DRAWINGS - TEMPORARY SPS_Part5.pdf
PDF 7 MB Posted
- Solicitation number
- 36C26125R0008
About this file
These drawings are technical documents for the renovation and expansion of the Sterile Processing Service (SPS) at the Veterans Affairs Palo Alto Healthcare System. The project involves constructing temporary modular buildings and trailers to serve as a swing space during renovation, with specific architectural, mechanical, electrical, and telecommunications plans for the temporary facilities. The drawings detail the layout, utility connections, and technical specifications for two SPS trailers and a temporary modular building, including floor plans, fire alarm systems, plumbing, electrical configurations, and technology infrastructure. The drawings provide comprehensive technical guidance for installing and configuring the temporary facilities to maintain operational continuity during the main SPS renovation in Building 100.
The technical drawings cover multiple disciplines, including architectural floor plans, fire suppression systems, electrical site plans, technology riser diagrams, and detailed equipment mounting instructions. Key elements include specifications for wall-mounted equipment, cable routing, power distribution, telecommunications infrastructure, security systems, and compliance with VA healthcare standards. The drawings are part of a larger project to modernize the SPS, with specific attention to maintaining functionality, safety, and operational efficiency during the renovation process.
View the file
Other files
Show all 49
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SPS TRAILER
S P
S T
R A
IL
E
R
75cd
75cd
F
75cd
M-108
TOILET
FEMALE
M-108
M-107
LOCKER
FEMALE
M-107
M-106
LOCKER
MALE
M-106
M-103
CORRIDOR
M-103
M-104
HAC
M-104
M-100B
WORKSTATION
M-100B
M-101
OFFICE
SPS
CHIEF
M-101
M-102
MANUAL
CART
WASH
M-102
M-100
CLEAN
STORAGE
M-100
M-100A
BIN
ASSEMBLY
M-100A 75cd
F c d c d c d
75cd
M-105
TOILET
MALE
M-105
15cd
15cd
F
75cd
F
TEMPORARY MODULAR BUILDING
F
F
75cd 75cd
75cd75cd
F
15cd
75cd
15cd
VSVSVSWF
CORRIDOR
ENTRY
KEY PLAN
RADIOLOGY BUILDING
BUILDING 100
BUILDING 102
BUILDING 05
TEMP.
MODULAR
OFFICE
TEMP. SPS
T E
M P
. S P
S
N
TEMP.
MODULAR
STORAGE
CORRIDOR
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
PROJECT NUMBERCONSULTANTS:
DRAWING #
VA HEALTH CARE SYSTEM APPROVAL:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH KS COA NO. A-930 EXP. 12/31/2025
ENG KS COA. NO. E-2586 EXP. 12/31/2025
CIVIL
H2B. INC.
1125 N LOOP WEST, STE 800
HOUSTON, TX 77008
(713) 864-2900
MEP / TECH ENGR
SPUR DESIGN
2519 MADISON AVE, STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
STRUCTURAL ENGR
H2B ENGINEERS, INC.
1225 NORTH LOOP WEST, #800
HOUSTON, TX 77008
(713) 864-2900
HEALTHCARE PLANNER
THE INNOVA GROUP
9442 N. CAPITAL OF TEXAS HWY, STE 325
AUSTIN, TX 78759
(512) 346-8700
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, STE 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
DRAWING NUMBER
BUILDING NUMBER
/2
/2
:1
:3
A
M
FIRE ALARM FLOOR PLAN
LAL 50 OF 75BLS
BID DOCUMENTS
RENOVATION AND EXPANSION OF SPS
05/30/2025
640-23-108
PALO ALTO VA MC
3801 MIRANDA AVENUE
PALO ALTO, CA 94304
FA102
B100
N
1/8" = 1'-0"
FIRE ALARM FLOOR PLAN - MODULAR BUILDING1
SHEET KEYNOTES
MARK KEYNOTE
01 SPS TRAILER PRE-MANUFACTURED FIRE ALARM SYSTEM TO BE
MONITORED BY THE BUILDING 102 FIRE ALARM PANEL. ON-SITE FIRE
ALARM SHOP PERSONNEL TO CONFIRM THE ADDRESSES TO BE
USED TO IDENTIFY THESE SPACES.
03 FOR FIRE RISER THAT IS LOCATED EXTERIOR TO THE BUILDING.
No. REVISION DESCRIPTION DATE
05/30/2025 721 ASI 1 05.30.2025
IN-BUILDING RISER ASSEMBLY
DOUBLE-CHECK BACKFLOW
PREVENTION ASSEMBLY
RISER MANIFOLD WITH
TEST AND DRAIN
BACKFLOW FORWARD
FLUSHING CONNECTION
WITH THREE 2-1/2" VALVES
FIRE DEPARTMENT
CONNECTION
BUTTERFLY CONTROL
VALVE
CHECK VALVE
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
PROJECT NUMBERCONSULTANTS:
DRAWING #
VA HEALTH CARE SYSTEM APPROVAL:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH KS COA NO. A-930 EXP. 12/31/2025
ENG KS COA. NO. E-2586 EXP. 12/31/2025
CIVIL/STRUCTURAL ENGR
H2B, INC.
1225 N LOOP WEST, STE 800
HOUSTON, TX 77008
(713) 864-2900
MEP / TECH ENGR
SPUR DESIGN
2519 MADISON AVE, STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
HEALTHCARE PLANNER
THE INNOVA GROUP
9442 N. CAPITAL OF TEXAS HWY, STE 325
AUSTIN, TX 78759
(512) 346-8700
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, STE 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
DRAWING NUMBER
BUILDING NUMBER
/2
/2
:1
:3
A
M
FIRE SUPPRESSION NOTES
LAL 51 OF 75BLS
BID DOCUMENTS
RENOVATION AND EXPANSION OF SPS
05/30/2025
640-23-108
PALO ALTO VA MC
3801 MIRANDA AVENUE
PALO ALTO, CA 94304
FX001
B100
FIRE SUPRESSION GENERAL NOTES
GENERAL:
1. THE CONTRACTOR SHALL CAREFULLY REVIEW ALL APPLICABLE
DESIGN CRITERIA, THESE DRAWINGS, AND THE PROJECT
SPECIFICATIONS FOR IMPORTANT QUALIFICATION, SUBMITTAL,
PRODUCT, INSTALLATION, AND TESTING REQUIREMENTS.
2. ALL SUBMITTALS, INSTALLATION, AND TESTING SHALL BE COMPLETED
IN A NEAT, WORKMAN-LIKE MANNER.
3. PRODUCT, DESIGN, INSTALLATION, AND TESTING ALTERNATE
APPROACHES AND/OR SUBSTITUTIONS WILL BE CONSIDERED BY THE
PROJECT FIRE PROTECTION ENGINEER IF THE CONTRACTOR
PROVIDES WRITEEN, WELL-DOCUMENTED, ENGINEERING-BASED
SUBSTANTIATION FOR PROPOSED ALTERNATIVE.
APPLICABLE CODES AND STANDARDS:
1. VA FIRE PROTECTION DESIGN MANUAL NINTH EDITION – NOVEMBER
2. NFPA 1: FIRE CODE (2024)
3. NFPA 13: STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS
(2022)
4. NFPA 24: STANDARD FOR THE INSTALLATION OF PRIVATE FIRE MAINS
AND THEIR APPURTENANCES (2022)
5. NFPA 25: STANDARD FOR THE INSPECTION, TESTING, AND
MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS (2023)
6. NFPA 70: NATIONAL ELECTRICAL CODE (2023)
7. NFPA 72: NATIONAL FIRE ALARM AND SIGNALING CODE (2022)
8. NFPA 101: LIFE SAFETY CODE (2024)
9. NFPA 170: STANDARD FOR FIRE SAFETY AND EMERGENCY SYMBOLS
(2024)
10. INTERNATIONAL BUILDING CODE – 2024 EDITION
PROJECT SCOPE:
1. THE SCOPE FOR THIS PROJECT IS TO INSTALL A NEW WET-PIPE FIRE
RISER FOR EACH PROJECT SCOPE AREA. A SINGLE FIRE RISER WILL
SERVE THE MODULAR BUILDINGS AND CONNECTING CORRIDOR. A
SINGLE FIRE RISER WILL SERVE THE STORAGE TRAILER LOCATED AT
THE LOADING DOCK.
2. CONTRACTOR IS RESPONSIBLE FOR CONNECTING PRE-
MANUFACTURED FIRE SPRINKLER SYSTEMS IN THE SPS TRAILERS TO
A WATER SUPPLY AND TESTING THE SYSTEMS. REFER TO CIVIL FOR
COORDINATION OF THE WATER TO THE TRAILERS.
INSTALLATION:
1. INSTALLATION SHALL BE COMPLETED IN ACCORDANCE WITH THE
REQUIREMENTS OF NFPA 13.
2. ALL EQUIPMENT SHALL BE SUPPORTED BY THE BUILDING STRUCTURE
USING APPROVED METHODS. ALL EQUIPMENT SHALL BE LISTED OR
APPROVED FOR FIRE PROTECTION USE BY A NATIONALLY
RECOGNIZED TESTING LABORATORY.
3. THE CONTRACTOR SHALL NOT APPRECIABLY DEVIATE FROM THE
APPROVED DESIGN WITHOUT WRITTEN APPROVAL FROM THE
PROJECT FIRE PROTECTION ENGINEER.
4. PENETRATIONS OF FIRE-RATED CONSTRUCTION SHALL BE PROTECTED
USING LISTED OR APPROVED METHODS.
5. THE CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL FIRE
SUPPRESSION EQUIPMENT TO AVOID CONFLICTS WITH OTHER
DISCIPLINES.
6. THE OWNER IS RESPONSIBLE FOR MAINTAINING THE BUILDING
ENVIROMENT AT A TEMPERATURE OF AT LEAST 40 DEGREES
FAHRENHEIT TO PREVENT FREEZING.
PIPING AND FITTINGS:
1. NEW PIPING SHALL BE BLACK STEEL. PIPING THAT IS 2 INCHES IN
DIAMETER OR SMALLER SHALL BE A MINIMUM OF SCHEDULE 40. PIPING
THAT IS 2 ½ INCHES IN DIAMATER OR LARGER SHALL BE A MINIMUM OF
SCHEDULE 10.
2. THE USE OF CPVC PIPING IS NOT PERMITTED.
3. PIPING SHALL BE ARRANGED FOR FLUSHING. READILY REMOVABLE
FITTINGS MUST BE PROVIDED AT THE END OF ALL CROSS MAINS.
HANGERS AND SEISMIC DESIGN:
1. HANGERS AND PIPE SUPPORTS SHALL BE PROVIDED AND INSTALLED
IN ACCORDANCE WITH NFPA 13.
2. THE SEISMIC DESIGN CATEGORY FOR THE PROJECT IS “F”. SEISMIC
SUPPORT BRACING IS REQUIRED TO BE PROVIDED FOR THE SYSTEM.
REFER TO THE STRUCTURAL DRAWING SHEETS FOR ADDITIONAL
INFORMATION REGARDING THE SEISMIC LOAD.
FIRE SPINKLERS:
1. NEW FIRE SPRINKLERS SHALL BE FM APPROVED AND QUICK-
RESPONSE TYPE, UNLESS INDICATED OTHERWISE.
2. NEW FIRE SPRINKLERS SHALL BE ORDINARY-TEMPERATURE RAYED,
UNLESS INDICATED OTHERWISE.
3. PENDENT SPRINKLERS SHALL BE INSTALLED IN THE CENTER OF
CEILING TILES.
4. FIRE SPRINKLER OBSTRUCTIONS ARE TO BE ADDRESSED IN
ACCORDANCE WITH NFPA 13.
VALVES AND DRAINS:
1. ALL FIRE SPRINKLER VALVES SHALL BE INSTALLED AND IDENTIFIED AS
REQUIRED BY NFPA 13.
2. THE FIRE SPRINKLER CONTRACTOR IS RESPONSIBLE FOR
COORDINATING THE FINAL LOCATION AND CONNECTION OF VALVE
TAMPER SWITCHES AND WATER FLOW SWITCHES WITH THE FIRE
ALARM CONTRACTOR.
3. DRAINS SHALL BE PIPED TO DISCHARGE TO THE EXTERIOR OF THE
BUILDINGS. SPLASH BLOCKS SHALL BE USED AT THE DRAIN
DISCHARGE WHERE REQUIRED TO PREVENT DAMAGE.
SYSTEM TESTING:
1. THE CONTRACTOR IS RESPONSIBLE FOR COMPLETING ALL REQUIRED
ACCEPTANCE AND RE-ACCEPTANCE TESTING PER NFPA 13 AND THE
PROJECT SPECIFICATIONS.
2. THE CONTRACTING OFFICERS’ REPRESENTATIVE OR A DESIGNATED
REPRESENTATIVE SHALL BE PRESENT TO WITNESS AND APPROVE THE
TESTING. THE PROJECT FIRE PROTECTION ENGINEER SHALL BE
PRESENT TO WITNESS THE FINAL ACCEPTANCE TESTING.
3. THE CONTRACTOR SHALL COORDINATE WITH THE UTILITY
CONTRACTOR TO ENSURE THAT THE UNDERGROUND LEAD-IN HAS
BEEN INSTALLED AND TESTED IN ACCORDANCE WITH NFPA 24 BEFORE
CONNECTION TO THE FIRE RISER.
FIRE SUPRESSION GENERAL NOTES CONTD
SCALE =1
FIRE SUPPRESSION RISER DETAIL
No. REVISION DESCRIPTION DATE
SPS TRAILER
P
S T
R A
IL
R
M-108
TOILET
FEMALE
M-108
M-107
LOCKER
FEMALE
M-107
M-106
LOCKER
MALE
M-106
M-103
CORRIDOR
M-103
M-104
HAC
M-104
M-100B
WORKSTATION
M-100B
M-101
OFFICE
SPS
CHIEF
M-101
M-102
MANUAL
CART
WASH
M-102
M-100
CLEAN
STORAGE
M-100
M-100A
BIN
ASSEMBLY
M-100A
TEMPORARY MODULAR BUILDING
M-105
TOILET
MALE
M-105
CORRIDOR
ENTRY
HAZARD CLASSIFICATION LEGEND
LIGHT HAZARD
(0.10 GPM/FT² OVER 1,500 FT² WITH 100 GPM EXTERIOR HOSE DEMAND)
DESCRIPTIONHATCH
OUT OF SCOPE
ORDINARY HAZARD 2
(0.20 GPM/FT² OVER 1,500 FT² WITH 250 GPM EXTERIOR HOSE DEMAND)
KEY PLAN
RADIOLOGY BUILDING
BUILDING 100
BUILDING 102
BUILDING 05
TEMP.
MODULAR
OFFICE
TEMP. SPS
T E
M P
. S P
S
N
TEMP.
MODULAR
STORAGE
CORRIDOR
SYMBOL DESCRIPTION
FIRE SUPPRESSION LEGEND
FIRE SUPPRESSION RISER
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
PROJECT NUMBERCONSULTANTS:
DRAWING #
VA HEALTH CARE SYSTEM APPROVAL:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH KS COA NO. A-930 EXP. 12/31/2025
ENG KS COA. NO. E-2586 EXP. 12/31/2025
CIVIL/STRUCTURAL ENGR
H2B, INC.
1225 N LOOP WEST, STE 800
HOUSTON, TX 77008
(713) 864-2900
MEP / TECH ENGR
SPUR DESIGN
2519 MADISON AVE, STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
HEALTHCARE PLANNER
THE INNOVA GROUP
9442 N. CAPITAL OF TEXAS HWY, STE 325
AUSTIN, TX 78759
(512) 346-8700
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, STE 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
DRAWING NUMBER
BUILDING NUMBER
/2
/2
:1
:4
A
M
FIRE SUPPRESSION FLOOR PLAN
LAL 52 OF 75BLS
BID DOCUMENTS
RENOVATION AND EXPANSION OF SPS
05/30/2025
640-23-108
PALO ALTO VA MC
3801 MIRANDA AVENUE
PALO ALTO, CA 94304
FX101
B100
N
1/8" = 1'-0"
FIRE SUPPRESSION HAZARD CLASSIFICATION FLOOR PLAN - TEMPORARY BUILDING1
No. REVISION DESCRIPTION DATE
MA
MV
CO
EV
VE
AI
FOV
FOR
FOS
FP
LPG
NPW
NO
O
N
G
MPG
G
MPG
CA
CD
ACD
V
VBG
VBF
AV
AW
AW
ST
OST
GW
GW
S
W
ID
T
T
SCW
WS
140°
S
W
CAP
AV
TYPICAL UNIT NO.
BUILDING NO. WHERE EQUIPMENT
PUMP NO.3 IN BUILDING NO.26
EQUIPMENT ABBREVIATION (PUMP)
IS LOCATED.
ORAL EVACUATION
LABORATORY VACUUM
LABORATORY AIR
TEMPERED WATER RETURN
TEMPERED WATER SUPPLY
INDUSTRIAL AIR
LA
LV
OA
IA
TWR
TWS
FILTERED COLD WATERFCW
FUEL OIL DISCHARGEFOD
ANCHOR
CONNECTION - SIDE
ECCENTRIC REDUCER
CONNECTION - BOTTOM, 45° OR 90°
CONNECTION - TOP, 45° OR 90°
DIRECTION OF PIPE PITCH (DOWN)
RISE OR DROP IN PIPE
STRAINER
FLOAT & THERMOSTATIC TRAP SET INCLUDING
PIPING ACCESSORIES
PIPING ACCESSORIES
INVERTED BUCKET TRAP SET INCLUDING
FLOOR DRAIN (FD), SIZE & TYPE
ROOF DRAIN (RD), SIZE & TYPE
FLOOR SINK (FS), SIZE & TYPE
NATURAL GAS BELOW GRADE (G)
CONDENSATE DRAIN (CD)
INDIRECT DRAIN (ID)
NATURAL GAS (G)
NITROUS OXIDE (NO)
LIQUIFIED PETROLEUM GAS (LPG)
FIRE PROTECTION (FP)
WATER SERVICE (WS)
COMPRESSED AIR (CA)
NITROGEN (N)
MEDICAL AIR (MA)
OXYGEN (O)
DOMESTIC HOT WATER RECIRC.
SOIL PIPING - ABOVE FLOOR (S)
SOIL PIPING - BELOW FLOOR (S)
STORM DRAIN - ABOVE FLOOR (ST)
ACID WASTE - ABOVE FLOOR (AW)
ACID WASTE - BELOW FLOOR (AW)
DOMESTIC COLD WATER
DOMESTIC HOT WATER
140° DOMESTIC HOT WATER (140°)
WASTE PIPING - ABOVE FLOOR (W)
WASTE PIPING - BELOW FLOOR (W)
GREASE WASTE - ABOVE FLOOR (GW)
GREASE WASTE - BELOW FLOOR (GW)
SOFTENED COLD WATER (SCW)
ACID VENT (AV)
VENT PIPING (V)
HOSE BIBB (HB)
NONFREEZE WALL HYDRANT (NW)
WALL CLEANOUT (WCO)
FLOOR CLEANOUT (FCO)
EXTERIOR CLEANOUT (ECO)
THERMOSTATIC MIXING VALVE
BACKFLOW PREVENTER
OVERFLOW STORM DRAIN - ABOVE FLOOR (OST)
NON POTABLE WATER (NPW)
FUEL OIL SUPPLY (FOS)
FUEL OIL RETURN (FOR)
FUEL OIL VENT (FOV)
AUXILIARY CONDENSATE DRAIN (ACD)
VENT BELOW GRADE (VBG)
VENT BELOW FLOOR (VBF)
CARBON DIOXIDE (CO)
MEDICAL VACUUM (MV)
EVACUATION (EV)
MEDICAL VACUUM EXHAUST (VE)
MEDICAL AIR INTAKE (AI)
TRAP PRIMER LINE (T)
WATER METER
MEDIUM PRESSURE NATURAL GAS (MPG)
MEDIUM PRESSURE NATURAL GAS ON ROOF (MPG)
ELBOW DOWN WITH SHUT-OFF VALVE (SOV)
TEE DOWN WITH SHUT-OFF VALVE (SOV)
TEE UP WITH SHUT-OFF VALVE (SOV)
RECIRCULATION PUMP
DIRECTION OF FLOW
EXISTING PIPING TO REMAIN
EXISTING PIPING TO BE REMOVED
FLANGE CONNECTION
CLEANOUT
ELBOW DOWN
ELBOW UP
TEE DOWN
ELBOW UP WITH SHUT-OFF VALVE (SOV)
TEE UP
UNION
THERMOMETER
PRESSURE GAUGE
PRESSURE REDUCING VALVE
REDUCER
BALL VALVE
GATE VALVE WITH 3/4 " HOSE ADAPTER
CHECK VALVE
ANGLE GLOBE VALVE
BUTTERFLY VALVE
MODULATING CONTROL VALVE
TWO POSITION CONTROL VALVE
THREE-WAY MODULATING CONTROL VALVE
BALANCING VALVE
PRESSURE RELIEF VALVE
GATE VALVE
MANUAL AIR VENT
TEST PLUG (PRESSURE/TEMPERATURE)
GLOBE VALVE
PRESSURE REGULATING VALVE
THREE-WAY TWO POSITION CONTROL VALVE
AUTOMATIC AIR VENT
PLUMBING KEYNOTE
PLUMBING EQUIPMENT DESIGNATION
MECHANICAL EQUIPMENT DESIGNATION TAG
OWNER FURNISHED, CONTRACTOR INSTALLED
EQUIPMENT DESIGNATION
NEW WORK TO EXISTING WORK CONNECTION POINT
DETAIL NUMBER
SHEET NUMBER
LIMIT OF DEMOLITION
TRAP PRIMER LINE - BELOW SLAB (T)
CO
DOUBLE EXTERIOR CLEANOUT (ECO)
CLEANOUTS
DRAINS AND TRAPS
EQUIPMENT
FITTINGS AND ACCESSORIES
SHEET NUMBER
SECTION NUMBER
MEDICAL GAS OUTLET (TYPE)
EXISTING TO REMAIN
A
A/E ARCHITECT / ENGINEER
AD AREA DRAIN/ACCESS DOOR
AFF ABOVE FINISH FLOOR
AFG ABOVE FINISH GRADE
AG AIR GAP
AP ACCESS PANEL
AS AUTOMATIC SPRINKLER
ASD ADJUSTABLE SPEED DRIVES
ASD AUTOMATIC SPRINKLER DRAIN
ASHRAE AMERICAN SOCIETY OF HEATING,REFRIGERATION, AIR
CONDITIONING ENGINEERS
ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS
ASPE AMERICAN SOCIETY OF PLUMBING ENGINEERS
ASR AUTOMATIC SPRINKLER RISER
AV ACID VENT
AW ACID WASTE
B
BFP REDUCED PRESSURE BACKFLOW PREVENTER
BHP BREAK HORSEPOWER
BSP BLACK STEEL PIPE
BT BATHTUB
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
C
C CELSIUS
CA COMPRESSED AIR
CGA COMPRESSED GAS ASSOCIATION
CFM CUBIC FEET PER MINUTE
CI CAST IRON
CO CLEANOUT
CS CLINICAL SINK
CV CONTROL VALVE
D
DCW DOMESTIC COLD WATER
DFU DRAINAGE FIXTURE UNITS
DHW DOMESTIC HOT WATER
DHWR DOMESTIC HOT WATER RETURN
DHWS DOMESTIC HOT WATER SUPPLY
DI DEIONIZED WATER
DN DOWN
DOE DEPARTMENT OF ENERGY
DS DOWNSPOUT
DW DISHWASHER
DWG DRAWING
DWH DOMESTIC WATER HEATER
DWR DRINKING WATER RETURN
DWS DRINKING WATER SUPPLY
DWV DRAIN WASTE VENT
E
EL ELEVATION
EMCS ENERGY MONOSERRAT AND CENTRAL SYSTEM
EPA ENVIROMENTAL PROTECTION AGENCY
EPACT ENERGY POLICY ACT
ESC ESCUTCHEON
ESH EMERGENCY SHOWER
ET EXPANSION TANK
EWH ELECTRIC WATER HEATER
EWS EYE WASH STATION
EWS/SH EYE WASH/DRENCH SHOWER
EX EXISTING
F
F FAHRENHEIT
FCO FLOOR CLEANOUT
FCW FILTERED COLD WATER
FD FLOOR DRAIN
FDC FIRE DEPARTMENT (HOSE) CONNECTION
FM FLOW METER
FOP FUEL OIL PUMP
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FOV FUEL OIL VENT
FS FLOOR SINK
FS FLOW SWITCH
FU FIXTURE UNITS
G
GAL GALLON
GCO GRADE CLEANOUTS
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPR GAS PRESSURE REGULATOR
GRS GAS REGULATOR STATION
GT GREASE TRAP
GVTR GAS VENT THROUGH ROOF
GWH GAS FIRED WATER HEATER
H
H&CW HOT AND COLD WATER
HB HOSE BIBB
HD HUB DRAIN
HEX HEAT EXCHANGER
HP HORSEPOWER
HS HAND SINK
HST HOT WATER STORAGE TANK (DOMESTIC)
HWB HOT WATER BOILER
HWCP HOT WATER CIRCULATING PUMP
HWP HOT WATER PUMP
HYD HYDRANT
I
ID INSIDE DIAMETER
IE INVERT ELEVATION
ICW INDUSTRIAL COLD WATER
IHW INDUSTRIAL HOT WATER
INV INVERT
IPC INTERNATIONAL PLUMBING CODE
IRW IRRIGATION WATER
IW INDIRECT WASTE
IWH INSTANTANEOUS WATER HEATER
IWR INDUSTRIAL WATER RETURN
IWS INDUSTRIAL WATER SUPPLY
K
KW KILOWATT
KWH KILOWATT-HOUR
L
L/S LITER PER SECOND
LA LABORATORY AIR
LAV LAVATORY
LBS/HR POUNDS PER HOUR
LCW LABORATORY COLD WATER
LHW LABORATORY HOT WATER
LNG LIQUID NATURAL GAS
LOX LIQUID OXYGEN
LV LABORATORY VACUUM
LW LOW WATER
M
M METER
MA MEDICAL AIR
MAV MANUAL AIR VENT
MBH 1000 BTUH
MED MEDICAL
MER MECHANICAL EQUIPMENT ROOM
MH MANHOLE
MOU MEMORANDUM OF UNDERSTANDING
MSB MOP SERVICE BASIN
MV MEDICAL VACUUM
N
N2 NITROGEN
N20 NITROUS OXIDE
NC NORMALLY CLOSED
NG NATURAL GAS
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NOM. NOMINAL
NPW NON POTABLE WATER
NTS NOT TO SCALE
O
O OXYGEN
OC ON CENTER
OD OUTSIDE DIAMETER
OFD OVERFLOW DRAIN
OR OPERATING ROOM
OVFL OVERFLOW
P
PA PASCAL
PD PRESSURE DROP OR DIFFERENCE
PDI PLUMBING AND DRAINAGE INSTITUTE
PG PRESSURE GAGE
PP PLUMBING PUMP
PPM PARTS PER MILLION
PRS PRESSURE REDUCING STATION
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH ATMOSPHERE
PSIG POUNDS PER SQUARE INCH GAUGE
PTRV PRESSURE TEMPERATURE RELIEF VALVE
PW POTABLE WATER
R
RD ROOF DRAIN
RDL ROOF DRAIN LEADER
RL ROOF LEADER
RP RECIRCULATION PUMP
RO REVERSE OSMOSIS WATER
RWL RAIN WATER LEADER
S
SAN SANITARY SEWER
SMACNA SHEET METAL AND AIR CONDITIONING
CONTRACTORS NATIONAL ASSOCIATION
SCFM STANDARD CUBIC FOOT/MINUTE
SCW SOFTENED COLD WATER
SDMH STORM DRAIN MANHOLE
SHW SOFTENED HOT WATER
SP SUMP PUMP
SPR SPRINKLER LINE
SQFT/SF SQUARE FEET
SS STAINLESS STEEL
ST STORAGE TANK
SW STORM WATER
T
TCV TEMPERATURE CONTROL VALVE
TD TEMPERATURE DIFFERENCE
TD TRENCH DRAIN
TDH TOTAL DYNAMIC HEAD
TEMP TEMPERATURE
TMV THERMOSTATIC MIXING VALVE
TP TRAP PRIMER
TSTAT THERMOSTAT
TWR TEMPERED WATER RETURN
TWS TEMPERED WATER SUPPLY
TYP TYPICAL
V
V VENT
VAC VACUUM
VB VACUUM BREAKER
VCO VACUUM CLEANER OUTLET
VP VACUUM PUMP
VS VENT STACK
VSD VARIABLE SPEED DRIVE
VTR VENT THROUGH ROOF
W
W WASTE
WC WATER CLOSET
WCO WALL CLEANOUT
WG WATER GAGE
WH WALL HYDRANT
WH WATER HEATER
WHA WATER HAMMER ARRESTER
WL WATER LINE
WM WATER METER
WPD WATER PRESSURE DROP
WS WASTE STACK
WSFU WATER SUPPLY FIXTURE UNITS
Y
YCO YARD CLEANOUT
YH YARD HYDRANT
26-P 3
PIPING SYMBOLS
ANNOTATION
XX-1
xx
PL-100
PL-100
GENERAL PLUMBING SYMBOLS
DENTAL
MEDICAL GASES
STORM
FUEL
EXISTING PIPING
WATER
WASTE
VALVE SYMBOLS
ETR
ABBREVIATIONS
ETR EXISTING TO REMAIN
TFA TO FLOOR ABOVE
TFB TO FLOOR BELOW
FFA FROM FLOOR ABOVE
FFB FROM FLOOR BELOW
THIS LEGEND DEFINING TYPICAL ABBREVIATIONS AND SYMBOLS IS INTENDED TO BE AN OVERALL LEGEND FOR ALL PROJECTS. PLEASE UNDERSTAND THAT NOT ALL ABBREVIATIONS OR SYMBOLS WILL BE UTILIZED FOR EVERY PROJECT. MANY OF THE SYMBOLS WILL BE UTILIZED IN DETAILS AND DIAGRAMS VICE PLAN SHEETS.
EXISTING TO DEMOLISHETD
ST STORM DRAIN - BELOW FLOOR (ST)
PLUMBING GENERAL NOTES:
A. SLOPE SOIL AND WASTE PIPE 3" AND LARGER AT 1/8" PER FT. MINIMUM, SIZE LESS
THAN 3" SLOPE 1/4" PER FT. MINIMUM, UNLESS NOTED OTHERWISE.
B. ALL PIPING SHALL BE COORDINATED WITH CIVIL UTILITY PIPING, FIRE PROTECTION,
DUCTWORK, MECHANICAL PIPING, LIGHTING, STRUCTURAL AND ARCHITECTURAL
SYSTEMS.
C. PIPE CLEANOUTS SHALL BE LINE SIZE (6" MAX.). LOCATE 100' APART MAXIMUM FOR
SIZES UP THROUGH 6".
D. PLUMBING VENTS THROUGH ROOF (VTR) SHALL BE 3" MINIMUM. SMALLER VTR'S
INDICATED SHALL INCREASE TO 3" PIPE, 12" BELOW ROOF.
E. ACCESS PANELS SHALL BE PROVIDED FOR ALL WATER HAMMER ARRESTORS
LOCATED IN WALLS TO ACCESS EQUIPMENT. PANEL SHALL BE AS LARGE AS
PRACTICAL FOR THE FUNCTION THEY ARE INTENDED.
F. DO NOT SCALE DRAWINGS, SEE ARCHITECTURAL FLOOR PLAN FOR DIMENSIONS.
G. ALL PLUMBING WORK SHALL COMPLY WITH THE LATEST INTERNATIONAL PLUMBING
CODE.
H. PIPE ROUTING IS SCHEMATIC AS SHOWN AND IS NOT INTENDED TO INDICATE EXACT
ROUTING. CONTRACTOR SHALL PROVIDE ANY ADDITIONAL OFFSET AND FITTINGS
REQUIRED FOR PROPER INSTALLATION AND TO MAINTAIN CLEARANCES.
I. CONCEAL PIPING ABOVE CEILING AND WITHIN WALLS OR CHASES, EXCEPT IN
MECHANICAL SPACES OR WHEN OTHERWISE NOTED.
J. SEE ARCHITECTURAL DRAWINGS FOR FIXTURE LOCATIONS AND MOUNTING HEIGHTS.
K. PROVIDE TRAP PROTECTION FOR ALL FLOOR DRAINS.
L. PROVIDE AN AIR GAP, WHEN REQUIRED BY CODE, SERVING INDIVIDUAL FIXTURES,
DEVICES, APPLIANCES AND APPARATUS.
M. COORDINATE PIPING WITH ELECTRICAL EQUIPMENT PRIOR TO INSTALLATION. ROUTE
PIPING TO AVOID ELECTRICAL EQUIPMENT AND CLEARANCE AREAS.
N. ANY DEVIATIONS IN ELECTRICAL REQUIREMENTS FROM THE BASIS OF DESIGN FOR
THE PLUMBING EQUIPMENT SHALL BE THE RESPONSIBILITY OF THE PLUMBING
CONTRACTOR TO ENSURE COORDINATION WITH THE ELECTRICAL CONTRACTOR FOR
PROPER SIZE ELECTRICAL MATERIAL AND EQUIPMENT AT NO ADDITIONAL COST.
O. PROVIDE WATER HAMMER ARRESTORS PER STANDARD PDI-WH-201.
P. CONTRATOR TO TEST THE CITY WATER TO MEET THESE PARAMETER FOR THE
TRAILERS;
PH : 6-9 pH
COLOR & TURBIDITY: COLORLESS, CLEAR WITH SEDIMENT
CHLORIDE: < 250 mg/L CONDUCTIVITY: <500 uS/cm Cu (COPPER) : <0.1 mg/L Fe (IRON) : <0.2 mg/L Mn (MANGANESE) : <0.1 mg/L TOTAL HARDNESS: <150 mg CaCO3/L th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
PROJECT NUMBERCONSULTANTS:
DRAWING #
VA HEALTH CARE SYSTEM APPROVAL:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH KS COA NO. A-930 EXP. 12/31/2025
ENG KS COA. NO. E-2586 EXP. 12/31/2025
CIVIL
H2B, INC.
1225 N LOOP WEST, STE 800
HOUSTON, TX 77008
(713) 864-2900
MEP / TECH ENGR
SPUR DESIGN
2519 MADISON AVE, STE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
STRUCTURAL ENGR
H2B, INC.
1225 N LOOP WEST, STE 800
HOUSTON, TX 77008
(713) 864-2900
HEALTHCARE PLANNER
THE INNOVA GROUP
9442 N. CAPITAL OF TEXAS HWY, STE 325
AUSTIN, TX 78759
(512) 346-8700
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, STE 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
DRAWING NUMBER
BUILDING NUMBER
/2
/2
:5
:2
A
M
PLUMBING LEGEND
RTB 57 OF 76RS
BID DOCUMENTS
RENOVATION AND EXPANSION OF SPS
05/30/2025
640-23-108
PALO ALTO VA MC
3801 MIRANDA AVENUE
PALO ALTO, CA 94304
P-000
B100
SPUR #: 1795.07No. REVISION DESCRIPTION DATE
53 OF 721 ASI 1 05.30.2025
BCDE A
SPS TRAILER NO.1
S P
S T
R A
IL
E
R N
O .2
TEMPORARY MODULAR BUILDING
APPROX. 1,855 SQ. FT
TEMPORARY
SPS TRAILER
STORAGE UNIT
RADIOLOGY
ADDITION
B U
IL
D
IN
G
TEMPORARY
SPS TRAILER
STORAGE UNIT
3/4" HWR
1 1/4" HW
1 1/2" CW
1 1/4" HW
3/4" HWR
1 1/2" CW
3/4" HWR
1 1/4" HW
1 1/2" CW
4" SS
4" SS
P-400
P-400
1 1/2" CW
MOBILE
DOMESTIC HOT
WATER SYSTEM
3" CW
RPZRPZ
2 1/2" CW
3/4" HWR
2" HW2" HW 1 1/2" HW
EWH-2EWH-2
2" CW2" CW
3" CW3" CW
DHWCP-2
4" CONCRETE PAD
3' CLEARANCE AREA
ET-2
DAYLIGHT DRAINS OFF
OF RPZ TO OUTSIDE.
KEY PLAN
RADIOLOGY BUILDING
BUILDING 100
BUILDING 102
BUILDING 05
TEMP.
MODULAR
OFFICE
TEMP. SPS
T E
M P
. S P
S
N
TEMP.
MODULAR
STORAGE
CORRIDOR
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
PROJECT NUMBERCONSULTANTS:
DRAWING #
VA HEALTH CARE SYSTEM APPROVAL:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH KS COA NO. A-930 EXP. 12/31/2025
ENG KS COA. NO. E-2586 EXP. 12/31/2025
CIVIL
H2B, INC.
1225 N LOOP WEST, STE 800
HOUSTON, TX 77008
(713) 864-2900
MEP / TECH ENGR
SPUR DESIGN
2519 MADISON AVE, STE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
STRUCTURAL ENGR
H2B, INC.
1225 N LOOP WEST, STE 800
HOUSTON, TX 77008
(713) 864-2900
HEALTHCARE PLANNER
THE INNOVA GROUP
9442 N. CAPITAL OF TEXAS HWY, STE 325
AUSTIN, TX 78759
(512) 346-8700
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, STE 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
DRAWING NUMBER
BUILDING NUMBER
/2
/2
:5
:2
A
M
PLUMBING SITE PLAN - TEMPORARY
SPS
RTB 58 OF 76RS
BID DOCUMENTS
RENOVATION AND EXPANSION OF SPS
05/30/2025
640-23-108
PALO ALTO VA MC
3801 MIRANDA AVENUE
PALO ALTO, CA 94304
PS100
B100
SPUR #: 1795.07
SITE PLUMBING KEYNOTES
41 4" DOWN TO MANHOLE.SS-8 CONNECTION SHALL BE SEALED VAPOR AND WATERTIGHT. SEE DETAIL #3 ON SHEET CS200.
47 4" SANITARY UP TO WASTE CONNECTION; 21" ABOVE GRADE.
48 1 1/2" UTILITY COLD AND 1 1/4" UTILITY HOT; UP TO WATER CONNECTION; 21" ABOVE GRADE.
49 1 1/2" DOMESTIC COLD TO TEMPORARY MODULAR SPACE; SEE SHEET P-400 FOR CONTINUATION.
50 2 1/2" UTILITY COLD, 1 1/2" UTILITY HOT AND 3/4" UTILITY HOT RETURN UP TO MOBILE DOMESTIC HOT WATER SYSTEM.
51 4" WASTE SERVING TEMPORARY MODULAR SPACE; SEE SHEET P-400 FOR CONTINUATION.
52 3" DOMESTIC COLD UP TO MOBILE DOMESTIC HOT WATER SYSTEM. SEE UTILITY SHEETS FOR CONTINUATION.
53 PROVIDE VALVES FOR SHUT-OFF WHERE MOST CONVENIENT FOR THE USER.
54 ROUTE DOMESTIC COLD WATER, HOT WATER AND HOT WATER RETURN PIPING BELOW DECKING.
55 DAYLIGHT DRAINS OFF OF RPZ TO OUTSIDE.
PLUMBING GENERAL NOTES:
1. CONTRACTOR TO VERIFY LOCATION AND SIZE OF THE UTILITIES BEFORE ANY CONSTRUCTION IS TO BEGIN. PIPING REFER TO CIVIL SHEETS FOR MORE
INFORMATION.
N
1/8" = 1'-0"
PLUMBING SITE PLAN - TEMPORARY SPS2
No. REVISION DESCRIPTION DATE
NOTES:
1. ALL LISTED EQUIPMENTS ARE FOR REFERENCE ONLY, MODULAR BUILDER TO PROVIDE AND INSTALL. SELECTION MAY VERIFY, BUT MUST MEET THIS DESIGN CRITERIA.
MOBILE WATER HEATER STATION EQUIPMENT SCHEDULE
MARK LOCATION SERVICE
BASIS OF DESIGN
TYPE
STORAGE
(GAL) CONNECTION SIZE Weight (lb)
ELECTRICAL
NOTES SPECIFICATION SECTIONMANUFACTURER MODEL NO. ELEMENTS KW PER ELEMENTS VOLTS/PH
EWH-2 WH STATION SPS TRAILERS PVI AquaPLEX-370 L
400A-VE
TANK 400 2" 1230 4 72 480/3 1 22 33 00 (1.4 - 1.5) | 22 33 00 (2.1) | 22 33 00 (2.4) | 22 33 00 (2.6 - 2.7)
ET-2 WH STATION SPS TRAILERS & MODULAR BLDG. Elbi of America DTL-200 TANK 53 1 1/4" 170 1 22 33 00 (2.3)
DHWCP-2 WH STATION SPS TRAILERS BELL & GOSSETT NBF-22 RECIRCUL
ATION
- 3/4" 10 115/Sing 1 22 11 23 (1.4) | 22 11 23 (2.2 - 2.3)
RPZ WH STATION SPS TRAILERS & MODULAR BLDG. WATTS 994RPDA-FS-OSY-3
ASSE 1013 - 3" 226 1 22 05 23 (2.9)
54 OF 721 ASI 1 05.30.2025
P-418
WCO
P-502 P-708
FD-C
FD-C
P-418
FD-C
WCO
FD-R
3" SS
2" SS
2" SS
3" SS
4" SS
2" V
2" V
2" V
4" SS
4" SS
3" SS
2" SS
2" V
2" V
2" SS
2" SS
2" V
LOCKER FEMALE
M-107
TOILET FEMALE
M-108
WORKSTATION
M-100B
OFFICE SPS CHIEF
M-101
MANUAL CART WASH
M-102
TOILET MALE
M-105
LOCKER MALE
M-106
CORRIDOR
M-103
BIN ASSEMBLY
M-100A
CLEAN STORAGE
M-100
2" VENT UP
FD-C
FD-C P-101
P-101
1 1/4" HW
1 1/4" CW
1 1/2" CW
3/4" HWR
3/4" HW
1 1/4" CW
3/4" HW
3/4" CW
1 1/2" CW3/4" HW
3/4" CW
P-802
3/4" HWR
1 1/4" HW
1 1/4" CW
1 1/2" HW
1 1/4" CW
1 1/2" CW
1 1/2" HW
P-708
P-502
P-418P-701
P-701
P-418
DHWCP-1
TOILET FEMALE
M-108
LOCKER FEMALE
M-107
HAC
M-104
WORKSTATION
M-100B
OFFICE SPS CHIEF
M-101
LOCKER MALE
M-106
CORRIDOR
M-103
TOILET MALE
M-105
MANUAL CART WASH
M-102
BIN ASSEMBLY
M-100A
CLEAN STORAGE
M-100
EWH-1ET-1
P-101 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
PROJECT NUMBERCONSULTANTS:
DRAWING #
VA HEALTH CARE SYSTEM APPROVAL:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH KS COA NO. A-930 EXP. 12/31/2025
ENG KS COA. NO. E-2586 EXP. 12/31/2025
CIVIL
H2B, INC.
1225 N LOOP WEST, STE 800
HOUSTON, TX 77008
(713) 864-2900
MEP / TECH ENGR
SPUR DESIGN
2519 MADISON AVE, STE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
STRUCTURAL ENGR
H2B, INC.
1225 N LOOP WEST, STE 800
HOUSTON, TX 77008
(713) 864-2900
HEALTHCARE PLANNER
THE INNOVA GROUP
9442 N. CAPITAL OF TEXAS HWY, STE 325
AUSTIN, TX 78759
(512) 346-8700
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, STE 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
DRAWING NUMBER
BUILDING NUMBER
/2
/2
:5
:3
A
M
TEMPORARY MODULAR BUILDING
PLUMBING PLAN
RTB 59 OF 76RS
BID DOCUMENTS
RENOVATION AND EXPANSION OF SPS
05/30/2025
640-23-108
PALO ALTO VA MC
3801 MIRANDA AVENUE
PALO ALTO, CA 94304
P-400
B100
SPUR #: 1795.07
KEYNOTES
8 1/2" DHW/DCW DOWN TO SHOWER. THERMOSTATIC MIXING VALVE SHALL BE 39" A.F.F.
11 1/2" DHW/DCW DOWN TO THERMOSTATIC MIXING VALVE TO SERVE EMERGENCY EYE/FACE WASH. PROVIDE MIXING VAVLE WITH A RECESSED CABINET. EYEWASH SHALL BE 42 INCHES A.F.F. TEMPERATURE TO BE SET
BETWEEN 85-95 DEGREES F.
41 4" DOWN TO MANHOLE.SS-8 CONNECTION SHALL BE SEALED VAPOR AND WATERTIGHT. SEE DETAIL #3 ON
SHEET CS200.
42 1 1/2" DOMESTIC COLD BELOW FLOOR. SEE PLUMBING SITE PLAN FOR CONTINUATION.
43 1 1/2" DOMESTIC COLD BELOW FLOOR.
44 1 1/2" DOMESTIC COLD UP.
45 1 1/2" CHECK VALVE.
46 1/2" TEMPERED LINE TO EMERGENCY EYE/FACE WASH.
GENERAL NOTES:
A. DRAWING IS TO BE USED FOR REFERENCE ONLY. FINAL LAYOUT AND PIPE ROUTING TO BE DONE BY
MODULAR BUILDING CONTRACTOR. REFER TO SCHEDULES FOR MORE INFORMATION.
B. LEGIONELLA MITIGATION: DOMESTIC COLD WATER AND DOMESTIC HOT WATER TRUNK LINES SHALL NOT EXCEED 2 FEET FROM FIXTURE RUN OUT DROP IN WALLS. DOMESTIC COLD AND DOMESTIC HOT TRUNK LINES SHALL BE 8' - 8" A.F.F. OR LESS. SEE KEYNOTES AND FIXTURE SCHEDULE FOR WATER STUB OUT HEIGHTS FOR FIXTURES. DOMESTIC HOT WATER WILL BE ON A CONTINUOUS LOOP, MAINTAINING TEMPERATURE 135 - 140 DEGREES F. PLACE TEMPERATURE GAUGE ON END RUN OF DOMESTIC COLD WATER. TURN ON FIXTURE TO FLUSH WATER IN LINE TO KEEP TEMPERATURE BELOW 67 DEGREES F. AS
NEEDED.
MODULAR RECIRCULATION PUMP SCHEDULE
MARK
BASIS OF DESIGN
BODY MATERIAL
FLOW
(GPM)
HEAD
(FT)
CONNECTION
TYPE
CONNECTION
SIZE (IN.)
ELECTRICAL
SPECIFICATION SECTIONMANUFACTURER MODEL NO. RPM FLA V/PH
DHWCP-1 BELL & GOSSETT NBF-12F/LW Bronze 8 16 Flange 3/4" 2800 0.48 115/1 22 11 23 (1.4) | 22 11 23 (2.2 - 2.3)
NOTES:
1. DHWCP-1 IS FOR REFERENCE ONLY, MODULAR BUILDER TO PROVIDE AND INSTALL. SELECTION MAY VARY, BUT MUST MEET THIS DESIGN CRITERIA.
NOTES:
1. EWH-1 IS FOR REFERENCE ONLY, MODULAR BUILDER TO PROVIDE AND INSTALL. SELECTION MAY VARY, BUT MUST MEET THIS DESIGN CRITERIA.
2. HEATING ELEMENTS DO NOT OPERATE SIMULTANEOUSLY, ONLY ONE AT A TIME.
MODULAR PLUMBING FIXTURE SCHEDULE
MARK DESCRIPTION
WASTE PIPE
(IN)
VENT PIPE
(IN)
COLD
WATER (IN)
HOT
WATER (IN)
BASIS OF DESIGN
DESCRIPTION SPECIFICATION SECTIONMANUFACTURER MODEL
P-101 Water Closet, Floor Mounted 3" 2" 1" - AMERICAN STANDARD 3043.001 Floor mounted, Sloan G2 Optima Plus 8186-0.5 sensor flush valve, ADA height. 22 40 00 (2.7)
P-418 Lavatory, Wall Hung 2" 2" 1/2"
1/2"
AMERICAN STANDARD 0356.421
Lavatory rim height shall be 34" A.F.F. Sensor faucet with plug-in AC power supply, American Standard Model No. 775B.215 or equal. Provide flat grid strainer with ofset tailpiece.
Provide 17-gauge 1.5" P-trap with 1.25" reducing washer. Threaded lock shield stops. Provide ASSE 1070 thermostatic mixing valve, temperature shall be 105 - 110 degrees F.
22 05 23 (2.11) | 22 40 00 (2.3 - 2.5) | 22 40 00 (2.10)
P-502 Service SInk 3" 2" 1/2" 1/2" ACORN ENGINEERING TRH-362410 Terrazzo mop sink approximately 10"H x 36"W x 24"D. One piece molded stone with Speakman SC-5811 faucet or equal, a service faucet hose, hose bracket and mop hanger. 22 05 23 (2.9) | 22 40 00 (2.11)
P-701 SHOWER - -
1/2"
1/2"
CHICAGO FAUCETS 151-ACP & 2500-VOCCP
Wall mounted, detachable 2.5 gpm shower hand spray assembly with 24 in. slide bar and 60 in. flexible metal hose. Type T/P combination thermostatic & presure balancing valve with temperature limit stops. Set stops for a maximum temp of 122 degrees F.
22 05 23 (2.9) | 22 40 00 (2.13)
P-708 Emergency Eye/Face Wash 2" 2" 1/2"
1/2"
BRADLEY S19224YZS & S19-2000 (EFX8)
Wall mounted eye/face wash shall be mounted 42" A.F.F. Provide Bradley S32-395 Foot Pedal Control. Provide ASSE 1071 temperature activated mixing valve. Temperature shall be set at 85 - 95 degrees F.
22 05 23 (2.11) | 22 40 00 (2.14)
P-802 Hose Bibb; Combination Faucet - - 1/2" 1/2" T&S BRASS B-1958 Wall mounted faucet, Shall be 48" A.F.F. 22 05 23 (2.9) | 22 40 00 (2.15)
No. REVISION DESCRIPTION DATE
N
1/4" = 1'-0"
WASTE AND VENT PLUMBING PLAN - MODULAR BUIDING1
N
1/4" = 1'-0"
DOMESTIC WATER PLUMBING PLAN - MODULAR BUILDING2
MODULAR EXPANSION TANK SCHEDULE (ET)
MARK
BASIS OF DESIGN
(MANUFACTURER/MODEL) SERVICE MOUNTING
TANK CAPACITY
(GAL)
ACCEPTANCE
FACTOR
MAXIMUM
TEMPERATURE (°F)
MINIMUM
PRESSURE (PSIG)
MAX SYSTEM WORKING
PRESSURE (PSIG)
WEIGHT
(LBS) NOTES
SPECIFICATION
SECTION
ET-1 AMTROL / ST-5 EWH-1 INLINE 2 0.45 200 °F 40.00 150 5 ALL LISTED 22 33 00 (2.3)
NOTES:
1. SUPPORT SUSPENDED UNIT FROM STRUCTURE WITH ALL THREAD RODS.
MODULAR DRAINS & CLEANOUT SCHEDULE
MARK DESCRIPTION
BASIS OF DESIGN
DESCRIPTION SPECIFICATION SECTIONMANUFACTURER MODEL
FD-C 2 IN. FLOOR DRAIN
WATTS FD-102-M6
Light duty nickel bronze grate, 6" square with vandal proof screws. Provide Trap Guard; Sioux Chief 835 Series or equal.
22 13 00 (2.6)
FD-R 4 IN. FLOOR DRAIN
WATTS FD-330
Body coated with acid resistant enamael finish, 8" square strainer with secondary dome strainer. Provide Trap Guard; Sioux Chief 835 Series or equal.
22 13 00 (2.6)
WCO 3 IN. WALL CLEAN OUT
WATTS CO-460
Provide wall cleanout with nickel-bronze square frame & stainless steeel cover with minimum opening of 6in x 6in.
Zurn Z1460 or equal.
22 13 00 (2.5)
MODULAR ELECTRIC WATER HEATER EQUIPMENT SCHEDULE (EWH)
MARK
BASIS OF DESIGN
LOCATION SERVICE TYPE
CONNECTION
SIZE (IN)
RELIEF VALVE
(PSIG)
STORAGE
(GAL)
HEAT OUTPUT ELECTRICAL DATA
NOTES SPECIFICATION SECTIONMANUFACTURER MODEL NO. 100° RISE 1ST HR GPH ELEMENTS KW PER ELEMENTS VOLTS/PH
EWH-1 A.O. SMITH DEL-50 ROOM No. M-104 MODULAR BLDG. TANK 0' - 0 3/4" 150 50 21 53 2 5 69 V ALL LISTED 22 33 00 (1.4 - 1.5) | 22 33 00 (2.1) | 22 33 00 (2.4) | 22 33 00 (2.6 - 2.7)
55 OF 721 ASI 1 05.30.2025
NOTE:
POINT-OF-USE THERMOSTATIC MIXING VALVES MUST
CONFORM TO ASSE 1070
TYPICAL FAUCET
(OR OTHER LEVER
CONTROLLED FIXTURE)
THERMOSTATIC
MIXING VALVE
TEMPERED WATER
SUPPLY OUTLET
COLD WATER
SUPPLY OUTLET
COLD WATER
SUPPLY INLET
HOT WATER
SUPPLY INLET
FINISHED
FLOOR
CHROME
WALL COVER
AND SCREW
STANDARD 1/8 BEND
PLUGGED TEE
WITH CLEANOUT
11-1/4" (286)
DOOR
5-3/8" (137)
9-3/4" (248) DOOR
FLANGE
14-1/2" (368)
3" (76)
5" (127)
11" (279) BOX
13" (330)
2-1/2" (64)
1/2" NPT
OUTLET
2" (51)
12-1/2" (318)7-1/2"
(191)
.28" DIA. HOLES
4 EACH SIDE
8 TOTAL
6-1/2" (165)
1/2" NPT INLETS
2-1/4" (57)
2" (51)
2-1/2" (64)
FRONT VIEW SIDE VIEW
DRAIN VALVE
(PIPE TO DRAIN)
PIPE T&P VALVE TO DRAIN
WITH NO SHUTOFF VALVES
OR RESTRICTIONS IN THE
LINE; OR PER LOCAL CODE
REQUIREMENT.
T&P RELIEF VALVE
WATER
HEATER
DUPLICATE PIPING
FOR T&P AND DRAIN
FOR ALL HEATERS
HOT WATER OUTLET - REVERSE RETURN OR BALANCES PIPING
REFER TO HEATER'S INSTALLATION
MANUAL FOR INFORMATION ON
SCALD PREVENTION
MIXING
VALVE
WATER
HEATER
BUILDING
RETURN
COLD WATER MAKEUP
MAXIMUM RECOMMENDED
FLOW (GPM) BY PIPE DIAMETER
FOR TYPE L COPPER
DIAMETER GPM
1" 15
1-1/4" 22
1-1/2" 34
2" 60
2-1/2" 90
3" 130
4" 230
6" 500
PIPE UNION
BALL VALVE, FULL PORT
T&P RELIEF VALVE
CHECK VALVE
PUMP
SHUTOFF VALVE
LEGEND
EXP.
TANK
3/4" PIPE FROM COLD
WATER SUPPLY TO WATER
HEATER, WITH NO CHECK
VALVES INTERVENING
FDA-COMPLIANT BUTYL
DIAPHRAGM
WELDED STEEL
EXPANSION TANK WITH
POLYPROPYLENE
LINING, NSF APPROVED
FOR DOMESTIC WATER
SERVICE
NOTE:
PIPING ARRANGEMENT SHOWN IS SCHEMATIC. ADJUST TO SUIT FIELD CONDITIONS.
FOLLOW MANUFACTURER'S INSTRUCTIONS FOR INSTALLATION PROCEDURE.
VERIFY PROPER OPERATION WHEN INSTALLED. PROVIDE SEISMIC STRAP OR
BRACING WHEN REQUIRED BY LOCAL AUTHORITIES.
PIPE HANGER NEXT TO
ELBOW
PROVIDE DIELECTRIC
PIPE UNION AT TANK
CONNECTION FOR
CONNECTION OF
DISSIMILAR METALS
AIR CHARGING VALVE, FILL
TANK WITH AIR PRESSURE
TO MATCH WATER
PRESSURE.
PIPE UNION
BALL VALVE, FULL PORT
T&P RELIEF VALVE
CHECK VALVE
PUMP
SHUTOFF VALVE
PIPE T&P VALVE TO DRAIN
WITH NO SHUTOFF VALVES
OR RESTRICTIONS IN THE
LINE; OR PER LOCAL CODE
REQUIREMENT.
DOMESTIC HOT WATER OUTLET
REFER TO HEATER'S INSTALLATION
MANUAL FOR INFORMATION ON
SCALD PREVENTION
WATER
HEATER
LEGEND
DOMESTIC HOT WATER
RETURN
DOMESTIC COLD WATER
SUPPLY
EXP.
TANK
DRAIN VALVE
(PIPE TO DRAIN)
T&P
RELIEF
VALVE
RECIRC. PUMP
DRAIN PAN
DRAIN PAN ROUTED
TO APPROVED
LOCATION
T O
C E
N T
E R
L
IN
U
P P
L Y
E L L
T O
C E
N T
E R
L
IN
E O
F O
U T
L E
T
[1 m m
24" [600mm]
SLIDE BAR
SHOWER CONTROL
TYPE T/P
WARP ENTIRE FLOOR
(ASSUMES TOPPING
SLAB)
DRAIN
[1 m m
[8 m m
GRAB BAR
[8 m m
[1 m m
[2 m m
[1 m m
[150mm] [225mm]
VACUUM
BREAKER
CURTAIN ROD
SHOWER HEAD
[225mm] [150mm]
[1 m m
[1 m m
6" 9" 9" 6"
(SEE CHART)
BODY HEIGHT
(SEE CHART)
PIPE SIZE
∅8 [203]
X1.5[38] DP
BOSS
TRAP PRIMER
4[100]NPS-8
DOUBLE DRAINAGE
WEEPHOLES FOR STRAINER ADJUSTMENT
(SEE CHART)
0.
[3
.2
SQ
SQ IN
FREE
SQUARE MAXMIN
ADJUSTMENT
(-30/-31)
PVC/ABS
3.75"(95) 3.75"(95)
2.94"(75)2"(51)
SQ IN
LBS
UPTO
2.000
4"(102) 2.75"(70)
5"(127)
2.75"(70)3"(76)
3.25"(83)6"(152)
ANSI/ASME RATING
AREA
NB(-1)
RATINGLOAD
HUBSIZE
NOPIPE
2.75"(70) 3.75"(95) 2.625"(67) 2.625"(67)
2.625"(67)
3.375"(86) 3.375"(86)
3.75"(95) 3.75"(95)
3.75"(95)
2.25"(57)
THREADED
(T)
BODY HEIGHT
PUSH
3.375"(86)
CAULK (X)
INSIDE
6"(152)
(SEE CHART)
0.88"(22)
SS(-3) 5.000 LBS
TO
7.499 LBS
14 [355.6]
ON (P)
4.75"(121)
2.75"(70)
STRAINER STRAINER
1.56"(40)
SIZE
SCB-4T4 3/8" [10mm]
SCB(H)-3
SCB(H)-1
SCB(H)-2
T3
T1
T2
1/4" [6mm]
1/8" [3mm]
3/16" [5mm]
SCB(H)
SIZE
SCBH-0T0
RESTRAINT
TYPE
CABLE
SIZE
"C"
3/32" [2.4mm]
6 3/4" [171mm]1" [25mm]
4" [102mm]
5" [127mm]
6" [152mm]3/4" [19mm]
5/8" [16mm]
1/2" [13mm]
3" [76mm]
ANCHOR
EMBEDMENT
"E"
ANCHOR
DIAMETER
"D"
3/8" [10mm]
MASON SAS "D" ANCHOR WITH "E"
EMBEDMENT (6 REQ'D.)
PIPE CLAMP OR
U-BOLT BY OTHERS
"C" AIRCRAFT CABLE
BY MASON
MASON SCBH (T4 + 4L4 RESTRAINT TYPE - SCB-4)
SEISMIC CABLE BRACE HOOK (2 REQ'D.)
MASON SCB (T0 + 4L0
RESTRAINT TYPE - SCBH-0)
SEISMIC CABLE BRACE (2
REQ'D.)
TRAPEZE SUPPORT
BY OTHERS
THREADED ROD
BY OTHERS
45° +/- 15°
5 FT
6 8 10
9 1110 12
-1312 14 -16 -
1614 17 2219 23
2725 28 3230
20 241814 16128 1064 532 2 1/21 1/21 1 1/4THRU 3/4
7 7
7 98
SIDE VIEW TRAPEZE HANGER FOR UP TO 1000
LB. UNIFORM LOAD
MAXIMUM PIPE/TUBING SUPPORT SPACING
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
ADJUSTABLE CLEVIS HANGER
TYPE 1 - SEE SPECIFICATIONS
NOM. SIZE IN.
FT.
FT.TUBING
PIPE
1" M
A X
ADJUSTABLE CLEVIS HANGER
TYPE 43 - SEE SPECIFICATIONS
PROVIDE HIGH COMPRESSIVE
STRENGTH INSULATION (9
PSF MIN. DENSITY) UNDER
INSULATION SHIELD
INSULATION SHIELD
AT HANGER
NOTES:
1. SEE SPECIFER FOR DETAILED HANGER REQUIREMENTS.
PROVIDE INSULATION
SHIELD & INSERT FOR
ALL PIPING (8" MIN)
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE)
HANGER ROD
1-5/8" 12 GAUGE
CHANNEL OR 2"x2"x1/4"
ANGLE
1/2" Ø HANGER RODS
WITH 36" MAX.
SPACING ON EACH
CHANNEL
BAND
SADDLE
WELD
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
PROJECT NUMBERCONSULTANTS:
DRAWING #
VA HEALTH CARE SYSTEM APPROVAL:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH KS COA NO. A-930 EXP. 12/31/2025
ENG KS COA. NO. E-2586 EXP. 12/31/2025
CIVIL
H2B, INC.
1225 N LOOP WEST, STE 800
HOUSTON, TX 77008
(713) 864-2900
MEP / TECH ENGR
SPUR DESIGN
2519 MADISON AVE, STE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
STRUCTURAL ENGR
H2B, INC.
1225 N LOOP WEST, STE 800
HOUSTON, TX 77008
(713) 864-2900
HEALTHCARE PLANNER
THE INNOVA GROUP
9442 N. CAPITAL OF TEXAS HWY, STE 325
AUSTIN, TX 78759
(512) 346-8700
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, STE 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
DRAWING NUMBER
BUILDING NUMBER
/2
/2
:5
:3
A
M
PLUMBING DETAILS
RTB 60 OF 76RS
BID DOCUMENTS
RENOVATION AND EXPANSION OF SPS
05/30/2025
640-23-108
PALO ALTO VA MC
3801 MIRANDA AVENUE
PALO ALTO, CA 94304
P-500
B100
SPUR #: 1795.07
NTS
POINT-OF-USE 4-PORT THERMOSTATIC MIXING VALVE DETAIL3
NTS
TYPICAL INTERIOR WALL CLEANOUT6
NTS
RECESSED MIXING VALVE FOR EYE WASH1
NTS
MOBILE WATER HEATING SYSTEM PIPING - EWH-28
No. REVISION DESCRIPTION DATE
NTS
SMALL EXPANSION TANK DETAIL7
NTS
TYPICAL WATER HEATING SYSTEM PIPING - EWH-19
NTS
P-701 SHOWER5
NTS
WOO FRAMING FLOOR DRAIN DETAIL4
NTS
TRANSVERSE SEISMIC CABLE BRACE FOR TRAPEZE SUPPORTED PIPE10
NTS
PIPE HANGERS2
56 OF 721 ASI 1 05.30.2025
WACU-1
RG-3W
SD-4
SD-4
SD-4
SD-4
MODULAR BUILDING
SPS TRAILER NO. 2
SPS TRAILER NO. 1
EXISTING CORRIDOR
ENTRY
CORRIDOR
8"x8" SA 8"x8" SA 8"x8" SA
28"x8" SA
10"x10" SA
8"x10" SA
1" CD
T
WACU-1
3434 34
12"x10" SA
12"x12" SA
8"x10" SA
WACU-2
MODULAR BUILDING
(TYP)
T
WACU-2
SD-4
SD-4
SD-4
RG-3W
8"x10" SA
10"x10" SA
12"x10" SA
8"x10" SA
KEY PLAN
RADIOLOGY BUILDING
BUILDING 100
BUILDING 102
BUILDING 05
TEMP.
MODULAR
OFFICE
TEMP. SPS
T E
M P
. S P
S
N
TEMP.
MODULAR
STORAGE
CORRIDOR
CONICAL TAP WITH
LOCKABLE VOLUME
DAMPER
ALL-DIRECTIONAL
SEISMIC CABLE
BRACE FOR
RECTANGULAR DUCT
SUPPORT FROM
STRUCTURE INSULATED
SHEETMETAL
SUPPLY DUCT
CEILING
NOTES:
1. SEAL CONNECTIONS WITH SEALANT AND TAPE.
2. FLEXIBLE DUCT ALLOWED ONLY IN VERTICAL DROP TO AIR DEVICE. MAXIMUM RUN-OUT LENGTH IS 5'-0".
3. PROVIDE VOLUME DAMPER IN NECK OF DIFFUSER FOR DIFFUSERS IN INACCESSIBLE CEILINGS.
T-BAR
SUPPLY DIFFUSER
(SEE NOTE 3)
1.5 X DUCT DIAMETER
SHEETMETAL ELBOW
W/EXTERIOR INSULATION
PRE-INSULATED
FLEXIBLE DUCT
DUCT COLLAR AT
DIFFUSER NECK.
INSULATED
PACKPAN/BOX
NOTE:
1. DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.
2. DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR
FOR MULTI-BLADE DAMPERS & ROUND DAMPERS.
INSULATION SEE
SPECIFICATION
DAMPER BLADE
1/8" [6mm]
CLEARANCE
ALL AROUND
OUTSIDE END BEARING
INSIDE END BEARING
HANDLE WITH
LOCKING
QUADRANT
INSULATION
STAND-OFF
1/2" [15mm] ROUND
ROD PIN
DUCT
STIFFEN BLADE
AS REQUIRED
SIDE ELEVATION SECTION
VANE VANE
R SHALL
EQUAL OR
BE GREATER
THAN W.
R SHALL
EQUAL OR
BE GREATER
THAN 1/3W.
R SHALL
EQUAL OR
BE GREATER
THAN 1/6W.
SHORT RADIUS ELBOW
WITH TWO VANES
SHORT RADIUS ELBOW
WITH ONE VANE
STANDARD RADIUS OR
LONG RADIUS ELBOW
NOTES:
1. THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.
2. ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS ELBOWS. ALL SHORT RADIUS ELBOWS
SHALL HAVE VANES. VANES SHALL BE CONSTRUCTED, SUPPORTED AND FASTENED AS RECOMMENDED BY SMACNA.
W
1/6W
1/ 3W1/2W
W
1/ 3W
2/3W
RR
W
R
SEQUENCE OF OPERATIONS
WALLPACK AIR CONDITIONING UNIT (WACU-1 & WACU-2)
GENERAL DESCRIPTION
The wallpack unit provides heating and cooling for a temporary enclosed corridor as shown on the drawings.
OPERATING MODES
NORMAL OPERATING MODE
The wallpack unit shall be in normal operating mode at all times unless overridden by the other mode outlined in this sequence.
ECONOMIZATION MODE
The ACCU and electric heating coil shall both be in standby mode. The Economizer damper shall be fully open.
COMPONENT CONTROLS
AIR COOLED CONDENSING UNIT
NORMAL OPERATING MODE:
The air cooled condensing unit shall be on.
STANDBY MODE:
The air cooled condensing unit shall be off.
ELECTRIC HEAT
NORMAL OPERATING MODE:
The electric heating coil shall be enabled.
STANDBY MODE:
The electric heating coil shall be off.
M
ACCU FACTORY CONTROLS
WITH CONTROL INTERLOCK
BY TCC.
S A
DX
STARTERCTM
WACU UNITARY CONTROLLER
W/ BACNET MSTP INTERFACE
T
E
LE
C D
X
BO FAN START/STOP
BI FAN STATUS
BO CONDENSING UNIT ENABLE
AO CONDENSING UNIT
BO HEATER ENABLE
AI ZONE TEMP
R A
OA
ER
MANUAL BAROMETRIC
RELIEF DAMPER BALANCED
TO 0.01 IN WC.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
PROJECT NUMBERCONSULTANTS:
DRAWING #
VA HEALTH CARE SYSTEM APPROVAL:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH KS COA NO. A-930 EXP. 12/31/2025
ENG KS COA. NO. E-2586 EXP. 12/31/2025
CIVIL
H2B, INC.
1225 N LOOP WEST, STE 800
HOUSTON, TX 77008
(713) 864-2900
MEP / TECH ENGR
SPUR DESIGN
2519 MADISON AVE, STE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
STRUCTURAL ENGR
H2B, INC.
1225 N LOOP WEST, STE 800
HOUSTON, TX 77008
(713) 864-2900
HEALTHCARE PLANNER
THE INNOVA GROUP
9442 N. CAPITAL OF TEXAS HWY, STE 325
AUSTIN, TX 78759
(512) 346-8700
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, STE 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
DRAWING NUMBER
BUILDING NUMBER
/2
/2
:5 :3
P
M
MECHANICAL HVAC NEW WORK -
MODULAR BUILDINGS
BAJ 60 OF 75RJS
BID DOCUMENTS
RENOVATION AND EXPANSION OF SPS
05/30/2025
640-23-108
PALO ALTO VA MC
3801 MIRANDA AVENUE
PALO ALTO, CA 94304
MS-101
B100
SPUR #: 1795.07
N
1/8" = 1'-0"
LEVEL 1 - SPS TRAILERS AND TEMPORARY BUILDINGS - REFERENCE PLAN1
KEYNOTES
30 STERIS TRAILER FURNISHED BY CONTRACTOR. TRAILER EQUIPPED WITH INTEGRAL HVAC EQUIPMENT. DESIGN IS
OUTSIDE OF PROJECT SCOPE.
31 MODULAR BUILDING FURNISHED BY CONTRACTOR. MODULAR BUILDING EQUIPPED WITH INTEGRAL HVAC
EQUIPMENT. DESIGN IS OUTSIDE OF PROJECT SCOPE.
32 CONTRACTOR TO INSTALL WALL-MOUNTED PACKAGE AIR CONDITIONER IN THE APPROXIMATE LOCATION SHOWN ROUGHLY 4'-9" ABOVE FINISHED FLOOR. COORDINATE WITH OTHER DISCIPLINES FOR EXACT LOCATION AND SEISMIN BRACING REQUIREMENTS PRIOR TO INSTALLATION. REFER TO WALLPACK AIR CONDITIONING UNIT SCHEDULE, CONTROLS DIAGRAM, AND POINTS LIST FOR MORE INFORMATION.
33 CONTRACTOR TO ROUTE CONDENSATE DRAIN PIPING TO NEAREST ACCESSIBLE SANITARY SEWER PIPING WITH A
CODE COMPLIANT INDIRECT DISCHARGE.
34 CONTRACTOR TO INSTALL VOLUME DAMPER PER DETAIL 4 IN THE LOCATION SHOWN.
35 CONTRACTOR TO INSTALL RADIUS ELBOW PER DETAIL 5 IN THE LOCATION SHOWN.
36 CONTRACTOR TO INSTALL SUPPLY DIFFUSER PER DETAIL 3 AND BALANCE ALL SUPPLY DIFFUSERS TO THE VALUES
SHOWN.
37 CONTRACTOR TO LOCATE WACU THERMOSTAT 48-INCHES ABOVE FINISHED FLOOR IN THE LOCATION SHOWN.
WALLPACK AIR CONDITIONING UNIT SCHEDULE
MARK
BASIS OF DESIGN
(MANUFACTURER / MODEL)
SUPPLY FAN DX COILS ELECTRIC HEAT ELECTRICAL
WEIGHT
(LBS) NOTES
AIRFLOW
(CFM)
MIN O/A
(CFM)
TSP
(IN WC) HP
TOTAL
CAP.
SENSIBLE
CAP.
EAT
DB (F°)
LAT
DB (F°)
HEATER
SIZE (KW)
SENSIBLE
(MBH)
EAT
DB (F°)
LAT
DB (F°) MCA MOCP V/PH
WACU-1 BARD / W30AY-C09XPXXXX 950 465 0.50 0.5 29200.0 21888.0 83.1 62.0 9.0 28260.0 53.5 80.8 16 20 460/3 365 1-3
WACU-2 BARD / W24AF-C05XPXXXX 800 315 0.50 0.3 24000.0 17943.0 81.3 61.4 5.0 15700.0 57.2 74.6 10 15 460/3 330 1-3
1. OUTSIDE AIR DAMPER TO BE MANUALLY SET DURING TAB OF SYSTEM.
2. RETURN AIR GRILLE TO BE BARD RG-3W OR EQUIVALENT.
3. POWER AND DISCONNECT TO BE PROVIDED BY DIVISION 26 CONTRACTOR.
2. SEE PROJECT DESIGN CONDITIONS SCHEDULE ON SHEET M-701 FOR APPLICABLE SETPOINTS.
1. SEE STANDARD TRENDING POINTS LIST SCHEDULE ON SHEET M-701 FOR APPLICABLE TREND INTERVALS.
NOTES:
COMPRESSOR RUNTIME EXCEEDED STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT (ADJ.) X 10 MIN.
COMPRESSOR IN HAND COMMANDED OFF, BUT THE STATUS IS ON X 10 MIN.
COMPRESSOR FAILURE COMMANDED ON, BUT THE STATUS IS OFF X 10 MIN.
FAN RUNTIME EXCEEDED STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT (ADJ.) X 10 MIN.
FAN IN HAND COMMANDED OFF, BUT THE STATUS IS ON X 10 MIN.
FAN FAILURE COMMANDED ON, BUT THE STATUS IS OFF X 10 MIN.
LOW SUPPLY AIR TEMPERATURE IF THE SUPPLY AIR TEMPERATURE IS 5°F LESS THAN ITS SETPOINT (ADJ.) X 10 MIN.
HIGH SUPPLY AIR TEMPERATURE IF THE SUPPLY AIR TEMPERATURE IS 5°F GREATER THAN ITS SETPOINT (ADJ.) X 10 MIN.
LOW ZONE TEMPERATURE IF THE ZONE TEMPERATURE IS 5°F LESS THAN ITS SETPOINT (ADJ.) X 10 MIN.
HIGH ZONE TEMPERATURE IF THE ZONE TEMPERATURE IS 5°F GREATER THAN ITS SETPOINT (ADJ.) X 10 MIN.
ALARMS DESCRIPTION ALARM ALARM DELAY
LAT SETPOINT X X
ZONE HEATING SETPOINT X X
ZONE COOLING SETPOINT X X
SETPOINT
HEATER ENABLE X X X
CONDENSING UNIT ENABLE X X X
CONDENSING UNIT X X X
ECONOMIZER AIRFLOW X X
ECONOMIZER DAMPER X X
FAN START/STOP X X X X
FAN STATUS X X X
UNIT ENABLE / ON-OFF X X
UNIT ON-OFF STATUS X X X
DISCHARGE AIR TEMPERATURE X X X
ZONE TEMPERATURE X X X X
WALLPACK AC UNIT
AI AO BI BO AV BV LOOP SCHED TREND ALARM
POINTS NAME
HARDWARE POINTS SOFTWARE POINTS
SHOWN ON GRAPHIC
POINTS LIST SCHEDULE - WALLPACK AIR CONDITIONING UNIT (WACU-1 & WACU-2)
NOT TO SCALE
3 TYPICAL SUPPLY DIFFUSER DETAIL
NOT TO SCALE
4 VOLUME DAMPER
NOT TO SCALE
5 DUCTWORK RADIUS ELBOWS
No. REVISION DESCRIPTION DATE
NOT TO SCALE
2 WALLPACK AIR CONDITIONING UNIT (WACU-X) TYPICAL CONTROL DIAGRAM
57 OF 721 ASI 1 05.30.2025
UE
OE
E/G 400A/3P
E/G 400A/3P
C
PC
R
TS
T
100/3
100/3/70
100/3/70/1
100/3/CB
PP
J
GF
OR
OR
OR
EPO
AM
VM
DM
ST
KK
GFR
M
SPD
R
LP1
A1
LIGHT FIXTURE, CEILING MOUNTED
a
LIGHTING TRACK WITH TRACK LIGHT FIXTURES
LIGHT FIXTURE, POLE MOUNTED
LIGHT FIXTURE, WALL MOUNTED
EMERGENCY BATTERY PACK LIGHT FIXTURE,
WALL MOUNTED
EMERGENCY BATTERY PACK LIGHT FIXTURE,
CEILING MOUNTED
EXIT SIGN, WALL MOUNTED, FACE/ARROWS AS INDICATED
EXIT SIGN, CEILING MOUNTED, FACE/ARROWS AS INDICATED
EMERGENCY LIGHT FIXTURE, CEILING MOUNTED
A1E a
A1 a
A1
A1
X1E
X1E
Y1E
Y1E
HOMERUN TO PANELBOARD, ARROWS INDICATE
NUMBER OF CIRCUITS, TICK MARKS INDICATE
NUMBER OF CONDUCTORS. DESIGNATIONS ARE
PANELBOARD AND CIRCUIT NUMBERS.
UNSWITCHED HOT CONDUCTORS SHOWN LEADING
NEUTRAL CONDUCTOR
NEUTRAL CONDUCTOR
SWITCHED HOT CONDUCTORS SHOWN TRAILING
GROUND CONDUCTOR
EQUIPMENT GROUNDING CONDUCTOR IN RACEWAY
ISOLATED GROUNDING CONDUCTOR IN RACEWAY
CONCEALED RACEWAY
EXPOSED RACEWAY
RACEWAY TURNING DOWN
RACEWAY TURNING UP
EQUIPMENT TERMINATION
LOW VOLTAGE CABLE (NOT ROUTED IN CONDUIT)
LIGHT FIXTURE, BOLLARDA1
RECEPTACLE, SIMPLEX, NEMA 5-20R, UNO
RECEPTACLE, DUPLEX, NEMA 5-20R, UNO
RECEPTACLE, DOUBLE-DUPLEX, NEMA 5-20R, UNO
RECEPTACLE, DUPLEX, CEILING MOUNTED, NEMA 5-20R, UNO
RECEPTACLE, SPECIAL PURPOSE
RECEPTACLE,…