Appendix D NFPA 780 LP Requirements Determination
View the file
Other versions and copies of NFPA 780
| File | Revision | Posted | Attached to |
|---|---|---|---|
| Military_Installations_to_NFPA_780__2016.pdf | 2016 | Fort Benning MATOC | |
| B.3.4 - 01020D - Appendix D NFPA 780 LP Determination Explanation.doc | Revision not stated | A&E DESIGN/BUILD FIRST ARTICLE TESTING STORAGE FACILITY |
Who attaches NFPA 780
Other files
Show all 40
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1
| App D LIGHTNING PROTECTION REQUIREMENT DETERMINATION | ||||||||
| PROJECT: | ||||||||
| LOCATION: | ||||||||
| DATE / BY: | ||||||||
| The calculations below indicate LP is required as follows: | ||||||||
| Lightning Protection Optional | ||||||||
| This is based on NFPA 780 (2004 edition) Lightning Risk Assessment (Annex L). The lightning risk assessment methodology is provided to assist the building owner or architect/engineer to determine the risk of damage due to lightning. Once the risk has been determined, deciding on the need for protection measures is much easier. The methodology considers only the damage caused by a direct strike to the building or structure to be protected and currents flowing through the lightning protection system. This risk assessment method is a guide that takes into account the following factors: | ||||||||
| # Building Environment | # Type of Construction | |||||||
| # Structure Occupancy | # Structure Contents | |||||||
| # Strike Consequences | # Lightning Flash Density | |||||||
| Select one index value from each of the following tables (C1,C2,C3,C4,C5,Ng) and enter that number in the green box at the bottom of each table. Also enter the building width, length and height. | ||||||||
| C1 -- Environmental Coefficient | ||||||||
| Structure located within a space containing structures or trees of the same height or taller within a distance of 3H. | 0.25 | |||||||
| Structure surrounded by smaller structures within a distance of 3H | 0.50 | |||||||
| Isolated structure. No others structures within a distance of 3H. | 1.00 | |||||||
| Isolated structure on hilltop. | 2.00 | |||||||
| C1= | 0.25 | |||||||
| C2 -- Structural Coefficient | ||||||||
| Roof | ||||||||
| Structure | Metal | Nonmetallic | Flammable | |||||
| Metal | 0.5 | 1.0 | 2.0 | |||||
| Nonmetallic | 1.0 | 1.0 | 2.5 | |||||
| Flammable | 2.0 | 2.5 | 3.0 | |||||
| C2= | 0.5 | |||||||
| C3 -- Structure Contents | ||||||||
| Low value and nonflammable | 0.5 | |||||||
| Standard value and nonflammable | 1.0 | |||||||
| High value, moderate flammability | 2.0 | |||||||
| Exceptional value, flammable, computer electronics | 3.0 | |||||||
| Exceptional value, irreplaceable cultural items | 4.0 | |||||||
| C3= | 0.5 | |||||||
| C4 -- Structure Occupancy | ||||||||
| Unoccupied | 0.5 | |||||||
| Normally Occupied | 1.0 | |||||||
| Difficult to evacuate or risk of panic | 3.0 | |||||||
| C4= | 0.5 | |||||||
| C5 -- Lightning Consequence Coefficient | ||||||||
| Continuity of facility services not required, no environmental impact | 1 | |||||||
| Continuity of facility services required, no environmental impact | 5 | |||||||
| Consequences to environment | 10 | |||||||
| C5= | 1.0 | |||||||
| Ng -- Lightning Flash Density | ||||||||
| Please enter the number corresponding to the structure's location on the following map | ||||||||
| Ng= | 5 | (Central Georgia = 5) | ||||||
| Equivalent Collection Area (Ae) | ||||||||
| Rectangular Structure | Structure with prominent part | |||||||
| ft | km | ft | km | |||||
| L= | 100 | 0.03048 | H= | 0 | 0 | |||
| W= | 40 | 0.012192 | ||||||
| H= | 25 | 0.00762 | ||||||
| Ae1= | 0.003964 | Ae2= | 0.000000 | |||||
| Results | ||||||||
| C = (C2)(C3)(C4)(C5) = | 0.12500 | |||||||
| Nc = 1.5 x 10-3/C = | 0.01200 | Nc is tolerable damage level. | ||||||
| Ae = MAX (Ae1, Ae2) = | 0.00396 | |||||||
| Nd = (Ng)(Ae)(C1) = | 0.00496 | Nd is probable damage level. | ||||||
| Nd/Nc | = | 0.41 | Required if > 1.0, Optional if <= 1.0. | |||||
| Lightning Protection Optional | ||||||||
| ** All Calculations Per NFPA 780 Lightning Risk Assessment | ||||||||
| For Further information, questions or quotations, contact Bill McSherry at Midwest Lightning Protection 708-479-2249 |
H L W H 3H 3H 3H 3H 3H W L C2 C3 C1 C4 C5 Ng Ae Results