This document provides details for a federal contract opportunity to renovate Building 200 at the James H. Quillen VAMC Mountain Home facility in Tennessee. The solicitation number is 36C24923R0030 to renovate the D Wing of Building 200 for use as an isolation ward. The project number is 621-20-107. The contracting agency is the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 9. The scope of work involves renovating the D Wing of Building 200 to accommodate use as an isolation ward. No further specifics on requirements, pricing, or response timing are provided in this document.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
F I N I S H L E G E N D
MARK DESCRIPTION BASIS OF DESIGN STYLE/ COLOR COMMENTS
ACT-1 2X2 ACOUSTICAL CEILING TILE ARMSTRONG CALLA GASKETING GRIDS -
RB-2 MILLWORK BASE JOHNSONITE
MANDALAY 4 1/2" -
44 DARK BROWN
USED WITH CPT-1 AND
LVT-2
LVT-1 LUXURY VINYL TILE
MANNINGTON
COMMERCIAL
NATURE'S PATHS - ABSTRACT
COLORWAYS - VIA CAMINO
STAGGER - 4" x 36"
P-2 PAINT - TYPE 2 PPG FOOTHILLS PPG1105-4
PT-1 PORCELAIN TILE FLORIDA TILE
RUSTIC SLATE AESTHETIC -
DELTA HAZE - FTI2991412X24
12"x24" FIELD WALL TILE
RF-1 RESINOUS FLOORING STONHARD STONTEC UTF - SANTA CRUZ INTEGRAL BASE
C-1 SOLID SURFACE CORIAN ARTISTA CANVAS -
CG-2 CORNER GUARD C/S ACROVYN DRIFTWOOD 262 -
PT-2
WP-1 WALL PROTECTION ACROVYN
WALL COVERING + PANEL SYSTEM
LINEN - NANTUCKET
ACT-2 2X2 ACOUSTICAL CEILING TILE ARMSTRONG STANDARD -
CG-1 CORNER GUARD C/S ACROVYN OYSTER GRAY 929 -
LVT-2 LUXURY VINYL TILE SHAW CONTRACT JEOGORI - BLACK TIE - 90590 QUARTER TURN - 18" x 18"
P-1 PAINT - TYPE 1 PPG COOL CONCRETE PPG1023-2
GENERAL WALL PAINT -
LATEX EGGSHELL
GENERAL WALL PAINT -
LATEX EGGSHELL
P-3 PAINT - TYPE 3 PPG DELICATE WHITE PPG1001-1
GENERAL WALL PAINT -
LATEX EGGSHELL
P-4 PAINT - TYPE 4 PPG COTTON TAIL PPG0998-1
GENERAL WALL PAINT -
LATEX EGGSHELL
P-5 PAINT - TYPE 5 PPG
CEILING PAINT -
LATEX FLAT
P-6 PAINT - TYPE 6 PPG
DELICATE WHITE PPG1001-1
CEILING PAINT -
EPOXY
DELICATE WHITE PPG1001-1
PORCELAIN TILE FLORIDA TILE
RUSTIC SLATE AESTHETIC -
COASTAL SAND - FTI2993612X24
12"x24" ACCENT WALL TILE
RB-1 RUBBER BASE JOHNSONITE A530 - 66 EITHER OR USED WITH LVT-1
CPT-1 CARPET TILE SHAW CONTRACT
BROADLOOM - JOIN -
68500 SMOKE
HR-1 HANDRAIL ACROVYN
HRB-4C -
688 LIGHTHOUSE GRAY
HR-2 HANDRAIL ACROVYN
HRB-4C -
187 TAN BARK
WP-2 WALL PROTECTION ACROVYN
WALL COVERING + PANEL SYSTEM
LINEN - NECTAR
EXP EXPOSED STRUCTURE - - -
PL-2 PLASTIC LAMINATE WILSONART
DARK BROWN WALNUT -
NEMSCHOFF, OW
RUSTIC SLATE AESTHETIC -
COASTAL SAND - FTI2993612X24
PL-1 PLASTIC LAMINATE WILSONART
WOODGRAIN LAMINATE -
OAK ON ASH, LLB
RF-2 RESINOUS FLOORING STONHARD STONTEC UTF - SANTA CRUZ
INTEGRAL BASE - TOILET ROOM
WITH CEMENT BOARD BACKER
P-7 PAINT - TYPE 7 PPG
HM DOOR FRAME PAINT -
SEMI-GLOSS
DELICATE WHITE PPG1001-1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
1100 Boulders Pkwy | Suite 503 Richmond, VA 23225
804.355.2067
A u to d e s k D o c s /M t H o m e
I s o la ti o n W a rd
D
/F F
E
M t H o m e
D rv t
/4 /2
:2
:1
P
M
AI601
FINISH SCHEDULE
11/04/2022 ET NM
RENOVATE D-WING FOR ISOLATION
WARD
621-20-107
MOUNTAIN HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER
Approved: MT Home VA
F I N I S H S C H E D U L E
ROOM NAME
ROOM
NUMBER FLOOR CEILING WALL FINISH WALL BASE
WALL FINISH
N E S W
CORRIDOR D2C2 LVT-1 ACT-2 - RB-1 - - - -
CORRIDOR D2C3 LVT-1 ACT-2 P-1 RB-1 P-1 P-1 P-1 P-1
CORRIDOR D2C3A LVT-1 ACT-2 P-2 RB-1 - P-2 P-2 P-2
CORRIDOR D2C3B LVT-1 ACT-2 P-3 RB-1 P-3 P-3 P-3 P-3
CORRIDOR D2C4B LVT-1 ACT-2 - RB-1 - - - -
CORRIDOR D2C5 LVT-1 ACT-2 - RB-1 - - - -
ELEVATOR LOBBY D2EL2 LVT-1 ACT-2 - RB-1 - - - -
ANTEROOM D201A RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3
ISO ROOM 1 D201B RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3
TOILET D201C RF-2 P-6 PT-1 RF-2 PT-1 / PT-2 PT-1 PT-1 / PT-2 PT-1
CHART ALCOVE D201D LVT-1 ACT-2 P-2 RB-1 P-2 P-2 P-2 P-2
ANTEROOM D202A RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3
ISO ROOM 2 D202B RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3
TOILET D202C RF-1 P-6 PT-1 RF-2 PT-1 / PT-2 PT-1 PT-1 / PT-2 PT-1
ANTEROOM D203A RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3
ISO ROOM 3 D203B RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3
TOILET D203C RF-1 P-6 PT-1 RF-2 PT-1 / PT-2 PT-1 PT-1 / PT-2 PT-1
CHART ALCOVE D203D LVT-1 ACT-2 P-2 RB-1 P-2 P-2 P-2 P-2
ANTEROOM D204A RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3
ISO ROOM 4 D204B RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3
TOILET D204C RF-1 P-6 PT-1 RF-2 PT-1 / PT-2 PT-1 PT-1 / PT-2 PT-1
ANTEROOM D205A RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3
ISO ROOM 5 D205B RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3
TOILET D205C RF-1 P-6 PT-1 RF-2 PT-1 / PT-2 PT-1 PT-1 / PT-2 PT-1
CHART ALCOVE D205D LVT-1 ACT-2 P-2 RB-1 P-2 P-2 - P-2
ANTEROOM D206A RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3
ISO ROOM 6 D206B RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3
ANTEROOM D207A RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3
ISO ROOM 7 D207B RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3
TOILET D207C RF-1 P-6 PT-1 RF-2 PT-1 / PT-2 PT-1 PT-1 / PT-2 PT-1
CHART ALCOVE D207D LVT-1 ACT-2 P-2 RB-1 P-2 P-2 - P-2
ANTEROOM D208A RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3
ISO ROOM 8 D208B RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3
TOILET D208C RF-1 P-6 PT-1 RF-2 PT-1 / PT-2 PT-1 PT-1 / PT-2 PT-1
ANTEROOM D209A RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3
ISO ROOM 9 D209B RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3
TOILET D209C RF-1 P-6 PT-1 RF-2 PT-1 / PT-2 PT-1 PT-1 / PT-2 PT-1
CHART ALCOVE D209D LVT-1 ACT-2 P-2 RB-1 - P-2 P-2 P-2
ANTEROOM D210A RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3
ISO ROOM 10 D210B RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3
TOILET D210C RF-1 P-6 PT-1 RF-2 PT-1 / PT-2 PT-1 PT-1 / PT-2 PT-1
ANTEROOM D211A RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3
ISO ROOM 11 D211B RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3
TOILET D211C RF-1 P-6 PT-1 RF-2 PT-1 / PT-2 PT-1 PT-1 / PT-2 PT-1
CHART ALCOVE D211D LVT-1 ACT-2 P-2 RB-1 - P-2 P-2 P-2
ANTEROOM D212A RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3
ISO ROOM 12 D212B RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3
TOILET D212C RF-1 P-6 PT-1 RF-2 PT-1 / PT-2 PT-1 PT-1 / PT-2 PT-1
ALCOVE D213 LVT-1 ACT-2 P-2 RB-1 - P-2 P-2 P-2
EQUIPMENT D214 RF-1 ACT-2 P-3 RB-1 P-3 P-3 P-3 P-3
NOURISHMENT D215 LVT-2 ACT-2 P-3 RB-2 P-3 P-3 P-3 P-3
HUDDLE D216 LVT-2 ACT-2 P-4 RB-2 P-4 P-4 P-4 P-4
ALCOVE D217 LVT-1 ACT-2 P-2 RB-1 - P-2 P-2 P-2
RESTROOM D218 RF-1 P-6 PT-1 RF-2 PT-1 PT-1 / PT-2 PT-1 PT-1 / PT-2
CLEAN D219 RF-1 ACT-2 P-3 RF-1 P-3 P-3 P-3 P-3
LINEN D220 RF-1 ACT-2 P-3 RF-1 P-3 P-3 P-3 P-3
SOILED D221 RF-1 ACT-2 P-3 RF-1 P-3 P-3 P-3 P-3
OIT D222 RF-1 EXP P-3 RF-1 P-3 P-3 P-3 P-3
NURSE STATION D223 LVT-1 ACT-2 P-2 RB-1 - P-2 P-2 P-2
MED D224 LVT-2 ACT-2 P-3 RB-1 P-3 P-3 P-3 P-3
X-RAY ALCOVE D225 LVT-1 ACT-2 P-2 RB-1 - P-2 P-2 P-2
LAB ALCOVE D226 LVT-1 ACT-2 P-2 RB-1 P-2 P-2 P-2 P-2
NURSE MANAGER D227 LVT-1 ACT-2 P-2 RB-1 P-2 P-2 P-2 P-2
LOUNGE D228 LVT-1 ACT-2 P-4 RB-2 P-4 P-4 P-4 P-4
STORAGE D229 LVT-1 ACT-2 P-4 RB-2 P-4 P-4 P-4 P-4
STAFF TOILET D230 RF-1 P-6 PT-1 RF-2 PT-1 PT-1 / PT-2 PT-1 PT-1 / PT-2
WOMEN'S LOCKER D231 LVT-2 ACT-2 P-4 RB-2 P-4 P-4 P-4 P-4
MEN'S LOCKER D232 LVT-2 ACT-2 P-4 RB-2 P-4 P-4 P-4 P-4
ELECTRICAL D233 RF-1 EXP P-3 RB-1 P-3 P-3 P-3 P-3
CONSULT D234 CPT-1 ACT-2 P-2 RB-2 P-2 P-2 P-2 P-2
BIOMED D235 CPT-1 EXP P-3 RB-2 P-3 P-3 P-3 P-3
TOILET D-206C RF-1 P-6 PT-1 RF-2 PT-1 / PT-2 PT-1 PT-1 / PT-2 PT-1
F I N I S H L E G E N D N O T E S
1. ALL PRODUCTS LISTED IN THE FINISH LEGEND ARE BASIS OF DESIGN ONLY UNLESS NOTED OTHERWISE.
2. PROVIDE TRANSITION STRIPS AT TRANSITIONS FOR ALL DISSIMILAR FLOORING MATERIALS, TYPICAL. SEE DIVISION 9 SPECIFICATIONS.
No. Revisions: Date:
BID DOCUMENTS 11/04/2022
P N M L K I H G F E C
35.1
D B.5 B A.5 A
30.1
32.8
O
ISO ROOM 1
D201B
ISO ROOM 2
D202B
ISO ROOM 3
D203B
ISO ROOM 4
D204B
ISO ROOM 5
D205B
ISO ROOM 6
D206B
ISO ROOM 7
D207B
ISO ROOM 8
D208B
ISO ROOM 9
D209B
ISO ROOM 10
D210B
ISO ROOM 11
D211B
ISO ROOM 12
D212B
TOILET
D201C
ANTEROOM
D201A
TOILET
D202C
ANTEROOM
D202A
TOILET
D204C
TOILET
D203C
ANTEROOM
D203A
ANTEROOM
D204A
ANTEROOM
D205A
TOILET
D205C
TOILET
D-206C
ANTEROOM
D206A
ANTEROOM
D207A
TOILET
D208C
TOILET
D207C
ANTEROOM
D208A
ANTEROOM
D209A
TOILET
D210C
TOILET
D209C
ANTEROOM
D210A
ANTEROOM
D211A
TOILET
D212C
TOILET
D211C
ANTEROOM
D212A
CHART ALCOVE
D201D
CHART ALCOVE
D203D
CHART ALCOVE
D205D
CHART ALCOVE
D207D
CHART ALCOVE
D209D
CHART ALCOVE
D211D
EQUIPMENT
D214
ELECTRICAL
D233
NOURISHMENT
D215
HUDDLE
D216
CLEAN
D219 LINEN
D220
SOILED
D221
NURSE STATION
D223
OIT
D222
MED
D224 NURSE MANAGER
D227
LAB ALCOVE
D226
BIOMED
D235
MECHANICAL
H.A.C.
STAIRS
S1
STAFF TOILET
D230
LOUNGE
D228
CORRIDOR
D2C3
RESTROOM
D218
ALCOVE
D217
ALCOVE
D213
WOMEN'S LOCKER
D231
MEN'S LOCKER
D232
STORAGE
D229
X-RAY ALCOVE
D225
SHAFT
CORRIDOR
D2C5
CORRIDOR
C6
CORRIDOR
D2C4B
CORRIDOR
D2C2
CORRIDOR
D2C1
CONSULT
D234
CORRIDOR
D2C3A
VESTIBULE
D236
14 15 16
03 04
05 06
222120
18 24
S135
12C
08C
07C06C
05C
04C
03C02C
01C
09C
10C 11C
ELEVATOR LOBBY
D2EL2
CORRIDOR
D2-C4A
9' - 6" 19' - 0" 1' - 8" 22' - 4" 22' - 6" 23' - 0" 22' - 6" 26' - 0" 26' - 0" 26' - 0" 10' - 0" 4' - 6" 10' - 3" 10' - 0" 10' - 0" 10' - 0"
1'
9'
9'
0"
6'
9'
BUILDING 200
#A##
FULL ROOM NUMBER
INCLUDING LETTERS
9"
3"
SIGN TYPE FOR ELECTRICAL
CLOSETS, MECHANICAL
ROOMS AND
TELECOMMUNICATION ROOMS
#A##
FULL ROOM NUMBER
INCLUDING LETTERS
ROOM NAME
9"
SECONDARY
MESSAGE
POTENTIAL
SECONDARY MESSAGE
MEN
9"
WOMEN
9"
RESTROOM
9"
9"
9"
STAIRS
5'
2"
SIGN
DOOR FRAME
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
1100 Boulders Pkwy | Suite 503 Richmond, VA 23225
804.355.2067
A u to d e s k D o c s /M t H o m e
I s o la ti o n W a rd
D
/F F
E
M t H o m e
D rv t
/4 /2
:2
:2
P
M
AW101
SECOND FLOOR WAYFINDING
11/04/2022 ET NM
RENOVATE D-WING FOR ISOLATION
WARD
621-20-107
MOUNTAIN HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER
Approved: MT Home VA
N
1/8" = 1'-0"
SECOND FLOOR WAYFINDING PLAN
N
NTS
KEYPLAN
1 1/2" = 1'-0"
IN-03.01 - SUPPORT ROOM SIGN
1 1/2" = 1'-0"
IN-04.01 - ROOM SIGN
1 1/2" = 1'-0"
IN-09.04 - RESTROOM IDENTIFICATION
1 1/2" = 1'-0"
IN-09.05 - RESTROOM IDENTIFICATION
1 1/2" = 1'-0"
IN-09.06 - RESTROOM IDENTIFICATION
1 1/2" = 1'-0"
IN-09.08 MESSAGE D STAIR SYMBOL
3/8" = 1'-0"
TYPICAL SIGNAGE ELEVATION
S I G N A G E N O T E S
1. ALL FINAL NAMES, NUMBERS AND SIGN TYPES TO BE
CHOSEN BY THE VA DURING CONSTRUCTION.
S I G N A G E S C H E D U L E
MARK TYPE MESSAGE COUNT
01 IN-04.01 ISOLATION ROOM 1 1
01C IN-09.06 RESTROOM 1
02 IN-04.01 ISOLATION ROOM 2 1
02C IN-09.06 RESTROOM 1
03 IN-04.01 ISOLATION ROOM 3 1
03C IN-09.06 RESTROOM 1
04 IN-04.01 ISOLATION ROOM 4 1
04C IN-09.06 RESTROOM 1
05 IN-04.01 ISOLATION ROOM 5 1
05C IN-09.06 RESTROOM 1
06 IN-04.01 ISOLATION ROOM 6 1
06C IN-09.06 RESTROOM 1
07 IN-04.01 ISOLATION ROOM 7 1
07C IN-09.06 RESTROOM 1
08 IN-04.01 ISOLATION ROOM 8 1
08C IN-09.06 RESTROOM 1
09 IN-04.01 ISOLATION ROOM 9 1
09C IN-09.06 RESTROOM 1
10 IN-04.01 ISOLATION ROOM 10 1
10C IN-09.06 RESTROOM 1
11 IN-04.01 ISOLATION ROOM 11 1
S I G N A G E S C H E D U L E
MARK TYPE MESSAGE COUNT
11C IN-09.06 RESTROOM 1
12 IN-04.01 ISOLATION ROOM 12 1
12C IN-09.06 RESTROOM 1
14 IN-03.01 EQUIPMENT 1
14 IN-04.01 EQUIPMENT 1
15 IN-04.01 NOURISHMENT 1
16 IN-04.01 MED 1
18 IN-04.01 RESTROOM 1
19 IN-04.01 CLEAN LAUNDRY 1
20 IN-04.01 LINEN 2
21 IN-04.01 SOILED 2
22 IN-03.01 OIT 1
24 IN-04.01 HUDDLE 1
27 IN-04.01 NURSE MANAGER 1
28 IN-04.01 LOUNGE 1
30 IN-09.06 RESTROOM 1
31 IN-09.05 WOMEN'S LOCKER 1
32 IN-09.04 MEN'S LOCKER 1
33 IN-03.01 ELECTRICAL 1
34 IN-04.01 CONSULT 1
35 IN-04.01 BIOMED 1
S1 IN-09.08 STAIRS 1
P N M L K I H G F E C
35.1
D B.5 B A.5 A
30.1
32.8
O
ISO ROOM 1
D201B
ISO ROOM 2
D202B
ISO ROOM 3
D203B
ISO ROOM 4
D204B
ISO ROOM 5
D205B
ISO ROOM 6
D206B
ISO ROOM 7
D207B
ISO ROOM 8
D208B
ISO ROOM 9
D209B
ISO ROOM 10
D210B
ISO ROOM 11
D211B
ISO ROOM 12
D212B
TOILET
D201C
ANTEROOM
D201A
TOILET
D202C
ANTEROOM
D202A
TOILET
D204C
TOILET
D203C
ANTEROOM
D203A
ANTEROOM
D204A
ANTEROOM
D205A
TOILET
D205C
TOILET
D-206C
ANTEROOM
D206A
ANTEROOM
D207A
TOILET
D208C
TOILET
D207C
ANTEROOM
D208A
ANTEROOM
D209A
TOILET
D210C
TOILET
D209C
ANTEROOM
D210A
ANTEROOM
D211A
TOILET
D212C
TOILET
D211C
ANTEROOM
D212A
CHART ALCOVE
D201D
CHART ALCOVE
D203D
CHART ALCOVE
D205D
CHART ALCOVE
D207D
CHART ALCOVE
D209D
CHART ALCOVE
D211D
EQUIPMENT
D214
ELECTRICAL
D233
NOURISHMENT
D215
HUDDLE
D216
CLEAN
D219
LINEN
D220
SOILED
D221
NURSE STATION
D223
OIT
D222
MED
D224 NURSE MANAGER
D227
LAB ALCOVE
D226
BIOMED
D235
MECHANICAL
STAIRS
S1
STAFF TOILET
D230
LOUNGE
D228
CORRIDOR
D2C3
RESTROOM
D218
ALCOVE
D217
ALCOVE
D213
WOMEN'S LOCKER
D231
MEN'S LOCKER
D232
STORAGE
D229X-RAY ALCOVE
D225
CORRIDOR
D2C5
CORRIDOR
C6
CORRIDOR
D2C4B
CORRIDOR
D2C2
CORRIDOR
D2C1
CONSULT
D234
CORRIDOR
D2C3B
CORRIDOR
D2C3A
VESTIBULE
D236
1 1 1
1 1 1
11 1 1
WP101
2 22
9' - 6" 19' - 0" 1' - 8" 22' - 4" 22' - 6" 23' - 0" 22' - 6" 26' - 0" 26' - 0" 26' - 0" 10' - 0" 4' - 6" 10' - 3" 10' - 0" 10' - 0" 10' - 0"
1'
9'
9'
0"
6'
9'
CG-1
RB-1
WP-1
HR-1
BG-1
TYP.
4 3/4"
TYP.
2"
T Y
P
T Y
P
ALIGN BOTTOM
OF BUMPER
GUARD WITH
TOP OF WALL
BASE.
P-1
INDICATOR LIGHT -
SEE ELECTRICAL
DRAWINGS
GYPSUM WALL BOARD
MIN. 20 GA. HORIZONTAL/VERTICAL
STEEL STUD AND STRAPPING
1/4-20 X 5" RD HD BOLT
W/ TOGGLE AND
LOCK WASHER
32" [812.8mm] O.C. MAX.
1 1/2"
3"
/2
ALUMINUM
RETAINER
ACROVYN CRASH
RAIL
ACROVYN
HANDRAIL
ACROVYN
ACCENT
REVEAL
LIGATURE RESISTANT MOUNTING
BRACKET
5/8" GYPSUM WALL BOARD -
REFER TO PARTITION TYPES
MIN. 20 GA HORIZONTAL STEEL STUD
1 1/2" ALUMINUM
RETAINER CLIP
(24F236001)
ACROVYN 4000 COVER
REGRIND BUMPER
CUSHION
(24U804108)
MOUNTING CUSHION
(24I066108)
1"
HANDRAIL2"
/2
/2
2"
CORNER
GUARD
1 1/2" 1 1/2"
D R
Y W
A L
L S
E T
B A
C K
/1
STEEL STUD
5/8" G.W.B.
FEATHERED
JOINT
R1" [R25.4mm]
ALUMINUM RETAINER
ACROVYN 4000 COVER
ACROVYN CHAMELEON
#6 X 1 5/8" BUGLE HD SMS
BUILDING 200
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
1100 Boulders Pkwy | Suite 503 Richmond, VA 23225
804.355.2067
A u to d e s k D o c s /M t H o m e
I s o la ti o n W a rd
D
/F F
E
M t H o m e
D rv t
/4 /2
:2
:1
P
M
WP101
WALL PROTECTION PLAN
11/04/2022 ET NM
RENOVATE D-WING FOR ISOLATION
WARD
621-20-107
MOUNTAIN HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER
Approved: MT Home VA
N
1/8" = 1'-0"
SECOND FLOOR PLAN WALL PROTECTION PLAN
D R A W I N G N O T E S
1 PROVIDE AND INSTALL ACRYLIC 48" HIGH CORNER GUARD.
2 ACRYLIC HANDRAIL.
1/2" = 1'-0"
INTERIOR ELEVATION AT WALL PROTECTION
6" = 1'-0"
HANDRAIL SECTION DETAIL
6" = 1'-0"
WALL BUMPER GUARD SECTION DETAIL
1" = 1'-0"
PLAN VIEW - HANDRAIL
6" = 1'-0"
ACROVYN CORNER GUARD DETAIL
N
NTS
KEYPLAN
P N M L K I H G F E C
35.1
D B.5 B A.5 A
30.1
32.8
O
CLEAN
D219
LINEN
D220
SOILED
D221
OIT
D222
ISO ROOM 1
D201B
ISO ROOM 2
D202B
ISO ROOM 3
D203B
ISO ROOM 4
D204B
ISO ROOM 5
D205B
ISO ROOM 9
D209B
ANTEROOM
D201A
TOILET
D202C
ANTEROOM
D202A
TOILET
D203C
ANTEROOM
D203A
ANTEROOM
D204A
ANTEROOM
D205A
TOILET
D-206C
ANTEROOM
D209A
CHART ALCOVE
D201D
CHART ALCOVE
D203D
CHART ALCOVE
D205D
EQUIPMENT
D214
ELECTRICAL
D233
NOURISHMENT
D215
HUDDLE
D216
NURSE STATION
D223
MED
D224
NURSE MANAGER
D227
LAB ALCOVE
D226
BIOMED
D235
MECHANICAL
H.A.C.
CORRIDOR
D2C3
RESTROOM
D218
ALCOVE
D217
ALCOVE
D213
X-RAY ALCOVE
D225
CORRIDOR
D2C5
CORRIDOR
C6
CORRIDOR
D2C4B
CORRIDOR
D2C2
CORRIDOR
D2C1
CONSULT
D234
CORRIDOR
D2C3B
CORRIDOR
D2C3A
VESTIBULE
D236 1 1 1 1
TOILET
D201C
TOILET
D205C ISO ROOM 6
D206B
ISO ROOM 7
D207B
ANTEROOM
D206A
ANTEROOM
D207A
TOILET
D208C
TOILET
D207C
ISO ROOM 8
D208B
CHART ALCOVE
D207D
ANTEROOM
D208A
LOUNGE
D228
MEN'S LOCKER
D232
WOMEN'S LOCKER
D231
STAFF TOILET
D230
ISO ROOM 12
D212B
ISO ROOM 11
D211B
ANTEROOM
D212A
STORAGE
D229CHART ALCOVE
D211DANTEROOM
D211A
ANTEROOM
D210A
ISO ROOM 10
D210B
CHART ALCOVE
D209D
1 1
TOILET
D211C
TOILET
D212C
1 1
1 1 1
TOILET
D210C
TOILET
D209C
TOILET
D204C
QT402
Sim
QT403
Sim
9' - 6" 19' - 0" 1' - 8" 22' - 4" 22' - 6" 23' - 0" 22' - 6" 26' - 0" 26' - 0" 26' - 0" 10' - 0" 4' - 6" 10' - 3" 10' - 0" 10' - 0" 10' - 0"
1'
9'
9'
0"
6'
9'
AE601
BUILDING 200
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
1100 Boulders Pkwy | Suite 503 Richmond, VA 23225
804.355.2067
A u to d e s k D o c s /M t H o m e
I s o la ti o n W a rd
D
/F F
E
M t H o m e
D rv t
/4 /2
:3
:0
P
M
QT101
D2 OVERALL EQUIPMENT PLAN
11/04/2022 ET TJ
RENOVATE D-WING FOR ISOLATION
WARD
621-20-107
MOUNTAIN HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER
Approved: MT Home VA
N
1/8" = 1'-0"
D2 OVERALL EQUIPMENT PLAN
N
NTS
KEYPLAN
D R A W I N G N O T E S
1 ANTEROOM AND ISOLATION ROOM EQUIPMENT SHOWN ON QT401.
2 BATHROOM ACCESSORIES SHOWN ON AE401.
3 CHART ALCOVE EQUIPMENT SHOWN ON QT401.
ISO ROOM 2
D202B
ANTEROOM
D202A
A5080
A5077
F2010
A5075
M3070
M3072
AE402 21
AE601
QT401 5
ISO ROOM 2
D202B
TOILET
D201C
TOILET
D202C
M7010
A5108
F3050
F3200
M0506
F0260
M7040
M3070M3072
F2010
A5080
A5075
A5077
M3025
G E N E R A L E Q U I P M E N T N O T E S
A. TYPICAL EQUIPMENT PLANS SHOW EQUIPMENT AND ACCESSORIES PER EACH ROOM TYPE.
THERE ARE (12) ISOLATION ROOMS EACH WITH A MAIN ROOM, ANTE ROOM AND BATHROOM.
THERE ARE (6) CHART ALCOVES IN THE PROJECT.
B. TOTAL EQUIPMENT, FURNITURE AND ACCESSORY LIST ON SHEET QT403.
C. REFER TO SHEET GI001 FOR APPLICABLE ACCESSIBLE INSTALLATION DIMENSIONS.
D. PROVIDE BACKING FOR WALL MOUNTED EQUIPMENT/ ACCESSORIES.
4' - 0" 4' - 0" 4' - 0"
1'
1'
1'
1'
1'
1'
6'
4 1/2" 4 1/2" 4 1/2" 4 1/2" 4 1/2" 4 1/2"4 1/2" 4 1/2" 4 1/2" 4 1/2" 3"
AIR
EPDNP
EP D NP
O2
O2
VAC
VACVAC
AIR O2
O2
VAC
VAC VAC
EPDNP
EP
D
EP
D
NP EP NPEP
EPPP EP PP
4 1/2"4 1/2"4 1/2"4 1/2"4 1/2"4 1/2"4 1/2"4 1/2"4 1/2"4 1/2"3"
AIR O2 O2 AIR
SURGE MONITOR
TILTED TOWARDS
CORRIDOR
MONITOR TILTED
TOWARDS CORRIDOR
CHARTING MONITOR AND
KEYBOARD / MOUSE
DIA
BUMPER GUARD RAILS FOR WALL PROTECTION
BUMPER GUARD RAILS FOR WALL PROTECTION
BUMPER GUARD RAILS FOR WALL PROTECTION
BUMPER GUARD RAILS FOR WALL PROTECTION
RECESSED
EQUIPMENT RAIL
DOOR SIDEWINDOW SIDE
CORRIDOR
D2C3
CHART ALCOVE
D201D
F0280 F0280
M1801
M1801
A5150 A5150
ANTEROOM
D206A M3070
M3072
F2010
A5077
A5075
A5080
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
1100 Boulders Pkwy | Suite 503 Richmond, VA 23225
804.355.2067
A u to d e s k D o c s /M t H o m e
I s o la ti o n W a rd
D
/F F
E
M t H o m e
D rv t
/4 /2
:3
:1
P
M
QT401
ENLARGED EQUIPMENT PLAN
11/04/2022 ET NM
RENOVATE D-WING FOR ISOLATION
WARD
621-20-107
MOUNTAIN HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER
Approved: MT Home VA
N
1/4" = 1'-0"
LARGE ANTE ROOM EQUIPMENT PLAN
N
1/4" = 1'-0"
TYPICAL ISOLATION BEDROOM EQUIPMENT PLAN
D R A W I N G N O T E S
1 BATHROOM ACCESSORIES SHOWN ON AE401.
1" = 1'-0"
TYPICAL HEADWALL
N
1/4" = 1'-0"
TYPICAL CHART ALCOVE
H E A D W A L L L E G E N D
MARK NAME COUNT
AIR MEDICAL AIR OUTLET 4
D DIGITAL COMMUNICATIONS - WALL PLATES TO INCLUDE (2) RJ45
JACKS.
DIA DIALYSIS 1
EP EMERGENCY POWER OUTLET - HOSPITAL GRADE 20A, 120 V
GROUNDED DUPLEX RECEPTACLE ON EMERGENCY POWER
CIRCUIT.
NP NORMAL POWER OUTLET - HOSPITAL GRADE 15A OR 20A, 120 V
GROUNDED DUPLEX RECEPTACLE ON NORMAL POWER CIRCUIT.
O2 OXYGEN OUTLET 6
PP PATIENT PLUG 1
VAC VACUUM OUTLET 6
N
1/4" = 1'-0"
SMALL ANTE ROOM EQUIPMENT PLAN
P N M L I HO
AE401
CLEAN
D219
LINEN
D220
SOILED
D221
OIT
D222
A5080
A5075
A1012
A5106
CT050
P2450
A5145
F3200 F0750
F0205
F2000
A1012M0506
A5145
E0078
F0110
F3200
F3200
F0280
F0280
F0280
F0280
M1855
M1840
A1015
A1015
M1820
F2000
M1801
M1801
M1801
M1801
F2000
F3050
F0275
M1801
A1015
F0205
F2000
M2055
384 SF
ISO ROOM 1
D201B
382 SF
ISO ROOM 2
D202B
382 SF
ISO ROOM 3
D203B
384 SF
ISO ROOM 4
D204B
ISO ROOM 5
D205B
ISO ROOM 9
D209B
ANTEROOM
D201A
ANTEROOM
D202A
69 SF
TOILET
D203C
ANTEROOM
D203A
ANTEROOM
D204A
ANTEROOM
D205A
TOILET
D-206C
ANTEROOM
D209A
CHART ALCOVE
D201D
CHART ALCOVE
D203D
CHART ALCOVE
D205D
EQUIPMENT
D214
ELECTRICAL
D233
NOURISHMENT
D215
HUDDLE
D216
NURSE STATION
D223
MED
D224
NURSE MANAGER
D227
LAB ALCOVE
D226
BIOMED
D235
951 SF
MECHANICAL
H.A.C.
CORRIDOR
D2C3
RESTROOM
D218
ALCOVE
D217
ALCOVE
D213
X-RAY ALCOVE
D225
CORRIDOR
D2C2
CORRIDOR
D2C1
CONSULT
D234
CORRIDOR
D2C3B
CORRIDOR
D2C3A
VESTIBULE
D236
A1014
A5075
A5077 A5082A5107
A5108
A5145
F2010
F3050
M1801
P1965
R7250
A5075A5080
F2015
K4665
R7250
R4650
M3150
E0945
1 1
X4790
M2055
M2055
F0205
F3200
A5220
A6046
F0220
F0220
F0765
A5212
M0512
F0220
F2000
AE402 21
AE4024
AE403 64
AE403
AE4033
AE403 7
AE403 2
A5077
F3200
M2055
P2000
WP101
AE4045
9' - 6" 19' - 0" 1' - 8" 22' - 4" 45' - 6" 22' - 6"
9'
AE601
G E N E R A L E Q U I P M E N T N O T E S
A. TYPICAL EQUIPMENT PLANS SHOW EQUIPMENT AND ACCESSORIES PER EACH ROOM TYPE.
THERE ARE (12) ISOLATION ROOMS EACH WITH A MAIN ROOM, ANTE ROOM AND BATHROOM.
THERE ARE (6) CHART ALCOVES IN THE PROJECT.
B. TOTAL EQUIPMENT, FURNITURE AND ACCESSORY LIST ON SHEET QT403.
C. REFER TO SHEET GI001 FOR APPLICABLE ACCESSIBLE INSTALLATION DIMENSIONS.
D. PROVIDE BACKING FOR WALL MOUNTED EQUIPMENT/ ACCESSORIES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
1100 Boulders Pkwy | Suite 503 Richmond, VA 23225
804.355.2067
A u to d e s k D o c s /M t H o m e
I s o la ti o n W a rd
D
/F F
E
M t H o m e
D rv t
/4 /2
:3
:2
P
M
QT402
ENLARGED EQUIPMENT PLAN
11/04/2022 ET NM
RENOVATE D-WING FOR ISOLATION
WARD
621-20-107
MOUNTAIN HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER
Approved: MT Home VA
N
1/4" = 1'-0"
D2 WEST EQUIPMENT PLAN
D R A W I N G N O T E S
1 ANTEROOM AND ISOLATION ROOM EQUIPMENT SHOWN ON QT401.
2 BATHROOM ACCESSORIES SHOWN ON AE401.
3 CHART ALCOVE EQUIPMENT SHOWN ON QT401.
E CD B.5 B A.5 A
30.1
32.8
AE401
AE4035
AE401
A1012
A5075
A5080
F2015
F3065
F3200
R7250
K4665
LOUNGE
D228
STAFF TOILET
D230
WOMEN'S LOCKER
D231
MEN'S LOCKER
D232
CORRIDOR
D2C3
F2000 A1030
A1080 F3200
F2000
A1030
A5020
A1080
ANTEROOM
D212A
STAIRS
S1
STORAGE
D229
F0225
F0795
F0795
F0225
F0225
F0225
A5020
A5150F3200
AE4031
10' - 0" 4' - 6" 10' - 3" 10' - 0" 10' - 0" 10' - 0"
G E N E R A L E Q U I P M E N T N O T E S
A. TYPICAL EQUIPMENT PLANS SHOW EQUIPMENT AND ACCESSORIES PER EACH ROOM TYPE.
THERE ARE (12) ISOLATION ROOMS EACH WITH A MAIN ROOM, ANTE ROOM AND BATHROOM.
THERE ARE (6) CHART ALCOVES IN THE PROJECT.
B. TOTAL EQUIPMENT, FURNITURE AND ACCESSORY LIST ON SHEET QT403.
C. REFER TO SHEET GI001 FOR APPLICABLE ACCESSIBLE INSTALLATION DIMENSIONS.
D. PROVIDE BACKING FOR WALL MOUNTED EQUIPMENT/ ACCESSORIES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
1100 Boulders Pkwy | Suite 503 Richmond, VA 23225
804.355.2067
A u to d e s k D o c s /M t H o m e
I s o la ti o n W a rd
D
/F F
E
M t H o m e
D rv t
/4 /2
:3
:1
P
M
QT403
ENLARGED EQUIPMENT PLAN
11/04/2022 ET NM
RENOVATE D-WING FOR ISOLATION
WARD
621-20-107
MOUNTAIN HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER
Approved: MT Home VA
N
1/4" = 1'-0"
D2 EAST EQUIPMENT PLAN
D R A W I N G N O T E S
1 ANTEROOM AND ISOLATION ROOM EQUIPMENT SHOWN ON QT401.
2 BATHROOM ACCESSORIES SHOWN ON AE401.
T O T A L E Q U I P M E N T A N D A C C E S S O R I E S
MARK NAME
RESPONSIBILITY
COUNTVV VC CC CV
A1012 TELEPHONE, WALL MOUNTED, 1 LINE X 3
A1014 TELEPHONE, WALL MOUNTED, 1 LINE, WITH SPEAKER X 1
A1015 TELEPHONE, DESK, MULTIPLE LINE X 3
A1030 LOCKER, 2 PERSON, OVER/UNDER X 15
A1066 MIRROR, FLOAT GLASS, WITH SS FRAME X 2
A1067 MIRROR, FLOAT GLASS, ADA ACCESSIBLE X 2
A1080 MIRROR, POSTURE, WALL MOUNTED X 2
A1205 LIFT SYSTEM, OVERHEAD, PATIENT ROOM X X 12
A5020 BENCH, LOCKER ROOM, FLOOR MOUNTED (5'-0") X 2
A5030 BENCH, STALL, SHOWER, BUILT IN X 1
A5075 DISPENSER, SOAP, DISPOSABLE X 11
A5077 DISPENSER, HAND SANITIZER, HANDS-FREE X 5
A5080 DISPENSER, PAPER TOWEL, SS, SURFACE MOUNTED X 7
A5082 DISPENSER, PAPER TOWEL, SENSOR, HANDS FREE X 4
A5090 DISPOSAL, SANITARY NAPKIN, SS, SURFACE MOUNTED X 4
A5106 WASTE DISPOSAL UNIT, SHARPS W/GLOVE DISPENSER X 1
A5107 DISPENSER, GLOVE, SURGICAL/EXAMINATION, WALL MNTD X 1
A5108 WASTE DISPOSAL UNIT, SHARPS X 2
A5109 GRAB BAR, 1-1/4" DIA., SS, 2 WALL, W/C ACCESSIBLE X 13
A5110 GRAB BAR, 1-1/4" DIA., SS, 2 WALL, SHOWER USE X 12
A5111 GRAB BAR, 1-1/4" DIA., SS, 2 WALL, W/C ACCESSIBLE (2'-0" & 3'-0") X 1
A5145 HOOK, GARMENT, DOUBLE, SS, SURFACE MOUNTED X 6
A5150 HOOK, GARMENT, TRIPLE, SURFACE MOUNTED X 17
A5175 SOAP DISH, WITH BAR, SS, RECESSED X 1
A5200 DISPENSER, TOILET TISSUE, SS, 2-ROLL, SURFACE MNTD X 4
A5205 BAR, TOWEL, 1" DIAMETER, SS, SURFACE MOUNTED X 2
A5210 BRACKET, TELEVISION, WALL MOUNTED, W/ ADJUST ARM X 1
A5212 BRACKET, TELEVISION, WALL MOUNTED X 1
A5220 BRACKET, TELEVISION, WALL BACKING X 2
A6010 BUMPER, WALL, BED LOCATOR X 13
A6046 ARTWORK, DECORATIVE WITH FRAME X 1
CT050 COUNTERTOP, STAINLESS STEEL X 1
E0078 WORKSTATION, L-SHAPED W/PENINSULA, FREE STD, 78X72 X 1
E0945 CART, COMPUTER, MOBILE X 1
F0110 BOOKCASE, 3 SHELF X 1
F0205 CHAIR, SIDE WITH ARMS X 3
F0220 CHAIR, CONFERENCE X 5
F0225 CHAIR, DINING ROOM X 8
F0260 CHAIR, HIGH BACK, PATIENT X 1
F0275 CHAIR, SWIVEL, HIGH BACK X 1
F0280 CHAIR, SWIVEL, LOW BACK X 16
F0750 OFFICE TABLE X 1
F0765 TABLE FOLDING - NESTING X 2
F0795 TABLE, DINING X 2
F2000 BASKET, WASTEPAPER, FIRE RESISTANT X 8
F2010 BASKET, WASTEPAPER, STEP-ON X 7
F2015 BASKET, WASTEPAPER, METAL/ PLASTIC, 2 SWINGING DOORS X 2
F3050 WHITEBOARD, DRY ERASE X 3
F3065 WHITEBOARD/ BULLETIN BOARD, COMBINATION X 1
F3200 CLOCK, BATTERY, 12" DIAMETER X 9
GB GRAB BAR, 1-1/4" DIA., SS, (2'-0") X 1
K4665 OVEN, MICROWAVE, CONSUMER X 2
M0506 TELEVISION, FLAT SCREEN X 1
M0512 TELEVISION, HDTV, LARGE SCREEN, 60" X 1
M0515 TELEVISION, HD, 40" CLASS X 12
M0750 FLOWMETER, AIR, CONNECT W/50 PSI SUPPLY X 50
M0755 FLOWMETER, OXYGEN, LOW FLOW X 76
M0765 REGULATOR, VACUUM X 78
M1801 COMPUTER, MICROPROCESSING, W/ FLAT PANEL MONITOR X 18
M1820 IMPRINTER, DATA RECORD, ELECTRIC X 1
M1840 PRINTER/ COPIER/ FAX COMBINATION X 1
M1855 FACSIMILE MACHINE X 1
M2055 SHELVING, STORAGE, WIRE, CRS, W/ADJUSTABLE SHELVES X 6
M3025 MATTRESS, PRESSURE REDUCTION X 1
M3070 HAMPER, LINEN, MOBILE, W/LID X 3
M3072 FRAME, INFECTIOUS WASTE BAG W/LID X 3
M3150 DISTRIBUTION SYSTEM, MEDICATION, AUTOMATIC X 1
M7010 BED, PATIENT, ELECTRIC X 12
T O T A L E Q U I P M E N T A N D A C C E S S O R I E S
MARK NAME
RESPONSIBILITY
COUNTVV VC CC CV
M7040 TABLE, OVERBED X 1
P1965 EYEWASH, EYE/FACE, SINK MOUNTED, HANDS-FREE X 1
P2000 EYEWASH, WALL MOUNTED, HANDS-FREE X 1
P2450 VALVE, MIXING, THERMOSTATIC X 1
R4650 ICE MAKER, FLAKED, WITH DISPENSER X 1
R7250 REFRIGERATOR/ FREEZER, 20 CUBIC FEET X 3
X4790 RADIOGRAPHIC UNIT, MOBILE, DIGITAL X 1
FIRE ALARM SYSTEM NOTES
1. THE BUILDING IS EQUIPPED WITH AN EXISTING SIMPLEX FIRE ALARM SYSTEM. SCOPE OF WORK INCLUDES DEMOLITION OF EXISTING DEVICES AND INSTALLATION OF NEW DEVICES AS NEEDED TO PROVIDE CODE- COMPLIANT FIRE ALARM COVERAGE TO THE AREAS DEPICTED IN THE CONTRACT DOCUMENTS. PROVIDE ALL ITEMS AND APPURTENANCES NECESSARY, REASONABLE, INCIDENTAL, OR CUSTOMARILY INCLUDED. PROVIDE ALL EQUIPMENT, MATERIALS LABOR, SUPERVISION, AND SERVICE NECESSARY SO AS TO PROVIDE A COMPLETE FUNCTIONING FIRE ALARM SYSTEM IN A SAFE WORKING ORDER. INVESTIGATE EXISTING MAINTENANCE CONTRACT
PRIOR TO STARTING WORK.
2. THE FACILITY USES THE SIMPLEX TRUESITE WORKSTATION (TSW) SOFTWARE TO MANAGE AND MONITOR THE EXISTING FIRE ALARM SYSTEM. ALL NEW DEVICES MUST BE CORRECTLY MAPPED AND INTEGRATED INTO THE TSW SYSTEM. CONTRACTOR RESPONSIBILITY TO VERIFY THAT TRANSPONDER IN ROOM E125 IS THE CORRECT
LOCATION TO MAP NEW FIRE ALARM DEVICES.
3. WALL MOUNTED, AUDIBLE NOTIFICATION DEVICES SHALL HAVE THEIR TOPS MOUNTED AT 90" MINIMUM AND 100" MAXIMUM ABOVE THE FINISHED FLOOR, AND NO CLOSER THAN 6" TO A HORIZONTAL STRUCTURE. (NFPA 72, 2016, CH. 18.4.8.1). ALL WALL MOUNTED VISUAL APPLIANCES AND COMBINATION AUDIBLE/VISUAL APPLIANCES SHALL HAVE THEIR BOTTOMS MOUNTED AT 80" MINIMUM AND 96" MAXIMUM ABOVE FINISHED FLOOR AS MEASURED TO
THE LENS. (NFPA 72, 2016, CH. 18.5.5.1)
4. ALL EQUIPMENT SHALL BE U.L. LISTED AND / OR FM APPROVED.
5. ALL FIRE ALARM WIRING SHALL BE FLP (FIRE POWER LIMITED) OR FPLP (FIRE POWER LIMITED PLENUM) AS
REQUIRED FOR APPLICATION. WIRING IN CONDUIT ABOVE GROUND MAY BE THHN OR THWN.
6. PER THE NEC, ALL WIRING IS TO BE PULLED THROUGH EACH JUNCTION BOX AND CONNECTED DIRECTLY TO EACH FIRE DEVICE. DO NOT SPLICE THE WIRE. THERE MUST BE AT LEAST 6' OF LEAD WIRE FROM THE BOX TO THE DEVICE. ALL BOXES TO BE SIZED PER NEC AND SHALL HAVE THEIR COVERS PAINTED RED WHERE
APPLICABLE.
7. DO NOT DEVIATE FROM CONDUIT RUNS AS SHOWN ON FLOOR PLANS WITHOUT PRIOR APPROVAL FROM ELECTRICAL ENGINEER. FACTORS SUCH AS EXCESSIVE VOLTAGE DROP, ADDITIONAL PARTS, ENGINEERING, ETC., THAT ARE A RESULT OF CONDUIT RUN DEVIATIONS SHALL BE THE SOLE RESPONSIBILITY OF THE ELECTRICAL
CONTRACTOR.
8. ALL FAN SHUTDOWN FUNCTIONS, DAMPER CLOSURES AND ASSOCIATED MECHANICAL SYSTEM FIRE ALARM
INTERFACE SHALL BE BY MECHANICAL CONTRACTOR, AND SHALL BE COORDINATED WITH FIRE
ALARM SYSTEM.
9. ALL DUCT SMOKE DETECTORS SHALL BE MOUNTED BY THE MECHANICAL CONTRACTOR. DUCT SMOKE DETECTORS
EXPOSED TO THE WEATHER SHALL BE UL LISTED FOR OUTDOOR INSTALLATION, AND WEATHER
PROTECTED BY THE MECHANICAL CONTRACTOR. ALL AIR VELOCITY TESTING SHALL BE PERFORMED BY THE
MECHANICAL CONTRACTOR.
10. ALL FIRE ALARM DEVICE BACKBOXES, FIRE ALARM TERMINAL CABINETS, GUTTERS, JUNCTION BOXES AND ASSOCIATED CONDUITS SHALL BE FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR UNLESS OTHERWISE NOTED. REFER TO FIRE ALARM SYMBOL LIST AND/OR MOUNTING DETAILS FOR ADDITIONAL
INFORMATION. SYSTEM SUPPLIER PROVIDED BACKBOXES SHALL BE INSTALLED BY ELECTRICAL
CONTRACTOR UNLESS OTHERWISE NOTED.
11. SMOKE DETECTOR TESTING SHALL BE PERFORMED TO ENSURE THAT EACH DETECTOR IS WITHIN ITS LISTED AND
MARKED SENSITIVITY RANGE USING THE METHODS RECOMMENDED PER CFC 907.8.4 AND
NFPA 72, 2016 14.4.4.3.4.
12. ALL WIRING, INITIATING DEVICES AND ANNUNCIATOR PANEL SHALL BE SUPERVISED TO THE PRINCIPAL POINT OF ANNUNCIATION. THE FIRE ALARM CONTROL PANEL TO SUPERVISE THE ANNUNCIATOR PANEL, ALL
INITIATING AND INDICATING DEVICE CIRCUITS.
A. INITIATING DEVICE CIRCUITS (IDC): CLASS B
B. SIGNALING LINE CIRCUITS (SLC): CLASS B
C. NOTIFICATION APPLICANCE CIRCUITS (NAC): CLASS B
13. ALL WIRING SHALL BE CUT FOR IN AND OUT. WIRING SHALL NOT BE LOOPED THROUGH DEVICES.
14. POINT AND COMMON ANNUNCIATION AND T-TAPPING ARE PROHIBITED. (T-TAPPING IS ALLOWABLE ON SLC LOOPS).
15. CONTRACTOR TO FIELD VERIFY AND PROVIDE DECIBEL METER FOR TESTING OF AMBIENT NOISE LEVELS AUDIBLE DEVICES TO BE AT LEAST 15 DBA ABOVE THE AVERAGE AMBIENT SOUND LEVEL BUT NOT LESS THAN 75 DBA AT 10 FEET OR MORE THAN 110 DBA AT THE MINIMUM HEARING DISTANCE. SOUND LEVEL SHALL BE MAINTAINED FOR DURATION OF AT LEAST 60 SECONDS; 5 DBA MUST BE MAINTAINED.) (IFC 907.5.2.1.1) THE CONTRACTOR SHALL ADJUST/INSTALL ALL DEVICES TO MAXIMIZE PERFORMANCE AND TO MINIMIZE FALSE ALARMS. PROVIDE UPDATED PLANS AND CALCULATIONS THROUGH THE "CHANGE ORDER" PROCESS WHEN INSTALLING ADDITIONAL DEVICES. 15 DBA ABOVE THE AVERAGE AMBIENT SOUND LEVEL BUT NOT LESS THAN 75 DBA AT 10 FEET OR MORE THAN 110 DBA AT THE MINIMUM HEARING DISTANCE. SOUND LEVEL SHALL BE MAINTAINED FOR DURATION OF AT LEAST 60 SECONDS; 5 DBA MUST BE MAINTAINED.) (IFC 907.5.2.1.1) THE CONTRACTOR SHALL ADJUST/INSTALL ALL DEVICES TO MAXIMIZE PERFORMANCE AND TO MINIMIZE FALSE ALARMS. PROVIDE UPDATED PLANS AND CALCULATIONS
THROUGH THE "CHANGE ORDER" PROCESS WHEN INSTALLING ADDITIONAL DEVICES.
16. VISUAL DEVICES SHOULD NOT EXCEED 2 FLASHES PER SECOND AND SHOULD NOT BE SLOWER THAN 1 FLASH EVERY SECOND. THE DEVICE SHALL HAVE A PULSING LIGHT SOURCE NOT LESS THAN 15-CANDELA. VISUAL
DEVICES WITHIN 55' FROM EACH OTHER SHALL BE SYNCHRONIZED.
17. ALL FIRE ALARM CIRCUITS SHALL BE IN CONDUIT, APPROVED SURFACE RACEWAY OR OPEN RUN ABOVE CEILINGS, UNDER FLOORS AND IN WALLS IN A NEAT AND PROTECTED MANNER AS INDICATED ON THE DESIGN DOCUMENTS.
EXPOSED CIRCUITS ARE ONLY PERMITTED WHEN NOTED AS EXPOSED ON DESIGN DOCUMENTS. ALL CONDUITS
SHALL BE 3/4" MINIMUM. CONTRACTOR TO VERIFY CONDUIT FILL PRIOR TO INSTALLATION.
18. ALL FLOW SWITCHES SHALL BE 2 WIRE WITH NON-ELECTRONIC RETARD TYPE SIMILAR TO THE SYSTEM SENSOR
MODEL "WFD SERIES" ONLY.
19. ALL DEVICES IN THE ALARM SYSTEM SHALL BE COMPATIBLE WITH EXISTING SIMPLEX ES 4100 PANEL AND
INSTALLED PER MANUFACTURER'S SPECIFICATIONS.
20. NEW FIRE ALARM DEVICES SHALL BE FURNISHED AND INSTALLED BY AN AUTHORIZED DISTRIBUTOR.
21. FIRE ALARM SYSTEM INSTALLATION COMPANY SHALL BE UL LISTED (UUJS).
22. FIRE ALARM PANEL, REMOTES, AND COMPONENTS SHALL BE SECURED TO MOUNTING SURFACES PER MANUFACTURER'S SPECIFICATIONS. NO SINGLE DEVICE SHALL EXCEED THE WEIGHT OF 20 LBS. WITHOUT SPECIAL
MOUNTING DETAILS.
23. SMOKE DETECTOR SHALL NOT BE ANY CLOSER THAN 1 FOOT FROM FIRE SPRINKLERS OR 3 FEET FROM ANY SUPPLY DIFFUSER. IN THE AREA OF CONSTRUCTION OR WHERE POSSIBLE DAMAGE/CONTANMINAION COULD OCCUR ON NEWLY INSTALLED FIRE ALARM DEVICES, DEVICES SHALL BE COVERED UNTIL THAT AREA IS READY TO BE TURNED OVER TO THE OWNER. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH CHAPTER 7. CLEANING OR REPLACEMENT OF DEVICES THAT WERE MOUNTED AT THE REQUEST OF THE CONTRACTOR WILL NOT BE PERFORMED WITHOUT WRITTEN AUTHORIZATION THAT ASSUMES FINANCIAL RESPONSIBILITY FOR COSTS INCURRED. TESTING OF
DETECTORS SHALL BE PERFORMED PER NFPA 72 2016 14.4.5.3 AND CFC 907.9.4.
24. PER BEST PRACTICES ACTIVATION OF INITIATING DEVICE SHALL NOT REQUIRE MORE THAN 5 LBS. (22.2N) OF
FORCE OR REQUIRE TIGHT GRASPING PINCHING, OR TWISTING OF WRIST.
25. WHERE A DETECTOR IS INSTALLED ABOVE THE CEILING, THE DETECTOR SHALL BE EASILY ACCESSIBLE AND THE LOCATION OF THE DETECTOR SHALL BE CLEARLY MARKED. FOR DUCT SMOKE DETECTORS A REMOTE TEST STATION SHALL BE PROVIDED. ELECTRICAL CONTRACTOR SHALL FURNISH ACCESS PANELS TO AREAS THAT
REQUIRE SERVICING, TROUBLE SHOOTING, ETC.
26. THE "END OF LINE RESISTANCE" OF EACH CIRCUIT SHALL BE TESTED IN THE PRESENCE OF THE I.O.R. AND SHALL
NOT EXCEED THE LISTED MANUFACTURER'S MINIMUM OPERATING VOLTAGE.
27. FIRE ALARM SYSTEM IS A FULLY AUTOMATIC SYSTEM. CONTRACTOR TO UTILIZE AREA COVERAGE SMOKE DETECTORS AND ADDRESSABLE CONTROL RELAYS FOR THE SHUTDOWN AND/OR CLOSURE OF HVAC UNITS AND COMBINATION SMOKE/FIRE DAMPERS. CONTROL RELAYS TO BE LOCATED WITHIN 3FT OF THE CONTROLLED
CIRCUIT OR APPLIANCE PER NFPA 72 SECTION 21.2.4.
28. PROVIDE APPROPRIATE MANUFACTURER PRODUCT DATA SHEETS FOR ALL SUBSTITUTED MANUFACTURER'S
MATERIAL, EQUIPMENT OR APPLIANCES, TO AHJ PRIOR TO START OF INSTALLATION.
29. CONTRACTOR SHALL PROVIDE FIRE WATCH FOR ALL OCCUPIED AREAS OF WORK WHERE THE REQUIRED FIRE ALARM SYSTEM IS OUT OF SERVICE FOR THE DURATION OF THE SYSTEM OUTAGE. FIRE WATCH AND
SYSTEM/EQUIPMENT SHALL BE PER 2012 IFC 901.7.
30. CARBON MONOXIDE DETECTORS SHALL BE EQUIPPED WITH A COMPATIBLE SOUNDER BASE. UPON DETECTION THE AUDIBLE CARBON MONOXIDE SENSING DETECTORS SHALL PRODUCE A FOUR-PULSE TEMPORAL PATTERN SIGNAL
WITHIN THE IMMEDIATE AREA AND COMPLY WITH NFPA 720 5.8.6.5.
31. ALL MEMBRANE AND THROUGH-PENETRATIONS OF RATED ASSEMBLIES SHALL BE PROTECTED BY AN APPROVED FIRE STOP SYSTEM AS IDENTIFIED IN IBC CHAPTER 7, UL OR OTHER LAB TESTING CRITERIA. APPROVED TYPES OF MATERIALS SHALL BE IDENTIFIED WITHIN THE FIRE ALARM SECTION OF THE PROJECT SPECIFICATIONS.
32. CONTROL PANELS AND REMOTE ANNUNCIATORS SHALL BE INSTALLED WITH THEIR BOTTOMS MOUNTED AT 48"
ABOVE THE FINISHED FLOOR.
33. EXISTING FIRE ALARM SYSTEM SEQUENCE OF OPERATION IS NOT TO BE MODIFIED. ALL NEW FIRE ALARM DEVICES
SHALL OPERATE IN ACCORDANCE WITH EXISTING SEQUENCE OF OPERATIONS.
34. SMOKE DETECTION IS NOT REQUIRED THROUGHOUT THE CORRIDOR DUE TO THE INSTALLATION OF THE
AUTOMATIC SPRINKLER SYSTEM (NFPA 101 SECTION 19.3.4.5.1).
35. SMOKE DETECTION IS REQUIRED IN ALL SPACES THAT OPEN TO THE CORRIDOR (NFPA 101 SECTION 19.3.6.1(7)).
36. THE WORK AREA IS UTILIZING A PRIVATE MODE SIGNALING STRATEGY, RESULTING IN NOTIFICATION NOT BEING PROIVDED THROUGHOUT PATIENT ROOMS. NOTIFICATION SHALL BE PROVIDED AT THE NURSE'S STATIONS.
SYMBOL
ALL SYMBOLS SHOWN MAY NOT APPEAR IN ALL DRAWINGS. SYMBOLS ARE SHOWN SCHEMATIC AND MAY NOT BE TO SCALE.
FIRE ALARM SYMBOLS LEGEND
DESCRIPTION
WATER FLOW SWITCHWF
VALVE SUPERVISORY SWITCHVS
PRESSURE SWITCHPS
SMOKE DETECTOR WALL MOUNTED
SMOKE DETECTOR CEILING MOUNTED
HIGH/LOW PRESSURE SUPERVISORY
DUCT SMOKE DETECTOR
FACP
DH
HEAT DETECTOR WALL MOUNTED
HEAT DETECTOR CEILING MOUNTED
ELECTRO-MAGNETIC DOOR HOLDER
FIRE ALARM BELL
FIRE ALARM CONTROL PANEL
ANN FIRE ALARM ANNUNCIATOR PANEL
FPAP FIRE PUMP ANNUNCIATOR PANEL
FSCS FIREFIGHTER'S SMOKE CONTROL STATION
FAPS
FIRE ALARM POWER SUPPLY FOUR CIRCUIT FIRE ALARM NOTIFICATION APPLIANCE POWER
EXTENDER
H/L
FIRE ALARM PULL STATION WALL MOUNTEDF
FIRE ALARM AUDIBLE VISUAL SIGNAL TYPICAL CEILING MOUNT, W = WALL MOUNT, 'X' DENOTES CANDELA
RATINGX
FIRE ALARM AUDIBLE SIGNAL TYPICAL CEILING MOUNT, W = WALL MOUNT, 'X' DENOTES CANDELA RATING X
FIRE ALARM VISUAL SIGNAL TYPICAL CEILING MOUNT, W = WALL MOUNT - 15CD UNLESS NOTED OTHERWISE
EVAC EMERGENCY VOICE/ALARM COMMUNICATION PANEL
CONDUIT RISER UP TO ABOVE
CONDUIT RISER UP AND DOWN
CONDUIT RISER DOWN TO BELOW
WP WEATHER PROOF
AIM
AOM
ADDRESSABLE INPUT MODULE
ADDRESSABLE OUTPUT MODULE
ETD EMERGENCY MESSAGE TEXTUAL DISPLAY
AMP FIRE ALARM AMPLIFIER
ETR EXISTING TO REMAIN
ABBREVIATIONS
A ALPHA-NUMERIC
ACT ACOUSTICAL CEILING TILE
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
EQL END OF LINE DEVICE
FA FIRE ALARM
FAA FIRE ALARM ANNUNCIATOR PANEL
FAC FIRE ALARM COMMUNICATOR
FACP FIRE ALARM CONTROL PANEL
FSA FIRE SYSTEM ANNUNCIATOR
FTR FIRE ALARM TRANSMITTER
G GRAPHIC
HVAC HEATING, VENTILATION AND AIR CONDITIONING
MIN MINIMUM
N.C. NORMALLY CLOSED (CONTACT)
N.O. NORMALLY OPEN (CONTACT)
NAC NOTIFICATION APPLIANCE CIRCUIT
NIC NOT IN CONTRACT
NTS NOT TO SCALE
POC POINT OF CONNECTION
RA RETURN AIR (HVAC)
RTU ROOF TOP UNIT
SA SUPPLY AIR (HVAC)
SLC SIGNALING LINE CIRCUIT
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
WP WEATHER PROOF
MAX MAXIMUM
CONVENTIONS
A
E-3
C
E-5
FIRE ALARM EQUIPMENT DENOTED BY DASHED,
HEAVY LINEWEIGHT SHALL BE DISPOSED OF,
UNLESS INDICATED TO BE REUSED OR TURNED
OVER TO THE OWNER
SECTION DESIGNATION - LETTER DENOTES SECTION
IDENTIFICATION
INDICATES DRAWING NUMBER WHERE SECTION IS DRAWN
DETAIL DESIGNATION - LETTER DENOTES DETAIL
IDENTIFICATION
INDICATES DRAWING NUMBER WHERE DETAIL IS DRAWN
UNLESS INDICATED OTHERWISE
LINEWEIGHT INDICATES EXISTING TO REMAIN,
FIRE ALARM EQUIPMENT DENOTED BY LIGHT, SOLID
FIRE ALARM EQUIPMENT DENOTED BY HEAVY,
SOLID LINEWEIGHT SHALL BE NEW WORK
PROVIDED BY CONTRACTOR
EXIT
80" MIN. TO
96"
MAX. (STROBE
LENS TO
FLOOR)
- OR 6" BELOW
FINISHED
CEILING
WHICHEVER
IS
LOWER
SPEAKER/STROBE
COMBINATION DEVICE
STROBE DEVICE
SPEAKER DEVICE
90" (TOP
OF DEVICE
TO
FLOOR) - OR
6" BELOW
FINISHED
CEILING
WHICHEVER
IS
LOWER
0' - 4" MINIMUM
SMOKE / HEAT
DETECTOR
1' - 0" MAXIMUM
AIR SUPPLY DIFFUSER OR
RETURN AIR OPENING
3' - 0" MINIMUM0' - 4" MINIMUM
ANNUNCIATOR
PANEL OR
TERMINAL
CABINET
FINISHED
FLOOR
SUSPENDED
CEILING
INSTALL PER NATIONAL ELECTRIC CODE
CONDUIT
FLEXIBLE RACEWAY TO SUSPENDED
CEILING MOUNTED DEVICE -
MAX.LENGTH OF 6' - 0"
MOUNT ON AN
APPROVED BOX
SMOKE / HEAT
DETECTOR
JUNCTION BOX
MANUAL PULL STATION
5' - 0" MAXIMUM
FROM EXIT OPENING 42" MIN. TO
48"
MAX.
(OPERATING
HANDLE TO
FLOOR)
5' - 6"
FIRE ALARM
CONTROL PANEL
OR EMERGENCY
VOICE PANEL
MOUNT AUDIBLE
AND
VISUAL DEVICES ON
APPROVED BOXES
FLOOR-
CEILING
ASSEMBLY
REMOTE LAMP W/
TEST SWITCH
60" MIN. TO
78" MAX.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
1100 Boulders Pkwy | Suite 503 Richmond, VA 23225
804.355.2067
A u to d e s k D o c s /M t H o m e
I s o la ti o n W a rd
D /W
S P
M t H o m e
D rv t
/7 /2
:5
:1
A
M
FA1.00
FIRE ALARM LEGEND AND NOTES
11/04/2022 TGS DM
RENOVATE D-WING FOR ISOLATION
WARD
621-20-107
MOUNTAIN HOME, TENNESSEE
BID DOCUMENTSJAMES H.
QUILLEN VA
MEDICAL
CENTER
Approved: Owner
NTS
FIRE ALARM DEVICE MOUNTING DETAIL
No. Revisions: Date:
1 BID DOCUMENTS 11/04/2022
11/04/2022
F
F
F
F
F
CORRIDOR
C6
CORRIDOR
D2C5
CORRIDOR
D2C4B
CORRIDOR
D2C4B
CORRIDOR
D2-C4A
CORRIDOR
D2C2
ELEVATOR LOBBY
D2EL2
29A-C
30.1
32.8
P O N M L K I H G F E D C B.5 B A.5 A
NOT IN SCOPE
ETR
ETR
ETR
OFFICE
D201B
TOILET
D201A
OFFICE
D201C
CONF. ROOM
D202
OFFICE
D202A
OFFICE
D202B
OFFICE
D202C
STAIR
WORKROOM
D203
WORKROOM
D205
TOILET
D205A
OFFICE
D207B
OFFICE
D209C
OFFICE
D209B
TOILET
D209A
OFFICE
D211B
OFFICE
D211C
OFFICE
D213C
OFFICE
D213B
TOILET
D213A
CONFERENCE AREA
D217A
ON-CALL ROOM
D215
OFFICE
D217
ELEC.
D256
TELE
D254
OFFICE
D253
OFFICE
D251
OFFICE
D249
OFFICE
D258OFFICE
D260
OFFICE
D262
OFFICE
D230
OFFICE
D228
OFFICE
D225
TOILET
D226
OFFICE
D223
OFFICE
D221
OFFICE
D219
ELEV LOBBY
CONFERENCE
D227
RECYCLING
D228A
WORKROOM
D222A
WORKROOM
D222B
SHARED SPACE
D222
TOILET
D222C
TOILET
D220A
WORKROOM
D220
WORKROOM
D218
TOILET
D218A
TOILET
D216A
WORKROOM
D216
OFFICE
D214
OFFICE
D212
TOILET
D214A
OFFICE
D210
OFFICE
D208
TOILET
D210A
OFFICE
D206
OFFICE
D204
TOILET
D206A
CORRIDOR
CORRIDOR
C2
STORAGE
D224
PHLEBOTOMY
D224A
MECH
D224
ELEV
E1
ELEV.
E2
CORRIDOR
CORRIDOR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
G E N E R A L P L A N N O T E S
KEYPLAN
1100 Boulders Pkwy | Suite 503 Richmond, VA 23225
804.355.2067
A u to d e s k D o c s /M t H o m e
I s o la ti o n W a rd
D /W
S P
M t H o m e
D rv t
/7 /2
:5
:0
A
M
FAD2.02
SECOND FLOOR FIRE ALARM
DEMOLITION PLAN
11/04/2022 TGS DM
RENOVATE D-WING FOR ISOLATION
WARD
621-20-107
MOUNTAIN HOME, TENNESSEE
BID DOCUMENTSJAMES H.
QUILLEN VA
MEDICAL
CENTER
Approved: Owner
N
1/8" = 1'-0"
SECOND FLOOR FIRE ALARM DEMOLITION PLAN
D R A W I N G N O T E S :
A. INFORMATION SHOWN IS DIAGRAMMATIC AND IS NOT INTENDED TO SHOW EVERY PIECE OF EXISTING
OR NEW EQUIPMENT.
B. DEMOLISH FIRE ALARM DEVICES IN COORDINATION WITH FINAL ARCHITECURAL LAYOUT.
C. REFER TO SHEET FA1.00 FOR ADDITIONAL INFORMATION.
No. Revisions: Date:
15CD
15CD
75CD
15CD
15CD
15CD
15CD
15CD
15CD
15CD
D H
FS TS
F
F
D H
F
15CD
29A-C
30.1
32.8
P O N M L K I H G F E D C B.5 B A.5 A
FIRE ALARM ZONE
ISO ROOM 1
D201B
ISO ROOM 2
D202B
ISO ROOM 3
D203B
ISO ROOM 4
D204B
ISO ROOM 5
D205B
ISO ROOM 6
D206B
ISO ROOM 7
D207B
ISO ROOM 8
D208B
ISO ROOM 9
D209B
ISO ROOM 10
D210B
ISO ROOM 11
D211B
ISO ROOM 12
D212B
TOILET
D201C
ANTEROOM
D201A
TOILET
D202C
ANTEROOM
D202A
TOILET
D204C
TOILET
D203C
ANTEROOM
D203A
ANTEROOM
D204A
ANTEROOM
D205A
TOILET
D205C
TOILET
D-206C
ANTEROOM
D206A
ANTEROOM
D207A
TOILET
D208C
TOILET
D207C
ANTEROOM
D208A
ANTEROOM
D209A
TOILET
D210C
TOILET
D209C
ANTEROOM
D210A
ANTEROOM
D211A
TOILET
D212C
TOILET
D211C
ANTEROOM
D212A
CHART ALCOVE
D201D
CHART ALCOVE
D203D
CHART ALCOVE
D205D
CHART ALCOVE
D207D
CHART ALCOVE
D209D
CHART ALCOVE
D211D
EQUIPMENT
D214
ELECTRICAL
D233
NOURISHMENT
D215
HUDDLE
D216
CLEAN
D219
LINEN
D220 SOILED
D221
NURSE STATION
D223
OIT
D222
MED
D224
NURSE MANAGER
D227
LAB ALCOVE
D226
BIOMED
D235
MECHANICAL
H.A.C.
STAIRS
S1
STAFF TOILET
D230
LOUNGE
D228
CORRIDOR
D2C3
RESTROOM
D218
ALCOVE
D217ALCOVE
D213
WOMEN'S LOCKER
D231
MEN'S LOCKER
D232
STORAGE
D229X-RAY ALCOVE
D225
CORRIDOR
D2C5
CORRIDOR
C6
CORRIDOR
D2C4B
CORRIDOR
D2C2
CORRIDOR
D2C1
CONSULT
D234
CORRIDOR
D2C3B
CORRIDOR
D2C3A
VESTIBULE
D236
NOT IN SCOPE
ETR
ETR
ETR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
G E N E R A L P L A N N O T E S
KEYPLAN
1100 Boulders Pkwy | Suite 503 Richmond, VA 23225
804.355.2067
A u to d e s k D o c s /M t H o m e
I s o la ti o n W a rd
D /W
S P
M t H o m e
D rv t
/7 /2
:5
:5
A
M
FA2.02
SECOND FLOOR FIRE ALARM NEW
WORK PLAN
11/04/2022 TGS DM
RENOVATE D-WING FOR ISOLATION
WARD
621-20-107
MOUNTAIN HOME, TENNESSEE
BID DOCUMENTSJAMES H.
QUILLEN VA
MEDICAL
CENTER
Approved: Owner
N
1/8" = 1'-0"
SECOND FLOOR FIRE ALARM NEW WORK PLAN
A. INFORMATION SHOWN IS DIAGRAMMATIC AND IS NOT INTENDED TO SHOW EVERY PIECE OF EXISTING OR NEW EQUIPMENT.
B. PROVIDE FIRE ALARM COVERAGE IN RENOVATED AREAS IN ACCORDANCE WITH NFPA 72. PROVIDE FULL COVERAGE AND
SYNCHRONIZATION OF DEVICES FOR FINISHED ARCHITECTURAL LAYOUT.
C. FIRE ALARM AND SPRINKLER ZONES SHALL COINCIDE WITH SMOKE COMPARTMENTS. REFER TO LIFE SAFETY SHEETS TO COORDINATE
SMOKE COMPARTMENT BOUNDARIES.
D. FINAL LOCATION AND QUANTITY OF NAC PANEL(S) SHALL BE DETERMINED BY POWER LOSS CALCULATIONS AS DETERMINED BY THE
CONTRACTOR.
E. PRIVATE MODE SIGNALING IS IMPLEMENTED IN PATIENT AREAS.
F. REFER TO SHEET FA1.00 FOR ADDITIONAL INFORMATION.
D R A W I N G N O T E S :
1. DOOR HOLDERS TO RELEASE UPON ACTIVATION OF ADJACENT SMOKE DETECTORS.
2. EXISTING SMOKE DETECTORS TO BE REINSTALLED CENTER OF CEILING TILE. REPLACE WITH NEW DEVICE IF NECESSARY.
No. Revisions: Date:
FIRE PROTECTION NOTES
1. BEFORE SUBMITTING A PROPOSAL FOR THE WORK, EACH BIDDER WILL
BE HELD RESPONSIBLE TO HAVE EXAMINED THE EXISTING SITE
CONDITIONS FOR THE WORK INCLUDED UNDER THIS CONTRACT. NO
ALLOWANCE WILL BE MADE SUBSEQUENTLY IN THIS CONNECTION ON
BEHALF OF THE CONTRACTOR FOR ANY ERROR OR NEGLIGENCE ON
THEIR PART.
2. FIRE PROTECTION CONTRACTOR SHALL BE RESPONSIBLE FOR THE
DEVELOPMENT AND SUBMITTING OF SHOP DRAWINGS.
3. DESIGN AND INSTALLATION SHALL BE SUBJECT TO FINAL INSPECTION
AND APPROVAL.
4. THE FIRE PROTECTION CONTRACTOR IS RESPONSIBLE FOR ALL
CUTTING, SEALING, PATCHING, AND PAINTING REQUIRED FOR
INSTALLATION OF THE STANDPIPE SYSTEM. ALL PENETRATIONS OF FIRE-
RATED ASSEMBLIES SHALL BE FIRE STOPPED WITH AN
APPROVED/LISTED FIRE STOPPING METHOD AS PRESCRIBED IN THE
TENNESSEE BUILDING CODE.
5. THE FIRE PROTECTION CONTRACTOR SHALL COMPLETE AND SIGN
CONTRACTOR’S MATERIAL AND TEST CERTIFICATE FOR THE ABOVE AND
UNDERGROUND PIPING AS WELL AS ANY EQUIPMENT. THE FORMS SHALL
BE GIVEN TO THE PROJECT INSPECTOR WHO WILL FORWARD TO AHJ
FOR FILLING IN PROJECT RECORDS. A COPY OF THIS CERTIFICATE SHALL
BE PROVIDED TO THE OWNER.
6. CONTRACTOR SHALL MAINTAIN A CLEAN WORK PREMISE AT ALL TIMES
AND SHALL CLEAN CONSTRUCTION SITE OF ALL THEIR DEBRIS AT THE
END OF THE DAY AND BEFORE FINAL PAYMENT IS MADE.
7. THE BUILDING IS ASSUMED TO BE STRUCTURALLY SOUND AND FULLY
CAPABLE OF SUPPORTING THE PROPOSED SPRINKLER PIPING AND ALL
ASSOCIATED FITTINGS, HANGERS, SEISMIC BRACING AND ASSOCIATED
APPURTENANCES.
8. REFER TO FIRE PROTECTION SPECIFICATIONS FOR ADDITIONAL
INFORMATION REGARDING THE FIRE PROTECTION SYSTEM.
9. REFER TO ARCHITECTURAL DRAWINGS FOR ACTUAL BUILDING
DIMENSIONS AND DETAILS. DO NOT SCALE “FP” DRAWINGS FOR
CONSTRUCTION PURPOSES.
10. OWNER SHALL BE PROVIDED WITH ALL REQUIRED TEST CERTIFICATES,
CARE & MAINTENANCE BOOK.
11. ALL MATERIALS, EQUIPMENT, APPURTENANCE AND RELATED DEVICES
SHALL BE APPROVED FOR FIRE PROTECTION USE AND BE UL LISTED
AND/OR FM APPROVED.
12. ALL WELDING SHALL BE DONE BY CERTIFIED WELDERS.
13. INSTALL ALL EQUIPMENT AND SPECIALTY DEVICES IN ACCORDANCE WITH
MANUFACTURER’S INSTRUCTIONS.
14. ALL PIPE SHALL BE BLACK STEEL SCHEDULE 40 UNLESS NOTED IN
DESIGN DRAWINGS.
15. FLOOR/ WALL PENETRATIONS THROUGH RATED SEPARATIONS SHALL BE
SEALED WITH AN APPROVED FIRE RATED MATERIAL AND/OR APPROVED
ASSEMBLY.
16. WALL PENETRATIONS THROUGH NON-RATED PARTITIONS SHALL BE
PROVIDED WITH A NON-SHRINKING GROUT OR CAULKING MATERIAL
AND/OR APPROVED ASSEMBLY.
17. JOINING OF PIPE AND FITTINGS SHALL BE DONE WITH GROOVED
COUPLINGS WHEN LIGHTWALL PIPE IS USED OR THREADED CAST IRON
OR DUCTILE IRON FITTINGS WITH THREADABLE PIPE.
18. SIGNAGE SHALL BE PROVIDED IN ACCORDANCE WITH AHJ AND NFPA 13.
19. THE SPRINKLER SYSTEM SHALL BE SUPERVISED BY THE EXISTING FIRE
ALARM SYSTEM. ALL TAMPER AND WATER FLOW SWITCHES SHALL BE
INSTALLED BY THE FIRE PROTECTION CONTRACTOR AND WIRED TO THE
EXISTING FIRE ALARM CONTROL PANEL BY THE FIRE ALARM
CONTRACTOR.
20. THE SPRINKLER SYSTEM SHALL BE HYDRAULICALLY TESTED IN
ACCORDANCE WITH NFPA 13. PRIOR TO CONNECTION TO THE ABOVE
GROUND SYSTEM, THE UNDERGROUND FIRE WATER SERVICE SHALL BE
FLUSHED IN ACCORDANCE WITH NFPA 13.
21. ALL SPRINKLER LOCATIONS SHALL BE COORDINATED WITH LIGHTING
FIXTURES, HVAC DIFFUSERS, FIRE ALARM DEVICES, SIGNS, AND OTHER
RELATED CEILING DEVICES PRIOR TO CONSTRUCTION. THE SPRINKLER
PIPE ROUTING SHALL ALSO BE COORDINATED WITH STRUCTURAL AND
OTHER DISCIPLINES PRIOR TO CONSTRUCTION TO ELIMINATE OR
MINIMIZE THE NUMBER OF LOW POINT DRAINS FOR THE SPRINKLER
SYSTEM.
22. ALL INSPECTOR’S TEST CONNECTION AND LOW POINT DRAINS SHALL BE
IN ACCORDANCE WITH NFPA 13 (UNLESS OTHERWISE NOTED) AND SHALL
BE DISPLAYED ON SHOP DRAWINGS. ALL PIPING RELATED SHALL BE
LOCATED TIGHT AGAINST THE PERIMETER WALLS. COORDINATE WITH
ARCHITECT FOR ACCEPTABLE LOCATIONS.
23. MOUNTING OF CONTROL VALVES SHALL BE AT MAXIMUM HEIGHT OF 7’-0”
A.F.F. UNLESS OTHERWISE NOTED WHICH WILL REQUIRE APPROVED
MEANS OF ACCESSIBILITY.
24. IN ACCORDANCE WITH THE PROJECTS NOTED CODES AND STANDARDS,
WHERE A WATERFLOW TEST IS USED FOR THE PURPOSE OF SYSTEM
DESIGN, THE TEST SHALL BE CONDUCTED NO MORE THAN 6 MONTHS
PRIOR TO WORKING PLAN SUBMITTAL UNLESS OTHERWISE APPROVED
BY THE AHJ.
25. WATER SUPPLY INFO USED IN DESIGN (DATED 7/13/2021):
STATIC: 115 PSI
RESIDUAL: 55 PSI
FLOW RATE: 1250 GPM
26. REMOTE AREA CALCULATION (WITH 5 PSI WATER SUPPLY DOWNGRADE)
FLOW RATE: 541 GPM
PRESSURE: 61 PSI
SAFETY MARGIN: 27 PSI
NAS NO AUTOMATIC SPRINKLERS
OFI
RN
S.F.
SPR
PSI
NTS
OFCI
NO
NC
NIC
INV
OWNER FURNISHED AND INSTALLED
POUNDS PER SQUARE INCH
RISER NIPPLE
SQUARE FEET
SPRINKLER
OWNER FURNISHED AND CONTRACTOR INSTALLED
NOT IN CONTRACT
NOT TO SCALE
NORMALLY CLOSED
NORMALLY OPEN
INVERT OF PIPE ELEVATION
GPM
GC
FLR
FFE
ELL
EL
DWG
AFF
CONT.
CONTR.
CLG
AFC
CONN
AP
FIRE PROTECTION CONTRACTOR
FINISHED FLOOR ELEVATION
GALLONS PER MINUTE
GENERAL CONTRACTOR
FLOOR
ELEVATION
ELBOW
DRAWING
ABOVE FINISHED FLOOR
ABOVE FINISHED CEILING
CONTINUATION
CONTRACTOR
CEILING
CONNECTION
ACCESS PANEL
ACOUSTICAL TILE CEILINGATC
ABBREVIATIONS
FPCR
FCC
FLOOR CONTROL VALVE ASSEMBLY
DN DOWN
TOP
WTS
TYP
TS
TOP OF PIPE ELEVATION
TAMPER / SUPERVISORY SWITCH
WATER TIGHT SLEEVE
TYPICAL
SYMBOL LEGEND
FS
PS
FSP
PRESSURE GAUGE
PRESSURE SWITCH
FLOW SWITCH
PIPING UP OR DN THROUGH FLOOR SLAB
PIPING RISE OR DROP NOT THROUGH FLOOR SLAB
SHUTOFF VALVE
CHECK VALVE WITH BALL DRIP
SHUTOFF VALVE WITH TAMPER SWITCH
FIRE STANDPIPE PIPING
EXISTING TO REMAIN (GENERAL)
EXISTING PIPING TO BE REMOVED (GENERAL)
CONNECT TO EXISTING PIPING (GENERAL)
NEW PIPING (GENERAL)
SWING CHECK VALVE
CUT AND CAP EXISTING PIPING (GENERAL)
CONTINUATION
PIPING LEGEND
SECTION DESIGNATION
DETAIL / SCHEMATIC DESIGNATION
SPRINKLER HYDRAULIC NODE TAG
UPRIGHT SPRINKLER HEAD
HORIZONTAL SIDEWALL SPRINKLER HEAD
CONCEALED PENDENT SPRINKLER HEAD
SEMI-RECESSED PENDENT SPRINKLER HEAD
PIPE CAP
DWG
EQUIPMENT TAG
FIRE HOSE VALVE
FIRE HOSE VALVE CABINET
DWG
EQ
WATER FLOW PRESSURE SWITCH
WATER FLOW SWITCH
HVAC HEATING VENTILATION AND AIR CONDITIONING CONTRACTOR
WF/PS
WF
FHV FIRE HOSE VALVE
FCVA
FIRE COMMAND CENTER
FDC FIRE DEPARTMENT CONNECTION
SP WET SPRINKLER PIPING
ETR EXISTING TO REMAIN
SPRINKLER DESIGN CRITERIA
ALL SPRINKLERS ARE TO BE QUICK RESPONSE THROUGHOUT THE SMOKE COMPARTMENT.
SPRINKLERS IN FINISHED CEILINGS SHALL BE SEMI-RECESSED PENDENTS. SPRINKLERS IN
UNFINISHED CEILING AREAS SHALL BE INSTALLED UPRIGHT. COORDINATE SPRINKLER FINISH
AND LOCATIONS WITH ARCHITECTS AND OWNER PRIOR TO INSTALLATION.
LIGHT HAZARD:
- DENSITY = 0.1 GPM/S.F. FOR MOST REMOTE 1,500 S.F. WITH 100 GPM TOTAL HOSE STREAM
- SPRINKLER COVERAGE 225 S.F. (MAX)
ORDINARY HAZARD, GROUP I:
- DENSITY = 0.15 GPM/S.F. FOR MOST REMOTE 1,500 SF WITH 250 GPM TOTAL HOSE STREAM
- SPRINKLER COVERAGE 130 S.F. (MAX)
LIGHT HAZARD CRITERIA ASSUMED FOR ALL AREAS, UNLESS NOTED OTHERWISE
ORDINARY HAZARD, GROUP I LABELED AS OH1
Project Number