Attachment 06_Drawings 07122024 Part 5.pdf
PDF 12 MB Posted
- Attached to
- Z2DA--506-21-705 EHRM Infrastructure Upgrades - Ann Arbor, MI - Construction (VA-25-00001864)
- Solicitation number
- 36c77624b0025
About this file
This document appears to be a set of drawings related to the federal contract opportunity for the construction of Electronic Health Record Modernization (EHRM) infrastructure upgrades at the Ann Arbor VA Medical Center. The contract opportunity is solicitation number 36c77624b0025, issued by the Department of Veterans Affairs Technology Acquisition Center in Austin. The drawings provide technical details and specifications for the construction work required under this contract. No further details about the required products, services, pricing, or other key contract terms are included in this particular document, as it appears to be solely a set of technical drawings.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
CAMPUS IMAGE
# 1E, 1W, 2, 3, 15, 22, 28, 29, 30, 31, 32, 37
U.S. DEPARTMENT OF VETERANS AFFAIRS
/2
/2
:5
:1
P
M C
U s e rs \a p u lle n \D o c u m e n ts \A
-0
A n n
A rb o r-
E H
R M
S it e
P la n a p u lle n V
D X
T .r v t
GE.001
COVER
1 1ANP
VA ANN ARBOR HEALTHCARE SYSTEM
2215 FULLER ROAD, ANN ARBOR, MI
48105 FEBRUARY 28, 2024
BID DOCUMENTS
506-21-70521-092
EHRM INFRASTRUCTURE UPGRADES
VA ANN ARBOR HEALTHCARE SYSTEM
2215 FULLER ROAD, ANN ARBOR, MI 48105
VA PROJECT #: 506-21-705
JAB
EHRM INFRASTRUCTURE
UPGRADES
NAME AND TITLE SIGNATURE
VA SIGNATURE BLOCK
VOLUME 4 OF 4
DRAWING LIST - VOLUME 4 OF 4
GENERAL
GE.001 COVER 1 1
ELECTRICAL
ET001 ELECTRICAL GENERAL NOTES, SYMBOL LEGENDS, AND ABBREVIATIONS 1 106
ET002 TECHNOLOGY GENERAL NOTES, SYMBOL LEGEND, AND ABBREVIATIONS 2 106
ET501 TYPICAL TELECOM ROOM DETAILS 3 106
ET502 ELECTRICAL AND TECHNOLOGY DETAILS 4 106
ET503 TECHNOLOGY DETAILS 5 106
ET504 TECHNOLOGY DETAILS 6 106
ET505 ELECTRICAL CHANNEL RACK DETAILS 7 106
ET506 ELECTRICAL AND TECHNOLOGY CHANNEL RACK DETAILS 8 106
ES101 CAMPUS FIBER DISTRIBUTION DIAGRAM 9 106
1E.ET401 BUILDING 1E, BASEMENT, TELEPHONE SWITCH ROOM CB07 10 106
1E.ET402 BUILDING 1E, BASEMENT, DELTA STACK, TELECOM ROOM DB60A 11 106
1E.ET402.A BUILDING 1E, BASEMENT, DELTA STACK, TELECOM ROOM DB60A - ELEVATIONS 12 106
1E.ET403 BUILDING 1E, BASEMENT, ECHO STACK, TELECOM ROOM EB60A 13 106
1E.ET403.A BUILDING 1E, BASEMENT, ECHO STACK, TELECOM ROOM EB60A - ELEVATIONS 14 106
1E.ET411 BUILDING 1E, FIRST FLOOR, DELTA STACK, TELECOM ROOM D178A 15 106
1E.ET411.A BUILDING 1E, FIRST FLOOR, DELTA STACK, TELECOM ROOM D178A - ELEVATIONS 16 106
1E.ET412 BUILDING 1E, FIRST FLOOR, ECHO STACK, TELECOM ROOM E178A 17 106
1E.ET412.A BUILDING 1E, FIRST FLOOR, ECHO STACK, TELECOM ROOM E178A - ELEVATIONS 18 106
1E.ET413 BUILDING 1E, FIRST FLOOR, TELECOM ROOM L133 19 106
1E.ET413.A BUILDING 1E, FIRST FLOOR, TELECOM ROOM L133 - ELEVATIONS 20 106
1E.ET431 BUILDING 1E, THIRD FLOOR, DELTA STACK, TELECOM ROOM D312A 21 106
1E.ET431.A BUILDING 1E, THIRD FLOOR, DELTA STACK, TELECOM ROOM D312A - ELEVATIONS 22 106
1E.ET432 BUILDING 1E, THIRD FLOOR, ECHO STACK, TELECOM ROOM E321A 23 106
1E.ET432.A BUILDING 1E, THIRD FLOOR, ECHO STACK, TELECOM ROOM E321A - ELEVATIONS 24 106
1E.ET451 BUILDING 1E, FIFTH FLOOR, DELTA STACK, TELECOM ROOM D530A 25 106
1E.ET451.A BUILDING 1E, FIFTH FLOOR, DELTA STACK, TELECOM ROOM D530A - ELEVATIONS 26 106
1E.ET452 BUILDING 1E, FIFTH FLOOR, ECHO STACK, TELECOM ROOM E530A 27 106
1E.ET452.A BUILDING 1E, FIFTH FLOOR, ECHO STACK, TELECOM ROOM E530A - ELEVATIONS 28 106
1E.ET471 BUILDING 1E, SEVENTH FLOOR, DELTA STACK, TELECOM ROOM D712A 29 106
1E.ET471.A BUILDING 1E, SEVENTH FLOOR, DELTA STACK, TELECOM ROOM D712A - ELEVATIONS 30 106
1E.ET472 BUILDING 1E, SEVENTH FLOOR, ECHO STACK, TELECOM ROOM E718A 31 106
1E.ET472.A BUILDING 1E, SEVENTH FLOOR, ECHO STACK, TELECOM ROOM E718A - ELEVATIONS 32 106
1W.ET401 BUILDING 1W, BASEMENT ELECTRICAL EQUIPMENT AB00 33 106
1W.ET402 BUILDING 1W, BASEMENT, ALPHA STACK, TELECOM ROOM AB29 34 106
1W.ET403 BUILDING 1W, BASEMENT, BRAVO STACK, TELECOM ROOM BB26 35 106
1W.ET403.A BUILDING 1W, BASEMENT, BRAVO STACK, TELECOM ROOM BB26 - ELEVATIONS 36 106
1W.ET404 BUILDING 1W, BASEMENT, TELECOM ROOM BB94 37 106
1W.ET411 BUILDING 1W, FIRST FLOOR, ALPHA STACK, TELECOM ROOM A149 38 106
1W.ET412 BUILDING 1W, FIRST FLOOR, BRAVO STACK, TELECOM ROOM B143 39 106
1W.ET412.A BUILDING 1W, FIRST FLOOR, BRAVO STACK, TELECOM ROOM B143 - ELEVATIONS 40 106
1W.ET421 BUILDING 1W, SECOND FLOOR, ALPHA STACK, TELECOM ROOM A237 41 106
1W.ET422 BUILDING 1W, SECOND FLOOR, BRAVO STACK, TELECOM ROOM B231 42 106
1W.ET422.A BUILDING 1W, SECOND FLOOR, BRAVO STACK, TELECOM ROOM B231 - ELEVATIONS 43 106
1W.ET431 BUILDING 1W, THIRD FLOOR, ALPHA STACK, TELECOM ROOM A339 44 106
1W.ET432 BUILDING 1W, THIRD FLOOR, BRAVO STACK, TELECOM ROOM B310B 45 106
1W.ET432.A BUILDING 1W, THIRD FLOOR, BRAVO STACK, TELECOM ROOM B310B - ELEVATIONS 46 106
1W.ET441 BUILDING 1W, FOURTH FLOOR, ALPHA STACK, TELECOM ROOM A437 47 106
1W.ET442 BUILDING 1W, FOURTH FLOOR, BRAVO STACK, TELECOM ROOM B432A 48 106
1W.ET442.A BUILDING 1W, FOURTH FLOOR, BRAVO STACK, TELECOM ROOM B432A - ELEVATIONS 49 106
1W.ET451 BUILDING 1W, FIFTH FLOOR, ALPHA STACK, TELECOM ROOM A535 50 106
1W.ET452 BUILDING 1W, FIFTH FLOOR, BRAVO STACK, TELECOM ROOM B525A 51 106
1W.ET452.A BUILDING 1W, FIFTH FLOOR, BRAVO STACK, TELECOM ROOM B525A - ELEVATIONS 52 106
1W.ET461 BUILDING 1W, SIXTH FLOOR, ALPHA STACK, TELECOM ROOM A633A 53 106
DRAWING LIST - VOLUME 4 OF 4
1W.ET462 BUILDING 1W, SIXTH FLOOR, BRAVO STACK, TELECOM ROOM B618A 54 106
1W.ET462.A BUILDING 1W, SIXTH FLOOR, BRAVO STACK, TELECOM ROOM B618A - ELEVATIONS 55 106
1W.ET471 BUILDING 1W, SEVENTH FLOOR, ALPHA STACK, TELECOM ROOM A753 56 106
1W.ET472 BUILDING 1W, SEVENTH FLOOR, BRAVO STACK, TELECOM ROOM B722A 57 106
1W.ET472.A BUILDING 1W, SEVENTH FLOOR, BRAVO STACK, TELECOM ROOM B722A - ELEVATIONS 58 106
1W.ET481 BUILDING 1W, EIGHTH FLOOR, ALPHA STACK, TELECOM ROOM A843A 59 106
1W.ET482 BUILDING 1W, EIGHTH FLOOR, BRAVO STACK, TELECOM ROOM B812 60 106
1W.ET482.A BUILDING 1W, EIGHTH FLOOR, BRAVO STACK, TELECOM ROOM B812 - ELEVATIONS 61 106
1W.ET491 BUILDING 1W, NINTH FLOOR, ALPHA STACK, TELECOM ROOM A921A 62 106
28.ET401 BUILDING 28, BASEMENT, FOXTROT STACK, TELECOM ROOM FG86 63 106
28.ET411 BUILDING 28, FIRST FLOOR, MAIN COMPUTER ROOM A180 - POWER 64 106
28.ET414 BUILDING 28, FIRST FLOOR, FOXTROT STACK, TELECOM ROOM F152 65 106
28.ET421 BUILDING 28, SECOND FLOOR, FOXTROT STACK, TELECOM ROOM F224A 66 106
2.ET421 BUILDING 2, FULLER HOUSE, SECOND FLOOR, TELECOM ROOM 210 67 106
3.ET401 BUILDING 3, FACILITY MANAGEMENT & SAFETY, BASEMENT, TELECOM ROOM 02C 68 106
15.ET401 BUILDING 15, NORTH METER HOUSE, FIRST FLOOR, TELECOM ROOM 15-2 69 106
22.ET401 BUILDING 22, RESEARCH BUILDING, GROUND FLOOR, TELECOM ROOM G12 70 106
22.ET411 BUILDING 22, RESEARCH BUILDING, FIRST FLOOR, TELECOM ROOM 08 71 106
22.ET411.A BUILDING 22, RESEARCH BUILDING, ROOF PLAN 72 106
29.ET411 BUILDING 29, EAST PARKING STRUCTURE, LEVEL A, TELECOM ROOM AA6 73 106
29.ET421 BUILDING 29, EAST PARKING STRUCTURE, LEVEL B, TELECOM ROOM EPS-B2 74 106
30.ET421 BUILDING 30, WEST PARKING STRUCTURE, LEVEL B, TELECOM ROOM WPS-B02 75 106
30.ET441 BUILDING 30, WEST PARKING STRUCTURE, LEVEL D, TELECOM ROOM WPS-D02 76 106
31.ET401 BUILDING 31, RESEARCH BUILDING, BASEMENT, TELECOM ROOM 27 77 106
31.ET401.A BUILDING 31, RESEARCH BUILDING, BASEMENT, TELECOM ROOM 27 - ELEVATIONS 78 106
31.ET411 BUILDING 31, RESEARCH BUILDING, FIRST FLOOR, TELECOM ROOM 117 79 106
31.ET411.A BUILDING 31, RESEARCH BUILDING, FIRST FLOOR, TELECOM ROOM 117 - ELEVATIONS 80 106
31.ET421 BUILDING 31, RESEARCH BUILDING, SECOND FLOOR, TELECOM ROOM 218 81 106
31.ET421.A BUILDING 31, RESEARCH BUILDING, SECOND FLOOR, TELECOM ROOM 218 - ELEVATIONS 82 106
32.ET401 BUILDING 32, ENERGY CENTER, BASEMENT, TELECOM ROOM 003 83 106
32.ET401.A BUILDING 32, ENERGY CENTER, BASEMENT, TELECOM ROOM 003 - ELEVATIONS 84 106
32.ET431 BUILDING 32, ENERGY CENTER , FIRST FLOOR CHILLER ROOM 101 AND ROOF ELECTRICAL PLAN 85 106
37.ET401 BUILDING 37, ADMINISTRATIVE BUILDING, BASEMENT, TELECOM ROOM 006 86 106
37.ET401.A BUILDING 37, ADMINISTRATIVE BUILDING, BASEMENT, TELECOM ROOM 006 - ELEVATIONS 87 106
37.ET411 BUILDING 37, ADMINISTRATIVE BUILDING, FIRST FLOOR, TELECOM ROOM 118 88 106
37.ET411.A BUILDING 37, ADMINISTRATIVE BUILDING, FIRST FLOOR, TELECOM ROOM 118 - ELEVATIONS 89 106
37.ET421 BUILDING 37, ADMINISTRATIVE BUILDING, SECOND FLOOR, TELECOM ROOM 217 90 106
37.ET421.A BUILDING 37, ADMINISTRATIVE BUILDING, SECOND FLOOR, TELECOM ROOM 217 - ELEVATIONS 91 106
37.ET431 BUILDING 37, ADMINISTRATIVE BUILDING, THIRD FLOOR, TELECOM ROOM 317 92 106
37.ET431.A BUILDING 37, ADMINISTRATIVE BUILDING, THIRD FLOOR, TELECOM ROOM 317 - ELEVATIONS 93 106
1.ET601 BUILDING 1E, 1W, AND 28 FIBER RISER DIAGRAM 94 106
1.ET602 MECHANICAL EQUIPMENT SCHEDULE AND BUILDING 1E AND 28 ELECTRICAL RISER DIAGRAMS 95 106
1.ET603 BUILDING 1W ELECTRICAL RISER DIAGRAM 96 106
1.ET604 BUILDING 1W EXISTING A STACK PHONE, CODE ONE, PA, PACS RISERS AND PACS PANELS
SCHEDULE
97 106
2.ET601 MECHANICAL EQUIPMENT SCHEDULE, SINGLE LINE AND FIBER RISER DIAGRAM 98 106
3.ET601 MECHANICAL EQUIPMENT SCHEDULE, SINGLE LINE AND FIBER RISER DIAGRAM 99 106
15.ET601 MECHANICAL EQUIPMENT SCHEDULE, SINGLE LINE AND FIBER RISER DIAGRAM 100 106
22.ET601 MECHANICAL EQUIPMENT SCHEDULE, SINGLE LINE AND FIBER RISER DIAGRAM 101 106
29.ET601 MECHANICAL EQUIPMENT SCHEDULE, SINGLE LINE AND FIBER RISER DIAGRAM 102 106
30.ET601 MECHANICAL EQUIPMENT SCHEDULE, SINGLE LINE AND FIBER RISER DIAGRAM 103 106
31.ET601 MECHANICAL EQUIPMENT SCHEDULE, SINGLE LINE AND FIBER RISER DIAGRAM 104 106
32.ET601 MECHANICAL EQUIPMENT SCHEDULE, SINGLE LINE AND FIBER RISER DIAGRAM 105 106
37.ET601 MECHANICAL EQUIPMENT SCHEDULE, SINGLE LINE AND FIBER RISER DIAGRAM 106 106
DocuSign Envelope ID: F024BA2E-7BBC-4DFF-BDAC-B255F954C023
2/26/2024
120V DUPLEX RECEPTACLE
RECEPTACLE MODIFIERS:
AC: 3" ABOVE COUNTERTOP/BACKSPLASH
GFI: GROUND FAULT CURRENT INTERRUPTER
WP: WEATHERPROOF ENCLOSURE
DED: DEDICATED CIRCUIT
120V DUPLEX RECEPTACLE EMERGENCY OUTLET
AND COVER PLATE SHALL BE RED IN COLOR
120V QUADRUPLEX RECEPTACLE
120V QUADRUPLEX RECEPTACLE EMERGENCY
OUTLET AND COVER PLATE SHALL BE RED IN COLOR
JUNCTION BOX, WALL MOUNTED, PURPOSE AS NOTED
DISCONNECT SWITCH NON-FUSED
DISCONNECT SWITCH FUSED
SINGLE POLE WALL SWITCH: 48" AFF STANDARD UNO
SYMBOL HEIGHT DESCRIPTION
18"
18"
18"
18"
AS
NOTED
72" TOP
72" TOP
SWITCH MODIFIERS:
M: MOTOR-RATED
48"
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
TOP: HEIGHT TO TOP OF DEVICE
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.
SPECIAL RECEPTACLE, REFER TO ET501 FOR NEMA
TYPE
EQUIPMENT CONNECTION
AS
NOTED
E
18"
120V DUPLEX RECEPTACLE FLOOR BOX
120V DUPLEX RECEPTACLE EMERGENCY FLOOR BOX
OUTLET AND COVER PLATE SHALL BE RED IN COLOR
120V QUADRUPLEX RECEPTACLE FLOOR BOX
120V QUADUPLEX RECEPTACLE EMERGENCY
FLOOR BOX OUTLET AND COVER PLATE SHALL BE
RED IN COLOR
CLNG
J
J
J
JUNCTION BOX, CEILING MOUNTED, PURPOSE AS
NOTED
JUNCTION BOX, FLOOR MOUNTED, PURPOSE AS
NOTED
120V SIMPLEX RECEPTACLE18"
2' X 2' RECESSED ARCHITECTURAL TROFFER
2' X 4' RECESSED ARCHITECTURAL TROFFER
SYMBOL
HEIGHT
AFF * DESCRIPTION
--- 2' X 4' RECESSED FLAT LENS TROFFER
2' LINEAR - WALL MOUNTED
7'-0"
CENTER
4' LINEAR - WALL MOUNTED
7'-0"
CENTER
WALL SCONCE
6'-0"
CENTER
6" DIAMETER RECESSED DOWNLIGHT---
EXIT SIGN - WALL MOUNTED
EXIT SIGN - CEILING MOUNTED---
7'-5"
BOTTOM
SINGLE POLE WALL SWITCH
SWITCH MODIFIERS:
OS: OCCUPANCY SENSOR, LOW VOLTAGE,
DUAL TECHNOLOGY
VS: VACANCY SENSOR, LOW VOLTAGE,
DUAL TECHNOLOGY
DR: DUAL RELAY
VSD: VACANCY SENSOR, LINE VOLTAGE, DIMMER
OSD: OCCUPANCY SENSOR, LINE VOLTAGE, DIMMER
LV: LOW VOLTAGE
LVD: LOW VOLTAGE DIMMER
D: LINE VOLTAGE DIMMER
T: DIGITAL TIMER
K: KEYED
3: 3 WAY
4: 4 WAY
48"
CENTER
OCCUPANCY SENSOR, LOW VOLTAGE,
DUAL TECHNOLOGY - CEILING MOUNTED
--- LOW VOLTAGE LIGHTING CONTROL DEVICE
OCCUPANCY SENSOR, LOW VOLTAGE, DUAL
TECHNOLOGY - WALL/CORNER MOUNTED
EMERGENCY LIGHT BATTERY
OPERATED - WALL MOUNTED
7'-6"
CENTER
RC
* - ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.
LIGHT LEVEL SENSOR, SINGLE ZONE
DIMMING CLOSED LOOP - CEILING MOUNTED
--- LOW VOLTAGE LIGHTING CONTROL
DEVICE WITH 0-10V DIMMING
RCD
OS
OS
LS
4' LINEAR STRIP - SUSPENDED---
L L
SPKR SPEAKER
SP SPARE
SR SURFACE RACEWAY
SS STAINLESS STEEL
SSW SELECTOR SWITCH
STD STANDARD
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SYM SYMMETRICAL
SYS SYSTEM
TC TIMECLOCK
TEL TELEPHONE
TEL/DATA TELEPHONE/DATA
TERM TERMINAL
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TR TAMPER RESISTANT
T-STAT THERMOSTAT
TTB TELEPHONE TERMINAL BOARD
TTC TELEPHONE TERMINAL CABINET
TV TELEVISION
TYP TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITER'S LABORATORY
UT UNDERGROUND TELEPHONE
UTP UNSHIELDED TWISTED PAIR
UTIL UTILITY
UV UNIT VENTILATOR OR
ULTRAVIOLET
UPS UNINTERUPTABLE POWER
SUPPLY
V VOLT
VA VOLT-AMPERES
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
W WATT
W/ WITH
WH WATER HEATER
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
XFR TRANSFER
ANGLE
@ AT
DELTA
' FEET
" INCHES
# NUMBER
Φ PHASE
C CENTER LINE
P PLATE
MTR MOTOR, MOTORIZED
MTS MANUAL TRANSFER SWITCH
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
NFDS NON-FUSED SAFETY DISCONNECT
SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OL OVERLOAD
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT
UNIT
PCB POLYCHLORINATED BIPHENYL
PC PHOTOELECTRIC CELL
PDU POWER DISTRIBUTION UNIT
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
POE POWER-OVER-ETHERNET
PR PAIR
PRI PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (CONDUIT)
PWR POWER
QTY QUANTITY
R RELOCATE/RELOCATED
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
RTU ROOF TOP UNIT
SC SURFACE CONDUIT
SEC SECONDARY
SF SQUARE FEET/FOOT
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SIM SIMILAR
S/N SOLID NEUTRAL
SPEC SPECIFICATION
1P 1 POLE (2P, 3P, 4P, ETC.)
1PH 1 PHASE
2/C TWO-CONDUCTOR (3/C, 4/C, ETC.)
2W TWO-WIRE (3W, 4W, ETC.)
3PH 3 PHASE
A AMPERE
AAP ALARM ANNUNCIATOR PANEL
AC ABOVE COUNTER
AIR CONDITIONER
ALTERNATING CURRENT
ACC ACCESSIBLE
ACLG ABOVE CEILING
ADO AUTOMATIC DOOR OPENER
A/E ARCHITECT/ENGINEER
AF AMP FRAME
AFC AVAILABLE FAULT CURRENT (KILOAMPS)
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC FAULT CIRCUIT INTERRUPTER
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
APPROX APPROXIMATELY
ARCH ARCHITECT, ARCHITECTURAL
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BAS BUILDING AUTOMATION SYSTEM
BATT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISHED FLOOR
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
BYP BYPASS
C CONDUIT
CAB CABINET
CALC CALCULATED
CAP CAPACITY
CAT CATALOG, CATEGORY
CATV COMMUNITY ANTENNA TELEVISION
CB CIRCUIT BREAKER
CCR CONTROL CONTACTOR
CCT CORRELATED COLOR TEMPERATURE
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR-FURNISHED
CKT CIRCUIT
CLG CEILING
CO CONTRACTING OFFICER
COAX COAXIAL CABLE
COMM COMMUNICATION
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE
COR CONTRACTING OFFICER'S
REPRESENTATIVE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CTR CENTER
CU COPPER
CU FT CUBIC FEET
D DEMOLITION
dB DECIBEL
DB DIRECT BURIAL
DC DIRECT CURRENT
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLISH/DEMOLITION
DEPT DEPARTMENT
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DS SAFETY DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
EC ELECTRICAL CONTRACTOR
EG EQUIPMENT GROUND
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
EM EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
ESMT EASEMENT
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WALL HEATER
ELECTRIC WATER HEATER
EX EXISTING
EXP EXPLOSION PROOF
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FCU FAN COIL UNIT
FIXT FIXTURE
FLR FLOOR
FU FUSE
FUDS FUSED SAFETY DISCONNECT
SWITCH
FVR FULL VOLTAGE REVERSING
FVNR FULL VOLTAGE NON-REVERSING
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
GND GROUND
GRS GALVANIZED RIGID STEEL (CONDUIT)
GYP BD GYPSUM BOARD
HID HIGH-INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING AND AIR
CONDITIONING
HW HARD WIRED
IES ILLUMINATION ENGINEERING SOCIETY
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
IR INFRARED
I/W INTERLOCK WITH
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LED LIGHT-EMITTING DIODE
LF LINEAR FEET/FOOT
LM LUMEN
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
METAL-CLAD (CONDUIT)
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT SWITCH
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MOA MULTIOUTLET ASSEMBLY
MSBD MAIN SWITCHBOARD
MT MOUNT
A1 b
E1 c d
T1
'LPN'
THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER OR AN UPPER
CASE LETTER AND NUMBER.
THE SWITCH DESIGNATION (IF NEEDED) IS INDICATED BY A LOWER CASE LETTER.
EXAMPLE: LIGHTING FIXTURE TYPE 'A1' IS CONTROLLED BY SWITCH 'b'.
EXIT SIGNS: STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING
MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES
DIRECTIONAL ARROW ON ILLUMINATED FACE(S).
DEVICES: THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
TRANSFORMERS: THE TRANSFORMER TYPE IS INDICATED BY A NUMBER
FOLLOWING THE UPPER CASE LETTER 'T'. SEE THE TRANSFORMER SCHEDULE OR
THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND
REQUIREMENTS.
PANELBOARDS: PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING
SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR
DESIGNATION CODES.
SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE
NUMBER INDICATED IN THE HEXAGON.
HOME RUN TO BRANCH CIRCUIT PANEL: THE PANEL DESIGNATION AND CIRCUIT
DESIGNATION ARE SHOWN ADJACENT TO THE HOME RUN ARROW.
CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL
SCHEDULE WITH THE CORRESPONDING PANEL AND CIRCUIT DESIGNATION.
SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE
A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.
'LPN'-1,3,5
EXAMPLE 1: WALL MOUNTED EXIT SIGN TYPE 'E1' WITH SINGLE FACE
AND DIRECTIONAL ARROW.
EXAMPLE 2: CEILING MOUNTED EXIT SIGN TYPE 'E2' WITH DOUBLE
FACE AND DIRECTIONAL ARROWS.
E2
EXAMPLE: SPLIT DUPLEX RECEPTACLE; ONE RECEPTACLE OUTLET IS
CONTROLLED BY SWITCH 'c'.
EXAMPLE: SINGLE POLE SWITCH 'd' TO CONTROL LIGHTING FIXTURES INDICATED BY 'd'.
EXAMPLE: TRANSFORMER TYPE 'T1'.
EXAMPLE: HOME RUN TO PANELBOARD 'LPN'; CIRCUITS 1, 3, 5.
# DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE
NOTE NUMBER INDICATED IN THE SQUARE.
A. PRIOR TO SUBMITTING PROPOSAL, BIDDER SHALL EXAMINE ALL GENERAL CONSTRUCTION DRAWINGS.
B. CERTAIN REMODELING OF ELECTRICAL FACILITIES WILL BE REQUIRED IN THE EXISTING BUILDING. EXISTING CONDUIT RUNS ARE GENERALLY NOT SHOWN. ALTHOUGH A FULL ATTEMPT HAS BEEN MADE TO SHOW SOME EXISTING CONDITIONS, OF WHICH INFORMATION HAS BEEN TAKEN FROM EXISTING RECORD DRAWINGS OF THIS PROJECT. THE DRAWINGS SHOWING LOCATION OF EXISTING EQUIPMENT, OUTLETS, FIXTURES, ETC., IN EXISTING
AREAS ARE APPROXIMATE ONLY (FIELD VERIFY).
C. BRANCH CIRCUITS SHALL BE REUSED WHERE PRACTICAL AND SHALL, IN ADDITION, BE REMODELED AS
REQUIRED. THE CONTRACTOR SHALL CONCEAL ALL WORK WHERE POSSIBLE.
D. EXISTING ELECTRICAL WIRING WHICH WILL NOT BE MADE OBSOLETE AND WHICH WILL BE DISTURBED DUE TO CONSTRUCTION CHANGES REQUIRED BY THIS CONTRACT SHALL BE RESTORED TO OPERATING CONDITION, AS REQUIRED AND/OR DIRECTED. WHERE REQUIRED, SHOWN AND/OR DIRECTED, OUTLETS AND CONDUIT RUNS SHALL BE RELOCATED. IN SOME CASES IT MAY BE NECESSARY TO EXTEND CONDUITS AND PULL IN NEW WIRING OR INSTALL JUNCTION BOXES AND SPLICE IN NEW WIRING OR REPLACE OLD WIRING WITH NEW.
E. OUTLETS FROM WHICH FIXTURES, SWITCHES, RECEPTACLES, AND/OR OTHER ELECTRICAL DEVICES ARE MOVED AND WHICH ARE NOT REPLACED OR REUSED SHALL BE REMOVED OR, IF IT IS NOT POSSIBLE TO REMOVE, PLACE A BLANK COVER ON THE OUTLET BOX. WHERE OUTLETS, BOXES, ETC., ARE COMPLETELY REMOVED, THE
CONTRACTOR SHALL CUT OFF CONDUITS AND REMOVE WIRING.
F. WHERE EXISTING LIGHT FIXTURES ARE TO BE REUSED, THE ELECTRICAL CONTRACTOR SHALL CLEAN AND REPLACE LAMPS, REPAIR OR REPLACE DEFECTIVE PARTS, LENS, BALLAST, ETC. AS REQUIRED.
G. WHERE CONDUITS EXTENDING THROUGH FLOORS ARE TO BE ABANDONED, THE CONTRACTOR SHALL CUT AND
CAP OR PLUG CONDUIT, THAT IT WILL NOT PROTRUDE ABOVE THE FLOOR.
H. WHERE EXISTING CONDUIT IS TO BE ABANDONED, THE CONDUIT SHALL BE REMOVED IF IT IS EXPOSED, IN A CRAWL SPACE OR IN AN ACCESSIBLE CEILING. WHERE IT IS IMPOSSIBLE TO REMOVE THE CONDUIT, IT SHALL BE
CUT OFF AND CAPPED OR PLUGGED.
I. THE CONTRACTOR SHALL BE HELD FULLY RESPONSIBLE FOR THE PROPER RESTORATION OF ALL EXISTING SURFACES REQUIRED PATCHING, PLASTERING, PAINTING AND/OR OTHER REPAIR DUE TO THE INSTALLATION OF ELECTRICAL WORK UNDER THE TERMS OF THIS SPECIFICATION. CLOSE ALL OPENINGS, REPAIR ALL SURFACES, ETC., AS REQUIRED. THE CONTRACTOR SHALL EMPLOY QUALIFIED AND EXPERIENCED WORKMEN FOR THIS WORK. ALL RESTORATION WORK SHALL BE SUBJECT TO THE APPROVAL OF THE ARCHITECT AND/OR THE
COR/VA.
J. ALL TEMPORARY AND REMODELING WORK SHALL BE CONSIDERED A PART OF THIS CONTRACT AND NO EXTRA CHARGES WILL BE ALLOWED. THIS SHALL INCLUDE MINOR ITEMS OF MATERIAL OR EQUIPMENT NECESSARY TO
MEET THE REQUIREMENTS AND INTENT OF THE PROJECT.
K. EXAMINE ARCHITECTURAL, STRUCTURAL, AND MECHANICAL DRAWINGS AND SPECIFICATIONS TO DETERMINE THE SEQUENCE OF CONSTRUCTION THROUGHOUT THE PROJECT, INCLUDING EXISTING, TEMPORARY, REMODELED AND NEW AREAS.
L. ALL ELECTRICAL CONNECTIONS REQUIRING AN OUTAGE SHALL BE MADE DURING AN APPROVED TIME LIMIT.
CHANGEOVERS SHALL BE AS SHORT A DURATION AS POSSIBLE AND SHALL NOT INTERFERE WITH NORMAL OPERATION OF THE COR/VA FACILITIES. NOTIFY COR/VA NO LESS THAN 14 DAYS (TWO WEEKS) IN ADVANCE OF A SHUTDOWN OF ANY ELECTRICAL CIRCUIT FOR CHANGEOVER, AND SUCH A CHANGEOVER SHALL BE DONE DURING HOURS AS DIRECTED BY COR/VA. WORK SHALL BE SCHEDULED SO THAT AT NO TIME WILL ANY EMERGENCY FEEDER, CIRCUIT, OR FIRE ALARM ZONE BE OUT OF SERVICE. PROVIDE NECESSARY TEMPORARY
FEEDERS TO ACCOMPLISH THIS REQUIREMENT.
M. EXISTING LOW VOLTAGE WIRING WHICH WILL NOT BE MADE OBSOLETE AND WHICH WILL BE DISTURBED DUE TO CONSTRUCTION CHANGES REQUIRED BY THIS CONTRACT SHALL BE RESTORED TO CONDITION, OR POSITION, AS REQUIRED. PROPERLY RE-SECURE CABLE IN CHASES, CRAWL SPACES, TUNNELS, AND CEILING SPACES AS REQUIRED BY NEC. IN SOME CASES IT MAY BE NECESSARY TO ADD SUPPORTING HARDWARE TO ACCOMPLISH
THIS REQUIREMENT.
N. IF POSSIBLE, ALL NEWLY INSTALLED RECEPTACLES SHALL BE INSTALLED IN SEPARATE OR ADJACENT STUD SPACES, TO AVOID SOUND TRANSMISSION AND WALL INTEGRITY ISSUES. ALL NEWLY INSTALLED RECEPTACLES LOCATED IN COMMON STUD SPACES OF FIRE-RESISTANT WALLS SHALL BE EQUIPPED WITH FIRE-RESISTANT
PUTTY PADS AT THE BACK OF EACH BOX IN ACCORDANCE WITH NEC 300.21.
1. ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT AND WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND VA
STANDARDS.
2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE BUILDING
CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.
3. FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL
ELECTRICAL CODE, UL LISTING REQUIREMENT AND THE APPLICABLE BUILDING CODES.
4. VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL REQUIRED MOUNTING HARDWARE TO
SUIT THE PARTICULAR INSTALLATION.
5. PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING CONSTRUCTION.
6. BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.
7. COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO AVOID CONFLICT DURING
CONSTRUCTION.
8. ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR SPARE, OR SPACE.
9. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE ACCEPTED. ALL PRODUCTS MUST COMPLY WITH "BUY AMERICAN ACT".
10. ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR PARTICULAR EQUIPMENT
MANUFACTURER'S SPECIFICATIONS.
11. CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE DEVICE'S SCREW
TERMINALS.
12. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT UNLESS NOTED
OTHERWISE.
13. ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.
14. ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.
15. ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON VIBRATING EQUIPMENT (MAXIMUM LENGTH OF 6 FEET). PVC SHALL BE USED FOR UNDERGROUND CONDUIT OR WHERE CONCRETE- ENCASED. WHERE VIBRATING EQUIPMENT IS LOCATED OUTSIDE, LFMC CONDUIT SHALL BE USED (MAXIMUM SIX FEET) FOR
FINAL CONNECTIONS.
16. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN APPROVED THIRD
PARTY TESTING AGENCY.
17. FOR ALL LED FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS.
PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION, WILL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY.
PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.
18. IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS DETERMINED BY THE GOVERNMENT, SHALL BE
PROVIDED.
19. COMPRESSION COUPLINGS SHALL BE USED. NO SET SCREW FITTINGS ARE ALLOWED.
20. MINIMUM CONDUIT SIZE TO BE USED IS 3/4".
21. FEEDER TAGS APPENDED WITH 'VD' ARE UPSIZED IN AMPACITY DUE TO VOLTAGE DROP.
22. IF FLOOR OR RATED WALL PENETRATIONS CANNOT BE FIRESTOPPED AT THE END OF THE WORK SHIFT, SUCH AS DUE TO THE NEED TO PULL ADDITIONAL CABLES, TEMPORARY FIRESTOPPING COMPOSED OF MINERAL WOOL SHOULD BE INSTALLED IN THE PENETRATION TO PROVIDE PROTECTION AGAINST FIRE/SMOKE SPREAD THROUGH THE UNSEALED
PENETRATION.
A. RETURN REMOVED MATERIAL DEEMED SALVAGEABLE BY THE COR. MATERIALS DEEMED NOT SALVAGEABLE SHALL BE
REMOVED FROM THE PREMISES.
B. ALL EXISTING CONDITIONS, INCLUDING BUT NOT LIMITED TO EQUIPMENT, DEVICES, FIXTURES, CONDUIT AND CIRCUITS, ARE BASED ON THE BEST AVAILABLE INFORMATION AT THE TIME OF SURVEY AND VISUAL INSPECTION.
C. THE DRAWINGS ARE GENERALLY DIAGRAMMATIC AND THE CONTRACTOR SHALL HARMONIZE HIS WORK SO THAT EACH PIECE OF EQUIPMENT WILL BE INSTALLED AS TO FUNCTION PROPERLY. THE CONTRACTOR SHALL COOPERATE WITH
OTHER TRADES.
D. REMOVE ALL EXISTING WIRING DEVICES, LIGHT FIXTURES, WIRE, CONDUIT, ETC., AS NOTED OR INDICATED WITHIN DEMOLITION AREA. (ALL ITEMS MAY NOT BE SHOWN). REWORK AS NECESSARY CIRCUITING WHICH REQUIRES
CONTINUATION THROUGH THE AREA.
E. ELECTRICAL CONTRACTOR TO PROVIDE ALL NECESSARY LABOR, CONDUIT, WIRE, CONNECTIONS, ETC., FOR DEVICES, FIXTURES, ETC., NOTED AS "EXISTING TO REMAIN" SUCH THAT EXISTING CIRCUIT CONTINUITY IS MAINTAINED.
F. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK REQUIRED TO REMOVE/RELOCATE ANY EXISTING ELECTRICAL EQUIPMENT SUCH THAT ELECTRIC SHOCK HAZARDS TO WORKMEN ARE ELIMINATED DURING DEMOLITION
AND NEW CONSTRUCTION.
G. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK IN REMOVING AND REPLACING "EXISTING TO REMAIN" FIXTURES, DEVICES, ETC., AS REQUIRED SO THAT THESE DEVICES ARE NOT DAMAGED DURING DEMOLITION.
RELOCATED TO NEAREST APPROPRIATE LOCATION TO AVOID CONFLICTS WITH OTHER TRADES' WORK. REPLACE WITH NEW ANY "EXISTING TO REMAIN" FIXTURE, DEVICE, ETC., NOT DEEMED SALVAGEABLE BY THE COR.
H. REMOVED OR DAMAGED CONDUIT, WIRE, AND FITTINGS SHALL NOT BE REUSED FOR RELOCATED OR NEW DEVICES.
I. MAKE AS-BUILTS WITH NEW TYPED DIRECTORIES FOR ALL PANELBOARDS, INDICATING CIRCUIT DESCRIPTION (USED OR
SPARE), CIRCUIT BREAKERS AND CIRCUIT LOAD.
J. WORK REQUIRED FOR EXISTING EQUIPMENT NOTED AS "EXISTING TO BE REMOVED" SHALL INCLUDE:
A. REMOVAL OF FEEDER FROM EQUIPMENT TO POINT OF FEED.
B. REMOVAL OR RE-CIRCUITING OF ALL BRANCH CIRCUITING.
C. REMOVAL OF ALL FITTINGS, SUPPORTS, BRACKETS, ETC.
D. PATCHING OF WALLS, FLOORS AND CEILINGS PER ARCHITECT'S INSTRUCTIONS.
E. CAPPING OF FEEDER CONDUIT AT 6" ABOVE OR BELOW FLOOR/CEILING AS REQUIRED AND MARKING LOCATION
OF POINT OF FEED WITH AN ENGRAVED BRASS TAG.
F. REMOVAL OF FEEDER CONDUIT IF FOUND TO BE UNSALVAGEABLE BY ARCHITECT, ENGINEER OR THE COR.
K. EXISTING EQUIPMENT NOT IMPLICITLY SHOWN ON THE DRAWINGS IS INTENDED TO BE "EXISTING TO REMAIN
UNCHANGED", UNLESS NOTED OTHERWISE.
IF FLOOR OR RATED WALL PENETRATIONS CANNOT BE FIRESTOPPED AT THE END OF THE WORK SHIFT DUE TO THE NEED TO PULL ADDITIONAL CABLES, TEMPORARY FIRESTOPPING COMPOSED OF MINERAL WOOL SHALL BE INSTALLED IN THE PENETRATION TO PROVIDE PROTECTION AGAINST FIRE/SMOKE SPREAD THROUGH THE UNSEALED
PENETRATION.
SHORT CIRCUIT CURRENT CALCULATIONS SHALL BE PERFORMED ON THE ELECTRICAL SYSTEM USING A BOLTED THREE PHASE FAULT CONDITION FOR CALCULATIONS TO ACHIEVE MAXIMUM THERMAL AND MECHANICAL STRESS TO THE SYSTEM FOR CALCULATIONS PURPOSES. EXISTING SHORT CIRCUIT VALUES WILL BE USED OUTSIDE THE WORK
AREA, FOR THE STARTING POINT OF THE CALCULATIONS.
NORMAL AND CRITICAL POWER BRANCHES ARE SIGNIFIED USING "A" AND "B" IN THIS SET.
- EQUIPMENT NOTED WITH "A" ARE ON THE NORMAL POWER BRANCH.
- EQUIPMENT NOTED WITH "B" ARE ON THE CRITICAL POWER BRANCH.
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:4
:0
P
M C
U s e rs
\a ri c h a rd s \D o c u m e n ts
\2 -0
T R
R o o m
D e ta ils a ri c h a rd s P
K P
J .r v t
ET001
ELECTRICAL GENERAL NOTES,
SYMBOL LEGENDS, AND
ABBREVIATIONS
1 106ADR
EHRM INFRASTRUCTURE
UPGRADES
VA ANN ARBOR HEALTHCARE SYSTEM
2215 FULLER ROAD, ANN ARBOR, MI
48105 FEBRUARY 28, 2024
BID DOCUMENTS
506-21-70521-092
JKM
1,2,3,15,22,28,29,30,31,32,37
ELECTRICAL SYMBOL LEGEND
LIGHTING SYMBOL LEGEND ELECTRICAL ABBREVIATIONS LIST
ELECTRICAL SYMBOL NOTES
GENERAL ELECTRICAL REMODELING NOTES
ELECTRICAL GENERAL NOTES
GENERAL ELECTRICAL DEMO NOTES
TEMPORARY FIRESTOPPING
METHOD OF SHORT CIRCUIT CURRENT CALCULATIONS
NORMAL AND CRITICAL POWER - "A" AND "B"
2/27/2024 2/26/2024
TECHNOLOGY SYMBOL LEGEND
DATA OUTLET - N-4 PR UTP
TELCO OUTLET - N-4 PR UTP
SYMBOL HEIGHT DESCRIPTION
18"
48"
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.
SEE DRAWINGS FOR MORE INFORMATION.
NOTE: NOT ALL SYMBOLS ARE USED.
ELECTRONIC LOCKING MECHANISM
DOOR CONTACT
REQUEST FOR EXIT SENSOR
CARD READER
(K - KEYPAD)
48"CR
ES
DC
RX
48" EMERGENCY EXIT BUTTON TO RELEASE DOOR (EEB)
WIRELESS ACCESS POINT - N-4 PR UTP
WALL PHONEW
N
S
NURSE CALL PATIENT STATION WITH PILLOW SPEAKER
2 ADDITIONAL PUSHBUTTONS, 1/4 RECEPTACLE AND COVER
(1 - SINGLE, 2 - DUAL, V - VANDAL RESISTANT)
P NURSE CALL PATIENT BED INTERFACE RECEPTACLE
B NURSE CALL CODE BLUE STATION WITH COVER
E NURSE CALL EMERGENCY STATION WITH PULL CORD AND AUDIO +40" AFF IN
RESTROOM, +72" AFF IN SHOWER (V - VANDAL RESISTANT, PB - PUSH BUTTON)
D NURSE CALL DUTY STATION
M NURSE CALL MASTER STATION/CONSOLE
NURSE CALL DOME LIGHT
(Z - ZONE LIGHT, V - VANDAL RESISTANT)
IC
INTERCOM WITH CAMERA
IC
INTERCOM MASTER WITH PUSH TO RELEASE DOORM
NURSE CALL WIRELESS ANTENNASNW
N
TV OUTLET WALL MOUNTED
48"
54"
DESK
CCTV DOME CAMERA FIXED
CCTV DOME CAMERA PAN/TILT/ZOOM
FOUR POST OIT EQUIPMENT RACK
OIT EQUIPMENT CABINET
NURSE CALL EQUIPMENT CABINET
MATV EQUIPMENT CABINET
CCTV EQUIPMENT CABINET
NCE
MATV
CCTV
LADDER CABLE TARY
N
N
FLOOR BOX FOR DATA
AS NOTED
DOOR
DOOR
ABOVE
DOOR
HEADWALL
18"
HEADWALL
/40"
40", 72"
18"
60"
CEILING
CEILING
6' TO TOP
6' TO TOP
FLOOR
PHYSICAL ACCESS CONTROL SYSTEMPACS 6' TO TOP
ELECTRONIC PANIC HARDWAREEP
DO DOOR OPERATOR
HANDWAVE
T
C
NURSE CALL STAFF TERMINAL
NURSE CALL PATIENT STATION WITH CALL CORD.
(1 - SINGLE, 2 - DUAL, V - VANDAL RESISTANT)
60"
HEADWALL
W WIRELESS PENDANT
L
KP PATIENT ROAM ALERT ACCESS CONTROL KEYPAD48"
PATIENT ROAM ALERT ANTENNACEILING
GROUND BUS
CEILING
DOOR
DOOR
48"
ABOVE
DOOR
NURSE CALL DOME LIGHT
FLOOR
FLOOR
FLOOR
ABOVE
CEILING
18"
4'x8'x3/4" FIRE RATED TTB8"
N
M
PATIENT STATION (PB - PUSH BUTTON, M - MICROPHONE, K -KEYED)
88" MOTION DETECTOR
MD
FLOOR TWO POST OIT EQUIPMENT RACK
CEILING MOUNTED SPEAKERSCEILING
WALL MOUNTED SPEAKERS96"
S
S
AREA OF REFUGE PANEL6' TO TOP
AREA OF REFUGE ANNUNCIATION PANEL6' TO TOP
AOF
AOFA
IC AREA OF REFUGE INTERCOM48"
AREA OF REFUGE STROBE LIGHTCEILINGSL
DP
DPP
DURESS PANIC ALARM PUSH BUTTON48"
DURESS PANIC ALARM PANEL6' TO TOP
N
SECURE WIRELESS ACCESS POINT - N-4 PR UTP
N
CEILING
S
(N - QUANTITY)
(N - QUANTITY)
(N - QUANTITY)
(N - QUANTITY)
CEILING
48"
CEILING
CEILING
TELEMETRY ANTENNA - 2-4 PRCEILING
ROBOT PHARMACY ANTENNA - 1-4 PRCEILINGR
CABLES AND CONNECTORS COLOR LEGEND
DESCRIPTION
ITEM JACK CABLE PATCH CABLES I.D. NOTES
DATA/COMPUTER
WIRELESS ACCESS
POINT - VA
FIBER - MULTI-MODE
FIBER - SINGLE-MODE
SECURITY/FIRE
BLUE
YELLOW
BLACK
IVORY
RED
BLUE
YELLOW
AQUA
YELLOW
RED
BLUE
YELLOW
AQUA
YELLOW
RED
C
WAP
FO
FO
CCTV, PACS, FIRE CCTV, PACS, FIRE
4 PAIR CABLE
4 PAIR CABLE
12/24
ORANGE ORANGE ORANGE RTLS 4 PAIR CABLE
WIRELESS ACCESS
POINT - GUEST
PINK PINK PINK WAP 4 PAIR CABLE
GREEN GREEN GREEN C 4 PAIR CABLE
RTLS
PATIENT MONITORING
PURPLE PURPLE PURPLE C 4 PAIR CABLEMEDICAL EQUIPMENT
WHITE WHITE WHITE T 4 PAIR CABLE
ANALOG PHONE
LINES
ADO AUTOMATIC DOOR OPERATOR
AFF ABOVE FINISH FLOOR
BOD BASIS OF DESIGN
CCTV CLOSED CIRCUIT TELEVISION
COAX COAXIAL CABLE
COMM COMMUNICATION
COR CONTRACTING OFFICER REPRESENTATIVE
DC DOOR CONTACT SWITCH
DN DOWN
DO DOOR OPERATOR
DVC DIGITAL VOICE COMMAND
DVR DIGITAL VIDEO RECORDER
E EXISTING DEVICES
EEB EMERGENCY EXIT BUTTON
EL ELECTRICAL STRIKE
ETR EXISTING TO REMAIN
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FAAP FIRE ALARM ANNUNCIATOR PANEL
FO FIBER OPTIC
FAGAP FIRE ALARM GRAPHIC ANNUNCIATOR PANEL
IT INTERCOMMUNICATION ROOM
MATV MASTER ANTENNA TELEVISION
MM MULTI MODE FIBER
NAC NETWORK APPLIANCE CIRCUIT PANEL
N NEW DEVICES
NCA NETWORK CONTROL ANNUNCIATOR
NS NO SCALE
NTS NOT TO SCALE
NVR NETWORK VIDEO RECORDER
TECHNOLOGY ABBREVIATIONS LIST
OC ON CENTER
OIT OFFICE OF INFORMATION TECHNOLOGY
PACS PHYSICAL ACCESS CONTROL SYSTEM
PAMN PUBLIC ADDRESS AND MASS NOTIFICATION SYSTEM
PB PUSH BUTTON
PBB PRIMARY BONDING BUSBAR
PDU RACK POWER DISTRIBUTION UNITS
POE POWER OVER ETHERNET
PR PAIR
RBB RACK BONDING BUSBAR
RX REQUEST TO EXIT
SBB SECONDARY BONDING BUSBAR
SEP SERVICE ENTRANCE PROTECTION
SLC SIGNALING LINE CIRCUIT
SM SINGLE MODE FIBER
TBB TELECOM BACKBONE CONDUCTOR
TEL TELEPHONE
TGB TELECOM GROUND BUS BAR
TM TELEMONITORING
TMGB TELECOM MAIN GROUND BUS BAR
TP TWISTED PAIR
TR TELECOM ROOM
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
WM WIRE MANAGEMENT
WAP WIRELESS ACCESS POINT
UL UNDERWRITERS LABORATORY
UPS UNINTERRUPTIBLE POWER SUPPLY
UTP UNSHIELDED TWISTED PAIR
TECHNOLOGY GENERAL NOTES
1. PROVIDE COMMUNICATIONS DEVICES AND EQUIPMENT IN ACCORDANCE WITH THE CONTRACT DOCUMENTS, MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT, LATEST EDITION OF THE NATIONAL ELECTRICAL CODE, BICSI STANDARDS, AND VA
STANDARDS.
2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES AND EQUIPMENT WHERE BUILDING CONSTRUCTION IS NOT
SUITABLE FOR DIRECT MOUNTING.
3. FIRESTOP, DRAFTSTOP, SMOKESTOP OR PROTECT ANNULAR SPACE AROUND PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILINGS, AND ROOF IN ACCORDANCE WITH REQUIREMENTS OF NFPA 70, UL
LISTING REQUIREMENT AND APPLICABLE BUILDING CODES.
4. PROVIDE CABLING THAT COMPLIES WITH THE LATEST EDITION OF TELECOMMUNICATIONS DISTRIBUTION
METHOD MANUAL AND ANSI/TIA/EIA PUBLICATIONS.
5. COMPLY WITH THE LATEST ANSI/TIA/EIA 758 AND 607 - GROUNDING AND BONDING REQUIREMENTS FOR
TELECOMMUNICATIONS IN COMMERCIAL BUILDING.
6. COMPLY WITH THE LATEST ANSI/TIA/EIA 568 - COMMERCIAL BUILDING TELECOMMUNICATIONS WIRING
STANDARD.
7. COMPLY WITH THE LATEST ANSI/TIA/EIA 569 - COMMERCIAL BUILDING STANDARD FOR TELECOMMUNICATIONS
PATHWAYS AND SPACES.
8. COMPLY WITH THE LATEST NFPA 70 NATIONAL ELECTRICAL CODE.
9. COMPLY WITH THE LATEST NFPA 99 HEALTHCARE FACILITIES CODE.
10. COMPLY WITH THE LATEST NFPA 101 LIFE SAFETY CODE.
11. COORDINATE WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION.
12. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES TO INDICATE A QUALITY STANDARD AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER.
PRODUCTS DEEMED EQUAL AND APPROVED BY THE COR WILL BE ACCEPTABLE. COMPLY WITH "BUY AMERICAN
ACT".
13. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, BOXES, OUTLET, OR EQUIPMENT UNLESS NOTED
OTHERWISE.
14. PROVIDE RGS OR EMT CONDUIT UNLESS OTHERWISE NOTED.
15. PROVIDE MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT LABEL LISTED BY APPROVED THIRD PARTY
TESTING AGENCY.
16. NOTIFY COR REGARDING DISCREPANCY BETWEEN PLANS AND SPECIFICATIONS FOR CLARIFICATION. THE
MORE STRINGENT OF THE THEM SHALL TAKE PRECEDENCE.
17. PROVIDE TIA/EIA CAT 6A COPPER OUTLETS AND CONNECTORS.
18. ALL WORK AREA OUTLETS SHALL BE 8 PIN, CAT 6A KEYSTONE JACK WIRED PER T568A OR T568B AS DIRECTED
BY THE VA COR.
19. LABEL DEVICES IN ACCORDANCE WITH LATEST ANSI/TIA 606A OR 606B EDITION AS WELL AS THE STANDARDS
SET FORTH BY THE VA HOSPITAL OIT.
20. PROVIDE A MINIMUM OF 12" CLEARANCE ABOVE THE CABLE TRAY PER TIA/EIA 569.
21. VA WILL CONDUCT A WAP SURVEY AND PROVIDE THE SURVEY TO THE CONTRACTOR. INSTALL CABLING AND
EQUIPMENT IN ACCORDANCE WITH THE SURVEY. COORDINATE WITH COR/OIT.
22. ALL CABLING INSTALLED ABOVE CEILING SHALL BE PLENUM RATED.
23. MINIMUM CONDUIT SIZE TO BE USED IS 1-1/4" EMT.
24. DEVICES PLACED IN INTERCOMMUNICATION ROOM TO BE MOUNTED ON FIRE RETARDANT PLYWOOD.
25. PROVIDE OUTDOOR AND INDOOR CONDUITS, INNERDUCTS, TELECOM HANDHOLES, TELECOM MANHOLES, HANDHOLE COVERS, CABLING BOTH FIBER AND COPPER, SUPPORTS, TESTING, AND ALL RELATED MATERIALS
FOR A COMPLETE SYSTEM AS SHOWN HEREIN AND DESCRIBED IN THE SPECIFICATIONS.
26. PROVIDE CABLE TRAY, LADDER TRAY J-HOOKS, CONDUITS, JUNCTION BOXES, SUPPORTS FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, FLOOR SLEEVES, CORE DRILLING, CABLING BOTH FIBER AND COVER, JACKS, TERMINATIONS, COVER PLATES, LABELING, PATCH PANELS, PATCH CORDS, CHANNEL RACKS, VERTICAL AND HORIZONTAL WIRE MANAGEMENT, GROUNDING BUS BARS, RACK MOUNTED GROUND BUS, GROUND CABLING, BONDING TO THE GROUNDING SYSTEM, GROUND CABLE IN THE CABLE AND LADDER TRAY, POWER STRIPS, UPD'S, UPS'S, TESTING AND RELATED MATERIALS FOR A COMPLETE CABLING SYSTEM AS SHOWN HEREIN AND
AS DESCRIBED IN THE SPECIFICATIONS.
27. PROVIDE J-HOOKS WHERE CABLE TRAY IS NOT SHOWN OR IF THERE IS OBSTRUCTION IN THE PATH OF THE CABLE TRAY, OR USE FLEXIBLE CONDUITS (NOT TO EXCEED 10 FEET), JUNCTION BOXES, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, COVER PLATES, LABELING, SUPPORT J-HOOKS AND CONDUITS, AS SHOWN
HEREIN AND AS DESCRIBED IN THE SPECIFICATIONS.
28. PROVIDE 12 PORT WALL MOUNTED COPPER PATCH PANEL I THE EXISTING TR/FACILITY ROOM AND ANOTHER 12 PORT IN EACH NEW TR AND RUN 12-4PR CAT 6A CABLE BETWEEN THESE TR'S TERMINATE AND TEST, LABEL
EACH PORT.
29. PROVIDE MULTI-SENSOR PANORAMIC SECURITY SURVEILLANCE TELEVISION SYSTEM (SSTV) CAMERAS, DVRS/NVRS, STORAGE, SOFTWARE, LICENSES, CONDUITS, JUNCTION BOXES, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, CABLING, COVER, JACKS, TERMINATIONS, COVER PLATES, LABELING, PATCH PANELS, PATCH CORDS, TESTING AND RELATED MATERIALS FOR A COMPLETE OPERATIONAL SSTV SYSTEM AS SHOWN HEREIN
AND AS DESCRIBED IN THE SPECIFICATIONS.
30. PROVIDE CARD READERS, DOOR CONTROLLERS, TR KEYPADS FOR PHYSICAL ACCESS AND CONTROL SYSTEM (PACS), SOFTWARE, LICENSES, CONDUITS, JUNCTION BOXES, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, CABLING, COVER, JACKS, TERMIANTIONS, COVER PLATES, LABELING, TESTING AND RELATED MATERIALS FOR A COMPLETE OPERATIONAL PACS SYSTEM AS SHOWN HEREIN AND AS DESCRIBED IN THE SPECIFICATIONS.
31. PROVIDE NEW FIRE ALARM SYSTEM DEVICES, FIRE ALARM PANEL, NAC PANEL, POWER SUPPLY, FOR A COMPLETE FIRE AND DETECTION SYSTEM, RED CONDUIT AND JUNCTION BOXES, COVERPLATES, LABELING, CABLING BOTH COPPER AND FIBER, PROGRAMMING, SOFTWARE, LICENSES, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, CABLING, COVER, JACKS, TERMINATIONS, TESTING AND RELATED MATERIALS FOR
SPECIFICATIONS.
32. CAMERAS SHALL BE PANORAMIC MULTI0SENSOR AND SHALL MEET THE NATIONAL DEFENSE AUTHORIZATION
ACT-NDAA.
33. IT IS THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE AND INSTALL COPPER PATCH CABLES IN ALL TELECOMMUNICATIONS ROOMS. ONE COPPER PATCH CABLE IS REQUIRED TO SERVE EVERY WORK AREA OUTLET, WIRELESS ACCESS POINT, AND ALL OTHER CONNECTION POINTS SERVED BY OIT NETWORK SWITCHES. THE APPROXIMATE AMOUNT OF PATCH CABLES NEEDED IS 6,500 (VARYING LENGTHS OF 2, 4, AND 8
FEET) TO REACH FROM THE SWITCH TO THE PATCH PANEL.
GENERAL TECHNOLOGY DEMOLITION NOTES
A. ALL EXISTING CONDITIONS - INCLUDING EQUIPMENT, CABINETS, CABLE TRAY, DEVICES, AND CONDUIT - ARE BASED ON THE BEST AVAILABLE INFORMATION AT THE TIME OF SURVEY AND VISUAL INSPECTION.
B. RETURN REMOVED MATERIAL DEEMED SALVAGEABLE BY THE COR. ALL OTHER MATERIAL SHALL BE REMOVED FROM THE PREMISES (E.G., PATCH PANELS, CABLES, COVER PLATES, PATCH CORDS, AND RELATED MATERIAL).
C. EXISTING CABLE TRAY SHALL REMAIN. REMOVE EXISTING CABLING SERVING WORK AREA OUTLETS (WAO). NO ABANDONED CABLING WILL BE ALLOWED TO REMAIN ABOVE THE CEILING. INSTALL NEW CABLE TRAY NEXT TO
THE EXISTING CABLE TRAY.
D. EXISTING CONDUIT AND SURFACE RACEWAY MAY BE REUSED FOR NEW WAO. COORDINATE LOCATION WITH
THE COR.
E. EXISTING TR: ONCE ALL ACTIVE CONNECTIONS TO AN EXISTING TR HAVE BEEN REPLACED BY CONNECTIONS TERMINATED IN THE NEW TR - AND OIT HAS CONFIRMED THAT THERE ARE NO LONGER ANY ACTIVE CONNECTIONS FROM THE EXISTING TR - COORDINATE REMOVAL OF ALL VA OWNED NETWORK SWITCHES.
REMOVE PATCH PANELS AND ALL ASSOCIATED CABLING. BID DEMOLITION AND DISPOSAL OF THE RACKS IN THE TR UNLESS THERE ARE REMAINING NON-NETWORK COMPONENTS WHICH SHALL REMAIN IN PLACE WITH THE
UPS AND POWER SOURCE IN TACT.
1. CONTRACTOR TO REFER TO TELECOMM ROOM PHASING NOTES, SHEETS A-001, FOR ADDITIONAL
INFOMATION.
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/8
/2
:4
:2
P M
C U s e rs
\a ri c h a rd s \D o c u m e n ts
\2 -0
T R
R o o m
D e ta ils a ri c h a rd s P
K P
J .r v t
ET002
TECHNOLOGY GENERAL NOTES,
SYMBOL LEGEND, AND
ABBREVIATIONS
2 106ADR
EHRM INFRASTRUCTURE
UPGRADES
VA ANN ARBOR HEALTHCARE SYSTEM
2215 FULLER ROAD, ANN ARBOR, MI
48105 FEBRUARY 28, 2024
BID DOCUMENTS
506-21-70521-092
JKM
CONDITIONAL NOTE
Docusign Envelope ID: 635BD638-6D8A-48CF-A710-8A74AD2E69A4
7/9/2024 7/9/2024
E
CR
DC ES RX
GFI
J
E
M M
E E
10 10
PANEL 'A' PANEL 'B'
ET5016
A-1,3,5
B-1,3,5
SBB
K
A-2
B-2
A-2
A-2 N
B-2
B-2
A-2
B-2
NORMAL CRITICAL
A
6FIRE RATED PATHWAYS
A-4
A
AA
PANEL A
FIRE RATED PATHWAYS
SSB
CABLE TRAY
RECEPTACLE
NEMA 5-20R
RECEPTACLE
NEMA 5-20R
MOTOR-RATED
SWITCH
"B" PANEL"A" PANEL
CABLE TRAY
RECEPTACLE
NEMA 5-20R
RECEPTACLE
NEMA 5-20R
SSB
1'-0"
LIGHT SWITCH
RECEPTACLE
NEMA 5-20R
RECEPTACLE
NEMA 5-20R
GFCI -
RECEPTACLE
NEMA 5-20R
"B" PANEL
SBB
RECEPTACLE
NEMA 5-20R
NEC REQUIRED WORKING
CLEARANCE, 30" WIDE BY
36" DEEP BY 72" HIGH
RECEPTACLE
NEMA 5-20R
DATA PORT
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:4
:1
P
M C
U s e rs
\a ri c h a rd s \D o c u m e n ts
\2 -0
T R
R o o m
D e ta ils a ri c h a rd s P
K P
J .r v t
ET501
TYPICAL TELECOM ROOM DETAILS
3 106ADR
EHRM INFRASTRUCTURE
UPGRADES
VA ANN ARBOR HEALTHCARE SYSTEM
2215 FULLER ROAD, ANN ARBOR, MI
48105 FEBRUARY 28, 2024
BID DOCUMENTS
506-21-70521-092
JKM
1 THE INDOOR HVAC UNITS – EITHER VARIABLE
REFRIGERANT VOLUME (VRV) UNITS OR
DUCTLESS MINI-SPLIT UNITS – SHALL BE
POWERED FROM THEIR ASSOCIATED
OUTDOOR CONDENSING UNITS. THE
ELECTRICAL CONTRACTOR SHALL PROVIDE
A CIRCUIT TO THE CONDENSING UNIT AS
SHOWN ON SHEET ET601s, INCLUDING THE
RACEWAYS AND CONDUCTORS TO POWER
THE INDOOR UNITS.
2 TELECOMMUNICATIONS CHANNEL RACK,19
INCHES WIDE, 30 INCHES DEEP, 84 INCHES
HIGH, 45RU, WHITE. PROVIDE ORTRONICS
(LEGRAND) MM2073038-W, OR APPROVED
EQUIVALENT. CONTRACTOR SHALL
COORDINATE ADDITIONAL DETAILS
INCLUDING BUT NOT LIMITED TO GROUNDING
AND BONDING DETAILS, DATA ELEVATIONS
AND POWER ELEVATIONS IN THE DRAWINGS.
3 VERTICAL CABLE MANAGEMENT CAGE WITH
DOOR, 6 INCHES WIDE, 84 INCHES HIGH,
45RU, WHITE. PROVIDE ORTRONICS
(LEGRAND) MM20VMD706-W, OR APPROVED
EQUIVALENT.
4 RACK POWER CONNECTION MOUNTED TO
THE CABLE TRAY WITH A MINIMUM OF 12"
SEPARATION BETWEEN THE CABLE TRAY
AND THE POWER CONNECTION. PROVIDE
RACK CONNECTION ACCORDING TO THE
POWER REQUIREMENTS TABLE ON THIS
SHEET. REFER TO CHANNEL
RACK/NETWORK CABINET POWER
CONNECTION DETAILS ON SHEET ET502 AND
RACK POWER ELEVATION AND SCHEMATIC
DIAGRAMS ON SHEET ET505.
5 SECONDARY BONDING BUSBAR TO BE
LOCATED BEHIND OR TO THE SIDE OF THE
RACKS. TELECOMMUNICATIONS EQUIPMENT
SHALL BE BONDED ACCORDING TO THE
GROUNDING AND BONDING DETAILS. REFER
TO DETAILS 3 AND 4 ON SHEET ET503 FOR
MORE INFORMATION.
6 FIRE/SMOKE SLEEVE ASSEMBLIES. PROVIDE
UL LISTED ASSEMBLIES, STI EZ-PATH, SERIES
33 FIRE-RATED PATHWAY, OR APPROVED
EQUIVALENT. INSTALL SLEEVES ABOVE
DOOR HEADER AT AN ELEVATION
COORDINATED TO BE ABOVE THE EXISTING
CEILING HEIGHT IN THE ADJACENT
COORIDOR. REFER TO 400 SERIES ET
SHEETS FOR QUANTITIES.
7 PROVIDE NEW 24 INCH WIDE BY 4-INCH-HIGH
WIRE MESH TRAY AROUND THE ROOM AND
ABOVE THE CHANNEL RACKS, WITH
WATERFALL DROPOUTS INTO EACH RACK, 90
DEGREE CORNERS AND ALL RELATED
FITTINGS. SEE WIRE MESH TRAY DETAIL ON
ET504 FOR MORE INFO. B.O.D.: CABLEOFIL
CF105/600 AND CF150/600 SERIES OR
EQUIVALENT.
8 RECEPTACLES, PROVIDE TWO RECEPTACLE
ON EACH WALL, AS SHOWN 1 FED FROM
PANEL A THE OTHER FROM PANEL B.
9 PLYWOOD BACKBOARD. SEE
ARCHITECTURAL.
10 LIGHTING AND APPLIANCE PANELBOARDS.
PROVIDE PANELS MOUNTED ON CHANNEL
STEEL SUPPORTS. UNLESS NOTED
OTHERWISE ON THE 400 SERIES ET SHEETS,
PANEL 'B' SHALL BE FED FROM A SOURCE
WITH GENERATOR BACKUP, AND PANEL 'A'
SHALL BE FED FROM A NORMAL UTILITY
SOURCE.
11 PROVIDE JUNCTION BOX WITH EMERGENCY
POWER TO THE PACS DOOR CONTROLLER.
12 PROVIDE MULTI SENSOR CAMERA AND
CONNECT TO EXISTING CAMERA SYSTEM.
LOCATION SHOULD BE COORDINATED WITH
THE CHANNEL RACK LAYOUT AND OIT.
13 PROVIDE CABLING FOR VA FURNISHED
WIRELESS ACCESS POINT.
14 PROVIDE GFCI RECEPTACLE NEAR DOOR,
WITH POWER EXTENDED FROM AN EXISTING
CONVENIENCE OUTLET CIRCUIT
ORIGINATING FROM A PANEL NOT IN THE
ROOM.
Scale: 3/8" = 1'-0"
ELECTRICAL FLOOR PLAN - TYPICAL 3-RACK TR
Scale: 3/8" = 1'-0"
ELECTRICAL CEILING PLAN - TYPICAL 3-RACK TR
Scale: 3/8" = 1'-0"
PLAN WEST ELEVATION
Scale: 3/8" = 1'-0"
PLAN NORTH ELEVATION
Scale: 3/8" = 1'-0"
PLAN SOUTH ELEVATION
Scale: 3/8" = 1'-0"
PLAN EAST ELEVATION
PER PHASE CONNECTED LOAD: 2.39 kVA 1.67 kVA 1.67 kVA
SPACE -- 1 41 -- -- 42 1 -- SPACE
SPACE -- 1 39 -- -- 40 1 -- SPACE
SPACE -- 1 37 -- -- 38 1 -- SPACE
SPACE -- 1 35 -- -- 36 1 -- SPACE
SPACE -- 1 33 -- -- 34 1 -- SPACE
SPACE -- 1 31 -- -- 32 1 -- SPACE
SPACE -- 1 29 -- -- 30 1 -- SPACE
SPACE -- 1 27 -- -- 28 1 -- SPACE
SPACE -- 1 25 -- -- 26 1 -- SPACE
SPACE -- 1 23 -- -- 24 1 -- SPACE
SPACE -- 1 21 -- -- 22 1 -- SPACE
SPARE 20 A 1 19 0 0 20
17 0 0 18
2 20 A SPARE
15 0 0 16SURGE PROTECTIVE DEVICE 30 A 3
13 0 0 14
2 20 A SPARE
11 0 0 12 1 20 A PACS J-BOX
9 0 0 10 1 20 A CONDENSATE PUMPSPARE 30 A 3
7 0 0 8 1 20 A SPARE
5 1.67 0 6 1 20 A SPARE
3 1.67 0 4 1 20 A TELECOM ROOM LTGRACK RECEPTACLE 60 A 3
1 1.67 0.72 2 1 20 A TELECOM ROOM RCPT
LOAD NAME BKR P CKT A (kVA) B (kVA) C (kVA) CKT P BKR LOAD NAME
ENCLOSURE: NEMA 1 BRANCH: SEE ONE-LINE EXISTING/NEW: New Construction
MOUNTING: SURFACE FED FROM: LOCATION:
PANEL: A
VOLTAGE: 120/208V, 3PH, 4W MAINS: 100 A MLO AIC:
10,000 AMPS
SYMMETRICAL
PER PHASE CONNECTED LOAD: 2.39 kVA 1.67 kVA 1.67 kVA
SPACE -- 1 41 -- -- 42 1 -- SPACE
SPACE -- 1 39 -- -- 40 1 -- SPACE
SPACE -- 1 37 -- -- 38 1 -- SPACE
SPACE -- 1 35 -- -- 36 1 -- SPACE
SPACE -- 1 33 -- -- 34 1 -- SPACE
SPACE -- 1 31 -- -- 32 1 -- SPACE
SPACE -- 1 29 -- -- 30 1 -- SPACE
SPACE -- 1 27 -- -- 28 1 -- SPACE
SPACE -- 1 25 -- -- 26 1 -- SPACE
SPACE -- 1 23 -- -- 24 1 -- SPACE
SPACE -- 1 21 -- -- 22 1 -- SPACE
SPARE 20 A 1 19 0 0 20 1 20 A SPARE
17 0 0 18 1 20 A SPARE
15 0 0 16 1 20 A SPARESURGE PROTECTIVE DEVICE 30 A 3
13 0 0 14 1 20 A SPARE
11 0 0 12 1 20 A SPARE
9 0 0 10 1 20 A SPARESPARE 30 A 3
7 0 0 8 1 20 A SPARE
5 1.67 0 6 1 20 A SPARE
3 1.67 0 4 1 20 A SPARERACK RECEPTACLE 60 A 3
1 1.67 0.72 2 1 20 A TELECOM ROOM RCPT
LOAD NAME BKR P CKT A (kVA) B (kVA) C (kVA) CKT P BKR LOAD NAME
ENCLOSURE: NEMA 1 BRANCH: SEE ONE-LINE EXISTING/NEW: New Construction
MOUNTING: SURFACE FED FROM: LOCATION:
PANEL: B
VOLTAGE: 120/208V, 3PH, 4W MAINS: 100 A MLO AIC:
10,000 AMPS
SYMMETRICAL
LUMINAIRE SCHEDULE
TYPE DESCRIPTION MOUNTING LAMP DRIVER VOLTAGE WATTS MANUFACTURER MODEL NUMBER
A 4' LINEAR LED STRIPLIGHT WITH FROSTED
LENS
CHAIN
SUSPEND
LED; 4,585
LUMENS;
80 CRI;
4000K
ELECTRONIC LED
DRIVER
120.00 V 35 W CREE LS4-40L-840-UL-10V
A. THIS SHEET IS INTENDED TO PROVIDE
DETAILED INFORMATION FOR THE TYPICAL
TELECOMMUN…
This is the start of the file's text. The full file is on GovTribe.