Attachment 06_Drawings 07122024 Part 5.pdf

PDF 12 MB Posted

Attached to
Z2DA--506-21-705 EHRM Infrastructure Upgrades - Ann Arbor, MI - Construction (VA-25-00001864)
Solicitation number
36c77624b0025
Issued by

About this file

This document appears to be a set of drawings related to the federal contract opportunity for the construction of Electronic Health Record Modernization (EHRM) infrastructure upgrades at the Ann Arbor VA Medical Center. The contract opportunity is solicitation number 36c77624b0025, issued by the Department of Veterans Affairs Technology Acquisition Center in Austin. The drawings provide technical details and specifications for the construction work required under this contract. No further details about the required products, services, pricing, or other key contract terms are included in this particular document, as it appears to be solely a set of technical drawings.

View the file

Other files

File Type Posted
S07 - Complete Abstract of Bids OF 1419- Ann Arbor EHRM 10 16 2024.pdf PDF
S07 - Complete Abstract of Bids OF 1419- Ann Arbor EHRM.pdf PDF
IFB 36C77624B0025 Amendment 0005 Asbestos Info.pdf PDF
IFB 36C77624B0025 Amendment 0004.pdf PDF
36C77624B0025 Amendment 0003.pdf PDF
S05 Ann_Arbor CMS_Question_Matrix_V3.xlsx XLSX spreadsheet
Attachment 12 - EHRM Window Screen Details.pdf PDF
Attachment 08 - 075423 TPO Roofing.pdf PDF
Attachment 14 - MS Versions of PDFs.zip ZIP file
Attachment 07 - 013323 Shop Drawings_CA Edits 2.pdf PDF
Attachment 02 - 1E.ET472.pdf PDF
Attachment 06 - 000110 TOC - updated TPO and 236323.pdf PDF
Attachment 11 - CABLE MATRICES.pdf PDF
Attachment 04 - 21-092 SubReg 100 Percent.pdf PDF
Attachment 10 - Addendum 1.pdf PDF
Attachment 09 -236323 AirCooledClosedCircuitFluidCooler.pdf PDF
36C77624B0025 0002.docx DOCX document
Attachment 05 - 21-092-Pre-Bid RFIs_AE responses 1.pdf PDF
Attachment 15 - DB WR GD No MI20240100 09062024.pdf PDF
Attachment 03 - 1W.A-491_Addendum 1.pdf PDF
Attachment 01 - Q and A Results Ann Arbor MI.docx DOCX document
Attachment 13 - G-003_Addendum 1.pdf PDF
S04 - Pre-Bid Site Visit Sign-in Sheet - 09 04 2024.pdf PDF
S04 - Virtual Visit Attendee List - 08 29 2024.docx DOCX document
36C77624B0025 Ammendment 0001.docx DOCX document
S04 -Virtual and Site Visit Agenda - IFB 2024 08 29 2024.doc DOC document
S04 - Pre-Bid Site Visit Sign-in Sheet - 09 04 2024.docx DOCX document
Attachment 02_Drawings 07122024 Part 1.pdf PDF
Attachment 04_Drawings 07122024 Part 3.pdf PDF
Attachment 11 Division Breakdown Template.xls XLS spreadsheet
Attachment 05_Drawings 07122024 Part 4.pdf PDF
Attachment 08_Limitations on Subcontracting - Construction.docx DOCX document
Attachment 03_Drawings 07122024 Part 2.pdf PDF
Attachment 07_Drawings 07122024 Part 6.pdf PDF
Attachment 09_JA Ann Arbor Final REDACTED.pdf PDF
Attachment 10 DB Wages General Decision Number MI20240100 07 26 24.pdf PDF
Attachment 01_Specifications Ann Arbor MI.pdf PDF
36C77624B0025_1.pdf PDF
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Engineers Architects

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

CAMPUS IMAGE

# 1E, 1W, 2, 3, 15, 22, 28, 29, 30, 31, 32, 37

U.S. DEPARTMENT OF VETERANS AFFAIRS

/2

/2

:5

:1

P

M C

U s e rs \a p u lle n \D o c u m e n ts \A

-0

A n n

A rb o r-

E H

R M

S it e

P la n a p u lle n V

D X

T .r v t

GE.001

COVER

1 1ANP

VA ANN ARBOR HEALTHCARE SYSTEM

2215 FULLER ROAD, ANN ARBOR, MI

48105 FEBRUARY 28, 2024

BID DOCUMENTS

506-21-70521-092

EHRM INFRASTRUCTURE UPGRADES

VA ANN ARBOR HEALTHCARE SYSTEM

2215 FULLER ROAD, ANN ARBOR, MI 48105

VA PROJECT #: 506-21-705

JAB

EHRM INFRASTRUCTURE

UPGRADES

NAME AND TITLE SIGNATURE

VA SIGNATURE BLOCK

VOLUME 4 OF 4

DRAWING LIST - VOLUME 4 OF 4

GENERAL

GE.001 COVER 1 1

ELECTRICAL

ET001 ELECTRICAL GENERAL NOTES, SYMBOL LEGENDS, AND ABBREVIATIONS 1 106

ET002 TECHNOLOGY GENERAL NOTES, SYMBOL LEGEND, AND ABBREVIATIONS 2 106

ET501 TYPICAL TELECOM ROOM DETAILS 3 106

ET502 ELECTRICAL AND TECHNOLOGY DETAILS 4 106

ET503 TECHNOLOGY DETAILS 5 106

ET504 TECHNOLOGY DETAILS 6 106

ET505 ELECTRICAL CHANNEL RACK DETAILS 7 106

ET506 ELECTRICAL AND TECHNOLOGY CHANNEL RACK DETAILS 8 106

ES101 CAMPUS FIBER DISTRIBUTION DIAGRAM 9 106

1E.ET401 BUILDING 1E, BASEMENT, TELEPHONE SWITCH ROOM CB07 10 106

1E.ET402 BUILDING 1E, BASEMENT, DELTA STACK, TELECOM ROOM DB60A 11 106

1E.ET402.A BUILDING 1E, BASEMENT, DELTA STACK, TELECOM ROOM DB60A - ELEVATIONS 12 106

1E.ET403 BUILDING 1E, BASEMENT, ECHO STACK, TELECOM ROOM EB60A 13 106

1E.ET403.A BUILDING 1E, BASEMENT, ECHO STACK, TELECOM ROOM EB60A - ELEVATIONS 14 106

1E.ET411 BUILDING 1E, FIRST FLOOR, DELTA STACK, TELECOM ROOM D178A 15 106

1E.ET411.A BUILDING 1E, FIRST FLOOR, DELTA STACK, TELECOM ROOM D178A - ELEVATIONS 16 106

1E.ET412 BUILDING 1E, FIRST FLOOR, ECHO STACK, TELECOM ROOM E178A 17 106

1E.ET412.A BUILDING 1E, FIRST FLOOR, ECHO STACK, TELECOM ROOM E178A - ELEVATIONS 18 106

1E.ET413 BUILDING 1E, FIRST FLOOR, TELECOM ROOM L133 19 106

1E.ET413.A BUILDING 1E, FIRST FLOOR, TELECOM ROOM L133 - ELEVATIONS 20 106

1E.ET431 BUILDING 1E, THIRD FLOOR, DELTA STACK, TELECOM ROOM D312A 21 106

1E.ET431.A BUILDING 1E, THIRD FLOOR, DELTA STACK, TELECOM ROOM D312A - ELEVATIONS 22 106

1E.ET432 BUILDING 1E, THIRD FLOOR, ECHO STACK, TELECOM ROOM E321A 23 106

1E.ET432.A BUILDING 1E, THIRD FLOOR, ECHO STACK, TELECOM ROOM E321A - ELEVATIONS 24 106

1E.ET451 BUILDING 1E, FIFTH FLOOR, DELTA STACK, TELECOM ROOM D530A 25 106

1E.ET451.A BUILDING 1E, FIFTH FLOOR, DELTA STACK, TELECOM ROOM D530A - ELEVATIONS 26 106

1E.ET452 BUILDING 1E, FIFTH FLOOR, ECHO STACK, TELECOM ROOM E530A 27 106

1E.ET452.A BUILDING 1E, FIFTH FLOOR, ECHO STACK, TELECOM ROOM E530A - ELEVATIONS 28 106

1E.ET471 BUILDING 1E, SEVENTH FLOOR, DELTA STACK, TELECOM ROOM D712A 29 106

1E.ET471.A BUILDING 1E, SEVENTH FLOOR, DELTA STACK, TELECOM ROOM D712A - ELEVATIONS 30 106

1E.ET472 BUILDING 1E, SEVENTH FLOOR, ECHO STACK, TELECOM ROOM E718A 31 106

1E.ET472.A BUILDING 1E, SEVENTH FLOOR, ECHO STACK, TELECOM ROOM E718A - ELEVATIONS 32 106

1W.ET401 BUILDING 1W, BASEMENT ELECTRICAL EQUIPMENT AB00 33 106

1W.ET402 BUILDING 1W, BASEMENT, ALPHA STACK, TELECOM ROOM AB29 34 106

1W.ET403 BUILDING 1W, BASEMENT, BRAVO STACK, TELECOM ROOM BB26 35 106

1W.ET403.A BUILDING 1W, BASEMENT, BRAVO STACK, TELECOM ROOM BB26 - ELEVATIONS 36 106

1W.ET404 BUILDING 1W, BASEMENT, TELECOM ROOM BB94 37 106

1W.ET411 BUILDING 1W, FIRST FLOOR, ALPHA STACK, TELECOM ROOM A149 38 106

1W.ET412 BUILDING 1W, FIRST FLOOR, BRAVO STACK, TELECOM ROOM B143 39 106

1W.ET412.A BUILDING 1W, FIRST FLOOR, BRAVO STACK, TELECOM ROOM B143 - ELEVATIONS 40 106

1W.ET421 BUILDING 1W, SECOND FLOOR, ALPHA STACK, TELECOM ROOM A237 41 106

1W.ET422 BUILDING 1W, SECOND FLOOR, BRAVO STACK, TELECOM ROOM B231 42 106

1W.ET422.A BUILDING 1W, SECOND FLOOR, BRAVO STACK, TELECOM ROOM B231 - ELEVATIONS 43 106

1W.ET431 BUILDING 1W, THIRD FLOOR, ALPHA STACK, TELECOM ROOM A339 44 106

1W.ET432 BUILDING 1W, THIRD FLOOR, BRAVO STACK, TELECOM ROOM B310B 45 106

1W.ET432.A BUILDING 1W, THIRD FLOOR, BRAVO STACK, TELECOM ROOM B310B - ELEVATIONS 46 106

1W.ET441 BUILDING 1W, FOURTH FLOOR, ALPHA STACK, TELECOM ROOM A437 47 106

1W.ET442 BUILDING 1W, FOURTH FLOOR, BRAVO STACK, TELECOM ROOM B432A 48 106

1W.ET442.A BUILDING 1W, FOURTH FLOOR, BRAVO STACK, TELECOM ROOM B432A - ELEVATIONS 49 106

1W.ET451 BUILDING 1W, FIFTH FLOOR, ALPHA STACK, TELECOM ROOM A535 50 106

1W.ET452 BUILDING 1W, FIFTH FLOOR, BRAVO STACK, TELECOM ROOM B525A 51 106

1W.ET452.A BUILDING 1W, FIFTH FLOOR, BRAVO STACK, TELECOM ROOM B525A - ELEVATIONS 52 106

1W.ET461 BUILDING 1W, SIXTH FLOOR, ALPHA STACK, TELECOM ROOM A633A 53 106

DRAWING LIST - VOLUME 4 OF 4

1W.ET462 BUILDING 1W, SIXTH FLOOR, BRAVO STACK, TELECOM ROOM B618A 54 106

1W.ET462.A BUILDING 1W, SIXTH FLOOR, BRAVO STACK, TELECOM ROOM B618A - ELEVATIONS 55 106

1W.ET471 BUILDING 1W, SEVENTH FLOOR, ALPHA STACK, TELECOM ROOM A753 56 106

1W.ET472 BUILDING 1W, SEVENTH FLOOR, BRAVO STACK, TELECOM ROOM B722A 57 106

1W.ET472.A BUILDING 1W, SEVENTH FLOOR, BRAVO STACK, TELECOM ROOM B722A - ELEVATIONS 58 106

1W.ET481 BUILDING 1W, EIGHTH FLOOR, ALPHA STACK, TELECOM ROOM A843A 59 106

1W.ET482 BUILDING 1W, EIGHTH FLOOR, BRAVO STACK, TELECOM ROOM B812 60 106

1W.ET482.A BUILDING 1W, EIGHTH FLOOR, BRAVO STACK, TELECOM ROOM B812 - ELEVATIONS 61 106

1W.ET491 BUILDING 1W, NINTH FLOOR, ALPHA STACK, TELECOM ROOM A921A 62 106

28.ET401 BUILDING 28, BASEMENT, FOXTROT STACK, TELECOM ROOM FG86 63 106

28.ET411 BUILDING 28, FIRST FLOOR, MAIN COMPUTER ROOM A180 - POWER 64 106

28.ET414 BUILDING 28, FIRST FLOOR, FOXTROT STACK, TELECOM ROOM F152 65 106

28.ET421 BUILDING 28, SECOND FLOOR, FOXTROT STACK, TELECOM ROOM F224A 66 106

2.ET421 BUILDING 2, FULLER HOUSE, SECOND FLOOR, TELECOM ROOM 210 67 106

3.ET401 BUILDING 3, FACILITY MANAGEMENT & SAFETY, BASEMENT, TELECOM ROOM 02C 68 106

15.ET401 BUILDING 15, NORTH METER HOUSE, FIRST FLOOR, TELECOM ROOM 15-2 69 106

22.ET401 BUILDING 22, RESEARCH BUILDING, GROUND FLOOR, TELECOM ROOM G12 70 106

22.ET411 BUILDING 22, RESEARCH BUILDING, FIRST FLOOR, TELECOM ROOM 08 71 106

22.ET411.A BUILDING 22, RESEARCH BUILDING, ROOF PLAN 72 106

29.ET411 BUILDING 29, EAST PARKING STRUCTURE, LEVEL A, TELECOM ROOM AA6 73 106

29.ET421 BUILDING 29, EAST PARKING STRUCTURE, LEVEL B, TELECOM ROOM EPS-B2 74 106

30.ET421 BUILDING 30, WEST PARKING STRUCTURE, LEVEL B, TELECOM ROOM WPS-B02 75 106

30.ET441 BUILDING 30, WEST PARKING STRUCTURE, LEVEL D, TELECOM ROOM WPS-D02 76 106

31.ET401 BUILDING 31, RESEARCH BUILDING, BASEMENT, TELECOM ROOM 27 77 106

31.ET401.A BUILDING 31, RESEARCH BUILDING, BASEMENT, TELECOM ROOM 27 - ELEVATIONS 78 106

31.ET411 BUILDING 31, RESEARCH BUILDING, FIRST FLOOR, TELECOM ROOM 117 79 106

31.ET411.A BUILDING 31, RESEARCH BUILDING, FIRST FLOOR, TELECOM ROOM 117 - ELEVATIONS 80 106

31.ET421 BUILDING 31, RESEARCH BUILDING, SECOND FLOOR, TELECOM ROOM 218 81 106

31.ET421.A BUILDING 31, RESEARCH BUILDING, SECOND FLOOR, TELECOM ROOM 218 - ELEVATIONS 82 106

32.ET401 BUILDING 32, ENERGY CENTER, BASEMENT, TELECOM ROOM 003 83 106

32.ET401.A BUILDING 32, ENERGY CENTER, BASEMENT, TELECOM ROOM 003 - ELEVATIONS 84 106

32.ET431 BUILDING 32, ENERGY CENTER , FIRST FLOOR CHILLER ROOM 101 AND ROOF ELECTRICAL PLAN 85 106

37.ET401 BUILDING 37, ADMINISTRATIVE BUILDING, BASEMENT, TELECOM ROOM 006 86 106

37.ET401.A BUILDING 37, ADMINISTRATIVE BUILDING, BASEMENT, TELECOM ROOM 006 - ELEVATIONS 87 106

37.ET411 BUILDING 37, ADMINISTRATIVE BUILDING, FIRST FLOOR, TELECOM ROOM 118 88 106

37.ET411.A BUILDING 37, ADMINISTRATIVE BUILDING, FIRST FLOOR, TELECOM ROOM 118 - ELEVATIONS 89 106

37.ET421 BUILDING 37, ADMINISTRATIVE BUILDING, SECOND FLOOR, TELECOM ROOM 217 90 106

37.ET421.A BUILDING 37, ADMINISTRATIVE BUILDING, SECOND FLOOR, TELECOM ROOM 217 - ELEVATIONS 91 106

37.ET431 BUILDING 37, ADMINISTRATIVE BUILDING, THIRD FLOOR, TELECOM ROOM 317 92 106

37.ET431.A BUILDING 37, ADMINISTRATIVE BUILDING, THIRD FLOOR, TELECOM ROOM 317 - ELEVATIONS 93 106

1.ET601 BUILDING 1E, 1W, AND 28 FIBER RISER DIAGRAM 94 106

1.ET602 MECHANICAL EQUIPMENT SCHEDULE AND BUILDING 1E AND 28 ELECTRICAL RISER DIAGRAMS 95 106

1.ET603 BUILDING 1W ELECTRICAL RISER DIAGRAM 96 106

1.ET604 BUILDING 1W EXISTING A STACK PHONE, CODE ONE, PA, PACS RISERS AND PACS PANELS

SCHEDULE

97 106

2.ET601 MECHANICAL EQUIPMENT SCHEDULE, SINGLE LINE AND FIBER RISER DIAGRAM 98 106

3.ET601 MECHANICAL EQUIPMENT SCHEDULE, SINGLE LINE AND FIBER RISER DIAGRAM 99 106

15.ET601 MECHANICAL EQUIPMENT SCHEDULE, SINGLE LINE AND FIBER RISER DIAGRAM 100 106

22.ET601 MECHANICAL EQUIPMENT SCHEDULE, SINGLE LINE AND FIBER RISER DIAGRAM 101 106

29.ET601 MECHANICAL EQUIPMENT SCHEDULE, SINGLE LINE AND FIBER RISER DIAGRAM 102 106

30.ET601 MECHANICAL EQUIPMENT SCHEDULE, SINGLE LINE AND FIBER RISER DIAGRAM 103 106

31.ET601 MECHANICAL EQUIPMENT SCHEDULE, SINGLE LINE AND FIBER RISER DIAGRAM 104 106

32.ET601 MECHANICAL EQUIPMENT SCHEDULE, SINGLE LINE AND FIBER RISER DIAGRAM 105 106

37.ET601 MECHANICAL EQUIPMENT SCHEDULE, SINGLE LINE AND FIBER RISER DIAGRAM 106 106

DocuSign Envelope ID: F024BA2E-7BBC-4DFF-BDAC-B255F954C023

2/26/2024

120V DUPLEX RECEPTACLE

RECEPTACLE MODIFIERS:

AC: 3" ABOVE COUNTERTOP/BACKSPLASH

GFI: GROUND FAULT CURRENT INTERRUPTER

WP: WEATHERPROOF ENCLOSURE

DED: DEDICATED CIRCUIT

120V DUPLEX RECEPTACLE EMERGENCY OUTLET

AND COVER PLATE SHALL BE RED IN COLOR

120V QUADRUPLEX RECEPTACLE

120V QUADRUPLEX RECEPTACLE EMERGENCY

OUTLET AND COVER PLATE SHALL BE RED IN COLOR

JUNCTION BOX, WALL MOUNTED, PURPOSE AS NOTED

DISCONNECT SWITCH NON-FUSED

DISCONNECT SWITCH FUSED

SINGLE POLE WALL SWITCH: 48" AFF STANDARD UNO

SYMBOL HEIGHT DESCRIPTION

18"

18"

18"

18"

AS

NOTED

72" TOP

72" TOP

SWITCH MODIFIERS:

M: MOTOR-RATED

48"

ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.

TOP: HEIGHT TO TOP OF DEVICE

ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.

SPECIAL RECEPTACLE, REFER TO ET501 FOR NEMA

TYPE

EQUIPMENT CONNECTION

AS

NOTED

E

18"

120V DUPLEX RECEPTACLE FLOOR BOX

120V DUPLEX RECEPTACLE EMERGENCY FLOOR BOX

OUTLET AND COVER PLATE SHALL BE RED IN COLOR

120V QUADRUPLEX RECEPTACLE FLOOR BOX

120V QUADUPLEX RECEPTACLE EMERGENCY

FLOOR BOX OUTLET AND COVER PLATE SHALL BE

RED IN COLOR

CLNG

J

J

J

JUNCTION BOX, CEILING MOUNTED, PURPOSE AS

NOTED

JUNCTION BOX, FLOOR MOUNTED, PURPOSE AS

NOTED

120V SIMPLEX RECEPTACLE18"

2' X 2' RECESSED ARCHITECTURAL TROFFER

2' X 4' RECESSED ARCHITECTURAL TROFFER

SYMBOL

HEIGHT

AFF * DESCRIPTION

--- 2' X 4' RECESSED FLAT LENS TROFFER

2' LINEAR - WALL MOUNTED

7'-0"

CENTER

4' LINEAR - WALL MOUNTED

7'-0"

CENTER

WALL SCONCE

6'-0"

CENTER

6" DIAMETER RECESSED DOWNLIGHT---

EXIT SIGN - WALL MOUNTED

EXIT SIGN - CEILING MOUNTED---

7'-5"

BOTTOM

SINGLE POLE WALL SWITCH

SWITCH MODIFIERS:

OS: OCCUPANCY SENSOR, LOW VOLTAGE,

DUAL TECHNOLOGY

VS: VACANCY SENSOR, LOW VOLTAGE,

DUAL TECHNOLOGY

DR: DUAL RELAY

VSD: VACANCY SENSOR, LINE VOLTAGE, DIMMER

OSD: OCCUPANCY SENSOR, LINE VOLTAGE, DIMMER

LV: LOW VOLTAGE

LVD: LOW VOLTAGE DIMMER

D: LINE VOLTAGE DIMMER

T: DIGITAL TIMER

K: KEYED

3: 3 WAY

4: 4 WAY

48"

CENTER

OCCUPANCY SENSOR, LOW VOLTAGE,

DUAL TECHNOLOGY - CEILING MOUNTED

--- LOW VOLTAGE LIGHTING CONTROL DEVICE

OCCUPANCY SENSOR, LOW VOLTAGE, DUAL

TECHNOLOGY - WALL/CORNER MOUNTED

EMERGENCY LIGHT BATTERY

OPERATED - WALL MOUNTED

7'-6"

CENTER

RC

* - ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.

LIGHT LEVEL SENSOR, SINGLE ZONE

DIMMING CLOSED LOOP - CEILING MOUNTED

--- LOW VOLTAGE LIGHTING CONTROL

DEVICE WITH 0-10V DIMMING

RCD

OS

OS

LS

4' LINEAR STRIP - SUSPENDED---

L L

SPKR SPEAKER

SP SPARE

SR SURFACE RACEWAY

SS STAINLESS STEEL

SSW SELECTOR SWITCH

STD STANDARD

SURF SURFACE MOUNTED

SW SWITCH

SWBD SWITCHBOARD

SYM SYMMETRICAL

SYS SYSTEM

TC TIMECLOCK

TEL TELEPHONE

TEL/DATA TELEPHONE/DATA

TERM TERMINAL

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TR TAMPER RESISTANT

T-STAT THERMOSTAT

TTB TELEPHONE TERMINAL BOARD

TTC TELEPHONE TERMINAL CABINET

TV TELEVISION

TYP TYPICAL

UC UNDER COUNTER

UE UNDERGROUND ELECTRICAL

UG UNDERGROUND

UH UNIT HEATER

UL UNDERWRITER'S LABORATORY

UT UNDERGROUND TELEPHONE

UTP UNSHIELDED TWISTED PAIR

UTIL UTILITY

UV UNIT VENTILATOR OR

ULTRAVIOLET

UPS UNINTERUPTABLE POWER

SUPPLY

V VOLT

VA VOLT-AMPERES

VERT VERTICAL

VFD VARIABLE FREQUENCY DRIVE

VOL VOLUME

W WATT

W/ WITH

WH WATER HEATER

W/O WITHOUT

WP WEATHERPROOF

XFMR TRANSFORMER

XFR TRANSFER

ANGLE

@ AT

DELTA

' FEET

" INCHES

# NUMBER

Φ PHASE

C CENTER LINE

P PLATE

MTR MOTOR, MOTORIZED

MTS MANUAL TRANSFER SWITCH

NA NOT APPLICABLE

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURER'S ASSOCIATION

NFDS NON-FUSED SAFETY DISCONNECT

SWITCH

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OH OVERHEAD

OL OVERLOAD

PA PUBLIC ADDRESS

PB PULL BOX OR PUSHBUTTON

PBPU PREFABRICATED BEDSIDE PATIENT

UNIT

PCB POLYCHLORINATED BIPHENYL

PC PHOTOELECTRIC CELL

PDU POWER DISTRIBUTION UNIT

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PIV POST INDICATING VALVE

PNL PANEL

POE POWER-OVER-ETHERNET

PR PAIR

PRI PRIMARY

PROJ PROJECTION

PRV POWER ROOF VENTILATOR

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE (CONDUIT)

PWR POWER

QTY QUANTITY

R RELOCATE/RELOCATED

RCP REFLECTED CEILING PLAN

RCPT RECEPTACLE

REQD REQUIRED

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

RTU ROOF TOP UNIT

SC SURFACE CONDUIT

SEC SECONDARY

SF SQUARE FEET/FOOT

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SIM SIMILAR

S/N SOLID NEUTRAL

SPEC SPECIFICATION

1P 1 POLE (2P, 3P, 4P, ETC.)

1PH 1 PHASE

2/C TWO-CONDUCTOR (3/C, 4/C, ETC.)

2W TWO-WIRE (3W, 4W, ETC.)

3PH 3 PHASE

A AMPERE

AAP ALARM ANNUNCIATOR PANEL

AC ABOVE COUNTER

AIR CONDITIONER

ALTERNATING CURRENT

ACC ACCESSIBLE

ACLG ABOVE CEILING

ADO AUTOMATIC DOOR OPENER

A/E ARCHITECT/ENGINEER

AF AMP FRAME

AFC AVAILABLE FAULT CURRENT (KILOAMPS)

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AFI ARC FAULT CIRCUIT INTERRUPTER

AHJ AUTHORITY HAVING JURISDICTION

AHU AIR HANDLING UNIT

AIC AMPERE INTERRUPTING CAPACITY

AL ALUMINUM

ALT ALTERNATE

AMP AMPERE

APPROX APPROXIMATELY

ARCH ARCHITECT, ARCHITECTURAL

AT AMP TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AV AUDIO VISUAL

AWG AMERICAN WIRE GAUGE

BAS BUILDING AUTOMATION SYSTEM

BATT BATTERY

BC BARE COPPER

BD BOARD

BFF BELOW FINISHED FLOOR

BLDG BUILDING

BMS BUILDING MANAGEMENT SYSTEM

BYP BYPASS

C CONDUIT

CAB CABINET

CALC CALCULATED

CAP CAPACITY

CAT CATALOG, CATEGORY

CATV COMMUNITY ANTENNA TELEVISION

CB CIRCUIT BREAKER

CCR CONTROL CONTACTOR

CCT CORRELATED COLOR TEMPERATURE

CCTV CLOSED CIRCUIT TELEVISION

cd CANDELA

CD CONSTRUCTION DOCUMENTS

CF CONTRACTOR-FURNISHED

CKT CIRCUIT

CLG CEILING

CO CONTRACTING OFFICER

COAX COAXIAL CABLE

COMM COMMUNICATION

CONN CONNECTION

CONST CONSTRUCTION

CONT CONTINUATION OR CONTINUOUS

CONTR CONTRACTOR

COORD COORDINATE

COR CONTRACTING OFFICER'S

REPRESENTATIVE

CPT CONTROL POWER TRANSFORMER

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CTR CENTER

CU COPPER

CU FT CUBIC FEET

D DEMOLITION

dB DECIBEL

DB DIRECT BURIAL

DC DIRECT CURRENT

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLISH/DEMOLITION

DEPT DEPARTMENT

DIA DIAMETER

DISC DISCONNECT

DIST DISTRIBUTION

DN DOWN

DS SAFETY DISCONNECT SWITCH

DT DOUBLE THROW

DWG DRAWING

EC ELECTRICAL CONTRACTOR

EG EQUIPMENT GROUND

ELEC ELECTRIC, ELECTRICAL

ELEV ELEVATOR

EM EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMS ENERGY MANAGEMENT SYSTEM

EMT ELECTRICAL METALLIC TUBING

EPO EMERGENCY POWER OFF

EQUIP EQUIPMENT

ESMT EASEMENT

ETR EXISTING TO REMAIN

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WALL HEATER

ELECTRIC WATER HEATER

EX EXISTING

EXP EXPLOSION PROOF

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FCU FAN COIL UNIT

FIXT FIXTURE

FLR FLOOR

FU FUSE

FUDS FUSED SAFETY DISCONNECT

SWITCH

FVR FULL VOLTAGE REVERSING

FVNR FULL VOLTAGE NON-REVERSING

GAL GALLON

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEN GENERATOR

GFI GROUND FAULT CIRCUIT INTERRUPTER

GND GROUND

GRS GALVANIZED RIGID STEEL (CONDUIT)

GYP BD GYPSUM BOARD

HID HIGH-INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HTR HEATER

HV HIGH VOLTAGE

HVAC HEATING, VENTILATING AND AIR

CONDITIONING

HW HARD WIRED

IES ILLUMINATION ENGINEERING SOCIETY

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

IR INFRARED

I/W INTERLOCK WITH

IWH INSTANTANEOUS WATER HEATER

J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT-AMPERE

KVAR KILOVOLT-AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

LED LIGHT-EMITTING DIODE

LF LINEAR FEET/FOOT

LM LUMEN

LRA LOCKED ROTOR AMPS

LT LIGHT

LTG LIGHTING

LTNG LIGHTNING

LV LOW VOLTAGE

MATV MASTER ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MC MECHANICAL CONTRACTOR

METAL-CLAD (CONDUIT)

MCA MINIMUM CIRCUIT AMPACITY

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MFR MANUFACTURER

MFS MAIN FUSED DISCONNECT SWITCH

MH MANHOLE

MIC MICROPHONE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MOA MULTIOUTLET ASSEMBLY

MSBD MAIN SWITCHBOARD

MT MOUNT

A1 b

E1 c d

T1

'LPN'

THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER OR AN UPPER

CASE LETTER AND NUMBER.

THE SWITCH DESIGNATION (IF NEEDED) IS INDICATED BY A LOWER CASE LETTER.

EXAMPLE: LIGHTING FIXTURE TYPE 'A1' IS CONTROLLED BY SWITCH 'b'.

EXIT SIGNS: STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING

MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES

DIRECTIONAL ARROW ON ILLUMINATED FACE(S).

DEVICES: THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.

THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.

TRANSFORMERS: THE TRANSFORMER TYPE IS INDICATED BY A NUMBER

FOLLOWING THE UPPER CASE LETTER 'T'. SEE THE TRANSFORMER SCHEDULE OR

THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND

REQUIREMENTS.

PANELBOARDS: PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING

SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR

DESIGNATION CODES.

SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE

NUMBER INDICATED IN THE HEXAGON.

HOME RUN TO BRANCH CIRCUIT PANEL: THE PANEL DESIGNATION AND CIRCUIT

DESIGNATION ARE SHOWN ADJACENT TO THE HOME RUN ARROW.

CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL

SCHEDULE WITH THE CORRESPONDING PANEL AND CIRCUIT DESIGNATION.

SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE

A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.

'LPN'-1,3,5

EXAMPLE 1: WALL MOUNTED EXIT SIGN TYPE 'E1' WITH SINGLE FACE

AND DIRECTIONAL ARROW.

EXAMPLE 2: CEILING MOUNTED EXIT SIGN TYPE 'E2' WITH DOUBLE

FACE AND DIRECTIONAL ARROWS.

E2

EXAMPLE: SPLIT DUPLEX RECEPTACLE; ONE RECEPTACLE OUTLET IS

CONTROLLED BY SWITCH 'c'.

EXAMPLE: SINGLE POLE SWITCH 'd' TO CONTROL LIGHTING FIXTURES INDICATED BY 'd'.

EXAMPLE: TRANSFORMER TYPE 'T1'.

EXAMPLE: HOME RUN TO PANELBOARD 'LPN'; CIRCUITS 1, 3, 5.

# DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE

NOTE NUMBER INDICATED IN THE SQUARE.

A. PRIOR TO SUBMITTING PROPOSAL, BIDDER SHALL EXAMINE ALL GENERAL CONSTRUCTION DRAWINGS.

B. CERTAIN REMODELING OF ELECTRICAL FACILITIES WILL BE REQUIRED IN THE EXISTING BUILDING. EXISTING CONDUIT RUNS ARE GENERALLY NOT SHOWN. ALTHOUGH A FULL ATTEMPT HAS BEEN MADE TO SHOW SOME EXISTING CONDITIONS, OF WHICH INFORMATION HAS BEEN TAKEN FROM EXISTING RECORD DRAWINGS OF THIS PROJECT. THE DRAWINGS SHOWING LOCATION OF EXISTING EQUIPMENT, OUTLETS, FIXTURES, ETC., IN EXISTING

AREAS ARE APPROXIMATE ONLY (FIELD VERIFY).

C. BRANCH CIRCUITS SHALL BE REUSED WHERE PRACTICAL AND SHALL, IN ADDITION, BE REMODELED AS

REQUIRED. THE CONTRACTOR SHALL CONCEAL ALL WORK WHERE POSSIBLE.

D. EXISTING ELECTRICAL WIRING WHICH WILL NOT BE MADE OBSOLETE AND WHICH WILL BE DISTURBED DUE TO CONSTRUCTION CHANGES REQUIRED BY THIS CONTRACT SHALL BE RESTORED TO OPERATING CONDITION, AS REQUIRED AND/OR DIRECTED. WHERE REQUIRED, SHOWN AND/OR DIRECTED, OUTLETS AND CONDUIT RUNS SHALL BE RELOCATED. IN SOME CASES IT MAY BE NECESSARY TO EXTEND CONDUITS AND PULL IN NEW WIRING OR INSTALL JUNCTION BOXES AND SPLICE IN NEW WIRING OR REPLACE OLD WIRING WITH NEW.

E. OUTLETS FROM WHICH FIXTURES, SWITCHES, RECEPTACLES, AND/OR OTHER ELECTRICAL DEVICES ARE MOVED AND WHICH ARE NOT REPLACED OR REUSED SHALL BE REMOVED OR, IF IT IS NOT POSSIBLE TO REMOVE, PLACE A BLANK COVER ON THE OUTLET BOX. WHERE OUTLETS, BOXES, ETC., ARE COMPLETELY REMOVED, THE

CONTRACTOR SHALL CUT OFF CONDUITS AND REMOVE WIRING.

F. WHERE EXISTING LIGHT FIXTURES ARE TO BE REUSED, THE ELECTRICAL CONTRACTOR SHALL CLEAN AND REPLACE LAMPS, REPAIR OR REPLACE DEFECTIVE PARTS, LENS, BALLAST, ETC. AS REQUIRED.

G. WHERE CONDUITS EXTENDING THROUGH FLOORS ARE TO BE ABANDONED, THE CONTRACTOR SHALL CUT AND

CAP OR PLUG CONDUIT, THAT IT WILL NOT PROTRUDE ABOVE THE FLOOR.

H. WHERE EXISTING CONDUIT IS TO BE ABANDONED, THE CONDUIT SHALL BE REMOVED IF IT IS EXPOSED, IN A CRAWL SPACE OR IN AN ACCESSIBLE CEILING. WHERE IT IS IMPOSSIBLE TO REMOVE THE CONDUIT, IT SHALL BE

CUT OFF AND CAPPED OR PLUGGED.

I. THE CONTRACTOR SHALL BE HELD FULLY RESPONSIBLE FOR THE PROPER RESTORATION OF ALL EXISTING SURFACES REQUIRED PATCHING, PLASTERING, PAINTING AND/OR OTHER REPAIR DUE TO THE INSTALLATION OF ELECTRICAL WORK UNDER THE TERMS OF THIS SPECIFICATION. CLOSE ALL OPENINGS, REPAIR ALL SURFACES, ETC., AS REQUIRED. THE CONTRACTOR SHALL EMPLOY QUALIFIED AND EXPERIENCED WORKMEN FOR THIS WORK. ALL RESTORATION WORK SHALL BE SUBJECT TO THE APPROVAL OF THE ARCHITECT AND/OR THE

COR/VA.

J. ALL TEMPORARY AND REMODELING WORK SHALL BE CONSIDERED A PART OF THIS CONTRACT AND NO EXTRA CHARGES WILL BE ALLOWED. THIS SHALL INCLUDE MINOR ITEMS OF MATERIAL OR EQUIPMENT NECESSARY TO

MEET THE REQUIREMENTS AND INTENT OF THE PROJECT.

K. EXAMINE ARCHITECTURAL, STRUCTURAL, AND MECHANICAL DRAWINGS AND SPECIFICATIONS TO DETERMINE THE SEQUENCE OF CONSTRUCTION THROUGHOUT THE PROJECT, INCLUDING EXISTING, TEMPORARY, REMODELED AND NEW AREAS.

L. ALL ELECTRICAL CONNECTIONS REQUIRING AN OUTAGE SHALL BE MADE DURING AN APPROVED TIME LIMIT.

CHANGEOVERS SHALL BE AS SHORT A DURATION AS POSSIBLE AND SHALL NOT INTERFERE WITH NORMAL OPERATION OF THE COR/VA FACILITIES. NOTIFY COR/VA NO LESS THAN 14 DAYS (TWO WEEKS) IN ADVANCE OF A SHUTDOWN OF ANY ELECTRICAL CIRCUIT FOR CHANGEOVER, AND SUCH A CHANGEOVER SHALL BE DONE DURING HOURS AS DIRECTED BY COR/VA. WORK SHALL BE SCHEDULED SO THAT AT NO TIME WILL ANY EMERGENCY FEEDER, CIRCUIT, OR FIRE ALARM ZONE BE OUT OF SERVICE. PROVIDE NECESSARY TEMPORARY

FEEDERS TO ACCOMPLISH THIS REQUIREMENT.

M. EXISTING LOW VOLTAGE WIRING WHICH WILL NOT BE MADE OBSOLETE AND WHICH WILL BE DISTURBED DUE TO CONSTRUCTION CHANGES REQUIRED BY THIS CONTRACT SHALL BE RESTORED TO CONDITION, OR POSITION, AS REQUIRED. PROPERLY RE-SECURE CABLE IN CHASES, CRAWL SPACES, TUNNELS, AND CEILING SPACES AS REQUIRED BY NEC. IN SOME CASES IT MAY BE NECESSARY TO ADD SUPPORTING HARDWARE TO ACCOMPLISH

THIS REQUIREMENT.

N. IF POSSIBLE, ALL NEWLY INSTALLED RECEPTACLES SHALL BE INSTALLED IN SEPARATE OR ADJACENT STUD SPACES, TO AVOID SOUND TRANSMISSION AND WALL INTEGRITY ISSUES. ALL NEWLY INSTALLED RECEPTACLES LOCATED IN COMMON STUD SPACES OF FIRE-RESISTANT WALLS SHALL BE EQUIPPED WITH FIRE-RESISTANT

PUTTY PADS AT THE BACK OF EACH BOX IN ACCORDANCE WITH NEC 300.21.

1. ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT AND WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND VA

STANDARDS.

2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE BUILDING

CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.

3. FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL

ELECTRICAL CODE, UL LISTING REQUIREMENT AND THE APPLICABLE BUILDING CODES.

4. VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL REQUIRED MOUNTING HARDWARE TO

SUIT THE PARTICULAR INSTALLATION.

5. PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING CONSTRUCTION.

6. BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.

7. COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO AVOID CONFLICT DURING

CONSTRUCTION.

8. ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR SPARE, OR SPACE.

9. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE ACCEPTED. ALL PRODUCTS MUST COMPLY WITH "BUY AMERICAN ACT".

10. ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR PARTICULAR EQUIPMENT

MANUFACTURER'S SPECIFICATIONS.

11. CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE DEVICE'S SCREW

TERMINALS.

12. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT UNLESS NOTED

OTHERWISE.

13. ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.

14. ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.

15. ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON VIBRATING EQUIPMENT (MAXIMUM LENGTH OF 6 FEET). PVC SHALL BE USED FOR UNDERGROUND CONDUIT OR WHERE CONCRETE- ENCASED. WHERE VIBRATING EQUIPMENT IS LOCATED OUTSIDE, LFMC CONDUIT SHALL BE USED (MAXIMUM SIX FEET) FOR

FINAL CONNECTIONS.

16. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN APPROVED THIRD

PARTY TESTING AGENCY.

17. FOR ALL LED FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS.

PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION, WILL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY.

PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.

18. IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS DETERMINED BY THE GOVERNMENT, SHALL BE

PROVIDED.

19. COMPRESSION COUPLINGS SHALL BE USED. NO SET SCREW FITTINGS ARE ALLOWED.

20. MINIMUM CONDUIT SIZE TO BE USED IS 3/4".

21. FEEDER TAGS APPENDED WITH 'VD' ARE UPSIZED IN AMPACITY DUE TO VOLTAGE DROP.

22. IF FLOOR OR RATED WALL PENETRATIONS CANNOT BE FIRESTOPPED AT THE END OF THE WORK SHIFT, SUCH AS DUE TO THE NEED TO PULL ADDITIONAL CABLES, TEMPORARY FIRESTOPPING COMPOSED OF MINERAL WOOL SHOULD BE INSTALLED IN THE PENETRATION TO PROVIDE PROTECTION AGAINST FIRE/SMOKE SPREAD THROUGH THE UNSEALED

PENETRATION.

A. RETURN REMOVED MATERIAL DEEMED SALVAGEABLE BY THE COR. MATERIALS DEEMED NOT SALVAGEABLE SHALL BE

REMOVED FROM THE PREMISES.

B. ALL EXISTING CONDITIONS, INCLUDING BUT NOT LIMITED TO EQUIPMENT, DEVICES, FIXTURES, CONDUIT AND CIRCUITS, ARE BASED ON THE BEST AVAILABLE INFORMATION AT THE TIME OF SURVEY AND VISUAL INSPECTION.

C. THE DRAWINGS ARE GENERALLY DIAGRAMMATIC AND THE CONTRACTOR SHALL HARMONIZE HIS WORK SO THAT EACH PIECE OF EQUIPMENT WILL BE INSTALLED AS TO FUNCTION PROPERLY. THE CONTRACTOR SHALL COOPERATE WITH

OTHER TRADES.

D. REMOVE ALL EXISTING WIRING DEVICES, LIGHT FIXTURES, WIRE, CONDUIT, ETC., AS NOTED OR INDICATED WITHIN DEMOLITION AREA. (ALL ITEMS MAY NOT BE SHOWN). REWORK AS NECESSARY CIRCUITING WHICH REQUIRES

CONTINUATION THROUGH THE AREA.

E. ELECTRICAL CONTRACTOR TO PROVIDE ALL NECESSARY LABOR, CONDUIT, WIRE, CONNECTIONS, ETC., FOR DEVICES, FIXTURES, ETC., NOTED AS "EXISTING TO REMAIN" SUCH THAT EXISTING CIRCUIT CONTINUITY IS MAINTAINED.

F. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK REQUIRED TO REMOVE/RELOCATE ANY EXISTING ELECTRICAL EQUIPMENT SUCH THAT ELECTRIC SHOCK HAZARDS TO WORKMEN ARE ELIMINATED DURING DEMOLITION

AND NEW CONSTRUCTION.

G. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK IN REMOVING AND REPLACING "EXISTING TO REMAIN" FIXTURES, DEVICES, ETC., AS REQUIRED SO THAT THESE DEVICES ARE NOT DAMAGED DURING DEMOLITION.

RELOCATED TO NEAREST APPROPRIATE LOCATION TO AVOID CONFLICTS WITH OTHER TRADES' WORK. REPLACE WITH NEW ANY "EXISTING TO REMAIN" FIXTURE, DEVICE, ETC., NOT DEEMED SALVAGEABLE BY THE COR.

H. REMOVED OR DAMAGED CONDUIT, WIRE, AND FITTINGS SHALL NOT BE REUSED FOR RELOCATED OR NEW DEVICES.

I. MAKE AS-BUILTS WITH NEW TYPED DIRECTORIES FOR ALL PANELBOARDS, INDICATING CIRCUIT DESCRIPTION (USED OR

SPARE), CIRCUIT BREAKERS AND CIRCUIT LOAD.

J. WORK REQUIRED FOR EXISTING EQUIPMENT NOTED AS "EXISTING TO BE REMOVED" SHALL INCLUDE:

A. REMOVAL OF FEEDER FROM EQUIPMENT TO POINT OF FEED.

B. REMOVAL OR RE-CIRCUITING OF ALL BRANCH CIRCUITING.

C. REMOVAL OF ALL FITTINGS, SUPPORTS, BRACKETS, ETC.

D. PATCHING OF WALLS, FLOORS AND CEILINGS PER ARCHITECT'S INSTRUCTIONS.

E. CAPPING OF FEEDER CONDUIT AT 6" ABOVE OR BELOW FLOOR/CEILING AS REQUIRED AND MARKING LOCATION

OF POINT OF FEED WITH AN ENGRAVED BRASS TAG.

F. REMOVAL OF FEEDER CONDUIT IF FOUND TO BE UNSALVAGEABLE BY ARCHITECT, ENGINEER OR THE COR.

K. EXISTING EQUIPMENT NOT IMPLICITLY SHOWN ON THE DRAWINGS IS INTENDED TO BE "EXISTING TO REMAIN

UNCHANGED", UNLESS NOTED OTHERWISE.

IF FLOOR OR RATED WALL PENETRATIONS CANNOT BE FIRESTOPPED AT THE END OF THE WORK SHIFT DUE TO THE NEED TO PULL ADDITIONAL CABLES, TEMPORARY FIRESTOPPING COMPOSED OF MINERAL WOOL SHALL BE INSTALLED IN THE PENETRATION TO PROVIDE PROTECTION AGAINST FIRE/SMOKE SPREAD THROUGH THE UNSEALED

PENETRATION.

SHORT CIRCUIT CURRENT CALCULATIONS SHALL BE PERFORMED ON THE ELECTRICAL SYSTEM USING A BOLTED THREE PHASE FAULT CONDITION FOR CALCULATIONS TO ACHIEVE MAXIMUM THERMAL AND MECHANICAL STRESS TO THE SYSTEM FOR CALCULATIONS PURPOSES. EXISTING SHORT CIRCUIT VALUES WILL BE USED OUTSIDE THE WORK

AREA, FOR THE STARTING POINT OF THE CALCULATIONS.

NORMAL AND CRITICAL POWER BRANCHES ARE SIGNIFIED USING "A" AND "B" IN THIS SET.

- EQUIPMENT NOTED WITH "A" ARE ON THE NORMAL POWER BRANCH.

- EQUIPMENT NOTED WITH "B" ARE ON THE CRITICAL POWER BRANCH.

Engineers Architects

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/2

/2

:4

:0

P

M C

U s e rs

\a ri c h a rd s \D o c u m e n ts

\2 -0

T R

R o o m

D e ta ils a ri c h a rd s P

K P

J .r v t

ET001

ELECTRICAL GENERAL NOTES,

SYMBOL LEGENDS, AND

ABBREVIATIONS

1 106ADR

EHRM INFRASTRUCTURE

UPGRADES

VA ANN ARBOR HEALTHCARE SYSTEM

2215 FULLER ROAD, ANN ARBOR, MI

48105 FEBRUARY 28, 2024

BID DOCUMENTS

506-21-70521-092

JKM

1,2,3,15,22,28,29,30,31,32,37

ELECTRICAL SYMBOL LEGEND

LIGHTING SYMBOL LEGEND ELECTRICAL ABBREVIATIONS LIST

ELECTRICAL SYMBOL NOTES

GENERAL ELECTRICAL REMODELING NOTES

ELECTRICAL GENERAL NOTES

GENERAL ELECTRICAL DEMO NOTES

TEMPORARY FIRESTOPPING

METHOD OF SHORT CIRCUIT CURRENT CALCULATIONS

NORMAL AND CRITICAL POWER - "A" AND "B"

2/27/2024 2/26/2024

TECHNOLOGY SYMBOL LEGEND

DATA OUTLET - N-4 PR UTP

TELCO OUTLET - N-4 PR UTP

SYMBOL HEIGHT DESCRIPTION

18"

48"

ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.

ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.

SEE DRAWINGS FOR MORE INFORMATION.

NOTE: NOT ALL SYMBOLS ARE USED.

ELECTRONIC LOCKING MECHANISM

DOOR CONTACT

REQUEST FOR EXIT SENSOR

CARD READER

(K - KEYPAD)

48"CR

ES

DC

RX

48" EMERGENCY EXIT BUTTON TO RELEASE DOOR (EEB)

WIRELESS ACCESS POINT - N-4 PR UTP

WALL PHONEW

N

S

NURSE CALL PATIENT STATION WITH PILLOW SPEAKER

2 ADDITIONAL PUSHBUTTONS, 1/4 RECEPTACLE AND COVER

(1 - SINGLE, 2 - DUAL, V - VANDAL RESISTANT)

P NURSE CALL PATIENT BED INTERFACE RECEPTACLE

B NURSE CALL CODE BLUE STATION WITH COVER

E NURSE CALL EMERGENCY STATION WITH PULL CORD AND AUDIO +40" AFF IN

RESTROOM, +72" AFF IN SHOWER (V - VANDAL RESISTANT, PB - PUSH BUTTON)

D NURSE CALL DUTY STATION

M NURSE CALL MASTER STATION/CONSOLE

NURSE CALL DOME LIGHT

(Z - ZONE LIGHT, V - VANDAL RESISTANT)

IC

INTERCOM WITH CAMERA

IC

INTERCOM MASTER WITH PUSH TO RELEASE DOORM

NURSE CALL WIRELESS ANTENNASNW

N

TV OUTLET WALL MOUNTED

48"

54"

DESK

CCTV DOME CAMERA FIXED

CCTV DOME CAMERA PAN/TILT/ZOOM

FOUR POST OIT EQUIPMENT RACK

OIT EQUIPMENT CABINET

NURSE CALL EQUIPMENT CABINET

MATV EQUIPMENT CABINET

CCTV EQUIPMENT CABINET

NCE

MATV

CCTV

LADDER CABLE TARY

N

N

FLOOR BOX FOR DATA

AS NOTED

DOOR

DOOR

ABOVE

DOOR

HEADWALL

18"

HEADWALL

/40"

40", 72"

18"

60"

CEILING

CEILING

6' TO TOP

6' TO TOP

FLOOR

PHYSICAL ACCESS CONTROL SYSTEMPACS 6' TO TOP

ELECTRONIC PANIC HARDWAREEP

DO DOOR OPERATOR

HANDWAVE

T

C

NURSE CALL STAFF TERMINAL

NURSE CALL PATIENT STATION WITH CALL CORD.

(1 - SINGLE, 2 - DUAL, V - VANDAL RESISTANT)

60"

HEADWALL

W WIRELESS PENDANT

L

KP PATIENT ROAM ALERT ACCESS CONTROL KEYPAD48"

PATIENT ROAM ALERT ANTENNACEILING

GROUND BUS

CEILING

DOOR

DOOR

48"

ABOVE

DOOR

NURSE CALL DOME LIGHT

FLOOR

FLOOR

FLOOR

ABOVE

CEILING

18"

4'x8'x3/4" FIRE RATED TTB8"

N

M

PATIENT STATION (PB - PUSH BUTTON, M - MICROPHONE, K -KEYED)

88" MOTION DETECTOR

MD

FLOOR TWO POST OIT EQUIPMENT RACK

CEILING MOUNTED SPEAKERSCEILING

WALL MOUNTED SPEAKERS96"

S

S

AREA OF REFUGE PANEL6' TO TOP

AREA OF REFUGE ANNUNCIATION PANEL6' TO TOP

AOF

AOFA

IC AREA OF REFUGE INTERCOM48"

AREA OF REFUGE STROBE LIGHTCEILINGSL

DP

DPP

DURESS PANIC ALARM PUSH BUTTON48"

DURESS PANIC ALARM PANEL6' TO TOP

N

SECURE WIRELESS ACCESS POINT - N-4 PR UTP

N

CEILING

S

(N - QUANTITY)

(N - QUANTITY)

(N - QUANTITY)

(N - QUANTITY)

CEILING

48"

CEILING

CEILING

TELEMETRY ANTENNA - 2-4 PRCEILING

ROBOT PHARMACY ANTENNA - 1-4 PRCEILINGR

CABLES AND CONNECTORS COLOR LEGEND

DESCRIPTION

ITEM JACK CABLE PATCH CABLES I.D. NOTES

DATA/COMPUTER

WIRELESS ACCESS

POINT - VA

FIBER - MULTI-MODE

FIBER - SINGLE-MODE

SECURITY/FIRE

BLUE

YELLOW

BLACK

IVORY

RED

BLUE

YELLOW

AQUA

YELLOW

RED

BLUE

YELLOW

AQUA

YELLOW

RED

C

WAP

FO

FO

CCTV, PACS, FIRE CCTV, PACS, FIRE

4 PAIR CABLE

4 PAIR CABLE

12/24

ORANGE ORANGE ORANGE RTLS 4 PAIR CABLE

WIRELESS ACCESS

POINT - GUEST

PINK PINK PINK WAP 4 PAIR CABLE

GREEN GREEN GREEN C 4 PAIR CABLE

RTLS

PATIENT MONITORING

PURPLE PURPLE PURPLE C 4 PAIR CABLEMEDICAL EQUIPMENT

WHITE WHITE WHITE T 4 PAIR CABLE

ANALOG PHONE

LINES

ADO AUTOMATIC DOOR OPERATOR

AFF ABOVE FINISH FLOOR

BOD BASIS OF DESIGN

CCTV CLOSED CIRCUIT TELEVISION

COAX COAXIAL CABLE

COMM COMMUNICATION

COR CONTRACTING OFFICER REPRESENTATIVE

DC DOOR CONTACT SWITCH

DN DOWN

DO DOOR OPERATOR

DVC DIGITAL VOICE COMMAND

DVR DIGITAL VIDEO RECORDER

E EXISTING DEVICES

EEB EMERGENCY EXIT BUTTON

EL ELECTRICAL STRIKE

ETR EXISTING TO REMAIN

FA FIRE ALARM

FACP FIRE ALARM CONTROL PANEL

FAAP FIRE ALARM ANNUNCIATOR PANEL

FO FIBER OPTIC

FAGAP FIRE ALARM GRAPHIC ANNUNCIATOR PANEL

IT INTERCOMMUNICATION ROOM

MATV MASTER ANTENNA TELEVISION

MM MULTI MODE FIBER

NAC NETWORK APPLIANCE CIRCUIT PANEL

N NEW DEVICES

NCA NETWORK CONTROL ANNUNCIATOR

NS NO SCALE

NTS NOT TO SCALE

NVR NETWORK VIDEO RECORDER

TECHNOLOGY ABBREVIATIONS LIST

OC ON CENTER

OIT OFFICE OF INFORMATION TECHNOLOGY

PACS PHYSICAL ACCESS CONTROL SYSTEM

PAMN PUBLIC ADDRESS AND MASS NOTIFICATION SYSTEM

PB PUSH BUTTON

PBB PRIMARY BONDING BUSBAR

PDU RACK POWER DISTRIBUTION UNITS

POE POWER OVER ETHERNET

PR PAIR

RBB RACK BONDING BUSBAR

RX REQUEST TO EXIT

SBB SECONDARY BONDING BUSBAR

SEP SERVICE ENTRANCE PROTECTION

SLC SIGNALING LINE CIRCUIT

SM SINGLE MODE FIBER

TBB TELECOM BACKBONE CONDUCTOR

TEL TELEPHONE

TGB TELECOM GROUND BUS BAR

TM TELEMONITORING

TMGB TELECOM MAIN GROUND BUS BAR

TP TWISTED PAIR

TR TELECOM ROOM

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

WM WIRE MANAGEMENT

WAP WIRELESS ACCESS POINT

UL UNDERWRITERS LABORATORY

UPS UNINTERRUPTIBLE POWER SUPPLY

UTP UNSHIELDED TWISTED PAIR

TECHNOLOGY GENERAL NOTES

1. PROVIDE COMMUNICATIONS DEVICES AND EQUIPMENT IN ACCORDANCE WITH THE CONTRACT DOCUMENTS, MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT, LATEST EDITION OF THE NATIONAL ELECTRICAL CODE, BICSI STANDARDS, AND VA

STANDARDS.

2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES AND EQUIPMENT WHERE BUILDING CONSTRUCTION IS NOT

SUITABLE FOR DIRECT MOUNTING.

3. FIRESTOP, DRAFTSTOP, SMOKESTOP OR PROTECT ANNULAR SPACE AROUND PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILINGS, AND ROOF IN ACCORDANCE WITH REQUIREMENTS OF NFPA 70, UL

LISTING REQUIREMENT AND APPLICABLE BUILDING CODES.

4. PROVIDE CABLING THAT COMPLIES WITH THE LATEST EDITION OF TELECOMMUNICATIONS DISTRIBUTION

METHOD MANUAL AND ANSI/TIA/EIA PUBLICATIONS.

5. COMPLY WITH THE LATEST ANSI/TIA/EIA 758 AND 607 - GROUNDING AND BONDING REQUIREMENTS FOR

TELECOMMUNICATIONS IN COMMERCIAL BUILDING.

6. COMPLY WITH THE LATEST ANSI/TIA/EIA 568 - COMMERCIAL BUILDING TELECOMMUNICATIONS WIRING

STANDARD.

7. COMPLY WITH THE LATEST ANSI/TIA/EIA 569 - COMMERCIAL BUILDING STANDARD FOR TELECOMMUNICATIONS

PATHWAYS AND SPACES.

8. COMPLY WITH THE LATEST NFPA 70 NATIONAL ELECTRICAL CODE.

9. COMPLY WITH THE LATEST NFPA 99 HEALTHCARE FACILITIES CODE.

10. COMPLY WITH THE LATEST NFPA 101 LIFE SAFETY CODE.

11. COORDINATE WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION.

12. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES TO INDICATE A QUALITY STANDARD AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER.

PRODUCTS DEEMED EQUAL AND APPROVED BY THE COR WILL BE ACCEPTABLE. COMPLY WITH "BUY AMERICAN

ACT".

13. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, BOXES, OUTLET, OR EQUIPMENT UNLESS NOTED

OTHERWISE.

14. PROVIDE RGS OR EMT CONDUIT UNLESS OTHERWISE NOTED.

15. PROVIDE MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT LABEL LISTED BY APPROVED THIRD PARTY

TESTING AGENCY.

16. NOTIFY COR REGARDING DISCREPANCY BETWEEN PLANS AND SPECIFICATIONS FOR CLARIFICATION. THE

MORE STRINGENT OF THE THEM SHALL TAKE PRECEDENCE.

17. PROVIDE TIA/EIA CAT 6A COPPER OUTLETS AND CONNECTORS.

18. ALL WORK AREA OUTLETS SHALL BE 8 PIN, CAT 6A KEYSTONE JACK WIRED PER T568A OR T568B AS DIRECTED

BY THE VA COR.

19. LABEL DEVICES IN ACCORDANCE WITH LATEST ANSI/TIA 606A OR 606B EDITION AS WELL AS THE STANDARDS

SET FORTH BY THE VA HOSPITAL OIT.

20. PROVIDE A MINIMUM OF 12" CLEARANCE ABOVE THE CABLE TRAY PER TIA/EIA 569.

21. VA WILL CONDUCT A WAP SURVEY AND PROVIDE THE SURVEY TO THE CONTRACTOR. INSTALL CABLING AND

EQUIPMENT IN ACCORDANCE WITH THE SURVEY. COORDINATE WITH COR/OIT.

22. ALL CABLING INSTALLED ABOVE CEILING SHALL BE PLENUM RATED.

23. MINIMUM CONDUIT SIZE TO BE USED IS 1-1/4" EMT.

24. DEVICES PLACED IN INTERCOMMUNICATION ROOM TO BE MOUNTED ON FIRE RETARDANT PLYWOOD.

25. PROVIDE OUTDOOR AND INDOOR CONDUITS, INNERDUCTS, TELECOM HANDHOLES, TELECOM MANHOLES, HANDHOLE COVERS, CABLING BOTH FIBER AND COPPER, SUPPORTS, TESTING, AND ALL RELATED MATERIALS

FOR A COMPLETE SYSTEM AS SHOWN HEREIN AND DESCRIBED IN THE SPECIFICATIONS.

26. PROVIDE CABLE TRAY, LADDER TRAY J-HOOKS, CONDUITS, JUNCTION BOXES, SUPPORTS FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, FLOOR SLEEVES, CORE DRILLING, CABLING BOTH FIBER AND COVER, JACKS, TERMINATIONS, COVER PLATES, LABELING, PATCH PANELS, PATCH CORDS, CHANNEL RACKS, VERTICAL AND HORIZONTAL WIRE MANAGEMENT, GROUNDING BUS BARS, RACK MOUNTED GROUND BUS, GROUND CABLING, BONDING TO THE GROUNDING SYSTEM, GROUND CABLE IN THE CABLE AND LADDER TRAY, POWER STRIPS, UPD'S, UPS'S, TESTING AND RELATED MATERIALS FOR A COMPLETE CABLING SYSTEM AS SHOWN HEREIN AND

AS DESCRIBED IN THE SPECIFICATIONS.

27. PROVIDE J-HOOKS WHERE CABLE TRAY IS NOT SHOWN OR IF THERE IS OBSTRUCTION IN THE PATH OF THE CABLE TRAY, OR USE FLEXIBLE CONDUITS (NOT TO EXCEED 10 FEET), JUNCTION BOXES, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, COVER PLATES, LABELING, SUPPORT J-HOOKS AND CONDUITS, AS SHOWN

HEREIN AND AS DESCRIBED IN THE SPECIFICATIONS.

28. PROVIDE 12 PORT WALL MOUNTED COPPER PATCH PANEL I THE EXISTING TR/FACILITY ROOM AND ANOTHER 12 PORT IN EACH NEW TR AND RUN 12-4PR CAT 6A CABLE BETWEEN THESE TR'S TERMINATE AND TEST, LABEL

EACH PORT.

29. PROVIDE MULTI-SENSOR PANORAMIC SECURITY SURVEILLANCE TELEVISION SYSTEM (SSTV) CAMERAS, DVRS/NVRS, STORAGE, SOFTWARE, LICENSES, CONDUITS, JUNCTION BOXES, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, CABLING, COVER, JACKS, TERMINATIONS, COVER PLATES, LABELING, PATCH PANELS, PATCH CORDS, TESTING AND RELATED MATERIALS FOR A COMPLETE OPERATIONAL SSTV SYSTEM AS SHOWN HEREIN

AND AS DESCRIBED IN THE SPECIFICATIONS.

30. PROVIDE CARD READERS, DOOR CONTROLLERS, TR KEYPADS FOR PHYSICAL ACCESS AND CONTROL SYSTEM (PACS), SOFTWARE, LICENSES, CONDUITS, JUNCTION BOXES, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, CABLING, COVER, JACKS, TERMIANTIONS, COVER PLATES, LABELING, TESTING AND RELATED MATERIALS FOR A COMPLETE OPERATIONAL PACS SYSTEM AS SHOWN HEREIN AND AS DESCRIBED IN THE SPECIFICATIONS.

31. PROVIDE NEW FIRE ALARM SYSTEM DEVICES, FIRE ALARM PANEL, NAC PANEL, POWER SUPPLY, FOR A COMPLETE FIRE AND DETECTION SYSTEM, RED CONDUIT AND JUNCTION BOXES, COVERPLATES, LABELING, CABLING BOTH COPPER AND FIBER, PROGRAMMING, SOFTWARE, LICENSES, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, CABLING, COVER, JACKS, TERMINATIONS, TESTING AND RELATED MATERIALS FOR

SPECIFICATIONS.

32. CAMERAS SHALL BE PANORAMIC MULTI0SENSOR AND SHALL MEET THE NATIONAL DEFENSE AUTHORIZATION

ACT-NDAA.

33. IT IS THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE AND INSTALL COPPER PATCH CABLES IN ALL TELECOMMUNICATIONS ROOMS. ONE COPPER PATCH CABLE IS REQUIRED TO SERVE EVERY WORK AREA OUTLET, WIRELESS ACCESS POINT, AND ALL OTHER CONNECTION POINTS SERVED BY OIT NETWORK SWITCHES. THE APPROXIMATE AMOUNT OF PATCH CABLES NEEDED IS 6,500 (VARYING LENGTHS OF 2, 4, AND 8

FEET) TO REACH FROM THE SWITCH TO THE PATCH PANEL.

GENERAL TECHNOLOGY DEMOLITION NOTES

A. ALL EXISTING CONDITIONS - INCLUDING EQUIPMENT, CABINETS, CABLE TRAY, DEVICES, AND CONDUIT - ARE BASED ON THE BEST AVAILABLE INFORMATION AT THE TIME OF SURVEY AND VISUAL INSPECTION.

B. RETURN REMOVED MATERIAL DEEMED SALVAGEABLE BY THE COR. ALL OTHER MATERIAL SHALL BE REMOVED FROM THE PREMISES (E.G., PATCH PANELS, CABLES, COVER PLATES, PATCH CORDS, AND RELATED MATERIAL).

C. EXISTING CABLE TRAY SHALL REMAIN. REMOVE EXISTING CABLING SERVING WORK AREA OUTLETS (WAO). NO ABANDONED CABLING WILL BE ALLOWED TO REMAIN ABOVE THE CEILING. INSTALL NEW CABLE TRAY NEXT TO

THE EXISTING CABLE TRAY.

D. EXISTING CONDUIT AND SURFACE RACEWAY MAY BE REUSED FOR NEW WAO. COORDINATE LOCATION WITH

THE COR.

E. EXISTING TR: ONCE ALL ACTIVE CONNECTIONS TO AN EXISTING TR HAVE BEEN REPLACED BY CONNECTIONS TERMINATED IN THE NEW TR - AND OIT HAS CONFIRMED THAT THERE ARE NO LONGER ANY ACTIVE CONNECTIONS FROM THE EXISTING TR - COORDINATE REMOVAL OF ALL VA OWNED NETWORK SWITCHES.

REMOVE PATCH PANELS AND ALL ASSOCIATED CABLING. BID DEMOLITION AND DISPOSAL OF THE RACKS IN THE TR UNLESS THERE ARE REMAINING NON-NETWORK COMPONENTS WHICH SHALL REMAIN IN PLACE WITH THE

UPS AND POWER SOURCE IN TACT.

1. CONTRACTOR TO REFER TO TELECOMM ROOM PHASING NOTES, SHEETS A-001, FOR ADDITIONAL

INFOMATION.

Engineers Architects

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/8

/2

:4

:2

P M

C U s e rs

\a ri c h a rd s \D o c u m e n ts

\2 -0

T R

R o o m

D e ta ils a ri c h a rd s P

K P

J .r v t

ET002

TECHNOLOGY GENERAL NOTES,

SYMBOL LEGEND, AND

ABBREVIATIONS

2 106ADR

EHRM INFRASTRUCTURE

UPGRADES

VA ANN ARBOR HEALTHCARE SYSTEM

2215 FULLER ROAD, ANN ARBOR, MI

48105 FEBRUARY 28, 2024

BID DOCUMENTS

506-21-70521-092

JKM

CONDITIONAL NOTE

Docusign Envelope ID: 635BD638-6D8A-48CF-A710-8A74AD2E69A4

7/9/2024 7/9/2024

E

CR

DC ES RX

GFI

J

E

M M

E E

10 10

PANEL 'A' PANEL 'B'

ET5016

A-1,3,5

B-1,3,5

SBB

K

A-2

B-2

A-2

A-2 N

B-2

B-2

A-2

B-2

NORMAL CRITICAL

A

6FIRE RATED PATHWAYS

A-4

A

AA

PANEL A

FIRE RATED PATHWAYS

SSB

CABLE TRAY

RECEPTACLE

NEMA 5-20R

RECEPTACLE

NEMA 5-20R

MOTOR-RATED

SWITCH

"B" PANEL"A" PANEL

CABLE TRAY

RECEPTACLE

NEMA 5-20R

RECEPTACLE

NEMA 5-20R

SSB

1'-0"

LIGHT SWITCH

RECEPTACLE

NEMA 5-20R

RECEPTACLE

NEMA 5-20R

GFCI -

RECEPTACLE

NEMA 5-20R

"B" PANEL

SBB

RECEPTACLE

NEMA 5-20R

NEC REQUIRED WORKING

CLEARANCE, 30" WIDE BY

36" DEEP BY 72" HIGH

RECEPTACLE

NEMA 5-20R

DATA PORT

Engineers Architects

# KEY NOTES:

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/2

/2

:4

:1

P

M C

U s e rs

\a ri c h a rd s \D o c u m e n ts

\2 -0

T R

R o o m

D e ta ils a ri c h a rd s P

K P

J .r v t

ET501

TYPICAL TELECOM ROOM DETAILS

3 106ADR

EHRM INFRASTRUCTURE

UPGRADES

VA ANN ARBOR HEALTHCARE SYSTEM

2215 FULLER ROAD, ANN ARBOR, MI

48105 FEBRUARY 28, 2024

BID DOCUMENTS

506-21-70521-092

JKM

1 THE INDOOR HVAC UNITS – EITHER VARIABLE

REFRIGERANT VOLUME (VRV) UNITS OR

DUCTLESS MINI-SPLIT UNITS – SHALL BE

POWERED FROM THEIR ASSOCIATED

OUTDOOR CONDENSING UNITS. THE

ELECTRICAL CONTRACTOR SHALL PROVIDE

A CIRCUIT TO THE CONDENSING UNIT AS

SHOWN ON SHEET ET601s, INCLUDING THE

RACEWAYS AND CONDUCTORS TO POWER

THE INDOOR UNITS.

2 TELECOMMUNICATIONS CHANNEL RACK,19

INCHES WIDE, 30 INCHES DEEP, 84 INCHES

HIGH, 45RU, WHITE. PROVIDE ORTRONICS

(LEGRAND) MM2073038-W, OR APPROVED

EQUIVALENT. CONTRACTOR SHALL

COORDINATE ADDITIONAL DETAILS

INCLUDING BUT NOT LIMITED TO GROUNDING

AND BONDING DETAILS, DATA ELEVATIONS

AND POWER ELEVATIONS IN THE DRAWINGS.

3 VERTICAL CABLE MANAGEMENT CAGE WITH

DOOR, 6 INCHES WIDE, 84 INCHES HIGH,

45RU, WHITE. PROVIDE ORTRONICS

(LEGRAND) MM20VMD706-W, OR APPROVED

EQUIVALENT.

4 RACK POWER CONNECTION MOUNTED TO

THE CABLE TRAY WITH A MINIMUM OF 12"

SEPARATION BETWEEN THE CABLE TRAY

AND THE POWER CONNECTION. PROVIDE

RACK CONNECTION ACCORDING TO THE

POWER REQUIREMENTS TABLE ON THIS

SHEET. REFER TO CHANNEL

RACK/NETWORK CABINET POWER

CONNECTION DETAILS ON SHEET ET502 AND

RACK POWER ELEVATION AND SCHEMATIC

DIAGRAMS ON SHEET ET505.

5 SECONDARY BONDING BUSBAR TO BE

LOCATED BEHIND OR TO THE SIDE OF THE

RACKS. TELECOMMUNICATIONS EQUIPMENT

SHALL BE BONDED ACCORDING TO THE

GROUNDING AND BONDING DETAILS. REFER

TO DETAILS 3 AND 4 ON SHEET ET503 FOR

MORE INFORMATION.

6 FIRE/SMOKE SLEEVE ASSEMBLIES. PROVIDE

UL LISTED ASSEMBLIES, STI EZ-PATH, SERIES

33 FIRE-RATED PATHWAY, OR APPROVED

EQUIVALENT. INSTALL SLEEVES ABOVE

DOOR HEADER AT AN ELEVATION

COORDINATED TO BE ABOVE THE EXISTING

CEILING HEIGHT IN THE ADJACENT

COORIDOR. REFER TO 400 SERIES ET

SHEETS FOR QUANTITIES.

7 PROVIDE NEW 24 INCH WIDE BY 4-INCH-HIGH

WIRE MESH TRAY AROUND THE ROOM AND

ABOVE THE CHANNEL RACKS, WITH

WATERFALL DROPOUTS INTO EACH RACK, 90

DEGREE CORNERS AND ALL RELATED

FITTINGS. SEE WIRE MESH TRAY DETAIL ON

ET504 FOR MORE INFO. B.O.D.: CABLEOFIL

CF105/600 AND CF150/600 SERIES OR

EQUIVALENT.

8 RECEPTACLES, PROVIDE TWO RECEPTACLE

ON EACH WALL, AS SHOWN 1 FED FROM

PANEL A THE OTHER FROM PANEL B.

9 PLYWOOD BACKBOARD. SEE

ARCHITECTURAL.

10 LIGHTING AND APPLIANCE PANELBOARDS.

PROVIDE PANELS MOUNTED ON CHANNEL

STEEL SUPPORTS. UNLESS NOTED

OTHERWISE ON THE 400 SERIES ET SHEETS,

PANEL 'B' SHALL BE FED FROM A SOURCE

WITH GENERATOR BACKUP, AND PANEL 'A'

SHALL BE FED FROM A NORMAL UTILITY

SOURCE.

11 PROVIDE JUNCTION BOX WITH EMERGENCY

POWER TO THE PACS DOOR CONTROLLER.

12 PROVIDE MULTI SENSOR CAMERA AND

CONNECT TO EXISTING CAMERA SYSTEM.

LOCATION SHOULD BE COORDINATED WITH

THE CHANNEL RACK LAYOUT AND OIT.

13 PROVIDE CABLING FOR VA FURNISHED

WIRELESS ACCESS POINT.

14 PROVIDE GFCI RECEPTACLE NEAR DOOR,

WITH POWER EXTENDED FROM AN EXISTING

CONVENIENCE OUTLET CIRCUIT

ORIGINATING FROM A PANEL NOT IN THE

ROOM.

Scale: 3/8" = 1'-0"

ELECTRICAL FLOOR PLAN - TYPICAL 3-RACK TR

Scale: 3/8" = 1'-0"

ELECTRICAL CEILING PLAN - TYPICAL 3-RACK TR

Scale: 3/8" = 1'-0"

PLAN WEST ELEVATION

Scale: 3/8" = 1'-0"

PLAN NORTH ELEVATION

Scale: 3/8" = 1'-0"

PLAN SOUTH ELEVATION

Scale: 3/8" = 1'-0"

PLAN EAST ELEVATION

PER PHASE CONNECTED LOAD: 2.39 kVA 1.67 kVA 1.67 kVA

SPACE -- 1 41 -- -- 42 1 -- SPACE

SPACE -- 1 39 -- -- 40 1 -- SPACE

SPACE -- 1 37 -- -- 38 1 -- SPACE

SPACE -- 1 35 -- -- 36 1 -- SPACE

SPACE -- 1 33 -- -- 34 1 -- SPACE

SPACE -- 1 31 -- -- 32 1 -- SPACE

SPACE -- 1 29 -- -- 30 1 -- SPACE

SPACE -- 1 27 -- -- 28 1 -- SPACE

SPACE -- 1 25 -- -- 26 1 -- SPACE

SPACE -- 1 23 -- -- 24 1 -- SPACE

SPACE -- 1 21 -- -- 22 1 -- SPACE

SPARE 20 A 1 19 0 0 20

17 0 0 18

2 20 A SPARE

15 0 0 16SURGE PROTECTIVE DEVICE 30 A 3

13 0 0 14

2 20 A SPARE

11 0 0 12 1 20 A PACS J-BOX

9 0 0 10 1 20 A CONDENSATE PUMPSPARE 30 A 3

7 0 0 8 1 20 A SPARE

5 1.67 0 6 1 20 A SPARE

3 1.67 0 4 1 20 A TELECOM ROOM LTGRACK RECEPTACLE 60 A 3

1 1.67 0.72 2 1 20 A TELECOM ROOM RCPT

LOAD NAME BKR P CKT A (kVA) B (kVA) C (kVA) CKT P BKR LOAD NAME

ENCLOSURE: NEMA 1 BRANCH: SEE ONE-LINE EXISTING/NEW: New Construction

MOUNTING: SURFACE FED FROM: LOCATION:

PANEL: A

VOLTAGE: 120/208V, 3PH, 4W MAINS: 100 A MLO AIC:

10,000 AMPS

SYMMETRICAL

PER PHASE CONNECTED LOAD: 2.39 kVA 1.67 kVA 1.67 kVA

SPACE -- 1 41 -- -- 42 1 -- SPACE

SPACE -- 1 39 -- -- 40 1 -- SPACE

SPACE -- 1 37 -- -- 38 1 -- SPACE

SPACE -- 1 35 -- -- 36 1 -- SPACE

SPACE -- 1 33 -- -- 34 1 -- SPACE

SPACE -- 1 31 -- -- 32 1 -- SPACE

SPACE -- 1 29 -- -- 30 1 -- SPACE

SPACE -- 1 27 -- -- 28 1 -- SPACE

SPACE -- 1 25 -- -- 26 1 -- SPACE

SPACE -- 1 23 -- -- 24 1 -- SPACE

SPACE -- 1 21 -- -- 22 1 -- SPACE

SPARE 20 A 1 19 0 0 20 1 20 A SPARE

17 0 0 18 1 20 A SPARE

15 0 0 16 1 20 A SPARESURGE PROTECTIVE DEVICE 30 A 3

13 0 0 14 1 20 A SPARE

11 0 0 12 1 20 A SPARE

9 0 0 10 1 20 A SPARESPARE 30 A 3

7 0 0 8 1 20 A SPARE

5 1.67 0 6 1 20 A SPARE

3 1.67 0 4 1 20 A SPARERACK RECEPTACLE 60 A 3

1 1.67 0.72 2 1 20 A TELECOM ROOM RCPT

LOAD NAME BKR P CKT A (kVA) B (kVA) C (kVA) CKT P BKR LOAD NAME

ENCLOSURE: NEMA 1 BRANCH: SEE ONE-LINE EXISTING/NEW: New Construction

MOUNTING: SURFACE FED FROM: LOCATION:

PANEL: B

VOLTAGE: 120/208V, 3PH, 4W MAINS: 100 A MLO AIC:

10,000 AMPS

SYMMETRICAL

LUMINAIRE SCHEDULE

TYPE DESCRIPTION MOUNTING LAMP DRIVER VOLTAGE WATTS MANUFACTURER MODEL NUMBER

A 4' LINEAR LED STRIPLIGHT WITH FROSTED

LENS

CHAIN

SUSPEND

LED; 4,585

LUMENS;

80 CRI;

4000K

ELECTRONIC LED

DRIVER

120.00 V 35 W CREE LS4-40L-840-UL-10V

A. THIS SHEET IS INTENDED TO PROVIDE

DETAILED INFORMATION FOR THE TYPICAL

TELECOMMUN…