M2-02 - SECOND FLOOR HVAC NEW WORK PLAN.pdf

PDF 847 KB Posted

Attached to
Y1DZ--Project 621-20-107 Renovate Bldg. -200_Wing D2 for Isolation Ward
Solicitation number
36C24923R0030
Issued by

About this file

This document package includes a mechanical drawing and related federal contract opportunity. The mechanical drawing titled "M2.02 SECOND FLOOR HVAC NEW WORK PLAN" depicts the layout of new and existing HVAC systems on the second floor of Building 200 at the James H. Quillen VA Medical Center in Mountain Home, Tennessee. The drawing shows the routing of ductwork, piping, air terminals, air handling equipment, and notes regarding balancing of existing fans and VAV units.

The related federal contract opportunity with Solicitation Number 36C24923R0030 is for Project 621-20-107 to renovate D Wing of Building 200 at the same location to create an isolation ward. The renovation work includes mechanical system upgrades and installations as depicted on the provided mechanical drawing. The solicitation is being conducted by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 9. The document package provides relevant details for prospective contractors to understand the scope of work required to bid on the contract opportunity.

View the file

Other files

File Type Posted
07.09_AE403 - CASEWORK ELEVATIONS.pdf PDF
P6.01 - PLUMBING DETAILS.pdf PDF
08.01_AI601 - FINISH SCHEDULE1.pdf PDF
08.00_AI101 - SECOND FLOOR FINISH PLAN-1.pdf PDF
FXD2.02 - SECOND FLOOR FIRE PROTECTION DEMOLITION PLAN.pdf PDF
08.05_WP101 - WALL PROTECTION PLAN.pdf PDF
P2.01 - FIRST FLOOR PLUMBING NEW WORK PLAN 02.pdf PDF
P3.02 - SECOND FLOOR MEDICAL GAS NEW WORK PLAN.pdf PDF
000110 Table of Contents.pdf PDF
FX2.02 - SECOND FLOOR FIRE PROTECTION NEW WORK PLAN.pdf PDF
102600 Wall and Door Protection.pdf PDF
FX1.00 - FIRE PROTECTION LEGEND AND NOTES.pdf PDF
07.08_AE402 - CASEWORK ELEVATIONS.pdf PDF
36C24923R0030 0006.docx DOCX document
Addendum 02 Summary R1.pdf PDF
07.05_AC141 - SECOND FLOOR REFLECTED CEILING PLAN.pdf PDF
07.07_AE401 - ENLARGED RESTROOM PLANS AND ELEVATIONS.pdf PDF
087100 Door Hardware.pdf PDF
E3.02 - SECOND FLOOR LIGHTING NEW WORK PLAN.pdf PDF
36C24923R0030 0005.docx DOCX document
36C24923R0030 0004.docx DOCX document
08.01_AI601 - FINISH SCHEDULE.pdf PDF
08.00_AI101 - SECOND FLOOR FINISH PLAN.pdf PDF
09.04_QT403 - ENLARGED EQUIPMENT PLAN.pdf PDF
36C24923R0030 0003.docx DOCX document
36C24923R0030 0002.docx DOCX document
36C24923R0030 0001.docx DOCX document
CALCULATION OF SELF PERFORMED WORK.docx DOCX document
Contractor EMR Certification Form.docx DOCX document
C27_UUpdated 621-20-107 Drawings Part 3 of 3.pdf PDF
C27_Updated 621-20-107 Drawings Part 2 of 3.pdf PDF
C27 Updated 621-20-107 Drawings Part 1 of 3.pdf PDF
UEI _ TAX ID.docx DOCX document
36C24923R0030_1.docx DOCX document
C28_621-20-107 Specifications.pdf PDF
P07_Wage Determination_621-20-107 Renovate Bldg.-200 - Wing D2 for Isolation Ward.pdf PDF
RFI Form.docx DOCX document
PERFORMANCE QUESTIONNAIRE.docx DOCX document
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FD

29A-C

30.1

32.8

P O N M L K I H G F E D C B.5 B A.5 A

(E

"x

S A

(E) 58"x20" SA

(E

"x

R A

(E ) 8

4" x1

8" R

A

(E

"ø

S A

(E

"x

S A

(E

"x

S A

(E

"ø

S A

(E) 12"x10" SA

(E

"x

S A

(E) 14"x10" SA

(E) 12"x8" SA

(E) VAV

(E) VAV

(E) VAV

(E) VAV

(E) 48"x20" SA

16"x12" SA 20"x14" SA

14"x12" SA18"x14" SA22"x14" SA24"x18" SA

42"X22"

SA UP TO

AHU

"ø

S A

VAV

2-18

VAV

2-14

VAV

2-13

VAV

2-15

VAV

2-16

VAV

2-17

18"x14" EA-I 28"x16" EA-I

(E)48"x16" EA UP

TO 200-EF-23

32"x22" EA-I 16"x12" EA-I24"x14" EA-I30"x18" EA-I

40"X36" EA-I

UP TO ISO EF

"x

E A

-I

"x

S A

"x

E A

-I

"x

S A

"x

S A

"x

E A

-I

"x

S A

"x

S A

"x

E A

-I

"x

E A

-I

12"x14" SA

"x

E A

-I

"x

S A

"x

S A

"x

S A

"x

S A

"x

E A

-I

"x

S A

"x

S A

"x

E A

-I

"x

S A 14

"x

E

A -I

"x

S A

10"x10" SA 12"x12" SA

14"x12" SA

(E) 12"x10" RA(E) 16"x10" RA

(E) 14"x8" SA (E) 12"x8" SA (E) 10"x6" SA

(E

"x

E A

(E

8" x6

E

A

(E) 10"x6" EA(E) 10"x8" EA

(E) 6"x6" EA

16"x10" RA22"x16" RA

"x

E A

"x

R A

"x

6" R

A

24"x14" SA

"x

S A

18"x14" SA

30"x18" SA

"x

S A

S3

12X12

E1

S1

S1

E1

S2

E1

S1

E1

S1

S2

E1

S1

S1

E1

S2

S1

E1

E1

S1

E1

S1

E1

E1

S1

E1

S1

R1

R1

S1

S1

E1

S1

S1

S1

E2

8"x14" SA

M4.00

M4.00

8" x4

S

A

36"x22" EA-I3

M4.00

M4.00

M4.00

M4.00

12"x14" SA 10"x10" SA

"x

S A

"x

E A

-I

"x

S A

8"x18" RA

E2

12"x12" RA12"x12" RA

R2

S1

8"x8" RA

10"x10" RA 12"x10" EA24

"x

E

A

S1

IU

IU

28"x14" SA

12"x18" RA 12"x14" RA

"x

R A

28"x20" EA-I

20"x10" RA

"x

R A

8" x8

R

A

VAV

2-19

12 3

(E) 66"x20" RA

ISO ROOM 1

D201B

ISO ROOM 2

D202B

ISO ROOM 3

D203B

ISO ROOM 4

D204B

ISO ROOM 5

D205B

ISO ROOM 6

D206B

ISO ROOM 7

D207B

ISO ROOM 8

D208B

ISO ROOM 9

D209B

ISO ROOM 10

D210B

ISO ROOM 11

D211B

ISO ROOM 12

D212B

TOILET

D201C

ANTEROOM

D201A

TOILET

D202C

ANTEROOM

D202A

TOILET

D204C

TOILET

D203C

ANTEROOM

D203A

ANTEROOM

D204A

ANTEROOM

D205A

TOILET

D205C

TOILET

D-206C

ANTEROOM

D206A

ANTEROOM

D207A

TOILET

D208C

TOILET

D207C

ANTEROOM

D208A

ANTEROOM

D209A

TOILET

D210C

TOILET

D209C

ANTEROOM

D210A

ANTEROOM

D211A

TOILET

D212C

TOILET

D211C

ANTEROOM

D212A

CHART ALCOVE

D201D

CHART ALCOVE

D203D CHART ALCOVE

D205D

CHART ALCOVE

D207D

CHART ALCOVE

D209D

CHART ALCOVE

D211D

EQUIPMENT

D214

ELECTRICAL

D233

NOURISHMENT

D215

HUDDLE

D216

CLEAN

D219

LINEN

D220

SOILED

D221

NURSE STATION

D223

OIT

D222

MED

D224

NURSE MANAGER

D227

LAB ALCOVE

D226

BIOMED

D235

MECHANICAL

H.A.C.

STAIRS

S1

STAFF TOILET

D230

LOUNGE

D228

CORRIDOR

D2C3

RESTROOM

D218

WOMEN'S LOCKER

D231

MEN'S LOCKER

D232

STORAGE

D229

CORRIDOR

D2C5

CORRIDOR

C6

CORRIDOR

D2C4B

CORRIDOR

D2C2

CORRIDOR

D2C1

CONSULT

D234

CORRIDOR

D2C3B

CORRIDOR

D2C3A

VESTIBULE

D236

"x

S A

R1

S1

"x

E A

-I

"x

E A

-I

"x

E A

-I

"x

E A

-I

"x

E A

-I

"x

E

A -I

12"x18" SA

S2

S1

3S1

R1

S1

S1

E2

S1

S1

S1

E1

S1

E2

S1

S1

S1

E2

E2

S1

E2

S1

E2

E1

E1

S1

R1

E1

S1

E1

E2

S1

E2

S1

E1

E1

2E1

E1

S1

E2

S1

E2

S1

E1

E1

S1

R1

S1

S1

R1

S1

E1

R1

S1

R1

S1

R1 100S1

S1

S1

VAV

2-01

VAV

2-02

VAV

2-03

VAV

2-04

VAV

2-05

VAV

2-06

VAV

2-07

VAV

2-08

VAV

2-09

VAV

2-09

VAV

2-11

VAV

2-12

VAV-E

2-01 20"x12" EA-I

VAV-E

2-02

"x

E A

-I

VAV-E

2-03

VAV-E

2-04

"x

E A

-I

"x

E A

-I

VAV-E

2-05

VAV-E

2-06

VAV-E

2-08

VAV-E

2-09

VAV-E

2-10

VAV-E

2-11

VAV-E

2-12

S1

S1

S1 220S1

"x

S A

"x

E A

-I

"x

S

A

"x

E

A -I

30"x18" SA

"x

S A

VAV-E

2-06

20"x20" RA

UP TO AHU

"x

E A

-I

"x

E A

-I

"x

E A

-I

"x

E A

-I

"x

E A

-I

"x

E A

-I

12"x14" SA

"x

S A

"x

" S

A

E1

S1

S1

S1

36"x26" EA-I

S1

S2

S1

S1

S1

S1

S1

S1

S1

S1

A. THE ROUTING OF ALL DUCTWORK AND PIPING AS SHOWN ON THE DRAWINGS IS

DIAGRAMMATIC ONLY, INTENDING TO SHOW GENERAL ROUTING AND LOCATIONS OF

EQUIPMENT, MECHANICAL PIPING, DUCTWORK, AND SPECIALTIES. THE CONTRACTOR IS

RESPONSIBLE FOR THE EXACT LOCATION AND COORDINATION OF ALL ITEMS.

B. UNLESS OTHERWISE NOTED, MEDIUM PRESSURE DUCT RUNOUTS TO TERMINAL BOXES

SHALL BE THE SAME SIZE AS THE TERMINAL BOX INLET. DUCT RUNOUTS TO VAV

TERMINAL BOXES SHALL BE 2" LARGER THAN INLET SIZE IF BOX IS MORE THAN 15 FT

FROM MAIN SUPPLY DUCT. SEE VAV SCHEDULE FOR TERMINAL BOX INLET SIZE AND

CAPACITY RANGE.

C. UNLESS OTHERWISE NOTED, LOW VELOCITY BRANCH DUCT RUNOUTS TO DIFFUSERS

SHALL BE THE SAME DIAMETER OR FREE AREA AS THE DIFFUSER NECK. SEE AIR

DEVICE SCHEDULE FOR NECK SIZES.

D. ANY FLEX DUCT USED FOR SUPPLY DIFFUSERS SHALL ONLY BE INSTALLED ABOVE

ACCESSIBLE CEILINGS, NOT HARD CEILINGS. FLEX DUCT SHALL NOT EXCEED 6 FT AND

SHALL NOT REST ON CEILING TILES.

E. COORDINATE ALL ROOF PENETRATIONS WITH EXISTING STRUCTURE. DO NOT

PENETRATE THICKEND SLAB AREAS NEAR COLUMNS. SUBMIT COORDINATED ROOF

PENETRATION PLANS TO STRUCTURAL ENGINEER FOR APROVAL.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

G E N E R A L P L A N N O T E S

KEYPLAN

1100 Boulders Pkwy | Suite 503 Richmond, VA 23225

804.355.2067

A u to d e s k D o c s /M t H o m e

I s o la ti o n W a rd

D /W

S P

M t H o m e

D rv t

/2

/2

:0

:5

P

M

M2.02

SECOND FLOOR HVAC NEW WORK

PLAN

11/04/2022 WLS JMP

RENOVATE D-WING FOR ISOLATION

WARD

621-20-107

MOUNTAIN HOME, TENNESSEE

BID DOCUMENTSJAMES H.

QUILLEN VA

MEDICAL

CENTER

Approved: Owner

N

1/8" = 1'-0"

Level 2 New Work HVAC Plan

D R A W I N G N O T E S :

1 PROVIDE DUCT SMOKE DETECTOR AT LOCATION INDICATED.

2 RE-BALANCE AHU RETURN FAN 200-RF 14 TO 17710 CFM.

3 RE-BALANCE AHU SUPPLY FAN 200-SF 14 TO 21180 CFM.

4 RE-BALANCE EXHAUST FAN 200-EF 23 TO

5 RE-BALANCE EXISTING VAV TO 1075 CFM.

6 RE-BALANCE EXISTING VAV TO 665 CFM.

No. Revisions: Date:

1 BID DOCUMENTS 11/04/2022

2 ADDENDUM 01 06/28/2023

ADDENDUM 01: REPRINTED TO FIX CORRUPTED FILE ERROR.

06/28/2023

Sheets
M2.02 - SECOND FLOOR HVAC NEW WORK PLAN