This document is a set of electrical bid drawings and specifications for the Admin Building Power Plans at Fort Bliss National Cemetery Expansion in El Paso, Texas. The project, identified as 2101-EP111 with project number 18528, requires comprehensive electrical work including demolition, new panel installation, and branch circuit extensions throughout basement and first-level areas of the facility.

Key work requirements include: removal of existing electrical connections, wiring, and conduit serving equipment to be demolished while maintaining fire ratings of affected walls and floors; installation of a new 240/120V, 200A rated main lug only panelboard (Panel A) with 42-circuit capacity in the existing storage/electrical room; extension of existing branch circuits to the new panelboard; provision of two L5-30R receptacles for telecom use coordinated with the low voltage contractor; single-point power provision to a mini-split unit from condensing unit CU-1; and access control installation coordinated with security management. The panelboard specifications indicate a 22 kA short-circuit current rating (SCCR), NEMA 1 enclosure with surface mounting, 100% neutral bus rating, and main lug only (MLO) configuration. Copper conductor and conduit sizing requirements are detailed in a chart, with typical runs using THWN-2 conductors ranging from #12 to 3/0 AWG in 3/4" to 2" EMT or Schedule 80 conduit. The drawings note that existing loads marked "E" are to be reconnected to the new panelboard, and electrical power outages should be strategically minimized and coordinated closely with the owner. The design was prepared by ANDERSON as designer of record, with IMEG providing low voltage/security and fire alarm consultant services.

View the file

Other files

File Type Posted
4101-AE201_ADD1.pdf PDF
2101-AE201_ADD1.pdf PDF
3004-E-111_ADD1.pdf PDF
S02_Attachment - Geotechnical Engineering Report.pdf PDF
092400 PORTLAND CEMENT PLASTERING_ADD1.pdf PDF
073213 CLAY ROOF TILES_ADD1.pdf PDF
2101-AE101_ADD1.pdf PDF
S02_Attachment - DOL Payroll Form updated.pdf PDF
S05_Attachment - RFIs and Responses.pdf PDF
2101-AE111_ADD1.pdf PDF
CE121_ADD1.pdf PDF
S02_Attachment - Statement of Work revised 10.26.2026.pdf PDF
3004-ED111_ADD1.pdf PDF
050385 HISTORIC DECORATIVE FORMED METAL REPAIR_WR IR_ADD1.pdf PDF
LK111_ADD1.pdf PDF
000110 TABLE OF CONTENTS_ADD1.pdf PDF
LP111_ADD1.pdf PDF
3003-ED111_ADD1.pdf PDF
2101-AD201_ADD1.pdf PDF
3003-E-501_ADD1.pdf PDF
S02_Attachment - SF 1413 updated.pdf PDF
S06_36C78626B0028 0002.pdf PDF
CB501_ADD1.pdf PDF
S02_Attachment - Addendum 1 Summary of Changes.pdf PDF
3003-E-111_ADD1.pdf PDF
087100 DOOR HARDWARE_ADD1.pdf PDF
2101-EL111_ADD1.pdf PDF
281300 PHYSICAL ACCESS CONTROL SYSTEM_ADD1.pdf PDF
CB502_ADD1.pdf PDF
S04_Attachment - Site Visit Attendance Roster.pdf PDF
S06_36C78626B0028 Amend. 0001.pdf PDF
Fort Bliss Gravesite Expansion BD Part 1.pdf PDF
S02_Attachment - Limitations on Subcontracting Cert.docx DOCX document
S02_Attachment - DOL Payroll Form.pdf PDF
Fort Bliss Gravesite Expansion BD Part 3.pdf PDF
Fort Bliss Gravesite Expansion BD Part 5.pdf PDF
Fort Bliss Gravesite Expansion BD Part 10.pdf PDF
Fort Bliss Gravesite Expansion - Specifications Full Book.pdf PDF
Fort Bliss Gravesite Expansion BD Part 9.pdf PDF
Fort Bliss Gravesite Expansion BD Part 8.pdf PDF
S02_Attachment - 886CM3026 Fort Bliss NC SOW.pdf PDF
Fort Bliss Gravesite Expansion BD Part 4.pdf PDF
Fort Bliss Gravesite Expansion BD Part 7.pdf PDF
S02_36C78626B0028 Solicitation.pdf PDF
S02_Attachment - Davis-Bacon Act Poster.pdf PDF
S02_Attachment - Standard Form 1413.pdf PDF
Fort Bliss Gravesite Expansion BD Part 2.pdf PDF
Fort Bliss Gravesite Expansion BD Part 11.pdf PDF
S02_Attachment - Price Schedule Sheet.pdf PDF
S02_Attachment - Wage Determination Heavy.pdf PDF
Show 40 more

Latest 50 of 52 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SPD

GFI

AC

38"

J

12"

J

J

J

J

WP

GFI

12"

48"

ELECTRICAL DEMOLITION

GENERAL NOTES

1. DEMOLITION DRAWINGS ARE BASED ON EXISTING AVAILABLE DRAWINGS AND

FIELD OBSERVATION. ELECTRICAL CONTRACTORS SHALL FIELD VERIFY THE SITE

AND INCLUDE ALL REQUIRED DEMOLITION IN THE BID.

2. ALL REQUIRED DEMOLITION MAY NOT BE INDICATED. IT IS THE INTENT OF THESE

DOCUMENTS THAT ALL MECHANICAL AND ELECTRICAL SYSTEMS (NOT TO BE

REUSED OR EXTENDED) BE REMOVED. COORDINATE WITH ARCHITECTURAL

DRAWINGS.

3. REMOVE ALL ELECTRICAL CONNECTIONS, WIRING, AND CONDUIT SERVING ALL

EQUIPMENT TO BE REMOVED.

4. MAINTAIN FIRE RATINGS OF WALLS AND FLOORS AFFECTED BY DEMOLITION.

5. REFER TO ARCHITECTURAL DRAWINGS FOR DETAILS ON FLOOR CUTTING AND

CEILING REMOVAL. CONTRACTOR SHALL COORDINATE WORK TO BE CONSISTENT

WITH SCOPE OF GENERAL CONTRACTOR'S DEMOLITION.

EX EX

E1

PANEL A

E3

E1

E5

ELECTRICAL PLAN KEYED NOTES

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

E1 NO ELECTRICAL SCOPE IN THIS AREA

E2

PROVIDE (2) L5-30R RECEPTACLES FOR TELECOM USE. REFER TO

TECHNOLOGY DRAWINGS FOR ADDITIONAL DETAILS. COORDINATE WITH

LOW VOLTAGE CONTRACTOR PRIOR TO ROUGH-IN.

E3

PROVIDE 240/120V, 200A RATED, MAIN LUG ONLY PANELBOARD WITH 42

CIRCUIT CAPACITY. EXTEND EXISTING BRANCH CIRCUITS TO NEW

PANELBOARD. REFER TO ONE-LINE DIAGRAM AND PANEL SCHEDULE FOR

ADDITIONAL DETAILS.

E4

PROVIDE SINGLE POINT POWER TO MINI-SPLIT FROM ASSOCIATE

CONDENSING UNIT CU-1. REFER TO MECHANICAL SHEETS FOR ADDITIONAL

DETAILS.

E5

ACCESS CONTROL LOCATION. REFER TO TECHNOLOGY DETAILS AND

ARCHITECTURAL SPECIFICATIONS 08-7100 FOR OPERATION AND FURTHER

ROUGH-IN/BIDDING INFORMATION. COORDINATE ALL DOOR HOLDS, CARD

READERS, AND OTHER ACCESSORIES WITH ALL TRADES PRIOR TO

ROUGH-IN.

E6

COORDINATE EXACT DEVICE LOCATION WITH SECURITY MANAGEMENT

PANEL PRIOR TO ROUGH-IN.

EXEX EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EXISTING DIRECTOR

EXISTING ADMIN OFFICER

EXISTING UNISEX TOILET

EXISTING PROGRAM

SPECIALIST

EXISTING CORRIDOR

EXISTING STAIR

EXISTING ALCOVE

EXISTING MENS

EXISTING BREAKROOM

EXISTING OPERATIONS

TE

EXISTING CONFERENCE

EXISTING RECEPTION

EXISTING STORAGE

EXISTING ADMIN STAFF

PROJECTOR

E1

E2

PRINTER

PANEL A-33

SHREDDER

PANEL A-35 E1

L5-30R

L5-30R

L5-30R RECEPT

120V-1P/30A

PANEL A-39

L5-30R RECEPT

120V-1P/30A

PANEL A-37

TE RECEPTS

120V-1P/20A

PANEL A-41

FA BELL

PANEL A-34

FACP

PANEL A-36

CU-1

240V-2P/20A

PANEL A-38,40

E4

WP

PANEL A-43

E5 E5

E5

E5

AC-SCP-1

PANEL A-42

E6

TO EXISTING SERVICE

DISCONNECT

30A-2P

30A-2P

EX

ER PANEL A

200A, 240/120V, 1PH, 3W

30A-1P

EX J AC/UNIT

EX J AC CONDENSER

20A-2P

EX J FLAG POLE LIGHTS

EX EX BRANCH

CIRCUITS TO REMAIN

ER1 ER2

J

J

J

J

TYPICAL ALL BRANCH

CIRCUITS

J

ER2

TO EXISTING SERVICE

DISCONNECT

30A-2P

30A-2P

EX

PANEL A

200A, 240/120V, 1PH, 3W

SCCR: 22,000A

30A-2P

EX J AC/UNIT

EX J AC CONDENSER

20A-1P

EX J FLAG POLE LIGHTS

EX EX BRANCH

CIRCUITS TO REMAIN

ER1

ER3

J

J

J

J

TYPICAL ALL BRANCH

CIRCUITS

30A-1P

30A-1P

30/2

30/2

J L5-30R RECEPT

J L5-30R RECEPT

J

ER4

ELECTRICAL RISER GENERAL

NOTES

1. ELECTRICAL POWER OUTAGES, IF REQUIRED, SHOULD BE STRATEGICALLY

MINIMIZED AND SCHEDULED CLOSELY WITH OWNER. CHANGEOVERS COULD BE

REQUIRED TO OCCUR AT ANY HOUR.

2. MAINTAIN ALL SERVICE CLEARANCES REQUIRED BY THE NEC.

3. INSTALL ALL CONDUCTORS AS PER MANUFACTURER'S RECOMMENDATIONS.

ELECTRICAL RISER KEYED NOTES

ER1

REFER TO PANEL SCHEDULE FOR ADDITIONAL PANEL AND CIRCUIT

DETAILS.

ER2

DISCONNECT CONDUCTORS FROM PANELBOARD AND PULL BACK TO

NEAREST JUNCTION BOX. PROVIDE NEW AS NECESSARY. PREPARE TO

EXTEND TO NEW PANELBOARD.

ER3

SPLICE AND EXTEND CONDUCTORS FROM EXISTING BRANCH CIRCUITS TO

NEW PANEL. REFER TO SCHEDULE FOR PANEL A FOR ADDITIONAL BRANCH

CIRCUIT INFORMATION. MINIMIZE AND COORDINATE REQUIRED DOWNTIME

WITH OWNER.

ER4

EXTEND EXISTING FEEDER TO NEW PANEL, SPLICING CONDUCTORS AS

REQUIRED. NEW CONDUCTORS SHALL MATCH EXISTING FEEDER

CHARACTERISTICS. REFER TO PANEL SCHEDULE FOR ADDITIONAL

INFORMATION. MINIMIZE AND COORDINATE REQUIRED DOWNTIME WITH

OWNER.

COPPER CONDUCTOR

AND CONDUIT SIZING CHART

CONDUCTORS (THWN-2) CONDUIT PARALLEL

RUNS

PHASE NEUTRAL GROUND EMT SCH 80

15/2 (2) #12 AWG #12 AWG 3/4" 1

20/2 (2) #12 AWG #12 AWG 3/4" 1

25/2 (2) #10 AWG #10 AWG 3/4" 1

30/2 (2) #10 AWG #10 AWG 3/4" 1

200/3 (2) 3/0 AWG #6 AWG 13/0 AWG

3/4"

3/4"

3/4"

3/4"

2" 2"

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

NOT SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

DESIGNER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

L0W VOLTAGE/SECURITY:

IMEG

623 26TH AVENUE

ROCK ISLAND, IL 61201

309.781.3770

PETE MCGHEE

IRRIGATION:

AQUA ENGINEERING

300 BOARDWALK DRIVE

UNIT 4B

FORT COLLINS,CO 80525

970.372.6104

JD LEONARD

GEOTECHNICAL:

TERRACON

6460 HILLER STREET

SUITE A

EL PASO, TX 79925

915.778.5233

IVAN AVELAR

FIRE ALARM:

IMEG

623 26TH AVENUE

ROCK ISLAND, IL 61201

309.781.3770

MATT SNYDER

C U s e rs \a w e b e r\

D o c u m e n ts \1

-A

D M

IN

-M

-R a w e b e r9

S

.r v t

/1 /2

:1

:3

P M

2101-EP111

ADMIN BLDG - POWER PLANS FT BLISS NATIONAL CEMETERY

EXPANSION

5200 FRED WILSON AVENUE, EL PASO, TEXAS

886CM3026

JUNE 15, 2026 ATW DIL

18528

1/4" = 1'-0"

BASEMENT POWER PLAN

Notes: G=GFI M=MOTORIZED E=EXISTING ST=SHUNT TRIP A=ARC FAULT H=HANDLE LOCK

Demand Current: 40 A

Demand Load: 10 kVA

Connected Current: 40 A

Receptacle - General 1620 VA 100.00% 1620 VA Connected Load: 10 kVA

Other 8080 VA 100.00% 8080 VA Panel Totals

Load Classification Connected Factor Demand

Connected Current: 44 A 37 A

Connected Load: 5 kVA 4 kVA

53 Space -- 1 -- 0 54

51 Space -- 1 -- 0

2 30 EXTERNAL SPD

49 Space -- 1 -- -- 1 -- Space 50

47 Spare 20 1 0 -- 1 -- Space 48

45 Spare 20 1 0 0 1 20 Spare 46

43 EXTERIOR RECEPT 20 1 180 0 1 20 Spare 44

41 TE RECEPTS 20 1 720 360 1 20 AC-SCP-1 42

39 L5-30R RECEPT 30 1 3500 180 40

37 L5-30R RECEPT 30 1 3500 180

2 20 CU-1

35 SHREDDER 20 1 180 360 1 20 FACP 36

33 PRINTER 20 1 180 360 1 20 FA BELL 34

31 0 0 E 1 15 WOMENS RESTROOM HAND DRYER 32

A/C 20 2 E

0 0 E 1 15 EXTERIOR GFCI UNIT 30

27 0 0 E 1 15 EXISTING LOAD 28

AC UNIT 30 2 E

0 0 E 1 20 SEWER 26

23 QUAD OUTLET 20 1 E 0 0 E 1 20 SEWER 24

21 ADMIN OUTLETS 20 1 E 0 0 E 1 30 AC CONDENSER 22

19 MECH LIGHTS/OUTLETS 20 1 E 0 0 E 1 30 AC CONDENSER 20

17 LAN OUTLET 20 1 E 0 0 E 1 20 KITCHEN OUTLET 18

15 ADMIN CUBICLE OUTLETS 20 1 E 0 0 E 1 20 FRIDGE OUTLET 16

13 MGR OUTLET 20 1 E 0 0 E 1 20 OPS COPY/FAX OUTLETS 14

11 CORR/BATH LIGHTS/OUTLETS 20 1 E 0 0 E 1 20 KIT. OUTLET 12

9 CONF OUTLETS 20 1 E 0 0 E 1 20 EXISTING LOAD 10

7 WAIT OUTLETS 20 1 E 0 0 E 1 20 EXISTING LOAD 8

5 EXISTING LOAD 20 1 E 0 0 E 1 20 OPS WINDOW OUTLET 6

3 STAFF LIGHTS & BLOWER 20 1 E 0 0 E 1 30 FLAG POLE LIGHTS 4

1 ADMIN LIGHTS 20 1 E 0 0 E 1 30 FLAG POLE LIGHTS 2

Ckt Description Trip (A) Poles FN/Note A B FN/Note Poles Trip (A) Description Ckt

NOTES: NEW BRANCH PANEL. LOADS TAGGED 'E' ARE EXISTING LOADS TO BE RECONNECTED TO NEW PANELBOARD.

Enclosure: NEMA 1

Mounting: Surface Features & Modifications: -

Supply: Feed-Thru Lugs: No SCCR: 22 kA

Location: EXISTING STORAGE/ELEC/OIT 117 Neutral: 100% Mains FN/Note: -

Bus Rating: 200 A Mains Rating: 200 A

Panelboard: PANEL A Voltage: 240 V, 1Ø, 3W Mains Type: MLO

1/4" = 1'-0"

FIRST LEVEL POWER PLAN

ONE-LINE DIAGRAM DEMO

ONE-LINE DIAGRAM - NEW

Revisions: Date:

Addendum 1 10/12/2026

Sheets
2101-EL111 - ADMIN BLDG - LIGHTING PLAN
2101-EP111 - ADMIN BLDG - POWER PLANS

File details come from the government source that posted it. Updated .