Fort Bliss Gravesite Expansion BD Part 11.pdf

PDF 8 MB Posted

Attached to
Fort Bliss National Cemetery, Gravesite Expansion and FCA Deficiencies
Solicitation number
36C78626B0028
Issued by

About this file

This document is a comprehensive set of technical bid documents and construction drawings for the Fort Bliss National Cemetery Expansion project located at 5200 Fred Wilson Avenue, El Paso, Texas. The project is sponsored by the U.S. Department of Veterans Affairs, Office of Construction and Facilities Management, and includes detailed specifications for low voltage/security, fire alarm, technology, and related infrastructure systems.

The technology scope encompasses communications infrastructure including telecommunications rooms (TE/1 and TE/2), fiber optic connectivity, network switches, modular patch panels, cable management systems, and bonding/grounding equipment. Specific equipment required includes SC-series components (grounding busbars, cable trays, terminal boards, UPS systems), network switches, fiber optic panels with LC connectors, and 25-pair copper and 6-strand fiber connections between buildings. The project also requires video surveillance systems with five megapixel cameras (VS-CM-1 model), a video management server, and KVM equipment for monitoring. Access control and intrusion detection systems are specified with integrated components including credential readers, door position switches, glass break sensors, motion detectors, and audible/visual alarm devices. Fire alarm systems must include addressable control panels, smoke/heat detectors, manual pull stations, and notification appliances with selectable tones and strobe ratings. All cabling specifications call for Category 6A plenum-rated horizontal cables, proper conduit routing in EMT or surface-mount raceway, and compliance with telecommunications bonding standards. The installation requires coordination across multiple building locations (Administration Building, Maintenance Building, PIC/Restroom Building) with seismic restraint provisions, firestop requirements, and adherence to 2024 IBC and IFC codes.

View the file

Other files

Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

C

C

R1

R1

T301

EXISTING TELECOM WALL FIELD.

LEVEL 01

100'-0"

LEVEL 01

100'-0"

FIRST LEVEL

100'-0"

WALL HEIGHT

106'-0"

2" CONDUIT

FIBER PATCH CORD

NETWORK

SWITCH

WAP FOR FIRE

ALARM PANEL

25-PAIR COPPER TO

ADMIN BLDG

COPPER

PROTECTION

MODULE

MODULAR PATCH

PANEL

NETWORK SWITCH

INTRUSION

DETECTION

SYSTEM WITH

WIRELESS

(2) 6-STRAND FIBERS

TO ADMIN BLDG

EXISTING TELECOM

WALL FIELD

FIBER OPTIC

PANEL

TE

SC-GND-2SC-CAB-2

(TYP.)

T301

AC-SCP-1

+84"

SC-TTB

CM-1

01-07

TE

(TYP OF 2)

PW-CPW-1

SC-CT-1

12"x4"

SC-CT-1

SC-LR-1

12"x1 1/2"

SC-LR-1

SC-LR-1

12"x1 1/2"

SC-LR-1

(TYP)

(TYP)

(TYP)

LEVEL 01

100'-0"

LEVEL 02

110'-0"

LEVEL 01

100'-0"

LEVEL 02

110'-0"

FIRST LEVEL

100'-0"

WALL HEIGHT

106'-0"

CEILING HEIGHT

110'-0"

AC-SCP-1

SC-CAB-2

SC-GND-2

SC-LR-1

12"x1 1/2"

SC-LR-1

SC-CT-1

12"x4"

SC-CT-1

SC-TTB

SC-FDC-1 SC-GND-3

SC-HWM-1

SC-MPP-1

GFGI NETWORK SWITCH

SC-HWM-1

SC-UPS

SC-PDU-1

SC-PDU-1

+84"

SC-NS-1

SC-UPS 3

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

NOT SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

DESIGNER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

L0W VOLTAGE/SECURITY:

IMEG

623 26TH AVENUE

ROCK ISLAND, IL 61201

309.781.3770

PETE MCGHEE

IRRIGATION:

AQUA ENGINEERING

300 BOARDWALK DRIVE

UNIT 4B

FORT COLLINS,CO 80525

970.372.6104

JD LEONARD

GEOTECHNICAL:

TERRACON

6460 HILLER STREET

SUITE A

EL PASO, TX 79925

915.778.5233

IVAN AVELAR

FIRE ALARM:

IMEG

623 26TH AVENUE

ROCK ISLAND, IL 61201

309.781.3770

MATT SNYDER

JUNE 15, 2026

A u to d e s k D o c s

/2

.0

V A

N C

A F t B lis s c a m p u s E x p a n s io n /E

T

.0

V

A N

C A

-1

-M

A

IN

T C

.r v t

/1

/2

:5

:2

A

M

T301

TECHNOLOGY ENLARGED PLANS FT BLISS NATIONAL

CEMETERY EXPANSION

5200 FRED WILSON AVE, EL PASO,TX

886CM3026

PETMCG RICWHI

18528

N O R

HT

1/2" = 1'-0"1

EXISTING EQUIPMENT ROOM LAYOUT

1" = 1'-0"2

EXISTING TELECOM WALL FIELD ELEVATION

N O R

HT

1/2" = 1'-0"3

COMMUNICATIONS ROOM EQUIPMENT LAYOUT - TE/2

N O R

HT

1/2" = 1'-0"4

COMMUNICATIONS ROOM PATHWAY LAYOUT - TE/2

1" = 1'-0"5

COMMUNICATIONS ROOM RACK LAYOUT - TE/2

KEYNOTES:

1. SC-GND-3 TO BE MOUNTED ON REAR OF RACK AT TOP RACK MOUNTING LOCATION.

2. RACK SPACE RESERVED FOR FUTURE EQUIPMENT.

3. UPS RESERVED FOR SECURITY NETWORK SWITCH. CONTRACTOR TO SIZE UPS PER SPECIFICATIONS AND PROVIDE

FINAL PRODUCT SELECTION.

4. RACK MOUNT PDU. PDU'S ARE SHOWN IN THE FRONT BUT ARE TO BE INSTALLED ON THE BACK OF THE RACK RAIL.

CONNECT ONE PDU TO WALL POWER OUTLET. CONNECT ONE PDU TO UPS.

KEYNOTES:

1. INSTALL LADDER RACK VERTICALLY ON WALL BETWEEN SC-CAB-2 TO TOP OF SC-CT-1 ABOVE. REFER TO 5/T301 FOR

MORE INFORMATION.

2. INSTALL LADDER RACK VERTICALLY ON WALL FROM BASE OF TTB TO TOP OF SC-CT-1 ABOVE.

3. TWO (2) 2" CONDUITS PENETRATING WALL FROM HANDHOLE OUTSIDE. REFER TO CIVIL DRAWINGS CU102 FOR

CONDUIT CONTINUATION.

KEYNOTES:

1. MOUNT CAMERA TO UNDERSIDE OF CABLE TRAY.

NOTES:

1. REMOVE ALL LOW VOLTAGE CABLING AND DEVICES BACK TO ITS SOURCE AND REMOVE ALL EQUIPMENT.

COORDINATE WITH VA OIT FOR THE REMOVAL OF ALL TELEPHONE AND NETWORK EQUIPMENT PRIOR TO

CABLE REMOVAL.

KEYNOTES:

1. SWITCH LOCATED ON FILE CABINET ON ADJACENT WALL.

2. IDS SYSTEM LOCATED ON ADJACENT WALL.

NOTES:

1. REMOVE ALL LOW VOLTAGE CABLING AND DEVICES BACK TO ITS SOURCE AND REMOVE ALL EQUIPMENT.

COORDINATE WITH VA OIT FOR THE REMOVAL OF ALL TELEPHONE AND NETWORK EQUIPMENT PRIOR TO

CABLE REMOVAL.

Revisions: Date: 144 of 155

BASE BID

CABLE EXTENDS TO THE NEAREST

TELECOMMUNICATIONS ROOM

J-HOOK2

COILED CATEGORY

SLACKLOOP

VELCRO CABLE STRAP4

NOTES:

1. THIS DIAGRAM MAY NOT REPRESENT THE QUANTITY OF CABLES TO EACH

INFORMATION OUTLET JUNCTION BOX. REFER TO THE DRAWINGS AND THE

DATA CONNECTION SCHEDULE FOR ADDITIONAL INFORMATION.

2. ALL DEVICES ARE INSTALLED ABOVE THE CEILING UNLESS OTHERWISE

NOTED.

KEYNOTES:

1. 2-PORT PLENUM RATED SURFACE MOUNTED BOX, SUPPORT FROM J-HOOK.

REFER TO THE DATA CONNECTION SCHEDULE AND TECHNOLOGY EQUIPMENT

SCHEDULE FOR ADDITIONAL INFORMATION.

2. MOUNT A DEDICATED J-HOOK TO THE NEAREST CEILING SUBSTRUCTURE,

COLUMN, JOIST, OR WALL ABOVE THE CEILING AS SHOWN ON THE DRAWINGS.

PROVIDE THE PROPER SUPPORT WHEN HANGING FROM THE CEILING

SUBSTRUCTURE OR COLUMN WALL OR JOIST. REFER TO SPECIFICATION

SECTION 27 05 28 FOR ADDITIONAL REQUIREMENTS.

3. PROVIDE A MINIMUM 15' SLACKLOOP. MAINTAIN THE MANUFACTURERS BEND

RADIUS FOR SLACKLOOP SIZE.

4. PROVIDE AND INSTALL A VELCRO CABLE STRAP ON THE SLACKLOOP

APPROXIMATELY EVERY 6" ALONG THE SLACKLOOP. FOR SLACKLOOPS

GREATER THAN 3' A MINIMUM OF (4) STRAPS WILL BE INSTALLED.

1.97"

W

IDTH

DEPTH

3.94"

118.2"

PART # DEPTH (IN) WIDTH (IN)

CAT 6 4-PAIR

PLENUM (0.35")

CF 105/450 4 18 373

CF 150/450 6 18 536

1.

2.

GENERAL NOTES:

MOUNT AT +96" AFF. UNLESS OTHERWISE SPECIFIED.

REFER TO THE ABOVE TABLE FOR PART NUMBER BASED ON EXPECTED

LOADING.

MOLDED POLYESTER -

FIBERGLASS INSULATOR

TBC AND/OR TBB AND/OR BE AS

APPLICABLE PER LOCATION. REFER

TO TECHNOLOGY BONDING RISER

DIAGRAM AND SPECIFICATION

SECTION 27 05 26.

TWO HOLE

COMPRESSION LUG

NOTES:

1. REFER TO TECHNOLOGY EQUIPMENT SCHEDULE SC-GND-2 FOR

MINIMUM DIMENSION REQUIREMENTS.

2. REFER TO TYPICAL TELECOM ROOM BONDING FLOW DIAGRAM.

COPPER BONDING CONDUCTOR TO

EQUIPMENT RACKS, CABLE TRAYS

& METALLIC SLEEVES. REFER TO

SPECIFICATIONS FOR DETAILS

BARE COPPER GROUND BAR,

INSULATORS, BRACKETS AND

BONDING PROVIDED BY E.C.

REFER TO TECHNOLOGY

EQUIPMENT SCHEDULE SC-GND-2

5/16" Ø

(TYP)

7/16" Ø

(TYP)

LID SHALL BE MARKED

"COMMUNICATIONS"

MOUSE HOLES - (4).

CONDUIT ENTRY PENETRATION NOT TO

EXCEED 25 PERCENT OF SIDE WALL AREA

STAINLESS STEEL HEX

HEAD BOLT W/WASHER

PULL SLOT

SKID RESISTANT SURFACE

EXTENSIONS AS

REQUIRED BY

CONDUIT DEPTH

KNOCKOUTS - (8)

SLOPE GRADE AWAY

FROM COVER 1" IN 3'

GRAVEL DRAINAGE BED MINIMUM 6"

DEPTH. MINIMUM SIZE GRAVEL 1"

NOTES:

1. ALL DIMENSIONS ARE NOMINAL INSIDE CLEARANCES.

2. PROVIDE ALL ACCESSORIES AS NEEDED TO SECURE CABLE TO SIDE WALL.

3. REFER TO CIVIL DRAWINGS CU102 AND CU103 FOR ADDITIONAL INFORMATION ON CONDUIT QUANTITY.

8" E

XTENSIO

N

LOGO

LENGTH

W

IDTH

DEPTH

RACK BONDING CONDUCTOR (6 AWG)

UNIT BONDING CONDUCTOR (6 AWG)

TOP MOUNTED RACK BONDING BUSBAR

SC-GND-3

RACK BONDING

CONDUCTOR

(6 AWG)

IRREVERSIBLE

COMPRESSION

CONNECTIONTELECOMMUNICATION

EQUIPMENT BONDING

CONDUCTOR (6 AWG)

CABLE TRAY BONDING CONDUCTOR

TYPICAL AT EACH SECTION CONNECTION POINT

TO SC-GND-2

IRREVERSIBLE CRIMP

CONNECTOR

TELECOMMUNICATIONS

EQUIPMENT BONDING

CONDUCTOR

INDIVIDUAL BONDING CONDUCTORS

FROM EACH PIECE OF EQUIPMENT

AND RACK TO THE SC-GND-2

BUSBAR (TYP.)

TWO HOLE COMPRESSION LUG

IRREVERSIBLE CRIMP

CONNECTOR

TO SC-GND-2

BASKET TRAY

1.

2.

3.

GENERAL NOTES:

REFER TO 3/T400 BONDING BUS BAR DETAIL FOR ADDITIONAL INFORMATION.

REFER TO 2/T500 TYPICAL TELECOM ROOM BONDING FLOW DIAGRAM FOR ADDITIONAL INFORMATION.

REFER TO T600 FOR TECHNOLOGY EQUIPMENT SCHEDULE.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

NOT SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

DESIGNER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

L0W VOLTAGE/SECURITY:

IMEG

623 26TH AVENUE

ROCK ISLAND, IL 61201

309.781.3770

PETE MCGHEE

IRRIGATION:

AQUA ENGINEERING

300 BOARDWALK DRIVE

UNIT 4B

FORT COLLINS,CO 80525

970.372.6104

JD LEONARD

GEOTECHNICAL:

TERRACON

6460 HILLER STREET

SUITE A

EL PASO, TX 79925

915.778.5233

IVAN AVELAR

FIRE ALARM:

IMEG

623 26TH AVENUE

ROCK ISLAND, IL 61201

309.781.3770

MATT SNYDER

JUNE 15, 2026

A u to d e s k D o c s

/2

.0

V A

N C

A F t B lis s c a m p u s E x p a n s io n /E

T

.0

V

A N

C A

-1

-A

D M

IN

C

.r v t

/1

/2

:4

:2

A

M

T400

TECHNOLOGY DETAILS FT BLISS NATIONAL

CEMETERY EXPANSION

5200 FRED WILSON AVE, EL PASO, TX

886CM3026

PETMCG RICWHI

18528

NO SCALE1

ABOVE CEILING INFORMATION OUTLET MOUNTING DETAIL

NO SCALE2

WIRE BASKET CAPACITY

NO SCALE3

BONDING BUS BAR DETAIL

NO SCALE4

EXTERIOR HAND HOLE DETAIL

NO SCALE5

PATHWAY, RACK, BONDING CONDUCTOR JOIN REQUIREMENT

Revisions: Date: 145 of 155

NYLON BUSHING

J-HOOK

GENERAL NOTES:

1. 1" EMT CONDUIT SHALL STUB UP TO NEAREST ACCESSIBLE CEILING AND TERMINATE ORIENTED

HORIZONTALLY AT THE HEIGHT OF THE ASSOCIATED J-HOOK ROUTE. CONDUIT RUN SHALL NOT

CONTAIN MORE THAN 180 DEGREES OF BEND BETWEEN ACCESSIBLE JUNCTION BOXES OR

BETWEEN JUNCTION BOX AND END OF CONDUIT.

2. WHERE CONDUIT STUB IS LOCATED IN A ROOM WITH AN ACCESSIBLE CEILING AND IS NOT REQUIRED

TO RUN TO CABLE ROUTE LOCATED OUTSIDE THE ROOM, STUB MUST TERMINATE ABOVE THE

ACCESSIBLE CEILING WITH A 90-DEGREE BEND AT THE TOP ORIENTED IN TO THE ROOM AT THE

HEIGHT OF THE ASSOCIATED J-HOOK ROUTE IN THE ROOM.

3. ALL STUBS MUST BE FITTED WITH A NYLON BUSHING ON EACH END OF THE CONDUIT.

4. INSTALLING CONTRACTOR SHALL FURNISH AND INSTALL FIRESTOP MATERIALS FOR TECHNOLOGY

ROUGH-INS PER PROJECT REQUIREMENTS. REFER TO SPECIFICATIONS FOR FIRESTOP

REQUIREMENTS.

KEYNOTES:

1. MOUNT A DEDICATED J-HOOK TO THE NEAREST CEILING SUBSTRUCTURE, COLUMN, JOIST, OR WALL

ABOVE THE CEILING. PROVIDE THE PROPER SUPPORT WHEN HANGING FROM THE CEILING

SUBSTRUCTURE OR COLUMN WALL OR JOIST. REFER TO THE SPECIFICATIONS FOR ADDITIONAL

REQUIREMENTS.

2. MAINTAIN A MINIMUM OF 3' COIL SLACKLOOP.

3. PROVIDE AND INSTALL A VELCRO CABLE STRAP ON THE SLACKLOOP APPROXIMATELY EVERY 6"

ALONG THE SLACKLOOP. FOR SLACKLOOPS GREATER THAN 3' A MINIMUM OF (4) STRAPS WILL BE

INSTALLED.

VELCRO CABLE STRAP

CABLE EXTENDS TO THE NEAREST

TELECOMMUNICATIONS ROOM

COILED CATEGORY

SLACKLOOP

REFER TO ARCHITECTURAL

PLANS FOR WALL CONSTRUCTION

STUD

SINGLE GANG PLASTER RING

TO COME WITHIN 1/8" OF

FINAL SURFACE

NOTES:

1. CONFIGURATIONS SHOWN IN THE DETAIL ABOVE ARE DIAGRAMMATIC, INTENDED TO DESCRIBE THE CONTROLLED SECURITY SCHEME ROUGH-IN REQUIREMENTS OF THE DOORS. DETAILS ABOVE MAY NOT ACCURATELY REPRESENT DOOR SIZE, DOOR SWING, DOOR HARDWARE, OR DOOR FUNCTIONALITY. REFER TO ARCHITECTURAL DOOR HARDWARE SCHEDULE, DOOR HARDWARE GROUPS AND DOOR HARDWARE SPECIFICATIONS

FOR COMPLETE INFORMATION. MIRROR THE DETAIL AS REQUIRED.

2. ROUGH IN SHOWN IN THE DETAIL ABOVE REPRESENTS THE MINIMUM REQUIREMENTS FOR ALL CONTROLLED SECURITY SYSTEM DEVICES AND CABLING UNLESS OTHERWISE NOTED. COORDINATE EXACT REQUIREMENTS WITH SELECTED DOOR MATERIALS, DOOR HARDWARE, AND

CONTROLLED SECURITY DEVICES AND CABLING PRIOR TO INSTALLATION.

3. ALL CABLING IN WALLS AND WHERE EXPOSED ON VERTICAL SURFACES SHALL BE INSTALLED IN EMT CONDUIT OR SURFACE MOUNT RACEWAY.

CABLING ROUTED HORIZONTALLY ABOVE THE ACCESSIBLE CEILING MAY BE INSTALLED FREE-AIR CABLING PROPERLY RATED FOR THE CEILING

ENVIRONMENT.

4. THE ELECTRICAL OR SECURITY CONTRACTOR SHALL NOT MODIFY ANY FIRE RATED DOOR AND/OR DOOR FRAME. REFER TO THE ARCHITECTURAL DOOR SCHEDULE, DOOR HARDWARE SCHEDULE, AND DOOR HARDWARE SPECIFICATION FOR ADDITIONAL INFORMATION. MODIFICATION TO ANY FIRE RATED DOOR AND/OR FRAME WILL REQUIRE A RE-CERTIFICATION OF THE DOOR AND FRAME WITH THE LOCAL AUTHORITY HAVING

JURISDICTION (AHJ).

5. INSTALLING CONTRACTOR SHALL FURNISH AND INSTALL FIRESTOP MATERIALS FOR ALL CONTROLLED SECURITY SCHEME ROUGH-INS PER PROJECT REQUIREMENTS. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.

6. REFER TO THE CONTROLLED SECURITY SCHEME SCHEDULE ON T600 FOR ADDITIONAL INFORMATION.

7. INSTALLATION SHALL INCLUDE ALL POWER REQUIRED FOR SYSTEM OPERATION INCLUDING +120VAC. REFER TO THE SUGGESTED MATRIX OF SCOPE

RESPONSIBILITY FOR ADDITIONAL INFORMATION.

KEYNOTES:

1. PROVIDE JUNCTION BOXES IN THE DOOR FRAME WHERE SHOWN ON THIS DETAIL. ROUGH-IN SHALL BE PROVIDED WHETHER THE CURRENT SECURITY SCHEME UTILIZES THEM OR NOT. ALL CONDUITS SHALL BE EMT CONDUIT UNLESS OTHERWISE NOTED. FLEXIBLE CONDUIT OF ANY TYPE WILL NOT BE ACCEPTED. COORDINATE INSTALLATION WITH ON-SITE DOOR FRAME INSTALLATION CONTRACTOR.

2. ALL DOOR POSITION SWITCHES ARE REQUIRED TO BE RECESSED UNLESS OTHERWISE NOTED. ELECTRIC HINGE MONITORS ARE NOT AN

ACCEPTABLE REPLACEMENT FOR THE RECESSED DOOR POSITION SWITCH.

3. 4" SQUARE BACKBOX WITH SINGLE GANG PLASTER RING. PROVIDE 2 1/2" DEEP MASONRY BOX WHERE APPLICABLE. REFER TO FLOOR PLAN(S) FOR

ACTUAL CREDENTIAL READER TYPE AND ROUGH-IN LOCATIONS.

4. CONDUIT SHALL ROUTE FROM THE CREDENTIAL READER TO THE SECURED SIDE OF THE DOOR. CONDUIT SHALL ROUTE TO THE NEAREST SECURITY

PANEL.

5. MOUNT A MINIMUM 4" SQUARE 2-1/8" DEEP JUNCTION BOX WITH BLANK COVER PLATE ON THE SECURED SIDE OF THE DOOR ABOVE ACCESSIBLE CEILING. INSTALLING CONTRACTOR SHALL SIZE THE JUNCTION BOXES PER SYSTEM INSTALLATION REQUIREMENTS AND APPLICABLE CODES.

MAINTAIN ACCESS TO THE JUNCTION BOX.

6. PROVIDE A HORIZONTALLY MOUNTED SINGLE GANG BACKBOX FOR THE REQUEST TO EXIT SENSOR. REFER TO THE CONTROLLED SECURITY

SCHEME SCHEDULE ON T600 FOR DOORS THAT REQUIRE THIS ROUGH-IN.

7. CONDUIT SHALL ROUTE TO THE NEAREST ACCESSIBLE CEILING. PROVIDE A NYLON BUSHING ON CONDUIT END.

DOOR FRAME ROUGH-IN DIAGRAM

(ALL SINGLE DOORS)

FINISHED ACCESSIBLE

CEILING

1/2" EMT CONDUIT

MINIMUM (TYP.)

FINISHED FLOOR

1" EMT CONDUIT

MINIMUM FOR DOOR

HARDWARE

POWER

SUPPLIES

3/4" EMT CONDUIT

MINIMUM TO ABOVE THE

ACCESSIBLE CEILING

CREDENTIAL READER

ROUGH-IN 3

REQUEST TO

EXIT DEVICE

ROUGH-IN

DOOR CONTACT

ROUGH-IN

4"

NOTES:

1. COORDINATE EXACT LOCATION ON SITE WITH WORK BY OTHER TRADES TO ENSURE

DESIRED VIEWING AREA AND SERVICE ACCESS AFTER COMPLETION OF PROJECT AND

TO MINIMIZE ANY POSSIBLE DAMAGE TO INSTALLED CAMERA OR ASSOCIATED CABLING.

2. PROVIDE CAMERA MOUNTING ACCESSORIES REQUIRED FOR A COMPLETE

INSTALLATION FROM THE SAME MANUFACTURER OF THE CAMERA AND APPROVED BY

THE MANUFACTURER FOR USE WITH THE SPECIFIC MODEL NUMBER OF CAMERA

INSTALLED.

ACCESSIBLE CEILING

CAMERA AS SPECIFIED

PROVIDE CADDY 512 SERIES

T-GRID BRIDGING SUPPORT,

OR APPROVED EQUAL

CAT 6A CABLE

SAFETY TIE WIRE

NOTES:

1. CONFIGURATIONS SHOWN IN THE DETAIL ABOVE ARE DIAGRAMMATIC, INTENDED TO

DESCRIBE THE EXISTING GARAGE DOOR SECURITY SCHEME. DETAILS ABOVE MAY NOT

ACCURATELY REPRESENT DOOR SIZE, DOOR HARDWARE, OR DOOR FUNCTIONALITY.

REFER TO ARCHITECTURAL DOOR HARDWARE SCHEDULE, DOOR HARDWARE GROUPS

AND DOOR HARDWARE SPECIFICATIONS FOR COMPLETE INFORMATION.

KEYNOTES:

1. DEDICATED 1" EMT CONDUIT ROUTED TO NEAREST CABLE TRAY.

2. STANDARD JUNCTION BOX, PROVIDE WITH 90 DEGREE FITTING.

3. PROVIDE TWO (2) 3/4" FLEXIBLE NONMETALLIC CONDUITS FROM JUNCTION BOX TO

DOOR POSITION SWITCH. COORDINATE CONNECTION FITTING AT BASE OF GARAGE

DOOR WITH FINAL APPROVED FROM SYSTEMS MANUFACTURER.

DPO SENSOR

GARAGE DOOR

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

NOT SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

DESIGNER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

L0W VOLTAGE/SECURITY:

IMEG

623 26TH AVENUE

ROCK ISLAND, IL 61201

309.781.3770

PETE MCGHEE

IRRIGATION:

AQUA ENGINEERING

300 BOARDWALK DRIVE

UNIT 4B

FORT COLLINS,CO 80525

970.372.6104

JD LEONARD

GEOTECHNICAL:

TERRACON

6460 HILLER STREET

SUITE A

EL PASO, TX 79925

915.778.5233

IVAN AVELAR

FIRE ALARM:

IMEG

623 26TH AVENUE

ROCK ISLAND, IL 61201

309.781.3770

MATT SNYDER

JUNE 15, 2026

A u to d e s k D o c s

/2

.0

V A

N C

A F t B lis s c a m p u s E x p a n s io n /E

T

.0

V

A N

C A

-1

-A

D M

IN

C

.r v t

/1

/2

:4

:3

A

M

T401

TECHNOLOGY DETAILS FT BLISS NATIONAL

CEMETERY EXPANSION

5200 FRED WILSON AVE, EL PASO, TX

886CM3026

PETMCG RICWHI

18528

NO SCALE1

TECHNOLOGY ROUGH-IN TO J-HOOK DETAIL

NO SCALE2

CONTROLLED SECURITY SCHEME DOOR ROUGH-IN DETAIL

NO SCALE3

ACCESSIBLE CEILING CAMERA MOUNT AND ROUGH-IN DETAIL

NO SCALE4

DOOR SENSOR J-BOX ROUGH-IN DETAIL

Revisions: Date: 146 of 155

SC-GND-2

NEAREST

ELECTRICAL

PANEL

BUILDING

STEEL

ACCESS

CONTROL

EQUIPMENT

METALLIC

CONDUITS AND

SLEEVES

RACK BONDING

BUSBAR (RBB)

LADDER RACK

(CONTINUOUS

BOND)

CABLE TRAY

(CONTINUOUS

BOND)

EQUIPMENT

CABINET

GROUND BAR

SC-GND-2

GROUND BAR SC-GND-2

SC-MPP-1

OWNER

PROVIDED

EQUIPMENT

SC-FDC-1

SC-MPP-1

OWNER

PROVIDED

EQUIPMENT

SC-FDC-1

VS-KVM-1

AC-SMS-1

VS-VMS-1

SC-NS-1

SC-NS-1

TELECOMMUNICATIONS

BONDING JUMPER (TBJ)

TELECOMMUNICATIONS ROOM (TYP) 1

TELECOMMUNICATIONS

BONDING JUMPER (TBJ)

NOTES:

1. THIS FLOW DIAGRAM IS DIAGRAMMATIC AND MAY NOT SHOW ACTUAL ROUTING OR QUANTITIES OF MATERIALS. THIS FLOW DIAGRAM IS SHOWN FOR CLARIFICATION OF CONNECTION LOCATIONS AND CONDUCTOR TYPE. ALL CONNECTIONS AND SYSTEM DEVICES SHOWN ARE TYPICAL AND NOT REPRESENTATIVE OF ACTUAL PROJECT QUANTITIES. REFER TO FLOOR PLANS AND ENLARGED FLOOR PLANS FOR ACTUAL QUANTITIES AND LOCATIONS OF DEVICES AND SPECIFIC ROUTING INFORMATION. REFER TO

SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

2. ALL CONDUCTORS IN THE TECHNOLOGY BONDING SYSTEM MUST BE PLENUM RATED COPPER (GREEN OR MARKED WITH A DISTINCTIVE GREEN COLOR). REFER TO BONDING CONDUCTOR SIZING SCHEDULE FOR SIZING CRITERIA FOR CONDUCTORS.

REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

3. ALL BONDING CONDUCTORS MUST BE CONNECTED BY COMPRESSION LUGS, EXOTHERMIC WELDING, OR IRREVERSIBLE COMPRESSION CONNECTORS. SOLDER IS NOT AN ACCEPTABLE MEANS OF CONNECTION. SHEET METAL SCREWS MUST NOT BE USED TO CONNECT COMMUNICATIONS BONDING CONDUCTORS TO EQUIPMENT. WHERE NECESSARY, REMOVE PAINT AND/OR USE

PAINT-PIERCING WASHERS TO PROVIDE PROPER ELECTRICAL BOND AT ALL CONNECTIONS.

4. REFER TO 3/T400 FOR BONDING BUS BAR DETAIL AND ADDITIONAL INFORMATION AND REQUIREMENTS FOR SC-GND-2.

KEYNOTES:

1. REFER TO TELECOM ROOM REFERENCES SCHEDULE ON THE COVERPAGE T000 FOR TELECOMMUNICATIONS ROOM NUMBER AND

LOCATION INFORMATION.

2. INCLUDES HORIZONTAL AND VERTICAL CONDUIT SLEEVES FOR TECHNOLOGY CABLING.

3. BONDING CONDUCTOR FOR TELECOMMUNICATIONS (BCT), TO ELECTRICAL ENTRANCE INTERSYSTEM BONDING TERMINATION.

REFER TO 3/T500 FOR TELECOMMUNICATIONS BONDING RISER DIAGRAM FOR CONTINUATION AND ADDITIONAL INFORMATION AND

REQUIREMENTS.

4. TELECOMMUNICATIONS BONDING BACKBONE (TBB) TO EXISTING GROUND BAR. REFER TO 3/T500 FOR TELECOMMUNICATIONS BONDING RISER DIAGRAM FOR CONTINUATION AND ADDITIONAL INFORMATION AND REQUIREMENTS.

5. REFER TO THE ELECTRICAL DRAWINGS FOR LOCATION.

6. PROVIDE SC-GND-3 RACK MOUNT TELECOMMUNICATIONS BONDING BUSBAR AT EACH EQUIPMENT RACK AND CABINET.

TELECOMMUNICATIONS

BONDING JUMPER (TBJ)

PRIMARY/SECONDARY

BONDING BUSBAR

(PBB/SBB)

CONDUCTOR

LENGTH IN FEET

BONDING CONDUCTOR SIZING SCHEDULE

MINIMUM ACCEPTABLE

SIZE - AWG

LESS THAN 13' 6

14' - 20' 4

21' - 26' 3

27' - 33' 2

34' - 41' 1

42' - 52' 1/0

53' - 66' 2/0

NOTES:

1. THIS RISER IS DIAGRAMMATIC AND MAY NOT SHOW ACTUAL ROUTING OR QUANTITIES OF

MATERIALS. THIS RISER IS SHOWN FOR CLARIFICATION OF CONNECTION LOCATIONS AND

CONDUCTOR TYPE. ALL CONNECTIONS AND SYSTEM DEVICES SHOWN ARE TYPICAL AND

NOT REPRESENTATIVE OF ACTUAL PROJECT QUANTITIES. REFER TO FLOOR PLANS AND

ENLARGED FLOOR PLANS FOR ACTUAL QUANTITIES AND LOCATIONS OF DEVICES AND

MORE SPECIFIC ROUTING INFORMATION. REFER TO SPECIFICATIONS FOR ADDITIONAL

REQUIREMENTS.

2. ALL CONDUCTORS IN THE TECHNOLOGY BONDING SYSTEM SHALL BE MINIMUM SIZE OF

3/0 AWG PLENUM RATED COPPER (GREEN OR MARKED WITH A DISTINCTIVE GREEN

COLOR) UNLESS CONDUCTOR LENGTH IS LESS THAN 66 FEET. REFER TO BONDING

CONDUCTOR SIZING SCHEDULE FOR SIZING CRITERIA FOR CONDUCTORS LESS THAN 66

FEET IN LENGTH. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

3. ALL BONDING CONDUCTORS AND BONDING JUMPERS SHALL BE CONNECTED BY

COMPRESSION LUGS, EXOTHERMIC WELDING, OR IRREVERSIBLE COMPRESSION

CONNECTORS. SOLDER IS NOT AN ACCEPTABLE MEANS OF CONNECTION. SHEET METAL

SCREWS SHALL NOT BE USED TO CONNECT COMMUNICATIONS BONDING CONDUCTORS

TO EQUIPMENT. WHERE NECESSARY, REMOVE PAINT AND/OR USE PAINT-PIERCING

WASHERS TO PROVIDE PROPER ELECTRICAL BOND AT ALL CONNECTIONS.

4. REFER TO 2/T500 FOR TYPICAL TELECOM ROOM BONDING FLOW DIAGRAM.

5. REFER TO TELECOM ROOM REFERENCES SCHEDULE ON THE COVERSHEET T000 FOR

TELECOMMUNICATIONS ROOM NUMBER AND LOCATION INFORMATION.

KEYNOTES:

1. BONDING CONDUCTOR FOR TELECOMMUNICATIONS (BCT). BCT SHALL BE THE SAME SIZE

AS THE TBB OR LARGER. REFER TO BONDING CONDUCTOR SIZING SCHEDULE FOR

SIZING REQUIREMENTS.

BASEMENT

ELECTRICAL ENTRANCE

INTERSYSTEM BONDING

TERMINATION

GROUNDING ELECTRODE

CONDUCTOR BY OTHERS

ELECTRICAL GROUNDING

ELECTRODE SYSTEM

GREATER THAN 301' 750 kcmil

FIRST

FLOOR

EXISTING

STORAGE/ELEC/OIT

ADMINISTRATION BUILDING

FIRST

FLOOR

ELECTRICAL ENTRANCE

INTERSYSTEM BONDING

TERMINATION

GROUNDING ELECTRODE

CONDUCTOR BY OTHERS

ELECTRICAL GROUNDING

ELECTRODE SYSTEM

MAINTENANCE BUILDING

(PBB)

TE/1

(SBB)

EXISTING OFFICE/ELEC

TELECOMMUNICATIONS

BONDING BACKBONE

(TBB) (TYP)

TELECOMMUNICATIONS

BONDING BACKBONE

(TBB) (TYP)

(TBB) (SBB)

TE/2

EXISTING BONDING

BUS BAR

EXISTING BONDING

BUS BAR

MAINTENANCE BUILDINGADMINISTRATION BUILDING

NOTES:

1. THIS RISER IS DIAGRAMMATIC AND MAY NOT SHOW ACTUAL ROUTING OR QUANTITIES OF MATERIALS SHOWN.

THIS RISER IS SHOWN FOR CLARIFICATION OF CONNECTION(S), LOCATIONS AND CABLE TYPE. ALL INFORMATION OUTLETS ARE TYPICAL OF THE OUTLETS IN THE AREA SHOWN. REFER TO FLOOR PLANS FOR MORE SPECIFIC

ROUTING INFORMATION. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

2. REFER TO FLOOR PLANS FOR QUANTITY OF CABLES AND JACKS TO BE INSTALLED AT EACH INFORMATION

OUTLET.

KEYNOTES:

1. CATEGORY 6A PLENUM RATED HORIZONTAL CABLE. REFER TO THE SPECIFICATIONS FOR ADDITIONAL

INFORMATION.

2. REFER TO THE INFORMATION OUTLET SCHEDULE ON T600 AND THE FLOOR PLANS FOR THE QUANTITY OF

CABLES AND JACKS TO BE INSTALLED AT EACH LOCATION.

3. CONTRACTOR PROVIDED GOVERNMENT INSTALLED PATCH CABLE. REFER TO SPECIFICATIONS.

4. CONTRACTOR PROVIDED AND INSTALLED PATCH CABLE. REFER TO SPECIFICATIONS.

5. 24-STRAND SINGLE MODE OPTICAL FIBER WITH LC CONNECTORS. EXTEND FIBER TO NEW

TELECOMMUNICATIONS ROOM TE/2 IN THE MAINTENANCE BUILDING AND TERMINATE ON NEW OPTICAL FIBER PANEL SC-FDC-1. COORDINATE FINAL LOCATION WITH OWNER PRIOR TO CABLE INSTALLATION.

6. HDMI CABLE.

7. CONTRACTOR PROVIDED AND INSTALLED PATCH CORD TO SUPPORT VIDEO SURVEILLANCE CAMERAS.

8. RACK OR CABINET AS DEFINED ON THE TELECOM ROOM LAYOUT. REFER TO THE TELECOM ROOM REFERENCES

MATRIX ON THE COVERPAGE FOR LOCATION.

9. REFER TO COVERPAGE AND FLOOR PLANS FOR TELECOMMUNICATIONS ROOM LOCATIONS.

10. INCOMING FIBER OPTIC CABLE FROM SERVICE PROVIDER EQUIPMENT IN BASEMENT.

11. REFER TO PIC BUILDING FLOOR PLANS FOR MORE INFORMATION.

12. INSTALL NEW NETWORK SWITCH (SC-NS-1) TO SUPPORT A NEW DEDICATED SECURITY NETWORK. CONNECT

VIDEO SURVEILLANCE AND ACCESS CONTROL SERVERS TO SECURITY NETWORK. INCLUDE IN BID ALL PROGRAMMING NECESSARY TO INSTALL AND CONFIGURE SECURITY NETWORK. TEST ALL DEVICES IN BOTH

BULDINGS TO ENSURE DEVICES ARE CONNECTED.

C#

C#

C#

C#

9 9

C#

PIC BUILDING 11

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

NOT SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

DESIGNER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

L0W VOLTAGE/SECURITY:

IMEG

623 26TH AVENUE

ROCK ISLAND, IL 61201

309.781.3770

PETE MCGHEE

IRRIGATION:

AQUA ENGINEERING

300 BOARDWALK DRIVE

UNIT 4B

FORT COLLINS,CO 80525

970.372.6104

JD LEONARD

GEOTECHNICAL:

TERRACON

6460 HILLER STREET

SUITE A

EL PASO, TX 79925

915.778.5233

IVAN AVELAR

FIRE ALARM:

IMEG

623 26TH AVENUE

ROCK ISLAND, IL 61201

309.781.3770

MATT SNYDER

JUNE 15, 2026

A u to d e s k D o c s

/2

.0

V A

N C

A F t B lis s c a m p u s E x p a n s io n /E

T

.0

V

A N

C A

-1

-A

D M

IN

C

.r v t

/1

/2

:4

:3

A

M

T500

TECHNOLOGY DIAGRAMS FT BLISS NATIONAL

CEMETERY EXPANSION

5200 FRED WILSON AVE, EL PASO, TX

886CM3026

PETMCG RICWHI

18528

NO SCALE2

TYPICAL TELECOM ROOM BONDING FLOW DIAGRAM

NO SCALE3

TECHNOLOGY BONDING RISER DIAGRAM - ADMIN/MAINT

NO SCALE1

FIBER AND COPPER CONNECTIVITY DIAGRAM

Revisions: Date: 147 of 155

AC-SCP-1

SC-MPP-1

ID-ICP-1

K1

M

AC-SMS-1

G

GB

DOOR HARDWARE

ADMINISTRATION BUILDING - TE/1

WALL MOUNTED

EQUIPMENT

EQUIPMENT RACK

1.

2.

3.

4.

5.

6.

7.

NOTES:

THIS RISER IS A DIAGRAMMATIC ND MAY NOT SHOW ACTUAL ROUTING OR QUANTITIES OF MATERIAL SHOWN. THIS RISER IS SHOWN FOR CLARIFICATION OF CONNECTION(S), LOCATIONS, AND CABLE TYPE. ALL INFORMATION OUTLETS ARE TYPICAL OF THE OUTLETS IN THE AREA SHOWN. REFER TO THE FLOOR PLANS FOR MORE SPECIFIC ROUTING

INFORMATION. REFER TO THE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

THIS INTEGRATED SYSTEM INCLUDES DEVICES FOR AN INTRUSION DETECTION SYSTEM AND AN ACCESS CONTROL SYSTEM. REFER TO THE SPECIFICATIONS FOR ADDITIONAL

INFORMATION .

ALL CABLING LISTED HERE ARE MINIMUM REQUIREMENTS. FINAL GAUGE AND QUANTITY IS BASED ON THE DISTANCE FROM THE NEAREST CONTROL PANEL AND THE NUMBER OF DOORS AT EACH LOCATION. CREDENTIAL READERS WILL OPEN A SINGLE DOOR WITH THE SECOND DOOR BEING MONITORED BY THE SYSTEM.

ALL ACCESS CONTROL EQUIPMENT AND DOOR HARDWARE WILL REQUIRE TO BE ON A MINIMUM OF 8 HOURS OF BATTERY TIME IN THE EVENT OF A POWER FAILURE. THIS INCLUDES ALL OF THE INPUT/OUTPUT CARDS, DOOR CONTROLLERS, ENDPOINTS (SUCH AS CARD READERS, MOTION DETECTIONS, AND DOOR POSITIONS SWITCHES), DOOR POWER SUPPLIES AND ALL OTHER DEVICES REQUIRED TO SUPPORT THE SYSTEM FUNCTIONALITY. REFER TO THE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

ALL DOORS REQUIRE ROUGH-IN AT ALL LOCATIONS. REFER TO 2/T401 FOR ROUGH-IN REQUIREMENTS.

THIS SYSTEM INCLUDES A SINGLE SYSTEM THAT IS CAPABLE OF PROVIDING CARD ACCESS AND INTRUSION DETECTION. COORDINATE WITH THE GOVERNMENT FOR PROGRAMMING REQUIREMENTS TO DISABLE THE ALARM SYSTEM. THE ALARM SYSTEM WILL BE DISABLED VIA A DEDICATED KEYPAD AND THE KEYPAD ON NAY CREDENTIAL

READER.

PROVIDE AND INSTALL SOFTWARE ON A NEW CONTRACTOR PROVIDED AND INSTALLED PC FOR AN ENROLLMENT STATION. REFER TO THE SPECIFICATIONS FOR ADDITIONAL INFORMATION AND REQUIREMENTS. REFER TO THE DRAWINGS FOR QUANTITY OF DOORS AND PROVIDE ONE CONNECTION FOR EACH LEAF DOOR.

REQUEST TO

EXIT

ELECTRONIC

LOCKING

HARDWARE

DOOR

POSITION

SWITCH

AC-R1-W

A

SC-NS-1

AC-ENROLL-1

DESK

KEYNOTES:

1. 18 AWG 2-CONDUCTOR UNSHIELDED CABLE TIED INTO THE DOOR POSITION SWITCH FOR ALL DOORS.

2. TYPICAL OF ALL DOORS AS SHOWN ON THE DRAWINGS. REFER TO THE CONTROLLED SECURITY SCHEME (CSS) TYPE SCHEDULE ON T600 AND SPECIFICATIONS FOR QUANTITY OF

DEVICES AT EACH LOCATION.

3. A MINIMUM OF 18 AWG 4-CONDUCTOR, UNSHIELDED CABLE. 2 CONDUCTORS WILL CONNECT TO THE ACCESS CONTROL SYSTEM AND THE REMAINING 2 CONDUCTORS WILL

CONNECT TO THE INTRUSION DETECTION SYSTEM. REFER TO THE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

4. A MINIMUM OF 18 AWG 4-CONDUCTOR, UNSHIELDED CABLE. REFER TO THE SPECIFICATIONS FOR ADDITIONAL INFORMATION

5. A MINIMUM OF 18 AWG 6-CONDUCTOR, UNSHIELDED CABLE. REFER TO THE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

6. CATEGORY 6 PATCH CABLE FROM THE ACCESS CONTROL SYSTEM TO THE SECURITY NETWORK. PATCH PANEL INSTALLED IN THE NEAREST TELECOM ROOM. REFER TO

TELECOM ROOM LAYOUTS ON 5/T300 AND 5/T301 FOR ADDITIONAL INFORMATION. REFER TO THE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

7. NETWORK SWITCH SHARED WITH THE VIDEO SURVEILLANCE SYSTEM.

8. CATEGORY 6 PATCH CORD, REFER TO THE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

9. THE SECURITY MANAGEMENT SERVER WILL BE INSTALLED IN TELECOM 1-G (TR-1). COORDINATE FOR CONNECTION AND INSTALLATION REQUIREMENTS.

10. PROVIDED AND INSTALLED BY THE DOOR HARDWARE CONTRACTOR.

11. DOOR POSITION SWITCH WILL CONNECT TO BOTH THE ACCESS CONTROL AND INTRUSION DETECTION SYSTEM. REFER TO FLOOR PLANS AND SITE PLANS FOR ADDITIONAL

INFORMATION.

12. ADD ALL ADDITIONAL EXPANSION MODULES REQUIRED TO EXPAND THE INTRUSION DETECTION SYSTEM TO EACH BUILDING. THE ADMINISTRATION BUILDING WILL BE THE MAIN

INTRUSION PANEL. EXPANSION CAN UTILIZE THE COPPER AND FIBER BACKBONE. REFER TO THE SPECIFICATIONS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.

13. COORDINATE WITH THE COR ON THE CONNECTION TO THE MONITORING SERVICE. PROVIDE ALL REQUIRED DEVICES TO NOTIFY THE MONITORING SERVICE PER THE MONITORING

SERVICE REQUIREMENTS.

14. REFER TO THE FLOOR PLANS FOR CREDENTIAL READER TYPE AND LOCATIONS.

15. COORDINATE WITH THE CONTRACTOR FOR THE LOCATION OF THE ENROLLMENT STATION.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

NOT SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

DESIGNER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

L0W VOLTAGE/SECURITY:

IMEG

623 26TH AVENUE

ROCK ISLAND, IL 61201

309.781.3770

PETE MCGHEE

IRRIGATION:

AQUA ENGINEERING

300 BOARDWALK DRIVE

UNIT 4B

FORT COLLINS,CO 80525

970.372.6104

JD LEONARD

GEOTECHNICAL:

TERRACON

6460 HILLER STREET

SUITE A

EL PASO, TX 79925

915.778.5233

IVAN AVELAR

FIRE ALARM:

IMEG

623 26TH AVENUE

ROCK ISLAND, IL 61201

309.781.3770

MATT SNYDER

JUNE 15, 2026

A u to d e s k D o c s

/2

.0

V A

N C

A F t B lis s c a m p u s E x p a n s io n /E

T

.0

V

A N

C A

-1

-A

D M

IN

C

.r v t

/1

/2

:4

:3

A

M

T501

TECHNOLOGY DIAGRAMS FT BLISS NATIONAL

CEMETERY EXPANSION

5200 FRED WILSON AVE, EL PASO, TX

886CM3026

PETMCG RICWHI

18528

NO SCALE1

ACCESS CONTROL & INTRUSION DETECTION CONNECTIVITY DIAGRAM

Revisions: Date: 148 of 155

2-Port Faceplate

IDENTIFICATION

IDENTIFICATION

IDENTIFICATION

IDENTIFICATION

1 2

4-Port Faceplate

PAIR 3

PAIR 1PAIR 2 PAIR 4

WO WGO BL WBL G WBR BR

1 32 4 5 6 7 8

ANSI/TIA/EIA T568B

PIN/PAIR ASSIGNMENT

REFER TO SPECIFICATIONS FOR

IDENTIFICATION REQUIREMENTS (TYP.)

NUMBER INDICATES

FACEPLATE POSITION (TYP.)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

NOT SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

DESIGNER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

L0W VOLTAGE/SECURITY:

IMEG

623 26TH AVENUE

ROCK ISLAND, IL 61201

309.781.3770

PETE MCGHEE

IRRIGATION:

AQUA ENGINEERING

300 BOARDWALK DRIVE

UNIT 4B

FORT COLLINS,CO 80525

970.372.6104

JD LEONARD

GEOTECHNICAL:

TERRACON

6460 HILLER STREET

SUITE A

EL PASO, TX 79925

915.778.5233

IVAN AVELAR

FIRE ALARM:

IMEG

623 26TH AVENUE

ROCK ISLAND, IL 61201

309.781.3770

MATT SNYDER

JUNE 15, 2026

A u to d e s k D o c s

/2

.0

V A

N C

A F t B lis s c a m p u s E x p a n s io n /E

T

.0

V

A N

C A

-1

-A

D M

IN

C

.r v t

/1

/2

:4

:3

A

M

T600

TECHNOLOGY SCHEDULES FT BLISS NATIONAL

CEMETERY EXPANSION

5200 FRED WILSON AVE, EL PASO, TX

886CM3026

PETMCG RICWHI

18528

THE EQUIPMENT LIST ABBREVIATIONS AND THE TECHNOLOGY EQUIPMENT SCHEDULE ARE FOR THE CONVENIENCE OF THE CONTRACTOR. EACH CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF QUANTITIES AND SHALL FURNISH ALL MATERIAL REQUIRED, WHETHER SPECIFIED OR NOT, TO PRODUCE A SATISFACTORY WORKING

SYSTEM.

CATALOG NUMBERS ARE NOT TO BE CONSIDERED COMPLETE BUT ARE GIVEN ONLY TO AID THE CONTRACTOR IN THE SEARCH FOR MATERIAL. NO MATERIAL SHALL BE ORDERED BY MANUFACTURER AND CATALOG NUMBER ONLY. EACH CONTRACTOR SHALL FIRST READ THE COMPLETE DESCRIPTION OF THE MATERIAL ON THESE DRAWINGS AND SPECIFICATIONS. MANUFACTURER PROVIDED SHALL BE CONSISTENT WITH APPROVED MANUFACTURERS LISTED. "STANDARD COLOR" INDICATES FACTORY FINISH AVAILABLE AT NO ADDITIONAL CHARGE. ALL EQUIPMENT MUST MEET BUY AMERICAN REQUIREMENTS.

TECHNOLOGY EQUIPMENT SCHEDULE

EQUIPMENT LIST

ABBREVIATION EQUIPMENT LIST DESCRIPTION

MANUFACTURER AND

MODEL

AC-ENROLL-1 USB DESKTOP SMART CARD READER FOR ENROLLMENT AND CREDENTIAL MANAGEMENT APPLICATIONS. READER SHALL SUPPORT ISO 7816, USB CCID, PS/SC, AND HBCI STANDARDS, AND SHALL BE COMPATIBLE WITH CONTACT SMART CARD OPERATIONS INCLUDING SINGLE SIGN-ON, ONLINE BANKING, AND DIGITAL SIGNATURE APPLICATIONS. PROVIDE NATIVE CCID DRIVER SUPPORT FOR EASY INSTALLATION WITHOUT ADDITIONAL DRIVERS. READER SHALL INCLUDE DUAL-COLOR LED STATUS INDICATOR, USB 2.0 FULL SPEED INTERFACE, USB TYPE A CONNECTOR, AND 59.1" CABLE. HOUSING SHALL BE

ROBUST ABS PLASTIC. DIMENSIONS: 3.15"W X 2.64"D X 1.1"H.

REFER TO SPECIFICATION SECTION 28 13 00 FOR ADDITIONAL INFORMATION.

HID

R31210320-01

AC-R1-W KEYPAD CARD READER. PROVIDED AS INTEGRAL PART OF SECURITY MANAGEMENT SYSTEM. REFER TO CONTROLLED SECURITY SCHEME (CSS) TYPE SCHEDULE ON T600 FOR ADDITIONAL INFORMATION. CARD READERS SHOWN ON PLANS TO IDENTIFY INTENDED MOUNTING LOCATION. REFER TO THE SPECIFICATIONS FOR COMPLETE INFORMATION.

HID

SIGNO40K SERIES

AC-SCP-1 SECURITY MANAGEMENT SYSTEM CONTROLLER, FOR USE WITH INTEGRATED SECURITY MANAGEMENT SYSTEM, REFER TO

SPECIFICATION SECTION 28 13 00 FOR COMPLETE INFORMATION.

HOFFMAN

AC-SMS-1 ELECTRONIC ACCESS CONTROL SERVER.

REFER TO THE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

HONEYWELL

PRO-WATCH

ID-AL1-W WALL MOUNTED AUDIBLE SIREN TO NOTIFY OF A BREACH.

INSTALL DEVICE IN A 4" SQUARE BACKBOX WITH SINGLE GANG PLASTER RING. INSTALL 1" EMT CONDUIT TO THE NEAREST

SUPPORTING SECURITY PANEL.

WBOX

OE-1GANGSIRN

ID-GB1-C GLASS BREAK SENSOR, SURFACE MOUNT, CEILING, TAMPER RESISTANT.

WEIGHT: 4.5 OZ. DIMENSIONS: 4.25"D X 0.875" H. POWER: 6-18 VDC, 12mA TYPICAL AT 12VDC. ALARM RELAY: FORM C, 125mA MAX, 25VDC MAX. RANGE: 25' RADIUS. PROVIDE 18/4 AWG TO THE SECURITY PANEL. FIELD VERIFY LOCATION. PROVIDE ONE

(1) 711S ADDRESSABLE MODULE FOR EACH LOCATION.

HONEYWELL

FG-1625RT

ID-K1-W INTRUSION ALARM KEYPAD. ILLUMINATED 4-LINE DISPLAY LCD SHOWS ZONE INFORMATION. ECP BUS COMPATIBLE.

INSTALL KEYPAD IN A 4" SQUARE BACKBOX WITH A SINGLE GANG PLASTER RING WITH (1) 1" CONDUIT TO ABOVE

ACCESSIBLE CEILING.

REFER TO CONTROLLED SECURITY SCHEME DOOR ROUGH-IN DETAIL FOR MORE INFORMATION.

HONEYWELL

VISTA 6160

ID-MD1-W INTRUSTION DETECTION MOTION DETECTION SENSOR, WALL OR CEILING MOUNTABLE. DIMENSIONS: 3.5" X 5.25" (HEIGHT X DIAMETER). REQUIRES INPUT POWER: 6-15VDC, 8mA STANDBY, 60mA IN ALARM WITH LEDs ENABLED. DEVICE COMPLIES

WITH PART 15 OF THE FCC RULES.

FOR CEILING MOUNTED APPLICATIONS, PROVIDE WITH UNIVERSAL CEILING-MOUNT BRACKET.

BOSCH

SENSOR:

ISC-CDL1-WA15G

MOUNT:

B338

PA-J-4 JUNCTION BOX 12" X 12" HOFFMAN

ASE12X12X4NK

PW-CPW-1 4" X 4" FIREPROOF CABLE PATHWAY FOR WALLS UP TO 10" THICK STI

44 SERIES

PW-HH-1 HANDHOLE COMPOSITE POLYMER CONCRETE BODY AND COVER. STAINLESS STEEL HARDWARE BOLTED NON-SKID COVER RATED FOR 15,000LB. DESIGN LOAD OCCASIONAL NON-DELIBERATE VEHICULAR TRAFFIC. UNITS IN LANDSCAPED AREAS

SHALL BE GREEN IN COLOR. “COMMUNICATIONS” LOGO ON HANHOLE COVER.

PROVIDE UNITS/EXTENSIONS AS REQUIRED BY CONDUIT DEPTH. CONTRACTOR SHALL FIELD VERIFY QUANTITY AND

LOCATIONS. REFER TO DETAIL 4/T400 FOR ADDITIONAL INFORMATION.

HUBBELL/QUAZITE

PG2424BB24

PG2424HA00

CARSON INDUSTRIES

ARMORCAST

HIGHLINE PRODUCTS

SYNERTECH

SC-CAB-1 WALL MOUNTED ENCLOSED CABINET. DIMENSIONS: 48"H X 24"W X 30"D, (26RU) PROVIDES 26 1.75" MOUNTING SPACES.

THREE-PART SWING-OUT DESIGN. LOCKABLE. SOLID METAL DOOR. REAR PANEL INCLUDES 1" AND 3" KNOCKOUTS. UL

LISTED. 19" PANEL MOUNTING. 300LB LOAD CAPACITY.

CHATSWORTH

CUBE-IT

11996-X48

SC-CAB-2 WALL MOUNTED ENCLOSED CABINET. DIMENSIONS: 36"H X 24"W X 30"D, PROVIDES 19 1.75" MOUNTING SPACES.

THREE-PART SWING-OUT DESIGN. LOCKABLE. SOLID METAL DOOR. REAR PANEL INCLUDES 1" AND 3" KNOCKOUTS. UL

LISTED. 19" PANEL MOUNTING. 300LB LOAD CAPACITY.

CHATSWORTH

CUBE-IT

11996-X36

SC-CT-1 CABLE TRAY, WIRE MESH TYPE, 12" LOADING DEPTH, 4" WIDTH, COMPLETE WITH ALL FITTINGS AND MOUNTING HARDWARE.

PROVIDE TRAPEZE SUPPORT WITH PLASTIC RETAINER. CUTTING OF THE MESH CABLE TRAY SHALL BE DONE WITH OFFSET BOLT CUTTERS ONLY. 10' MAXIMUM SUPPORT SPAN. EITHER SPLICE WASHERS OR TERMINAL GROUND SUPPORT AND JUMPER WIRE SHALL BE USED TO ATTAIN GROUNDING CONTINUITY THROUGHOUT. Z-BRACKETS SHALL BE USED FOR WALL MOUNTED APPLICATIONS. REFER TO MANUFACTURERS INSTALLATION INSTRUCTIONS AND SPECIFICATION SECTION 27 05 36 FOR ADDITIONAL INFORMATION. REVER TO 5/T400 FOR PATHWAY, RACK, AND BONDING CONDUCTOR JOIN

REQUIREMENTS. REFER TO 2/T400 FOR EXPECTED CABLE TRAY LOADING CAPACITY.

WBT

WBT12X4

CABOLFIL

B-LINE

CHATSWORTH

SC-FDC-1 1-RU ANGLED FIBER DISTRIBUTION ENCLOSURE. 144 MAXIMUM FIBERS WITH SLIDING TRAY. PROVIDE COMPLETE WITH FIBER ADAPTER PANELS WITH LC CONNECTORS FOR ALL TERMINATED FIBERS. PROVIDE BLANK PANELS FOR ALL UNUSED

OPENINGS. PROVIDE CABLE CLAMP KITS AS REQUIRED, 5RCMP-KIT.

LEVITON

HDX1A-144

FIBER ADAPTER PANELS

SPLCH-12A (OM4)

SPLCH-12L (SM)

CABLE MANAGER:

E2XHD-CMB

BLANKS:

5F100-PLT

SC-GND-2 GROUNDING BUSBAR, WALL MOUNT. 4" H X 12" L X 1/4" D COPPER, ELECTRICALLY ISOLATED BY INSULATORS INTEGRAL TO MOUNTING BRACKETS. COPPER GROUND BAR IS 1/4" THICK AND STAND OFF 2.75" FROM WALL. THE 12" BUSBAR PROVIDES CONNECTION FOR EIGHTEEN (18) 2-HOLE COMPRESSION LUGS RESPECTIVELY WITH 5/8" OR 1" CENTERS. ANSI/TIA-607 AND

BICSI COMPLIANT. UL LISTED.

REFER TO GROUND BAR DETAIL ON 4/T400 AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.

CHATSWORTH

40158-012

PANDUIT

ERICO

HARGER

SC-GND-3 19" RACK-MOUNT HORIZONTAL GROUND BAR. 1/4"H X 19"L X 3/4"D. SOLID COPPER, ELECTRICALLY ISOLATED BY INSULATORS

INTEGRAL TO STAINLESS STEEL MOUNTING BRACKETS.

PROVIDE UNIT CONFIGURED WITH 15 SETS OF 5/16" HOLES SPACED 5/8" ON CENTER TO ACCOMMODATE "A" SPACED TWO-HOLE COMPRESSION LUGS AND 3 SETS OF 7/16" HOLES SPACED 1" ON CENTER TO ACCOMMODATE "C" SPACED

TWO-HOLE COMPRESSION LUGS. ANSI/EIA/TIA-607 AND BICSI COMPLIANT. UL LISTED.

REFER TO THE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

HUBBELL

HBBBHR19

BERK-TEK ORTRONICS

SYSTIMAX

SC-HWM-1 1RU HORIZONTAL CABLE MANAGER FOR 19' RACK MOUNTING, SINGLE SIDED, BLACK. FRONT COVER WITH HINGE CLIPS.

8.31" DEEP.

ORTRONICS

SHMC1RU

SC-HWM-2 2RU HORIZONTAL CABLE MANAGER FOR 19' RACK MOUNTING, SINGLE SIDED, BLACK. FRONT COVER WITH HINGE CLIPS.

8.86" DEEP.

ORTRONICS

SHMC2RU

SC-IO-C INFORMATION OUTLET, CEILING MOUNT. 2-PORT COVERPLATE AS INDICATED ON DRAWINGS AND INFORMATION

OUTLET SCHEDULE. REFER TO INFORMATION OUTLETSCHEDULE FOR PIN CONFIGURATION.

" # " INDICATES INFORMATION OUTLET FACEPLATE CONFIGURATION AS INDICATED ON THE PLANS.

PROVIDE REMOVABLE BLANK INSERTS ON ALL UNSUSED PORTS. CABLING IS INSTALLED IN A SURFACE-MOUNT RACEWAY BOX WITH DUST COVER JACKS. COIL THE SLACK LOOP ON A J-HOOK LOCATED ON THE NEAREST STRUCTURAL ELEMENT IN

THE AREAS SHOWN ON THE DRAWINGS.

PANDUIT

BOX:

MINI-COM SERIES

JACK:

6AUJK-**6

SC-IO-W INFORMATION OUTLET, WALL MOUNT. 2, 4-PORT COVERPLATE AS INDICATED ON DRAWINGS AND INFORMATION OUTLET

SCHEDULE. REFER TO INFORMATION OUTLET SCHEDULE FOR PIN CONFIGURATION.

" # "INDICATES INFORMATION OUTLET FACEPLATE CONFIGURATION AS INDICATED ON THE DRAWINGS.

INSTALL INFORMATION OUTLET IN A 4" SQUARE BACKBOX WITH A SINGLE GANG PLASTER RING. INSTALL A 1" EMT CONDUIT TO NEAREST ACCESSIBLE CEILING OR UNLESS OTHERWISE NOTED. PROVIDE REMOVABLE BLANK INSERTS FOR UNUSED PORTS AND FIRE RATED PUTTY PAD IN FIRE RATED WALLS. REFER TO THE TECHNOLOGY ROUGH-IN TO J-HOOK DETAIL AND

THE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

LEVITON

WALLPLATE:

41081-4WP

JACK (CAT-6A):

6AUJK-**

BLANK INSERT:

41804-**

SC-LR-1 LADDER RACK, (12"W X 1.5"H X 9.71'L) TUBULAR STEEL CONSTRUCTION. RUST RESISTANT ENAMEL FINISH. REMOVE SHARP BURRS FROM LADDER RACK AND REPAINT ALL AREAS THAT HAVE BEEN FIELD MODIFIED, CUT, OR EXPOSED. UL LISTED.

PROVIDE WITH ALL NECESSARY MOUNTING BRACKETS, RACK ELEVATION KITS, AND (2) CABLE RADIUS DROPS PER RACK.

LADDER RACK ONLY FOR VERTICAL CABLE MANAGEMENT.

CHATSWORTH

LADDER RACK:

11275-712

RACK ELEVATION KIT:

10506-706

CABLE RADIUS DROP:

12100-712

SC-MPP-1 MODULAR PATCH PANEL, 48 MODULAR RJ-45 TERMINATIONS, MOUNTS DIRECTLY TO EIA/TIA STANDARD 19" RELAY RACK, PORT IDENTIFICATION NUMBERS, PROVIDED WITH COLOR CODING AND LABEL HOLDER KITS, U.L. LISTED. REQUIRES (1)

1.75" MOUNTING SPACES.

LEVITON

PANEL:

49255-Q48

JACK (CAT-6A):

6AUJK-**6

SC-NS-1 8-PORT LAYER 2/3/4 10/100/1000 GIGABIT SWITCH - POE. 48 RJ-45 CONNECTORS FOR 10BASE - T/100BASE-TX/1000 BASE-T WITH 4 GIGABIT COMBO PORTS SHARED BETWEEN MINI-GBIC PORTS: CONSOLE PORT: AUTO MEDIUM DEPENDENT

INTERFACE (MDI) AND MDI CROSSOVER (MDI-X). AUTO.

CISCO

5500 SERIES

SC-PDU-1 MODULAR POWER DISTRIBUTION SYSTEM, RACK MOUNT, 1RU. INPUT VOLTAGE 100V, OUTPUT VOLTAGE 120V. INPUT PLUG TYPE: NEMA L5-30P. OUTLET TYPE AND QUANTITY 10 NEMA 5-20R. MAX LINE CURRENT 24A, INPUT CURRENT LIMITS 30A, LOAD CAPACITY 2880VA.

APC

AP9560

SC-TTB TELECOMMUNICATIONS TERMINAL BOARD, 4’X8’X3/4” A-C GRADE FIRE-RATED PLYWOOD. EXPOSED SIDE SHALL BE SMOOTH. MOUNT VERTICALLY WITH TOP OF PLYWOOD AT 8’-6” AFF. IN THE EVENT THE MANUFACTURER’S RATING STAMP IS NOT VISIBLE ON THE SMOOTH SIDE, THE CONTRACTOR SHALL PROVIDE A LAMINATED LETTER FROM THE MANUFACTURER OR SUPPLIER CERTIFYING THAT THE PLYWOOD IS FIRE-RATED AND ATTACH THE LETTER WITH A PICTURE OF THE RATING STAMP, TO THE PLYWOOD. FIRE RATED PLYWOOD SHALL NOT BE PAINTED OR TREATED WITH ANY TYPE OF

SEALANT THAT WOULD LESSEN THE INTEGRITY OF THE FIRE RATING.

SC-UPS RACK MOUNT 3KVA SMART UPS. 2 RACK UNITS. NEMA L5-30P INPUT. (3) NEMA 5-15R, (3) NEMA 5-20R, AND (1) NEMA L5-30R

OUTPUTS, RACK MOUNTABLE.

APC

SMX3000RMLV2U

SUPPORT FOR POSSIBLE RELOCATION AFTER WIRELESS SURVEY.

1. LOCATION OF FUTURE OR OWNER PROVIDED WIRELESS ACCESS POINT. PROVIDE A 20' SLACK COIL AT THE NEAREST CABLE

SCHEDULE NOTES:

2. REFER TO SPECIFICATIONS SECTION 27 05 53 FOR ADDITIONAL INFORMATION ON LABELING REQUIREMENTS. BLANK BLANK FILLER MODULE

1. PROVIDE REMOVABLE BLANK INSERT(S) FOR ALL UNUSED PORTS. DATA CAT 6A RJ-45

NOTES: LEGEND

SINGLE GANG WALLPLATES

INFORMATION OUTLET SCHEDULE

CONFIGURATION F

A

C E

P L

A T

E P

O R

T S

FACEPLATE PORT IDENTIFICATION

NOTESP

O

S

IT

IO

N

J

A C

K T

Y P

E

P O

S

IT

IO

N

J

A C

K T

Y P

E

P O

S

IT

IO

N

J

A C

K T

Y P

E

P O

S

IT

IO

N

J

A C

K T

Y P

E

P O

S

IT

IO

N

J

A C

K T

Y P

E

P O

S

IT

IO

N

J

A C

K T

Y P

E

C1 2 DATA BLANK

C2 2 DATA DATA

C2-WAP 2 DATA DATA 1.

C3 4 DATA DATA DATA BLANK

C4 4 DATA DATA DATA DATA

1. ELECTRONIC DOOR HARDWARE SUCH AS ELECTRIC STRIKES, ELECTRIC LATCH RETRACTION, ETC. SHALL BE PROVIDED AND INSTALLED BY OTHERS.

2. REFER TO THE TECHNOLOGY EQUIPMENT SCHEDULE FOR CREDENTIAL READER TYPE INFORMATION.

ACCESS CONTROL DOOR TYPE SCHEDULE

S E

C U

R

IT

Y D

O O

R T

Y P

E

D E

T A

IL

R

E F

E R

E N

C E

DOOR #

CREDENTIAL

READER

REQUEST

TO EXIT DOOR HARDWARE / MONITORING INTEGRATION

OTHER

(REFER TO

NOTES)

NOTESC

R

E D

E N

T

IA

L R

E A

D E

R T

Y P

E

M U

L T

IP

L

E C

R E

D E

N T

IA

L

R E

A D

E R

S O

P E

R A

T E

S S

IN

G

L E

D O

O R

O P

E R

A T

E S

M U

L T

IP

L

E D

O O

R S

IN

T

E R

N A

L E

L E

C T

R

IF

IE

D

H A

R D

W A

R E

C O

N N

E C

T

IO

N

B Y

O T

H E

R S

M O

T

IO

N D

E T

E C

T O

R

L O

C A

L P

U S

H B

U T

T O

N D

O O

R H

A R

D W

A R

E O

V E

R R

ID

E

E L

E C

T R

O N

IC

L

O C

K

IN

G H

A R

D W

A R

E

B Y

O T

H E

R S

M A

G L

O C

K

L O

C A

L A

L A

R M

H O

R N

L A

T C

H S

T A

T U

S D

E T

E C

T

IO

N

B Y

O T

H E

R S

M O

N

IT

O R

L A

T C

H B

O L

T

B Y

O T

H E

R S

M O

N

IT

O R

D O

O R

P O

S

IT

IO

N

S W

IT

C

H S

P D

T

M O

N

IT

O R

D O

O R

P O

S

IT

IO

N

S W

IT

C

H D

P D

T

M O

N

IT

O R

D O

O R

P O

S

IT

IO

N

S W

IT

C

H

O V

E R

H E

A D

D O

O R

M O

N

IT

O R

D O

O R

P O

S

IT

IO

N

S W

IT

C

H

R O

O F

H A

T C

H

A U

T O

M A

T

IC

D O

O R

O P

E R

A T

O R

E L

E V

A T

O R

L O

C K

E D

B Y

E M

E R

G E

N C

Y D

U R

E S

S S

E Q

U E

N C

E

IN

F

A N

T P

R O

T E

C T

IO

N

R E

M O

T E

U N

L O

C K

V

IA

I N

T E

R C

O M

M A

S T

E R

R E

M O

T E

U N

L O

C K

V

IA

P U

S H

B U

T T

O N

IN

T

R U

S

IO

N D

E T

E C

T

IO

N

R E

M O

T E

U N

L O

C K

V

IA

F

IR

E C

O M

M A

N D

C E

N T

E R

V

ID

E O

S U

R V

E

IL

L A

N C

E

W A

N D

E R

P R

E V

E N

T

IO

N S

Y S

T E

M

D E

L A

Y E

D E

G R

E S

S

B Y

O T

H E

R S

L O

C A

L

V

A C

P O

W E

R S

U P

P L

Y

S C

H E

D U

L E

B A

S E

D L

O C

K

IN

G

V

IS

U A

L S

T R

O B

E /A

U D

IB

L

E A

L A

R M

101 DPS R1 ●

115 DPS R1 ●

121 DPO ●

C1945BBBB DPS R1 ● ●

C1945FFF DPS ●

C1945HHH DPS R1 ●

C1945HHH DPS ●

C1945JJJ DPS ●

C1945LLL DPS R1 ● ●

C1945NNNN DPO ●

C1945PPPP DPO ●

C1945RRRR DPO ●

C1945TTTT RIE ● ●

C1945TTTT DPO ●

C1945VVV DPS R1 ●

C1945WW DPO ●

C1945XXX DPS R1 ●

GATE 117 DPS R1 ●

THE EQUIPMENT LIST ABBREVIATIONS AND THE TECHNOLOGY EQUIPMENT SCHEDULE ARE FOR THE CONVENIENCE OF THE CONTRACTOR. EACH CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF QUANTITIES AND SHALL FURNISH ALL MATERIAL REQUIRED, WHETHER SPECIFIED OR NOT, TO PRODUCE A SATISFACTORY WORKING

SYSTEM.

CATALOG NUMBERS ARE NOT TO BE CONSIDERED COMPLETE BUT ARE GIVEN ONLY TO AID THE CONTRACTOR IN THE SEARCH FOR MATERIAL. NO MATERIAL SHALL BE ORDERED BY MANUFACTURER AND CATALOG NUMBER ONLY. EACH CONTRACTOR SHALL FIRST READ THE COMPLETE DESCRIPTION OF THE MATERIAL ON THESE DRAWINGS AND SPECIFICATIONS. MANUFACTURER PROVIDED SHALL BE CONSISTENT WITH APPROVED MANUFACTURERS LISTED. "STANDARD COLOR" INDICATES FACTORY FINISH AVAILABLE AT NO ADDITIONAL CHARGE. ALL EQUIPMENT MUST MEET BUY AMERICAN REQUIREMENTS.

TECHNOLOGY EQUIPMENT SCHEDULE

EQUIPMENT LIST

ABBREVIATION EQUIPMENT LIST DESCRIPTION

MANUFACTURER AND

MODEL

VS-CM-1 EXTERIOR/INTERIOR 5MP (SINGLE SENSOR) CAMERA. FIXED DOME CAMERA FOR OUTDOOR, HDTV 1080P VIDEO QUALITY, VANDAL-RESISTANT WITH WDR.

PROVIDE A PROPER MOUNT BASED ON THE INSTALLED APPLICATIONS ON THE WALL OR CEILING. FOR WALL APPLICATIONS, PROVIDE A 4" SQUARE BACKBOX WITH CONDUIT TO ABOVE THE NEAREST ACCESSIBLE CEILING.

ALL CABLING SHALL BE EITHER ABOVE THE ACCESSIBLE CEILING OR INSTALLED IN CONDUIT. NO CABLING SHALL BE EXPOSED. FOR OPEN CEILINGS, INSTALL IN CONDUIT. REFER TO THE DRAWINGS FOR ADDITIONAL INFORMATION.

THE TECHNOLOGY EQUIPMENT SCHEDULE ONLY DESCRIBES CAMERA SERIES AND PERFORMANCE INFORMATION. REFER TO INDIVIDUAL CAMERA SCHEDULE ON SHEET T600 FOR ADDITIONAL INFORMATION ON INDIVIDUAL CAMERA

REQUIREMENTS, ROUGH-IN, AND MOUNTING.

AXIS COMMUNICATIONS

P3367-VE

VS-KVM-1 17" LCD RACK MOUNT SLIDE OUT MONITOR WITH KEYBOARD AND TWO BUTTON TOUCH PAD MOUSE AND BUILT-IN 8-PORT DVI/USB KVM. COORDINATE WITH OWNER ON MONITOR HEIGHT IN RACK. REQUIRES (1) 1.75 MOUNTING SPACE. PROVIDE

WITH ALL NECESSARY CABLES TO CONNECT TO ALL CCTV EQUIPMENT.

NTI

RACKMUX-D17-N-8DVIHD

VS-VMS-1 VIDEO MANAGEMENT SERVER. REQUIRES (2) RACK UNITS.

REFER TO THE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

GENETEC

INDIVIDUAL CAMERA REQUIREMENTS SCHEDULE

CAMERA #

CAMERA

TYPE

CAMERA

ENVIRONMENT

TELECOM

ROOM # LOCATION FIELD OF VIEW DESCRIPTION

MOUNTING

TYPE

DETAIL

REFERENCE F

R A

M E

R A

T E

P E

R C

E N

T M

O T

IO

N

ADDITIONAL

INFORMATION NOTES

01-01 CM-1 INTERIOR TE/1 100/RECEPTION STANDARD VIEW CEILING 3/T401 15 50

01-02 CM-1 INTERIOR TE/1 110/EXISTING

ADMIN STAFF

STANDARD VIEW CEILING 3/T401 15 50

01-03 CM-1 INTERIOR TE/1 113/ALCOVE STANDARD VIEW CEILING 3/T401 15 50

01-04 CM-1 INTERIOR TE/1 TE/1 STANDARD VIEW CEILING 3/T401 15 50

01-05 CM-1 INTERIOR TE/2 EXISTING

LUNCH

STANDARD VIEW CEILING 3/T401 15 50

01-06 CM-1 INTERIOR TE/2 MAINTENANCE

BAYS

STANDARD VIEW CEILING N/A 15 50

01-07 CM-1 INTERIOR TE/2 TE/2 STANDARD VIEW CEILING N/A 15 50

Revisions: Date: 149 of 155

GENERAL FIRE ALARM EQUIPMENT SCHEDULE

THE SYMBOLS AND THE EQUIPMENT SCHEDULE ARE FOR THE CONVENIENCE OF THE CONTRACTOR. EACH CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF QUANTITIES AND SHALL FURNISH ALL MATERIAL REQUIRED, WHETHER SPECIFIED OR NOT, TO PRODUCE A SATISFACTORY WORKING

SYSTEM.

CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE BUT ARE GIVEN ONLY TO AID THE CONTRACTOR IN THE SEARCH FOR MATERIAL. NO MATERIAL SHALL BE ORDERED BY MANUFACTURER AND CATALOG NUMBER ONLY. EACH CONTRACTOR SHALL FIRST READ THE COMPLETE DESCRIPTION OF THE MATERIAL ON THESE DRAWINGS AND SPECIFICATIONS. MANUFACTURER PROVDED SHALL BE CONSISTENT WITH APPROVED MANUFACTURERS LISTED.

"STANDARD COLOR" INDICATES FACTORY FINISH AVAILABLE AT NO ADDITIONAL CHARGE. ALL EQUIPMENT MUST MEET BUY AMERICAN REQUIREMENTS. REFER

TO SPECIFICATIONS FOR MORE INFORMATION.

ITEM

NO

SYMBOL DESCRIPTION

FIRE ALARM ANNUNCIATOR PANEL, POWERED FROM FIRE ALARM CONTROL PANEL, SURFACE

MOUNT.

NOTIFIER BY HONEYWELL

SIEMENS FIRE SAFETY

EDWARDS - EST

HOCHIKI AMERICA

FAA-#

SMOKE DETECTOR, ADDRESSABLE, ANALOG PHOTOELECTRIC SENSOR, 24 VDC, 2-PIECE DESIGN, LOW-PROFILE MOUNTING BASE WITH MULTI-FUNCTION LED INDICATOR, COMPLETE WITH

MOUNTING HARDWARE AND BACKBOX.

NOTIFIER BY HONEYWELL

SIEMENS FIRE SAFETY

EDWARDS - EST

HOCHIKI AMERICA

HEAT DETECTOR, ADDRESSABLE, ANALOG SENSOR, COMBINATION RATE OF RISE AND 135

DEGREE FAHRENHEIT FIXED TEMPERATURE, 2-WIRE OPERATION, 24 VDC, 2-PIECE DESIGN, LOW-

PROFILE MOUNTING BASE WITH MULTI-FUNCTION LED INDICATOR, COMPLETE WITH MOUNTING

HARDWARE AND BACKBOX. PROVIDE A REMOTE LED INDICATOR DEVICE IF DETECTOR IS NOT

VISIBLE FROM A FLOOR-STANDING POSITION.

FIRE ALARM MANUAL PULL STATION, ADDRESSABLE, SINGLE ACTION WITH PLASTIC BREAKROD, RESET KEY LOCK, SEMI-FLUSH MOUNT, RED HIGH-ABUSE PLASTIC OR CAST METAL

CONSTRUCTION WITH WHITE LETTERING. USE SURFACE MOUNT ONLY ON PRECAST CONCRETE

OR STRUCTURE.

NOTIFIER BY HONEYWELL

SIEMENS FIRE SAFETY

EDWARDS - EST

HOCHIKI AMERICA

F

FIRE ALARM CEILING AUDIO/VISUAL NOTIFICATION APPLIANCE, ELECTRONIC HORN WITH

SELECTABLE CONTINUOUS OR TEMPORAL TONE, SELECTABLE SOUND OUTPUT, AND HIGH

INTENSITY STROBE, WHITE HOUSING WITH RED LETTERING OR PICTOGRAM, SEMI-FLUSH CEILING

MOUNT, 24 VDC.

CANDELA RATINGS: 15cd, 75cd. CANDELA

RATING SHALL BE VISIBLE FROM THE OUTSIDE OF THE DEVICE.

NOTIFIER BY HONEYWELL

SIEMENS FIRE SAFETY

EDWARDS - EST

HOCHIKI AMERICA

FIRE ALARM WALL AUDIO/VISUAL NOTIFICATION APPLIANCE, ELECTRONIC HORN WITH SELECTABLE CONTINUOUS OR TEMPORAL TONE, SELECTABLE SOUND OUTPUT, AND HIGH-INTENSITY STROBE, RED

HOUSING WITH WHITE LETTERING OR PICTOGRAM, SEMI-FLUSH WALL MOUNT, 24 VDC.

CANDELA RATINGS: 15cd, 75cd. CANDELA

RATING SHALL BE VISIBLE FROM THE OUTSIDE OF THE DEVICE.

NOTIFIER BY HONEYWELL

SIEMENS FIRE SAFETY

EDWARDS - EST

HOCHIKI AMERICA

F

F

S

H

FIRE ALARM CONTROL PANEL, ADDRESSABLE SYSTEM, FEATURING INTERFACE WITH ANALOG

SENSING INITIATING DEVICES, EXPANDABLE MODULAR DESIGN, MICROPROCESSOR BASED

ELECTRONICS, 120 VAC OPERATION, SURFACE MOUNT.

NOTIFIER BY HONEYWELL

SIEMENS FIRE SAFETY

EDWARDS - EST

HOCHIKI AMERICA

FACP-#

GAS DETECTOR, ADDRESSABLE, ANALOG CARBON MONOXIDE TYPE SENSOR, CARBON MONOXIDE

ELECTROLYTIC SENSING MODULE SHALL PROVIDE TOXIC GAS SENSING TO UL2034 AND UL2075

STANDARDS, 24 VDC, LOW-PROFILE MOUNTING BASE WITH MULTI-FUNCTION LED INDICATOR,

COMPLETE WITH MOUNTING HARDWARE AND BACKBOX. CO SENSOR CARTRIDGE ELEMENT SHALL

BE FIELD REPLACEABLE.

NOTIFIER BY HONEYWELL

SIEMENS FIRE SAFETY

EDWARDS - EST

HOCHIKI AMERICA

NOTIFIER BY HONEYWELL

SIEMENS FIRE SAFETY

EDWARDS - EST

HOCHIKI AMERICA

APPROVED MANUFACTURERS

FIRE ALARM CEILING VISUAL NOTIFICATION APPLIANCE, HIGH-INTENSITY STROBE, WHITE HOUSING

WITH RED LETTERING OR PICTOGRAM, SEMI-FLUSH CEILING MOUNT; 24 VDC.

CANDELA RATINGS: 15cd, 75cd. CANDELA

RATING SHALL BE VISIBLE FROM THE OUTSIDE OF THE DEVICE.

NOTIFIER BY HONEYWELL

SIEMENS FIRE SAFETY

EDWARDS - EST

HOCHIKI AMERICA

FIRE ALARM ADDRESSABLE RELAY CONSISTING OF AN ADDRESSABLE CONTROL MODULE AND

SLAVE RELAY WITH CONTACTS SUITABLE FOR CONTROLLING THE DESIGNATED AUXILIARY LOAD, PROVIDE AN ADDITIONAL CHILD RELAY(S) AS REQUIRED, 24 VDC, 4-WIRE OPERATION, MOUNT IN

ENCLOUSER IN AN ACCESSIBLE SERVICE LOCATION.

NOTIFIER BY HONEYWELL

SIEMENS FIRE SAFETY

EDWARDS - EST

HOCHIKI AMERICA

CM

FIRE ALARM WALL VISUAL NOTIFICATION APPLIANCE, HIGH-INTENSITY STROBE, RED HOUSING

WITH WHITE LETTERING OR PICTOGRAM, SEMI-FLUSH WALL MOUNT; 24 VDC.

CANDELA RATINGS: 15cd, 75cd. CANDELA

RATING SHALL BE VISIBLE FROM THE OUTSIDE OF THE DEVICE.

NOTIFIER BY HONEYWELL

SIEMENS FIRE SAFETY

EDWARDS - EST

HOCHIKI AMERICA

PLAN OR DETAIL NUMBER

PLAN OR DETAIL NAME

PLAN OR DETAIL SCALE

DETAIL REFERRED TO BY SECTION CUT

SHEET DETAIL IS LOCATED ON

NAME

VIEW NAME

1/8" = 1'-0"

M101

SIMSIM

INDICATES SIMILAR DETAIL REFERENCED

IN MULTIPLE LOCATIONS

LEVEL NAME

10'-0" HEIGHT ABOVE

PROJECT 0'-0"

1 KEYNOTE: INDICATES NOTE USED TO

DESCRIBE ADDITIONAL INFORMATION

ABOUT WORK REQUIRED, SPECIFIC

TO THE SHEET AND/OR DETAIL

N

O R HT

INDICATES DIRECTION OF TRUE NORTH

VIEW KEY

LINE TYPE AND TAG KEY:

NEW WORK BY THIS CONTRACTOR (WIDE LINE)

EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)

HALF TONING DOES NOT MODIFY SCOPE.

'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING

TAG-1 UNDERLINED TAG…

This is the start of the file's text. The full file is on GovTribe.