This file attachment relates to a federal contract solicitation for elevator refurbishment and upgrades. The solicitation number is 36C26024R0009 and is titled "Y1DA--CON-NRM 668-18-109 Refurbish and Upgrade Elevators in Bldg 1 and 27." It was issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 20 for elevator modernization work at two buildings located at an unspecified VA medical center. Responses were due on an unspecified date, with award anticipated by an unspecified future date. The 16MB file attachment contains project drawings related to the scope of work.
View the file
Other files
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
KEY NOTES
EXISTING EQUIPMENT AND
ASSOCIATED RACEWAYS AND
CONDUCTORS TO BE DEMOLISHED.
EXISTING FEEDER CONDUCTOR TO BE
DEMOLISHED. ASSOCIATED CONDUIT
TO BE REUSED.
EXISTING CIRCUIT BREAKER TO BE
REMOVED AND REPLACED. SALVAGE
EXISTING CIRCUIT BREAKER TO VA.
EXISTING PULL BOX(ES) TO REMAIN.
EXISTING SPACE TO HOUSE NEW
CIRCUIT BREAKER.
EXISTING EQUIPMENT BUSWAY HAS
OTHER LOADS NOT SHOWN ON
DRAWING. IF NEEDED, COORDINATE
WITH VA FOR ALL EXISTING BUSWAY
LOADS.
EXISTING PANELBOARD TO BE
REVISED.
SHEET NOTES
1. REFERENCE ONE-LINE DIAGRAM
ON DRAWING E-602 FOR ALL
REVISIONS.
2. WHERE WORK IS BEING
CONDUCTED, ALL FEEDERS OLDER
THAN 15 YEARS OF AGE, OR IF AGE
CANNOT BE CONFIRMED, SHALL BE
DEMOLISHED AND REPLACED AS
REQUIRED, UNLESS OTHERWISE
NOTED.
EXISTING ATS-3
4P-1200A
EXISTING ATS-5
4P-1200A
EXISTING ATS-4
4P-1200A
EMH-G
A
E
FEEDER 'A2'
FEEDER 'E2'
FEEDER 'A2'
FEEDER 'E2'
EXISTING SWBD 'EDSS'
EXISTING SWBD 'NDSS'
EXISTING SWBD 'EQ1'
TO EMH-O
TO EMH-F
EXISTING (3)#3/0 15-KV &
(1)#2 600VAC GND
A
BU
S
EXISTING
(10) SETS OF: (4)#600KCMIL, 4"C
(2)#3/0
N G
(2)#3/0
EXISTING
(10) SETS OF:
(4)#600KCMIL, 4"C
(2)#3/0
(2)#3/0
N G
EXISTING ATS-6
4P-1200A
EXISTING SWBD 'EQ2'
A
BU
S
3P-800A SPACE
3P-600A SPACE
MAIN
LIFE SAFETY
CRITICAL
EQUIP
A
BU
S
A
BU
S
EQ
U
IP
P
U
LL
B O
X
EQ
U
IP
S
EC
TI
O N
3P-800A SPACE
3P-600A SPACE
3P-600A SPACE
v5 v6 v7 v8
2i"CO
2i"CO
EXISTING
STUB-OUT
BELOW FLR
LINE FOR
FUTURE
FEEDER.
EXISTING
METER
MINIMUM %IZ=8.5
MINIMUM %IZ=8.5
ISC=
ISC =
ISC=
(4)#4/0 & (1)#4GND,2i"C
(2) SETS: (4)#500KCMIL & (1)#1/0 GND, 3i"C
(2) SETS: (3)#500KCMIL & (1)#2/0 GND, 3i"C
(3)#500KCMIL,(1)#4/0 N & (1)#1
GND,3i"C
EXISTING PULL BOX #3
EXISTING PULL
BOXES, (1) PULL
BOX SHOWN FOR
CLARITY
ISC=
ISC =
ISC =
ISC =
ISC =
ISC=
ISC=
ISC =
ISC=
(3)#500KCMIL,(1)#4/0 N & (1)#1
GND,3i"C
DISTRIBUTION EQUIPMENT RATINGS & NOTES
SWBD 'NDSS': MAIN CB = SQUARE-D NW-H FRAME, 100KAIC
BRANCH CB = SQUARE-D RK FRAME, 100KAIC
MINIMUM SYMMETRICAL INTERRUPTING RATING = 50KA
SWBD 'EDSS': MAIN CB = SQUARE-D NW-H FRAME, 100 KAIC
BRANCH CB = SQUARE-D RK FRAME, 100KAIC
MINIMUM SYMMETRICAL INTERRUPTING RATING = 50KA
SWBD 'EQ1': 600A BRANCH = SQUARE-D PG FRAME
400A BRANCH = SQUARE-D DJ-MC FRAME
200A BRANCH = SQUARE-D DJ-MC FRAME
MINIMUM SYMMETRICAL INTERRUPTING RATING = 35KA
SWBD 'EQ2': 400A BRANCH = SQUARE-D DJ-MC FRAME
250A BRANCH = SQUARE-D DJ-MC FRAME
150A BRANCH = SQUARE-D DJ-MC FRAME
MINIMUM SYMMETRICAL INTERRUPTING RATING = 65KA
SWBD 'LS': 400A BRANCH = SQUARE-D DJ-MC FRAME
200A BRANCH = SQUARE-D DJ-MC FRAME
100A BRANCH = SQUARE-D DJ-MC FRAME
MINIMUM SYMMETRICAL INTERRUPTING RATING = 50KA
SWBD 'CB': 800A BRANCH = SQUARE-D PG FRAME
200A BRANCH = SQUARE-D DJ-MC FRAME
100A BRANCH = SQUARE-D DJ-MC FRAME
MINIMUM SYMMETRICAL INTERRUPTING RATING = 50KA
ATS-1 THRU
ATS-6: 30-CYCLE WITHSTAND RATING = 65KA
3-PHASE SYMMETRICAL
FAULT CURRENT VALUE
FOR CLOSED-TRANSITION
POSITION OF TRANSFER
SWITCH
3-PHASE
SYMMETRICAL FAULT
CURRENT VALUE FOR
NON-CLOSED-TRANSITION
POSITION OF
TRANSFER SWITCH
SCALE : NTS
BUILDING 1 - EXISTING PARTIAL ONE-LINE DIAGRAM
- THIS DIAGRAM IS ALL EXISTING EQUIPMENT UNLESS OTHERWISE NOTED
3P-600A SPACE
SPARE
FEEDER 'A2'
FEEDER 'E2'
EXISTING SWBD 'A'
3P-400A
E-601
BUILDING 1 - EXISTING PARTIAL
ONE-LINE DIAGRAM
EXISTING SWBD 'EQ3'
A
BU
S
SPARE
ELEVATOR
CONTROLLER
EXISTING ELEVATOR
CONTROL UNIT
EXISTING PASSENGER
ELEVATOR "P2"400A/3 150A/3
ELEVATOR
CONTROLLER
EXISTING ELEVATOR
CONTROL UNIT
EXISTING PASSENGER
ELEVATOR "P1"400A/3 150A/3
ELEVATOR
CONTROLLER
EXISTING ELEVATOR
CONTROL UNIT
EXISTING SERVICE
ELEVATOR "S3"400A/3 250A/3
EXISTING PULL
BOXES, (1) PULL
BOX SHOWN FOR
CLARITY
EXISTING
PANELBOARD
BEING USED AS A
PULL BOX
(LOCATED IN
ELEVATOR
MACHINE ROOM)
EXISTING (3) SETS OF:(4)#600KCMIL & (1)#4/0 GND, 4"C
EXISTING (3) SETS OF:(4)#600KCMIL & (1)#4/0
GND, 4"C
HUM-2
3P-40A
M
LIEBERT 2 CONDENSER
3P-15A
LIEBERT 1 CONDENSER
3P-15A
PANEL "EB" BLDG 27
MCC-BLDG 27 (025)
3P-200A
BEQB4
3P-150A
3P-70A
3P-70A
3P-100A
LIEBERT 2 100A
3P-100A
LIEBERT 1 100A
3P-400A
EXISTING PNL '2M3' 400A MLO
3P-400A
EXISTING PNL 'NH1M' 400A MLO
EXISTING PNL 'BEQB2D' 400A MLO
3P-400A
EXISTING XFMR T18
13,200: 208Y/120VAC
58,600A 29,300A
58,600A 29,300A
58,600A 29,300A
46,800A
16,600A
18,300A
26,100A
13,700A
14,900A
M
M
M
3P-100A SPACE
3P-100A SPACE
3P-225A SPACE
3P-225A SPACE
3P-225A SPARE
3P-225A SPARE
3P-400A SPARE
3P-1200A
EXISTING XFMR T22
13,200: 208Y/120VAC
1500KVA
3P-1200A
3P-150A SPARE
3P-150A SPARE
3P-250A SPARE
EXISTING X-RAY #3 XFMR
EXISTING PNL '1M2' 800A MLO
EXISTING PNL 'A' 400A MLO
CLOSED
OPEN
OPEN
OPEN
CLOSED
OPEN
OPEN
OPEN
CLOSED
CLOSED
CLOSED
CLOSED
3P-1200A
3P-1200A
3P-1200A
3P-800A
3P-1200A
3P-4000A
3P-225A SPACE
3P-225A SPACE
3P-225A SPACE
3P-400A
3P-600A
3P-400A
3P-600A
3P-200A
3P-600A
3P-1200A
EXISTING EQUIP BUSWAY
3P-1200A
3P-1200A
3P-800A
3P-1200A
3P-4000A
EXISTING XFMR T23
13,200: 208Y/120VAC
1500KVA
TYP.
TYP.3
SPACE
EXISTING (3) SETS OF:(4)#600KCMIL & (1)#4/0
GND, 4"C
EXISTING (3) SETS OF:(4)#600KCMIL & (1)#4/0
GND, 4"C
EXISTING (3) SETS OF:(4)#600KCMIL & (1)#4/0 GND, 4"C
EXISTING (3) SETS OF:(4)#600KCMIL & (1)#4/0 GND, 4"C
EXISTING (3) SETS OF:(4)#600KCMIL & (1)#4/0 GND, 4"C
EXISTING (3) SETS OF:(4)#600KCMIL & (1)#4/0 GND, 4"C
EXISTING PULL
BOXES, (1) PULL
BOX SHOWN FOR
CLARITY
800AS SWBD "9EQ1" 9M 600A
PANEL "9EQ3" 90
MOTOR CONTROL CENTER "MCC3" 600A
PANEL "9EQ2" 9A 100A
PANEL "9EQ4" 9B 225A
M
M
M
DISCONNECT "9M"
OR CONDENSOR
OR CHILLER
REVISED PNL BEQ4 100A(4)#2 & (1)#8GND, 1-1/2"C
EXISTING '3N1'
3P-100A 3P-600A
EXISTING SWBD 'B'
2500A (4)#2 & (1)#8GND, 1-1/2"C EXISTING PANEL '4N3'
ISC = 33,500A
ISC=33,500A
ISC =
ISC=15,600A
13,700A
ISC=58,600A
ISC=58,600A
PhaseARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
A/E:
625 First Ave #301 Seattle, WA, 98104
(206) 590 - 2118
RAY SPEES, PRESIDENT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
STAMPCONSULTANT
321 4 5 6 7 8 9 10
668-18-109
Revisions: Date:
SPEES DESIGN BUILD
REFURBISH AND UPGRADE
ELEVATORS IN BLDG
1 AND 27
11/16/2021
Mann-Grandstaff VA Medical Center
- Spokane, WA
LRL/WNM JPS/FEB 137 OF 143
EXISTING ATS-3
4P-1200A
EXISTING ATS-5
4P-1200A
EXISTING ATS-4
4P-1200A
FEEDER 'A2'
FEEDER 'E2'
FEEDER 'A2'
FEEDER 'E2'
EXISTING SWBD 'EDSS'
EXISTING SWBD 'NDSS'
TO EMH-O
TO EMH-F
EXISTING (3)#3/0 15-KV &
(1)#2 600VAC GND
EXISTING (10) SETS OF:
(4)#600KCMIL, 4"C
(2)#3/0
(2)#3/0
EXISTING
(10) SETS OF:
(4)#600KCMIL, 4"C
(2)#3/0
(2)#3/0
N G
EXISTING ATS-6
4P-1200A
EXISTING SWBD 'EQ2'
A
BU
S
3P-800A SPACE
3P-600A SPACE
MAIN
LIFE SAFETY
CRITICAL
EQUIP
A
BU
S
A
BU
S
EQ
U
IP
P
U
LL
B O
X
EQ
U
IP
S
EC
TI
O N
3P-800A SPACE
3P-600A SPACE
3P-600A SPACE
v5 v6 v7 v8
2i"CO
2i"CO
EXISTING
STUB-OUT
BELOW FLR LINE
FOR FUTURE
FEEDER.
EXISTING
METER
MINIMUM %IZ=8.5
ISC=
EXISTING PULL
BOXES, (1) PULL
BOX SHOWN FOR
CLARITY
DISTRIBUTION EQUIPMENT RATINGS & NOTES
SWBD 'NDSS': MAIN CB = SQUARE-D NW-H FRAME, 100KAIC
BRANCH CB = SQUARE-D RK FRAME, 100KAIC
MINIMUM SYMMETRICAL INTERRUPTING RATING = 50KA
SWBD 'EDSS': MAIN CB = SQUARE-D NW-H FRAME, 100 KAIC
BRANCH CB = SQUARE-D RK FRAME, 100KAIC
MINIMUM SYMMETRICAL INTERRUPTING RATING = 50KA
SWBD 'EQ1': 600A BRANCH = SQUARE-D PG FRAME
400A BRANCH = SQUARE-D DJ-MC FRAME
200A BRANCH = SQUARE-D DJ-MC FRAME
MINIMUM SYMMETRICAL INTERRUPTING RATING = 35KA
SWBD 'EQ2': 400A BRANCH = SQUARE-D DJ-MC FRAME
250A BRANCH = SQUARE-D DJ-MC FRAME
150A BRANCH = SQUARE-D DJ-MC FRAME
MINIMUM SYMMETRICAL INTERRUPTING RATING = 65KA
SWBD 'LS': 400A BRANCH = SQUARE-D DJ-MC FRAME
200A BRANCH = SQUARE-D DJ-MC FRAME
100A BRANCH = SQUARE-D DJ-MC FRAME
MINIMUM SYMMETRICAL INTERRUPTING RATING = 50KA
SWBD 'CB': 800A BRANCH = SQUARE-D PG FRAME
200A BRANCH = SQUARE-D DJ-MC FRAME
100A BRANCH = SQUARE-D DJ-MC FRAME
MINIMUM SYMMETRICAL INTERRUPTING RATING = 50KA
ATS-1 THRU
ATS-6: 30-CYCLE WITHSTAND RATING = 65KA
3-PHASE SYMMETRICAL
FAULT CURRENT VALUE
FOR CLOSED-TRANSITION
POSITION OF TRANSFER
SWITCH
ISC = 3-PHASE SYMMETRICAL
FAULT CURRENT VALUE FOR
NON-CLOSED-TRANSITION
POSITION OF TRANSFER
SWITCH
SCALE : NTS
BUILDING 1 - REVISED PARTIAL ONE-LINE DIAGRAM
- THIS DIAGRAM IS ALL EXISTING EQUIPMENT UNLESS OTHERWISE NOTED
3P-600A SPACE
FEEDER 'A2'
FEEDER 'E2'
EXISTING SWBD 'A'
3P-400A
LSIG
E-602
BUILDING 1 - REVISED PARTIAL
ONE-LINE DIAGRAM
ELEVATOR
CONTROLLER
ELEVATOR CONTROL UNIT
PASSENGER
ELEVATOR "P1"
ELEVATOR
CONTROLLER
ELEVATOR
CONTROL UNIT
SERVICE ELEVATOR "S3"
EXISTING PULL BOXES,
(1) PULL BOX SHOWN
FOR CLARITY
EXISTING XFMR T18
13,200: 208Y/120VAC
56,800A
33,500A
M
M
M
3P-100A SPACE
3P-100A SPACE
3P-225A SPACE
3P-225A SPACE
3P-225A SPARE
3P-225A SPARE
3P-400A SPARE
3P-1200A
3P-1200A
3P-150A SPARE
3P-150A SPARE
3P-250A SPARE
CLOSED
OPEN
OPEN
OPEN
CLOSED
OPEN
OPEN
OPEN
CLOSED
CLOSED
CLOSED
CLOSED
3P-1200A
3P-1200A
3P-1200A
3P-800A
3P-1200A
3P-4000A
3P-1200A
EXISTING EQUIP BUSWAY
3P-1200A
3P-1200A
3P-800A
3P-1200A
3P-4000A
EXISTING XFMR T23
13,200: 208Y/120VAC
1500KVA
KEY NOTES
PROVIDE NEW LSIG CIRCUIT BREAKER. COORDINATE WITH
GENERAL ELECTRIC (GE) MANUFACTURER REPRESENTATIVE
AS REQUIRED. CIRCUIT BREAKER SHALL BE PBII WITH
ENTELLIGUARD TRIP UNIT, OR EQUIPMENT MODEL.
PROVIDE NEW LSIG CIRCUIT BREAKER. COORDINATE WITH
SQUARE-D MANUFACTURER REPRESENTATIVE AS REQUIRED.
CIRCUIT BREAKER SHALL BE #LGA36400U44X, OR EQUIPMENT
MODEL.
PROVIDE NEW LSIG CIRCUIT BREAKER. COORDINATE WITH
EATON MANUFACTURER REPRESENTATIVE AS REQUIRED.
CIRCUIT BREAKER SHALL BE #AKDB3400FT36W, OR
EQUIPMENT MODEL.
PROVIDE (3) 500KCMIL AND (1) 1AWG GND. UTILIZE EXISTING
3-1/2" RACEWAY AND PROVIDE ADDITIONAL 3-1/2" RACEWAYS
AS INDICATED ON PLANS.
REVISED SWITCHBOARD. REFERENCE PANEL SCHEDULE ON
SHEET E-603 FOR ADDITIONAL INFORMATION.
PULL BOX "PB-S3". REFERENCE SHEET EP111 FOR
ADDITIONAL INFORMATION.
PROVIDE (3) 500KCMIL AND (1) 1AWG GND. UTILIZE
EXISTING 3-1/2" RACEWAY AND PROVIDE
ADDITIONAL 3-1/2" RACEWAYS AS INDICATED ON
PLANS.
ELEVATOR CONTROL SWITCH SHALL INCLUDE SHUNT TRIP
DISCONNECT SWITCH AND SHALL BE INTERFACED WITH THE
EXISTING FIRE ALARM CONTROL SYSTEM TO DE-ENERGIZE
CIRCUIT UPON ACTIVATION OF SPRINKLER SYSTEM. PROVIDE
SHUNT TRIP DISCONNECT PER ELEVATOR MANUFACTURER'S
REQUIREMENTS. COORDINATE WITH ELEVATOR
MANUFACTURER AND AHJ AS REQUIRED.
PROVIDE CURRENT SENSORS FOR METERING INDIVIDUAL
FEEDERS AND LOADS. PROVIDE WITH ALL REQUIRED
LABELING, CONNECTIONS, AND APPURTENANCES FOR A
FULLY FUNCTIONAL SYSTEM. INSTALL PER MANUFACTURER
RECOMMENDATIONS. SEE PANEL SCHEDULES FOR
ADDITIONAL INFORMATION. HARDWARE SHALL MATCH VA
FACILITY STANDARD: CENTRICA HARDWARE (CT'S/BRIDGES)
AND POWER RADAR SOFTWARE, REFERENCE SPECIFICATION
25 10 10 FOR ADDITIONAL INFORMATION.
PROVIDE 25HP VFD WITH ALL REQUIRED I/O PER MECHANICAL
DRAWINGS. VFD SHALL PROVIDE 3% INPUT LINE REACTOR
AND INTEGRAL CIRCUIT BREAKER FOR DISCONNECTION.
REVISED PANELBOARD. REFERENCE PANEL SCHEDULE ON
SHEET E-604 FOR ADDITIONAL INFORMATION.
REVISED PANELBOARD. REFERENCE PANEL SCHEDULE ON
DRAWING E-603 FOR ADDITONAL INFORMATION.
PROVIDE CURRENT SENSORS TO METER THE PANEL MAIN.
PROVIDE WITH ALL REQUIRED LABELING, CONNECTIONS, AND
APPURTENANCES FOR A FULLY FUNCTIONAL SYSTEM.
INSTALL PER MANUFACTURER RECOMMENDATIONS. SEE
PANEL SCHEDULES FOR ADDITIONAL INFORMATION.
HARDWARE SHALL MATCH VA FACILITY STANDARD: CENTRICA
HARDWARE(CT'S/BRIDGES) AND POWER RADAR SOFTWARE,
REFERENCE SPECIFICATION
25 10 10 FOR ADDITIONAL INFORMATION.
EXISTING SWBD 'EQ1'
A
BU
S
EXISTING SWBD 'EQ3'
A
BU
S
SPARE
HUM-2
3P-40A
LIEBERT 2 CONDENSER
3P-15A
LIEBERT 1 CONDENSER
3P-15A
PANEL "EB" BLDG 27
MCC-BLDG 27 (025)
3P-200A
BEQB4
3P-150A
3P-70A
3P-70A
3P-100A
LIEBERT 2 100A
3P-100A
LIEBERT 1 100A
3P-400A
EXISTING PNL '2M3' 400A MLO
3P-400A
EXISTING PNL 'NH1M' 400A MLO
EXISTING PNL 'BEQB2D' 400A MLO
3P-400A
3P-225A SPACE
3P-225A SPACE
3P-225A SPACE
3P-600A SPARE
3P-400A
3P-600A
3P-200A
3P-600A
(4)#4/0 & (1)#4GND,2i"C
(2) SETS: (4)#500KCMIL & (1)#1/0 GND, 3i"C
(2) SETS: (3)#500KCMIL & (1)#2/0 GND, 3i"C
EXISTING PULL BOX #3
EXISTING X-RAY #3 XFMR
EXISTING PNL '1M2' 800A MLO
EXISTING PNL 'A' 400A MLO
EXISTING (3) SETS OF:
(4)#600KCMIL &
(1)#4/0 GND, 4"C
EXISTING (3) SETS OF:
(4)#600KCMIL &
(1)#4/0 GND, 4"C
ELEVATOR
CONTROL SWITCH
"ECS-S3", 22 KAIC
ELEVATOR CONTROL SWITCH
"ECS-P1" 22 KAIC
3P-400A
LSIG
3P-400A
LSIG
FLA = 152A
FLA = 184A
800AS
PANEL "9EQ3" 90
MOTOR CONTROL CENTER "MCC3" 600A
PANEL "9EQ2" 9A 100A
PANEL "9EQ4" 9B 225A
SHEET NOTES
1. MANUFACTURER'S CATALOGUE EQUIPMENT NUMBERS
SUBJECT TO CHANGE ANYTIME WITHOUT NOTICE.
COORDINATE WITH MANUFACTURER AS REQUIRED.
2. WHERE WORK IS BEING CONDUCTED, ALL FEEDERS OLDER
THAN 15 YEARS OF AGE, OR IF AGE CANNOT BE CONFIRMED,
SHALL BE DEMOLISHED AND REPLACED AS REQUIRED,
UNLESS OTHERWISE NOTED.
3. ALL WIRING FROM DIFFERENT SOURCES (IE: LIFE SAFETY,
CRITICAL, EQUIPMENT, NORMAL) SHALL BE ROUTED IN
SEPARATE RACEWAYS AND BOXES AS REQUIRED TO
CONFORM WITH NEC 517.31(C)(1).
4. ALL CURRENT SENSORS MAY NOT BE SHOWN ON ONELINE.
SEE PANEL SCHEDULES ON SHEET E-607 FOR ADDITIONAL
INFORMATION.
5. WHERE CONDUIT AND WIRE SIZES ARE NOT EXPLICITLY
SHOWN ON THIS SHEET, REFERENCE BUILDING 1
EQUIPMENT SCHEDULE ON SHEET E-604 FOR ADDITIONAL
INFORMATION.
6. WHERE ADDITIONAL 0-5A CTs ARE REQUIRED FOR
ELECTRICAL POWER METERING PURPOSES, CONTRACTOR
SHALL PROVIDE ALL REQUIRED CABELING, JUNCTION
BOXES/ENCLOSURES, AND APPURTENANCES AS REQUIRED
FOR A COMPLETE AND FUNCTIONAL SYSTEM.
SPD
SPD
400AS 400AF
ST
400AS 400AF
ST
M
M
M
SWBD "9EQ1" 9M 1200A
DISCONNECT
"9M"
OR CONDENSOR
OR CHILLER
VFD
SUPPLY FAN "SF-1"
100/3P
EXISTING PULL BOXES,
(1) PULL BOX SHOWN
FOR CLARITY
REVISED PNL BEQ4 100A(4)#2 & (1)#8GND, 1-1/2"C
EXISTING '3N1'
3P-100A
3P-400A
EXISTING SWBD 'B'
2500A (4)#2 & (1)#8GND, 1-1/2"C
REVISED PANEL '4N3'
MINIMUM %IZ=8.5
EXISTING XFMR T23
13,200: 208Y/120VAC
1500KVA
ISC =58,600A
ISC =29,300A
ISC =29,300A
ISC =58,600A
EXISTING (3) SETS OF:
(4)#600KCMIL &
(1)#4/0 GND, 4"C
EXISTING (3) SETS OF:
(4)#600KCMIL &
(1)#4/0 GND, 4"C
EXISTING (3) SETS OF:
(4)#600KCMIL &
(1)#4/0 GND, 4"C
EXISTING (3) SETS OF:
(4)#600KCMIL &
(1)#4/0 GND, 4"C
ISC=29,300A
ISC=58,600A
ISC =29,300A
ISC =58,600A
EXISTING (3) SETS OF:
(4)#600KCMIL &
(1)#4/0 GND, 4"C
EXISTING (3) SETS OF:
(4)#600KCMIL &
(1)#4/0 GND, 4"C
ISC=26,100A
ISC=46,800A
ISC =14,900A
ISC =18,300A
ISC =13,700A
ISC =16,600A
ISC=13,700A
ISC=15,600A
ELEVATOR
CONTROLLER
ELEVATOR CONTROL UNIT
PASSENGER
ELEVATOR "P2"60
ELEVATOR CONTROL SWITCH
"ECS-P2" 22 KAIC
FLA = 152ASPD
400AS 400AF
ST
ISC = 56,800A
PhaseARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
A/E:
625 First Ave #301 Seattle, WA, 98104
(206) 590 - 2118
RAY SPEES, PRESIDENT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
STAMPCONSULTANT
321 4 5 6 7 8 9 10
668-18-109
Revisions: Date:
SPEES DESIGN BUILD
REFURBISH AND UPGRADE
ELEVATORS IN BLDG
1 AND 27
11/16/2021
Mann-Grandstaff VA Medical Center
- Spokane, WA
LRL/WNM JPS/FEB
SUMP
PUMP
"SP-1"
E-603
BUILDING 1 - ELECTRICAL LOAD
SCHEDULES
KEY NOTES
SHEET NOTES
1. WHERE WORK IS BEING CONDUCTED, ALL FEEDERS
OLDER THAN 15 YEARS OF AGE, OR IF AGE CANNOT
BE CONFIRMED, SHALL BE DEMOLISHED AND
REPLACED AS REQUIRED, UNLESS OTHERWISE
NOTED.
2. WHERE ADDITIONAL 0-5A CTs ARE REQUIRED FOR
ELECTRICAL POWER METERING PURPOSES,
CONTRACTOR SHALL PROVIDE ALL REQUIRED
CABELING, JUNCTION BOXES/ENCLOSURES, AND
APPURTENANCES AS REQUIRED FOR A COMPLETE
AND FUNCTIONAL SYSTEM.
REVISED PANELBOARD CIRCUITS AND/OR LOADS.
PROVIDE CIRCUIT BREAKERS AND PANEL
DIRECTORY AS REQUIRED.
A RECENT 30-DAY POWER DEMAND STUDY WAS
CONDUCTED ON PANEL BEQ4 AND RESULTED IN A
MAXIMUM LOAD OF 58.7 AMPS. THIS PANEL
SCHEDULE SHOWS THE ADDED LOAD FOR THIS
PROJECT. WITH THE ADDED LOAD AND THE
METERED LOAD, IT PROVIDES A TOTAL SUM OF 65.3
AMPS; THIS IS WELL BELOW 80% RATING OF THE
100A PANEL (OR 80 AMPS) AND THEREFORE HAS
ADEQUATE CAPACITY FOR THE NEW LOAD.
PROVIDE CURRENT SENSORS TO METER THE PANEL
MAIN. PROVIDE WITH ALL REQUIRED LABELING,
CONNECTIONS, AND APPURTENANCES FOR A FULLY
FUNCTIONAL SYSTEM. INSTALL PER MANUFACTURER
RECOMMENDATIONS. HARDWARE SHALL MATCH VA
FACILITY STANDARD: CENTRICA HARDWARE
(CT'S/BRIDGES) AND POWER RADAR SOFTWARE,
REFERENCE SPECIFICATION 25 10 10 FOR
ADDITIONAL INFORMATION.
PROVIDE CURRENT SENSORS FOR METERING
INDICATED INDIVIDUAL FEEDERS AND LOADS.
PROVIDE WITH ALL REQUIRED LABELING,
CONNECTIONS, AND APPURTENANCES FOR A FULLY
FUNCTIONAL SYSTEM. INSTALL PER MANUFACTURER
RECOMMENDATIONS. HARDWARE SHALL MATCH VA
FACILITY STANDARD: CENTRICA HARDWARE
(CT'S/BRIDGES) AND POWER RADAR SOFTWARE,
REFERENCE SPECIFICATION 25 10 10 FOR
ADDITIONAL INFORMATION.
METER PANEL "4N3" FEEDER LOAD FROM UPSTREAM
PANEL "3N1" LOCATED IN ROOM A344. REFERENCE
KEY NOTE "3" ON THIS SHEET FOR REQUIRED
METERING INFORMATION.
PhaseARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
A/E:
625 First Ave #301 Seattle, WA, 98104
(206) 590 - 2118
RAY SPEES, PRESIDENT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
STAMPCONSULTANT
321 4 5 6 7 8 9 10
668-18-109
Revisions: Date:
SPEES DESIGN BUILD
REFURBISH AND UPGRADE
ELEVATORS IN BLDG
1 AND 27
11/16/2021
Mann-Grandstaff VA Medical Center
- Spokane, WA
LRL/WNM JPS/FEB
5 3
E-604
BUILDING 1 -
ELECTRICAL SCHEDULES
EXISTING CIRCUITS AND
CORRESPONDING LOADS TO BE
REMOVED. REFERENCE REVISED
PANEL SCHEDULE FOR ADDITIONAL
INFORMATION.
REVISED PANELBOARD CIRCUITS
AND/OR LOADS. PROVIDE CIRCUIT
BREAKERS AND PANEL DIRECTORY AS
REQUIRED.
FAN COIL UNIT "FC-1" SHALL UTILIZE
EXISTING CIRCUIT (FEEDER BREAKER,
CONDUIT, AND WIRE). REFERENCE
DRAWINGS ED107 AND EP107 FOR
ADDITIONAL INFORMATION.
A RECENT 30-DAY POWER DEMAND
STUDY WAS CONDUCTED ON PANEL
8LS1 AND RESULTED IN A MAXIMUM
LOAD OF 16 AMPS. THIS PANEL
SCHEDULE SHOWS THE ADDED LOAD
FOR THIS PROJECT. WITH THE ADDED
LOAD AND THE METERED LOAD, IT
PROVIDES A TOTAL SUM OF 38.5 AMPS;
THIS IS BELOW 80% RATING OF THE
50A PANEL (OR 40 AMPS) AND
THEREFORE HAS ADEQUATE CAPACITY
FOR THE NEW LOAD.
PROVIDE CURRENT SENSORS TO
METER THE PANEL MAIN. PROVIDE
WITH ALL REQUIRED LABELING,
CONNECTIONS, AND APPURTENANCES
FOR A FULLY FUNCTIONAL SYSTEM.
INSTALL PER MANUFACTURER
RECOMMENDATIONS. HARDWARE
SHALL MATCH VA FACILITY STANDARD:
CENTRICA HARDWARE (CT'S/BRIDGES)
AND POWER RADAR SOFTWARE,
REFERENCE SPECIFICATION 25 10 10
FOR ADDITIONAL INFORMATION.
PROVIDE CURRENT SENSORS FOR
METERING INDICATED INDIVIDUAL
FEEDERS AND LOADS. PROVIDE WITH
ALL REQUIRED LABELING,
CONNECTIONS, AND APPURTENANCES
FOR A FULLY FUNCTIONAL SYSTEM.
INSTALL PER MANUFACTURER
RECOMMENDATIONS. HARDWARE
SHALL MATCH VA FACILITY STANDARD:
CENTRICA HARDWARE (CT'S/BRIDGES)
AND POWER RADAR SOFTWARE,
REFERENCE SPECIFICATION 25 10 10
FOR ADDITIONAL INFORMATION.
METER PANEL "8LS1" LOAD FROM
UPSTREAM RISER CLOSET LOCATED IN
ROOM A729A. REFERENCE KEY NOTE
"5" ON THIS SHEET FOR REQUIRED
METERING INFORMATION.
1. WHERE WORK IS BEING
CONDUCTED, ALL FEEDERS OLDER
THAN 15 YEARS OF AGE, OR IF AGE
CANNOT BE CONFIRMED, SHALL BE
DEMOLISHED AND REPLACED AS
REQUIRED, UNLESS OTHERWISE
NOTED.
2. WHERE ADDITIONAL 0-5A CTs ARE
REQUIRED FOR ELECTRICAL
POWER METERING PURPOSES,
CONTRACTOR SHALL PROVIDE ALL
REQUIRED CABELING, JUNCTION
BOXES/ENCLOSURES, AND
APPURTENANCES AS REQUIRED
FOR A COMPLETE AND
FUNCTIONAL SYSTEM.
PhaseARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
A/E:
625 First Ave #301 Seattle, WA, 98104
(206) 590 - 2118
RAY SPEES, PRESIDENT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
STAMPCONSULTANT
321 4 5 6 7 8 9 10
668-18-109
Revisions: Date:
SPEES DESIGN BUILD
REFURBISH AND UPGRADE
ELEVATORS IN BLDG
1 AND 27
11/16/2021
Mann-Grandstaff VA Medical Center
- Spokane, WA
LRL/WNM JPS/FEB
KEY NOTES
EXISTING EQUIPMENT AND
ASSOCIATED RACEWAYS AND
CONDUCTORS TO BE DEMOLISHED
UNLESS OTHERWISE NOTED.
EXISTING CONDUCTORS TO BE
DEMOLISHED BACK TO SOURCE.
EXISTING RACEWAY TO REMAIN.
EXISTING CIRCUIT BREAKER TO BE
REMOVED AND REPLACED.
EXISTING PANEL TO BE REVISED.
REFERENCE SHEETS E-606 AND E-607
FOR ADDITIONAL INFORMATION.
SHEET NOTES
1. REFERENCE ONE-LINE DIAGRAM
ON DRAWING E-606 FOR ALL
REVISIONS.
2. WHERE WORK IS BEING
CONDUCTED, ALL FEEDERS OLDER
THAN 15 YEARS OF AGE, OR IF AGE
CANNOT BE CONFIRMED, SHALL BE
DEMOLISHED AND REPLACED AS
REQUIRED, UNLESS OTHERWISE
NOTED.
3P-400A
3P-200A
3P-200A
3P-100A3P-1000AEXISTING PULL BOX
EXISTING SECONDARY FEEDER
3 SETS 4#400 KCMIL-3"C
4.5% IMPEDANCE (MIN)
T300
EXISTING 300 KVA
PADMOUNT TRANSFORMER
EXISTING 'MDS' 1000A MAIN
DISTRIBUTION SWITCHBOARD
208Y/120V-30, 4 WIRE
4#3/0, 1#6G-2 1/2"C (EXISTING)
4#3/0, 1#6G-2 1/2"C (EXISTING)
4#1, 1#8G-2"C (EXISTING)
2 SETS 4#4/0, 1#2G-2 1/2"C (EXISTING)
EXISTING PANEL 'P'
EXISTING PANEL 'M'
EXISTING PANEL 'L'
3P-100A/60AF
EXISTING MAIN SWITCH
SPACE
SPACE
3P-400A
3P-250A
3P-200A
3P-100A
3P-150A
3P-400A
EXISTING 'DP' 400A DISTRIBUTION PANEL
208Y/120V-30, 4 WIRE 42KAIC
3P-100A
3P-100A
SPARE
SPARE
10KAIC
10KAIC
10KAIC
EXISTING FEED THROUGH LUGS
3P-250A
ENCLOSED
SHUNT TRIP
CIRCUIT
BREAKER
EXISTING PANEL 'LS1'
10KAIC
EXISTING 3P-100A/100AF BUS
TAP DISCONNECT SWITCH
EXISTING LIFE SAFETY
BRANCH BUS DUCT
EXISTING PANEL 'CB1'
10KAIC
EXISTING 3P-100A/100AF BUS TAP
DISCONNECT SWITCH
EXISTING CRITICAL
BRANCH BUS DUCT
EXISTING PANEL 'EB'
10KAIC
EXISTING 3P-100A/100AF BUS TAP
DISCONNECT SWITCH
EXISTING CRITICAL
BRANCH BUS DUCT
EXISTING PANEL 'LSL'
10KAIC
EXISTING FUSED DISCONNECT
3P-200A/200AF
EXISTING MCC
22KAIC
E-605
SCALE : NTS
BUILDING 27 - EXISTING ONE-LINE DIAGRAM (DEDUCTIVE BID ALTERNATE)
- THIS DIAGRAM IS ALL EXISTING EQUIPMENT UNLESS OTHERWISE NOTED
BUILDING 27 - EXISTING ONE-LINE
DIAGRAM (DEDUCTIVE BID ALTERNATE)
EXISTING PULL BOX
EXISTING PANEL 'LL'
EXISTING PANEL 'PL'
EXISTING PANEL 'P1A'
EXISTING PANEL 'L1'
ELEVATOR
DEDUCTIVE BID ALTERNATE
EXISTING
ELEVATOR
CONTROL
UNIT
PhaseARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
A/E:
625 First Ave #301 Seattle, WA, 98104
(206) 590 - 2118
RAY SPEES, PRESIDENT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
STAMPCONSULTANT
321 4 5 6 7 8 9 10
668-18-109
Revisions: Date:
SPEES DESIGN BUILD
REFURBISH AND UPGRADE
ELEVATORS IN BLDG
1 AND 27
11/16/2021
Mann-Grandstaff VA Medical Center
- Spokane, WA
LRL/WNM JPS/FEB 141 OF 143
10KAIC
10KAIC
10KAIC
EXISTING FEED THROUGH LUGS
10KAIC
EXISTING 3P-100A/100AF BUS
TAP DISCONNECT SWITCH
EXISTING LIFE
SAFETY BRANCH
BUS DUCT
10KAIC
EXISTING 3P-100A/100AF BUS
TAP DISCONNECT SWITCH
EXISTING CRITICAL
BRANCH BUS DUCT
10KAIC
EXISTING 3P-100A/100AF BUS
TAP DISCONNECT SWITCH
EXISTING CRITICAL
BRANCH BUS DUCT
10KAIC
3P-200A/200AF
EXISTING FUSED
DISCONNECT
22KAIC
E-606
SCALE : NTS
BUILDING 27 - REVISED ONE-LINE DIAGRAM (DEDUCTIVE BID ALTERNATE)
- THIS DIAGRAM IS ALL EXISTING EQUIPMENT UNLESS OTHERWISE NOTED
BUILDING 27 - REVISED ONE-LINE
DIAGRAM (DEDUCTIVE BID ALTERNATE)
EXISTING PULL BOX
EXISTING PANEL 'LL'
EXISTING PANEL 'PL'
EXISTING PANEL 'P1A'
EXISTING PANEL 'L1'
KEY NOTES
PROVIDE LSIG CIRCUIT BREAKER.
COORDINATE WITH EQUIPMENT
GENERAL ELECTRIC (GE)
MANUFACTURER REPRESENTATIVE AS
REQUIRED.
PROVIDE (3) 250KCMIL AND (1) 4AWG
GND IN 3"C.
PROVIDE (3) 250KCMIL AND (1) 4AWG
GND IN EXISTING CONDUIT.
REVISED PANEL "LSL" REFERENCE
ASSOCIATED PANEL SCHEDULE ON
SHEET E-607 FOR ADDITIONAL
INFORMATION.
ELEVATOR CONTROL SWITCH SHALL
INCLUDE SHUNT TRIP DISCONNECT
SWITCH AND SHALL BE INTERFACED
WITH THE EXISTING FIRE ALARM
CONTROL SYSTEM TO DE-ENERGIZE
CIRCUIT UPON ACTIVATION OF
SPRINKLER SYSTEM. PROVIDE SHUNT
TRIP DISCONNECT PER ELEVATOR
MANUFACTURER'S REQUIREMENTS.
COORDINATE WITH ELEVATOR
MANUFACTURER AND AHJ AS
REQUIRED.
PROVIDE CURRENT SENSORS FOR
METERING INDIVIDUAL FEEDERS AND
LOADS. PROVIDE WITH ALL REQUIRED
LABELING, CONNECTIONS, AND
APPURTENANCES FOR A FULLY
FUNCTIONAL SYSTEM. INSTALL PER
MANUFACTURER RECOMMENDATIONS.
SEE PANEL SCHEDULES FOR
ADDITIONAL INFORMATION. HARDWARE
SHALL MATCH VA FACILITY STANDARD:
CENTRICA HARDWARE (CT'S/BRIDGES)
AND POWER RADAR SOFTWARE,
REFERENCE SPECIFICATION 25 10 10
FOR ADDITIONAL INFORMATION.
PROVIDE CURRENT SENSORS TO
METER THE PANEL MAIN. PROVIDE
WITH ALL REQUIRED LABELING,
CONNECTIONS, AND APPURTENANCES
FOR A FULLY FUNCTIONAL SYSTEM.
INSTALL PER MANUFACTURER
RECOMMENDATIONS. SEE PANEL
SCHEDULES FOR ADDITIONAL
INFORMATION. HARDWARE SHALL
MATCH VA FACILITY STANDARD:
CENTRICA HARDWARE (CT'S/BRIDGES)
AND POWER RADAR SOFTWARE,
REFERENCE SPECIFICATION 25 10 10
FOR ADDITIONAL INFORMATION.
EXISTING PULL BOX
EXISTING SECONDARY
FEEDER 3 SETS 4#400
KCMIL-3"C
4.5% IMPEDANCE (MIN)
T300
EXISTING 300 KVA
PADMOUNT
TRANSFORMER
EXISTING 'MDS' 1000A
MAIN DISTRIBUTION SWITCHBOARD
208Y/120V-30, 4 WIRE
4#3/0, 1#6G-2 1/2"C (EXISTING)
4#3/0, 1#6G-2 1/2"C (EXISTING)
4#1, 1#8G-2"C (EXISTING)
2 SETS 4#4/0, 1#2G-2 1/2"C (EXISTING)
EXISTING PANEL 'L'
3P-100A/60AF
EXISTING MAIN
SWITCH
EXISTING 'DP' 400A
DISTRIBUTION PANEL
208Y/120V-30, 4 WIRE 42KAIC
SPARE
SPARE
3P-100A
3P-100A3P-400A
3P-150A
3P-100A
3P-200A
3P-400A
SPACE
SPACE
EXISTING PANEL 'M'
EXISTING PANEL 'P'
3P-1000A 3P-100A
3P-200A
3P-200A
3P-400A
MCC
PANEL 'LSL'
PANEL 'EB'
PANEL 'CB1'
PANEL 'LS1'
3P-250A
LSIG
ELEVATOR
CONTROL SWITCH
"ECS-P4", 42KAIC
PASSENGER
ELEVATOR "P4"40
FLA = 111ASPD
DEDUCTIVE BID ALTERNATE
5ELEVATOR
CONTROL
UNIT
SHEET NOTES
1. MANUFACTURER'S CATALOGUE
EQUIPMENT NUMBERS SUBJECT TO
CHANGE ANYTIME WITHOUT
NOTICE. COORDINATE WITH
MANUFACTURER AS REQUIRED.
2. WHERE WORK IS BEING
CONDUCTED, ALL FEEDERS OLDER
THAN 15 YEARS OF AGE, OR IF AGE
CANNOT BE CONFIRMED, SHALL BE
DEMOLISHED AND REPLACED AS
REQUIRED, UNLESS OTHERWISE
NOTED.
3. ALL WIRING FROM DIFFERENT
SOURCES (IE: LIFE SAFETY,
CRITICAL, EQUIPMENT, NORMAL)
SHALL BE ROUTED IN SEPARATE
RACEWAYS AND BOXES AS
REQUIRED TO CONFORM WITH NEC
517.31(C)(1).
4. ALL CURRENT SENSORS MAY NOT
BE SHOWN ON ONELINE. SEE
PANEL SCHEDULES ON SHEET
E-607 FOR ADDITIONAL
INFORMATION.
5. WHERE ADDITIONAL 0-5A CTs ARE
REQUIRED FOR ELECTRICAL
POWER METERING PURPOSES,
CONTRACTOR SHALL PROVIDE ALL
REQUIRED CABELING, JUNCTION
BOXES/ENCLOSURES, AND
APPURTENANCES AS REQUIRED
FOR A COMPLETE AND
FUNCTIONAL SYSTEM.
400AS 250AF
ST
PhaseARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
A/E:
625 First Ave #301 Seattle, WA, 98104
(206) 590 - 2118
RAY SPEES, PRESIDENT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
STAMPCONSULTANT
321 4 5 6 7 8 9 10
668-18-109
Revisions: Date:
SPEES DESIGN BUILD
REFURBISH AND UPGRADE
ELEVATORS IN BLDG
1 AND 27
11/16/2021
Mann-Grandstaff VA Medical Center
- Spokane, WA
LRL/WNM JPS/FEB
E-607
BUILDING 27 - ELECTRICAL SCHEDULES
(DEDUCTIVE BID ALTERNATE)
SCALE : NTS
BUILDING 27 - ELECTRICAL SCHEDULES (DEDUCTIVE BID ALTERNATE)1
KEY NOTES
EXISTING CIRCUITS AND
CORRESPONDING LOADS TO BE
REMOVED. REFERENCE REVISED
PANEL SCHEDULE FOR ADDITIONAL
INFORMATION.
REVISED PANELBOARD CIRCUITS
AND/OR LOADS. PROVIDE CIRCUIT
BREAKERS AND PANEL DIRECTORY AS
REQUIRED.
PANELS SCHEDULES ARE SHOWN ONLY
TO INDICATE THE OVERALL LOAD IS
NOT CHANGING DUE TO THE ELEVATOR
BEING THE SAME HP.
PROVIDE CURRENT SENSORS TO
METER THE PANEL MAIN. PROVIDE
WITH ALL REQUIRED LABELING,
CONNECTIONS, AND APPURTENANCES
FOR A FULLY FUNCTIONAL SYSTEM.
INSTALL PER MANUFACTURER
RECOMMENDATIONS. HARDWARE
SHALL MATCH VA FACILITY STANDARD:
CENTRICA HARDWARE (CT'S/BRIDGES)
AND POWER RADAR SOFTWARE,
REFERENCE SPECIFICATION 25 10 10
FOR ADDITIONAL INFORMATION.
PROVIDE CURRENT SENSORS FOR
METERING INDIVIDUAL FEEDERS AND
LOADS. PROVIDE WITH ALL REQUIRED
LABELING, CONNECTIONS, AND
APPURTENANCES FOR A FULLY
FUNCTIONAL SYSTEM. INSTALL PER
MANUFACTURER RECOMMENDATIONS.
HARDWARE SHALL MATCH VA FACILITY
STANDARD: CENTRICA HARDWARE
(CT'S/BRIDGES) AND POWER RADAR
SOFTWARE, REFERENCE
SPECIFICATION 25 10 10 FOR
ADDITIONAL INFORMATION.
DEDUCTIVE BID ALTERNATE
SHEET NOTES
1. WHERE WORK IS BEING
CONDUCTED, ALL FEEDERS OLDER
THAN 15 YEARS OF AGE, OR IF AGE
CANNOT BE CONFIRMED, SHALL BE
DEMOLISHED AND REPLACED AS
REQUIRED, UNLESS OTHERWISE
NOTED.
2. WHERE ADDITIONAL 0-5A CTs ARE
REQUIRED FOR ELECTRICAL
POWER METERING PURPOSES,
CONTRACTOR SHALL PROVIDE ALL
REQUIRED CABELING, JUNCTION
BOXES/ENCLOSURES,
APPURTENANCES AS REQUIRED
FOR COMPLETE AND FUNCTIONAL
SYSTEM.
PhaseARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
A/E:
625 First Ave #301 Seattle, WA, 98104
(206) 590 - 2118
RAY SPEES, PRESIDENT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
STAMPCONSULTANT
321 4 5 6 7 8 9 10
668-18-109
Revisions: Date:
SPEES DESIGN BUILD
REFURBISH AND UPGRADE
ELEVATORS IN BLDG
1 AND 27
11/16/2021
Mann-Grandstaff VA Medical Center
- Spokane, WA
LRL/WNM JPS/FEB
2 5