Attachment 5 668-18-109_Project Drawings 1 of 6.pdf

PDF 9 MB Posted

Attached to
Y1DA--CON-NRM 668-18-109 Refurbish and Upgrade Elevators in Bldg 1 and 27
Solicitation number
36C26024R0009
Issued by

About this file

This package includes construction drawings and specifications for a project to refurbish and upgrade elevators in Buildings 1 and 27 at the Mann-Grandstaff VA Medical Center in Spokane, Washington. The project involves renovating elevator equipment and machine rooms in both buildings, including demolition and installation of new components. The construction is identified as a Type C activity posing high infection control risks, requiring Class III and IV precautions. The drawings depict demolition, new construction, fire safety, and mechanical plans. Specifications address safety requirements and infection control measures. The solicitation number is 36C26024R0009 for this project awarded by the Department of Veterans Affairs.

View the file

Other files

File Type Posted
Wage Determination 1.19.24.pdf PDF
36C26024R0009 0006.pdf PDF
36C26024R0009 0005.pdf PDF
Wage Determination 1.5.24.pdf PDF
Wage Determination 12.22.23.pdf PDF
36C26024R0009 0004.pdf PDF
36C26024R0009 0003.pdf PDF
36C26024R0009 0002.pdf PDF
36C26024R0009 0001.pdf PDF
WD 11.24.23.pdf PDF
668-18-109_Pre Bid Site Walk Sign In Sheet_2023.12.03.pdf PDF
Attachment 17 Security Requirements.pdf PDF
Attachment 18 Contractor Rules of Behavior.pdf PDF
Attachment 4 668-18-109_Supplement to SPEC 01 00 00 Part 1-6-I.pdf PDF
Attachment 10 668-18-109_Project Drawings 6 of 6.pdf PDF
Attachment 15 Wage Determination 11.17.23.pdf PDF
Attachment 2 668-18-109_Project Specifications 1 of 2_R1.pdf PDF
Attachment 13 668-18-109_Lead Sampling Report.pdf PDF
Attachment 6 668-18-109_Project Drawings 2 of 6.pdf PDF
Attachment 19 Calculation of Self Performed Work REV 1.pdf PDF
36C26024R0009.pdf PDF
Attachment 7 668-18-109_Project Drawings 3 of 6.pdf PDF
Attachment 12 668-18-109_Limited Asbestos Good Faith Survey - Addendum 1.pdf PDF
Attachment 16 Price Breakout.xlsx XLSX spreadsheet
Attachment 3 668-18-109_Project Specifications 2 of 2_R1.pdf PDF
Attachment 1 668-18-109_SOW-CON_2023-08-15.pdf PDF
Attachment 8 668-18-109_Project Drawings 4 of 6.pdf PDF
Attachment 11 668-18-109_Limited Asbestos Good Faith Survey.pdf PDF
Attachment 9 668-18-109_Project Drawings 5 of 6.pdf PDF
Attachment 14 668-18-109_DWG Clarification Document_2023-06-22.pdf PDF
Show all 30

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FR

EE

D O

M W

A Y

A S S

EM

B

LY

S

TR

EE

T

M

EM

O R

IA

L C

IR

C

LE

WELLESLEY AVE

IN

D

EP

EN

D

EN

C E

D R

IV

E

INDEPENDENCE DRIVE

RESERVE ROAD

PA

R K

IN

G L

O T

"A

PA

R K

IN

G L

O T

"B

PA

R K

IN

G L

O T

"C

PA

R K

IN

G L

O T

"E

PA

RK

IN

G

LO

T

"L

PA

RK

IN

G

L O

T "D

PA

R K

IN

G

LO

T "J

PA

R K

IN

G L

O T

"H

PA

RK

IN

G

L O

T "G

PA

RK

IN

G

LO

T

"K

PA

R K

IN

G

LO

T "F

14a

16 3 2

6a

6 5

25 15

1e

41 30

G-001

ECMK

COVER SHEET

N/A

REFURBISH AND UPGRADE ELEVATORS IN BLDG 1 & 27

MANN-GRANDSTAFF VA MEDICAL CENTER - SPOKANE, WA

4815 North Assembly St. Spokane, Washington 99205-6197

Project Number: 668-18-109

PhaseARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

A/E:

625 First Ave #301 Seattle, WA, 98104

(206) 590 - 2118

RAY SPEES, PRESIDENT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

STAMPCONSULTANT

321 4 5 6 7 8 9 10

668-18-109

Revisions: Date:

SPEES DESIGN BUILD

REFURBISH AND UPGRADE

ELEVATORS IN BLDG

1 AND 27

11/16/2021

Mann-Grandstaff VA Medical Center

- Spokane, WA

2 VICINITY PLAN & CAMPUS MAP

NOT TO SCALE1 LOCATION PLAN

NOT TO SCALE

MANN-GRANDSTAFF VA

MEDICAL CENTER - SPOKANE WA

MANN-GRANDSTAFF VA MEDICAL CENTER

BUILDINGS WITHIN

SCOPE OF THIS PROJECT

ElenaCortez Image

G-002

ECMK

DRAWING INDEX &

PROJECT TEAM

PhaseARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

A/E:

625 First Ave #301 Seattle, WA, 98104

(206) 590 - 2118

RAY SPEES, PRESIDENT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

STAMPCONSULTANT

321 4 5 6 7 8 9 10

668-18-109

Revisions: Date:

SPEES DESIGN BUILD

REFURBISH AND UPGRADE

ELEVATORS IN BLDG

1 AND 27

11/16/2021

Mann-Grandstaff VA Medical Center

- Spokane, WA

N/A

DRAWING INDEX

PROJECT TEAM

Spees Design Build 625 First Ave #301 Seattle WA, 98104 Mark Kartchner, P.E.

Cell: 509.688.4215 Email:markk@speesdb.com

PLUMBING/HVAC

Spees Design Build 625 First Ave #301 Seattle WA, 98104 Richard McPhee Cell: 770.557.4296 Email: RichardM@speesdb.com

AE PROJECT

MANAGER

Mann-Grandstaff VA Medical Center 4815 N. Assembly Street Spokane, WA 99205

OWNER

Spees Design Build 625 First Ave #301 Seattle WA, 98104 Ryan Litzko Cell: 208.691.0853 Email: ryanl@speesdb.com

ELECTRICAL/SPECIAL SYSTEMS

Spees Design Build 625 First Ave #301 Seattle WA, 98104 Matt King, Architect Cell: 206.257.8785 Email: mattk@speesdb.com

ARCHITECT

PAGE # SHEET # SHEET NAME

GENERAL

1 G-001 COVER SHEET

2 G-002 DRAWING INDEX & PROJECT TEAM

3 G-003 SYMBOLS, ABBREVIATIONS AND GENERAL NOTES

4 GC101 BUILDING 1 - BASEMENT FLOOR - ICRA FLOOR PLANS

5 GC102 BUILDING 1 - FIRST FLOOR - ICRA FLOOR PLANS

6 GC103 BUILDING 1 - SECOND FLOOR - ICRA FLOOR PLANS

7 GC104 BUILDING 1 - THIRD FLOOR - ICRA FLOOR PLANS

8 GC105 BUILDING 1 - FOURTH FLOOR - ICRA FLOOR PLANS

9 GC106 BUILDING 1 - FIFTH FLOOR - ICRA FLOOR PLANS

10 GC107 BUILDING 1 - SIXTH FLOOR - ICRA FLOOR PLANS

11 GC108 BUILDING 1 - SEVENTH FLOOR - ICRA FLOOR PLANS

12 GC109 BUILDING 1 - EIGHTH FLOOR - ICRA FLOOR PLANS

13 GC110 BUILDING 1 - NINTH FLOOR & MACHINE ROOM - ICRA FLOOR PLANS

14 GC111 BUILDING 27 - BASEMENT - ICRA FLOOR PLAN (DEDUCTIVE BID ALTERNATE)

15 GC112 BUILDING 27 -FIRST FLOOR - ICRA FLOOR PLAN (DEDUCTIVE BID ALTERNATE)

16 GC113 BUILDING 27 - SECOND FLOOR - ICRA FLOOR PLAN (DEDUCTIVE BID ALTERNATE)

17 LS101 BUILDING 1 - BASEMENT FLOOR - FIRE SAFETY PLAN

18 LS102 BUILDING 1 - FIRST FLOOR - FIRE SAFETY PLAN

19 LS103 BUILDING 1 - SECOND FLOOR - FIRE SAFETY PLAN

20 LS104 BUILDING 1 - THIRD FLOOR - FIRE SAFETY PLAN

21 LS105 BUILDING 1 - FOURTH & FIFTH FLOORS - FIRE SAFETY PLANS

22 LS106 BUILDING 1 - SIXTH & SEVENTH FLOORS - FIRE SAFETY PLANS

23 LS107 BUILDING 1 - EIGHTH, NINTH FLOORS & MACHINE ROOM - FIRE SAFETY PLANS

24 LS108 BUILDING 27 - BASEMENT - FIRE SAFETY PLAN (DEDUCTIVE BID ALTERNATE)

25 LS109 BUILDING 27 - FIRST FLOOR - FIRE SAFETY PLAN (DEDUCTIVE BID ALTERNATE)

26 LS110 BUILDING 27 - SECOND FLOOR - FIRE SAFETY PLAN (DEDUCTIVE BID ALTERNATE)

ARCHITECTURAL

27 AD100 BUILDING 1 - BASEMENT FLOOR - DEMOLITION PLANS

28 AD101 BUILDING 1 - FIRST FLOOR - DEMOLITION PLANS

29 AD102 BUILDING 1 - SECOND FLOOR - DEMOLITION PLANS

30 AD103 BUILDING 1 - THIRD FLOOR - DEMOLITION PLANS

31 AD104 BUILDING 1 - FOURTH FLOOR- DEMOLITION PLANS

32 AD105 BUILDING 1 - FIFTH FLOOR- DEMOLITION PLANS

33 AD106 BUILDING 1 - SIXTH FLOOR - DEMOLITION PLANS

34 AD107 BUILDING 1 - SEVENTH FLOOR - DEMOLITION PLANS

35 AD108 BUILDING 1 - EIGHTH FLOOR - DEMOLITION PLANS

36 AD109 BUILDING 1 - NINTH FLOOR - DEMOLITION PLAN

37 AD110 BUILDING 1 - ELEVATOR MACHINE ROOM - DEMOLITION PLANS

38 AD111 BUILDING 27 - BASEMENT FLOOR- DEMOLITION PLANS (DEDUCTIVE BID ALTERNATE)

39 AD112 BUILDING 27 - FIRST FLOOR - DEMOLITION PLANS (DEDUCTIVE BID ALTERNATE)

40 AD113 BUILDING 27 - SECOND FLOOR - DEMOLITION PLANS (DEDUCTIVE BID ALTERNATE)

41 A-100 BUILDING 1 - BASEMENT FLOOR - PLANS

42 A-101 BUILDING 1- FIRST FLOOR - PLANS

43 A-102 BUILDING 1 - SECOND FLOOR - PLANS

44 A-103 BUILDING 1 - THIRD FLOOR - PLANS

45 A-104 BUILDING 1 - FOURTH FLOOR - PLANS

46 A-105 BUILDING 1 - FIFTH FLOOR - PLANS

47 A-106 BUILDING 1 - SIXTH FLOOR - PLANS

48 A-107 BUILDING 1 - SEVENTH FLOOR - PLANS

49 A-108 BUILDING 1 - EIGHTH FLOOR - PLANS

50 A-109 BUILDING 1 - NINTH FLOOR - PLAN - WALL FINISH

51 A-110 BUILDING 1 - ELEVATOR MACHINE ROOM - PLANS

52 A-111 BUILDING 27 - BASEMENT FLOOR PLANS (DEDUCTIVE BID ALTERNATE)

53 A-112 BUILDING 27 - FIRST FLOOR PLANS (DEDUCTIVE BID ALTERNATE)

54 A-113 BUILDING 27 - SECOND FLOOR PLANS (DEDUCTIVE BID ALTERNATE)

55 A-121 BUILDING 1 - ROOF PLAN

56 A-122 BUILDING 27 - ROOF PLAN (DEDUCTIVE BID ALTERNATE)

57 A-201 BUILDING 1 - ELEVATOR ELEVATIONS

58 A-202 BUILDING 1 - INTERIOR ELEVATIONS

59 A-203 BUILDING 27 - ELEVATOR ELEVATIONS (DEDUCTIVE BID ALTERNATE)

60 A-401 BUILDING 1 - ENLARGED PLANS

61 A-402 BUILDING 27 - ELEVATOR CAB - ENLARGED FLOOR PLANS (DEDUCTIVE BID ALTERNATE)

62 A-601 BUILDING 1 - FINISH SCHEDULES, WALL SECTIONS & DETAILS

63 A-602 BUILDING 1 - DOOR SCHEDULE, TYPES AND DETAILS

PAGE # SHEET # SHEET NAME

STRUCTURAL

64 S-001 GENERAL NOTES

65 S-002 GENERAL NOTES

66 S-003 SPECIAL INSPECTIONS

67 S-101 BUILDING 1 BASEMENT FLOOR PLAN

68 S-102 BUILDING 1 - FIRST THRU EIGHT FLOOR PLAN

69 S-110 BUILDING 1 - NINTH FLOOR PLAN

70 S-111 BUILDING 1 - MACHINE ROOM FLOOR PLAN

71 S-113 BUILDING 27 BASEMENT FLOOR PLAN (DEDUCTIVE BID ALTERNATE)

72 S-114 BUILDING 27 - FIRST FLOOR PLAN (DEDUCTIVE BID ALTERNATE)

73 S-115 BUILDING 27 - SECOND FLOOR AND MAIN ROOF PLAN (DEDUCTIVE BID ALTERNATE)

74 S-116 BUILDING 27 - HIGH ROOF PLAN (DEDUCTIVE BID ALTERNATE)

75 S-501 BUILDING 1 DETAILS

76 S-502 BUILDING 27 DETAILS (DEDUCTIVE BID ALTERNATE)

MECHANICAL

77 M-001 MECHANICAL: LEGENDS & SYMBOLS

78 MD100 BLDG 1 SIXTH FLOOR PLAN MECHANICAL DEMO

79 MD101 BLDG 1 MACHINE ROOM FLOOR PLAN MECHANICAL DEMO

80 MD102 BLDG 1 ROOF FLOOR PLAN MECHANICAL DEMO

81 MH101 BLDG 1 SIXTH FLOOR PLAN MECHANICAL

82 MH102 BLDG 1 NINTH FLOOR PLAN MECHANICAL

83 MH103 BLDG 1 MACHINE ROOM FLOOR PLAN MECHANICAL

84 MH104 BLDG 27 BASEMENT FLOOR PLAN MECHANICAL DEDUCTIVE BID ALTERNATE

85 MH105 BLDG 27 FIRST FLOOR PLAN MECHANICAL DEDUCTIVE BID ALTERNATE

86 MH106 BLDG 27 ROOF PLAN MECHANICAL DEDUCTIVE BID ALTERNATE

87 M-501 MECHANICAL: BLDG 1 DETAILS

88 M-502 MECHANICAL: BLDG 27 DETAILS DEDUCTIVE BID ALTERNATE

89 M-601 MECHANICAL: BLDG 1 SCHEDULES

90 M-602 MECHANICAL: BLDG 27 SCHEDULES DEDUCTIVE BID ALTERNATE

91 M-901 MECHANICAL: BLDG 1 CONTROL DIAGRAMS

92 M-902 MECHANICAL: BLDG 27 CONTROL DIAGRAMS DEDUCTIVE BID ALTERNATE

93 FD101 BLDG 1 MACHINE ROOM DEMO FLOOR PLAN FIRE SPRINKLER

94 FX101 BLDG 1 MACHINE ROOM FLOOR PLAN FIRE SPRINKLER

95 FX102 BLDG 27 BASEMENT FLOOR PLAN FIRE SPRINKLER DEDUCTIVE BID ALTERNATE

PLUMBING

96 P-001 PLUMBING NOTES & LEGENDS

97 P-101 BLDG 1 BASEMENT FLOOR PLAN PLUMBING

98 P-102 BLDG 27 - FOUNDATION FLOOR PLAN PLUMBING DEDUCTIVE BID ALTERNATE

99 P-103 BLDG 27 BASEMENT FLOOR PLAN PLUMBING DEDUCTIVE BID ALTERNATE

100 P-501 BLDG 1 PLUMBING DETAILS

101 P-502 BLDG 27 PLUMBING DETAILS DEDUCTIVE BID ALTERNATE

102 P-601 BLDG 1 PLUMBING SCHEDULES

103 P-602 BLDG 27 PLUMBING SCHEDULES DEDUCTIVE BID ALTERNATE

ELECTRICAL

104 E-001 GENERAL NOTES, ABBREVIATIONS AND LEGENDS

105 ED101-1 BUILDING 1 - BASEMENT FLOOR: ELECTRICAL DEMOLITION PLAN

106 ED101-2 BUILDING 1 - BASEMENT FLOOR: ELECTRICAL DEMOLITION PLAN

107 ED102 BUILDING 1 - FIRST FLOOR: ELECTRICAL DEMOLITION PLAN

108 ED103 BUILDING 1 - SECOND FLOOR: ELECTRICAL DEMOLITION PLAN

109 ED104 BUILDING 1 - THIRD FLOOR: ELECTRICAL DEMOLITION PLAN

110 ED105 BUILDING 1 - FOURTH FLOOR: ELECTRICAL DEMOLITION PLAN

111 ED106 BUILDING 1 - FIFTH FLOOR: ELECTRICAL DEMOLITION PLAN

112 ED107 BUILDING 1 - SIXTH FLOOR: ELECTRICAL DEMOLITION PLAN

113 ED108 BUILDING 1 - SEVENTH FLOOR: ELECTRICAL DEMOLITION PLAN

114 ED109 BUILDING 1 - EIGHTH FLOOR: ELECTRICAL DEMOLITION PLAN

115 ED110 BUILDING 1 - NINTH FLOOR: ELECTRICAL DEMOLITION PLAN

116 ED111 BUILDING 1 - MACHINE ROOM: ELECTRICAL DEMOLITION PLAN

117 ED112

BUILDING 27 - BASEMENT FLOOR: ELECTRICAL DEMOLITION PLAN (DEDUCTIVE BID

ALTERNATE)

118 ED113 BUILDING 27 - FIRST FLOOR: ELECTRICAL DEMOLITION PLAN (DEDUCTIVE BID ALTERNATE)

119 ED114

BUILDING 27 - SECOND FLOOR: ELECTRICAL DEMOLITION PLAN (DEDUCTIVE BID

ALTERNATE)

120 EP101-1 BUILDING 1 - BASEMENT FLOOR: POWER, LIGHTING, AND SPECIAL SYSTEMS PLAN

121 EP101-2 BUILDING 1 - BASEMENT FLOOR: POWER AND SPECIAL SYSTEMS PLAN

122 EP102 BUILDING 1 - FIRST FLOOR: POWER AND SPECIAL SYSTEMS PLAN

123 EP103 BUILDING 1 - SECOND FLOOR: POWER AND SPECIAL SYSTEMS PLAN

124 EP104 BUILDING 1 - THIRD FLOOR: POWER AND SPECIAL SYSTEMS PLAN

125 EP105 BUILDING 1 - FOURTH FLOOR: POWER AND SPECIAL SYSTEMS PLAN

126 EP106 BUILDING 1 - FIFTH FLOOR: POWER AND SPECIAL SYSTEMS PLAN

PAGE # SHEET # SHEET NAME

127 EP107 BUILDING 1 - SIXTH FLOOR: POWER AND SPECIAL SYSTEMS PLAN

128 EP108 BUILDING 1 - SEVENTH FLOOR: POWER AND SPECIAL SYSTEMS PLAN

129 EP109 BUILDING 1 - EIGHT FLOOR: POWER AND SPECIAL SYSTEMS PLAN

130 EP110 BUILDING 1 - NINTH FLOOR: POWER, LIGHTING, AND SPECIAL SYSTEMS PLAN

131 EP111 BUILDING 1 - MACHINE ROOM: POWER AND SPECIAL SYSTEMS PLAN

132 EP112

BUILDING 27 - BASEMENT FLOOR: POWER AND SPECIAL SYSTEMS PLAN (DEDUCTIVE BID

ALTERNATE)

133 EP113

BUILDING 27 - FIRST FLOOR: POWER AND SPECIAL SYSTEMS PLAN (DEDUCTIVE BID

ALTERNATE)

134 EP114

BUILDING 27 - SECOND FLOOR: POWER, LIGHTING, AND SPECIAL SYSTEMS PLAN

(DEDUCTIVE BID ALTERNATE)

135 EL111 BUILDING 1 - MACHINE ROOM: LIGHTING PLAN

136 E-501 ELECTRICAL DETAILS

137 E-601 BUILDING 1 - EXISTING PARTIAL ONE-LINE DIAGRAM

138 E-602 BUILDING 1 - REVISED PARTIAL ONE-LINE DIAGRAM

139 E-603 BUILDING 1 - ELECTRICAL LOAD SCHEDULES

140 E-604 BUILDING 1 - ELECTRICAL SCHEDULES

141 E-605 BUILDING 27 - EXISTING ONE-LINE DIAGRAM (DEDUCTIVE BID ALTERNATE)

142 E-606 BUILDING 27 - REVISED ONE-LINE DIAGRAM (DEDUCTIVE BID ALTERNATE)

143 E-607 BUILDING 27 - ELECTRICAL SCHEDULES (DEDUCTIVE BID ALTERNATE)

DCI Engineers 707 W 2nd Ave Spokane WA, 99201 Dylan Larson Cell: 509.227.6937 Email: dlarson@dci-engineers.com

STRUCTURAL

Lerch Bates 19515 North Creek Parkway, #304 Bothell WA, 98011 Carl Cary Cell: 425.213.9932 Email: Carl.Cary@LerchBates.com

ELEVATOR

PhaseARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

A/E:

625 First Ave #301 Seattle, WA, 98104

(206) 590 - 2118

RAY SPEES, PRESIDENT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

STAMPCONSULTANT

321 4 5 6 7 8 9 10

668-18-109

Revisions: Date:

SPEES DESIGN BUILD

REFURBISH AND UPGRADE

ELEVATORS IN BLDG

1 AND 27

11/16/2021

Mann-Grandstaff VA Medical Center

- Spokane, WA

N/A

HIDDEN ABV OR BLW

NEGATIVE AIR MACHINE

TACKY CONSTRUCTION

WALK-OFF MATS

1. COORDINATE WORK WITH ALL CONTRACT DOCUMENTS, INCLUDING BUT NOT LIMITED TO

DRAWINGS AND SPECIFICATIONS.

2. SPECIFICATIONS SHALL SUPERSEDE DRAWING PLANS IN THE CASE OF ANY CONFLICTING

INFORMATION. VERIFY AND RESOLVE CONFLICTS WITH VA COR AND ARCHITECT BEFORE

PROCEEDING.

3. CONTRACTOR AND ANY SUB-CONTRACTORS SHALL ENSURE ALL WORK IS DONE IN

CONFORMANCE WITH ALL APPLICABLE CODES, ORDINANCES AND REGULATIONS. RELEVANT

CODES INCLUDE, BUT ARE NOT LIMITED TO THE FOLLOW:

A. 2021 INTERNATIONAL BUILDING CODE

B. 2021 INTERNATIONAL MECHANICAL CODE

C. 2021 INTERNATIONAL PLUMBING CODE

D. 2021 NFPA 101

E. 2021 NFPA 99

F. 2020 NFPA 70 & 70E

G. 2019 NFPA 13

4. THE INFECTION CONTROL CLASSIFICATION FOR THIS PROJECT IS III/IV. USE 6 MIL

VISQUEEN SHEETING AS INFECTION CONTROL BARRIERS FOR SHORT-TERM PROJECTS THAT

WILL GENERATE MINIMAL DUST. THESE SHOULD BE COMPLETELY AIRTIGHT AND SEALED

FROM CEILING TO FLOOR WITH OVERLAPPING CURTAINS. HOLES, TEARS, OR OTHER

PERFORATIONS REPAIRED PROMPTLY WITH TAPE. A PORTABLE, INDUSTRIAL GRADE HEPA

FILTER EXHAUST FAN ON CONTINUOUS OPERATION IS NEEDED WITHIN THE CONTAINED

AREA, WITH THE FILTERED AIR EXHAUSTED TO THE OUTSIDE OF THE WORK ZONE. PHASING

AND BARRIER LOCATIONS TO BE COORDINATED WITH VA, CONTRACTOR, AND ARCHITECT

PRIOR TO COMMENCING WORK.

5. ALL WORK SHALL BE PERFORMED IN A NEAT AND WORKMANLIKE MANNER WITHIN STANDARD

OF CARE FOR PROFESSION. PROJECT DOCUMENTATION MAY INDICATE WORK OR STANDARDS

WHICH EXCEED CODE MINIMUMS. SPECIFICATIONS AND PLAN DRAWINGS ARE TO BE TAKEN

TOGETHER AND UNDERSTOOD AS ONE. THOROUGHLY AND COMPLETELY CLEAN THE

CONSTRUCTION ZONE BEFORE THE CONSTRUCTION BARRIERS ARE REMOVED.

6. DISCREPANCIES OR OMISSIONS BETWEEN EXISTING CONDITIONS AND PROJECT

DOCUMENTATION SHALL BE BROUGHT TO THE ATTENTION OF THE COR AND ARCHITECT

PRIOR TO BID OR WORK.

7. ALL COMPONENTS, DEVICES, MATERIALS, AND UTILIZATION EQUIPMENT FURNISHED OR

PROVIDED UNDER THIS SECTION SHALL BE NEW AND ORIGINAL, LISTED AND LABELED TO

U.L. OR EQUIVALENT FOR ITS INTENDED PURPOSE, SUITABLE FOR ITS USE AND SHALL BE

INSTALLED PER MANUFACTURER'S RECOMMENDATIONS OR WRITTEN INSTRUCTIONS,

OPERATE PER DESIGN INTENT, BE UNDAMAGED AND HAVE MANUFACTURER'S FULL

WARRANTY IN EFFECT AT THE DATE OF FINAL ACCEPTANCE OF THIS WORK.

8. BY THE ACT OF SUBMITTING A BID THE CONTRACTOR SHALL BE DEEMED TO HAVE EXAMINED

THE SITE, ALL CONSTRUCTION DOCUMENTS, IDENTIFIED HAZARDS PRESENT AND TO HAVE

ACCEPTED GENERAL AND EXISTING CONDITIONS AND INCLUDED ALLOWANCES IN THE BID.

9. PATCHING SHALL BE OF THE SAME MATERIALS AND MATCH ADJACENT FINISHES; FINISH

SAMPLES TO BE SUBMITTED TO THE VA COR AND THE ARCHITECT FOR APPROVAL.

CONTRACTOR SHALL COMPLY WITH VA DUST & INFECTION CONTROL RISK FOR

CONSTRUCTION & RENOVATION; AT MINIMUM, REFER TO AND COMPLY WITH ASHE DEFINED

"TYPE A" INSPECTION AND NON-INVASIVE ACTIVITIES; "TYPE B" SMALL SCALE, SHORT

DURATION ACTIVITIES WHICH CREATE MINIMAL DUST.

10. CONTRACTOR AND ANY SUB-CONTRACTORS SHALL FAMILIARIZE THEMSELVES WITH

EXISTING CONDITIONS, LOCATIONS AND PROJECT REQUIREMENTS PRIOR TO SUBMITTING A

BID.

11. THE CONTRACTOR SHALL CHECK AND FIELD VERIFY ALL EXISTING CONDITIONS AND

DIMENSIONS BEFORE BEGINNING WORK. ANY CONFLICTS BETWEEN EXISTING CONDITIONS

AND THE DRAWINGS AND SPECIFICATIONS SHALL BE BROUGHT IMMEDIATELY TO THE

ATTENTION OF THE VA COR AND THE ARCHITECT.

12. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING ALL PRODUCT TYPES AND QUANTITIES

DURING SITE WALK THROUGH WITH THE COR, BEFORE PURCHASING ANY MATERIALS,

EQUIPMENT, PRODUCTS OR LABOR.

13. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION AND COORDINATION WITH

ALL INSTALLERS TO ENSURE COMPLIANCE TO THE DRAWINGS AND SPECIFICATIONS.

14. CONTRACTOR SHALL BE RESPONSIBLE FOR SUBMITTING A CONSTRUCTION SCHEDULE. THE

PLAN WILL BE REVIEWED AND APPROVED BY THE VA COR PRIOR TO BEGINNING WORK.

15. DIMENSIONS ARE NOT ADJUSTABLE UNLESS NOTED WITH A +/- SYMBOL. ONLY NORMAL

INDUSTRY STANDARD TOLERANCES ARE ACCEPTABLE DEVIATIONS FROM DIMENSIONS

INDICATED. DO NOT SCALE DRAWINGS. ALL DIMENSIONS NOTED AS CLEAR SHALL MAINTAIN

THE FULL SPACE INDICATED WITHOUT ENCROACHMENTS. ALL VERTICAL HEIGHTS INDICATED

ARE FROM THE FINISH FLOOR ELEVATION UNLESS OTHERWISE NOTED.

16. SEE ABOVE FOR ARCHITECTURAL SYMBOLS & ABBREVIATIONS.

17. SEE SHEET G-002 FOR DRAWING INDEX.

18. ALL WORK IS "NEW" WORK USING "NEW" MATERIALS UNLESS IT IS LABELED AS EXISTING.

19. FURNISH ALL PRODUCTS TO COMPLY WITH VA STANDARDS.

20. ELEVATOR EQUIPMENT SHOWN IN DRAWINGS ARE FOR REFERENCE PURPOSES ONLY AND

WILL BE DEPENDANT ON THE ELEVATOR MANUFACTURER'S DESIGN DURING CONSTRUCTION.

AB

ABV

ADJ

A/E

AFF

AGG

ALT

ALUM

APPROX

ARCH

ASPH

A/V

BARR

BATH

BRKT

BLDG

BLK

BLKG

BLW

BM

BMTU

BRNG

BOC

BOS

BO

BTM

BRC

CAB

CLG

CTR

CLR

CO

COL

COMP

CONC

CMU

CONN

CONST

CONT

COR

CJ

CS

COORD

CORR

DEMO

DIA

DC

DIM

DN

DR

DBL

DTL

DWG

E

EA

ELEV

ELEC

EOC

EOP

EQ

EQUIP

ES

EX(IST)

EXP

EJ

ETS

EXT

FA

FD

FE(C)

FF

FFB

FFL

FIN

FLASH

FLR

FLOUR

FNDN

FOC

FOF

FOS

FP

FRM

FT

FTG

FUR

FURN

GA

GALV

GC

GMU

GLB

GB/GWB

GFGI

GOVT

GYP

HDWE

HDR

HT

HM

HORZ

HR

ICRA

INCL

INST

ID

INSUL

INT

JT

KV

LAM

LAV

LT

MAT

MAX

MECH

MFR

MIN

MISC

MTL

MOD

N/A

NOM

N

NTS

NO.

O.C.

OFCI

OFOI

OPNG

OPP

OVHD

P

PR

PNL

PTN(S)

PVMT

P.C.

PRFB

PT

PL

PLYWD

PLAM

PS

QTY

RAD

REF

REINF

REQ

REQ'D

REQ'MT

RESIL

REV

RM

RO

S

SCHED

SECT

SF

SHG

SHT(G)

SIM

SM

SPEC

SQ

SS

STDG

STL

STOR

STRUCT

SUSP

SV

SYS

THK

THRESH

TOC

TOS

TPH

T&G

TRANS

TS

TYP

UON

VA

VAR

VB

VERT

VIF

W

WT

W/

W/O

WD

WDW

WP

WH

WR

WT

AND

ANGLE

AT

CENTERLINE

DEGREES

NUMBER

ANCHOR BOLT

ABOVE

ADJACENT

ARCHITECT/ENGINEER

ABOVE FINISH FLOOR

AGGREGATE

ALTERNATE

ALUMINUM

APPROXIMATELY

ARCHITECT(URAL)

ASPHALT

AUDIO / VIDEO

BARRIER

BATHROOM

BRACKET

BUILDING

BLOCK

BLOCKING

BELOW

BEAM

BONE MARROW TRANSPLANT UNIT

BEARING

BOTTOM OF CURB

BOTTOM OF SLAB

BOTTOM OF

BOTTOM

BRACE, BRACING

CABINET

CEILING

CENTER

CLEAR

CONTRACTING OFFICER

COLUMN

COMPOSITION

CONCRETE

CONCRETE MASONRY UNIT

CONNECTION

CONSTRUCTION

CONTINUOUS

CONTRACTING OFFICER'S REP.

CONTROL JOINT

CONCRETE SEALER

COORDINATE

CORRIDOR

DEMOLISH(ION)

DIAMETER

DIRECT CURRENT

DIMENSION

DOWN

DOOR

DOUBLE

DETAIL

DRAWING(S)

EAST

EACH

ELEVATION

ELECTRIC(AL)

END OF CURB

EDGE OF PAVEMENT

EQUAL

EQUIPMENT

EACH SIDE

EXISTING

EXPANSION

EXPANSION JOINT

EXPOSED TO STRUCTURE

EXTERIOR

FIRE ALARM

FLOOR DRAIN

FIRE EXTINGUISHER (CABINET)

FACTORY FINISH

FINISH FLOOR BREAK

FINISH FLOOR LINE

FINISH(ED)

FLASHING

FLOOR(ING)

FLOURESCENT

FOUNDATION

FACE OF CONCRETE

FACE OF FINISH

FACE OF STUDS

FIRE PROOF

FRAME

FOOT, FEET

FOOTING

FURRING

FURNISHED

GAGE, GAUGE

GALVANIZED

GENERAL CONTRACTOR

GLASS MASONRY UNIT

GLUE LAMINATED BEAM

GYPSUM WALL BOARD

GOVT FURN. GOVT INSTALLED

GOVERNMENT

GYPSUM

HARDWARE

HEADER

HEIGHT

HOLLOW METAL

HORIZONTAL

HOUR

INFECTIOUS CONTROL RISK

ASSESSMENT

INCLUDE(D,ING)

INSTALL

INSIDE DIAMETER OR DIMENSION

INSULATION

INTERIOR

JOINT

KILOVOLT

LAMINATE(D)

LAVATORY

LIGHT

MATERIAL(S)

MAXIMUM

MECHANIC(AL)

MANUFACTURE(R)

MINIMUM

MISCELLANEOUS

METAL

MODIFIED

NOT APPLICABLE

NOMINAL

NORTH

NOT TO SCALE

NUMBER

ON CENTER(S)

OWNER FURN. CONTRACTOR INST.

OWNER FURN. OWNER INST.

OPENING

OPPOSITE

OVERHEAD

PAINT

PAIR

PANEL

PARTITION(S)

PAVEMENT

PRECAST CONCRETE

PREFABRICATED

PRESSURE TREATED

PLATE

PLYWOOD

PLASTIC LAMINATE

PLASTIC

QUANTITY

RADIUS

REFERENCE

REINFORCE(D,ING)

REQUIRE

REQUIRED

REQUIREMENT

RESILIENT

REVERSE

ROOM

ROUGH OPENING

SOUTH

SCHEDULE

SECTION

SQUARE FEET

SHINGLES

SHEET (SHEATHING)

SIMILAR

SEAM

SPECIFICATION

SQUARE

STAINLESS STEEL

STANDING

STEEL

STORAGE

STRUCTURAL

SUSPENDED

SHEET VINYL

SYSTEM

THICK(NESS)

THRESHOLD

TOP OF CURB

TOP OF SIDEWALK/PAD

TOILET PAPER HOLDER

TONGUE AND GROOVE

TRANSITION

TUBE STEEL

TYPICAL

UNLESS OTHERWISE NOTED

US DEPT. OF VETERANS AFFAIRS

VARIES

VAPOR BARRIER

VERTICAL

VERIFY IN FIELD

WEST

WEIGHT

WITH

WITHOUT

WOOD

WINDOW

WATERPROOF(ING)

WATER HEATER

WATER RESISTANT

WOOD TRIM

PATH OF TRAVEL FOR DEMOLITION DEBRIS

AND NEW EQUIPMENT

BATT INSULATION

ARCHITECTURAL SYMBOLS ABBREVIATIONS

G-003

ECMK

SYMBOLS, ABBREVIATIONS

AND GENERAL NOTES

WINDOW TAG

FIRE SPRINKLER SHUT OFF VALVE

FIRE EXTINGUISHER

2 HOUR FIRE BARRIER

SMOKE PARTITION

GENERAL & ARCHITECTURAL NOTES

KEY NOTE

EXTERIOR ELEVATION FLAG

BUILDING SECTION FLAG

WALL SECTION FLAG

CALLOUT FLAG

TRUE NORTH ARROW (PROJECT

NORTH DASHED)

HORIZONTAL GRID LINE

VERTICAL GRID LINE

WALL TYPE TAG

DOOR TAG

ELEVATION MARKER

ROOM TAG

CEILING HEIGHT TAG

BATH

INTERIOR ELEVATION FLAG

A-101 1

A-101

A-101

A-101

A

9'-0"

9'-0"

D2 A-512

AutoCAD SHX Text

FEX

R

AM

P D N

U P

2"

2" 2" 2"

GC101

JW/MCMK

BUILDING 1 - BASEMENT FLOOR-

ICRA FLOOR PLANS

1 BASEMENT FLOOR ADJACENCY FLOOR PLAN - BLDG 1

1/16" = 1'-0"

PhaseARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

A/E:

625 First Ave #301 Seattle, WA, 98104

(206) 590 - 2118

RAY SPEES, PRESIDENT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

FOR CONSTRUCTION

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

STAMPCONSULTANT

321 4 5 6 7 8 9 10

668-18-109

Revisions: Date:

SPEES DESIGN BUILD

REFURBISH AND UPGRADE

ELEVATORS IN BLDG

1 AND 27

11/16/2021

Mann-Grandstaff VA Medical Center

- Spokane, WA

N

DUMPSTER

REFRIGERATION

MISC

STORAGE

MAIN

KITCHEN

RECORDS

KITCHEN

OFFICES

LOADING

BAY

AREA OF

WORK

BUILDING 27

KITCHEN

IT

OFFICES

ENGINEERING

STORAGE

KITCHEN

STORAGE

EMS

OFFICE

CLASS III ICRA NOTES

GENERAL NOTES

1. DURING CONSTRUCTION, THE ENTIRE UNIT WILL BE

VACATED. DOORS WILL BE SECURED TO EVERYONE BUT

CONSTRUCTION STAFF AND ESSENTIAL VA STAFF.

2. REMOVE EQUIPMENT AND ANY CONSTRUCTION DEBRIS

FROM SPACE USING COVERED SEALED CARTS.

3. SEE SPEC SECTION 01 35 26 FOR SAFETY REQUIREMENTS.

4. MAINTAIN 4'-0" MINIMUM CLEARANCE FOR EGRESS

AROUND ICRA WALLS.

5. MAINTAIN CALL BUTTON ACCESSIBILITY OUTSIDE OF ICRA

BARRIERS DURING PHASE 1 AND 2.

4 PHASE 3 - BASEMENT FLOOR ICRA FLOOR PLAN - BLDG 1

1/8" = 1'-0" N

SHEET KEYNOTES

1. DOOR TO REMAIN CLOSED AND SEALED DURING ENTIRETY

OF CONSTRUCTION PHASE.

2. TEMP ICRA DOOR TO REMAIN IN PLACE FOR ENTIRETY OF

CONSTRUCTION PHASE.PROVIDE TACKY CONSTRUCTION

WALK-OFF MATS ON ENTRANCE AND EXIT SIDE OF

CONSTRUCTION ACTIVITY ACCESS POINTS

3. VERIFY EXISTING WALLS ISOLATING THE WORK AREA ARE

FIRESTOPPED AND GO TO CONCRETE FLOOR ABOVE. IF NOT,

INSTALL FIRESTOPPING AND LT1 TEMP BARRIER FROM TOP

OF EXISTING WALLS TO CONCRETE FLOOR ABOVE.

4. NEGATIVE PRESSURE, ISOLATED CONSTRUCTION ZONE.

5. HEPA ISO CLASS 7 FILTERED NEGATIVE AIR TO BE

MAINTAINED WITHIN CONSTRUCTION AREA. COVER ALL

HOLES, CONDUITS, AND ENTRANCE/EXIT TO CONSTRUCTION

SITE. COVER INTAKE/RETURNS WITH PAPER FLUTED FILTERS,

IN AREA WHERE WORK IS BEING DONE TO PREVENT

CONTAMINATION OF DUCT SYSTEM.

6. LT1 TEMP BARRIER TO REMAIN FOR DURATION OF

CONSTRUCTION PHASE. DEMOLISH ONCE CONSTRUCTION

PHASE HAS BEEN COMPLETED.

3 PHASE 2 - BASEMENT FLOOR ICRA FLOOR PLAN - BLDG 1

1/8" = 1'-0" N 2 PHASE 1 - BASEMENT FLOOR ICRA FLOOR PLAN - BLDG 1

1/8" = 1'-0" N

- 2

LEGEND

REFER TO KEYNOTE 3

PROJECT CONSTRUCTION IS IDENTIFIED AS TYPE C

CONSTRUCTION ACTIVITY

PROJECT RISK FOR <HOSPITAL UNIT> IS HIGH RISK GROUP

THIS COMBINATION INVOKES CLASS III & IV ICRA

PRECAUTIONS

REFER TO SPECIFICATION SECTION 01 35 26 - SAFETY

REQUIREMENTS FOR CLASS III INFECTION CONTROL

REQUIREMENTS.

GC102

JW/MCMK

BUILDING 1 - FIRST FLOOR -

ICRA FLOOR PLANS

1 FIRST FLOOR ADJACENCY FLOOR PLAN - BLDG 1

1/16"= 1'-0"

PhaseARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

A/E:

625 First Ave #301 Seattle, WA, 98104

(206) 590 - 2118

RAY SPEES, PRESIDENT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

FOR CONSTRUCTION

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

STAMPCONSULTANT

321 4 5 6 7 8 9 10

668-18-109

Revisions: Date:

SPEES DESIGN BUILD

REFURBISH AND UPGRADE

ELEVATORS IN BLDG

1 AND 27

11/16/2021

Mann-Grandstaff VA Medical Center

- Spokane, WA

N

AREA OF WORK

BUILDING 27

PHARMACY

ADMIN

OFFICES

IT

CLOSET

PHARMACY

OFFICES

4 PHASE 3 - FIRST FLOOR ICRA FLOOR PLAN - BLDG 1

1/8" = 1'-0" N

BUILDING 1E

3 PHASE 2 - FIRST FLOOR ICRA FLOOR PLAN - BLDG 1

1/8" = 1'-0" N 2 PHASE 1 - FIRST FLOOR ICRA FLOOR PLAN - BLDG 1

1/8" = 1'-0" N

- 4

GENERAL NOTES

SHEET KEYNOTES

1. DOOR TO REMAIN CLOSED AND SEALED DURING ENTIRETY

OF CONSTRUCTION PHASE. CONTRACTOR TO PROVIDE

TEMPORARY INTERCOM SYSTEM AT ANOTHER ENTRY POINT

FOR HOSPITAL OPERATIONS. COORDINATE WITH VA COR FOR

LOCATION OF ENTRY POINT.

2. TEMP ICRA DOOR TO REMAIN IN PLACE FOR ENTIRETY OF

CONSTRUCTION PHASE.PROVIDE TACKY CONSTRUCTION

WALK-OFF MATS ON ENTRANCE AND EXIT SIDE OF

CONSTRUCTION ACTIVITY ACCESS POINTS

3. VERIFY EXISTING WALLS ISOLATING THE WORK AREA ARE

FIRESTOPPED AND GO TO CONCRETE FLOOR ABOVE. IF NOT,

INSTALL FIRESTOPPING AND LT1 TEMP BARRIER FROM TOP

OF EXISTING WALLS TO CONCRETE FLOOR ABOVE.

4. NEGATIVE PRESSURE, ISOLATED CONSTRUCTION ZONE.

5. HEPA ISO CLASS 7 FILTERED NEGATIVE AIR TO BE

MAINTAINED WITHIN CONSTRUCTION AREA. COVER ALL

HOLES, CONDUITS, AND ENTRANCE/EXIT TO CONSTRUCTION

SITE. COVER INTAKE/RETURNS WITH PAPER FLUTED FILTERS,

IN AREA WHERE WORK IS BEING DONE TO PREVENT

CONTAMINATION OF DUCT SYSTEM.

6. LT1 TEMP BARRIER TO REMAIN FOR DURATION OF

CONSTRUCTION PHASE. DEMOLISH ONCE CONSTRUCTION

PHASE HAS BEEN COMPLETED.

1. DURING CONSTRUCTION, THE ENTIRE UNIT WILL BE

VACATED. DOORS WILL BE SECURED TO EVERYONE BUT

CONSTRUCTION STAFF AND ESSENTIAL VA STAFF.

2. REMOVE EQUIPMENT AND ANY CONSTRUCTION DEBRIS

FROM SPACE USING COVERED SEALED CARTS.

3. SEE SPEC SECTION 01 35 26 FOR SAFETY REQUIREMENTS.

4. MAINTAIN 4'-0" MINIMUM CLEARANCE FOR EGRESS

AROUND ICRA WALLS.

5. MAINTAIN CALL BUTTON ACCESSIBILITY OUTSIDE OF ICRA

BARRIERS DURING PHASE 1 AND 2.

LEGEND

REFER TO KEYNOTE 3

CLASS III ICRA NOTES

PROJECT CONSTRUCTION IS IDENTIFIED AS TYPE C

CONSTRUCTION ACTIVITY

PROJECT RISK FOR <HOSPITAL UNIT> IS HIGH RISK GROUP

THIS COMBINATION INVOKES CLASS III & IV ICRA

PRECAUTIONS

REFER TO SPECIFICATION SECTION 01 35 26 - SAFETY

REQUIREMENTS FOR CLASS III INFECTION CONTROL

REQUIREMENTS.

AutoCAD SHX Text

DN

EXTERIOR

ROOF AREA

GC103

JW/MCMK

BUILDING 1 - SECOND FLOOR -

ICRA FLOOR PLANS

PhaseARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

A/E:

625 First Ave #301 Seattle, WA, 98104

(206) 590 - 2118

RAY SPEES, PRESIDENT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

FOR CONSTRUCTION

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

STAMPCONSULTANT

321 4 5 6 7 8 9 10

668-18-109

Revisions: Date:

SPEES DESIGN BUILD

REFURBISH AND UPGRADE

ELEVATORS IN BLDG

1 AND 27

11/16/2021

Mann-Grandstaff VA Medical Center

- Spokane, WA

N1 SECOND FLOOR ADJACENCY FLOOR PLAN - BLDG 1

1/16" = 1'-0"

IMAGING

LAB

AREA OF WORK

NUCLEAR

MEDICINE

IT

CLOSET

EMS

OFFICE

4 PHASE 3 - SECOND FLOOR ICRA FLOOR PLAN - BLDG 1

1/8" = 1'-0" N

CLASS III ICRA NOTES

3 PHASE 2 - SECOND FLOOR ICRA FLOOR PLAN - BLDG 1

1/8" = 1'-0" N 2 PHASE 1 - SECOND FLOOR ICRA FLOOR PLAN - BLDG 1

1/8" = 1'-0" N

+ 2

1 3

6 2

GENERAL NOTES

SHEET KEYNOTES

1. DOOR TO REMAIN CLOSED AND SEALED DURING ENTIRETY

OF CONSTRUCTION PHASE.

2. TEMP ICRA DOOR TO REMAIN IN PLACE FOR ENTIRETY OF

CONSTRUCTION PHASE.PROVIDE TACKY CONSTRUCTION

WALK-OFF MATS ON ENTRANCE AND EXIT SIDE OF

CONSTRUCTION ACTIVITY ACCESS POINTS

3. VERIFY EXISTING WALLS ISOLATING THE WORK AREA ARE

FIRESTOPPED AND GO TO CONCRETE FLOOR ABOVE. IF NOT,

INSTALL FIRESTOPPING AND LT1 TEMP BARRIER FROM TOP

OF EXISTING WALLS TO CONCRETE FLOOR ABOVE.

4. NEGATIVE PRESSURE, ISOLATED CONSTRUCTION ZONE.

5. HEPA ISO CLASS 7 FILTERED NEGATIVE AIR TO BE

MAINTAINED WITHIN CONSTRUCTION AREA. COVER ALL

HOLES, CONDUITS, AND ENTRANCE/EXIT TO CONSTRUCTION

SITE. COVER INTAKE/RETURNS WITH PAPER FLUTED FILTERS,

IN AREA WHERE WORK IS BEING DONE TO PREVENT

CONTAMINATION OF DUCT SYSTEM.

6. LT1 TEMP BARRIER TO REMAIN FOR DURATION OF

CONSTRUCTION PHASE. DEMOLISH ONCE CONSTRUCTION

PHASE HAS BEEN COMPLETED.

1. DURING CONSTRUCTION, THE ENTIRE UNIT WILL BE

VACATED. DOORS WILL BE SECURED TO EVERYONE BUT

CONSTRUCTION STAFF AND ESSENTIAL VA STAFF.

2. REMOVE EQUIPMENT AND ANY CONSTRUCTION DEBRIS

FROM SPACE USING COVERED SEALED CARTS.

3. SEE SPEC SECTION 01 35 26 FOR SAFETY REQUIREMENTS.

4. MAINTAIN 4'-0" MINIMUM CLEARANCE FOR EGRESS

AROUND ICRA WALLS.

5. MAINTAIN CALL BUTTON ACCESSIBILITY OUTSIDE OF ICRA

BARRIERS DURING PHASE 1 AND 2.

LEGEND

REFER TO KEYNOTE 3

PROJECT CONSTRUCTION IS IDENTIFIED AS TYPE C

CONSTRUCTION ACTIVITY

PROJECT RISK FOR <HOSPITAL UNIT> IS HIGH RISK GROUP

THIS COMBINATION INVOKES CLASS III & IV ICRA

PRECAUTIONS

REFER TO SPECIFICATION SECTION 01 35 26 - SAFETY

REQUIREMENTS FOR CLASS III INFECTION CONTROL

GC104

BUILDING 1 - THIRD FLOOR -

ICRA FLOOR PLANS

1 THIRD FLOOR ADJACENCY FLOOR PLAN

1/16" = 1'-0"

PhaseARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

A/E:

625 First Ave #301 Seattle, WA, 98104

(206) 590 - 2118

RAY SPEES, PRESIDENT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

FOR CONSTRUCTION

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

STAMPCONSULTANT

321 4 5 6 7 8 9 10

668-18-109

Revisions: Date:

SPEES DESIGN BUILD

REFURBISH AND UPGRADE

ELEVATORS IN BLDG

1 AND 27

11/16/2021

Mann-Grandstaff VA Medical Center

- Spokane, WA

N

INPATIENT

PSYCHIATRIC

OUTPATIENT

EXAM RMS

AREA OF WORK

TOILET

IT

CLOSET

ADMIN

OFFICES

APU

4 PHASE 3 - THIRD FLOOR ICRA FLOOR PLAN - BLDG 1

1/8" = 1'-0" N

CLASS III ICRA NOTES

3 PHASE 2 - THIRD FLOOR ICRA FLOOR PLAN - BLDG 1

1/8" = 1'-0" N

2 PHASE 1 - THIRD FLOOR ICRA FLOOR PLAN - BLDG 1

1/8" = 1'-0" N

+ 1 5

3 4

GENERAL NOTES

SHEET KEYNOTES

1. TEMP ICRA DOOR TO REMAIN IN PLACE FOR ENTIRETY OF

CONSTRUCTION PHASE.PROVIDE TACKY CONSTRUCTION

WALK-OFF MATS ON ENTRANCE AND EXIT SIDE OF

CONSTRUCTION ACTIVITY ACCESS POINTS

2. VERIFY EXISTING WALLS ISOLATING THE WORK AREA ARE

FIRESTOPPED AND GO TO CONCRETE FLOOR ABOVE. IF NOT,

INSTALL FIRESTOPPING AND LT1 TEMP BARRIER FROM TOP

OF EXISTING WALLS TO CONCRETE FLOOR ABOVE.

3. NEGATIVE PRESSURE, ISOLATED CONSTRUCTION ZONE.

4. HEPA ISO CLASS 7 FILTERED NEGATIVE AIR TO BE

MAINTAINED WITHIN CONSTRUCTION AREA. COVER ALL

HOLES, CONDUITS, AND ENTRANCE/EXIT TO CONSTRUCTION

SITE. COVER INTAKE/RETURNS WITH PAPER FLUTED FILTERS,

IN AREA WHERE WORK IS BEING DONE TO PREVENT

CONTAMINATION OF DUCT SYSTEM.

5. LT1 TEMP BARRIER TO REMAIN FOR DURATION OF

CONSTRUCTION PHASE. DEMOLISH ONCE CONSTRUCTION

PHASE HAS BEEN COMPLETED.

1. DURING CONSTRUCTION, THE ENTIRE UNIT WILL BE

VACATED. DOORS WILL BE SECURED TO EVERYONE BUT

CONSTRUCTION STAFF AND ESSENTIAL VA STAFF.

2. REMOVE EQUIPMENT AND ANY CONSTRUCTION DEBRIS

FROM SPACE USING COVERED SEALED CARTS.

3. SEE SPEC SECTION 01 35 26 FOR SAFETY REQUIREMENTS.

4. MAINTAIN 4'-0" MINIMUM CLEARANCE FOR EGRESS

AROUND ICRA WALLS.

5. MAINTAIN CALL BUTTON ACCESSIBILITY OUTSIDE OF ICRA

BARRIERS DURING PHASE 1 AND 2.

LEGEND

REFER TO KEYNOTE 2

PROJECT CONSTRUCTION IS IDENTIFIED AS TYPE C

CONSTRUCTION ACTIVITY

PROJECT RISK FOR <HOSPITAL UNIT> IS HIGH RISK GROUP

III-IV

THIS COMBINATION INVOKES CLASS III ICRA PRECAUTIONS

REFER TO SPECIFICATION SECTION 01 35 26 - SAFETY

REQUIREMENTS FOR CLASS III INFECTION CONTROL

1 FOURTH FLOOR ADJACENCY FLOOR PLAN

1/16" = 1'-0"

PhaseARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

A/E:

625 First Ave #301 Seattle, WA, 98104

(206) 590 - 2118

RAY SPEES, PRESIDENT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

FOR CONSTRUCTION

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

STAMPCONSULTANT

321 4 5 6 7 8 9 10

668-18-109

Revisions: Date:

SPEES DESIGN BUILD

REFURBISH AND UPGRADE

ELEVATORS IN BLDG

1 AND 27

11/16/2021

Mann-Grandstaff VA Medical Center

- Spokane, WA

N

GC105

JW/MCMK

BUILDING 1 - FOURTH FLOOR -

ICRA FLOOR PLANS

INPATIENT

ROOMS

INPATIENT

ROOMS

AREA OF WORK

IT

CLOSET

ADMIN

OFFICES

CLEAN

LINEN

STORAGE

2 PHASE 1 - FOURTH FLOOR ICRA FLOOR PLAN - BLDG 1

1/8" = 1'-0" N

3 PHASE 2 - FOURTH FLOOR ICRA FLOOR PLAN - BLDG 1

1/8" = 1'-0" N4 PHASE 3 - FOURTH FLOOR ICRA FLOOR PLAN - BLDG 1

1/8" = 1'-0" N

32 3

GENERAL NOTES

SHEET KEYNOTES

CLASS III ICRA NOTES

1. DOOR TO REMAIN CLOSED AND SEALED DURING ENTIRETY

OF CONSTRUCTION PHASE.

2. TEMP ICRA DOOR TO REMAIN IN PLACE FOR ENTIRETY OF

CONSTRUCTION PHASE.PROVIDE TACKY CONSTRUCTION

WALK-OFF MATS ON ENTRANCE AND EXIT SIDE OF

CONSTRUCTION ACTIVITY ACCESS POINTS

3. VERIFY EXISTING WALLS ISOLATING THE WORK AREA ARE

FIRESTOPPED AND GO TO CONCRETE FLOOR ABOVE. IF NOT,

INSTALL FIRESTOPPING AND LT1 TEMP BARRIER FROM TOP

OF EXISTING WALLS TO CONCRETE FLOOR ABOVE.

4. NEGATIVE PRESSURE, ISOLATED CONSTRUCTION ZONE.

5. HEPA ISO CLASS 7 FILTERED NEGATIVE AIR TO BE

MAINTAINED WITHIN CONSTRUCTION AREA. COVER ALL

HOLES, CONDUITS, AND ENTRANCE/EXIT TO CONSTRUCTION

SITE. COVER INTAKE/RETURNS WITH PAPER FLUTED FILTERS,

IN AREA WHERE WORK IS BEING DONE TO PREVENT

CONTAMINATION OF DUCT SYSTEM.

6. LT1 TEMP BARRIER TO REMAIN FOR DURATION OF

CONSTRUCTION PHASE. DEMOLISH ONCE CONSTRUCTION

PHASE HAS BEEN COMPLETED.

1. DURING CONSTRUCTION, THE ENTIRE UNIT WILL BE

VACATED. DOORS WILL BE SECURED TO EVERYONE BUT

CONSTRUCTION STAFF AND ESSENTIAL VA STAFF.

2. REMOVE EQUIPMENT AND ANY CONSTRUCTION DEBRIS

FROM SPACE USING COVERED SEALED CARTS.

3. SEE SPEC SECTION 01 35 26 FOR SAFETY REQUIREMENTS.

4. MAINTAIN 4'-0" MINIMUM CLEARANCE FOR EGRESS

AROUND ICRA WALLS.

5. MAINTAIN CALL BUTTON ACCESSIBILITY OUTSIDE OF ICRA

BARRIERS DURING PHASE 1 AND 2.

LEGEND

REFER TO KEYNOTE 3

PROJECT CONSTRUCTION IS IDENTIFIED AS TYPE C

CONSTRUCTION ACTIVITY

PROJECT RISK FOR <HOSPITAL UNIT> IS HIGH RISK GROUP

THIS COMBINATION INVOKES CLASS III & IV ICRA

PRECAUTIONS

REFER TO SPECIFICATION SECTION 01 35 26 - SAFETY

REQUIREMENTS FOR CLASS III INFECTION CONTROL

SP

SD

SD

SPSPSP

PhaseARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

A/E:

625 First Ave #301 Seattle, WA, 98104

(206) 590 - 2118

RAY SPEES, PRESIDENT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

FOR CONSTRUCTION

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

STAMPCONSULTANT

321 4 5 6 7 8 9 10

668-18-109

Revisions: Date:

SPEES DESIGN BUILD

REFURBISH AND UPGRADE

ELEVATORS IN BLDG

1 AND 27

11/16/2021

Mann-Grandstaff VA Medical Center

- Spokane, WA

N

GC106

JW/MCMK

BUILDING 1 - FIFTH FLOOR -

ICRA FLOOR PLANS

1 FIFTH FLOOR ADJACENCY FLOOR PLAN

1/16" = 1'-0"

AREA OF WORK

INPATIENT

ROOMS

INPATIENT

ROOMS

IT

CLOSET

EMS

OFFICE

MEDICAL

EQUIPMENT

STORAGE

MEDICAL

OFFICES LOCKER / TOILET

CLEAN

STORAGE

2 PHASE 1 - FIFTH FLOOR ICRA FLOOR PLAN - BLDG 1

1/8" = 1'-0" N

3 PHASE 2 - FIFTH FLOOR ICRA FLOOR PLAN - BLDG 1

1/8" = 1'-0" N4 PHASE 3 - FIFTH FLOOR ICRA FLOOR PLAN - BLDG 1

1/8" = 1'-0" N

2 3

GENERAL NOTES

SHEET KEYNOTES

1. DOOR TO REMAIN CLOSED AND SEALED DURING ENTIRETY

OF CONSTRUCTION PHASE.

2. TEMP ICRA DOOR TO REMAIN IN PLACE FOR ENTIRETY OF

CONSTRUCTION PHASE.PROVIDE TACKY CONSTRUCTION

WALK-OFF MATS ON ENTRANCE AND EXIT SIDE OF

CONSTRUCTION ACTIVITY ACCESS POINTS

3. VERIFY EXISTING WALLS ISOLATING THE WORK AREA ARE

FIRESTOPPED AND GO TO CONCRETE FLOOR ABOVE. IF NOT,

INSTALL FIRESTOPPING AND LT1 TEMP BARRIER FROM TOP

OF EXISTING WALLS TO CONCRETE FLOOR ABOVE.

4. NEGATIVE PRESSURE, ISOLATED CONSTRUCTION ZONE.

5. HEPA ISO CLASS 7 FILTERED NEGATIVE AIR TO BE

MAINTAINED WITHIN CONSTRUCTION AREA. COVER ALL

HOLES, CONDUITS, AND ENTRANCE/EXIT TO CONSTRUCTION

SITE. COVER INTAKE/RETURNS WITH PAPER FLUTED FILTERS,

IN AREA WHERE WORK IS BEING DONE TO PREVENT

CONTAMINATION OF DUCT SYSTEM.

6. LT1 TEMP BARRIER TO REMAIN FOR DURATION OF

CONSTRUCTION PHASE. DEMOLISH ONCE CONSTRUCTION

PHASE HAS BEEN COMPLETED.

CLASS III ICRA NOTES

1. DURING CONSTRUCTION, THE ENTIRE UNIT WILL BE

VACATED. DOORS WILL BE SECURED TO EVERYONE BUT

CONSTRUCTION STAFF AND ESSENTIAL VA STAFF.

2. REMOVE EQUIPMENT AND ANY CONSTRUCTION DEBRIS

FROM SPACE USING COVERED SEALED CARTS.

3. SEE SPEC SECTION 01 35 26 FOR SAFETY REQUIREMENTS.

4. MAINTAIN 4'-0" MINIMUM CLEARANCE FOR EGRESS

AROUND ICRA WALLS.

5. MAINTAIN CALL BUTTON ACCESSIBILITY OUTSIDE OF ICRA

BARRIERS DURING PHASE 1 AND 2.

LEGEND

REFER TO KEYNOTE 3

PROJECT CONSTRUCTION IS IDENTIFIED AS TYPE C

CONSTRUCTION ACTIVITY

PROJECT RISK FOR <HOSPITAL UNIT> IS HIGH RISK GROUP

THIS COMBINATION INVOKES CLASS III & IV ICRA

PRECAUTIONS

REFER TO SPECIFICATION SECTION 01 35 26 - SAFETY

REQUIREMENTS FOR CLASS III INFECTION CONTROL

A/E:

625 First Ave #301 Seattle, WA, 98104

(206) 590 - 2118

RAY SPEES, PRESIDENT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

FOR CONSTRUCTION

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

STAMPCONSULTANT

321 4 5 6 7 8 9 10

668-18-109

Revisions: Date:

SPEES DESIGN BUILD

REFURBISH AND UPGRADE

ELEVATORS IN BLDG

1 AND 27

11/16/2021

Mann-Grandstaff VA Medical Center

- Spokane, WA

N

GC107

JW/MCMK

BUILDING 1 - SIXTH FLOOR -

ICRA FLOOR PLANS

1 SIXTH FLOOR ADJACENCY FLOOR PLAN

1/16" = 1'-0"

OUTPATIENT

EXAM RMS

SMALL

PROCEDURE

ROOMS

AREA OF

WORK

ADMIN

OFFICES

IT

CLOSET

2 PHASE 1 - SIXTH FLOOR ICRA FLOOR PLAN - BLDG 1

1/8" = 1'-0" N

CLASS III ICRA NOTES

3 PHASE 2 - SIXTH FLOOR ICRA FLOOR PLAN - BLDG 1

1/8" = 1'-0"4 PHASE 3 - SIXTH FLOOR ICRA FLOOR PLAN - BLDG 1

1/8" = 1'-0"

GENERAL NOTES

SHEET KEYNOTES

1. TEMP ICRA DOOR TO REMAIN IN PLACE FOR ENTIRETY OF

CONSTRUCTION PHASE.PROVIDE TACKY CONSTRUCTION

WALK-OFF MATS ON ENTRANCE AND EXIT SIDE OF

CONSTRUCTION ACTIVITY ACCESS POINTS

2. VERIFY EXISTING WALLS ISOLATING THE WORK AREA ARE

FIRESTOPPED AND GO TO CONCRETE FLOOR ABOVE. IF NOT,

INSTALL FIRESTOPPING AND LT1 TEMP BARRIER FROM TOP

OF EXISTING WALLS TO CONCRETE FLOOR ABOVE.

3. NEGATIVE PRESSURE, ISOLATED CONSTRUCTION ZONE.

4. HEPA ISO CLASS 7 FILTERED NEGATIVE AIR TO BE

MAINTAINED WITHIN CONSTRUCTION AREA. COVER ALL

HOLES, CONDUITS, AND ENTRANCE/EXIT TO CONSTRUCTION

SITE. COVER INTAKE/RETURNS WITH PAPER FLUTED FILTERS,

IN AREA WHERE WORK IS BEING DONE TO PREVENT

CONTAMINATION OF DUCT SYSTEM.

5. LT1 TEMP BARRIER TO REMAIN FOR DURATION OF

CONSTRUCTION PHASE. DEMOLISH ONCE CONSTRUCTION

PHASE HAS BEEN COMPLETED.

1. DURING CONSTRUCTION, THE ENTIRE UNIT WILL BE

VACATED. DOORS WILL BE SECURED TO EVERYONE BUT

CONSTRUCTION STAFF AND ESSENTIAL VA STAFF.

2. REMOVE EQUIPMENT AND ANY CONSTRUCTION DEBRIS

FROM SPACE USING COVERED SEALED CARTS.

3. SEE SPEC SECTION 01 35 26 FOR SAFETY REQUIREMENTS.

4. MAINTAIN 4'-0" MINIMUM CLEARANCE FOR EGRESS

AROUND ICRA WALLS.

5. MAINTAIN CALL BUTTON ACCESSIBILITY OUTSIDE OF ICRA

BARRIERS DURING PHASE 1 AND 2.

LEGEND

REFER TO KEYNOTE 2

PROJECT CONSTRUCTION IS IDENTIFIED AS TYPE C

CONSTRUCTION ACTIVITY

PROJECT RISK FOR <HOSPITAL UNIT> IS HIGH RISK GROUP

THIS COMBINATION INVOKES CLASS III & IV ICRA

PRECAUTIONS

REFER TO SPECIFICATION SECTION 01 35 26 - SAFETY

REQUIREMENTS FOR CLASS III INFECTION CONTROL

A/E:

625 First Ave #301 Seattle, WA, 98104

(206) 590 - 2118

RAY SPEES, PRESIDENT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

FOR CONSTRUCTION

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

STAMPCONSULTANT

321 4 5 6 7 8 9 10

668-18-109

Revisions: Date:

SPEES DESIGN BUILD

REFURBISH AND UPGRADE

ELEVATORS IN BLDG

1 AND 27

11/16/2021

Mann-Grandstaff VA Medical Center

- Spokane, WA

1 SEVENTH FLOOR ADJACENCY FLOOR PLAN

1/16" = 1'-0" N

GC108

JW/MCMK

BUILDING 1 - SEVENTH FLOOR -

ICRA FLOOR PLANS

OUTPATIENT

PSYCHIATRY

OUTPATIENT

PSYCHIATRY

AREA OF

WORK

ADMIN

OFFICES

IT CLOSET

TOILET

TOILET

2 PHASE 1 - SEVENTH FLOOR ICRA FLOOR PLAN - BLDG 1

1/8" = 1'-0" N

CLASS III ICRA NOTES

3 PHASE 2 - SEVENTH FLOOR ICRA FLOOR PLAN - BLDG 1

1/8" = 1'-0" N4 PHASE 3 - SEVENTH FLOOR ICRA FLOOR PLAN - BLDG 1

1/8" = 1'-0" N

2 3

2 6

3 2

4 5

GENERAL NOTES

SHEET KEYNOTES

1. DOOR TO REMAIN CLOSED AND SEALED DURING ENTIRETY

OF CONSTRUCTION PHASE.

2. TEMP ICRA DOOR TO REMAIN IN PLACE FOR ENTIRETY OF

CONSTRUCTION PHASE.PROVIDE TACKY CONSTRUCTION

WALK-OFF MATS ON ENTRANCE AND EXIT SIDE OF

CONSTRUCTION ACTIVITY ACCESS POINTS

3. VERIFY EXISTING WALLS ISOLATING THE WORK AREA ARE

FIRESTOPPED AND GO TO CONCRETE FLOOR ABOVE. IF NOT,

INSTALL FIRESTOPPING AND LT1 TEMP BARRIER FROM TOP

OF EXISTING WALLS TO CONCRETE FLOOR ABOVE.

4. NEGATIVE PRESSURE, ISOLATED CONSTRUCTION ZONE.

5. HEPA ISO CLASS 7 FILTERED NEGATIVE AIR TO BE

MAINTAINED WITHIN CONSTRUCTION AREA. COVER ALL

HOLES, CONDUITS, AND ENTRANCE/EXIT TO CONSTRUCTION

SITE. COVER INTAKE/RETURNS WITH PAPER FLUTED FILTERS,

IN AREA WHERE WORK IS BEING DONE TO PREVENT

CONTAMINATION OF DUCT SYSTEM.

6. LT1 TEMP BARRIER TO REMAIN FOR DURATION OF

CONSTRUCTION PHASE. DEMOLISH ONCE CONSTRUCTION

PHASE HAS BEEN COMPLETED.

1. DURING CONSTRUCTION, THE ENTIRE UNIT WILL BE

VACATED. DOORS WILL BE SECURED TO EVERYONE BUT

CONSTRUCTION STAFF AND ESSENTIAL VA STAFF.

2. REMOVE EQUIPMENT AND ANY CONSTRUCTION DEBRIS

FROM SPACE USING COVERED SEALED CARTS.

3. SEE SPEC SECTION 01 35 26 FOR SAFETY REQUIREMENTS.

4. MAINTAIN 4'-0" MINIMUM CLEARANCE FOR EGRESS

AROUND ICRA WALLS.

5. MAINTAIN CALL BUTTON ACCESSIBILITY OUTSIDE OF ICRA

BARRIERS DURING PHASE 1 AND 2.

LEGEND

REFER TO KEYNOTE 3

PROJECT CONSTRUCTION IS IDENTIFIED AS TYPE C

CONSTRUCTION ACTIVITY

PROJECT RISK FOR <HOSPITAL UNIT> IS HIGH RISK GROUP

THIS COMBINATION INVOKES CLASS III & IV ICRA

PRECAUTIONS

REFER TO SPECIFICATION SECTION 01 35 26 - SAFETY

REQUIREMENTS FOR CLASS III INFECTION CONTROL

GC109

BUILDING 1 - EIGHTH FLOOR -

ICRA FLOOR PLANS

PhaseARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

A/E:

625 First Ave #301 Seattle, WA, 98104

(206) 590 - 2118

RAY SPEES, PRESIDENT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

FOR CONSTRUCTION

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

STAMPCONSULTANT

321 4 5 6 7 8 9 10

668-18-109

Revisions: Date:

SPEES DESIGN BUILD

REFURBISH AND UPGRADE

ELEVATORS IN BLDG

1 AND 27

11/16/2021

Mann-Grandstaff VA Medical Center

- Spokane, WA

1 EIGHTH FLOOR ADJACENCY FLOOR PLAN

1/16" = 1'-0" N

OPERATING

ROOMS

OPERATING

ROOM

SUPPORT

AREA OF WORK

ENGINEERING

OFFICE/STORAGE

MEDICAL STORAGE

IT CLOSET

MECHANICAL

CLOSET

2 PHASE 1 - EIGHTH FLOOR ICRA FLOOR PLAN - BLDG 1

1/8" = 1'-0"

CLASS III ICRA NOTES

3 PHASE 2 - EIGHTH FLOOR ICRA FLOOR PLAN - BLDG 1

1/8" = 1'-0"4 PHASE 3 - EIGHTH FLOOR ICRA FLOOR PLAN - BLDG 1

1/8" = 1'-0"

GENERAL NOTES

SHEET KEYNOTES

1. DOOR TO REMAIN CLOSED AND SEALED DURING

ENTIRETY OF CONSTRUCTION PHASE.

2. TEMP ICRA DOOR TO REMAIN IN PLACE FOR ENTIRETY OF

CONSTRUCTION PHASE.PROVIDE TACKY CONSTRUCTION

WALK-OFF MATS ON ENTRANCE AND EXIT SIDE OF

CONSTRUCTION ACTIVITY ACCESS POINTS

3. VERIFY EXISTING WALLS ISOLATING THE WORK AREA

ARE FIRESTOPPED AND GO TO CONCRETE FLOOR ABOVE. IF

NOT, INSTALL FIRESTOPPING AND LT1 TEMP BARRIER FROM

TOP OF EXISTING WALLS TO CONCRETE FLOOR ABOVE.

4. NEGATIVE PRESSURE, ISOLATED CONSTRUCTION ZONE.

5. HEPA ISO CLASS 7 FILTERED NEGATIVE AIR TO BE

MAINTAINED WITHIN CONSTRUCTION AREA. COVER ALL

HOLES, CONDUITS, AND ENTRANCE/EXIT TO

CONSTRUCTION SITE. COVER INTAKE/RETURNS WITH PAPER

FLUTED FILTERS, IN AREA WHERE WORK IS BEING DONE TO

PREVENT CONTAMINATION OF DUCT SYSTEM.

6. LT1 TEMP BARRIER TO REMAIN FOR DURATION OF

CONSTRUCTION PHASE. DEMOLISH ONCE CONSTRUCTION

PHASE HAS BEEN COMPLETED.

1. DURING CONSTRUCTION, THE ENTIRE UNIT WILL BE

VACATED. DOORS WILL BE SECURED TO EVERYONE BUT

CONSTRUCTION STAFF AND ESSENTIAL VA STAFF.

2. REMOVE EQUIPMENT AND ANY CONSTRUCTION DEBRIS

FROM SPACE USING COVERED SEALED CARTS.

3. SEE SPEC SECTION 01 35 26 FOR SAFETY REQUIREMENTS.

4. MAINTAIN 4'-0" MINIMUM CLEARANCE FOR EGRESS

AROUND ICRA WALLS.

5. MAINTAIN CALL BUTTON ACCESSIBILITY OUTSIDE OF ICRA

BARRIERS DURING PHASE 1 AND 2.

LEGEND

REFER TO KEYNOTE 3

PROJECT CONSTRUCTION IS IDENTIFIED AS TYPE C

CONSTRUCTION ACTIVITY

PROJECT RISK FOR <HOSPITAL UNIT> IS HIGH RISK GROUP

THIS COMBINATION INVOKES CLASS III & IV ICRA

PRECAUTIONS

REFER TO SPECIFICATION SECTION 01 35 26 - SAFETY

REQUIREMENTS FOR CLASS III INFECTION CONTROL

FS

EQUIPMENT FOR

S3

EQUIPMENT FOR

P1

EQUIPMENT FOR

P2

EQUIPMENT

ARRAY FOR P2

EQUIPMENT

ARRAY FOR S3

EQUIPMENT

ARRAY FOR P1

STACKED

EQUIPMENT

A1000

FS

EQUIPMENT FOR

S3

EQUIPMENT FOR

P1

EQUIPMENT FOR

P2

EQUIPMENT

ARRAY FOR P2

EQUIPMENT

ARRAY FOR S3

EQUIPMENT

ARRAY FOR P1

STACKED

EQUIPMENT

A1000

3 MACHINE ROOM ADAJCENCY FLOOR PLAN

1/16"= 1'-0"

PhaseARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

A/E:

625 First Ave #301 Seattle, WA, 98104

(206) 590 - 2118

RAY SPEES, PRESIDENT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

FOR CONSTRUCTION

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

STAMPCONSULTANT

321 4 5 6 7 8 9 10

668-18-109

Revisions: Date:

SPEES DESIGN BUILD

REFURBISH AND UPGRADE

ELEVATORS IN BLDG

1 AND 27

11/16/2021

Mann-Grandstaff VA Medical Center

- Spokane, WA

N

N

GC110

JW/MCMK

BUILDING 1 -NINTH FLOOR &

MACHINE ROOM - ICRA FLOOR PLANS

1 NINTH FLOOR ADJACENCY FLOOR PLAN

1/16"= 1'-0"

ACCESS STAIR TO

MACHINE ROOM AREA OF WORK

MECHANICAL

AREA OF WORK

(SOME WORK ON ROOF ASSOCIATED

WITH MECHANICAL)

ROOF

4 ENLARGED MACHINE ROOM ICRA FLOOR PLAN - BLDG 1

1/8" = 1'-0" N 2 ENLARGED NINTH FLOOR ICRA FLOOR PLAN - BLDG 1

1/8" = 1'-0" N

-ANTE -4'

13' CLEAR

ANTE

5 GENERAL NOTES

SHEET KEYNOTES

1. TEMP ICRA DOOR TO REMAIN IN PLACE FOR ENTIRETY OF

CONSTRUCTION. PROVIDE TACKY CONSTRUCTION WALK-OFF

MATS ON ENTRANCE AND EXIT SIDE OF CONSTRUCTION

ACTIVITY ACCESS POINTS

2. VERIFY EXISTING WALLS ISOLATING THE WORK AREA ARE

FIRESTOPPED AND GO TO CONCRETE FLOOR ABOVE. IF NOT,

INSTALL FIRESTOPPING AND LT1 TEMP BARRIER FROM TOP

OF EXISTING WALLS TO CONCRETE FLOOR ABOVE.

3. NEGATIVE PRESSURE, ISOLATED CONSTRUCTION ZONE.

4. HEPA ISO CLASS 7 FILTERED NEGATIVE AIR TO BE

MAINTAINED WITHIN CONSTRUCTION AREA. COVER ALL

HOLES, CONDUITS, AND ENTRANCE/EXIT TO CONSTRUCTION

SITE. COVER INTAKE/RETURNS WITH PAPER FLUTED FILTERS,

IN AREA WHERE WORK IS BEING DONE TO PREVENT

CONTAMINATION OF DUCT SYSTEM.

5. LT1 TEMP BARRIER TO REMAIN FOR DURATION OF

CONSTRUCTION. DEMOLISH ONCE CONSTRUCTION HAS BEEN

COMPLETED.

CLASS III ICRA NOTES

1. DURING CONSTRUCTION, THE ENTIRE UNIT WILL BE

VACATED. DOORS WILL BE SECURED TO EVERYONE BUT

CONSTRUCTION STAFF AND ESSENTIAL VA STAFF.

2. REMOVE EQUIPMENT AND ANY CONSTRUCTION DEBRIS

FROM SPACE USING COVERED SEALED CARTS.

3. SEE SPEC SECTION 01 35 26 FOR SAFETY REQUIREMENTS.

4. MAINTAIN 4'-0" MINIMUM CLEARANCE FOR EGRESS

AROUND ICRA WALLS

5. ANTE ROOM IMPLEMENTED TO MAINTAIN PRESSURIZATION

OF BUILDING BETWEEN INTERIOR AND EXTERIOR SPACES.

LEGEND

REFER TO KEYNOTE 2

PROJECT CONSTRUCTION IS IDENTIFIED AS TYPE C

CONSTRUCTION ACTIVITY

PROJECT RISK FOR <HOSPITAL UNIT> IS HIGH RISK GROUP

THIS COMBINATION INVOKES CLASS III & IV ICRA

PRECAUTIONS

REFER TO SPECIFICATION SECTION 01 35 26 - SAFETY

REQUIREMENTS FOR CLASS III INFECTION CONTROL

AC-1

GC111

JW/MCMK

BUILDING 27 - BASEMENT -

ICRA FLOOR PLAN

(DEDUCTIVE BID ALTERNATE)

1 BASEMENT FLOOR ADJACENCY FLOOR PLAN

1/16" = 1'-0"

PhaseARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

A/E:

625 First Ave #301 Seattle, WA, 98104

(206) 590 - 2118

RAY SPEES, PRESIDENT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

FOR CONSTRUCTION

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

STAMPCONSULTANT

321 4 5 6 7 8 9 10

668-18-109

Revisions: Date:

SPEES DESIGN BUILD

REFURBISH AND UPGRADE

ELEVATORS IN BLDG

1 AND 27

11/16/2021

Mann-Grandstaff VA Medical Center

- Spokane, WA

N

AREA OF WORK

ENGINEERING

STORAGE

2 ENLARGED BASEMENT FLOOR ICRA FLOOR PLAN

1/8" = 1'-0" N

GENERAL NOTES

SHEET KEYNOTES

1. DOOR TO REMAIN CLOSED AND SEALED DURING ENTIRETY

OF CONSTRUCTION PHASE.

2. TEMP ICRA DOOR TO REMAIN IN PLACE FOR ENTIRETY OF

CONSTRUCTION PHASE.PROVIDE TACKY CONSTRUCTION

WALK-OFF MATS ON ENTRANCE AND EXIT SIDE OF

CONSTRUCTION ACTIVITY ACCESS POINTS

3. VERIFY EXISTING WALLS ISOLATING THE WORK AREA ARE

FIRESTOPPED AND GO TO CONCRETE FLOOR ABOVE. IF NOT,

INSTALL FIRESTOPPING AND LT1 TEMP BARRIER FROM TOP

OF EXISTING WALLS TO CONCRETE FLOOR ABOVE.

4. NEGATIVE PRESSURE, ISOLATED CONSTRUCTION ZONE.

5. HEPA ISO CLASS 7 FILTERED NEGATIVE AIR TO BE

MAINTAINED WITHIN CONSTRUCTION AREA. COVER ALL

HOLES, CONDUITS, AND ENTRANCE/EXIT TO CONSTRUCTION

SITE. COVER INTAKE/RETURNS WITH PAPER FLUTED FILTERS,

IN AREA WHERE WORK IS BEING DONE TO PREVENT

CONTAMINATION OF DUCT SYSTEM.

6. LT1 TEMP BARRIER TO REMAIN FOR DURATION OF

CONSTRUCTION PHASE. DEMOLISH ONCE CONSTRUCTION

PHASE HAS BEEN COMPLETED.

CLASS III ICRA NOTES

1. DURING CONSTRUCTION, THE ENTIRE UNIT WILL BE

VACATED. DOORS WILL BE SECURED TO EVERYONE BUT

CONSTRUCTION STAFF AND ESSENTIAL VA STAFF.

2. REMOVE EQUIPMENT AND ANY CONSTRUCTION DEBRIS

FROM SPACE USING COVERED SEALED CARTS.

3. SEE SPEC SECTION 01 35 26 FOR SAFETY REQUIREMENTS.

4. MAINTAIN 4'-0" MINIMUM CLEARANCE FOR EGRESS

AROUND ICRA WALLS

LEGEND

REFER TO KEYNOTE 3

PROJECT CONSTRUCTION IS IDENTIFIED AS TYPE C

CONSTRUCTION ACTIVITY

PROJECT RISK FOR <HOSPITAL UNIT> IS HIGH RISK GROUP

THIS COMBINATION INVOKES CLASS III & IV ICRA

PRECAUTIONS

REFER TO SPECIFICATION SECTION 01 35 26 - SAFETY

REQUIREMENTS FOR CLASS III INFECTION CONTROL

WF

CAM FS

SD

WF

SD

FS

CAM

SP

SD

A121

A122 A119

A102

C1-A1

A103

A105S3 P1

P2

PhaseARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

A/E:

625 First Ave #301 Seattle, WA, 98104

(206) 590 - 2118

RAY SPEES, PRESIDENT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

FOR CONSTRUCTION

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

STAMPCONSULTANT

321 4 5 6 7 8 9 10

668-18-109

Revisions: Date:

SPEES DESIGN BUILD

REFURBISH AND UPGRADE

ELEVATORS IN BLDG

1 AND 27

11/16/2021

Mann-Grandstaff VA Medical Center

- Spokane, WA GC112

JW/MCMK

BUILDING 27 - FIRST FLOOR -

ICRA FLOOR PLAN

(DEDUCTIVE BID ALTERNATE)

1 FIRST FLOOR ICRA FLOOR PLAN - BLDG 27

1/16"= 1'-0"

N

EGRESS FROM FURTHEST POINT = 171'-8" (FREIGHT ELEV)

144'-5" (PASSENGER ELEV)

AREA OF WORK

BUILDING 1

MRI

SHEET KEYNOTES

GENERAL NOTES

2 ENLARGED FIRST FLOOR ICRA FLOOR PLAN - BLDG 27

1/8"= 1'-0" N

CLASS III ICRA NOTES

1. DURING CONSTRUCTION, THE ENTIRE UNIT WILL BE

VACATED. DOORS WILL BE SECURED TO EVERYONE BUT

CONSTRUCTION STAFF AND ESSENTIAL VA STAFF.

2. REMOVE EQUIPMENT AND ANY CONSTRUCTION DEBRIS

FROM SPACE USING COVERED SEALED CARTS.

3. SEE SPEC SECTION 01 35 26 FOR SAFETY REQUIREMENTS.

4. MAINTAIN 4'-0" MINIMUM CLEARANCE FOR EGRESS

AROUND ICRA WALLS

1. TEMP ICRA DOOR TO REMAIN IN PLACE FOR ENTIRETY OF

CONSTRUCTION PHASE.PROVIDE TACKY CONSTRUCTION

WALK-OFF MATS ON ENTRANCE AND EXIT SIDE OF

CONSTRUCTION ACTIVITY ACCESS POINTS

2. VERIFY EXISTING WALLS ISOLATING THE WORK AREA ARE

FIRESTOPPED AND GO TO CONCRETE FLOOR ABOVE. IF NOT,

INSTALL FIRESTOPPING AND LT1 TEMP BARRIER FROM TOP

OF EXISTING WALLS TO CONCRETE FLOOR ABOVE.

3. NEGATIVE PRESSURE, ISOLATED CONSTRUCTION ZONE.

4. HEPA ISO CLASS 7 FILTERED NEGATIVE AIR TO BE

MAINTAINED WITHIN CONSTRUCTION AREA. COVER ALL

HOLES, CONDUITS, AND…