This document appears to be a set of architectural drawings and specifications related to the renovation of a telecom room (TR A921A) and surrounding areas as part of an Electronic Health Record Modernization (EHRM) infrastructure upgrade project at the Ann Arbor VA Medical Center.

The key details include the scope of work, which involves demolition activities, new construction such as a new door and frame, sealing of penetrations, new flooring and wall base, installation of a card reader, fire-retardant plywood for telecommunications equipment, a new fire extinguisher cabinet, and new lighting and cable tray. The project is part of Solicitation Number 36c77624b0025, which was issued by the Department of Veterans Affairs Technology Acquisition Center Austin for the construction of EHRM infrastructure upgrades at the Ann Arbor facility. The bid documents are dated February 28, 2024.

View the file

Other files

File Type Posted
S07 - Complete Abstract of Bids OF 1419- Ann Arbor EHRM 10 16 2024.pdf PDF
S07 - Complete Abstract of Bids OF 1419- Ann Arbor EHRM.pdf PDF
IFB 36C77624B0025 Amendment 0005 Asbestos Info.pdf PDF
IFB 36C77624B0025 Amendment 0004.pdf PDF
36C77624B0025 Amendment 0003.pdf PDF
S05 Ann_Arbor CMS_Question_Matrix_V3.xlsx XLSX spreadsheet
Attachment 12 - EHRM Window Screen Details.pdf PDF
Attachment 08 - 075423 TPO Roofing.pdf PDF
Attachment 14 - MS Versions of PDFs.zip ZIP file
Attachment 07 - 013323 Shop Drawings_CA Edits 2.pdf PDF
Attachment 02 - 1E.ET472.pdf PDF
Attachment 06 - 000110 TOC - updated TPO and 236323.pdf PDF
Attachment 11 - CABLE MATRICES.pdf PDF
Attachment 04 - 21-092 SubReg 100 Percent.pdf PDF
Attachment 10 - Addendum 1.pdf PDF
Attachment 09 -236323 AirCooledClosedCircuitFluidCooler.pdf PDF
36C77624B0025 0002.docx DOCX document
Attachment 05 - 21-092-Pre-Bid RFIs_AE responses 1.pdf PDF
Attachment 15 - DB WR GD No MI20240100 09062024.pdf PDF
Attachment 01 - Q and A Results Ann Arbor MI.docx DOCX document
Attachment 13 - G-003_Addendum 1.pdf PDF
S04 - Pre-Bid Site Visit Sign-in Sheet - 09 04 2024.pdf PDF
S04 - Virtual Visit Attendee List - 08 29 2024.docx DOCX document
36C77624B0025 Ammendment 0001.docx DOCX document
S04 -Virtual and Site Visit Agenda - IFB 2024 08 29 2024.doc DOC document
S04 - Pre-Bid Site Visit Sign-in Sheet - 09 04 2024.docx DOCX document
Attachment 02_Drawings 07122024 Part 1.pdf PDF
Attachment 04_Drawings 07122024 Part 3.pdf PDF
Attachment 11 Division Breakdown Template.xls XLS spreadsheet
Attachment 06_Drawings 07122024 Part 5.pdf PDF
Attachment 05_Drawings 07122024 Part 4.pdf PDF
Attachment 08_Limitations on Subcontracting - Construction.docx DOCX document
Attachment 03_Drawings 07122024 Part 2.pdf PDF
Attachment 07_Drawings 07122024 Part 6.pdf PDF
Attachment 09_JA Ann Arbor Final REDACTED.pdf PDF
Attachment 10 DB Wages General Decision Number MI20240100 07 26 24.pdf PDF
Attachment 01_Specifications Ann Arbor MI.pdf PDF
36C77624B0025_1.pdf PDF
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CR

M

L

SERVICE

ELEVATOR

LOBBY

C9-4

EQUIPMENT

LIFT

OPEN

OFFICE

A931

OFFICE

A931B

PUBLIC

AFFAIRS

PHOTOS

A923

CORRIDOR

C-92

DATA

A921A

BREAKROOM

A927

M

L

116 SF

TR

A921A

161 SF

SERVICE

ELEVATOR

LOBBY

C9-4

103 SF

EQUIPMENT

LIFT

76 SF

PRINTER

A927

132 SF

PUBLIC

AFFAIRS

PHOTOS

A923

71 SF

OFFICE

A931B

390 SF

OPEN

OFFICE

A931

826 SF

CORRIDOR

C-92

109 8

9'-3" V.I.F.

A921A

'-8 " V .I.

F.

M

L

SERVICE

ELEVATOR

LOBBY

C9-4

EQUIPMENT

LIFT

OPEN

OFFICE

A931

OFFICE

A931B

PUBLIC

AFFAIRS

PHOTOS

A923

CORRIDOR

C-92

DATA

A921A

BREAKROOM

A927

M

L

116 SF

TR

A921A

161 SF

SERVICE

ELEVATOR

LOBBY

C9-4 103 SF

EQUIPMENT

LIFT

132 SF

PUBLIC

AFFAIRS

PHOTOS

A923

76 SF

PRINTER

A927

390 SF

OPEN

OFFICE

A931

71 SF

OFFICE

A931B

826 SF

CORRIDOR

C-92

OPEN

10'5"

A.

B.

C.

D.

E.

F.

G.

ALL EXISTING CONDITIONS ARE BASED ON

THE BEST AVAILABLE INFORMATION AT THE

TIME OF SURVEY AND VISUAL INSPECTION.

CONTRACTOR SHALL FIELD VERIFY ALL

EXISTING CONDITIONS.

ELEMENTS SHOWN WITH LIGHT, GRAY LINES

ARE EXISTING TO REMAIN. ELEMENTS

SHOWN WITH DARK, DASHED LINES ARE

EXISTING TO BE DEMOLISHED. DEMOLITION

SHALL INCLUDE, BUT NOT BE LIMITED TO,

THOSE ELEMENTS SHOWN.

ALL WORK SHALL BE COORDINATED

BETWEEN TRADES.

ALL WORK SHALL BE COORDINATED WITH

THE COR TO MINIMIZE DISRUPTION OF

AREAS OUTSIDE OF THE PROJECT LIMITS OF

WORK.

GENERAL CONTRACTOR TO ALSO REFER TO

MECHANICAL, AND ELECTRICAL/TECHNOLOGY

DRAWINGS FOR ADDITIONAL INFORMATION.

GC TO PROVIDE EQUIVALENT CFM TEMPORARY

COOLING, FOR THE DURATION OF TIME THAT THE

TR ROOM(S) ARE WITHOUT PERMANENT

HEATING/COOLING, UNTIL THE FULL TR STACK

HVAC SYSTEM IS OPERATIONAL, PRODUCING

THE REQUIRED CFM LOADS, AND SIGNED OFF BY

THE VA COR. SEE MECHANICAL DRAWINGS FOR

MORE INFORMATION.

ALL NEW FLOOR/CEILING HVAC CHILLED WATER

LINE PENETRATIONS SHALL BE FIRECAULKED TO

MAINTAIN A 2 HOUR FIRE RATING.

Engineers Architects

# KEY NOTES:

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREA

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

S S S S

1 HR - SMOKE SEPARATIONS S S S

9/ /2 5:

:3

PM

C :\U se rs \a pu lle n\ D oc um en ts \A _2 1- 2_ An n_ Ar bo r-E H R M _B ld g- 1W _a pu lle nV D

XT

7.

rv t

1W. A-491

BUILDING 1W, NINTH FLOOR, ALPHA

STACK, TELECOM ROOM A921A

37 62ANP

EHRM INFRASTRUCTURE

UPGRADES

VA ANN ARBOR HEALTHCARE SYSTEM

2215 FULLER ROAD, ANN ARBOR, MI

48105 FEBRUARY 28, 2024

BID DOCUMENTS

506-21-70521-092

JAB

1W

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

Scale: 1/4" = 1'-0"

DATA A921A & BREAKROOM

A927 EXISTING FLOOR PLAN

Scale: 1/4" = 1'-0"

TELECOM A921A NEW WORK FLOOR PLAN

Scale: 1/4" = 1'-0"

DATA A921A EXISTING

REFLECTED CEILING PLAN

Scale: 1/4" = 1'-0"

TELECOM A921A NEW WORK

REFLECTED CEILING PLAN

NO

RT

H

0 4 8 16

NO

RT

H

0 4 8 16

NO

RT

H

0 4 8 16

NO

RT

H

0 4 8 16

2 NEW DOOR & FRAME, SEE SCHEDULE

3 SEAL ALL PERIMETER AND PENETRATIONS

JOINTS.

4 NEW FLOORING AND RUBBER WALL BASE, SEE

SCHEDULE

5 PATCH ALL HOLES & LEVEL UNEVEN SUBFLOOR

6 NEW CARD READER, REF TO ELEC DRAWINGS

7 3/4" FIRE RETARDANT PLYWOOD APPLIED OVER

GYP BD FOR MOUNTING OF

TELECOMMUNICATIONS EQUIPMENT, 8” AFF TO

8’-8” AFF, PAINT W/ (3) COATS OF FIRE

RETARDANT PAINT

8 INSTALL NEW SEMI-RECESSED FIRE

EXTINGUISHER CABINET

9 NEW FIRE EXTINGUISHER SIGN, REF TO A-602

10 REUSE EXISTING ROOM SIGN

11 EXPOSED STRUCTURE

12 NEW LIGHT FIXTURE, TYPICAL. SEE ELECTRICAL

DRAWINGS.

13 CABLE TRAY, SEE ELECTRICAL DRAWINGS

14 HVAC EQUIPMENT, SEE MECHANICAL DRAWINGS.

DEMOLITION ACTIVITIES HAVE ALREADY TAKEN

PLACE UNDER A SEPARATE PROJECT.

DEMOLITION ACTIVITIES HAVE ALREADY TAKEN

PLACE UNDER A SEPARATE PROJECT.

1 Addendum 1 09/16/2024

PHOTO TAKEN BEFORE RENOVATION PHOTO TAKEN BEFORE RENOVATION

PHOTO TAKEN BEFORE RENOVATION PHOTO TAKEN BEFORE RENOVATION

PHOTO TAKEN BEFORE RENOVATION

PHOTO TAKEN BEFORE RENOVATION

Docusign Envelope ID: 3BDA30EA-46B3-42DB-9886-C4C84A541471

9/16/2024

2024-09-16T15:39:49-0700
Digitally verifiable PDF exported from www.docusign.com

File details come from the government source that posted it. Updated .