Attachment 10 668-18-109_Project Drawings 6 of 6.pdf

PDF 16 MB Posted

Attached to
Y1DA--CON-NRM 668-18-109 Refurbish and Upgrade Elevators in Bldg 1 and 27
Solicitation number
36C26024R0009
Issued by

About this file

This file attachment relates to a federal contract solicitation for elevator refurbishment and upgrades. The solicitation number is 36C26024R0009 and is titled "Y1DA--CON-NRM 668-18-109 Refurbish and Upgrade Elevators in Bldg 1 and 27." It was issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 20 for elevator modernization work at two buildings located at an unspecified VA medical center. Responses were due on an unspecified date, with award anticipated by an unspecified future date. The 16MB file attachment contains project drawings related to the scope of work.

View the file

Other files

File Type Posted
Wage Determination 1.19.24.pdf PDF
36C26024R0009 0006.pdf PDF
36C26024R0009 0005.pdf PDF
Wage Determination 1.5.24.pdf PDF
Wage Determination 12.22.23.pdf PDF
36C26024R0009 0004.pdf PDF
36C26024R0009 0003.pdf PDF
36C26024R0009 0002.pdf PDF
36C26024R0009 0001.pdf PDF
WD 11.24.23.pdf PDF
668-18-109_Pre Bid Site Walk Sign In Sheet_2023.12.03.pdf PDF
Attachment 17 Security Requirements.pdf PDF
Attachment 18 Contractor Rules of Behavior.pdf PDF
Attachment 4 668-18-109_Supplement to SPEC 01 00 00 Part 1-6-I.pdf PDF
Attachment 15 Wage Determination 11.17.23.pdf PDF
Attachment 2 668-18-109_Project Specifications 1 of 2_R1.pdf PDF
Attachment 5 668-18-109_Project Drawings 1 of 6.pdf PDF
Attachment 13 668-18-109_Lead Sampling Report.pdf PDF
Attachment 6 668-18-109_Project Drawings 2 of 6.pdf PDF
Attachment 19 Calculation of Self Performed Work REV 1.pdf PDF
36C26024R0009.pdf PDF
Attachment 7 668-18-109_Project Drawings 3 of 6.pdf PDF
Attachment 12 668-18-109_Limited Asbestos Good Faith Survey - Addendum 1.pdf PDF
Attachment 16 Price Breakout.xlsx XLSX spreadsheet
Attachment 3 668-18-109_Project Specifications 2 of 2_R1.pdf PDF
Attachment 1 668-18-109_SOW-CON_2023-08-15.pdf PDF
Attachment 8 668-18-109_Project Drawings 4 of 6.pdf PDF
Attachment 11 668-18-109_Limited Asbestos Good Faith Survey.pdf PDF
Attachment 9 668-18-109_Project Drawings 5 of 6.pdf PDF
Attachment 14 668-18-109_DWG Clarification Document_2023-06-22.pdf PDF
Show all 30

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

KEY NOTES

EXISTING EQUIPMENT AND

ASSOCIATED RACEWAYS AND

CONDUCTORS TO BE DEMOLISHED.

EXISTING FEEDER CONDUCTOR TO BE

DEMOLISHED. ASSOCIATED CONDUIT

TO BE REUSED.

EXISTING CIRCUIT BREAKER TO BE

REMOVED AND REPLACED. SALVAGE

EXISTING CIRCUIT BREAKER TO VA.

EXISTING PULL BOX(ES) TO REMAIN.

EXISTING SPACE TO HOUSE NEW

CIRCUIT BREAKER.

EXISTING EQUIPMENT BUSWAY HAS

OTHER LOADS NOT SHOWN ON

DRAWING. IF NEEDED, COORDINATE

WITH VA FOR ALL EXISTING BUSWAY

LOADS.

EXISTING PANELBOARD TO BE

REVISED.

SHEET NOTES

1. REFERENCE ONE-LINE DIAGRAM

ON DRAWING E-602 FOR ALL

REVISIONS.

2. WHERE WORK IS BEING

CONDUCTED, ALL FEEDERS OLDER

THAN 15 YEARS OF AGE, OR IF AGE

CANNOT BE CONFIRMED, SHALL BE

DEMOLISHED AND REPLACED AS

REQUIRED, UNLESS OTHERWISE

NOTED.

EXISTING ATS-3

4P-1200A

EXISTING ATS-5

4P-1200A

EXISTING ATS-4

4P-1200A

EMH-G

A

E

FEEDER 'A2'

FEEDER 'E2'

FEEDER 'A2'

FEEDER 'E2'

EXISTING SWBD 'EDSS'

EXISTING SWBD 'NDSS'

EXISTING SWBD 'EQ1'

TO EMH-O

TO EMH-F

EXISTING (3)#3/0 15-KV &

(1)#2 600VAC GND

A

BU

S

EXISTING

(10) SETS OF: (4)#600KCMIL, 4"C

(2)#3/0

N G

(2)#3/0

EXISTING

(10) SETS OF:

(4)#600KCMIL, 4"C

(2)#3/0

(2)#3/0

N G

EXISTING ATS-6

4P-1200A

EXISTING SWBD 'EQ2'

A

BU

S

3P-800A SPACE

3P-600A SPACE

MAIN

LIFE SAFETY

CRITICAL

EQUIP

A

BU

S

A

BU

S

EQ

U

IP

P

U

LL

B O

X

EQ

U

IP

S

EC

TI

O N

3P-800A SPACE

3P-600A SPACE

3P-600A SPACE

v5 v6 v7 v8

2i"CO

2i"CO

EXISTING

STUB-OUT

BELOW FLR

LINE FOR

FUTURE

FEEDER.

EXISTING

METER

MINIMUM %IZ=8.5

MINIMUM %IZ=8.5

ISC=

ISC =

ISC=

(4)#4/0 & (1)#4GND,2i"C

(2) SETS: (4)#500KCMIL & (1)#1/0 GND, 3i"C

(2) SETS: (3)#500KCMIL & (1)#2/0 GND, 3i"C

(3)#500KCMIL,(1)#4/0 N & (1)#1

GND,3i"C

EXISTING PULL BOX #3

EXISTING PULL

BOXES, (1) PULL

BOX SHOWN FOR

CLARITY

ISC=

ISC =

ISC =

ISC =

ISC =

ISC=

ISC=

ISC =

ISC=

(3)#500KCMIL,(1)#4/0 N & (1)#1

GND,3i"C

DISTRIBUTION EQUIPMENT RATINGS & NOTES

SWBD 'NDSS': MAIN CB = SQUARE-D NW-H FRAME, 100KAIC

BRANCH CB = SQUARE-D RK FRAME, 100KAIC

MINIMUM SYMMETRICAL INTERRUPTING RATING = 50KA

SWBD 'EDSS': MAIN CB = SQUARE-D NW-H FRAME, 100 KAIC

BRANCH CB = SQUARE-D RK FRAME, 100KAIC

MINIMUM SYMMETRICAL INTERRUPTING RATING = 50KA

SWBD 'EQ1': 600A BRANCH = SQUARE-D PG FRAME

400A BRANCH = SQUARE-D DJ-MC FRAME

200A BRANCH = SQUARE-D DJ-MC FRAME

MINIMUM SYMMETRICAL INTERRUPTING RATING = 35KA

SWBD 'EQ2': 400A BRANCH = SQUARE-D DJ-MC FRAME

250A BRANCH = SQUARE-D DJ-MC FRAME

150A BRANCH = SQUARE-D DJ-MC FRAME

MINIMUM SYMMETRICAL INTERRUPTING RATING = 65KA

SWBD 'LS': 400A BRANCH = SQUARE-D DJ-MC FRAME

200A BRANCH = SQUARE-D DJ-MC FRAME

100A BRANCH = SQUARE-D DJ-MC FRAME

MINIMUM SYMMETRICAL INTERRUPTING RATING = 50KA

SWBD 'CB': 800A BRANCH = SQUARE-D PG FRAME

200A BRANCH = SQUARE-D DJ-MC FRAME

100A BRANCH = SQUARE-D DJ-MC FRAME

MINIMUM SYMMETRICAL INTERRUPTING RATING = 50KA

ATS-1 THRU

ATS-6: 30-CYCLE WITHSTAND RATING = 65KA

3-PHASE SYMMETRICAL

FAULT CURRENT VALUE

FOR CLOSED-TRANSITION

POSITION OF TRANSFER

SWITCH

3-PHASE

SYMMETRICAL FAULT

CURRENT VALUE FOR

NON-CLOSED-TRANSITION

POSITION OF

TRANSFER SWITCH

SCALE : NTS

BUILDING 1 - EXISTING PARTIAL ONE-LINE DIAGRAM

- THIS DIAGRAM IS ALL EXISTING EQUIPMENT UNLESS OTHERWISE NOTED

3P-600A SPACE

SPARE

FEEDER 'A2'

FEEDER 'E2'

EXISTING SWBD 'A'

3P-400A

E-601

BUILDING 1 - EXISTING PARTIAL

ONE-LINE DIAGRAM

EXISTING SWBD 'EQ3'

A

BU

S

SPARE

ELEVATOR

CONTROLLER

EXISTING ELEVATOR

CONTROL UNIT

EXISTING PASSENGER

ELEVATOR "P2"400A/3 150A/3

ELEVATOR

CONTROLLER

EXISTING ELEVATOR

CONTROL UNIT

EXISTING PASSENGER

ELEVATOR "P1"400A/3 150A/3

ELEVATOR

CONTROLLER

EXISTING ELEVATOR

CONTROL UNIT

EXISTING SERVICE

ELEVATOR "S3"400A/3 250A/3

EXISTING PULL

BOXES, (1) PULL

BOX SHOWN FOR

CLARITY

EXISTING

PANELBOARD

BEING USED AS A

PULL BOX

(LOCATED IN

ELEVATOR

MACHINE ROOM)

EXISTING (3) SETS OF:(4)#600KCMIL & (1)#4/0 GND, 4"C

EXISTING (3) SETS OF:(4)#600KCMIL & (1)#4/0

GND, 4"C

HUM-2

3P-40A

M

LIEBERT 2 CONDENSER

3P-15A

LIEBERT 1 CONDENSER

3P-15A

PANEL "EB" BLDG 27

MCC-BLDG 27 (025)

3P-200A

BEQB4

3P-150A

3P-70A

3P-70A

3P-100A

LIEBERT 2 100A

3P-100A

LIEBERT 1 100A

3P-400A

EXISTING PNL '2M3' 400A MLO

3P-400A

EXISTING PNL 'NH1M' 400A MLO

EXISTING PNL 'BEQB2D' 400A MLO

3P-400A

EXISTING XFMR T18

13,200: 208Y/120VAC

58,600A 29,300A

58,600A 29,300A

58,600A 29,300A

46,800A

16,600A

18,300A

26,100A

13,700A

14,900A

M

M

M

3P-100A SPACE

3P-100A SPACE

3P-225A SPACE

3P-225A SPACE

3P-225A SPARE

3P-225A SPARE

3P-400A SPARE

3P-1200A

EXISTING XFMR T22

13,200: 208Y/120VAC

1500KVA

3P-1200A

3P-150A SPARE

3P-150A SPARE

3P-250A SPARE

EXISTING X-RAY #3 XFMR

EXISTING PNL '1M2' 800A MLO

EXISTING PNL 'A' 400A MLO

CLOSED

OPEN

OPEN

OPEN

CLOSED

OPEN

OPEN

OPEN

CLOSED

CLOSED

CLOSED

CLOSED

3P-1200A

3P-1200A

3P-1200A

3P-800A

3P-1200A

3P-4000A

3P-225A SPACE

3P-225A SPACE

3P-225A SPACE

3P-400A

3P-600A

3P-400A

3P-600A

3P-200A

3P-600A

3P-1200A

EXISTING EQUIP BUSWAY

3P-1200A

3P-1200A

3P-800A

3P-1200A

3P-4000A

EXISTING XFMR T23

13,200: 208Y/120VAC

1500KVA

TYP.

TYP.3

SPACE

EXISTING (3) SETS OF:(4)#600KCMIL & (1)#4/0

GND, 4"C

EXISTING (3) SETS OF:(4)#600KCMIL & (1)#4/0

GND, 4"C

EXISTING (3) SETS OF:(4)#600KCMIL & (1)#4/0 GND, 4"C

EXISTING (3) SETS OF:(4)#600KCMIL & (1)#4/0 GND, 4"C

EXISTING (3) SETS OF:(4)#600KCMIL & (1)#4/0 GND, 4"C

EXISTING (3) SETS OF:(4)#600KCMIL & (1)#4/0 GND, 4"C

EXISTING PULL

BOXES, (1) PULL

BOX SHOWN FOR

CLARITY

800AS SWBD "9EQ1" 9M 600A

PANEL "9EQ3" 90

MOTOR CONTROL CENTER "MCC3" 600A

PANEL "9EQ2" 9A 100A

PANEL "9EQ4" 9B 225A

M

M

M

DISCONNECT "9M"

OR CONDENSOR

OR CHILLER

REVISED PNL BEQ4 100A(4)#2 & (1)#8GND, 1-1/2"C

EXISTING '3N1'

3P-100A 3P-600A

EXISTING SWBD 'B'

2500A (4)#2 & (1)#8GND, 1-1/2"C EXISTING PANEL '4N3'

ISC = 33,500A

ISC=33,500A

ISC =

ISC=15,600A

13,700A

ISC=58,600A

ISC=58,600A

PhaseARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

A/E:

625 First Ave #301 Seattle, WA, 98104

(206) 590 - 2118

RAY SPEES, PRESIDENT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

STAMPCONSULTANT

321 4 5 6 7 8 9 10

668-18-109

Revisions: Date:

SPEES DESIGN BUILD

REFURBISH AND UPGRADE

ELEVATORS IN BLDG

1 AND 27

11/16/2021

Mann-Grandstaff VA Medical Center

- Spokane, WA

LRL/WNM JPS/FEB 137 OF 143

EXISTING ATS-3

4P-1200A

EXISTING ATS-5

4P-1200A

EXISTING ATS-4

4P-1200A

FEEDER 'A2'

FEEDER 'E2'

FEEDER 'A2'

FEEDER 'E2'

EXISTING SWBD 'EDSS'

EXISTING SWBD 'NDSS'

TO EMH-O

TO EMH-F

EXISTING (3)#3/0 15-KV &

(1)#2 600VAC GND

EXISTING (10) SETS OF:

(4)#600KCMIL, 4"C

(2)#3/0

(2)#3/0

EXISTING

(10) SETS OF:

(4)#600KCMIL, 4"C

(2)#3/0

(2)#3/0

N G

EXISTING ATS-6

4P-1200A

EXISTING SWBD 'EQ2'

A

BU

S

3P-800A SPACE

3P-600A SPACE

MAIN

LIFE SAFETY

CRITICAL

EQUIP

A

BU

S

A

BU

S

EQ

U

IP

P

U

LL

B O

X

EQ

U

IP

S

EC

TI

O N

3P-800A SPACE

3P-600A SPACE

3P-600A SPACE

v5 v6 v7 v8

2i"CO

2i"CO

EXISTING

STUB-OUT

BELOW FLR LINE

FOR FUTURE

FEEDER.

EXISTING

METER

MINIMUM %IZ=8.5

ISC=

EXISTING PULL

BOXES, (1) PULL

BOX SHOWN FOR

CLARITY

DISTRIBUTION EQUIPMENT RATINGS & NOTES

SWBD 'NDSS': MAIN CB = SQUARE-D NW-H FRAME, 100KAIC

BRANCH CB = SQUARE-D RK FRAME, 100KAIC

MINIMUM SYMMETRICAL INTERRUPTING RATING = 50KA

SWBD 'EDSS': MAIN CB = SQUARE-D NW-H FRAME, 100 KAIC

BRANCH CB = SQUARE-D RK FRAME, 100KAIC

MINIMUM SYMMETRICAL INTERRUPTING RATING = 50KA

SWBD 'EQ1': 600A BRANCH = SQUARE-D PG FRAME

400A BRANCH = SQUARE-D DJ-MC FRAME

200A BRANCH = SQUARE-D DJ-MC FRAME

MINIMUM SYMMETRICAL INTERRUPTING RATING = 35KA

SWBD 'EQ2': 400A BRANCH = SQUARE-D DJ-MC FRAME

250A BRANCH = SQUARE-D DJ-MC FRAME

150A BRANCH = SQUARE-D DJ-MC FRAME

MINIMUM SYMMETRICAL INTERRUPTING RATING = 65KA

SWBD 'LS': 400A BRANCH = SQUARE-D DJ-MC FRAME

200A BRANCH = SQUARE-D DJ-MC FRAME

100A BRANCH = SQUARE-D DJ-MC FRAME

MINIMUM SYMMETRICAL INTERRUPTING RATING = 50KA

SWBD 'CB': 800A BRANCH = SQUARE-D PG FRAME

200A BRANCH = SQUARE-D DJ-MC FRAME

100A BRANCH = SQUARE-D DJ-MC FRAME

MINIMUM SYMMETRICAL INTERRUPTING RATING = 50KA

ATS-1 THRU

ATS-6: 30-CYCLE WITHSTAND RATING = 65KA

3-PHASE SYMMETRICAL

FAULT CURRENT VALUE

FOR CLOSED-TRANSITION

POSITION OF TRANSFER

SWITCH

ISC = 3-PHASE SYMMETRICAL

FAULT CURRENT VALUE FOR

NON-CLOSED-TRANSITION

POSITION OF TRANSFER

SWITCH

SCALE : NTS

BUILDING 1 - REVISED PARTIAL ONE-LINE DIAGRAM

- THIS DIAGRAM IS ALL EXISTING EQUIPMENT UNLESS OTHERWISE NOTED

3P-600A SPACE

FEEDER 'A2'

FEEDER 'E2'

EXISTING SWBD 'A'

3P-400A

LSIG

E-602

BUILDING 1 - REVISED PARTIAL

ONE-LINE DIAGRAM

ELEVATOR

CONTROLLER

ELEVATOR CONTROL UNIT

PASSENGER

ELEVATOR "P1"

ELEVATOR

CONTROLLER

ELEVATOR

CONTROL UNIT

SERVICE ELEVATOR "S3"

EXISTING PULL BOXES,

(1) PULL BOX SHOWN

FOR CLARITY

EXISTING XFMR T18

13,200: 208Y/120VAC

56,800A

33,500A

M

M

M

3P-100A SPACE

3P-100A SPACE

3P-225A SPACE

3P-225A SPACE

3P-225A SPARE

3P-225A SPARE

3P-400A SPARE

3P-1200A

3P-1200A

3P-150A SPARE

3P-150A SPARE

3P-250A SPARE

CLOSED

OPEN

OPEN

OPEN

CLOSED

OPEN

OPEN

OPEN

CLOSED

CLOSED

CLOSED

CLOSED

3P-1200A

3P-1200A

3P-1200A

3P-800A

3P-1200A

3P-4000A

3P-1200A

EXISTING EQUIP BUSWAY

3P-1200A

3P-1200A

3P-800A

3P-1200A

3P-4000A

EXISTING XFMR T23

13,200: 208Y/120VAC

1500KVA

KEY NOTES

PROVIDE NEW LSIG CIRCUIT BREAKER. COORDINATE WITH

GENERAL ELECTRIC (GE) MANUFACTURER REPRESENTATIVE

AS REQUIRED. CIRCUIT BREAKER SHALL BE PBII WITH

ENTELLIGUARD TRIP UNIT, OR EQUIPMENT MODEL.

PROVIDE NEW LSIG CIRCUIT BREAKER. COORDINATE WITH

SQUARE-D MANUFACTURER REPRESENTATIVE AS REQUIRED.

CIRCUIT BREAKER SHALL BE #LGA36400U44X, OR EQUIPMENT

MODEL.

PROVIDE NEW LSIG CIRCUIT BREAKER. COORDINATE WITH

EATON MANUFACTURER REPRESENTATIVE AS REQUIRED.

CIRCUIT BREAKER SHALL BE #AKDB3400FT36W, OR

EQUIPMENT MODEL.

PROVIDE (3) 500KCMIL AND (1) 1AWG GND. UTILIZE EXISTING

3-1/2" RACEWAY AND PROVIDE ADDITIONAL 3-1/2" RACEWAYS

AS INDICATED ON PLANS.

REVISED SWITCHBOARD. REFERENCE PANEL SCHEDULE ON

SHEET E-603 FOR ADDITIONAL INFORMATION.

PULL BOX "PB-S3". REFERENCE SHEET EP111 FOR

ADDITIONAL INFORMATION.

PROVIDE (3) 500KCMIL AND (1) 1AWG GND. UTILIZE

EXISTING 3-1/2" RACEWAY AND PROVIDE

ADDITIONAL 3-1/2" RACEWAYS AS INDICATED ON

PLANS.

ELEVATOR CONTROL SWITCH SHALL INCLUDE SHUNT TRIP

DISCONNECT SWITCH AND SHALL BE INTERFACED WITH THE

EXISTING FIRE ALARM CONTROL SYSTEM TO DE-ENERGIZE

CIRCUIT UPON ACTIVATION OF SPRINKLER SYSTEM. PROVIDE

SHUNT TRIP DISCONNECT PER ELEVATOR MANUFACTURER'S

REQUIREMENTS. COORDINATE WITH ELEVATOR

MANUFACTURER AND AHJ AS REQUIRED.

PROVIDE CURRENT SENSORS FOR METERING INDIVIDUAL

FEEDERS AND LOADS. PROVIDE WITH ALL REQUIRED

LABELING, CONNECTIONS, AND APPURTENANCES FOR A

FULLY FUNCTIONAL SYSTEM. INSTALL PER MANUFACTURER

RECOMMENDATIONS. SEE PANEL SCHEDULES FOR

ADDITIONAL INFORMATION. HARDWARE SHALL MATCH VA

FACILITY STANDARD: CENTRICA HARDWARE (CT'S/BRIDGES)

AND POWER RADAR SOFTWARE, REFERENCE SPECIFICATION

25 10 10 FOR ADDITIONAL INFORMATION.

PROVIDE 25HP VFD WITH ALL REQUIRED I/O PER MECHANICAL

DRAWINGS. VFD SHALL PROVIDE 3% INPUT LINE REACTOR

AND INTEGRAL CIRCUIT BREAKER FOR DISCONNECTION.

REVISED PANELBOARD. REFERENCE PANEL SCHEDULE ON

SHEET E-604 FOR ADDITIONAL INFORMATION.

REVISED PANELBOARD. REFERENCE PANEL SCHEDULE ON

DRAWING E-603 FOR ADDITONAL INFORMATION.

PROVIDE CURRENT SENSORS TO METER THE PANEL MAIN.

PROVIDE WITH ALL REQUIRED LABELING, CONNECTIONS, AND

APPURTENANCES FOR A FULLY FUNCTIONAL SYSTEM.

INSTALL PER MANUFACTURER RECOMMENDATIONS. SEE

PANEL SCHEDULES FOR ADDITIONAL INFORMATION.

HARDWARE SHALL MATCH VA FACILITY STANDARD: CENTRICA

HARDWARE(CT'S/BRIDGES) AND POWER RADAR SOFTWARE,

REFERENCE SPECIFICATION

25 10 10 FOR ADDITIONAL INFORMATION.

EXISTING SWBD 'EQ1'

A

BU

S

EXISTING SWBD 'EQ3'

A

BU

S

SPARE

HUM-2

3P-40A

LIEBERT 2 CONDENSER

3P-15A

LIEBERT 1 CONDENSER

3P-15A

PANEL "EB" BLDG 27

MCC-BLDG 27 (025)

3P-200A

BEQB4

3P-150A

3P-70A

3P-70A

3P-100A

LIEBERT 2 100A

3P-100A

LIEBERT 1 100A

3P-400A

EXISTING PNL '2M3' 400A MLO

3P-400A

EXISTING PNL 'NH1M' 400A MLO

EXISTING PNL 'BEQB2D' 400A MLO

3P-400A

3P-225A SPACE

3P-225A SPACE

3P-225A SPACE

3P-600A SPARE

3P-400A

3P-600A

3P-200A

3P-600A

(4)#4/0 & (1)#4GND,2i"C

(2) SETS: (4)#500KCMIL & (1)#1/0 GND, 3i"C

(2) SETS: (3)#500KCMIL & (1)#2/0 GND, 3i"C

EXISTING PULL BOX #3

EXISTING X-RAY #3 XFMR

EXISTING PNL '1M2' 800A MLO

EXISTING PNL 'A' 400A MLO

EXISTING (3) SETS OF:

(4)#600KCMIL &

(1)#4/0 GND, 4"C

EXISTING (3) SETS OF:

(4)#600KCMIL &

(1)#4/0 GND, 4"C

ELEVATOR

CONTROL SWITCH

"ECS-S3", 22 KAIC

ELEVATOR CONTROL SWITCH

"ECS-P1" 22 KAIC

3P-400A

LSIG

3P-400A

LSIG

FLA = 152A

FLA = 184A

800AS

PANEL "9EQ3" 90

MOTOR CONTROL CENTER "MCC3" 600A

PANEL "9EQ2" 9A 100A

PANEL "9EQ4" 9B 225A

SHEET NOTES

1. MANUFACTURER'S CATALOGUE EQUIPMENT NUMBERS

SUBJECT TO CHANGE ANYTIME WITHOUT NOTICE.

COORDINATE WITH MANUFACTURER AS REQUIRED.

2. WHERE WORK IS BEING CONDUCTED, ALL FEEDERS OLDER

THAN 15 YEARS OF AGE, OR IF AGE CANNOT BE CONFIRMED,

SHALL BE DEMOLISHED AND REPLACED AS REQUIRED,

UNLESS OTHERWISE NOTED.

3. ALL WIRING FROM DIFFERENT SOURCES (IE: LIFE SAFETY,

CRITICAL, EQUIPMENT, NORMAL) SHALL BE ROUTED IN

SEPARATE RACEWAYS AND BOXES AS REQUIRED TO

CONFORM WITH NEC 517.31(C)(1).

4. ALL CURRENT SENSORS MAY NOT BE SHOWN ON ONELINE.

SEE PANEL SCHEDULES ON SHEET E-607 FOR ADDITIONAL

INFORMATION.

5. WHERE CONDUIT AND WIRE SIZES ARE NOT EXPLICITLY

SHOWN ON THIS SHEET, REFERENCE BUILDING 1

EQUIPMENT SCHEDULE ON SHEET E-604 FOR ADDITIONAL

INFORMATION.

6. WHERE ADDITIONAL 0-5A CTs ARE REQUIRED FOR

ELECTRICAL POWER METERING PURPOSES, CONTRACTOR

SHALL PROVIDE ALL REQUIRED CABELING, JUNCTION

BOXES/ENCLOSURES, AND APPURTENANCES AS REQUIRED

FOR A COMPLETE AND FUNCTIONAL SYSTEM.

SPD

SPD

400AS 400AF

ST

400AS 400AF

ST

M

M

M

SWBD "9EQ1" 9M 1200A

DISCONNECT

"9M"

OR CONDENSOR

OR CHILLER

VFD

SUPPLY FAN "SF-1"

100/3P

EXISTING PULL BOXES,

(1) PULL BOX SHOWN

FOR CLARITY

REVISED PNL BEQ4 100A(4)#2 & (1)#8GND, 1-1/2"C

EXISTING '3N1'

3P-100A

3P-400A

EXISTING SWBD 'B'

2500A (4)#2 & (1)#8GND, 1-1/2"C

REVISED PANEL '4N3'

MINIMUM %IZ=8.5

EXISTING XFMR T23

13,200: 208Y/120VAC

1500KVA

ISC =58,600A

ISC =29,300A

ISC =29,300A

ISC =58,600A

EXISTING (3) SETS OF:

(4)#600KCMIL &

(1)#4/0 GND, 4"C

EXISTING (3) SETS OF:

(4)#600KCMIL &

(1)#4/0 GND, 4"C

EXISTING (3) SETS OF:

(4)#600KCMIL &

(1)#4/0 GND, 4"C

EXISTING (3) SETS OF:

(4)#600KCMIL &

(1)#4/0 GND, 4"C

ISC=29,300A

ISC=58,600A

ISC =29,300A

ISC =58,600A

EXISTING (3) SETS OF:

(4)#600KCMIL &

(1)#4/0 GND, 4"C

EXISTING (3) SETS OF:

(4)#600KCMIL &

(1)#4/0 GND, 4"C

ISC=26,100A

ISC=46,800A

ISC =14,900A

ISC =18,300A

ISC =13,700A

ISC =16,600A

ISC=13,700A

ISC=15,600A

ELEVATOR

CONTROLLER

ELEVATOR CONTROL UNIT

PASSENGER

ELEVATOR "P2"60

ELEVATOR CONTROL SWITCH

"ECS-P2" 22 KAIC

FLA = 152ASPD

400AS 400AF

ST

ISC = 56,800A

PhaseARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

A/E:

625 First Ave #301 Seattle, WA, 98104

(206) 590 - 2118

RAY SPEES, PRESIDENT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

STAMPCONSULTANT

321 4 5 6 7 8 9 10

668-18-109

Revisions: Date:

SPEES DESIGN BUILD

REFURBISH AND UPGRADE

ELEVATORS IN BLDG

1 AND 27

11/16/2021

Mann-Grandstaff VA Medical Center

- Spokane, WA

LRL/WNM JPS/FEB

SUMP

PUMP

"SP-1"

E-603

BUILDING 1 - ELECTRICAL LOAD

SCHEDULES

KEY NOTES

SHEET NOTES

1. WHERE WORK IS BEING CONDUCTED, ALL FEEDERS

OLDER THAN 15 YEARS OF AGE, OR IF AGE CANNOT

BE CONFIRMED, SHALL BE DEMOLISHED AND

REPLACED AS REQUIRED, UNLESS OTHERWISE

NOTED.

2. WHERE ADDITIONAL 0-5A CTs ARE REQUIRED FOR

ELECTRICAL POWER METERING PURPOSES,

CONTRACTOR SHALL PROVIDE ALL REQUIRED

CABELING, JUNCTION BOXES/ENCLOSURES, AND

APPURTENANCES AS REQUIRED FOR A COMPLETE

AND FUNCTIONAL SYSTEM.

REVISED PANELBOARD CIRCUITS AND/OR LOADS.

PROVIDE CIRCUIT BREAKERS AND PANEL

DIRECTORY AS REQUIRED.

A RECENT 30-DAY POWER DEMAND STUDY WAS

CONDUCTED ON PANEL BEQ4 AND RESULTED IN A

MAXIMUM LOAD OF 58.7 AMPS. THIS PANEL

SCHEDULE SHOWS THE ADDED LOAD FOR THIS

PROJECT. WITH THE ADDED LOAD AND THE

METERED LOAD, IT PROVIDES A TOTAL SUM OF 65.3

AMPS; THIS IS WELL BELOW 80% RATING OF THE

100A PANEL (OR 80 AMPS) AND THEREFORE HAS

ADEQUATE CAPACITY FOR THE NEW LOAD.

PROVIDE CURRENT SENSORS TO METER THE PANEL

MAIN. PROVIDE WITH ALL REQUIRED LABELING,

CONNECTIONS, AND APPURTENANCES FOR A FULLY

FUNCTIONAL SYSTEM. INSTALL PER MANUFACTURER

RECOMMENDATIONS. HARDWARE SHALL MATCH VA

FACILITY STANDARD: CENTRICA HARDWARE

(CT'S/BRIDGES) AND POWER RADAR SOFTWARE,

REFERENCE SPECIFICATION 25 10 10 FOR

ADDITIONAL INFORMATION.

PROVIDE CURRENT SENSORS FOR METERING

INDICATED INDIVIDUAL FEEDERS AND LOADS.

PROVIDE WITH ALL REQUIRED LABELING,

CONNECTIONS, AND APPURTENANCES FOR A FULLY

FUNCTIONAL SYSTEM. INSTALL PER MANUFACTURER

RECOMMENDATIONS. HARDWARE SHALL MATCH VA

FACILITY STANDARD: CENTRICA HARDWARE

(CT'S/BRIDGES) AND POWER RADAR SOFTWARE,

REFERENCE SPECIFICATION 25 10 10 FOR

ADDITIONAL INFORMATION.

METER PANEL "4N3" FEEDER LOAD FROM UPSTREAM

PANEL "3N1" LOCATED IN ROOM A344. REFERENCE

KEY NOTE "3" ON THIS SHEET FOR REQUIRED

METERING INFORMATION.

PhaseARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

A/E:

625 First Ave #301 Seattle, WA, 98104

(206) 590 - 2118

RAY SPEES, PRESIDENT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

STAMPCONSULTANT

321 4 5 6 7 8 9 10

668-18-109

Revisions: Date:

SPEES DESIGN BUILD

REFURBISH AND UPGRADE

ELEVATORS IN BLDG

1 AND 27

11/16/2021

Mann-Grandstaff VA Medical Center

- Spokane, WA

LRL/WNM JPS/FEB

5 3

E-604

BUILDING 1 -

ELECTRICAL SCHEDULES

EXISTING CIRCUITS AND

CORRESPONDING LOADS TO BE

REMOVED. REFERENCE REVISED

PANEL SCHEDULE FOR ADDITIONAL

INFORMATION.

REVISED PANELBOARD CIRCUITS

AND/OR LOADS. PROVIDE CIRCUIT

BREAKERS AND PANEL DIRECTORY AS

REQUIRED.

FAN COIL UNIT "FC-1" SHALL UTILIZE

EXISTING CIRCUIT (FEEDER BREAKER,

CONDUIT, AND WIRE). REFERENCE

DRAWINGS ED107 AND EP107 FOR

ADDITIONAL INFORMATION.

A RECENT 30-DAY POWER DEMAND

STUDY WAS CONDUCTED ON PANEL

8LS1 AND RESULTED IN A MAXIMUM

LOAD OF 16 AMPS. THIS PANEL

SCHEDULE SHOWS THE ADDED LOAD

FOR THIS PROJECT. WITH THE ADDED

LOAD AND THE METERED LOAD, IT

PROVIDES A TOTAL SUM OF 38.5 AMPS;

THIS IS BELOW 80% RATING OF THE

50A PANEL (OR 40 AMPS) AND

THEREFORE HAS ADEQUATE CAPACITY

FOR THE NEW LOAD.

PROVIDE CURRENT SENSORS TO

METER THE PANEL MAIN. PROVIDE

WITH ALL REQUIRED LABELING,

CONNECTIONS, AND APPURTENANCES

FOR A FULLY FUNCTIONAL SYSTEM.

INSTALL PER MANUFACTURER

RECOMMENDATIONS. HARDWARE

SHALL MATCH VA FACILITY STANDARD:

CENTRICA HARDWARE (CT'S/BRIDGES)

AND POWER RADAR SOFTWARE,

REFERENCE SPECIFICATION 25 10 10

FOR ADDITIONAL INFORMATION.

PROVIDE CURRENT SENSORS FOR

METERING INDICATED INDIVIDUAL

FEEDERS AND LOADS. PROVIDE WITH

ALL REQUIRED LABELING,

CONNECTIONS, AND APPURTENANCES

FOR A FULLY FUNCTIONAL SYSTEM.

INSTALL PER MANUFACTURER

RECOMMENDATIONS. HARDWARE

SHALL MATCH VA FACILITY STANDARD:

CENTRICA HARDWARE (CT'S/BRIDGES)

AND POWER RADAR SOFTWARE,

REFERENCE SPECIFICATION 25 10 10

FOR ADDITIONAL INFORMATION.

METER PANEL "8LS1" LOAD FROM

UPSTREAM RISER CLOSET LOCATED IN

ROOM A729A. REFERENCE KEY NOTE

"5" ON THIS SHEET FOR REQUIRED

METERING INFORMATION.

1. WHERE WORK IS BEING

CONDUCTED, ALL FEEDERS OLDER

THAN 15 YEARS OF AGE, OR IF AGE

CANNOT BE CONFIRMED, SHALL BE

DEMOLISHED AND REPLACED AS

REQUIRED, UNLESS OTHERWISE

NOTED.

2. WHERE ADDITIONAL 0-5A CTs ARE

REQUIRED FOR ELECTRICAL

POWER METERING PURPOSES,

CONTRACTOR SHALL PROVIDE ALL

REQUIRED CABELING, JUNCTION

BOXES/ENCLOSURES, AND

APPURTENANCES AS REQUIRED

FOR A COMPLETE AND

FUNCTIONAL SYSTEM.

PhaseARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

A/E:

625 First Ave #301 Seattle, WA, 98104

(206) 590 - 2118

RAY SPEES, PRESIDENT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

STAMPCONSULTANT

321 4 5 6 7 8 9 10

668-18-109

Revisions: Date:

SPEES DESIGN BUILD

REFURBISH AND UPGRADE

ELEVATORS IN BLDG

1 AND 27

11/16/2021

Mann-Grandstaff VA Medical Center

- Spokane, WA

LRL/WNM JPS/FEB

KEY NOTES

EXISTING EQUIPMENT AND

ASSOCIATED RACEWAYS AND

CONDUCTORS TO BE DEMOLISHED

UNLESS OTHERWISE NOTED.

EXISTING CONDUCTORS TO BE

DEMOLISHED BACK TO SOURCE.

EXISTING RACEWAY TO REMAIN.

EXISTING CIRCUIT BREAKER TO BE

REMOVED AND REPLACED.

EXISTING PANEL TO BE REVISED.

REFERENCE SHEETS E-606 AND E-607

FOR ADDITIONAL INFORMATION.

SHEET NOTES

1. REFERENCE ONE-LINE DIAGRAM

ON DRAWING E-606 FOR ALL

REVISIONS.

2. WHERE WORK IS BEING

CONDUCTED, ALL FEEDERS OLDER

THAN 15 YEARS OF AGE, OR IF AGE

CANNOT BE CONFIRMED, SHALL BE

DEMOLISHED AND REPLACED AS

REQUIRED, UNLESS OTHERWISE

NOTED.

3P-400A

3P-200A

3P-200A

3P-100A3P-1000AEXISTING PULL BOX

EXISTING SECONDARY FEEDER

3 SETS 4#400 KCMIL-3"C

4.5% IMPEDANCE (MIN)

T300

EXISTING 300 KVA

PADMOUNT TRANSFORMER

EXISTING 'MDS' 1000A MAIN

DISTRIBUTION SWITCHBOARD

208Y/120V-30, 4 WIRE

4#3/0, 1#6G-2 1/2"C (EXISTING)

4#3/0, 1#6G-2 1/2"C (EXISTING)

4#1, 1#8G-2"C (EXISTING)

2 SETS 4#4/0, 1#2G-2 1/2"C (EXISTING)

EXISTING PANEL 'P'

EXISTING PANEL 'M'

EXISTING PANEL 'L'

3P-100A/60AF

EXISTING MAIN SWITCH

SPACE

SPACE

3P-400A

3P-250A

3P-200A

3P-100A

3P-150A

3P-400A

EXISTING 'DP' 400A DISTRIBUTION PANEL

208Y/120V-30, 4 WIRE 42KAIC

3P-100A

3P-100A

SPARE

SPARE

10KAIC

10KAIC

10KAIC

EXISTING FEED THROUGH LUGS

3P-250A

ENCLOSED

SHUNT TRIP

CIRCUIT

BREAKER

EXISTING PANEL 'LS1'

10KAIC

EXISTING 3P-100A/100AF BUS

TAP DISCONNECT SWITCH

EXISTING LIFE SAFETY

BRANCH BUS DUCT

EXISTING PANEL 'CB1'

10KAIC

EXISTING 3P-100A/100AF BUS TAP

DISCONNECT SWITCH

EXISTING CRITICAL

BRANCH BUS DUCT

EXISTING PANEL 'EB'

10KAIC

EXISTING 3P-100A/100AF BUS TAP

DISCONNECT SWITCH

EXISTING CRITICAL

BRANCH BUS DUCT

EXISTING PANEL 'LSL'

10KAIC

EXISTING FUSED DISCONNECT

3P-200A/200AF

EXISTING MCC

22KAIC

E-605

SCALE : NTS

BUILDING 27 - EXISTING ONE-LINE DIAGRAM (DEDUCTIVE BID ALTERNATE)

- THIS DIAGRAM IS ALL EXISTING EQUIPMENT UNLESS OTHERWISE NOTED

BUILDING 27 - EXISTING ONE-LINE

DIAGRAM (DEDUCTIVE BID ALTERNATE)

EXISTING PULL BOX

EXISTING PANEL 'LL'

EXISTING PANEL 'PL'

EXISTING PANEL 'P1A'

EXISTING PANEL 'L1'

ELEVATOR

DEDUCTIVE BID ALTERNATE

EXISTING

ELEVATOR

CONTROL

UNIT

PhaseARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

A/E:

625 First Ave #301 Seattle, WA, 98104

(206) 590 - 2118

RAY SPEES, PRESIDENT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

STAMPCONSULTANT

321 4 5 6 7 8 9 10

668-18-109

Revisions: Date:

SPEES DESIGN BUILD

REFURBISH AND UPGRADE

ELEVATORS IN BLDG

1 AND 27

11/16/2021

Mann-Grandstaff VA Medical Center

- Spokane, WA

LRL/WNM JPS/FEB 141 OF 143

10KAIC

10KAIC

10KAIC

EXISTING FEED THROUGH LUGS

10KAIC

EXISTING 3P-100A/100AF BUS

TAP DISCONNECT SWITCH

EXISTING LIFE

SAFETY BRANCH

BUS DUCT

10KAIC

EXISTING 3P-100A/100AF BUS

TAP DISCONNECT SWITCH

EXISTING CRITICAL

BRANCH BUS DUCT

10KAIC

EXISTING 3P-100A/100AF BUS

TAP DISCONNECT SWITCH

EXISTING CRITICAL

BRANCH BUS DUCT

10KAIC

3P-200A/200AF

EXISTING FUSED

DISCONNECT

22KAIC

E-606

SCALE : NTS

BUILDING 27 - REVISED ONE-LINE DIAGRAM (DEDUCTIVE BID ALTERNATE)

- THIS DIAGRAM IS ALL EXISTING EQUIPMENT UNLESS OTHERWISE NOTED

BUILDING 27 - REVISED ONE-LINE

DIAGRAM (DEDUCTIVE BID ALTERNATE)

EXISTING PULL BOX

EXISTING PANEL 'LL'

EXISTING PANEL 'PL'

EXISTING PANEL 'P1A'

EXISTING PANEL 'L1'

KEY NOTES

PROVIDE LSIG CIRCUIT BREAKER.

COORDINATE WITH EQUIPMENT

GENERAL ELECTRIC (GE)

MANUFACTURER REPRESENTATIVE AS

REQUIRED.

PROVIDE (3) 250KCMIL AND (1) 4AWG

GND IN 3"C.

PROVIDE (3) 250KCMIL AND (1) 4AWG

GND IN EXISTING CONDUIT.

REVISED PANEL "LSL" REFERENCE

ASSOCIATED PANEL SCHEDULE ON

SHEET E-607 FOR ADDITIONAL

INFORMATION.

ELEVATOR CONTROL SWITCH SHALL

INCLUDE SHUNT TRIP DISCONNECT

SWITCH AND SHALL BE INTERFACED

WITH THE EXISTING FIRE ALARM

CONTROL SYSTEM TO DE-ENERGIZE

CIRCUIT UPON ACTIVATION OF

SPRINKLER SYSTEM. PROVIDE SHUNT

TRIP DISCONNECT PER ELEVATOR

MANUFACTURER'S REQUIREMENTS.

COORDINATE WITH ELEVATOR

MANUFACTURER AND AHJ AS

REQUIRED.

PROVIDE CURRENT SENSORS FOR

METERING INDIVIDUAL FEEDERS AND

LOADS. PROVIDE WITH ALL REQUIRED

LABELING, CONNECTIONS, AND

APPURTENANCES FOR A FULLY

FUNCTIONAL SYSTEM. INSTALL PER

MANUFACTURER RECOMMENDATIONS.

SEE PANEL SCHEDULES FOR

ADDITIONAL INFORMATION. HARDWARE

SHALL MATCH VA FACILITY STANDARD:

CENTRICA HARDWARE (CT'S/BRIDGES)

AND POWER RADAR SOFTWARE,

REFERENCE SPECIFICATION 25 10 10

FOR ADDITIONAL INFORMATION.

PROVIDE CURRENT SENSORS TO

METER THE PANEL MAIN. PROVIDE

WITH ALL REQUIRED LABELING,

CONNECTIONS, AND APPURTENANCES

FOR A FULLY FUNCTIONAL SYSTEM.

INSTALL PER MANUFACTURER

RECOMMENDATIONS. SEE PANEL

SCHEDULES FOR ADDITIONAL

INFORMATION. HARDWARE SHALL

MATCH VA FACILITY STANDARD:

CENTRICA HARDWARE (CT'S/BRIDGES)

AND POWER RADAR SOFTWARE,

REFERENCE SPECIFICATION 25 10 10

FOR ADDITIONAL INFORMATION.

EXISTING PULL BOX

EXISTING SECONDARY

FEEDER 3 SETS 4#400

KCMIL-3"C

4.5% IMPEDANCE (MIN)

T300

EXISTING 300 KVA

PADMOUNT

TRANSFORMER

EXISTING 'MDS' 1000A

MAIN DISTRIBUTION SWITCHBOARD

208Y/120V-30, 4 WIRE

4#3/0, 1#6G-2 1/2"C (EXISTING)

4#3/0, 1#6G-2 1/2"C (EXISTING)

4#1, 1#8G-2"C (EXISTING)

2 SETS 4#4/0, 1#2G-2 1/2"C (EXISTING)

EXISTING PANEL 'L'

3P-100A/60AF

EXISTING MAIN

SWITCH

EXISTING 'DP' 400A

DISTRIBUTION PANEL

208Y/120V-30, 4 WIRE 42KAIC

SPARE

SPARE

3P-100A

3P-100A3P-400A

3P-150A

3P-100A

3P-200A

3P-400A

SPACE

SPACE

EXISTING PANEL 'M'

EXISTING PANEL 'P'

3P-1000A 3P-100A

3P-200A

3P-200A

3P-400A

MCC

PANEL 'LSL'

PANEL 'EB'

PANEL 'CB1'

PANEL 'LS1'

3P-250A

LSIG

ELEVATOR

CONTROL SWITCH

"ECS-P4", 42KAIC

PASSENGER

ELEVATOR "P4"40

FLA = 111ASPD

DEDUCTIVE BID ALTERNATE

5ELEVATOR

CONTROL

UNIT

SHEET NOTES

1. MANUFACTURER'S CATALOGUE

EQUIPMENT NUMBERS SUBJECT TO

CHANGE ANYTIME WITHOUT

NOTICE. COORDINATE WITH

MANUFACTURER AS REQUIRED.

2. WHERE WORK IS BEING

CONDUCTED, ALL FEEDERS OLDER

THAN 15 YEARS OF AGE, OR IF AGE

CANNOT BE CONFIRMED, SHALL BE

DEMOLISHED AND REPLACED AS

REQUIRED, UNLESS OTHERWISE

NOTED.

3. ALL WIRING FROM DIFFERENT

SOURCES (IE: LIFE SAFETY,

CRITICAL, EQUIPMENT, NORMAL)

SHALL BE ROUTED IN SEPARATE

RACEWAYS AND BOXES AS

REQUIRED TO CONFORM WITH NEC

517.31(C)(1).

4. ALL CURRENT SENSORS MAY NOT

BE SHOWN ON ONELINE. SEE

PANEL SCHEDULES ON SHEET

E-607 FOR ADDITIONAL

INFORMATION.

5. WHERE ADDITIONAL 0-5A CTs ARE

REQUIRED FOR ELECTRICAL

POWER METERING PURPOSES,

CONTRACTOR SHALL PROVIDE ALL

REQUIRED CABELING, JUNCTION

BOXES/ENCLOSURES, AND

APPURTENANCES AS REQUIRED

FOR A COMPLETE AND

FUNCTIONAL SYSTEM.

400AS 250AF

ST

PhaseARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

A/E:

625 First Ave #301 Seattle, WA, 98104

(206) 590 - 2118

RAY SPEES, PRESIDENT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

STAMPCONSULTANT

321 4 5 6 7 8 9 10

668-18-109

Revisions: Date:

SPEES DESIGN BUILD

REFURBISH AND UPGRADE

ELEVATORS IN BLDG

1 AND 27

11/16/2021

Mann-Grandstaff VA Medical Center

- Spokane, WA

LRL/WNM JPS/FEB

E-607

BUILDING 27 - ELECTRICAL SCHEDULES

(DEDUCTIVE BID ALTERNATE)

SCALE : NTS

BUILDING 27 - ELECTRICAL SCHEDULES (DEDUCTIVE BID ALTERNATE)1

KEY NOTES

EXISTING CIRCUITS AND

CORRESPONDING LOADS TO BE

REMOVED. REFERENCE REVISED

PANEL SCHEDULE FOR ADDITIONAL

INFORMATION.

REVISED PANELBOARD CIRCUITS

AND/OR LOADS. PROVIDE CIRCUIT

BREAKERS AND PANEL DIRECTORY AS

REQUIRED.

PANELS SCHEDULES ARE SHOWN ONLY

TO INDICATE THE OVERALL LOAD IS

NOT CHANGING DUE TO THE ELEVATOR

BEING THE SAME HP.

PROVIDE CURRENT SENSORS TO

METER THE PANEL MAIN. PROVIDE

WITH ALL REQUIRED LABELING,

CONNECTIONS, AND APPURTENANCES

FOR A FULLY FUNCTIONAL SYSTEM.

INSTALL PER MANUFACTURER

RECOMMENDATIONS. HARDWARE

SHALL MATCH VA FACILITY STANDARD:

CENTRICA HARDWARE (CT'S/BRIDGES)

AND POWER RADAR SOFTWARE,

REFERENCE SPECIFICATION 25 10 10

FOR ADDITIONAL INFORMATION.

PROVIDE CURRENT SENSORS FOR

METERING INDIVIDUAL FEEDERS AND

LOADS. PROVIDE WITH ALL REQUIRED

LABELING, CONNECTIONS, AND

APPURTENANCES FOR A FULLY

FUNCTIONAL SYSTEM. INSTALL PER

MANUFACTURER RECOMMENDATIONS.

HARDWARE SHALL MATCH VA FACILITY

STANDARD: CENTRICA HARDWARE

(CT'S/BRIDGES) AND POWER RADAR

SOFTWARE, REFERENCE

SPECIFICATION 25 10 10 FOR

ADDITIONAL INFORMATION.

DEDUCTIVE BID ALTERNATE

SHEET NOTES

1. WHERE WORK IS BEING

CONDUCTED, ALL FEEDERS OLDER

THAN 15 YEARS OF AGE, OR IF AGE

CANNOT BE CONFIRMED, SHALL BE

DEMOLISHED AND REPLACED AS

REQUIRED, UNLESS OTHERWISE

NOTED.

2. WHERE ADDITIONAL 0-5A CTs ARE

REQUIRED FOR ELECTRICAL

POWER METERING PURPOSES,

CONTRACTOR SHALL PROVIDE ALL

REQUIRED CABELING, JUNCTION

BOXES/ENCLOSURES,

APPURTENANCES AS REQUIRED

FOR COMPLETE AND FUNCTIONAL

SYSTEM.

PhaseARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

A/E:

625 First Ave #301 Seattle, WA, 98104

(206) 590 - 2118

RAY SPEES, PRESIDENT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

STAMPCONSULTANT

321 4 5 6 7 8 9 10

668-18-109

Revisions: Date:

SPEES DESIGN BUILD

REFURBISH AND UPGRADE

ELEVATORS IN BLDG

1 AND 27

11/16/2021

Mann-Grandstaff VA Medical Center

- Spokane, WA

LRL/WNM JPS/FEB

2 5