3003-E-111_ADD1.pdf

PDF 409 KB Posted

Attached to
Fort Bliss National Cemetery, Gravesite Expansion and FCA Deficiencies
Solicitation number
36C78626B0028
Issued by

About this file

This document is an Electrical Plans drawing set for a maintenance building expansion project at Fort Bliss National Cemetery in El Paso, Texas. The drawing number 3003-E-111 was issued June 15, 2026, with Addendum 1 dated October 12, 2026, and depicts both electrical lighting and power plans at a scale of 1/8" = 1'-0".

The project involves electrical work in an existing maintenance facility with multiple functional areas including offices, HVAC, mud room, restrooms, lunch room, wash bay, vehicle storage, maintenance bays, and storage areas for flammable materials and pesticides. Key electrical requirements include: installation of GFI-protected receptacles throughout; provision of two L5-30R receptacles for telecom use coordinated with the low-voltage contractor; extension of existing lighting circuits to new fixtures; single-point power supply to a mini-split unit from condensing unit CU-1; disconnection and reconnection of swamp cooler power with a new 240V, 3-pole, 30A weatherproof disconnect; installation of a 208Y/120V, 400A main lug only panelboard with 66 circuits capacity fed from an adjacent existing panelboard; and access control locations requiring coordination with technology and architectural specifications. The general notes specify compliance with NEC Article 250 for grounding and bonding, device installation requirements with minimum spacing distances, coordination with architectural plans and reflected ceiling plans, maintenance of service clearances around equipment, and GFI protection in accordance with NEC Article 210.8. The design team, Anderson, and various consultants (IMEG for low-voltage/security and fire alarm; Aqua Engineering for irrigation; Terracon for geotechnical) are listed as responsible parties.

View the file

Other files

File Type Posted
4101-AE201_ADD1.pdf PDF
2101-AE201_ADD1.pdf PDF
3004-E-111_ADD1.pdf PDF
S02_Attachment - Geotechnical Engineering Report.pdf PDF
092400 PORTLAND CEMENT PLASTERING_ADD1.pdf PDF
073213 CLAY ROOF TILES_ADD1.pdf PDF
2101-AE101_ADD1.pdf PDF
S02_Attachment - DOL Payroll Form updated.pdf PDF
S05_Attachment - RFIs and Responses.pdf PDF
2101-AE111_ADD1.pdf PDF
CE121_ADD1.pdf PDF
S02_Attachment - Statement of Work revised 10.26.2026.pdf PDF
3004-ED111_ADD1.pdf PDF
050385 HISTORIC DECORATIVE FORMED METAL REPAIR_WR IR_ADD1.pdf PDF
LK111_ADD1.pdf PDF
000110 TABLE OF CONTENTS_ADD1.pdf PDF
LP111_ADD1.pdf PDF
3003-ED111_ADD1.pdf PDF
2101-AD201_ADD1.pdf PDF
3003-E-501_ADD1.pdf PDF
S02_Attachment - SF 1413 updated.pdf PDF
S06_36C78626B0028 0002.pdf PDF
CB501_ADD1.pdf PDF
S02_Attachment - Addendum 1 Summary of Changes.pdf PDF
087100 DOOR HARDWARE_ADD1.pdf PDF
2101-EL111_ADD1.pdf PDF
281300 PHYSICAL ACCESS CONTROL SYSTEM_ADD1.pdf PDF
2101-EP111_ADD1.pdf PDF
CB502_ADD1.pdf PDF
S04_Attachment - Site Visit Attendance Roster.pdf PDF
S06_36C78626B0028 Amend. 0001.pdf PDF
Fort Bliss Gravesite Expansion BD Part 1.pdf PDF
S02_Attachment - Limitations on Subcontracting Cert.docx DOCX document
S02_Attachment - DOL Payroll Form.pdf PDF
Fort Bliss Gravesite Expansion BD Part 3.pdf PDF
Fort Bliss Gravesite Expansion BD Part 5.pdf PDF
Fort Bliss Gravesite Expansion BD Part 10.pdf PDF
Fort Bliss Gravesite Expansion - Specifications Full Book.pdf PDF
Fort Bliss Gravesite Expansion BD Part 9.pdf PDF
Fort Bliss Gravesite Expansion BD Part 8.pdf PDF
S02_Attachment - 886CM3026 Fort Bliss NC SOW.pdf PDF
Fort Bliss Gravesite Expansion BD Part 4.pdf PDF
Fort Bliss Gravesite Expansion BD Part 7.pdf PDF
S02_36C78626B0028 Solicitation.pdf PDF
S02_Attachment - Davis-Bacon Act Poster.pdf PDF
S02_Attachment - Standard Form 1413.pdf PDF
Fort Bliss Gravesite Expansion BD Part 2.pdf PDF
Fort Bliss Gravesite Expansion BD Part 11.pdf PDF
S02_Attachment - Price Schedule Sheet.pdf PDF
S02_Attachment - Wage Determination Heavy.pdf PDF
Show 40 more

Latest 50 of 52 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GFI

AC

GFI

AC

GFI

AC

48"

J

J

S P

D

GFI GFI

G F

I

GFI GFI G

F

I A

C G

F I

A C

G F

I A

C G

F I

A C

G F

I A

C

GFI

G F

I G

F I

GFI

G F

I G

F I

EX EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX EX

EX EX EX

EX EX

EXEXEX EX

EX EX EX EX

EX EX EX EX

EX EX EX EX

EX

EX

EX

EX

FA

EX

EX EX

EX

EXISTING OFFICE

EXISTING HVAC

EXISTING MUD RM

EXISTING MENS

EXISTING WOMEN'S

EXISTING LUNCH

EXISTING OFFICE

EXISTING OFFICE/ ELEC

EXISTING MAINTENANCE

BAYS

EXISTING FLAMABLE

STORAGE

EXISTING PESTICIDE

STORAGE

EXISTING PARTS & TOOLS

TE

EXISTING WASH BAY

EXISTING VEHICLE STORAGE

E1

A

E1

PANEL A

PANEL B

E3

MAINTENANCE YARD

ELECTRICAL GENERAL NOTES

1. NOT USED.

2. SURFACE RACEWAY SHALL NOT BE USED IN ANY FINISHED AREAS WITHOUT

PRIOR APPROVAL OF THE DESIGN TEAM.

3. INSTALL DEVICES SUCH THAT NO TWO DEVICES ON OPPOSITES SIDES OF THE

SAME WALL ARE WITHIN 6" OF EACH OTHER.

4. COORDINATE ALL DEVICES WITH ARCHITECTURAL PLANS AND CASEWORK.

5. ALL LIGHTING FIXTURES SHALL BE INSTALLED IN SUCH A WAY THAT DRIVERS ARE

ACCESSIBLE WITHOUT CUTTING OF CEILING. THE DESIGN TEAM SHALL BE

NOTIFIED IMMEDIATELY OF AREAS WHERE THIS IS NOT POSSIBLE.

6. ALL WALL-MOUNTED FIXTURES SHALL HAVE THEIR EXACT ROUGH-IN LOCATION

DETERMINED BY THE DESIGN TEAM PRIOR TO ROUGH-IN.

7. UNLESS NOTED OTHERWISE BY DESIGNATED LIGHTING CONTROL ZONES,

SWITCHES SHOWN SHALL CONTROL ALL FIXTURES IN THE ROOM.

8. REFER TO ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS FOR

THE SPECIFIC DEVICE ROUGH-IN AND PLACEMENT. ANY DEVIATIONS FROM THE

ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS SHALL BE

REVIEWED AND APPROVED BY THE DESIGN TEAM PRIOR TO ROUGH-IN.

9. ALL DEVICES, EQUIPMENT, FIXTURES, AND THE LIKE MUST BE GROUNDED BY USE

OF A PROPERLY SIZED GROUNDING CONDUCTOR. MECHANICAL AND

ELECTRICAL BONDS OF THE METALLIC RACEWAY SYSTEM SHALL BE MAINTAINED.

GROUND AND BOND PER NEC ARTICLE 250.

10. ALL DISCONNECTS ON MECHANICAL EQUIPMENT SHALL BE MOUNTED ON

STRUCTURE TO ALLOW REMOVAL OF THE EQUIPMENT FOR MAINTENANCE WITH

A MINIMUM OF WIRING WORK. VERIFY NEC CLEARANCE REQUIREMENTS ARE MET

PRIOR TO ROUGH-IN.

11. MAINTAIN SERVICE CLEARANCE AROUND MECHANICAL & ELECTRICAL

EQUIPMENT. DO NOT ROUTE PIPING OR CONDUIT IN CLEARANCE SPACE.

12. SURFACE RACEWAY SHALL NOT BE USED IN ANY FINISHED AREAS WITH PRIOR

APPROVAL FROM THE DESIGN TEAM.

13. ALL RECEPTACLE CIRCUITS SHALL HAVE DEDICATED NEUTRAL.

14. INSTALL DEVICES SUCH THAT NO TWO DEVICES ON OPPOSITE SIDES OF THE

SAME WALL ARE WITHIN 24" OF EACH OTHER.

EX EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX EX EX

EX EX

EX EX

EX

EX

EX

EX

EX

EX

EX

EX

EX EX EX

EX

EX

EX

EX

EX

EX EX

EXISTING OFFICE

EXISTING HVAC

EXISTING MUD RM

EXISTING MENS

EXISTING WOMEN'S

EXISTING VEHICLE STORAGE

EXISTING WASH BAY

EXISTING LUNCH

EXISTING OFFICE

EXISTING OFFICE/ ELEC

EXISTING MAINTENANCE

BAYS

EXISTING FLAMABLE

STORAGE

EXISTING PESTICIDE

STORAGE

EXISTING PARTS & TOOLS

TE

PANEL A

PANEL B

E1

L5-30R L5-30R

E2

CU-1

PANEL B-85,87

E4

AS-SCP-1

PANEL B-89

L5-30R RECEPT

120V-1P/30A

PANEL B-91

L5-30R RECEPT

120V-1P/30A

PANEL B-93

WP

E6

MAINTENANCE YARD

E8

E8

E7 E7 E7 E7 E7

E7 E7

E7

E7

E7

E7

E7

PANEL B-95

ELECTRICAL PLAN KEYED NOTES

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

E1 NO ELECTRICAL SCOPE IN THIS AREA.

E2

PROVIDE (2) L5-30R RECEPTACLES FOR TELECOM USE. REFER TO

TECHNOLOGY DRAWINGS FOR ADDITIONAL DETAILS. COORDINATE WITH

LOW VOLTAGE CONTRACTOR PRIOR TO ROUGH-IN.

E3 EXTEND NEAREST EXISTING LIGHTING CIRCUIT TO NEW FIXTURE.

E4

PROVIDE SINGLE POINT POWER TO MINI-SPLIT FROM ASSOCIATE

CONDENSING UNIT CU-1. REFER TO MECHANICAL SHEETS FOR ADDITIONAL

DETAILS.

E5

POWER TO SWAMP COOLER SHALL BE DISCONNECTED AND

RECONNECTED TO NEW UNIT. EXISTING WIRING AND RACEWAY MAY BE

REUSED WHERE IN GOOD CONDITION AND UP TO CURRENT CODES.

PROVIDE NEW 240V RATE 3-POLE, 30A, WEATHERPROOF DISCONNECT.

E6

PROVIDE 208Y/120V, 400A RATED, MAIN LUG ONLY PANELBOARD WITH 66

CIRCUITS CAPACITY. PANEL SHALL BE FED FROM ADJACENT PANELBOARD

EXISTING SUB-FEED/FEED THROUGH LUGS. EXTEND EXISTING BRANCH

CIRCUITS TO NEW PANELBOARD. REFER TO ONE-LINE DIAGRAM AND

PANEL SCHEUDLE FOR ADDITIONAL DETAILS.

E7

ACCESS CONTROL LOCATION. REFER TO TECHNOLOGY DETAILS AND

ARCHITECTURAL SPECIFICATIONS 08-7100 FOR OPERATION AND FURTHER

ROUGH-IN/BIDDING INFORMATION. COORDINATE ALL DOOR HOLDS, CARD

READERS, AND OTHER ACCESSORIES WITH ALL TRADES PRIOR TO

ROUGH-IN.

E8

EXISTING 15A RECEPTACLES IN THIS ROOM SHALL BE REMOVED AND

REPLACED IN PLACE WITH 20A RECEPTACLES. EXISTING BACKBOXES

SHALL BE REUSED. ALL NEW DEVICES SHALL BE GFI PROTECTED IN

ACCORDANCE WITH NEC ARTICLE 210.8. DEVICES INDICATED FOR BIDDING

PURPOSES. VERIFY EXISTING DEVICE LOCATIONS.

E9

COORDINATE FINAL DEVICE LOCATION WITH AC-SCP-1 PRIOR TO

ROUGH-IN.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

NOT SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

DESIGNER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

BID DOCUMENTS

L0W VOLTAGE/SECURITY:

IMEG

623 26TH AVENUE

ROCK ISLAND, IL 61201

309.781.3770

PETE MCGHEE

IRRIGATION:

AQUA ENGINEERING

300 BOARDWALK DRIVE

UNIT 4B

FORT COLLINS,CO 80525

970.372.6104

JD LEONARD

GEOTECHNICAL:

TERRACON

6460 HILLER STREET

SUITE A

EL PASO, TX 79925

915.778.5233

IVAN AVELAR

FIRE ALARM:

IMEG

623 26TH AVENUE

ROCK ISLAND, IL 61201

309.781.3770

MATT SNYDER

C U s e rs \a w e b e r\

D o c u m e n ts

\1

-M A

IN

T

-M -R a w e b e r9

S

.r v t

/1 /2

:0

:4

P M

3003-E-111

MAINTENANCE BLDG - ELECTRICAL PLANS FT BLISS NATIONAL CEMETERY

EXPANSION

5200 FRED WILSON AVENUE, EL PASO, TEXAS

886CM3026

JUNE 15, 2026 ATW DIL

18528

1/8" = 1'-0"

ELECTRICAL LIGHTING PLAN

1/8" = 1'-0"

ELECTRICAL POWER PLAN

A MANUAL ON/OFF MANUAL LINE VOLTAGE TOGGLE SWITCH N/A

TAG ACTIVATION DECRIPTION SCHEDULE

LIGHTING CONTROL - SEQUENCE OF OPERATION

E7

E9

Revisions: Date:

Addendum 1 10/12/2026

Sheets
3003-E-111 - MAINTENANCE BLDG - ELECTRICAL PLANS
3003-E-501 - MAINTENANCE BLDG - ELECTRICAL SCHEDULES AND DETAILS
3003-ED111 - MAINTENANCE BLDG - ELECTRICAL DEMOLITION PLANS

File details come from the government source that posted it. Updated .