DRAWINGS - TEMPORARY SPS_Part4.pdf
PDF 12 MB Posted
- Solicitation number
- 36C26125R0008
About this file
These architectural and engineering drawings provide detailed plans for a Veterans Affairs (VA) Palo Alto Healthcare System project to renovate and expand the Sterile Processing Service (SPS) in Building 100. The comprehensive set of documents includes structural, civil, architectural, and mechanical plans for temporary modular buildings and a connecting corridor to be used during the renovation, with specific details on foundation, framing, roof, floor plans, electrical, fire alarm systems, and interior finishes.
The project involves constructing temporary modular facilities to maintain SPS operations during a 720-calendar-day renovation, including two SPS trailers, a connecting corridor, and a temporary clean supply storage building. The modular structures will be fully functional with spaces like clean storage, workstations, offices, toilets, and corridors, and will be equipped with necessary infrastructure including fire alarm systems, electrical connections, and meet VA healthcare design standards. The drawings provide intricate technical specifications for construction, including structural details, material specifications, and compliance requirements for healthcare facility construction.
View the file
Other files
Show all 49
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
INV. 4" IN=96.40
INV. 4" OUT=100.10
AD RIM= 101.51
INV. 4" OUT=100.26 INV.=99.59TOP OF TD=100.46
INV.=99.45TOP OF TD=100.44
AD RIM=101.51
INV. 6" OUT=100.01
6" SDCO w/ BOX & COVER
TRENCH DRAIN
RIM=100.46
AD RIM=101.51
INV. 4" OUT= 100.41
6" SDCO w/ BOX & COVER
INV. 4" OUT=100.26
AD RIM=101.51
RIM=100.46
INV.=100.08
BOX INV.=72.21
BUBBLER CB RIM=97.50
INV. 8" IN=96.47
INV. 8" OUT=95.38
INV. 6" IN=97.04
JB RIM=100.16
BUBBLER CB, RIM=
INV. 6" IN=96.93
INV. 6" IN=96.99
BUBBLER CB, RIM=INV. 8" SD THRU=95.26WYE ION
INV.=97.61 5' FROM BLDG.
6" RL (3060 Ø)
INV.=97.61 FROM BLDG.
6" OL (3060 Ø)
INV.=97.11 FROM BLDG.
6" OL (10,650 Ø)
INV.=95.73 5' FROM BLDG.
6" RL (10,650 Ø)
INV.=97.11 FROM BLDG.
6" OL (3060 Ø)
INV.=97.11 5' FROM BLDG.
6" RL (3060 Ø)
INV. 6" OUT=97.21
AD RIM=100.21
INV. 6" OUT=97.21
AD RIM=100.21
INV. 6" OUT=97.21
AD RIM=100.21
AD RIM=100.37
INV. 4" OUT=97.83
INV. 4" OUT=97.88
AD RIM=100.38
INV. 4" OUT=97.85
AD RIM=100.35
INV. 4" OUT=97.83
AD RIM=100.33
INV. 4" OUT=97.21
AD RIM=100.01
INV. 4" OUT=97.87
AD RIM=100.37
INV. 4" OUT=97.98
AD RIM=100.48
AD RIM=100.41
INV. 4" OUT=97.91
INV. 4" OUT=97.98AD RIM=100.48
INV. 12" OUT=94.50
INV. 12" IN=94.60
AD RIM=100.16
INV. 6" OUT=97.16
INV. 8" IN=96.51BUBBLER CB
8" RL (10,800 Ø)
INV.=96.61 5' FROM BLDG.
INV.=96.61 5' FROM BLDG.8" OL (10,800 Ø)
INV.=100.08
RIM=100.46
TRENCH DRAIN
TRENCH DRAIN
INV. 12" IN=74.11
SD PUMP STATION
FL OF TRENCH DRAIN
@ S=1%
JB, SOLID TOP, RIM=98.26
INV. 4" IN=97.82
INV. 6" OUT=96.93INV. 6" OUT=97.21AD RIM=100.21
INV. 6" OUT=97.21AD RIM=100.21
INV. 6" OUT=97.21AD RIM=100.21
INV. 6" OUT=100.01
INV. 4" OUT=100.01
AD RIM=101.51
AD RIM=101.51
INV. 4" OUT= 100.10
BUBBLER CB, RIM=97.80
INV. 8" IN=96.438" OL (11,100 Ø)
INV.=96.61 5' FROM BLDG.
8" RL (11,100 Ø)
INV.=96.61 FROM BLDG.
INV. 6" OUT=97.89
AD RIM=100.39
INV. 6" OUT=97.44
AD RIM=100.21
AD RIM=100.28
INV. 6" OUT=97.78
INV. 6" OUT=97.81
AD RIM=100.31
INV. 6" OUT=97.57
AD RIM=100.15
INV. 12" OUT=96.00
AD RIM=100.00
8" RL (9300 Ø)
INV.=96.61 5' FROM BLDG.
INV.=96.61 5' FROM BLDG.8" OL (9300 Ø)
INV.=97.43
RIM=100.34
BUBBLER CATCH BASIN
8" OL
INV.=97.65 3' FROM BLDG.
INV.=97.06 5' FROM BLDG.8" RL
AD RIM=100.12
INV. 12" IN=95.02
INV. 12" THRU=95.28AD RIM=99.98
INV. 12" PVC THRU=95.82AD RIM=99.92
INV. 12" OUT=95.02
INV. 4" OUT=99.59
INV. 4" IN TO ELBOW=99.51
INV. 4" OUT FROM ELBOW=98.46
24"x36" HATCH
GRATE 83.80
TWO VERTICAL ELBOWS
INV. 12" IN=88.01
TC @ CI=93.01
INV. 21" IN=87.45
SDMH RIM=96.35
INV. 21" OUT=87.25
INV. 12" OUT=93.19
TC @ CI=98.09
CB RIM=92.41
INV. 12" OUT=88.41
TC @ CI=89.98
INV. 12" OUT=84.98
INV. 21" IN=86.28
INV. 21" OUT=86.18
EX 2,000 GAL SS TANK
SSMHRIM=98.44
INV=90.54 8" PIPE (SW)
INV=90.54 8" PIPE (N)
AREA LIGHT
ST LT BOX
98.73
AREA LIGHT
99.92
ST LT BOX
100.14AREA LIGHT
99.88
AREA LIGHT
99.58
AREA LIGHT98.86
AREA LIGHT98.35
AREA LIGHT97.46
ST LT BOX
98.86
ELECTROLIER ON
2' CONC BASE99.23
AREA DRAIN
INV=97.28 6" PIPE THRU(N&S)
4" PIPE
MH99.37 99.35
CLEAN OUT
MONITOR WELL
"BP-70"
(APPROX.)
ABANDONED
SSMHRIM=100.41
INV=93.61 6" VCP (IN W)
INV=93.51 6" VCP (IN SW)
INV=93.41 8" VCP (OUT)
SDDI #8222
GRATE= 100.25
8" (IN) W INV= 96.45
12" RCP (IN) E INV= 94.85
12" RCP (IN) S INV= 93.65
18" RCP (OUT) N INV= 93.45
SDAI #8221
GRATE= 100.48
4" PVC (OUT) S INV= 97.68
INV=90.31 8" PVC (S)
INV=69.19 12" PIPE THRU(E&W)
RIM=98.19
SSMH
SSMH #7876
RIM= 82.58
TOP OF FLUID= 71.60
TOP OF SLUDGE= 70.60
SSMH #7877
RIM= 81.47
4" VCP (IN) NE INV= 77.07
4" VCP (IN) NE INV= 76.87
8" VCP (IN) SE INV= 76.07
8" VCP (OUT) N INV= 76.02
6" IRRI MAIN
6" IRRI MAIN
4" IRRI M
AIN
6" IRRI M
AIN
6" IRRI MAIN
6" IRRI MAIN
6" IRRI MAIN
ACID NEUTRALIZATION TANK
RIM=97.65
4" IN=93.53
4" OUT=93.28
TANK INV= 87.20
SSMH (NOT USED)
RIM 83.60
EX INV 72.65
INV OUT 72.55 (8" E)
EX SSMH
INV OUT 75.60 (8" N)
INV OUT 75.68 (8" N)
SSMHRIM TBD (SEE LANDSCAPE PLANS FOR SURFACE GRADES)
EX INV 74.30±
INV OUT 74.13
JB RIM
FLUSH w/ PAVEM
ENT
INV. 6" IN=75.69
INV. 12" IN=75.18
INV. 12" OUT=75.08
TC @
CI=98.14
INV. 12" IN=90.54 N
INV. 15" IN=90.24 S
INV. 18" IN=88.24
INV. 21" OUT=88.24
SSMH
RIM=97.80
INV=68.70 (12" THRU)
INV=91.5 (6" E)
TC @
CI=97.31
INV. 12" IN=91.81 W
INV. 12" IN=90.91 S
INV. 15" OUT=90.81 E
TC @
CI=98.41
INV. 6" IN=95.72
INV. 12" IN=91.91
INV. 12" OUT=91.81
AD RIM=101.51
INV. 6" IN=96.52 SW
INV. 6" IN=99.55 N
INV. 6" OUT=96.42
6" SDCO w/ BOX & COVER
INV.=99.65
TOP OF TD=80.54
INV. OF TD=80.04
6" RL
INV.=96.71
TC @
CI=96.81
INV. 12" OUT=92.71
AD RIM=98.80
INV. 4" OUT=100.02FL OF TD
@ 0.6%
TOP OF TD=80.31
INV. TD=75.31
INV. 12" OUT=75.31
TOP OF TD=80.31
INV. TD=79.36
INV. TD=75.31
TOP OF TD=80.31
INV. TD=79.24
INV. TD=75.31
TOP OF TD=100.46
INV.=99.61
TOP OF TD=100.46
INV. 4" OUT=98.46
AD RIM
=100.16
INV. 6" OUT=97.16
JB, SOLID TOP, RIM
=100.40
INV. 4" IN=96.61 E
INV. 4" IN=98.20 S
INV. 8" RL IN=96.13
INV. 8" IN=96.93 W
INV. 12" OUT=95.80
AD RIM
=100.28
INV. 6" OUT=97.78
AD RIM
=100.39
INV. 6" OUT=97.78
JB, SOLID TOP, RIM
=100.51
INV. 2-6" IN=97.72
INV. 8" OUT=97.39
JB, SOLID TOP, RIM
=100.51
INV. 2-6" IN=97.64
INV. 10" OUT=97.31
AD RIM
=100.31
INV. 6" OUT=97.67
12" W
IDE TRENCH DRAIN
RIM
=80.31
TOP OF TD=80.31
INV. TD=79.81
4" RL (3240Ø)
INV.=99.42 5' FROM
12" WIDE TRENCH DRAIN
RIM=80.54
TOP OF TD=80.54
INV. OF TD=79.71
INV. OF TD=76.21
INV. 6" OUT=76.21
TOP OF TD=80.31
INV. TD=79.81
TC @ CI=96.98
INV. 12" OUT=94.48
POTHOLE
EG 97.6
DEPTH 78"
LOOP RD
JSSTJH
BID DOCUMENTS
05/30/2025
PALO ALTO VA MC
3801 MIRANDA AVENUE
PALO ALTO, CA 94304
B100
RENOVATION AND
EXPANSION OF SPS
640-23-108 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
Veterans Health
Administration
VA FORM 08-6231
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
PROJECT NUMBERCONSULTANTS:
DRAWING #
VA HEALTH CARE SYSTEM APPROVAL:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH KS COA NO. A-930 EXP. 12/31/2025
ENG KS COA. NO. E-2586 EXP. 12/31/2025
FULLY SPRINKLERED
1 2 � 4 � 6 � 8 �
1 2 � 4 � 6 � 8 �
STAMP:
DRAWING NUMBER
BUILDING NUMBER
C 90672
HEN.J NIND GOT
C I V I L
RE
G I
ST
ER
ED PROFESSIONAL ENGINEER
STATE OF CA L I FORN IA
OF 75
CIVIL/STRUCTURAL ENGR
H2B. INC.
1225 N LOOP WEST, STE 800
HOUSTON, TX 77008
(713) 864-2900
MEP / TECH ENGR
SPUR DESIGN
2519 MADISON AVE, STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
HEALTHCARE PLANNER
THE INNOVA GROUP
9442 N. CAPITAL OF TEXAS HWY, STE 325
AUSTIN, TX 78759
(512) 346-8700
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, STE 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
BENCHMARK: .
CS109
STORMWATER POLLUTION
PREVENTION PLAN - LOADING DOCK
EXISTING FEATURES AND ELEVATIONS PRESENTED ON
THIS SHEET ARE BASED ON THE BEST AVAILABLE
INFORMATION. HORIZONTAL AND VERTICAL DATUMS
HAVE NOT BEEN CONFIRMED.
SCALE: 1" = 20'
0 20' 40'
LEGEND: .
EXISTING FEATURES:
NEW FEATURES: .
NOTES: .
1. ALL SUBCONTRACTORS WILL BE EDUCATED TO
FOLLOW STORM WATER POLLUTION PREVENTION
REQUIREMENTS.
2. ANY LAND CLEARING, CONSTRUCTION,
DEVELOPMENT, OR OTHER ACTIVITIES INVOLVING
THE MOVEMENT OF EARTH SHALL BE IN
ACCORDANCE WITH THE SWPPP.
3. A SITE OPERATOR SHALL BE ON SITE ON ALL DAYS
WHERE CONSTRUCTION OR GRADING ACTIVITY
TAKES PLACE.
4. STRUCTURAL BMP's WILL BE INSPECTED AND
MAINTAINED AT LEAST EVERY 14 DAYS AND AFTER
ANY PRECIPITATION OR RUNOFF EVENT THAT
CAUSES SURFACE EROSION, SEDIMENT
TRANSPORT OR VEHICULAR TRACKING.
5. SCRAPING AND SWEEPING OF STREETS,
SIDEWALKS AND FLOWLINES MUST BE CONDUCTED
AT THE END OF EACH WORK DAY WHEN DIRT AND
OTHER CONSTRUCTION MATERIAL HAS BEEN
TRACKED ONTO STREETS.
6. EARTH MATERIALS AND LANDSCAPE MATERIALS
SUCH AS SOD, ROCK AND MULCH SHALL NOT BE
STOCKPILED, PLACED OR STORED ON DRIVEWAYS,
STREETS, SIDEWALKS OR IN STORM WATER
FLOWLINES.
7. CONSTRUCTION SUPPLIES (e.g., TRUSSES AND
LUMBER), ROLL OFF CONTAINERS, DUMPSTERS,
PORTABLE TOILETS, TRAILERS, ETC., SHALL NOT BE
STORED ON STREETS OR SIDEWALKS OR OTHER
IMPERVIOUS SURFACES. THESE ITEMS SHALL BE
STORED ON THE CONSTRUCTION SITE OR STAGING
AREAS.
8. SANITARY FACILITIES SHALL BE LOCATED ON
NATURAL GROUND AND AT LEAST 25 FEET FROM
ANY STORM SEWER INLET OR WATER BODY AND
SHALL BE SERVICED REGULARLY AS NEEDED.
INLET PROTECTION BARRIER
RE: DTL 1 / CS201
IPB
FILTER FABRIC FENCE
RE: DTL 3 / CS201
UNDERGROUND ELECTRIC LINEUGE
STORM DRAINSD
SANITARY SEWERSS
COMMUNICATION LINECOM
WATER LINEW
CHILLED WATER LINECW
GAS LINEG
STREET SWEEPING/CLEANINGSTC
STC
STC
15 721 ASI 1 05.30.2025
W
WATER VALVEELEV=99.64'TN ELEV=XX.XX'
W
WATER VALVEELEV=99.70'TN ELEV=XX.XX'
W
WATER VALVEELEV=99.68'TN ELEV=XX.XX'
SS
ST
W
WATER VALVEELEV=99.35'TN ELEV=XX.XX'
G
TE
99.27'
99.24'
99.24'
98.92'98.33'98.33'97.49' 97.41'
.3
9'
97.47'97.71'
G
TE
M
M
SS
SS
ST
SS
ST
SS
SS
SS
CO
SS
SS
MISC
SS
T
W
WATER VALVEELEV=98.34'TN ELEV=XX.XX'
E
IR
UK
E
CB
CB
CB
G G G G G G
EEE
GGGGG
E
M
IRIR
PB
TV
MISC
MISCCO
CO
GTE
E
E
C B
G
TE
CB
E
T
E
G
TEAC
AC
AC
CO
AC
AC
CO
E
MISC
MISC
IR
W
JSSTJH
BID DOCUMENTS
05/30/2025
PALO ALTO VA MC
3801 MIRANDA AVENUE
PALO ALTO, CA 94304
B100
RENOVATION AND
EXPANSION OF SPS
640-23-108 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
Veterans Health
Administration
VA FORM 08-6231
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
PROJECT NUMBERCONSULTANTS:
DRAWING #
VA HEALTH CARE SYSTEM APPROVAL:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH KS COA NO. A-930 EXP. 12/31/2025
ENG KS COA. NO. E-2586 EXP. 12/31/2025
FULLY SPRINKLERED
1 2 � 4 � 6 � 8 �
1 2 � 4 � 6 � 8 �
STAMP:
DRAWING NUMBER
BUILDING NUMBER
C 90672
HEN.J NIND GOT
C I V I L
RE
G I
ST
ER
ED PROFESSIONAL ENGINEER
STATE OF CA L I FORN IA
OF 75
CIVIL/STRUCTURAL ENGR
H2B. INC.
1225 N LOOP WEST, STE 800
HOUSTON, TX 77008
(713) 864-2900
MEP / TECH ENGR
SPUR DESIGN
2519 MADISON AVE, STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
HEALTHCARE PLANNER
THE INNOVA GROUP
9442 N. CAPITAL OF TEXAS HWY, STE 325
AUSTIN, TX 78759
(512) 346-8700
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, STE 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
BENCHMARK: .
SCALE: 1" = 10'
0 10' 20'
CS110
RESTORATION PLAN
EXISTING FEATURES:
LEGEND: .
REFERENCE TOPOGRAPHIC SURVEY SHEET CS000 FOR
BENCHMARK INFORMATION.
UNDERGROUND ELECTRIC LINEUGE
STORM DRAINSD
SANITARY SEWERSS
COMMUNICATION LINECOM
WATER LINEW
CHILLED WATER LINECW
GAS LINEG
NOTES: .
1. REMOVE ALL ABOVE-GROUND FEATURES INSTALLED IN
PHASES 1-3.
2. REMOVE ALL UNDERGROUND UTILITIES INSTALLED IN
PHASES 1-3.
3. INSTALL ASPHALT PAVEMENT AND CURBS SHOWN.
4. RETURN SITE TO EXISTING CONDITIONS. CONTRACTOR TO
COORDINATE WITH VA COR FOR ANY MATERIALS TO BE
RETURNED TO VA.
NEW FEATURES:
NEW ASPHALT PAVEMENT
RE: DTL 1 / CS200
NEW GRAVEL
RE: DTL 2 / CS201
721 ASI 1 05.30.2025
JSSTJH
BID DOCUMENTS
05/30/2025
PALO ALTO VA MC
3801 MIRANDA AVENUE
PALO ALTO, CA 94304
B100
RENOVATION AND
EXPANSION OF SPS
640-23-108 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
Veterans Health
Administration
VA FORM 08-6231
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
PROJECT NUMBERCONSULTANTS:
DRAWING #
VA HEALTH CARE SYSTEM APPROVAL:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH KS COA NO. A-930 EXP. 12/31/2025
ENG KS COA. NO. E-2586 EXP. 12/31/2025
FULLY SPRINKLERED
1 2 � 4 � 6 � 8 �
1 2 � 4 � 6 � 8 �
STAMP:
DRAWING NUMBER
BUILDING NUMBER
C 90672
HEN.J NIND GOT
C I V I L
RE
G I
ST
ER
ED PROFESSIONAL ENGINEER
STATE OF CA L I FORN IA
OF 75
CIVIL/STRUCTURAL ENGR
H2B. INC.
1225 N LOOP WEST, STE 800
HOUSTON, TX 77008
(713) 864-2900
MEP / TECH ENGR
SPUR DESIGN
2519 MADISON AVE, STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
HEALTHCARE PLANNER
THE INNOVA GROUP
9442 N. CAPITAL OF TEXAS HWY, STE 325
AUSTIN, TX 78759
(512) 346-8700
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, STE 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
CS200
CIVIL DETAILS
CONCRETE BARRIER DETAIL 3
SCALE: NTS
SCALE: NTSSCALE: NTS
SEWER CONNECTION TO EXIST MANHOLEPIPE SUPPORT DETAIL
1VERTICAL CURB DETAIL
NOTES:
1. CONCRETE USED FOR CURBS SHALL HAVE A MINIMUM COMPRESSIVE
STRENGTH OF 3,000 PSI IN 28 DAYS.
2. MAXIMUM SPACING OF CONTROL JOINTS SHALL BE 15-FEET.
�3. 1
2" THICK EXPANSION JOINTS SHALL BE LOCATED AT TANGENT
POINTS IN CURB RETURNS, TRANSITIONS, AND AT A MAXIMUM OF
60-FOOT INTERVALS. EXPANSION MATERIAL SHALL ALSO BE PLACED
BETWEEN CURBS AND ADJACENT STRUCTURES, SIDEWALKS, DRIVEWAYS
AND CURB ACCESS RAMPS. THE �JOINT FILLER SHALL EXTEND
THE FULL DEPTH OF THE CONCRETE.
4. CONCRETE SHALL BE FINISHED WITH A STEEL TROWEL FOLLOWED BY
BRUSHING WITH A FINE BRUSH ALONG THE LENGTH OF THE CURB.
5. SINGLE CURB MAY BE CONSTRUCTED BY THE USE OF FORMS OR MAY
BE SLIP FORMED.
6. ALL EXPOSED EDGES AND HAND TOOLED JOINTS SHALL BE FINISHED
WITH A TOOL HAVING A 1/4" RADIUS UNLESS A LARGER RADIUS IS
INDICATED BY THE APPLICABLE STANDARD DETAILS OR PROJECT PLANS.
7. OMIT 6-INCH BASE EXTENSION WHEN PROPOSED CURB IS ADJACENT
TO AN EXISTING STRUCTURE.
5SCALE: 1" = 1'
6SCALE: NTS
WATERLINE OFFSET DETAIL7SCALE: NTS
WATERLINE BEDDING & BACKFILL DETAIL
UTILITY CONC PAD DETAIL 8SCALE: 1" = 1'
FLUSH CURB 6" CURB
17 721 ASI 1 05.30.2025
JSSTJH
BID DOCUMENTS
05/30/2025
PALO ALTO VA MC
3801 MIRANDA AVENUE
PALO ALTO, CA 94304
B100
RENOVATION AND
EXPANSION OF SPS
640-23-108 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
Veterans Health
Administration
VA FORM 08-6231
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
PROJECT NUMBERCONSULTANTS:
DRAWING #
VA HEALTH CARE SYSTEM APPROVAL:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH KS COA NO. A-930 EXP. 12/31/2025
ENG KS COA. NO. E-2586 EXP. 12/31/2025
FULLY SPRINKLERED
1 2 � 4 � 6 � 8 �
1 2 � 4 � 6 � 8 �
STAMP:
DRAWING NUMBER
BUILDING NUMBER
C 90672
HEN.J NIND GOT
C I V I L
RE
G I
ST
ER
ED PROFESSIONAL ENGINEER
STATE OF CA L I FORN IA
OF 75
CIVIL/STRUCTURAL ENGR
H2B. INC.
1225 N LOOP WEST, STE 800
HOUSTON, TX 77008
(713) 864-2900
MEP / TECH ENGR
SPUR DESIGN
2519 MADISON AVE, STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
HEALTHCARE PLANNER
THE INNOVA GROUP
9442 N. CAPITAL OF TEXAS HWY, STE 325
AUSTIN, TX 78759
(512) 346-8700
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, STE 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
CS201
CIVIL DETAILS
721 ASI 1 05.30.2025
American Welding Society
American National Standards Institute
American Society for Testing and Materials
American Iron and Steel Institute
American Institute of Steel Construction
American Institute of Architects
American Concrete Institute
CC Carried Column
CIP Cast In Place
Addition
Alternate
Air Condition
Aggregate
Anchor BoltAB
ALT
A/C
AGGR
ADD
Angle
And
Asphalt
Approximate
AIA
ACI
AISI
ANSI
ASTM
AISC
L
ASPH
ARCH
APPROX
AWS
Average
Bottom
Bearing
Bending Moment
Base Plate
Building
Center
Ceiling
Center to Center
Center of Gravity
Bottom of Deck
M
BOT
BRG
B PL
AVG
CG
CEN
CLG
BLDG
B/D
AssemblyASSY
Architect or Architectural
Column
Clear
Channel
Concrete
Control Joint
Connection
Cubic Yard
Cubic Foot
Continuous
Construction
C
CJ
CONN
CONC
COL
CLR
CY
CF
CMU
CMP
CONT
CONST
Diagonal
Detail
Ditto
Diameter
Double Angle
Dimensions
Drawing
Douglas Fir
2L
DO
DIM
DIA
DIAG
DET
DF
DWG
DoubleDBL
Concrete Masonry Units
Corrugated Metal Pipe
C/C
AluminumAL
MB Machine Bolt
Glu lam BeamGLB
Quarter
Radius
Reference
Reinforce, Reinforced, QTR
REF
RAD
REINF
Round
Required
Section
Schedule
Revise or Revision
South
Similar
Steel
Standard
Square
Specifications
Sheet
Stock
Tangent
Separation Joint
Structural
Strut Force
Through
Top of Concrete
Top and Bottom
Tongue & Groove
Tolerance
Thick
Top of Footing or Top of Foundation
RD
REV
SECT
SCHED
REQD
S
SIM
STL
STD
SQ
SPECS
SHT
SJ
STK
TAN
SF
STRUCT
TOL
T/F
T/C
T & B
T & G
THRU
THK
Typical
Total
Transverse
Top of Steel
Top of Masonry
Vertical
Verify in the Field
Unless Noted
Unless Noted Otherwise
Top of Concrete Wall
West
Without
With
Work Point
Wide Flange
Welded Wire Fabric
Yard
T/S
T/M
TYP
TOT
TRANS
UNO
UN
VIF
VERT
W
W
WWF
WP
W/O
W/
YD
T/W
Reinforcement, or Reinforcing
Long
Light
Length
Laminated
Longitudinal
LAM
LGTH
LG
LT
LONGIT
Each
East
EF
EA
E
EW
ELECT Electric or Electrical
Each way
Each face
Mark
Metal
Maximum
Material
Maximum
Mechanical
Manufacturer
LLH
LLBB
LLV
MK
MAX
MECH
MATL
MAX
MET
MFR
Medium
Mezzanine
Minimum
Minute
Miscellaneous
Mixture
North
Nominal
Near Side
Near Face
Multiple
MED
MIN
MEZZ
MIX
MISC
MIN
NF
N
NOM
NS
MULT
EQ
ENGR
ETC
EST
EXCAV
EQUIP
EXT
EJ
EXIST
X-STR
X-HVY
Etcetera
Extra Strong
Extra Heavy
Exterior
Expansion Joint
Existing
Excavate
Estimate
Equipment
Equal
Engineer
FS
FF
FT or '
FIN
FIG
FBM
FTG
FD
FRMG
FND
FLR
Framing
Foundation
Footing
Floor Drain
Floor
Finish
Figure
Feet Board Measure
Feet or Foot
Far Side
Far Face
FabricationFAB
Opposite
Opening
On Center
Number
Perpendicular
Permanent
Original
OPP
OPNG
OC
OD
PERP
PERM
d
ORIG
Point
Plate
Pound
Plywood
Project
PT
PL
PLYWD
PSF
PCF
LB
PROJ
PSI
Piece, Pile CapPC
GEN
GI
GALV
GRND
GR
HEX
HGT
HORIZ
S
IN or " Inches
I Beam
Horizontal
Hexagon
Height
Ground
Grade
General (Notes)
Galvanized Iron
Galvanize
Joint
Joist
ID
JT
JST
KO
K
Knockout
Kip (1,000 lbs)
Inside Diameter
Include or IncludedINCL
Not to ScaleGage or Gauge NTSGA
Elevation LHEELEV
Pounds Per Square Inch
Pounds Per Square Foot
Pounds Per Cubic Foot
Penny (Nails, etc)
Outside Diameter
Long Leg Vertical
Long Leg Horizontal
Long Leg Back To Back
Low Hydrogen Electrode
General NotesGN
ABBREVIATIONSGENERAL NOTES
LEGEND:
INDICATES TUBE COLUMN
INDICATES WIDE FLANGE COLUMN
INDICATES BEAM SPLICE
INDICATES FOOTING SIZE. SEE SCHEDULE.F1
SYMBOLS AND ABBREVIATIONS FOR CONCRETE (as per ACI)
SLOPE DIRECTION DOWN
MISCELLANEOUS ELEVATION
FLOOR OR STEEL ELEVATION
REQUIRED NUMBER OF HEADED SHEAR STUDS
RIGID CONNECTION
CAMBER UP
00'-0"
00'-0"
(00'-0")
C=0"
[00]
STEEL ELEVATION
SPAN DIRECTION
To Indicate Size of Deformed Bar.#
Clear
Bottom
Bent
Each Face
Column Tie
Each Way
Limits of Area Covered By Bars
Direction in Which Bars Extend
Spacing Center to Center
Spiral
Stirrup
Plain Bar
Outside Face
Near Face
Inside Face
Top
Straight
Far Face
AT
EF
CT
CL
BOT
BT
EW
T
STR
SP
STIR
PL
OF
NF
IF
FF
Plain Rounds, as Spirals/
INDICATES STD PIPE COLUMN
SYMBOL LEGEND
INDICATES EXISTING ELEMENTS
NOTE: ALL SYMBOLS MAY NOT BE USED
GENERAL
1. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR TO STARTING CONSTRUCTION. NOTIFY
COR OF ANY DISCREPANCIES
2. DO NOT SCALE THE DRAWINGS.
3. GENERAL STRUCTURAL NOTES AND TYPICAL DETAILS APPLY UNLESS NOTED OTHERWISE ON
PLANS, ELEVATIONS, DETAILS AND SPECIFICATIONS. IN CASE OF CONFLICT THE GREATER
REQUIREMENT GOVERNS.
4. THE CONTRACT STRUCTURAL DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED
STRUCTURE. THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION.
5. THE STRUCTURAL ENGINEER SHALL NOT HAVE CONTROL OR CHARGE OF, AND SHALL NOT BE
RESPONSIBLE FOR, CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES OR
PROCEDURES, FOR SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE WORK, FOR
THE ACTS OF OMISSIONS OF THE CONTRACTOR, SUB-CONTRACTORS OR ANY OTHER PERSONS
PERFORMING AN OF THE WORK, OR FOR THE FAILURE OF ANY OF THEM TO CARRY OUT THE WORK
IN ACCORDANCE WITH THE CONTRACT DOCUMENTS.
6. THE CONTRACTOR SHALL PROVIDE ALL MEASURES NECESSARY TO PROTECT THE STRUCTURE
DURING CONSTRUCTION. SUCH MEASURES SHALL INCLUDE, BUT NOT BE LIMITED TO BRACING AND SHORING FOR LOADS DUE TO HYDROSTATIC, EARTH, WIND OR SEISMIC FORCES, CONSTRUCTION EQUIPMENT, ETC. OBSERVATION VISITS TO THE SITE BY THE STRUCTURAL ENGINEER SHALL NOT
INCLUDE INSPECTION OF THE ABOVE ITEMS.
7. NOTIFY THE STRUCTURAL ENGINEER THROUGH THE COR WHEN DRAWINGS BY OTHERS SHOW
OPENINGS, POCKETS, ETC., NOT SHOWN ON THE STRUCTURAL DRAWINGS, BUT WHICH ARE
LOCATED IN THE STRUCTURAL MEMBER.
8. ALL SPECIFICATIONS AND CODES NOTED SHALL BE THE LATEST APPROVED EDITIONS AND
REVISIONS BY THE GOVERNMENTAL AGENCY HAVING JURISDICTION OVER THIS PROJECT.
9. COST OF ADDITIONAL FIELD AND OFFICE WORK NECESSITATED BY REQUESTS BY THE
CONTRACTOR FOR AN OPTION OR DUE TO ERRORS OR OMISSIONS IN CONSTRUCTION SHALL BE
BORNE BY THE CONTRACTOR. OPTIONS ARE FOR CONTRACTOR'S CONVENIENCE. HE SHALL BE
RESPONSIBLE FOR ALL CHANGES NECESSARY IF HE CHOOSES AN OPTION AND HE SHALL
COORDINATE ALL DETAILS.
10. ANY ENGINEERING DESIGN PROVIDED BY OTHERS AND SUBMITTED FOR REVIEW SHALL BEAR THE
SEAL OF AN ENGINEER REGISTERED IN CALIFORNIA.
11. UNLESS NOTED OTHERWISE, DETAILS ON STRUCTURAL DRAWINGS ARE TYPICAL AS INDICATED BY
CUTS, REFERENCES OR TITLE.
12. CONTRACTOR SHALL VERIFY ALL DIMENSIONS WITH ARCHITECTURAL DRAWINGS.
13. FIELD VERIFY ALL EXISTING DIMENSIONS AND CONDITIONS PRIOR TO THE START OF SHOP
DRAWINGS OR CONSTRUCTION.
14. EXISTING CONDITIONS REQUIRING MODIFICATIONS TO DOCUMENTS FOR PROPOSED
CONSTRUCTION SHALL BE IMMEDIATELY SUBMITTED TO THE COR.
CODE AND DESIGN CRITERIA
1. BUILDING CODE: LATEST EDITION OF U.S. DEPARTMENT OF VETERANS AFFAIRS DESIGN GUIDES, STANDARDS, AND MANUALS.
2024 INTERNATIONAL BUILDING CODE (IBC)
2. DESIGN LIVE LOADS:
a. ROOF LL --------------------------------------------------- 20 PSF
b. FLOOR LL ------------------------------------------------- 100 PSF
c. MECHANICAL ROOMS -------------------------------- 150 PSF (UNREDUCIBLE)
3. WIND DESIGN DATA:
a. BUILDING RISK CATEGORY ------------------------- IV
b. BASIC WIND SPEED ----------------------------------- 103 MPH (ULTIMATE)
c. EXPOSURE ----------------------------------------------- C
INTERNAL PRESSURE COEFFICIENT----------- +/- 0.18
4. SNOW DESIGN DATA:
a. GROUND SNOW LOAD (Pg) ------------------------- 7 PSF
b. FLAT ROOF SNOW LOAD (Pf) ---------------------- 5.9 PSF
c. SNOW EXPOSURE FACTOR (Ce) ----------------- 1.0
d. THERMAL FACTOR (Ct) ------------------------------ 1.0
5. RAIN DESIGN DTA:
a. BUILDING RISK CATEGORY ------------------------ IV
b. 15-MINUTE INTENSITY ------------------------------- 3.01 In/Hr
c. 30-MINUTE INTENSITY ------------------------------- 1.46 In/Hr
6. SEISMIC DESIGN DATA:
a. BUILDING RISK CATEGORY------------------------- IV
b. IMPORTANCE FACTOR (IE) ------------------------- 1.5
c. SS ------------------------------------------------------------ 2.15g
d. S1 ------------------------------------------------------------ 0.87g
e. SITE CLASS ---------------------------------------------- C
f. SDS ----------------------------------------------------------- 1.47g
g. SD1------------------------------------------------------------ 0.79g
h. SEISMIC DESIGN CATEGORY---------------------- F
ANALYSIS PROCEDURE USED -------------------- EQUIVALENT LATERAL FORCE
FOUNDATION
1. FOUNDATION:
a. FOUNDATION DESIGN IS BASED ON THE GEOTECHNICAL TECHNICAL REPORT PREPARED BY
TERRACON UES PROJECT NO. R1245041, DATED AUGUST 23, 2024 AND ADDENDUM REPORT
PREPARED BY TERRACON UES PROJECT NO. R1245041, DATED SEPETEMBER 27, 2024.
b. FOOTING SHALL BEAR ON PROPERLY COMPACTED FILL AT 1'-6" MIN BELOW FINISH GRADE, SEE
GEOTECHNICAL REPORT. NET ALLOWABLE BEARING = 2,500 PSF FOR DEAD PLUS LIVE LOAD.
2. SEE PLAN FOR TOP OF FOOTING ELEVATIONS. CONTRACTOR SHALL VERIFY AND LOWER FOOTINGS
AS REQUIRED TO MAINTAIN 1'-6” MINIMUM BELOW FINISH GRADE.
3. CONTRACTOR SHALL PROVIDE FOR PROPER DEWATERING OF EXCAVATIONS FROM SURFACE
WATER, GROUND WATER, SEEPAGE, ETC.
4. CONTRACTOR SHALL PROVIDE FOR THE DESIGN AND INSTALLATION OF ALL CRIBBING, SHEATHING
AND SHORING REQUIRED TO SAFELY AND ADEQUATELY RETAIN THE EARTH BANKS AND ANY
EXISTING STRUCTURE.
5. ALL EARTHWORK, FOOTING DEPTHS, AND EXCAVATIONS FOR FOUNDATIONS SHALL BE INSPECTED
BY THE SOILS ENGINEER TO VERIFY ASSUMED ALLOWABLE SOIL BEARING PRESSURE AND TO
MAKE ANY ADDITIONAL RECOMMENDATIONS.
6. EXCAVATIONS FOR FOOTINGS SHALL BE APPROVED BY THE GEOTECHNICAL ENGINEER PRIOR TO
PLACING THE CONCRETE AND REINFORCING. THE CONTRACTOR SHALL NOTIFY THE
GEOTECHNICAL ENGINEER WHEN THE EXCAVATIONS ARE READY FOR INSPECTION. THE
GEOTECHNICAL ENGINEER SHALL SUBMIT A LETTER OF COMPLIANCE TO THE COR.
7. ALL EXCAVATIONS SHALL BE PROPERLY BACKFILLED. DO NOT PLACE BACKFILL BEHIND RETAINING
WALLS BEFORE CONCRETE OR MASONRY HAS ATTAINED FULL DESIGN STRENGTH. CONTRACTOR
SHALL BRACE OR PROTECT ALL BUILDING AND PIT WALLS BELOW GRADE FROM LATERAL LOADS
UNTIL ATTACHING FLOORS ARE COMPLETELY IN PLACE AND HAVE ATTAINED FULL DESIGN
STRENGTH. CONTRACTOR SHALL PROVIDE FOR DESIGN, PERMITS AND INSTALLATION OF SUCH
BRACING AND PROTECTION.
8. FOOTING BACKFILL AND UTILITY TRENCH BACKFILL WITHIN THE BUILDING PERIMETER SHALL BE
MECHANICALLY COMPACTED IN LAYERS, TO THE APPROVAL OF THE GEOTECHNICAL ENGINEER.
FLOODING WILL NOT BE PERMITTED.
9. ALL ABANDONED FOOTINGS, UTILITIES, ETC., THAT INTERFERE WITH THE NEW CONSTRUCTION
SHALL BE REMOVED.
REINFORCING STEEL
1. ALL REINFORCING STEEL SHALL BE DETAILED AND PLACED IN CONFORMANCE WITH THE `BUILDING
CODE REQUIREMENTS FOR REINFORCED CONCRETE' (ACI 318) AND THE `MANUAL OF STANDARD
PRACTICE FOR REINFORCED CONCRETE CONSTRUCTION' BY CRSI AND WCRSI, AS MODIFIED BY
THE PROJECT DRAWINGS AND SPECIFICATIONS.
2. DEFORMED REINFORCING BARS SHALL CONFORM TO THE REQUIREMENTS OF ASTM A615 GRADE 60.
3. WELDING OF REINFORCING SHALL BE WITH LOW HYDROGEN ELECTRODES IN CONFORMANCE WITH
'RECOMMENDED PRACTICES FOR WELDING REINFORCING STEEL, ETC.', AMERICAN WELDING
SOCIETY, AWS D1.4. WELDING OF REINFORCING STEEL IS LIMITED TO A706 REBAR.
4. ALL REINFORCING BAR BENDS SHALL BE MADE COLD.
5. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A185.
6. MINIMUM LAP OF WELDED WIRE FABRIC SHALL BE 6 INCHES OR ONE FULL MESH AND ONE HALF, WHICH EVER IS GREATER.
7. SPLICES SHALL BE MADE ONLY AS AND WHERE INDICATED ON THE STRUCTURAL DRAWINGS.
8. DOWELS BETWEEN FOOTINGS AND WALLS OR COLUMNS SHALL BE THE SAME GRADE, SIZE,
SPACING AND NUMBER AS THE SPECIFIED VERTICAL REINFORCING, UNO
9. ALL BARS SHALL BE MARKED SO THEIR IDENTIFICATION CAN BE MADE WHEN THE FINAL IN-PLACE
INSPECTION OCCURS.
10. PROVIDE SHOP DRAWINGS AND FABRICATE AFTER THE COR'S REVIEW. ALL SPLICE LOCATIONS ARE
SUBJECT TO APPROVAL. PLACE REBAR PER CRSI STANDARDS.
CONCRETE
1. ALL PHASES OF WORK PERTAINING TO THE CONCRETE CONSTRUCTION SHALL CONFORM TO THE
'BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE', ACI 318, AND THE
`SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS', ACI 301, LATEST EDITIONS, WITH
MODIFICATIONS AS NOTED ON THE DESIGN DRAWINGS OR SPECIFICATIONS.
2. REINFORCED CONCRETE DESIGN IS BY THE ULTIMATE STRENGTH DESIGN METHOD.
3. CONCRETE MIXES SHALL BE DESIGNED BY A QUALIFIED TESTING LABORATORY AND SHALL BEAR
THE WET SEAL OF A CIVIL ENGINEER IN THE STATE OF CALIFORNIA FOR REVIEW BY THE
STRUCTURAL ENGINEER THROUGH THE COR. THE CONCRETE MIX SHALL COMPLY WITH ACI 318
FOR THE FOLLOWING EXPOSURE CLASSES: F0, S0, W1, C1.
a. CONCRETE SLAB-ON-GRADE AND FOOTINGS
i. MAXIMUM WATER/CEMENT RATIO OF 0.50. SLUMP SHALL BE 4" +/-1".
b. TOPPING CONCRETE SLAB
i. MAXIMUM WATER/CEMENT RATIO OF 0.50. SLUMP SHALL BE 4" +/-1".
4. SCHEDULE OF STRUCTURAL CONCRETE 28-DAY STRENGTHS AND TYPES:
LOCATION IN STRUCTURE STRENGTH (PSI) TYPE
TOPPING CONCRETE SLAB 3500 LIGHT-WEIGHT
FOOTINGS 4000 NORMAL-WEIGHT
ALL CONCRETE UNO 4000 NORMAL-WEIGHT
5. PORTLAND CEMENT SHALL CONFORM TO ASTM C150, TYPE II.
6. AGGREGATE FOR HARD ROCK CONCRETE SHALL CONFORM TO ALL REQUIREMENTS AND TESTS OF ASTM C33 AND PROJECT SPECIFICATIONS. EXCEPTIONS MAY BE USED ONLY WITH PERMISSION OF
THE STRUCTURAL ENGINEER THROUGH THE COR.
7. CONCRETE MIXING OPERATIONS, ETC., SHALL CONFORM TO ASTM C94.
8. PLACEMENT OF CONCRETE SHALL CONFORM TO ACI STANDARD 304 AND PROJECT
SPECIFICATIONS. SANDBLAST ALL CONCRETE SURFACES AGAINST WHICH CONCRETE IS TO BE
PLACED.
9. PLACING OF CONCRETE SHALL CONFORM TO ACI 305 "HOT WEATHER CONCRETING" AND ACI 306
"COLD WEATHER CONCRETE" WHEN APPLICABLE.
10. CLEAR COVERAGE OF CONCRETE OVER REINFORCING BARS BE AS FOLLOWS:
a. CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH ------------- 3”
b. CONCRETE EXPOSED TO EARTH OR WEATHER:
i. NO. 6 THROUGH NO. 18 BAR ----------------------------------------------------------------------- 2”
ii. NO. 5 BAR AND SMALLER --------------------------------------------------------------------------- 1 1/2”
c. CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND
i. SLABS, WALLS, JOISTS:
1. NO. 14 AND NO. 18 BAR ----------------------------------------------------------------------------- 1 1/2”
2. NO. 11 BAR AND SMALLER ------------------------------------------------------------------------- 3/4”
ii. BEAMS, COLUMNS:
1. PRIMARY REINFORCEMENT, TIES, STIRRUPS, SPIRALS --------------------------------1 1/2”
d. SLABS ON GRADE (FROM TOP)----------------------------------------------------------------------- 1 1/2”
11. ALL REINFORCING BARS, ANCHOR BOLTS AND OTHER CONCRETE INSERTS SHALL BE WELL
SECURED IN POSITION PRIOR TO PLACING CONCRETE.
12. MECHANICAL PIPES AND ELECTRICAL CONDUITS WHICH PASS THROUGH SLAB ON GRADE,
CONCRETE ON STEEL DECK, FRAMED CONCRETE FLOORS AND WALLS DO NOT REQUIRE SLEEVES,
UNLESS OTHERWISE INDICATED IN THE PROJECT SPECIFICATIONS, MECHANICAL OR ELECTRICAL DRAWINGS. IF SLEEVES ARE REQUIRED, INSTALL SLEEVES BEFORE PLACING CONCRETE. DO NOT CUT ANY REINFORCING WHICH MAY INTERFERE WITH SLEEVE PLACEMENT. CORING OPENINGS IN
CONCRETE IS NOT PERMITTED. NOTIFY THE STRUCTURAL ENGINEER THROUGH THE COR IN
ADVANCE OF CONDITIONS NOT SHOWN ON THE STRUCTURAL DRAWINGS. NO PIPES OR
ELECTRICAL CONDUIT SHALL PASS THROUGH CONCRETE BEAMS OR COLUMNS UNLESS
SPECIFICALLY DETAILED.
13. PROJECTING CORNERS OF BEAMS, WALLS, COLUMNS, ETC., SHALL BE FORMED WITH A 3/4 IN.
CHAMFER, UNLESS OTHERWISE NOTED ON ARCHITECTURAL DRAWINGS.
14. CURING COMPOUNDS USED ON CONCRETE THAT IS TO RECEIVE A RESILIENT TILE FINISH SHALL BE
APPROVED BY THE FINISH APPLICATOR BEFORE USE.
15. MODULUS OF ELASTICITY OF CONCRETE, WHEN TESTED IN ACCORDANCE WITH ASTM C469, SHALL
BE AT LEAST THE VALUE GIVEN BY THE EQUATIONS IN SECTION 8.5.1 OF ACI 318 FOR THE
SPECIFIED CONCRETE 28-DAY STRENGTH.
16. MINIMUM STRENGTH FOR REMOVAL OF FORMS AND SHORING SHALL BE 75% OF SPECIFIED
STRENGTH AT 28 DAYS.
17. ALL CONCRETE NOT SPECIFICALLY SHOWN WITH REINFORCEMENT SHALL BE REINFORCED IN THE
SAME MANNER AS SIMILAR CONDITIONS OR WITH REINFORCEMENT MEETING THE MINIMUM
REQUIREMENTS OF ACI-318.
18. CONCRETE SLAB SHALL BE WET MAT, MOIST CURED FOR A MINIMUM OF 7 DAYS.
19. CONCRETE MIXES MAY CONTAIN FLY ASH AS NOTED PER SPECIFICATIONS.
STRUCTURAL STEEL
1. STRUCTURAL STEEL SHALL BE DESIGNED, DETAILED, FABRICATED AND ERECTED IN ACCORDANCE WITH THE AISC 'SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS' AND 'CODE OF STANDARD
PRACTICE FOR STEEL BUILDINGS AND BRIDGES' (LATEST EDITION AND SUPPLEMENTS).
2. ALL WIDE FLANGE SHAPES SHALL CONFORM TO ASTM A992.
3. ALL CHANNELS, ANGLES, PLATES & BARS SHALL CONFORM TO ASTM A36. UNLESS NOTED
OTHERWISE.
4. ALL PIPE COLUMNS SHALL CONFORM TO ASTM A53 (TYPES E OR S), GRADE B OR ASTM A501.
5. ALL SQUARE OR RECTANGULAR TUBING SECTIONS SHALL CONFORM TO ASTM A500, GRADE C, OR ASTM A501 WITH Fy= 50 KSI.
6. ALL SIMPLE BEAM TO BEAM OR COLUMN CONNECTION PLATE MATERIAL, INCLUDING BEARING PLATES, GUSSET PLATES, STIFFENER PLATES, FILLER PLATES, ETC. SHALL CONFORM TO A36, UNLESS NOTED OTHERWISE.
7. ALL CONNECTION ANGLE MATERIAL SHALL CONFORM TO ASTM A36 UNLESS NOTED OTHERWISE.
8. CONNECTING OR SPLICING OF STRUCTURAL STEEL NOT SHOWN ON THE DRAWINGS IS PROHIBITED
WITHOUT PRIOR WRITTEN APPROVAL OF THE COR/ ENGINEER-OF-RECORD.
9. THE STRUCTURAL STEEL FABRICATOR SHALL FURNISH SHOP DRAWINGS OF ALL STRUCTURAL
STEEL, FOR COR'S REVIEW BEFORE FABRICATION. SHOP DRAWINGS SHALL SHOW THE ERECTION PROCEDURES AND DETAILS. THE ICC REPORT, INCLUDING VERTICAL LOAD AND DIAPHRAGM SHEAR
CAPACITY SHALL BE FURNISHED.
STRUCTURAL STEEL (CONTINUED)
10. BOLT HOLES IN STEEL SHALL BE 1/16 INCH LARGER THAN NOMINAL SIZE OF BOLT USED. HOLE SIZES FOR F1554 ANCHOR BOLTS MAY BE MADE OVERSIZE TO FACILITATE ERECTION AS FOLLOWS:
a. BOLTS 3/4 TO 1 INCH: 5/16" LARGER THAN NORMAL SIZE OF BOLT.
b. BOLTS 1 TO 2 INCH: 1/2" LARGER THAN NORMAL SIZE OF BOLT.
c. BOLTS OVER 2 INCHES: 1" LARGER THAN NORMAL SIZE OF BOLT.
IF F1554 ANCHOR BOLTS ARE OVERSIZED, AN ASTM F436 HARDENED WASHER SHALL BE
INSTALLED UNDER THE BOLT HEAD AND THE NUTS SHALL MEET THE REQUIREMENTS OF ASTM
A563.
11. SEE SPECIFICATIONS FOR FINISH/PAINTING REQUIREMENTS FOR STRUCTURAL STEEL SURFACES.
VERIFY WITH ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
12. WELDED JOINTS SHALL CONFORM TO THE PREQUALIFIED JOINT DETAILS AS INDICATED IN THE
STRUCTURAL WELDING CODE (AWS D1.1) BY THE AMERICAN WELDING SOCIETY.
13. ALL WELDING SHALL BE BY WELDERS HOLDING CURRENT VALID CERTIFICATES AND HAVING
CURRENT EXPERIENCE IN TYPE OF WELD CALLED FOR. WELDING RODS TO BE LOW HYDROGEN
TYPE, E70.
14. ALL GROOVE WELDS TO BE FULL PENETRATION UNLESS NOTED. FULL PENETRATION WELDS AND
ALL BUTT WELDED SPLICES OR CONNECTIONS SHALL BE ULTRASONICALLY TESTED AND
INSPECTED BY AN INDEPENDENT TESTING LABORATORY TO CERTIFY ALL SPLICES AS MEETING OR
EXCEEDING STRENGTH OF MATERIALS SPLICED. REDUCTION IN TESTING MAY BE MADE IN
ACCORDANCE WITH THE BUILDING CODE WITH APPROVAL OF THE ENGINEER. TWO COPIES OF ALL
TEST REPORTS AND A LETTER OF SUCH CERTIFICATION SHALL BE SUBMITTED TO THE COR.
15. WELDS MAY BE MADE IN SHOP OR FIELD WITH APPROVAL.
16. WELD LENGTHS CALLED FOR ON PLANS ARE THE NET EFFECTIVE LENGTH REQUIRED. WELD SIZE SHALL BE AISC MINIMUM PER AISC SECTION J2.1b AND 2.2b UNLESS A LARGER SIZE IS NOTED.
17. WELD TEST AND INSPECTIONS, SEE SPECIFICATIONS.
18. EXCEPT AS SUBSEQUENTLY NOTED, HIGH STRENGTH BOLTS NEED NOT BE TIGHTENED BEYOND
THE SNUG-TIGHT CONDITION, AS DEFINED IN SECTION 8.1 OF THE SPECIFICATIONS FOR
STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS. FOR CONNECTIONS SUBJECT TO DIRECT
TENSION, CONNECTIONS FOR BRACED FRAMES, AND OTHER CONNECTIONS SHOWN OR NOTED ON
THE PLANS AS SC (SLIP CRITICAL) OR FULLY TENSIONED, BOLTS SHALL BE TIGHTENED BY ONE OF THE METHODS DESCRIBED IN SECTION 8.2 AND TO THE MINIMUM TENSION SPECIFIED IN SECTION
8.2, TABLE 8.1.
19. SEE MECHANICAL DRAWINGS FOR MECHANICAL EQUIPMENT SUPPORT FRAMING.
DEFERRED SUBMITTALS
1. THE MODULAR BUILDING FOUNDATIONS SHALL BE DESIGNED AND SEALED BY A LICENSED
ENGINEER IN THE STATE OF CALIFORNIA. THE CALCULATIONS AND DETAIL DRAWINGS SHALL BE
SUBMITTED FOR APPROVAL SHOWING ALL CALCULATIONS, INCLUDING DESIGN LOADS, MEMBER
SIZES AND CONNECTIONS.
2. PREFABRICATED METAL RAMPS & METAL STAIRS INCLUDING HANDRAILS AND THEIR CONNECTIONS SHALL BE DESIGNED AND SEALED BY A LICENSED ENGINEER IN THE STATE OF CALIFORNIA. THE
CALCULATIONS AND DETAIL DRAWINGS SHALL BE SUBMITTED FOR APPROVAL SHOWING ALL
CALCULATIONS, INCLUDING DESIGN LOADS, MATERIAL, MEMBER SIZES AND CONNECTIONS. REFER
TO SPECIFICATION 05 51 00.
WOOD FRAMING
1. LUMBER AND ITS FASTENINGS SHALL CONFORM TO THE NATIONAL DESIGN SPECIFICATIONS FOR
WOOD CONSTRUCTION, LATEST EDITION.
2. ALL WOOD FRAMING SIZES, FRAMING, FASTENING REQUIREMENTS, ANCHORAGES, FIRESTOPS, AND CONNECTORS NOT SHOWN ON THESE PLANS TO BE PER THE SPECIFIED BUILDING CODE.
WOOD FRAMING SIZES SHOWN ARE THE MINIMUM REQUIRED STRUCTURALLY; COORDINATE WITH
OTHER DISCIPLINES FOR FURTHER DEPTH REQUIREMENTS FOR NON-STRUCTURAL PURPOSES.
3. SAWN LUMBER: WEST COAST DOUGLAS FIR - LARCH, SURFACED DRY. 6 X BEAMS AND POSTS:
FREE OF HEART CENTERS. ALL STRUCTURAL FRAMING: NO. 2 OR BETTER.
4. ALL WOOD FRAMING EXPOSED TO WEATHER SHALL BE PRESSURE-TREATED. ALL FASTENERS IN
CONTACT WITH PRESSURE-TREATED WOOD TO BE HOT DIP GALVANIZED PER THE
MANUFACTURERS RECOMMENDATIONS AND THE APPLICABLE BUILDING CODE. ALL STRUCTURAL
COLUMNS TO BE HELD 1" ABOVE THE SLAB BY A SPECIFIED OR APPROVED CONNECTION DEVICE.
5. THE FRAMING LAYOUTS DEPICTED ON THE PLANS ARE TO ILLUSTRATE GENERAL FRAMING
CONDITIONS BUT DO NOT NECESSARILY DEPICT THE CORRECT QUANTITIES OR CONNECTIONS
REQUIRED.
6. FASTENING FOR ALL STRUCTURAL MEMBERS NOT SPECIFICALLY SHOWN IN THE PLANS TO BE PER
THE FASTENING SCHEDULE OF THE APPLICABLE BUILDING CODE.
7. BOLTS SHALL CONFORM TO ASTM A307, ANSI D18.2.1. SCREWS AND LAG SCREWS SHALL CONFORM TO ANSI B18.2.1. AND ANSI B18.6.1, RESPECTIVELY. BOLTS THROUGH WOOD SHALL BE FITTED WITH
STANDARD WASHERS.
8. BOLT HOLES SHALL BE AT LEAST A MINIMUM DIAMETER OF 1/32" AND NO MORE THAN A MAXIMUM
OF 1/16" LARGER THAN THE BOLT DIAMETER.
9. BOLT NUTS SHALL BE FINGER-TIGHT PLUS 1/3 TO 1/2 TURN WITH A HAND WRENCH, WITH
CONSIDERATION GIVEN TO POSSIBLE FUTURE WOOD SHRINKAGE. CARE SHOULD BE TAKEN NOT
TO OVER-TORQUE THE NUT. IMPACT WRENCHES SHOULD NOT BE USED AS THEY MAY PRELOAD
THE CONNECTORS. BOLT NUTS SHALL BE PERIODICALLY RETIGHTENED.
10. UNLESS OTHERWISE NOTED, CONNECTORS SHALL BE INSTALLED WITH THE MAXIMUM NUMBER AND SIZE OF FASTENERS AS REQUIRED IN THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.
11. THE NUMBER AND SIZE OF NAILS USED TO CONNECT WOOD MEMBERS SHALL BE ACCORDING TO
THE APPLICABLE BUILDING CODE. REFER TO MANUFACTURER FOR NAILING REQUIREMENTS (TO
ATTAIN MAXIMUM TABLE VALUES) FOR ALL WOOD-TO-WOOD MECHANICAL FASTENERS.
12. MULTIPLE STUDS SHALL BE GLUED AND NAILED WITH 10d NAILS 24" OC.
13. BRACING SHALL BE PROVIDED FOR ALL WALLS UNTIL SHEAR PANELS, FLOOR FRAMING, ROOF
FRAMING, AND DECKING ARE INSTALLED.
14. CUTTING AND NOTCHING OF ALL LOAD BEARING STUDS SHALL BE LIMITED TO 25% OF THE STUD
DEPTH.
15. ALL LOAD BEARING WALLS SHALL CONSIST OF A SINGLE STUD SILL PLATE AT THE BOTTOM AND A DOUBLE STUD TOP PLATE AT THE TOP. STUDS USED IN PLATES SHALL MATCH THE DIMENSIONS USED FOR STUDS WITHIN THE WALLS. STUD WALLS SHALL END WITH DOUBLE STUDS ON EACH END.
16. WHERE HEADERS FRAME INTO STUDS, DOUBLE STUDS SHALL BE PROVIDED, UNO.
17. ALL BEAMS AND JOISTS TO BE FRAMED FLUSH WITH SUPPORTING MEMBER TO BE SUPPORTED BY
APPROVED HANGERS WITHIN ENCLOSED CONDITIONED SPACE.
18. DOUBLE JOISTS ARE TO BE PROVIDED BELOW PARTITION WALLS THAT RUN PARALLEL TO JOISTS AND SOLID BLOCKING THE DEPTH OF THE JOISTS SHALL BE PROVIDED BETWEEN JOISTS BELOW
PARTITION WALLS THAT FRAME PERPENDICULAR TO JOISTS.
19. PLYWOOD WALL SHEATHING SHALL BE APA RATED CD EXTERIOR. THICKNESS AS SHOWN ON THE DRAWINGS. SPAN RATING SHALL BE 32/16. NAIL PLYWOOD AT 6” OC ALONG PANEL EDGES AND 12” OC AT INTERMEDIATE SUPPORTS AND BLOCKING WITH 10d HOT-DIP GALVANIZED NAILS UNLESS
SHOWN OTHERWISE ON THE DRAWINGS. SEE SHEARWALL PLAN FOR NAILING REQUIREMENTS AT
SHEARWALLS.
20. PLYWOOD FLOOR DECK SHALL BE APA RATED CD INTERIOR WITH EXTERIOR GLUE, THICKNESS AS
SHOWN ON THE DRAWINGS. INSTALL PLYWOOD WITH FACE GRAIN ALONG SUPPORTS. PLYWOOD
SPAN RATING SHALL BE 48/24. NAIL PLYWOOD TO FRAMING WITH 10d HOT-DIP GALVANIZED NAILS.
SEE PLAN FOR NAILING.
21. FOR OVERLAY FRAMING AT ROOF OR OTHER CONVENTIONAL ROOF FRAMING, CONTRACTOR SHALL PROVIDE 2X FRAMING IN ACCORDANCE WITH ROOF RAFTER TABLES IN THE APPLICABLE BUILDING
CODE.
22. ALL PLYWOOD SHEATHING SHALL BE STAGGERED.
23. PLYWOOD ROOF DECKING SHALL BE APA RATED CD EXTERIOR. THICKNESS AS SHOWN ON THE
DRAWINGS. INSTALL PLYWOOD WITH FACE GRAIN ACROSS SUPPORTS. PLYWOOD SPAN RATING
SHALL BE 32/16. NAIL PLYWOOD TO FRAMING WITH 10d HOT-DIP GALVANIZED NAILS. SEE PLAN FOR
NAILING.
PRE-MANUFACTURED WOOD TRUSSES
1. DESIGN AND DETAILING OF PRE-MANUFACTURED PRODUCTS, CONNECTIONS, AND ACCESSORIES
SHALL BE IN ACCORDANCE WITH THE RECOMMENDATIONS OF THE NATIONAL DESIGN
SPECIFICATIONS FOR WOOD CONSTRUCTION.
2. CONTRACTOR SHALL TAKE NECESSARY PRECAUTIONS TO PROPERLY BRACE TRUSSES DURING
LIFTING AND ERECTION. CONSULT THE BUILDING COMPONENT SAFETY INFORMATION (BCSI),
LATEST EDITION OR APPROVED EQUAL FOR APPROVED METHODS.
3. TRUSS MANUFACTURER SHALL DESIGN ALL TRUSS COMPONENTS FOR ALL GRAVITY, SHEAR, WIND, AND SNOW (IF APPLICABLE) LOADS AS NOTED ON STRUCTURAL DRAWINGS. THE MANUFACTURER
SHALL EXAMINE THE DRAWINGS FOR SPECIAL CONDITIONS AND/OR LOADS NOT SHOWN AND
PROVIDE FOR SUCH IN THE DESIGN.
4. OVERALL TRUSS DIMENSIONS SHALL BE COORDINATED WITH ARCHITECTURAL DRAWINGS PRIOR
TO FABRICATION.
5. CONTRACTOR SHALL KEEP TRUSSES PROPERLY BRACED DURING ERECTION UNTIL ALL BRIDGING, RAFTERS, JOISTS AND DIAPHRAGMS ARE INSTALLED.
6. TRUSS MANUFACTURER SHALL SUBMIT SHOP DRAWINGS FOR APPROVAL SHOWING ALL MEMBER
FORCES, SIZE AND CONNECTORS. DRAWINGS SHALL BE SEALED BY A REGISTERED PROFESSIONAL
ENGINEER IN THE STATE WHERE THE PROJECT IS LOCATED. THE FOLLOWING DATA SHALL BE
INCLUDED ON THE SHOP DRAWINGS:
A. DESIGN AND FABRICATION DATE.
B. METAL CONNECTORS' GAUGE, SIZE OF PLATE, LOCATION AND NAME OF MANUFACTURER.
C. LUMBER GRADING AT ALL TRUSS MEMBERS.
D. SPAN AND SPACING OF TRUSSES.
E. DESIGN LOADINGS AND ALLOWABLE UNIT STRESS INCREASES, IF ANY.
F. DEAD AND LIVE LOAD DEFLECTIONS.
G. ERECTION PLAN
7. THE MOISTURE CONTENT OF ALL LUMBER SHALL NOT EXCEED 19% IN ANY CASE AT THE TIME OF
FABRICATION.
8. TRUSS LUMBER SHALL MATCH THE LUMBER USED FOR OTHER WOOD ELEMENTS ON THIS
PROJECT, AS SPECIFIED IN THE GENERAL NOTES.
9. ALL TRUSS CONNECTOR PLATES SHALL BE MANUFACTURED FROM STRUCTURAL QUALITY
GALVANIZED SHEET METAL OF NOT LESS THAN 20 GAUGE THICKNESS. THE SHEET METAL SHALL NOT HAVE A MINIMUM YIELD STRESS LESS THAN 33 KSI AND A MINIMUM ULTIMATE STRENGTH LESS
THAN 45 KSI.
10. ALL TRUSS MEMBERS SHALL BE ACCURATELY CUT TO LENGTH, ANGLE, AND TRUE TO LINE TO
ASSURE TIGHT JOINTS OR THE FINISHED TRUSS.
11. OPEN JOINTS WHICH DEPEND ON THE STIFFNESS OF THE METAL CONNECTOR PLATE TO TRANSMIT
STRESSES AND IMPROPER FITTING JOINTS WILL NOT BE PERMITTED. TRUSSES WITH ANY
LOOSENESS OR SEPARATION OF THE CONNECTOR PLATES SHALL NOT BE ACCEPTED.
12. DEAD KNOTS AND WANES ON LUMBER SHALL NOT BE PRESENT UNDER THE CONNECTOR PLATES.
13. TRUSSES SHALL NOT BE ALLOWED TO GET WET AT ANY TIME. TRUSSES SHALL BE KEPT COVERED
DURING SHIPPING, STORAGE, AND CONSTRUCTION.
14. MAXIMUM LIVE LOAD DEFLECTION SHALL BE SPAN/240 FOR ROOF TRUSSES AND SPAN/360 FOR
FLOOR, BALCONY, AND BREEZEWAY TRUSSES.
15. ALL TRUSS HANGERS AND MISCELLANEOUS FASTENERS TO BE PROVIDED BY TRUSS
MANUFACTURER.
16. COORDINATE ALL ROOF TRUSS PROFILES AND CLEARANCES WITH MECHANICAL DRAWINGS.
17. TRUSSES SHALL BE DESIGNED TO ACCOMMODATE A LIVE LOAD OF 20 PSF ON THE BOTTOM CHORD
IN ADDITION TO ANY OTHER LOADS DENOTED WITHIN THE DRAWINGS.
18. AT BUILDING ENDS, SPECIAL GABLE-END TRUSSES SHALL BE USED. TRUSSES SHALL BE DESIGNED
AND FABRICATED WITH VERTICAL STUDS NO MORE THAN 16 INCHES ON CENTER. NARROW FACE
OF STUD SHALL BE //PARALLEL//PERPENDICULAR// TO FACE OF EXTERIOR WALL. STUDS SHALL BE
BRACED AS REQUIRED FOR THE DESIGN WIND LOAD. AT GABLE END WALLS, STUDS SHALL BE
BALLOON FRAMED TO THE BOTTOM OF THE TRUSS.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
PROJECT NUMBERCONSULTANTS:
DRAWING #
VA HEALTH CARE SYSTEM APPROVAL:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH KS COA NO. A-930 EXP. 12/31/2025
ENG KS COA. NO. E-2586 EXP. 12/31/2025
CIVIL/STRUCTURAL ENGR
H2B. INC.
1225 N LOOP WEST, STE 800
HOUSTON, TX 77008
(713) 864-2900
MEP / TECH ENGR
SPUR DESIGN
2519 MADISON AVE, STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
HEALTHCARE PLANNER
THE INNOVA GROUP
9442 N. CAPITAL OF TEXAS HWY, STE 325
AUSTIN, TX 78759
(512) 346-8700
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, STE 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
DRAWING NUMBER
BUILDING NUMBER
05/30/2025
09/30/2026
/3
/2
:5 :1
A
M
GENERAL NOTES, ABBREVIATIONS, AND
LEGEND
IG 19 OF 72GMG
BID DOCUMENTS
RENOVATION AND EXPANSION OF SPS
05/30/2025
640-23-108
PALO ALTO VA MC
3801 MIRANDA AVENUE
PALO ALTO, CA 94304
S-000
B100
SPUR #: 1795.07No. REVISION DESCRIPTION DATE
1 ASI 1 05.30.2025
QUALITY ASSURANCE PLAN AND STATEMENT OF SPECIAL INSPECTION
1. SPECIAL INSPECTION, PER THE 2024 INTERNATIONAL BUILDING CODE CHAPTER 17, SECTION 1704 AND 1705. SEE PROJECT SPECIFICATIONS AND STATEMENT OF SPECIAL INSPECTIONS BELOW FOR
SPECIFIED REQUIREMENTS.
2. STATEMENT OF SPECIAL INSPECTIONS THIS STATEMENT OF SPECIAL INSPECTIONS IS IN
ACCORDANCE WITH SECTIONS 1704.3 OF THE IBC 2024 CODE. THE INTENT OF THIS SECTION IS THAT ALL SPECIAL INSPECTIONS SHALL BE PERFORMED IN ACCORDANCE WITH THE PROVISIONS OF CHAPTER 17 OF THE 2024 IBC UNLESS SPECIFICALLY NOTED OTHERWISE. SPECIAL INSPECTION
IS REQUIRED FOR THE FOLLOWING:
a. STEEL CONSTRUCTION (IBC 1705.2, AISC 360-22)
i. WELDING:
ii. HIGH STRENGTH BOLTS:
b. CONCRETE CONSTRUCTION (IBC 1705.3, ACI 318)
c. SOILS (IBC 1705.6)
d. ANCHORAGE OF PLUMBING, MECHANICAL, AND ELECTRICAL EQUIPMENT (IBC 1705.13.6
i. PERIODIC PER IBC 1705.13.6
e. VERIFY THAT THE COMPONENT LABEL, ANCHORAGE, AND MOUNTING CONFORMS TO THE
CERTIFICATE OF COMPLIANCE FOR ELEMENTS OF THE DESIGNATED SEISMIC SYSTEMS
REQUIRING SEISMIC QUALIFICATION (IBC 1705.13.4)
i. PERIODIC PER IBC 1705.13.4
3. THE SPECIAL INSPECTOR (SI) SHALL BE RETAINED BY THE CONTRACTOR AND APPROVED BY THE
CONTRACTING OFFICER AS HAVING THE COMPETENCE NECESSARY TO INSPECT A PARTICULAR
TYPE OF CONSTRUCTION REQUIRING SPECIAL INSPECTIONS. THE SI MUST BE AN INDEPENDENT
THIRD PARTY HIRED DIRECTLY BY THE PRIME CONTRACTOR.
4. ITEMS SPECIFIED AS QUALITY CONTROL (QC) IN THE FOLLOWING TABLES SHALL BE PROVIDED BY
THE CONTRACTOR'S FABRICATOR AND ERECTOR AS REQUIRED PER AISC 360.
5. ITEMS NOTED AS QUALITY ASSURANCE (QA) SHALL BE PROVIDED BY THE CONTRACTOR'S SPECIAL
INSPECTOR.
SPECIAL INSPECTIONS
A. ALL CONCRETE WORK FOR STRENGTHS GREATER THAN 2500 PSI, EXCEPT FOR NON-STRUCTURAL
CONCRETE.
B. ALL REINFORCING STEEL FOR CONCRETE STRENGTHS GREATER THAN 2500 PSI.
C. ALL FIELD WELDING (EXCEPT METAL STUDS, FURRING CHANNELS, ETC). SHOP WELDING FOR
PROCEDURES AND MULTIPLE PASS WELDS.
D. ALL FULL PENETRATION WELDS SHALL BE SPECIALLY INSPECTED ACCORDANCE WITH AWS AND
THE CURRENT INTERNATIONAL BUILDING CODE.
E. ALL FILLET WELDS SHALL BE VISUALLY INSPECTED IN ACCORDANCE WITH AWS AND THE CURRENT
INTERNATIONAL BUILDING CODE.
F. BOLTS INSTALLED IN CONC. OR MASONRY.
G. ALL EXPANSION BOLTS AND ADHESIVE ANCHORS.
REQUIRED SPECIAL INSPECTION AND TESTS OF STRUCTURAL WOOD - REFERENCE 2024 IBC 1705.12.1
AND 1705.13.2
PERIODIC SPECIAL INSPECTION SHALL BE REQUIRED FOR NAILING, BOLTING, ANCHORING, AND OTHER FASTENING ELEMENTS OF THE SEISMIC FORCE-RESISTING SYSTEM, INCLUDING WOOD SHEAR WALLS, WOOD DIAPHRAGMS, DRAG STRUTS, BRACES, SHEAR PANELS AND HOLD-DOWNS.
REQUIRED SPECIAL INSPECTIONS OF PREFABRICATED WOOD TRUSSES - REFERENCE 2024 IBC 1705.5 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
PROJECT NUMBERCONSULTANTS:
DRAWING #
VA HEALTH CARE SYSTEM APPROVAL:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH KS COA NO. A-930 EXP. 12/31/2025
ENG KS COA. NO. E-2586 EXP. 12/31/2025
CIVIL/STRUCTURAL ENGR
H2B. INC.
1225 N LOOP WEST, STE 800
HOUSTON, TX 77008
(713) 864-2900
MEP / TECH ENGR
SPUR DESIGN
2519 MADISON AVE, STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
HEALTHCARE PLANNER
THE INNOVA GROUP
9442 N. CAPITAL OF TEXAS HWY, STE 325
AUSTIN, TX 78759
(512) 346-8700
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, STE 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
DRAWING NUMBER
BUILDING NUMBER
05/30/2025
09/30/2026
/3
/2
:5 :1
A
M
SPECIAL INSPECTIONS
IG 20 OF 72GMG
BID DOCUMENTS
RENOVATION AND EXPANSION OF SPS
05/30/2025
640-23-108
PALO ALTO VA MC
3801 MIRANDA AVENUE
PALO ALTO, CA 94304
SA011
B100
SPUR #: 1795.07
5. Prior to placement of compacted fill, inspect subgrade and verify that site has been prepared properly.
X
4. During fill placement, verify use of proper materials and procedures in accordance with the provisions of the approved geotechnical report. Verify densities and lift thickness during placement and comapction of compacted fill.
X
3. Perform classification and testing of compacted fill materials.
X
2. Verify excavations are extended to proper depth and have reached proper material.
X
1. Verify materials below shallow foundations are adequate to achieve the design capacity.
X
TYPE
CONTINUOUS
SPECIAL
INSPECTION
PERIODIC SPECIAL INSPECTION
REQUIRED SPECIAL INSPECTIONS AND TESTS OF SOILS - REFERENCE 2024 IBC TABLE 1705.6
7. Verify maintenance of specified curing temperature techniques.
X ACI 318: 26.5.3-26.5.5
6. Inspect concrete placement for proper application techniques.
X ACI 318: 26.5
5. Prior to concrete placement, fabricate specimens for strength tests, perform slump and air content tests, and determine the temperature of the concrete.
X
ASTM C172 ASTM C31
ACI 318: 26.5, 26.12
4. Verify use of required design mix.
X
ACI 318: CH. 19, 26.4.3,
26.4.4 1904.1, 1904.2
3. Inspect anchors post-installed in hardened concrete members.
X ACI 318: 26.13
2. Inspect anchors cast in concrete.
X ACI 318: 26.13.3.3
1. Inspect reinforcement and verify placement.
X
ACI 318 CH. 20, 25.2,
25.3, 26.6.1, 26.6.3
TYPE
CONTINUOUS
SPECIAL
INSPECTION
PERIODIC SPECIAL
INSPECTION
REFERENCE STANDARD IBC REFERENCE
REQUIRED SPECIAL INSPECTIONS AND TESTS OF CONCRETE CONSTRUCTION - REFERENCE 2024 IBC TABLE 1705.3
O – Observe these items on a random basis. Operations need not be delayed pending these inspections.
P – Perform these tasks for each welded joint or member.
Check welding equipment O -
Fit-up of fillet welds
• Dimensions (alignment, gaps at root)
• Cleanliness (condition of steel surfaces)
• Tacking (tack weld quality and location)
O O
Configuration and finish of access holes O O
Fit-up of CJP groove welds of HSS T-, Y-, and K-joints without backing (including joint geometry)
• Joint preparation
• Dimensions (alignment, root opening, root face, bevel)
• Cleanliness (condition of steel surfaces)
• Tacking (tack weld quality and location)
O O
Fit-up of groove welds (including joint geometry)
• Joint preparation
• Dimensions (alignment, root opening, root face, bevel)
• Cleanliness (condition of steel surfaces)
• Tacking (tack weld quality and location)
• Backing type and fit (if applicable)
P O
Welder identification system
• Fabricator or erector, as applicable, shall maintain a system by which a welder who has welded a joint or member…
This is the start of the file's text. The full file is on GovTribe.