BUILDING AUTOMATION SYSTEMS
Fire - Security - CCTV - HVAC Control F:\CLIENT\ENER-TEL\DOCS\21-000\21-999FIRE
Dyess AFB Building 8040
1081 2nd St.
Repair Maintenance Shop
FNWZ 12-0053
BACnet Direct Digital Control System
Section 23 09 23.13 20
Submittal
Job# 4162
BUILDING AUTOMATION SYSTEMS
Fire - Security - CCTV - HVAC Control F:\CLIENT\ENER-TEL\DOCS\21-000\21-999FIRE
Datasheets (Sorted by Device ID# of Equipment Schedule on Sheet 1 of Shop Drawings)
© 2012 Kele, Inc. All rights reserved. The Kele name and logo are registered trademarks of Kele, Inc. kele.com 888-397-5353 USA 001-901-382-6084 International 931
RELAYS & CONTACTORS
RELAYS & CO
N
TACTO
RS
January 2012
RH SERIES
RR Series
RH SERIES (UL ratings)
RR SERIES (UL ratings)
RATED
VOLTAGE
RATED CURRENT (mA) ±15% @ 20°C 60 Hz 50 Hz
INRUSH CURRENT
(mA)
AC
DC
4PDT
3PDT
DPDT
SPDT
19.5 9.8
16.4 8.2
59.7 12.9 6.5
8.6 3.7
16.5 8.3
14.2 7.1
5.5
7.5 3.2
36.9
VOLTAGE
RESISTIVE (A) INDUCTIVE (A)
cos = 0.3 MOTOR LOAD (hp)
1/3 1/6
1/6
1/6
3PDTSPDT4PDT
240 AC
120 AC
30 DC
28 DC
Rated Voltage
Rated Current (mA) ±15% @ 20°C 60 Hz 50 Hz
INRUSH CURRENT
(mA)
20.5 10.5
12.1
RJ Series
* Note: 6.5A, 20A Total
VOLTAGE RESITIVE (A) INDUCTIVE (A)
cos = 0.3
MOTOR LOAD (hp)
1/4
240 AC
120 AC
30 DC
Maximum continuous applied voltage RH, RR 110% of rated voltage RJ 140% of rated voltage Pull-in voltage RH, RR, RJ/AC 80% of rated voltage RJ, RJ/DC 70% of rated voltage Drop-out voltage AC 30% or more of rated voltage DC 10% or more of rated voltage Contact material RH Silver cadmium oxide RR Silver RJ Silver nickel alloy Contact resistance RH 50 mΩ maximum RR 30 mΩ maximum RJ 50 mΩ maximum
Operate time RH, RR 25 ms maximum RJ 15 ms maximum Release time RH, RR 25 ms maximum RJ 10 ms maximum Min load RH 24 VDC/30 mA, 5 VDC/100 mA RR 24 VDC/10 mA, 5 VDC/20 mA RJ 5 VDC/100 mA Operating temp -22° to 158°F (-30° to 70°C) Agency approvals UL-recognized component, (RH, RR): File #E66043, (RJ): File #E55996 CSA certified, File #LR35144;
CE certified (not RR blade style) Warranty 1 year
COIL RATINGS CONTACT RATINGS
RJ1S RJ2S
12A @ 250 VAC/30 VDC
12A @ 250 VAC; 6A @ 30 VDC
7.5A @ 250 VAC; 6A @ 30 VDC
7.5A @ 250 VAC; 3A @ 30 VDC
N.O.
N.C.
N.O.
N.C.
Resistive Load (Maximum)
CONTACT
8A @ 250 VAC/30 VDC
8A @ 250 VAC; 4A @ 30 VDC
4A @ 250 VAC; 4A @ 30 VDC
4A @ 250 VAC; 2A @ 30 VDC
Inductive Load (Maximum)
Nominal Current Coil Resistance
25.7 mA
41.1 mA
8.1 mA
24V
24V 120V
DC Coil
Nominal Voltage
1080Ω 243Ω
5270Ω AC Coil (60 Hz)
Coil Sensitivity
IDEC GENERAL-PURPOSE RELAYS
RH, RJ, RR SERIES
DESCRIPTION
IDEC general-purpose relays are available in the RH Series blade-style relays and the RR Series pin-style relays and the RJ Series compact relays.
The RH Series features a 10A switching capacity. They are available in SPDT, DPDT, 3PDT, and 4PDT contact confi gurations, driven by AC or DC coils, and they have blade terminals for socket mounting.The RR Series has a 10A contact rating.
The RR Series relays are available in SPDT, DPDT, and 3PDT confi gurations driven by AC or DC coils, and they have pin or blade terminals for socket mounting.
The RJ Series is compact to reduce space requirements.
They are available in a 12A SPDT version and an 8A DPDT version. They are driven by AC or DC coils and have blade terminals for socket mounting.
FEATURES
• Blade style, pin style, and compact models
• Indicator light and/or check button available
• Surface or DIN rail mount
• UL recognized, CSA certifi ed
SPECIFICATIONS
RH, RJ, RR Series
001-901-382-6084 International 888-397-5353 USA kele.com © 2012 Kele, Inc. All rights reserved. The Kele name and logo are registered trademarks of Kele, Inc.
RE
LA
YS
C O
TA
CT
IDEC GENERAL-PURPOSE RELAYS
RH, RJ, RR SERIES
1.39 (3.56) or less in (cm)
2.19 (5.55)
0.55 (1.39) 0.82 (2.1)
1.
2.
1.22 (3.1)
1.14 (2.9) 1.42 (3.6) 1.87 (4.8) or less 1.42 (3.64)
0.2 (0.5)
1.42 (3.64)
(3
.6
(3
.6
RR2P RR1BA, RR2BA, RR3B
RR Series Power Relays (blade)
RH Series Relays (blade)
RR3PA
RH2B RH3BRH1B
1.60 (4.1)
RH4B
RR Series Relays (pin)
1 5
1.06 (2.7) 0.5 (1.27)
RJ Series Relays (blade)
4 5
1 8
RR2P
3 9
2 10
1 11
RR3PA
A B
RR1BA
BA
RR2BA
BA
RR3B
13 14
RH1B
13 (-) 14(+)
RH3B
13 (-) 14(+)
RH4B
13 14(-) (+)
RH2B
1 5 1 8
RJ1S RJ2S
WIRING
DIMENSIONS
ORDERING INFORMATION
RH1B U AC24V
Example: RR2PUAC24V DPDT relay 8 pin with 24VAC coil
U Standard relay UL Indicator light ULC Indicator light and check button
AC12V 12 VAC coil voltage AC24V 24 VAC coil voltage AC120V 120 VAC coil voltage AC240V 240 VAC coil voltage DC12V 12 VDC coil voltage DC24V 24 VDC coil voltage
MODEL DESCRIPTION
RH1B Relay, SPDT, blade (use SH1B-05 socket) RH2B Relay, DPDT, blade (use SH2B-05 socket) RH3B Relay, 3PDT, blade (use SH3B-05 socket) RH4B Relay, 4PDT, blade (use SH4B-05 socket)
RJ1S C A24
C No options CL LED indicator
A24 24 VAC coil voltage A120 120 VAC coil voltage D24 24 VDC coil voltage
RJ1S Relay, SPDT (use SJ1S-05B socket) RJ2S Relay, DPDT (use SJ2S-05B socket)
RR2P U AC24V
U Standard relay UL Indicator light ULC Indicator light and check button
AC12V 12 VAC coil voltage AC24V 24 VAC coil voltage AC120V 120 VAC coil voltage AC240V 240 VAC coil voltage DC12V 12 VDC coil voltage DC24V 24 VDC coil voltage
RR2P Relay, DPDT, 8 pin (use SR2P-05 or SR2P-06) RR3PA Relay, 3PDT, 11 pin (use SR3P-06 socket) RR1BA Relay, SPDT, 11 blade (use SR3B-05 socket) RR2BA Relay, DPDT, 11 blade (use SR3B-05 socket) RR3B Relay, 3PDT, 11 blade (use SR3B-05 socket)
Legend
NC
NO
Bottom View
RELATED PRODUCTS PAGE
DINRSTL, DINRALU DIN rail 229 brian.miller
Highlight
© 2012 Kele, Inc. All rights reserved. The Kele name and logo are registered trademarks of Kele, Inc. kele.com 888-397-5353 USA 001-901-382-6084 International 933
TACTO
Model Socket Type Rated
Rated Current
Hold Down Clip or SpringWire Size Wire Size Weight Approvals
SJ1S-05B Blade, DIN rail or surface mount 250V 12A Lever: SJ9Z-C1 (provided) Two 14 AWG 0.06 lb (0.03 kg) UL recognized File #E62437, CSA certifi ed File #LR84913, CE
SJ2S-05B Blade, DIN rail or surface mount 250V 8A Lever: SJ9Z-C1 (provided) Two 14 AWG 0.07 lb (0.034 kg) UL recognized File #E62437, CSA certifi ed File #LR84913, CE
SH1B-05 Blade, DIN rail or surface mount 250V 10A Spring: SYS-02F1;
Clip: SFA-101, SFA-202 Two 12 AWG 0.06 lb (0.03 kg) UL recognized File #E62437, CSA certifi ed File #LR35144e, CE
SH2B-05 Blade, DIN rail or surface mount 300V 10A Spring: SY4S-02F1;
Clip: SFA-101, SFA-202 Two 12 AWG 0.10 lb (0.05 kg) UL recognized File #E62437, SH3B-05 Blade, DIN rail or surface mount 300V 10A Spring: SH3B05F1;
Clip: SFA-101, SFA-202 Two 12 AWG 0.13 lb (0.06 kg) UL recognized File #E62437, SH4B-05 Blade, DIN rail or surface mount 300V 10A Spring: SH4B-02F1;
Clip: SFA-101, SFA-202 Two 12 AWG 0.16 lb (0.07 kg) UL recognized File #E62437, SR2P-05 8-Pin DIN rail or surface mount 300V 10A Spring: SR2B-02F1 (RR2P only);
Clip: SFA-203 (RTE-P1 only) Two 12 AWG 0.10 lb (0.05 kg) UL recognized File #E62437, SR2P-06 8-Pin, DIN rail or surface mount 300V 10A Spring: SR2B-02F1 (RR2P only);
Clip: SFA-202 (RTE-P1 only) Two 12 AWG 0.10 lb (0.05 kg) UL recognized File #E62437, SR3P-06 11-Pin, DIN rail or surface mount 300V 10A Spring: SR3B-02F1 (RR only);
Clip: SFA-202 (RTE-P2 only) Two 12 AWG 0.13 lb (0.06 kg) UL recognized File #E62437, SR3B-05 Blade, DIN rail or surface mount 300V 10A Spring: SR3B-02F1 (RR3PA only);
Clip: SFA-202 (RTE-P2 only) Two 12 AWG 0.14 lb (0.06 kg) UL recognized File #E62437, IDEC RELAY SOCKETS
SH, SJ, SR SERIES
The SH and SR Series of IDEC relay sockets are for use with the IDEC RH / RR Series relays and RTE Series timers. The SH and SR Series include both blade and pin style sockets and are available for one, two, three and four pole relays.
The SH and SR sockets can be DIN rail or surface mounted.
The SJ Series of IDEC relay sockets are for use with the IDEC RJ1S and RJ2S Series relays. They can be DIN rail or surface mounted.
• Use with IDEC RH / RR / RJ relays and RTE timers
• Screw terminals with captive wire clamp
• Surface or DIN rail mount
• UL recognized, CSA certifi ed and CE approved
SJ1S, SJ2S SH1B-05
SH2B-05 SH3B-05
SH4B-05 SR2P-05 SR2P-06 SR3P-06 SR3B-05
001-901-382-6084 International 888-397-5353 USA kele.com © 2012 Kele, Inc. All rights reserved. The Kele name and logo are registered trademarks of Kele, Inc.
TA
CT
IDEC RELAY SOCKETS
SH, SJ, SR SERIES
SH1B-05 Relay socket, SPDT blade type, DIN/surface mount SH1B-05C SH1B-05QT20 SH2B-05 Relay socket, DPDT blade type, DIN/surface mount SH2B-05C SH2B-05QT10 SH3B-05 Relay socket, 3PDT blade type, DIN/surface mount SH4B-05 Relay socket, 4PDT blade type, DIN/surface mount SH4B-05C SJ1S-05B Relay socket, SPDT blade type, DIN/surface mount SJ2S-05B Relay socket, DPDT blade type, DIN/surface mount SR2P-05 Relay socket, DPDT pin type, DIN/surface mount SR2P-06 Relay socket, DPDT pin type, DIN/surface mount SR3B-05 Relay socket, three-pole blade type, DIN/surface mount SR3P-06 Relay socket, 3PDT pin type, DIN/surface mount
14 13
0.32 (0.8)
0.66 (1.7)
0.63 (1.6)
0.63 (1.6)
0.78 (2.0)
0.10 (0.25)
0.57 (1.5)
0.98 (2.5)
1.12 (2.85)
2.62 (6.7)
1.83 (4.8)
0.16 dia.
(0.42)
2 Mounting Holes
0.16 dia
DIN
Rail
SH1B-05
0.86 (2.2)
1.03 (2.6)
1.03 (2.6)1.17
(3.0)
0.7 (1.88)
SH2B-05
1.25 (3.2)
(3.6)
1.56 (4.0)
SH3B-05
SJ1S
SJ1S,
SJ2S
SJ2S
4 5
0.6 (1.6) 0.2 (0.4)
0.1 (0.2)
1.2 (2.9)
2.8 (7.1)
1.4 (3.5)
1.9 (4.9)
2.2 (5.6)
SJ1S, SJ2S
1.65 (4.2)
1.81 (4.6)
1.81 (4.6)
1.97 (5.0)
2 Mounting Holes
0.16 dia (0.42)
(.25)
SH4B-05
1.40
1.14 (2.9)
1.14 (2.9)
0.64 (1.7)
0.78 (2.0)
1.25
2.03 (5.2)
1.28 (3.3)
0.9
0.16 dia. (0.42)
0.12
5 4
SR2P-05
1.56 (4.0)
1.3
(1.8)
1.0 (2.55)
2.34 (6.0)
0.97
0.04
5 4 3
7 8
SR2P-06
2.3 (5.9)
2.34 (6.0)
0.12
2 31
7 6
9 1110
8 5
(1.8)
1.0 (2.55)
1.05
SR3P-06
.07 (0.2)
0.16 dia.
0.31 (0.8) M3.5
Terminal Screw
(0.42)2.9
(7.6)
1.41
1.45 (3.7)
1.69 (4.3)
2.2 (5.6)
1.45 (3.7)
9 8
B A
SR3B-05
Sw itches &
Pilot Lights Signaling Lights
Relays & Sockets
Tim ers
Contactors Term inal Blocks Circuit Breakers
799800-262-IDEC (4332) • USA & Canada
RY/RMRelays & Sockets
RY/RM Series Miniature Relays
Key features:
| • | RY2 (3A), RY4 (5A), RM2 (5A) |
| • | General purpose miniature relays |
| • | 3A or 5A contact capacity |
| • | Wide variety of terminal styles and coil voltages meet a wide range of applications |
| • | All 4PDT types have arc barriers. |
Part Number Selection Part Number
Contact Model Plug-in Terminal PC Board Terminal Coil Voltage Code
DPDT (Slim) 3A Standard RY2S-U 0 RY2V-U 0
AC6V, AC12V, AC24V, AC110V, AC120V,
AC220V, AC240V
DC6V, DC12V, D24V, DC48V, DC110V
With Indicator RY2S-UL 0 RY2V-UL 0
With Check Button RY2S-UC 0
—With Indicator and Check Button RY2S-ULC 0
Top Bracket Mounting RY2S-UT 0
With Diode (DC coil only) RY2S-UD 0 RY2V-UD 0 DC6V, DC12V, DC24V, DC48V, DC110V
DPDT (Wide) 5A
Standard RM2S-U 0 RM2V-U 0
RYAC6V, AC12V, AC24V, AC110-120V, AC220-240V
DC6V, DC12V, DC24V, DC48V, DC100-110V
With Indicator RM2S-UL 0 RM2V-UL 0
With Check Button RM2S-UC 0
With Indicator and Check Button RM2S-ULC 0
Top Bracket Mounting RM2S-UT 0
With Diode (DC coil only) RM2S-UD 0
With Indicator and Diode (DC coil only) RM2S-ULD 0
4PDT 5A
Standard RY4S-U 0 RY4V-U 0
AC6V, AC12V, AC24V, AC110-120V,
AC220-240V
With Indicator RY4S-UL 0 RY4V-UL 0
With Check Button RY4S-UC 0
With Indicator and Check Button RY4S-ULC 0
Top Bracket Mounting RY4S-UT 0
With Diode (DC coil only) RY4S-UD 0
With Indicator and Diode (DC coil only) RY4S-ULD 0
Top mount models are designed to mount directly to a panel and do not require a socket.
Ordering Information When ordering, specify the Part No. and coil voltage code:
(example) RY4S-U AC110-120V Part No. Coil Voltage Code itc he s
P ilo t L ig ht
Si gn al g
Li gh ts Re la ys
S oc ke
Ti m er
Co nt ac to rs
Te rm
B lo ck
Ci rc ui t B re ak
RY/RM Relays & Sockets
800 www.IDEC.com
Relays Standard DIN Rail Mount
Finger-safe DIN Rail Mount Through Panel Mount PCB Mount
RY2S SY2S-05 SY2S-05C SY2S-51 SY2S-61
RM2 SM2S-05 SM2S-05C SM2S-51 SY4S-61
SY4S-62RY4S SY4S-05 SY4S-05C SY4S-51
Hold Down Springs & Clips
Appearance Item Relay For DIN Mount Socket
For Through Panel & PCB Mount Socket
Pullover Wire Spring
RY2S SY2S-02F1 SY4S-51F1
RM2
SY4S-51F1 SY4S-51F1
RY4S
Leaf Spring 1 (side latch)
RY2S
SFA-202 2 SFA-302
RM2, RY4S
Leaf Spring 1 (top latch)
RY2S
SFA-101 2 SFA-301RM2
RY4S
1. Not available for PCB mount socket SY4S-62.
2. Order 2 pieces per relay.
Accessories Item Appearance Use with Part No. Remarks
Aluminum DIN Rail (1 meter length)
All DIN rail sockets BNDN1000
The BNDN1000 is designed to accommodate DIN mount sockets.
Made of durable extruded aluminum, the BNDN1000 measures 0.413 (10.5mm) in height and 1.37 (35mm) in width (DIN standard). Standard length is 39” (1,000mm).
DIN Rail End Stop DIN rail BNL5 9.1 mm wide.
Replacement Hold-Down Spring Anchor
Horseshoe clip for all DIN rail sockets Y778-011 For use on DIN rail mount socket when using pullover wire hold down spring. 2 pieces included with each socket.
801800-262-IDEC (4332) • USA & Canada
Specifications
Contact Model Standard Contact
RY2 - DPDT Slim RM2 - DPDT Wide RY4 - 4PDT
Contact Material Gold-plated silver Silver Gold-plated silver
Contact Resistance 1 50 mΩ maximum 30 mΩ maximum 50 mΩ maximum
Minimum Applicable Load 24V DC, 5 mA; 5V DC, 10 mA (reference value)
24V DC, 10 mA; 5V DC, 20 mA (reference value)
24V DC, 5 mA; 5V DC, 10 mA (reference value)
Operating Time 2 20 ms maximum
Release Time 2 20 ms maximum
Power Consumption (approx.)
AC: 1.1 VA (50 Hz), 1 VA (60 Hz)
DC: 0.8W
AC: 1.4 VA (50 Hz), 1.2 VA (60 Hz)
DC: 0.9W
AC: 1.4 VA (50 Hz), 1.2 VA (60 Hz)
DC: 0.9W
Insulation Resistance 100 MΩ minimum (500V DC megger)
Dielectric Strength
Between live and dead parts:
1500V AC, 1 minute 2000V AC, 1 minute 2000V AC, 1 minute
Between contact and coil:
Between contacts of different poles:
Between contacts of the same pole:
1000V AC, 1 minute 1000V AC, 1 minute 1000V AC, 1 minute
Operating Frequency Electrical: 1800 operations/h maximum Mechanical: 18,000 operations/h maximum
Vibration Resistance Damage limits: 10 to 55 Hz, amplitude 0.5 mm Operating extremes: 10 to 55 Hz, amplitude 0.5 mm
Shock Resistance Damage limits: 1000 m/s2
Operating extremes: 100 m/s2 (DPDT Slim), 200 m/s2 (4PDT, DPDT Wide)
Mechanical Life 50,000,000 operations
Electrical Life 200,000 operations (220V AC, 3A) 500,000 operations (220V AC, 5A) 100,000 operations (220V AC, 5A) 200,000 operations (220V AC, 3A)
Operating Temperature 3 –25 to +55°C (no freezing) –25 to +45°C (no freezing) –25 to +55°C (no freezing) 4
Operating Humidity 45 to 85% RH (no condensation)
Weight (approx.) 23g 35g 34g
Note: Above values are initial values.
1. Measured using 5V DC, 1A voltage drop method
2. Measured at the rated voltage (at 20°C), excluding contact bouncing Release time of relays with diode: 40 ms maximum
3. For use under different temperature conditions, refer to Continuous Load Current vs. Operating Temperature Curve. The operating temperature range of relays with indicator or diode is –25 to +40°C.
4. When the total current of 4 contacts is less than 15A, the operating tem-perature range is –25 to +70°C.
802 www.IDEC.com
AC Coil Ratings
Voltage (V)
Rated Current (mA) ±15% at 20°C Coil Resistance (Ω) ±10% at 20°C
Operation Characteristics (against rated values at 20ºC)AC 50Hz AC 60Hz
Slim
DPDT Wide &
Max. Continuous Applied Voltage
Pickup
Dropout
6 170 240 150 200 18.8 9.4
110% 80% maximum 30% minimum
12 86 121 75 100 76.8 39.3
24 42 60.5 37 50 300 153
110 9.6 — 8.4 — 6,950 —
110-120 — 9.4-10.8 — 8.0-9.2 — 4,290
120 8.6 — 7.5 — 8,100 —
220 4.7 — 4.1 — 25,892 —
220-240 — 4.7-5.4 — 4.0-4.6 — 18,820
240 4.9 — 4.3 — 26,710 —
DC Coil Ratings
Voltage (V)
Rated Current (mA) ±15% at 20°C
Coil Resistance (Ω) ±10% at 20°C
Operation Characteristics (against rated values at 20ºC)
DPDT Slim DPDT Wide & 4PDT DPDT Slim DPDT Wide & 4PDT Max. Continuous Applied Voltage
Pickup
Dropout
6 128 150 47 40
110% 80% maximum 10% minimum
12 64 75 188 160
24 32 36.9 750 650
48 18 18.5 2,660 2,600
100-110 — 8.2-9.0 — 12,250
110 8 — 13,800 —
Contact Ratings UL Ratings Maximum Contact Capacity
Resistive General use
Wide 4PDT DPDT
Wide 4PDT
240V AC 3A 5A 5A 0.8A 2A 5A
120V AC — — — 1.5A 2.5A —
100V DC 0.2A 0.4A 0.2A 0.2A — 0.2A
30V DC 3A 5A 5A 3A — 5A
CSA Ratings
Resistive General use
Wide 4PDT DPDT
240V AC 3A 5A 5A 0.8A 2A 5A
120V AC 3A 5A — 1.5A 2.5A —
100V DC — — — 0.2A 0.4A 0.2A
30V DC 3A 5A 5A 1.5A 2.5A 1.5A
Contact Continuous Current
Allowable Contact Power Rated Load
Resistive Load Inductive Load Voltage (V) Res. Load Ind. Load
DPDT Slim
(RY2) 3A 660 VA AC
90W DC
176 VA AC
45W DC
110V AC 3A 1.5A
220V AC 3A 0.8A
30V DC 3A 1.5A
DPDT Wide
(RM2) 5A 1100VA AC
150W DC
440VA AC
75W DC
110V AC 5A 2.5A
220V AC 5A 2A
30V DC 5A 2.5A
4PDT (RY4) 5A 1200 VA AC
150W DC
288 VA AC
60W DC
240V AC 5A 1.2A
30V DC 5A 2A
Note: Inductive load for the rated load — cos ø = 0.3, L/R = 7 ms
TÜV Ratings
Voltage DPDT
240V AC 3A 5A 5A
30V DC 3A 5A 5A
AC: cos ø = 1.0, DC: L/R = 0 ms
803800-262-IDEC (4332) • USA & Canada
Socket Specifications Sockets Terminal Electrical Rating Wire Size Torque
Mount
SY2S-05 M3 screws with captive wire clamp 300V, 7A Maximum up to 2–#14AWG 5.5 - 9 in•lbs
SM2S-05 M3 screw with captive wire clamp 300V, 10A Maximum up to 2–#14AWG 5.5 - 9 in•lbs
SY4S-05 M3 screw with captive wire clamp 300V, 7A* Maximum up to 2–#14AWG 5.5 - 9 in•lbs
Finger-safe
Mount
SY2S-05C M3 screws with captive wire clamp, fingersafe 300V, 7A Maximum up to 2–#14AWG 5.5 - 9 in•lbs
SM2S-05C M3 screw with captive wire clamp, fingersafe 300V, 10A Maximum up to 2–#14AWG 5.5 - 9 in•lbs
SY4S-05C M3 screw with captive wire clamp, fingersafe 300V, 7A* Maximum up to 2–#14AWG 5.5 - 9 in•lbs
Through Panel Mount Socket
SY2S-51 Solder 250V, 7A — —
SM2S-51 Solder 250V, 10A — —
SY4S-51 Solder 250V, 7A* — —
PCB Mount Socket
SY2S-61 PCB Mount 300V, 7A — —
SY4S-61 PCB Mount 300V, 7A — —
SY4S-62 PCB Mount 250V, 7A — —
* When using only 2 poles of the 4-poles, the UL recognized current is 10A.
806 www.IDEC.com
Internal Connection (View from Bottom) Standard Type
DPDT Slim (RY2) DPDT Wide (RM2) 4PDT (RY4) With Check Button
Front Pushbutton
Contacts can be operated by pressing the check button.
With Indicator (-L type) DPDT Slim (RY2) DPDT Wide (RM2) 4PDT (RY4)
Coil Below 100V
AC/DC
24V AC/
When the relay is energized, the indicator goes on.
• An LED protection diode is not contained in DPDT relays for coils below 100V
DC.
• If coil polarity is reversed LED will not light.
100V and over
Coil 24V and over
With Diode (-D type) DPDT Slim (RY2) DPDT Wide (RM2) 4PDT (RY4)
Contains a diode to absorb the back emf gener-ated when the coil is de-energized. The release time is slightly longer.
• Diode Characteristics
Reverse withstand voltage: 1,000V Forward current: 1A
With Indicator and Diode (-LD type)
DPDT Wide (RM2) 4PDT (RY4) DPDT Wide (RM2) 4PDT (RY4)
24V DC
Coil 24V DC and over
(+)1413(–)
13(–) (+)14
Contains an LED indicator and a surge absorber.
807800-262-IDEC (4332) • USA & Canada
Dimensions (mm)
RY2S RY4S RM2S
SY2S-05: 61.5 (63.5) max., SY2S-51: 39.6 (41.6) max.
35.6 max. 5.4 14
.5
0.
Total length from panel surface including relay socket
Dimensions in the ( ) include a hold-down spring.3 × ø1.2 oblong hole
1 2
35.6 max. 6.4 21
Total length from the panel surface including relay socket SY4S-05: 61.5 (63.5) max., SY4S-51: 39.6 (41.6) max.
2.2 × ø1.2 oblong hole Dimensions in the ( ) include a hold-down spring.
35.6 max. 6.4 21
Total length from the panel surface including relay socket.
SM2S-05: 61.5 (63.5) max., SM2S-51: 39.6 (41.6) max.
Dimensions in the ( ) include a hold-down spring.
2.2 × ø1.2 hole
RY2V RY4V RM2V
35.6 max. 4 14 4.4
.7
4.
6.
7.
8 2.
60.5
8-ø1 holes
35.6 max. 4 21 4.4 4.4
4.4
6.6
0.5
14-ø1 holes
35.6 max. 4 21 13.2
15 6.
60.5
8-ø1 hole
RY2S-UT RY4S-UT RM2S-UT
14.5
3.5
35.6 max. 5.4
.2
6 4.
43 ¥ ø1.2 oblong hole
21.5
35.6 max. 6.4
42.
2.2 ¥ ø1.2 oblong hole
21.5
35.6 max. 6.4
.53843
2.2 ¥ ø1.2 hole
808 www.IDEC.com
Dimensions
Standard DIN Rail Mount Sockets
SY2S-05 SM2S-05
2 20
M3 Terminal
14.5
(BNDN)
31.5
Terminal Arrangement
2-ø4.2 Mounting Holes (or M4 Tapped Holes)
5.9 max.
4 max. 4.8 min.
ø3.2 min.
(Top View)
18.5
SY4S-05
18.5
12 11 10
4 3 2
Finger-safe DIN Rail Mount Sockets
SY2S-05C SM2S-05C
ø5
18.2
17.2
20 2
35.5
Ring terminals cannot be used.
ø5.5
Ring terminals cannot be used. (Top View)
SY4S-05C
ø5.5 18
12 11 10
4 3 2
(Top View)Ring terminals cannot be used.
NEW!
NTACTO
HUGE IN-STOCK INVENTORY, AVAILABLE TO SHIP SAME DAY kele.com 877-826-9037 USASeptember 2016
MODEL FULL-LOAD AMP (FLA) LOCKED-ROTOR AMP (LRA) RESISTIVE HP, SINGLE PHASE HP, THREE PHASE
DPC24A2D30
DPC01A2D30
DPC02A2D30
30 FLA @ 240-600 VAC 180 LRA @ 240/277 VAC
150 LRA @ 480 VAC
120 LRA @ 600 VAC
40A @ 240-600 VAC 2 hp @ 120 VAC 3 hp @ 240 VAC
DPC24A2D40
DPC01A2D40
40 FLA @ 240-600 VAC 240 LRA @ 240/277 VAC
200 LRA @ 480 VAC
160 LRA @ 600 VAC
50A @ 240-600 VAC 2 hp @ 120 VAC 3 hp @ 240 VAC
DPC24A3C30
DPC01A3C30
5 hp @ 240/277 VAC
DPC24A3C40
DPC01A3C40
40 FLA @ 240-600 VAC 240 LRA @ 240/277 VAC
50A @ 240-600 VAC 3 hp @ 120 VAC
7.5 hp @ 240/277 VAC
DPC24A3B50
DPC01A3B50
50 FLA @ 240-600 VAC 300 LRA @ 240 VAC
250 LRA @ 480 VAC
200 LRA @ 600 VAC
65A @ 240-600 VAC 3 hp @ 120 VAC
7.5 hp @ 200/208 VAC 10 hp @ 240 VAC
10 hp @ 200/208 VAC 10 hp @ 240/277 VAC 15 hp @ 480 VAC 20 hp @ 600 VAC 10 hp @ 200/208 VAC 10 hp @ 240/277 VAC 20 hp @ 480 VAC 25 hp @ 600 VAC 15 hp @ 200/208 VAC 15 hp @ 240 VAC 25 hp @ 480/600 VAC
DPC24A4A30
DPC01A4A30
5 hp @ 240/277 VAC
DPC24A4A40
DPC01A4A40
40 FLA @ 240-600 VAC
DPST-N.O.
DPST-N.O.
3PST-N.O.
DPC24A3B60
DPC01A3B60
60 FLA @ 240-600 VAC 360 LRA @ 240 VAC
300 LRA @ 480 VAC
240 LRA @ 600 VAC
75A @ 240-600 VAC 3 hp @ 120 VAC
7.5 hp @ 200/208 VAC 10 hp @ 240 VAC
25 hp @ 200/208 VAC 25 hp @ 240 VAC 30 hp @ 480/600 VAC
4PST-N.O.
4PST-N.O.
240 LRA @ 240/277 VAC
50A @ 240-600 VAC 3 hp @ 120 VAC
7.5 hp @ 240/277 VAC
15 hp @ 480 VAC
10 hp @ 480 VAC
POLES
DEFINITE PURPOSE CONTACTORS
DPC SERIES
The Hecheng Electrical DPC Series is an economical line of definite-purpose contactors designed to control electrical loads such as air conditioning, refrigeration compressor, motors, and resistance heaters.
• Two-, three-, and four-pole models
• Contact ratings from 30-60 FLA
• Optional auxiliary contacts on select models
CONTACT RATINGS
Two-pole Three-pole Four-pole
IEC 60947-4-1
Line Load Terminals Box lug or dual 0.25” quick connects Coil Terminals Dual 0.25” quick connects Auxiliary Contacts 10A, 1/3 hp @ 120/250 VAC 4A @
120 VAC for lamp load Wire Size 14-4 AWG
Operating Temperature -40° to 149°F (-40° to 65°C) Approvals UL recognized, File #E246810, CE certified Weight 1.5 lbs (0.68 Kg)
MODEL COIL VOLTAGE
(VAC)
INRUSH @ 50 Hz
(VA)
SEALED @ 50 Hz
INRUSH @ 60 Hz
SEALED @ 60 Hz
PULL-IN
DROP-OUT RANGE
DPC24A2D30, 40 24 31 6 28 5 18 6-15
DPC01A2D30, 40 120 31 6 28 5 88 20-70
DPC02A2D30 208/240 35 7 32 6 177 40-140
DPC24A3C30, 40 24 65 7.5 60 6 18 6-15
DPC01A3C30, 40 120 65 7.5 60 6 88 20-70
DPC24A3B50, 60 24 140 20 132 14 18 6-15
DPC01A3B50, 60 120 140 20 132 14 93 20-70
DPC24A4A30, 40 24 68 14 60 9 19.2 6-15
DPC01A4A30, 40 120 68 14 60 9 88 20-70
COIL RATINGS
NT
TO
TRY KELE'S UL-LISTED PANEL SHOPkele.com877-826-9037 USA September 2016
DEFINITE PURPOSE CONTACTORS
DPC SERIES
RELATED PRODUCTS
CN1C Auxiliary contact, (1) SPDT
MODEL
CONTACT AMP RATING
NUMBER
OF POLES
COIL
VOLTAGE (VAC)
DIMENSIONS in (cm) APPROX.
WEIGHT
lb (Kg)
Optional Aux.
Switch Inductive Full Load
Resistive Length Width Height
DPC24A2D30 30 40 2 24 3.29 (8.36) 2.0 (5.08) 2.61 (6.63) 0.6 (0.27) No
DPC01A2D30 30 40 2 120 3.29 (8.36) 2.0 (5.08) 2.61 (6.63) 0.6 (0.27 No
DPC02A2D30 30 40 2 208/240 3.29 (8.36) 2.0 (5.08) 2.61 (6.63) 0.6 (0.27 No
DPC24A2D40 40 50 2 24 3.29 (8.36) 2.0 (5.08) 2.61 (6.63) 0.6 (0.27 No
DPC01A2D40 40 50 2 120 3.29 (8.36) 2.0 (5.08) 2.61 (6.63) 0.6 (0.27 No
DPC24A3C30 30 40 3 24 3.30 (8.38) 2.90 (7.37) 3.0 (7.62) 1.0 (0.45) Yes
DPC01A3C30 30 40 3 120 3.30 (8.38) 2.90 (7.37) 3.0 (7.62) 1.0 (0.45) Yes
DPC24A3C40 40 50 3 24 3.30 (8.38) 2.90 (7.37) 3.0 (7.62) 1.0 (0.45) Yes
DPC01A3C40 40 50 3 120 3.30 (8.38) 2.90 (7.37) 3.0 (7.62) 1.0 (0.45) Yes
DPC24A3B50 50 65 3 24 4.06 (10.3) 3.19 (8.10) 3.56 (9.04) 2.0 (0.91) No
DPC01A3B50 50 65 3 120 4.06 (10.3) 3.19 (8.10) 3.56 (9.04) 2.0 (0.91) No
DPC24A3B60 60 75 3 24 4.06 (10.3) 3.19 (8.10) 3.56 (9.04) 2.0 (0.91) No
DPC01A3B60 60 75 3 120 4.06 (10.3) 3.19 (8.10) 3.56 (9.04) 2.0 (0.91) No
DPC24A4A30 30 40 4 24 3.42 (8.69) 2.75 (7.0) 3.03 (7.7) 1.5 (0.68) Yes
DPC01A4A30 30 40 4 120 3.42 (8.69) 2.75 (7.0) 3.03 (7.7) 1.5 (0.68) Yes
DPC24A4A40 40 50 4 24 3.42 (8.69) 2.75 (7.0) 3.03 (7.7) 1.5 (0.68) Yes
DPC01A4A40 40 50 4 120 3.42 (8.69) 2.75 (7.0) 3.03 (7.7) 1.5 (0.68) Yes
POWER MONITORING & PROTECTION
PO
W
ER M
NITO
RING & PRO
TECTIO
GROWING SELECTION AVAILABLE ON KELE.COM kele.com 877-826-9037 USASeptember 2016
CURRENT-OPERATED SWITCHES & TRANSDUCERS
RIBXG, RIBXK, RIBXK420 SERIES
RIBXK, RIBXG SERIES
Monitored AC Current
RIBXKF, RIBXKTF 0.25-150A
RIBXKA, RIBXKTA 0.5-150A
RIBXGF, RIBXGTF 0.35-150A
RIBXGA, RIBXGTA 0.75-150A
Relay Trip Point RIBXKF, RIBXKTF 0.25A, fixed RIBXKA, RIBXKTA 0.5-150A, adjustable RIBXGF, RIBXGTF 0.35A, fixed RIBXGFL, RIBXGTFL 0.75A, fixed RIBXGA, RIBXGTA 0.75-150A, adjustable Relay Type Solid state, normally open Relay Rating 30 VAC/VDC, 0.4A maximum Off State Leakage <30 µA @ 30 VAC/VDC On State Voltage Drop <0.3 VAC/VDC @ 0.1A
<1.6 VAC/VDC @ 0.4A
RIBXK420 SERIES
Supply Voltage 24 VDC Output 4-20 mA @ 600Ω, 30 mA maximum Accuracy ±5% FS Linearity ±1% FS Input Range 20, 50, or 100A General Frequency Suitable for most VFD applications Maximum Sensed Voltage 600 VAC Terminations 16" (40.6 cm), 18 AWG, 600V wires or terminals for 14-22 AWG Operating Temperature -30° to 140°F (-34.4° to 60°C) Weight 0.3 lb (0.13 Kg) Approvals UL916, UL864 UL File #S7312, CE, RoHs
0.50 (1.27)
1.46 (3.7)
1.86 (4.73)
1.508 (3.83)
1.008 (2.56)
Ratcheting Cam
Clamp
Removable Mounting Tab
RIBXK420 RIBXK , RIBXG
RIBXK
(cm)
24 VDC
Power Supply
(black)
(red) BAS Input or Other
4-20 mA Load
2.52 (6.4)
2.00 (5.1)
1.10 (2.8)
1.75 (4.4)
Load Wire Opening
0.52 x 0.52 (1.3 x 1.3)
LEDs
Trip
Adjust
Wire Clamp
Removable Mounting Tab
Wh/Yel
Load Wire
Load Wire
Normally open solid-state switch is not polarity sensitive
Models with Screw Terminals
Models with Wire Leads
RIBXG
The Functional Devices RIBXK, RIBXG, RIBXK420 Series include both current-operated switches and current transducers. Solid-core and split-core current-operated switch models have a solid-state switch that operates when the current level sensed by the internal current transformer exceeds a fixed or adjustable set point. Solid-core current transducer models output a 4-20 mA signal proportional to the line current being monitored.
• Solid- and split-core switch models have fixed (go/no go) or adjustable trip points
• Solid-core transducer models have a 4-20 mA output
• Low cost
• Ratcheting cam clamp to secure switch to wire
• Removable mounting tab
RIBXKF Solid-core current-operated switch, wire leads, fixed-trip RIBXKTF Solid-core current-operated switch, terminals, fixed-trip RIBXKA Solid-core current-operated switch, wire leads, adjustable-trip RIBXKTA Solid-core current-operated switch, terminals, adjustable-trip RIBXK420-20 Solid-core current transducer, 0-20A RIBXK420-50 Solid-core current transducer, 0-50A RIBXK420-100 Solid-core current transducer, 0-100A RIBXGF Split-core current-operated switch, fixed 0.35A trip, wire leads RIBXGTF Split-core current-operated switch, fixed 0.35A trip, terminal strip RIBXGFL Split-core current-operated switch, fixed 0.75A trip, wire leads, LEDs RIBXGTFL Split-core current-operated switch, fixed 0.75A trip, terminal strip, LEDs RIBXGA Split-core current-operated switch, adjustable trip, wire leads, LEDs RIBXGTA Split-core current-operated switch, adjustable trip, terminal strip, LEDs
RIBXKF
RIBXKA
RIBXGTF
RIBXK420
RIBXKTF
RIBXKTA
Automation Server Enables StruxureWare Building Operation v1.3
A StruxureWareTM Building Operation server is the core of the system and performs key functionality, such as control logic, trend logging, and alarm supervision. The Automation Server software is pre-loaded on Schneider Electric supplied hardware that supports communication and connectivity to the I/O and field buses. The distributed intelligence of the Automation Server ensures fault tolerance in the system and provides a fully featured user interface through WorkStation and WebStation.
Make the most of your energy SM
Compatible
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9698 www.schneider-electric.com/buildings
SDS-AUTOMATIONSERVER-A4.BU.N.EN.11.2012.0.00.CC
ch ne id
E le ct ric . A ll rig se rv ed
Features
The Automation Server is a powerful device that can act as a standalone StruxureWare Building Operation server and also control I/O modules and monitor and manage field bus devices.
In a small installation, the embedded Automation Server acts as a stand-alone StruxureWare Building Operation server, mounted with its I/O modules in a small footprint. In medium and large installations, functionality is distributed over multiple Automation Servers that communicate over TCP/IP.
Communications hub Capable of coordinating traffic from above and below its location, the Automation Server can deliver data directly to you or to other servers throughout the site. The Automation Server can run multiple control programs, manage local I/O, alarms, and users, handle scheduling and logging, and communicate using a variety of protocols. Because of this, most parts of the system function autonomously and will continue to run as a whole even if communication fails or individual servers or devices go offline.
Variety of connectivity options The Automation Server has numerous ports that enable it to communicate with a wide range of protocols, devices, and servers. The Automation Server has one 10/100 Ethernet port, two RS-485 ports, and one built-in I/O bus port. Additionally, there are two USB host ports and one USB device port. The device port allows you to upgrade and interact with the Automation Server using the Device Administrator.
WorkStation/WebStation interface Through any client, the user experience is similar regardless of which StruxureWare Building Operation server the user is logged on to. The user can log directly on to an Automation Server to engineer, commission, supervise, and monitor the Automation Server as well as its attached I/O modules and field bus devices. See the WorkStation and WebStation data sheets for additional information.
Native support for open protocols One of the cornerstones of StruxureWare Building Operation is support for open standards.
Native BTL-listed BACnet support The Automation Server communicates directly to BACnet/IP and BACnet MS/ TP networks. Compliant with ASHRAE 135-2004, the Automation Server is BTL-listed as a BACnet Building Controller (B-BC)*, the most advanced BACnet Device Profile and as a BACnet Operator Workstation (B-OWS)*.
This capability provides access to the full range of BACnet devices from Schneider Electric and other vendors. The Automation Server can also serve as a BACnet Broadcast Management Device (BBMD) to facilitate BACnet systems that span multiple IP networks.
*See the BTL Product Catalog for up-to-date details on BTL listed firmware revisions: http://www.bacnetinternational.net/btl/index.php?m=20
PrOduCT AT A GLANCE
• Communications hub
• Variety of connectivity options
• WorkStation/WebStation interface
• Native support for open protocols – BACnet, LonWorks and Modbus
• Web Services support
• EcoStruxure Web Services support
• Scalable custom configurations
• Two programming options
• 4 GB of memory for data and backup
• IT friendly and secure
• Hot-connect / Hot-swap
• Patented two-piece design
• Auto-addressing
• Simple dIN-rail installation
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9698 www.schneider-electric.com/buildings
Features (continued)
Native LonWorks support The Automation Server has a built in FTT-10 port for integrated LonWorks functionality to enable access to any Schneider Electric LonWorks field controller or third-party LonWorks devices.
Lonworks networks can be commissioned, bound, and configured from the Automation Server using the built-in LonWorks Network Management Tool. No third-party tools are needed. A protocol analyzer with powerful debugging and network quality monitoring features is also included.
Native Modbus support The Automation Server natively integrates Modbus RS-485 master and slave configurations, as well as TCP client and server. This allows full access to third-party products and the range of Schneider Electric products that communicate on the Modbus protocol, such as power meters, UPS, circuit breakers, and lighting controllers.
Web Services support The Automation Server supports the use of Generic Web Services based on open standards such as SOAP and REST to consume data into StruxureWare Building Operation. Use incoming third-party data (e.g. temperature forecast, energy cost) over the Web to determine site modes, scheduling and programming.
EcoStruxure Web Services support EcoStruxure Web Services, Schneider Electric’s Web Services standard, is natively supported in the Automation Server. EcoStruxure Web Services offers extra features between compliant systems whether within Schneider Electric or authorized third-party systems, including system directory browsing, read/write of current values, alarm receipt and acknowledgement, and historical trend log data. EcoStruxure Web Services is secure.
User name and password are required to log on to the system.
Scalable custom configurations The Automation Server and its family of I/O modules were designed to meet the unique needs of each installation. Depending on the configuration, each Automation Server can control up to 464 I/O points. Because power and communications are delivered along a common bus, multiple modules can be plugged together without tools in a simple one-step process using the built-in connectors.
Two programming options Unique to the industry, the Automation Server has both Script and Function Block programming options. This flexibility ensures that the best programming method can be selected for the application.
4 GB of memory for data and backup The Automation Server has an available capacity of 4 GB of memory. This represents 2 GB for application and historical data and 2 GB dedicated for backup storage. This ensures that all data is safe from damage, loss, or unintended edits.
Users can also manually back up or restore the Automation Server to a storage location on a PC or network. Through the Enterprise Server, users have the ability to perform scheduled backups of associated Automation Servers to network storage for even greater levels of protection.
IT friendly and secure The Automation Server communicates using networking standards, such as DHCP, HTTP, and HTTPS (see sidebar for more). This makes installation easy, management simple, and transactions secure.
Hot-connect / Hot-swap Because critical applications require 24-hour operation, Schneider Electric designed the entire family of I/O modules for hot-connection of terminal bases and hot-swapping of modules to and from their bases. This design ensures continuous power and communication during many service operations.
Patented two-piece design Each module can be separated from its terminal base to allow the site to be wired prior to the installation of the electronics. The patented locking mechanism serves as handles for removing the module from its base. All critical components have a protective cover that permits natural convection cooling to occur.
Auto-addressing The auto-addressing feature eliminates the need for setting DIP switches or pressing commission buttons. With the Automation Server family, each I/O module automatically knows its order in the chain and assigns itself accordingly.
Simple DIN-rail installation Fasteners easily snap into a locked position for panel installation. The fastener has a quick-release feature for easy DIN rail removal.
Supported Protocols
• IP addressing
• TCP communications
• dHCP / dNS for rapid deployment and lookup of addresses
• HTTP/HTTPS - Internet access through firewalls, enabling for remote monitoring and control
• NTP (Network Time Protocol) for time synchronization throughout the system
• SMTP enables sending email messages
3.
3.
November 2012 gg
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9698 www.schneider-electric.com/buildings
All brand names, trademarks, and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice.
v1.3 Specifications
Specifications
AS-L
LO
-2
LO
-1
TP/FTRS-485
h ie ld
R
T
V
X
/R
Operator Panel
LON
F a c ry
1 2 3 4 5 6 7 8 9 10 11 12
The connection cable for these USB ports must not exceed 3 m (10 ft).
The connection cable for this USB port must not exceed 3 m (10 ft).
Host 10/100
Ethernet
13 15 16 19
.3
V
RS-485
Com A Com B
Add-on options
SW-EWS-1, EcoStruxure Web Services
(run-time) option – Consume only for one Automation Server, no mainte-nance
P/N: SXWSWEWSX00001
SW-EWS-2, EcoStruxure Web Services
(run-time) option – Serve & Consume for one Automation Server, no maintenance
P/N: SXWSWEWSX00002
SW-EWS-3, EcoStruxure Web Services
(run-time) option – Serve & Consume, plus Historical trend log data for one
Automation Server, no maintenance
P/N: SXWSWEWSX00003
SW-GWS-1, Web Services (Generic
Consume) option for one Automation
Server, no maintenance
P/N: SXWSWGWSX00001
Connectors
USB 1 device and 2 host ports
BACnet
BACnet/IP and MS/TP
BTL B-BC (BACnet Building Controller)*
BTL B-OWS (BACnet Operator
Workstation)*
WSPCert
*Specific firmwares versions may be required for BTL Listing status see: http:// www.bacnetinternational.net/btl/index.
php?m=20
LonWorks TP/FT-10
COM A 2-wire RS-485
COM B 2-wire RS-485 and 3.3 VDC
I/O Modules RS-485
TCP
Binary, port configurable, default 4444
HTTP
Non-binary, port configurable, default 80
HTTPS
Encrypted supporting SSL 1.0, 2.0, 3.0 and TSL 1.0, port configurable default 443
SMTP
Email sending, port configurable, default 25
CPU
Frequency 160 MHz
SDRAM 128 MB
Flash memory 4 GB
Part numbers
P/N: SXWAUTSVR10001
TB-AS-W1, Terminal Base for
(Required for each Automation
Server)
P/N: SXWTBASW110001
Electrical
DC input
Nominal voltage
24 VDC
Power consumption
Max. 7 W
Mechanical
Enclosure
Eco Friendly ABS/PC
Enclosure rating
IP 20
Plastic rating
UL94-5VB rated plastic
Dimensions (including terminal base)
90 W x 114 H x 64 D mm
(3.6 W x 4.5 H x 2.5 D in.)
Weight (including terminal base)
0.294 kg (0.65 lb)
Weight (excluding terminal base)
0.194 kg (0.43 lb)
Installation DIN-rail or panel installation
Operation environment
Ambient temperature, operating
0 °C to 50 °C (32 °F to 122 °F)
Ambient temperature, storage
–20 °C to +70 °C (–4 °F to +158 °F)
Humidity Max. 95 % RH (non-condensing)
Agency compliances
Emission
C-Tick; EN 61000-6-3;
FCC Part 15, Sub-part B, Class B
Immunity EN 61000-6-2
Safety UL 916 C-UL US Listed
Real-Time Clock backup
30 days
Communications
Ethernet LAN interface
10/100 Mbit/s; twisted pair cable with RJ-45 connector
StruxureWareTM Building Operation
AS PICS
Product Implementation Conformance Statement
Date 22 August 2012
Vendor name Schneider Electric
Vendor ID 10
Website www.Schneider-Electric.com/buildings
Range name StruxureWare Building Operation
Product name Automation Server
Product model number AS
Application software version N/A
Firmware revision 1.3
Base ASHRAE standard 135-2004-d,e,f
BACnet Protocol version 1
BACnet Protocol revision 6
Product description
The Automation Server is a native BACnet/IP protocol operator workstation and controller with a built-in web server and expandable Input/Output through the use of expansion modules. It has 2 serial ports, one of which may be used to communicate with MS/TP controller devices. The Automation Server also serves as a BACnet protocol router and BACnet/ IP Broadcast Management Device (BBMD). It performs BACnet routing functions among attached MS/TP networks.
The Automation Server also natively supports other protocols, such as LonWorks, Modbus, and Web Services, and can be used as a gateway device to exchange values between protocols.
Note: Requires StruxureWare Workstation P/N SW-STATION for user interface.
StruxureWare has been designed to • strictly comply with the ASHRAE BACnet standard.
BACnet enables integration between •
Devices designed for a wide variety of applications.
Natively supports BACnet, LonWorks, •
Modbus, and Web Services, and can serve as a gateway between protocols
This Protocol Implementation Confor-• mance Statement (PICS) document details the BACnet Interoperability
Building Blocks that are supported in
StruxureWare.
n e r ri c.
A ri r d
PP-AS-PICS-US.BU.N.EN.08.2012. August 2012 BAS
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9698 www.schneider-electric.com/buildings
All brand names, trademarks and registered marks are the property of their respective owners. Information contained within this document is subject to change without notice.
AS
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9698 www.schneider-electric.com/buildings ©
Device Profi le Support
Controller Profi le:
BACnet Building Controller (B-BC) X
BACnet Advanced Application Controller (B-AAC)
BACnet Application Specifi c Controller (B-ASC)
BACnet Smart Actuator (B-SA)
BACnet Smart Sensor (B-SS)
Operator Profi le:
BACnet Advanced Operator Workstation (B-AWS)
BACnet Operator Workstation (B-OWS) X
BACnet Operator Display (B-OD)
Segmentation Capability
Segmentation Supported Window
Size
Able to transmit segmented messages X 1
Able to receive segmented messages X 1
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9698 www.schneider-electric.com/buildings ©
Data Link Layer and Routing Options
Data Link Supported Data Rates Router for Data Link
BACnet/IP X Hardware dependent
Ethernet - ISO 8802_3
MS/TP master X 9600, 19200, 38400, 76800
Kbit/s
MS/TP slave
Zigbee
ARCnet - ANSI/ATA 878.1
RS-485 ANSI/ATA 878.1
LonTalk TP/FT - 10
LonTalk/IP
Point-to-Point EIA 232
Point-to-Point - modem
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9698 www.schneider-electric.com/buildings ©
Other Networking Options
Networking Option Supported
Static Device Binding Supported
Annex H, BACnet Tunneling Router over IP
BACnet Broadcast Management Device (BBMD) X
BBMD supports registration by foreign device X
Device support registration as foreign device X
Character Sets Supported
Character Sets Supported
ANSI X3.4 X
ISO 8859-1 X
ISO 10646 (USC-2) X
ISO 10646 (UCS-4) X
IBM/Microsoft DBCS
JIS C 6226
Note: For messages received in UTF-8 encoding, responses are transmitted with the narrowest character set for optimal interoperability.
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9698 www.schneider-electric.com/buildings ©
DS-RP-A ReadProperty-A x x x x x
DS-RP-B ReadProperty-B x x x x x x x x x
DS-RPM-A ReadPropertyMultiple-A x x x x
DS-RPM-B ReadPropertyMultiple-B x x x
DS-RPC-A ReadPropertyConditional-A
DS-RPC-B ReadPropertyConditional-B x
DS-WP-A WriteProperty-A x x x x x
DS-WP-B WriteProperty-B x x x x x
DS-WPM-A WritePropertyMultiple-A x x x
DS-WPM-B WritePropertyMultiple-B x x x
DS-COV-A COV-A x
DS-COV-B COV-B x
DS-COVP-A COVP-A
DS-COVP-B COVP-B
DS-COVU-A COV-Unsolicited-A
DS-COVU-B COV-Unsolicited-B
DS-V-A View-A x x x
DS-M-A Modify-A x x x
DS-AV-A Advanced View-A x
DS-AM-A Advanced Modify-A x
BACnet Interoperability Building Blocks (BIBBs) Support
BIBB Description
BACnet Standard ro u o fo an ce
Data Sharing
-A
-O
D
-B
-S
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9698 www.schneider-electric.com/buildings ©
AE-N-A Notifi cation-A x x x
AE-N-I-B Notifi cation Internal-B x x x
AE-N-E-B Notifi cation External-B
AE-ACK-A ACK-A x x x
AE-ACK-B ACK-B x x x
AE-ASUM-A Summary-A x
AE-ASUM-B Alarm Summary-B
AE-ESUM-A Enrollment Summary-A x
AE-ESUM-B Enrollment Summary-B x x
AE-INFO-A Information-A x
AE-INFO-B Information-B x x x
AE-LS-A LifeSafety-A
AE-LS-B LifeSafety-B
AE-AS-A Alarm Summary-A x x x
AE-VN-A View Notifi cation-A x x x
AE-VM-A View Modify-A x x
AE-AVM-A Advanced View Modify-A x
AE-AVN-A
Advanced View Notifi cations-A x
AE-ELVM-A
Event Log View and Modify-A x1
Alarms and Events
1 Not required for devices claiming conformance to a protocol revision less than 7.
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9698 www.schneider-electric.com/buildings ©
T-VMT-I-B
Viewing and Modifying Trends Internal-B x x
T-VMT-E-B
Viewing and Modifying Trends External-B
T-ATR-A
Automated Trend Retrieval-A
T-ATR-B
Automated Trend Retrieval-B
T-V-A View-A x x
T-A-A Archiving-A x
T-AVM-A
Advanced View and Modify-A
SCHED-I-B Scheduling - Internal-B x x
SCHED-E-B Scheduling - External-B x x
SCH-VM-A Scheduling - View Modify x x
SCH-AVM-A
Scheduling - Advanced View Modify
SCHED-WS-A
Scheduling - Weekly Schedule-A
SCHED-WS-I-B
Scheduling Weekly Schedule Internal-B
SCHED-R-B Scheduling - Readonly-B
Schedules
Trends
Note: The SCHED-A BACnet interoperability building block was removed from the BACnet Standard.
Note: The T-VMT-A BACnet interoperability building block was removed from the BACnet Standard.
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9698 www.schneider-electric.com/buildings ©
DM-DDB-A Dynamic Device Binding-A x x x x x
DM-DDB-B Dynamic Device Binding-B x x x x x x x1 x1 x
DM-DOB-A Dynamic Object Binding-A
DM-DOB-B Dynamic Object Binding-B x x x x x x x1 x1 x
DM-DCC-A
DeviceCommunication Control-A
DM-DCC-B
DeviceCommunication Control-B x x x x
DM-PT-A Private Transfer-A
DM-PT-B Private Transfer-B
DM-TM-A Text Message-A
DM-TM-B Text Message-B
DM-TS-A TimeSynchronization-A x
DM-TS-B TimeSynchronization-B x x x x
DM-UTC-A UTCTimeSynchronization-A
DM-UTC-B UTCTimeSynchronization-B x x x
DM-RD-A ReinitializeDevice-A x x
DM-RD-B ReinitializeDevice-B x x x x
DM-BR-A Backup and Restore-A x x
DM-BR-B Backup and Restore-B x x
DM-R-A Restart-A
DM-R-B Restart-B
DM-LM-A List Manipulation-A
DM-LM-B List Manipulation-B
DM-OCD-A
Object Creation and Deletion-A
DM-OCD-B
Object Creation and Deletion-B
Device Management
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9698 www.schneider-electric.com/buildings ©
DM-VT-A Virtual Terminal-A
DM-VT-B Virtual Terminal-B
DM-ANM-A
Automatic Network Mapping-A
DM-ADM-A
Automatic Device Mapping-A
DM-ATS-A
Automatic Time Synchronization
DM-MTS-A
Manual Time Synchronization-A x x x
Device Management (continued)
1 Not required if the device is a BACnet MS/TP Slave.
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9698 www.schneider-electric.com/buildings ©
NM-CE-A Connection Establishment-A
NM-CE-B Connection Establishment-B
NM-RC-A Router Confi guration-A
NM-RC-B Router Confi guration-B x
Network Management
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9698 www.schneider-electric.com/buildings ©
23 Accumulator P P P P P
0 Analog Input P P x P P
1 Analog Ouput P P x P P
2 Analog Value P P x x x
18 Averaging P P P P P
3 Binary Input P P x P P
4 Binary Output P P x P P
5 Binary Value P P x x x
6 Calendar P P x x x
7 Command P P P P P
8 Device x x x x x x x x x
9 Event Enrollment P P x x x
10 File P x P P
11 Group P
21 Life Safety Point
22 Life Safety Zone
12 Loop P P x x x
13 Multi-state Input P P x P P
14 Multi-state Output P P x P P
19 Multi-state Value P P x x x
15 Notifi cation Class P P x x x
16 Program P P x P P
24 Pulse Converter P P P P P
17 Schedule P P x x x
20 Trend Log P P x x x
30 Access Door
25 Event Log P
28 Load Control P P P P P
29 Structured View P
27 Trend Log Multiple P
32 Access Credential
Supported BACnet Object Types
ID Description C at ab el et
Product ConformanceBACnet Standard
Supported
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9698 www.schneider-electric.com/buildings ©
33 Access Point
34 Access Rights
35 Access User
36 Access Zone
37 Credential Data Input
26 Global Group P
Supported BACnet Object Types (continued)
ID Description C at el et
Product ConformanceBACnet Standard
Supported
Note: P indicates ‘‘Proxy Only,’’ which means that the object is only supported by Workstation.
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9698 www.schneider-electric.com/buildings ©
Accumulator
75 object-identifi er R Object ID P
77 object-name R BACnet name P P
79 object-type R BACnet type P
85 present-value R1 Value P P
28 description O Description P P
31 device-type O Device type P P
111 status-fl ags R Status fl ags P
36 event-state R Event state P
103 reliability O Reliability P
81 out-of-service R Out of service P P
186 scale R
117 units R
188 prescale O
65 max-pres-value R Maximum value P P
192 value-change-time O2 Value change time P
190 value-before-change O2, 3 Value before change P P
191 value-set O2, 3 Value set P P
184 logging-record O
183 logging-object O
186 pulse-rate O1, 4 Pulse rate P P
45 high-limit O4 Upper limit P P
59 low-limit O4 Lower limit P P
182 limit-monitoring-interval O4 Limit Monitoring interval
P P
17 notifi cation-class O4 BACnet notifi cation P P
113 time-delay O4 Time delay P P
52 limit-enable O4 Limit enable P P
35 event-enable O4 Event enable P P
ID
eq rit property name R ea da bl
Internal device property nameO pt io na l
Accumulator (proxy)
StruxureWare Device
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9698 www.schneider-electric.com/buildings ©
0 acked-transitions O4 Acknowledged transitions
72 notify-type O4 Notify type P P
130 event-time-stamps O To-off-normal time To-fault time To-normal time
168 profi le-name O Profi le name P
1 This property is required to be writable when out-of-service is TRUE.
2 These properties are required if either Value_Before_Change or Value_Set is writable.
3 Either Value_Before_Change or Value_Set may be writable, but not both.
4 These properties are required if the object supports intrinsic reporting.
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9698 www.schneider-electric.com/buildings ©
Analog Input
2 This property is required if the object supports COV reporting.
3 These properties are required if the object supports intrinsic reporting.
75 object-identifi er R Object ID R
77 object-name R…