Att. 9 - Set 7 of 8 Final Drawings By Building 590 22 700.pdf
PDF 39 MB Posted
- Attached to
- Y1DA--590-22-700 | Construct EHRM Infrastructure Upgrade | Hampton, VA | Federal contract opportunity
- Solicitation number
- 36C77626R0041
About this file
This document is a set of final construction drawings (100% Construction Documents) for infrastructure upgrades at Hampton VA Medical Center in Hampton, Virginia, dated July 18, 2025, under project number 590-22-700 EHRM.
The drawings encompass electrical, mechanical, telecommunications, and architectural work across multiple buildings (113, 114, 116, 135, and 137). Key electrical work includes upgrades to distribution panels, transformers, automatic transfer switches (ATS), and power distribution systems serving various clinical and support spaces. Telecommunications infrastructure includes replacement of Category 6 cabling with Category 6A cabling, installation of new fiber optic backbone cables (24-strand OS2 fiber), telecommunications rooms (TR) with new channel racks and distribution cabinets, and data outlet upgrades throughout the facilities. Mechanical systems include installation of VRF/VRV cooling units, hydronic piping modifications, sprinkler system adjustments, and HVAC equipment relocation. The project involves extensive renovation of multiple rooms and telecommunications closets, with phasing plans to coordinate work around occupied clinical spaces, including ICRA (Infection Control Risk Assessment) barriers and temporary power provisions. Construction details address fire ratings, cable tray installation, conduit sizing, equipment specifications, and coordination requirements between trades. The drawings include one-line diagrams, panelboard schedules, enlarged floor plans, and equipment load schedules to guide contractor installation and modifications to existing building systems.
View the file
Other files for this federal contract opportunity
Show all 32
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A V KW WH
PANEL
PANEL
PANEL PANEL
PANEL
PANEL
PANEL PANEL PANEL PANEL
PANEL
PANEL PANELPANEL
PANEL
PANELPANEL
G
PANEL
FEEDER
NO.
FEEDER SCHEDULE
FEEDER AND CONDUIT SIZE
NOTES: ALL CALCULATIONS ARE BASED ON COPPER CONDUCTORS.
EQ-H
480Y/277V
225A BUS
200A MCB
RM. BE1
EQ-L1
208Y/120V
100A BUS
100A MCB
RM. BE1
LS-H1
480Y/277V
100A BUS
100A MCB
RM. BE1
70A, 5KV-3P3W
400A-3P4W
100A-3P4W
175A-3P3W
208Y/120V
480V
30 kVA
LP
480Y/277V
100A BUS
100A MCB
RM. BE1
LS-L
208Y/120V
100A BUS
60A MCB
RM. BE1
MP-H
480Y/277V
225A BUS
200A MCB
RM. BE1
208Y/120V
480V
112.5 kVA
RP1
208Y/120V
100A BUS
100A MCB
RM. BE1
RP2
208Y/120V
100A BUS
100A MCB
RM. AG06
RP3
208Y/120V
100A BUS
100A MCB
RM. AG06
RP4
208Y/120V
200A BUS
150A MCB
RM. A163
208Y/120V
480V
15 kVA
CR-H
480Y/277V
225A BUS
200A MCB
RM. BE1
CR-L1
208Y/120V
400A BUS
300A MCB
RM. BE1
208Y/120V
480V
75 kVA
200A-3P4W
400A-3P4W
50A-3P3W
70A-3P3W
225A-3P4W
125A-3P4W
MP-L1
208Y/120V
100A BUS
100A MCB
RM. BE1
208Y/120V
480V
30 kVA
MP-L2
208Y/120V
100A BUS
60A MCB
RM. A163
LS-H2
480Y/277V
100A BUS
60A MCB
RM. AG06
EQ-L2
208Y/120V
100A BUS
60A MCB
RM. AG06
CR-L2
208Y/120V
225A BUS
200A MCB
RM. AG06
1160A-3P4W
500 kVA Z=4.9% 5 kV 480Y/277V
O U
T S
ID
E
P A
D M
O U
N T
E D
T R
A N
S F
O R
M E
R
150A-3P4W
25A-3P3W
125A-3P3W
300A-3P4W
60A-3P4W
350A-3P4W
CR-L3
208Y/120V
100A BUS
60A MCB
RM. AG06
INCOMING PRIMARY
4160V SERVICE FROM
CAMPUS MV LOOP
SERVES
BUILDINGS
33, 114 & 115
200AT
3P
200AT
3P
100AT
3P
AT
3P
PANEL 'MDP' - SERVICE RATED
600A BUS, 600A MCB, 480Y/277V, 3∅, 4W, 42 POLE
100AT
3P
200AT
3P
200AT
3P
AT
3P
PANEL 'EMDP''
400A BUS, 350A MCB, 480Y/277V, 3∅, 4W, 30 POLE BLDG. 113 - RM. BE1
100AT
3P
225AT
3P
175AT
3P
400A 3P
100A 3P
100A 3P
100A 3P
150A 3P
3P SPACE
(QTY=3)
30AT
3P
(2) SPARES
3P SPACE
(QTY=2)
30AT
3P
(2) SPARES
3 44 3 9 5
3 3 3 12
13 14 7
43 4
AT
3P
AT
3P
PANEL 'GEN-DP'
1200A BUS, MLO, 480Y/277V,
3∅, 4W, 18 POLE, NEMA 3R
BLDG 171
(12)225
AF
SPACE
3 3
T-MP
RM. BE1
T-RP
RM. BE1
T-EQ
RM. BE1
T-CR
RM. BE1
T-LS
RM. BE1
4 1111
GEN-110B
825kVA/660kW
480V, 3∅, 4W
STANDBY
GENERATOR
BLDG. 171
1000AT
3P
GENERATOR
CONTROL
PANEL
UNDERGROUND
DUCTBANK TO
BUILDING 114
(2) 4#350 + 1#1/0G. IN 4"C.
(3) 4#600 +
1#3/0 IN
4"C.
PANEL 'RDP'
400A BUS, 400A MCB,
208/120V, 3∅, 4W, 24POLE
BLDG. 113 - RM. BE1
BLDG. 113 - RM. BE1
ATS 'LS'
100A
3∅, 4W, 4P
500 KVA
4160V 480Y/277V Z = 5% 150° C 60 kV BIL
70A
ATS 'CR'
200A
3∅, 4W, 4P
ATS 'EQ'
200A
3∅, 4W, 4P E N
L
3-#2, 5KV + 1#8G IN 4" UNDERGROUND CONDUIT.
4-#600 + 1#1/0G IN 4"C IN NEW 2X1 DUCTBANK
4-#1 + 1#8G IN 2"C
3-#2/0 + 1#6G IN 2"C
4-#3/0 + 1#6G IN 2"C
4-#600 + 1#1/0G IN 4"C
3-#6 + 1#10G IN 1"C
3-#4 + 1#8G IN 1-1/4"C
4-#4/0 + 1#4G IN 2-1/2"C
4-#3/0 + 1#6G IN 2-1/2"C
4-#4 + 1#10G IN 1-1/4"C
4-#1/0 + 1#6G IN 2"C
3-#10 + 1#10G IN 3/4"C
3-#1 + 1#6G IN 1-1/2"C
4-#350 + 1#4G IN 3"C
4-#4 + 1#8G IN 1-1/4"C
4-#500 + 1#3G IN 4"C
PANELBOARD
113-BG10A
100A 208/120V
3PH
113-P-01
60A/3P
O U
T S
ID
E
P A
D M
O U
N T
E D
T R
A N
S F
O R
M E
R
113-P-02A
TRANSFORMER
"TX-113-DP-TRB"
30KVA
PRI: 480V
SEC:208/120V
K-13 RATED
1 REFERENCE ASSOCIATED PANEL SCHEDUELS FOR ADDITIONAL INFORMATION.
UTILIZE EXISTING PANELBOARD SPACE TO PROVIDE CIRCUIT BREAKER AND
FEEDER AS INDICATED.
PANELBOARD
113-AG15SA
100A 208/120V
3PH
113-P-03
113-P-02B
125A 3P
30A 3P
113-P-05
NEMA L21-30R
30A, 208V
LOCKING
TR AG15S
SIDE B
30A 3P
113-P-04
30A 3P
SPDDPM
PANELBOARD ''113-
DP-TRB''
208/120V 125A
3PH, 4W
1 1
P
S
NEMA L21-30R
30A, 208V
LOCKING
TR BG-10
SIDE B
SPDSPD
E N
L
E N
L
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/2
/2
:4
:4
A
M
B
IM
/5
-2
-7
V A
H a m p to n E
H R
M /V
A H
A M
P T
O N
L e g e n d s
G e n e ra l N o te s
D ia g ra m s a n d
D e ta ils .r v t
113EP601
BLDG 113 - ONE-LINE DIAGRAM
JPB/WNM BCL/GPB
100% CONSTRUCTION
DOCUMENTS
07/18/2025
590-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
GENERAL NOTES
- NTS
1 BLDG 113 - ONE-LINE DIAGRAM
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY DISCREPANCIES
FOUND SHALL BE REPORTED TO THE ENGINEER.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS, TEMPORARY POWER PLANS,
AND PHASING PLANS FOR VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED FOR REVIEW 30-DAYS PRIOR
TO IMPLEMENTATION.
3. SHORT CIRCUIT CALCULATIONS BASED ON VA PROVIDED AS-BUILTS.
4. REFERENCE SHEET(S) "113E-701" THROUGH "113E-702" FOR ELECTRICAL EQUIPMENT
LOAD SCHEDULES.
5. REFERENCE SHEET "113E-701" FOR ALL CONDUIT AND WIRING INFORMATION.
6. COMPLETE BUILDING ONE-LINE PROVIDED FOR INFORMATIONAL PURPOSES AND AS-
BUILDING PURPOSES.
KEY NOTESKEY NOTES
METERING NOTESPOWER DATA RETRIEVAL POINT NOTES
POWER DATA RETRIEVAL POINT: EXISTING PANELBOARD ''CR-L1'' MAIN HAS
BEEN METERED. REFERENCE EQUIPMENT LOAD SCHEDULE VIA BUILDING 113 700-
SERIES SCHEDULE SHEET FOR ADDITIONAL INFORMATION.
POWER DATA RETRIEVAL POINT: EXISTING PANELBOARD ''CR-H'' MAIN HAS
BEEN METERED. REFERENCE EQUIPMENT LOAD SCHEDULE VIA BUILDING 113 700-
SERIES SCHEDULE SHEET FOR ADDITIONAL INFORMATION.
POWER DATA RETRIEVAL POINT: EXISTING DISTRIBUTION PANELBOARD "MDP" PEAK
DEMAND DETERMINED FROM GENERATOR LOAD TEST REPORT DATA.
REFERENCE EQUIPMENT LOAD SCHEDULE VIA BUILDING 113 700-SERIES
SCHEDULE SHEET FOR ADDITIONAL INFORMATION.
Revisions: Date:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/2
/2
:4
:1
A
M
B
IM
/5
-2
-7
V A
H a m p to n E
H R
M /V
A H
A M
P T
O N
L e g e n d s
G e n e ra l N o te s
D ia g ra m s a n d
D e ta ils .r v t
113E-701
BLDG 113 - ELECTRICAL PANELBOARD AND
CONDUIT AND WIRE SCHEDULES
JPB/WNM BCL/GPB
100% CONSTRUCTION
DOCUMENTS
07/18/2025
590-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE IN
ANY AND ALL CHANGES; ALL REVISED CIRCUIT DIRECTORIES SHALL BE
TYPEWRITTEN.
2. FOR ALL "REVISED" PANEL SCHEDULES REFERENCE "METERING AND LOAD
INFORMATION SCHEDULE" LOCATED ON SHEET E-703 FOR OVERALL PANEL
LOAD. "REVISED" PANEL SCHEDULES ON THIS SHEET ARE SHOWN FOR ADDED
BRANCH CIRCUIT SIZING ONLY.
3. ALL DIGITAL POWER METERS (DPM) AND SURGE PROTECTIVE DEVICES (SPD)
ARE INTEGRAL TO ELECTRICAL DISTRIBUTION EQUIPMENT, UNLESS
OTHERWISE NOTED.
GENERAL NOTES
KEY NOTES
UTILIZE EXISTING SPACE TO PROVIDE CIRCUIT BREAKER AS INDICATED.
EXISTING PANELBOARD OR SWITCHBOARD TO BE MODIFIED AS INDICATED BY
BLACK TEXT. ALL GRAY TEXT SHOWS AS-BUILT EXISTING CONDITIONS.
SCHEDULE IS PROVIDED TO SHOW CIRCUITING INFORMATION ONLY.
REFERENCE ASSOCIATED LOAD SCHEDULE FOR OVERALL PANEL LOAD.
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/2
/2
:4
:3
A
M
B
IM
/5
-2
-7
V A
H a m p to n E
H R
M /V
A H
A M
P T
O N
L e g e n d s
G e n e ra l N o te s
D ia g ra m s a n d
D e ta ils .r v t
113E-702
BLDG 113 - ELECTRICAL PANELBOARD
SCHEDULES
JPB/WNM BCL/GPB
100% CONSTRUCTION
DOCUMENTS
07/18/2025
590-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE IN
ANY AND ALL CHANGES; ALL REVISED CIRCUIT DIRECTORIES SHALL BE
TYPEWRITTEN.
2. FOR ALL "REVISED" PANEL SCHEDULES REFERENCE "METERING AND LOAD
INFORMATION SCHEDULE" LOCATED ON SHEET E-703 FOR OVERALL PANEL
LOAD. "REVISED" PANEL SCHEDULES ON THIS SHEET ARE SHOWN FOR ADDED
BRANCH CIRCUIT SIZING ONLY.
3. ALL DIGITAL POWER METERS (DPM) AND SURGE PROTECTIVE DEVICES (SPD)
ARE INTEGRAL TO ELECTRICAL DISTRIBUTION EQUIPMENT, UNLESS
OTHERWISE NOTED.
GENERAL NOTES
KEY NOTES
UTILIZE EXISTING SPACE TO PROVIDE CIRCUIT BREAKER AS INDICATED.
EXISTING PANELBOARD OR SWITCHBOARD TO BE MODIFIED AS INDICATED BY
BLACK TEXT. ALL GRAY TEXT SHOWS AS-BUILT EXISTING CONDITIONS.
SCHEDULE IS PROVIDED TO SHOW CIRCUITING INFORMATION ONLY.
REFERENCE ASSOCIATED LOAD SCHEDULE FOR OVERALL PANEL LOAD.
2 3
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP WAPWAP
WAP
WAP
W A
P
WAP
WAP
WAPWAP
AREA SHOWN
A B C D E F G H
A1 B1
1a
1b
1c
1d
113TN401b
113TN401b
113TN401b
113TN401b
113TN401a
113TN401a
113TN401a
113TN401a
DD4
DD4
DD2
DD4
DD4
DD4
DD4
DD4
DD4
DD4
DD4
DD4
DD4
DD4
DD4 DD4
DD4
DD4
DD4 DD4
N2N2
DD4
DD4
N2
DD4 DD4 DD4 DD4 DD4
DD4 DD1
DD2
DD4
DD4
DD4
DD4DD4DD4DD4DD4DD4
DD4
DD4
DD4
DD4
DD4
DD4
N2N2N2N2N2N2N2N2
DD4
DD4
DD4
DD4
DD4
DD4
DD2DD4
DD4
DD4 DD4
DD4
DD4
DD4
N2
DD4
DD4 DD4 DD4
DD4
DD4 DD4
DD4
DD4
DD4
DD4
DD4
DD4
DD4
DD4DD4
DD4DD4
DD4
DD4
DD4 DD4
DD4
DD4 DD4
DD2
DD2
DD4
N2N2
DD2
DD2
DD2
DD2
DD2
DD2
DD4
DD4
DD4
N2
DD4
DD4
DD2DD2
DD2
DD2
DD2
DD2 DD2
DD2
DD2
DD2
DATA OUTLETS AND DEVICES IN THIS
AREA SHALL BE SERVED FROM
TELECOMMUNICATIONS ROOM AG15S.
DATA OUTLETS AND DEVICES IN THIS
AREA SHALL BE SERVED FROM
TELECOMMUNICATIONS ROOM BG10.
STAFF LOUNGE
AG40
PACT TEAM ROOM
AG41
CONFERENCE
AG38
CHIEF DIALYSIS CENTER
AG33
CHIEF NURSE
AG31
NURSE PRACTITIONER
AG29
TR
AG15S
TOILET
AG27STAIR
SGA2
EQUIPMENT STORAGE
AG15C
CLEAN SUPPLY/
STERILE SUPPLY
AG15D
SOILED UTILITY
AG15E
MED PREP
AG15F
HOME TRAINING
AG17
TOILET
AG19A
HOME TRAINING
AG19
EXAM
AG21
EXAM
AG25
RENAL DIALYSIS
ISOLATION ROOM
AG15Q
TOILET
AG15Q.1
VESTIBULE
AV-1
BREAK DOWN
AG13
MECHANICAL
AM1EQUIP PROCESSING
CLEAN STORAGE
AG12
EQUIPMENT MAINTENANCE
AG10A
TOILET
AG07
TOILET
AG05
RECEPTION
AG04
HAC
AG22
ELEC
AG06
TOILET/SHOWER
AG24
EXAM/PROCEDURE
AG32
WAITING
AG01.1
ELV 1
ELV2
LOBBY
AG01
STAIR
SGA1
WATER TREATMENT ROOM
AG10C
CORRIDOR
AG10
CHAIR STATION
AG15.6
CHAIR STATION
AG15.5
CHAIR STATION
AG15.4
CHAIR STATION
AG15.3
CHAIR STATION
AG15.2
CHAIR STATION
AG15.28
CHAIR STATION
AG15.27
CHAIR STATION
AG15.26
CHAIR STATION
AG15.25
CHAIR STATION
AG15.24
CHAIR STATION
AG15.23
CHAIR STATION
AG15.22
CHAIR STATION
AG15.21
CHAIR STATION
AG15.20
CHAIR STATION
AG15.19
CHAIR STATION
AG15.18
CHAIR STATION
AG15.17
TOILET
AG15P.1
RENAL DIALYSIS
ISOLATION ROOM CHAIR 16
AG15P
CHAIR STATION
AG15.15
CHAIR STATION
AG15.14
CHAIR STATION
AG15.13
CHAIR STATION
AG15.12
CHAIR STATION
AG15.11
CHAIR STATION
AG15.10
CHAIR STATION
AG15.9
CHAIR STATION
AG15.8
RENAL DIALYSIS
ISOLATION ROOM CHAIR 9
AG15M
TOILET
AG15M.1
NURSE STATION
AG16
VESTIBULE
BV-1
OFFICE
BG-05
TLT
BG07
BG-11
OFFICE
BG-15
CHAPLAIN
BG19
STORAGE
BG-17
GROUP THERAPY
BG-21
GROUP THERAPY
BG-23A
GROUP THERAPY
BG-23B
CORRIDOR
CGB-2
SOCIAL WORKER
BG-16
NOURISHMENT
BG-12
TR
BG-10
COUNSELING
BG-08
COUNSELING
BG-06
COUNSELING
BG-04
COUNSELING
BG-02
CORRIDOR
CGB-1
ELECTRICAL
BE-1
SPRINKLER
BM1
TLT
BG09
RESOURCE/PROG ASSIST
BG01
TYP.
TYP.
ALERTUS DEVICE5
ALERTUS DEVICE
DDC CONTROL PANEL
N2
N2
N2
N2
N2
N2
N2
N2
N2 N2
N2
N2 N2
N2 N2
N2 N2
N2 N2
N2N2
N2
N2
N2
N2 N2
DD4
DD4DD4
N2 N2
DD4 DD4
N2 N2
N2
N2
N2
N2
DD4
DD4
N2
N2 N2
N2
N2
N2
N2
N2
N2 N2 N2
N2
N2
N2
N2
N2 N2
N2
N2 N2
N2 N2
N2
N2
N2 N2
N2 N2
N2 N2
N2
N2
N2N2
N2
N2N2
N2
N2
N2
N2
N2
N2
N2 N2
N2N2 DD4 DD4 DD4 DD4 DD4 DD4 DD4 DD4
N2 N2
N2 N2
N2
N2
N2
N2
N2
N2
N2 N2 N2 N2 N2 N2
N2N2N2N2N2
N2
N2
N2 N2
N2
N2
2 22
2 2
DD2
DD2 DD2 DD2
N2
N2 N2 N2
BLDG 113
Y
D# N#
Y
D# N#
OUTLET, DATA OR VOIP TELEPHONE. THE FOLLOWING INFORMATION
INDICATED ON THE SYMBOL:
"#" = QUANTITY OF OUTLET PORTS.
"D" = EXISTING CABLES TO BE DEMOLISHED.
"N" = REPLACEMENT CABLES TO BE PROVIDED.
REFERENCE SHEET TNG002 FOR ADDITIONAL INFORMATION.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/0 /2
:1
:4 a m
B
IM
/5
-2
-7
V A
H a m p to n E
H R
M /E
E
B L D
G
.r v t
113TN101
BLDG 113 - LEVEL 01 - TELECOMMUNICATIONS
PLAN
KG BCL/GPB
100% CONSTRUCTION
DOCUMENTS
07/18/2025
590-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
- 1" = 10'-0"
1 BLDG 113 - LEVEL 01 - TELECOMMUNICATIONS PLAN 0 10' 20'
PROJECT
NORTH
Revisions: Date:
KEY PLAN
KEY NOTES
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS
REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE
DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE
NOTED.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO ASSOCIATED TR.
6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO
REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,
MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE
INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY
FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
7. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 1" CONDUIT FROM NEW BACKBOX TO
ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO
TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM
OUTLET TO TR AS REQUIRED.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES.
9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION
OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL
IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;
DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.
11. THE CONTRACTOR SHALL BID AND INSTALL CAT6A CABLE WITH AN OD NOT GREATER
THAN 0.250 INCH (6.35mm) (4) CAT6A CABLES WITH AN 0.250 INCH (6.35mm) OD OR
SMALLER CAN BE INSTALLED IN A ¾” CONDUIT SUPPORTING A 40% FILL RATIO.
12. CONTRACTOR TO BID AN ADDITIONAL 10% OF THE TOTAL NUMBER OF WAO's PER
FLOOR. A WAO IS DEFINED AS TWO CAT6A OUTLETS.
13. (5) DDC CONTROLLERS WILL BE FED WITH (1) CAT6A CABLE EACH FROM TRBG10.
CONTRACTOR TO COORDINATE LOCATION OF DDC CONTROLLER WITH THE STATION.
TRUE
NORTH
GENERAL NOTES
PROVIDE TELECOMMUNICATIONS OUTLET WITH PORT QUANTITY SHOWN TO REPLACE
EXISTING TELECOMMUNICATIONS OUTLET; EXISTING OUTLET CONDUIT SHALL REMAIN
AND BE UTILIZED TO FEED NEW CABLING; REFERENCE SHEET DETAIL '1' ON SHEET
TN501 AND THE GENERAL NOTES ON THIS SHEET FOR ADDITIONAL INFORMATION.
COORDINATE WITH VA FOR EXACT OUTLET PLACEMENT.
EXISTING WIRELESS ACCESS POINT TO BE RE-FED WITH (2) CAT6A CABLES.
PROVIDE CONDUIT (4", MINIMUM) WITH APPROPRIATE FIRE-PROOFING AND CAULKING
AS REQUIRED TO EXTEND FROM ROOM BG08 CABLE TRAY TO ROOM AG15.17 CABLE
TRAY. CONDUIT PROVIDED TO SERVE HORIZONTAL CABLING SERVING WAOs FROM TR
AS INDICATED ON PLANS.
PROVIDE CABLE TRAY AS INDICATED. REFERENCE DETAIL "6" ON SHEET TN501 AND
TELECOMMUNICATIONS WAO AND CABLE TRAY SCHEDULE ON SHEET TN701. WHERE
WALL EXTENDS TO CEILING, CABLE TRAY SHALL STOP AND TRANSITION TO
HORIZONTAL FIRE STOP SLEEVES [(2) 4", MINIMUM]. WHERE EXISTING CABLE TRAY IS
PRESENT, IT SHALL BE DEMOLISHED AND REPLACED AS INDICATED. EXISTING SLEEVES
MAY BE UTILIZED IF SUITABLE FOR REUSE, BUT NOT IN PLACE OF FIRE STOP SLEEVES
AS MENTIONED ABOVE. WHERE CLEARANCES OR OBSTRUCTIONS DO NOT PERMIT
INSTALLATION OF CABLE TRAY, PROVIDE J-HOOKS AS REQUIRED FOR CABLE
DISTRIBUTION.
EXISTING ALERTUS DEVICE TO BE RECABLED WITH (1) CAT6A CABLE AS REQUIRED.
COORDINATE WITH VA FOR EXACT LOCATION.
EXISTING DDC CONTROL PANEL TO BE RECABLED WITH (1) CAT6A CABLE AS REQUIRED.
COORDINATE WITH VA FOR EXACT LOCATION.
180°
W
360°C
D
WS
X
X
W
AREA SHOWN
AG15S
A B
EXISTING BONDING
BUSBAR
DISC.
DATA RACK, TYP.
TELECOMMUNICATIONS
ENCLOSURE
CARD READER
ACCESS CONTROL
PANEL
TYP.
A B
TR
AG15S
89 SF
DISC. ACCESS CONTROL
PANEL
SECONDARY
BONDING BUSBAR
TN502
113-AG15SA
C
DATA RACK,
TYP.
TN503
113-AC-03-AG15S
113-AC-04-AG15S
A B
TYP.
A B
TR
AG15S
89 SF
TYP.
TN501
TYP.
TN501
DATA RACK,
TYP.
97 SF
IT
AG15S
97 SF
IT
AG15S
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/0 /2
:1
:5 a m
B
IM
/5
-2
-7
V A
H a m p to n E
H R
M /E
E
B L D
G
.r v t
113TN401a
BLDG 113 - LEVEL 01 - ENLARGED
TELECOMMUNICATIONS PLANS
KG BCL/GPB
100% CONSTRUCTION
DOCUMENTS
07/18/2025
590-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
KEY NOTES
GENERAL NOTES
1/2" = 1'-0"113TN101
1 RM AG15S - DEMOLITION FLOOR PLAN
1/2" = 1'-0"113TN101
2 RM AG15S - TELECOMMUNICATIONS PLAN
PROJECT
NORTH
1'0 2' 4'
1/2" = 1'-0"113TN101
3 RM AG15S - DEMOLITION OVERHEAD PLAN
1/2" = 1'-0"113TN101
4 RM AG15S - OVERHEAD PLAN
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
Revisions: Date:
EXISTING DATA RACK TO BE DECOMMISIONED BY VA. CONTRACTOR SHALL
COORDINATE WITH VA AS REQUIRED.
EXISTING EQUIPMENT TO BE DEMOLISHED. ASSOCIATED RACEWAYS AND CABLING
SHALL BE DEMOLISHED BACK TO SOURCE.
EXISTING CABLE TRAY TO BE DEMOLISHED.
EXISTING HORIZONTAL CABLING SLEEVE TO BE PRESERVED. EXISTING FIBER OPTIC
AND/OR EXISTING HORIZONTAL CABLING RELATED TO EXISTING TR RACKS TO BE
DEMOLISHED.
PROVIDE RIGID CONDUIT SLEEVES WITH FIRE PROOFING AS REQUIRED. SIDE 'A' AND
SIDE 'B' SLEEVES SHALL BE SEPARATED BY AT LEAST 10-FT.
WIRE BASKET CABLE TRAY.
KEY PLAN
1. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO ASSOCIATED TR.
5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO
REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,
MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE
INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY
FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
6. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 1" CONDUIT FROM NEW BACKBOX TO
ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO
TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM
OUTLET TO TR AS REQUIRED.
7. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION OF
HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL IN
AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
8. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD
BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS
REQUIRED.
9. ANY LIVE SYSTEMS IN DEMO'D TR'S MUST REMAIN LIVE. CONTRACTOR TO
COORDINATE WITH THE STATION TO IDENTIFY SYSTEMS THAT ARE LIVE. IF SYSTEMS
ARE LIVE; INSTALL NEW CABLE FROM DEMO’D TR TO NEW TR. REFER TO DETAIL '3' ON
TN506.
10. RAIL KITS ARE PROVIDED BY THE GC FOR EQUIPMENT MOUNTED IN THE TR CHANNEL
RACKS.
11. LADDER RACK IN ALL TR'S WILL BE MOUNTED 6" OFF THE WALLS TO ACCOMMODATE
ELECTRICAL AND MECHNICAL EQUIPMENT.
360°
D
C
WW
X
W
W
X
AREA SHOWN
TELECOMMUNICATIONS
PANELS
FIBER OPTIC PANEL
DATA RACK,
TYP.
TELEPHONE
TERMINAL
BOARD
BONDING
BUSBAR
TR
BG-10
107 SF
FIBER OPTIC PANEL
TELEPHONE
TERMINAL
BOARD
TN502
TELECOMMUNICATIONS
PANELS
C
SECONDARY
BONDING
BUSBAR
113-BG10A
TN503
ACCESS CONTROL PANEL8
DATA RACK,
TYP.
113-DP-TRB
113-AC-01-BG10
113-AC-02-BG10
TYP.
TR
BG-10
107 SF
TYP.
TN501
TYP.
TN501
DATA RACK,
TYP.
BG10
75 SF
IT
BG10
75 SF
IT
BG10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/0 /2
:1
:5 a m
B
IM
/5
-2
-7
V A
H a m p to n E
H R
M /E
E
B L D
G
.r v t
113TN401b
BLDG 113 - LEVEL 01 - ENLARGED
TELECOMMUNICATIONS PLANS
KG BCL/GPB
100% CONSTRUCTION
DOCUMENTS
07/18/2025
590-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
KEY NOTES
KEY PLAN
GENERAL NOTES
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS
REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE
DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE
NOTED.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS
TO EXTEND TO ASSOCIATED TR AS REQUIRED.
6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO
REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,
MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE
INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY
FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
7. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 1" CONDUIT FROM NEW BACKBOX TO
ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO
TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM
OUTLET TO TR AS REQUIRED.
8. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION
OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL
IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
9. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD
BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS
REQUIRED.
10. ANY LIVE SYSTEMS IN DEMO'D TR'S MUST REMAIN LIVE. CONTRACTOR TO
COORDINATE WITH THE STATION TO IDENTIFY SYSTEMS THAT ARE LIVE. IF SYSTEMS
ARE LIVE; INSTALL NEW CABLE FROM DEMO’D TR TO NEW TR. REFER TO DETAIL '3' ON
TN506.
11. LADDER RACK IN ALL TR'S WILL BE MOUNTED 6" OFF THE WALLS TO ACCOMMODATE
ELECTRICAL AND MECHNICAL EQUIPMENT.
PROJECT
NORTH
1/2" = 1'-0"113TN101
1 RM BG10 - DEMOLITION FLOOR PLAN
1/2" = 1'-0"113TN101
2 RM BG10 - TELECOMMUNICATIONS PLAN
1/2" = 1'-0"113TN101
3 RM BG10 - DEMOLITION OVERHEAD PLAN
1/2" = 1'-0"113TN101
4 RM BG10 - OVERHEAD PLAN
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
Revisions: Date:
EXISTING DATA RACK TO BE DECOMMISIONED BY VA. CONTRACTOR SHALL
COORDINATE WITH VA AS REQUIRED.
PROVIDE RIGID CONDUIT SLEEVES WITH FIRE PROOFING AS REQUIRED. SIDE 'A' AND
SIDE 'B' SLEEVES SHALL BE SEPARATED BY AT LEAST 10-FT.
WIRE BASKET CABLE TRAY.
EXISTING CABLE TRAY TO BE DEMOLISHED.
EXISTING EQUIPMENT TO BE RELOCATED AS SHOWN IN DETAIL '2' ON THIS SHEET.
RELOCATED EQUIPMENT. EXTEND CONDUIT AND WIRE AS REQUIRED.
EXISTING HORIZONTAL CABLING SLEEVE TO BE PRESERVED. EXISTING FIBER OPTIC
AND/OR EXISTING HORIZONTAL CABLING RELATED TO EXISTING TR RACKS TO BE
DEMOLISHED.
PROVIDE (2)-DOOR ACCESS CONTROL PANEL TO SERVE ALL PACS DOOR SECURITY
EQUIPMENT FOR THIS TR ROOM. PROVIDE ALL REQUIRED CONNECTIONS,
PROGRAMMING, POWER SUPPLIES, AND COMPONENTS TO PROVIDE A COMPLETE AND
FULLY FUNCTIONAL SYSTEM. REFERENCE SPECIFICATION "28 13 00 - PHYSICAL ACCESS
CONTROL SYSTEM" FOR ADDITIONAL INFORMATION.
A B C D E F G H
B1A1
1a
1b
1c
1d
STAFF
LOUNGE
AG40
PACT TEAM
ROOM
AG41
CONFERENCE
AG38
CHIEF
DIALYSIS
CENTER
AG33
CHIEF NURSE
AG31
NURSE
PRACTITIONER
AG29
TR
AG15S
TOILET
AG27
STAIR
SGA2
EQUIPMENT
STORAGE
AG15C
CLEAN
SUPPLY/
STERILE
SUPPLY
AG15D
SOILED
UTILITY
AG15E
MED PREP
AG15F
HOME
TRAINING
AG17
TOILET
AG19A
HOME
TRAINING
AG19
EXAM
AG21
EXAM
AG25
RENAL
DIALYSIS
ISOLATION
ROOM
AG15Q
TOILET
AG15Q.1
VESTIBULE
AV-1
BREAK
DOWN
AG13
MECHANICAL
AM1
EQUIP
PROCESSING
CLEAN
STORAGE
AG12
EQUIPMENT
MAINTENANCE
AG10A
TOILET
AG07
TOILET
AG05
RECEPTION
AG04
HAC
AG22
ELEC
AG06
TOILET/SHOWER
AG24
EXAM/PROCEDURE
AG32
WAITING
AG01.1
ELV 1
ELV2
LOBBY
AG01
STAIR
SGA1
WATER
TREATMENT
ROOM
AG10C
CORRIDOR
AG10
CHAIR
STATION
AG15.6
CHAIR
STATION
AG15.5
CHAIR
STATION
AG15.4
CHAIR
STATION
AG15.3
CHAIR
STATION
AG15.2
CHAIR
STATION
AG15.28
CHAIR
STATION
AG15.27
CHAIR
STATION
AG15.26
CHAIR
STATION
AG15.25
CHAIR
STATION
AG15.24
CHAIR
STATION
AG15.23
CHAIR
STATION
AG15.22
CHAIR
STATION
AG15.21
CHAIR
STATION
AG15.20
CHAIR
STATION
AG15.19
CHAIR
STATION
AG15.18
CHAIR
STATION
AG15.17
TOILET
AG15P.1
RENAL
DIALYSIS
ISOLATION
ROOM CHAIR
AG15P CHAIR
STATION
AG15.15
CHAIR
STATION
AG15.14
CHAIR
STATION
AG15.13
CHAIR
STATION
AG15.12
CHAIR
STATION
AG15.11
CHAIR
STATION
AG15.10
CHAIR
STATION
AG15.9
CHAIR
STATION
AG15.8
RENAL
DIALYSIS
ISOLATION
ROOM CHAIR
AG15M
TOILET
AG15M.1
NURSE
STATION
AG16
VESTIBULE
BV-1
OFFICE
BG-05
TLT
BG07
BG-11
OFFICE
BG-15
CHAPLAIN
BG19
STORAGE
BG-17
GROUP
THERAPY
BG-21
GROUP
THERAPY
BG-23A
GROUP
THERAPY
BG-23B
CORRIDOR
CGB-2
SOCIAL
WORKER
BG-16
NOURISHMENT
BG-12
TR
BG-10
COUNSELING
BG-08
COUNSELING
BG-06
COUNSELING
BG-04
COUNSELING
BG-02
CORRIDOR
CGB-1
ELECTRICAL
BE-1
SPRINKLER
BM1
TLT
BG09
RESOURCE/PROG
ASSIST
BG01
EXISTING
TELECOM
ROOM
TR #BG10
113T-400
113T-400
TR #AG15S
REFER TO TS001 FOR
CONTINUATION
HH49
B
B
A
A
B
REFER TO TS001
FOR CONTINUATION
HH50
A
PW-PB-1
PW-PB-1
PW-PB-1
(1) 4"C - (2) 24-STRAND OS2
FIBER CABLES (A)
(1) 4"C - (1) 24-STRAND OS2 FIBER CABLE (A)
(1) 4"C - (1) 24-STRAND OS2 FIBER CABLE (B)
(1) 4"C - (2) 24-STRAND
OS2 FIBER CABLES (B)
113T-400
113T-400
(1) 4"C - (1) 24-STRAND
OS2 FIBER CABLE
(1) 4"C - (1) 24-STRAND
OS2 FIBER CABLE (A)
(1) 4"C - (1) 24-STRAND
OS2 FIBER CABLE (B)
(1) 4"C - (1) 24-STRAND
OS2 FIBER CABLE 9 (A)
(1) 4"C - (2) 24-STRAND OS2 FIBER
CABLES (A) AND (1) 4"C - SPARE
(1) 4"C - (2) 24-STRAND OS2 FIBER
CABLES (B) AND (1) 4"C - SPARE
(1) 4"C - (1) 24-STRAND
OS2 FIBER CABLE (A)
(1) 4"C - (1) 24 STRAND OS2 FIBER CABLE (A)
Eddie C. Willis, Jr.
REG. NO. 191562R
EXPIRES 12-31-2025
REGIS
TE
R
ED
CO
MMUNICA T IONS DISTRIBUT IO
N
DESIGNER
RCDD
225 W WASHINGTON STREET
SUITE 2700
CHICAGO, IL 60606
P: 312.294.0501 F: 312.294.0003 www.imegcorp.com
PROJECT #22010109.00
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/2
/2
:2
:2
A
M
B
IM
/5
-2
-7
V A
H a m p to n E
H R
M /5
-7
.B
.T R
.r v t
113T-101
BLDG.113 LEVEL 01 PLAN - TECHNOLOGY
EW IMEG
100% CONSTRUCTION
DOCUMENTS
05/09/2025
509-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
N O R
HT
1" = 10'-0"
LEVEL 01 PLAN - TECHNOLOGY
SHEET NOTES:
1. REFER TO SITE PLAN TS001 FOR ADDITIONAL
INFORMATION.
2. REFER TO T500 AND T501 FOR CAMPUS OPTICAL
FIBER CABLE RISER DIAGRAMS.
3. REFER TO 2/T400 FOR HANDHOLE DETAIL.
4. NEW BACKBONE OPTICAL FIBER CABLES SHALL BE
INDOOR/OUTDOOR TYPE.
5. ALL BACKBONE OPTICAL FIBER CABLE PATHWAYS SHALL
BE NEW. DO NOT RE-USE EXISTING BACKBONE CABLE
PATHWAYS FOR NEW BACKBONE CABLES.
6. TRANSITION PVC CONDUITS TO GRC IN CRAWL SPACE.
TRANSITION TO EMT CONDUITS AT INTERIOR OF
BUILDING. SEAL ALL PENETRATIONS TO MAINTAIN FIRE-
RATINGS OF WALL, CEILING AND FLOORS.
KEY NOTES:
1. PROVIDE PULLBOX ON EXTERIOR WALL AT HEIGHT
ABOVE FINSIHED CEILING. ROUTE CONDUIT UP WALL
INTO PULLBOX. PROVIDE PENETRATION THRU WALL AND
ROUTE CONDUIT THRU WALL ABOVE CORRIDOR
CEILINGS INTO TR #AG29 AND TR #BG10.
Revisions: Date: 507 of 713
FIBER
DISTRIBUTION
CABINET
FIBER
DISTRIBUTION
CABINET
TR
BG-10
B
A
WORK IN ROOM
BY OTHER
(1) 4"C - (1) 24-STRAND OS2 FIBER CABLE (A)
(1) 4"C - (1) 24-STRAND OS2 FIBER CABLE (B)
B
TR
AG15S
B
(1) 4"C - (1) 24-STRAND OS2 FIBER CABLE (B)
A
(1) 4"C - (1) 24-STRAND OS2 FIBER CABLE (A)
WORK IN ROOM
BY OTHER
TR
BG-10B
A
(1) 4"C - (1) 24-STRAND OS2 FIBER CABLE (A)
(1) 4"C - (1) 24-STRAND OS2 FIBER CABLE (B)
B
TR
AG15S
B
(1) 4"C - (1) 24-STRAND OS2 FIBER CABLE (B)
A
(1) 4"C - (1) 24-STRAND OS2 FIBER CABLE (A)
NOTES:
1. THIS RISER IS DIAGRAMMATIC AND MAY NOT SHOW
ACTUAL ROUTING OR QUANTITIES OF MATERIALS
SHOWN. THIS RISER IS SHOWN FOR CLARIFICATION OF
CONNECTION(S), LOCATIONS AND CABLE TYPE. ALL
INFORMATION OUTLETS ARE TYPICAL OF THE OUTLETS
IN THE AREA SHOWN. REFER TO FLOOR PLANS FOR
MORE SPECIFIC ROUTING INFORMATION. REFER TO
SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
2. REFER TO ELECTRICAL DRAWINGS FOR CHANNEL RACK
AND FIBER OPTIC DISTRIBUTION CABINET
SPECIFICATIONS
TELECOMMUNICATIONS ROOM TR #BG10
24 STRANDS OS2 FIBER OPTIC
CABLE, CORE "A" , TO BUILDING 135
24 STRANDS OS2 FIBER OPTIC
CABLE, CORE "B" , TO BUILDING 135
CHANNEL RACK
LEVEL 01
NOTES:
1. THIS RISER IS DIAGRAMMATIC AND MAY NOT SHOW
ACTUAL ROUTING OR QUANTITIES OF MATERIALS
SHOWN. THIS RISER IS SHOWN FOR CLARIFICATION
OF CONNECTION(S), LOCATIONS AND CABLE TYPE.
ALL INFORMATION OUTLETS ARE TYPICAL OF THE
OUTLETS IN THE AREA SHOWN. REFER TO FLOOR
PLANS FOR MORE SPECIFIC ROUTING INFORMATION.
REFER TO SPECIFICATIONS FOR ADDITIONAL
REQUIREMENTS.
2. REFER TO ELECTRICAL DRAWINGS FOR CHANNEL
RACK AND FIBER OPTIC DISTRIBUTION CABINET
SPECIFICATIONS
TELECOMMUNICATIONS ROOM TR #AG15S
24 STRANDS OS2 FIBER OPTIC
CABLE, CORE "A" , TO BUILDING 135
24 STRANDS OS2 FIBER OPTIC
CABLE, CORE "B" , TO BUILDING 135
CHANNEL RACK
LEVEL 01
Eddie C. Willis, Jr.
REG. NO. 191562R
EXPIRES 12-31-2025
REGIS
TE
R
ED
CO
MMUNICA T IONS DISTRIBUT IO
N
DESIGNER
RCDD
225 W WASHINGTON STREET
SUITE 2700
CHICAGO, IL 60606
P: 312.294.0501 F: 312.294.0003 www.imegcorp.com
PROJECT #22010109.00
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/2
/2
:2
:2
A
M
B
IM
/5
-2
-7
V A
H a m p to n E
H R
M /5
-7
.B
.T R
.r v t
113T-400
BLDG.113 TECHNOLOGY ENLARGED PLANS
EW IMEG
100% CONSTRUCTION
DOCUMENTS
05/09/2025
509-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
N O R
HT
1/2" = 1'-0"
TELECOM ROOM ENLARGEMENT TR #BG10
N O R
HT
1/2" = 1'-0"
TELECOM ROOM ENLARGEMENT TR #AG15S
NOTES:
1. REFER TO ELECTRICAL DRAWINGS FOR ROOM LAYOUT AND RACK ELEVATIONS.
2. ROUTE OPTICAL FIBER CABLE TO OVERHEAD CABLE TRAY AND TERMINATE IN FIBER DISTRIBUTION
CABINET.
KEY NOTES:
1. THROUGH WALL PENETRATION FOR BACKBONE CONDUIT. OPTICAL FIBER CABLE CONTINUES ON CABLE
TRAY TO RACKS.
N O R
HT
1/2" = 1'-0"
TELECOMROOM PATHWAY TR #BG10
NOTES:
1. REFER TO ELECTRICAL DRAWINGS FOR ROOM LAYOUT AND RACK ELEVATIONS.
2. ROUTE OPTICAL FIBER CABLE TO OVERHEAD CABLE TRAY AND TERMINATE IN FIBER DISTRIBUTION
CABINET.
KEY NOTES:
1. THROUGH WALL PENETRATION FOR BACKBONE CONDUIT. OPTICAL FIBER CABLE CONTINUES ON CABLE
TRAY TO RACKS.
N O R
HT
1/2" = 1'-0"
TELECOM ROOM PATHWAY TR #AG15S
NO SCALE
FIBER RISER DIAGRAM
5 NO SCALE
FIBER RISER DIAGRAM
Revisions: Date: 508 of 713
27B
27 31
27A
110A
110B
110D
13W
148-D
148-S
148-A
148T
146B
146A
138A 138136
137A
137C
137D
137B
137C
148B
173A
148-C
170 150
110C
143 167
G R
A V
E L
R O
A D
FRANKLIN BOULEVARD
FRANKLIN BOULEVARD
AVERILL AVENUE
AVERILL AVENUE
A M
E S
S T
R E
E T
HARRIS AVENUE
JONES CREEK
K N
O X S
T R
E E
T
T H
O M
P S
O N
S T
R E
E T
F R A N
K
LI
N B
O U
LE
V A R
D
MALLORY STREET
M A
R T
IN
L. K
IN
G
JR
. B O
U L E
V A R
D
M A R
TIN
L. K
IN
G
JR
. B O U
LE
V
AR
D
E M
A N
C
IP
A T
IO
N D
R
SHORE ROAD
H A R R
IS
A V E N
U E
HARRIS AVENUE
M c C
L E
L L A
N
S E
W E
LL
A
V E
N U
E
A V
E N
U E
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
A
B
C
E
G
H
J
K
L
M
N
P
Q
R
S
413 SF
CHAPEL/VIEWING
ROOM
AG13
129 SF
PHYSICIAN
OFFICE
AG15
66 SF
VESTIBULE
AG17
144 SF
STAIR
SGA-3
68 SF
ELEVATOR
EGA-1
286 SF
STORAGE
AG18
122 SF
CORRIDOR
CGA-A
276 SF
CORRIDOR
CGA-3
119 SF
DIETETICS
AG16
399 SF
KITCHEN
AG12
190 SF
STAIR
SGA-1
30 SF
ELECTRIC
AG03B
43 SF
TELECOM
AG03A
105 SF
LAUNDRY
AG03
55 SF
STAFF
TOILET
AG07A
34 SF
H.A.C.
AG05
258 SF
STAFF
AG07
98 SF
QUIET
ROOM/OFFICE
SGA-9
97 SF
QUIET ROOM/
OFFICE
AG08
56 SF
CORRIDOR
CGA-2
214 SF
NURSE
MANAGER
AG04
46 SF
TOILET
AG02
260 SF
CONFERENCE
ROOM
AG06
726 SF
CORRIDOR
CGB-2
541 SF
CORRIDOR
CGB-1
141 SF
NURSE
STATION
BG01A
525 SF
MAIN LOBBY
BG01
345 SF
VESTIBULE
BG03
95 SF
MEDICATION
BG12
99 SF
CAREGIVER
BG13B
279 SF
PATIENT
ROOM 6
BG13
PATIENT
TOILET
BG13A
PATIENT
TOILET
BG14A
229 SF
PATIENT
ROOM 7
BG14
236 SF
PATIENT
ROOM 8
BG15
227 SF
PATIENT
ROOM 9
BG16
94 SF
CAREGIVER
BG17B
94 SF
CAREGIVER
BG16B
252 SF
PATIENT 10
BG17
64 SF
PATIENT
TOILET
BG17A
59 SF
H.A.C.
BG18563 SF
CORRIDOR
CGB-3
PATIENT
TOILET
BG15A
PATIENT
TOILET
BG16A
52 SF
SOILED
BG04
41 SF
ELECTRIC
BG03A
99 SF
CAREGIVER
BG05B
279 SF
PATIENT 1
BG05
PATIENT
TOILET
BG05A
PATIENT
TOILET
BG06A
229 SF
PATIENT 2
BG06
236 SF
PATIENT 3
BG07
227 SF
PATIENT 4
BG08
PATIENT
TOILET
BG08A
PATIENT
TOILET
BG07A
94 SF
CAREGIVER
BG09B
94 SF
CAREGIVER
BG08B
261 SF
PATIENT 5
BG09
64 SF
PATIENT
TOILET
BG09A
59 SF
LINEN
STORAGE
BG010
368 SF
SOLARIUM
BG02
247 SF
CORRIDOR
CGA-1
SECTION 1A:
CONTRACTOR TO COORDINATE WITH VA
FOR ROOM CLOSURES AND AVAILABILITY TO
COMPLETE DATA WIRING IN THIS AREA.
918 SF
CORRIDOR
AG01
FE
FE
FE
FE
FE
FE
FE
FE
SECTION 1B:
CONTRACTOR TO COORDINATE WITH VA
FOR ROOM CLOSURES AND AVAILABILITY
TO COMPLETE DATA WIRING IN THIS AREA.
CHASE
CHASE
CHASE
C H
A S
E
CHASE
XX
TR
ICRA PHASING LINE
ICRA CLASS II
ICRA CLASS III
ICRA CLASS IV
FEC
FE
FIRE EXTINGUISHER CABINET
FIRE EXTINGUISHER
1 HR SMOKE BARRIER
1 HR FIRE BARRIER
BUILDING 114
KEY AREA SHOWN
TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/0 /2
:0
:4 a m
B
IM
/5
-2
-7
V A
H a m p to n
E H
R M
/B L D
G
.r v t
114AS101
BUILDING 114 - LEVEL 01 - PHASING PLAN
MA KB
100% CONSTRUCTION
DOCUMENTS
07/18/2025
590-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
1/8" = 1'-0"
BUILDING 114 - LEVEL 01 - PHASING PLAN
LEGEND
KEY PLAN
PROJECT
NORTH
0' 4' 8' 16'
Revisions: Date: 509 of 713
27B
27 31
27A
110A
110B
110D
13W
148-D
148-S
148-A
148T
146B
146A
138A 138136
137A
137C
137D
137B
137C
148B
173A
148-C
170 150
110C
143 167
G R
A V
E L
R O
A D
FRANKLIN BOULEVARD
FRANKLIN BOULEVARD
AVERILL AVENUE
AVERILL AVENUE
A M
E S
S T
R E
E T
HARRIS AVENUE
JONES CREEK
K N
O X S
T R
E E
T
T H
O M
P S
O N
S T
R E
E T
F R A N
K
LI
N B
O U
LE
V A R
D
MALLORY STREET
M A
R T
IN
L. K
IN
G
JR
. B O
U L E
V A R
D
M A R
TIN
L. K
IN
G
JR
. B O U
LE
V
AR
D
E M
A N
C
IP
A T
IO
N D
R
SHORE ROAD
H A R R
IS
A V E N
U E
HARRIS AVENUE
M c C
L E
L L A
N
S E
W E
LL
A
V E
N U
E
A V
E N
U E
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
A
B
C
E
G
H
J
K
266 SF
CORRIDOR
A102
104 SF
PRIVATE
ROOM
A102C
93 SF
LAUNDRY
ROOM
A102B
161 SF
PRIVATE ADA
ROOM
A102D
100 SF
PRIVATE
ROOM
A102E
99 SF
PRIVATE
ROOM
A102F
107 SF
PRIVATE
ROOM
A102G
92 SF
PRIVATE
ROOM
A102H
92 SF
PRIVATE
ROOM
A102J
32 SF
TOILET
SHOWER
A102J.1
32 SF
TOILET
SHOWER
A102G.1
32 SF
TOILET
SHOWER
A102E.1
33 SF
TOILET
SHOWER
A102E.2
32 SF
TOILET
SHOWER
A102H.1
32 SF
TOILET
SHOWER
A102F.1
52 SF
ADA TOILET
SHOWER
A102D.1
131 SF
PRIVATE
ROOM
A102A
33 SF
TOILET
SHOWER
A102A.1
394 SF
CONFERENCE
ROOM
A101
165 SF
KITCHEN
A104
127 SF
CONFERENCE
ROOM
A105
252 SF
OFFICE
A106
245 SF
OFFICE
A107
184 SF
OFFICE
A110
155 SF
OFFICE
A111
109 SF
WORK ROOM
A112
50 SF
MEN'S
TOILET
A113
58 SF
WOMEN'S
TOILET
A115
99 SF
JANITOR
STORAGE
A116
72 SF
ELEVATOR
AG09
151 SF
STAIR
S1A-3
514 SF
CORRIDOR
C1A-1
165 SF
STAIR
S1A-1
SECTION 1A:
CONTRACTOR TO COORDINATE WITH VA
FOR ROOM CLOSURES AND AVAILABILITY
TO COMPLETE DATA WIRING IN THIS AREA.FE
FE
LEFT SIDE
INGRESS/EGRESS 02
108 SF
TR
A114
PHASE 1:
CONTRACTOR TO COMPLETE THE WORK OF
THIS TR AND ASSOCIATED DATA DROPS.
COMPLETE ONE SECTION AT A TIME AS
DIRECTED TO COR.
DIAMOND LINE
D
IA
M O
N D
L
IN
E
RIGHT SIDE
INGRESS/EGRESS
LEFT SIDE
INGRESS/EGRESS
LEFT SIDE
INGRESS/EGRESS
EXISTING FE. REPLACE WITH NEW SEMI-RECESSED
FEC. REPLACE EXISTING FE WITH NEW CLEAN AGENT
EXTINGUISHER THAT MEETS OR EXCEEDS THE ABC
RATING AND SIZE OF EXISTING EXTINGUISHER. SEE
DETAIL 3/A-603.
CHASE
CHASE
CHASE C
H
A S
E
TR
ICRA PHASING LINE
ICRA CLASS II
ICRA CLASS III
ICRA CLASS IV
FEC
FE
FIRE EXTINGUISHER CABINET
FIRE EXTINGUISHER
1 HR SMOKE BARRIER
1 HR FIRE BARRIER
BUILDING 114
KEY AREA SHOWN
TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/0 /2
:0
:4 a m
B
IM
/5
-2
-7
V A
H a m p to n
E H
R M
/B L D
G
.r v t
114AS102
BUILDING 114 - LEVEL 02 - PHASING PLAN
MA KB
100% CONSTRUCTION
DOCUMENTS
07/18/2025
590-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
1/8" = 1'-0"
BUILDING 114 - LEVEL 02 - PHASING PLAN
LEGEND
KEY PLAN
PROJECT
NORTH
0' 4' 8' 16'
ICRA BLOCKED
CORRIDOR
Revisions: Date: 510 of 713
KEY AREA SHOWN
PROJECT
NORTH
18 19 20
B
C
E
G
12 12
DUCT TO
EXTERIOR
EXISTING FE. REPLACE WITH NEW SEMI-
RECESSED FEC. REPLACE EXISTING FE
WITH NEW CLEAN AGENT EXTINGUISHER
THAT MEETS OR EXCEEDS THE ABC
RATING AND SIZE OF EXISTING
EXTINGUISHER. SEE DETAIL 3/A-603.
ANTE
ROOM
CORRIDOR C1A-1 WILL BE TEMPORARILY
BLOCKED BY ICRA BARRIERS DURING
THE COURSE OF CONSTRUCTION.
SEE SHEET 114AS102 FOR SUGGESTED
INGRESS AND EGRESS, TO ACCESS
BOTH SIDES OF BLOCKED AREA.
18 19 20
B
C
E
G
18 19 20
B
C
E
G
109 SF
WORK ROOM
A112
50 SF
MEN'S TOILET
A113
108 SF
TR
A114
151 SF
STAIR
S1A-3
512 SF
CORRIDOR
C1A-1
155 SF
OFFICE
A111
N E
W
F L O
O R
IN
G
E X
IS
T
IN
G
F
L O
O R
IN
G
FOR EXCEPTION
± 9' - 7 1/2" (EXIST.)
/4
(E X
IS
T
10'x10' TR FORM
FACTOR
A 4 8
IN-04.02-22
NEW SEMI-RECESSED FEC. NEW
CLEAN AGENT FIRE EXTINGUISHER.
SEE DETAIL 3/A-603.
IN-01.31
18 19 20
B
C
E
G
109 SF
WORK ROOM
A112
50 SF
MEN'S TOILET
A113
108 SF
TR
A114
151 SF
STAIR
S1A-3
512 SF
CORRIDOR
C1A-1
155 SF
OFFICE
A111
EXPOSED
2' - 9"
2' - 9"
109 SF
WORK
ROOM
A112
50 SF
MEN'S TOILET
A113
108 SF
TR
A114
151 SF
STAIR
S1A-3
514 SF
CORRIDOR
C1A-1
514 SF
CORRIDOR
C1A-1
155 SF
OFFICE
A111
109 SF
WORK
ROOM
A112
50 SF
MEN'S TOILET
A113
108 SF
TR
A114
151 SF
STAIR
S1A-3
514 SF
CORRIDOR
C1A-1
RM A114
1. ALL PRODUCTS AND WALL FINISHES SHALL MATCH EXISTING
OR ADJACENT EXISTING UNLESS OTHERWISE NOTED.
2. PATCH AND REPAIR WALLS, FLOORS AND CEILINGS WHERE
MECHANICAL, PLUMBING, AND ELECTRICAL ITEMS ARE
DEMOLISHED.
3. PROTECT FINISHES IN ROOMS ADJACENT TO NEW
TELECOMMUNICATION ROOMS AND AREAS NOT SCHEDULED
FOR NEW WORK.
4. CONTRACTORS SHALL LEAVE FIRE RATING STAMP
UNPAINTED AND VISIBLE ON THE NEW INSTALLED FRT
PLYWOOD. SEE DETAIL 5/A3421.
5. REFER TO SHEET AS101 FOR ICRA REQUIREMENTS AND
DETAILS.
6. PATCH AND REPAIR CEILING, WALLS AND FLOORS AS
REQUIRED WHERE ICRA BARRIERS WILL BE CONSTRUCTED
AND REMOVED .
7. PATCH AND REPAIR GWB WHERE DOORS ARE DEMOLISHED
AND NEW DOORS ARE INSTALLED.
1 HR SMOKE BARRIER
1 HR FIRE BARRIER
TO DEMOLISH
EXISTING DOOR TO REMAIN
EXISTING DOOR TO DEMOLISH
EXISTING LIGHTS TO DEMOLISH
NEW DOOR
NEW LIGHTS (SEE ELECTRICAL DETAILS)
PENDENT SPRINKLER
UPRIGHT SPRINKLER WITH GUARD
POSITIVE ( + ) PRESSURE
CONSTRUCTION ZONE (--) PRESSURE
ANTE ROOM ( - ) PRESSURE
EXISTING WALL ACTING AS ICRA
BOUNDARY. SEAL ANY OPENINGS AND
PENETRATIONS AS REQUIRED.
TEMPORARY ICRA BARRIER
TEMPORARY ICRA DOOR
CONSTRUCTION TACKY MAT
HEPA EQUIPPED EXHAUST
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/0 /2
:5
:4 a m
B
IM
/5
-2
-7
V A
H a m p to n
E H
R M
/B L D
G
.r v t
114A-102
BUILDING 114 - LEVEL 02 - DEMO FLOOR PLAN,
DEMO RCP, FLOOR PLAN & RCP
MA AL
100% CONSTRUCTION
DOCUMENTS
07/18/2025
590-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
GENERAL NOTES
KEY NOTES (THIS SHEET ONLY)
KEY PLAN
1/4" = 1'-0"
RM A114 - DEMO FLOOR PLAN
1/4" = 1'-0"
RM A114 - DEMO RCP
1/4" = 1'-0"
RM A114 - FLOOR PLAN
PROJECT
NORTH
PROJECT
NORTH
PROJECT
NORTH
PROJECT
NORTH
1/4" = 1'-0"
RM A114 - RCP
DEMOLISH EXISTING DOOR/FRAME. PREPARE FOR NEW
DOOR/FRAME.
DEMOLISH EXISTING FLOOR FINISH TO EXPOSE BARE
STRUCTURAL FLOOR UNDERNEATH. REMOVE ANY EXISTING
SUBSTANCE/BONDING AGENT IF ANY. PREPARE FLOORING
FOR NEW WORK.
DEMOLISH EXISTING BASE REMOVE EXISTING ADHESIVE AND
PREPARE FOR NEW BASE.
DEMOLISH EXISTING ACT COMPLETELY INCLUDING ALL
GRIDS, SUPPORTING WIRES, CLIPS, AND PERIMETER WALL
ANGLES TO EXPOSE UNDERSIDE OF STRUCTURE ABOVE.
PATCH WALLS WHERE CEILING IS REMOVED.
INSTALL NEW DOOR/FRAME.
INSTALL NEW RESILIENT RUBBER BASE AT ROOM
PERIMETER WITH SEALANT AT THE BOTTOM.
APPLY ANTI-STATIC COATING TO EXPOSED FLOOR. PROVIDE
VINYL REDUCER STRIP AT EXISTING FLOORING TRANSITION.
INSTALL FRT PLYWOOD OVER WALLS PER DETAIL 3/AE421,
TYPICAL.
INSTALL SPANDREL GLASS AND METAL AT INTERIOR OF
EXISTING WINDOW. REFERENCE DETAIL 1/A603.
ICRA KEYNOTES
INSTALL TEMPORARY 1 HR CONSTRUCTION ICRA BARRIER
TO SEPARATE CONSTRUCTION AREA FROM OCCUPIED
SPACE.
INSTALL FIRE RESISTANT TEMPORARY SELF-CLOSING DOOR,
SOLID CORE WOOD IN STEEL FRAME, PAINTED, AT OPENING
AND MATCH RATING OF ICRA BARRIER, TYPICAL.
PLACE TACKY MATS AT ENTRANCE AND EXIT OF
CONSTRUCTION AREA, MINIMUM SIZE 24"X36", TYPICAL.
LEGEND
ICRA LEGEND - CLASS IV
Revisions: Date: 511 of 713
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
A
B
C
E
G
H
J
K
L
M
N
P
Q
R
S
A102K
CGB-4
PRIVATE
ROOM
A102J
PRIVATE
ROOM
A102G
PRIVATE
ROOM
A102E
PRIVATE
ROOM
A102C
TOILET
SHOWER
A102J.1
TOILET
SHOWER
A102G.1
TOILET
SHOWER
A102E.1
TOILET
SHOWER
A102E.2
PRIVATE
ROOM
A102A
TOILET
SHOWER
A102A.1
STAIR
S1A-1
KITCHEN
A104
OFFICE
A106
OFFICE
A110
WORK ROOM
A112
TR
A114
STAIR
S1A-3
ELEVATOR
AG09
JANITOR
STORAGE
A116WOMEN'S
TOILET
A115
MEN'S
TOILET
A113
OFFICE
A111
OFFICE
A107
CONFERENCE
ROOM
A105
CONFERENCE
ROOM
A101
LAUNDRY
ROOM
A102B
ADA TOILET
SHOWER
A102D.1
PRIVATE ADA
ROOM
A102D
PRIVATE
ROOM
A102F
PRIVATE
ROOM
A102H
TOILET
SHOWER
A102H.1
TOILET
SHOWER
A102F.1
CORRIDOR
A102
114-M-402
114-M-402
114-M-402
114-M-402
BUILDING 114
AREA SHOWN
TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/DISCIPLINE
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/0
/2
:3
:1 a m
B
IM
/5
-2
-7
V A
H a m p to n E
H R
M /M
E C
H
B L D
G
.r v t
114-M-101
BLDG 114 - LVL 02 - OVERALL PLAN
MGH/JW AP/CY/JJ/MA/EA/RQ/BC
100% CONSTRUCTION
DOCUMENTS
07/18/2025
590-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
PROJECT
NORTH
1/8" = 1'-0"1
BLDG 114 - LVL 02 - OVERALL PLAN
SITE PLAN
7/18/25 512 of 713
SHOWN AREA
PROJECT
NORTH
17 18 19
A
B
C
E
PHYSICIAN
OFFICE
AG15
VESTIBULE
AG17
CHAPEL/VIEWING
ROOM
AG13
CORRIDOR
CGA-3
114-CU-01-A114 1
AG15
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/DISCIPLINE
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/0
/2
:3
:1 a m
B
IM
/5
-2
-7
V A
H a m p to n E
H R
M /M
E C
H
B L D
G
.r v t
114-M-401
BLDG 114 - LVL 01 - ENLARGED FLOOR PLAN
MGH/JW AP/CY/JJ/MA/EA/RQ/BC
100% CONSTRUCTION
DOCUMENTS
07/18/2025
590-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
1/4" = 1'-0"1
RM AG15 ENLARGE FLOOR PLAN
PROJECT
NORTH
1 SEE "CONDENSING UNIT WALL MOUNT SUPPORT DETAIL" ON
SHEET M-501.
TO FLOOR ABOVE, FOR CONTINUATION SEE SHEET
114-M-402.
FIRE PROTECTION NOTES
1. FOR THE PURPOSES OF CLEARNESS AND LEGIBILITY,
DRAWINGS ARE DIAGRAMMATIC AND FOR DESIGN INTENT
ONLY. CONTRACTOR MUST VERIFY ALL DIMENSIONS BY
FIELD MEASUREMENT BEFORE BEGINNING ANY
FABRICATION OR CONSTRUCTION.
2. ALL WORK SHALL BE COMPLETED IN STRICT ACCORDANCE
WITH THE CURRENT VA GUIDES AND LOCAL FIRE
PROTECTION CODES AND ORDINANCES.
3. CONTRACTOR SHALL HAVE NICET III/IV TECHNICIAN DESIGN
DRAWINGS OR A LICENSED FIRE PROTECTION ENGINEER
STAMP ON ALL SHOP DRAWINGS.
4. COORDINATE EXACT LOCATION OF PIPING, SPRINKLERS,
EQUIPMENT AND MATERIALS WITH OTHER TRADES IN
ACCORDANCE WITH NFPA 13.
5. CONTRACTOR SHALL COORDINATE WITH GENERAL
CONTRACTOR AND VA COR PRIOR TO ANY CUTTING OF
WALLS AND ROOF.
6. THE CONTRACTOR SHALL PROVIDE FIRE CAULKING AT ALL
PIPING PENETRATIONS OF FIRE RATED ASSEMBLIES AS
REQUIRED.
7. TELECOM ROOMS SHALL HAVE FM APPROVED, UPRIGHT,
STANDARD RESPONSE SPRINKLERS WITH FUSIBLE LINKS.
PROVIDE LISTED MECHANICAL GUARDS. ALL EXPOSED
FIRE PROTECTION LINES SHALL BE PAINTED RED.
8. TELECOM ROOMS ARE CONSIDERED LIGHT HAZARD FOR
SPRINKLER HEAD DENSITY. ANY OTHER HAZARD
CLASSIFICATION AND SPRINKLER DENSITY ARE TO BE IN
ACCORDANCE WITH THE LATEST VERSIONS OF NFPA 13
AND VA FIRE PROTECTION DESIGN GUIDE.
9. DO NOT INSTALL SPRINKLER HEADS OR PIPING ABOVE
TELECOMMUNICATION RACKS WHERE FEASIBLE BUT STILL
IN ACCORDANCE WITH NFPA 13.
KEYNOTES #
KEY PLAN
GENERAL NOTES
1. ALL PIPING IS SHOWN OFFSET AND DIAGRAMMATIC FOR
CLARITY. CONTRACTOR SHALL RACK PIPING AS CLOSE AS
POSSIBLE TO INSIDE WALL OF TELECOM ROOM.
2. NEW WORK SHOWN DARK, EXISTING WORK SHOWN
LIGHT.
3. A SINGLE LINE IS USED TO INDICATE ALL REFRIGERANT
PIPING ROUTED BETWEEN THE INDOOR AND OUTDOOR
UNIT(S). THIS SINGLE LINE REPRESENTS ALL PIPING
REQUIRED TO PROVIDE A COMPLETE AND FUNCTIONING
SYSTEM.
4. ROUTE ALL INTERIOR CONDENSATE AND REFRIGERANT
PIPING CONCEALED IN WALLS, CHASES OR CEILING
SPACES.
7/18/25 513 of 713
18 19 20 21
A
B
C
E
G
H
T
TR
A114
WORK
ROOM
A112
CORRIDOR
C1A-1
STAIR
S1A-3
JANITOR
STORAGE
A116
ELEVATOR
EGA-1
WOMEN'S TOILET
A115
MEN'S TOILET
A113
OFFICE
A111
18 19 20 21
A
B
C
E
G
H
TR
A114
WORK ROOM
A112
CORRIDOR
C1A-1
STAIR
S1A-3
M
H
D
3/4"Ø7 8
R
D
T
3/4"Ø 7
114-VRF-01-A1144
3/8"Ø, 5/8"Ø 6
D
MEN'S TOILET
A113
WOMEN'S
TOILET
A115
JANITOR
STORAGE
A116
D
ELEVATOR
AG09
114-VRF-02-A1144
3/8"Ø, 5/8"Ø 6
18 19 20 21
A
B
C
E
G
H
18 19 20 21
A
B
C
E
G
H
TR
A114
STAIR
S1A-3
EXPOSED
MEN'S TOILET
A113
WOMEN'S
TOILET
A115
OFFICE
A111
CORRIDOR
C1A-1
WORK ROOM
A112
JANITOR
STORAGE
A116
ELEVATOR
AG09
A114
TR
A114
WORK
ROOM
A112
STAIR
S1A-3
JANITOR
STORAGE
A116
WOMEN'S TOILET
A115
MEN'S TOILET
A113
OFFICE
A111
CORRIDOR
C1A-1
ELEVATOR
EGA-1
SHOWN AREA
PROJECT
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/DISCIPLINE
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/0
/2
:3
:1 a m
B
IM
/5
-2
-7
V A
H a m p to n E
H R
M /M
E C
H
B L D
G
.r v t
114-M-402
BLDG 114 - LVL 02 - DEMOLITION, FLOOR
PLANS & RCPS
MGH/JW AP/CY/JJ/MA/EA/RQ/BC
100% CONSTRUCTION
DOCUMENTS
07/18/2025
590-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
1/4" = 1'-0"1
RM A114 - DEMOLITION FLOOR PLAN
PROJECT
NORTH
1/4" = 1'-0"3
RM A114 - FLOOR PLAN
PROJECT
NORTH
1/4" = 1'-0"2
RM A114 - DEMOLITION RCP
1/4" = 1'-0"4
RM A114 - RCP
PROJECT
NORTH
PROJECT
NORTH
DEMOLISH EXISTING DUCTLESS AC UNIT. DEMOLISH
REFRIGERANT PIPE SERVING DUCTLESS AC UNIT. DEMOLISH
CONDENSATE PIPE. DEMOLISH ASSOCIATED CONDENSING
UNIT.
DEMOLISH EXISTING THERMOSTAT. TURN OVER TO COR.
DEMOLISH CEILING SUPPLY DIFFUSER. DEMOLISH BRANCH
DUCTWORK BACK TO MAIN. CAP AND SEAL DUCTWORK AT
MAIN.
INSTALL NEW VRF/VRV INDOOR WALL MOUNTED COOLING
UNIT. SEE EQUIPMENT SCHEDULES ON SHEET M-601.
INSTALL REFRIGERANT SENSOR AT A HEIGHT OF NOT MORE
THAN 1 FT. ABOVE FINISHED FLOOR.
INSTALL NEW REFRIGERANT LINES PER MANUFACTURER
REQUIREMENTS (INDOOR UNIT TO OUTDOOR UNIT). PROVIDE
PIPE INSULATION FOR ALL REFRIGERANT LINES PER
SPECIFICATION SECTION 23 07 11. PROVIDE PIPE SUPPORT
PER SPECIFICATION SECTION 23 05 11. PIPE SIZES SHOWN
ON PLANS ARE ONLY APPLICABLE TO BASIS OF DESIGN
MANUFACTURER.
INSTALL NEW CONDENSATE LINE. PROVIDE PIPE SUPPORT
PER SPECIFICATION SECTION 23 05 11.
CONDENSATE LINE TO BE ROUTED TO THE EXISTING SINK
SANITARY LINE. SEE "INDIRECT DRAIN MOP SINK DETAIL" ON
SHEET M-502.
PROVIDE WALL OPENING AND PIPE SLEEVE. SEE "PIPE THRU
WALL (RATED/UNRATED) DETAIL" ON SHEET M-501.
INSTALL NEW STANDARD RESPONSE SPRINKLER IN AN
UPRIGHT POSITION. INSTALL NEW BRANCH LINE, TIE-IN TO
NEAREST EXISTING MAIN.
FROM FLOOR BELOW, FOR CONTINUATION SEE SHEET
114-M-401.
FIRE PROTECTION NOTES
1. FOR THE PURPOSES OF CLEARNESS AND LEGIBILITY,
DRAWINGS ARE DIAGRAMMATIC AND FOR DESIGN INTENT
ONLY. CONTRACTOR MUST VERIFY ALL DIMENSIONS BY
FIELD MEASUREMENT BEFORE BEGINNING ANY
FABRICATION OR CONSTRUCTION.
2. ALL WORK SHALL BE COMPLETED IN STRICT ACCORDANCE
WITH THE CURRENT VA GUIDES AND LOCAL FIRE
PROTECTION CODES AND ORDINANCES.
3. CONTRACTOR SHALL HAVE NICET III/IV TECHNICIAN DESIGN
DRAWINGS OR A LICENSED FIRE PROTECTION ENGINEER
STAMP ON ALL SHOP DRAWINGS.
4. COORDINATE EXACT LOCATION OF PIPING, SPRINKLERS,
EQUIPMENT AND MATERIALS WITH OTHER TRADES IN
ACCORDANCE WITH NFPA 13.
5. CONTRACTOR SHALL COORDINATE WITH GENERAL
CONTRACTOR AND VA COR PRIOR TO ANY CUTTING OF
WALLS AND ROOF.
6. THE CONTRACTOR SHALL PROVIDE FIRE CAULKING AT ALL
PIPING PENETRATIONS OF FIRE RATED ASSEMBLIES AS
REQUIRED.
7. TELECOM…
This is the start of the file's text. The full file is on GovTribe.