FX2.02 - SECOND FLOOR FIRE PROTECTION NEW WORK PLAN.pdf
PDF 2 MB Posted
- Solicitation number
- 36C24923R0030
About this file
This document includes construction plans for a second floor fire protection system as part of a federal contract opportunity to renovate building D wing at the James H. Quillen VA Medical Center in Mountain Home, Tennessee. The plans show the layout of sprinkler zones, occupancy classifications, hydraulic calculations, and other details for the new fire protection system. The related solicitation is for project number 621-20-107 to renovate D wing to create an isolation ward. The Department of Veterans Affairs Veterans Health Administration VISN 9 is the contracting agency. Bids are due by the date specified in solicitation number 36C24923R0030. The renovation work includes installing an automatic sprinkler system in the areas as shown on the construction plans, in accordance with NFPA 13 standards.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
29A-C
30.1
32.8
P O N M L K I H G F E D C B.5 B A.5 A
3"3"3"3"2 1/2"2 1/2" 3"3"
3"3"
2"2"2 1/2"2 1/2"3"3"3"3"
SPRINKLER ZONE
ISO ROOM 1
D201B
ISO ROOM 2
D202B
ISO ROOM 3
D203B
ISO ROOM 4
D204B
ISO ROOM 5
D205B
ISO ROOM 6
D206B
ISO ROOM 7
D207B
ISO ROOM 8
D208B
ISO ROOM 9
D209B
ISO ROOM 10
D210B
ISO ROOM 11
D211B
ISO ROOM 12
D212B
TOILET
D201C
ANTEROOM
D201A
TOILET
D202C
ANTEROOM
D202A
TOILET
D204C
TOILET
D203C
ANTEROOM
D203A
ANTEROOM
D204A
ANTEROOM
D205A
TOILET
D205C
TOILET
D-206C
ANTEROOM
D206A
ANTEROOM
D207A
TOILET
D208C
TOILET
D207C
ANTEROOM
D208A
ANTEROOM
D209A
TOILET
D210C
TOILET
D209C
ANTEROOM
D210A
ANTEROOM
D211A
TOILET
D212C
TOILET
D211C
ANTEROOM
D212A
CHART ALCOVE
D201D
CHART ALCOVE
D203D
CHART ALCOVE
D205D
CHART ALCOVE
D207D
CHART ALCOVE
D209D
CHART ALCOVE
D211D
EQUIPMENT
D214
ELECTRICAL
D233
NOURISHMENT
D215
HUDDLE
D216
CLEAN
D219
LINEN
D220
SOILED
D221
NURSE STATION
D223
OIT
D222
MED
D224
NURSE MANAGER
D227
LAB ALCOVE
D226
BIOMED
D235
MECHANICAL
H.A.C.
STAIRS
S1
STAFF TOILET
D230
LOUNGE
D228
CORRIDOR
D2C3
RESTROOM
D218
ALCOVE
D217
ALCOVE
D213
WOMEN'S LOCKER
D231
MEN'S LOCKER
D232
STORAGE
D229
X-RAY ALCOVE
D225
CORRIDOR
D2C5
CORRIDOR
C6
CORRIDOR
D2C4B
CORRIDOR
D2C2
CORRIDOR
D2C1
CONSULT
D234
CORRIDOR
D2C3B
CORRIDOR
D2C3A
VESTIBULE
D236
OH1
OH1 OH1 OH1
OH1
OH1
OH1
OH1
Remote area number:
Occupancy classification:
Density:
Area of application:
Total water required (including hose streams):
@ a required system pressure of:
Fire Protection System Demand:
No. of sprinklers calculated:
Inside Hose Streams:
Outside Hose Streams:
OH1
0.15 Gpm/SqFt
1,574 SqFt
534.433 GPM
78.7231 Psi
0 GPM
250 GPMNOT IN SCOPE
HATCHING LEGEND
SMOKE ZONE #20
HYDRAULICALLY REMOTE
AREA 1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
G E N E R A L P L A N N O T E S
KEYPLAN
1100 Boulders Pkwy | Suite 503 Richmond, VA 23225
804.355.2067
A u to d e s k D o c s /M t H o m e
I s o la ti o n W a rd
D /W
S P
M t H o m e
D rv t
/1
/2
:4
:2
P
M
FX2.02
SECOND FLOOR FIRE
PROTECTION NEW WORK PLAN
11/04/2022 TGS DM
RENOVATE D-WING FOR ISOLATION
WARD
621-20-107
MOUNTAIN HOME, TENNESSEE
BID DOCUMENTSJAMES H.
QUILLEN VA
MEDICAL
CENTER
Approved: Owner
N
1/8" = 1'-0"
SECOND FLOOR FIRE PROTECTION NEW WORK PLAN
A. INFORMATION SHOWN IS DIAGRAMMATIC AND IS NOT INTENDED TO SHOW EVERY PIECE OF EXISTING OR NEW EQUIPMENT.
B. PROVIDE AUTOMATIC SPRINKLER COVERAGE IN RENOVATED AREAS IN ACCORDANCE WITH NFPA 13.
C. FIRE ALARM AND SPRINKLER ZONES SHALL COINCIDE WITH SMOKE COMPARTMENTS. REFER TO LIFE SAFETY SHEETS TO COORDINATE
SMOKE COMPARTMENT BOUNDARIES.
D. ALL AREAS ARE CONSIDERED TO BE LIGHT HAZARD DESIGNED AT 0.1 GPM/1500 FT2, UNLESS MARKED OTHERWISE.
E. INSTALL SEMI-RECESSED SPRINKLERS IN AREAS WITH FINISHED CEILINGS. COORDINATE WITH ARCHITECT AND OWNER PRIOR TO
INSTALLATION.
F. INSTALL UPRIGHT SPRINKLERS IN AREAS WITHOUT FINISHED CEILINGS. COORDINATE WITH ARCHITECT AND OWNER PRIOR TO
INSTALLATION.
G. SPRINKLERS INSTALLED IN AREAS WITH ACOUSTIC CEILING TILES ARE TO BE INSTALLED AT THE CENTER OF TILE.
H. STORAGE AREAS ARE CONSIDERED TO BE ORDINARY HAZARD 1 DESIGNED AT 0.15 GPM/1500 FT2, AND ARE MARKED AS OH1.
I. NEW SPRINKLERS IN ZONE 20 TO BE CONNECTED TO EXISTING MAINS.
J. REFER TO SHEET FX1.00 FOR ADDITIONAL INFORMATION.
K. REFER TO SHEET FX7.00 FOR ADDITIONAL DETAILS.
D R A W I N G N O T E S :
1. NEW FLOOR CONTROL VALVE CONNECTING TO EXISTING RISER. DETAIL SHOWN ON SHEET FX7.00.
2. EXISTING RISER TO REMAIN
3. SMOKE ZONE #20. CONNECT TO EXISTING SPRINKLERS IN ZONE. CONTRACTOR TO DETERMINE DISCONNECT FROM EXISTING
SPRINKLER MAIN.
No. Revisions: Date:
1 BID DOCUMENTS 11/04/2022
2 ADDENDUM 02 07/13/2023