This document appears to be structural drawings for a construction project to upgrade the Electronic Health Record Modernization (EHRM) infrastructure at the VA Ann Arbor Healthcare System. The drawings provide design details for the low roof framing, platform framing, and associated structural components including beams, columns, and connections. Key details include the design criteria, material specifications, and submittal requirements. The drawings are part of the construction bid documents for the VA's solicitation #36c77624b0025 for the EHRM Infrastructure Upgrades project at the Ann Arbor, MI facility. The solicitation is being issued by the VA Technology Acquisition Center.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AFF ABOVE FINISHED FLOOR
ACP/APC ACOUSTIC CEILING PANEL/
ACOUSTIC PANEL CEILING
ACT ACOUSTIC(AL) TILE
ADJ ADJUSTABLE
ADT'L ADDITIONAL
AGG AGGREGATE
ALT ALTERNATE
AL ALUMINUM
APPROX APPROXIMATE(LY)
ASPH ASPHALT
AUTO AUTOMATIC
B/O BOTTOM OF
BD BOARD
BLDG BUILDING
BLKG BLOCKING
BOT BOTTOM
BRG BEARING
CENTERLINE
C/C CENTER TO CENTER
CJ CONTROL JOINT
CLL CONTRACT LIMIT LINE
CEM CEMENT(ITIOUS)
CMU CONCRETE MASONRY UNIT
CLG CEILING
CLR CLEAR
COL COLUMN
CONC CONCRETE
CONST CONSTRUCTION
CONT CONTINUOUS
CPT CARPET
CT CERAMIC TILE
CTR CENTER(ED)
DF DRINKING FOUNTAIN
DS DOWNSPOUT
DBL DOUBLE
DEG DEGREE
DEMO DEMOLITION
DET/DTL DETAIL
DIA DIAMETER
DIM DIMENSION
DN DOWN
DWG(S) DRAWING(S)
E EAST
EC ELECTRICAL CONTRACTOR
EHO ELECTRICAL HOLD OPEN
EJ EXPANSION JOINT
EW EACH WAY
EA EACH
EIFS EXTERIOR INSULATION
FINISH SYSTEM
EL ELEVATION
ELEC ELECTRIC(AL)
ELEV ELEVATOR
EMER EMERGENCY
EQ EQUAL
EQUIP EQUIPMENT
EXIST EXISTING
EXT EXTERIOR
EWC ELECTRIC WATER COOLER
FD FLOOR DRAIN
FE FIRE EXTINGUISHER
FFE FINISH FLOOR ELEVATION
FV FIELD VERIFY
FEC FIRE EXTINGUISHER CABINET
FDN FOUNDATION
FIN FINISH
FLSHG FLASHING
FLR FLOOR
FRMG FRAMING
FT FOOT/FEET
FTG FOOTING
GC GENERAL CONTRACTOR
GA GAUGE
GALV GALVANIZED
GEN GENERAL
GYP GYPSUM
HM HOLLOW METAL
HDWR HARDWARE
HOL HOLLOW
HOR HORIZONTAL
HT HEIGHT
HVAC HEATING/VENTILATION/AIR
CONDITIONING
ID INSIDE DIAMETER
IN INCH
INCL INCLUDING
INSUL INSULATION
INT INTERIOR
JAN JANITOR
JT JOINT
LAV LAVATORY
LB(S) POUND(S)
L/S LANDSCAPE
LT LIGHT
MO MASONRY OPENING
MAS MASONRY
MAT'L MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MTD MOUNTED
MTL METAL
N NORTH
NIC NOT IN CONTRACT
NTS NOT TO SCALE
NOM NOMINAL
OC ON CENTER
OD OUTSIDE DIAMETER
O TO O OUT TO OUT
OPNG OPENING
OPP OPPOSITE
OVHD OVERHEAD
PEB PRE-ENGINEERED BUILDING
PJF PREFORMED JOINT FILLER
PT PRESSURE TREATED
PERIM PERIMETER
PL PLATE
PLAM PLASTIC LAMINATE
PLBG PLUMBING
PLYWD PLYWOOD
PNT PAINT
PR PAIR
PTD PAINTED
PWR POWER
RB RUBBER BASE
RD ROOF DRAIN
RO ROUGH OPENING
RAD RADIUS
REC RECESSED
REINF REINFORCED
REQ'D REQUIRED
REV REVISED (REVISION)
RM ROOM
S SOUTH
SB SPLASH BLOCK
SF SQUARE FEET
SS STAINLESS STEEL
SIM SIMILAR
SPEC SPECIFICATIONS
SQ SQUARE
STD STANDARD
STL STEEL
STOR STORAGE
STRUCT STRUCTURAL
SUSP SUSPENDED
T&G TONGUE AND GROOVE
T/O TOP OF
TELE TELEPHONE
TRTD TREATED
TS TUBE STEEL
TYP TYPICAL
UNFIN UNFINISHED
UNO UNLESS NOTED OTHERWISE
VCT VINYL COMPOSITION TILE
VIF VERIFY IN FIELD
VERT VERTICAL
W WEST
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WWF WELDED WIRE FABRIC
WD WOOD
WH WATER HEATER
WT WEIGHT
CL
ROOF PITCH SYMBOLTYPICAL KEYNOTE
6#
DESIGN CRITERIA
1. BUILDING CODES
a. INTERNATIONAL BUILDING CODE 2021 EDITION
b. MINIMUM DESIGN LOADS FOR BUILDING AND OTHER STRUCTURES, ASCE 7-22
2. LIVE LOAD
ROOF 20 PSF
PLATFORM 60 PSF
3. SNOW LOAD
GROUND SNOW LOAD, Pg 20 PSF
4. WIND LOADS
ANALYSIS PROCEDURE DIRECTIONAL PROCEDURE
WIND SPEED, V (3 SECOND GUST) 115 MPH
RISK CATEGORY III
EXPOSURE B
5. SEISMIC LOADS
ANALYSIS PROCEDURE EQUIVALENT LATERAL FORCE
RISK CATEGORY III
SOIL SITE CLASS D, ASSUMED
MAPPED SPECTRAL RESPONSE ACCELERATION, Ss 0.104
MAPPED SPECTRAL RESPONSE ACCELERATION, S1 0.048
LONG-PERIOD TRANSITION PERIOD, Tl 12 SEC.
SEISMIC FORCE RESISTING SYSTEM BUILDING FRAME SYSTEM,
STEEL SYSTEMS NOT
SPECIFICALLY DETAILED FOR
SEISMIC RESISTANCE.
SEISMIC DESIGN CATEGORY B
GENERAL CONSTRUCTION SPECIFICATION
1. THIS STRUCTURE IS ONLY STABLE IN ITS COMPLETED FORM. THE CONTRACTOR SHALL
PROVIDE ALL REQUIRED TEMPORARY BRACING DURING CONSTRUCTION TO STABILIZE THE
STRUCTURE. TEMPORARY SHORING AND BRACING METHODS ARE NOT THE RESPONSIBILITY
OF APOGEE CONSULTING GROUP AND ARE BEYOND THE SCOPE OF THESE DRAWINGS.
2. THE SER IS NOT RESPONSIBLE FOR CONSTRUCTION SEQUENCES, METHODS, OR
TECHNIQUES IN CONNECTION WITH THE CONSTRUCTION OF THIS STRUCTURE. THE SER WILL
NOT BE HELD RESPONSIBLE FOR THE CONTRACTOR'S FAILURE TO CONFORM TO THE
CONSTRUCTION DOCUMENTS, SHOULD ANY NON-CONFORMITIES OCCUR.
3. ANY STRUCTURAL ELEMENTS OR DETAILS NOT FULLY DEVELOPED ON THE CONSTRUCTION
DRAWINGS SHALL BE COMPLETED UNDER THE DIRECTION OF A LICENSED PROFESSIONAL
ENGINEER. THESE SHOP DRAWINGS SHALL BE SUBMITTED TO APOGEE CONSULTING GROUP
FOR REVIEW BEFORE ANY CONSTRUCTION BEGINS.
4. STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH AND COORDINATED WITH
THE ARCHITECTURAL, MECHANICAL, PLUMBING, ELECTRICAL, AND CIVIL DRAWINGS. SHOULD
ANY DISCREPANCIES BECOME APPARENT THE CONTRACTOR SHALL NOTIFY APOGEE
CONSULTING GROUP BEFORE ANY CONSTRUCTION BEGINS.
5. THE STRUCTURAL ENGINEER OF RECORD IS NOT RESPONSIBLE FOR ANY SECONDARY
STRUCTURAL ELEMENTS OR NON-STRUCTURAL ELEMENTS, EXCEPT FOR THE ELEMENTS
SPECIFICALLY NOTED ON THE STRUCTURAL DRAWINGS.
MATERIAL SPECIFICATION
1. ALL STRUCTURAL STEEL TO BE PREFERRED MATERIAL SPECIFICATION IN ACCORDANCE WITH:
a. AISC 360-16, SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS
b. AISC 348-14, RCSC SPECIFICATION FOR STRUCTURAL JOINTS USING HIGH-STRENGTH BOLTS
c. AISC 303-16, CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES.
2. ALL WELDING TO BE PERFORMED BY CERTIFIED WELDERS AND IN ACCORDANCE WITH:
a. AWS D1.1:2015, STRUCTURAL WELDING CODE - STEEL
3. ALL GALVANIZED STEEL SHALL BE IN ACCORDANCE WITH:
a. ASTM A123/A123M-15, "STANDARD SPECIFICATION FOR ZINC (HOT-DIP GALVANIZED) COATINGS
ON IRON AND STEEL PRODUCTS."
b. ASTM A153/A153M-16a, "STANDARD SPECIFICATION FOR ZINC COATING (HOT-DIP) ON IRON
AND STEEL HARDWARE."
c. ASTM A780-09 (2015), "STANDARD PRACTICE FOR REPAIR OF DAMAGED AND UNCOATED
AREAS OF HOT-DIP GALVANIZED COATINGS."
d. ASTM D6386-16a, "STANDARD PRACTICE FOR PREPARATION OF ZINC (HOT-DIPPED
GALVANIZED) COATED IRON AND STEEL PRODUCTS AND HARDWARE SURFACES FOR
PAINTING."
SUBMITTALS
1. SHOP DRAWINGS AND SUBMITTALS SHALL BE SUBMITTED TO APOGEE CONSULTING GROUP,
P.A. FOR REVIEW BEFORE ANY CONSTRUCTION BEGINS. THESE SUBMITTALS WILL BE
REVIEWED FOR OVERALL COMPLIANCE AS IT RELATES TO THE STRUCTURAL DESIGN OF
THIS PROJECT. VERIFICATION OF THE SHOP DRAWINGS FOR DIMENSIONS, OR FOR ACTUAL
FIELD CONDITIONS IS NOT THE RESPONSIBILTY OF APOGEE CONSULTING GROUP, P.A.
2. HIGHLIGHT, ENCIRCLE, OR OTHERWISE SPECIFICALLY IDENTIFY DEVIATIONS FROM THE
CONTRACT DOCUMENTS ON SUBMITTALS.
3. REVIEW EACH SUBMITTAL AND CHECK FOR COORDINATION WITH OTHER TRADES AND FOR
COMPLIANCE WITH THE CONTRACT DOCUMENTS. NOTE CORRECTIONS AND FIELD
DIMENSIONS. MARK WITH APPROVAL STAMP BEFORE SUBMITTING TO APOGEE
CONSULTING GROUP, P.A. STAMP SHALL INCLUDE NAME OF REVIEWER, DATE OF
CONTRACTOR'S APPROVAL, AND STATEMENT CERTIFYING THAT SUBMITTAL HAS BEEN
REVIEWED, CHECKED, AND APPROVED FOR COMPLIANCE WITH THE CONTRACT
DOCUMENTS.
4. WHERE PROFESSIONAL DESIGN SERVICE OR CERTIFICATIONS BY A DESIGN PROFESSIONAL
ARE SPECIFICALLY REQUIRED OF THE CONTRACTOR BY THE CONTRACT DOCUMENTS,
PROVIDE PRODUCTS AND SYSTEMS COMPLYING WITH SPECIFIC PERFORMANCE AND
DESIGN CRITERIA INDICATED. IN ADDITION, SUBMIT COPIES OF A STATEMENT, SIGNED AND
SEALED BY THE RESPONSIBLE DESIGN PROFESSIONAL, FOR EACH PRODUCT AND SYSTEM
SPECIFICALLY ASSIGNED TO THE CONTRACTOR TO BE DESIGNED OR CERTIFIED BY A
DESIGN PROFESSIONAL.
5. PROVIDE THE FOLLOWING SUBMITTALS FOR THIS PROJECT:
a. STRUCTURAL STEEL
1. SHOP DRAWINGS: SHOW FABRICATION OF STRUCTURAL STEEL COMPONENTS.
2. WELDING PROCEDURES AND WELDING CERTIFICATES WITH CONTINUITY LOGS
AS REQ'D.
3. ALL CONNECTIONS NOT FULLY DEVELOPED IN THESE DOCUMENTS SHALL BE
DESIGNATED AS A DELEGATED DESIGN IN ACCORDANCE WITH AISC 303-22, SECT
3.1.2(3).
a. NO RESTRICTIONS ON TYPE OF CONNECTION.
b. LOADS ARE PROVIDED ON FRAMING PLANS. (USE 10k MINIMUM WHERE NO
LOAD IS SHOWN.)
c. ALL LOADS ARE SERVICE-LOAD LEVEL (UNFACTORED).
d. LRFD OR ASD MAY BE USED IN THE SELECTION AND DESIGN OF
CONNECTIONS.
e. PROVIDE CALCULATIONS FOR ALL CONNECTIONS NOT FULLY DEVELOPED
IN THESE DOCUMENTS, CERTIFIED BY A LICENSED PROFESSIONAL
ENGINEER WORKING FOR THE FABRICATOR.
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:5
:0
A
M C
U s e rs
\a c ru z \D o c u m e n ts
\S
-0
A n n
A rb o r-
E H
R M
B ld g -0 a c ru z T
Z J
.r v t
S-001
STRUCTURAL SYMBOLS,
ABBREVIATIONS AND NOTES
1 5AC
EHRM INFRASTRUCTURE
UPGRADES
VA ANN ARBOR HEALTHCARE SYSTEM
2215 FULLER ROAD, ANN ARBOR, MI
48105 FEBRUARY 28, 2024
BID DOCUMENTS
506-21-70521-092
BM
ABBREVIATIONS
STRUCTURAL SYMBOL LEGEND
DESIGN CRITERIA
GENERAL NOTES
MATERIAL SPECIFICATIONS
SUBMITTALS
DocuSign Envelope ID: F024BA2E-7BBC-4DFF-BDAC-B255F954C023
2/26/2024
B CB.75B.3
6.5
7.5
E X
IS
T
IN
G
W X
E X
IS
T
IN
G
W X
E X
IS
T
IN
G
W X
E X
IS
T
IN
G
W X
E X
IS
T
IN
G
W X
E X
IS
T
IN
G
W X
E X
IS
T
IN
G
W X
E X
IS
T
IN
G
W X
EXISTING
W21X50
EXISTING
W21X50
EXISTING
W21X50
EXISTING
W21X50
EXISTING
W21X50
EXISTING
W21X50
EXISTING
W21X50
EXISTING
W30X99
EXISTING
W30X99
EXISTING
W30X99
EXISTING
W30X99
EXISTING
W30X99
EXISTING
W30X99
EXISTING
W30X99
E X
IS
T
IN
G
W X
E X
IS
T
IN
G
W X
E X
IS
T
IN
G
W X
E X
IS
T
IN
G
W X
E X
IS
T
IN
G
W X
E X
IS
T
IN
G
W X
E X
IS
T
IN
G
W X
E X
IS
T
IN
G
W X
E X
IS
T
IN
G
W X
E X
IS
T
IN
G
W X
E X
IS
T
IN
G
W X
E X
IS
T
IN
G
W X
E X
IS
T
IN
G
W X
E X
IS
T
IN
G
W X
15'-7" 15'-6" 15'-7" 11'-7"
N
EW
H
SS
6X 6X
1/
PO
S T U
P
N
EW
H
SS
6X 6X
1/
PO
S T U
P
S-301
S-301
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:5
:0
A
M C
U s e rs
\a c ru z \D o c u m e n ts
\S
-0
A n n
A rb o r-
E H
R M
B ld g -0 a c ru z T
Z J
.r v t
S-101
LO ROOF FRAMING PLAN
2 5AC
EHRM INFRASTRUCTURE
UPGRADES
VA ANN ARBOR HEALTHCARE SYSTEM
2215 FULLER ROAD, ANN ARBOR, MI
48105 FEBRUARY 28, 2024
BID DOCUMENTS
506-21-70521-092
BM
N O R
TH
0 4 8 16
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
Scale: 1/4" = 1'-0"
LO ROOF FRAMING PLAN
A. T/BEAM ELEVATION (+831'-4).
N O R
TH
0 4 8 16
Scale: 1/4" = 1'-0"
LOW ROOF FRAMING PLAN
LOW ROOF FRAMING PLAN
B CB.75B.3
6.5
7.5
E X
IS
T
IN
G
W X
E X
IS
T
IN
G
W X
EXISTING
W24X55
EXISTING
W21X44
EXISTING
W24X76
EXISTING
W21X44
EXISTING
W24X76
EXISTING
W21X44
EXISTING
W24X76
EXISTING
W21X44
EXISTING
W24X76
EXISTING
W24X55
W21X68
W21X68
W X
W X
W10X12
W10X12
W10X33
W10X33
W10X12
W X
W X
W X
W10X12
W X
W10X12
W X
E X
IS
T
IN
G
W X
E X
IS
T
IN
G
W X
S-201
S-201
S-201
S-201
S-201
W10X12
5'-8 1/2"
VERIFY w/ MANUFACTURER
8'-10" 5'-8 1/2"
20'-3"
/2
V E
R
IF
Y w
M
A N
U F
A C
T U
R E
R
/2
KB
KB
F L U
ID
C
O O
L E
R ,0
M
A X
S-301
EXIS
TIN
G
H S S6X
6X 1/
EXIS
TIN
G
H S S6X
6X 1/
GRATING
SPAN DIRECTION
S-301
25k 25k k k
25k 25k k k
N
EW
H
SS
6X 6X
1/
N
EW
H
SS
6X 6X
1/
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:5
:0
A
M C
U s e rs
\a c ru z \D o c u m e n ts
\S
-0
A n n
A rb o r-
E H
R M
B ld g -0 a c ru z T
Z J
.r v t
S-102
PLATFORM FRAMING PLAN
3 5AC
EHRM INFRASTRUCTURE
UPGRADES
VA ANN ARBOR HEALTHCARE SYSTEM
2215 FULLER ROAD, ANN ARBOR, MI
48105 FEBRUARY 28, 2024
BID DOCUMENTS
506-21-70521-092
BM
N O R
TH
0 4 8 16
1 EXISTING 2-LINE GUARDRAIL
2 NEW GALVANIZED 2-LINE GUARDRAIL
3 NEW GALVANIZED BAR GRATING TO MATCH
EXISTING (19W4 w/ 1" x 3/16" BEARING BARS, MIN.)
4 REMOVE EXISTING GUARDRAIL IN DENOTED
AREA
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
Scale: 1/4" = 1'-0"
PLATFORM FRAMING PLAN
A. NEW T/BEAM ELEVATION TO MATCH
EXISTING PLATFORM (+837'-0).
B. KB DENOTES EXISTING KNEE BRACE TO BE
FIELD MODIFIED. SEE DETAIL 1/S301.
C. ALL NEW STEEL TO BE HOT-DIPPED
GALVANIZED AND FIELD PAINTED. DO NOT
QUENCH.
D. SEE MECHANICAL DWGS FOR NEW ROOF
MOUNTED, 70 TON FLUID COOLER UNIT &
DETAILS.
E. GC TO CONSULT WITH VA-ANN ARBOR ROOF
MAINTENANCE WARRANTY/SUPPLIER FOR
ROOF PENETRATION STANDARDS &
REQUIREMENTS PRIOR TO ANY ROOF WORK
BEING PERFORMED.
PLATFORM FRAMING
PLAN
837' - 0"
S-301
S-301
LO ROOF FRAMING PLAN
831' - 4"
PLATFORM FRAMING
PLAN
837' - 0"
4"
S-301
S-301
S-301
PLATFORM FRAMING
PLAN
837' - 0"
S-301
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:5
:0
A
M C
U s e rs
\a c ru z \D o c u m e n ts
\S
-0
A n n
A rb o r-
E H
R M
B ld g -0 a c ru z T
Z J
.r v t
S-201
SECTIONS
4 5AC
EHRM INFRASTRUCTURE
UPGRADES
VA ANN ARBOR HEALTHCARE SYSTEM
2215 FULLER ROAD, ANN ARBOR, MI
48105 FEBRUARY 28, 2024
BID DOCUMENTS
506-21-70521-092
BM
Scale: 3/4" = 1'-0"
Section 1
Scale: 3/4" = 1'-0"
Section 2
Scale: 3/4" = 1'-0"
Section 3
PLATFORM FRAMING
PLAN
837' - 0"
NEW GRATING
NEW BEAM
SEE PLAN
EXISTING HSS BRACE
TO REMAIN
EXISTING HSS BRACE
TO BE DEMO'D
1/4
BRACE TO
NEW BEAM
PLATFORM FRAMING
PLAN
837' - 0"
1/4
BRACE TO
BEAM
EXISTING BRACE
NOTE 1
EXISTING POST
NOTES:
1. CUT BACK EXISTING SCREEN WALL ANGLE BRACE
AS REQ'D FOR NEW BEAM INSTALLATION. WELD
EXISTING BRACE TO NEW BEAM.
PLATFORM FRAMING
PLAN
837' - 0"
NEW W21
SEE PLAN
NEW GRATING
SEE PLAN
NEW GUARDRAIL
SEE PLAN
NEW HSS
SEE PLAN
AISC FULL DEPTH CONNECTION
1/4" CAP ⅊
EXISTING HSS 10 x 6
NEW HSS 6 x 6
5/16
BASE ⅊ 3/4"
EXISTING BEAM
SEE PLAN
1/4
PLATFORM FRAMING
PLAN
837' - 0"
EXISTING BEAM
SEE PLAN
EXISTING GRATINGNEW GRATING
SEE PLAN
EXISTING GUARDRAIL
TO BE DEMO'D
NEW BEAM
SEE PLAN
AISC FULL DEPTH
CONNECTION
'-9
3/16
TYP
3/16
POST TO
BEAM
TOP RAIL
NOTE 1
⅊ 1/4 x 4
CONT.
NEW BEAM
SEE PLAN
SADDLE-STYLE CLIP
TOP OF GRATING
POST @ 4'-0 o.c. MAX
NOTE 1
MID RAIL
NOTE 1
NOTES:
1. TOP RAIL, MID RAIL, & POST TO BE GALVANIZED 1-1/2"ø STD. PIPE SCH. 40, U.N.O.
/4
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:5
:0
A
M C
U s e rs
\a c ru z \D o c u m e n ts
\S
-0
A n n
A rb o r-
E H
R M
B ld g -0 a c ru z T
Z J
.r v t
S-301
DETAILS
5 5AC
EHRM INFRASTRUCTURE
UPGRADES
VA ANN ARBOR HEALTHCARE SYSTEM
2215 FULLER ROAD, ANN ARBOR, MI
48105 FEBRUARY 28, 2024
BID DOCUMENTS
506-21-70521-092
BM
Scale: 1 1/2" = 1'-0"
DETAIL 1
Scale: 1 1/2" = 1'-0"
DETAIL 2
Scale: 1 1/2" = 1'-0"
DETAIL 3
Scale: 1 1/2" = 1'-0"
DETAIL 4
Scale: 1 1/2" = 1'-0"
DETAIL 5
Scale: 1 1/2" = 1'-0"
DETAIL 7
Scale: 1 1/2" = 1'-0"
DETAIL 6