This package includes construction documents and drawings for a federal contract opportunity to refurbish and upgrade elevators in Building 1 and 27 at the Mann-Grandstaff VA Medical Center in Spokane, Washington. The solicitation number is 36C26024R0009 and the project involves replacing elevator equipment and modernizing elevator systems in the two buildings. The documents provide specifications for mechanical, electrical, and plumbing work. Schematics illustrate demolition of existing structures and installation of new HVAC, fire protection, and plumbing systems. Product data is included for mechanical equipment such as air handling units, fan coils, and a rooftop unit. Construction details specify scope of work and compliance with applicable building codes.
The opportunity is a solicitation issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 20. The documents contain requirements for the elevator modernization but no information about proposal due dates, award timing, or pricing terms for the federal contract.
View the file
Other files
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HVAC BASIS OF DESIGN
SUMMER OUTDOOR
DESIGN DB (°F) 92 STATE COUNTY CLIMATE ZONE
SUMMER OUTDOOR
DESIGN WB (°F) 65 WASHINGTON SPOKANE 5B
WINTER OUTDOOR
DESIGN DB (°F) 4 DESIGN ALTITUDE 2,364
INDOOR SPACE
SUMMER INDOOR DESIGN CONDITIONS WINTER INDOOR DESIGN CONDITIONS
TEMPERATURE DB
(°F)
RELATIVE HUMIDITY
TEMPERATURE DB
(°F)
RELATIVE HUMIDITY
CONTROL ROOM 75 20-60 70 20-60
ELEVATOR
MACHINE ROOM 75 20-60 70 20-60
AIR FLOW AND PRESSURE RELATION
SPACE
DESIGNATION
MIN.
OCCUPIED/UNOCC.
TOTAL AIR
CHANGES/HR
MIN. OA AIR
CHANGES/HR ROOM AIR ROOM AIR BALANCE
CONTROL ROOM 8 / 4 2 RETURN NEUTRAL
ELEVATOR
MACHINE ROOM 20 / 10 4 RETURN NEUTRAL
DUCTWORK SYMBOLS
ADDITIONAL SYMBOLS
LIMIT OF DEMOLITION
(WALL TYPE)
(WALL TYPE)
DN
DN
UP
UP
SUPPLY DUCT (UP & DOWN)
EXHAUST DUCT (UP & DOWN)
ROUND AND SQUARE 4-WAY CEILING DIFFUSERS
SUPPLY TOP REGISTER OR GRILLE (WALL TYPE)
EXHAUST OR RETURN CEILING REGISTER OR GRILLE
EXHAUST OR RETURN BOTTOM REGISTER OR GRILLE
EXHAUST OR RETURN REGISTER OR TOP GRILLE
VANED ELBOW & AIR SPLIT TYPE DUCT TAKE-OFF
CONNECT NEW DUCT TO EXISTING DUCT
INCLINED RISE, IN DIRECTION OF AIR FLOW
INCLINED DROP, IN DIRECTION OF AIR FLOW
DNUP RETURN DUCT (UP & DOWN)
SQUARE 3-WAY CEILING DIFFUSERS
SQUARE 2-WAY CEILING DIFFUSERS
LINEAR SLOT DIFFUSER
SQUARE 1-WAY CEILING DIFFUSERS
BACK DRAFT DAMPER
SECTION.)
10X8
FLEXIBLE CONNECTION, EQUIPMENT,
VANED ELBOW (PROVIDE ALL SQUARE OR
RECTANGULAR ELBOWS WITH VANES EVEN IF
SYMBOL IS MISSING)
VANED ELBOW (SHORT RADIUS)
STANDARD RADIUS ELBOW (LONG RADIUS)
NEW DUCT (INSIDE DIMENSIONS: WIDTH x DEPTH)
EXISTING DUCT TO REMAIN
LOUVER (LOUVER SPECIFIED IN ARCHITECTURAL
FIRE DAMPER
DUCT WITH SOUND LINING
FLEXIBLE DUCTWORK (INSULATED)
MANUAL VOLUME DAMPER
EXISTING DUCT TO BE REMOVED
VIBRATION, OR SEISMIC
H4
H7
A
26-SF 3
26-TU-I-I
DETAIL NUMBER
DRAWING NUMBER WHERE SHOWN
SECTION LETTER
TYPICAL UNIT NO.
BUILDING NO. WHERE EQUIPMENT IS LOCATED.
SUPPLY FAN NO. 3 IN BUILDING NO. 26
EQUIPMENT ABBREVIATION (SUPPLY FAN)
ITEM NUMBER (TERMINAL UNIT NO. 1)
ITEM (TERMINAL UNIT SHOWN)
SERVED BY AIR HANDLER UNIT NO. 1
DRAWING NUMBER WHERE DRAWN
BUILDING NO. WHERE EQUIPMENT IS LOCATED
NECK SIZE (IN)
AIR OUTLET TYPE
AIRFLOW (CFM)
SIZE (IN) OF CONNECTING BRANCH DUCT
ANGLE OF THROW, DOWN FROM HORIZONTAL (°)
AIR OUTLET CALLOUT
26-SF 3
26-TU-I-I
OR
OR
BALL VALVE
CHILLED WATER SUPPLY
CHILLED WATER RETURN
PIPING LEGEND
CHS
CHR
RISE OR DROP IN PIPE
NEW WORK KEY
DEMOLITION KEY
REFRIGERANT LIQUID LINE
REFRIGERANT SUCTION LINE
RL
RS
TEMPERATURE SENSOR OR
THERMOSTAT
T
M MOTORIZED DAMPER
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
A/E:
625 First Ave #301 Seattle, WA, 98104
(206) 590 - 2118
RAY SPEES, PRESIDENT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
STAMPCONSULTANT
321 4 5 6 7 8 9 10
668-18-109
Revisions: Date:
SPEES DESIGN BUILD
REFURBISH AND UPGRADE
ELEVATORS IN BLDG
1 AND 27
11/16/2021
Mann-Grandstaff VA Medical Center
- Spokane, WA M-001
SHMK
MECHANICAL:
LEGENDS & SYMBOLS
AutoCAD SHX Text D
AutoCAD SHX Text R
AutoCAD SHX Text
BDD
AutoCAD SHX Text
FC
AutoCAD SHX Text
FD
AutoCAD SHX Text
VD
AutoCAD SHX Text XxX [X] XXX,XxX,XX°
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXISTING WORK (LIGHT)
AutoCAD SHX Text
NEW WORK (DARK)
AutoCAD SHX Text
CONNECT NEW TO EXISTING
AutoCAD SHX Text
EXISTING WORK (LIGHT)
AutoCAD SHX Text
DEMOLITION (DARK)
AutoCAD SHX Text
POINT OF DEMOLITION
AutoCAD SHX Text
EXPIRES 2/20/22
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text 44961
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text H
AutoCAD SHX Text C
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text K
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text K
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text R
1 BLDG 1 SIXTH FLOOR PLAN - MECHANICAL DEMO
0 4'2'
SCALE: 1/4" = 1'-0"
1. REFER TO ALL DRAWINGS FOR COORDINATION BETWEEN
DEMOLITION AND NEW WORK. COORDINATE DEMOLITION WORK
WITH THAT OF OTHER TRADES.
2. COORDINATE SALVAGE AND REUSE OF EXISTING EQUIPMENT
WITH OWNER. ITEMS OF VALUE WHICH ARE NOT DIRECTED TO
BE RETURNED TO THE OWNER, SHALL BECOME THE PROPERTY
OF THE CONTRACTOR. STORAGE OR SALE OF ITEMS ON THE
PROJECT SITE IS PROHIBITED.
3. PROTECTION: CONTRACTOR SHALL BE RESPONSIBLE FOR
PROTECTING, COVERING, AND SEALING EXISTING EQUIPMENT
AND SURROUNDINGS DURING DEMOLITION FROM DIRT, DUST
AND DEBRIS. ENSURE THE SAFE PASSAGE OF PERSONS IN AND
AROUND BUILDING DURING DEMOLITION. PREVENT INJURY TO
PERSONS AND DAMAGE TO PROPERTY. PROVIDE ADEQUATE
SHORING AND BRACING TO PREVENT COLLAPSE. IMMEDIATELY
REPAIR DAMAGED PROPERTY TO THE CONDITION BEFORE
BEING DAMAGED. TAKE EFFECTIVE MEASURES TO PREVENT
DUST MIGRATION.
4. UTILITIES: MAINTAIN ALL UTILITIES EXCEPT THOSE REQUIRING
REMOVAL OR RELOCATION. KEEP UTILITIES IN SERVICE AND
PROTECT FROM DAMAGE. DO NOT INTERRUPT UTILITIES
SERVING AREAS OUTSIDE OF PRESENT SCOPE WITHOUT FIRST
OBTAINING PERMISSION FROM THE UTILITY COMPANY AND/OR
OWNER. PROVIDE TEMPORARY SERVICES AS REQUIRED.
5. REMOVE AND DISPOSE OF EXISTING MECHANICAL EQUIPMENT
AS SHOWN, UNLESS NOTED OTHERWISE. COORDINATE WITH
ARCHITECT, AREAS OF DEMOLITION AROUND, ADJACENT, OR
CONNECTED TO EXISTING MECHANICAL EQUIPMENT THAT IS TO
REMAIN.
DEMOLITION SHEET NOTES
REMOVE AND DISPOSE OF EXISTING FAN COIL AND ASSOCIATED
CHILLED WATER COIL, AND CONTROLS. COORDINATE EXTENT OF
DEMOLITION WITH NEW WORK.
REMOVE AND DISPOSE OF EXISTING DUCTWORK AND REGISTERS.
CAP DUCTWORK AT POINT OF BRANCH CONNECTION TO DUCT MAIN
IN HALLWAY. COORDINATE EXTENT OF DEMOLITION WITH NEW
WORK.
DEMO KEYED NOTES
N
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
A/E:
625 First Ave #301 Seattle, WA, 98104
(206) 590 - 2118
RAY SPEES, PRESIDENT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
STAMPCONSULTANT
321 4 5 6 7 8 9 10
668-18-109
Revisions: Date:
SPEES DESIGN BUILD
REFURBISH AND UPGRADE
ELEVATORS IN BLDG
1 AND 27
11/16/2021
Mann-Grandstaff VA Medical Center
- Spokane, WA MD100
JWMK
BLDG 1 SIXTH FLOOR PLAN
MECHANICAL DEMO
AREA OF
WORK
KEY PLAN - N.T.S.
AutoCAD SHX Text
EXPIRES 2/20/22
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text 44961
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text H
AutoCAD SHX Text C
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text K
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text K
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
1 BLDG 1 MACHINE ROOM FLOOR PLAN- DEMO
0 4' 8'2'
SCALE: 1/4" = 1'-0"
1. REFER TO ALL DRAWINGS FOR COORDINATION BETWEEN
DEMOLITION AND NEW WORK. COORDINATE DEMOLITION WORK
WITH THAT OF OTHER TRADES.
2. COORDINATE SALVAGE AND REUSE OF EXISTING EQUIPMENT
WITH OWNER. ITEMS OF VALUE WHICH ARE NOT DIRECTED TO
BE RETURNED TO THE OWNER, SHALL BECOME THE PROPERTY
OF THE CONTRACTOR. STORAGE OR SALE OF ITEMS ON THE
PROJECT SITE IS PROHIBITED.
3. PROTECTION: CONTRACTOR SHALL BE RESPONSIBLE FOR
PROTECTING, COVERING, AND SEALING EXISTING EQUIPMENT
AND SURROUNDINGS DURING DEMOLITION FROM DIRT, DUST
AND DEBRIS. ENSURE THE SAFE PASSAGE OF PERSONS IN AND
AROUND BUILDING DURING DEMOLITION. PREVENT INJURY TO
PERSONS AND DAMAGE TO PROPERTY. PROVIDE ADEQUATE
SHORING AND BRACING TO PREVENT COLLAPSE. IMMEDIATELY
REPAIR DAMAGED PROPERTY TO THE CONDITION BEFORE
BEING DAMAGED. TAKE EFFECTIVE MEASURES TO PREVENT
DUST MIGRATION.
4. UTILITIES: MAINTAIN ALL UTILITIES EXCEPT THOSE REQUIRING
REMOVAL OR RELOCATION. KEEP UTILITIES IN SERVICE AND
PROTECT FROM DAMAGE. DO NOT INTERRUPT UTILITIES
SERVING AREAS OUTSIDE OF PRESENT SCOPE WITHOUT FIRST
OBTAINING PERMISSION FROM THE UTILITY COMPANY AND/OR
OWNER. PROVIDE TEMPORARY SERVICES AS REQUIRED.
5. REMOVE AND DISPOSE OF EXISTING MECHANICAL EQUIPMENT
AS SHOWN, UNLESS NOTED OTHERWISE. COORDINATE WITH
ARCHITECT, AREAS OF DEMOLITION AROUND, ADJACENT, OR
CONNECTED TO EXISTING MECHANICAL EQUIPMENT THAT IS TO
REMAIN.
DEMOLITION SHEET NOTES
REMOVE AND DISPOSE OF EXISTING AHU-1000 AND ASSOCIATED
CHILLED WATER COIL, DUCTWORK, AND CONTROLS. COORDINATE
EXTENT OF DEMOLITION WITH NEW WORK.
REMOVE AND DISPOSE OF EXISTING DUCTWORK. SEE DETAIL 3 ON
M501 FOR EXTENT OF DEMOLITION.
DEMO KEYED NOTES
1 11
60X48
AHU AND CURB SHALL
BE DEMOED
N
PROVIDE (2) 5 TON OCEANAIRE PAC6012 OR EQUAL FOR INTERMIT
COOLING DURING CONSTRUCTION
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
A/E:
625 First Ave #301 Seattle, WA, 98104
(206) 590 - 2118
RAY SPEES, PRESIDENT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
STAMPCONSULTANT
321 4 5 6 7 8 9 10
668-18-109
Revisions: Date:
SPEES DESIGN BUILD
REFURBISH AND UPGRADE
ELEVATORS IN BLDG
1 AND 27
11/16/2021
Mann-Grandstaff VA Medical Center
- Spokane, WA MD101
JWMK
BLDG 1 MACHINE ROOM FLOOR PLAN
MECHANICAL DEMO
AREA OF
WORK
KEY PLAN - N.T.S.
AutoCAD SHX Text
EXPIRES 2/20/22
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text 44961
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text H
AutoCAD SHX Text C
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text K
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text K
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
1 BLDG 1 ROOF FLOOR PLAN- MECHANICAL DEMO
SCALE: 1/4" = 1'-0"
1. REFER TO ALL DRAWINGS FOR COORDINATION BETWEEN
DEMOLITION AND NEW WORK. COORDINATE DEMOLITION WORK
WITH THAT OF OTHER TRADES.
2. COORDINATE SALVAGE AND REUSE OF EXISTING EQUIPMENT
WITH OWNER. ITEMS OF VALUE WHICH ARE NOT DIRECTED TO
BE RETURNED TO THE OWNER, SHALL BECOME THE PROPERTY
OF THE CONTRACTOR. STORAGE OR SALE OF ITEMS ON THE
PROJECT SITE IS PROHIBITED.
3. PROTECTION: CONTRACTOR SHALL BE RESPONSIBLE FOR
PROTECTING, COVERING, AND SEALING EXISTING EQUIPMENT
AND SURROUNDINGS DURING DEMOLITION FROM DIRT, DUST
AND DEBRIS. ENSURE THE SAFE PASSAGE OF PERSONS IN AND
AROUND BUILDING DURING DEMOLITION. PREVENT INJURY TO
PERSONS AND DAMAGE TO PROPERTY. PROVIDE ADEQUATE
SHORING AND BRACING TO PREVENT COLLAPSE. IMMEDIATELY
REPAIR DAMAGED PROPERTY TO THE CONDITION BEFORE
BEING DAMAGED. TAKE EFFECTIVE MEASURES TO PREVENT
DUST MIGRATION.
4. UTILITIES: MAINTAIN ALL UTILITIES EXCEPT THOSE REQUIRING
REMOVAL OR RELOCATION. KEEP UTILITIES IN SERVICE AND
PROTECT FROM DAMAGE. DO NOT INTERRUPT UTILITIES
SERVING AREAS OUTSIDE OF PRESENT SCOPE WITHOUT FIRST
OBTAINING PERMISSION FROM THE UTILITY COMPANY AND/OR
OWNER. PROVIDE TEMPORARY SERVICES AS REQUIRED.
5. REMOVE AND DISPOSE OF EXISTING MECHANICAL EQUIPMENT
AS SHOWN, UNLESS NOTED OTHERWISE. COORDINATE WITH
ARCHITECT, AREAS OF DEMOLITION AROUND, ADJACENT, OR
CONNECTED TO EXISTING MECHANICAL EQUIPMENT THAT IS TO
REMAIN.
DEMOLITION SHEET NOTES
REMOVE AND DISPOSE OF EXISTING GRAVITY VENTILATOR AND
DUCTWORK. COORDINATE EXTENT OF DEMOLITION WITH NEW
WORK.
PROVIDE INSULATED CURB CAP.
DEMO KEYED NOTES
DEMO (E) GRAVITY VENTILATOR
LOWER ROOF
LOWER ROOF
DEMO KEYED NOTES
N
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
A/E:
625 First Ave #301 Seattle, WA, 98104
(206) 590 - 2118
RAY SPEES, PRESIDENT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
STAMPCONSULTANT
321 4 5 6 7 8 9 10
668-18-109
Revisions: Date:
SPEES DESIGN BUILD
REFURBISH AND UPGRADE
ELEVATORS IN BLDG
1 AND 27
11/16/2021
Mann-Grandstaff VA Medical Center
- Spokane, WA MD102
JWMK
BLDG 1 ROOF FLOOR PLAN
MECHANICAL DEMO
AREA OF
WORK
KEY PLAN - N.T.S.
AutoCAD SHX Text
EXPIRES 2/20/22
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text 44961
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text H
AutoCAD SHX Text C
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text K
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text K
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
1 BLDG 1 SIXTH FLOOR PLAN - MECHANICAL
PROJECT
NORTH
0 4'2'
SCALE: 1/4" = 1'-0"
1. ALL PIPING AND DUCTS IN FINISHED ROOMS OR SPACES SHALL
BE CONCEALED IN A FURRED CHASE OR ABOVE HARD
SUSPENDED CEILING, OR ACOUSTICAL CEILING.
2. ACCESS PANELS IN HARD SUSPENDED CEILING ARE REQUIRED
FOR ALL VALVES, TRAPS, DAMPERS, CLEANOUTS, CONTROLS,
ETC. ACCESS PANELS SHALL BE FURNISHED AND INSTALLED
UNDER THE ARCHITECTURAL SPECIFICATIONS COORDINATE
LOCATION WITH MECHANICAL INSTALLATION AND
DEMONSTRATE ACCESS TO EQUIPMENT SERVED.
3. WALL TYPE EXHAUST REGISTERS NOTED ON DRAWINGS TO BE
INSTALLED WITH BOTTOM ELEVATION OF REGISTER AT 7" ABOVE
FINISHED FLOOR.
4. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR
EXACT LOCATIONS OF CEILING DIFFUSERS, AND GRILLES.
5. SEISMIC PROVISIONS REQUIRED - SEE SPECIFICATIONS.
6. ALL PRESSURES LISTED ARE GAGE PRESSURE UNLESS
OTHERWISE NOTED.
SHEET NOTES
FC
1/2"CHW AND
CHR AND 3/4"
CD LINE TO
CONNECT TO
EXISTING
CHW, CHR, &
3/4" CD LINE
CEILING
FLOOR
2 SECTION VIEW
0 4' 8'2'
SCALE: 1/4" = 1'-0"
CABLE RACKS
FC
DRIP PAN
MOUNT TOP OF
UNIT 6" BELOW
CEILING
2MH101
2MH101
M-501
T
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
A/E:
625 First Ave #301 Seattle, WA, 98104
(206) 590 - 2118
RAY SPEES, PRESIDENT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
STAMPCONSULTANT
321 4 5 6 7 8 9 10
668-18-109
Revisions: Date:
SPEES DESIGN BUILD
REFURBISH AND UPGRADE
ELEVATORS IN BLDG
1 AND 27
11/16/2021
Mann-Grandstaff VA Medical Center
- Spokane, WA MH101
JWMK
BLDG 1 SIXTH FLOOR PLAN
MECHANICAL
AREA OF
WORK
KEY PLAN - N.T.S.
AutoCAD SHX Text
EXPIRES 2/20/22
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text 44961
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text H
AutoCAD SHX Text C
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text K
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text K
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
S3 P1
P2
PROJECT
NORTH
1 BLDG 1 NINTH FLOOR PLAN - MECHANICAL
0 4'2'
SCALE: 1/4" = 1'-0"
40"X72" EXISTING
PENETRATION IN
ELEVATOR SHAFT
72"X71" EXISTING
PENETRATION IN
ELEVATOR SHAFT
EXISTING PENETRATION
TO REMAIN. SEE DETAIL
3/M5.01.
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
A/E:
625 First Ave #301 Seattle, WA, 98104
(206) 590 - 2118
RAY SPEES, PRESIDENT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
STAMPCONSULTANT
321 4 5 6 7 8 9 10
668-18-109
Revisions: Date:
SPEES DESIGN BUILD
REFURBISH AND UPGRADE
ELEVATORS IN BLDG
1 AND 27
11/16/2021
Mann-Grandstaff VA Medical Center
- Spokane, WA MH102
JWMK
BLDG 1 NINTH FLOOR PLAN
MECHANICAL
AREA OF
WORK
KEY PLAN - N.T.S.
AutoCAD SHX Text
EXPIRES 2/20/22
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text 44961
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text H
AutoCAD SHX Text C
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text K
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text K
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
A1000
A1001
1 BLDG 1 MACHINE ROOM FLOOR PLAN- MECHANICAL
0 4' 8'2'
SCALE: 1/4" = 1'-0"
AHU
SF
CU
L
M-501
M-501
EH
M-501
(E) 2"CHW AND CHR.
CONNEECT NEW 2" LINE,
ROUTE ALONG BASE OF
WALL AND OUT TO UNIT.
M-501
M-501
M-501
70X34
RS RS RS RS RS RS
RL RL RL RL RL RL
ROUTE NEW DUCT
THROUGH (E) WINDOW
CEILING
FLOOR
MH103
2 SECTION VIEW
0 4' 8'2'
SCALE: 1/4" = 1'-0"
26X20
18[2]1000
(TYP-4)
36X36[1]4000
18[2]1000
(TYP-4)
36X36[1]4000
2"CHW AND CHR ROUTE
ALONG BASE OF WALL AND
OUT TO UNIT.
MH103
26X20
26X20
26X20
M-501
SHEET NOTES
T
UNUSED WINDOW
AREA SHALL BE FLASH
AND SEALED WATER
TIGHT AT WALL
PENETRATION
UNUSED WINDOW
AREA SHALL BE FLASH
AND SEALED WATER
TIGHT AT WALL
PENETRATION
60X48 DN SEE MH102
FOR CONTINUATION
SEE ARCHITECTURAL
DRAWINGS FOR
WINDOW FILL
SEE ARCHITECTURAL
DRAWINGS FOR
WINDOW FILL
M-501
M
1. FOR THE PURPOSES OF CLEARNESS AND LEGIBILITY, DRAWINGS
ARE DIAGRAMMATIC AND FOR DESIGN INTENT ONLY.
CONTRACTOR MUST VERIFY ALL DIMENSIONS BY FIELD
MEASUREMENT BEFORE BEGINNING ANY FABRICATION OR
CONSTRUCTION.
2. ALL WORK SHALL BE IN ACCORDANCE WITH VA STANDARD
DESIGN GUIDES.
3. ALL NEW MATERIAL, METHODS, AND EQUIPMENT SHALL BE
INSTALLED IN STRICT ACCORDANCE WITH THE BUILDING
STANDARDS AS APPROVED BY THE OWNER.
4. CONTRACTOR SHALL INSTALL ALL EQUIPMENT IN STRICT
ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS.
5. COORDINATE EXACT LOCATION OF DUCTWORK WITH
EQUIPMENT, LIGHTING, PIPING, ETC..
6. BALANCE AIR SYSTEMS WITHIN 10% OF CAPACITIES LISTED.
7. CONTRACTOR SHALL COORDINATE WITH GENERAL
CONTRACTOR OR OWNER PRIOR TO ANY CUTTING OF ROOF.
8. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF
FACE SHOWN OR INDICATED. DUCT SIZES ARE NET INSIDE
DIMENSIONS.
1-5/8"
REFRIGERATION
SUCTION & 1-1/8"
REFRIGERATION
LIQUID
SF-1 VFD AND SMOKE
CONTROL PANEL
N
MANUAL PULL STATION. SEE ELECTRICAL, TYP.
KEYED NOTES
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
A/E:
625 First Ave #301 Seattle, WA, 98104
(206) 590 - 2118
RAY SPEES, PRESIDENT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
STAMPCONSULTANT
321 4 5 6 7 8 9 10
668-18-109
Revisions: Date:
SPEES DESIGN BUILD
REFURBISH AND UPGRADE
ELEVATORS IN BLDG
1 AND 27
11/16/2021
Mann-Grandstaff VA Medical Center
- Spokane, WA MH103
JWMK
BLDG 1 MACHINE ROOM FLOOR PLAN
MECHANICAL
AREA OF
WORK
KEY PLAN - N.T.S.
AutoCAD SHX Text
FS
AutoCAD SHX Text
FS
AutoCAD SHX Text
EXPIRES 2/20/22
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text 44961
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text H
AutoCAD SHX Text C
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text K
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text K
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
FS
SP
WF
FS
FS
FA
SP
1 BLDG 27 BASEMENT FLOOR PLAN- MECHANICAL
0 4' 8'2'
SCALE: 1/4" = 1'-0"
AC
R S
R S
R S
R S
R L
R L
R L
R L
3/8"REFRIGERATION
SUCTION & 1/4"
REFRIGERATION
LIQUID UP TO HP-1
AC
MH104
MH104
2 SECTION VIEW
0 4' 8'2'
SCALE: 1/4" = 1'-0"
CEILING
FLOOR
MOUNT TOP OF
UNIT 6" BELOW
CEILING
T
SHEET NOTES
1. FOR THE PURPOSES OF CLEARNESS AND LEGIBILITY, DRAWINGS
ARE DIAGRAMMATIC AND FOR DESIGN INTENT ONLY.
CONTRACTOR MUST VERIFY ALL DIMENSIONS BY FIELD
MEASUREMENT BEFORE BEGINNING ANY FABRICATION OR
CONSTRUCTION.
2. ALL WORK SHALL BE IN ACCORDANCE WITH VA STANDARD
DESIGN GUIDES.
3. ALL NEW MATERIAL, METHODS, AND EQUIPMENT SHALL BE
INSTALLED IN STRICT ACCORDANCE WITH THE BUILDING
STANDARDS AS APPROVED BY THE OWNER.
4. CONTRACTOR SHALL INSTALL ALL EQUIPMENT IN STRICT
ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS.
5. COORDINATE EXACT LOCATION OF DUCTWORK WITH
EQUIPMENT, LIGHTING, PIPING, ETC..
6. BALANCE AIR SYSTEMS WITHIN 10% OF CAPACITIES LISTED.
7. CONTRACTOR SHALL COORDINATE WITH GENERAL
CONTRACTOR OR OWNER PRIOR TO ANY CUTTING OF ROOF.
8. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF
FACE SHOWN OR INDICATED. DUCT SIZES ARE NET INSIDE
DIMENSIONS.
001A
S0-C1, TYP.
BC1-27,
TYP.
002 P4, TYP.
N
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
A/E:
625 First Ave #301 Seattle, WA, 98104
(206) 590 - 2118
RAY SPEES, PRESIDENT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
STAMPCONSULTANT
321 4 5 6 7 8 9 10
668-18-109
Revisions: Date:
SPEES DESIGN BUILD
REFURBISH AND UPGRADE
ELEVATORS IN BLDG
1 AND 27
11/16/2021
Mann-Grandstaff VA Medical Center
- Spokane, WA MH104
JWMK
BLDG 27 BASEMENT FLOOR PLAN
MECHANICAL
DEDUCTIVE BID ALTERNATE 27
AREA OF
WORK
KEY PLAN - N.T.S.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXPIRES 2/20/22
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text 44961
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text H
AutoCAD SHX Text C
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text K
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text K
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
1 BLDG 27 FIRST FLOOR PLAN - MECHANICAL
1=1/40 4' 8'2'
SCALE: 1/4" = 1'-0"
SHEET NOTES
1. FOR THE PURPOSES OF CLEARNESS AND LEGIBILITY, DRAWINGS
ARE DIAGRAMMATIC AND FOR DESIGN INTENT ONLY.
CONTRACTOR MUST VERIFY ALL DIMENSIONS BY FIELD
MEASUREMENT BEFORE BEGINNING ANY FABRICATION OR
CONSTRUCTION.
2. ALL WORK SHALL BE IN ACCORDANCE WITH VA STANDARD
DESIGN GUIDES.
3. ALL NEW MATERIAL, METHODS, AND EQUIPMENT SHALL BE
INSTALLED IN STRICT ACCORDANCE WITH THE BUILDING
STANDARDS AS APPROVED BY THE OWNER.
4. CONTRACTOR SHALL INSTALL ALL EQUIPMENT IN STRICT
ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS.
5. COORDINATE EXACT LOCATION OF DUCTWORK WITH
EQUIPMENT, LIGHTING, PIPING, ETC..
6. BALANCE AIR SYSTEMS WITHIN 10% OF CAPACITIES LISTED.
7. CONTRACTOR SHALL COORDINATE WITH GENERAL
CONTRACTOR OR OWNER PRIOR TO ANY CUTTING OF ROOF.
8. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF
FACE SHOWN OR INDICATED. DUCT SIZES ARE NET INSIDE
DIMENSIONS.
N
R L
R L
R L
R L
R L
R L
R S
R S
R S
R S
R S
R S
RL RL RL RL RL RL RL RL RL RL
RS RS RS RS RS RS RS RS RS RS
3/8"REFRIGERATION
SUCTION & 1/4"
REFRIGERATION
LIQUID UP TO HP-1
3/8"REFRIGERATION
SUCTION & 1/4"
REFRIGERATION
LIQUID DN
R L
R S
R S
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
A/E:
625 First Ave #301 Seattle, WA, 98104
(206) 590 - 2118
RAY SPEES, PRESIDENT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
STAMPCONSULTANT
321 4 5 6 7 8 9 10
668-18-109
Revisions: Date:
SPEES DESIGN BUILD
REFURBISH AND UPGRADE
ELEVATORS IN BLDG
1 AND 27
11/16/2021
Mann-Grandstaff VA Medical Center
- Spokane, WA MH105
JWMK
BLDG 27 FIRST FLOOR PLAN
MECHANICAL
DEDUCTIVE BID ALTERNATE 27
AREA OF
WORK
KEY PLAN - N.T.S.
AutoCAD SHX Text
EXPIRES 2/20/22
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text 44961
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text H
AutoCAD SHX Text C
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text K
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text K
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
1 BLDG 27 ROOF PLAN- MECHANICAL
SCALE: 1/4" = 1'-0"
HP
3/8" REFRIGERATION
SUCTION & 1/4"
REFRIGERATION
LIQUID DN TO AC-1
IN BASEMENT
M-502
SHEET NOTES
1. FOR THE PURPOSES OF CLEARNESS AND LEGIBILITY, DRAWINGS
ARE DIAGRAMMATIC AND FOR DESIGN INTENT ONLY.
CONTRACTOR MUST VERIFY ALL DIMENSIONS BY FIELD
MEASUREMENT BEFORE BEGINNING ANY FABRICATION OR
CONSTRUCTION.
2. ALL WORK SHALL BE IN ACCORDANCE WITH VA STANDARD
DESIGN GUIDES.
3. ALL NEW MATERIAL, METHODS, AND EQUIPMENT SHALL BE
INSTALLED IN STRICT ACCORDANCE WITH THE BUILDING
STANDARDS AS APPROVED BY THE OWNER.
4. CONTRACTOR SHALL INSTALL ALL EQUIPMENT IN STRICT
ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS.
5. COORDINATE EXACT LOCATION OF DUCTWORK WITH
EQUIPMENT, LIGHTING, PIPING, ETC..
6. BALANCE AIR SYSTEMS WITHIN 10% OF CAPACITIES LISTED.
7. CONTRACTOR SHALL COORDINATE WITH GENERAL
CONTRACTOR OR OWNER PRIOR TO ANY CUTTING OF ROOF.
8. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF
FACE SHOWN OR INDICATED. DUCT SIZES ARE NET INSIDE
DIMENSIONS.
R S
R S
R L
R L
N
STACK PIPING
HORIZONTALLY
THROUGH WALL
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
A/E:
625 First Ave #301 Seattle, WA, 98104
(206) 590 - 2118
RAY SPEES, PRESIDENT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
STAMPCONSULTANT
321 4 5 6 7 8 9 10
668-18-109
Revisions: Date:
SPEES DESIGN BUILD
REFURBISH AND UPGRADE
ELEVATORS IN BLDG
1 AND 27
11/16/2021
Mann-Grandstaff VA Medical Center
- Spokane, WA MH106
JWMK
BLDG 27 ROOF PLAN
MECHANICAL
DEDUCTIVE BID ALTERNATE 27
AREA OF
WORK
KEY PLAN - N.T.S.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXPIRES 2/20/22
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text 44961
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text H
AutoCAD SHX Text C
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text K
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text K
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
PACKAGED
UNIT
ROUTE CONDENSATE TO
GRADEPROVIDE 12" 14GA
GALVANIZED STEEL CURB.
CONNECT TO STRUCTURE.
1 TOP DISCHARGE AHU MOUNT
NOT TO SCALE
12"
NOTES:
CONTRACTOR SHALL PROVIDE SUPPORT FOR THE DUCTWORK PER SMACNA. BASIS OF DESIGN IS BIG FOOT H
FRAME SET 305MM (12"). EQUIVALENT SUBSTITUTION IS PERMITTED.
1. 12"X12" FOOT PLATES SHALL BE INSTALLED PER MANUFACTURER REQUIREMENTS.
2. DISTANCE BETWEEN SUPPORTS PER SMACNA HVAC DUCT CONSTRUCTION STANDARDS METAL AND FLEXIBLE
CHAPTER 6.
3. ALL ROOF SUPPORTS TO BE APPROVED BY STRUCTURAL ENGINEER (DCI).
4. X= H FROM TABLE ON FIGURE 6-4 SMACNA HVAC DUCT CONSTRUCTION STANDARDS METAL AND FLEXIBLE. UP
T0 24" WIDE = 14", 25"-36" WIDE = 18", 37"-48" WIDE = 24"
5. PER SMACNA HVAC DUCT CONSTRUCTION PROVIDE SUPPORT ON BOTH SIDES OF THE ELBOW
DUCTWORK
ROOF
BIG FOOT H305 OR EQUAL
SECURE DUCTWORK TO FRAME
PER MANUFACTURERS
DIRECTIONS.
2 EXTERIOR ROOF DUCT SUPPORT
NOT TO SCALE
3 SUPPLY FAN DETAIL
NOT TO SCALE
CAULK ALL AROUND
STORM-PROOF LOUVER
1/2" BIRDSCREEN
4 COMBINATION LOUVER DETAIL
NOT TO SCALE
AD
JA
C
EN
T W
AL
L
6" MIN
UNIT HEATER
10" MIN
5 ELECTRIC WALL HEATER DETAIL
NOT TO SCALE
AIRFLOW
AIR VENT, 1/4" BALL VALVE.
INSTALL IN HIGH POINT OF
HEADER OR RETURN PIPE
TO ALLOW COMPLETE VENTING
OR AIR FROM COIL
CAPPED DRAIN, 3/4" BALL
VALVE. INSTALL IN
LOW POINT OF HEADER OR SUPPLY
DRAIN DOWN OF COIL
UNION IN OFFSET
FOR COIL REMOVAL
(TYP.)
P/T TEST PLUG (TYP.)
ISOLATION VALVE (TYP.)
FLOW CONTROL DEVICE
TWO WAY TEMPERATURE
CONTROL VALVE
6 2-WAY WATER COIL
NOT TO SCALE
BASEMENT
1ST FLOOR
2ND FLOOR
(3-8) FLOORS
9TH FLOOR
10TH FLOOR
ROOF
ELEVATOR
PRESSURIZATION
FAN (EPF)
FIRE FIGHTER'S SMOKE
CONTROL PANEL (LOCATION
TO BE APPROVED BY FIRE
CHIEF)
SEE CONTROL DIAGRAM
BUILDING DIAGRAM
SD
SD
SD
SD
SD
SD
ELEVATOR
TRACTION
ELEVATOR
SHAFT
VFD
FLOW
SWITCH
PRESSURE
DIFFERENTIAL
TRANSDUCER
0.1" (MIN.) TO 0.25" (MAX.) POSITIVE PRESSURE TO
BE MAINTAINED IN 1ST FLOOR SHAFT RELATIVE TO
1ST FLOOR LOBBY (WITH BOTH ELEVATOR DOORS
OPEN AND PARKED AT 1ST FLOOR) DURING EPF
ACTIVATION
(E) SMOKE DETECTORS
(BY OTHERS)
7 ELEVATOR PRESSURIZATION
NOT TO SCALE WEATHER PROOF DUCT
PENETRATION THROUGH
(2) (E) 36X60 WINDOW.
SEE ARCHITECTURAL
DRAWINGS FOR DETAIL.
ELEVATOR
TRACTION
ELEVATOR
SHAFT
1"Ø GRADE S THRUBOLT WITH 1"Ø
WASHER TO STRUCTURAL A36 PLATE
(3/16" MIN HOST) 4 ANCHORS PER PLATE.
TOP OF ROOF FINISH
3" ASSUMED ROOFING
THICKNESS
ROOFER WILL SEAL
AROUND LEGS FOR
COMPLETE WATER
PROOF (TYP)
WALL
34X70
PROVIDE FLEX
CONNECTION
MECHANICAL
ROOM FLOOR
PROVIDE BIRD SCREEN
60X484'-6 9 16"
9'- 913 16
6'-9 3 16"
SLR-A-200 OR EQUIVALENT
SPRING ISOLATORS MOUNTED
TO STRUCTURE.
8 CONDENSING UNIT MOUNTING DETAIL
NOT TO SCALE
SLR-A-200 OR EQUIVALENT
SPRING ISOLATORS MOUNTED
TO STRUCTURE.
PROVIDE 12" 14GA
GALVANIZED STEEL CURB.
COOLING COIL
PROVIDE SPRING OR NEOPRENE ISOLATORS AS
SPECIFIED. INSTALLATION PER
FAN MFRS RECOMMENDATIONS.
FAN COIL UNIT
RETURN AIR
9 FAN COIL MOUNTING DETAIL
NOT TO SCALE
SD
(E) SMOKE DETECTORS IN
SHAFT (BY OTHERS)
SD
4" CONCRETE SLAB
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
A/E:
625 First Ave #301 Seattle, WA, 98104
(206) 590 - 2118
RAY SPEES, PRESIDENT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
STAMPCONSULTANT
321 4 5 6 7 8 9 10
668-18-109
Revisions: Date:
SPEES DESIGN BUILD
REFURBISH AND UPGRADE
ELEVATORS IN BLDG
1 AND 27
11/16/2021
Mann-Grandstaff VA Medical Center
- Spokane, WA M-501
JWMK
MECHANICAL:
BLGD 1 DETAILS
AutoCAD SHX Text
EXPIRES 2/20/22
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text 44961
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text H
AutoCAD SHX Text C
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text K
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text K
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
SECURELY ATTACH CONDENSING
UNIT TO CROSS MEMBER . (4 BOLTS
TOTAL). TWO 1/4"Ø S.S. THRUBOLTS
WITH 5/8" WASHERS AND NUTS
3/8"Ø GRADE S SCREWS OR THRUBOLT
WITH 1"Ø WASHER TO STRUCTURAL
A36 STEEL MEMBERS (3/16" MIN HOST)
4 ANCHORS PER PLATE .
ROOF HOST
STRUCTURE
TOP OF ROOF
FINISH
CROSS MEMBER
USE MIAMI TECH (MTI)
AS14S OR VA APPROVED
SUBSTITUTE.
3" ASSUMED
ROOFING
THICKNESS
ROOFER WILL SEAL
AROUND LEGS FOR
COMPLETE WATER
PROOF (TYP)
(1) 5/16-18
THRUBOLT TO
INTERLOCK
SQUARE TUBING
20" 18"
INSTALL LINE SET PER
MANUFACTURE
RECOMMENDATIONS.
RS AND RL LINES TO
DUCTLESS SPLIT
CONDENSING UNIT
WALL
90° SWEEP
D L S
20 GAGE SHEET METAL PAN AROUND
REFRIGERANT LINES FROM BOTTOM
WALL ANCHOR TO EAVE. PAINT PAN
TO MATCH BUILDING COLOR OF OIL
BASE PAINT . FASTEN SECURELY TO
WALL.
1" COND. DRAIN LINE.
TERMINATE 4" ABOVE
GRADE.
SUPPORT ON WALL WITH 3/8" Ø POWERS CARBON
STEEL WEDGE BOLT CONCRETE ANCHOR WITH 1" Ø
MIN WASHER, 1-1/2" EMBEDMENT AND 6" MIN EDGE
DISTANCE. SUPPORT PIPING EVERY 6' MINIMUM.
4" DIA. HOLE THRU WALL OR SOFFIT
SEAL WEATHER TIGHT
PROVIDE ISOLATION
VALVES ON EACH SIDE
OF BRAIDED FLEXIBLE
REFRIGERANT LINE
MINIMUM 12"
BRAIDED
FLEXIBLE
REFRIGERANT
LINE
1 CONDENSING UNIT ROOF MOUNT SUPPORT DETAIL
NOT TO SCALE
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
A/E:
625 First Ave #301 Seattle, WA, 98104
(206) 590 - 2118
RAY SPEES, PRESIDENT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
STAMPCONSULTANT
321 4 5 6 7 8 9 10
668-18-109
Revisions: Date:
SPEES DESIGN BUILD
REFURBISH AND UPGRADE
ELEVATORS IN BLDG
1 AND 27
11/16/2021
Mann-Grandstaff VA Medical Center
- Spokane, WA M-502
JWMK
MECHANICAL:
BLDG 27 DETAILS
DEDUCTIVE BID ALTERNATE
AutoCAD SHX Text
EXPIRES 2/20/22
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text 44961
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text H
AutoCAD SHX Text C
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text K
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text K
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
AIR OUTLET SCHEDULE
TAG MANUFACTURER MODEL NO. SERVICE TYPE MATERIAL MOUNTING BORDER PATTERN
BLADE
SPACING
(INCH)
BLADE
POSITION
BLADE
DEFLECTION NOTES
[1] TITUS 350 RL RETURN GRILLE STEEL SURFACE TYPE 1 FIXED 3/4" FRONT
HORIZONTAL 35° 1, 2, 3
[2] PRICE ND SUPPLY NOZZLE ALUMINUM DUCT - ANGULARLY
ADJUSTABLE N/A N/A N/A -
NOTES:
1. COLOR TO BE MANUFACTURER STANDARD WHITE
2. PROVIDE BALANCING DAMPER IN BRANCH DUCT SERVING AIR OUTLET AT TAKEOFF
FROM TRUNK DUCT. (ADDITIONAL DAMPERS FOR SYSTEM BALANCING ARE SHOWN
ON DRAWINGS)
3. PROVIDE SQUARE TO ROUND ADAPTER AS REQUIRED
4. PROVIDE 24"X24" PAN FOR LAY-IN CEILING INSTALLATION AS REQUIRED (SEE
ARCHITECTURAL REFLECTED CEILING PLANS FOR LOCATION)
5. PROVIDE RETURN GRILLE WITHOUT SCREW HOLES FOR LAY-IN CEILING APPLICATION
(SEE ARCHITECTURAL REFLECTED CEILING PLANS FOR LOCATION)
6. PROVIDE OPPOSED BLADE DAMPER..
ROOFTOP AC UNIT SCHEDULE
TAG SERVICE MFG MODEL CFM
CFM
(OSA) ESP (") REFRI-
GERANT
DX COOLING CHILLED WATER COIL ELECTRICAL
WEIGHT
LBS. NOTES
NET TOTAL
(MBH)
NET SENS
(MBH)
EAT
(DB)
EAT
(WB)
AMBIENT
(DB) EER
INPUT
(MBH)
SENSIBL
E (MBH) GPM PD EWT LWT
EAT
(DB) LAT (DB) MCA MOCP VOLT PHASE
ELEVATOR
MACHINE
ROOM
DAIKIN OAH011GDCM 4000 400 0.5 410A 119.82 115.59 86 63.5 98 13.0 115.59 115.59 23 1.2 45°F 55°F 86 57.6 24.8 35.0 208 3 2426 1,2,3,4,5,6,7
AHU
SUPPLY FAN SCHEDULE
TAG MFG MODEL SERVICE DRIVE CFM ESP (") FAN
RPM
SONE
LEVEL
MOTOR
NOTES
HP VOLTS PHASE
GREENHECK USF-54 ELEVATOR
SHAFTS MFG 50,000 0.5 579 36 20 208 3 1
SF
NOTES:
1. PROVIDE W/ VFD
NOTES:
1. PROVIDE ECONOMIZER. INTERLOCK W/ RELIEF LOUVER
2. PROVIDE FACTORY ROOF CURB
3. PROVIDE FACTORY DISCONNECT
4. INTERLOCK WITH BMS
5. PROVIDE FACTORY INSTALLED SMOKE DETECTOR IN RETURN DUCT
6. PROVIDE 2 STAGES OF COOLING
7. PROVIDE ULTRA LOW LEAK DAMPERS ON OUTSIDE AIR. MOTORIZED
DAMPERS SHALL HAVE A TESTED MAXIMUM LEAKAGE RATE NOT TO
EXCEED 4 CFM/S
CONDENSING UNIT
TAG LOCATION INTERLOCK
WITH CU MFR MODEL# NOMINAL
TONS WEIGHT EER
ELECTRICAL
NOTES
VOLT PHASE MCA MOCP
ROOF AAON
CFA-009-B-A-2-AC00J 9 1069 13.0 208 3 36 45 1
NOTES:
1. PROVIDE CURB FOR CONDENSING UNIT
CU
AHU
LOUVER SCHEDULE
TAG MANUF. MODEL NO. SERVICE TYPE MATERIAL
AIR FLOW
(CFM)
VELOCITY
(FPM)
PRESS.
DROP
("WC)
SIZE MIN.
FREE
AREA
(SF)
NOTESWIDTH
(INCH)
HEIGHT
(INCH)
DEPTH
(INCH)
RUSKIN ELF375DXH INTAKE COMBINATI
ON ALUMINUM 4000 545 .03 48 42 4 6.67 1, 2, 3, 4
NOTES:
1. PROVIDE 1/2"x1/2" 19 GAUGE ALUMINUM BIRD SCREEN ON INSIDE OF
LOUVER
2. PROVIDE BAKED ENAMEL FINISH OF COLOR SELECTED BY ARCHITECT
FROM MANUFACTURERS STANDARD COLORS.
3. PROVIDE MOTORIZED BACKDRAFT DAMPER WITH 24 VOLT ACTUATOR.
DAMPER SHALL BE LOW LEAKAGE TYPE NOT TO EXCEED 4 CFM/SF
LEAKAGE WHEN TESTED IN ACCORDANCE WITH AMCA 5000 @ 1.0" WC.
4. INTERLOCK WITH AHU-100.
L
ELECTRIC WALL HEATER
TAG MFR/ MODEL # SERVICE CFM
ELECTRICAL
WEIGHT NOTES
KW V/Ø
INDEECO WRI MACHINE ROOM
ENTRY 40 2 208/ 1 - 1, 2EH
NOTES:
1. PROVIDE SURFACE MOUNT KIT.
2. PROVIDE BUILT IN THERMOSTAT.
SHEET NOTES
1. ALL EQUIPMENT WITH MANUFACTURERS NAME AND NUMBER IS THE BASIS OF DESIGN AND
EQUIVALENT APPROVED EQUIPMENT IS ACCEPTABLE
FAN COIL SCHEDULE
TAG MFG MODEL
SUPPLY FAN CHILLED WATER
NOTES
CFM
E.S.P.
("W.C) MCA HP V/Ø
SENSIBLE
CAPCAITY
(MBH)
EAT
(DB)
EAT
(WB)
LAT
(DB)
LAT
(WB)
EWT
(DB)
LWT
(DB)
MAX
PD GPM
DAKINE FCHC204 400 0.3 3.2 1/8 208/1 9.5 80 63.1 56.6 55.0 45 55 2.8 2.1 1, 2, 3, 4
NOTES
FC
1. PROVIDE UNIT WITH INTEGRAL DISCONNECT.
2. PROVIDE UNIT WITH 2-WAY CONTROL VALVE PIPING PACKAGE.
3. PROVIDE UNIT WITH BUILT-IN DRIP PAN.
4. PROVIDE WALL MOUNTED THERMOSTAT THAT INTERLOCKS WITH BMS.
5. PROVIDE SECONDARY DRIP PAN. SEE DETAIL 2/MH101.
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
A/E:
625 First Ave #301 Seattle, WA, 98104
(206) 590 - 2118
RAY SPEES, PRESIDENT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
STAMPCONSULTANT
321 4 5 6 7 8 9 10
668-18-109
Revisions: Date:
SPEES DESIGN BUILD
REFURBISH AND UPGRADE
ELEVATORS IN BLDG
1 AND 27
11/16/2021
Mann-Grandstaff VA Medical Center
- Spokane, WA M-601
JWMK
MECHANICAL:
BLDG 1 SCHEDULES
AutoCAD SHX Text
EXPIRES 2/20/22
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text 44961
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text H
AutoCAD SHX Text C
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text K
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text K
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
DUCTLESS SPLIT SYSTEM SCHEDULE
HEAT PUMP WALL MOUNTED FAN COIL
NOTES
EQUIP# MFR/ MODEL MODEL #
OPERATING
WEIGHT
(LBS)
SEER/HSPF
UNIT
EQUIP# MFR MODEL # CFM
COOLING BTUH
(SENSIBLE)
HEATING BTUH
(SENSIBLE)
ELECTRICAL
AMB-AIR
(°F) AMPS MOCP V/Ø MCA V/Ø MCA
MITSUBISHI MUZ-HM09NA 73 18 95 9 15 208 /1 MITSUBISHI MSZ-HM09NA 237 9,000 10,900 208 1 1.0 1,2,3,4,5,6,7
HP
NOTES:
1. PROVIDE FACTORY WALL MOUNTING HARDWARE.
2. PROVIDE FACTORY WALL MOUNTED T-STAT TO INTERLOCK WITH BMS
3. PROVIDE SLIDE-IN AIR FILTER.
4. ROUTE CONDENSATE DOWN EXTERIOR OF BUILDING. TERMINATE 18" ABOVE GRADE. COORDINATE ROUTING WITH OWNER AND GENERAL CONTRACTOR.
5. PROVIDE LOW AMBIENT CONTROLS & CRANK CASE HEATER
6. PROVIDE FACTORY BASE SUPPORT ASSEMBLY.
7. PROVIDE FACTORY REFRIGERANT LINE SET.
AC
SHEET NOTES
1. ALL EQUIPMENT WITH MANUFACTURERS NAME AND NUMBER IS THE BASIS OF DESIGN AND
EQUIVALENT APPROVED EQUIPMENT IS ACCEPTABLE
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
A/E:
625 First Ave #301 Seattle, WA, 98104
(206) 590 - 2118
RAY SPEES, PRESIDENT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
STAMPCONSULTANT
321 4 5 6 7 8 9 10
668-18-109
Revisions: Date:
SPEES DESIGN BUILD
REFURBISH AND UPGRADE
ELEVATORS IN BLDG
1 AND 27
11/16/2021
Mann-Grandstaff VA Medical Center
- Spokane, WA M-602
JWMK
MECHANICAL:
BLDG 27 SCHEDULES
DEDUCTIVE BID ALTERNATE
AutoCAD SHX Text
EXPIRES 2/20/22
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text 44961
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text H
AutoCAD SHX Text C
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text K
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text K
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
OFF
AUTOON
ELEVATOR
PRESSURIZATION FAN
(EPF) SWITCH
FIRE FIGHTER'S SMOKE CONTROL PANEL
FAN CONTACTOR
24V
ELEV. SHAFT
SMOKE DETECTOR
SD-1
BUILDING SMOKE
ALARMS (BY
OTHERS)
208/3Ø
EPF
FLOW
SWITCH
EPF
AIRFLOW
INDICATOR
LIGHT
VFD
FAN VFD PANEL
PRESSURE
DIFFERENTIAL
TRANSDUCER
2 ELEVATOR PRESSURIZATION CONTROL DIAGRAM
NOT TO SCALE
ROOFTOP UNIT SEQUENCE OF OPERATIONS
COOLING CYCLE:
ON A CALL FOR COOLING THE DDC SYSTEM SHALL START THE FAN AND MODULATE THE OUTSIDE AIR, RETURN AIR, AND RELIEF AIR
DAMPERS TO MINIMUM VENTILATION POSITION.
CHILLED WATER COIL: WHEN FAN IS RUNNING, CHILLED WATER CONTROL VALVE SHALL MODULATE AS REQUIRED TO MAINTAIN SPACE
TEMPERATURE SET POINT. (2ND STAGE OF COOLING).
DX COOLING: WHEN FAN IS RUNNING AND THE CHILLED WATER SYSTEM IS DISABLED, THE DDC SYSTEM SHALL CYCLE THE DX COOLING
TO MAINTAIN SPACE TEMPERATURE SET POINT. (3RD STAGE OF COOLING).
ECONOMIZER DAMPER CONTROL:
AT OUTSIDE AIR TEMPERATURES BELOW 70°F (ADJUSTABLE) THE DDC SYSTEM MODULATES OUTSIDE-AIR, RELIEF AIR AND RETURN AIR DAMPERS ON THE ECONOMIZER CYCLE (1ST STAGE OF COOLING) TO MAINTAIN SPACE SPACE COOLING SET POINT, IF THE SPACE SET POINT TEMPERATURE IS NOT SATISFIED THE MECHANICAL COOLING SHALL STAGE ON AS INDICATED ABOVE TO MAINTAIN SPACE SET POINT TEMPERATURE. AT OUTSIDE AIR TEMPERATURES ABOVE 70°F (ADJUSTABLE) THE ECONOMIZER DAMPERS SHALL RETURN TO
MINIMUM VENTILATION POSITION.
OUTPUTS
- SPACE TEMPERATURE SET POINT
- SPACE TEMPERATURE
- OUTSIDE AIR TEMPERATURE
- ECONOMIZER STATUS
- SUPPLY FAN STATUS
- Dx COOLING ENABLE
- COOLING COIL ENABLE
DO DX COOLING ENABLE
AO RETURN DAMPER
CONTROLLER
120 VAC
TO OPERATOR'S TERMINAL
POWER & WIRING BY DIV 23.
COORDINATE WITH DIV 26.
DDC
CONTROLLER
ROOFTOP UNIT
SUPPLY FAN ENABLEDO
T1AI SPACE TEMPERATURE
T2AI SUPPLY AIR TEMPERATURE
T3AI OUTSIDE AIR TEMPERATURE
AO RELIEF AIR DAMPER
AO
V-1
CW CONTROL VALVE
2-WAY OR 3-WAY
CONTROL VALVE BY
CONTROL CONTRACTOR
LOUVER ACTUATOR
AO OUTSIDE AIR DAMPER
1…