Attachment 07_Drawings 07122024 Part 6.pdf

PDF 8 MB Posted

Attached to
Z2DA--506-21-705 EHRM Infrastructure Upgrades - Ann Arbor, MI - Construction (VA-25-00001864)
Solicitation number
36c77624b0025
Issued by

About this file

This document is a set of construction drawings for the Electronic Health Record Modernization (EHRM) infrastructure upgrades at the Ann Arbor VA Medical Center. The drawings provide detailed plans for electrical, telecommunications, and technology system upgrades in several buildings on the campus, including telecom room layouts, power and technology plans, and demolition requirements. Key details include the need to relocate and install new data racks, servers, cabling, and related infrastructure to support the EHRM system updates. The project is part of Solicitation #36c77624b0025 issued by the Department of Veterans Affairs Technology Acquisition Center in Austin, with a bid due date of February 28, 2024. The construction work is required to support the broader EHRM infrastructure upgrades at the VA Ann Arbor Healthcare System facility.

View the file

Other files

File Type Posted
S07 - Complete Abstract of Bids OF 1419- Ann Arbor EHRM 10 16 2024.pdf PDF
S07 - Complete Abstract of Bids OF 1419- Ann Arbor EHRM.pdf PDF
IFB 36C77624B0025 Amendment 0005 Asbestos Info.pdf PDF
IFB 36C77624B0025 Amendment 0004.pdf PDF
36C77624B0025 Amendment 0003.pdf PDF
S05 Ann_Arbor CMS_Question_Matrix_V3.xlsx XLSX spreadsheet
Attachment 12 - EHRM Window Screen Details.pdf PDF
Attachment 08 - 075423 TPO Roofing.pdf PDF
Attachment 14 - MS Versions of PDFs.zip ZIP file
Attachment 07 - 013323 Shop Drawings_CA Edits 2.pdf PDF
Attachment 02 - 1E.ET472.pdf PDF
Attachment 06 - 000110 TOC - updated TPO and 236323.pdf PDF
Attachment 11 - CABLE MATRICES.pdf PDF
Attachment 04 - 21-092 SubReg 100 Percent.pdf PDF
Attachment 10 - Addendum 1.pdf PDF
Attachment 09 -236323 AirCooledClosedCircuitFluidCooler.pdf PDF
36C77624B0025 0002.docx DOCX document
Attachment 05 - 21-092-Pre-Bid RFIs_AE responses 1.pdf PDF
Attachment 15 - DB WR GD No MI20240100 09062024.pdf PDF
Attachment 03 - 1W.A-491_Addendum 1.pdf PDF
Attachment 01 - Q and A Results Ann Arbor MI.docx DOCX document
Attachment 13 - G-003_Addendum 1.pdf PDF
S04 - Pre-Bid Site Visit Sign-in Sheet - 09 04 2024.pdf PDF
S04 - Virtual Visit Attendee List - 08 29 2024.docx DOCX document
36C77624B0025 Ammendment 0001.docx DOCX document
S04 -Virtual and Site Visit Agenda - IFB 2024 08 29 2024.doc DOC document
S04 - Pre-Bid Site Visit Sign-in Sheet - 09 04 2024.docx DOCX document
Attachment 02_Drawings 07122024 Part 1.pdf PDF
Attachment 04_Drawings 07122024 Part 3.pdf PDF
Attachment 11 Division Breakdown Template.xls XLS spreadsheet
Attachment 06_Drawings 07122024 Part 5.pdf PDF
Attachment 05_Drawings 07122024 Part 4.pdf PDF
Attachment 08_Limitations on Subcontracting - Construction.docx DOCX document
Attachment 03_Drawings 07122024 Part 2.pdf PDF
Attachment 09_JA Ann Arbor Final REDACTED.pdf PDF
Attachment 10 DB Wages General Decision Number MI20240100 07 26 24.pdf PDF
Attachment 01_Specifications Ann Arbor MI.pdf PDF
36C77624B0025_1.pdf PDF
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

48"

SS SS

EM

E

SS SS

CR

DC ES RX

F

SS SS

DC ES RX

CR

J

SS SS

SD OS

SS SS

FSSD OS

SS SS

M

N

OFFICE

WARD

CLERK

A757

SELF-CHECK/INFO

A755

SERVICE

ELEVATOR

LOBBY

CHECK-IN

B708B

1 2

ELEC

ROOM

A753

M

N

WARD

CLERK

A757

SELF-CHECK/INFO

A755

TR

A753

SERVICE

ELEVATOR

LOBBY

CHECK-IN

B708B

PANEL 'A'

PANEL 'B'

A

N

B

A

B

A

B

A

A

B

B

1W-SS-A753

SBB

A

M

N

WARD

CLERK

A757

SELF-CHECK/INFO

A755

SERVICE

ELEVATOR

LOBBY

CHECK-IN

B708B

ELEC

ROOM

A753

TELECOM

SECURITY

PA RISER

SECURITYCODE ONE 7 7

M

N

WARD

CLERK

A757

SELF-CHECK/INFO

A755

TR

A753

SERVICE

ELEVATOR

LOBBY

CHECK-IN

B708B

K

TELECOM

DATA

POWER

CODE ONE

PA RISER

SECURITY

SBB

M

N

OFFICE

WARD

CLERK

A757

SELF-CHECK/INFO

A755

SERVICE

ELEVATOR

LOBBY

CHECK-IN

B708B

5 6

ELEC

ROOM

A753

ETR

ETR

ETR

ETR

ETR

ETR

M

N

WARD

CLERK

A757

SELF-CHECK/INFO

A755

TR

A753

SERVICE

ELEVATOR

LOBBY

CHECK-IN

B708B

A

A A

ETR

ETR

ETR

ETR ETR

ETR

Engineers Architects

# KEY NOTES:

# KEY NOTES:

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREA

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

S S S S

1 HR - SMOKE SEPARATIONS S S S

/2

/2

:0

:5

A

M C

U s e rs

\a ri c h a rd s \D o c u m e n ts

\E

-0

A n n

A rb o r- E

H R

M B ld g

-1 W a ri c h a rd s P

K P

J .r v t

1W.ET471

BUILDING 1W, SEVENTH FLOOR, ALPHA

STACK, TELECOM ROOM A753

56 106ADR

EHRM INFRASTRUCTURE

UPGRADES

VA ANN ARBOR HEALTHCARE SYSTEM

2215 FULLER ROAD, ANN ARBOR, MI

48105 FEBRUARY 28, 2024

BID DOCUMENTS

506-21-70521-092

JKM

1W

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

Scale: 1/4" = 1'-0"

ELECTRICAL ROOM A753, POWER DEMOLITION PLAN

Scale: 1/4" = 1'-0"

TELECOM ROOM A753, POWER PLAN

Scale: 1/4" = 1'-0"

ELECTRICAL ROOM A753, TECHNOLOGY DEMOLITION PLAN

Scale: 1/4" = 1'-0"

TELECOM ROOM A753, TECHNOLOGY PLAN

Scale: 1/4" = 1'-0"

ELECTRICAL ROOM A753, CEILING DEMOLITION PLAN

Scale: 1/4" = 1'-0"

TELECOM ROOM A753, CEILING PLAN

NORTH

0 2 4 8

NORTH

0 2 4 8

NORTH

0 2 4 8

NORTH

0 2 4 8

NORTH

0 2 4 8

NORTH

0 2 4 8

1 DISCONNECT MECHANICAL EQUIPMENT.

REMOVE WIRING AND CONDUIT BACK TO

LAST OPERABLE DEVICE OR PANELBOARD.

2 DISCONNECT AND REMOVE RECEPTACLE.

REMOVE WIRING AND CONDUIT BACK TO

LAST OPERABLE DEVICE OR PANELBOARD.

3 DISCONNECT AND REMOVE ALL UNUSED

CABLING FROM EXISTING EQUIPMENT RACK.

4 DISCONNECT AND REMOVE CAMERA. RETAIN

CONDUIT AND CABLING FOR NEW WORK.

5 DISCONNECT AND REMOVE LIGHT SWITCH.

REMOVE WIRING AND CONDUIT BACK TO

LAST OPERABLE DEVICE OR PANELBOARD.

6 DISCONNECT AND REMOVE LIGHTING

FIXTURE. REMOVE WIRING AND CONDUIT

BACK TO LAST OPERABLE DEVICE OR

PANELBOARD.

7 DISCONNECT AND REMOVE EXISTING WALL

MOUNTED EQUIPMENT RACK.

8 CONDUITS TO BE DEMOLISHED. REROUTE

CABLES TO NEW PATHWAYS NOTED IN

TECHNOLOGY PLAN BELOW.

9 EXISTING SBB. RELOCATE TO NEW LOCATION

AS SHOWN.

10 RELOCATE CONVENIENCE RECEPTACLE AS

SHOWN ON NEW WORK PLAN.

11 RELOCATE FIRE ALARM AUDIO/VISUAL

APPLIANCE AS SHOWN ON NEW WORK PLAN.

12 RELOCATE CAMERA AS SHOWN ON NEW

WORK PLAN.

A. ALL EXISTING CONDITIONS, CONDUITS AND

DEVICES ARE BASED ON THE BEST

AVAILABLE INFORMATION AT THE TIME OF

SURVEY AND VISUAL INSPECTION. VERIFY

EXISTING CONDITIONS.

B. DEVICES SHOWN WITH LIGHT, GRAY LINES

ARE EXISTING TO REMAIN. DEVICES SHOWN

WITH DARK, DASHED LINES ARE EXISTING TO

BE DEMOLISHED. DEMOLITION SHALL

INCLUDE, BUT NOT BE LIMITED TO, THOSE

DEVICES AND SYSTEMS SHOWN.

COORDINATE WITH ALL OTHER DISCIPLINES.

C. AT ALL TIMES, FIRE ALARM SERVICES ARE TO

REMAIN ACTIVE OUTSIDE THE DESIGNATED

DEMOLITION AREA NOTED ON THE PLANS.

D. REMOVE ALL UNUSED CONDUIT AND

CABLING.

E. WHERE CONDUIT IS REMOVED FROM AN

EXISTING RATED ASSEMBLY NOT SUBJECT TO

DEMOLITION, THE REMAINING PENETRATION

SHALL BE PATCHED/REPAIRED TO MAINTAIN

THE RATING OF THE ASSEMBLY.

F. COORDINATE ALL WORK BETWEEN TRADES

AND DISCIPLINES.

G. NEW DEVICES AND EQUIPMENT SHOWN ON

SHEET SPECIFY NEW TELECOM ROOM

LAYOUT. FOR EQUIPMENT SPECIFICS AND

MORE INFORMATION SEE SHEET ET501.

1 PROVIDE CRITICAL POWER FEEDER CIRCUIT

TO PANEL 'A'.

2 PROVIDE NORMAL POWER FEEDER CIRCUIT

TO PANEL 'B'.

3 PROVIDE POWER TO THE NEW RECEPTACLE

FROM EXISTING CONVENIENCE OUTLET

CIRCUIT IN THE CORRIDOR.

4 PROVIDE 120V POWER FOR DOOR SECURITY

HARDWARE. SEE DETAIL 5/ET503.

5 MOUNT OUTLETS ABOVE DATA RACK ON

CABLE TRAY. SEE DETAIL 6/ET502 FOR MORE

INFORMATION.

6 PROVIDE POWER CONNECTION AND MOTOR

RATED SWITCH FOR SPLIT UNIT.

7 8"X8"X4" HINGED CONTROLLER BOX,

MOUNTED ABOVE DOOR. SEE DETAIL 5/ET503.

8 PROVIDE 4 FIRE/SMOKE SLEEVE ASSEMBLIES.

REFERENCE DETAIL 2/ET501 FOR MORE

INFORMATION.

9 RELOCATED SBB. EXTEND EXISTING BONDING

CONDUCTOR TO NEW LOCATION.

10 PROVIDE ONE (1) 12" BY 18" RECTANGULAR

HOLE FOR EIGHT (8) UL LISTED, FIRE/THERMAL

RATED CONDUIT PATHWAY ASSEMBLIES.

RE-ROUTE EXISTING CABLES THROUGH

ASSEMBLIES. PROVIDE ALL SHORING AND

SUPPORT. BOD STI-EZDG844S2.

11 RELOCATED FIRE ALARM AUDIO/VISUAL

APPLIANCE. EXTEND CONDUIT AND CABLING

TO NEW LOCATION.

12 RELOCATED CONVENIENCE RECEPTACLE.

EXTEND CONDUIT AND CABLING TO NEW

LOCATION.

13 RELOCATE CAMERA TO NEW LOCATION.

EXTEND CABLING TO NEW LOCATION.

14 PROVIDE TWO (2) 4" CORE HOLE AND INSTALL

TWO (2) FIRE AND THERMAL RATED ASSEMBLY

(BOD P/N STI-EZDP133FK) FOR RE-ROUTING

EXISTING CABLES.

DocuSign Envelope ID: F024BA2E-7BBC-4DFF-BDAC-B255F954C023

2/27/2024 2/26/2024

E M

E

CR

DCESRX

CR

RX ESDCJ

G.1 J K

STORAGE

B718

STORAGE

B720

EXAM

B726

EXAM

B727

ELEC

B724

CORRIDOR

C7-2

ELEC

G

1 2

DATA

ROOM

B722A

STORAGE

ROOM

B722B

1W.ET472.A

1 8

G.1 J K

STORAGE

B718

STORAGE

B720

EXAM

B726

EXAM

B727

TR

B722A

ELEC

B724

EXAM

B719

CHECK-IN

B717

ELEC

G

PANEL 'A'

PANEL 'B'

ABNAB

A

B A

A

B

SBB

B

CORRIDOR

C7-2

A

1W-FCU-B722A

G.1 J K

STORAGE

B718

STORAGE

B720

EXAM

B726

EXAM

B727

ELEC

B724

CORRIDOR

C7-2

ELEC

G

DATA

ROOM

B722A

STORAGE

ROOM

B722B

NURSE

CALL

SECURITY

TELECOM

G.1 J K

STORAGE

B718

STORAGE

B720

EXAM

B726

EXAM

B727

TR

B722A

ELEC

B724

CORRIDOR

C7-2

CHECK-IN

B717

ELEC

G

K

NURSE CALL

SECURITY

SBB

G.1 J K

STORAGE

B718

STORAGE

B720

EXAM

B726

EXAM

B727

ELEC

B724

CORRIDOR

C7-2

ELEC

G

5 6

DATA

ROOM

B722A

STORAGE

ROOM

B722B

G.1 J K

STORAGE

B718

STORAGE

B720

EXAM

B726

EXAM

B727

TR

B722A

ELEC

B724

CORRIDOR

C7-2

ELEC

G

A A

A 2

Engineers Architects

# KEY NOTES:

# KEY NOTES:

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREA

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

S S S S

1 HR - SMOKE SEPARATIONS S S S

/2

/2

:5

:3

A

M C

U s e rs

\a ri c h a rd s \D o c u m e n ts

\E

-0

A n n

A rb o r- E

H R

M B ld g

-1 W a ri c h a rd s P

K P

J .r v t

1W.ET472

BUILDING 1W, SEVENTH FLOOR,

BRAVO STACK, TELECOM ROOM B722A

57 106ADR

EHRM INFRASTRUCTURE

UPGRADES

VA ANN ARBOR HEALTHCARE SYSTEM

2215 FULLER ROAD, ANN ARBOR, MI

48105 FEBRUARY 28, 2024

BID DOCUMENTS

506-21-70521-092

JKM

1W

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

Scale: 1/4" = 1'-0"

DATA ROOM B722A, POWER DEMOLITION PLAN

Scale: 1/4" = 1'-0"

TELECOM ROOM B722A, POWER PLAN

Scale: 1/4" = 1'-0"

DATA ROOM B722A, TECHNOLOGY DEMOLITION PLAN

Scale: 1/4" = 1'-0"

TELECOM ROOM B722A, TECHNOLOGY PLAN

Scale: 1/4" = 1'-0"

DATA ROOM B722A, CEILING DEMOLITION PLAN

Scale: 1/4" = 1'-0"

TELECOM ROOM B722A, CEILING PLAN

1 PROVIDE CRITICAL POWER FEEDER CIRCUIT

TO PANEL 'A'.

2 PROVIDE NORMAL POWER FEEDER CIRCUIT

TO PANEL 'B'.

3 PROVIDE POWER TO THE NEW RECEPTACLE

FROM EXISTING CONVENIENCE OUTLET

CIRCUIT IN THE CORRIDOR.

4 PROVIDE 120V POWER FOR DOOR SECURITY

HARDWARE. SEE DETAIL 5/ET503.

5 MOUNT OUTLETS ABOVE DATA RACK ON

CABLE TRAY. SEE DETAIL 6/ET502 FOR MORE

INFORMATION.

6 PROVIDE POWER CONNECTION AND MOTOR

RATED SWITCH FOR SPLIT UNIT.

7 8"X8"X4" HINGED CONTROLLER BOX,

MOUNTED ABOVE DOOR. SEE DETAIL

5/ET503.

8 PROVIDE 4 FIRE/SMOKE SLEEVE

ASSEMBLIES. REFERENCE DETAIL 2/ET501

FOR MORE INFORMATION.

9 RELOCATED SBB. EXTEND EXISTING

BONDING CONDUCTOR TO NEW LOCATION.

NORTH

0 2 4 8

NORTH

0 2 4 8

NORTH

0 2 4 8

NORTH

0 2 4 8

NORTH

0 2 4 8

NORTH

0 2 4 8

1 DISCONNECT MECHANICAL EQUIPMENT.

REMOVE WIRING AND CONDUIT BACK TO

LAST OPERABLE DEVICE OR PANELBOARD.

2 DISCONNECT AND REMOVE RECEPTACLE.

REMOVE WIRING AND CONDUIT BACK TO

LAST OPERABLE DEVICE OR PANELBOARD.

3 DISCONNECT AND REMOVE ALL UNUSED

CABLING FROM EXISTING EQUIPMENT RACK.

4 DISCONNECT AND REMOVE CAMERA.

RETAIN CONDUIT AND CABLING FOR NEW

WORK.

5 DISCONNECT AND REMOVE LIGHT SWITCH.

REMOVE WIRING AND CONDUIT BACK TO

LAST OPERABLE DEVICE OR PANELBOARD.

6 DISCONNECT AND REMOVE LIGHTING

FIXTURE. REMOVE WIRING AND CONDUIT

BACK TO LAST OPERABLE DEVICE OR

PANELBOARD.

7 DISCONNECT AND REMOVE EXISTING WALL

MOUNTED EQUIPMENT RACK.

8 EXISTING SBB. RELOCATE TO NEW

LOCATION AS SHOWN.

A. ALL EXISTING CONDITIONS, CONDUITS AND

DEVICES ARE BASED ON THE BEST

AVAILABLE INFORMATION AT THE TIME OF

SURVEY AND VISUAL INSPECTION. VERIFY

EXISTING CONDITIONS.

B. DEVICES SHOWN WITH LIGHT, GRAY LINES

ARE EXISTING TO REMAIN. DEVICES SHOWN

WITH DARK, DASHED LINES ARE EXISTING TO

BE DEMOLISHED. DEMOLITION SHALL

INCLUDE, BUT NOT BE LIMITED TO, THOSE

DEVICES AND SYSTEMS SHOWN.

COORDINATE WITH ALL OTHER DISCIPLINES.

C. AT ALL TIMES, FIRE ALARM SERVICES ARE TO

REMAIN ACTIVE OUTSIDE THE DESIGNATED

DEMOLITION AREA NOTED ON THE PLANS.

D. REMOVE ALL UNUSED CONDUIT AND

CABLING.

E. WHERE CONDUIT IS REMOVED FROM AN

EXISTING RATED ASSEMBLY NOT SUBJECT TO

DEMOLITION, THE REMAINING PENETRATION

SHALL BE PATCHED/REPAIRED TO MAINTAIN

THE RATING OF THE ASSEMBLY.

F. COORDINATE ALL WORK BETWEEN TRADES

AND DISCIPLINES.

G. NEW DEVICES AND EQUIPMENT SHOWN ON

SHEET SPECIFY NEW TELECOM ROOM

LAYOUT. FOR EQUIPMENT SPECIFICS AND

MORE INFORMATION SEE SHEET ET501.

Engineers Architects

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/2

/2

:5

:3

A

M C

U s e rs

\a ri c h a rd s \D o c u m e n ts

\E

-0

A n n

A rb o r- E

H R

M B ld g

-1 W a ri c h a rd s P

K P

J .r v t

1W.ET472.A

BUILDING 1W, SEVENTH FLOOR,

BRAVO STACK, TELECOM ROOM B722A

- ELEVATIONS

58 106ADR

EHRM INFRASTRUCTURE

UPGRADES

VA ANN ARBOR HEALTHCARE SYSTEM

2215 FULLER ROAD, ANN ARBOR, MI

48105 FEBRUARY 28, 2024

BID DOCUMENTS

506-21-70521-092

JKM

1W

A. ALL DEVICES IN THIS SPACE ARE

POTENTIALLY MISSION CRITICAL AND LIFE

SAFETY SUPPORTING. EXTREME CAUTION

SHOULD BE TAKEN TO PROTECT EVERY

DEVICE AND COORDINATE ANY DOWNTIME

NO LESS THAN TWENTY-ONE DAYS PRIOR

TO OUTAGE.

B. THIS SHEET IS PROVIDED TO

DEMONSTRATE THE EXISTING CONDITIONS

OF THE SPACE'S WALLS. WHERE POSSIBLE,

REMOVE AND REATTACH WALL-MOUNTED

SUPPORTS, BRACKETS, ETC. TO MAXIMIZE

THE BLOCKING MATERIAL BEING APPLIED

TO THE WALLS.

Scale: No Scale

TR B722A WALL ELEVATION - 01

Scale: No Scale

TR B722A WALL ELEVATION - 02

Scale: No Scale

TR B722A WALL ELEVATION - 03

Scale: No Scale

TR B722A WALL ELEVATION - 04

OS

E

M

E

E

M

CR

DCESRX

F

S

DCESRX

CR

J

F

S

OS

F

S

OS

M

N

OFFICE

A855

OFFICE

A854

STORAGE

A853

TR

A843A

SERVICE

ELEVATOR

LOBBY

A843

CORRIDOR

C8-04

COPY/BREAK

A843B

OFFICE

A841

1 2

1 2

M

N

STORAGE

A853

TR

A843A

SERVICE

ELEVATOR

LOBBY

A843

CORRIDOR

C8-04

COPY/BREAK

A843B

OFFICE

A841

A N

B

A

B

A

B

A

B

A

B

PANEL 'A' PANEL 'B'

SBB

1 2

A

A

M

N

STORAGE

A853

TR

A843A

SERVICE

ELEVATOR

LOBBY

A843

CORRIDOR

C8-04

COPY/BREAK

A843B

OFFICE

A841

3 4

TELECOM

SECURITY

CODE ONE

DATA

LV

EMPTY

GND

M

N

STORAGE

A853

TR

A843A

SERVICE

ELEVATOR

LOBBY

A843

CORRIDOR

C8-04

COPY/BREAK

A843B

OFFICE

A841

K

DATA

LV

EMPTY

GND

PA RISER

SBB

M

N

STORAGE

A853

TR

A843A

SERVICE

ELEVATOR

LOBBY

A843

CORRIDOR

C8-04

COPY/BREAK

A843B

OFFICE

A841

5 6

5 6

ETR ETR

ETRETR

ETR

ETR

M

N

STORAGE

A853

TR

A843A

SERVICE

ELEVATOR

LOBBY

A843

CORRIDOR

C8-04

COPY/BREAK

A843B

OFFICE

A841

A A

A

A

ETR ETR

ETRETR

ETR

ETR

Engineers Architects

# KEY NOTES:

# KEY NOTES:

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREA

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

S S S S

1 HR - SMOKE SEPARATIONS S S S

/2

/2

:2

:1

A

M C

U s e rs

\a ri c h a rd s \D o c u m e n ts

\E

-0

A n n

A rb o r- E

H R

M B ld g

-1 W a ri c h a rd s P

K P

J .r v t

1W.ET481

BUILDING 1W, EIGHTH FLOOR, ALPHA

STACK, TELECOM ROOM A843A

59 106ADR

EHRM INFRASTRUCTURE

UPGRADES

VA ANN ARBOR HEALTHCARE SYSTEM

2215 FULLER ROAD, ANN ARBOR, MI

48105 FEBRUARY 28, 2024

BID DOCUMENTS

506-21-70521-092

JKM

1W

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

Scale: 1/4" = 1'-0"

OFFICE A841, POWER DEMOLITION PLAN

Scale: 1/4" = 1'-0"

TELECOM ROOM A843A, POWER PLAN

Scale: 1/4" = 1'-0"

OFFICE A841, TECHNOLOGY DEMOLITION PLAN

Scale: 1/4" = 1'-0"

TELECOM ROOM A843A, TECHNOLOGY PLAN

Scale: 1/4" = 1'-0"

OFFICE A841, CEILING DEMOLITION PLAN

Scale: 1/4" = 1'-0"

TELECOM ROOM A843A, CEILING PLAN

NORTH

0 2 4 8

NORTH

0 2 4 8

NORTH

0 2 4 8

NORTH

0 2 4 8

NORTH

0 2 4 8

NORTH

0 2 4 8

A. ALL EXISTING CONDITIONS, CONDUITS AND

DEVICES ARE BASED ON THE BEST

AVAILABLE INFORMATION AT THE TIME OF

SURVEY AND VISUAL INSPECTION. VERIFY

EXISTING CONDITIONS.

B. DEVICES SHOWN WITH LIGHT, GRAY LINES

ARE EXISTING TO REMAIN. DEVICES SHOWN

WITH DARK, DASHED LINES ARE EXISTING TO

BE DEMOLISHED. DEMOLITION SHALL

INCLUDE, BUT NOT BE LIMITED TO, THOSE

DEVICES AND SYSTEMS SHOWN.

COORDINATE WITH ALL OTHER DISCIPLINES.

C. AT ALL TIMES, FIRE ALARM SERVICES ARE TO

REMAIN ACTIVE OUTSIDE THE DESIGNATED

DEMOLITION AREA NOTED ON THE PLANS.

D. REMOVE ALL UNUSED CONDUIT AND

CABLING.

E. WHERE CONDUIT IS REMOVED FROM AN

EXISTING RATED ASSEMBLY NOT SUBJECT TO

DEMOLITION, THE REMAINING PENETRATION

SHALL BE PATCHED/REPAIRED TO MAINTAIN

THE RATING OF THE ASSEMBLY.

F. COORDINATE ALL WORK BETWEEN TRADES

AND DISCIPLINES.

G. NEW DEVICES AND EQUIPMENT SHOWN ON

SHEET SPECIFY NEW TELECOM ROOM

LAYOUT. FOR EQUIPMENT SPECIFICS AND

MORE INFORMATION SEE SHEET ET501.

1 DISCONNECT MECHANICAL EQUIPMENT.

REMOVE WIRING AND CONDUIT BACK TO

LAST OPERABLE DEVICE OR PANELBOARD.

2 DISCONNECT AND REMOVE RECEPTACLE.

RETAIN CIRCUIT FOR REUSE DURING NEW

CONSTRUCTION.

3 DISCONNECT AND REMOVE ALL UNUSED

CABLING FROM EXISTING EQUIPMENT RACK.

4 DISCONNECT AND REMOVE CAMERA.

RETAIN CONDUIT AND CABLING FOR NEW

WORK.

5 DISCONNECT AND REMOVE LIGHT SWITCH.

REMOVE WIRING AND CONDUIT BACK TO

LAST OPERABLE DEVICE OR PANELBOARD.

6 DISCONNECT AND REMOVE LIGHTING

FIXTURE. REMOVE WIRING AND CONDUIT

BACK TO LAST OPERABLE DEVICE OR

PANELBOARD.

7 CONDUITS TO BE DEMOLISHED. REROUTE

CABLES TO NEW PATHWAYS NOTED IN

TECHNOLOGY PLAN BELOW.

8 EXISTING SBB. RELOCATE TO NEW

LOCATION AS SHOWN.

9 RELOCATE WIRELESS ACCESS POINT TO

ADJACENT EXISTING CEILING TO REMAIN AS

SHOWN ON NEW WORK PLAN.

1 PROVIDE CRITICAL POWER FEEDER

CIRCUIT TO PANEL 'A'.

2 PROVIDE NORMAL POWER FEEDER

CIRCUIT TO PANEL 'B'.

3 PROVIDE POWER TO THE NEW

RECEPTACLE FROM EXISTING

CONVENIENCE OUTLET CIRCUIT IN THE

CORRIDOR.

4 PROVIDE 120V POWER FOR DOOR

SECURITY HARDWARE. SEE DETAIL

5/ET503.

5 MOUNT OUTLETS ABOVE DATA RACK ON

CABLE TRAY. SEE DETAIL 6/ET502 FOR

MORE INFORMATION.

6 PROVIDE POWER CONNECTION AND

MOTOR RATED SWITCH FOR SPLIT UNIT.

7 8"X8"X4" HINGED CONTROLLER BOX,

MOUNTED ABOVE DOOR. SEE DETAIL

5/ET503.

8 PROVIDE 4 FIRE/SMOKE SLEEVE

ASSEMBLIES. REFERENCE DETAIL 2/ET501

FOR MORE INFORMATION.

9 RELOCATED SBB. EXTEND EXISTING

BONDING CONDUCTOR TO NEW

LOCATION.

10 PROVIDE ONE (1) 12" BY 18"

RECTANGULAR HOLE FOR EIGHT (8) UL

LISTED, FIRE/THERMAL RATED CONDUIT

PATHWAY ASSEMBLIES. RE-ROUTE

EXISTING CABLES THROUGH

ASSEMBLIES. PROVIDE ALL SHORING AND

SUPPORT. BOD STI-EZDG844S2.

11 RELOCATED WIRELESS ACCESS POINT.

EXTEND CABLING TO NEW LOCATION.

12 POWER NEW RECEPTACLE USING

CIRCUIT RETAINED DURING DEMOLITION.

EXTEND CONDUIT AND CABLING TO NEW

RECEPTACLE.

13 PROVIDE TWO (2) 4" CORE HOLE AND

INSTALL TWO (2) FIRE AND THERMAL

RATED ASSEMBLY (BOD P/N

STI-EZDP133FK) FOR RE-ROUTING

EXISTING CABLES.

E

E

M

E M

CR

DCESRX

CR

DCESRXJ

G.1 J K

COPY

B806

OFFICE

B807

ELEC

B813

CORRIDOR

C8-23

ELEC

B817

OFFICE

B820

CORRIDOR

C8-08

G

1 2

DATA

ROOM

B812

CONFERENCE

B810

SBB

G.1 J K

COPY

B806

OFFICE

B807

CONFERENCE

B810

TR

B812

ELEC

B813

CORRIDOR

C8-23

ELEC

B817

OFFICE

B820

CORRIDOR

C8-08

G

PANEL 'B'

PANEL 'A'

B

A

B A B N

A

B

A

A

B

SBB

A

A

1W-FCU-B812

1W-SF-B812

G.1 J K

COPY

B806

OFFICE

B807

CONFERENCE

B810

ELEC

B813

CORRIDOR

C8-23

ELEC

B817

OFFICE

B820

CORRIDOR

C8-08

G

DATA

ROOM

B812

TELECOM

SECURITY

12 1W.ET482.A

G.1 J K

COPY

B806

OFFICE

B807

CONFERENCE

B810

TR

B812

ELEC

B813

CORRIDOR

C8-23

ELEC

B817

OFFICE

B820

CORRIDOR

C8-08

K

G

SBB

G.1 J K

COPY

B806

OFFICE

B807

CONFERENCE

B810

ELEC

B813

CORRIDOR

C8-23

ELEC

B817

OFFICE

B820

CORRIDOR

C8-08

G

5 6

DATA

ROOM

B812

G.1 J K

COPY

B806

OFFICE

B807

CONFERENCE

B810

TR

B812

ELEC

B813

CORRIDOR

C8-23

ELEC

B817

OFFICE

B820

CORRIDOR

C8-08

G

A

A

A

OFFICE

B807

Engineers Architects

# KEY NOTES:

# KEY NOTES:

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREA

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

S S S S

1 HR - SMOKE SEPARATIONS S S S

/2

/2

:5

:4

A

M C

U s e rs

\a ri c h a rd s \D o c u m e n ts

\E

-0

A n n

A rb o r- E

H R

M B ld g

-1 W a ri c h a rd s P

K P

J .r v t

1W.ET482

BUILDING 1W, EIGHTH FLOOR, BRAVO

STACK, TELECOM ROOM B812

60 106ADR

EHRM INFRASTRUCTURE

UPGRADES

VA ANN ARBOR HEALTHCARE SYSTEM

2215 FULLER ROAD, ANN ARBOR, MI

48105 FEBRUARY 28, 2024

BID DOCUMENTS

506-21-70521-092

JKM

1W

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

Scale: 1/4" = 1'-0"

DATA ROOM B812, POWER DEMOLITION PLAN

Scale: 1/4" = 1'-0"

TELECOM ROOM B812, POWER PLAN

Scale: 1/4" = 1'-0"

DATA ROOM B812, TECHNOLOGY DEMOLITION PLAN

Scale: 1/4" = 1'-0"

TELECOM ROOM B812, TECHNOLOGY PLAN

Scale: 1/4" = 1'-0"

DATA ROOM B812, CEILING DEMOLITION PLAN

Scale: 1/4" = 1'-0"

TELECOM ROOM B812, CEILING PLAN

NORTH

0 2 4 8

NORTH

0 2 4 8

NORTH

0 2 4 8

NORTH

0 2 4 8

NORTH

0 2 4 8

NORTH

0 2 4 8

1 DISCONNECT MECHANICAL EQUIPMENT.

REMOVE WIRING AND CONDUIT BACK TO

LAST OPERABLE DEVICE OR PANELBOARD.

2 DISCONNECT AND REMOVE RECEPTACLE.

REMOVE WIRING AND CONDUIT BACK TO

LAST OPERABLE DEVICE OR PANELBOARD.

3 DISCONNECT AND REMOVE ALL UNUSED

CABLING FROM EXISTING EQUIPMENT RACK.

4 DISCONNECT AND REMOVE CAMERA.

RETAIN CONDUIT AND CABLING FOR NEW

WORK.

5 DISCONNECT AND REMOVE LIGHT SWITCH.

REMOVE WIRING AND CONDUIT BACK TO

LAST OPERABLE DEVICE OR PANELBOARD.

6 DISCONNECT AND REMOVE LIGHTING

FIXTURE. REMOVE WIRING AND CONDUIT

BACK TO LAST OPERABLE DEVICE OR

PANELBOARD.

7 RETAIN EXISTING GROUND BAR TO

RELOCATE IN NEW TELECOM ROOM.

8 RETAIN EXISTING ELECTRICAL OUTLET FOR

NEW TELECOM ROOM.

9 RELOCATE EXISTING DOOR SECURITY TO

NEW DOOR.

10 RETAIN EXISTING SWITCH FOR NEW

TELECOM ROOM.

11 DEMOLISH EXISTING SMOKE DETECTOR AND

REROUTE FIRE ALARM CONDUITS.

12 DISCONNECT AND REMOVE EXISTING WALL

MOUNTED EQUIPMENT RACK.

A. ALL EXISTING CONDITIONS, CONDUITS AND

DEVICES ARE BASED ON THE BEST

AVAILABLE INFORMATION AT THE TIME OF

SURVEY AND VISUAL INSPECTION. VERIFY

EXISTING CONDITIONS.

B. DEVICES SHOWN WITH LIGHT, GRAY LINES

ARE EXISTING TO REMAIN. DEVICES SHOWN

WITH DARK, DASHED LINES ARE EXISTING TO

BE DEMOLISHED. DEMOLITION SHALL

INCLUDE, BUT NOT BE LIMITED TO, THOSE

DEVICES AND SYSTEMS SHOWN.

COORDINATE WITH ALL OTHER DISCIPLINES.

C. AT ALL TIMES, FIRE ALARM SERVICES ARE TO

REMAIN ACTIVE OUTSIDE THE DESIGNATED

DEMOLITION AREA NOTED ON THE PLANS.

D. REMOVE ALL UNUSED CONDUIT AND

CABLING.

E. WHERE CONDUIT IS REMOVED FROM AN

EXISTING RATED ASSEMBLY NOT SUBJECT TO

DEMOLITION, THE REMAINING PENETRATION

SHALL BE PATCHED/REPAIRED TO MAINTAIN

THE RATING OF THE ASSEMBLY.

F. COORDINATE ALL WORK BETWEEN TRADES

AND DISCIPLINES.

G. NEW DEVICES AND EQUIPMENT SHOWN ON

SHEET SPECIFY NEW TELECOM ROOM

LAYOUT. FOR EQUIPMENT SPECIFICS AND

MORE INFORMATION SEE SHEET ET501.

1 PROVIDE CRITICAL POWER FEEDER

CIRCUIT TO PANEL 'A'.

2 PROVIDE NORMAL POWER FEEDER

CIRCUIT TO PANEL 'B'.

3 PROVIDE POWER TO THE NEW

RECEPTACLE FROM EXISTING

CONVENIENCE OUTLET CIRCUIT IN THE

CORRIDOR.

4 PROVIDE 120V POWER FOR DOOR

SECURITY HARDWARE. SEE DETAIL

5/ET503.

5 MOUNT OUTLETS ABOVE DATA RACK ON

CABLE TRAY. SEE DETAIL 6/ET502 FOR

MORE INFORMATION.

6 PROVIDE POWER CONNECTION AND

MOTOR RATED SWITCH FOR SPLIT UNIT.

7 8"X8"X4" HINGED CONTROLLER BOX,

MOUNTED ABOVE DOOR. SEE DETAIL

5/ET503.

8 PROVIDE 4 FIRE/SMOKE SLEEVE

ASSEMBLIES. REFERENCE DETAIL 2/ET501

FOR MORE INFORMATION.

9 RELOCATED SBB. EXTEND EXISTING

BONDING CONDUCTOR TO NEW

LOCATION.

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/2

/2

:5

:4

A

M C

U s e rs

\a ri c h a rd s \D o c u m e n ts

\E

-0

A n n

A rb o r- E

H R

M B ld g

-1 W a ri c h a rd s P

K P

J .r v t

1W.ET482.A

BUILDING 1W, EIGHTH FLOOR, BRAVO

STACK, TELECOM ROOM B812 -

ELEVATIONS

61 106ADR

EHRM INFRASTRUCTURE

UPGRADES

VA ANN ARBOR HEALTHCARE SYSTEM

2215 FULLER ROAD, ANN ARBOR, MI

48105 FEBRUARY 28, 2024

BID DOCUMENTS

506-21-70521-092

JKM

1W

A. ALL DEVICES IN THIS SPACE ARE

POTENTIALLY MISSION CRITICAL AND LIFE

SAFETY SUPPORTING. EXTREME CAUTION

SHOULD BE TAKEN TO PROTECT EVERY

DEVICE AND COORDINATE ANY DOWNTIME

NO LESS THAN TWENTY-ONE DAYS PRIOR

TO OUTAGE.

B. THIS SHEET IS PROVIDED TO

DEMONSTRATE THE EXISTING CONDITIONS

OF THE SPACE'S WALLS. WHERE POSSIBLE,

REMOVE AND REATTACH WALL-MOUNTED

SUPPORTS, BRACKETS, ETC. TO MAXIMIZE

THE BLOCKING MATERIAL BEING APPLIED

TO THE WALLS.

Scale: No Scale

TR B813 WALL ELEVATION - 01

Scale: No Scale

TR B813 WALL ELEVATION - 02

Scale: No Scale

TR B813 WALL ELEVATION - 03

Scale: No Scale

TR B813 WALL ELEVATION - 04

48"

E M

E

M

E

RX ES DC

CR

CR

DC ES RX J

SD

M

L

SERVICE

ELEVATOR

LOBBY

C9-4

EQUIPMENT

LIFT

PUBLIC

AFFAIRS

PHOTOS

A923

PRINTER

A927

OPEN

OFFICE

A931

OFFICE

A931B

DATA

ROOM

A921A

1 2

M

L

TR

A921A

SERVICE

ELEVATOR

LOBBY

C9-4

EQUIPMENT

LIFT

PUBLIC

AFFAIRS

PHOTOS

A923

PRINTER

A927

OPEN

OFFICE

A931

OFFICE

A931B

A N

B

SBB

A

PANEL 'B'

BA

PANEL 'A'

B

A

B

A

B

A

A

1W-SF-A921A

1W-FCU-A921A

M

L

SERVICE

ELEVATOR

LOBBY

C9-4

EQUIPMENT

LIFT

PUBLIC

AFFAIRS

PHOTOS

A923 PRINTER

A927

OPEN

OFFICE

A931

OFFICE

A931B

DATA

ROOM

A921A

3 4

CODE ONE

SECURITY

SECURITY

TELECOM

PA RISER

GND

M

L

TR

A921A

SERVICE

ELEVATOR

LOBBY

C9-4

EQUIPMENT

LIFT

PUBLIC

AFFAIRS

PHOTOS

A923

PRINTER

A927

OPEN

OFFICE

A931

OFFICE

A931B

K

SBB

M

L

SERVICE

ELEVATOR

LOBBY

C9-4

EQUIPMENT

LIFT

PUBLIC

AFFAIRS

PHOTOS

A923

PRINTER

A927

OPEN

OFFICE

A931

OFFICE

A931B

DATA

ROOM

A921A

5 6

M

L

TR

A921A

SERVICE

ELEVATOR

LOBBY

C9-4

EQUIPMENT

LIFT

PUBLIC

AFFAIRS

PHOTOS

A923

PRINTER

A927

OPEN

OFFICE

A931

OFFICE

A931B

A

A

A

TR

A921A

Engineers Architects

# KEY NOTES:

# KEY NOTES:

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREA

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

S S S S

1 HR - SMOKE SEPARATIONS S S S

/2

/2

:0

:1

A

M C

U s e rs

\a ri c h a rd s \D o c u m e n ts

\E

-0

A n n

A rb o r- E

H R

M B ld g

-1 W a ri c h a rd s P

K P

J .r v t

1W.ET491

BUILDING 1W, NINTH FLOOR, ALPHA

STACK, TELECOM ROOM A921A

62 106ADR

EHRM INFRASTRUCTURE

UPGRADES

VA ANN ARBOR HEALTHCARE SYSTEM

2215 FULLER ROAD, ANN ARBOR, MI

48105 FEBRUARY 28, 2024

BID DOCUMENTS

506-21-70521-092

JKM

1W

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

1 DISCONNECT MECHANICAL EQUIPMENT.

REMOVE WIRING AND CONDUIT BACK TO

LAST OPERABLE DEVICE OR PANELBOARD.

2 DISCONNECT AND REMOVE RECEPTACLE.

REMOVE WIRING AND CONDUIT BACK TO

LAST OPERABLE DEVICE OR PANELBOARD.

3 DISCONNECT AND REMOVE ALL UNUSED

CABLING FROM EXISTING EQUIPMENT RACK.

4 DISCONNECT AND REMOVE CAMERA.

RETAIN CONDUIT AND CABLING FOR NEW

WORK.

5 DISCONNECT AND REMOVE LIGHT SWITCH.

REMOVE WIRING AND CONDUIT BACK TO

LAST OPERABLE DEVICE OR PANELBOARD.

6 DISCONNECT AND REMOVE LIGHTING

FIXTURE. REMOVE WIRING AND CONDUIT

BACK TO LAST OPERABLE DEVICE OR

PANELBOARD.

7 DISCONNECT AND REMOVE EXISTING WALL

MOUNTED EQUIPMENT RACK.

8 CONDUITS TO BE DEMOLISHED. REROUTE

CABLES TO NEW PATHWAYS NOTED IN

TECHNOLOGY PLAN BELOW.

9 EXISTING SBB. RELOCATE TO NEW

LOCATION AS SHOWN.

1 PROVIDE CRITICAL POWER FEEDER CIRCUIT

TO PANEL 'A'.

2 PROVIDE NORMAL POWER FEEDER CIRCUIT

TO PANEL 'B'.

3 PROVIDE POWER TO THE NEW RECEPTACLE

FROM EXISTING CONVENIENCE OUTLET

CIRCUIT IN THE CORRIDOR.

4 PROVIDE 120V POWER FOR DOOR SECURITY

HARDWARE. SEE DETAIL 5/ET503.

5 MOUNT OUTLETS ABOVE DATA RACK ON

CABLE TRAY. SEE DETAIL 6/ET502 FOR MORE

INFORMATION.

6 PROVIDE POWER CONNECTION AND MOTOR

RATED SWITCH FOR SPLIT UNIT.

7 8"X8"X4" HINGED CONTROLLER BOX,

MOUNTED ABOVE DOOR. SEE DETAIL

5/ET503.

8 PROVIDE 4 FIRE/SMOKE SLEEVE

ASSEMBLIES. REFERENCE DETAIL 2/ET501

FOR MORE INFORMATION.

9 RELOCATED SBB. EXTEND EXISTING

BONDING CONDUCTOR TO NEW LOCATION.

10 PROVIDE ONE (1) 12" BY 18" RECTANGULAR

HOLE FOR EIGHT (8) UL LISTED,

FIRE/THERMAL RATED CONDUIT PATHWAY

ASSEMBLIES. RE-ROUTE EXISTING CABLES

THROUGH ASSEMBLIES. PROVIDE ALL

SHORING AND SUPPORT. BOD

STI-EZDG844S2.

Scale: 1/4" = 1'-0"

DATA ROOM A921A, POWER DEMOLITION PLAN

Scale: 1/4" = 1'-0"

TELECOM ROOM A921A, POWER PLAN

Scale: 1/4" = 1'-0"

DATA ROOM A921A, TECHNOLOGY DEMOLITION PLAN

Scale: 1/4" = 1'-0"

TELECOM ROOM A921A, TECHNOLOGY PLAN

Scale: 1/4" = 1'-0"

DATA ROOM A921A, CEILING DEMOLITION PLAN

Scale: 1/4" = 1'-0"

TELECOM ROOM A921A, CEILING PLAN

NORTH

0 2 4 8

NORTH

0 2 4 8

NORTH

0 2 4 8

NORTH

0 2 4 8

NORTH

0 2 4 8

NORTH

0 2 4 8

A. ALL EXISTING CONDITIONS, CONDUITS AND

DEVICES ARE BASED ON THE BEST

AVAILABLE INFORMATION AT THE TIME OF

SURVEY AND VISUAL INSPECTION. VERIFY

EXISTING CONDITIONS.

B. DEVICES SHOWN WITH LIGHT, GRAY LINES

ARE EXISTING TO REMAIN. DEVICES SHOWN

WITH DARK, DASHED LINES ARE EXISTING TO

BE DEMOLISHED. DEMOLITION SHALL

INCLUDE, BUT NOT BE LIMITED TO, THOSE

DEVICES AND SYSTEMS SHOWN.

COORDINATE WITH ALL OTHER DISCIPLINES.

C. AT ALL TIMES, FIRE ALARM SERVICES ARE TO

REMAIN ACTIVE OUTSIDE THE DESIGNATED

DEMOLITION AREA NOTED ON THE PLANS.

D. REMOVE ALL UNUSED CONDUIT AND

CABLING.

E. WHERE CONDUIT IS REMOVED FROM AN

EXISTING RATED ASSEMBLY NOT SUBJECT TO

DEMOLITION, THE REMAINING PENETRATION

SHALL BE PATCHED/REPAIRED TO MAINTAIN

THE RATING OF THE ASSEMBLY.

F. COORDINATE ALL WORK BETWEEN TRADES

AND DISCIPLINES.

G. NEW DEVICES AND EQUIPMENT SHOWN ON

SHEET SPECIFY NEW TELECOM ROOM

LAYOUT. FOR EQUIPMENT SPECIFICS AND

MORE INFORMATION SEE SHEET ET501.

S

SS S

MEE

S

SS S

RX

ES

DC

CR

S

SS S

DC

ES

RX

CR

J

S

SS S

S

SS S

S

SS S

1514 1716

K

L

J

M

OFFICE

FG34

ELEC

FG36

CLEAN

LINEN

FG83

OFFICE

FG85

NOURISHMENT

FG55

BREAK

ROOM

FG88

LAV

FG88A

TR

FG86

2BR

FG84

1 2

1514 1716

K

L

J

M

OFFICE

FG34

ELEC

FG36

CLEAN

LINEN

FG83

OFFICE

FG85

NOURISHMENT

FG55

BREAK

ROOM

FG88

LAV

FG88A

TR

FG86

2BR

FG84

A

B A B A

B

AB

PANEL 'A'

PANEL 'B'

GFI

N

A

B

SBB4

6A

28-CP-FG88

1514 1716

K

L

J

M

OFFICE

FG34

ELEC

FG36

CLEAN

LINEN

FG83

OFFICE

FG85

NOURISHMENT

FG55

BREAK

ROOM

FG88

LAV

FG88A

TR

FG86

2BR

FG84

DAMPER

CONTROL

TV HEAD-IN

SECURITY

NURSE CALL

TELECOM

1514 1716

K

L

J

M

OFFICE

FG34

ELEC

FG36

CLEAN

LINEN

FG83

OFFICE

FG85

NOURISHMENT

FG55

BREAK

ROOM

FG88

LAV

FG88A

TR

FG86

2BR

FG84

K

4 SBB

1514 1716

K K

L L

J J

M M

OFFICE

FG34

ELEC

FG36

CLEAN

LINEN

FG83

OFFICE

FG85

NOURISHMENT

FG55

BREAK

ROOM

FG88

LAV

FG88A

TR

FG86

2BR

FG84

LV

1514 1716

K

L

J

M

OFFICE

FG34

ELEC

FG36

CLEAN

LINEN

FG83

OFFICE

FG85

NOURISHMENT

FG55

BREAK

ROOM

FG88

LAV

FG88A

TR

FG86

2BR

FG84

A A

Engineers Architects

# KEY NOTES:

# KEY NOTES:

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREAS S S S

1 HR - SMOKE SEPARATIONS S S S

/2

/2

:1

:5

A

M C

U s e rs

\a ri c h a rd s \D o c u m e n ts \E

-0

A n n

A rb o r-

E H

R M

B ld g -0 a ri c h a rd s P

K P

J .r v t

28.ET401

BUILDING 28, BASEMENT, FOXTROT

STACK, TELECOM ROOM FG86

63 106ADR

EHRM INFRASTRUCTURE

UPGRADES

VA ANN ARBOR HEALTHCARE SYSTEM

2215 FULLER ROAD, ANN ARBOR, MI

48105 FEBRUARY 28, 2024

BID DOCUMENTS

506-21-70521-092

JKM

1 PROVIDE CRITICAL POWER FEEDER CIRCUIT

TO PANEL 'A'.

2 PROVIDE NORMAL POWER FEEDER CIRCUIT

TO PANEL 'B'.

3 PROVIDE POWER TO THE NEW RECEPTACLE

FROM EXISTING CONVENIENCE OUTLET

CIRCUIT IN THE CORRIDOR.

4 PROVIDE 120V POWER FOR DOOR SECURITY

HARDWARE. SEE DETAIL 5/ET503.

5 MOUNT OUTLETS ABOVE DATA RACK ON

CABLE TRAY. SEE DETAIL 6/ET502 FOR MORE

INFORMATION.

6 PROVIDE POWER CONNECTION AND MOTOR

RATED SWITCH FOR SPLIT UNIT.

7 RELOCATED SBB. EXTEND

TELECOMMUNICATIONS BACKBONE

CONDUCTOR TO NEW LOCATION.

8 8"X8"X4" HINGED CONTROLLER BOX,

MOUNTED ABOVE DOOR. SEE DETAIL 5/ET503.

9 PROVIDE 4 FIRE/SMOKE SLEEVE ASSEMBLIES.

REFERENCE DETAIL 2/ET501 FOR MORE

INFORMATION.

A. ALL EXISTING CONDITIONS, CONDUITS AND

DEVICES ARE BASED ON THE BEST AVAILABLE

INFORMATION AT THE TIME OF SURVEY AND

VISUAL INSPECTION. VERIFY EXISTING

CONDITIONS.

B. DEVICES SHOWN WITH LIGHT, GRAY LINES ARE

EXISTING TO REMAIN. DEVICES SHOWN WITH

DARK, DASHED LINES ARE EXISTING TO BE

DEMOLISHED. DEMOLITION SHALL INCLUDE, BUT

NOT BE LIMITED TO, THOSE DEVICES AND

SYSTEMS SHOWN. COORDINATE WITH ALL

OTHER DISCIPLINES.

C. AT ALL TIMES, FIRE ALARM SERVICES ARE TO

REMAIN ACTIVE OUTSIDE THE DESIGNATED

DEMOLITION AREA NOTED ON THE PLANS.

D. REMOVE ALL UNUSED CONDUIT AND CABLING.

E. WHERE CONDUIT IS REMOVED FROM AN

EXISTING RATED ASSEMBLY NOT SUBJECT TO

DEMOLITION, THE REMAINING PENETRATION

SHALL BE PATCHED/REPAIRED TO MAINTAIN THE

RATING OF THE ASSEMBLY.

F. COORDINATE ALL WORK BETWEEN TRADES AND

DISCIPLINES.

G. NEW DEVICES AND EQUIPMENT SHOWN ON

SHEET SPECIFY NEW TELECOM ROOM LAYOUT.

FOR EQUIPMENT SPECIFICS AND MORE

INFORMATION SEE SHEET ET501.

H. THIS IS A MENTAL HEALTH AREA. WORK AREA

MUST BE SECURED AT ALL TIMES. NO WORK

SHALL BE PERFORMED BY ONLY (1) PERSON. ALL

EQUIPMENT & TOOLS MUST BE CONTROLLED &

INVENTORIED THROUGHOUT CONSTRUCTION.

I. TOOLS, EQUIPMENT, OR MISCELLANEOUS ITEMS

SHALL NOT BE LEFT UNATTENDED IN THE

PATIENT CARE AREA.

J. LOUD AND/OR REPETITIVE NOISES IN THIS AREA

SHALL BE AVOIDED, TO THE MAXIMUM EXTENT

PRACTICAL.

NORTH

0 2 4 8

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

Scale: 1/4" = 1'-0"

TELECOM ROOM FG86, POWER DEMOLITION PLAN

Scale: 1/4" = 1'-0"

TELECOM ROOM FG86, POWER PLAN

Scale: 1/4" = 1'-0"

TELECOM ROOM FG86, TECHNOLOGY DEMOLITION PLAN

Scale: 1/4" = 1'-0"

TELECOM ROOM FG86, TECHNOLOGY PLAN

Scale: 1/4" = 1'-0"

TELECOM ROOM FG86, CEILING DEMOLITION PLAN

Scale: 1/4" = 1'-0"

TELECOM ROOM FG86, CEILING PLAN

NORTH

0 2 4 8

NORTH

0 2 4 8

NORTH

0 2 4 8

NORTH

0 2 4 8

NORTH

0 2 4 8

1 DISCONNECT MECHANICAL EQUIPMENT.

REMOVE WIRING AND CONDUIT BACK TO LAST

OPERABLE DEVICE OR PANELBOARD.

2 DISCONNECT AND REMOVE RECEPTACLE.

REMOVE WIRING AND CONDUIT BACK TO LAST

OPERABLE DEVICE OR PANELBOARD.

3 DISCONNECT ALL UNUSED CABLING FROM

EXISTING EQUIPMENT RACK.

4 DISCONNECT AND REMOVE CAMERA. RETAIN

CONDUIT AND CABLING FOR NEW WORK.

5 DISCONNECT AND REMOVE LIGHT SWITCH.

REMOVE WIRING AND CONDUIT BACK TO LAST

OPERABLE DEVICE OR PANELBOARD.

6 DISCONNECT AND REMOVE LIGHTING FIXTURE.

REMOVE WIRING AND CONDUIT BACK TO LAST

OPERABLE DEVICE OR PANELBOARD.

7 THIS ROOM SHALL BE CLOSED-OFF FOR

PATIENT CARE WHEN DEMOLITION AND/OR

CONSTRUCTION IS BEING PERFORMED IN

ROOM FG86.

8 EXISTING SBB. RELOCATE TO NEW LOCATION

AS SHOWN.

2 3 4 5

R

B

B.5

2.5

MAIN

COMPUTER

ROOM

A180

EXISTING

PANEL 'UPS-DP'

28-SS-FG88

PDU

PDU

UPS A180

PANEL

'UPS2-DP'

EXISTING

PANEL 'ADP6'ETR

ETR

ETR

ETR

ETR ETR

ETR

FACP

ETRETR

SPA 180

-TT

SPA 180

-SS

SPA 180 -WSPA 180 -X

SPA 180 -USPA 180 -TSPA 180 -P SPA 180 -SSPA 180 -QSPA 180 -OSPA 180 -NSPA 180 -RSPA 180 -ZSPA 180 -Y

SPA 180 -MSPA 180 -LSPA 180 -K

SPA 180 -GSPA 180 -FSPA 180 -ESPA 180 -D

H15

SPA 180 -V

6 6

CRAC-1

2 3 4 5

R

B

B.5

2.5

MAIN

COMPUTER

ROOM

A180

EXISTING

PANEL 'UPS-DP'

FACP

PDU

PDU

ETR

ETR

ETR

ETR

ETR ETR

ETR

EXISTING

PANEL 'ADP6'

96"

ETR

2 6

ETR

CRAC-1

28-SS-FG88

SPA 180

-TT

SPA 180

-SS

SPA 180 -WSPA 180 -X

SPA 180 -USPA 180 -TSPA 180 -P SPA 180 -SSPA 180 -QSPA 180 -OSPA 180 -NSPA 180 -RSPA 180 -ZSPA 180 -Y

SPA 180 -MSPA 180 -LSPA 180 -K

SPA 180 -GSPA 180 -FSPA 180 -ESPA 180 -D

H15

SPA 180 -V

Engineers Architects

# KEY NOTES:

# KEY NOTES:

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREAS S S S

1 HR - SMOKE SEPARATIONS S S S

/8

/2

:5

:3

P M

C U s e rs

\a ri c h a rd s \D o c u m e n ts \E

-0

A n n

A rb o r-

E H

R M

B ld g -0 a ri c h a rd s P

K P

J .r v t

28.ET411

BUILDING 28, FIRST FLOOR, MAIN

COMPUTER ROOM A180 - POWER

64 106ADR

EHRM INFRASTRUCTURE

UPGRADES

VA ANN ARBOR HEALTHCARE SYSTEM

2215 FULLER ROAD, ANN ARBOR, MI

48105 FEBRUARY 28, 2024

BID DOCUMENTS

506-21-70521-092

JKM

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

A. ALL EXISTING CONDITIONS, CONDUITS AND

DEVICES ARE BASED ON THE BEST AVAILABLE

INFORMATION AT THE TIME OF SURVEY AND

VISUAL INSPECTION. VERIFY EXISTING

CONDITIONS.

B. DEVICES SHOWN WITH LIGHT, GRAY LINES ARE

EXISTING TO REMAIN. DEVICES SHOWN WITH

DARK, DASHED LINES ARE EXISTING TO BE

DEMOLISHED. DEMOLITION SHALL INCLUDE, BUT

NOT BE LIMITED TO, THOSE DEVICES AND

SYSTEMS SHOWN. COORDINATE WITH ALL

OTHER DISCIPLINES.

C. AT ALL TIMES, FIRE ALARM SERVICES ARE TO

REMAIN ACTIVE OUTSIDE THE DESIGNATED

DEMOLITION AREA NOTED ON THE PLANS.

D. REMOVE ALL UNUSED CONDUIT AND CABLING.

E. WHERE CONDUIT IS REMOVED FROM AN

EXISTING RATED ASSEMBLY NOT SUBJECT TO

DEMOLITION, THE REMAINING PENETRATION

SHALL BE PATCHED/REPAIRED TO MAINTAIN THE

RATING OF THE ASSEMBLY.

F. COORDINATE ALL WORK BETWEEN TRADES AND

DISCIPLINES.

G. NEW DEVICES AND EQUIPMENT SHOWN ON

SHEET SPECIFY NEW TELECOM ROOM LAYOUT.

FOR EQUIPMENT SPECIFICS AND MORE

INFORMATION SEE SHEET ET501.

H. THIS IS A MENTAL HEALTH AREA. WORK AREA

MUST BE SECURED AT ALL TIMES. NO WORK

SHALL BE PERFORMED BY ONLY (1) PERSON. ALL

EQUIPMENT & TOOLS MUST BE CONTROLLED &

INVENTORIED THROUGHOUT CONSTRUCTION.

I. TOOLS, EQUIPMENT, OR MISCELLANEOUS ITEMS

SHALL NOT BE LEFT UNATTENDED IN THE

PATIENT CARE AREA.

J. LOUD AND/OR REPETITIVE NOISES IN THIS AREA

SHALL BE AVOIDED, TO THE MAXIMUM EXTENT

PRACTICAL.

NORTH

0 2 4 8

NORTH

0 2 4 8

Scale: 1/4" = 1'-0"

MAIN COMPUTER ROOM A180, POWER PLAN PHASE 1

Scale: 1/4" = 1'-0"

MAIN COMPUTER ROOM A180, POWER DEMOLITION PLAN

1 EXISTING LEIBERT CRAC UNIT TO BE REMOVED AND

REPLACED WITH NEW. DISCONNECT UNIT AND

RETAIN CIRCUIT FOR REUSE DURING NEW

CONSTRUCTION.

2 EXISTING DISCONNECT TO REMAIN.

3 DEMOLISH ABANDONED RECEPTACLES UNDER

RAISED FLOOR BACK TO THE SOURCE. REMOVE ALL

CONDUIT AND CABLING. NOTIFY COR OF ANY

ABONDONED CABLING FOUND DURING

CONSTRUCTION.

4 EXISTING SPECIALTY OUTLET AND WALL MOUNTED

SPEAKER TO REMAIN.

5 EXISTING PDU TO REMAIN.

6 EXISTING FIRE ABORT TO REMAIN.

7 DEMOLISH ABANDONED COPPER AND FIBER CABLES

UNDER RAISED FLOOR. BID APPROXIMATELY 20

COPPER CABLES AT 45 FEET EACH AND 20 FIBER

CABLES 45 FEET EACH. GET APPROVAL FROM COR

PRIOR TO REMOVING ANY UNDERFLOOR CABLES.

1 PROVIDE NEW 80 kW/80 kVA, 208Y/120V UPS. SEE

BUILDING 28 DATA CENTER ELECTRICAL RISER

DIAGRAM ON SHEET 1.ET602 FOR MORE

INFORMATION.

2 PROVIDE NEW 208Y/110V 250A MCB POWER PANEL.

SEE 1.ET602 FEEDER SCHEDULE ON SHEET 1.ET602

FOR MORE INFORMATION.

3 INTERCEPT EXISTING FEED TO EXISTING PDU AND

RECONNECT TO NEW PANEL UPS2-DP.

4 PROVIDE UPS PLATFORM BENEATH UPS. LEVEL

PLATFORM AND MATCH THE HEIGHT OF THE

SURROUNDING RAISED FLOOR. SEAL JOINT

BETWEEN PLATFORM AND RAISED FLOOR.

5 NEW CRAC UNIT. CONNECT TO 480V/3 PHASE

CIRCUIT RETAINED DURING DEMOLITION. IF THE

EXISTING OVERCURRENT DEVICE ON THE EXISTING

UNIT IS GREATER THAN 80A, INSTALL A 3 POLE/100A

FUSIBLE DISCONNECT SWITCH UPSTREAM OF THE

CRAC UNIT AND FUSE THE DISCONNECT AT 80A TO

SERVE THE NEW CRAC UNIT.

6 PATCH FIBER FROM TRs TO EXISTING CORE SWITCH

IN DATA RACK. USE PRE-TERMINATED FIBER TO

PATCH BETWEEN THE NEW FIBER PATCH PANEL

AND THE CORE SWITCH. CONTRACTOR TO BID 1000

PATCH CABLES.

Notes:

Total Est. Demand: 175 A

Total Conn.: 175 A

Total Est. Demand: 63.00 kVA

Total Conn. Load: 63.00 kVA

Spare 63.00 kVA 100.00% 63.00 kVA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 175 A 175 A 175 A

Total Load: 21.00 kVA 21.00 kVA 21.00 kVA

41 SPARE 20 A 1 0.00 0.00 1 20 A SPARE 42

39 SPARE 20 A 1 0.00 0.00 1 20 A SPARE 40

37 SPARE 20 A 1 0.00 0.00 1 20 A SPARE 38

35 SPARE 20 A 1 0.00 0.00 1 20 A SPARE 36

33 SPARE 20 A 1 0.00 0.00 1 20 A SPARE 34

31 SPARE 20 A 1 0.00 0.00 1 20 A SPARE 32

29 SPARE 20 A 1 0.00 0.00 1 20 A SPARE 30

27 SPARE 20 A 1 0.00 0.00 1 20 A SPARE 28

25 SPARE 20 A 1 0.00 0.00 1 20 A SPARE 26

23 SPARE 20 A 1 0.00 0.00 1 20 A SPARE 24

21 SPARE 20 A 1 0.00 0.00 1 20 A SPARE 22

19 SPARE 20 A 1 0.00 0.00 1 20 A SPARE 20

17 SPARE 20 A 1 0.00 0.00 1 20 A SPARE 18

15 SPARE 20 A 1 0.00 0.00 1 20 A SPARE 16

13 SPARE 20 A 1 0.00 0.00 1 20 A SPARE 14

11 SPARE 20 A 1 0.00 0.00 1 20 A SPARE 12

9 SPARE 20 A 1 0.00 0.00 1 20 A SPARE 10

7 SPARE 20 A 1 0.00 0.00 1 20 A SPARE 8

5 10.50 10.50 6

3 10.50 10.50 4

EXISTING PDU 225 A 3

10.50 10.50

3 225 A EXISTING PDU

CKT Circuit Description Trip Poles

A B C A B C

Poles Trip Circuit Description CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 400 A

Mounting: SURFACE Wires: 4 Mains Rating:

Supply From: Phases: 3 Mains Type: MCB

Location: MAIN COMPUTER ROOM A180 Volts: 120/208 A.I.C. Rating: 22,000 AIC

Branch Panel: UPS2-DP

F/250AT

Docusign Envelope ID: 635BD638-6D8A-48CF-A710-8A74AD2E69A4

7/9/2024 7/9/2024

E

M

CR

DC

ES

RX

CR

DC

ES

RX

J

SD

1514 1716

K

L

J

M

ELEC

F147A

LAUNDRY

F163

INTERVIEW

ROOM

F161

TR

F152

AQUARIUM

F154A

INTERVIEW

ROOM

F153

MED

ROOM

F147G

LOUNGE

F150

STORAGE

F154

1 2

SBB 9

1514 1716

K

L

J

M

ELEC

F147A

LAUNDRY

F163

INTERVIEW

ROOM

F161

TR

F152

AQUARIUM

F154A

INTERVIEW

ROOM

F153

MED

ROOM

F147G

LOUNGE

F150

STORAGE

F154

PANEL 'A'

PANEL 'B'

A

B

A

GFI

N

B A B

A

B

AB

SBB 4

28-CP-FG89

1514 1716

K

L

J

M

ELEC

F147A

LAUNDRY

F163

INTERVIEW

ROOM

F161

TR

F152

AQUARIUM

F154A

INTERVIEW

ROOM

F153

MED

ROOM

F147G

LOUNGE

F150

STORAGE

F154

3 4

SECURITY

MATV

SECURITY

TELECOM

LV

LV

TELECOM

1514 1716

K

L

J

M

ELEC

F147A

LAUNDRY

F163

INTERVIEW

ROOM

F161

TR

F152

AQUARIUM

F154A

INTERVIEW

ROOM

F153

MED

ROOM

F147G

LOUNGE

F150

STORAGE

F154

K

SBB

1514 1716

K

L

J

M

ELEC

F147A

LAUNDRY

F163

INTERVIEW

ROOM

F161

TR

F152

AQUARIUM

F154A

INTERVIEW

ROOM

F153

MED

ROOM

F147G

LOUNGE

F150

STORAGE

F154

5 6

1514 1716

K

L

J

M

ELEC

F147A

LAUNDRY

F163

INTERVIEW

ROOM

F161

TR

F152

AQUARIUM

F154A

INTERVIEW

ROOM

F153

MED

ROOM

F147G

LOUNGE

F150

STORAGE

F154

A

A

Engineers Architects

# KEY NOTES:

# KEY NOTES:

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREAS S S S

1 HR - SMOKE SEPARATIONS S S S

/2

/2

:1

:0

A

M C

U s e rs

\a ri c h a rd s \D o c u m e n ts \E

-0

A n n

A rb o r-

E H

R M

B ld g -0 a ri c h a rd s P

K P

J .r v t

28.ET414

BUILDING 28, FIRST FLOOR, FOXTROT

STACK, TELECOM ROOM F152

65 106ADR

EHRM INFRASTRUCTURE

UPGRADES

VA ANN ARBOR HEALTHCARE SYSTEM

2215 FULLER ROAD, ANN ARBOR, MI

48105 FEBRUARY 28, 2024

BID DOCUMENTS

506-21-70521-092

JKM

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

Scale: 1/4" = 1'-0"

TELECOM ROOM F152, POWER DEMOLITION PLAN

Scale: 1/4" = 1'-0"

TELECOM ROOM F152, POWER PLAN

Scale: 1/4" = 1'-0"

TELECOM ROOM F152, TECHNOLOGY

DEMOLITION PLAN

Scale: 1/4" = 1'-0"

TELECOM ROOM F152, TECHNOLOGY PLAN

Scale: 1/4" = 1'-0"

TELECOM ROOM F152, CEILING DEMOLITION PLAN

Scale: 1/4" = 1'-0"

TELECOM ROOM F152, CEILING PLAN

NORTH

0 2 4 8

NORTH

0 2 4 8

NORTH

0 2 4 8

NORTH

0 2 4 8

NORTH

0 2 4 8

NORTH

0 2 4 8

1 DISCONNECT MECHANICAL EQUIPMENT.

REMOVE WIRING AND CONDUIT BACK TO LAST

OPERABLE DEVICE OR PANELBOARD.

2 DISCONNECT AND REMOVE RECEPTACLE.

REMOVE WIRING AND CONDUIT BACK TO LAST

OPERABLE DEVICE OR PANELBOARD.

3 DISCONNECT ALL UNUSED CABLING FROM

EXISTING EQUIPMENT RACK.

4 DISCONNECT AND REMOVE CAMERA. RETAIN

CONDUIT AND CABLING FOR NEW WORK.

5 DISCONNECT AND REMOVE LIGHT SWITCH.

REMOVE WIRING AND CONDUIT BACK TO LAST

OPERABLE DEVICE OR PANELBOARD.

6 DISCONNECT AND REMOVE LIGHTING

FIXTURE. REMOVE WIRING AND CONDUIT

BACK TO LAST OPERABLE DEVICE OR

PANELBOARD.

7 THIS AREA REQUIRES A HARD PLASTIC,

POP-UP BARRIER, DURING HARD BARRIER

INSTALLATION & REMOVAL, TO PROTECT THE

EXISTING LOUNGE AREA.

8 EXISTING HVAC EQUIPMENT TO REMAIN.

9 EXISTING SBB. RELOCATE TO NEW LOCATION

AS SHOWN.

A. ALL EXISTING CONDITIONS, CONDUITS AND

DEVICES ARE BASED ON THE BEST AVAILABLE

INFORMATION AT THE TIME OF SURVEY AND

VISUAL INSPECTION. VERIFY EXISTING

CONDITIONS.

B. DEVICES SHOWN WITH LIGHT, GRAY LINES ARE

EXISTING TO REMAIN. DEVICES SHOWN WITH

DARK, DASHED LINES ARE EXISTING TO BE

DEMOLISHED. DEMOLITION SHALL INCLUDE, BUT

NOT BE LIMITED TO, THOSE DEVICES AND

SYSTEMS SHOWN. COORDINATE WITH ALL

OTHER DISCIPLINES.

C. AT ALL TIMES, FIRE ALARM SERVICES ARE TO

REMAIN ACTIVE OUTSIDE THE DESIGNATED

DEMOLITION AREA NOTED ON THE PLANS.

D. REMOVE ALL UNUSED CONDUIT AND CABLING.

E. WHERE CONDUIT IS REMOVED FROM AN

EXISTING RATED ASSEMBLY NOT SUBJECT TO

DEMOLITION, THE REMAINING PENETRATION

SHALL BE PATCHED/REPAIRED TO MAINTAIN THE

RATING OF THE ASSEMBLY.

F. COORDINATE ALL WORK BETWEEN TRADES AND

DISCIPLINES.

G. NEW DEVICES AND EQUIPMENT SHOWN ON

SHEET SPECIFY NEW TELECOM ROOM LAYOUT.

FOR EQUIPMENT SPECIFICS AND MORE

INFORMATION SEE SHEET ET501.

H. THIS IS A MENTAL HEALTH AREA. WORK AREA

MUST BE SECURED AT ALL TIMES. NO WORK

SHALL BE PERFORMED BY ONLY (1) PERSON. ALL

EQUIPMENT & TOOLS MUST BE CONTROLLED &

INVENTORIED THROUGHOUT CONSTRUCTION.

I. TOOLS, EQUIPMENT, OR MISCELLANEOUS ITEMS

SHALL NOT BE LEFT UNATTENDED IN THE

PATIENT CARE AREA.

J. LOUD AND/OR REPETITIVE NOISES IN THIS AREA

SHALL BE AVOIDED, TO THE MAXIMUM EXTENT

PRACTICAL.

1 PROVIDE CRITICAL POWER FEEDER CIRCUIT

TO PANEL 'A'.

2 PROVIDE NORMAL POWER FEEDER CIRCUIT

TO PANEL 'B'.

3 PROVIDE POWER TO THE NEW RECEPTACLE

FROM EXISTING CONVENIENCE OUTLET

CIRCUIT IN THE CORRIDOR.

4 PROVIDE 120V POWER FOR DOOR SECURITY

HARDWARE. SEE DETAIL 5/ET503.

5 MOUNT OUTLETS ABOVE DATA RACK ON

CABLE TRAY. SEE DETAIL 6/ET502 FOR MORE

INFORMATION.

6 PROVIDE POWER CONNECTION AND MOTOR

RATED SWITCH FOR FCU.

8 8"X8"X4" HINGED CONTROLLER BOX,

MOUNTED ABOVE DOOR. SEE DETAIL 5/ET503.

9 PROVIDE 4 FIRE/SMOKE SLEEVE ASSEMBLIES.

REFERENCE DETAIL 2/ET501 FOR MORE

INFORMATION.

M

E

DC

ES

RX

CR

J

1514 1716

K

L

J

M

OFFICE

F242

OFFICE

F240

ELEC

F226

LAV

F224F

LAV

F224G

OFFICE

F224

OFFICE

OFFICE

F224A

1 2

1514 1716

K

L

J

M

TR

F224A

OFFICE

F242

OFFICE

F240

ELEC

F226

LAV

F224F

LAV

F224G

CORRIDOR

C213

OFFICE

F224

OFFICE

PANEL 'A'PANEL 'B'

A

GFI

N

B

A B

A

B

AB

A

B

SBB

28-CP-FG90

1514 1716

K

L

J

M

OFFICE

F242

OFFICE

F240

ELEC

F226

LAV

F224F

LAV

F224G

OFFICE

F224

OFFICE

OFFICE

F224A

1514 1716

K

L

J

M

TR

F224A

OFFICE

F242

OFFICE

F240

ELEC

F226

LAV

F224F

LAV

F224G

OFFICE

F224

OFFICE

K

SBB

1514 1716

K

L

J

M M

OFFICE

F242

OFFICE

F240

ELEC

F226

LAV

F224F

LAV

F224G

OFFICE

F224

OFFICE

OFFICE

F224A

3 4

1514 1716

K

L

J

M

TR

F224A

OFFICE

F242

OFFICE

F240

ELEC

F226

LAV

F224F

LAV

F224G

OFFICE

F224

OFFICE

A A

A A

Engineers Architects

# KEY NOTES:

# KEY NOTES:

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREAS S S S

1 HR - SMOKE SEPARATIONS S S S

/2

/2

:1

:0

A

M C

U s e rs

\a ri c h a rd s \D o c u m e n ts \E

-0

A n n

A rb o r-

E H

R M

B ld g -0 a ri c h a rd s P

K P

J .r v t

28.ET421

BUILDING 28, SECOND FLOOR,

FOXTROT STACK, TELECOM ROOM

F224A

66 106ADR

EHRM INFRASTRUCTURE

UPGRADES

VA ANN ARBOR HEALTHCARE SYSTEM

2215 FULLER ROAD, ANN ARBOR, MI

48105 FEBRUARY 28, 2024

BID DOCUMENTS

506-21-70521-092

JKM

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

Scale: 1/4" = 1'-0"

OFFICE F224A, POWER DEMOLITION PLAN

Scale: 1/4" = 1'-0"

TELECOM ROOM F224A, POWER PLAN

Scale: 1/4" = 1'-0"

OFFICE F224A, TECHNOLOGY DEMOLITION PLAN

Scale: 1/4" = 1'-0"

TELECOM ROOM F224A, TECHNOLOGY PLAN

Scale: 1/4" = 1'-0"

OFFICE F224A, CEILING DEMOLITION PLAN

Scale: 1/4" = 1'-0"

TELECOM ROOM F224A, CEILING PLAN

1 DISCONNECT MECHANICAL EQUIPMENT.

REMOVE WIRING AND CONDUIT BACK TO

LAST OPERABLE DEVICE OR PANELBOARD.

2 DISCONNECT AND REMOVE RECEPTACLE.

REMOVE WIRING AND CONDUIT BACK TO

LAST OPERABLE DEVICE OR PANELBOARD.

3 DISCONNECT AND REMOVE LIGHT SWITCH.

REMOVE WIRING AND CONDUIT BACK TO

LAST OPERABLE DEVICE OR PANELBOARD.

4 DISCONNECT AND REMOVE LIGHTING

FIXTURE. REMOVE WIRING AND CONDUIT

BACK TO LAST OPERABLE DEVICE OR

PANELBOARD.

1 PROVIDE CRITICAL POWER FEEDER CIRCUIT

TO PANEL 'A'.

2 PROVIDE NORMAL POWER FEEDER CIRCUIT

TO PANEL 'B'.

3 PROVIDE POWER TO THE NEW RECEPTACLE

FROM EXISTING CONVENIENCE OUTLET

CIRCUIT IN THE CORRIDOR.

4 PROVIDE 120V POWER FOR DOOR SECURITY

HARDWARE. SEE DETAIL 5/ET503.

5 MOUNT OUTLETS ABOVE DATA RACK ON

CABLE TRAY. SEE DETAIL 6/ET502 FOR MORE

INFORMATION.

6 PROVIDE POWER CONNECTION AND MOTOR

RATED SWITCH FOR SPLIT UNIT.

7 8"X8"X4" HINGED CONTROLLER BOX,

MOUNTED ABOVE DOOR. SEE DETAIL 5/ET503.

8 PROVIDE 4 FIRE/SMOKE SLEEVE

ASSEMBLIES. REFERENCE DETAIL 2/ET501

FOR MORE INFORMATION.

NORTH

0 2 4 8

NORTH

0 2 4 8

NORTH

0 2 4 8

NORTH

0 2 4 8

NORTH

0 2 4 8

NORTH

0 2 4 8

A. ALL EXISTING CONDITIONS, CONDUITS AND

DEVICES ARE BASED ON THE BEST

AVAILABLE INFORMATION AT THE TIME OF

SURVEY AND VISUAL INSPECTION. VERIFY

EXISTING CONDITIONS.

B. DEVICES SHOWN WITH LIGHT, GRAY LINES

ARE EXISTING TO REMAIN. DEVICES SHOWN

WITH DARK, DASHED LINES ARE EXISTING TO

BE DEMOLISHED. DEMOLITION SHALL

INCLUDE, BUT NOT BE LIMITED TO, THOSE

DEVICES AND SYSTEMS SHOWN.

COORDINATE WITH ALL OTHER DISCIPLINES.

C. AT ALL TIMES, FIRE ALARM SERVICES ARE TO

REMAIN ACTIVE OUTSIDE THE DESIGNATED

DEMOLITION AREA NOTED ON THE PLANS.

D. REMOVE ALL UNUSED CONDUIT AND

CABLING.

E. WHERE CONDUIT IS REMOVED FROM AN

EXISTING RATED ASSEMBLY NOT SUBJECT TO

DEMOLITION, THE REMAINING PENETRATION

SHALL BE PATCHED/REPAIRED TO MAINTAIN

THE RATING OF THE ASSEMBLY.

F. COORDINATE ALL WORK BETWEEN TRADES

AND DISCIPLINES.

G. NEW DEVICES AND EQUIPMENT SHOWN ON

SHEET SPECIFY NEW TELECOM ROOM

LAYOUT. FOR EQUIPMENT SPECIFICS AND

MORE INFORMATION SEE SHEET ET501.

G

FI

W P

E

E

E

M

DC

ES

RX

CR

J

FSD

CRAWLSPACE

CRAWLSPACE

1 2

TR

CRAWLSPACE

CRAWLSPACE

TR

PANEL 'B'

PANEL 'A'

BA

B

A

B A

B

GFI

N

A B

A

SBB

02-SS-210

02-CU-210

(ON GRADE)

M 02-SF-210

TR

CRAWLSPACE

CRAWLSPACE

3 4

TR

K

SBB

TR

CRAWLSPACE

CRAWLSPACE

5 6 7

CRAWLSPACE

CRAWLSPACE

TR

AAA

A A9

9 9

Engineers Architects

# KEY NOTES:

# KEY NOTES:

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

NOT FOR

CONSTRUCTIO

N

NOT FOR

CONSTRUCTIO

N

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREA

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

S S S S

/2

/2

:4

:4

A

M C

U s e rs

\a ri c h a rd s \D o c u m e n ts

\E

-0

A n n

A rb o r- E

H R

M B ld g

-0 a ri c h a rd s P

K P

J .r v t

2.ET421

BUILDING 2, FULLER HOUSE, SECOND

FLOOR, TELECOM ROOM 210

67 106ADR

EHRM INFRASTRUCTURE

UPGRADES

VA ANN ARBOR HEALTHCARE SYSTEM

2215 FULLER ROAD, ANN ARBOR, MI

48105 FEBRUARY 28, 2024

BID DOCUMENTS

506-21-70521-092

JKM

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

Scale: 1/4" = 1'-0"

TELECOM ROOM 210, POWER DEMOLITION PLAN

Scale: 1/4" = 1'-0"

TELECOM ROOM 210, POWER PLAN

Scale: 1/4" = 1'-0"

TELECOM ROOM 210, TECHNOLOGY DEMOLITION PLAN

Scale: 1/4" = 1'-0"

TELECOM ROOM 210, TECHNOLOGY PLAN

Scale: 1/4" = 1'-0"

TELECOM ROOM 10, CEILING DEMOLITION PLAN

Scale: 1/4" = 1'-0"

TELECOM ROOM 210, CEILING PLAN

N O

R T

H0 2 4 8

N O

R T

H0 2 4 8

N O

R T

H0 2 4 8

N O

R T

H0 2 4 8

N O

R T

H0 2 4 8

N O

R T

H0 2 4 8

1 PROVIDE CRITICAL POWER FEEDER CIRCUIT

TO PANEL 'A'.

2 PROVIDE NORMAL POWER FEEDER CIRCUIT

TO PANEL 'B'.

3 PROVIDE POWER TO THE NEW RECEPTACLE

FROM EXISTING CONVENIENCE OUTLET

CIRCUIT IN THE CORRIDOR.

4 PROVIDE 120V POWER FOR DOOR SECURITY

HARDWARE. SEE DETAIL 5/ET503.

5 MOUNT OUTLETS ABOVE DATA RACK ON

CABLE TRAY. SEE DETAIL 6/ET502 FOR MORE

INFORMATION.

6 PROVIDE POWER CONNECTION AND MOTOR

RATED SWITCH FOR SPLIT UNIT.

7 8"X8"X4" HINGED CONTROLLER BOX,

MOUNTED ABOVE DOOR. SEE DETAIL 5/ET503.

8 PROVIDE 4 FIRE/SMOKE SLEEVE

ASSEMBLIES. REFERENCE DETAIL 2/ET501

FOR MORE INFORMATION.

9 MOUNT LIGHTS TO ANGLED CEILING.

1 DISCONNECT MECHANICAL EQUIPMENT.

REMOVE WIRING AND CONDUIT BACK TO

LAST OPERABLE DEVICE OR PANELBOARD.

2 DISCONNECT AND REMOVE RECEPTACLE.

REMOVE WIRING AND CONDUIT BACK TO

LAST OPERABLE DEVICE OR PANELBOARD.

3 DISCONNECT ALL UNUSED CABLING FROM

EXISTING EQUIPMENT RACK.

4 DISCONNECT AND REMOVE CAMERA. RETAIN

CONDUIT AND CABLING FOR NEW WORK.

5 DISCONNECT AND REMOVE LIGHT SWITCH.

REMOVE WIRING AND CONDUIT BACK TO

LAST OPERABLE DEVICE OR PANELBOARD.

6 DISCONNECT AND REMOVE LIGHTING

FIXTURE. REMOVE WIRING AND CONDUIT

BACK TO LAST OPERABLE DEVICE OR

PANELBOARD.

7 REMOVE AND PATCH EXISTING SKYLIGHT

WINDOWS.

A. ALL EXISTING CONDITIONS, CONDUITS AND

DEVICES ARE BASED ON THE BEST

AVAILABLE INFORMATION AT THE TIME OF

SURVEY AND VISUAL INSPECTION. VERIFY

EXISTING CONDITIONS.

B. DEVICES SHOWN WITH LIGHT, GRAY LINES

ARE EXISTING TO REMAIN. DEVICES SHOWN

WITH DARK, DASHED LINES ARE EXISTING TO

BE DEMOLISHED. DEMOLITION SHALL

INCLUDE, BUT NOT BE…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .