APPENDIX B TO
01020 – (DESIGN-BUILD) CONSTRUCTION DESIGN PERFORMANCE REQUIREMENTS
UHHZ 100138, Construct First Article Testing Storage Facility, Near Building 323
FIRE PROTECTION/LIFE SAFETY CODE ANALYSIS
NOTE TO CONTRACTOR’S DESIGNER: This document is a preliminary analysis used for concept development. It does not contain all requirements and does not relieve the designer of complete code and criteria review, compliance and documentation responsibilities during proposal preparation and final design development.
REFERENCES:
Unified Facilities Code (UFC) 3-600-01 dated September 26, 2006 on Fire Protection
Engineering Circular EC 1110-1-92, Classification of Type of Construction, 21 June 2000
International Building Code (IBC) 2006 NFPA 101, Life Safety Code, 2006 NFPA 10, Standard for Portable Fire Extinguishers, 1998
BUILDING DESCRIPTION:
One Story Storage Building, Approximately 4,500 Square Feet total AUTOMATIC SPRINKLER SYSTEM (UFC 3-600-01 dated Sept. 26, 2006): Not required by UFC or NFPA, but required by Robins AFB Facility Standard.
IBC OCCUPANCY:
Assembly
NFPA 101 OCCUPANCY:
Business (Chapter 38)
All Other Spaces: Storage: (Chapter 42) CONSTRUCTION TYPE (IBC Table 503): Type II-A and Type III-A Construction may be of any materials allowed by IBC, nonrated and rated.
References:
505.2 Unlimited area increase – 60’ yards all sides
504.3 exc 2 H Occupancy less than 10% of building area
EXTERIOR WALL AND OPENING PROTECTION (IBC Table 602):
No requirements based on location on property.
FIRE RATED SEPARATIONS:
Assembly adjacent to Storage: Two Hour (UFC 3-600-01)
OCCUPANT LOAD (NFPA 101, Table 7.1.3.2):
Occupancy
Area
Occupant Load
Storage
4,500
TOTAL
4,500
EGRESS REQUIREMENTS (NFPA 101)
CAPACITY (Table 7.3.3.1): Level Components and Ramps: 333(0.2)=67 inches
MINIMUM CORRIDOR WIDTH (38.2.3.2): 44 inches
NUMBER OF EXITS (7.4.1, 40.2.4.1 exc, 42.2.4.1 exc 2):
Two required at Business
One permitted at Storage if reached in Common Path distance
One permitted at Industrial if reached in Common Path distance
MAXIMUM DEAD END (38.2.5.2, 40.2.5.2, 42.2.5.3 exc):
50 feet at Business, Industrial
100 feet at Storage
MAXIMUM COMMON PATH OF TRAVEL (38.2.5.3, 40.2.5.3, 42.2.5.4 exc): 100 feet
MAXIMUM TRAVEL DISTANCE (38.2.6, 40.2.6.1 exc 1, 42.2.6.2):
300 feet at Business
250 feet at Industrial
400 feet at Storage
INTERIOR FINISHES:
WALL AND CEILING FINISHES (UFC 3-600-01 dated Sept. 26, 2006):
Class A in Exits and Exit Passageways.
Class A, B or C all other areas.
Class A materials shall not exceed FS 25 and SD 50.
Class B materials shall not exceed FS 75 and SD 100.
Class C materials shall not exceed FS 200 and SD 200.
Cellular Plastics not permitted.
FLOOR FINISHES (NFPA 101 38.3.3.3, 10.2.8.2):
No requirements.
PORTABLE FIRE EXTINGUISHERS (NFPA 10):
Maximum travel to fire extinguisher: 75 feet
01020 APPENDIX B - 1 of 2 B.3.2 - 01020B - Appendix B Fire Protection & Life Safety 29-Apr-09