087100 DOOR HARDWARE_ADD1.pdf

PDF 166 KB Posted

Attached to
Fort Bliss National Cemetery, Gravesite Expansion and FCA Deficiencies
Solicitation number
36C78626B0028
Issued by

About this file

This is Section 08 71 00 (Door Hardware) of the specification documents for the Fort Bliss National Cemetery Gravesite Expansion project (VA Project 886CM3026) in El Paso, Texas, issued as Addendum 1 to the bid documents.

The specification establishes comprehensive requirements for door hardware installation and operation, including hinges, continuous hinges, door closers, door stops, floor door holders, locks and latches, keys, kick plates, thresholds, wire guards, and miscellaneous hardware. All hardware must comply with ABAAS accessibility standards and relevant ANSI/BHMA standards. Mortise locksets must be Series 1000 minimum Grade 2 with stainless steel lever handles; cylindrical locksets must be Series 4000 Grade I. All cylinders require interchangeable removable cores keyed to the Schlage "C" keyway master key system. Door closers must conform to ANSI A156.4 Grade 1, be non-handed with full metal covers, and have surpassed 15 million cycles. Continuous hinges must comply with ANSI/BHMA A156.26 Grade 1-600 with stainless steel base metal. Warranties extend two years for most items, five years for locks and panic hardware, and ten years for door closers and continuous hinges. The specification includes detailed hardware sets (HW-1, HW-SH-1 through HW-SH-12, HW-G1, HW-OH-1) specifying components for individual doors and gates with manufacturer abbreviations (McKinney, ASSA ABLOY ACCENTRA, Rockwood, Schlage, Securitron, Best, and others). Multiple doors require electrified fail-secure locks with electric power transfers, position switches, and credential readers coordinated through Division 28 contractor. Hardware must be delivered in original containers with manufacturer identification, with samples required for non-previously-approved items. A preinstallation meeting is required at least 30 days before hardware installation, and final inspection requires verification of proper operation, maintenance procedures, and identification of any deteriorated items.

View the file

Other files

File Type Posted
4101-AE201_ADD1.pdf PDF
2101-AE201_ADD1.pdf PDF
3004-E-111_ADD1.pdf PDF
S02_Attachment - Geotechnical Engineering Report.pdf PDF
092400 PORTLAND CEMENT PLASTERING_ADD1.pdf PDF
073213 CLAY ROOF TILES_ADD1.pdf PDF
2101-AE101_ADD1.pdf PDF
S02_Attachment - DOL Payroll Form updated.pdf PDF
S05_Attachment - RFIs and Responses.pdf PDF
2101-AE111_ADD1.pdf PDF
CE121_ADD1.pdf PDF
S02_Attachment - Statement of Work revised 10.26.2026.pdf PDF
3004-ED111_ADD1.pdf PDF
050385 HISTORIC DECORATIVE FORMED METAL REPAIR_WR IR_ADD1.pdf PDF
LK111_ADD1.pdf PDF
000110 TABLE OF CONTENTS_ADD1.pdf PDF
LP111_ADD1.pdf PDF
3003-ED111_ADD1.pdf PDF
2101-AD201_ADD1.pdf PDF
3003-E-501_ADD1.pdf PDF
S02_Attachment - SF 1413 updated.pdf PDF
S06_36C78626B0028 0002.pdf PDF
CB501_ADD1.pdf PDF
S02_Attachment - Addendum 1 Summary of Changes.pdf PDF
3003-E-111_ADD1.pdf PDF
2101-EL111_ADD1.pdf PDF
281300 PHYSICAL ACCESS CONTROL SYSTEM_ADD1.pdf PDF
2101-EP111_ADD1.pdf PDF
CB502_ADD1.pdf PDF
S04_Attachment - Site Visit Attendance Roster.pdf PDF
S06_36C78626B0028 Amend. 0001.pdf PDF
Fort Bliss Gravesite Expansion BD Part 1.pdf PDF
S02_Attachment - Limitations on Subcontracting Cert.docx DOCX document
S02_Attachment - DOL Payroll Form.pdf PDF
Fort Bliss Gravesite Expansion BD Part 3.pdf PDF
Fort Bliss Gravesite Expansion BD Part 5.pdf PDF
Fort Bliss Gravesite Expansion BD Part 10.pdf PDF
Fort Bliss Gravesite Expansion - Specifications Full Book.pdf PDF
Fort Bliss Gravesite Expansion BD Part 9.pdf PDF
Fort Bliss Gravesite Expansion BD Part 8.pdf PDF
S02_Attachment - 886CM3026 Fort Bliss NC SOW.pdf PDF
Fort Bliss Gravesite Expansion BD Part 4.pdf PDF
Fort Bliss Gravesite Expansion BD Part 7.pdf PDF
S02_36C78626B0028 Solicitation.pdf PDF
S02_Attachment - Davis-Bacon Act Poster.pdf PDF
S02_Attachment - Standard Form 1413.pdf PDF
Fort Bliss Gravesite Expansion BD Part 2.pdf PDF
Fort Bliss Gravesite Expansion BD Part 11.pdf PDF
S02_Attachment - Price Schedule Sheet.pdf PDF
S02_Attachment - Wage Determination Heavy.pdf PDF
Show 40 more

Latest 50 of 52 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Fort Bliss National Cemetery VA Project 886CM3026

Gravesite Expansion Bid Documents

El Paso, TX 79906 Addendum 1

08 71 00-1

SECTION 08 71 00

DOOR HARDWARE

PART 1 - GENERAL

1.1 DESCRIPTION

Door hardware and related items necessary for complete installation and operation of doors.

1.2 RELATED WORK

Caulking: Section 07 92 00 JOINT SEALANTS.

Application of Hardware: Section 08 11 13, HOLLOW METAL DOORS AND FRAMES

Section 10 22 13, WIRE MESH PARTITIONS, Section 08 41 13 ALUMINUM FRAMED

ENTRANCES AND STOREFRONTS.

Card Readers: Section 28 13 00, PHYSICAL ACCESS CONTROL SYSTEMS.

Electrical: Division 26, ELECTRICAL.

Fire Detection: Section 28 31 00, FIRE DETECTION AND ALARM.

1.3 GENERAL

All hardware shall comply with ABAAS, (Architectural Barriers Act

Accessibility Standard) unless specified otherwise.

Provide rated door hardware assemblies where required by most current version of the International Building Code (IBC) and where doors are scheduled to be fire rated in the drawings or hardware sets specified.

Hardware for Labeled Fire Doors: Conform to requirements of NFPA 80 for labeled fire doors, as well as to other requirements specified. Provide hardware listed by UL, except where heavier materials, large size, or better grades are specified herein under paragraph HARDWARE SETS. In lieu of UL labeling and listing, test reports from a nationally recognized testing agency may be submitted showing that hardware has been tested in accordance with UL test methods and that it conforms to NFPA requirements. The word “FIRE” must be included as part of the certification on the Underwriters Laboratories label on exit devices to be used on fire doors.

Hardware for application on metal and wood doors and frames shall be made to standard templates. Furnish templates to the fabricator of these items in sufficient time so as not to delay the construction.

The following items shall be of the same manufacturer, except as otherwise specified:

1. Mortise locksets.

2. Hinges for hollow metal doors.

3. Surface applied overhead door closers.

4. Exit devices.

El Paso, TX 79906 Addendum 1

08 71 00-2

1.4 WARRANTY

Subject to the terms of FAR Clause 52.246-21, except that the Warranty period shall be two years in lieu of one year for all items except as noted below:

1. Locks, latchsets, and panic hardware: 5 years.

2. Door closers and continuous hinges: 10 years.

1.5 MAINTENANCE MANUALS

In accordance with Section 01 00 00, GENERAL REQUIREMENTS Article titled

"INSTRUCTIONS", furnish maintenance manuals and instructions on all door hardware. Provide installation instructions with the submittal documentation.

1.6 SUBMITTALS

Submittals shall be in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.

Hardware Schedule: AHC certified hardware consultant to prepare and submit hardware schedule in the following form:

Hardware

Item

Quantity Size Reference

Publication

Type No.

Finish Mfr.

Name and

Catalog

No.

Key

Control

Symbols

UL Mark

(if fire rated and listed)

ANSI/BHMA

Finish

Designation

Samples:

1. Samples: All hardware items (proposed for the project) that have not been previously approved by Builders Hardware Manufacturers

Association shall be submitted for approval. Tag and mark all items with manufacturer's name, catalog number and project number.

2. Samples are not required for hardware listed in the specifications by manufacturer's catalog number, if the contractor proposes to use the manufacturer's product specified.

Manufacturer’s Literature: For all components scheduled.

Record of opening force measurement for all doors equipped with closers

1.7 DELIVERY AND MARKING

Deliver items of hardware to job site in their original containers, complete with necessary appurtenances including screws, keys, and

El Paso, TX 79906 Addendum 1

08 71 00-3 instructions. Tag one of each different item of hardware and deliver to COR for reference purposes. Tag shall identify items by Project Specification number and manufacturer's catalog number. These items shall remain on file in

COR's office until all other similar items have been installed in project, at which time the COR will deliver items on file to Contractor for installation in predetermined locations on the project.

1.8 PREINSTALLATION MEETING

Convene a preinstallation meeting not less than 30 days before start of installation of door hardware. Require attendance of parties directly affecting work of this section, including Contractor and Installer, Architect, Project Engineer and VA Locksmith, Hardware Consultant, and Hardware

Manufacturer’s Representative. Review the following:

1. Inspection of door hardware.

2. Job and surface readiness.

3. Coordination with other work.

4. Protection of hardware surfaces.

5. Substrate surface protection.

6. Installation.

7. Adjusting.

8. Repair.

9. Field quality control.

10. Cleaning.

1.9 INSTRUCTIONS

Hardware Set Symbols on Drawings: Except for protective plates, door stops, mutes, thresholds and the like specified herein, hardware requirements for each door are indicated in Opening Schedules in the drawings . Hardware sets consist of letters (e.g., "HW") followed by a number. Each number designates a set of hardware items applicable to a door type.

Keying: All cylinders shall be keyed into existing Master Key System. Provide

Schlage large format “C” keyway type with removable keyway that are removable only with a special control key without disassembly of lockset. Key identification to be stamped on permanent keys rekeyed by the VA to the current Master key system once construction is complete.

1.10 APPLICABLE PUBLICATIONS

The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. In text, hardware items are referred to by series, types, etc., listed in such specifications and standards, except as otherwise

El Paso, TX 79906 Addendum 1

08 71 00-4 specified. Most current version of the listed publications at time of bidding applies, even if that differs from the version listed in this section.

ASTM International(ASTM):

F883-13.................Padlocks

American National Standards Institute/Builders Hardware Manufacturers

Association (ANSI/BHMA):

A156.1-06...............Butts and Hinges

A156.2-03...............Bored and Pre-assembled Locks and Latches

A156.4-08...............Door Controls (Closers)

A156.5-14...............Cylinders and Input Devices for Locks.

A156.6-05...............Architectural Door Trim

A156.8-05...............Door Controls-Overhead Stops and Holders

A156.12-05 .............Interconnected Locks and Latches

A156.13-05..............Mortise Locks and Latches Series 1000

A156.15-06..............Release Devices-Closer Holder, Electromagnetic and Electromechanical

A156.16-08..............Auxiliary Hardware

A156.17-04 .............Self-Closing Hinges and Pivots

A156.18-06..............Materials and Finishes

A156.20-06 .............Strap and Tee Hinges, and Hasps

A156.21-09..............Thresholds

A156.22-05..............Door Gasketing and Edge Seal Systems

A156.23-04..............Electromagnetic Locks

A156.25-07 .............Electrified Locking Devices

A156.26-06..............Continuous Hinges

A156.28-07 .............Master Keying Systems

A156.29-07 .............Exit Locks and Alarms

A156.30-03 .............High Security Cylinders

A156.36-10..............Auxiliary Locks

A250.8-03...............Standard Steel Doors and Frames

National Fire Protection Association (NFPA):

80-10...................Fire Doors and Other Opening Protectives

101-09..................Life Safety Code

Underwriters Laboratories, Inc. (UL):

Building Materials Directory (2008)

Architectural Barriers Act Accessibility Standards (ABAAS)

El Paso, TX 79906 Addendum 1

08 71 00-5

PART 2 - PRODUCTS

2.1 BUTT HINGES

ANSI A156.1. Provide only three-knuckle hinges, except five-knuckle where the required hinge type is not available in a three-knuckle version

(e.g., some types of swing-clear hinges). The following types of butt hinges shall be used for the types of doors listed, except where otherwise specified:

1. Interior Doors: Type A8112/A5112 for doors 900 mm (3 feet) wide or less.

Provide quantity and size of hinges per door leaf as follows:

1. Doors 1210 mm (4 feet) to 2260 mm (7 feet 5 inches) high: 3 hinges minimum.

2. Doors greater than 2260 mm (7 feet 5 inches) high: 4 hinges.

3. Doors up to 900 mm (3 feet) wide, standard weight: 114 mm x 114 mm

(4-1/2 inches x 4-1/2 inches) hinges.

4. Doors over 900 mm (3 feet) to 1065 mm (3 feet 6 inches) wide, standard weight: 127 mm x 114 mm (5 inches x 4-1/2 inches).

5. Doors over 1065 mm (3 feet 6 inches) to 1210 mm (4 feet), heavy weight: 127 mm x 114 mm (5 inches x 4-1/2 inches).

6. Provide heavy-weight hinges where specified.

See Articles "MISCELLANEOUS HARDWARE" and "HARDWARE SETS" for pivots and hinges other than butts specified above and continuous hinges specified below.

2.2 CONTINUOUS HINGES

ANSI/BHMA A156.26, Grade 1-600.

1. Listed under Category N in BHMA's "Certified Product Directory."

General: Minimum 0.120-inch- (3.0-mm-) thick, hinge leaves with minimum overall width of 4 inches (102 mm); fabricated to full height of door and frame and to template screw locations; with components finished after milling and drilling are complete

Continuous, Barrel-Type Hinges: Hinge with knuckles formed around a

Teflon-coated 6.35mm (0.25-inch) minimum diameter pin that extends entire length of hinge.

1. Base Metal for Hinges: Stainless steel.

2. Where required to clear adjacent casing, trim, and wall conditions and allow full door swing, provide wide throw hinges of minimum width required.

3. Provide with manufacturer’s cut-outs for separate mortised power transfers and/or mortised automatic door bottoms where they occur.

El Paso, TX 79906 Addendum 1

08 71 00-6

4. Where thru-wire power transfers are integral to the hinge, provide hinge with easily removable portion to allow easy access to wiring connections.

5. Where models are specified that provide an integral wrap-around edge guard for the hinge edge of the door, provide manufacturer’s adjustable threaded stud and machine screw mechanism to allow the door to be adjusted within the wrap-around edge guard.

2.3 DOOR CLOSING DEVICES

Closing devices shall be products of one manufacturer.

Closers shall not be installed on exterior or corridor side of doors.

Provide door closer accessories including custom templates, special mounting brackets, spacers and drop plates as required for proper installation. Provide through-bolt and security type fasteners as specified in the hardware sets.

Comply with manufacturer’s written recommendations for sizing of door closers depending on size of door, exposure to weather, and anticipated frequency of use.

Provide closers which have surpassed 15 million cycles.

Closers to be non-handed with full sized covers.

2.4 OVERHEAD CLOSERS

Conform to ANSI A156.4, Grade 1.

Closers shall conform to the following:

1. The closer shall have minimum 50 percent adjustable closing force over minimum value for that closer and have adjustable hydraulic back check effective between 60 degrees and 85 degrees of door opening.

2. Where specified, closer shall have hold-open feature.

3. Size Requirements: Provide multi-size closers, sizes 1 through 6, except where multi-size closer is not available for the required application.

4. Material of closer body shall be forged or cast.

5. Arm and brackets for closers shall be steel, malleable iron or high strength ductile cast iron.

6. Where closers are mounted in the Maintenance Building, provide closer body and arm assembly of stainless steel material.

7. Closers shall have full size metal cover; plastic covers will not be accepted.

El Paso, TX 79906 Addendum 1

08 71 00-7

8. Closers shall have adjustable hydraulic back-check, separate valves for closing and latching speed, adjustable back-check positioning valve, and adjustable delayed action valve.

9. Provide closers with any accessories required for the mounting application, including (but not limited to) drop plates, special soffit plates, spacers for heavy-duty parallel arm fifth screws, bull-nose or other regular arm brackets, longer or shorter arm assemblies, and special factory templating. Provide special arms, drop plates, and templating as needed to allow mounting at doors with overhead stops and/or holders.

10. Closer arms or backcheck valve shall not be used to stop the door from overswing, except in applications where a separate wall, floor, or overhead stop cannot be used.

11. Provide parallel arm closers with heavy duty rigid arm.

12. Where closers are to be installed on the push side of the door, provide parallel arm type except where conditions require use of top jamb arm.

13. Provide all surface closers with the same body attachment screw pattern for ease of replacement and maintenance.

14. All closers shall have a 1 ½” (38mm) minimum piston diameter.

2.5 DOOR STOPS

Conform to ANSI A156.16.

Provide door stops wherever an opened door or any item of hardware thereon would strike a wall, column, equipment or other parts of building construction. For concrete, masonry or quarry tile construction, use expansion shields for mounting door stops.

Where cylindrical locks with turn pieces or pushbuttons occur, equip wall bumpers Type L02251 (rubber pads having concave face) to receive turn piece or button.

Provide floor stops Type L02121 x 3, where specified, screwed into floor. Wall bumpers, where used, must be installed to impact the trim or the door within the leading half of its width. Floor stops, where used, must be installed within 4-inches of the wall face and impact the door within the leading half of its width.

At outswing doors where a floor stop can be installed in concrete, provide stop mated to concrete anchor set in 76mm (3-inch) core-drilled hole and filled with quick-setting cement.

El Paso, TX 79906 Addendum 1

08 71 00-8

Provide concealed overhead stops(surface-mounted where concealed cannot be used) where noted in the hardware sets at the end of this Section.

2.6 FLOOR DOOR HOLDERS

Conform to ANSI Standard A156.16. Provide extension strikes for Types

L01301 and L01311 holders where necessary.

2.7 LOCKS AND LATCHES

Conform to ANSI A156.2. Locks and latches for doors 45 mm (1-3/4 inch) thick or over shall have beveled fronts. Lock cylinders shall have either six or seven pins – match cemetery standard. Cylinders for all locksets shall be removable core type. Cylinders shall be furnished with construction removable cores and construction master keys. Cylinder shall be removable by special key. Construct all cores so that they will be interchangeable into the core housings of all mortise locks, rim locks, cylindrical locks, and any other type lock included in the Master Key System. Disassembly of lever or lockset shall not be required to remove core from lockset. Provide temporary keying device or construction core to allow opening and closing during construction and prior to the installation of final cores.

In addition to above requirements, locks and latches shall comply with following requirements:

1. Mortise Lock and Latch Sets: Conform to ANSI/BHMA A156.13. Mortise locksets shall be series 1000, minimum Grade 2. All locksets and latchsets shall have lever handles fabricated from cast stainless steel. General Contractor to field verify existing and provide sectional (lever x rose) lever design to match existing. No substitute lever material shall be accepted. All locks and latchsets shall be furnished with 122.55 mm (4-7/8-inch) curved lip strike and wrought box. Lock function F02 shall be furnished with emergency tools/keys for emergency entrance. Furnish armored fronts for all mortise locks. Where mortise locks are installed in high-humidity locations or where exposed to the exterior on both sides of the opening, provide non-ferrous mortise lock case.

2. Cylindrical Lock and Latch Sets: levers shall meet ADA (Americans with Disabilities Act) requirements. Cylindrical locksets shall be series 4000 Grade I. All locks and latchsets shall be furnished with

122.55 mm (4-7/8-inch) curved lip strike and wrought box. At outswing pairs with overlapping astragals, provide flat lip strip with 21mm

(7/8-inch) lip-to-center dimension. Provide lever design to match existing lever design.

El Paso, TX 79906 Addendum 1

08 71 00-9

3. Auxiliary locks shall be as specified under hardware sets and conform to ANSI A156.36.

2.8 ELECTROMAGNETIC LOCKS – NOT USED

2.9 ELECTRIC STRIKES – NOT USED

2.10 KEYS

Stamp all keys with change number and key set symbol. Furnish keys in quantities as follows:

Locks/Keys Quantity

Cylinder locks 2 keys each

Cylinder lock change key blanks

100 each different key way

Master-keyed sets 6 keys each

Control key 2 keys

2.11 KEY CABINET – NOT USED

2.12 KICK PLATES AND DOOR EDGING

Conform to ANSI Standard A156.6.

Provide protective plates and door edging as specified below:

1. Kick plates of metal, Type J100 series.

2. Provide kick plates where specified. Kick plates shall be 254 mm (10 inches) high, except in existing facilities, match height of existing kickplates in the same area. Contractor to field verify heights of existing kick plates prior to providing product submittals. Kick plates shall be minimum 1.27 mm (0.050 inches) thick. Provide kick plates beveled on all 4 edges (B4E). On push side of doors where jamb stop extends to floor, make kick plates 38 mm (1-1/2 inches) less than width of door. Extend all other kick plates to within 6 mm

(1/4 inch) of each edge of doors. Kick plates shall butt astragals.

For jamb stop requirements, see specification sections pertaining to door frames.

3. Provide stainless steel edge guards where so specified. Provide mortised type instead of surface type except where door construction and/or ratings will not allow. Provide edge guards of bevel and thickness to match door. Provide edge guards with factory cut-outs for door hardware that must be installed through or extend through the edge guard. Provide full-height edge guards except where door rating does not allow; in such cases, provide edge guards to height

El Paso, TX 79906 Addendum 1

08 71 00-10 of bottom of typical lockset armor front. Forward edge guards to door manufacturer for factory installation on doors.

2.13 THRESHOLDS

Conform to ANSI A156.21, mill finish extruded aluminum, except as otherwise specified. In existing construction, thresholds shall be installed in a bed of sealant with ¼-20 stainless steel machine screws and expansion shields. Furnish thresholds for the full width of the openings.

Provide with miter returns where threshold extends more than 12 mm (0.5 inch) beyond face of frame.

2.14 HINGED WIRE GUARDS (FOR WINDOWS, DOORS) AND WIRE PARTITION DOORS

Butt hinges, type A8133 (special swaging) 100 mm by 90 mm (4 inches by

3-1/2 inches), Finish US2C.

1. 3 hinges for guards over 1060 mm (3-1/2 feet) high.

2. 2 hinges for guards less than 1060 mm (3-1/2 feet) high.

Conform to ANSI A156.36. Lock Type E06081 for guards and Type E06061 for partitions.

1. Keying: Except as noted otherwise, key locks like entrance door or space wherein partitions are located except as otherwise specified.

2.15 MISCELLANEOUS HARDWARE

Access Doors (including Sheet Metal Types): Except for fire-rated doors, equip each access door with Lock Type E07213, conforming to ANSI

A156.11. Key locks as directed. Ship lock prepaid to the door manufacturer.

Hinges shall be provided by door manufacturer.

Cylinders for Various Partitions and Doors: Key cylinders same as entrance doors of area in which partitions and door occur. Provide cylinders to operate locking devices where specified for following partitions and doors:

1. Fire-rated access doors-Engineer's key set.

Mutes: Conform to ANSI A156.16. Provide door silencers Type L03011 or

L03021, depending on frame material, of light gray color on each door frame, except at fire-rated frames. Furnish 3 mutes for single doors.

2.16 FINISHES

Exposed surfaces of hardware shall have ANSI A156.18, finishes as specified below. Finishes on all hinges, pivots, closers, thresholds, etc., shall be as specified below under "Miscellaneous Finishes." For field painting

(final coat) of ferrous hardware, see Section 09 91 00, PAINTING.

626 or 630: All surfaces on exterior and interior of buildings, except where other finishes are specified.

El Paso, TX 79906 Addendum 1

08 71 00-11

Miscellaneous Finishes:

1. Hinges --interior doors: 652 or 630.

2. Door Closers: Factory applied paint finish. Dull or Satin Aluminum color.

3. Thresholds: Mill finish aluminum.

4. Other primed steel hardware: 600.

Hardware Finishes for Existing Buildings: U.S. Standard finishes shall match finishes of hardware in (similar) existing space except where otherwise specified.

Special Finish: Exposed surfaces of hardware for dark bronze anodized aluminum doors shall have oxidized oil rubbed bronze finish (dark bronze) finish on door closers shall closely match doors.

2.17 BASE METALS

Apply specified U.S. Standard finishes on different base metals as following:

Finish Base Metal

652 Steel

626 Brass or bronze

630 Stainless steel

PART 3 - EXECUTION

3.1 HARDWARE HEIGHTS

For existing buildings locate hardware on doors at heights to match existing hardware. The Contractor shall visit the site, verify location of existing hardware and submit locations to VA COR for approval.

3.2 INSTALLATION

Closer devices, including those with hold-open features, shall be equipped and mounted to provide maximum door opening permitted by building construction or equipment. Closers shall be mounted on side of door inside rooms, inside stairs, and away from corridors. Where closers are mounted on doors they shall be mounted with hex nuts and bolts; foot shall be fastened to frame with machine screws. Door opening force shall not exceed 22.2 N (5 pounds) maximum in accordance with ABAAS. Measure and adjust opening force for all doors equipped with closers.

El Paso, TX 79906 Addendum 1

08 71 00-12

Hinge Size Requirements:

Door Thickness Door Width Hinge Height

45 mm (1-3/4 inch) 900 mm (3 feet) and less 113 mm (4-1/2 inches)

45 mm (1-3/4 inch) Over 900 mm (3 feet) but not more than 1200 mm (4 feet)

125 mm (5 inches)

Hinge leaves shall be sufficiently wide to allow doors to swing clear of door frame trim and surrounding conditions.

Where new hinges are specified for new doors in existing frames or existing doors in new frames, sizes of new hinges shall match sizes of existing hinges; or, contractor may reuse existing hinges provided hinges are restored to satisfactory operating condition as approved by COR. Existing hinges shall not be reused on door openings having new doors and new frames.

Coordinate preparation for hinge cut-outs and screw-hole locations on doors and frames.

Hinges Required Per Door:

Door Description Number butts

Doors over 1500 mm (5 ft) high and not over 2280 mm

(7 ft 6 in) high

3 butts

Doors over 2280 mm (7 feet 6 inches) high 4 butts

Fastenings: Suitable size and type and shall harmonize with hardware as to material and finish. Provide machine screws and lead expansion shields to secure hardware to concrete, ceramic or quarry floor tile, or solid masonry.

Fiber or rawl plugs and adhesives are not permitted. All fastenings exposed to weather shall be of nonferrous metal.

After locks have been installed; show in presence of COR that keys operate their respective locks in accordance with keying requirements. (All keys, Master Key level and above shall be sent Registered Mail to the Cemetery

Director along with the bitting list. Also a copy of the invoice shall be sent to the COR for his records.) Installation of locks which do not meet specified keying requirements shall be considered sufficient justification for rejection and replacement of all locks installed on project.

3.3 FINAL INSPECTION

Installer to provide letter to VA Resident Engineer that upon completion, installer has visited the Project and has accomplished the following:

El Paso, TX 79906 Addendum 1

08 71 00-13

1. Re-adjust hardware.

2. Evaluate maintenance procedures and recommend changes or additions, and instruct VA personnel.

3. Identify items that have deteriorated or failed.

4. Submit written report identifying problems.

3.4 DEMONSTRATION

Demonstrate efficacy of mechanical hardware and electrical, and electronic hardware systems, including adjustment and maintenance procedures, to satisfaction of Resident/Project Engineer and VA Locksmith.

3.5 HARDWARE SETS

Following sets of hardware correspond to hardware sets shown on drawings. Only those hardware sets that are shown on drawings will be required. Disregard hardware sets listed in specifications but not shown on drawings.

Hardware Consultant working on a project will be responsible for providing additional information regarding these hardware sets. The numbers shown in the following sets come from BHMA standards.

120 volt power if required shall be provided by electrical contractor.

120 volt power required if magnetic locks or automatic openers are scheduled.

D. The hardware sets represent the design intent and direction of the Owner and Architect. They are a guideline only and should not be considered a detailed hardware schedule. Discrepancies, conflicting hardware and missing items shall be brought to the attention of the Architect with correction made prior to the bidding process. Omitted items not included in a hardware set should be scheduled with the appropriate hardware required for proper application and functionality.

1.Quantities listed are for each pair of doors or for each single door.

2. The supplier is responsible for handing and sizing all products.

3. Where multiple options for a piece of hardware are given in a single line item, the supplier shall provide the appropriate application for the opening.

4. At existing openings with new hardware, the supplier shall field inspect existing conditions prior to the submittal stage to verify the specified hardware will work as required. Provide alternate solutions and proposals as needed.

El Paso, TX 79906 Addendum 1

08 71 00-14

5. Manufacturer’s Abbreviations:

1. MK – McKinney

2. YA – ASSA ABLOY ACCENTRA

3. OT – OTHER

4. HS – Hes

5. RO – ROCKWOOD

6. PE – PEMKO

7. SC - Schlage

7. SU – Securitron

8. BE - Best

INTERIOR SINGLE DOORS

HW-1

PIC Restroom, Building 3004, Door 101

Each Door to Have: NON-RATED

3 Hinges (A8112) TA714 US26D MK

1 Storeroom Lock (F07) AUR 8805FL Temp Core 626 YA

1 Interchangeable Core LFIC – Coordinate with Owner 26 SC to Match Facility Standard

1 Surface Closer (C02021-PT4G) 5831 689 YA

3 Silencers (L03011) 608 RO

1 Kick Down (L01382) 461 US26D RO

HW-SH-1 (TE Rooms Only)

Administration, Building 2101, Door 115

Maintenance Office, Building 3003, Door 101

Each Interior Door to Have: RATED 45 MIN

1 Continuous Hinge(A51331BxHGxAS)HG305 CTP AS 630 MR

(with power transfer prep)

1 Fail Secure Lock (F07,E01,E06) AUR 8891FL Temp Core REX 630 YA

1 Electric Power Transfer CEPT-10 SU

1 Interchangeable Core LFIC – Coordinate with Owner 26 SC

El Paso, TX 79906 Addendum 1

08 71 00-15

To Match Facility Standard

1 Surface Closer C02021-PT4G 5831 689 YA

1 Kick Plate (J102) K1050 10" high CSK BEV US32D RO

1 Adhesive Gasketing (R0Y154) S88BL NGP

1 Edge Guard (J208M / J211) 310B/302B(UL Label as Required)US32D RO

1 Frame Harness QC-C1500 MK

1 Door Harness QC-C___ MK

1 Position Switch (E08) BY SECURITY INTEGRATOR OT

1 Credential Reader BY SECURITY INTEGRATOR OT

1 Power Supply BY SECURITY INTEGRATOR OT

Notes: Conduit, backboxes and rough-in for access control components by

Division 26 Electrical Contractor. Division 28 contractor to provide all access control components, devices, wiring and connections required for fully functional system in accordance with control scheme. Credential Reader by division 28.

Operation:

• Door is normally closed, latched and locked.

• Presenting valid credential or key override activates electrified lock and allows for ingress.

• Door position switch will report the doors OPEN/CLOSED status to access control and intrusion alarm systems.

• Door remains locked when power fails.

• Free egress at all times from the unsecured side (inside the TE Room).

• When a proper credential is presented to the Credential Reader (by Others) the lever on the secure side of the opening will be momentarily released to allow entry.

El Paso, TX 79906 Addendum 1

08 71 00-16

HW-SH-2

Administration, Building 2101, Door 100.1

Each Exterior Door to Have: NON-RATED

1 Continuous Hinge FM300 CTP (Size as Req.) 630 MR

1 Fail Secure Lock (F07) 45H7-TD15H (IC CORE PATD) 630 BE

1 Electric Power Transfer CEPT-10 SU

1 Interchangeable Core LFIC – Coordinate with Owner 26 SC

To Match Facility Standard

1 Surface Closer (C02021-PT4G) 5831 689 YA

1 Gasketing By Aluminum Frame Mfg. OT

1 Sweep (R3B434) 315CN PE

1 Threshold (J32100) 172A PE

1 Frame Harness QC-C1500P MK

1 Door Harness QC-C___ MK

1 Position Switch (E08) BY SECURITY INTEGRATOR OT access control components, devices, wiring and connections required for fully

• Presenting valid credential or key override activates electrified lock and allows for ingress.

• Door position switch will report the doors OPEN/CLOSED status to access control and intrusion alarm systems.

• Door remains locked when power fails.

• Free egress at all times from the unsecured side.

• When a proper credential is presented to the Credential Reader (by Others)

El Paso, TX 79906 Addendum 1

08 71 00-17

HW-SH-3

Maintenance Office Building 3003, Door E01

1 Fail Secure Lock (F07,E01,E06) AUR 8891FL REX Temp LFIC 630 YA

1 Electric Rim Exit, Nightlatch 6100ED B MELR 121NL 630 YA

(Type 1, 03, E04)

1 Electric Power Transfer CEPT-10 SU

1 Interchangeable Core LFIC – Coordinate with Owner 26 SC

To Match Facility Standard

1 Surface Closer (C02021-PT4G) 5831 689 YA

1 Gasketing By Aluminum Frame Mfg. OT

1 Sweep (R3B434) 315CN PE

1 Threshold (J32100) 172A PE

1 Frame Harness QC-C1500P MK

1 Door Harness QC-C___ MK

1 Position Switch (E08) BY SECURITY INTEGRATOR OT access control components, devices, wiring and connections required for fully

• Presenting valid credential or key override activates electrified lock and allows for ingress.

• Door position switch will report the doors OPEN/CLOSED status to access control and intrusion alarm systems.

• Door remains locked when power fails.

El Paso, TX 79906 Addendum 1

08 71 00-18

• Free egress at all times from the unsecured side.

• When a proper credential is presented to the Credential Reader (by Others)

HW-SH-4

Maintenance Office, Building 3003, Door F03

1 Fail Secure Lock (F07,E01,E06) AUR 8891FL REX Temp LFIC 630 YA

1 Electric Power Transfer CEPT-10 SU

1 Interchangeable Core LFIC – Coordinate with Owner 26 SC

To Match Facility Standard

1 Surface Closer (C02021-PT4G) 5801 689 YA

1 Gasketing (R3E164) 303AS (HEAD/JAMBS) PE

1 Sweep (R3B434) 315CN PE

1 Threshold (J32100) 172A PE

1 Frame Harness QC-C1500P MK

1 Door Harness QC-C___ MK

1 Position Switch (E08) BY SECURITY INTEGRATOR OT access control components, devices, wiring and connections required for fully

• Presenting valid credential or key override activates electrified lock and allows for ingress.

El Paso, TX 79906 Addendum 1

08 71 00-19

• Door position switch will report the doors OPEN/CLOSED status to access control and intrusion alarm systems.

• Door remains locked when power fails.

• Free egress at all times from the unsecured side.

• When a proper credential is presented to the Credential Reader (by Others)

HW-SH-5

Administration, Building 2101, Door 100.2

Each Interior Door to Have: NON-RATED

1 Fail Secure Lock (F07,E01,E06) AUR 8891FL REX Temp LFIC 630 YA

1 Electric Power Transfer CEPT-10 SU

1 Interchangeable Core LFIC – Coordinate with Owner 26 SC

To Match Facility Standard

1 Surface Closer (C02021-PT4G) 5801 689 YA

1 Door Stop(L02251) 403 US26D RO

1 Gasketing By Aluminum Frame Manufacturer OT

1 Frame Harness QC-C1500P MK

1 Door Harness QC-C___ MK

1 Position Switch (E08) BY SECURITY INTEGRATOR OT access control components, devices, wiring and connections required for fully

El Paso, TX 79906 Addendum 1

08 71 00-20

• Presenting valid credential or key override activates electrified lock and allows for ingress.

• Door position switch will report the doors OPEN/CLOSED status to access control and intrusion alarm systems.

• Door remains locked when power fails.

• Free egress at all times from the unsecured side.

• When a proper credential is presented to the Credential Reader (by Others)

HW-SH-6

Administration, Building 2101, Door 113

Each Interior Door to Have: NON-RATED

1 Fail Secure Lock (F07,E01,E06) AUR 8891FL REX Temp LFIC 630 YA

1 Electric Power Transfer CEPT-10 SU

1 Interchangeable Core LFIC – Coordinate with Owner 26 SC

To Match Facility Standard

1 Surface Closer (C02021-PT4G) 5801 689 YA

1 Kick Plate (J102) K1050 10” high CSK BEV US32D RO

1 Door Stop (L02251/L02121) 403/470 US26D RO

3 Silencers (L03011) 608 RO

1 Frame Harness QC-C1500P MK

1 Door Harness QC-C___ MK

1 Position Switch (E08) BY SECURITY INTEGRATOR OT access control components, devices, wiring and connections required for fully

El Paso, TX 79906 Addendum 1

08 71 00-21

Operation:

• Door is normally closed, latched and locked.

• Presenting valid credential or key override activates electrified lock and allows for ingress.

• Door position switch will report the doors OPEN/CLOSED status to access control and intrusion alarm systems.

• Door remains locked when power fails.

• Free egress at all times from the unsecured side.

• When a proper credential is presented to the Credential Reader (by Others)

HW-SH-10 (Exit Only w/ Door Position Switch)

Maintenance Office, Building 3003, Door F10

1 Mortise lock (F31) w/ AUR 8828 630 YA

Active Interior Lever and blank plate on exterior to cover both holes

1 Interchangeable Core LFIC – Coordinate with Owner 26 SC

To Match Facility Standard

1 Door Position Switch(E08) BY SECURITY INTEGRATOR (DIV 28) OT

• Door is always locked from the building exterior (exit-only function)

• Door is always unlocked from the building interior to provide immediate egress

HW-SH-11 (Door Position Switch Only)

Maintenance Office, Building 3003, Door F11 and F12

El Paso, TX 79906 Addendum 1

08 71 00-22

HW-SH-12 (Exit Only w/ Door Position Switch)

Administration, Building 2101, Door 111

1 Existing thumbturn to remain

1 blank dummy cylinder for exterior (blank color to match storefront finish)

1 Interchangeable Core LFIC – Coordinate with Owner 26 SC

To Match Facility Standard

• Door is always locked from the building exterior (exit-only function)

• Door is always unlocked from the building interior, do not need key to exit

• Door swings inward (existing condition)

SINGLE GATES (WIRE MESH)

HW-G1

Administration, Building 2101

Each Gate to Have: NON-RATED

Hinges w/ power transfer prep BY WIRE MESH PARTITION MANUFACTURER OT

1 Fail Secure Lock 70 68-8271(24 VDC)RX LNL X D Knob X US10B

(F12, E02, E06) Temp Core REX 626 YA

1 Interchangeable Core LFIC – Coordinate with Owner 26 SC

To Match Facility Standard

1 Armor Loop Power Transfer TSB SU

1 Weldable Panic Box

1 Anti-Vandal Pull

1 Rim Panic Device TYPE 1 F03 LESS TRIM

1 Door Coordinator TSB-C SU

1 Door Spring 452 D4 MK

1 Frame Harness QC-C1500P MK

1 Door Harness QC-C___ MK

1 Position Switch (E08) BY SECURITY INTEGRATOR OT

El Paso, TX 79906 Addendum 1

08 71 00-23

Balance of hardware by wire mesh supplier.

access control components, devices, wiring and connections required for fully

• Presenting valid credential or key override activates electrified lock and allows for ingress.

• Door position switch will report the doors OPEN/CLOSED status to access control and intrusion alarm systems.

• Door remains locked when power fails.

• Free egress at all times from the unsecured side (inside the TE Room).

• When a proper credential is presented to the Credential Reader (by Others)

E. OVERHEAD COILING DOORS

HW-OH-1

Each Existing Overhead Door to Have: NON-RATED

- - - E N D - - -

File details come from the government source that posted it. Updated .