3003-E-501_ADD1.pdf
PDF 324 KB Posted
- Solicitation number
- 36C78626B0028
About this file
This is an electrical riser diagram and schedule document for a maintenance building renovation at Fort Bliss National Cemetery in El PASO, Texas. The document serves as bid documents for the U.S. Department of Veterans Affairs and includes detailed electrical specifications, panel schedules, conductor sizing charts, and a lighting fixture schedule.
The project involves electrical modifications to existing infrastructure, including two main panelboards: Panel A (existing EATON PRL-1A, 400A, 208/120V, 3-phase) and Panel B (new, 400A, 208V, 3-phase with 22kA SCCR rating). Key equipment requiring electrical service includes HVAC systems (heat pump, condensing unit, AC units), vehicle lift, air compressor, welding equipment, hand dryers, lighting circuits, receptacles, and fuel pumps. Panel B will receive a subfeed from Panel A with existing loads to be reconnected. The document specifies copper THWN-2 conductors with sizing ranging from #12 AWG to 3/0 AWG and conduit sizing from 1/2" to 2-1/2" EMT or Schedule 80. General notes require strategic coordination of electrical power outages with the owner, maintenance of NEC clearances, adherence to manufacturer installation guidelines, and external surge protection device installation. The document also includes a lighting fixture schedule specifying a Lithonia CLX-L48 48-foot LED linear fixture (4,000 lumens, 25.5 watts, 3500K/80 CRI). The consulting design firm is Anderson, with electrical coordination through IMEG.
View the file
Other files
Show 40 more
Latest 50 of 52 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELECTRICAL RISER GENERAL
NOTES
1. ELECTRICAL POWER OUTAGES, IF REQUIRED, SHOULD BE STRATEGICALLY
MINIMIZED AND SCHEDULED CLOSELY WITH OWNER. CHANGEOVERS COULD BE
REQUIRED TO OCCUR AT ANY HOUR.
2. MAINTAIN ALL SERVICE CLEARANCES REQUIRED BY THE NEC.
3. INSTALL ALL CONDUCTORS AS PER MANUFACTURER'S RECOMMENDATIONS.
4. EXTERNAL MOUNTED SURGE PROTECTION DEVICES SHALL BE INSTALLED PER
MANUFACTURER'S GUIDELINES.
ELECTRICAL RISER KEYED NOTES
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
ER1
REFER TO PANEL SCHEDULE FOR ADDITIONAL PANEL AND CIRCUIT
DETAILS.
ER2
PULL BACK CIRCUIT TO NEAREST JUNCTION BOX. PROVIDE NEW AS
NECESSARY. PREPARE TO EXTEND TO NEW PANELBOARD.
ER3
SPLICE AND EXTEND CONDUCTORS FROM EXISTING BRANCH CIRCUITS TO
NEW PANEL. REFER TO SCHEDULES FOR PANEL A AND PANEL B FOR
ADDITIONAL BRANCH CIRCUIT INFORMATION.
UTILITY TRANSFOMER
WITH
208/120V SECONDARY
30A-3P
EX
M
EX PANEL A
400A, 208/120V, 3PH, 4W
EX UTILITY METER
EXISTING UTILITY FEED EX
400A-3P
15A-2P
EX J HAND DRYER WOMENS
EX J WELDING EQUIPMENT
20A-3P
EX
EX BRANCH
CIRCUITS TO REMAIN
ER1
EX 400A DISCONNECT
20A-2P
ER PANEL B
400A, 240/120V, 3PH, 4W
40A-2P
EX J GATE FENCE
EX J NEW AC UNIT
20A-2P
EX
EX BRANCH
CIRCUITS TO REMAIN
ER1
ER2
J
J
J
TYPICAL ALL BRANCH
CIRCUITS
SUB FEED/ FEED-THROUGH
60A-3P
EX J HEAT PUMP
60A-3P
EX J CONDENSING UNIT
30A-2P
EX J VEHICLE LIFT
30A-3P
EX J AIR COMPRESSOR
20A-2P
EX J HAND DRYER MENS
20A-3P
EX J A/C UNIT
ER
UTILITY TRANSFOMER
WITH
208/120V SECONDARY
30A-3P
EX
M
EX PANEL A
400A, 208/120V, 3PH, 4W
EX UTILITY METER
EXISTING UTILITY FEED EX
400A-3P
15A-2P
EX J HAND DRYER WOMENS
EX J WELDING EQUIPMENT
20A-3P
EX
EX BRANCH
CIRCUITS TO REMAIN
ER1
EX 400A DISCONNECT
20A-2P
PANEL B
400A, 208/120V, 3PH, 4W
SCCR: 22,000A
40A-2P
EX J GATE FENCE
EX J NEW AC UNIT
20A-1P
EX
EX BRANCH
CIRCUITS TO REMAIN
ER1
ER3
J
J
J
TYPICAL ALL BRANCH
CIRCUITS
SUB FEED
60A-3P
EX J HEAT PUMP
60A-3P
EX J CONDENSING UNIT
30A-2P
EX J VEHICLE LIFT
30A-3P
EX J AIR COMPRESSOR
20A-2P
EX J HAND DRYER MENS
20A-3P
EX J A/C UNIT
400/4
30A-1P
30/2 J L5-30R RECEPT
30A-1P
30/2 J L5-30R RECEPT
COPPER CONDUCTOR
AND CONDUIT SIZING CHART
CONDUCTORS (THWN-2) CONDUIT PARALLEL
RUNS
PHASE NEUTRAL GROUND EMT SCH 80
15/2 (2) #12 AWG #12 AWG 1/2" 3/4" 1
20/2 (2) #12 AWG #12 AWG 1/2" 3/4" 1
25/2 (2) #10 AWG #10 AWG 1/2" 3/4" 1
30/2 (2) #10 AWG #10 AWG 1/2" 3/4" 1
COPPER CONDUCTOR
AND CONDUIT SIZING CHART
CONDUCTORS (THWN-2) CONDUIT PARALLEL
RUNS
PHASE NEUTRAL GROUND EMT SCH 80
(3) 3/0 AWG 3/0 AWG #3 AWG 2" 2-1/2" 2400/4
40/2 13/4" 1"(2) #8 AWG #10 AWG-
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
NOT SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
DESIGNER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
L0W VOLTAGE/SECURITY:
IMEG
623 26TH AVENUE
ROCK ISLAND, IL 61201
309.781.3770
PETE MCGHEE
IRRIGATION:
AQUA ENGINEERING
300 BOARDWALK DRIVE
UNIT 4B
FORT COLLINS,CO 80525
970.372.6104
JD LEONARD
GEOTECHNICAL:
TERRACON
6460 HILLER STREET
SUITE A
EL PASO, TX 79925
915.778.5233
IVAN AVELAR
FIRE ALARM:
IMEG
623 26TH AVENUE
ROCK ISLAND, IL 61201
309.781.3770
MATT SNYDER
C U s e rs \a w e b e r\
D o c u m e n ts
\1
-M A
IN
T
-M -R a w e b e r9
S
.r v t
/1 /2
:0
:4
P M
3003-E-501
MAINTENANCE BLDG - ELECTRICAL
SCHEDULES AND DETAILS
FT BLISS NATIONAL CEMETERY
EXPANSION
5200 FRED WILSON AVENUE, EL PASO, TEXAS
886CM3026
JUNE 15, 2026 ATW DIL
18528
Notes: G=GFI M=MOTORIZED E=EXISTING ST=SHUNT TRIP A=ARC FAULT H=HANDLE LOCK
Demand Current: 51 A
Demand Load: 18 kVA
Connected Current: 51 A
Receptacle - General 1080 VA 100.00% 1080 VA Connected Load: 18 kVA
Other 17360 VA 100.00% 17360 VA Panel Totals
Load Classification Connected Factor Demand
Connected Current: 82 A 82 A 9 A
Connected Load: 9 kVA 9 kVA 1 kVA (Includes load connected via feed-thru lugs.)
A-41 0 0 A-42
A-39
HAND DRYER MENS 20 2 E
0 0 A-40
A-37 GARAGE DOOR 20 1 e 0 0
E 3 20 A/C UNIT
A-38
A-35 GARAGE DOOR 20 1 E 0 0 E 1 20 UNIT HEATER A-36
A-33 OUTSIDE BREAK LIGHTS 20 1 E 0 0 A-34
A-31 GARAGE DOOR 20 1 E 0 0 A-32
A-29 GARAGE DOOR 20 1 E 0 0
E 3 30 AIR COMPRESSOR
A-30
A-27 0 0 E 1 20 Spare A-28
A-25
VEHICLE LIFT 30 2 E
0 0 A-26
A-23 EXISTING LOAD 20 1 E 0 0 A-24
A-21 GENERAL LIGHT 20 1 E 0 0
E 3 60 CONDENSING UNIT
A-22
A-19 OUTSIDE LIGHT 20 1 E 0 0 A-20
A-17 OUTSIDE LIGHT 20 1 E 0 0 A-18
A-15 OUTSIDE LIGHT 20 1 E 0 0
E 3 60 HEAT PUMP
A-16
A-13 STOCK/POL LIGHT 20 1 E 0 0 A-14
A-11 BAY 2 LIGHT 20 1 E 0 0 A-12
A-9 BATH LIGHT 20 1 E 0 0
E 3 30 WELDING EQUIPMENT
A-10
A-7 BREAK ROOM LIGHT 20 1 E 0 0 A-8
A-5 MAINT LIGHT 20 1 E 0 0
E 2 15 HAND DRYER WOMANS
A-6
A-3 MAINT LIGHT 20 1 E 0 0 E 1 20 GENERAL RECEPT A-4
A-1 MAINT. LIGHT 20 1 E 0 0 E 1 20 WATER FOUNTAIN A-2
Ckt Description Trip (A) Poles FN/Note Phase A
Load (VA) Phase B
Load (VA) Phase C
Load (VA) FN/Note Poles Trip (A) Description Ckt
NOTES: EXISTING EATON PANELBOARD TYPE PRL-1A.
Enclosure: NEMA 1
Mounting: Surface Features & Modifications: -
Supply: Feed-Thru Lugs: Yes SCCR: 10 kA
Location: EXISTING OFFICE/ ELEC 33 Neutral: 100% Mains FN/Note: -
Bus Rating: 400 A Mains Rating: 400 A
Panelboard: PANEL A Voltage: 208 V, 3Ø, 4W Mains Type: MLO
Notes: G=GFI M=MOTORIZED E=EXISTING ST=SHUNT TRIP A=ARC FAULT H=HANDLE LOCK
Demand Current: 51 A
Demand Load: 18 kVA
Connected Current: 51 A
Receptacle - General 1080 VA 100.00% 1080 VA Connected Load: 18 kVA
Other 17360 VA 100.00% 17360 VA Panel Totals
Load Classification Connected Factor Demand
Connected Current: 82 A 82 A 9 A
Connected Load: 9 kVA 9 kVA 1 kVA
107 Space -- 1 -- 0 108
105 Space -- 1 -- 0 106
103 Space -- 1 -- 0
3 30 EXTERNAL SPD
101 Spare 20 1 0 -- 1 -- Space 102
99 Spare 20 1 0 -- 1 -- Space 100
97 Spare 20 1 0 -- 1 -- Space 98
95 TE RECEPTS 20 1 720 0 1 20 Spare 96
93 L5-30R RECEPT 30 1 8500 0 1 20 Spare 94
91 L5-30R RECEPT 30 1 8500 0 1 20 Spare 92
89 AS-SCP-1 20 1 360 0 1 20 Spare 90
87 180 0 1 20 Spare 88
CU-1 20 2
180 0 1 20 Spare 86
83 FUEL PUMP DEISEL. 20 1 E 0 0 84
81 FIRE ALARM SYSTEM 20 1 E 0 0
E 2 20 AC UNIT
79 FUEL PUMP UNLEAD. 20 1 E 0 0 E 1 20 EF 5 80
77 0 0 E 1 20 EF 4 78
75 0 0 E 1 20 EF 3 76
GATE FENCE 30 3 E
0 0 E 1 20 EF 2 74
71 KITCHEN RECEPT. 20 1 E 0 0 E 1 20 EF 1 72
69 DISH WASHER 20 1 E 0 0 E 1 20 Spare 70
67 NEW DED. RECEPT. 20 1 E 0 0 E 1 20 DEDICATED RECEPT. 68
65 BAY RECEPTICLES 20 1 E 0 0 E 1 20 RECEPT. AT EYE WASH 66
63 RECEPTICLES 20 1 E 0 0 E 1 20 GENERAL RECEPT 64
61 RECEPTICLES 20 1 E 0 0 E 1 20 VENDING RECEPT 62
59 RESTROOM RECEPTICLES 20 1 E 0 0 E 1 20 VENDING RECEPT 60
57 RECEPTICLES 20 1 E 0 0 E 1 20 RECEPTICLE 58
55 FRIDGE RECEPTICLES 20 1 E 0 0 E 1 20 MICRO 3 56
53 FRIDGE RECEPTICLES 20 1 E 0 0 E 1 20 MICRO 2 54
51 GFCI RECEPTICLES 20 1 E 0 0 E 1 20 MICRO 1 52
49 DISPOSAL 20 1 E 0 0 E 1 20 GFCI RECEPT. 50
47 RECEPTICLES 20 1 E 0 0 E 1 20 GFCI RECEPT. 48
45 RECEPTICLES 20 1 E 0 0 E 1 20 ICE MAKER 46
43 RECEPTICLES 20 1 E 0 0 E 1 20 GFCI RECEPT. 44
Ckt Description Trip (A) Poles FN/Note A B C FN/Note Poles Trip (A) Description Ckt
NOTES: NEW BRANCH PANEL. LOADS TAGGED 'E' ARE EXISTING LOADS TO BE RECONNECTED TO NEW PANELBOARD. PROVIDE SPD AND MOUNT ADJACENT TO PANELBOARD.
Enclosure: NEMA 1
Mounting: Surface Features & Modifications: -
Supply: PANEL A Feed-Thru Lugs: No SCCR: 22 kA
Location: EXISTING OFFICE/ ELEC 33 Neutral: 100% Mains FN/Note: -
Bus Rating: 400 A Mains Rating: 400 A
Panelboard: PANEL B Voltage: 208 V, 3Ø, 4W Mains Type: MLO
ONE-LINE DIAGRAM - DEMO
ONE-LINE DIAGRAM - NEW
Revisions: Date:
Addendum 1 10/12/2026
FA LITHONIA CLX-L48-4000LM-SEF-FDL-WD-MVOLT-GZ10-35K-80CRI-WH
48' LED Linear w/ Standard efficiency. Flat diffuse lens. Wide distribution. White finish. Provide accessories required for suspended installation.
Coordinate final suspension height and location with all trades. BAA and BABA Compliant.
LED/3500K/80 0-10V 10% 4,236 25.5 MVOLT
TYPE
BOD
MANUFACTURER
MODEL NUMBER DESCRIPTION LAMP/CCT/CRI CONTROL
DELIVERED
LUMENS
WATTS VOLTS
LIGHTING FIXTURE SCHEDULE
| Sheets |
| 3003-E-111 - MAINTENANCE BLDG - ELECTRICAL PLANS |
| 3003-E-501 - MAINTENANCE BLDG - ELECTRICAL SCHEDULES AND DETAILS |
| 3003-ED111 - MAINTENANCE BLDG - ELECTRICAL DEMOLITION PLANS |
File details come from the government source that posted it. Updated .