ATTACH CC SPS - Drawings_Part2.pdf
PDF 4 MB Posted
- Solicitation number
- 36C26125R0008
About this file
These architectural and engineering drawings depict the renovation and expansion of the Sterile Processing Service (SPS) for the Veterans Affairs Palo Alto Health Care System. The project involves renovating approximately 18,486 square feet in the basement of Building 100, with the primary objectives of modernizing the SPS, improving functional adjacencies, and creating a unidirectional workflow with controlled access for reusable medical devices and staff.
The project is divided into five phases over 720 calendar days, including preparing a temporary modular SPS swing space, deactivating the existing SPS, demolishing the current space, constructing a new SPS, and ultimately demolishing the temporary facilities. Key requirements include maintaining hospital operations with minimal disruption, complying with VA healthcare standards and design guides, implementing infection control measures, and coordinating utility shutdowns. The solicitation seeks a qualified contractor to provide labor, materials, equipment, and supervision for the comprehensive renovation and expansion project.
View the file
Other files
Show all 49
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
16 15 14 13 12 11
B
C
D
E
F
A
AE-501
TYP CART WASHER
BELOW
AE-501
TYP
AE-501
TYP
AE-501
TYP
CJ
CJ
CJ
REF MFR
REF MFR
KEY PLAN
BLDG 100
AREA OF WORK
BASEMENT OUTLINE
EXIT LIGHT
2' x 2' ACOUSTICAL CEILING
GYPSUM BOARD CEILING
2 x 2 RELOCATED EXISTING LIGHT
FIXTURE, REF: ELECTRICAL
SMOKE DETECTOR
CEILING HEIGHT,
ABOVE FINISH FLOOR
RECESSED CAN LIGHT
REF: ELECTRICAL
2 x 4 RECESSED LIGHT FIXTURE, REF: ELECTRICAL
00'-00"
EXISTING CEILING TO REMAIN
REFLECTED CEILING PLAN LEGEND
2' x 4' ACOUSTICAL CEILING
RETURN AIR GRILLE
SUPPLY AIR GRILLE
EXHAUST AIR GRILLE
ACCESS DOOR
SUSPENDED LIGHT FIXTURE
REF: ELECTRICAL
NOT IN SCOPE
CONTROL JOINT
FIRE SPRINKLER,
REF. FIRE PROTECTION
SPEAKER,
REF. ELECTRICAL
SECURITY CAMERA,
REF. TECHNOLOGY
ACCESS PANEL
REF. MECH
OCCUPANCY SENSOR,
REF. ELECTRICAL
2 x 4 SURFACE MOUNTED LIGHT
FIXTURE, REF: ELECTRICAL
1. ALL SURFACES OF FURRDOWNS TO BE PAINTED, MATCH ADJACENT WALL FINISH COLOR,
SEE FINISH SCHEDULE
2. PROVIDE HOLD DOWN CLIPS AT VESTIBULES AND AREA NEAR EGRESS DOORS.
3. ALL CEILINGS TO BE INSTALLED AT 9' - 0" UNLESS NOTED OTHERWISE.
4. INSTALL ACOUSTICAL CEILINGS IN ACCORDANCE WITH ASTM E580/E580M-14.
5. INSTALL GYPSUM BOARD CEILINGS, CEILING FRAMING AND CEILING ITEMS IN ACCORDANCE WITH
ASCE 7-10, SEISMIC CATEGORY D.
GENERAL REFLECTED CEILING PLAN NOTES
1/8" = 1'-0"
16 15 14 13 12 11
C
D
E
F
A
EQ
EQ
EQ EQ
EQ
EQ
EQ
EQ
EQ
EQ
EQ
EQ
3'- 9"
EQ EQ
EQ EQ
EQ
EQ8'-0" 8'-0" 10'-0" 8'-0" 8'-0" 4'-9"
8'- 0"
8'- 0"
5'- 0"
3'- 0"
4'-0" 5'-6" 5'-6"
3'- 9"
'-0
3'-10"
6'- 0"
6'- 0"
6'- 0"
4'- 0"
6'-0"
EQ
EQ
EQ
2'-
9"
EQ EQ
EQ
EQ
5'-2 1/2"
8'-0" 8'-0" 8'-0" 11'-2"
EQ EQ
EQ
EQ
4'-0" 4'-0"
EQ EQ
EQ
EQ
3'- 6"
3'- 6"
5'-4 1/2"
4'- 9"4'-0" 8'-0" 8'-0" 8'-0"
EQ
EQ
AE-401
AE-401
1'-9"
EQ
EQ
CE
NT
ER
OF
T
ILE
EQ EQ
EQ
EQ
EQ EQ
AE-401
EQ EQ
EQ
EQ
EQ
EQ
4'- 6"
3'-6" 5'-0"
5'- 4"
33'-9" PER MFR REQ CLEARANCE
5'-0"5'-0"
EQ
EQ
5'-0"5'-0" EQ EQ EQ
4'-6"2'-0"
EQ
EQ
EQ
EQ
EQ
CART WASHER
BELOW
ALIGN
1'-1"
AL
IG
N
EQ
EQ
5'-0" EQ EQ EQ
EQ EQ
EQ
EQ
EQ
EQ
EQ EQ EQ EQ
EQ
EQ
ALIGN
EQ
EQ
EQ EQ
3'- 9"
EQ
EQ
EQ EQ
1. ALL SURFACES OF FURRDOWNS TO BE PAINTED, MATCH ADJACENT WALL FINISH COLOR,
SEE FINISH SCHEDULE
2. PROVIDE HOLD DOWN CLIPS AT VESTIBULES AND AREA NEAR EGRESS DOORS.
3. ALL CEILINGS TO BE INSTALLED AT 9' - 0" UNLESS NOTED OTHERWISE.
4. INSTALL ACOUSTICAL CEILINGS IN ACCORDANCE WITH ASTM E580/E580M-14.
5. INSTALL GYPSUM BOARD CEILINGS, CEILING FRAMING AND CEILING ITEMS IN ACCORDANCE WITH
ASCE 7-10, SEISMIC CATEGORY D.
GENERAL REFLECTED CEILING PLAN NOTES
EXIT LIGHT
2' x 2' ACOUSTICAL CEILING
GYPSUM BOARD CEILING
2 x 2 RELOCATED EXISTING LIGHT
FIXTURE, REF: ELECTRICAL
SMOKE DETECTOR
CEILING HEIGHT,
ABOVE FINISH FLOOR
RECESSED CAN LIGHT
REF: ELECTRICAL
2 x 4 RECESSED LIGHT FIXTURE, REF: ELECTRICAL
00'-00"
EXISTING CEILING TO REMAIN
REFLECTED CEILING PLAN LEGEND
2' x 4' ACOUSTICAL CEILING
RETURN AIR GRILLE
SUPPLY AIR GRILLE
EXHAUST AIR GRILLE
ACCESS DOOR
SUSPENDED LIGHT FIXTURE
REF: ELECTRICAL
NOT IN SCOPE
CONTROL JOINT
FIRE SPRINKLER,
REF. FIRE PROTECTION
SPEAKER,
REF. ELECTRICAL
SECURITY CAMERA,
REF. TECHNOLOGY
ACCESS PANEL
REF. MECH
OCCUPANCY SENSOR,
REF. ELECTRICAL
2 x 4 SURFACE MOUNTED LIGHT
FIXTURE, REF: ELECTRICAL
KEY PLAN
BLDG 100
AREA OF WORK
BASEMENT OUTLINE
UP
16 15 14 13 12
B
C
D
E
F
A
DOCK AREA
AQ-805
AQ-805
AQ-805
AQ-805
AQ-806
AQ-802
AQ-806
AQ-802
AQ-804
AQ-804
AQ-803
AQ-803
AQ-806
AQ-807
INSTALLATION
CLEARANCE
1. ALL DOOR FRAMES TO BE LOCATED 4" FROM OUTSIDE OF FRAME TO FINISH FACE OF ADJACENT
WALL UNLESS NOTED OTHERWISE.
2. ALL WALLS ARE TYPE C3 PARTITIONS UNLESS OTHERWISE NOTED. REFER TO PARTITION TYPE
SHEET FOR WALL TYPES.
3. REFER TO DOOR & WINDOW SCHEDULES SHEET (100-AE601) FOR DOOR AND WINDOW INFORMATION.
4. ALL WALLS ARE DIMENSIONED TO CENTERLINE OF METAL STUD, UNLESS NOTED OTHERWISE.
5. BLOCK OUT SLAB FOR PENETRATIONS SHALL BE 2" LARGER THAN DUCT SIZE TO ALLOW TOLERANCE
FOR DUCT PASSAGE AND FIRE SAFING. COORDINATE WITH MEP FOR DUCT SIZES.
6. FURR AROUND ALL COLUMN PROTRUSIONS AS NEEDED UNLESS NOTED OTHERWISE.
7. CONTRACTOR TO VERIFY ALL EQUIPMENT QUANTITY REQUIREMENTS.
GENERAL PLAN NOTES
KEY PLAN
BLDG 100
AREA OF WORK
BASEMENT OUTLINE
15 14
D
E
EXIST STAFF
LOUNGE
EB-358
EXIST HAC
EB-336
EXIST CARTLIFT
MACH RM
C-2.0
S3185
A5080 F0505 A5135
M2600
M2080
A5075
AQ-802
F0225
F0225 F0225
F0225
F0795
A5075
NIS
A5145 A5210 A5220F3065
F3200
M0515
R7250
K4665
16 15 14
B
C
A
HAC
EB-300A
CLEAN SUPPLY
STORAGE ROOM
EB-300
M2055 M2055 M2055 M2055 M2055 M2055 M2055 M2055 M2055 M2055 M2055 M2055 M2055 M2055 M2055
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
A5135 F0505
M2080
M2600
M2055 M2055
M2055 M2055
M2055
M2055
F0275
M1801 M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2
M2055
EQUIPMENT
STORAGE
EB-316F
SCS OFFICE
EB-316D
SCS OPEN OFFICE
EB-316E
M2055 M2055 M2055 M2055 M2055 M2055 M2055 M2055M2055 M2055 M2055 M2055 M2055 M2055
A5080 A5075
AQ-802 7
M1801 F0275
F0275 M1801
M1801
F0275
E0120 F0275
M1801
F2000
F2000
F2000
F2000
F0420
F0420
F0420
F0420
A1015
A1015
F0420
A1015
A5145
F0205
A5145 A5145 A5145 A5145
AQ-802
8A1015
F3200
F3200 A1015
E0120
E0120
M1801
E0120
AQ-802 9
A1015
M1801 F0275
E0120
F2000
M1840
A5080
A5075
K4665
R7250
2'-
1/2
1'-
/2" 3'-
2"
1'-6" 1'-6" 3'-0"
(PT1)
(VSB)
1'-6"1'-6"
(SSM)
(PLAM)
(PLAM)
F0225 F0225
F0225 F0795
M0515 F3065
(PT1)
(RB2)
6'- 0"
(PLAM)
(SS)
R7250
F0225 F0225
F0225
A5210
A5145
A5220
F0795 F3065
M0515 F3200
(PT1)
(RB2)
5'- 0"
1'-0"4'-0"
A5145
11'-10 5/8" F.V.
3'-8" 3'-4 1/2" 9 1/4"4'-0"
8'- 0"
1'- 0"
SC
HE
D.
DI
M.
SCHED. DIM.
AE-511
AE-511
M1801
F0275 E0120
M1801 F0275
F0275 M1801
F0275 M1801
A A A A
(PT1)
(RB1)
(RB1)
3'- 6"
A1015
F0420
A5145 A5145
A1015 A1015
F2000
(PT1)
A5145 A5145
CJ CJ
EQ EQ EQ EQ
F2000
E0120 E0120
F2000 E0120 A1015
F0275
E0120 F2000
F0275 A1015
M2055 M2055
(VSB)
(WP)
(VSB)
7'- 0"
PLUMBING
EQUIPMENT LEGEND
A
B
D
E
F
G
I
CODE
HOT AND COLD WATER
COLD WATER AND DRAIN
COLD AND HOT WATER AND DRAIN
COLD, HOT, AND TREATED WATER AND DRAIN
DRAIN ONLY
ELECTRICAL
120 VOLT, CONVENTIONAL OUTLET
120 VOLT, SPECIAL OUTLET
SPECIAL ELECTRICAL REQUIREMENTS
208/220 VOLT, 3 PHASE
MEDICAL GAS
M --
MISC GAS
STEAM--
MISC
-- AIR, HIGH PRESSURE (85 PSIG) MAX -- --
VENT TO ATMOSPHERE
EARTH, GROUND AND
WALL/CEILING SUPPORT REQUIRED
EQUIPMENT SCHEDULE
1/4" = 1'-0"
1/4" = 1'-0"
3/8" = 1'-0"3/8" = 1'-0" 3/8" = 1'-0"3/8" = 1'-0"
3/8" = 1'-0"3/8" = 1'-0"3/8" = 1'-0"
14 13
C
CLEAN WORKROOM
INSTRUMENT SET
ASSEMBLY
EB-312
PREPARATION AND
ASSEMBLY
EB-312B
AQ-803
7 5
F0230 F0230
E0135 E0135
E0135 E0135
F0230
F0230
F2000
F2000
M1801
M1801
M1801
M1801
AQ-803
S2
S2
U0019
CE050CE050CE050
F0410
M1825
A1015
F3050
U0000 U0000 U0000 U0000
A5080 A5077 A5075
S0955 S0955 S0955
F0230 F0230
E0135 E0135
E0135 E0135
F0230
F0230
F2000
F2000
M1801
M1801
M1801
M1801
F3200
M0515 A5210
A5077
M1830 M1830
CE050
C
D
STERILIZATION AREA
LOW TEMP
EB-314
STEAM
STERILIZATION
EB-314B
AQ-803
S0595
S0595
S0535
S0595
S0535
S0535
S0595 S0595 S0595
S5505 S5505 S5505
STEAM STERILE
STORAGE
EB-314C
S0105
S5505
M1801 F0230
F0230
E0135
E0135
F2000
S2630
M1801
(PT2)
(SS)
(EPX)
4'- 0"
(PT2)
(CG1) (CG1)
E0135
S0955
A5080 A5077
A5075
F0230 M1801
M1801 F0230
U0000
(PT2) (PT2)
(SS)(SS)
(EPX)(EPX)
4'- 0"
4'- 0"
4'- 0"
(CG1)(CG1)
E0135
S0955 S0955 S0955 U0019
(SS)
(EPX)
HEIGHT/WIDTH OF EQUIPMENT
PLUS MANUFACTURERS
RECOMMENDED CLEARANCES
EQ EQ EQ3'-8"
S0535
S0595 S0595 S0595
S0535 S0535
(EPX)
(SS)
(EPX)
(SS)
EQUIPMENT ACCESS PANEL
5'-6" 5'-6"
EQ EQ
HEIGHT/WIDTH OF EQUIPMENT
PLUS MANUFACTURERS
RECOMMENDED CLEARANCES
S5505 S5505 S5505
(SS)
(EPX)
(PT2)
(SS)
(EPX)
4'- 0"
(CG1)
S5505 S0105
S0105
S5505
2'-1"2'-6"
S2630S2630
U0019
CT050
A1015
CE050
4'- 0"
(PT2)
(PT2)
(SS)
(EPX) (EPX)
(SS)
(CG1)
M0515
CE050
U0002U0002U0002
CT050
U0002
CT050
CE050
CE050
CE050
F3200
F3050
M1825 M1830
F0410
CT050
A1015
U0000 U0000 U0000U0000
2'-0"2'-0"2'-0"2'-0"2'-0"2'-0"
3'- 0"
2'- 0"
3'- 2"
4'-0"4'-0"4'-0"
4'- 0"
(SS)
(SS)
(PT2)
4'- 6"
7'- 0"
(EXP)
CJ
M1830
U0002 U0002 U0002 U0002 U0002 U0002
PLUMBING
EQUIPMENT LEGEND
A
B
D
E
F
G
I
CODE
HOT AND COLD WATER
COLD WATER AND DRAIN
COLD AND HOT WATER AND DRAIN
COLD, HOT, AND TREATED WATER AND DRAIN
DRAIN ONLY
ELECTRICAL
120 VOLT, CONVENTIONAL OUTLET
120 VOLT, SPECIAL OUTLET
SPECIAL ELECTRICAL REQUIREMENTS
208/220 VOLT, 3 PHASE
MEDICAL GAS
M --
MISC GAS
STEAM--
MISC
-- AIR, HIGH PRESSURE (85 PSIG) MAX -- --
VENT TO ATMOSPHERE
EARTH, GROUND AND
WALL/CEILING SUPPORT REQUIRED
1/4" = 1'-0"1/4" = 1'-0"
EQUIPMENT SCHEDULE
3/8" = 1'-0"
3/8" = 1'-0"
3/8" = 1'-0"
3/8" = 1'-0" 3/8" = 1'-0" 3/8" = 1'-0"
3/8" = 1'-0"
14 13
E
DECONTAMINATION
WORK AREA
EB-320B
VESTIBULE
EB-C30
EXISTING CORRIDOR
EB-C03
AQ-804
M1803
M1803
A1195
A1195
F2020
M3072
A5080 A5077 A5075
A5080 A5077 A5075
A1195
F2700
A5075 A5077 A5080
F2020
S2640
S2635
S2635
F2700
A5108
F2700
A1014
F3200 M1801
M1801
M1801 M1803
K1910 M0515 A5210
M1803
M3072
F2020 A1195 F2020
(SS)
(EPX)
(SS)
(EPX)
(PT2)
6'- 0"
4'- 0"
A5077 A5075 A5080
(SSM)
M1801
(CG3)
M1803
M1801
(CG1)
(CG1)
F2700 F2700
A1195
A5080 A5077 A5075
F2020 S2635
6'- 0"
(SS)
(PT2)
(EPX)
(CG1)
F3200
M1803
F2700 A1195
4'- 0"
(PT2)
(SS)
(EPX)
7'- 0"M1801
5'- 6"
M0515
6'- 0"
A5080 A5077
A5075 A5108
A1195 S2640
(SS)
(EPX)
F2020
(SS)
(SSM)
F2700
(CG3)
(CG3)
14 13
D
DECONTAMINATION
EB-320
AQ-804
S1905
S0955 S0955 S0955U0019
AUTOMATED CART
WASHER
EB-338
S3185
S2615
A5077 A5075
TBD
A5080
U1195
HLD ALCOVE
EB-322C
U0001
S0955S0955S0955
U0019 S1905
S3185
(SS)
(EPX)
(SS)
(EPX)
TBD
EQ EQ EQ3'-8" 3'-8"
HEIGHT/WIDTH OF EQUIPMENT
PLUS MANUFACTURERS
RECOMENDED CLEARANCES
EXISTING CART LIFT
2'-
/4"
S1905
(SS)
(EPX)
(PT2)
(SS)
(EPX)
6'- 0"
CJ CJ
S2615 U0001
U1195
A5075 A5077
A5080
PLUMBING
EQUIPMENT LEGEND
A
B
D
E
F
G
I
CODE
HOT AND COLD WATER
COLD WATER AND DRAIN
COLD AND HOT WATER AND DRAIN
COLD, HOT, AND TREATED WATER AND DRAIN
DRAIN ONLY
ELECTRICAL
120 VOLT, CONVENTIONAL OUTLET
120 VOLT, SPECIAL OUTLET
SPECIAL ELECTRICAL REQUIREMENTS
208/220 VOLT, 3 PHASE
MEDICAL GAS
M --
MISC GAS
STEAM--
MISC
-- AIR, HIGH PRESSURE (85 PSIG) MAX -- --
VENT TO ATMOSPHERE
EARTH, GROUND AND
WALL/CEILING SUPPORT REQUIRED
EQUIPMENT SCHEDULE
1/4" = 1'-0"
3/8" = 1'-0"3/8" = 1'-0"3/8" = 1'-0"
3/8" = 1'-0"
1/4" = 1'-0"
E
LOCKER/CHANGING
FEMALE
EB-330
TLT STAFF FEMALE
EB-330A
AQ-805
AQ-805
A1030
A1030
A1030 A1030
A1030 A1030 A1030
A1030 A1030
F2000
A1080
A5109
A1067
A5082
A5075
A5145
A5200
F2010
A5090
F3200
A1030 A1030
A1030 A1030 A1030 A1030 A1030
REFER SPEC
P3200
D
LOCKER/CHANGING
MALE
EB-332
EXISTING TELE
CLOSET
FB-SC1
TLT STAFF MALE
EB-332A
AQ-805
AQ-805
F2000
A1030 A1030 A1030 A1030 A1030 A1030 A1030
A1030 A1030 A1030
A1080
A5109
A5075
F2010 A5145
A1067
A5200 A5082
F3200REFER SPEC
A1030
A1030
A1030
A1030
A1030
A1030
A1030
(CT1)
(EPX)
A5109 A1067
A5075
A5082
A1030 A1030 A1030
A1030
A1080
(PT2)
(EPX)
(PT2)
(EPX)
CJ CJ
ADA BENCH
4'-0"
6'- 0"
1'-0" 1'-0" 1'-0"
ADAADAADA
A1030 A1030 A1030 A1030 A1030 A1030 A1030
(PT2)
(EPX) (EPX)
(PT2)
1'-0" 1'-0" 1'-0" 1'-0" 1'-0" 1'-0" 1'-0"
A1030
A1030 A1030 A1030 A1030 A1030
A1030 A1030 A1030 A1030
(PT2)
(EPX)
ADAADA
6'- 0"
1'-0" 1'-0" 1'-0" 1'-0" 1'-0" 1'-0" 1'-0" 1'-0" 1'-0" 1'-0"
A5109
(CT1)
(EPX)
A1067
A5200 A5075
A5082
ANTE/PPE
EB-322B
AQ-805 10
A5160
M2035 A5077 U0038 F2020
F0205
A5145 A5145
(PT2)
(EXP)
(SS)
F0205 F2020
U0038
A5077
A5145 A5160
ANTE
EB-322A
TOILET/SHOWER
EB-318
AQ-805
AQ-805
AQ-805
M2035
F2020 A5080 A5075
A5077
A5110
A5030
A5109
A5110
A5077
A5082 A5075
A5170
A5145 A5205
A5200 A5090
A5109
F2010
A1090
A5145 A5145
F0205
A5160
A1090
(EPX)
(PT2)
M2035
A5160
A5145 A5145
(PT2)
(EPX)
CJ CJ
A5077 A5080
F2020
A5075
A1090
F0205
(CT2)
(CT2)
F2010
A5082 A5075 A5077
A5090
A5109 A1090
(CT1)
(CT2)
A5170 A5110
A5030
PLUMBING
EQUIPMENT LEGEND
A
B
D
E
F
G
I
CODE
HOT AND COLD WATER
COLD WATER AND DRAIN
COLD AND HOT WATER AND DRAIN
COLD, HOT, AND TREATED WATER AND DRAIN
DRAIN ONLY
ELECTRICAL
120 VOLT, CONVENTIONAL OUTLET
120 VOLT, SPECIAL OUTLET
SPECIAL ELECTRICAL REQUIREMENTS
208/220 VOLT, 3 PHASE
MEDICAL GAS
M --
MISC GAS
STEAM--
MISC
-- AIR, HIGH PRESSURE (85 PSIG) MAX -- --
VENT TO ATMOSPHERE
EARTH, GROUND AND
WALL/CEILING SUPPORT REQUIRED
1/4" = 1'-0"1/4" = 1'-0"
EQUIPMENT SCHEDULE
3/8" = 1'-0" 3/8" = 1'-0" 3/8" = 1'-0"3/8" = 1'-0"3/8" = 1'-0"
1/4" = 1'-0"
3/8" = 1'-0"
1/4" = 1'-0"
3/8" = 1'-0"3/8" = 1'-0"3/8" = 1'-0"3/8" = 1'-0"
E
EXIST TEAM ROOM
EB-362
CLERICAL
WORKSTATION
EB-360
EXIST STERILE SPS
CHIEF
EB-370
EXISTING SPS
ASSISTANT CHIEF
EB-368
F0420
E0123
E0123
F0420
E0123 F0420
F0420
E0120
E0120 F0420
F2000
F0205 F0205
M1840 F0275F0275
F0275
F0275
F0275
F0205
F0275
F0205
F0420
F2000
F2000 F0420
F3200
F3200
A5145
A5145 A5145
M1801
A1015 F3200
M1801 F2000
M1801
A1015
F2000
M1801
A1015
F2000 M1801 A1015
F2000
M1801 A1015
F0275
A1015
M1801
E0090
A1015
AQ-806
AQ-806
AQ-806
AQ-806 6
E0090
A5145
C
D
BREAKOUT/BULK
STORAGE
EB-350
M2105 M2115
F0775 F2700
M1801
U0038
M1840
AQ-806
F0420 F3200
F3200
F0275 F0275
M1801 M1801 M1840
F0420 F2000
F0420 F2000
A1015 A1015
(PT3)
(RB1)
EQEQ
F0420
E0123
E0123
E0123
F0420
F0420 F0275 F2000
F0275
F2000
F2000
F0275
F3200
(RB1)
(PT1)
F0420 F2000
E0090 F0275
F0205
M1801 A1015
A5145
(PT2)
(RB1)
(PT2)
(RB1)
CJ CJ
F0420
E0090 F0275
F0205
M1801 A1015
(PT1)
(RB1)
F3200
U0038 M1801 F2700 M1840 F0775
F3200
(PT1)
(WP)
(VSB)
F0420
(CG1)
3'- 6"
13 12
B
UPH01
UPH01
M8910
STERILE STORAGE
EB-316
M8910
F3200
M8910
M8910
M8910
UPH01
UPH01
UPH01
U0000 U0000
U0000 U0000
M1803 M1801
U0000
U0000
U0000
U0000
M2055
AQ-806
9 M8910
M1803 M1801
UPH01UPH01
M8910 M8910
U0000
F3200
EQ EQ
(PT2)
(SS)
(EPX)
4'- 0"
PLUMBING
EQUIPMENT LEGEND
A
B
D
E
F
G
I
CODE
HOT AND COLD WATER
COLD WATER AND DRAIN
COLD AND HOT WATER AND DRAIN
COLD, HOT, AND TREATED WATER AND DRAIN
DRAIN ONLY
ELECTRICAL
120 VOLT, CONVENTIONAL OUTLET
120 VOLT, SPECIAL OUTLET
SPECIAL ELECTRICAL REQUIREMENTS
208/220 VOLT, 3 PHASE
MEDICAL GAS
M --
MISC GAS
STEAM--
MISC
-- AIR, HIGH PRESSURE (85 PSIG) MAX -- --
VENT TO ATMOSPHERE
EARTH, GROUND AND
WALL/CEILING SUPPORT REQUIRED
1/4" = 1'-0"
1/4" = 1'-0"
EQUIPMENT SCHEDULE
3/8" = 1'-0" 3/8" = 1'-0"3/8" = 1'-0"3/8" = 1'-0"
3/8" = 1'-0"
1/4" = 1'-0"
E
M2055M2055
M8910
M8910
M8910
F0280
E0120 M1801
M1810
F2020
F3050
F3025
F3050
F3050
F3025
U0000
AQ-8072 DISPATCH
EB-356
EXIST DISPATCH
EB-356B
M7300
F3050 F3025
F3050 F3050
F3025
F2020
F0280
M1810
(VSB)
(WP)
(PT2)
(CG1)
(WP)
(VSB)
E0120
(PT2)
4'- 0"
4'- 0"
M1801
PLUMBING
EQUIPMENT LEGEND
A
B
D
E
F
G
I
CODE
HOT AND COLD WATER
COLD WATER AND DRAIN
COLD AND HOT WATER AND DRAIN
COLD, HOT, AND TREATED WATER AND DRAIN
DRAIN ONLY
ELECTRICAL
120 VOLT, CONVENTIONAL OUTLET
120 VOLT, SPECIAL OUTLET
SPECIAL ELECTRICAL REQUIREMENTS
208/220 VOLT, 3 PHASE
MEDICAL GAS
M --
MISC GAS
STEAM--
MISC
-- AIR, HIGH PRESSURE (85 PSIG) MAX -- --
VENT TO ATMOSPHERE
EARTH, GROUND AND
WALL/CEILING SUPPORT REQUIRED1/4" = 1'-0"
EQUIPMENT SCHEDULE
16 15 14 13 12 11 10
C
D
E
A
EXIST TEL
EB-TC2
EXIST ELEC
EB-EC2
EXIST STAFF
LOUNGE
EB-358
EXIST HAC
EB-336
EXIST CARTLIFT
MACH RM
C-2.0
EXISTING SPS
ASSISTANT CHIEF
EB-368
EXIST STERILE SPS
CHIEF
EB-370
CLERICAL
WORKSTATION
EB-360
EXIST TEAM ROOM
EB-362
EXIST DISPATCH
EB-356B
EXIST CART LIFT 2
F1-269
EXIST CART LIFT 1
F1-271
EXISTING CORRIDOR
EB-C03
STERILE STORAGE
EB-316
STAIRWAY
F1-257
BREAKOUT/BULK
STORAGE
EB-350
DISPATCH
EB-356
ANTE
EB-322A
TOILET/SHOWER
EB-318
ANTE/PPE
EB-322B
LOCKER/CHANGING
FEMALE
EB-330
LOCKER/CHANGING
MALE
EB-332
EXISTING TELE
CLOSET
FB-SC1
CLEAN SUPPLY
STORAGE ROOM
EB-300
DECONTAMINATION
EB-320
PREPARATION AND
ASSEMBLY
EB-312B
CORRIDOR
EB-322
VESTIBULE
EB-C30
CORRIDOR
FB-C04
EQUIPMENT TEST
EB-340A
AUTOMATED CART
WASHER
EB-338
TLT STAFF FEMALE
EB-330A
TLT STAFF MALE
EB-332A
DECONTAMINATION
WORK AREA
EB-320B
CLEAN WORKROOM
INSTRUMENT SET
ASSEMBLY
EB-312
STERILIZATION AREA
LOW TEMP
EB-314
STEAM
STERILIZATION
EB-314B
HAC
EB-300A
CORRIDOR
EB-300C
ELEC
EB-300G
SCS OFFICE
EB-316D
SCS OPEN OFFICE
EB-316E
EQUIPMENT
STORAGE
EB-316F
STEAM STERILE
STORAGE
EB-314C
HLD ALCOVE
EB-322C
ROOM SIGN
EYE WASH SIGN
RESTROOM SIGN
EMERGENCY SHOWER SIGN
STAIR SIGN
SIGNAGE LEGEND
PERSONNEL ONLY SIGN
B A
C
/8"
1"5/8
1/4
3/4"
3/4
5/8
3/8
/2"
9"
D
E
F
A. A. 3/16" ACRYLIC P95 COLORLESS ACRYLIC SIGN PANEL. PAINT 1/16" SECOND SURFACE TO MATCH COLOR (MP03849
INERTE GRAY) OR (BM HC-166 KENDALL CHARCOAL). DO NOT PAINT EDGES
B. ROWMARK TEACTILE COPY PIPPED INTO A WITH MINIMUM 1/32" RELIEF. COLOR TO MATCH (ROWMARK 3X1-201,WHITE).
TYPEFACE IS HELVETICA BOLD CONDENSED
C. CLEAR ACRYLIC BEAD BRAILLE.
D. 1/4" X 3/8" SOLID ALUMINUM PLATE WITH #4 HORIZONTAL BRUSHED FINISH AND MATTE CLEAR COAT.
E. SCREENPRINTED COPY. COLOR TO MATCH (BM 2134-30 IRON MOUNTAIN)/ TYPEFACE IS HELVETICA BOLD CONDENSED.
F. 3/16" ACRYLIC P95 COLORLESS ACRYLIC SIGN PANEL. PAINT SECOND SURFACE TO MATCH (MP32071 WHITE WONDER)
(BM I-04 DECORATOR'S WHITE). DO NOT PAINT EDGES
NOTE: 1/16" THICK BLACK ACRYLIC BACKER PANEL
XX-###
ROOM NAME
NAME
NAME
3/4"
CONT.
CONT.
B A
/4"
/8"
1/4
3/4"
5/8
3/4
3/4
/2"
9"
D
E
F
A. A. 3/16" ACRYLIC P95 COLORLESS ACRYLIC SIGN PANEL. PAINT 1/16" SECOND SURFACE TO MATCH COLOR C-1
(MP03849 INERTE GRAY) OR (BM HC-166 KENDALL CHARCOAL).
B. SCREENPRINTED COPY, COLOR TO MATCH(MP32071 WHITE WONDER) (BM I-04 DECORATOR'S WHITE).
TYPEFACE IS HELVETICA BOLD CONDENSED.
C. CLEAR ACRYLIC BEAD BRAILLE.
D. 1/4" X 3/8" SOLID ALUMINUM PLATE WITH #4 HORIZONTAL BRUSHED FINISH AND MATTE CLEAR COAT.
E. ROWMARK TACTILE GRAPHICS AND COPY TIPPED INTO PANEL WITH MINIMUM 1/32" RELIEF.. COLOR TO MATCH
(BM 2134-30 IRON MOUNTAIN). TYPEFACE IS HELVETICA BOLD CONDENSED. ISA SYMBOL TO BE DISPLAYED
WHERE APPLICABLE. SELECT GRAPHIC (MALE OR FEMALE) ACCORDINGLY.
F. 3/16" ACRYLIC P95 COLORLESS ACRYLIC SIGN PANEL. PAINT SECOND SURFACE TO MATCH (MP32071 WHITE
WONDER) (BM I-04 DECORATOR'S WHITE).
XX-###
GENDER
/8"
C
/8"
3/4 "3/8
3/4
E
B
A
9"
A. A. 3/16" ACRYLIC P95 COLORLESS ACRYLIC SIGN PANEL. PAINT SECOND
SURFACE TO MATCH (MP32071 WHITE WONDER) (BM I-04 DECORATOR'S WHITE).
B. COPY SCREENPRINTED TO MATCH (MP03849 INERTE GRAY) (BM HC-166
KENDALL CHARCOAL). TYPEFACE TO BE HELVETICA BOLD.
9"
EMERGENCY EYE
WASH B
A
9"
A. A. 3/16" ACRYLIC P95 COLORLESS ACRYLIC SIGN PANEL. PAINT SECOND SURFACE TO MATCH
(MP32071 WHITE WONDER) (BM I-04 DECORATOR'S WHITE).
B. COPY SCREENPRINTED TO MATCH (MP03849 INERTE GRAY) (BM HC-166 KENDALL CHARCOAL).
TYPEFACE TO BE HELVETICA BOLD.
9"
EMERGENCY
SHOWER
B
A
9"
A. A. 3/16" ACRYLIC P95 COLORLESS ACRYLIC SIGN PANEL. PAINT SECOND SURFACE
TO MATCH (MP32071 WHITE WONDER) (BM I-04 DECORATOR'S WHITE).
B. COPY SCREENPRINTED TO MATCH (MP03849 INERTE GRAY) (BM HC-166 KENDALL
CHARCOAL). TYPEFACE TO BE HELVETICA BOLD.
9"
STAIR (#)
Keep Door Closed
3/4
3/4
3/8
3/4
3/8
3/4
3/8
3/4
1/2
LEVEL B
3/4"
3/4
5/8
EXIT
STAIR UP
B
A. A. 3/16" ACRYLIC P95 COLORLESS ACRYLIC SIGN PANEL. PAINT SECOND SURFACE
TO MATCH (MP32071 WHITE WONDER) (BM I-04 DECORATOR'S WHITE).
B. COPY SCREENPRINTED TO MATCH (MP03849 INERTE GRAY) (BM HC-166 KENDALL
CHARCOAL). TYPEFACE TO BE HELVETICA BOLD.
B
A
9"
9"
1/2
4" 1/4
3/4
1/4
3/4
1/4
3/4
1/4
3/4
1/2
SPS Personnel
DO NOT
ENTER
Beyond This Point.
Area Under Surveillance
1/8" = 1'-0"
BASEMENT ROOM SIGNAGE
C-2.0 EXIST CARTLIFT MACH RM MECHANICAL ROOM
EB-300 CLEAN SUPPLY STORAGE ROOM CLEAN SUPPLY STORAGE ROOM
EB-300A HAC HOUSEKEEPING CLOSET
EB-300C CORRIDOR --
EB-300G ELEC ELECTRICAL CLOSET
EB-312 CLEAN WORKROOM INSTRUMENT SET ASSEMBLY --
EB-312B PREPARATION AND ASSEMBLY PREPARATION AND ASSEMBLY ROOM
EB-314 STERILIZATION AREA LOW TEMP --
EB-314B STEAM STERILIZATION --
EB-314C STEAM STERILE STORAGE STEAM STERILE STORAGE
EB-316 STERILE STORAGE STERILE STORAGE ROOM
EB-316D SCS OFFICE SCS OFFICE
EB-316E SCS OPEN OFFICE SCS OFFICE
EB-316F EQUIPMENT STORAGE EQUIPTMENT/STORAGE ROOM
EB-318 TOILET/SHOWER ANTE/SHOWER ROOM
EB-320 DECONTAMINATION DECONTAMINATION ROOM
EB-320B DECONTAMINATION WORK AREA --
EB-322 CORRIDOR --
EB-322A ANTE ANTE ROOM
EB-322B ANTE/PPE ANTI/ PPE ROOM
EB-322C HLD ALCOVE --
EB-330 LOCKER/CHANGING FEMALE FEMALE LOCKER ROOM
EB-330A TLT STAFF FEMALE WOMEN
EB-332 LOCKER/CHANGING MALE MALE LOCKER ROOM
EB-332A TLT STAFF MALE MEN
EB-336 EXIST HAC HOUSEKEEPING CLOSET
EB-338 AUTOMATED CART WASHER --
EB-340A EQUIPMENT TEST --
EB-350 BREAKOUT/BULK STORAGE BREAKOUT/BULK STORAGE ROOM
EB-356 DISPATCH DISPATCH ROOM
EB-358 EXIST STAFF LOUNGE LOUNGE
EB-360 CLERICAL WORKSTATION SPS OFFICE
EB-362 EXIST TEAM ROOM SPS OFFICE
EB-368 EXISTING SPS ASSISTANT CHIEF SPS ASSISTANT CHEIF
EB-370 EXIST STERILE SPS CHIEF SPS CHIEF
EB-C30 VESTIBULE DECONTAMINATION ROOM
EB-EC2 EXIST ELEC ELECTRICAL CLOSET
EB-TC2 EXIST TEL TELECOM CLOSET
F1-269 EXIST CART LIFT 2 --
F1-271 EXIST CART LIFT 1 --
FB-C04 CORRIDOR --
FB-SC1 EXISTING TELE CLOSET TELECOM CLOSET
3" = 1'-0" 3" = 1'-0" 3" = 1'-0" 3" = 1'-0"3" = 1'-0" 3" = 1'-0"
ALL SIGNAGE TO BE MOUNTED PER ADA GUIDELINES
640-23-108
FCO
FCOFCO
640-23-108