This document is an addendum to a specification section for a federal construction project to renovate a building wing at the James H. Quillen VA Medical Center in Mountain Home, Tennessee for use as an isolation ward. The specification addresses requirements for wall and door protection products including corner guards, handrail and wall guard combinations, and bumper guards. The resilient materials must meet standards for impact resistance, flame spread, smoke development, and extinguishing. Aluminum and stainless steel compositions are identified. The installation of these products is also outlined.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Addendum #2 James H. Quillen VA Medical Center Renovation Wing D2 for Isolation Ward
VA Project Number: 621-20-107
01-01-21
10 26 00 - 1
WALL AND DOOR PROTECTION
SECTION 10 26 00
WALL AND DOOR PROTECTION
PART 1 - GENERAL
1.1 DESCRIPTION
A. This section specifies bumper guards (BG-1), handrail/wall guard combinations (HR-1), corner guards (CG-1).
1.2 RELATED WORK
A. Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS: Sustainable
Design Requirements.
B. Section 08 71 00, DOOR HARDWARE: Armor plates and kick plates not specified in this section.
1.3 QUALITY ASSURANCE
A. Manufacturer’s Qualifications: Manufacturer with a minimum of three (3) years’ experience in providing items of type specified.
1. Obtain wall and door protection from single manufacturer.
B. Installer’s Qualifications: Installers are to have a minimum of three
(3) years’ experience in the installation of units required for this project.
1.4 SUBMITTALS
A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT
DATA, AND SAMPLES.
B. Sustainable Design Submittals, as described below:
1. 1. Volatile organic compounds per volume as specified in PART 2 -
PRODUCTS.
C. Shop Drawings: show design and installation details.
D. Manufacturer's Literature and Data:
1. Handrail/Wall Guard Combinations.
2. Bumper Guards.
3. Corner Guards.
4. High Impact Wall covering.
E. Test Report: Showing that resilient material complies with specified fire and safety code requirements.
F. Manufacturer’s qualifications.
G. Installer’s qualifications.
H. Manufacturer’s warranty.
10 26 00 - 2
WALL AND DOOR PROTECTION
1.5 DELIVERY AND STORAGE
A. Deliver materials to the site in original sealed packages or containers marked with the name and brand, or trademark of the manufacturer.
B. Protect from damage from handling and construction operations before, during and after installation.
C. Store in a dry environment of approximately 21 degrees C (70 degrees F) for at least 48 hours prior to installation.
1.6 WARRANTY
A. Construction Warranty: Comply with FAR clause 52.246-21 “Warranty of
Construction”.
B. Manufacturer Warranty: Manufacturer shall warranty their wall and door protection for a minimum of five (5) years from date of installation and final acceptance by the Government. Submit manufacturer warranty.
1.7 APPLICABLE PUBLICATIONS
A. publications listed below form a part of this specification to extent referenced. publications are referenced in text by basic designation only.
B. ASTM International (ASTM):
A240/A240M-20...........Chromium and Chromium-Nickel Stainless Steel
Plate, Sheet, and Strip for Pressure Vessels and For General Applications
B221-14.................Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes
B221M-13................Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes (Metric)
D256-10(2018)...........Determining the Izod Pendulum Impact Resistance of Plastics
D635-18.................Rate of Burning and/or Extent and Time of
Burning of Plastics in a Horizontal Position
E84-23..................Surface Burning Characteristics of Building
Materials
C. Aluminum Association (AA):
DAF 45-09...............Designation System for Aluminum Finishes
D. American Architectural Manufacturers Association (AAMA):
611-14..................Voluntary Specification for Anodized
Architectural Aluminum
E. Code of Federal Regulation (CFR):
10 26 00 - 3
WALL AND DOOR PROTECTION
40 CFR 59(2020) Subpart D National Volatile Organic Compound
Emission Standards for Architectural Coatings
F. The National Association of Architectural Metal Manufacturers (NAAMM):
AMP 500-06..............Metal Finishes Manual
G. National Fire Protection Association (NFPA):
80-2019.................Standard for Fire Doors and Other Opening
Protectives
H. SAE International (SAE):
J 1545-2014-10..........Instrumental Color Difference Measurement for
Exterior Finishes, Textiles and Colored Trim.
I. Underwriters Laboratories Inc. (UL):
Annual Issue............Building Materials Directory
PART 2 - PRODUCTS
2.1 MATERIALS
A. Stainless Steel: A240/A240M, Type 304.
B. Aluminum Extruded: ASTM B221M (B221), Alloy 6063, Temper T5 or T6.
C. Resilient Material:
1. Provide resilient material consisting of high impact resistant extruded acrylic vinyl, polyvinyl chloride, or injection molded thermal plastic conforming to the following:
a. Minimum impact resistance of 960.8 N-m/m (18 feet-pounds/square inch) when tested in accordance with ASTM D256 (Izod impact, feet-pounds per inch notched).
b. Class 1 fire rating when tested in accordance with ASTM E84, having a maximum flame spread of 25 and a smoke developed rating of 450 or less.
c. Rated self-extinguishing when tested in accordance with
ASTM D635.
d. Provide material labeled and tested by Underwriters Laboratories or other approved independent testing laboratory.
e. Provide resilient material for protection on fire rated doors and frames assemblies that is listed by the testing laboratory performing the tests.
f. Provide resilient material installed on fire rated wood/steel door and frame assemblies that have been tested on similar type assemblies. Test results of material tested on any other combination of door and frame assembly are not acceptable.
10 26 00 - 4
WALL AND DOOR PROTECTION
g. Provide integral color with colored components matched in accordance with SAE J 1545 to within plus or minus 1.0 on the
CIE-LCH scales.
2.2 CORNER GUARDS (CG-1)
A. Resilient, Shock-Absorbing Corner Guards: Surface mounted type.
1. Snap-on corner guard formed from resilient material, minimum 1.98 mm (0.078-inch) thick, free floating on a continuous 1.52 mm
(0.060-inch) thick extruded aluminum retainer. Provide appropriate mounting hardware, cushions and base plates as required.
2. Profile: Minimum 76 mm (3 inch) long leg and 6 mm (1/4 inch) corner radius.
3. Height: 1.22 m (4 feet).
4. Retainer Clips: Provide manufacturer’s standard impact-absorbing clips.
5. Provide factory fabricated end closure caps at top and bottom of surface mounted corner guards.
6. Flush mounted corner guards installed on any fire rated wall to be installed in a manner that maintains the fire rating of the wall.
Provide fire test of proposed corner guard system to verify compliance.
a. Where insulating materials are an integral part of the corner guard system, provide insulating materials furnished by the manufacturer of the corner guard system.
2.3 WALL GUARDS AND HANDRAILS
A. Resilient Wall Guards and Handrails: (HR-1)
1. Handrail/Wall Guard Combination:
a. Snap-on covers of resilient material, minimum 2 mm (0.078-inch) thick.
b. Free-floating on a continuous, extruded aluminum retainer, minimum 1.82 mm (0.072-inch) thick.
c. Anchor to wall at maximum 762 mm (30 inches) on center.
2. Bumper Guards: (BG-1)
a. Snap-on covers of resilient material, minimum 2.54 mm (0.100-inch) thick. Free-floating over 51 mm (2 inch) wide aluminum retainer clips, minimum 2.28 mm (0.090-inch) thick, anchored to wall at maximum 610 mm (24 inches) on center, supporting a continuous aluminum retainer, minimum 1.57 mm (0.062-inch)
10 26 00 - 5
WALL AND DOOR PROTECTION
thick free-floated over a continuous extruded aluminum retainer, minimum 2.03 mm (0.080-inch) thick anchored to wall at maximum
610 mm (24 inches) on center. Provide handrails and wall guards with prefabricated end closure caps, inside and outside corners, concealed splices, cushions, mounting hardware and other accessories as required. End caps and corners to be field adjustable to assure close alignment with handrails and wall guards. Screw or bolt closure caps to aluminum retainer in a concealed manner.
2.4 HIGH IMPACT WALL COVERING
A. Provide wall covering/panels consisting of high impact rigid acrylic vinyl or polyvinyl chloride resilient material.
B. Panel sizes to be 0.61 x 1.21 meter (2 x 4 feet) C. Submit fire rating and extinguishing test results for resilient material.
D. Submit statements attesting that the items comply with specified fire and safety code requirements.
E. High Impact Wall Panels: Wall panel face and edge thickness to be 0.56 mm (0.022 inch). Panel face to be factory banded to a 9.53 mm (0.375 inch) thick fiberboard core. The backside of the panel is to be laminated with a moisture resistant vapor barrier.
F. Provide adhesive as recommended by the wall covering manufacturer.
2.5 FASTENERS AND ANCHORS
A. Provide fasteners and anchors as required for each specific type of installation.
B. Where type, size, spacing or method of fastening is not shown or specified in construction documents, submit shop drawings showing proposed installation details.
2.6 FINISH
A. Resilient Material: Embossed textures and color in accordance with
SAE J1545.
PART 3 - INSTALLATION
3.1 RESILIENT CORNER GUARDS (CG-1)
A. Install corner guards on walls in accordance with manufacturer's instructions.
10 26 00 - 6
WALL AND DOOR PROTECTION
3.2 RESILIENT HANDRAILS / WALL GUARD COMBINATION (HR-1)
A. Secure to walls with fasteners in accordance with manufacturer's details and instructions.
3.3 RESILIENT BUMPER GUARD (BG-1)
A. Secure to walls with fasteners in accordance with manufacturer's details and instructions.
- - - E N D - - -
| SECTION 10 26 00 WALL AND DOOR PROTECTION |
| PART 1 - GENERAL |
| 1.1 DESCRIPTION |
| 1.2 RELATED WORK |
| A. Section 09 06 00, SCHEDULE FOR FINISHES: Color and texture of aluminum and resilient material. |
| 1.3 QUALITY ASSURANCE |
| 1.4 SUBMITTALS |
| 1.5 DELIVERY AND STORAGE |
| 1.6 WARRANTY |
| 1.7 APPLICABLE PUBLICATIONS |
| PART 2 - PRODUCTS |
| 1.1 SPEC WRITER NOTE: Make material requirements agree with applicable requirements specified in the referenced Applicable Publications. Update and specify only that which applies to the project. |
| 1.1 |
| 2.1 MATERIALS |
| 1.1 SPEC WRITER NOTE: All corner guards in new construction to be flush mounted. Existing surface mounted corner guards can be replaced with surface mounted units. |
| 1.1 |
| 2.2 CORNER GUARDS (CG-1) |
| 1.1 Fabricate stainless steel corner guards of 1.27 mm (.05 inch) thick material conforming to ASTM A240/A240M, Type // 302 // // 304 //. Install corner guards // from floor to ceiling. // // as indicated on construction documents. // // Form corner g... |
| 2.3 WALL GUARDS AND HANDRAILS |
| 1.1 Aluminum Wall Guards: Extruded aluminum, closed tubular bumper assembly mounted on wall brackets. |
| 1.1 Provide wall bumper with factory fabricated end closure caps, and inside and outside corner assemblies, concealed splice plates, and other accessories standard with the manufacturer. |
| 1.1 Fabricate tubular wall guards from material with a nominal wall thickness of 6.35 mm (0.250-inch), form grooves for and provide two (2) strips of continuous polyvinyl chloride cushion bumper inserts. |
| 1.1 Fabricate adjustable wall brackets from aluminum having a nominal wall thickness of 5.08 mm (0.20-inch). Fasten bumper to brackets with 6.35 mm (1/4-inch) diameter aluminum or stainless steel bolts with locknuts. |
| 1.1 Stainless Steel Wall Guards: Construct wall guard, including brackets, of minimum 4.76 mm (0.1875-inch) thick stainless steel. |
| 1.1 SPEC WRITER NOTE: |
| 1.1 Coordinate door and door frame protection material requirements with door and frame suppliers to ensure fit for all components. |
| 1.1 |
| 1.1 DOOR AND DOOR FRAME PROTECTION |
| 1.1 Fabricate door and door frame protection items from vinyl acrylic or polyvinyl chloride resilient material, minimum 1.52 mm (0.060-inch) thick, for doors // and 0.89 mm (0.035-inch) thick for door frames //. |
| 1.1 Provide adhesive as recommended by resilient material manufacturer. |
| 2.4 HIGH IMPACT WALL COVERING |
| 2.5 FASTENERS AND ANCHORS |
| 2.6 FINISH |
| PART 3 - INSTALLATION |
| 1.1 |
| 3.1 RESILIENT CORNER GUARDS (CG-1) |
| 1.1 STAINLESS STEEL CORNER GUARDS |
| 1.1 Mount guards on external corners of interior walls, partitions and columns as shown on construction documents. |
| 1.1 SPEC WRITER NOTE: Edit to suit type of guards specified and details shown on the drawings. |
| 1.1 |
| 1.1 Where corner guards are installed on walls, partitions or columns finished with plaster or ceramic tile, // anchor corner guards as shown on construction documents. // // provide continuous 16 gauge perforated, galvanized Z-shape steel anchors wel... |
| 1.1 Where corner guards are installed on exposed structural glazed facing tile units or masonry wall, partitions or columns, // anchor corner guards as shown on the construction documents // // anchor corner guards to existing walls with 6.35 mm (1/4-... |
| 1.1 Where corner guards are installed on gypsum board, clean surface and anchor guards with a neoprene solvent-type contact adhesive specifically manufactured for use on gypsum board construction. Remove excess adhesive from around edge of guard and a... |
| 3.2 RESILIENT // wall guards // // HANDRAILs // // / WALL GUARD handrail COMBINATION // (HR-1) |
| 3.3 RESILIENT bumper GUARD (BG-1) |