MATERIAL APPROVAL SUBMITTAL
(See Instructions on Reverse)
Form Approved OMB No 9000-0062
Expires May 31, 2005
Public reporting burden for this collection of information is estimated to average 20 minutes per response, including the time for reviewing instructions, searching existing data sources, gathering and maintaining the data needed, and completing and reviewing the collection of information. Send comments regarding this burden estimate or any other aspect of this collection of information, including suggestions for reducing this burden to the Department of Defense, Washington Headquarters Services, Directorate for Information Operations and
Reports, 1215 Jefferson Davis Highway, Suite 1204, Arlington VA 22202-4302, and to the Office of Management and Budget, Paperwork Reduction Project OMB No 9000-0062, Washington DC 20503. Please DO NOT RETURN your form to either of these addresses. Send your completed form to: SAF/AQCP, 1060 Air Force Pentagon, Washington DC
TO: (Contracting Officer) FROM: (Contractor) DATE
CONTRACT NUMBER SUBMISSION NUMBER SUBMITTAL
PREVIOUS SUBMISSION NUMBER PROJECT NUMBER
TO BE COMPLETED BY CONTRACTOR FOR GOVERNMENT USE ONLY
ITEM
NO.
SPECIFICATION SECTION/
PARA NO./DRAWING NO.
DESCRIPTION OF MATERIAL
(Include Type, Model Number, Catalog Number, Mfg., etc.)
AP-
PROVED
DISAP-
PROVED
SEE
REVERSE
INITIAL
BY COMPLETING THIS FORM, THE UNDERSIGNED CONTRACTOR CERTIFIES THAT
THE MATERIAL COMPLIES WITH ALL SPECIFICATIONS OF SUBJECT CONTRACT.
DATE (YYYYMMDD) TYPE OR PRINT NAME AND GRADE SIGNATURE
FOR GOVERNMENT USE ONLY
TO: (Base Civil Engineering Officer)
For Evaluation and Action RNLT ________________ OR SOONER
DATE (YYYYMMDD) TYPE OR PRINT NAME AND GRADE SIGNATURE
TO: (AF Contracting Office)
RECOMMEND APPROVAL DISAPPROVAL AS INDICATED ABOVE AND SUBJECT TO ANY APPLICABLE COMMENTS ON THE REVERSE
DATE (YYYYMMDD) TYPE OR PRINT NAME AND GRADE SIGNATURE
TO: (Contractor)
APPROVED
DISAPROVED AS INDICATED ABOVE AND SUBJECT TO ANY APPLICABLE COMMENTS ON THE REVERSE SIDE. REQUEST
RESUBMITTAL ON DISAPPROVED ITEMS WITHIN ____ DAYS OF DATE SHOWN BELOW.
DATE (YYYYMMDD) TYPE OR PRINT NAME AND GRADE SIGNATURE
AF IMT 3000, 20030901, V1 PREVIOUS EDITION IS OBSOLETE.
New Resubmittal
Project:
Dyess AFB Remodel Bldg 8040
Contractor:
RDZ Paving, LLC.
Submitted By: Ingram Concrete, LLC
Date: 2/17/18
Ingram Enterprises, L. P. P.O. Box 1166 Brownwood, TX 76804 ph 325-646-6518 fx 325-646-3415
PLEASE READ THE FOLLOWING:
PROPOSED MIX DESIGNS
The following concrete mix designs are based on procedures suggested in ACI 211 (American Concrete Institute).
Ingram Enterprises, L. P. can not control the testing, placement, or end use of this product; therefore, all warranties are void if concrete is not tested and placed in compliance with all applicable ASTM Standards and job specifications.
DESIGN VERIFICATION DATA
Enclosed in this submittal package you will find design verification data. A 5 point cement content curve was created from the data which complies with ACI 318R-39 recommendations. According to ACI 318R-39, concrete strength may be interpolated from these curves.
TEST REPORTS
In accordance with ASTM C 94, section 14, paragraph 14.4, which states, ”When the strength of concrete is used as a basis of acceptance, the manufacturer shall be entitled to copies of all test reports.”, we request that Ingram Enterprises, L. P. receive copies of any test reports pertaining to our products delivered to your project. This is not only beneficial for future projects, but, also to detect any foreseeable problems that could occur during your project.
Please notify the testing lab of our address for distribution.
Ingram Concrete LLC Attn: QA/QC Dept.
P.O. Box 1166 Brownwood, TX 76804
ORDERING CONCRETE
When placing an order with our Plant Manager or Assistant Plant Manager, please inform them of the design number, mix description, concrete application, yardage, and any other pertinent information. This will help avoid any confusion on what design is delivered to your project. As you know, most projects specify the use of more than one concrete design and some are very similar, yet different, designs (ex. 3000 psi with 4% air for exterior placement and 3000 psi without air for slab on grade).
ADDED PRODUCTS (fibers, chemical additives, etc.)
All additional products to be added to the concrete, such as, superplasticizer, ice, integral color, etc., are the responsibility of the contractor unless a prior agreement has been made with Ingram Enterprises, L. P. When fibers and/or a retarding admixture are ordered, they will be added at the plant during the batching process. Allow a minimum of 10 to 14 working days prior to use when ordering any extra products. Typically, these products are not kept in stock and must be shipped to our facilities or your jobsite via common carrier. When using a superplasticizer, please contact us for assistance in training your personnel on the dosage amounts and procedures. We also have portable chemical dispensing equipment, when available, for use on larger projects.
Your cooperation and business is greatly appreciated.
B. Evans Operations Manager
Proposed Mix Design
Customer :
Project :
Unit Weight :
RDZ PAVING, LLC.
DYESS AFB REMODEL BLDG 8040
Compressive Strength : 4000 psi at 28 days
1" -- 25 mmAggregate size :
Water/Cement ratio : 151.70
Constituents : Quantity Density Volume
0.452
Slump : 4.00 ± 1.00 in
0.0 0.0 %Air :
CONCRETE DESIGN SUBMITTAL
4-156TW5DA-4000 PSI [0]
4000 psi
02/17/2018
Contractor : RDZ PAVING, LLC.
Source of Concrete : ABILENE
Construction type : FOOTINGS AND INTERIOR SOG
Placement : END DUMP OR PUMP pcf
Design Date : 07/07/2015
MIX DESIGN
P.O. BOX 1166
BROWNWOOD, TX 76804
rgreaves@ingramconcrete.com
325-646-6518
CEMENT - ASTM C 150, TYPE I/II 451 lb 3.150 2.29
FLY ASH - ASTM C 618, CLASS F 113 lb 2.450 0.74
CITY WATER 255 lb 1.000 4.09
GRAVEL - #57 1889 lb 2.650 11.42
SAND - NATURAL 1388 lb 2.630 8.46
ASTM C 494, TYPE A - MRWRA 45.12 floz (US)/yd³ 1.000 0.00
Air 0.0 %. 0.00
Remarks :
FOR INCREASED FINISHABILITY AND PUMPABILITY, ADDED SLUMP MAY BE USED FOR A MAXIMUM 7"
SLUMP UPON ENGINEER APPROVAL
4096 27.00Total :
Date :
Ryan Greaves
02/17/2018
Reported by : Approval by :
Date : / /
102/17/2018
STRENGTH PERFORMANCE
REPORT
Period :
Mix : 156TW5DA - *CM-560LB-V47-1"-20%FFA-MR6/NA
17 Nov 2017 11 Jan 2018To
4000 Specified Strength Number of Tests Average Strength
Over Design Type
Required Strength f'c + 1.34*s f'c + 2.33*s - 500 Standard Deviation
ACI 318 >= 30 Tests
Compressive Test Strength Type
Air Content
Slump in
Concrete Temp deg F
7D Str psi
28D Str psi
Count
Average
STDEV
COV%
Range Min
Range Max
4 30 29 29 30
0.80 5.60 70.9 4130 5390
0.93 1.07 4.9 570 680
115.9 19.1 6.9 13.7 12.7
4.00 60.0 3270 4220
1.70 7.50 76.0 5460 7150
Air Content
Slump in
Concrete Temp deg F
7D Str psi
28D Str psi
1/11/2018 0800-1 1/8/2018 0800-1
1/4/2018 0800-2 0800-1
1/3/2018 2015-1
12/20/2017 2232-2 2232-1
12/19/2017 2015-5 2015-4
12/14/2017 2015-1 12/13/2017 2015-1 12/12/2017 2015-1
12/8/2017 0830-1 2232-1
12/6/2017 2015-1
12/5/2017 2015-2 2015-1
12/4/2017 2015-1 11/30/2017 2015-1 11/29/2017 2015-1 11/28/2017 2015-1 11/27/2017 2224-1
11/21/2017 2015-3 2015-2
11/17/2017
2015-12 2015-10 2015-11 2015-9 2015-8 2015-7
Date Sample
5.50 69.0 4660 6170
6.00 74.0 4780 5780
4.00 70.0 4380 5380
4.00 70.0 4380 5380
4.00 71.0 4140 5680
1.50 5.00 60.0 4120 5950
1.70 5.50 62.0 4670 5900
7.00 63.0 3720 4900
6.75 64.0 4440 5680
6.00 71.0 4140 5240
4.00 72.0 4700 5260
6.00 70.0 3780 4700
4.50 60.0 4420 5680
6.00 75.0 5420
6.25 74.0 5180 6430
5.00 76.0 5460 7150
5.00 72.0 4740 6740
4.50 76.0 3390 4680
4.00 67.0 3820 5870
5.50 68.0 4060 5420
7.00 75.0 4180 5280
6.50 75.0 3940 5320
4.50 73.0 3530 4540
5.50 73.0 3650 4940
6.25 76.0 3270 4220
6.00 3940 5300
6.50 75.0 3390 4500
7.50 75.0 4220 4980
6.50 74.0 3270 4700
7.25 75.0 3430 4560
Date : 22/17/2018 Page 1 of
Customer :
Project :
Unit Weight :
RDZ PAVING, LLC.
DYESS AFB REMODEL BLDG 8040
Compressive Strength : 4000 psi at 28 days
1" -- 25 mmAggregate size :
Water/Cement ratio : 143.78
Constituents : Quantity Density Volume
0.443
Slump : 4.00 ± 1.00 in
4.5 ± 1.5 %Air :
CONCRETE DESIGN SUBMITTAL
4-156PY5D5-4000 PSI W/ AEA [1]
4000 psi
02/17/2018
Contractor : RDZ PAVING, LLC.
Source of Concrete : ABILENE
Construction type : FOUNDATION
Placement : END DUMP OR PUMP pcf
Design Date : 01/28/2016
MIX DESIGN
P.O. BOX 1166
BROWNWOOD, TX 76804
rgreaves@ingramconcrete.com
325-646-6518
ASTM C 150, TYPE I/II 451 lb 3.150 2.29
FLYASH - ASTM C 618, CLASS F 113 lb 2.450 0.74
CITY WATER 250 lb 1.000 4.01
GRAVEL - #57 1861 lb 2.650 11.25
SAND - NATURAL 1207 lb 2.630 7.35
ASTM C 260, AEA 1.00 floz (US)/yd³ 1.000 0.00
ASTM C 494, TYPE A - MRWRA 35.91 floz (US)/yd³ 1.000 0.00
Air 5.0 %. 1.35
Remarks :
FOR INCREASED FINISHABILITY AND PUMPABILITY, ADDED SLUMP MAY BE USED FOR A MAXIMUM 7"
SLUMP UPON ENGINEER APPROVAL
3882 27.00Total :
Date :
Ryan Greaves
02/17/2018
Reported by : Approval by :
Date : / /
102/17/2018
Period :
Mix : 156PY5D5 - 36-77485*CM-560LB-V09-1"-20%FFA-MR/NA
20 Oct 2017 09 Jan 2018To
4000 Specified Strength Number of Tests Average Strength
Over Design Type
Required Strength f'c + 1.34*s f'c + 2.33*s - 500 Standard Deviation
ACI 318 >= 30 Tests
Compressive Test Strength Type
Air Content
Slump in
Concrete Temp deg F
7D Str psi
28D Str psi
Count
Average
STDEV
COV%
Range Min
Range Max
30 30 30 30 30
5.09 6.78 66.7 4270 5340
0.89 1.57 5.3 710 670
17.4 23.1 7.9 16.5 12.6
3.20 3.50 53.0 3200 4430
6.30 9.50 81.0 5710 6980
Air Content
Slump in
Concrete Temp deg F
7D Str psi
28D Str psi
1/9/2018 2315-6 1/8/2018 18000026
1/5/2018 2315-4 2353-1
1/3/2018 2315-3 12/20/2017 2315-2 12/18/2017 18000013 12/14/2017 0293-2 11/30/2017 1883-9 11/29/2017 1883-8 11/28/2017 2223-1 11/22/2017 1883-7 11/21/2017 1883-6 11/20/2017 1883-5 11/17/2017 1883-4 11/16/2017 1883-3 11/15/2017 1883-2
11/3/2017 1767-29 1767-28
11/1/2017 1767-25 1524-16
10/26/2017 1883-1
10/25/2017 1767-24 1767-23 1767-22
10/21/2017 1767-21
10/20/2017
2101-1 1979-4
1889-19 1889-18
Date Sample
6.00 8.50 60.0 5710 6980
5.60 8.00 58.0 5190 6380
5.90 9.50 62.0 5400 6420
3.80 6.50 58.0 4920 5930
4.50 8.50 53.0 5610 6490
5.30 9.00 65.0 4370 5870
4.80 7.25 64.0 3290 4500
3.60 4.50 67.0 5180 6180
4.50 5.00 68.0 4320 5370
5.10 6.75 63.0 4910 5220
4.30 5.00 69.0 3420 4710
6.30 6.50 70.0 4160 5000
5.80 7.00 72.0 4450 5520
6.00 7.50 68.0 4170 5750
6.00 7.50 68.0 4140 5040
6.00 6.00 72.0 3790 4700
5.00 6.50 70.0 3530 4920
5.40 7.50 64.0 3200 4500
5.90 5.25 64.0 3590 4640
4.20 5.00 66.0 4010 5230
6.00 5.50 68.0 3550 4530
5.00 3.50 70.0 3650 4950
5.00 7.00 70.0 4230 5320
5.90 7.25 66.0 4220 5060
5.30 8.50 66.0 3610 4970
3.20 3.50 70.0 4720 5440
5.70 6.75 81.0 3550 4430
3.50 8.50 72.0 4660 5530
3.80 8.25 70.0 3840 4830
5.30 7.25 68.0 4680 5650
Date : 22/12/2018 Page 1 of
Period :
Mix : 156PY5D5 - 36-77485*CM-560LB-V09-1"-20%FFA-MR/NA
20 Oct 2017 09 Jan 2018To
Date : 22/12/2018 Page 2 of
Admixture Data
MSDS Sheets
Mill Test Report Maryneal Plant
Buzzi Unicem USA
202 CR 306
Maryneal, TX 79535
Phone:
Fax:
Cement Type: ASTM C150 Type I/II and
AASHTO Type I
Manufacture Date:
From:
To:
December 15, 2017
February 3, 2018
Silo Number:
N/A
Chemical
SiO2 (%)
Al2O3 (%)
Fe2O3 (%)
CaO (%)
MgO (%)
SO3 (%)
C3A (%)
Total Alkali
(Na2O + 0.658K2O)
Time of Set (Vicat)
Initial Set (min.)
Final Set (min.)
Compressive Strength
1 Day
3 Day
7 Day
28 Day
Air Content (%)
Fineness, Blaine (cm2/g)
Ignition Loss
Insoluble Residue (%)
Don Simmons, Quality Supervisor
PSI
C3S (%)
21.3
5.0
3.6
64.3
1.6
3.0
53.1
7.1
0.03
6.8
1.1
0.42
MPa
17.7
27.5
34.0
40.7
We certify that the above described cement, at the time of shipment, meets the chemical and physical requirements of ASTM C-150, AASHTO M-85, or ASTM C-91.
C2S (%)
C4AF (%)
Physical
Cube Flow
325 Mesh (%)
Normal Consistency (%)
False Set (%)
Autoclave Expansion (%)
Date: 2/3/2018 3:58:42PM
- 21.0
10.9
27.1
CO2 (%)
Limestone (%)
CaCO3 in Limestone (%)
C3S + 4.75C3A 86.7
0.59
PO Box 38
Thompsons, TX 77481-0038
P: 281.343.0079
ASTM C618 / AASHTO M295 Testing of
Class “F” Fly Ash Oak Grove Plant Franklin, Texas Unit #1.2
Sample Date: October 2017 Report Date: 12/18/17
Sample Type: Monthly MTRF ID: 3139OG
Sample ID: #131-2017
ASTM Limit AASHTO Limit
Chemical Analysis Results Class F/C Class F/C
Silicon Dioxide (SiO2) 56.65 %
Aluminum Oxide (Al2O3) 20.42 %
Iron Oxide (Fe2O3) 4.79 %
Sum (SiO2+Al2O3+Fe2O3) 81.86 % 70.0/50.0 min 70.0/50.0 min
Sulfur Trioxide (SO3) 0.54 % 5.0 max 5.0 max
Calcium Oxide (CaO) 11.29 %
Magnesium Oxide (MgO) 2.49 %
Sodium Oxide (Na2O) 0.32 %
Potassium Oxide (K2O) 1.00 %
Sodium Oxide Equivalent (Na2O+0.658K2O) 0.98 %
Moisture 0.06 % 3.0 max 3.0 max
Loss on Ignition 0.22 % 6.0 max 5.0 max
Available Alkalies, as Na2Oe 0.34 % *Not Required 1.5 max*
*when required by purchaser
Physical Analysis
Fineness, % retained on 45-µm sieve 29.25 % 34 max 34 max
Strength Activity Index - 7 or 28 day requirement
7 day, % of control 82 % 75 min 75 min
28 day, % of control 96 % 75 min 75 min
Water Requirement, % control 95 % 105 max 105 max
Autoclave Soundness - 0.02 % 0.8 max 0.8 max
Density 2.28 %
Boral Resources certifies that pursuant to current ASTM C618 protocol for testing, the test data listed herein was generated by applicable ASTM methods and meets the requirements of ASTM C618.
AUTHORIZED SIGNATURE:
AGGREGATE MATERIAL EVALUATION REPORT
Report Date: 9/21/2017 Sample Date: 9/21/2017
Report No.: 57 092117-1
Material Source: R E Janes Material Type: #57
Abilene 36
Sieve ASTM C 144
Size Individual Fine %passing
% Retained % Retained %Passing #467 (#2) (#3) #57 (#4) #67 (#5) #8 (8) Concrete Sand Masonry Sand
2" 0 0 100 100 100
1-1/2" 0 0 100 95 - 100 95 - 100 100
1" 5 5 95 95 - 100 100
3/4" 27 32 68 35 - 70 60 - 90 90 - 100
1/2" 27 59 41 25 - 60 25 - 60 100
3/8" 12 71 29 10 - 30 20 - 55 85 - 100 100
#4 23 94 6 0 - 5 0 - 5 0 - 10 0 - 10 10 - 30 95 - 100 100
#8 3 97 3 0 - 5 0 - 5 0 - 10 80 - 100 95 - 100
#16 1 98 2 0 - 5 50 - 85 70 - 100
#30 0 98 2 25 - 60 40 - 75
#50 0 98 2 10 - 30 10 - 35
#100 0 98 2 2 - 10 2 - 15
#200 0.3 98.3 1.7
6.86 2.3 - 3.1
ASTM C 127 Bulk Specific Gravity 2.66 ASTM C 128 Bulk Specific Gravity ASTM C 40 Organic
ASTM C 127 Absorption % 0.9 ASTM C 128 Absorption % Impurities
ASTM C 29 Unit Weight - Dry Rodded 108 ASTM C 29 Unit Weight - Dry Rodded ASTM C 88 Soundness of
ASTM C 29 Void Content %- Dry Rodded 35 ASTM C 29 Void Content - Dry Rodded aggregate by use of
ASTM C 131 L.A. Abrasion - % loss ASTM D 2419 Sand Equivalent sodium sulfate - % loss
Comments: Quality Report
Technician: Trent Taylor
Fine Aggregate
ASTM C 33 Designation (TxDOT Item 421- Grade) - %passing
Coarse
Sample Data
ASTM C 136
Finess Modulus
Coarse Aggregate
AGGREGATE MATERIAL EVALUATION REPORT
Report Date: 6/1/2017 Sample Date: 6/1/2017
Report No.: CS 060117-1
Material Source: R E Janes Material Type: Concrete Sand
Ingram 36
Sieve ASTM C 144
Size Individual Fine %passing
% Retained % Retained %Passing #467 (#2) (#3) #57 (#4) #67 (#5) #8 (8) Concrete Sand Masonry Sand
2" 0 0 100 100 100
1-1/2" 0 0 100 95 - 100 95 - 100 100
1" 0 0 100 95 - 100 100
3/4" 0 0 100 35 - 70 60 - 90 90 - 100
1/2" 0 0 100 25 - 60 25 - 60 100
3/8" 0 0 100 10 - 30 20 - 55 85 - 100 100
#4 0 0 100 0 - 5 0 - 5 0 - 10 0 - 10 10 - 30 95 - 100 100
#8 7 7 93 0 - 5 0 - 5 0 - 10 80 - 100 95 - 100
#16 26 33 67 0 - 5 50 - 85 70 - 100
#30 21 54 46 25 - 60 40 - 75
#50 24 78 22 10 - 30 10 - 35
#100 19 97 3 2 - 10 2 - 15
#200 2.6 99.6 0.4
2.69 2.3 - 3.1
ASTM C 127 Bulk Specific Gravity ASTM C 128 Bulk Specific Gravity 2.61 ASTM C 40 Organic
ASTM C 127 Absorption % ASTM C 128 Absorption % 0.8 Impurities
ASTM C 29 Unit Weight - Dry Rodded ASTM C 29 Unit Weight - Dry Rodded 118 ASTM C 88 Soundness of
ASTM C 29 Void Content %- Dry Rodded ASTM C 29 Void Content - Dry Rodded 28 aggregate by use of
ASTM C 131 L.A. Abrasion - % loss ASTM D 2419 Sand Equivalent 94.2 sodium sulfate - % loss
Comments: Quality Report
Technician: Trent Taylor
Sample Data
ASTM C 136
Finess Modulus
Coarse Aggregate Fine Aggregate
ASTM C 33 Designation (TxDOT Item 421- Grade) - %passing
Coarse
SINCE 1952
GUIDE SPECIFICATION FOR 10 MIL UNDERSLAB VAPOR BARRIER
PART 1 – GENERAL
1.1 SUMMARY
A. Products supplied under this section:
1. Vapor barrier, seam tape, and mastic for installation under concrete slabs.
B. Related sections:
1. Section 03 30 00 Cast-in-Place Concrete
2. Section 07 26 00 Vapor Retarders
1.2 REFERENCES
A. American Society for Testing and Materials (ASTM):
1. ASTM E 1745-09 Standard Specification for Plastic Water Vapor Retarders Used in
Contact with Soil or Granular Fill Under Concrete Slabs.
2. ASTM E 154-99 (2005) Standard Test Methods for Water Vapor Retarders Used in
Contact with Earth Under Concrete Slabs, on Walls, or as Ground Cover.
3. ASTM E 96-05 Standard Test Methods for Water Vapor Transmission of Materials.
4. ASTM F 1249-06 Standard Test Method for Water Vapor Transmission Rate Through
Plastic Film and Sheeting Using a Modulated Infrared Sensor.
5. ASTM E 1643-09 Selection, Design, Installation, and Inspection of Water Vapor
Retarders Used in Contact with Earth or Granular Fill Under Concrete Slabs.
B. American Concrete Institute (ACI):
1. ACI 302.2R-06 Guide for Concrete Slabs that Receive Moisture-Sensitive Flooring
Materials.
1.3 SUBMITTALS
A. Quality Control/Assurance:
1. Summary of test results as per ASTM E 1745.
2. Manufacturer’s samples, literature, and summary of test results.
3. Manufacturer’s instructions for product installation and penetration repair.
PART 2 – PRODUCTS
2.1 MATERIALS
A. Vapor Barrier/Retarder must exceed the ASTM E 1745 Class A requirements:
1. Water Vapor Permeance: ASTM F 1249 or ASTM E 96 - 0.1 Perm
2. Puncture Resistance: ASTM 1709 - 2200 grams or more
P.O. BOX 58, CHANNELVIEW, TEXAS 77530
O. 281.452.5961 F. 281.452. 5642
WWW.TEX-TRUDE.COM ISO 9001-2008
SINCE 1952
3. Tensile Strength: ASTM D 882 - 45.0 lbf/in3
4. Life Expectancy: ASTM E 154 Indefinite
5. Must Be 100% Virgin Resin Polyethylene/Polyolefin
B. Thickness: 10 mil minimum
C. Vapor barrier products:
1. Basis of Design: Xtreme Vapor Barrier (10-mil) by Tex-Trude LP, 281.452.5961 www.tex-trude.com
2.2 ACCESSORIES
A. Seam tape:
1. Xtreme Seam Tape, by Tex-Trude LP, 281.452.5961 www.tex-trude.com
B. Penetration Mastic:
1. Xtreme Mastic, by Tex-Trude LP, 281.452.5961 www.tex-trude.com
PART 3 – EXECUTION
3.1 PREPARATION
A. Ensure base material is approved by Architect or Geotechnical Engineer.
1. Level and compact base material.
3.2 INSTALLATION
A. Install vapor barrier follow the guidelines of the ASTM E 1643 and/or by manufacturer’s instructions.
1. Unroll vapor barrier with the longest dimension parallel with the direction of the concrete placement.
2. Overlap joints 6 inches and seal with manufacturer’s tape.
3. Lap vapor barrier over footings and/or seal to foundation walls.
4. Seal all penetrations (including pipes) per manufacturer’s instructions.
5. Repair damaged areas by cutting a patch of vapor barrier, overlapping damaged area 6 inches on all sides and taping all sides with seam tape or by manufacturer’s recommendations.
P.O. BOX 58, CHANNELVIEW, TEXAS 77530
O. 281.452.5961 F. 281.452. 5642
WWW.TEX-TRUDE.COM ISO 9001-2008
COMMENTS
(Number to correspond with applicable Item Number on reverse)
INSTRUCTIONS TO CONTRACTORS
1. The term "material" is defined as articles, supplies, raw materials, equipment, parts, components, and end items that are to be incorporated into the work required by the contract.
2. This form is to be used by contractors for submitting Shop Drawings, Equipment Data, Manufacturer's Literature and Certificates and samples of Materials to the Government for approval in accordance with the provisions of this contract. Unless otherwise specified, it is to be prepared in 4 copies, signed, and provided to the contracting officer with appropriate attachments.
3. Item(s) to be approved will be clearly tabbed or identified. Data pertaining to item(s) to be approved will be clearly identified or tabbed, particularly where documents are voluminous, in order to properly evaluate the materials or articles to be incorporated in the work. Each attachment will be numbered to correspond with the item number shown on the face of this form.
4. Requests submitted shall be numbered consecutively, by contract, in the space entitled "Submission No.". This number, in addition to the Contract No., will be used to identify each Material Approval Submittal. Resubmissions will be indicated in the appropriate block and the insertion of previous submission number and data in addition to a new submission number. A single submission should be used for all work of a section of the specifications, but in NO instance should the submission include work for more than one (1) contract. Submittals requiring priority handling will be submitted by separate submittal using the form and so marked across the face of the form.
5. This Material Approval Submittal is not valid unless it is signed by the contracting officer. This approval is required as called for by the contracting officer under the terms of this contract.
AF IMT 3000, 20030901, V1 (REVERSE)
| 2018-02-23T15:07:41-0600 | |
| JEON.YEONGSOO.1538040130 |
| 2018-02-23T14:50:30-0600 | |
| ROLAN.PATRICK.M.1515150249 |
| 2018-02-23T15:47:08-0600 | |
| INCE.HILARY.RAE.1368173785 |
| TO Contracting Officer: Capt. Hillary Ince |
| FROM Contractor: FARR Builders LLC |
S. Gevers, San Antonio, TX 78210
| DATE: 20 Feb. 2018 |
| CONTRACT NUMBER: FA4661-15-D-0001 |
| SUBMISSION NUMBER: 32 |
| PREVIOUS SUBMISSION NUMBER: 31 |
| PROJECT NUMBER: FNWZ 12-0053 |
| ITEM NORow1: 1 |
| SPECIFICATION SECTION PARA NODRAWING NORow1: Per Sow |
| DESCRIPTION OF MATERIAL Include Type Model Number Catalog Number Mfg etcRow1: Vapor Barrier Specifications |
| INITIALRow1: PR |
| ITEM NORow2: 2 |
| SPECIFICATION SECTION PARA NODRAWING NORow2: Per SOW |
| DESCRIPTION OF MATERIAL Include Type Model Number Catalog Number Mfg etcRow2: Concrete Specifications |
| INITIALRow2: PR |
| ITEM NORow3: |
| SPECIFICATION SECTION PARA NODRAWING NORow3: |
| DESCRIPTION OF MATERIAL Include Type Model Number Catalog Number Mfg etcRow3: |
| INITIALRow3: |
| ITEM NORow4: |
| SPECIFICATION SECTION PARA NODRAWING NORow4: |
| DESCRIPTION OF MATERIAL Include Type Model Number Catalog Number Mfg etcRow4: |
| INITIALRow4: |
| ITEM NORow5: |
| SPECIFICATION SECTION PARA NODRAWING NORow5: |
| DESCRIPTION OF MATERIAL Include Type Model Number Catalog Number Mfg etcRow5: |
| INITIALRow5: |
| ITEM NORow6: |
| SPECIFICATION SECTION PARA NODRAWING NORow6: |
| DESCRIPTION OF MATERIAL Include Type Model Number Catalog Number Mfg etcRow6: |
| INITIALRow6: |
| ITEM NORow7: |
| SPECIFICATION SECTION PARA NODRAWING NORow7: |
| DESCRIPTION OF MATERIAL Include Type Model Number Catalog Number Mfg etcRow7: |
| INITIALRow7: |
| ITEM NORow8: |
| SPECIFICATION SECTION PARA NODRAWING NORow8: |
| DESCRIPTION OF MATERIAL Include Type Model Number Catalog Number Mfg etcRow8: |
| INITIALRow8: |
| ITEM NORow9: |
| SPECIFICATION SECTION PARA NODRAWING NORow9: |
| DESCRIPTION OF MATERIAL Include Type Model Number Catalog Number Mfg etcRow9: |
| INITIALRow9: |
| ITEM NORow10: |
| SPECIFICATION SECTION PARA NODRAWING NORow10: |
| DESCRIPTION OF MATERIAL Include Type Model Number Catalog Number Mfg etcRow10: |
| INITIALRow10: |
| ITEM NORow11: |
| SPECIFICATION SECTION PARA NODRAWING NORow11: |
| DESCRIPTION OF MATERIAL Include Type Model Number Catalog Number Mfg etcRow11: |
| INITIALRow11: |
| DATE YYYYMMDD: 2018-02-20 |
| TYPE OR PRINT NAME AND GRADE: Wayne Owens, PS |
| TO Base Civil Engineering Officer: 502 CE |
| RNLT: |
| DATE YYYYMMDD_2: 20180223 |
| TYPE OR PRINT NAME AND GRADE_2: A1C Yeongsoo Jeon |
| TO AF Contracting Office: 7 CONS |
| DATE YYYYMMDD_3: 20180223 |
| TYPE OR PRINT NAME AND GRADE_3: Patrick Rolan, GS-12 |
| TO Contractor: FARR Builders LLC |
| DATE YYYYMMDD_4: 20180223 |
| TYPE OR PRINT NAME AND GRADE_4: Capt Hilary Ince |
| Text5: |
| Check Box6: Yes |
| Check Box7: Off |
| Check Box8: Off |
| Check Box9: Yes |
| Check Box10: Off |
| Check Box11: Off |
| Check Box12: Off |
| Check Box13: Off |
| Check Box14: Off |
| Check Box15: Off |
| Check Box16: Off |
| Check Box17: Off |
| Check Box18: Off |
| Check Box19: Off |
| Check Box20: Off |
| Check Box21: Off |
| Check Box22: Off |
| Check Box23: Off |
| Check Box24: Off |
| Check Box25: Off |
| Check Box26: Off |
| Check Box27: Off |
| Check Box28: Off |
| Check Box29: Off |
| Check Box30: Off |
| Check Box31: Off |
| Check Box32: Off |
| Check Box33: Off |
| Check Box34: Off |
| Check Box35: Off |
| Check Box36: Off |
| Check Box37: Off |
| Check Box38: Off |
| Check Box3: Yes |
| Check Box50: Off |
| Check Box4: Yes |
| Check Box5: Off |
| Check Box39: Yes |
| Check Box40: Off |
| COMMENTS Number to correspond with applicable Item Number on reverseRow1: |
File details come from the government source that posted it. Updated .