Attachment 04_Drawings 07122024 Part 3.pdf

PDF 20 MB Posted

Attached to
Z2DA--506-21-705 EHRM Infrastructure Upgrades - Ann Arbor, MI - Construction (VA-25-00001864)
Solicitation number
36c77624b0025
Issued by

About this file

This document appears to be Attachment 04_Drawings 07122024 Part 3.pdf, which contains engineering drawings related to the federal contract opportunity Z2DA--506-21-705 EHRM Infrastructure Upgrades - Ann Arbor, MI - Construction (VA-25-00001864). This construction solicitation is being issued by the Department of Veterans Affairs Technology Acquisition Center Austin for the Electronic Health Record Modernization (EHRM) infrastructure upgrades at the Ann Arbor VA Medical Center. The drawings provide technical details on the construction and infrastructure requirements for this project. No further details on the overall scope of work, response dates, pricing, or other key terms are provided in this particular attachment.

View the file

Other files

File Type Posted
S07 - Complete Abstract of Bids OF 1419- Ann Arbor EHRM 10 16 2024.pdf PDF
S07 - Complete Abstract of Bids OF 1419- Ann Arbor EHRM.pdf PDF
IFB 36C77624B0025 Amendment 0005 Asbestos Info.pdf PDF
IFB 36C77624B0025 Amendment 0004.pdf PDF
36C77624B0025 Amendment 0003.pdf PDF
S05 Ann_Arbor CMS_Question_Matrix_V3.xlsx XLSX spreadsheet
Attachment 12 - EHRM Window Screen Details.pdf PDF
Attachment 08 - 075423 TPO Roofing.pdf PDF
Attachment 14 - MS Versions of PDFs.zip ZIP file
Attachment 07 - 013323 Shop Drawings_CA Edits 2.pdf PDF
Attachment 02 - 1E.ET472.pdf PDF
Attachment 06 - 000110 TOC - updated TPO and 236323.pdf PDF
Attachment 11 - CABLE MATRICES.pdf PDF
Attachment 04 - 21-092 SubReg 100 Percent.pdf PDF
Attachment 10 - Addendum 1.pdf PDF
Attachment 09 -236323 AirCooledClosedCircuitFluidCooler.pdf PDF
36C77624B0025 0002.docx DOCX document
Attachment 05 - 21-092-Pre-Bid RFIs_AE responses 1.pdf PDF
Attachment 15 - DB WR GD No MI20240100 09062024.pdf PDF
Attachment 03 - 1W.A-491_Addendum 1.pdf PDF
Attachment 01 - Q and A Results Ann Arbor MI.docx DOCX document
Attachment 13 - G-003_Addendum 1.pdf PDF
S04 - Pre-Bid Site Visit Sign-in Sheet - 09 04 2024.pdf PDF
S04 - Virtual Visit Attendee List - 08 29 2024.docx DOCX document
36C77624B0025 Ammendment 0001.docx DOCX document
S04 -Virtual and Site Visit Agenda - IFB 2024 08 29 2024.doc DOC document
S04 - Pre-Bid Site Visit Sign-in Sheet - 09 04 2024.docx DOCX document
Attachment 02_Drawings 07122024 Part 1.pdf PDF
Attachment 11 Division Breakdown Template.xls XLS spreadsheet
Attachment 06_Drawings 07122024 Part 5.pdf PDF
Attachment 05_Drawings 07122024 Part 4.pdf PDF
Attachment 08_Limitations on Subcontracting - Construction.docx DOCX document
Attachment 03_Drawings 07122024 Part 2.pdf PDF
Attachment 07_Drawings 07122024 Part 6.pdf PDF
Attachment 09_JA Ann Arbor Final REDACTED.pdf PDF
Attachment 10 DB Wages General Decision Number MI20240100 07 26 24.pdf PDF
Attachment 01_Specifications Ann Arbor MI.pdf PDF
36C77624B0025_1.pdf PDF
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Engineers Architects

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

CAMPUS IMAGE

# 1E, 1W, 2, 3, 15, 22, 28, 29, 30, 31, 32, 37

U.S. DEPARTMENT OF VETERANS AFFAIRS

/2

/2

:5

:0

P

M C

U s e rs \a p u lle n \D o c u m e n ts \A

-0

A n n

A rb o r-

E H

R M

S it e

P la n a p u lle n V

D X

T .r v t

GA.001

COVER

1 1ANP

VA ANN ARBOR HEALTHCARE SYSTEM

2215 FULLER ROAD, ANN ARBOR, MI

48105 FEBRUARY 28, 2024

BID DOCUMENTS

506-21-70521-092

EHRM INFRASTRUCTURE UPGRADES

VA ANN ARBOR HEALTHCARE SYSTEM

2215 FULLER ROAD, ANN ARBOR, MI 48105

VA PROJECT #: 506-21-705

JAB

EHRM INFRASTRUCTURE

UPGRADES

NAME AND TITLE SIGNATURE

VA SIGNATURE BLOCK

VOLUME 2 OF 4

DRAWING LIST - VOLUME 2 OF 4

GENERAL

GA.001 COVER 1 1

ARCHITECTURAL

A-001 ARCHITECTURAL SYMBOLS, ABBREVIATIONS AND NOTES 1 62

A-002 UL DETAILS 2 62

A-003 UL DETAILS 3 62

A-004 HVAC HOUSEKEEPING PAD LOCATION PLAN 4 62

1E. A-401 BUILDING 1E, BASEMENT, TELEPHONE SWITCH ROOM CB07 5 62

1E. A-402 BUILDING 1E, BASEMENT, DELTA STACK, TELECOM ROOM DB60A 6 62

1E. A-403 BUILDING 1E, BASEMENT, ECHO STACK, TELECOM ROOM EB60A 7 62

1E. A-411 BUILDING 1E, FIRST FLOOR, DELTA STACK, TELECOM ROOM D178A 8 62

1E. A-412 BUILDING 1E, FIRST FLOOR, ECHO STACK, TELECOM ROOM E178A 9 62

1E. A-413 BUILDING 1E, FIRST FLOOR, TELECOM ROOM L133 10 62

1E. A-431 BUILDING 1E, THIRD FLOOR, DELTA STACK, TELECOM ROOM D312A 11 62

1E. A-432 BUILDING 1E, THIRD FLOOR, ECHO STACK, TELECOM ROOM E321A 12 62

1E. A-451 BUILDING 1E, FIFTH FLOOR, DELTA STACK, TELECOM ROOM D530A 13 62

1E. A-452 BUILDING 1E, FIFTH FLOOR, ECHO STACK, TELECOM ROOM E530A 14 62

1E. A-471 BUILDING 1E, SEVENTH FLOOR, DELTA STACK, TELECOM ROOM D712A 15 62

1E. A-472 BUILDING 1E, SEVENTH FLOOR, ECHO STACK, TELECOM ROOM E718A 16 62

1W. A-401 BUILDING 1W, BASEMENT, ELECTRICAL EQUIPMENT AB00 17 62

1W. A-402 BUILDING 1W, BASEMENT, ALPHA STACK, TELECOM ROOM AB29 18 62

1W. A-403 BUILDING 1W, BASEMENT, BRAVO STACK, TELECOM ROOM BB26 19 62

1W. A-404 BUILDING 1W, BASEMENT, TELECOM ROOM BB94 20 62

1W. A-411 BUILDING 1W, FIRST FLOOR, ALPHA STACK, TELECOM ROOM A149 21 62

1W. A-412 BUILDING 1W, FIRST FLOOR, BRAVO STACK, TELECOM ROOM B143 22 62

1W. A-421 BUILDING 1W, SECOND FLOOR, ALPHA STACK, TELECOM ROOM A237 23 62

1W. A-422 BUILDING 1W, SECOND FLOOR, BRAVO STACK, TELECOM ROOM B231 24 62

1W. A-431 BUILDING 1W, THIRD FLOOR, ALPHA STACK, TELECOM ROOM A339 25 62

1W. A-432 BUILDING 1W, THIRD FLOOR, BRAVO STACK, TELECOM ROOM B310B 26 62

1W. A-441 BUILDING 1W, FOURTH FLOOR, ALPHA STACK, TELECOM ROOM A437 27 62

1W. A-442 BUILDING 1W, FOURTH FLOOR, BRAVO STACK, TELECOM ROOM B432A 28 62

1W. A-451 BUILDING 1W, FIFTH FLOOR, ALPHA STACK, TELECOM ROOM A535 29 62

DRAWING LIST - VOLUME 2 OF 4

1W. A-452 BUILDING 1W, FIFTH FLOOR, BRAVO STACK, TELECOM ROOM B525 30 62

1W. A-461 BUILDING 1W, SIXTH FLOOR, ALPHA STACK, TELECOM ROOM A633A 31 62

1W. A-462 BUILDING 1W, SIXTH FLOOR, BRAVO STACK, TELECOM ROOM B618A 32 62

1W. A-471 BUILDING 1W, SEVENTH FLOOR, ALPHA STACK, TELECOM ROOM A753 33 62

1W. A-472 BUILDING 1W, SEVENTH FLOOR, BRAVO STACK, TELECOM ROOM B722A 34 62

1W. A-481 BUILDING 1W, EIGHTH FLOOR, ALPHA STACK, TELECOM ROOM A843A 35 62

1W. A-482 BUILDING 1W, EIGHTH FLOOR, BRAVO STACK, TELECOM ROOM B812 36 62

1W. A-491 BUILDING 1W, NINTH FLOOR, ALPHA STACK, TELECOM ROOM A921A 37 62

28. A-401 BUILDING 28, BASEMENT, FOXTROT STACK, TELECOM ROOM FG86 38 62

28. A-411 BUILDING 28, FIRST FLOOR, MAIN COMPUTER ROOM A180 39 62

28. A-412 BUILDING 28, FIRST FLOOR, FOXTROT STACK, TELECOM ROOM F152 40 62

28. A-421 BUILDING 28, SECOND FLOOR, FOXTROT STACK, TELECOM ROOM F224A 41 62

2. A-421 BUILDING 2, FULLER HOUSE, SECOND FLOOR, TELECOM ROOM 210 42 62

3. A-401 BUILDING 3, FACILITY MANAGEMENT & SAFETY, BASEMENT, TELECOM ROOM 02C 43 62

15. A-401 BUILDING 15, NORTH METER HOUSE, FIRST FLOOR, TELECOM ROOM 15-2 44 62

22. A-401 BUILDING 22, RESEARCH BUILDING, GROUND FLOOR, TELECOM ROOM G12 45 62

22. A-411 BUILDING 22, RESEARCH BUILDING, FIRST FLOOR, TELECOM ROOM 08 46 62

29. A-411 BUILDING 29, EAST PARKING STRUCTURE, LEVEL A, TELECOM ROOM AA6 47 62

29. A-421 BUILDING 29, EAST PARKING STRUCTURE, LEVEL B, TELECOM ROOM EPS-B2 48 62

30. A-421 BUILDING 30, WEST PARKING STRUCTURE, LEVEL B, TELECOM ROOM WPS-B02 49 62

30. A-441 BUILDING 30, WEST PARKING STRUCTURE, LEVEL D, TELECOM ROOM WPS-D02 50 62

31. A-401 BUILDING 31, RESEARCH BUILDING, BASEMENT, TELECOM ROOM 27 51 62

31. A-411 BUILDING 31, RESEARCH BUILDING, FIRST FLOOR, TELECOM ROOM 117 52 62

31. A-421 BUILDING 31, RESEARCH BUILDING, SECOND FLOOR, TELECOM ROOM 218 53 62

32. A-401 BUILDING 32, ENERGY CENTER, BASEMENT, TELECOM ROOM 003 54 62

32. A-431 BUILDING 32, ENERGY CENTER, ROOF PLAN AND PLATFORM 55 62

37. A-401 BUILDING 37, ADMINISTRATIVE BUILDING, BASEMENT, TELECOM ROOM 006 56 62

37. A-411 BUILDING 37, ADMINISTRATIVE BUILDING, FIRST FLOOR, TELECOM ROOM 118 57 62

37. A-421 BUILDING 37, ADMINISTRATIVE BUILDING, SECOND FLOOR, TELECOM ROOM 217 58 62

37. A-431 BUILDING 37, ADMINISTRATIVE BUILDING, THIRD FLOOR, TELECOM ROOM 317 59 62

A-501 PARTITION TYPES AND DETAILS 60 62

A-601 DOOR SCHEDULE, ELEVATIONS AND DETAILS 61 62

A-602 GENERAL NOTES, ABBREVIATIONS AND ROOM FINISH SCHEDULE 62 62

DocuSign Envelope ID: F024BA2E-7BBC-4DFF-BDAC-B255F954C023

2/26/2024

1. INDICATIONS OF PROJECT LIMITS OR LINES OF DEMARCATION ARE SHOWN FOR GENERAL SCOPE DEFINITION AND REFLECT THE UNDERSTANDING OF THE DESIGNER AS TO THE LIMITATIONS OF THE WORK AREA IN AN OCCUPIED AREA. ACTUAL CONTRACT LIMITS ARE TO BE DETERMINED BY AGREEMENT BETWEEN THE COR AND

CONTRACTOR BEFORE THE START OF THE WORK.

2. DRAWINGS ARE PREPARED USING PRODUCT DIMENSIONS AND DETAILS FROM BASIS OF DESIGN PRODUCT.

PRODUCTS MAY CHANGE IN DIMENSION AND DETAIL BEFORE THEY ARE INCORPORATED INTO

WORK. PRODUCTS FROM OTHER MANUFACTURER’S ARE ALSO ACCEPTABLE. DIMENSIONS AND DETAILS FOR ALTERNATE PRODUCTS MAY VARY FROM BASIS OF DESIGN. CONTRACTOR SHALL VERIFY INSTALLATION REQUIREMENTS FOR ALL PRODUCTS TO BE INCORPORATED INTO WORK (INCLUDING THICKNESS FOR RECESSED OR SEMI-RECESSED PRODUCTS) AND IS RESPONSIBLE FOR ACCOMMODATING AND COORDINATING CHANGES TO OTHER MATERIALS OR PRODUCTS THAT ARE NECESSARY BECAUSE OF THESE DIFFERENCES.

3. THE DRAWINGS AND SPECIFICATIONS ARE SEPARATED INTO DISCIPLINES FOR CONVENIENCE. THE SEPARATIONS ARE USED ONLY FOR THE PURPOSES OF CONVENIENCE AND REFERENCE AND IN NO WAY DO THEY DEFINE OR LIMIT THE SCOPE OR INTENT OF ANY PART OF THE DRAWINGS AND SPECIFICATIONS AS A WHOLE. THE FACT THAT THE DRAWINGS ARE SEPARATED IN NO WAY SUGGESTS THAT THE WORK IS NOT TO

BE CONSTRUCTED AS A COMPLETE, INTEGRATED AND UNIFIED WHOLE.

4. THE DRAWINGS AND SPECIFICATIONS, INCLUDING DRAWINGS PREPARED BY SPECIFIC ENGINEERING DISCIPLINES ARE COMPLEMENTARY; ITEMS SHOWN IN ANY ONE LOCATION IN THE DRAWINGS SHALL BE CONSIDERED TO BE REQUIREMENTS OF THE CONTRACT FOR CONSTRUCTION. IN THE EVENT OF AN INCONSISTENCY BETWEEN THE DRAWINGS AND SPECIFICATIONS, OR WITHIN EITHER DOCUMENT, THE CONTRACTOR SHALL SEEK CLARIFICATION OR INTERPRETATION FROM THE COR PRIOR TO BIDDING. WHERE INCONSISTENCIES ARE NOT CLARIFIED PRIOR TO BIDDING, AND WHERE THE ACTUAL SOLUTION OR INTENT CANNOT BE REASONABLY INFERRED, THE CONTRACTOR SHALL PROVIDE THE BETTER QUALITY OR GREATER

QUANTITY OF WORK.

5. THE CONTRACTOR SHALL NOTIFY THE COR IMMEDIATELY SHOULD DISCREPANCIES BE FOUND IN THE

DRAWINGS AND SPECIFICATIONS.

6. THE CONTRACTOR IS RESPONSIBLE FOR CHECKING ALL FIELD CONDITIONS AND DIMENSIONS AS THEY RELATE TO THIS PROJECT, FOR EACH PHASE. SHOULD DISCREPANCIES EXIST BETWEEN THE WORK INDICATED AND

ACTUAL FIELD CONDITIONS, NOTIFY THE COR PRIOR TO PROCEEDING WITH THE WORK.

7. DO NOT SCALE THE DRAWINGS. DRAWING SCALES AS INDICATED ARE FOR REFERENCE ONLY AND ARE NOT INTENDED TO ACCURATELY DEPICT ACTUAL OR DESIGNATED CONDITIONS. WRITTEN DIMENSIONS SHALL

GOVERN.

8. PROVIDE SEALANT AT ALL INTERSECTIONS BETWEEN DIFFERENT MATERIALS.

9. COORDINATE WORK OF ALL TRADES PRIOR TO STARTING CONSTRUCTION.

10. REFER TO ALL OTHER TRADE DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION ON THIS

PROJECT.

11. PROVIDE BLOCKING AT PARTITIONS AS REQUIRED FOR MOUNTING OF WALL-MOUNTED ITEMS: PROVIDE SUPPLEMENTAL FRAMING AT WALL OPENINGS INCLUDING KING STUDS, JACK STUDS, AND CRIPPLE STUDS, AS

REQUIRED FOR COMPLETION OF THE WORK.

12. DIMENSIONS SHOWN ARE TO FACE OF STUD FRAMING, FACE OF CONCRETE/MASONRY WALLS, OR FINISHED

FACE OF EXISTING WALL SURFACE.

13. ALL WOOD IN CONTACT WITH CONCRETE SHALL BE PRESSURE TREATED.

14. THE CONTRACTOR IS REQUIRED TO FILE A SUBMITTAL PRIOR TO THE START OF CONSTRUCTION THAT LISTS ALL OF THE MAJOR EQUIPMENT I.E. MECHANICAL, ELECTRICAL PLUMBING, ETC. WHICH WILL BE INSTALLED

DURING THIS PROJECT.

15. CONTRACTOR TO UTILIZE SUBMITTAL EXCHANGE OR AN EQUIVALENT PROGRAM FOR THE DISTRIBUTION OF

SUBMITTALS AND RFIS.

16. IN HIGH SECURITY AREAS, NO OUTSIDE SECURITY COMPANY SHALL BE APPROVED BY THE VA. ALL SECURITY

OVERSIGHT SHALL BE PERFORMED BY ONSITE VA PERSONNEL.

1. KEY NOTES AND DRAWINGS ARE INTENDED TO GRAPHICALLY REPRESENT GENERAL WORK AND DO NOT

PORTRAY FULL SCOPE OF THE PROJECT. SEE SPECIFICATIONS FOR DETAILED REQUIREMENTS.

2. REMOVE EXISTING CONSTRUCTION AS DESIGNATED HEREIN AND CLEAR AREA OF DEBRIS PRIOR TO

PROCEEDING WITH NEW CONSTRUCTION.

3. EXISTING EQUIPMENT REMOVED SHALL BE PROPERLY DISPOSED OF, OFF PROJECT GROUNDS. COORDINATE

WITH COR.

4. AT AREAS INDICATED TO BE PATCHED AND REPAIRED, FOR ADDITION AND RENOVATION PROJECTS: THE CONSTRUCTION AND ASSEMBLY OF THE PATCH OR REPAIR SHALL MATCH THE ASSEMBLY AND INTEGRITY OF THE ADJACENT EXISTING CONSTRUCTION, FOR FIRE RATING, MATERIALS, FINISH, THICKNESS, AND QUALITY.

5. COORDINATE WORKING HOURS ALLOWED FOR DEMOLITION AND WASTE REMOVAL WITH COR.

6. NOTIFY COR OF ANY DEMOLITION REQUIRED AND NOT INDICATED FOR INSTALLATION OF ELECTRICAL OR DATA ITEMS. AFTER SUCH DEMOLITION AND INSTALLATION, PATCH OR REPLACE MATERIALS AND FINISHES TO MATCH

EXISTING.

7. CONTRACTOR SHALL PROTECT AREA ADJACENT TO THE DEMOTION AND NEW CONSTRUCTION WORK TO PREVENT DAMAGES, (IF DAMAGED REPAIR, RE-PATCH, SAND SMOOTH AND REFINISH TO MATCH EXISTING.)

REPAIR OR REPLACE ITEMS DAMAGED DURING CONSTRUCTION ACTIVITIES AT NO ADDITIONAL COST.

8. THE INFORMATION CONTAINED IN THESE DEMOLITION DOCUMENTS DEFINES GENERAL SCOPE ONLY AND DOES NOT RELIEVE THE CONTRACTOR OF THE RESPONSIBILITY OF PROVIDING ALL DEMOLITION REQUIRED FOR THE

COMPLETION OF THE PROJECT.

9. DO NOT ENCROACH ON ADJACENT OCCUPIED AREAS NOT IDENTIFIED WITHIN THE SCOPE OF WORK.

10. REFER TO THE ELECTRICAL DRAWINGS FOR FURTHER INFORMATION REGARDING DEMOLITION OF ELECTRICAL

SYSTEMS.

11. BEFORE THE START OF WORK, IDENTIFY ANY REQUIRED DEMOLITION BEYOND THE IDENTIFIED PROJECT SCOPE WHETHER ABOVE, BELOW, OR OUTSIDE THE PROJECT AREA. NOTIFY AND COORDINATE WITH THE COR, PROVIDE DEMOLITION OF THESE AREAS AND PATCH THE SAME AS A PART OF THE SCOPE OF THE PROJECT.

12. ALL DEMOLITION WORK SHALL BE PERFORMED WITH DUE CARE AND DILIGENCE IN ORDER TO PREVENT ARBITRARY DAMAGE OR INTERRUPTION OF SERVICE OR CONCEALED UTILITIES INTENDED TO REMAIN IN SERVICE. DISCOVERY OF UTILITIES OR CONDITIONS LOCATED DIFFERING FROM THOSE INDICATED OR THAT

ARE NOT IDENTIFIED, SHALL BE REPORTED TO THE COR.

13. AFTER REMOVAL OF EXISTING SOLID CONCRETE MASONRY WALL, FILL FLOOR VOIDS UP TO FINISH CONCRETE

LEVEL AND PERFORM FLOOR LEVELING FOR ENTIRE AREA OF RENOVATION.

14. VERIFY ALL EXISTING CONDITIONS PRIOR TO BEGINNING WORK. NOTIFY COR AND ARCHITECT OF ANY

CONFLICTS PRIOR TO PROCEEDING WITH DEMOLITION.

15. ALL ITEMS BEING SALVAGED OR REMOVED SHALL REMAIN THE PROPERTY OF THE OWNER UNTIL CONFIRMATION HAS BEEN MADE AS TO WHETHER THE OWNER WILL RETAIN SUCH ITEMS. ALL ITEMS NOT BEING RETAINED BY THE OWNER OR DESIGNATED ON THE DRAWINGS, ARE TO BE RELOCATED OR

REINSTALLED FROM THE SITE BY CONTRACTOR IN APPROVED MANNER.

16. CONTRACTOR SHALL NOTIFY COR OF ANY AREA REQUIRING DEMOLITION OTHER THAN SHOWN IN THESE DRAWINGS DUE TO UNFORESEEN CONDITIONS, TO ACCOMMODATE INSTALLATION OF ALL OTHER TRADES (INCLUDING ROOF PENETRATIONS). AFTER SUCH DEMOLITION AND INSTALLATION, PATCH OR REPLACE

MATERIALS AND FINISHES TO MATCH EXISTING.

17. COORDINATE WITH COR FOR CONSTRUCTION ACCESS ROUTE AND LOCATIONS OF DUMPSTER AREA.

COORDINATE WITH COR FOR SCHEDULE OF USE OF ACCESS ROUTE FOR WASTE REMOVAL AND CONTRACTOR

USE OF FREIGHT ELEVATOR (AS REQUIRED).

18. CONTRACTOR IS REQUIRED TO MAINTAIN ALL RECYCLING DUMP TICKETS AND HAVE AVAILABLE TO VA

VERIFICATION.

AFF ABOVE FINISHED FLOOR

ACP/APC ACOUSTIC CEILING PANEL/

ACOUSTIC PANEL CEILING

ACT ACOUSTIC(AL) TILE

ADJ ADJUSTABLE

ADT'L ADDITIONAL

AGG AGGREGATE

ALT ALTERNATE

AL ALUMINUM

APPROX APPROXIMATE(LY)

ASPH ASPHALT

AUTO AUTOMATIC

B/O BOTTOM OF

BD BOARD

BLDG BUILDING

BLKG BLOCKING

BOT BOTTOM

BRG BEARING

CENTERLINE

C/C CENTER TO CENTER

CJ CONTROL JOINT

CLL CONTRACT LIMIT LINE

CEM CEMENT(ITIOUS)

CMU CONCRETE MASONRY UNIT

CLG CEILING

CLR CLEAR

COL COLUMN

CONC CONCRETE

CONST CONSTRUCTION

CONT CONTINUOUS

CPT CARPET

CT CERAMIC TILE

CTR CENTER(ED)

DF DRINKING FOUNTAIN

DS DOWNSPOUT

DBL DOUBLE

DEG DEGREE

DEMO DEMOLITION

DET/DTL DETAIL

DIA DIAMETER

DIM DIMENSION

DN DOWN

DWG(S) DRAWING(S)

E EAST

EC ELECTRICAL CONTRACTOR

EHO ELECTRICAL HOLD OPEN

EJ EXPANSION JOINT

EW EACH WAY

EA EACH

EIFS EXTERIOR INSULATION

FINISH SYSTEM

EL ELEVATION

ELEC ELECTRIC(AL)

ELEV ELEVATOR

EMER EMERGENCY

EQ EQUAL

EQUIP EQUIPMENT

EXIST EXISTING

EXT EXTERIOR

EWC ELECTRIC WATER COOLER

FD FLOOR DRAIN

FE FIRE EXTINGUISHER

FFE FINISH FLOOR ELEVATION

FV FIELD VERIFY

FEC FIRE EXTINGUISHER CABINET

FDN FOUNDATION

FIN FINISH

FLSHG FLASHING

FLR FLOOR

FRMG FRAMING

FT FOOT/FEET

FTG FOOTING

GC GENERAL CONTRACTOR

GA GAUGE

GALV GALVANIZED

GEN GENERAL

GYP GYPSUM

HM HOLLOW METAL

HDWR HARDWARE

HOL HOLLOW

HOR HORIZONTAL

HT HEIGHT

HVAC HEATING/VENTILATION/AIR

CONDITIONING

ID INSIDE DIAMETER

IN INCH

INCL INCLUDING

INSUL INSULATION

INT INTERIOR

JAN JANITOR

JT JOINT

LAV LAVATORY

LB(S) POUND(S)

L/S LANDSCAPE

LT LIGHT

MO MASONRY OPENING

MAS MASONRY

MAT'L MATERIAL

MAX MAXIMUM

MECH MECHANICAL

MFR MANUFACTURER

MIN MINIMUM

MISC MISCELLANEOUS

MTD MOUNTED

MTL METAL

N NORTH

NIC NOT IN CONTRACT

NTS NOT TO SCALE

NOM NOMINAL

OC ON CENTER

OD OUTSIDE DIAMETER

O TO O OUT TO OUT

OPNG OPENING

OPP OPPOSITE

OVHD OVERHEAD

PEB PRE-ENGINEERED BUILDING

PJF PREFORMED JOINT FILLER

PT PRESSURE TREATED

PERIM PERIMETER

PL PLATE

PLAM PLASTIC LAMINATE

PLBG PLUMBING

PLYWD PLYWOOD

PNT PAINT

PR PAIR

PTD PAINTED

PWR POWER

RB RUBBER BASE

RD ROOF DRAIN

RO ROUGH OPENING

RAD RADIUS

REC RECESSED

REINF REINFORCED

REQ'D REQUIRED

REV REVISED (REVISION)

RM ROOM

S SOUTH

SB SPLASH BLOCK

SF SQUARE FEET

SS STAINLESS STEEL

SIM SIMILAR

SPEC SPECIFICATIONS

SQ SQUARE

STD STANDARD

STL STEEL

STOR STORAGE

STRUCT STRUCTURAL

SUSP SUSPENDED

T&G TONGUE AND GROOVE

T/O TOP OF

TELE TELEPHONE

TRTD TREATED

TS TUBE STEEL

TYP TYPICAL

UNFIN UNFINISHED

UNO UNLESS NOTED OTHERWISE

VCT VINYL COMPOSITION TILE

VIF VERIFY IN FIELD

VERT VERTICAL

W WEST

W/ WITH

W/O WITHOUT

WC WATER CLOSET

WWF WELDED WIRE FABRIC

WD WOOD

WH WATER HEATER

WT WEIGHT

CL

DEMOLITION KEYNOTE

WINDOW TYPE

TOILET ACCESSORY

ROOF PITCH SYMBOL

DOOR NUMBER

TYPICAL KEYNOTE CEILING/ SOFFIT

HEIGHT

MATL

1'-0"

1 #

WALL SECTION

SYMBOL

INTERIOR ELEVATION

SYMBOL

COLUMN GRID

ELEVATION SYMBOL

REVISION NOTE

ENLARGED DETAIL CALLOUT

ROOM DESIGNATION

SYMBOL

BREAK LINE

ROOF SLOPE

DIRECTION SYMBOL

TYPICAL GRAPHIC SCALE

DETAIL #

PAGE #

DETAIL #

PAGE #

VIEW NORTH ARROW

A8.1

EXTERIOR ELEVATION

SYMBOL

DETAIL #

PAGE #

A8.1

A8.1

A8.1

BUILDING SECTION

SYMBOL

DETAIL #

PAGE #

A8.1

A8.1

DETAIL SECTION

SYMBOL

DETAIL #

PAGE #

A8.1

WALL GRID

(REPRESENTS

FACE OF EXISTING

WALL)

XX.X

XX.X

ELEVATION

0'-0"

ROOM

NAME

101A

NORTHNORTH

0 4 8 16

1. THIRD PARTY INSPECTION AGENCY

2. CONFORMANCE TO INDICATED PRODUCT STANDARD

3. EXPOSURE DURABILITY CLASSIFICATION

4. THICKNESS

5. SPAN RATING

6. DENOTES PANELS THAT HAVE BEEN SIZED TO ALLOW FOR SPACING OF

PANEL EDGES DURING INSTALLATION TO REDUCE TO POSSIBILITY OF

BUCKLING

7. RECOGNITION AS QUALITY ASSURANCE AGENCY

8. PERFORMANCE RATED PANEL STANDARD INDICATION STRUCTURAL-USE

PANEL TEST PROCEDURES

9. MANUFACTURING MILL IDENTIFICATION NUMBER

10. GRADE OF FACE AND CORE VENEERS

11. STRENGTH AXIS (OSB ONLY)

EXAMPLE OF CERTIFICATION STAMP

ONE OF THE PLYWOOD FR PRESSURE TREATMENT

MANUFACTURER'S CERTIFICATION STAMP ON THE FACE OF

EACH SHEET OF PLYWOOD SHALL REMAIN OPEN FOR

INSPECTION AND SHALL NOT BE PAINTED WITH THE FIRE

RETARDANT PAINT. THE "PICTURE FRAMING" OF THE STAMP

BY THE PAINT COATING SHALL BE DONE NEATLY WITH

STRAIGHT LINES AND SQUARE CORNERS AND SHALL BE THE

SAME SIZE ON ALL SHEET.

Engineers Architects

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

# 1E, 1W, 2, 3, 15, 22, 28, 29, 30, 31, 32, 37

/2

/2

:3

:3

P

M C

U s e rs \a p u lle n \D o c u m e n ts \A

-0

A n n

A rb o r-

E H

R M

S it e

P la n a p u lle n V

D X

T .r v t

A-001

ARCHITECTURAL SYMBOLS,

ABBREVIATIONS AND NOTES

1 62ANP

VA ANN ARBOR HEALTHCARE SYSTEM

2215 FULLER ROAD, ANN ARBOR, MI

48105 FEBRUARY 28, 2024

BID DOCUMENTS

506-21-70521-092

JAB

EHRM INFRASTRUCTURE

UPGRADES

GENERAL NOTES

DEMOLITION NOTES

ABBREVIATIONS

ARCHITECTURAL SYMBOL LEGEND

GENERAL SYMBOL LEGENDFIRE RETARDANT CERTIFICATION STAMP

UTILITY SHUT OFF

ANY UTILITY SHUTDOWN REQUIRES 3 WEEK ADVANCE NOTICE.

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

# 1E, 1W, 2, 3, 15, 22, 28, 29, 30, 31, 32, 37

/2

/2

:3

:4

P

M C

U s e rs \a p u lle n \D o c u m e n ts \A

-0

A n n

A rb o r-

E H

R M

S it e

P la n a p u lle n V

D X

T .r v t

A-002

UL DETAILS

2 62ANP

VA ANN ARBOR HEALTHCARE SYSTEM

2215 FULLER ROAD, ANN ARBOR, MI

48105 FEBRUARY 28, 2024

BID DOCUMENTS

506-21-70521-092

JAB

EHRM INFRASTRUCTURE

UPGRADES

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

# 1E, 1W, 2, 3, 15, 22, 28, 29, 30, 31, 32, 37

/6

/2

:2

:3

P M

C U s e rs \a p u lle n \D o c u m e n ts \A

-0

A n n

A rb o r-

E H

R M

S it e

P la n a p u lle n V

D X

T .r v t

A-003

UL DETAILS

3 62ANP

VA ANN ARBOR HEALTHCARE SYSTEM

2215 FULLER ROAD, ANN ARBOR, MI

48105 FEBRUARY 28, 2024

BID DOCUMENTS

506-21-70521-092

JAB

EHRM INFRASTRUCTURE

UPGRADES

THIS DETAIL REFERS TO A 2 HR T RATING TO BE INCORPORATED FOR FLOOR PENETRATIONS

IN THE DELTA AND ECHO STACKS IN BUILDING 1E.

DocuSign Envelope ID: 68E04A76-2CE8-40A7-8DB8-165FE1E5CCB8

3/8/2024

1W

1E

T9

FULLER COURT

FULLER COURT

FULLER COURT

FULLER R

OAD

FULLER R

OAD

V A

M E

D

IC

A L C

IR

C

L E

1W LIBERTY BUILDING - ORIGINAL HOSPITAL BUILDING

1E FREEDOM BUILDING - CLINICAL ADDITION

2 FULLER HOUSE

3 FACILITY MANAGEMENT & SAFETY

7 GROUNDS GARAGE (NO WORK)

T9 ADMINISTRATIVE BUILDING (NO WORK)

15 NORTH METER HOUSE

22 RESEARCH BUILDING

28 INDEPENDENCE BUILDING

31 RESEARCH BUILDING

32 ENERGY CENTER

35 SOUTH METER HOUSE (NO WORK)

37 ADMINISTRATIVE BUILDING

29 EAST PARKING

STRUCTURE (PATIENT, VISITOR, & STAFF)

30 WEST PARKING STRUCTURE (STAFF ONLY)

BUILDINGS

PARKING

BUILDING KEY

BUILDINGS THAT ARE

SHADED INDICATE

AREAS OF WORK

LEGEND

A-004

CHILLER

ROOM

PLUMBING

SHOP

OFFICE

112A

HVAC SHOP

FENCED AREA

Engineers Architects

# KEY NOTES:

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

# 1E, 1W, 2, 3, 15, 22, 28, 29, 30, 31, 32, 37

/2

/2

:3

:4

P

M C

U s e rs \a p u lle n \D o c u m e n ts \A

-0

A n n

A rb o r-

E H

R M

S it e

P la n a p u lle n V

D X

T .r v t

A-004

HVAC HOUSEKEEPING PAD LOCATION

PLAN

4 62Author

VA ANN ARBOR HEALTHCARE SYSTEM

2215 FULLER ROAD, ANN ARBOR, MI

48105 FEBRUARY 28, 2024

BID DOCUMENTS

506-21-70521-092

Checker

EHRM INFRASTRUCTURE

UPGRADES

A. GENERAL CONTRACTOR IS RESPONSIBLE FOR THE

LABOR, MATERIALS, AND SITE MODIFICATIONS OF

ALL ROOF MOUNTED & GROUND MOUNTED

CONCRETE HOUSEKEEPING PADS FOR THE TR MINI-

SPLIT CONDENSING UNITS FOR THE ENTIRE

PROJECT. BEFORE INSTALLATION OCCURS, THE

GENERAL CONTRACTOR SHALL COORDINATE, WITH

ALL OTHER SUB-CONTRACTORS TO DETERMINE THE

FINAL PLATFORM SIZE AND THICKNESS, AS

DETAILED ON SHEET MP502, ROUTING PATH OF

CONDENSING LINE SET, AND SPECIFIC SITE

LOCATION OF EACH HOUSEKEEPING PAD. THE FINAL

LOCATION, AND LINE SET ROUTING PATH, OF EACH

HOUSEKEEPING PAD SHALL BE CONFIRMED BY THE

VA COR PRIOR TO THE START OF ANY

HOUSEKEEPING PAD INSTALLATION WORK.

Scale: No Scale

HVAC HOUSEKEEPING PAD LOCATION PLAN

NORTH

1. GRADE MOUNTED HOUSEKEEPING PAD

2. ROOF MOUNTED HOUSEKEEPING PAD

3. FLOOR MOUNTED HOUSEKEEPING PAD

4. NEW STRUCTURAL ROOF TOP PLATFORM BY

GENERAL CONTRACTOR. NEW 70 TON FLUID

COOLER BY MECHANICAL CONTRACTOR.

5. NEW MINI SPLIT SYSTEM SHALL USE THE

SAME LOCATION AS THE EXISTING UNIT IN

PARKING GARAGE 29.

Scale: 1/8" = 1'-0"

BLDG 32 FIRST FLOOR, CHILLER ROOM 101

NORTH

S

CR

CRCR

S

S

S

H J

O

G.7 H.3 H.9

0.9

1226 SF

TELEPHONE

SWITCH

ROOM

CB07

89 SF

OFFICE

CB08A

CORRIDOR

CB-7

H J

O

G.7 H.3 H.9

0.9

1226 SF

TELEPHONE

SWITCH

ROOM

CB07

89 SF

OFFICE

CB08A

C B

CORRIDOR

CB-7

33'-8" V.I.F.

V .I .F

V .I .F

H J

O

G.7 H.3 H.9

0.9

1226 SF

TELEPHONE

SWITCH

ROOM

CB07

89 SF

OFFICE

CB08A

EXIST

9'-1"

H J

O

G.7 H.3 H.9

0.9

1226 SF

TELEPHONE

SWITCH

ROOM

CB07

89 SF

OFFICE

CB08A

A. ALL EXISTING CONDITIONS ARE BASED ON

THE BEST AVAILABLE INFORMATION AT THE

TIME OF SURVEY AND VISUAL INSPECTION.

CONTRACTOR SHALL FIELD VERIFY ALL

EXISTING CONDITIONS.

B. ELEMENTS SHOWN WITH LIGHT, GRAY LINES

ARE EXISTING TO REMAIN. ELEMENTS

SHOWN WITH DARK, DASHED LINES ARE

EXISTING TO BE DEMOLISHED. DEMOLITION

SHALL INCLUDE, BUT NOT BE LIMITED TO,

THOSE ELEMENTS SHOWN.

C. ALL WORK SHALL BE COORDINATED

BETWEEN TRADES.

D. ALL WORK SHALL BE COORDINATED WITH

THE COR TO MINIMIZE DISRUPTION OF

AREAS OUTSIDE OF THE PROJECT LIMITS OF

WORK.

E. CONTRACTOR TO ALSO REFER TO MECHANICAL,

AND ELECTRICAL/TECHNOLOGY DRAWINGS FOR

ADDITIONAL INFORMATION.

F. GC TO PROVIDE EQUIVALENT CFM TEMPORARY

COOLING, FOR THE DURATION OF TIME THAT THE

TR ROOM(S) ARE WITHOUT PERMANENT

HEATING/COOLING, UNTIL THE FULL TR STACK

HVAC SYSTEM IS OPERATIONAL, PRODUCING

THE REQUIRED CFM LOADS, AND SIGNED OFF BY

THE VA COR. SEE MECHANICAL DRAWINGS FOR

MORE INFORMATION.

Engineers Architects

# KEY NOTES:

# KEY NOTES:

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREAS S S S

1 HR - SMOKE SEPARATIONS S S S

/2

/2

:4

:3

P

M C

U s e rs \a p u lle n \D o c u m e n ts \A

-0

A n n

A rb o r-

E H

R M

B ld g -1

E a p u lle n V

D X

T .r v t

1E. A-401

BUILDING 1E, BASEMENT, TELEPHONE

SWITCH ROOM CB07

5 62ANP

EHRM INFRASTRUCTURE

UPGRADES

VA ANN ARBOR HEALTHCARE SYSTEM

2215 FULLER ROAD, ANN ARBOR, MI

48105 FEBRUARY 28, 2024

BID DOCUMENTS

506-21-70521-092

JAB

1E

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

Scale: 1/4" = 1'-0"

TELEPHONE SWITCH ROOM CB07 DEMOLITION FLOOR PLAN

Scale: 1/4" = 1'-0"

TELEPHONE SWITCH ROOM CB07 NEW WORK FLOOR PLAN

Scale: 1/4" = 1'-0"

TELEPHONE SWITCH ROOM CB07 EXISTING REFLECTED CEILING PLAN

Scale: 1/4" = 1'-0"

TELEPHONE SWITCH ROOM CB07 NEW WORK REFLECTED CEILING PLAN

NORTH

0 4 8 16

NORTH

0 4 8 16

NORTH

0 4 8 16

NORTH

0 4 8 16

1 REMOVE EXISTING DOOR & FRAME. NEW

DOOR TO BE INSTALLED IN SAME LOCATION.

PREPARE EXISTING ROUGH OPENING AS

REQUIRED.

1 NEW DOOR & FRAME IN EXISTING CMU WALL.

SEE SCHEDULE

2 NEW CARD READER, REF TO ELEC

DRAWINGS

3 REUSE EXISTING ROOM SIGN

4 EXISTING LIGHTING TO REMAIN, TYPICAL.

5 EXISTING CABLE TRAY TO REMAIN, TYPICAL.

FOR REFERENCE ONLY

S

S S

S

SSS

S S

S S

S

SSS

S S

S S

S

SSS

S S

S S

S

SSS

HG G.3

8.1

8.8

9.7

210 SF

TR

DB60A

420 SF

ELEC

DB60B

605 SF

CORRIDOR

CB-13

DB60A

V .I .F

2338 SF

MECH

DB60

7'-5" V.I.F.

HG G.3

8.1

8.8

9.7

420 SF

ELEC

DB60B

2338 SF

MECH

DB60

605 SF

CORRIDOR

CB-13

TELECOM

DB60A

HG G.3

8.1

8.8

9.7

2338 SF

MECH

DB60

420 SF

ELEC

DB60B

605 SF

CORRIDOR

CB-13

TELECOM

DB60A

EXIST

19'-0"

HG G.3

8.1

8.8

9.7

TR

DB60A

420 SF

ELEC

DB60B

2338 SF

MECH

DB60

605 SF

CORRIDOR

CB-13

A. ALL EXISTING CONDITIONS ARE BASED ON

THE BEST AVAILABLE INFORMATION AT THE

TIME OF SURVEY AND VISUAL INSPECTION.

CONTRACTOR SHALL FIELD VERIFY ALL

EXISTING CONDITIONS.

B. ELEMENTS SHOWN WITH LIGHT, GRAY LINES

ARE EXISTING TO REMAIN. ELEMENTS

SHOWN WITH DARK, DASHED LINES ARE

EXISTING TO BE DEMOLISHED. DEMOLITION

SHALL INCLUDE, BUT NOT BE LIMITED TO,

THOSE ELEMENTS SHOWN.

C. ALL WORK SHALL BE COORDINATED

BETWEEN TRADES.

D. ALL WORK SHALL BE COORDINATED WITH

THE COR TO MINIMIZE DISRUPTION OF

AREAS OUTSIDE OF THE PROJECT LIMITS OF

WORK.

E. CONTRACTOR TO ALSO REFER TO MECHANICAL,

AND ELECTRICAL/TECHNOLOGY DRAWINGS FOR

ADDITIONAL INFORMATION.

F. GC TO PROVIDE EQUIVALENT CFM TEMPORARY

COOLING, FOR THE DURATION OF TIME THAT THE

TR ROOM(S) ARE WITHOUT PERMANENT

HEATING/COOLING, UNTIL THE FULL TR STACK

HVAC SYSTEM IS OPERATIONAL, PRODUCING

THE REQUIRED CFM LOADS, AND SIGNED OFF BY

THE VA COR. SEE MECHANICAL DRAWINGS FOR

MORE INFORMATION.

Engineers Architects

# KEY NOTES:

# KEY NOTES:

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREAS S S S

1 HR - SMOKE SEPARATIONS S S S

/2

/2

:4

:4

P

M C

U s e rs \a p u lle n \D o c u m e n ts \A

-0

A n n

A rb o r-

E H

R M

B ld g -1

E a p u lle n V

D X

T .r v t

1E. A-402

BUILDING 1E, BASEMENT, DELTA

STACK, TELECOM ROOM DB60A

6 62ANP

EHRM INFRASTRUCTURE

UPGRADES

VA ANN ARBOR HEALTHCARE SYSTEM

2215 FULLER ROAD, ANN ARBOR, MI

48105 FEBRUARY 28, 2024

BID DOCUMENTS

506-21-70521-092

JAB

1E

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

Scale: 1/4" = 1'-0"

TELECOM ROOM DB60A

NEW WORK FLOOR PLAN

Scale: 1/4" = 1'-0"

TELECOM DB60A

DEMOLITION FLOOR PLAN

Scale: 1/4" = 1'-0"

TELECOM DB60A

DEMOLITION REFLECTED

CEILING PLAN

Scale: 1/4" = 1'-0"

TELECOM DB60A NEW

WORK REFLECTED CEILING

PLAN

NORTH

0 4 8 16

NORTH

0 4 8 16

NORTH

0 4 8 16

NORTH

0 4 8 16

1 REMOVE EXISTING DOOR & FRAME. NEW

DOOR TO BE INSTALLED IN SAME LOCATION.

PREPARE EXISTING ROUGH OPENING AS

REQUIRED.

2 REMOVE EXISTING SIGNAGE AND STORE FOR

REUSE

3 PREP EXISTING CONCRETE SLAB TO RECEIVE

NEW FLOORING PER SPECIFICATIONS

4 REMOVE EXISTING LIGHTING, TYPICAL. SEE

ELECTRICAL DRAWINGS

5 EXISTING SPRINKLER TO REMAIN, TYPICAL.

SEE MECHANICAL DRAWINGS

6 EXISTING CABLE TRAY TO REMAIN

1 NEW DOOR & FRAME IN EXISTING CMU WALL.

SEE SCHEDULE

2 SEAL ALL PERIMETER AND PENETRATIONS

JOINTS

3 NEW FLOORING, RUBBER WALL BASE, AND

PAINT, SEE SCHEDULE

4 PATCH ALL HOLES & LEVEL UNEVEN

SUBFLOOR

5 NEW CARD READER, REF TO ELEC

DRAWINGS

6 3/4" FIRE RETARDANT PLYWOOD OVER CMU

FOR MOUNTING OF TELECOMMUNICATIONS

EQUIPMENT, 8' AFF TO 8'-8" AFF, PAINT WITH

(3) COATS OF FIRE RETARDANT PAINT

7 INSTALL NEW WALL MOUNTED FIRE

EXTINGUISHER.

8 NEW FIRE EXTINGUISHER SIGN, REF TO A-602

9 REUSE EXISTING ROOM SIGN

10 PAINT AND PATCH WALL BASE AT NEW DOOR

11 EXPOSED STRUCTURE

12 NEW LIGHT FIXTURES, TYPICAL. SEE

ELECTRICAL DRAWINGS

13 CABLE TRAY, SEE ELECTRICAL DRAWINGS

14 COORDINATE FINAL LOCATION OF NEW

CHILLED WATER LINES WITH EXISTING

EQUIPMENT. SEE MECHANICAL DRAWINGS

FOR MORE INFORMATION.

15 NEW FLOORING TRANSITION WITH REDUCER

AS NECESSARY

S S

S

CR

S S

S S

S

S S

S S

S

S S

S S

S

M NM.7

8.1

8.8

9.7

422 SF

ELEC

EB60B

2389 SF

MECH

EB60

838 SF

CORRIDOR

CB-15

TELECOM

EB60A

M NM.7

8.1

8.8

9.7

209 SF

TR

EB60A

422 SF

ELEC

EB60B

838 SF

CORRIDOR

CB-15

2389 SF

MECH

EB60

EB60A

7'-5" V.I.F.

V .I .F

M NM.7

8.1

8.8

9.7

422 SF

ELEC

EB60B

2389 SF

MECH

EB60

838 SF

CORRIDOR

CB-15

TELECOM

EB60A

EXIST

18'-7"

M NM.7

8.1

8.8

9.7

TR

EB60A

422 SF

ELEC

EB60B

838 SF

CORRIDOR

CB-15

2389 SF

MECH

EB60

A. ALL EXISTING CONDITIONS ARE BASED ON

THE BEST AVAILABLE INFORMATION AT THE

TIME OF SURVEY AND VISUAL INSPECTION.

CONTRACTOR SHALL FIELD VERIFY ALL

EXISTING CONDITIONS.

B. ELEMENTS SHOWN WITH LIGHT, GRAY LINES

ARE EXISTING TO REMAIN. ELEMENTS

SHOWN WITH DARK, DASHED LINES ARE

EXISTING TO BE DEMOLISHED. DEMOLITION

SHALL INCLUDE, BUT NOT BE LIMITED TO,

THOSE ELEMENTS SHOWN.

C. ALL WORK SHALL BE COORDINATED

BETWEEN TRADES.

D. ALL WORK SHALL BE COORDINATED WITH

THE COR TO MINIMIZE DISRUPTION OF

AREAS OUTSIDE OF THE PROJECT LIMITS OF

WORK.

E. CONTRACTOR TO ALSO REFER TO MECHANICAL,

AND ELECTRICAL/TECHNOLOGY DRAWINGS FOR

ADDITIONAL INFORMATION.

F. GC TO PROVIDE EQUIVALENT CFM TEMPORARY

COOLING, FOR THE DURATION OF TIME THAT THE

TR ROOM(S) ARE WITHOUT PERMANENT

HEATING/COOLING, UNTIL THE FULL TR STACK

HVAC SYSTEM IS OPERATIONAL, PRODUCING

THE REQUIRED CFM LOADS, AND SIGNED OFF BY

THE VA COR. SEE MECHANICAL DRAWINGS FOR

MORE INFORMATION.

Engineers Architects

# KEY NOTES:

# KEY NOTES:

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREAS S S S

1 HR - SMOKE SEPARATIONS S S S

/2

/2

:4

:5

P

M C

U s e rs \a p u lle n \D o c u m e n ts \A

-0

A n n

A rb o r-

E H

R M

B ld g -1

E a p u lle n V

D X

T .r v t

1E. A-403

BUILDING 1E, BASEMENT, ECHO

STACK, TELECOM ROOM EB60A

7 62ANP

EHRM INFRASTRUCTURE

UPGRADES

VA ANN ARBOR HEALTHCARE SYSTEM

2215 FULLER ROAD, ANN ARBOR, MI

48105 FEBRUARY 28, 2024

BID DOCUMENTS

506-21-70521-092

JAB

1E

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

Scale: 1/4" = 1'-0"

TELECOM EB60A

DEMOLITION FLOOR PLAN

Scale: 1/4" = 1'-0"

TELECOM EB60A NEW

WORK FLOOR PLAN

Scale: 1/4" = 1'-0"

TELECOM EB60A

DEMOLITION REFLECTED

CEILING PLAN

Scale: 1/4" = 1'-0"

TELECOM EB60A NEW

WORK REFLECTED CEILING

PLAN

NORTH

0 4 8 16

NORTH

0 4 8 16

NORTH

0 4 8 16

NORTH

0 4 8 16

1 NEW DOOR & FRAME IN EXISTING CMU WALL.

SEE SCHEDULE

2 SEAL ALL PERIMETER AND PENETRATIONS

JOINTS

3 NEW FLOORING, RUBBER WALL BASE, AND

PAINT, SEE SCHEDULE

4 PATCH ALL HOLES & LEVEL UNEVEN

SUBFLOOR

5 NEW CARD READER, REF TO ELEC

DRAWINGS

6 3/4" FIRE RETARDANT PLYWOOD OVER CMU

FOR MOUNTING OF TELECOMMUNICATIONS

EQUIPMENT, 8' AFF TO 8'-8" AFF, PAINT WITH

(3) COATS OF FIRE RETARDANT PAINT

7 REUSE EXISTING ROOM SIGN

8 PAINT AND PATCH WALL BASE AT NEW DOOR

9 EXPOSED STRUCTURE

10 NEW LIGHT FIXTURES, TYPICAL. SEE

ELECTRICAL DRAWINGS

11 CABLE TRAY, SEE ELECTRICAL DRAWINGS

12 COORDINATE FINAL LOCATION OF NEW

CHILLED WATER LINES WITH EXISTING

EQUIPMENT. SEE MECHANICAL DRAWINGS

FOR MORE INFORMATION.

1 REMOVE EXISTING DOOR & FRAME. NEW

DOOR TO BE INSTALLED IN SAME LOCATION.

PREPARE EXISTING ROUGH OPENING AS

REQUIRED.

2 REMOVE EXISTING SIGNAGE AND STORE FOR

REUSE

3 EXISTING FIRE EXSTINGUISHER CABINET TO

REMAIN

4 PREP EXISTING CONCRETE SLAB TO RECEIVE

NEW FLOORING PER SPECIFICATIONS

5 REMOVE EXISTING LIGHTING, TYPICAL. SEE

ELECTRICAL DRAWINGS

6 DEMOLISH EXISTING CABLE TRAY. SEE

ELECTRICAL DRAWINGS

7 EXISTING SPRINKLER TO REMAIN, TYPICAL.

SEE MECHANICAL DRAWINGS

SSSS

SSSSSSSSSSSS

HG G.3

8.1

8.8

9.7

EXAM

D171

EXAM

D169

CORRIDOR

C1-21

EXAM

D165

MECH

D178

ELEC

D178B

TELECOM

D178A

HG G.3

8.1

8.8

9.7

EXAM

D171

EXAM

D169

CORRIDOR

C1-21

EXAM

D165

MECH

D178

211 SF

TR

D178A

ELEC

D178B

D178A

V .I .F

7'-5" V.I.F.

HG G.3

8.1

8.8

9.7

ELEC

D178B

EXAM

D171

MECH

D178

EXAM

D169

CORRIDOR

C1-21

EXAM

D165

TELECOM

D178A

EXIST

22'-8"

HG G.3

8.1

8.8

9.7

ELEC

D178B

211 SF

TR

D178A

MECH

D178

EXAM

D171

EXAM

D169

CORRIDOR

C1-21

EXAM

D165

A. ALL EXISTING CONDITIONS ARE BASED ON

THE BEST AVAILABLE INFORMATION AT THE

TIME OF SURVEY AND VISUAL INSPECTION.

CONTRACTOR SHALL FIELD VERIFY ALL

EXISTING CONDITIONS.

B. ELEMENTS SHOWN WITH LIGHT, GRAY LINES

ARE EXISTING TO REMAIN. ELEMENTS

SHOWN WITH DARK, DASHED LINES ARE

EXISTING TO BE DEMOLISHED. DEMOLITION

SHALL INCLUDE, BUT NOT BE LIMITED TO,

THOSE ELEMENTS SHOWN.

C. ALL WORK SHALL BE COORDINATED

BETWEEN TRADES.

D. ALL WORK SHALL BE COORDINATED WITH

THE COR TO MINIMIZE DISRUPTION OF

AREAS OUTSIDE OF THE PROJECT LIMITS OF

WORK.

E. CONTRACTOR TO ALSO REFER TO MECHANICAL,

AND ELECTRICAL/TECHNOLOGY DRAWINGS FOR

ADDITIONAL INFORMATION.

F. GC TO PROVIDE EQUIVALENT CFM TEMPORARY

COOLING, FOR THE DURATION OF TIME THAT THE

TR ROOM(S) ARE WITHOUT PERMANENT

HEATING/COOLING, UNTIL THE FULL TR STACK

HVAC SYSTEM IS OPERATIONAL, PRODUCING

THE REQUIRED CFM LOADS, AND SIGNED OFF BY

THE VA COR. SEE MECHANICAL DRAWINGS FOR

MORE INFORMATION.

Engineers Architects

# KEY NOTES:

# KEY NOTES:

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREAS S S S

1 HR - SMOKE SEPARATIONS S S S

/2

/2

:4

:0

P

M C

U s e rs \a p u lle n \D o c u m e n ts \A

-0

A n n

A rb o r-

E H

R M

B ld g -1

E a p u lle n V

D X

T .r v t

1E. A-411

BUILDING 1E, FIRST FLOOR, DELTA

STACK, TELECOM ROOM D178A

8 62ANP

EHRM INFRASTRUCTURE

UPGRADES

VA ANN ARBOR HEALTHCARE SYSTEM

2215 FULLER ROAD, ANN ARBOR, MI

48105 FEBRUARY 28, 2024

BID DOCUMENTS

506-21-70521-092

JAB

1E

Scale: 1/4" = 1'-0"

TELECOM D178A

DEMOLITION FLOOR PLAN

Scale: 1/4" = 1'-0"

TELECOM D178A NEW

WORK FLOOR PLAN

Scale: 1/4" = 1'-0"

TELECOM D178A

DEMOLITION REFLECTED

CEILING PLAN

Scale: 1/4" = 1'-0"

TELECOM D178A NEW

REFLECTED CEILING PLAN

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

NORTH

0 4 8 16

NORTH

0 4 8 16

NORTH

0 4 8 16

NORTH

0 4 8 16

1 NEW DOOR & FRAME IN EXISTING CMU WALL.

SEE SCHEDULE

2 SEAL ALL PERIMETER AND PENETRATIONS

JOINTS

3 NEW FLOORING, RUBBER WALL BASE, AND

PAINT, SEE SCHEDULE

4 PATCH ALL HOLES & LEVEL UNEVEN

SUBFLOOR

5 NEW CARD READER, REF TO ELEC DRAWINGS

6 3/4" FIRE RETARDANT PLYWOOD OVER CMU

FOR MOUNTING OF TELECOMMUNICATIONS

EQUIPMENT, 8' AFF TO 8'-8" AFF, PAINT WITH (3)

COATS OF FIRE RETARDANT PAINT

7 INSTALL NEW SEMI-RECESSED FIRE

EXTINGUISHER CABINET

8 NEW FIRE EXTINGUISHER SIGN, REF TO A-602

9 REUSE EXISTING ROOM SIGN

10 PAINT AND PATCH WALL BASE AT NEW DOOR

11 EXPOSED STRUCTURE

12 NEW LIGHT FIXTURES, TYPICAL. SEE

ELECTRICAL DRAWINGS

13 CABLE TRAY, SEE ELECTRICAL DRAWINGS

14 COORDINATE FINAL LOCATION OF NEW

CHILLED WATER LINES WITH EXISTING

EQUIPMENT. SEE MECHANICAL DRAWINGS FOR

MORE INFORMATION.

1 REMOVE EXISTING DOOR & FRAME. NEW

DOOR TO BE INSTALLED IN SAME LOCATION.

PREPARE EXISTING ROUGH OPENING AS

REQUIRED.

2 REMOVE EXISTING SIGNAGE AND STORE FOR

REUSE

3 PREP EXISTING CONCRETE SLAB TO RECEIVE

NEW FLOORING PER SPECIFICATIONS

4 REMOVE EXISTING LIGHTING, TYPICAL. SEE

ELECTRICAL DRAWINGS

5 DEMOLISH EXISTING CABLE TRAY. SEE

ELECTRICAL DRAWINGS

6 EXISTING SPRINKLER TO REMAIN, TYPICAL.

SEE MECHANICAL DRAWINGS

SSSSS

M NM.7

8.1

8.8

9.7

428 SF

ELEC

E178B

93 SF

EXAM

E165

48 SF

CORRIDOR

C1-34

95 SF

EXAM

E169

95 SF

EXAM

E171

2339 SF

MECH

E178E

TELECOM

E178A

M NM.7

8.1

8.8

9.7

209 SF

TR

E178A

428 SF

ELEC

E178B

93 SF

EXAM

E165

48 SF

CORRIDOR

C1-34

95 SF

EXAM

E169

95 SF

EXAM

E171

2339 SF

MECH

E178E

E178A

7'-5" V.I.F.

V .I .F

M NM.7

8.1

8.8

9.7

428 SF

ELEC

E178B

2339 SF

MECH

E178E

93 SF

EXAM

E165

48 SF

CORRIDOR

C1-34

95 SF

EXAM

E169

95 SF

EXAM

E171

TELECOM

E178A

EXIST

22'-5"

M NM.7

8.1

8.8

9.7

428 SF

ELEC

E178B

209 SF

TR

E178A

2339 SF

MECH

E178E

95 SF

EXAM

E171

95 SF

EXAM

E169

48 SF

CORRIDOR

C1-34

93 SF

EXAM

E165

A. ALL EXISTING CONDITIONS ARE BASED ON

THE BEST AVAILABLE INFORMATION AT THE

TIME OF SURVEY AND VISUAL INSPECTION.

CONTRACTOR SHALL FIELD VERIFY ALL

EXISTING CONDITIONS.

B. ELEMENTS SHOWN WITH LIGHT, GRAY LINES

ARE EXISTING TO REMAIN. ELEMENTS

SHOWN WITH DARK, DASHED LINES ARE

EXISTING TO BE DEMOLISHED. DEMOLITION

SHALL INCLUDE, BUT NOT BE LIMITED TO,

THOSE ELEMENTS SHOWN.

C. ALL WORK SHALL BE COORDINATED

BETWEEN TRADES.

D. ALL WORK SHALL BE COORDINATED WITH

THE COR TO MINIMIZE DISRUPTION OF

AREAS OUTSIDE OF THE PROJECT LIMITS OF

WORK.

E. CONTRACTOR TO ALSO REFER TO MECHANICAL,

AND ELECTRICAL/TECHNOLOGY DRAWINGS FOR

ADDITIONAL INFORMATION.

F. GC TO PROVIDE EQUIVALENT CFM TEMPORARY

COOLING, FOR THE DURATION OF TIME THAT THE

TR ROOM(S) ARE WITHOUT PERMANENT

HEATING/COOLING, UNTIL THE FULL TR STACK

HVAC SYSTEM IS OPERATIONAL, PRODUCING

THE REQUIRED CFM LOADS, AND SIGNED OFF BY

THE VA COR. SEE MECHANICAL DRAWINGS FOR

MORE INFORMATION.

Engineers Architects

# KEY NOTES:

# KEY NOTES:

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREAS S S S

1 HR - SMOKE SEPARATIONS S S S

/2

/2

:4

:1

P

M C

U s e rs \a p u lle n \D o c u m e n ts \A

-0

A n n

A rb o r-

E H

R M

B ld g -1

E a p u lle n V

D X

T .r v t

1E. A-412

BUILDING 1E, FIRST FLOOR, ECHO

STACK, TELECOM ROOM E178A

9 62ANP

EHRM INFRASTRUCTURE

UPGRADES

VA ANN ARBOR HEALTHCARE SYSTEM

2215 FULLER ROAD, ANN ARBOR, MI

48105 FEBRUARY 28, 2024

BID DOCUMENTS

506-21-70521-092

JAB

1E

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

Scale: 1/4" = 1'-0"

TELECOM E178A

DEMOLITION FLOOR PLAN

Scale: 1/4" = 1'-0"

TELECOM E178A NEW WORK

FLOOR PLAN

Scale: 1/4" = 1'-0"

TELECOM E178A

DEMOLITION REFLECTED

CEILING PLAN

Scale: 1/4" = 1'-0"

TELECOM E178A NEW

REFLECTED CEILING PLAN

NORTH

0 4 8 16

NORTH

0 4 8 16

NORTH

0 4 8 16

NORTH

0 4 8 16

1 NEW DOOR & FRAME IN EXISTING CMU WALL.

SEE SCHEDULE

2 SEAL ALL PERIMETER AND PENETRATIONS

JOINTS

3 NEW FLOORING, RUBBER WALL BASE, AND

PAINT, SEE SCHEDULE

4 PATCH ALL HOLES & LEVEL UNEVEN

SUBFLOOR

5 NEW CARD READER, REF TO ELEC

DRAWINGS

6 3/4" FIRE RETARDANT PLYWOOD OVER CMU

FOR MOUNTING OF TELECOMMUNICATIONS

EQUIPMENT, 8' AFF TO 8'-8" AFF, PAINT WITH

(3) COATS OF FIRE RETARDANT PAINT

7 INSTALL NEW SEMI-RECESSED FIRE

EXTINGUISHER CABINET

8 NEW FIRE EXTINGUISHER SIGN, REF TO A-602

9 REUSE EXISTING ROOM SIGN

10 PAINT AND PATCH WALL BASE AT NEW DOOR

11 EXPOSED STRUCTURE

12 NEW LIGHT FIXTURES, TYPICAL. SEE

ELECTRICAL DRAWINGS

13 CABLE TRAY, SEE ELECTRICAL DRAWINGS

14 COORDINATE FINAL LOCATION OF NEW

CHILLED WATER LINES WITH EXISTING

EQUIPMENT. SEE MECHANICAL DRAWINGS

FOR MORE INFORMATION.

1 REMOVE EXISTING DOOR & FRAME. NEW

DOOR TO BE INSTALLED IN SAME LOCATION.

PREPARE EXISTING ROUGH OPENING AS

REQUIRED.

2 REMOVE EXISTING SIGNAGE AND STORE FOR

REUSE

3 PREP EXISTING CONCRETE SLAB TO RECEIVE

NEW FLOORING PER SPECIFICATIONS

4 REMOVE EXISTING LIGHTING, TYPICAL. SEE

ELECTRICAL DRAWINGS

5 DEMOLISH EXISTING CABLE TRAY. SEE

ELECTRICAL DRAWINGS

6 REMOVE EXISTING RUBBER WALL BASE

7 EXISTING SPRINKLER TO REMAIN, TYPICAL.

SEE MECHANICAL DRAWINGS

841 SF

ATM &

VENDING

L128

72 SF

ELEC

L133B

TELECOM

L133

120 SF

TR

L133

841 SF

ATM &

VENDING

L128

72 SF

ELEC

L133B

L

11'-11" V.I.F.

V .I .F

Ma3

72 SF

ELEC

L133B

841 SF

ATM &

VENDING

L128

TELECOM

L133

EXIST

15'-1"

120 SF

TR

L133

841 SF

ATM &

VENDING

L128

72 SF

ELEC

L133B

A. ALL EXISTING CONDITIONS ARE BASED ON

THE BEST AVAILABLE INFORMATION AT THE

TIME OF SURVEY AND VISUAL INSPECTION.

CONTRACTOR SHALL FIELD VERIFY ALL

EXISTING CONDITIONS.

B. ELEMENTS SHOWN WITH LIGHT, GRAY LINES

ARE EXISTING TO REMAIN. ELEMENTS

SHOWN WITH DARK, DASHED LINES ARE

EXISTING TO BE DEMOLISHED. DEMOLITION

SHALL INCLUDE, BUT NOT BE LIMITED TO,

THOSE ELEMENTS SHOWN.

C. ALL WORK SHALL BE COORDINATED

BETWEEN TRADES.

D. ALL WORK SHALL BE COORDINATED WITH

THE COR TO MINIMIZE DISRUPTION OF

AREAS OUTSIDE OF THE PROJECT LIMITS OF

WORK.

E. CONTRACTOR TO ALSO REFER TO MECHANICAL,

AND ELECTRICAL/TECHNOLOGY DRAWINGS FOR

ADDITIONAL INFORMATION.

F. GC TO PROVIDE EQUIVALENT CFM TEMPORARY

COOLING, FOR THE DURATION OF TIME THAT THE

TR ROOM(S) ARE WITHOUT PERMANENT

HEATING/COOLING, UNTIL THE FULL TR STACK

HVAC SYSTEM IS OPERATIONAL, PRODUCING

THE REQUIRED CFM LOADS, AND SIGNED OFF BY

THE VA COR. SEE MECHANICAL DRAWINGS FOR

MORE INFORMATION.

Engineers Architects

# KEY NOTES:

# KEY NOTES:

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREAS S S S

1 HR - SMOKE SEPARATIONS S S S

/2

/2

:4

:2

P

M C

U s e rs \a p u lle n \D o c u m e n ts \A

-0

A n n

A rb o r-

E H

R M

B ld g -1

E a p u lle n V

D X

T .r v t

1E. A-413

BUILDING 1E, FIRST FLOOR, TELECOM

ROOM L133

10 62ANP

EHRM INFRASTRUCTURE

UPGRADES

VA ANN ARBOR HEALTHCARE SYSTEM

2215 FULLER ROAD, ANN ARBOR, MI

48105 FEBRUARY 28, 2024

BID DOCUMENTS

506-21-70521-092

JAB

1E

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

Scale: 1/4" = 1'-0"

TELECOM L133 DEMOLITION

FLOOR PLAN

Scale: 1/4" = 1'-0"

TELECOM L133 NEW WORK

FLOOR PLAN

Scale: 1/4" = 1'-0"

TELECOM L133 DEMOLITION

REFLECTED CEILING PLAN

Scale: 1/4" = 1'-0"

TELECOM L133 NEW WORK

REFLECTED CEILING PLAN

1 NEW WALL, SEE A-501

2 NEW DOOR & FRAME. SEE SCHEDULE

3 SEAL ALL PERIMETER AND PENETRATIONS

JOINTS

4 NEW FLOORING, RUBBER WALL BASE, AND

PAINT, SEE SCHEDULE

5 PATCH ALL HOLES & LEVEL UNEVEN

SUBFLOOR

6 NEW CARD READER, REF TO ELEC DRAWINGS

7 3/4" FIRE RETARDANT PLYWOOD OVER GYP

BD FOR MOUNTING OF

TELECOMMUNICATIONS EQUIPMENT, 8' AFF

TO 8'-8" AFF, PAINT WITH (3) COATS OF FIRE

RETARDANT PAINT

8 APPLY SAFETY WINDOW FILM TO INTERIOR

FACE OF GLAZING, AND INSTALL AN

EXPANDED METAL SCREEN AT EXISTING

WINDOW. FLAT BAR STEEL SECURITY GRILL

TO BE INSTALLED ON EXTERIOR OF WINDOW.

INSULATE AND FUR OUT EXISTING WINDOW.

9 INSTALL NEW SEMI-RECESSED FIRE

EXTINGUISHER CABINET

10 NEW FIRE EXTINGUISHER SIGN, REF TO A-602

11 REUSE EXISTING ROOM SIGN

12 PAINT AND PATCH WALL BASE AT NEW DOOR

TO MATCH EXISTING

13 NEW LIGHT FIXTURES, TYPICAL. SEE

ELECTRICAL DRAWINGS

14 CABLE TRAY, SEE ELECTRICAL DRAWINGS

15 EXPOSED STRUCTURE

1 REMOVE EXISTING DOOR & FRAME, PREPARE

ROUGH OPENING AS REQUIRED FOR NEW

DOOR

2 REMOVE EXISTING SIGNAGE AND STORE FOR

REUSE

3 REMOVE EXISTING FLOORING AND RUBBER

WALL BASE

4 REMOVE EXISTING LIGHTING, TYPICAL. SEE

ELECTRICAL DRAWINGS

5 DEMOLISH EXISTING CABLE TRAY. SEE

ELECTRICAL DRAWINGS

6 EXISTING SPRINKLER TO REMAIN, TYPICAL.

SEE MECHANICAL DRAWINGS

NORTH

0 4 8 16

NORTH

0 4 8 16

NORTH

0 4 8 16

NORTH

0 4 8 16

HG G.3

8.1

8.8

9.7

424 SF

ELEC

D312B

539 SF

PROCEDURE

D318

315 SF

PROCEDURE

D316

2329 SF

MECH

D312

TELECOM

D312A

HG G.3

8.1

8.8

9.7

209 SF

TR

D312A

424 SF

ELEC

D312B

2329 SF

MECH

D312

315 SF

PROCEDURE

D316

539 SF

PROCEDURE

D318

D312A

V .I .F

7'-5" V.I.F.

HG G.3

8.1

8.8

9.7

424 SF

ELEC

D312B

2329 SF

MECH

D312

315 SF

PROCEDURE

D316

539 SF

PROCEDURE

D318

TELECOM

D312A

EXIST

23'-7"

HG G.3

8.1

8.8

9.7

209 SF

TR

D312A

424 SF

ELEC

D312B

2329 SF

MECH

D312

315 SF

PROCEDURE

D316

539 SF

PROCEDURE

D318

A. ALL EXISTING CONDITIONS ARE BASED ON

THE BEST AVAILABLE INFORMATION AT THE

TIME OF SURVEY AND VISUAL INSPECTION.

CONTRACTOR SHALL FIELD VERIFY ALL

EXISTING CONDITIONS.

B. ELEMENTS SHOWN WITH LIGHT, GRAY LINES

ARE EXISTING TO REMAIN. ELEMENTS

SHOWN WITH DARK, DASHED LINES ARE

EXISTING TO BE DEMOLISHED. DEMOLITION

SHALL INCLUDE, BUT NOT BE LIMITED TO,

THOSE ELEMENTS SHOWN.

C. ALL WORK SHALL BE COORDINATED

BETWEEN TRADES.

D. ALL WORK SHALL BE COORDINATED WITH

THE COR TO MINIMIZE DISRUPTION OF

AREAS OUTSIDE OF THE PROJECT LIMITS OF

WORK.

E. CONTRACTOR TO ALSO REFER TO MECHANICAL,

AND ELECTRICAL/TECHNOLOGY DRAWINGS FOR

ADDITIONAL INFORMATION.

F. GC TO PROVIDE EQUIVALENT CFM TEMPORARY

COOLING, FOR THE DURATION OF TIME THAT THE

TR ROOM(S) ARE WITHOUT PERMANENT

HEATING/COOLING, UNTIL THE FULL TR STACK

HVAC SYSTEM IS OPERATIONAL, PRODUCING

THE REQUIRED CFM LOADS, AND SIGNED OFF BY

THE VA COR. SEE MECHANICAL DRAWINGS FOR

MORE INFORMATION.

Engineers Architects

# KEY NOTES:

# KEY NOTES:

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREAS S S S

1 HR - SMOKE SEPARATIONS S S S

/2

/2

:4

:3

P

M C

U s e rs \a p u lle n \D o c u m e n ts \A

-0

A n n

A rb o r-

E H

R M

B ld g -1

E a p u lle n V

D X

T .r v t

1E. A-431

BUILDING 1E, THIRD FLOOR, DELTA

STACK, TELECOM ROOM D312A

11 62ANP

EHRM INFRASTRUCTURE

UPGRADES

VA ANN ARBOR HEALTHCARE SYSTEM

2215 FULLER ROAD, ANN ARBOR, MI

48105 FEBRUARY 28, 2024

BID DOCUMENTS

506-21-70521-092

JAB

1E

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

Scale: 1/4" = 1'-0"

TELECOM D312A

DEMOLITION FLOOR PLAN

Scale: 1/4" = 1'-0"

TELECOM D312A NEW

WORK FLOOR PLAN

Scale: 1/4" = 1'-0"

TELECOM D312A

DEMOLITION REFLECTED

CEILING PLAN

Scale: 1/4" = 1'-0"

TELECOM D312A NEW

WORK REFLECTED CEILING

PLAN

NORTH

0 4 8 16

NORTH

0 4 8 16

NORTH

0 4 8 16

NORTH

0 4 8 16

1 NEW DOOR & FRAME IN EXISTING CMU WALL.

SEE SCHEDULE

2 SEAL ALL PERIMETER AND PENETRATIONS

JOINTS

3 NEW FLOORING, RUBBER WALL BASE, AND

PAINT, SEE SCHEDULE

4 PATCH ALL HOLES & LEVEL UNEVEN

SUBFLOOR

5 NEW CARD READER, REF TO ELEC

DRAWINGS

6 3/4" FIRE RETARDANT PLYWOOD OVER CMU

FOR MOUNTING OF TELECOMMUNICATIONS

EQUIPMENT, 8' AFF TO 8'-8" AFF, PAINT WITH

(3) COATS OF FIRE RETARDANT PAINT

7 INSTALL NEW SEMI-RECESSED FIRE

EXTINGUISHER CABINET

8 NEW FIRE EXTINGUISHER SIGN, REF TO A-602

9 REUSE EXISTING ROOM SIGN

10 PAINT AND PATCH WALL BASE AT NEW DOOR

11 EXPOSED STRUCTURE

12 NEW LIGHT FIXTURES, TYPICAL. SEE

ELECTRICAL DRAWINGS

13 CABLE TRAY, SEE ELECTRICAL DRAWINGS

14 COORDINATE FINAL LOCATION OF NEW

CHILLED WATER LINES WITH EXISTING

EQUIPMENT. SEE MECHANICAL DRAWINGS

FOR MORE INFORMATION.

1 REMOVE EXISTING DOOR & FRAME. NEW

DOOR TO BE INSTALLED IN SAME LOCATION.

PREPARE EXISTING ROUGH OPENING AS

REQUIRED.

2 REMOVE EXISTING SIGNAGE AND STORE FOR

REUSE

3 PREP EXISTING CONCRETE SLAB TO RECEIVE

NEW FLOORING PER SPECIFICATIONS

4 REMOVE EXISTING LIGHTING, TYPICAL. SEE

ELECTRICAL DRAWINGS

5 EXISTING SPRINKLER TO REMAIN, TYPICAL.

SEE MECHANICAL DRAWINGS

6 EXISTING CABLE TRAY TO REMAIN

M NM.7

8.1

8.8

9.7

424 SF

ELEC

E321B

2280 SF

MECH

E321

1468 SF

LAB

E315

277 SF

BIO

SAFETY

AREA

E320

TELECOM

E312A

M NM.7

8.1

8.8

9.7

209 SF

TR

E321A

424 SF

ELEC

E321B

2280 SF

MECH

E321

1468 SF

LAB

E315

277 SF

BIO

SAFETY

AREA

E320

E321A

5 1

147'-5" V.I.F.

V .I .F

M NM.7

8.1

8.8

9.7

424 SF

ELEC

E321B

2280 SF

MECH

E321

1468 SF

LAB

E315

277 SF

BIO

SAFETY

AREA

E320

TELECOM

E312A

EXIST

23'-7"

M NM.7

8.1

8.8

9.7

424 SF

ELEC

E321B

2280 SF

MECH

E321

1468 SF

LAB

E315

277 SF

BIO

SAFETY

AREA

E320

TR

E321A

A. ALL EXISTING CONDITIONS ARE BASED ON

THE BEST AVAILABLE INFORMATION AT THE

TIME OF SURVEY AND VISUAL INSPECTION.

CONTRACTOR SHALL FIELD VERIFY ALL

EXISTING CONDITIONS.

B. ELEMENTS SHOWN WITH LIGHT, GRAY LINES

ARE EXISTING TO REMAIN. ELEMENTS

SHOWN WITH DARK, DASHED LINES ARE

EXISTING TO BE DEMOLISHED. DEMOLITION

SHALL INCLUDE, BUT NOT BE LIMITED TO,

THOSE ELEMENTS SHOWN.

C. ALL WORK SHALL BE COORDINATED

BETWEEN TRADES.

D. ALL WORK SHALL BE COORDINATED WITH

THE COR TO MINIMIZE DISRUPTION OF

AREAS OUTSIDE OF THE PROJECT LIMITS OF

WORK.

E. CONTRACTOR TO ALSO REFER TO MECHANICAL,

AND ELECTRICAL/TECHNOLOGY DRAWINGS FOR

ADDITIONAL INFORMATION.

F. GC TO PROVIDE EQUIVALENT CFM TEMPORARY

COOLING, FOR THE DURATION OF TIME THAT THE

TR ROOM(S) ARE WITHOUT PERMANENT

HEATING/COOLING, UNTIL THE FULL TR STACK

HVAC SYSTEM IS OPERATIONAL, PRODUCING

THE REQUIRED CFM LOADS, AND SIGNED OFF BY

THE VA COR. SEE MECHANICAL DRAWINGS FOR

MORE INFORMATION.

Engineers Architects

# KEY NOTES:

# KEY NOTES:

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREAS S S S

1 HR - SMOKE SEPARATIONS S S S

/2

/2

:4

:4

P

M C

U s e rs \a p u lle n \D o c u m e n ts \A

-0

A n n

A rb o r-

E H

R M

B ld g -1

E a p u lle n V

D X

T .r v t

1E. A-432

BUILDING 1E, THIRD FLOOR, ECHO

STACK, TELECOM ROOM E321A

12 62ANP

EHRM INFRASTRUCTURE

UPGRADES

VA ANN ARBOR HEALTHCARE SYSTEM

2215 FULLER ROAD, ANN ARBOR, MI

48105 FEBRUARY 28, 2024

BID DOCUMENTS

506-21-70521-092

JAB

1E

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

Scale: 1/4" = 1'-0"

TELECOM E321A

DEMOLITION FLOOR PLAN

Scale: 1/4" = 1'-0"

TELECOM E321A NEW WORK

FLOOR PLAN

Scale: 1/4" = 1'-0"

TELECOM E321A

DEMOLITION REFLECTED

CEILING PLAN

Scale: 1/4" = 1'-0"

TELECOM E321A NEW WORK

REFLECTED CEILING PLAN

NORTH

0 4 8 16

NORTH

0 4 8 16

NORTH

0 4 8 16

NORTH

0 4 8 16

1 NEW DOOR & FRAME IN EXISTING CMU WALL.

SEE SCHEDULE

2 SEAL ALL PERIMETER AND PENETRATIONS

JOINTS

3 NEW FLOORING, RUBBER WALL BASE, AND

PAINT, SEE…