL
TOE WALL
A1
A1
MANHOLE DETAILS
NTS
C1
MANHOLE FRAME AND COVER DETAILS
SECTION"A-A"
PLAN
A
A
1.75"
1.0"
SANITARY SEWER
MANHOLE BASE SET ON
6" OF #8 STONE
8"
3" MIN. ABOVE BASE
#4 BARS - 12" O.C. BOTH WAYS, 3" MIN COVER
PRECAST CONCRETE SECTIONS
FILL WITH CONCRETE, SLOPE SIDES AT 1/2"/FOOT
(MIN)
NOTES:
1. MANHOLE MUST CONFORM TO ASTM C-478.
2. JOINTS MUST CONFORM TO ASTM C-443.
3. PROVIDE STEEL LADDER WITH RUNGS SPACED AT 12" ON
CENTER FOR STRUCTURE GREATER THAN 12 FEET DEEP.
4' DIAM. MIN.
O-RING GASKET BETWEEN ALL RISER AND CONE
SECTIONS, PLUS 1/2" EXTRUDABLE GASKET (KENT
SEAL OR EQUAL)
ECCENTRIC CONE SECTION
BUTYL RUBBER BASE EXTERIOR BACKPLASTER
MATERIAL. 1/4"±1/16" MIN. THICKNESS FROM 2"
BELOW TOP OF CONE TO CASTING.
PRECAST CONCRETE ADJUSTER RINGS
4" MIN. - 12" MAX.
FRAME AND COVER
TOP OF FRAME ELEVATION (SEE PLANS)
34" OR 36", DEPENDENT
UPON O.D. OF RING SECTION IN USE
26"
21"
MACHINED BEARING SURFACE
22.75"
SELF-SEALING APPLICATON
7" OR 9"
FRAME AND COVER WITH
"SELF-SEALING" APPLICATION
TYPE "B" LID DESIGN
CONCEALED PICKHOLES
12" O.C.
24" MAX.
24" MAX.
"WATER", "SANITARY SEWER" OR "WATER"
AS APPROPRIATE.
21" 11" 3'-6"2-3/4 " 6'-3" 3'-6"
24" 1'-0" 2'-8"3 " 6'-3" 4'-0"
D
(+/-1")
24"
24"
24"
24"
BLAZE ORANGE HIGH
DENSITY
POLYETHYLENE
FABRIC FENCE
STEEL POSTS
GROUND LINE
GROUND PLATES
10'-0"
NTS
A4
CONSTRUCTION FENCE DETAIL
TAPPING SADDLE WITH NEOPRENE
GASKET
TAPPING SADDLE BAND
DOUBLE STRAP
(8-INCH PIPE & LARGER)
COPPER TUBING
COPPER TUBING GOOSENECK
COPPER TUBING
COMPRESSION JOINT
COMPRESSION JOINT
CORPORATION STOP
ACP, PVC, DI OR CI PIPE
SINGLE BOLT & NUT (SHOWN)
TAPPING SADDLE BAND SINGLE STRAP
6-INCH PIPE & SMALLER
NTS
C2
TAPPING SADDLE FOR COPPER WATER SERVICE
AIR GAP
501 North Broadway
Saint Louis, MO 63102
(314) 335-4000
LAUREN SHIPMAN
B R
I
D
T H
6"
10'-0" MAXIMUM
6"
M
I N
16" MIN. DIA.
CONCRETE BASE
TENSION WIRE
BRACE RAIL
LINE POST
LINE POST
GRADE
HOG RINGS (TYP.)
10" MIN. DIA.
TOP RAIL OR TENSION WIRE
PULL POST
LINE POST
LINE POST
TRUSS ROD
TRUSS ROD
10'-0" MAX.
10'-0" MAX.
NO SCALE
NO SCALE
STEEL POST SCHEDULE
USE AND SECTION
MINIMUM OUTSIDE DIMENSIONS (NOMINAL)
FABRIC WIDTH 72" OR LESS
FABRIC WIDTH 84" TO 96"
FABRIC WIDTH 108" AND OVER
CORNER, END & PULL POSTS
TUBULAR - ROUND
TUBULAR - SQUARE
C-SECTION (ROLL-FORMED)
LINE POSTS
TUBULAR - ROUND
H-SECTION
C-SECTION (ROLL-FORMED)
TOP, BOTTOM & BRACE RAILS
TUBULAR - ROUND
TUBULAR - SQUARE
H-SECTION
C-SECTION (ROLL-FORMED)
BRACE RAILS
BRACE RAILS
2"
CHAIN-LINK SECURITY FENCE DETAIL
BRACE PANEL DETAIL
PROVIDE BRACE PANEL WHENEVER STRAIGHT
RUNS EXCEED 500 FEET.
TRUSS ROD (3/8" MIN. DIA.)
CHAIN-LINK FABRIC (9 GAGE, 2" MESH)
NOTE:
2.375" O.D.
2.00" SQ.
3.50" X 3.50"
2.875" O.D.
2.50" SQ.
3.50" X 3.50"
4.00" O.D.
3.00" SQ.
1.90" O.D.
2.25" X 1.70"
1.875" X 1.625"
2.375" O.D.
2.25" X 1.70"
2.25" X 1.70"
2.875" O.D. 2.25" X
1.70"
CORNER, END,
OR PULL POST
TIE WIRES OR
CLIPS (TYP.)
TIE WIRES OR HOG
RINGS (TYP.)
TENSION WIRE
BOTTOM OF FABRIC
1.66" O.D.
1.50" SQ.
1.625" X 1.50"
1.625" X 1.25"
NOTES:
1. DETAILS SHOWN ARE TO CLARIFY REQUIREMENTS AND ARE NOT INTENDED TO LIMIT OTHER TYPES OF
FENCE SECTIONS AND METHODS OF INSTALLATION THAT COMPLY WITH THE SPECIFICATIONS.
2. FENCING MUST BE FE5 OR FE6 IN ACCORDANCE WITH COR DIRECTION.
3. WIRE TIES, RAILS, POSTS, AND BRACES MUST BE CONSTRUCTED ON THE SECURE SIDE OF THE FENCE
ALIGNMENT. CHAIN-LINK FABRIC MUST BE PLACED ON THE SIDE OPPOSITE THE SECURE AREA.
4. UNLESS SPECIFICALLY SHOWN OR SPECIFIED, ALL FE6 FENCE MUST HAVE AN APRON EXTENDED
OUTWARD FROM THE AREA BEING PROTECTED.
5. C-SECTION POSTS MUST BE INSTALLED SO THAT THE VOID INSIDE THE POST IS COMPLETELY FILLED WITH
CONCRETE UP TO THE TOP OF THE FOUNDATION.
FENCE LEGEND:
TYPE FE5 - CHAIN-LINK FENCE WITHOUT BARBED-WIRE APRON
TYPE FE6 - CHAIN-LINK FENCE W/BARBED-WIRE ON SINGLE OUTRIGGER
TYPE FE7 - CHAIN-LINK FENCE W/BARBED WIRE ON DOUBLE OUTRIGGER
TYPE FE8 - CHAIN-LINK FENCE W/BARBED-WIRE AND BARBED-TAPE ON DOUBLE OUTRIGGER
TR - FENCE WITH TOP RAIL AND TENSION WIRE AT BOTTOM
TBR - FENCE WITH TOP AND BOTTOM RAILS
TWB - TENSION WIRE TOP AND BOTTOM
TWBR - FENCE WITH TOP TENSION WIRE AND BOTTOM RAIL
FINAL NUMBER IS FABRIC WIDTH IN INCHES.
EXAMPLES
FE6-TR-72 - CHAIN-LINK SECURITY FENCE WITH BARBED-WIRE ON SINGLE OUTRIGGER, TOP RAIL, AND 72
INCH FABRIC WIDTH.
FE5-TWB-84 - CHAIN-LINK SECURITY FENCE WITH NO APRON, TOP AND BOTTOM TENSION WIRE, AND 84 INCH
FABRIC WIDTH.
10'-0" O.C. MAXIMUM
LINE POSTS TO BE EQUALLY SPACED
0" MIN
2" MAX
TENSION WIRE
NTS
A1
FENCE DETAILS
REFER TO FENCE DETAIL
ABOVE FOR BASE DIMENSIONS
REFER TO FENCE DETAIL
ABOVE FOR BASE DIMENSIONS
501 North Broadway
Saint Louis, MO 63102
(314) 335-4000
LAUREN SHIPMAN
N C
E
F
A B
R
L A
N
BRACE RAIL
LATCH
BRACE RAIL
GRADE LINE
TRUSS ROD
TRUSS
ROD
10"
GATE POST SCHEDULE
GATE LEAF WIDTH OUTSIDE DIMENSION
(NOMINAL)
(NOMINAL)
6' OR LESS
2.875" OD
2.5" SQ
4.0" OD
MORE THAN 18'
8.625" OD
6.625" OD
GATE OPENING
GATE LEAF
HINGE
HINGE
TOP TENSION WIRE
OR RAIL AS SPECIFIED
STANDARD HINGE
GATE KEEPER
(TO HOLD GATE OPEN)
NOTES:
2. SWING GATES WILL BE CONSTRUCTED WITH DROP RODS, PADLOCKS, LATCH
ASSEMBLY AND GATE KEEPERS EXCEPT AS NOTED.
GATE
POST
NO SCALE
PERSONNEL GATE
TYPE FE-5 FENCE
LATCH ASSEMBLY
1. FOR NON-SENSORED FENCES, DETAILS SHOWN ARE TO CLARIFY REQUIREMENTS
AND ARE NOT INTENDED TO LIMIT OTHER TYPE OF FENCE SECTIONS AND
METHODS OF INSTALLATION WHICH COMPLY WITH THE SPECIFICATIONS.
4. GATES WILL BE DESIGNATED AS FOLLOWS:
FENCE TYPE - FE5, FE6, ETC.
FENCE HEIGHT - INCHES
TYPE OPENING - SO (SINGLE)
- DO (DOUBLE)
HINGE - RA (STANDARD)
- HO (OFFSET)
OPENING - FEET (CLEAR OPENING BETWEEN GATE POSTS)
EXAMPLES: FE6-84-DO-RA-24
FE5-48-SO-HO-6
GREATER THAN 6' TO 12'
GREATER THAN 12' TO 18'
BOTTOM TENSION
WIRE OR RAIL AS
SPECIFIED
3. ALL GATE FRAMES WILL MEET THE MINIMUM REQUIREMENTS OF ASTM F900
1.90" NOMINAL (ROUND) OR 2.00" NOMINAL (SQUARE). GATE FRAMES
WILL BE OF WELDED CONSTRUCTION OR WILL BE ASSEMBLED USING
HEAVY FITTINGS. AT CONTRACTOR'S OPTION A WELDED HORIZONTAL
BRACE MAY BE USED IN LIEU OF TRUSS RODS TO BRACE ALL-WELDED GATE
FRAMES. THE CONTRACTOR WILL BE RESPONSIBLE FOR THE PROPER RIGID
CONSTRUCTION OF ALL GATES SUPPLIED.
NTS
A1
GATE DETAILS
OFFSET HINGE
10'-0" MAXIMUM
M
I N
16" MIN. DIA.
CONCRETE BASE
BRACE RAIL
LINE POST
GUIDE WHEEL
ELEVATION
PLAN
2" MAX. CLEAR TOP
& BOTTOM MEMBERS
TIE WIRES OR
CLIPS (TYP.)
TRUSS ROD
(3/8" MIN. DIA.)
4" DIA. GATE POST
(1 OF 3)
4" O.D.
POST
GATE
SECTION
BAR & BANDS
3/8" DIA.
TRUSS ROD
2" O.D. PIPE
(TYP.)
WELDED PLATE
WITH HOLE FOR
TRUSS ROD
TRUSS RODS
WELDED AT
UPPER CORNERS
10'-0"
GATE
OUTSIDE
INSIDE
38'-0" GATE FRAME
38'-0" CLEAR OPENING
1'-3"
POST DIA. 4"
GATE OPENING 38'-0"
STRETCHER
TOP TENSION WIRE
2 1/2" O.D. PIPE (TYP.)
SLIDE GATE (TYPE FE-5 FENCE)
NO SCALE
BACK FRAME AS REQUIRED
BY MANUFACTURER
5. GATE DIMENSIONS MAY VARY, DEPENDING ON GATE MANUFACTURER.
10" MIN. DIA.
501 North Broadway
Saint Louis, MO 63102
(314) 335-4000
LAUREN SHIPMAN
2'
1' 2'
R
#3 BAR
DIRECTION
OF FLOW
SECURE ENDS OF
STAKES AS DIRECTED
DIRECTION
OF FLOW
1/2"
REBAR STAKE FOR
EROSION CONTROL
FILTER SOCK LAP DETAIL
NOTE: STAKES SHOULD EXTEND 8" BELOW SOCK.
PARALLEL OVERLAPS - SAME MAT
NOTES:
1. INSTALLATION OF EROSION CONTROL MAT/BLANKETS WILL
COMPLY WITH MANUFACTURER'S SPECIFICATIONS.
2. TEMPORARY EROSION CONTROL BLANKET USE ONE 9" BIO-STAKE
OR SOD PIN (SEE DETAIL).
3. PERMANENT EROSION CONTROL BLANKETS USE 12" SOD PIN
(SEE DETAIL).
S
L
O
P
E
F
L
O
W
S
L
O
P
E
WASHRACK
(OPTIONAL)
INDOT TYPE 2A
GEOTEXTILE
WASHRACK (OPTIONAL)
2"-3" CRUSHED AGGREGATE
PLAN
A A
SECTION
A
NTS
IF WASH RACK IS USED, DISCHARGE MUST DRAIN
TO A EROSION CONTROL BMP.
NOTES:
24"
M
I N
20' MIN.
1. WASHOUT LOCATION TO BE COORDINATED WITH
CONTRACTING OFFICER.
2. DRY CONCRETE TO BE REMOVED FROM THE SITE
PERIODICALLY AND DISPOSED OF BY APPROVED METHODS.
3. THE CONCRETE WASHOUT SIGN WILL BE INSTALLED
WITHIN 30 FT. OF THE TEMP. CONCRETE WASHOUT FACILITY.
NOTES:
WOOD POSTS
4" x 4" x 8'
0.5" LAG SCREWS
3/8 " TREATED PLYWOOD
48" x 24" PAINTED WHITE
CONCRETE
WASHOUT
BURY LINING
IN STONE
BERM (#8 STONE)
10 MIL. PLASTIC LINING
TO TERMINATE IN STONE
BERM (#8 STONE)
LATH & FLAGGING ON
ALL SIDES
10 MIL. PLASTIC LINING
M
I N
M
I N
70' MINIMUM
NTS
D1
FILTER SOCK EROSION CONTROL DETAILS
NTS
B1
EROSION CONTROL BLANKET
NTS
C3
TEMPORARY CONSTRUCTION EXIT
NTS
A1
CONCRETE WASHOUT WITH SIGN
2"X 2"X 36" LONG HARDWOOD STAKES W/ ONE END
SHAPPENED &SPACED 5'-0" O.C.
CUT CONTINUOUS TRENCH, 6" TO 8" DEEP & INSERT
LOOSE END OF FABRIC, BACKFILL W/ EXCAVATED
MATERIAL & COMPACT
MAINTAIN BY REMOVING ACCUMULATED SILT
36" EIDE NON-WOVEN POLYPROPYLENE GEOTEX
FABRIC (4.5 OZ/S.Q YARD)
WOOD LATH TO SECURE TO STAKES
V A
R I E
S
T
Y P
DOWN SLOPE
NTS
C4
SILT FENCE DETAIL
NTS
A3
RIP-RAP APRON
4"
1'
RIP-RAP
SECTION B-B
DDD
MIN. 3D
18" MIN.
D
SECTION A-A
3DL
FLARED END SECTION PLAN
RIP-RAP
3D
MIN.
D
D
D
B
B
D
A
A
FILTER FABRIC
FILTER FABRIC
D
D
FLARED END SECTION
FLARED END SECTION
501 North Broadway
Saint Louis, MO 63102
(314) 335-4000
LAUREN SHIPMAN
B1
PUMP/VALVE VAULT PLAN VIEW
INVERT ELEVATION
HIGH LEVEL ALARM
2ND PUMP START
1ST PUMP START
PUMPS STOP
LOW LEVEL ALARM
BASE OF LIFT STATION
PROPOSED OPERATING LEVELS
0°
90°
180°
270°
VALVE VAULT BASE
CENTER
6" INLET PIPE
INVERT
GENERAL SHEET NOTES
KEYNOTES
2" SCHEDULE 80 PVC FORCED MAIN.
2" SCHEDULE 80 PVC FORCED MAIN. REFER TO A1 / C1411 FOR CONTINUATION.
2" BALL VALVE.
5' DIAMETER VALVE VAULT.
2" CHECK VALVE.
ELECTRICAL CONDUIT CONNECTIONS.
OUTLINE OF ACCESS HATCH CLEAR OPENING ABOVE.
LADDER.
3" SCHEDULE 80 PVC DRAIN PIPE. SLOPE TO LIFT STATION WET WELL.
GUIDE RAILS.
5' DIAMETER PUMP VAULT.
SUBMERSIBLE CENTRIFUGAL GRINDER PUMP (QTY. 2). PROVIDE 4HP/208V/3PH, LEAK
DETECTION, STAINLESS STEEL LIFTING CHAIN, AND 20' OF ELECTRICAL CABLE. REFER TO
SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
6" INLET PIPE. REFER TO A1 / C1411 FOR CONTINUATION.
FLANGED COUPLING ADAPTOR OR VANSTONE FLANGE (TYP.)
LOCKABLE ACCESS HATCH. SIZE AND POSITION OF HATCH AS RECOMMENDED BY PUMP
STATION MANUFACTURER.
4" VENT PIPE WITH ODOR CONTROL CANISTER AND INSECT SCREEN.
PIPE SIZE FLANGED FLEX CONNECTOR IN SCHEDULE 80 PVC PIPE.
MANUFACTURER'S PROVIDED CONTROL PANEL SUPPLIED WITH PRE-MANUFACTURED LIFT
STATION. REFER TO ELECTRICAL DRAWINGS FOR POWER SUPPLIED TO PANEL AND
DISCONNECT INSTALLED ADJACENT TO PANEL.
SQUARE METAL TUBE SUPPORT BRACE FOR MANUFACTURER'S PROVIDED PANEL. SECURE
TO CONCRETE LIFT STATION PAD WITH CONCRETE ANCHORS.
REINFORCED CONCRETE FOUNDATION. FOUNDATION MUST BE DESIGNED BY LICENSED
PROFESSIONAL ENGINEER IN STATE OF INDIANA.
2" VENT PIPE WITH ODOR CONTROL CANISTER AND INSECT SCREEN.
LADDER WITH "LADDER-UP" RETRACTABLE POLE.
3"RUBBER DUCKBILL CHECK VALVE.
STAINLESS STEEL GUIDE RAIL SUPPORT (TYP.).
STAINLESS STEEL PIPE SUPPORT (TYP.).
2" SCHEDULE 80 PVC MALE ADAPTER (4 REQUIRED).
3/4" SCHEDULE 40 STAINLESS STEEL GUIDE RAIL PIPE.
GUIDE RAIL (TYP.).
STAINLESS STEEL PIPE THRUST RESTRAINT (TYP.).
STAINLESS STEEL CROSS BAR (1/4" x 2" x 40 4/16" APPROX.) WITH U-BOLT FOR PIPE
SUPPORT.
2" SCHEDULE 80 PVC PIPE AND FITTINGS.
JUNCTION BOX.
FLOAT SWITCHES TO BE PROVIDED BY PACKAGED LIFT STATION MANUFACTURER.
STAINLESS STEEL FLOAT BRACKET.
2" TEMPORARY PUMP CONNECTION. COORDINATE OUTLET CONNECTION
TYPE WITH PWD CRANE.
18'-0"
0°
270°
CONCRETE PAD, REFER
TO DETAIL D3 / C5131
NTS
D1
PUMP/VALVE VAULT "A-A" SECTION VIEW
NTS
A1
PUMP/VALVE VAULT ELEVATION
577.50'
576.75'
576.25'
575.75'
572.67'
572.25'
571.33'
1. SEE SHEET C0011 FOR GENERAL NOTES.
2. EXISTING UTILITY AND TOPO MAPPING PROVIDED BY BRCJ. SEE EXISTING
CONDITION / SURVEY SHEET FOR AS SURVEYED CONDITIONS (V1011 TO
V1051).
3. TREE CLEARING ALLOWED ONLY BETWEEN THE DATES OF OCTOBER 1ST
AND MARCH 31ST. COORDINATE WITH CONTRACTING OFFICER PRIOR TO
BEGINNING WORK.
4. ALL EXISTING UNDERGROUND UTILITIES MUST BE PROTECTED UNLESS
OTHERWISE NOTED OTHERWISE.
5. FOR ORIENTATION OF PIPING REFER TO SITE UTILITY PLAN.
6. WET WELL (CYLINDER) AND VALVE VAULT MUST BE FACTORY
PRE-ASSEMBLED. REFER TO SPECIFICATIONS FOR REQUIREMENTS.
7. REFER TO C5141 FOR LIFT STATION CONTROLS.
8'-0"
90°
180°
NTS
D3
CONCRETE LIFT STATION PAD
4" P.C. CONCRETE
4" AGGREGATE BASE
COURSE
UNDISTURBED EARTH
OR COMPACTED FILL
PREPARED SUBGRADE
10'-0"
NOTES:
1. PORTLAND CEMENT CONCRETE MUST BE MIN. 4500 PSI COMPRESSIVE
STRENGTH.
2. PRIOR TO PLACING BASE MATERIALS, THE SUBGRADE SOIL MUST BE
PREPARED PER GEOTECHNICAL REPORT. FILL MATERIALS WITHIN
PAVEMENT AREAS MUST BE PLACED IN LIFTS NOT EXCEEDING 8 INCHES
AND COMPACTED TO A MIN. 98% OF THE SOIL'S STANDARD PROCTOR
(ASTM D 698) MAXIMUM DRY DENSITY.
3. AGGREGATE BASE MUST BE COMPACED TO A MIN. 98% OF MODIFIED
PROCTOR MAXIMUM DRY DENSITY (ASTM D 1557).
4. CONCRETE PAVEMENT IN THE LIFT STATION AREA MUST BE
REINFORCED WITH #4 @ 12" EACH DIRECTION.
A A
EL. 581.33' TOP
EL. 581.00'
GRADE
EL. 577.50'
EL. 576.33'
EL. 581.00'
GRADE
EL. 577.50'
LIFT STATION BASE
10'-0"
1'-0"
EL. 571.33'
5 5
CONCRETE BLOCK
EXISTING 8"
DUCTILE IRON PIPE
SMITH BLAIR 2" SS
SINGLE STRAP DUCTILE
IRON BODY SADDLE
CLAMP OR EQUAL
SADDLE CLAMP
VALVE BOX
2" SS THREADED
PIPE NIPPLE
INTEGRITY FUSION PRODUCTS,
INC. STANDARD NPT MALE
TRANSITION SDR 11 OR EQUAL NEW 2" HDPE
FORCE MAIN
EXISTING 8"
DUCTILE IRON PIPE
FINISHED GRADE
SEE VALVE BOX DETAIL
FOR CONCRETE COLLAR
VALVE BOX
NEW 2" HDPE
FORCE MAIN
2" BALL VALVE
TRACE WIRE
NTS
A3
FORCE MAIN TAPPING DETAIL
2" SS BALL VALVE W/
NUT OPERATOR
501 North Broadway
Saint Louis, MO 63102
(314) 335-4000
LAUREN SHIPMAN
PUMP
NO. 1
TSH
PMP210A
PUMP
NO. 2
YS
PMP210B
TSH
PMP210B
SANITARY LIFT STATION
LSLL
PMP210
YS
PMP210A
SEAL LEAK
LSL
PMP210
LSH
PMP210
LSH
PMP210
YL
PMP210B
FAULT
PUMPING STATION CONTROL PANEL (PROVIDED BY PRE-PACKAGE LIFT STATION MANUFACTURER)
LCP-PMP210A/B
HS
PMP210B
HOA
YL
PMP210A
FAULT
HS
PMP210A
HOA
NOTE 1
NOTES:
1. INSTALL THE LEVEL SWITCH INTRINSICALLY SAFE RELAYS IN THE SANITARY
PUMP STATION LOCAL CONTROL PANEL. ALSO INSTALL THE PUMP VENDOR
SUPPLIED SEAL LEAK DETECTION RELAYS IN THE LOCAL CONTROL PANEL.
NEW CLEANOUT
EX. 8"
NOTE: VALVES ARE THE SAME SIZE AND SPECIFICATION AS THE
LINE THEY ARE IN UNLESS STATED OTHERWISE ON THE DRAWING.
ARV AIR RELEASE VALVE
VL
VP
VY
VN
VO
ANGLE
BUTTERFLY
PLUG
NEEDLE
PINCH
DESIGNATION
VG
VK
VC
VD
VA
VB
SYMBOL
KNIFE GATE
GLOBE
DIAPHRAGM
CHECK
GATE
BALL
TYPE
OPTIONAL
DESIGNATION
NONE
NONE
NONE
NONE
NONE
NONE
NONE
TP
NONE
ST
FLC
PSE
CC
QCU
QCH
SCOPE, SUPPLY OR LOCATION
CHANGE IN SPECIFICATION,
(XXX) (XXX)
ECCENTRIC REDUCER
FOT = FLAT SIDE ON TOP
FOB = FLAT SIDE ON BOTTOM
FLEXIBLE CONNECTION
MECHANICAL COUPLING
PRESSURE SAFETY ELEMENT
RUPTURE DISC -
HOSE COUPLING
QUICK COUPLING
TRAP
STRAINER
FLOOR DRAIN
HUB DRAIN
FLANGED CONNECTION
CONCENTRIC REDUCER
FOB
SYMBOL
UNION
TYPE
BLIND FLANGE
CAP/PLUG
SYMBOL
(CENTRIFUGAL)
SUBMERSIBLE PUMP
CENTRIFUGAL PUMP
TYPE
MUD (DRAIN)
MUD
ELECTRIC MOTOR
M
TW
3 WAY
SUBMERSIBLE MOTOR
M
NONE
CHECK VALVE
*= 24VDCFIELD DEVICE ELECTRICAL
120 VACPOWER SUPPLY
ES*
UNIQUE NUMBER WITHIN AREA CODE/FUNCTION CODE
TYPE OR OPERATIONAL INFO (AS REQUIRED)
PLC INTERLOCK
IN-LINE INSTRUMENT
PANEL MOUNTED DEVICE
ISA INSTRUMENT FUNCTION CODE
FIELD MOUNTED INSTRUMENT
EXAMPLE SYMBOLS
AREA CODE (AS REQUIRED)
TYPE OR OPERATIONAL INFO (AS REQUIRED)
PLC INTERFACE
NODE FUNCTION
X = NUMBER
NOTE X
AI
P#X
N = NETWORK
I = INPUT
O = OUTPUT
# = AREA
A = ANALOG
D = DISCRETE
SIGNAL TYPE PLC INFORMATION
X = PLC NO.
A1 / C1411
6"GRAVITY SANITARY
SEWER FROM
OPERATIONS BUILDING
EX. 8
PLC/COMPUTER COMMUNICATION SIGNAL
D = DEVICENET
C = CONTROLNET
P = PROFIBUS
E = ETHERNET
INSTRUMENTATION (ANALOG, DISCRETE
OR NETWORK SIGNAL)
PRIMARY PROCESS PIPING/FLOW
SKID/VENDOR PACKAGE BOUNDARY
EXISTING PIPING
SOURCE/DESTINATION
DESCRIPTION
CAPILLARY LINE
NEW 2"
FORCED MAIN
VALVE BOX
2VB1
2VB1
3 DRAIN
P & ID LINE LEGEND
INTERFACE SYMBOLS
A1 / C1411
EXISTING 8"
FORCED MAIN
A1 / C1411
EXISTING 8"
FORCED MAIN
PIPING & PIPING EQUIPMENT SYMBOLS
INSTRUMENT IDENTIFICATION
VALVE SYMBOLS
PIPING & PIPING EQUIPMENT SYMBOLS
2VC
2VC
PRESSURE GAUGE WITH
DIAPHRAGM SEAL AND
ISOLATION VALVE.
PRESSURE GAUGE WITH
DIAPHRAGM SEAL AND
ISOLATION VALVE.
2" TEMPORARY PUMP
CONNECTION
VALVE VAULT
2VB1
F I E
L D
2"X8" TAPPING
TEE
2VB1
2VC
LSHH
PMP210
PLC CONTROLLER
501 North Broadway
Saint Louis, MO 63102
(314) 335-4000
LAUREN SHIPMAN
| 04_Civil |
| C5011 - WATER LINE CONNECTION DETAILS |
| C5021 - DETENTION BASIN DETAILS |
| C5031 - DETENTION BASIN DETAILS |
| C5041 - DETENTION BASIN DETAILS |
| C5051 - DETAILS |
| C5061 - DETAILS |
| C5071 - DETAILS |
| C5081 - DETAILS |
| C5091 - DETAILS |
| C5101 - DETAILS |
| C5111 - DETAILS |
| C5121 - DETAILS |
| C5131 - LIFT STATION DETAILS |
| C5141 - LIFT STATION DETAILS |
2020-02-04T15:09:16-0500
2020-02-04T15:09:36-0500
2020-02-04T15:09:35-0500
2020-02-04T15:09:34-0500
2020-02-04T15:09:34-0500
2020-02-04T15:09:33-0500
2020-02-04T15:09:33-0500
2020-02-04T15:09:32-0500
2020-02-04T15:09:32-0500
2020-02-04T15:09:39-0500
2020-02-04T15:09:39-0500
2020-02-04T15:09:38-0500
2020-02-04T15:09:37-0500
2020-02-04T15:09:36-0500
2020-02-05T07:19:28-0500
2020-02-05T07:21:34-0500
2020-02-05T07:21:36-0500
2020-02-05T07:21:37-0500
2020-02-05T07:23:09-0500
2020-02-05T07:23:10-0500
2020-02-05T07:23:12-0500
2020-02-05T07:23:14-0500
2020-02-05T07:23:16-0500
2020-02-05T07:23:17-0500
2020-02-05T07:23:19-0500
2020-02-05T07:23:21-0500
2020-02-05T07:23:22-0500
2020-02-05T07:23:24-0500
| 2020-02-06T14:18:30-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-02-06T14:19:01-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-02-06T14:19:02-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-02-06T14:19:36-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-02-06T14:20:09-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-02-06T14:20:40-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-02-06T14:20:41-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-02-06T14:20:42-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-02-06T14:21:06-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-02-06T14:21:37-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-02-06T14:22:07-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-02-06T14:22:37-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-02-06T14:23:09-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-02-06T14:23:10-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-02-06T14:24:37-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-02-06T14:25:48-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-02-06T14:25:49-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-02-06T14:25:50-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-02-06T14:25:51-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-02-06T14:25:52-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-02-06T14:25:53-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-02-06T14:25:54-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-02-06T14:25:55-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-02-06T14:25:56-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-02-06T14:25:57-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-02-06T14:25:58-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-02-06T14:25:59-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-02-06T14:26:01-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
File details come from the government source that posted it. Updated .