posted beside the diagrams. The framed instructions shall be posted before acceptance testing of the systems.
3.13 PERFORMANCE OF WATER HEATING EQUIPMENT
Standard rating condition terms are as follows:
EF = Energy factor, overall efficiency.
ET = Thermal efficiency with 70 degrees F delta T.
EC = Combustion efficiency, 100 percent - flue loss when smoke = o (trace is permitted).
SL = Standby loss in W/0.093 sq. m. (W/sq. ft.) based on 80 degrees F delta T, or in percent per hour based on nominal 90 degrees F delta T.
HL = Heat loss of tank surface area.
V = Storage volume in liters
3.13.1 Storage Water Heaters
3.13.1.1 Electric
a. Storage capacity of 120 gallons or less, and input rating of 12 kW or less: minimum energy factor (EF) shall be 0.95-0.00132V per 10 CFR 430.
b. Storage capacity of more than 120 gallons or input rating more than 12 kW: maximum SL shall be 1.9 W/sq. ft. per ASHRAE 90.1 - SI( ASHRAE 90.1 - IP), Addenda B.
3.13.1.2 Gas
a. Storage capacity of 100 gallons or less, and input rating of 21980 W (75,000 Btu/h) or less:
minimum EF shall be 0.62-0.0019V per 10 CFR 430.
b. Storage capacity of more than 100 gallons - or input rating more than 21980 W: (75,000 Btu/h:)
Et shall be 77 percent; maximum SL shall be 1.3+38/V, per CSA/AM Z21.10.3.
3.13.1.3 Oil
a. Storage capacity of 50 gallons or less and input rating of 30773 W (105,000 Btu/h) or less:
minimum EF shall be 0.80-0.0019V per 10 CFR 430.
b. Storage capacity of more than 50 gallons or input rating more than 30773 W: (105,000 Btu/h:)
EC shall be 83 percent; maximum SL shall be 1.3+38/V, per 10 CFR 430.
3.13.2 Unfired Hot Water Storage
3.13.2.1 Volumes and inputs: maximum HL shall be 6.5 Btu/h/sq. ft.
3.13.3 Instantaneous Water Heater
3.13.3.1 Gas
a. Volumes and inputs: ET shall be 80 percent per CSA/AM Z21.10.3.
22 00 00-51
SABER Specifications
FA2517-13-R-5000
Attachment 1 20 May 2014
3.13.3.2 Oil
a. Capacities and inputs: EC shall be 83 percent per CSA/AM Z21.10.3.
3.13.4 Pool Heaters
3.13.4.1 Gas/oil fuel, capacities and inputs: ET shall be 78 percent per CSA/AM Z21.56.
3.14 TABLES
TABLE I
PIPE AND FITTING MATERIALS FOR
DRAINAGE, WASTE, AND VENT PIPING SYSTEMS
SERVICE
Item # Pipe and Fitting Materials A B C D E F
1. Cast iron soil pipe and fittings, hub X X X X X and spigot, ASTM A 74 with compression gaskets. Pipe and fittings shall be marked with the CISPI trademark.
2. Cast iron soil pipe and fittings hubless, X X X X CISPI 301 and ASTM A 888. Pipe and fittings shall be marked with the CISPI trademark.
3. Cast iron drainage fittings, threaded, X X X ASME B16.12 for use with Item 10
4. Cast iron screwed fittings (threaded) X X ASME B16.4 for use with Item 10
5. Grooved pipe couplings, ferrous and X X X X non-ferrous pipe ASTM A 536 and ASTM A 47
6. Ductile iron grooved joint fittings X X X X for ferrous pipe ASTM A 536 and ASTM A 47 for use with Item 5
7. Bronze sand casting grooved joint X X X X pressure fittings for non-ferrous pipe ASTM B 584, for use with Item 5
22 00 00-52
SABER Specifications
FA2517-13-R-5000
Attachment 1
8. Wrought copper grooved joint pressure X X pressure fittings for non-ferrous pipe
ASTM B 75M (ASTM B 75) C12200,
ASTM B 152, C11000,
ASME B16.22
ASME B16.22 for use with Item 5
9. Malleable-iron threaded fittings, X X galvanized ASME B16.3 for use with Item 10
10. Steel pipe, seamless galvanized, X X X ASTM A 53, Type S, Grade B
11. Seamless red brass pipe, ASTM B 43 X X
12. Bronzed flanged fittings, X X ASME B16.24 for use with Items 11 and 14
13. Cast copper alloy solder joint X X pressure fittings, ASME B16.18 or use with Item 14
14. Seamless copper pipe, ASTM B 42 X
15. Cast bronze threaded fittings, X X
ASME B16.15
16. Copper drainage tube, (DWV), X* X X* X X
ASTM B 306
17. Wrought copper and wrought X X X X X alloy solder-joint drainage fittings. ASME B16.29
18. Cast copper alloy solder joint X X X X X drainage fittings, DWV, ASME B16.23
19. Acrylonitrile-Butadiene-Styrene (ABS) X X X X X X plastic drain, waste, and vent pipe and fittings ASTM D 2661, ASTM F 628
20. Polyvinyl Chloride plastic drain, X X X X X X waste and vent pipe and fittings, ASTM D 2665, ASTM F 891, (Sch 40)
ASTM F 1760
22 00 00-53
SABER Specifications
FA2517-13-R-5000
Attachment 1
21. Process glass pipe and fittings, X
ASTM C 1053
22. High-silicon content cast iron pipe X X X and fittings (hub and spigot, and mechanical joint), ASTM A 518/A 518M
23. Polypropylene (PP) waste pipe and X fittings, ASTM D 4101
24. Filament-wound reinforced thermosetting X resin (RTRP) pipe, ASTM D 2996
SERVICE:
A - Underground Building Soil, Waste and Storm Drain B - Aboveground Soil, Waste, Drain In Buildings C - Underground Vent D - Aboveground Vent E - Interior Rainwater Conductors Aboveground F - Corrosive Waste And Vent Above And Belowground
* - Hard Temper
22 00 00-54
FA2517-13-R-5000
Attachment 1
TABLE II
PIPE AND FITTING MATERIALS FOR PRESSURE PIPING SYSTEMS
SERVICE
Item # Pipe and Fitting Materials A B C D
1. Malleable-iron threaded fittings, X X X X
a. Galvanized, ASME B16.3 for use with Item 4a
b. Same as "a" but not galvanized X for use with Item 4b
2. Grooved pipe couplings, ferrous pipe X X X ASTM A 536 and ASTM A 47, non-ferrous pipe, ASTM A 536 and ASTM A 47,
3. Ductile iron grooved joint fittings X X X for ferrous pipe ASTM A 536 and ASTM A 47, for use with Item 2
4. Steel pipe: X X X X
a. Seamless, galvanized, ASTM A 53, Type S, Grade B
b. Seamless, black, X
ASTM A 53,
Type S, Grade B
5. Seamless red brass pipe, X X X
ASTM B 43
6. Bronze flanged fittings, X X X
ASME B16.24
for use with Items 5 and 7
7. Seamless copper pipe, X X X
ASTM B 42
8. Seamless copper water tube, X** X** X** X***
ASTM B 88, ASTM B 88M
9. Cast bronze threaded fittings, X X X ASME B16.15 for use with Items 5 and 7
22 00 00-55
FA2517-13-R-5000
Attachment 1
10. Wrought copper and bronze solder-joint X X X X pressure fittings, ASME B16.22 for use with Items 5, 7 and 8
11. Cast copper alloy solder-joint X X X X pressure fittings, ASME B16.18 or use with Item 8
12. Bronze and sand castings grooved X X X joint pressure fittings for non-ferrous pipe ASTM B 584, for use with Item 2
13. Polyethylene (PE) plastic pipe, X X Schedules 40 and 80, based on outside diameter
ASTM D 2447
14. Polyethylene (PE) plastic pipe X X (SDR-PR), based on controlled outside diameter, ASTM D 3035
15. Polyethylene (PE) plastic pipe X X (SIDR-PR), based on controlled inside diameter, ASTM D 2239
16. Butt fusion polyethylene (PE) plastic X X pipe fittings, ASTM D 3261 for use with Items 14, 15, and 16
17. Socket-type polyethylene fittings X X for outside diameter-controlled polyethylene pipe, ASTM D 2683 for use with Item 15
18. Polyethylene (PE) plastic tubing, X X
ASTM D 2737
19. Chlorinated polyvinyl chloride X X X (CPVC) plastic hot and cold water distribution system, ASTM D 2846
20. Chlorinated polyvinyl chloride X X X (CPVC) plastic pipe, Schedule 40 and 80, ASTM F 441
22 00 00-56
SABER Specifications
FA2517-13-R-5000
Attachment 1
21. Chlorinated polyvinyl chloride X X X (CPVC) plastic pipe (SDR-PR)
ASTM F 442
22. Threaded chlorinated polyvinyl chloride X X X (chloride CPVC) plastic pipe fittings, Schedule 80, ASTM F 437, for use with Items 20, and 21
23. Socket-type chlorinated polyvinyl X X X chloride (CPVC) plastic pipe fittings, Schedule 40, ASTM F 438 for use with Items 20, 21, and 22
24. Socket-type chlorinated polyvinyl X X X chloride (CPVC) plastic pipe fittings Schedule 80, ASTM F 439 for use with Items 20, 21, and 22
25. Polyvinyl chloride (PVC) plastic pipe, X X Schedules 40, 80, and 120, ASTM D 1785
26. Polyvinyl chloride (PVC) pressure-rated X X pipe (SDR Series), ASTM D 2241
27. Polyvinyl chloride (PVC) plastic pipe X X fittings, Schedule 40, ASTM D 2466
28. Socket-type polyvinyl chloride (PVC) X X plastic pipe fittings, schedule 80, ASTM D 2467 for use with Items 26 and 27
29. Threaded polyvinyl chloride (PVC) X X plastic pipe fittings, schedule 80, ASTM D 2464
30. Joints for IPS pvs pipe using solvent X X cement, ASTM D 2672
31. Filament-wound reinforced X X thermosetting resin (RTRP) pipe, ASTM D 2996
32. Steel pipeline flanges, X X
MSS SP-44
22 00 00-57
SABER Specifications
FA2517-13-R-5000
Attachment 1
33. Fittings: brass or bronze; X X ASME B16.15, and
ASME B16.18
ASTM B 828
34. Carbon steel pipe unions, X X X socket-welding and threaded, MSS SP-83
35. Malleable-iron threaded pipe X X unions ASME B16.39
36. Nipples, pipe threaded X X X
ASTM A 733
37. Crosslinked Polyethylene (PEX) X X Plastic Pipe ASTM F 877.
38. Press Fittings X X
A - Cold Water Service Aboveground B - Hot and Cold Water Distribution 180 degrees F Maximum Aboveground C - Compressed Air Lubricated D - Cold Water Service Belowground Indicated types are minimum wall thicknesses.
** - Type L - Hard
*** - Type K - Hard temper with brazed joints only or type K-soft temper without joints in or under floors
**** - In or under slab floors only brazed joints
22 00 00-58
FA2517-13-R-5000
Attachment 1
TABLE III
STANDARD RATING CONDITIONS AND MINIMUM PERFORMANCE RATINGS FOR WATER
HEATING
EQUIPMENT
A. STORAGE WATER HEATERS
STORAGE
CAPACITY INPUT
FUEL LITERS RATING TEST PROCEDURE REQUIRED
PERFORMANCE
Elect. 454 max. 12 kW max. 10 CFR 430 EF = 0.95-0.00132V minimum
Elect. 454 min. OR 12 kW min. ASHRAE 90.1 - SI SL = 1.9 W/0.09 sq.m.
(Addenda B) maximum
Gas 380 max. 22 kW max. 10 CFR 430 EF = 0.80-0.0019V minimum
Gas 380 min. OR 22 kW min. CSA/AM Z21.10.3 ET= 80 percent;
SL = 1.3+38/V max.
Oil 190 max. 30.8 kW 10 CFR 430 EF = 0.80-0.0019V minimum
Oil 190 min. OR 30.8 kW 10 CFR 430 EC = 83 percent;
SL = 1.3+38/V
maximum
B. Unfired Hot Water Storage, Instantaneous water heater, and pool heater.
Volumes and inputs: maximum HL shall be 20.5 W/sq. meter
C. Instantaneous Water Heater
Gas All All CSA/AM Z21.10.3 ET = 80 percent
Oil All All CSA/AM Z21.10.3 EC = 83 percent
D. Pool Heater
Gas or All All CSA/AM Z21.56 ET = 78 percent Oil
TERMS:
EF = Energy factor, overall efficiency.
ET = Thermal efficiency with 21 degrees C delta T.
EC = Combustion efficiency, 100 percent - flue loss when smoke = 0
22 00 00-59
SABER Specifications
FA2517-13-R-5000
Attachment 1
(trace is permitted).
SL = Standby loss in W/0.09 sq. m. based on 27 degrees C delta T, or in percent per hour based on nominal 32 degrees C delta T.
HL = Heat loss of tank surface area V = Storage volume in gallons
TABLE III
STANDARD RATING CONDITIONS AND MINIMUM PERFORMANCE RATINGS FOR WATER
HEATING
EQUIPMENT
A. STORAGE WATER HEATERS
STORAGE
CAPACITY INPUT
FUEL GALLONS RATING TEST PROCEDURE REQUIRED
PERFORMANCE
Elect. 120 max. 12 kW max. 10 CFR 430 EF = 0.95-0.00132V minimum
Elect. 120 min. OR 12 kW min. ASHRAE 90.1 - IP SL = 1.9 W/sq. ft.
(Addenda B) maximum
Gas 100 max. 75,000 Btu/h 10 CFR 430 EF = [0.62][80]-max. 0.0019V minimum
Gas 100 min. OR 75,000 Btu/h CSA/AM Z21.10.3 ET = 80 percent;
SL = 1.3+38/V max.
Oil 50 max. 105,000 Btu/h 10 CFR 430 EF = 0.80-0.0019V minimum
Oil 51 min. OR 105,000 Btu/h 10 CFR 430 EC = 83 percent;
SL = 1.3+38/V
maximum
B. Unfired Hot Water Storage, instantaneous water heater, and pool heater.
Volumes and inputs: maximum HL shall be 6.5 Btu/h/sq. ft.
C. Instantaneous Water Heater
Gas All All CSA/AM Z21.10.3 ET = 80 percent
Oil All All CSA/AM Z21.10.3 EC = 83 percent
D. Pool Heater
Gas or All All CSA/AM Z21.56 ET = 78 percent
22 00 00-60
SABER Specifications
FA2517-13-R-5000
Attachment 1
Oil
TERMS:
EF = Energy factor, overall efficiency.
ET = Thermal efficiency with 70 degrees F delta T.
EC = Combustion efficiency, 100 percent - flue loss when smoke = 0 (trace is permitted).
SL = Standby loss in W/sq. ft. based on 80 degrees F delta T, or in percent per hour based on nominal 90 degrees F delta T.
HL = Heat loss of tank surface area V = Storage volume in gallons
END OF SECTION 22 00 00
22 00 00-61
SABER Specifications
FA2517-13-R-5000
Attachment 1
SECTION 22 04 00.00 10
PLUMBING, HOSPITAL
PART 1 GENERAL
1.1 REFERENCES
1.1.1 The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation only. Unless other wise noted, the latest published version and/or revision shall be used.
1.1.1.1 AIR-CONDITIONING, HEATING AND REFRIGERATION INSTITUTE (AHRI)
a. AHRI 1010 Self-Contained, Mechanically Refrigerated Drinking-Water Coolers
1.1.1.2 AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR-CONDITIONING
ENGINEERS (ASHRAE)
a. ASHRAE 146 Method of Testing and Rating Pool Heaters
b. ASHRAE 90.1 - IP Energy Standard for Buildings Except Low-Rise Residential Buildings, I-P Edition
1.1.1.3 AMERICAN SOCIETY OF SANITARY ENGINEERING (ASSE)
a. ASSE 1001 Atmospheric Type Vacuum Breakers
b. ASSE 1003 Performance Requirements for Water Pressure Reducing Valves
c. ASSE 1006 Residential Use Dishwashers
d. ASSE 1011 Hose Connection Vacuum Breakers
e. ASSE 1012 Backflow Preventer with Intermediate Atmospheric Vent
f. ASSE 1013 Reduced Pressure Principle Backflow Preventers and Reduced Pressure Fire Protection Principle Backflow Preventers
g. ASSE 1018 Trap Seal Primer Valves - Potable, Water Supplied
h. ASSE 1020 Pressure Vacuum Breaker Assembly
i. ASSE 1037 Performance Requirements for Pressurized Flushing Devices (Flushometer) for Plumbing Fixtures
j. ASSE Series 6000 WARNING: Text in tags exceeds the maximum length of 300 characters
1.1.1.4 AMERICAN WATER WORKS ASSOCIATION (AWWA)
a. AWWA 10084 Standard Methods for the Examination of Water and Wastewater
b. AWWA B300 Hypochlorites
c. AWWA B301 Liquid Chlorine
d. AWWA C105/A21.5 Polyethylene Encasement for Ductile-Iron Pipe Systems
22 04 00.00 10-1
SABER Specifications
FA2517-13-R-5000
Attachment 1
e. AWWA C203 Coal-Tar Protective Coatings and Linings for Steel Water Pipelines - Enamel and Tape - Hot-Applied
f. AWWA C606 Grooved and Shouldered Joints
g. AWWA C651 Standard for Disinfecting Water Mains
h. AWWA C652 Disinfection of Water-Storage Facilities
i. AWWA D100 Welded Steel Tanks for Water Storage
1.1.1.5 AMERICAN WELDING SOCIETY (AWS)
a. AWS A5.8/A5.8M Specification for Filler Metals for Brazing and Braze Welding
1.1.1.6 ASME INTERNATIONAL (ASME)
a. ASME A112.1.2 Standard for Air Gaps in Plumbing Systems (For Plumbing Fixtures and Water-Connected Receptors)
b. ASME A112.14.1 Backwater Valves
c. ASME A112.18.1 Standard for Plumbing Fixture Fittings
d. ASME A112.19.1 Enameled Cast Iron Plumbing Fixtures
e. ASME A112.19.2 Standard for Vitreous China Plumbing Fixtures and Hydraulic Requirements for Water Closets and Urinals
f. ASME A112.19.3 Stainless Steel Plumbing Fixtures (Designed for Residential Use)
g. ASME A112.6.3 Standard for Floor and Trench Drains
h. ASME B1.20.1 Pipe Threads, General Purpose (Inch)
i. ASME B1.20.7 Standard for Hose Coupling Screw Threads (Inch)
j. ASME B16.12 Cast Iron Threaded Drainage Fittings
k. ASME B16.15 Cast Bronze Threaded Fittings Classes 125 and 250
l. ASME B16.18 Cast Copper Alloy Solder Joint Pressure Fittings
m. ASME B16.21 Nonmetallic Flat Gaskets for Pipe Flanges
n. ASME B16.22 Standard for Wrought Copper and Copper Alloy Solder Joint Pressure Fittings
o. ASME B16.23 Cast Copper Alloy Solder Joint Drainage Fittings – DWV
p. ASME B16.24 Cast Copper Alloy Pipe Flanges and Flanged Fittings: Classes 150, 300, 400, 600, 900, 1500, and 2500
q. ASME B16.29 Wrought Copper and Wrought Copper Alloy Solder Joint Drainage Fittings – DWV
r. ASME B16.3 Malleable Iron Threaded Fittings, Classes 150 and 300
s. ASME B16.34 Valves - Flanged, Threaded and Welding End
t. ASME B16.39 Standard for Malleable Iron Threaded Pipe Unions; Classes 150, 250, and 300
u. ASME B16.4 Standard for Gray Iron Threaded Fittings; Classes 125 and 250
22 04 00.00 10-2
SABER Specifications
FA2517-13-R-5000
Attachment 1
v. ASME B16.5 Standard for Pipe Flanges and Flanged Fittings: NPS 1/2 Through NPS 24
w. ASME B19.3 Safety Standard for Compressors for Process Industries
x. ASME B31.1 Power Piping
y. ASME B31.5 Refrigeration Piping and Heat Transfer Components
z. ASME B40.100 Pressure Gauges and Gauge Attachments
aa. ASME BPVC SEC IV Boiler and Pressure Vessel Code; Section IV, Recommended Rules for the Care and Operation of Heating Boilers
bb. ASME BPVC SEC IX Boiler and Pressure Vessel Code; Section IX, Welding and Brazing Qualifications
cc. ASME BPVC SEC VIII D1 Boiler and Pressure Vessel Code; Section VIII, Pressure Vessels Division 1 - Basic Coverage
dd. ASME CSD-1 Control and Safety Devices for Automatically Fired Boilers
1.1.1.7 ASSOCIATION FOR IRON AND STEEL TECHNOLOGY (AIST)
a. AIST PB-224 Stainless Steels
1.1.1.8 ASTM INTERNATIONAL (ASTM)
a. ASTM A 105 Standard Specification for Carbon Steel Forgings for Piping Applications
b. ASTM A 183 Standard Specification for Carbon Steel Track Bolts and Nuts
c. ASTM A 193 Standard Specification for Alloy-Steel and Stainless Steel Bolting Materials for High-Temperature Service
d. ASTM A 47 Standard Specification for Steel Sheet, Aluminum-Coated, by the Hot-Dip Process
e. ASTM A 515 Standard Specification for Pressure Vessel Plates, Carbon Steel, for Intermediate- and Higher-Temperature Service
f. ASTM A 516 Standard Specification for Pressure Vessel Plates, Carbon Steel, for Moderate- and Lower-Temperature Service
g. ASTM A 518 Standard Specification for Corrosion-Resistant High-Silicon Iron Castings
h. ASTM A 53 Standard Specification for Pipe, Steel, Black and Hot Dipped, Zinc-Coated, Welded and Seamless
i. ASTM A 536 Standard Specification for Ductile Iron Castings
j. ASTM A 733 Standard Specification for Welded and Seamless Carbon Steel and Austenitic Stainless Steel Pipe Nipples
k. ASTM A 74 Standard Specification for Cast Iron Soil Pipe and Fittings
l. ASTM A 888 Standard Specification for Hubless Cast Iron Soil Pipe and Fittings for Sanitary and Storm Drain, Waste, and Vent Piping Applications
22 04 00.00 10-3
SABER Specifications
FA2517-13-R-5000
Attachment 1
m. ASTM B 111 Standard Specification for Copper and Copper-Alloy Seamless Condenser Tubes and Ferrule Stock
n. ASTM B 117 Standing Practice for Operating Salt Spray (Fog) Apparatus
o. ASTM B 152 Standard Specification for Copper Sheet, Strip, Plate, and Rolled Bar
p. ASTM B 280 Standard Specification for Seamless Copper Tube for Air Conditioning and Refrigeration Field Service
q. ASTM B 306 Standard Specification for Copper Drainage Tube (DWV)
r. ASTM B 32 Standard Specification for Solder Metal
s. ASTM B 339 Standard Specification for Pig Tin
t. ASTM B 370 Standard Specification for Copper Sheet and Strip for Building Construction
u. ASTM B 42 Standard Specification for Seamless Copper Pipe, Standard Sizes
v. ASTM B 43 Standard Specification for Seamless Red Brass Pipe, Standard Sizes
w. ASTM B 584 Standard Specification for Copper Alloy Sand Castings for General Applications
x. ASTM B 75 Standard Specification for Seamless Copper Tube
y. ASTM B 813 Standard Specification for Liquid and Paste Fluxes for Soldering of Copper and Copper Alloy Tube
z. ASTM B 819 Standard Specification for Seamless Copper Tube for Medical Gas Systems
aa. ASTM B 828 Standard Practice for Making Capillary Joints by Soldering of Copper and Copper Alloy Tube and Fittings
bb. ASTM B 88 Standard Specification for Seamless Copper Water Tube
cc. ASTM C 1053 Standard Specification for Borosilicate Glass Pipe and Fittings for Drain, Waste, and Vent (DWV) Applications
dd. ASTM C 564 Standard Specification for Rubber Gaskets for Cast Iron Soil Pipe and Fittings
ee. ASTM C 920 Standard Specification for Elastomeric Joint Sealants
ff. ASTM D 1004 Initial Tear Resistance of Plastic Film and Sheeting
gg. ASTM D 1193 Reagent Water
hh. ASTM D 1248 Standard Specification for Polyethylene Plastics Extrusion Materials for Wire and Cable
ii. ASTM D 1527 Standard Specification for Acrylonitrile-Butadiene-Styrene (ABS) Plastic Pipe, Schedules 40 and 80
jj. ASTM D 1784 Standard Specification for Rigid Poly(Vinyl Chloride) (PVC) Compounds and Chlorinated Poly(Vinyl Chloride) (CPVC) Compounds
22 04 00.00 10-4
SABER Specifications
FA2517-13-R-5000
Attachment 1
kk. ASTM D 1785 Standard Specification for Poly(Vinyl Chloride) (PVC), Plastic Pipe, Schedules 40, 80, and 120
ll. ASTM D 2000 Standard Classification System for Rubber Products in Automotive Applications
mm. ASTM D 2235 Standard Specification for Solvent Cement for Acrylonitrile- Butadiene-Styrene (ABS) Plastic Pipe and Fittings
nn. ASTM D 2241 Standard Specification for Poly(Vinyl Chloride) (PVC) Pressure- Rated Pipe (SDR Series)
oo. ASTM D 2447 Standard Specification for Polyethylene (PE) Plastic Pipe, Schedules 40 and 80, Based on Outside Diameter
pp. ASTM D 2464 Standard Specification for Threaded Poly(Vinyl Chloride) (PVC) Plastic Pipe Fittings, Schedule 80
qq. ASTM D 2466 Standard Specification for Poly(Vinyl Chloride) (PVC) Plastic Pipe Fittings, Schedule 40
rr. ASTM D 2467 Standard Specification for Poly(Vinyl Chloride) (PVC) Plastic Pipe Fittings, Schedule 80
ss. ASTM D 2485 Evaluating Coatings for High Temperature Service
tt. ASTM D 2564 Standard Specification for Solvent Cements for Poly(Vinyl Chloride) (PVC) Plastic Piping Systems
uu. ASTM D 2661 Standard Specification for Acrylonitrile-Butadiene-Styrene (ABS) Schedule 40, Plastic Drain, Waste, and Vent Pipe and Fittings
vv. ASTM D 2665 Standard Specification for Poly(Vinyl Chloride) (PVC) Plastic Drain, Waste, and Vent Pipe and Fittings
ww. ASTM D 2672 Joints for IPS PVC Pipe Using Solvent Cement
xx. ASTM D 2683 Standard Specification for Socket-Type Polyethylene Fittings for Outside Diameter-Controlled Polyethylene Pipe and Tubing
yy. ASTM D 2822 Asphalt Roof Cement
zz. ASTM D 2846 Chlorinated Poly(Vinyl Chloride) (CPVC) Plastic Hot- and Cold- Water Distribution Systems aaa. ASTM D 2855 Standard Practice for Making Solvent-Cemented Joints with Poly(Vinyl Chloride) (PVC) Pipe and Fittings bbb. ASTM D 2996 Filament-Wound "Fiberglass" (Glass-Fiber-Reinforced Thermosetting-Resin) Pipe ccc. ASTM D 3035 Polyethylene (PE) Plastic Pipe (DR-PR) Based on Controlled Outside Diameter ddd. ASTM D 3122 Solvent Cements for Styrene-Rubber (SR) Plastic Pipe and Fittings eee. ASTM D 3138 Solvent Cements for Transition Joints Between Acrylonitrile- Butadiene-Styrene (ABS) and Poly(Vinyl Chloride) (PVC) Non- Pressure Piping Components
22 04 00.00 10-5
SABER Specifications
FA2517-13-R-5000
Attachment 1 fff. ASTM D 3139 Joints for Plastic Pressure Pipes Using Flexible Elastomeric Seals ggg. ASTM D 3212 Standard Specification for Joints for Drain and Sewer Plastic Pipes Using Flexible Elastomeric Seals hhh. ASTM D 3261 Standard Specification for Butt Heat Fusion Polyethylene (PE) Plastic Fittings for Polyethylene (PE) Plastic Pipe and Tubing
iii. ASTM D 3308 PTFE Resin Skived Tape jjj. ASTM D 4060 Abrasion Resistance of Organic Coatings by the Taber Abraser kkk. ASTM D 4101 Standard Specification for Polypropylene Injection and Extrusion Materials lll. ASTM D 4551 Poly (Vinyl Chloride) (PVC) Plastic Flexible Concealed Water- Containment Membrane mmm. ASTM D 609 Preparation of Cold-Rolled Steel Panels for Testing Paint, Varnish, Conversion Coatings, and Related Coating Products nnn. ASTM D 638 Standard Test Method for Tensile Properties of Plastics ooo. ASTM E 1 Standard Specification for ASTM Liquid-in-Glass Thermometers ppp. ASTM E 96 Standard Test Methods for Water Vapor Transmission of Materials qqq. ASTM F 1866 Poly(Vinyl Chloride) (PVC) Plastic Schedule 40 Drainage and DWV Fabricated Fittings rrr. ASTM F 409 Thermoplastic Accessible and Replaceable Plastic Tube and Tubular Fittings sss. ASTM F 437 Standard Specification for Threaded Chlorinated Poly(Vinyl Chloride) (CPVC) Plastic Pipe Fittings, Schedule 80 ttt. ASTM F 438 Standard Specification for Socket-Type Chlorinated Poly(Vinyl Chloride) (CPVC) Plastic Pipe Fittings, Schedule 40 uuu. ASTM F 439 Standard Specification for Chlorinated Poly(Vinyl Chloride) (CPVC) Plastic Pipe Fittings, Schedule 80
vvv. ASTM F 441 Standard Specification for Chlorinated Poly(Vinyl Chloride) (CPVC) Plastic Pipe, Schedules 40 and 80 www. ASTM F 442 Standard Specification for Chlorinated Poly(Vinyl Chloride) (CPVC) Plastic Pipe (SDR-PR)
xxx. ASTM F 477 Standard Specification for Elastomeric Seals (Gaskets) for Joining Plastic Pipe yyy. ASTM F 493 Solvent Cements for Chlorinated Poly(Vinyl Chloride) (CPVC) Plastic Pipe and Fittings zzz. ASTM F 876 Crosslinked Polyethylene (PEX) Tubing aaaa. ASTM F 877 Crosslinked Polyethylene (PEX) Plastic Hot- and Cold- Water Distribution Systems bbbb. ASTM F 913 Thermoplastic Elastomeric Seals (Gaskets) for Joining Plastic Pipe
22 04 00.00 10-6
SABER Specifications
FA2517-13-R-5000
Attachment 1
1.1.1.9 CAST IRON SOIL PIPE INSTITUTE (CISPI)
a. CISPI 301 Hubless Cast Iron Soil Pipe and Fittings for Sanitary and Storm Drain, Waste, and Vent Piping Applications
b. CISPI 310 Coupling for Use in Connection with Hubless Cast Iron Soil Pipe and Fittings for Sanitary and Storm Drain, Waste, and Vent Piping Applications
1.1.1.10 COMPRESSED GAS ASSOCIATION (CGA)
a. CGA V-5 Diameter-Index Safety System (Non-Interchangeable Low Pressure Connections for Medical Gas Applications)
1.1.1.11 COPPER DEVELOPMENT ASSOCIATION (CDA)
a. CDA A4015 Copper Tube Handbook
1.1.1.12 CSA AMERICA, INC. (CSA/AM)
a. CSA/AM Z21.10.1 Gas Water Heaters Vol. I, Storage Water Heaters with Input Ratings of 75,000 Btu Per Hour or Less
b. CSA/AM Z21.10.3 Gas Water Heaters Vol.III, Storage Water Heaters With Input Ratings Above 75,000 Btu Per Hour, Circulating and Instantaneous
c. CSA/AM Z21.22 Relief Valves for Hot Water Supply Systems
1.1.1.13 FOUNDATION FOR CROSS-CONNECTION CONTROL AND HYDRAULIC RESEARCH
(FCCCHR)
a. FCCCHR Manual Manual of Cross-Connection Control
1.1.1.14 INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS
(IAPMO)
a. IAPMO PS 117 Press Type Or Plain End Rub Gsktd W/ Nail CU & CU Alloy Fittings for Install On CU Tubing
b. IAPMO Z124.1.2 Plastic Bathtub and Shower Units
c. IAPMO Z124.5 Plastic Toilet (Water Closet) Seats
1.1.1.15 INTERNATIONAL CODE COUNCIL (ICC)
a. ICC A117.1 Standard for Accessible and Usable Buildings and Facilities
b. ICC IPC International Plumbing Code
1.1.1.16 INTERNATIONAL SAFETY EQUIPMENT ASSOCIATION (ISEA)
a. ISEA Z358.1 Emergency Eyewash and Shower Equipment
1.1.1.17 MANUFACTURERS STANDARDIZATION SOCIETY OF THE VALVE AND FITTINGS
INDUSTRY (MSS)
a. MSS SP-110 Ball Valves Threaded, Socket-Welding, Solder Joint, Grooved and Flared Ends
22 04 00.00 10-7
SABER Specifications
FA2517-13-R-5000
Attachment 1
b. MSS SP-25 Standard Marking System for Valves, Fittings, Flanges and Unions
c. MSS SP-44 Steel Pipeline Flanges
d. MSS SP-58 Standard for Pipe Hangers and Supports - Materials, Design and Manufacture
e. MSS SP-67 Standard for Butterfly Valves
f. MSS SP-69 Standard for Pipe Hangers and Supports - Selection and Application
g. MSS SP-70 Standard for Cast Iron Gate Valves, Flanged and Threaded Ends
h. MSS SP-71 Standard for Gray Iron Swing Check Valves, Flanged and Threaded Ends
i. MSS SP-72 Standard for Ball Valves with Flanged or Butt-Welding Ends for General Service
j. MSS SP-73 Brazing Joints for Copper and Copper Alloy Pressure Fittings
k. MSS SP-78 Cast Iron Plug Valves, Flanged and Threaded Ends
l. MSS SP-80 Bronze Gate, Globe, Angle and Check Valves
m. MSS SP-83 Standard for Class 3000 Steel Pipe Unions Socket Welding and Threaded
n. MSS SP-85 Standard for Cast Iron Globe & Angle Valves, Flanged and Threaded Ends
1.1.1.18 NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
a. NEMA 250 Enclosures for Electrical Equipment (1000 Volts Maximum)
b. NEMA MG 1 Standard for Motors and Generators
1.1.1.19 NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
a. NFPA 31 Installation of Oil Burning Equipment
b. NFPA 54 National Fuel Gas Code
c. NFPA 90A Standard for the Installation of Air Conditioning and Ventilating Systems
d. NFPA 99 Health Care Facilities
1.1.1.20 NSF INTERNATIONAL (NSF)
a. NSF 14 Plastics Piping System Components and Related Materials
b. NSF 3 Commercial Warewashing Equipment
c. NSF 5 Water Heaters, Hot Water Supply Boilers, and Heat Recovery Equipment
d. NSF 61 Drinking Water System Components - Health Effects
1.1.1.21 PLUMBING AND DRAINAGE INSTITUTE (PDI)
22 04 00.00 10-8
SABER Specifications
FA2517-13-R-5000
Attachment 1
a. PDI G 101 Testing and Rating Procedure for Grease Interceptors with Appendix of Sizing and Installation Data
b. PDI WH 201 Water Hammer Arresters Standard
1.1.1.22 SOCIETY OF AUTOMOTIVE ENGINEERS INTERNATIONAL (SAE)
a. SAE J1508 Hose Clamp Specifications
1.1.1.23 THE SOCIETY FOR PROTECTIVE COATINGS (SSPC)
a. SSPC SP 5 White Metal Blast Cleaning
1.1.1.24 U.S. DEPARTMENT OF DEFENSE (DOD)
a. MIL-STD-1691 (Rev F) Construction and Material Schedule for Military Medical and Dental Facilities
1.1.1.25 U.S. ENVIRONMENTAL PROTECTION AGENCY (EPA)
a. PL 93-523 Safe Drinking Water Act
1.1.1.26 U.S. GENERAL SERVICES ADMINISTRATION (GSA)
a. CID A-A-50012 (Basic) Garbage Disposal Machine, Commercial
1.1.1.27 U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
a. 10 CFR 430 Energy Conservation Program for Consumer Products
b. 21 CFR 175 Indirect Food Additives: Adhesives and Components of Coatings
c. PL 109-58 Energy Policy Act of 2005 (EPAct05)
1.1.1.28 UNDERWRITERS LABORATORIES (UL)
a. UL 174 Household Electric Storage Tank Water Heaters
b. UL 732 Oil-Fired Storage Tank Water Heaters
c. UL 749 Household Dishwashers
d. UL 921 Commercial Electric Dishwashers
1.2 SYSTEM DESCRIPTION
1.2.1 Electrical Work
1.2.1.1 Motors, motor controllers and motor efficiencies shall conform to the applicable requirements of Section 26 20 00 Interior Distribution System. Electric motor-driven equipment specified herein shall be provided complete with motors. Equipment shall be rated at 60 Hz, single phase, ac unless otherwise indicated. Motors shall be open, dripproof type unless otherwise indicated. Where a motor controller is not provided in a motor-control center on the electrical drawings, a motor controller shall be provided with the mechanical equipment. Electrical characteristics shall be as indicated. Motor controllers shall be provided complete with properly sized thermal-overload protection in each ungrounded conductor, auxiliary contact, and other equipment at the specified capacity including an allowable service factor, and other appurtenances necessary for the motor control specified. Manual or automatic control and
22 04 00.00 10-9
SABER Specifications
FA2517-13-R-5000
Attachment 1 protective or signal devices required for operation herein specified and any wiring required to such devices not shown on the electrical drawings shall be provided under this section.
Complete electrical schematic lineless or full line interconnection and connection diagram for each piece of mechanical equipment having more than one automatic or manual electrical control device shall be submitted for approval. Manual or automatic control and protective or signal devices required for operation herein specified and any wiring required to such devices not shown on the electrical drawings shall be provided under this section.
1.2.2 Cathodic Protection and Pipe Joint Bonding
1.2.2.1 Cathodic protection and pipe joint bonding systems shall be in accordance with Section 26 42
14.00 10 Cathodic Protection System (Sacrificial Anode).
1.2.3 Medical Gas and Vacuum System Work
1.2.3.1 All work on medical gas and vacuum systems shall be in accordance with NFPA 99.
1.3 SUBMITTALS
1.3.1 Government approval may be required on any of the following items. Items requiring submittals will be listed on the Submittal Register. Provide copies of all submittals per the requirements in Section 01 33 00, Submittal Procedures, or as listed on the Submittal Register.
1.3.1.1 SD-02 Shop Drawings
a. Control Diagrams
(1) Complete electrical schematic lineless or full line interconnection and connection diagrams for each piece of mechanical equipment having more than one automatic or manual electrical control device.
b. Plumbing System
(1) Detail drawings consisting of illustrations, schedules, performance charts, instructions, brochures, diagrams, and other information to illustrate the requirements and operation of each system. Detail drawings for the complete plumbing system including piping layout and location of connections; dimensions for roughing-in, foundation, and support points;
schematic diagrams; and wiring diagrams or connection and interconnection diagrams.
Indicate in the Detail drawings clearances required for maintenance and operation.
Where piping and equipment are to be supported other than as indicated, include in the details loadings and proposed support method. All mechanical drawing plans, elevations, views, and details, shall be drawn to scale.
1.3.1.2 SD-03 Product Data
a. Welding
(1) A copy of qualified procedures and a list of names and identification symbols of qualified welders and welding operators.
b. Fixtures
c. Fixtures and Fixture Trimmings
(1) Plumbing Fixture Schedule with catalog cuts of specified plumbing fixtures, valves, and
22 04 00.00 10-10
SABER Specifications
FA2517-13-R-5000
Attachment 1 related piping system and system location where installed.
d. Vibration-Absorbing Features
(1) Details of vibration-absorbing features, including arrangement, foundation plan, dimensions and specifications.
e. Framed Instructions
(1) Diagrams, instructions, and other sheets, prior to posting. Manufacturer's recommendations for the installation of bell and spigot and hubless joints for cast iron soil pipe.
1.3.1.3 SD-06 Test Reports
a. Tests, Flushing and Disinfection
(1) Test reports in booklet form showing all field tests performed to adjust each component and field tests performed to prove compliance with the specified performance criteria, upon completion and testing of the installed system. Indicate in each test report the final position of controls.
b. Test of Backflow Prevention Assemblies
(1) Certification of proper operation shall be accomplished with requirements in accordance with state regulations by an individual certified by the state to perform such test. If no state requirement exists, have the manufacturer's representative test the device, to ensure the unit is properly installed and performing as intended. Provide written documentation of the tests performed and signed by the individual performing the tests.
1.3.1.4 SD-07 Certificates
a. Station Outlets
(1) Proof that outlets as an assembly conform to the requirements of Underwriters Laboratories, Inc.
b. Materials and Equipment
(1) Where materials or equipment are specified to comply with requirements of AGA, ASME, or NSF include proof of such compliance. The label or listing of the specified agency will be acceptable evidence. In lieu of the label or listing, a written certificate may be submitted from an approved, nationally recognized testing organization equipped to perform such services, stating that the items have been tested and conform to the requirements and testing methods of the specified agency. Where equipment is specified to conform to ASME requirements, the design, fabrication, and installation shall conform to the code.
c. Bolts
(1) Written certification from the bolt manufacturer that the bolts furnished comply with specified requirements. Include in the certification illustrations of product-required markings, date of manufacture, and number of each type of bolt to be furnished based on this certification.
d. Medical Gas and Vacuum System Work
(1) Written certificate of installer certification in accordance with ASSE Series 6000 and written certificate of verifier certification in accordance with ASSE Series 6000.
22 04 00.00 10-11
SABER Specifications
FA2517-13-R-5000
Attachment 1
1.3.1.5 SD-10 Operation and Maintenance Data
a. Plumbing System
(1) Complete copies of the operation manual outlining the step-by-step procedures required for system startup, operation and shutdown. Include in the manual the manufacturer's name, model number, service manual, parts list, and brief description of all equipment and their basic operating features. Complete copies of the maintenance manual listing routine maintenance procedures, possible breakdowns and repairs. Include in the manual piping and equipment layout and simplified wiring and control diagrams of the system as installed.
1.4 QUALITY ASSURANCE
1.4.1 Welding
1.4.1.1 Piping shall be welded in accordance with qualified procedures using performance-qualified welders and welding operators. Procedures and welders shall be qualified in accordance with ASME BPVC SEC IX. Welding procedures qualified by others, and welders and welding operators qualified by another employer, may be accepted as permitted by ASME B31.1. The Contracting Officer shall be notified 24 hours in advance of tests, and the tests shall be performed at the work site if practicable. Welders or welding operators shall apply their assigned symbols near each weld they make as a permanent record. Structural members shall be welded in accordance with Section 05 05 23 Welding, Structural.
1.4.2 General Requirements
1.4.2.1 Unless otherwise required herein, plumbing work shall be in accordance with ICC IPC. Water flow and consumption rates shall, at a minimum, comply with requirements in PL 109-58 and Executive Order 13423 dated January 26, 2007. Equipment energy efficiencies shall meet or exceed requirements of ( ASHRAE 90.1 - IP).
PART 2 PRODUCTS
2.1 MATERIALS AND EQUIPMENT
2.1.1 Provide materials and equipment which are standard items of a manufacturer regularly engaged in the manufacture of such products and that essentially duplicate equipment that has performed satisfactorily at least 2 years prior to bid opening.
2.2 MATERIALS
2.2.1 Provide materials for various services in accordance with TABLES I and II. Pipe fittings shall be compatible with the applicable pipe materials. Plastic pipe, fittings, and solvent cement shall meet NSF 14 and shall be NSF listed for the service intended. Plastic pipe, fittings, and solvent cement used for potable hot and cold water service shall bear the NSF seal "NSF-PW."
Polypropylene pipe and fittings shall conform to dimensional requirements of Schedule 40, Iron Pipe size. Pipe threads (except dry seal) shall conform to ASME B1.20.1. Grooved pipe couplings and fittings shall be from the same manufacturer. Material or equipment containing lead shall not be used in any potable water system. In line devices such as water meters, building
22 04 00.00 10-12
SABER Specifications
FA2517-13-R-5000
Attachment 1 valves, check valves, meter stops, valves, fittings and back flow preventers shall comply with PL 93-523 and NSF 61, section 8. End point devices such as drinking water fountains, lavatory faucets, kitchen and bar faucets, residential ice makers, supply stops and end point control valves used to dispense water for drinking shall meet the requirements of NSF 61, section 9. Hubless cast-iron soil pipe shall not be installed underground, under concrete floor slabs or in crawl spaces below kitchen floors. Plastic pipe shall not be installed in air plenums. Plastic pipe shall not be installed in a pressure piping system in buildings greater than three stories including any basement levels.
2.2.2 Pipe Joint Materials
2.2.2.1 Grooved pipe and hubless cast-iron soil pipe shall not be used under ground. Joint and gasket materials shall conform to the following:
a. Coupling for Hubless Cast-Iron Pipe: For hub and spigot type ASTM A 74, AWWA C606.
For hubless type: CISPI 310
b. Coupling for Steel Pipe: AWWA C606.
c. Couplings for Grooved Pipe: Ductile Iron ASTM A 536 (Grade 65-45-12) or Malleable Iron ASTM A 47, Grade 32510 or Copper ASTM A 536.
d. Flange Gaskets: Gaskets shall be made of non-asbestos material in accordance with ASME B16.21. Gaskets shall be flat, 1/16 inch thick, and contain aramid fibers bonded with Styrene Butadiene Rubber (SBR) or Nitro Butadiene Rubber (NBR). Gaskets shall be full face or self centering flat ring type. Gaskets used for hydrocarbon service shall be bonded with NBR.
e. Brazing Material: Brazing material shall conform to AWS A5.8, BCup-5.
f. Brazing Flux: Flux shall be in paste or liquid form, be appropriate for use with brazing material, be lead free, have a 100 percent flushable residue, contain slightly acidic reagents, contain potassium bromides, and contain fluorides.
g. Solder Material: Solder metal shall conform to ASTM B 32.
h. Solder Flux: Flux shall be liquid form, non-corrosive, and shall conform to ASTM B 813, Standard Test 1.
i. Polytetrafluoroethylene Tape, for use with Threaded Metal or Plastic Pipe, and Distilled Water- Piping: ASTM D 3308.
j. Rubber Gaskets for Cast-Iron Soil Pipe and Fittings (hub and spigot type and hubless type):
ASTM C 564.
k. Rubber Gaskets for Grooved Pipe: ASTM D 2000, maximum temperature 230 degrees F.
l. Flexible Elastomeric Seals: ASTM D 3139, ASTM D 3212 or ASTM F 477.
m. Bolts and Nuts for Grooved Pipe Couplings: Heat treated carbon steel, ASTM A 183.
n. Solvent Cement for Transition Joints between ABS and PVC Nonpressure Piping Components:
ASTM D 3138.
o. Plastic Solvent Cement for ABS Plastic Pipe: ASTM D 2235.
p. Plastic Solvent Cement for PVC Plastic Pipe: ASTM D 2564 and ASTM D 2855.
q. Plastic Solvent Cement for CPVC Plastic Pipe: ASTM F 493.
r. Flanged Fittings: Flanged fittings including flanges, bolts, nuts, bolt patterns, etc. shall be in
22 04 00.00 10-13
SABER Specifications
FA2517-13-R-5000
Attachment 1 accordance with ASME B16.5 Class 150 and shall have the manufacturers trademark affixed in accordance with MSS SP-25. Flange material shall conform to ASTM A 105. Blind flange material shall conform to ASTM A 516 cold service and ASTM A 515 for hot service. Bolts shall be high strength or intermediate strength with material conforming to ASTM A 193.
s. Elastomeric Seals: Elastomeric seals (gaskets) for joining plastic pipe ASTM F 477:
thermoplastic elastomeric seals (gaskets) for joining plastic pipe ASTM F 913.
t. Plastic Solvent Cement for Styrene Rubber Plastic Pipe: ASTM D 3122.
u. Press Fittings for Copper Pipe and Tube: Copper press fittings shall conform to the material and sizing requirements of ASME B16.18 or ASME B16.22. Sealing elements for copper press fittings shall be EPDM, FKM or HNBR. Sealing elements shall be factory installed or an alternative supplied by fitting manufacturer. Sealing element shall be selected based on manufacturers' approved application guide.
2.2.3 Copper Tubing and Fittings
a. Copper Tube: Copper tubing shall conform to ASTM B 88M, Type K, L or M.
b. Press Fittings: Copper and bronze press fittings shall conform to material requirements of ASME B16.18 or ASME B16.22 and performance criteria of IAPMO PS 117. Sealing elements shall be of EPDM and be factory installed or an alternative supplied by fitting manufacturer.
2.2.4 Miscellaneous Materials
2.2.4.1 Miscellaneous materials shall conform to the following:
a. Water Hammer Arresters: PDI WH 201.
b. Copper, Sheet and Strip for Building Construction: ASTM B 370.
c. Asphalt Roof Cement: ASTM D 2822.
d. Hose Clamps: SAE J1508.
e. Supports for Off-The-Floor Plumbing Fixtures:
f. Metallic Cleanouts:
g. Plumbing Fixture Setting Compound: A preformed flexible ring seal molded from hydrocarbon wax material. The seal material shall be nonvolatile, nonasphaltic and contain germicide and provide watertight, gastight, odorproof and verminproof properties.
h. Coal-Tar Protective Coating and Linings for Steel Water Pipelines: AWWA C203.
i. Hypochlorites: AWWA B300.
j. Liquid Chlorine: AWWA B301.
k. Polyethylene Encasement for Ductile Iron Piping: AWWA C105/A21.5.
l. Gauges - Pressure and Vacuum Indicating Dial Type-Elastic Element: ASME B40.100.
m. Thermometers: ASTM E 1. Mercury shall not be used in thermometers
2.2.5 Pipe Insulation Material
2.2.5.1 Insulation shall be as specified in Section 23 07 00 Thermal Insulation for Mechanical Systems.
22 04 00.00 10-14
SABER Specifications
FA2517-13-R-5000
Attachment 1
2.3 PIPE HANGERS, INSERTS, AND SUPPORTS
2.3.1 Pipe hangers, inserts, and supports shall conform to MSS SP-58 and MSS SP-69.
2.4 VALVES
2.4.1 Provide valves on supplies to equipment and fixtures. Valves shall be gate valves, unless otherwise specified or indicated. Valves 2-1/2 inches and smaller shall be bronze, with threaded bodies for pipe and solder-type connections for tubing. Valves 3 inches and larger shall have flanged iron bodies and bronze trim. Pressure ratings shall be based upon the application.
Grooved end valves may be provided if the manufacturer certifies that the valves meet the performance requirements of applicable MSS standard. Valves shall conform to the following standards:
Description Standard
Butterfly Valves MSS SP-67
Cast-Iron Gate Valves, Flanged MSS SP-70 and Threaded Ends
Cast-Iron Swing Check Valves, MSS SP-71 Flanged and Threaded Ends
Ball Valves with Flanged or MSS SP-72 Butt-Welding Ends for General Service
Ball Valves Threaded, Socket- MSS SP-110 Welding, Solder Joint, Grooved and Flared Ends
Cast-Iron Plug Valves, Flanged MSS SP-78 and Threaded Ends
Bronze Gate, Globe, Angle, and MSS SP-80 Check Valves
Steel Valves-Socket Welding and ASME B16.34 Threaded Ends
Faucets For High-Purity Water (De-ionized or Distilled) Either of the Following:
Polyvinyl Chloride Composition ASTM D 1784, Class 1245-B of Valves
Cast-Iron Globe and Angle MSS SP-85 Valves, Flanged and Threaded Ends
22 04 00.00 10-15
SABER Specifications
FA2517-13-R-5000
Attachment 1
Backwater Valves ASME A112.14.1
Vacuum Relief Valves CSA/AM Z21.22
Water Pressure Reducing Valves ASSE 1003
Trap Seal Primer Valves ASSE 1018
Temperature and Pressure CSA/AM Z21.22, and Relief Valves for Hot ASME BPVC SEC IV Water Supply Systems
Temperature and Pressure ASME CSD-1, Relief Valves for Part CW, Article 5 Automatically Fired Hot Water Boilers
2.4.2 Backwater Valves
2.4.2.1 Backwater valves shall be either separate from the floor drain or a combination floor drain, "P" trap, and backwater valve, as shown. Valves shall have cast-iron bodies with cleanouts large enough to permit removal of interior parts. Valves shall be of the flap type, hinged or pivoted, with revolving disks. Hinge pivots, disks, and seats shall be nonferrous metal. Disks shall be slightly open in a no-flow, no-backwater condition. Cleanouts shall extend to finished floor and be fitted with threaded countersunk plugs.
2.4.3 Wall Faucets
2.4.3.1 Wall faucets with vacuum breaker backflow preventer shall be brass with 3/4 inch male inlet threads, hexagon shoulder, and 3/4 inch hose connection. Faucet handle shall be securely attached to stem.
2.4.4 Wall Hydrants
2.4.4.1 Wall hydrants with vacuum breaker backflow preventer shall have a nickel-brass or nickel-bronze wall plate or flange with nozzle and detachable key handle. A brass or bronze operating rod shall be provided within a galvanized iron casing of sufficient length to extend through wall so that the valve is inside the building, and the portion of the hydrant between the outlet and valve is self-draining. A brass or bronze valve with coupling and union elbow having metal-to-metal seat shall be provided. Valve rod and seat washer shall be removeable through the face of the hydrant. The hydrant shall have 3/4 inch exposed hose thread on spout and 3/4 inch male pipe thread on inlet.
2.4.5 Lawn Faucets
2.4.5.1 Lawn faucets shall be brass, with either straight or angle bodies, and shall be of the compression type. Body flange shall be provided with internal pipe thread to suit 3/4 inch pipe.
Body shall be suitable for wrench grip. Faucet spout shall have 3/4 inch exposed hose threads.
Faucet handle shall be securely attached to stem.
22 04 00.00 10-16
SABER Specifications
FA2517-13-R-5000
Attachment 1
2.4.6 Yard Hydrants
2.4.6.1 Yard box or post hydrants shall have valve housings located below frost lines. Water from the casing shall be drained after valve is shut off. Hydrant shall be bronze with cast-iron box or casing guard. "T" handle key shall be provided.
2.4.7 Relief Valves
2.4.7.1 Water heaters and hot water storage tanks shall have a combination pressure and temperature (P&T) relief valve. The pressure relief element of a P&T relief valve shall have adequate capacity to prevent excessive pressure buildup in the system when the system is operating at the maximum rate of heat input. The temperature element of a P&T relief valve shall have a relieving capacity which is at least equal to the total input of the heaters when operating at their maximum capacity. Relief valves shall be rated according to CSA/AM Z21.22, have 3/4 inch minimum inlets, and 3/4 inch outlets for systems where the maximum rate of heat input is less than 200,000 Btuh. Relief valves rated according to ASME BPVC SEC IV, or ASME CSD-1, shall have 1 inch minimum inlets, and 1 inch outlets for systems where the maximum rate of heat input is greater than 200,000 Btuh. The discharge pipe from the (P&T) valve shall be the size of the valve outlet.
2.4.8 Thermostatic Mixing Valves and Cabinets
2.4.8.1 Mixing Valves
a. Mixing valves, thermostatic type, pressure-balanced or combination thermostatic and pressure-balanced shall be line size and shall be constructed with rough or finish bodies either with or without plating. Each valve shall be constructed to control the mixing of hot and cold water and to deliver water at a desired temperature regardless of pressure or input temperature changes. The control element shall be of an approved type. The body shall be of heavy cast bronze, and interior parts shall be brass, bronze, corrosion-resisting steel or copper. The valve shall be equipped with necessary stops, check valves, unions, and sediment strainers on the inlets. Mixing valves shall maintain water temperature within 5 degrees F of any setting.
2.4.8.2 Cabinets
a. Cabinets for mixing valves shall be constructed of 16 gauge minimum thickness sheet metal of a size to accommodate the equipment to be installed therein, shall be rigidly assembled with joints welded, and shall be punched or drilled for the passage of required pipes and services.
Cabinets shall be designed for recessed mounting in wall construction, with front flush with tile or plaster finish, and shall have flush-fitting continuously hinged doors. Keyed locks on cabinets located in neuropsychiatric wards shall be provided. Other cabinets shall be equipped with friction catch and pull. Doors and trim shall be flush with front of cabinet and shall be constructed of 16 gauge minimum thickness sheet metal. Doors shall open through 180 degrees.
This is the start of the file's text. The full file is on GovTribe.