C27_Updated 621-20-107 Drawings Part 2 of 3.pdf

PDF 17 MB Posted

Attached to
Y1DZ--Project 621-20-107 Renovate Bldg. -200_Wing D2 for Isolation Ward
Solicitation number
36C24923R0030
Issued by

About this file

This document provides details for a federal contract opportunity to renovate Building 200 at the James H. Quillen VAMC Mountain Home facility in Tennessee. The solicitation number is 36C24923R0030 to renovate the D Wing of Building 200 for use as an isolation ward. The project number is 621-20-107. The contracting agency is the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 9. The scope of work involves renovating the D Wing of Building 200 to accommodate use as an isolation ward. No further specifics on requirements, pricing, or response timing are provided in this document.

View the file

Other files

File Type Posted
07.09_AE403 - CASEWORK ELEVATIONS.pdf PDF
P6.01 - PLUMBING DETAILS.pdf PDF
08.01_AI601 - FINISH SCHEDULE1.pdf PDF
08.00_AI101 - SECOND FLOOR FINISH PLAN-1.pdf PDF
FXD2.02 - SECOND FLOOR FIRE PROTECTION DEMOLITION PLAN.pdf PDF
08.05_WP101 - WALL PROTECTION PLAN.pdf PDF
P2.01 - FIRST FLOOR PLUMBING NEW WORK PLAN 02.pdf PDF
P3.02 - SECOND FLOOR MEDICAL GAS NEW WORK PLAN.pdf PDF
000110 Table of Contents.pdf PDF
FX2.02 - SECOND FLOOR FIRE PROTECTION NEW WORK PLAN.pdf PDF
102600 Wall and Door Protection.pdf PDF
FX1.00 - FIRE PROTECTION LEGEND AND NOTES.pdf PDF
07.08_AE402 - CASEWORK ELEVATIONS.pdf PDF
36C24923R0030 0006.docx DOCX document
Addendum 02 Summary R1.pdf PDF
07.05_AC141 - SECOND FLOOR REFLECTED CEILING PLAN.pdf PDF
07.07_AE401 - ENLARGED RESTROOM PLANS AND ELEVATIONS.pdf PDF
087100 Door Hardware.pdf PDF
E3.02 - SECOND FLOOR LIGHTING NEW WORK PLAN.pdf PDF
36C24923R0030 0005.docx DOCX document
M2-02 - SECOND FLOOR HVAC NEW WORK PLAN.pdf PDF
36C24923R0030 0004.docx DOCX document
08.01_AI601 - FINISH SCHEDULE.pdf PDF
08.00_AI101 - SECOND FLOOR FINISH PLAN.pdf PDF
09.04_QT403 - ENLARGED EQUIPMENT PLAN.pdf PDF
36C24923R0030 0003.docx DOCX document
36C24923R0030 0002.docx DOCX document
36C24923R0030 0001.docx DOCX document
CALCULATION OF SELF PERFORMED WORK.docx DOCX document
Contractor EMR Certification Form.docx DOCX document
C27_UUpdated 621-20-107 Drawings Part 3 of 3.pdf PDF
C27 Updated 621-20-107 Drawings Part 1 of 3.pdf PDF
UEI _ TAX ID.docx DOCX document
36C24923R0030_1.docx DOCX document
C28_621-20-107 Specifications.pdf PDF
P07_Wage Determination_621-20-107 Renovate Bldg.-200 - Wing D2 for Isolation Ward.pdf PDF
RFI Form.docx DOCX document
PERFORMANCE QUESTIONNAIRE.docx DOCX document
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

F I N I S H L E G E N D

MARK DESCRIPTION BASIS OF DESIGN STYLE/ COLOR COMMENTS

ACT-1 2X2 ACOUSTICAL CEILING TILE ARMSTRONG CALLA GASKETING GRIDS -

RB-2 MILLWORK BASE JOHNSONITE

MANDALAY 4 1/2" -

44 DARK BROWN

USED WITH CPT-1 AND

LVT-2

LVT-1 LUXURY VINYL TILE

MANNINGTON

COMMERCIAL

NATURE'S PATHS - ABSTRACT

COLORWAYS - VIA CAMINO

STAGGER - 4" x 36"

P-2 PAINT - TYPE 2 PPG FOOTHILLS PPG1105-4

PT-1 PORCELAIN TILE FLORIDA TILE

RUSTIC SLATE AESTHETIC -

DELTA HAZE - FTI2991412X24

12"x24" FIELD WALL TILE

RF-1 RESINOUS FLOORING STONHARD STONTEC UTF - SANTA CRUZ INTEGRAL BASE

C-1 SOLID SURFACE CORIAN ARTISTA CANVAS -

CG-2 CORNER GUARD C/S ACROVYN DRIFTWOOD 262 -

PT-2

WP-1 WALL PROTECTION ACROVYN

WALL COVERING + PANEL SYSTEM

LINEN - NANTUCKET

ACT-2 2X2 ACOUSTICAL CEILING TILE ARMSTRONG STANDARD -

CG-1 CORNER GUARD C/S ACROVYN OYSTER GRAY 929 -

LVT-2 LUXURY VINYL TILE SHAW CONTRACT JEOGORI - BLACK TIE - 90590 QUARTER TURN - 18" x 18"

P-1 PAINT - TYPE 1 PPG COOL CONCRETE PPG1023-2

GENERAL WALL PAINT -

LATEX EGGSHELL

GENERAL WALL PAINT -

LATEX EGGSHELL

P-3 PAINT - TYPE 3 PPG DELICATE WHITE PPG1001-1

GENERAL WALL PAINT -

LATEX EGGSHELL

P-4 PAINT - TYPE 4 PPG COTTON TAIL PPG0998-1

GENERAL WALL PAINT -

LATEX EGGSHELL

P-5 PAINT - TYPE 5 PPG

CEILING PAINT -

LATEX FLAT

P-6 PAINT - TYPE 6 PPG

DELICATE WHITE PPG1001-1

CEILING PAINT -

EPOXY

DELICATE WHITE PPG1001-1

PORCELAIN TILE FLORIDA TILE

RUSTIC SLATE AESTHETIC -

COASTAL SAND - FTI2993612X24

12"x24" ACCENT WALL TILE

RB-1 RUBBER BASE JOHNSONITE A530 - 66 EITHER OR USED WITH LVT-1

CPT-1 CARPET TILE SHAW CONTRACT

BROADLOOM - JOIN -

68500 SMOKE

HR-1 HANDRAIL ACROVYN

HRB-4C -

688 LIGHTHOUSE GRAY

HR-2 HANDRAIL ACROVYN

HRB-4C -

187 TAN BARK

WP-2 WALL PROTECTION ACROVYN

WALL COVERING + PANEL SYSTEM

LINEN - NECTAR

EXP EXPOSED STRUCTURE - - -

PL-2 PLASTIC LAMINATE WILSONART

DARK BROWN WALNUT -

NEMSCHOFF, OW

RUSTIC SLATE AESTHETIC -

COASTAL SAND - FTI2993612X24

PL-1 PLASTIC LAMINATE WILSONART

WOODGRAIN LAMINATE -

OAK ON ASH, LLB

RF-2 RESINOUS FLOORING STONHARD STONTEC UTF - SANTA CRUZ

INTEGRAL BASE - TOILET ROOM

WITH CEMENT BOARD BACKER

P-7 PAINT - TYPE 7 PPG

HM DOOR FRAME PAINT -

SEMI-GLOSS

DELICATE WHITE PPG1001-1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

1100 Boulders Pkwy | Suite 503 Richmond, VA 23225

804.355.2067

A u to d e s k D o c s /M t H o m e

I s o la ti o n W a rd

D

/F F

E

M t H o m e

D rv t

/4 /2

:2

:1

P

M

AI601

FINISH SCHEDULE

11/04/2022 ET NM

RENOVATE D-WING FOR ISOLATION

WARD

621-20-107

MOUNTAIN HOME, TENNESSEE

BID DOCUMENTS

JAMES H.

QUILLEN VA

MEDICAL

CENTER

Approved: MT Home VA

F I N I S H S C H E D U L E

ROOM NAME

ROOM

NUMBER FLOOR CEILING WALL FINISH WALL BASE

WALL FINISH

N E S W

CORRIDOR D2C2 LVT-1 ACT-2 - RB-1 - - - -

CORRIDOR D2C3 LVT-1 ACT-2 P-1 RB-1 P-1 P-1 P-1 P-1

CORRIDOR D2C3A LVT-1 ACT-2 P-2 RB-1 - P-2 P-2 P-2

CORRIDOR D2C3B LVT-1 ACT-2 P-3 RB-1 P-3 P-3 P-3 P-3

CORRIDOR D2C4B LVT-1 ACT-2 - RB-1 - - - -

CORRIDOR D2C5 LVT-1 ACT-2 - RB-1 - - - -

ELEVATOR LOBBY D2EL2 LVT-1 ACT-2 - RB-1 - - - -

ANTEROOM D201A RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3

ISO ROOM 1 D201B RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3

TOILET D201C RF-2 P-6 PT-1 RF-2 PT-1 / PT-2 PT-1 PT-1 / PT-2 PT-1

CHART ALCOVE D201D LVT-1 ACT-2 P-2 RB-1 P-2 P-2 P-2 P-2

ANTEROOM D202A RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3

ISO ROOM 2 D202B RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3

TOILET D202C RF-1 P-6 PT-1 RF-2 PT-1 / PT-2 PT-1 PT-1 / PT-2 PT-1

ANTEROOM D203A RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3

ISO ROOM 3 D203B RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3

TOILET D203C RF-1 P-6 PT-1 RF-2 PT-1 / PT-2 PT-1 PT-1 / PT-2 PT-1

CHART ALCOVE D203D LVT-1 ACT-2 P-2 RB-1 P-2 P-2 P-2 P-2

ANTEROOM D204A RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3

ISO ROOM 4 D204B RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3

TOILET D204C RF-1 P-6 PT-1 RF-2 PT-1 / PT-2 PT-1 PT-1 / PT-2 PT-1

ANTEROOM D205A RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3

ISO ROOM 5 D205B RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3

TOILET D205C RF-1 P-6 PT-1 RF-2 PT-1 / PT-2 PT-1 PT-1 / PT-2 PT-1

CHART ALCOVE D205D LVT-1 ACT-2 P-2 RB-1 P-2 P-2 - P-2

ANTEROOM D206A RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3

ISO ROOM 6 D206B RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3

ANTEROOM D207A RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3

ISO ROOM 7 D207B RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3

TOILET D207C RF-1 P-6 PT-1 RF-2 PT-1 / PT-2 PT-1 PT-1 / PT-2 PT-1

CHART ALCOVE D207D LVT-1 ACT-2 P-2 RB-1 P-2 P-2 - P-2

ANTEROOM D208A RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3

ISO ROOM 8 D208B RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3

TOILET D208C RF-1 P-6 PT-1 RF-2 PT-1 / PT-2 PT-1 PT-1 / PT-2 PT-1

ANTEROOM D209A RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3

ISO ROOM 9 D209B RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3

TOILET D209C RF-1 P-6 PT-1 RF-2 PT-1 / PT-2 PT-1 PT-1 / PT-2 PT-1

CHART ALCOVE D209D LVT-1 ACT-2 P-2 RB-1 - P-2 P-2 P-2

ANTEROOM D210A RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3

ISO ROOM 10 D210B RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3

TOILET D210C RF-1 P-6 PT-1 RF-2 PT-1 / PT-2 PT-1 PT-1 / PT-2 PT-1

ANTEROOM D211A RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3

ISO ROOM 11 D211B RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3

TOILET D211C RF-1 P-6 PT-1 RF-2 PT-1 / PT-2 PT-1 PT-1 / PT-2 PT-1

CHART ALCOVE D211D LVT-1 ACT-2 P-2 RB-1 - P-2 P-2 P-2

ANTEROOM D212A RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3

ISO ROOM 12 D212B RF-1 ACT-1 P-3 RF-1 P-3 P-3 P-3 P-3

TOILET D212C RF-1 P-6 PT-1 RF-2 PT-1 / PT-2 PT-1 PT-1 / PT-2 PT-1

ALCOVE D213 LVT-1 ACT-2 P-2 RB-1 - P-2 P-2 P-2

EQUIPMENT D214 RF-1 ACT-2 P-3 RB-1 P-3 P-3 P-3 P-3

NOURISHMENT D215 LVT-2 ACT-2 P-3 RB-2 P-3 P-3 P-3 P-3

HUDDLE D216 LVT-2 ACT-2 P-4 RB-2 P-4 P-4 P-4 P-4

ALCOVE D217 LVT-1 ACT-2 P-2 RB-1 - P-2 P-2 P-2

RESTROOM D218 RF-1 P-6 PT-1 RF-2 PT-1 PT-1 / PT-2 PT-1 PT-1 / PT-2

CLEAN D219 RF-1 ACT-2 P-3 RF-1 P-3 P-3 P-3 P-3

LINEN D220 RF-1 ACT-2 P-3 RF-1 P-3 P-3 P-3 P-3

SOILED D221 RF-1 ACT-2 P-3 RF-1 P-3 P-3 P-3 P-3

OIT D222 RF-1 EXP P-3 RF-1 P-3 P-3 P-3 P-3

NURSE STATION D223 LVT-1 ACT-2 P-2 RB-1 - P-2 P-2 P-2

MED D224 LVT-2 ACT-2 P-3 RB-1 P-3 P-3 P-3 P-3

X-RAY ALCOVE D225 LVT-1 ACT-2 P-2 RB-1 - P-2 P-2 P-2

LAB ALCOVE D226 LVT-1 ACT-2 P-2 RB-1 P-2 P-2 P-2 P-2

NURSE MANAGER D227 LVT-1 ACT-2 P-2 RB-1 P-2 P-2 P-2 P-2

LOUNGE D228 LVT-1 ACT-2 P-4 RB-2 P-4 P-4 P-4 P-4

STORAGE D229 LVT-1 ACT-2 P-4 RB-2 P-4 P-4 P-4 P-4

STAFF TOILET D230 RF-1 P-6 PT-1 RF-2 PT-1 PT-1 / PT-2 PT-1 PT-1 / PT-2

WOMEN'S LOCKER D231 LVT-2 ACT-2 P-4 RB-2 P-4 P-4 P-4 P-4

MEN'S LOCKER D232 LVT-2 ACT-2 P-4 RB-2 P-4 P-4 P-4 P-4

ELECTRICAL D233 RF-1 EXP P-3 RB-1 P-3 P-3 P-3 P-3

CONSULT D234 CPT-1 ACT-2 P-2 RB-2 P-2 P-2 P-2 P-2

BIOMED D235 CPT-1 EXP P-3 RB-2 P-3 P-3 P-3 P-3

TOILET D-206C RF-1 P-6 PT-1 RF-2 PT-1 / PT-2 PT-1 PT-1 / PT-2 PT-1

F I N I S H L E G E N D N O T E S

1. ALL PRODUCTS LISTED IN THE FINISH LEGEND ARE BASIS OF DESIGN ONLY UNLESS NOTED OTHERWISE.

2. PROVIDE TRANSITION STRIPS AT TRANSITIONS FOR ALL DISSIMILAR FLOORING MATERIALS, TYPICAL. SEE DIVISION 9 SPECIFICATIONS.

No. Revisions: Date:

BID DOCUMENTS 11/04/2022

P N M L K I H G F E C

35.1

D B.5 B A.5 A

30.1

32.8

O

ISO ROOM 1

D201B

ISO ROOM 2

D202B

ISO ROOM 3

D203B

ISO ROOM 4

D204B

ISO ROOM 5

D205B

ISO ROOM 6

D206B

ISO ROOM 7

D207B

ISO ROOM 8

D208B

ISO ROOM 9

D209B

ISO ROOM 10

D210B

ISO ROOM 11

D211B

ISO ROOM 12

D212B

TOILET

D201C

ANTEROOM

D201A

TOILET

D202C

ANTEROOM

D202A

TOILET

D204C

TOILET

D203C

ANTEROOM

D203A

ANTEROOM

D204A

ANTEROOM

D205A

TOILET

D205C

TOILET

D-206C

ANTEROOM

D206A

ANTEROOM

D207A

TOILET

D208C

TOILET

D207C

ANTEROOM

D208A

ANTEROOM

D209A

TOILET

D210C

TOILET

D209C

ANTEROOM

D210A

ANTEROOM

D211A

TOILET

D212C

TOILET

D211C

ANTEROOM

D212A

CHART ALCOVE

D201D

CHART ALCOVE

D203D

CHART ALCOVE

D205D

CHART ALCOVE

D207D

CHART ALCOVE

D209D

CHART ALCOVE

D211D

EQUIPMENT

D214

ELECTRICAL

D233

NOURISHMENT

D215

HUDDLE

D216

CLEAN

D219 LINEN

D220

SOILED

D221

NURSE STATION

D223

OIT

D222

MED

D224 NURSE MANAGER

D227

LAB ALCOVE

D226

BIOMED

D235

MECHANICAL

H.A.C.

STAIRS

S1

STAFF TOILET

D230

LOUNGE

D228

CORRIDOR

D2C3

RESTROOM

D218

ALCOVE

D217

ALCOVE

D213

WOMEN'S LOCKER

D231

MEN'S LOCKER

D232

STORAGE

D229

X-RAY ALCOVE

D225

SHAFT

CORRIDOR

D2C5

CORRIDOR

C6

CORRIDOR

D2C4B

CORRIDOR

D2C2

CORRIDOR

D2C1

CONSULT

D234

CORRIDOR

D2C3A

VESTIBULE

D236

14 15 16

03 04

05 06

222120

18 24

S135

12C

08C

07C06C

05C

04C

03C02C

01C

09C

10C 11C

ELEVATOR LOBBY

D2EL2

CORRIDOR

D2-C4A

9' - 6" 19' - 0" 1' - 8" 22' - 4" 22' - 6" 23' - 0" 22' - 6" 26' - 0" 26' - 0" 26' - 0" 10' - 0" 4' - 6" 10' - 3" 10' - 0" 10' - 0" 10' - 0"

1'

9'

9'

0"

6'

9'

BUILDING 200

#A##

FULL ROOM NUMBER

INCLUDING LETTERS

9"

3"

SIGN TYPE FOR ELECTRICAL

CLOSETS, MECHANICAL

ROOMS AND

TELECOMMUNICATION ROOMS

#A##

FULL ROOM NUMBER

INCLUDING LETTERS

ROOM NAME

9"

SECONDARY

MESSAGE

POTENTIAL

SECONDARY MESSAGE

MEN

9"

WOMEN

9"

RESTROOM

9"

9"

9"

STAIRS

5'

2"

SIGN

DOOR FRAME

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

1100 Boulders Pkwy | Suite 503 Richmond, VA 23225

804.355.2067

A u to d e s k D o c s /M t H o m e

I s o la ti o n W a rd

D

/F F

E

M t H o m e

D rv t

/4 /2

:2

:2

P

M

AW101

SECOND FLOOR WAYFINDING

11/04/2022 ET NM

RENOVATE D-WING FOR ISOLATION

WARD

621-20-107

MOUNTAIN HOME, TENNESSEE

BID DOCUMENTS

JAMES H.

QUILLEN VA

MEDICAL

CENTER

Approved: MT Home VA

N

1/8" = 1'-0"

SECOND FLOOR WAYFINDING PLAN

N

NTS

KEYPLAN

1 1/2" = 1'-0"

IN-03.01 - SUPPORT ROOM SIGN

1 1/2" = 1'-0"

IN-04.01 - ROOM SIGN

1 1/2" = 1'-0"

IN-09.04 - RESTROOM IDENTIFICATION

1 1/2" = 1'-0"

IN-09.05 - RESTROOM IDENTIFICATION

1 1/2" = 1'-0"

IN-09.06 - RESTROOM IDENTIFICATION

1 1/2" = 1'-0"

IN-09.08 MESSAGE D STAIR SYMBOL

3/8" = 1'-0"

TYPICAL SIGNAGE ELEVATION

S I G N A G E N O T E S

1. ALL FINAL NAMES, NUMBERS AND SIGN TYPES TO BE

CHOSEN BY THE VA DURING CONSTRUCTION.

S I G N A G E S C H E D U L E

MARK TYPE MESSAGE COUNT

01 IN-04.01 ISOLATION ROOM 1 1

01C IN-09.06 RESTROOM 1

02 IN-04.01 ISOLATION ROOM 2 1

02C IN-09.06 RESTROOM 1

03 IN-04.01 ISOLATION ROOM 3 1

03C IN-09.06 RESTROOM 1

04 IN-04.01 ISOLATION ROOM 4 1

04C IN-09.06 RESTROOM 1

05 IN-04.01 ISOLATION ROOM 5 1

05C IN-09.06 RESTROOM 1

06 IN-04.01 ISOLATION ROOM 6 1

06C IN-09.06 RESTROOM 1

07 IN-04.01 ISOLATION ROOM 7 1

07C IN-09.06 RESTROOM 1

08 IN-04.01 ISOLATION ROOM 8 1

08C IN-09.06 RESTROOM 1

09 IN-04.01 ISOLATION ROOM 9 1

09C IN-09.06 RESTROOM 1

10 IN-04.01 ISOLATION ROOM 10 1

10C IN-09.06 RESTROOM 1

11 IN-04.01 ISOLATION ROOM 11 1

S I G N A G E S C H E D U L E

MARK TYPE MESSAGE COUNT

11C IN-09.06 RESTROOM 1

12 IN-04.01 ISOLATION ROOM 12 1

12C IN-09.06 RESTROOM 1

14 IN-03.01 EQUIPMENT 1

14 IN-04.01 EQUIPMENT 1

15 IN-04.01 NOURISHMENT 1

16 IN-04.01 MED 1

18 IN-04.01 RESTROOM 1

19 IN-04.01 CLEAN LAUNDRY 1

20 IN-04.01 LINEN 2

21 IN-04.01 SOILED 2

22 IN-03.01 OIT 1

24 IN-04.01 HUDDLE 1

27 IN-04.01 NURSE MANAGER 1

28 IN-04.01 LOUNGE 1

30 IN-09.06 RESTROOM 1

31 IN-09.05 WOMEN'S LOCKER 1

32 IN-09.04 MEN'S LOCKER 1

33 IN-03.01 ELECTRICAL 1

34 IN-04.01 CONSULT 1

35 IN-04.01 BIOMED 1

S1 IN-09.08 STAIRS 1

P N M L K I H G F E C

35.1

D B.5 B A.5 A

30.1

32.8

O

ISO ROOM 1

D201B

ISO ROOM 2

D202B

ISO ROOM 3

D203B

ISO ROOM 4

D204B

ISO ROOM 5

D205B

ISO ROOM 6

D206B

ISO ROOM 7

D207B

ISO ROOM 8

D208B

ISO ROOM 9

D209B

ISO ROOM 10

D210B

ISO ROOM 11

D211B

ISO ROOM 12

D212B

TOILET

D201C

ANTEROOM

D201A

TOILET

D202C

ANTEROOM

D202A

TOILET

D204C

TOILET

D203C

ANTEROOM

D203A

ANTEROOM

D204A

ANTEROOM

D205A

TOILET

D205C

TOILET

D-206C

ANTEROOM

D206A

ANTEROOM

D207A

TOILET

D208C

TOILET

D207C

ANTEROOM

D208A

ANTEROOM

D209A

TOILET

D210C

TOILET

D209C

ANTEROOM

D210A

ANTEROOM

D211A

TOILET

D212C

TOILET

D211C

ANTEROOM

D212A

CHART ALCOVE

D201D

CHART ALCOVE

D203D

CHART ALCOVE

D205D

CHART ALCOVE

D207D

CHART ALCOVE

D209D

CHART ALCOVE

D211D

EQUIPMENT

D214

ELECTRICAL

D233

NOURISHMENT

D215

HUDDLE

D216

CLEAN

D219

LINEN

D220

SOILED

D221

NURSE STATION

D223

OIT

D222

MED

D224 NURSE MANAGER

D227

LAB ALCOVE

D226

BIOMED

D235

MECHANICAL

STAIRS

S1

STAFF TOILET

D230

LOUNGE

D228

CORRIDOR

D2C3

RESTROOM

D218

ALCOVE

D217

ALCOVE

D213

WOMEN'S LOCKER

D231

MEN'S LOCKER

D232

STORAGE

D229X-RAY ALCOVE

D225

CORRIDOR

D2C5

CORRIDOR

C6

CORRIDOR

D2C4B

CORRIDOR

D2C2

CORRIDOR

D2C1

CONSULT

D234

CORRIDOR

D2C3B

CORRIDOR

D2C3A

VESTIBULE

D236

1 1 1

1 1 1

11 1 1

WP101

2 22

9' - 6" 19' - 0" 1' - 8" 22' - 4" 22' - 6" 23' - 0" 22' - 6" 26' - 0" 26' - 0" 26' - 0" 10' - 0" 4' - 6" 10' - 3" 10' - 0" 10' - 0" 10' - 0"

1'

9'

9'

0"

6'

9'

CG-1

RB-1

WP-1

HR-1

BG-1

TYP.

4 3/4"

TYP.

2"

T Y

P

T Y

P

ALIGN BOTTOM

OF BUMPER

GUARD WITH

TOP OF WALL

BASE.

P-1

INDICATOR LIGHT -

SEE ELECTRICAL

DRAWINGS

GYPSUM WALL BOARD

MIN. 20 GA. HORIZONTAL/VERTICAL

STEEL STUD AND STRAPPING

1/4-20 X 5" RD HD BOLT

W/ TOGGLE AND

LOCK WASHER

32" [812.8mm] O.C. MAX.

1 1/2"

3"

/2

ALUMINUM

RETAINER

ACROVYN CRASH

RAIL

ACROVYN

HANDRAIL

ACROVYN

ACCENT

REVEAL

LIGATURE RESISTANT MOUNTING

BRACKET

5/8" GYPSUM WALL BOARD -

REFER TO PARTITION TYPES

MIN. 20 GA HORIZONTAL STEEL STUD

1 1/2" ALUMINUM

RETAINER CLIP

(24F236001)

ACROVYN 4000 COVER

REGRIND BUMPER

CUSHION

(24U804108)

MOUNTING CUSHION

(24I066108)

1"

HANDRAIL2"

/2

/2

2"

CORNER

GUARD

1 1/2" 1 1/2"

D R

Y W

A L

L S

E T

B A

C K

/1

STEEL STUD

5/8" G.W.B.

FEATHERED

JOINT

R1" [R25.4mm]

ALUMINUM RETAINER

ACROVYN 4000 COVER

ACROVYN CHAMELEON

#6 X 1 5/8" BUGLE HD SMS

BUILDING 200

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

1100 Boulders Pkwy | Suite 503 Richmond, VA 23225

804.355.2067

A u to d e s k D o c s /M t H o m e

I s o la ti o n W a rd

D

/F F

E

M t H o m e

D rv t

/4 /2

:2

:1

P

M

WP101

WALL PROTECTION PLAN

11/04/2022 ET NM

RENOVATE D-WING FOR ISOLATION

WARD

621-20-107

MOUNTAIN HOME, TENNESSEE

BID DOCUMENTS

JAMES H.

QUILLEN VA

MEDICAL

CENTER

Approved: MT Home VA

N

1/8" = 1'-0"

SECOND FLOOR PLAN WALL PROTECTION PLAN

D R A W I N G N O T E S

1 PROVIDE AND INSTALL ACRYLIC 48" HIGH CORNER GUARD.

2 ACRYLIC HANDRAIL.

1/2" = 1'-0"

INTERIOR ELEVATION AT WALL PROTECTION

6" = 1'-0"

HANDRAIL SECTION DETAIL

6" = 1'-0"

WALL BUMPER GUARD SECTION DETAIL

1" = 1'-0"

PLAN VIEW - HANDRAIL

6" = 1'-0"

ACROVYN CORNER GUARD DETAIL

N

NTS

KEYPLAN

P N M L K I H G F E C

35.1

D B.5 B A.5 A

30.1

32.8

O

CLEAN

D219

LINEN

D220

SOILED

D221

OIT

D222

ISO ROOM 1

D201B

ISO ROOM 2

D202B

ISO ROOM 3

D203B

ISO ROOM 4

D204B

ISO ROOM 5

D205B

ISO ROOM 9

D209B

ANTEROOM

D201A

TOILET

D202C

ANTEROOM

D202A

TOILET

D203C

ANTEROOM

D203A

ANTEROOM

D204A

ANTEROOM

D205A

TOILET

D-206C

ANTEROOM

D209A

CHART ALCOVE

D201D

CHART ALCOVE

D203D

CHART ALCOVE

D205D

EQUIPMENT

D214

ELECTRICAL

D233

NOURISHMENT

D215

HUDDLE

D216

NURSE STATION

D223

MED

D224

NURSE MANAGER

D227

LAB ALCOVE

D226

BIOMED

D235

MECHANICAL

H.A.C.

CORRIDOR

D2C3

RESTROOM

D218

ALCOVE

D217

ALCOVE

D213

X-RAY ALCOVE

D225

CORRIDOR

D2C5

CORRIDOR

C6

CORRIDOR

D2C4B

CORRIDOR

D2C2

CORRIDOR

D2C1

CONSULT

D234

CORRIDOR

D2C3B

CORRIDOR

D2C3A

VESTIBULE

D236 1 1 1 1

TOILET

D201C

TOILET

D205C ISO ROOM 6

D206B

ISO ROOM 7

D207B

ANTEROOM

D206A

ANTEROOM

D207A

TOILET

D208C

TOILET

D207C

ISO ROOM 8

D208B

CHART ALCOVE

D207D

ANTEROOM

D208A

LOUNGE

D228

MEN'S LOCKER

D232

WOMEN'S LOCKER

D231

STAFF TOILET

D230

ISO ROOM 12

D212B

ISO ROOM 11

D211B

ANTEROOM

D212A

STORAGE

D229CHART ALCOVE

D211DANTEROOM

D211A

ANTEROOM

D210A

ISO ROOM 10

D210B

CHART ALCOVE

D209D

1 1

TOILET

D211C

TOILET

D212C

1 1

1 1 1

TOILET

D210C

TOILET

D209C

TOILET

D204C

QT402

Sim

QT403

Sim

9' - 6" 19' - 0" 1' - 8" 22' - 4" 22' - 6" 23' - 0" 22' - 6" 26' - 0" 26' - 0" 26' - 0" 10' - 0" 4' - 6" 10' - 3" 10' - 0" 10' - 0" 10' - 0"

1'

9'

9'

0"

6'

9'

AE601

BUILDING 200

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

1100 Boulders Pkwy | Suite 503 Richmond, VA 23225

804.355.2067

A u to d e s k D o c s /M t H o m e

I s o la ti o n W a rd

D

/F F

E

M t H o m e

D rv t

/4 /2

:3

:0

P

M

QT101

D2 OVERALL EQUIPMENT PLAN

11/04/2022 ET TJ

RENOVATE D-WING FOR ISOLATION

WARD

621-20-107

MOUNTAIN HOME, TENNESSEE

BID DOCUMENTS

JAMES H.

QUILLEN VA

MEDICAL

CENTER

Approved: MT Home VA

N

1/8" = 1'-0"

D2 OVERALL EQUIPMENT PLAN

N

NTS

KEYPLAN

D R A W I N G N O T E S

1 ANTEROOM AND ISOLATION ROOM EQUIPMENT SHOWN ON QT401.

2 BATHROOM ACCESSORIES SHOWN ON AE401.

3 CHART ALCOVE EQUIPMENT SHOWN ON QT401.

ISO ROOM 2

D202B

ANTEROOM

D202A

A5080

A5077

F2010

A5075

M3070

M3072

AE402 21

AE601

QT401 5

ISO ROOM 2

D202B

TOILET

D201C

TOILET

D202C

M7010

A5108

F3050

F3200

M0506

F0260

M7040

M3070M3072

F2010

A5080

A5075

A5077

M3025

G E N E R A L E Q U I P M E N T N O T E S

A. TYPICAL EQUIPMENT PLANS SHOW EQUIPMENT AND ACCESSORIES PER EACH ROOM TYPE.

THERE ARE (12) ISOLATION ROOMS EACH WITH A MAIN ROOM, ANTE ROOM AND BATHROOM.

THERE ARE (6) CHART ALCOVES IN THE PROJECT.

B. TOTAL EQUIPMENT, FURNITURE AND ACCESSORY LIST ON SHEET QT403.

C. REFER TO SHEET GI001 FOR APPLICABLE ACCESSIBLE INSTALLATION DIMENSIONS.

D. PROVIDE BACKING FOR WALL MOUNTED EQUIPMENT/ ACCESSORIES.

4' - 0" 4' - 0" 4' - 0"

1'

1'

1'

1'

1'

1'

6'

4 1/2" 4 1/2" 4 1/2" 4 1/2" 4 1/2" 4 1/2"4 1/2" 4 1/2" 4 1/2" 4 1/2" 3"

AIR

EPDNP

EP D NP

O2

O2

VAC

VACVAC

AIR O2

O2

VAC

VAC VAC

EPDNP

EP

D

EP

D

NP EP NPEP

EPPP EP PP

4 1/2"4 1/2"4 1/2"4 1/2"4 1/2"4 1/2"4 1/2"4 1/2"4 1/2"4 1/2"3"

AIR O2 O2 AIR

SURGE MONITOR

TILTED TOWARDS

CORRIDOR

MONITOR TILTED

TOWARDS CORRIDOR

CHARTING MONITOR AND

KEYBOARD / MOUSE

DIA

BUMPER GUARD RAILS FOR WALL PROTECTION

BUMPER GUARD RAILS FOR WALL PROTECTION

BUMPER GUARD RAILS FOR WALL PROTECTION

BUMPER GUARD RAILS FOR WALL PROTECTION

RECESSED

EQUIPMENT RAIL

DOOR SIDEWINDOW SIDE

CORRIDOR

D2C3

CHART ALCOVE

D201D

F0280 F0280

M1801

M1801

A5150 A5150

ANTEROOM

D206A M3070

M3072

F2010

A5077

A5075

A5080

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

1100 Boulders Pkwy | Suite 503 Richmond, VA 23225

804.355.2067

A u to d e s k D o c s /M t H o m e

I s o la ti o n W a rd

D

/F F

E

M t H o m e

D rv t

/4 /2

:3

:1

P

M

QT401

ENLARGED EQUIPMENT PLAN

11/04/2022 ET NM

RENOVATE D-WING FOR ISOLATION

WARD

621-20-107

MOUNTAIN HOME, TENNESSEE

BID DOCUMENTS

JAMES H.

QUILLEN VA

MEDICAL

CENTER

Approved: MT Home VA

N

1/4" = 1'-0"

LARGE ANTE ROOM EQUIPMENT PLAN

N

1/4" = 1'-0"

TYPICAL ISOLATION BEDROOM EQUIPMENT PLAN

D R A W I N G N O T E S

1 BATHROOM ACCESSORIES SHOWN ON AE401.

1" = 1'-0"

TYPICAL HEADWALL

N

1/4" = 1'-0"

TYPICAL CHART ALCOVE

H E A D W A L L L E G E N D

MARK NAME COUNT

AIR MEDICAL AIR OUTLET 4

D DIGITAL COMMUNICATIONS - WALL PLATES TO INCLUDE (2) RJ45

JACKS.

DIA DIALYSIS 1

EP EMERGENCY POWER OUTLET - HOSPITAL GRADE 20A, 120 V

GROUNDED DUPLEX RECEPTACLE ON EMERGENCY POWER

CIRCUIT.

NP NORMAL POWER OUTLET - HOSPITAL GRADE 15A OR 20A, 120 V

GROUNDED DUPLEX RECEPTACLE ON NORMAL POWER CIRCUIT.

O2 OXYGEN OUTLET 6

PP PATIENT PLUG 1

VAC VACUUM OUTLET 6

N

1/4" = 1'-0"

SMALL ANTE ROOM EQUIPMENT PLAN

P N M L I HO

AE401

CLEAN

D219

LINEN

D220

SOILED

D221

OIT

D222

A5080

A5075

A1012

A5106

CT050

P2450

A5145

F3200 F0750

F0205

F2000

A1012M0506

A5145

E0078

F0110

F3200

F3200

F0280

F0280

F0280

F0280

M1855

M1840

A1015

A1015

M1820

F2000

M1801

M1801

M1801

M1801

F2000

F3050

F0275

M1801

A1015

F0205

F2000

M2055

384 SF

ISO ROOM 1

D201B

382 SF

ISO ROOM 2

D202B

382 SF

ISO ROOM 3

D203B

384 SF

ISO ROOM 4

D204B

ISO ROOM 5

D205B

ISO ROOM 9

D209B

ANTEROOM

D201A

ANTEROOM

D202A

69 SF

TOILET

D203C

ANTEROOM

D203A

ANTEROOM

D204A

ANTEROOM

D205A

TOILET

D-206C

ANTEROOM

D209A

CHART ALCOVE

D201D

CHART ALCOVE

D203D

CHART ALCOVE

D205D

EQUIPMENT

D214

ELECTRICAL

D233

NOURISHMENT

D215

HUDDLE

D216

NURSE STATION

D223

MED

D224

NURSE MANAGER

D227

LAB ALCOVE

D226

BIOMED

D235

951 SF

MECHANICAL

H.A.C.

CORRIDOR

D2C3

RESTROOM

D218

ALCOVE

D217

ALCOVE

D213

X-RAY ALCOVE

D225

CORRIDOR

D2C2

CORRIDOR

D2C1

CONSULT

D234

CORRIDOR

D2C3B

CORRIDOR

D2C3A

VESTIBULE

D236

A1014

A5075

A5077 A5082A5107

A5108

A5145

F2010

F3050

M1801

P1965

R7250

A5075A5080

F2015

K4665

R7250

R4650

M3150

E0945

1 1

X4790

M2055

M2055

F0205

F3200

A5220

A6046

F0220

F0220

F0765

A5212

M0512

F0220

F2000

AE402 21

AE4024

AE403 64

AE403

AE4033

AE403 7

AE403 2

A5077

F3200

M2055

P2000

WP101

AE4045

9' - 6" 19' - 0" 1' - 8" 22' - 4" 45' - 6" 22' - 6"

9'

AE601

G E N E R A L E Q U I P M E N T N O T E S

A. TYPICAL EQUIPMENT PLANS SHOW EQUIPMENT AND ACCESSORIES PER EACH ROOM TYPE.

THERE ARE (12) ISOLATION ROOMS EACH WITH A MAIN ROOM, ANTE ROOM AND BATHROOM.

THERE ARE (6) CHART ALCOVES IN THE PROJECT.

B. TOTAL EQUIPMENT, FURNITURE AND ACCESSORY LIST ON SHEET QT403.

C. REFER TO SHEET GI001 FOR APPLICABLE ACCESSIBLE INSTALLATION DIMENSIONS.

D. PROVIDE BACKING FOR WALL MOUNTED EQUIPMENT/ ACCESSORIES.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

1100 Boulders Pkwy | Suite 503 Richmond, VA 23225

804.355.2067

A u to d e s k D o c s /M t H o m e

I s o la ti o n W a rd

D

/F F

E

M t H o m e

D rv t

/4 /2

:3

:2

P

M

QT402

ENLARGED EQUIPMENT PLAN

11/04/2022 ET NM

RENOVATE D-WING FOR ISOLATION

WARD

621-20-107

MOUNTAIN HOME, TENNESSEE

BID DOCUMENTS

JAMES H.

QUILLEN VA

MEDICAL

CENTER

Approved: MT Home VA

N

1/4" = 1'-0"

D2 WEST EQUIPMENT PLAN

D R A W I N G N O T E S

1 ANTEROOM AND ISOLATION ROOM EQUIPMENT SHOWN ON QT401.

2 BATHROOM ACCESSORIES SHOWN ON AE401.

3 CHART ALCOVE EQUIPMENT SHOWN ON QT401.

E CD B.5 B A.5 A

30.1

32.8

AE401

AE4035

AE401

A1012

A5075

A5080

F2015

F3065

F3200

R7250

K4665

LOUNGE

D228

STAFF TOILET

D230

WOMEN'S LOCKER

D231

MEN'S LOCKER

D232

CORRIDOR

D2C3

F2000 A1030

A1080 F3200

F2000

A1030

A5020

A1080

ANTEROOM

D212A

STAIRS

S1

STORAGE

D229

F0225

F0795

F0795

F0225

F0225

F0225

A5020

A5150F3200

AE4031

10' - 0" 4' - 6" 10' - 3" 10' - 0" 10' - 0" 10' - 0"

G E N E R A L E Q U I P M E N T N O T E S

A. TYPICAL EQUIPMENT PLANS SHOW EQUIPMENT AND ACCESSORIES PER EACH ROOM TYPE.

THERE ARE (12) ISOLATION ROOMS EACH WITH A MAIN ROOM, ANTE ROOM AND BATHROOM.

THERE ARE (6) CHART ALCOVES IN THE PROJECT.

B. TOTAL EQUIPMENT, FURNITURE AND ACCESSORY LIST ON SHEET QT403.

C. REFER TO SHEET GI001 FOR APPLICABLE ACCESSIBLE INSTALLATION DIMENSIONS.

D. PROVIDE BACKING FOR WALL MOUNTED EQUIPMENT/ ACCESSORIES.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

1100 Boulders Pkwy | Suite 503 Richmond, VA 23225

804.355.2067

A u to d e s k D o c s /M t H o m e

I s o la ti o n W a rd

D

/F F

E

M t H o m e

D rv t

/4 /2

:3

:1

P

M

QT403

ENLARGED EQUIPMENT PLAN

11/04/2022 ET NM

RENOVATE D-WING FOR ISOLATION

WARD

621-20-107

MOUNTAIN HOME, TENNESSEE

BID DOCUMENTS

JAMES H.

QUILLEN VA

MEDICAL

CENTER

Approved: MT Home VA

N

1/4" = 1'-0"

D2 EAST EQUIPMENT PLAN

D R A W I N G N O T E S

1 ANTEROOM AND ISOLATION ROOM EQUIPMENT SHOWN ON QT401.

2 BATHROOM ACCESSORIES SHOWN ON AE401.

T O T A L E Q U I P M E N T A N D A C C E S S O R I E S

MARK NAME

RESPONSIBILITY

COUNTVV VC CC CV

A1012 TELEPHONE, WALL MOUNTED, 1 LINE X 3

A1014 TELEPHONE, WALL MOUNTED, 1 LINE, WITH SPEAKER X 1

A1015 TELEPHONE, DESK, MULTIPLE LINE X 3

A1030 LOCKER, 2 PERSON, OVER/UNDER X 15

A1066 MIRROR, FLOAT GLASS, WITH SS FRAME X 2

A1067 MIRROR, FLOAT GLASS, ADA ACCESSIBLE X 2

A1080 MIRROR, POSTURE, WALL MOUNTED X 2

A1205 LIFT SYSTEM, OVERHEAD, PATIENT ROOM X X 12

A5020 BENCH, LOCKER ROOM, FLOOR MOUNTED (5'-0") X 2

A5030 BENCH, STALL, SHOWER, BUILT IN X 1

A5075 DISPENSER, SOAP, DISPOSABLE X 11

A5077 DISPENSER, HAND SANITIZER, HANDS-FREE X 5

A5080 DISPENSER, PAPER TOWEL, SS, SURFACE MOUNTED X 7

A5082 DISPENSER, PAPER TOWEL, SENSOR, HANDS FREE X 4

A5090 DISPOSAL, SANITARY NAPKIN, SS, SURFACE MOUNTED X 4

A5106 WASTE DISPOSAL UNIT, SHARPS W/GLOVE DISPENSER X 1

A5107 DISPENSER, GLOVE, SURGICAL/EXAMINATION, WALL MNTD X 1

A5108 WASTE DISPOSAL UNIT, SHARPS X 2

A5109 GRAB BAR, 1-1/4" DIA., SS, 2 WALL, W/C ACCESSIBLE X 13

A5110 GRAB BAR, 1-1/4" DIA., SS, 2 WALL, SHOWER USE X 12

A5111 GRAB BAR, 1-1/4" DIA., SS, 2 WALL, W/C ACCESSIBLE (2'-0" & 3'-0") X 1

A5145 HOOK, GARMENT, DOUBLE, SS, SURFACE MOUNTED X 6

A5150 HOOK, GARMENT, TRIPLE, SURFACE MOUNTED X 17

A5175 SOAP DISH, WITH BAR, SS, RECESSED X 1

A5200 DISPENSER, TOILET TISSUE, SS, 2-ROLL, SURFACE MNTD X 4

A5205 BAR, TOWEL, 1" DIAMETER, SS, SURFACE MOUNTED X 2

A5210 BRACKET, TELEVISION, WALL MOUNTED, W/ ADJUST ARM X 1

A5212 BRACKET, TELEVISION, WALL MOUNTED X 1

A5220 BRACKET, TELEVISION, WALL BACKING X 2

A6010 BUMPER, WALL, BED LOCATOR X 13

A6046 ARTWORK, DECORATIVE WITH FRAME X 1

CT050 COUNTERTOP, STAINLESS STEEL X 1

E0078 WORKSTATION, L-SHAPED W/PENINSULA, FREE STD, 78X72 X 1

E0945 CART, COMPUTER, MOBILE X 1

F0110 BOOKCASE, 3 SHELF X 1

F0205 CHAIR, SIDE WITH ARMS X 3

F0220 CHAIR, CONFERENCE X 5

F0225 CHAIR, DINING ROOM X 8

F0260 CHAIR, HIGH BACK, PATIENT X 1

F0275 CHAIR, SWIVEL, HIGH BACK X 1

F0280 CHAIR, SWIVEL, LOW BACK X 16

F0750 OFFICE TABLE X 1

F0765 TABLE FOLDING - NESTING X 2

F0795 TABLE, DINING X 2

F2000 BASKET, WASTEPAPER, FIRE RESISTANT X 8

F2010 BASKET, WASTEPAPER, STEP-ON X 7

F2015 BASKET, WASTEPAPER, METAL/ PLASTIC, 2 SWINGING DOORS X 2

F3050 WHITEBOARD, DRY ERASE X 3

F3065 WHITEBOARD/ BULLETIN BOARD, COMBINATION X 1

F3200 CLOCK, BATTERY, 12" DIAMETER X 9

GB GRAB BAR, 1-1/4" DIA., SS, (2'-0") X 1

K4665 OVEN, MICROWAVE, CONSUMER X 2

M0506 TELEVISION, FLAT SCREEN X 1

M0512 TELEVISION, HDTV, LARGE SCREEN, 60" X 1

M0515 TELEVISION, HD, 40" CLASS X 12

M0750 FLOWMETER, AIR, CONNECT W/50 PSI SUPPLY X 50

M0755 FLOWMETER, OXYGEN, LOW FLOW X 76

M0765 REGULATOR, VACUUM X 78

M1801 COMPUTER, MICROPROCESSING, W/ FLAT PANEL MONITOR X 18

M1820 IMPRINTER, DATA RECORD, ELECTRIC X 1

M1840 PRINTER/ COPIER/ FAX COMBINATION X 1

M1855 FACSIMILE MACHINE X 1

M2055 SHELVING, STORAGE, WIRE, CRS, W/ADJUSTABLE SHELVES X 6

M3025 MATTRESS, PRESSURE REDUCTION X 1

M3070 HAMPER, LINEN, MOBILE, W/LID X 3

M3072 FRAME, INFECTIOUS WASTE BAG W/LID X 3

M3150 DISTRIBUTION SYSTEM, MEDICATION, AUTOMATIC X 1

M7010 BED, PATIENT, ELECTRIC X 12

T O T A L E Q U I P M E N T A N D A C C E S S O R I E S

MARK NAME

RESPONSIBILITY

COUNTVV VC CC CV

M7040 TABLE, OVERBED X 1

P1965 EYEWASH, EYE/FACE, SINK MOUNTED, HANDS-FREE X 1

P2000 EYEWASH, WALL MOUNTED, HANDS-FREE X 1

P2450 VALVE, MIXING, THERMOSTATIC X 1

R4650 ICE MAKER, FLAKED, WITH DISPENSER X 1

R7250 REFRIGERATOR/ FREEZER, 20 CUBIC FEET X 3

X4790 RADIOGRAPHIC UNIT, MOBILE, DIGITAL X 1

FIRE ALARM SYSTEM NOTES

1. THE BUILDING IS EQUIPPED WITH AN EXISTING SIMPLEX FIRE ALARM SYSTEM. SCOPE OF WORK INCLUDES DEMOLITION OF EXISTING DEVICES AND INSTALLATION OF NEW DEVICES AS NEEDED TO PROVIDE CODE- COMPLIANT FIRE ALARM COVERAGE TO THE AREAS DEPICTED IN THE CONTRACT DOCUMENTS. PROVIDE ALL ITEMS AND APPURTENANCES NECESSARY, REASONABLE, INCIDENTAL, OR CUSTOMARILY INCLUDED. PROVIDE ALL EQUIPMENT, MATERIALS LABOR, SUPERVISION, AND SERVICE NECESSARY SO AS TO PROVIDE A COMPLETE FUNCTIONING FIRE ALARM SYSTEM IN A SAFE WORKING ORDER. INVESTIGATE EXISTING MAINTENANCE CONTRACT

PRIOR TO STARTING WORK.

2. THE FACILITY USES THE SIMPLEX TRUESITE WORKSTATION (TSW) SOFTWARE TO MANAGE AND MONITOR THE EXISTING FIRE ALARM SYSTEM. ALL NEW DEVICES MUST BE CORRECTLY MAPPED AND INTEGRATED INTO THE TSW SYSTEM. CONTRACTOR RESPONSIBILITY TO VERIFY THAT TRANSPONDER IN ROOM E125 IS THE CORRECT

LOCATION TO MAP NEW FIRE ALARM DEVICES.

3. WALL MOUNTED, AUDIBLE NOTIFICATION DEVICES SHALL HAVE THEIR TOPS MOUNTED AT 90" MINIMUM AND 100" MAXIMUM ABOVE THE FINISHED FLOOR, AND NO CLOSER THAN 6" TO A HORIZONTAL STRUCTURE. (NFPA 72, 2016, CH. 18.4.8.1). ALL WALL MOUNTED VISUAL APPLIANCES AND COMBINATION AUDIBLE/VISUAL APPLIANCES SHALL HAVE THEIR BOTTOMS MOUNTED AT 80" MINIMUM AND 96" MAXIMUM ABOVE FINISHED FLOOR AS MEASURED TO

THE LENS. (NFPA 72, 2016, CH. 18.5.5.1)

4. ALL EQUIPMENT SHALL BE U.L. LISTED AND / OR FM APPROVED.

5. ALL FIRE ALARM WIRING SHALL BE FLP (FIRE POWER LIMITED) OR FPLP (FIRE POWER LIMITED PLENUM) AS

REQUIRED FOR APPLICATION. WIRING IN CONDUIT ABOVE GROUND MAY BE THHN OR THWN.

6. PER THE NEC, ALL WIRING IS TO BE PULLED THROUGH EACH JUNCTION BOX AND CONNECTED DIRECTLY TO EACH FIRE DEVICE. DO NOT SPLICE THE WIRE. THERE MUST BE AT LEAST 6' OF LEAD WIRE FROM THE BOX TO THE DEVICE. ALL BOXES TO BE SIZED PER NEC AND SHALL HAVE THEIR COVERS PAINTED RED WHERE

APPLICABLE.

7. DO NOT DEVIATE FROM CONDUIT RUNS AS SHOWN ON FLOOR PLANS WITHOUT PRIOR APPROVAL FROM ELECTRICAL ENGINEER. FACTORS SUCH AS EXCESSIVE VOLTAGE DROP, ADDITIONAL PARTS, ENGINEERING, ETC., THAT ARE A RESULT OF CONDUIT RUN DEVIATIONS SHALL BE THE SOLE RESPONSIBILITY OF THE ELECTRICAL

CONTRACTOR.

8. ALL FAN SHUTDOWN FUNCTIONS, DAMPER CLOSURES AND ASSOCIATED MECHANICAL SYSTEM FIRE ALARM

INTERFACE SHALL BE BY MECHANICAL CONTRACTOR, AND SHALL BE COORDINATED WITH FIRE

ALARM SYSTEM.

9. ALL DUCT SMOKE DETECTORS SHALL BE MOUNTED BY THE MECHANICAL CONTRACTOR. DUCT SMOKE DETECTORS

EXPOSED TO THE WEATHER SHALL BE UL LISTED FOR OUTDOOR INSTALLATION, AND WEATHER

PROTECTED BY THE MECHANICAL CONTRACTOR. ALL AIR VELOCITY TESTING SHALL BE PERFORMED BY THE

MECHANICAL CONTRACTOR.

10. ALL FIRE ALARM DEVICE BACKBOXES, FIRE ALARM TERMINAL CABINETS, GUTTERS, JUNCTION BOXES AND ASSOCIATED CONDUITS SHALL BE FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR UNLESS OTHERWISE NOTED. REFER TO FIRE ALARM SYMBOL LIST AND/OR MOUNTING DETAILS FOR ADDITIONAL

INFORMATION. SYSTEM SUPPLIER PROVIDED BACKBOXES SHALL BE INSTALLED BY ELECTRICAL

CONTRACTOR UNLESS OTHERWISE NOTED.

11. SMOKE DETECTOR TESTING SHALL BE PERFORMED TO ENSURE THAT EACH DETECTOR IS WITHIN ITS LISTED AND

MARKED SENSITIVITY RANGE USING THE METHODS RECOMMENDED PER CFC 907.8.4 AND

NFPA 72, 2016 14.4.4.3.4.

12. ALL WIRING, INITIATING DEVICES AND ANNUNCIATOR PANEL SHALL BE SUPERVISED TO THE PRINCIPAL POINT OF ANNUNCIATION. THE FIRE ALARM CONTROL PANEL TO SUPERVISE THE ANNUNCIATOR PANEL, ALL

INITIATING AND INDICATING DEVICE CIRCUITS.

A. INITIATING DEVICE CIRCUITS (IDC): CLASS B

B. SIGNALING LINE CIRCUITS (SLC): CLASS B

C. NOTIFICATION APPLICANCE CIRCUITS (NAC): CLASS B

13. ALL WIRING SHALL BE CUT FOR IN AND OUT. WIRING SHALL NOT BE LOOPED THROUGH DEVICES.

14. POINT AND COMMON ANNUNCIATION AND T-TAPPING ARE PROHIBITED. (T-TAPPING IS ALLOWABLE ON SLC LOOPS).

15. CONTRACTOR TO FIELD VERIFY AND PROVIDE DECIBEL METER FOR TESTING OF AMBIENT NOISE LEVELS AUDIBLE DEVICES TO BE AT LEAST 15 DBA ABOVE THE AVERAGE AMBIENT SOUND LEVEL BUT NOT LESS THAN 75 DBA AT 10 FEET OR MORE THAN 110 DBA AT THE MINIMUM HEARING DISTANCE. SOUND LEVEL SHALL BE MAINTAINED FOR DURATION OF AT LEAST 60 SECONDS; 5 DBA MUST BE MAINTAINED.) (IFC 907.5.2.1.1) THE CONTRACTOR SHALL ADJUST/INSTALL ALL DEVICES TO MAXIMIZE PERFORMANCE AND TO MINIMIZE FALSE ALARMS. PROVIDE UPDATED PLANS AND CALCULATIONS THROUGH THE "CHANGE ORDER" PROCESS WHEN INSTALLING ADDITIONAL DEVICES. 15 DBA ABOVE THE AVERAGE AMBIENT SOUND LEVEL BUT NOT LESS THAN 75 DBA AT 10 FEET OR MORE THAN 110 DBA AT THE MINIMUM HEARING DISTANCE. SOUND LEVEL SHALL BE MAINTAINED FOR DURATION OF AT LEAST 60 SECONDS; 5 DBA MUST BE MAINTAINED.) (IFC 907.5.2.1.1) THE CONTRACTOR SHALL ADJUST/INSTALL ALL DEVICES TO MAXIMIZE PERFORMANCE AND TO MINIMIZE FALSE ALARMS. PROVIDE UPDATED PLANS AND CALCULATIONS

THROUGH THE "CHANGE ORDER" PROCESS WHEN INSTALLING ADDITIONAL DEVICES.

16. VISUAL DEVICES SHOULD NOT EXCEED 2 FLASHES PER SECOND AND SHOULD NOT BE SLOWER THAN 1 FLASH EVERY SECOND. THE DEVICE SHALL HAVE A PULSING LIGHT SOURCE NOT LESS THAN 15-CANDELA. VISUAL

DEVICES WITHIN 55' FROM EACH OTHER SHALL BE SYNCHRONIZED.

17. ALL FIRE ALARM CIRCUITS SHALL BE IN CONDUIT, APPROVED SURFACE RACEWAY OR OPEN RUN ABOVE CEILINGS, UNDER FLOORS AND IN WALLS IN A NEAT AND PROTECTED MANNER AS INDICATED ON THE DESIGN DOCUMENTS.

EXPOSED CIRCUITS ARE ONLY PERMITTED WHEN NOTED AS EXPOSED ON DESIGN DOCUMENTS. ALL CONDUITS

SHALL BE 3/4" MINIMUM. CONTRACTOR TO VERIFY CONDUIT FILL PRIOR TO INSTALLATION.

18. ALL FLOW SWITCHES SHALL BE 2 WIRE WITH NON-ELECTRONIC RETARD TYPE SIMILAR TO THE SYSTEM SENSOR

MODEL "WFD SERIES" ONLY.

19. ALL DEVICES IN THE ALARM SYSTEM SHALL BE COMPATIBLE WITH EXISTING SIMPLEX ES 4100 PANEL AND

INSTALLED PER MANUFACTURER'S SPECIFICATIONS.

20. NEW FIRE ALARM DEVICES SHALL BE FURNISHED AND INSTALLED BY AN AUTHORIZED DISTRIBUTOR.

21. FIRE ALARM SYSTEM INSTALLATION COMPANY SHALL BE UL LISTED (UUJS).

22. FIRE ALARM PANEL, REMOTES, AND COMPONENTS SHALL BE SECURED TO MOUNTING SURFACES PER MANUFACTURER'S SPECIFICATIONS. NO SINGLE DEVICE SHALL EXCEED THE WEIGHT OF 20 LBS. WITHOUT SPECIAL

MOUNTING DETAILS.

23. SMOKE DETECTOR SHALL NOT BE ANY CLOSER THAN 1 FOOT FROM FIRE SPRINKLERS OR 3 FEET FROM ANY SUPPLY DIFFUSER. IN THE AREA OF CONSTRUCTION OR WHERE POSSIBLE DAMAGE/CONTANMINAION COULD OCCUR ON NEWLY INSTALLED FIRE ALARM DEVICES, DEVICES SHALL BE COVERED UNTIL THAT AREA IS READY TO BE TURNED OVER TO THE OWNER. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH CHAPTER 7. CLEANING OR REPLACEMENT OF DEVICES THAT WERE MOUNTED AT THE REQUEST OF THE CONTRACTOR WILL NOT BE PERFORMED WITHOUT WRITTEN AUTHORIZATION THAT ASSUMES FINANCIAL RESPONSIBILITY FOR COSTS INCURRED. TESTING OF

DETECTORS SHALL BE PERFORMED PER NFPA 72 2016 14.4.5.3 AND CFC 907.9.4.

24. PER BEST PRACTICES ACTIVATION OF INITIATING DEVICE SHALL NOT REQUIRE MORE THAN 5 LBS. (22.2N) OF

FORCE OR REQUIRE TIGHT GRASPING PINCHING, OR TWISTING OF WRIST.

25. WHERE A DETECTOR IS INSTALLED ABOVE THE CEILING, THE DETECTOR SHALL BE EASILY ACCESSIBLE AND THE LOCATION OF THE DETECTOR SHALL BE CLEARLY MARKED. FOR DUCT SMOKE DETECTORS A REMOTE TEST STATION SHALL BE PROVIDED. ELECTRICAL CONTRACTOR SHALL FURNISH ACCESS PANELS TO AREAS THAT

REQUIRE SERVICING, TROUBLE SHOOTING, ETC.

26. THE "END OF LINE RESISTANCE" OF EACH CIRCUIT SHALL BE TESTED IN THE PRESENCE OF THE I.O.R. AND SHALL

NOT EXCEED THE LISTED MANUFACTURER'S MINIMUM OPERATING VOLTAGE.

27. FIRE ALARM SYSTEM IS A FULLY AUTOMATIC SYSTEM. CONTRACTOR TO UTILIZE AREA COVERAGE SMOKE DETECTORS AND ADDRESSABLE CONTROL RELAYS FOR THE SHUTDOWN AND/OR CLOSURE OF HVAC UNITS AND COMBINATION SMOKE/FIRE DAMPERS. CONTROL RELAYS TO BE LOCATED WITHIN 3FT OF THE CONTROLLED

CIRCUIT OR APPLIANCE PER NFPA 72 SECTION 21.2.4.

28. PROVIDE APPROPRIATE MANUFACTURER PRODUCT DATA SHEETS FOR ALL SUBSTITUTED MANUFACTURER'S

MATERIAL, EQUIPMENT OR APPLIANCES, TO AHJ PRIOR TO START OF INSTALLATION.

29. CONTRACTOR SHALL PROVIDE FIRE WATCH FOR ALL OCCUPIED AREAS OF WORK WHERE THE REQUIRED FIRE ALARM SYSTEM IS OUT OF SERVICE FOR THE DURATION OF THE SYSTEM OUTAGE. FIRE WATCH AND

SYSTEM/EQUIPMENT SHALL BE PER 2012 IFC 901.7.

30. CARBON MONOXIDE DETECTORS SHALL BE EQUIPPED WITH A COMPATIBLE SOUNDER BASE. UPON DETECTION THE AUDIBLE CARBON MONOXIDE SENSING DETECTORS SHALL PRODUCE A FOUR-PULSE TEMPORAL PATTERN SIGNAL

WITHIN THE IMMEDIATE AREA AND COMPLY WITH NFPA 720 5.8.6.5.

31. ALL MEMBRANE AND THROUGH-PENETRATIONS OF RATED ASSEMBLIES SHALL BE PROTECTED BY AN APPROVED FIRE STOP SYSTEM AS IDENTIFIED IN IBC CHAPTER 7, UL OR OTHER LAB TESTING CRITERIA. APPROVED TYPES OF MATERIALS SHALL BE IDENTIFIED WITHIN THE FIRE ALARM SECTION OF THE PROJECT SPECIFICATIONS.

32. CONTROL PANELS AND REMOTE ANNUNCIATORS SHALL BE INSTALLED WITH THEIR BOTTOMS MOUNTED AT 48"

ABOVE THE FINISHED FLOOR.

33. EXISTING FIRE ALARM SYSTEM SEQUENCE OF OPERATION IS NOT TO BE MODIFIED. ALL NEW FIRE ALARM DEVICES

SHALL OPERATE IN ACCORDANCE WITH EXISTING SEQUENCE OF OPERATIONS.

34. SMOKE DETECTION IS NOT REQUIRED THROUGHOUT THE CORRIDOR DUE TO THE INSTALLATION OF THE

AUTOMATIC SPRINKLER SYSTEM (NFPA 101 SECTION 19.3.4.5.1).

35. SMOKE DETECTION IS REQUIRED IN ALL SPACES THAT OPEN TO THE CORRIDOR (NFPA 101 SECTION 19.3.6.1(7)).

36. THE WORK AREA IS UTILIZING A PRIVATE MODE SIGNALING STRATEGY, RESULTING IN NOTIFICATION NOT BEING PROIVDED THROUGHOUT PATIENT ROOMS. NOTIFICATION SHALL BE PROVIDED AT THE NURSE'S STATIONS.

SYMBOL

ALL SYMBOLS SHOWN MAY NOT APPEAR IN ALL DRAWINGS. SYMBOLS ARE SHOWN SCHEMATIC AND MAY NOT BE TO SCALE.

FIRE ALARM SYMBOLS LEGEND

DESCRIPTION

WATER FLOW SWITCHWF

VALVE SUPERVISORY SWITCHVS

PRESSURE SWITCHPS

SMOKE DETECTOR WALL MOUNTED

SMOKE DETECTOR CEILING MOUNTED

HIGH/LOW PRESSURE SUPERVISORY

DUCT SMOKE DETECTOR

FACP

DH

HEAT DETECTOR WALL MOUNTED

HEAT DETECTOR CEILING MOUNTED

ELECTRO-MAGNETIC DOOR HOLDER

FIRE ALARM BELL

FIRE ALARM CONTROL PANEL

ANN FIRE ALARM ANNUNCIATOR PANEL

FPAP FIRE PUMP ANNUNCIATOR PANEL

FSCS FIREFIGHTER'S SMOKE CONTROL STATION

FAPS

FIRE ALARM POWER SUPPLY FOUR CIRCUIT FIRE ALARM NOTIFICATION APPLIANCE POWER

EXTENDER

H/L

FIRE ALARM PULL STATION WALL MOUNTEDF

FIRE ALARM AUDIBLE VISUAL SIGNAL TYPICAL CEILING MOUNT, W = WALL MOUNT, 'X' DENOTES CANDELA

RATINGX

FIRE ALARM AUDIBLE SIGNAL TYPICAL CEILING MOUNT, W = WALL MOUNT, 'X' DENOTES CANDELA RATING X

FIRE ALARM VISUAL SIGNAL TYPICAL CEILING MOUNT, W = WALL MOUNT - 15CD UNLESS NOTED OTHERWISE

EVAC EMERGENCY VOICE/ALARM COMMUNICATION PANEL

CONDUIT RISER UP TO ABOVE

CONDUIT RISER UP AND DOWN

CONDUIT RISER DOWN TO BELOW

WP WEATHER PROOF

AIM

AOM

ADDRESSABLE INPUT MODULE

ADDRESSABLE OUTPUT MODULE

ETD EMERGENCY MESSAGE TEXTUAL DISPLAY

AMP FIRE ALARM AMPLIFIER

ETR EXISTING TO REMAIN

ABBREVIATIONS

A ALPHA-NUMERIC

ACT ACOUSTICAL CEILING TILE

AFF ABOVE FINISHED FLOOR

AHU AIR HANDLING UNIT

EQL END OF LINE DEVICE

FA FIRE ALARM

FAA FIRE ALARM ANNUNCIATOR PANEL

FAC FIRE ALARM COMMUNICATOR

FACP FIRE ALARM CONTROL PANEL

FSA FIRE SYSTEM ANNUNCIATOR

FTR FIRE ALARM TRANSMITTER

G GRAPHIC

HVAC HEATING, VENTILATION AND AIR CONDITIONING

MIN MINIMUM

N.C. NORMALLY CLOSED (CONTACT)

N.O. NORMALLY OPEN (CONTACT)

NAC NOTIFICATION APPLIANCE CIRCUIT

NIC NOT IN CONTRACT

NTS NOT TO SCALE

POC POINT OF CONNECTION

RA RETURN AIR (HVAC)

RTU ROOF TOP UNIT

SA SUPPLY AIR (HVAC)

SLC SIGNALING LINE CIRCUIT

TYP TYPICAL

UON UNLESS OTHERWISE NOTED

WP WEATHER PROOF

MAX MAXIMUM

CONVENTIONS

A

E-3

C

E-5

FIRE ALARM EQUIPMENT DENOTED BY DASHED,

HEAVY LINEWEIGHT SHALL BE DISPOSED OF,

UNLESS INDICATED TO BE REUSED OR TURNED

OVER TO THE OWNER

SECTION DESIGNATION - LETTER DENOTES SECTION

IDENTIFICATION

INDICATES DRAWING NUMBER WHERE SECTION IS DRAWN

DETAIL DESIGNATION - LETTER DENOTES DETAIL

IDENTIFICATION

INDICATES DRAWING NUMBER WHERE DETAIL IS DRAWN

UNLESS INDICATED OTHERWISE

LINEWEIGHT INDICATES EXISTING TO REMAIN,

FIRE ALARM EQUIPMENT DENOTED BY LIGHT, SOLID

FIRE ALARM EQUIPMENT DENOTED BY HEAVY,

SOLID LINEWEIGHT SHALL BE NEW WORK

PROVIDED BY CONTRACTOR

EXIT

80" MIN. TO

96"

MAX. (STROBE

LENS TO

FLOOR)

- OR 6" BELOW

FINISHED

CEILING

WHICHEVER

IS

LOWER

SPEAKER/STROBE

COMBINATION DEVICE

STROBE DEVICE

SPEAKER DEVICE

90" (TOP

OF DEVICE

TO

FLOOR) - OR

6" BELOW

FINISHED

CEILING

WHICHEVER

IS

LOWER

0' - 4" MINIMUM

SMOKE / HEAT

DETECTOR

1' - 0" MAXIMUM

AIR SUPPLY DIFFUSER OR

RETURN AIR OPENING

3' - 0" MINIMUM0' - 4" MINIMUM

ANNUNCIATOR

PANEL OR

TERMINAL

CABINET

FINISHED

FLOOR

SUSPENDED

CEILING

INSTALL PER NATIONAL ELECTRIC CODE

CONDUIT

FLEXIBLE RACEWAY TO SUSPENDED

CEILING MOUNTED DEVICE -

MAX.LENGTH OF 6' - 0"

MOUNT ON AN

APPROVED BOX

SMOKE / HEAT

DETECTOR

JUNCTION BOX

MANUAL PULL STATION

5' - 0" MAXIMUM

FROM EXIT OPENING 42" MIN. TO

48"

MAX.

(OPERATING

HANDLE TO

FLOOR)

5' - 6"

FIRE ALARM

CONTROL PANEL

OR EMERGENCY

VOICE PANEL

MOUNT AUDIBLE

AND

VISUAL DEVICES ON

APPROVED BOXES

FLOOR-

CEILING

ASSEMBLY

REMOTE LAMP W/

TEST SWITCH

60" MIN. TO

78" MAX.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

1100 Boulders Pkwy | Suite 503 Richmond, VA 23225

804.355.2067

A u to d e s k D o c s /M t H o m e

I s o la ti o n W a rd

D /W

S P

M t H o m e

D rv t

/7 /2

:5

:1

A

M

FA1.00

FIRE ALARM LEGEND AND NOTES

11/04/2022 TGS DM

RENOVATE D-WING FOR ISOLATION

WARD

621-20-107

MOUNTAIN HOME, TENNESSEE

BID DOCUMENTSJAMES H.

QUILLEN VA

MEDICAL

CENTER

Approved: Owner

NTS

FIRE ALARM DEVICE MOUNTING DETAIL

No. Revisions: Date:

1 BID DOCUMENTS 11/04/2022

11/04/2022

F

F

F

F

F

CORRIDOR

C6

CORRIDOR

D2C5

CORRIDOR

D2C4B

CORRIDOR

D2C4B

CORRIDOR

D2-C4A

CORRIDOR

D2C2

ELEVATOR LOBBY

D2EL2

29A-C

30.1

32.8

P O N M L K I H G F E D C B.5 B A.5 A

NOT IN SCOPE

ETR

ETR

ETR

OFFICE

D201B

TOILET

D201A

OFFICE

D201C

CONF. ROOM

D202

OFFICE

D202A

OFFICE

D202B

OFFICE

D202C

STAIR

WORKROOM

D203

WORKROOM

D205

TOILET

D205A

OFFICE

D207B

OFFICE

D209C

OFFICE

D209B

TOILET

D209A

OFFICE

D211B

OFFICE

D211C

OFFICE

D213C

OFFICE

D213B

TOILET

D213A

CONFERENCE AREA

D217A

ON-CALL ROOM

D215

OFFICE

D217

ELEC.

D256

TELE

D254

OFFICE

D253

OFFICE

D251

OFFICE

D249

OFFICE

D258OFFICE

D260

OFFICE

D262

OFFICE

D230

OFFICE

D228

OFFICE

D225

TOILET

D226

OFFICE

D223

OFFICE

D221

OFFICE

D219

ELEV LOBBY

CONFERENCE

D227

RECYCLING

D228A

WORKROOM

D222A

WORKROOM

D222B

SHARED SPACE

D222

TOILET

D222C

TOILET

D220A

WORKROOM

D220

WORKROOM

D218

TOILET

D218A

TOILET

D216A

WORKROOM

D216

OFFICE

D214

OFFICE

D212

TOILET

D214A

OFFICE

D210

OFFICE

D208

TOILET

D210A

OFFICE

D206

OFFICE

D204

TOILET

D206A

CORRIDOR

CORRIDOR

C2

STORAGE

D224

PHLEBOTOMY

D224A

MECH

D224

ELEV

E1

ELEV.

E2

CORRIDOR

CORRIDOR

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

G E N E R A L P L A N N O T E S

KEYPLAN

1100 Boulders Pkwy | Suite 503 Richmond, VA 23225

804.355.2067

A u to d e s k D o c s /M t H o m e

I s o la ti o n W a rd

D /W

S P

M t H o m e

D rv t

/7 /2

:5

:0

A

M

FAD2.02

SECOND FLOOR FIRE ALARM

DEMOLITION PLAN

11/04/2022 TGS DM

RENOVATE D-WING FOR ISOLATION

WARD

621-20-107

MOUNTAIN HOME, TENNESSEE

BID DOCUMENTSJAMES H.

QUILLEN VA

MEDICAL

CENTER

Approved: Owner

N

1/8" = 1'-0"

SECOND FLOOR FIRE ALARM DEMOLITION PLAN

D R A W I N G N O T E S :

A. INFORMATION SHOWN IS DIAGRAMMATIC AND IS NOT INTENDED TO SHOW EVERY PIECE OF EXISTING

OR NEW EQUIPMENT.

B. DEMOLISH FIRE ALARM DEVICES IN COORDINATION WITH FINAL ARCHITECURAL LAYOUT.

C. REFER TO SHEET FA1.00 FOR ADDITIONAL INFORMATION.

No. Revisions: Date:

15CD

15CD

75CD

15CD

15CD

15CD

15CD

15CD

15CD

15CD

D H

FS TS

F

F

D H

F

15CD

29A-C

30.1

32.8

P O N M L K I H G F E D C B.5 B A.5 A

FIRE ALARM ZONE

ISO ROOM 1

D201B

ISO ROOM 2

D202B

ISO ROOM 3

D203B

ISO ROOM 4

D204B

ISO ROOM 5

D205B

ISO ROOM 6

D206B

ISO ROOM 7

D207B

ISO ROOM 8

D208B

ISO ROOM 9

D209B

ISO ROOM 10

D210B

ISO ROOM 11

D211B

ISO ROOM 12

D212B

TOILET

D201C

ANTEROOM

D201A

TOILET

D202C

ANTEROOM

D202A

TOILET

D204C

TOILET

D203C

ANTEROOM

D203A

ANTEROOM

D204A

ANTEROOM

D205A

TOILET

D205C

TOILET

D-206C

ANTEROOM

D206A

ANTEROOM

D207A

TOILET

D208C

TOILET

D207C

ANTEROOM

D208A

ANTEROOM

D209A

TOILET

D210C

TOILET

D209C

ANTEROOM

D210A

ANTEROOM

D211A

TOILET

D212C

TOILET

D211C

ANTEROOM

D212A

CHART ALCOVE

D201D

CHART ALCOVE

D203D

CHART ALCOVE

D205D

CHART ALCOVE

D207D

CHART ALCOVE

D209D

CHART ALCOVE

D211D

EQUIPMENT

D214

ELECTRICAL

D233

NOURISHMENT

D215

HUDDLE

D216

CLEAN

D219

LINEN

D220 SOILED

D221

NURSE STATION

D223

OIT

D222

MED

D224

NURSE MANAGER

D227

LAB ALCOVE

D226

BIOMED

D235

MECHANICAL

H.A.C.

STAIRS

S1

STAFF TOILET

D230

LOUNGE

D228

CORRIDOR

D2C3

RESTROOM

D218

ALCOVE

D217ALCOVE

D213

WOMEN'S LOCKER

D231

MEN'S LOCKER

D232

STORAGE

D229X-RAY ALCOVE

D225

CORRIDOR

D2C5

CORRIDOR

C6

CORRIDOR

D2C4B

CORRIDOR

D2C2

CORRIDOR

D2C1

CONSULT

D234

CORRIDOR

D2C3B

CORRIDOR

D2C3A

VESTIBULE

D236

NOT IN SCOPE

ETR

ETR

ETR

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

G E N E R A L P L A N N O T E S

KEYPLAN

1100 Boulders Pkwy | Suite 503 Richmond, VA 23225

804.355.2067

A u to d e s k D o c s /M t H o m e

I s o la ti o n W a rd

D /W

S P

M t H o m e

D rv t

/7 /2

:5

:5

A

M

FA2.02

SECOND FLOOR FIRE ALARM NEW

WORK PLAN

11/04/2022 TGS DM

RENOVATE D-WING FOR ISOLATION

WARD

621-20-107

MOUNTAIN HOME, TENNESSEE

BID DOCUMENTSJAMES H.

QUILLEN VA

MEDICAL

CENTER

Approved: Owner

N

1/8" = 1'-0"

SECOND FLOOR FIRE ALARM NEW WORK PLAN

A. INFORMATION SHOWN IS DIAGRAMMATIC AND IS NOT INTENDED TO SHOW EVERY PIECE OF EXISTING OR NEW EQUIPMENT.

B. PROVIDE FIRE ALARM COVERAGE IN RENOVATED AREAS IN ACCORDANCE WITH NFPA 72. PROVIDE FULL COVERAGE AND

SYNCHRONIZATION OF DEVICES FOR FINISHED ARCHITECTURAL LAYOUT.

C. FIRE ALARM AND SPRINKLER ZONES SHALL COINCIDE WITH SMOKE COMPARTMENTS. REFER TO LIFE SAFETY SHEETS TO COORDINATE

SMOKE COMPARTMENT BOUNDARIES.

D. FINAL LOCATION AND QUANTITY OF NAC PANEL(S) SHALL BE DETERMINED BY POWER LOSS CALCULATIONS AS DETERMINED BY THE

CONTRACTOR.

E. PRIVATE MODE SIGNALING IS IMPLEMENTED IN PATIENT AREAS.

F. REFER TO SHEET FA1.00 FOR ADDITIONAL INFORMATION.

D R A W I N G N O T E S :

1. DOOR HOLDERS TO RELEASE UPON ACTIVATION OF ADJACENT SMOKE DETECTORS.

2. EXISTING SMOKE DETECTORS TO BE REINSTALLED CENTER OF CEILING TILE. REPLACE WITH NEW DEVICE IF NECESSARY.

No. Revisions: Date:

FIRE PROTECTION NOTES

1. BEFORE SUBMITTING A PROPOSAL FOR THE WORK, EACH BIDDER WILL

BE HELD RESPONSIBLE TO HAVE EXAMINED THE EXISTING SITE

CONDITIONS FOR THE WORK INCLUDED UNDER THIS CONTRACT. NO

ALLOWANCE WILL BE MADE SUBSEQUENTLY IN THIS CONNECTION ON

BEHALF OF THE CONTRACTOR FOR ANY ERROR OR NEGLIGENCE ON

THEIR PART.

2. FIRE PROTECTION CONTRACTOR SHALL BE RESPONSIBLE FOR THE

DEVELOPMENT AND SUBMITTING OF SHOP DRAWINGS.

3. DESIGN AND INSTALLATION SHALL BE SUBJECT TO FINAL INSPECTION

AND APPROVAL.

4. THE FIRE PROTECTION CONTRACTOR IS RESPONSIBLE FOR ALL

CUTTING, SEALING, PATCHING, AND PAINTING REQUIRED FOR

INSTALLATION OF THE STANDPIPE SYSTEM. ALL PENETRATIONS OF FIRE-

RATED ASSEMBLIES SHALL BE FIRE STOPPED WITH AN

APPROVED/LISTED FIRE STOPPING METHOD AS PRESCRIBED IN THE

TENNESSEE BUILDING CODE.

5. THE FIRE PROTECTION CONTRACTOR SHALL COMPLETE AND SIGN

CONTRACTOR’S MATERIAL AND TEST CERTIFICATE FOR THE ABOVE AND

UNDERGROUND PIPING AS WELL AS ANY EQUIPMENT. THE FORMS SHALL

BE GIVEN TO THE PROJECT INSPECTOR WHO WILL FORWARD TO AHJ

FOR FILLING IN PROJECT RECORDS. A COPY OF THIS CERTIFICATE SHALL

BE PROVIDED TO THE OWNER.

6. CONTRACTOR SHALL MAINTAIN A CLEAN WORK PREMISE AT ALL TIMES

AND SHALL CLEAN CONSTRUCTION SITE OF ALL THEIR DEBRIS AT THE

END OF THE DAY AND BEFORE FINAL PAYMENT IS MADE.

7. THE BUILDING IS ASSUMED TO BE STRUCTURALLY SOUND AND FULLY

CAPABLE OF SUPPORTING THE PROPOSED SPRINKLER PIPING AND ALL

ASSOCIATED FITTINGS, HANGERS, SEISMIC BRACING AND ASSOCIATED

APPURTENANCES.

8. REFER TO FIRE PROTECTION SPECIFICATIONS FOR ADDITIONAL

INFORMATION REGARDING THE FIRE PROTECTION SYSTEM.

9. REFER TO ARCHITECTURAL DRAWINGS FOR ACTUAL BUILDING

DIMENSIONS AND DETAILS. DO NOT SCALE “FP” DRAWINGS FOR

CONSTRUCTION PURPOSES.

10. OWNER SHALL BE PROVIDED WITH ALL REQUIRED TEST CERTIFICATES,

CARE & MAINTENANCE BOOK.

11. ALL MATERIALS, EQUIPMENT, APPURTENANCE AND RELATED DEVICES

SHALL BE APPROVED FOR FIRE PROTECTION USE AND BE UL LISTED

AND/OR FM APPROVED.

12. ALL WELDING SHALL BE DONE BY CERTIFIED WELDERS.

13. INSTALL ALL EQUIPMENT AND SPECIALTY DEVICES IN ACCORDANCE WITH

MANUFACTURER’S INSTRUCTIONS.

14. ALL PIPE SHALL BE BLACK STEEL SCHEDULE 40 UNLESS NOTED IN

DESIGN DRAWINGS.

15. FLOOR/ WALL PENETRATIONS THROUGH RATED SEPARATIONS SHALL BE

SEALED WITH AN APPROVED FIRE RATED MATERIAL AND/OR APPROVED

ASSEMBLY.

16. WALL PENETRATIONS THROUGH NON-RATED PARTITIONS SHALL BE

PROVIDED WITH A NON-SHRINKING GROUT OR CAULKING MATERIAL

AND/OR APPROVED ASSEMBLY.

17. JOINING OF PIPE AND FITTINGS SHALL BE DONE WITH GROOVED

COUPLINGS WHEN LIGHTWALL PIPE IS USED OR THREADED CAST IRON

OR DUCTILE IRON FITTINGS WITH THREADABLE PIPE.

18. SIGNAGE SHALL BE PROVIDED IN ACCORDANCE WITH AHJ AND NFPA 13.

19. THE SPRINKLER SYSTEM SHALL BE SUPERVISED BY THE EXISTING FIRE

ALARM SYSTEM. ALL TAMPER AND WATER FLOW SWITCHES SHALL BE

INSTALLED BY THE FIRE PROTECTION CONTRACTOR AND WIRED TO THE

EXISTING FIRE ALARM CONTROL PANEL BY THE FIRE ALARM

CONTRACTOR.

20. THE SPRINKLER SYSTEM SHALL BE HYDRAULICALLY TESTED IN

ACCORDANCE WITH NFPA 13. PRIOR TO CONNECTION TO THE ABOVE

GROUND SYSTEM, THE UNDERGROUND FIRE WATER SERVICE SHALL BE

FLUSHED IN ACCORDANCE WITH NFPA 13.

21. ALL SPRINKLER LOCATIONS SHALL BE COORDINATED WITH LIGHTING

FIXTURES, HVAC DIFFUSERS, FIRE ALARM DEVICES, SIGNS, AND OTHER

RELATED CEILING DEVICES PRIOR TO CONSTRUCTION. THE SPRINKLER

PIPE ROUTING SHALL ALSO BE COORDINATED WITH STRUCTURAL AND

OTHER DISCIPLINES PRIOR TO CONSTRUCTION TO ELIMINATE OR

MINIMIZE THE NUMBER OF LOW POINT DRAINS FOR THE SPRINKLER

SYSTEM.

22. ALL INSPECTOR’S TEST CONNECTION AND LOW POINT DRAINS SHALL BE

IN ACCORDANCE WITH NFPA 13 (UNLESS OTHERWISE NOTED) AND SHALL

BE DISPLAYED ON SHOP DRAWINGS. ALL PIPING RELATED SHALL BE

LOCATED TIGHT AGAINST THE PERIMETER WALLS. COORDINATE WITH

ARCHITECT FOR ACCEPTABLE LOCATIONS.

23. MOUNTING OF CONTROL VALVES SHALL BE AT MAXIMUM HEIGHT OF 7’-0”

A.F.F. UNLESS OTHERWISE NOTED WHICH WILL REQUIRE APPROVED

MEANS OF ACCESSIBILITY.

24. IN ACCORDANCE WITH THE PROJECTS NOTED CODES AND STANDARDS,

WHERE A WATERFLOW TEST IS USED FOR THE PURPOSE OF SYSTEM

DESIGN, THE TEST SHALL BE CONDUCTED NO MORE THAN 6 MONTHS

PRIOR TO WORKING PLAN SUBMITTAL UNLESS OTHERWISE APPROVED

BY THE AHJ.

25. WATER SUPPLY INFO USED IN DESIGN (DATED 7/13/2021):

STATIC: 115 PSI

RESIDUAL: 55 PSI

FLOW RATE: 1250 GPM

26. REMOTE AREA CALCULATION (WITH 5 PSI WATER SUPPLY DOWNGRADE)

FLOW RATE: 541 GPM

PRESSURE: 61 PSI

SAFETY MARGIN: 27 PSI

NAS NO AUTOMATIC SPRINKLERS

OFI

RN

S.F.

SPR

PSI

NTS

OFCI

NO

NC

NIC

INV

OWNER FURNISHED AND INSTALLED

POUNDS PER SQUARE INCH

RISER NIPPLE

SQUARE FEET

SPRINKLER

OWNER FURNISHED AND CONTRACTOR INSTALLED

NOT IN CONTRACT

NOT TO SCALE

NORMALLY CLOSED

NORMALLY OPEN

INVERT OF PIPE ELEVATION

GPM

GC

FLR

FFE

ELL

EL

DWG

AFF

CONT.

CONTR.

CLG

AFC

CONN

AP

FIRE PROTECTION CONTRACTOR

FINISHED FLOOR ELEVATION

GALLONS PER MINUTE

GENERAL CONTRACTOR

FLOOR

ELEVATION

ELBOW

DRAWING

ABOVE FINISHED FLOOR

ABOVE FINISHED CEILING

CONTINUATION

CONTRACTOR

CEILING

CONNECTION

ACCESS PANEL

ACOUSTICAL TILE CEILINGATC

ABBREVIATIONS

FPCR

FCC

FLOOR CONTROL VALVE ASSEMBLY

DN DOWN

TOP

WTS

TYP

TS

TOP OF PIPE ELEVATION

TAMPER / SUPERVISORY SWITCH

WATER TIGHT SLEEVE

TYPICAL

SYMBOL LEGEND

FS

PS

FSP

PRESSURE GAUGE

PRESSURE SWITCH

FLOW SWITCH

PIPING UP OR DN THROUGH FLOOR SLAB

PIPING RISE OR DROP NOT THROUGH FLOOR SLAB

SHUTOFF VALVE

CHECK VALVE WITH BALL DRIP

SHUTOFF VALVE WITH TAMPER SWITCH

FIRE STANDPIPE PIPING

EXISTING TO REMAIN (GENERAL)

EXISTING PIPING TO BE REMOVED (GENERAL)

CONNECT TO EXISTING PIPING (GENERAL)

NEW PIPING (GENERAL)

SWING CHECK VALVE

CUT AND CAP EXISTING PIPING (GENERAL)

CONTINUATION

PIPING LEGEND

SECTION DESIGNATION

DETAIL / SCHEMATIC DESIGNATION

SPRINKLER HYDRAULIC NODE TAG

UPRIGHT SPRINKLER HEAD

HORIZONTAL SIDEWALL SPRINKLER HEAD

CONCEALED PENDENT SPRINKLER HEAD

SEMI-RECESSED PENDENT SPRINKLER HEAD

PIPE CAP

DWG

EQUIPMENT TAG

FIRE HOSE VALVE

FIRE HOSE VALVE CABINET

DWG

EQ

WATER FLOW PRESSURE SWITCH

WATER FLOW SWITCH

HVAC HEATING VENTILATION AND AIR CONDITIONING CONTRACTOR

WF/PS

WF

FHV FIRE HOSE VALVE

FCVA

FIRE COMMAND CENTER

FDC FIRE DEPARTMENT CONNECTION

SP WET SPRINKLER PIPING

ETR EXISTING TO REMAIN

SPRINKLER DESIGN CRITERIA

ALL SPRINKLERS ARE TO BE QUICK RESPONSE THROUGHOUT THE SMOKE COMPARTMENT.

SPRINKLERS IN FINISHED CEILINGS SHALL BE SEMI-RECESSED PENDENTS. SPRINKLERS IN

UNFINISHED CEILING AREAS SHALL BE INSTALLED UPRIGHT. COORDINATE SPRINKLER FINISH

AND LOCATIONS WITH ARCHITECTS AND OWNER PRIOR TO INSTALLATION.

LIGHT HAZARD:

- DENSITY = 0.1 GPM/S.F. FOR MOST REMOTE 1,500 S.F. WITH 100 GPM TOTAL HOSE STREAM

- SPRINKLER COVERAGE 225 S.F. (MAX)

ORDINARY HAZARD, GROUP I:

- DENSITY = 0.15 GPM/S.F. FOR MOST REMOTE 1,500 SF WITH 250 GPM TOTAL HOSE STREAM

- SPRINKLER COVERAGE 130 S.F. (MAX)

LIGHT HAZARD CRITERIA ASSUMED FOR ALL AREAS, UNLESS NOTED OTHERWISE

ORDINARY HAZARD, GROUP I LABELED AS OH1

Project Number