2101-EP111_ADD1.pdf
PDF 323 KB Posted
- Solicitation number
- 36C78626B0028
About this file
This document is a set of electrical bid drawings and specifications for the Admin Building Power Plans at Fort Bliss National Cemetery Expansion in El Paso, Texas. The project, identified as 2101-EP111 with project number 18528, requires comprehensive electrical work including demolition, new panel installation, and branch circuit extensions throughout basement and first-level areas of the facility.
Key work requirements include: removal of existing electrical connections, wiring, and conduit serving equipment to be demolished while maintaining fire ratings of affected walls and floors; installation of a new 240/120V, 200A rated main lug only panelboard (Panel A) with 42-circuit capacity in the existing storage/electrical room; extension of existing branch circuits to the new panelboard; provision of two L5-30R receptacles for telecom use coordinated with the low voltage contractor; single-point power provision to a mini-split unit from condensing unit CU-1; and access control installation coordinated with security management. The panelboard specifications indicate a 22 kA short-circuit current rating (SCCR), NEMA 1 enclosure with surface mounting, 100% neutral bus rating, and main lug only (MLO) configuration. Copper conductor and conduit sizing requirements are detailed in a chart, with typical runs using THWN-2 conductors ranging from #12 to 3/0 AWG in 3/4" to 2" EMT or Schedule 80 conduit. The drawings note that existing loads marked "E" are to be reconnected to the new panelboard, and electrical power outages should be strategically minimized and coordinated closely with the owner. The design was prepared by ANDERSON as designer of record, with IMEG providing low voltage/security and fire alarm consultant services.
View the file
Other files
Show 40 more
Latest 50 of 52 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SPD
GFI
AC
38"
J
12"
J
J
J
J
WP
GFI
12"
48"
ELECTRICAL DEMOLITION
GENERAL NOTES
1. DEMOLITION DRAWINGS ARE BASED ON EXISTING AVAILABLE DRAWINGS AND
FIELD OBSERVATION. ELECTRICAL CONTRACTORS SHALL FIELD VERIFY THE SITE
AND INCLUDE ALL REQUIRED DEMOLITION IN THE BID.
2. ALL REQUIRED DEMOLITION MAY NOT BE INDICATED. IT IS THE INTENT OF THESE
DOCUMENTS THAT ALL MECHANICAL AND ELECTRICAL SYSTEMS (NOT TO BE
REUSED OR EXTENDED) BE REMOVED. COORDINATE WITH ARCHITECTURAL
DRAWINGS.
3. REMOVE ALL ELECTRICAL CONNECTIONS, WIRING, AND CONDUIT SERVING ALL
EQUIPMENT TO BE REMOVED.
4. MAINTAIN FIRE RATINGS OF WALLS AND FLOORS AFFECTED BY DEMOLITION.
5. REFER TO ARCHITECTURAL DRAWINGS FOR DETAILS ON FLOOR CUTTING AND
CEILING REMOVAL. CONTRACTOR SHALL COORDINATE WORK TO BE CONSISTENT
WITH SCOPE OF GENERAL CONTRACTOR'S DEMOLITION.
EX EX
E1
PANEL A
E3
E1
E5
ELECTRICAL PLAN KEYED NOTES
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
E1 NO ELECTRICAL SCOPE IN THIS AREA
E2
PROVIDE (2) L5-30R RECEPTACLES FOR TELECOM USE. REFER TO
TECHNOLOGY DRAWINGS FOR ADDITIONAL DETAILS. COORDINATE WITH
LOW VOLTAGE CONTRACTOR PRIOR TO ROUGH-IN.
E3
PROVIDE 240/120V, 200A RATED, MAIN LUG ONLY PANELBOARD WITH 42
CIRCUIT CAPACITY. EXTEND EXISTING BRANCH CIRCUITS TO NEW
PANELBOARD. REFER TO ONE-LINE DIAGRAM AND PANEL SCHEDULE FOR
ADDITIONAL DETAILS.
E4
PROVIDE SINGLE POINT POWER TO MINI-SPLIT FROM ASSOCIATE
CONDENSING UNIT CU-1. REFER TO MECHANICAL SHEETS FOR ADDITIONAL
DETAILS.
E5
ACCESS CONTROL LOCATION. REFER TO TECHNOLOGY DETAILS AND
ARCHITECTURAL SPECIFICATIONS 08-7100 FOR OPERATION AND FURTHER
ROUGH-IN/BIDDING INFORMATION. COORDINATE ALL DOOR HOLDS, CARD
READERS, AND OTHER ACCESSORIES WITH ALL TRADES PRIOR TO
ROUGH-IN.
E6
COORDINATE EXACT DEVICE LOCATION WITH SECURITY MANAGEMENT
PANEL PRIOR TO ROUGH-IN.
EXEX EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EXISTING DIRECTOR
EXISTING ADMIN OFFICER
EXISTING UNISEX TOILET
EXISTING PROGRAM
SPECIALIST
EXISTING CORRIDOR
EXISTING STAIR
EXISTING ALCOVE
EXISTING MENS
EXISTING BREAKROOM
EXISTING OPERATIONS
TE
EXISTING CONFERENCE
EXISTING RECEPTION
EXISTING STORAGE
EXISTING ADMIN STAFF
PROJECTOR
E1
E2
PRINTER
PANEL A-33
SHREDDER
PANEL A-35 E1
L5-30R
L5-30R
L5-30R RECEPT
120V-1P/30A
PANEL A-39
L5-30R RECEPT
120V-1P/30A
PANEL A-37
TE RECEPTS
120V-1P/20A
PANEL A-41
FA BELL
PANEL A-34
FACP
PANEL A-36
CU-1
240V-2P/20A
PANEL A-38,40
E4
WP
PANEL A-43
E5 E5
E5
E5
AC-SCP-1
PANEL A-42
E6
TO EXISTING SERVICE
DISCONNECT
30A-2P
30A-2P
EX
ER PANEL A
200A, 240/120V, 1PH, 3W
30A-1P
EX J AC/UNIT
EX J AC CONDENSER
20A-2P
EX J FLAG POLE LIGHTS
EX EX BRANCH
CIRCUITS TO REMAIN
ER1 ER2
J
J
J
J
TYPICAL ALL BRANCH
CIRCUITS
J
ER2
TO EXISTING SERVICE
DISCONNECT
30A-2P
30A-2P
EX
PANEL A
200A, 240/120V, 1PH, 3W
SCCR: 22,000A
30A-2P
EX J AC/UNIT
EX J AC CONDENSER
20A-1P
EX J FLAG POLE LIGHTS
EX EX BRANCH
CIRCUITS TO REMAIN
ER1
ER3
J
J
J
J
TYPICAL ALL BRANCH
CIRCUITS
30A-1P
30A-1P
30/2
30/2
J L5-30R RECEPT
J L5-30R RECEPT
J
ER4
ELECTRICAL RISER GENERAL
NOTES
1. ELECTRICAL POWER OUTAGES, IF REQUIRED, SHOULD BE STRATEGICALLY
MINIMIZED AND SCHEDULED CLOSELY WITH OWNER. CHANGEOVERS COULD BE
REQUIRED TO OCCUR AT ANY HOUR.
2. MAINTAIN ALL SERVICE CLEARANCES REQUIRED BY THE NEC.
3. INSTALL ALL CONDUCTORS AS PER MANUFACTURER'S RECOMMENDATIONS.
ELECTRICAL RISER KEYED NOTES
ER1
REFER TO PANEL SCHEDULE FOR ADDITIONAL PANEL AND CIRCUIT
DETAILS.
ER2
DISCONNECT CONDUCTORS FROM PANELBOARD AND PULL BACK TO
NEAREST JUNCTION BOX. PROVIDE NEW AS NECESSARY. PREPARE TO
EXTEND TO NEW PANELBOARD.
ER3
SPLICE AND EXTEND CONDUCTORS FROM EXISTING BRANCH CIRCUITS TO
NEW PANEL. REFER TO SCHEDULE FOR PANEL A FOR ADDITIONAL BRANCH
CIRCUIT INFORMATION. MINIMIZE AND COORDINATE REQUIRED DOWNTIME
WITH OWNER.
ER4
EXTEND EXISTING FEEDER TO NEW PANEL, SPLICING CONDUCTORS AS
REQUIRED. NEW CONDUCTORS SHALL MATCH EXISTING FEEDER
CHARACTERISTICS. REFER TO PANEL SCHEDULE FOR ADDITIONAL
INFORMATION. MINIMIZE AND COORDINATE REQUIRED DOWNTIME WITH
OWNER.
COPPER CONDUCTOR
AND CONDUIT SIZING CHART
CONDUCTORS (THWN-2) CONDUIT PARALLEL
RUNS
PHASE NEUTRAL GROUND EMT SCH 80
15/2 (2) #12 AWG #12 AWG 3/4" 1
20/2 (2) #12 AWG #12 AWG 3/4" 1
25/2 (2) #10 AWG #10 AWG 3/4" 1
30/2 (2) #10 AWG #10 AWG 3/4" 1
200/3 (2) 3/0 AWG #6 AWG 13/0 AWG
3/4"
3/4"
3/4"
3/4"
2" 2"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
NOT SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
DESIGNER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
L0W VOLTAGE/SECURITY:
IMEG
623 26TH AVENUE
ROCK ISLAND, IL 61201
309.781.3770
PETE MCGHEE
IRRIGATION:
AQUA ENGINEERING
300 BOARDWALK DRIVE
UNIT 4B
FORT COLLINS,CO 80525
970.372.6104
JD LEONARD
GEOTECHNICAL:
TERRACON
6460 HILLER STREET
SUITE A
EL PASO, TX 79925
915.778.5233
IVAN AVELAR
FIRE ALARM:
IMEG
623 26TH AVENUE
ROCK ISLAND, IL 61201
309.781.3770
MATT SNYDER
C U s e rs \a w e b e r\
D o c u m e n ts \1
-A
D M
IN
-M
-R a w e b e r9
S
.r v t
/1 /2
:1
:3
P M
2101-EP111
ADMIN BLDG - POWER PLANS FT BLISS NATIONAL CEMETERY
EXPANSION
5200 FRED WILSON AVENUE, EL PASO, TEXAS
886CM3026
JUNE 15, 2026 ATW DIL
18528
1/4" = 1'-0"
BASEMENT POWER PLAN
Notes: G=GFI M=MOTORIZED E=EXISTING ST=SHUNT TRIP A=ARC FAULT H=HANDLE LOCK
Demand Current: 40 A
Demand Load: 10 kVA
Connected Current: 40 A
Receptacle - General 1620 VA 100.00% 1620 VA Connected Load: 10 kVA
Other 8080 VA 100.00% 8080 VA Panel Totals
Load Classification Connected Factor Demand
Connected Current: 44 A 37 A
Connected Load: 5 kVA 4 kVA
53 Space -- 1 -- 0 54
51 Space -- 1 -- 0
2 30 EXTERNAL SPD
49 Space -- 1 -- -- 1 -- Space 50
47 Spare 20 1 0 -- 1 -- Space 48
45 Spare 20 1 0 0 1 20 Spare 46
43 EXTERIOR RECEPT 20 1 180 0 1 20 Spare 44
41 TE RECEPTS 20 1 720 360 1 20 AC-SCP-1 42
39 L5-30R RECEPT 30 1 3500 180 40
37 L5-30R RECEPT 30 1 3500 180
2 20 CU-1
35 SHREDDER 20 1 180 360 1 20 FACP 36
33 PRINTER 20 1 180 360 1 20 FA BELL 34
31 0 0 E 1 15 WOMENS RESTROOM HAND DRYER 32
A/C 20 2 E
0 0 E 1 15 EXTERIOR GFCI UNIT 30
27 0 0 E 1 15 EXISTING LOAD 28
AC UNIT 30 2 E
0 0 E 1 20 SEWER 26
23 QUAD OUTLET 20 1 E 0 0 E 1 20 SEWER 24
21 ADMIN OUTLETS 20 1 E 0 0 E 1 30 AC CONDENSER 22
19 MECH LIGHTS/OUTLETS 20 1 E 0 0 E 1 30 AC CONDENSER 20
17 LAN OUTLET 20 1 E 0 0 E 1 20 KITCHEN OUTLET 18
15 ADMIN CUBICLE OUTLETS 20 1 E 0 0 E 1 20 FRIDGE OUTLET 16
13 MGR OUTLET 20 1 E 0 0 E 1 20 OPS COPY/FAX OUTLETS 14
11 CORR/BATH LIGHTS/OUTLETS 20 1 E 0 0 E 1 20 KIT. OUTLET 12
9 CONF OUTLETS 20 1 E 0 0 E 1 20 EXISTING LOAD 10
7 WAIT OUTLETS 20 1 E 0 0 E 1 20 EXISTING LOAD 8
5 EXISTING LOAD 20 1 E 0 0 E 1 20 OPS WINDOW OUTLET 6
3 STAFF LIGHTS & BLOWER 20 1 E 0 0 E 1 30 FLAG POLE LIGHTS 4
1 ADMIN LIGHTS 20 1 E 0 0 E 1 30 FLAG POLE LIGHTS 2
Ckt Description Trip (A) Poles FN/Note A B FN/Note Poles Trip (A) Description Ckt
NOTES: NEW BRANCH PANEL. LOADS TAGGED 'E' ARE EXISTING LOADS TO BE RECONNECTED TO NEW PANELBOARD.
Enclosure: NEMA 1
Mounting: Surface Features & Modifications: -
Supply: Feed-Thru Lugs: No SCCR: 22 kA
Location: EXISTING STORAGE/ELEC/OIT 117 Neutral: 100% Mains FN/Note: -
Bus Rating: 200 A Mains Rating: 200 A
Panelboard: PANEL A Voltage: 240 V, 1Ø, 3W Mains Type: MLO
1/4" = 1'-0"
FIRST LEVEL POWER PLAN
ONE-LINE DIAGRAM DEMO
ONE-LINE DIAGRAM - NEW
Revisions: Date:
Addendum 1 10/12/2026
| Sheets |
| 2101-EL111 - ADMIN BLDG - LIGHTING PLAN |
| 2101-EP111 - ADMIN BLDG - POWER PLANS |
File details come from the government source that posted it. Updated .