Appendix D NFPA 780 LP Requirements Determination
View the file
Other versions and copies of NFPA 780
| File | Revision | Posted | Attached to |
|---|---|---|---|
| Military_Installations_to_NFPA_780__2016.pdf | 2016 | Fort Benning MATOC | |
| B.3.5 - 01020E - Appendix D NFPA 780 LP Requirement Determination.xls | Revision not stated | A&E DESIGN/BUILD FIRST ARTICLE TESTING STORAGE FACILITY |
Who attaches NFPA 780
Other files
Show all 40
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
October 15, 2004
APPENDIX D -- NFPA 780 Lightning Risk Assessment
The NFPA 780 Lightning Risk Assessment is designed to assist engineers and building owners in determining the risk of damage to a facility due to lightning strike. Several factors such as the size and height of a structure, occupancy, contents, and geographical location help to determine the need for a lightning protection system. Each factor is given a particular number or coefficient that is entered into a formula to determine the expected lightning stroke frequency and the tolerable lightning stroke frequency to a structure.
The first coefficient is based on the location of a structure and its relationship to its surroundings and other structures. A structure located close to other buildings is assigned a low coefficient and a structure isolated from other buildings and located on a hilltop would be assigned the highest coefficient. This coefficient is used separate from the other coefficients to determine the expected lightning frequency.
The second coefficient applies to the physical construction of the structure. A structure with a metal roof and metal walls is assigned the lowest coefficient. A structure constructed of wood or other flammable materials is given the highest coefficient.
The third coefficient considers the contents of the structure. If the contents of the structure are of low value and non-flammable, a low coefficient is assigned. If the contents are flammable, exceptional value or irreplaceable items the highest coefficient is assigned.
The fourth coefficient considers the occupancy and ability to evacuate the structure. Unoccupied structures are given the lowest coefficient. Structures such a schools or stadiums that are difficult to evacuate are assigned the highest coefficient.
The fifth coefficient is determined by the consequence of a lightning strike to the structure. If the services of the structure provide no environmental impact then the lowest coefficient is assigned. If interruption of services results in consequences to the environment then the highest coefficient is assigned.
The structural, contents, occupancy, and lightning consequence coefficients are then applied to a formula that determines the tolerable lightning frequency. Tolerable lightning frequency measures the damage risk to a structure, the environment, and monetary loss. The tolerable lightning frequency is compared to the expected lightning frequency in determining the need for a lightning protection system.
The expected lightning frequency is formulated using the lightning flash density for the region where the structure is located, the collective area of the structure, and the environmental coefficient.
The lightning flash density is a number corresponding to the location of the structure. A map shows the lightning flash density in flash/km(/year provided by Global Atmospherics and U.S. National Lightning Detection Network.
The collective area of a structure is simply determined by the height, width, and length of the structure.
After the results of the expected lightning frequency and the tolerable lightning frequency have been calculated then the determination of a lightning protection system can be made. If the expected lightning frequency figure is less than the tolerable lightning frequency (Nd < Nc), then the need for a lightning protection system is optional. If the expected lightning frequency is higher than the tolerable lightning frequency (Nd > Nc), then a lightning protection system should be installed on the structure.
There are a lot of factors involved in determining the need for a lightning protection system. The safety of the occupants and the monetary loss are the most important when determining that need. The NFPA Lightning Risk Assessment provides valuable information to engineers and owners when deciding on that important investment.