J-1502000-08.a Monthly and Yearly Checklist for AST - DHA.pdf

PDF 333 KB Posted

Attached to
Base Operations Support (BOS) Services at U. S. Naval Air Station (NAS) Sigonella and its outlying support activities, Sicily, Italy
Solicitation number
N6247025R0020
Issued by

About this file

This document is a set of inspection checklists from the Steel Tank Institute (STI) SP001 standard for various types of tank and container inspections. The file contains three main checklists: a Monthly Inspection Checklist for Aboveground Storage Tanks (ASTs), an Annual Inspection Checklist for ASTs, and a Portable Container Monthly Inspection Checklist. Each checklist provides detailed guidance and a comprehensive set of items to inspect, covering areas such as tank foundation, shell, equipment, containment, piping, and overall structural integrity. The checklists are designed for owners and inspectors to systematically evaluate the condition of storage tanks and containers, with checkboxes for each inspection item, spaces for comments, and guidance on what to look for during the inspection process. The documents emphasize the importance of regular visual inspections to ensure safe and proper operation of storage tanks and containers, with instructions to retain completed checklists for at least 36 months.

View the file

Other files

File Type Posted
Solicitation Amendment N6247025R00200011 SF 30.pdf PDF
Annex 1606001 C Water (Overseas) - Amend 0010.pdf PDF
J-1601000 Utility Management - Amend 0010.pdf PDF
Solicitation Amendment N6247025R00200009 SF 30.pdf PDF
Solicitation Amendment N6247025R00200008 SF 30.pdf PDF
J-1602000 Electrical - Amend 0008.pdf PDF
Solicitation Amendment N6247025R00200007.pdf PDF
Annex 1502000 C Facility Investment Amend 0007.pdf PDF
Annex 1503010 C Custodial - Amend 0007.pdf PDF
Annex 1601000 C Utility Management - Amend 0007.pdf PDF
J-12 PPI Responses (Ament 0007).pdf PDF
J-0200000-12 ELINs Sigonella - Amend 0007.xlsx XLSX spreadsheet
J-1606001 Water (Overseas) Amend 0007.pdf PDF
Solicitation Amendment N6247025R00200003.pdf PDF
Annex 0100000 General Information- Amendment 0002.pdf PDF
Solicitation Amendment N6247025R00200001 SF 30.pdf PDF
Section F Deliverables.pdf PDF
J-1 Past Performance Questionnaire (Form PPQ).pdf PDF
Annex 0100000 General Information.pdf PDF
Annex 1401000 Family Housing.pdf PDF
Annex 1402000 Unaccompanied Housing.pdf PDF
Annex 1503010 Custodial.pdf PDF
Annex 1503050 Grounds Maintenance and Landscaping.pdf PDF
Annex 1602000 Electrical.pdf PDF
J-0200000 Management and Adminstration.pdf PDF
J-1401000 Family Housing.pdf PDF
J-1501000 Facility Management.pdf PDF
J-1502000 Facility Investment.pdf PDF
J-1502000-04 Bldg 273 Critical Areas Requiring ICRA.pdf PDF
J-1502000-07.a POL Fuel Depot Equipment Description.xlsx XLSX spreadsheet
J-1503010-06.b Custodial Inventory and Frequencies.xlsx XLSX spreadsheet
J-1503030-04 Solid Waste Collection Pick-Up Points Maps.pdf PDF
J-1503050 Grounds Maintenance and Landscaping.pdf PDF
J-1503060 Pavement Clearance.pdf PDF
J-1601000-03 Annual Utility Service Order Workload.pdf PDF
1603000 J Natural Gas.pdf PDF
J-1603000-04 Critical Spare Parts Inventory.xlsx XLSX spreadsheet
1604000 J Wastewater.pdf PDF
1700000 J Transportation.pdf PDF
J-1700000-04 Bus Stops Maps.pdf PDF
J-1700000-05 Shuttle Bus Services Satisfaction Survey Sample.pdf PDF
1800000 J Environmental.pdf PDF
J3 Section B Supplies or Services and Prices.pdf PDF
J-5 Pre Proposal Site Visit Sigonella.pdf PDF
Annex 1503030 Integrated Solid Waste Management.pdf PDF
Annex 1503060 Pavement Clearance.pdf PDF
Annex 1601000 Utility Management.pdf PDF
Annex 1800000 Environmental.pdf PDF
J-0200000-10 Oil and Hazardous Substance Spill Response Procedures.pdf PDF
J-1502000-07 Base Systems Description RFP.xlsx XLSX spreadsheet
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Monthly Checklist Page 1 of 3

STI SP001 Monthly Inspection Checklist

General Inspection Information:

Inspection Date: __________________

Prior Inspection Date: _________________

Retain until date: __________________

Inspector Name (print): _______________________________________________________________

Title: _____________________________

Inspector’s Signature ___________________________________________________________________________

Tank(s) inspected ID ___________________________________________________________________

Regulatory facility name and ID number (if applicable) ____________________________________________________________________

Inspection Guidance:

This checklist is intended as a model. Locally developed checklists are acceptable as long as they are substantially equivalent (as applicable). Inspections of multiple tanks may be captured on one form as long as the tanks are substantially the same.

For equipment not included in this Standard, follow the manufacturer recommended inspection/testing schedules and procedures.

The periodic AST Inspection is intended for monitoring the external AST condition and its containment structure. This visual inspection does not require a Certified

Inspector. It shall be performed by an owner’s inspector per paragraph 4.1.2 of the standard.

Upon discovery of water in the primary tank, secondary containment area, interstice, or spill container, remove promptly or take other corrective action. Inspect the liquid for regulated products or other contaminants and dispose of properly.

Non-conforming items important to tank or containment integrity require evaluation by an engineer experienced in AST design, a Certified Inspector, or a tank manufacturer who will determine the corrective action. Note the non-conformance and corresponding corrective action in the comment section.

Retain the completed checklists for at least 36 months.

After severe weather (snow, ice, wind storms) or maintenance (such as coating) that could affect the operation of critical components (normal and emergency vents, valves), an inspection of these components is required as soon as the equipment is safely accessible after the event.

ITEM STATUS COMMENTS / DATE CORRECTED

Tank and Piping

Is tank exterior (roof, shell, heads, bottom, connections, fittings, valves, etc.) free of visible leaks?

Note: If "No", identify tank and describe leak and actions taken.

□ Yes □ No

2 Is the tank liquid level gauge legible and in good working condition? □ Yes □ No □ N/A

3 Is the area around the tank (concrete surfaces, ground, containment, etc.) free of visible signs of leakage? □ Yes □ No

Monthly Checklist Page 2 of 3

Is the primary tank free of water or has another preventative measure been taken?

NOTE: Refer to paragraphs 6.10 and 6.11 of the standard for alternatives for Category 1 tanks. N/A is only appropriate for these alternatives.

□ Yes □ No □ N/A

5 For double-wall or double bottom tanks or CE-ASTs, is interstitial monitoring equipment (where applicable) in good working condition? □ Yes □ No □ N/A

6 For double-wall tanks or double bottom tanks or CE-ASTs, is interstice free of liquid?

Remove the liquid if it is found. If tank product is found, investigate possible leak. □ Yes □ No □ N/A

Equipment on tank

7 If overfill equipment has a “test” button, does it activate the audible horn or light to confirm operation? If battery operated, replace battery if needed. □ Yes □ No □ N/A

8 Is overfill prevention equipment in good working condition? If it is equipped with a mechanical test mechanism, actuate the mechanism to confirm operation. □ Yes □ No □ N/A

9 Is the spill container (spill bucket) empty, free of visible leaks and in good working condition? □ Yes □ No □ N/A

10 Are piping connections to the tank (valves, fittings, pumps, etc.) free of visible leaks?

Note: If "No", identify location and describe leak. □ Yes □ No

11 Do the ladders/platforms/walkways appear to be secure with no sign of severe corrosion or damage? □ Yes □ No □ N/A

Containment (Diking/Impounding)

12 Is the containment free of excess liquid, debris, cracks, corrosion, erosion, fire hazards and other integrity issues? □ Yes □ No □ N/A

13 Are dike drain valves closed and in good working condition? □ Yes □ No □ N/A

14 Are containment egress pathways clear and any gates/doors operable? □ Yes □ No □ N/A

Concrete Exterior AST (CE-AST)

15 Inspect all sides for cracks in concrete. Are there any cracks in the concrete exterior larger than 1/16”? □ Yes □ No □ N/A

16 Inspect concrete exterior body of the tank for cleanliness, need of coating, or rusting where applicable. Tank exterior in acceptable condition? □ Yes □ No □ N/A

Visual inspect all tank top openings including nipples, manways, tank top overfill containers, and leak detection tubes. Is the sealant between all tank top openings and concrete intact and in good condition?

□ Yes □ No □ N/A

Other Conditions

18 Is the system free of any other conditions that need to be addressed for continued safe operation? □ Yes □ No

Monthly Checklist Page 3 of 3

Additional Comments:

Annual Checklist Page 1 of 4

STI SP001 Annual Inspection Checklist

Inspector Name (print):________________________________________________________________

Inspector’s Signature: ___________________________________________________________________________

Tank(s) inspected ID ___________________________________________________________________

Regulatory facility name and ID number (if applicable) ____________________________________________________________________

This checklist is intended as a model. Locally developed checklists are acceptable as long as they are substantially equivalent (as applicable).

For equipment not included in this Standard, follow the manufacturer recommended inspection/testing schedules and procedures.

The periodic AST Inspection is intended for monitoring the external AST condition and its containment structure. This visual inspection does not require a Certified

Inspector. It shall be performed by an owner’s inspector per paragraph 4.1.2 of the standard.

Remove promptly standing water or liquid discovered in the primary tank, secondary containment area, interstice, or spill container. Before discharge to the environment, inspect the liquid for regulated products or other contaminants and disposed of it properly.

In order to comply with EPA SPCC (Spill Prevention, Control and Countermeasure) rules, a facility should regularly test liquid level sensing devices to ensure proper operation (40 CFR 112.8(c)(8)(v)).

Non-conforming items important to tank or containment integrity require evaluation by an engineer experienced in AST design, a Certified Inspector, or a tank manufacturer who will determine the corrective action. Note the non-conformance and corresponding corrective action in the comment section.

Retain the completed checklists for at least 36 months.

Complete this checklist on an annual basis, supplemental to the owner monthly-performed inspection checklists.

Note: If a change has occurred to the tank system or containment that may affect the SPCC plan, the condition should be evaluated against the current plan requirement by a Professional Engineer knowledgeable in SPCC development and implementation.

ITEM STATUS COMMENTS / DATE CORRECTED

Tank Foundation/Supports

1 Free of tank settlement or foundation washout? □Yes □No

2 Concrete pad or ring wall free of cracking and spalling? □Yes □No □N/A

Annual Checklist Page 2 of 4

3 Tank supports in satisfactory condition? □Yes □No □N/A

4 Is water able to drain away from tank if tank is resting on a foundation or on the ground? □Yes □No □N/A

5 Is the grounding strap between the tank and foundation/supports in good condition? □Yes □No □N/A

Tank Shell, Heads and Roof

6 Free of visible signs of coating failure? □Yes □No

7 Free of noticeable distortions, buckling, denting, or bulging? □Yes □No

8 Free of standing water on roof? □Yes □No □N/A

9 Are all labels and tags intact and legible? □Yes □No

Tank Manways, Piping, and Equipment

10 Flanged connection bolts tight and fully engaged with no sign of wear or corrosion? □Yes □No □N/A

Tank Equipment

11 Normal and emergency vents free of obstructions? □Yes □No

12 Normal vent on tanks storing gasoline equipped with pressure/vacuum vent? □Yes □No □N/A

13 Are flame arrestors free of corrosion and are air passages free of blockage? □Yes □No □N/A

Is the emergency vent in good working condition and functional, as required by manufacturer? Consult manufacturer’s requirements. Verify that components are moving freely (including long-bolt manways).

□Yes □No □N/A

Is interstitial leak detection equipment in good condition? Are windows on sight gauges clear? Are wire connections intact? If equipment has a test function, does it activate to confirm operation?”

□Yes □No □N/A

Annual Checklist Page 3 of 4

Are all valves free of leaks, corrosion and other damage? Follow manufacturers’ instructions for regular maintenance of these items. Check the following and verify (as applicable):

□ Anti-siphon valve

□ Check valve

□ Gate valve

□ Pressure regulator valve

□ Expansion relief valve

□ Solenoid valve

□ Fire valve

□ Shear valve

□Yes □No □N/A □Yes □No □N/A □Yes □No □N/A

17 Are strainers and filters clean and in good condition? □Yes □No □N/A

Insulated Tanks

Free of missing insulation?

Insulation free of visible signs of damage?

Insulation adequately protected from water intrusion?

□Yes □No □N/A

19 Insulation free of noticeable areas of moisture? □Yes □No □N/A

20 Insulation free of mold? □Yes □No □N/A

21 Free of visible signs of coating failure? □Yes □No □N/A

Tank / Piping Release Detection

22 Is inventory control being performed and documented if required? □Yes □No □N/A

23 Is release detection being performed and documented if required? □Yes □No □N/A

Other Equipment

24 Are electrical wiring and boxes in good condition? □Yes □No □N/A

Has the cathodic protection system on the tank been tested as required by the designing engineer?

Annual Checklist Page 4 of 4

Additional Comments:

Portable Container Checklist Page 1 of 2

STI SP001 Portable Container Monthly Inspection Checklist

Inspector Name (print): _______________________________________________________________

Inspector’s Signature (): ___________________________________________________________________________

Container(s) inspected ID ___________________________________________________________________

Regulatory facility name and ID number (if applicable) ____________________________________________________________________

This checklist is intended as a model. Locally developed checklists are acceptable as long as they are substantially equivalent (as applicable).

This periodic Inspection is intended for monitoring the external condition and its containment structure. This visual inspection does not require a

Certified Inspector. It shall be performed by an owner’s inspector who is familiar with the site and can identify changes and developing problems. Note the non-conformance and corresponding corrective action in the comment section.

Retain the completed checklists for at least 36 months.

Item Area: Area: Area: Area:

Portable Container Containment/Storage Area

1 Are all portable container(s) within designated storage area? Yes No Yes No Yes No Yes No

2 Is the containment and storage area free of excess liquid, debris, cracks or fire hazards? Yes No Yes No Yes No Yes No

3 Are drain valves closed and in good working condition? Yes No N/A Yes No N/A Yes No N/A Yes No N/A

4 Are containment egress pathways clear and any gates/doors operable? Yes No N/A Yes No N/A Yes No N/A Yes No N/A

Container 5 Is the container free of leaks?

Note: If "No", identify container and describe leak.

Yes No Yes No Yes No Yes No

6 Is the container free of distortions, buckling, denting or bulging? Yes No Yes No Yes No Yes No

SP001 AST Inspection Standard COPYRIGHT© 2018 Steel Tank Institute

January 2018

Comments: