Att. 6 - Set 4 of 8 Final Drawings By Building 590 22 700.pdf
PDF 32 MB Posted
- Attached to
- Y1DA--590-22-700 | Construct EHRM Infrastructure Upgrade | Hampton, VA | Federal contract opportunity
- Solicitation number
- 36C77626R0041
About this file
This document is a comprehensive set of final construction drawings for the EHRM (Electronic Health Record and Facilities Infrastructure Modernization) Infrastructure Upgrades project at Hampton VA Medical Center in Hampton, Virginia. The drawings represent 100% construction document phase dated July 18, 2025, and cover multiple buildings (027, 028, 031, 033, 036, 037, and 043) with detailed specifications for electrical, mechanical, telecommunications, and architectural work.
The project scope encompasses renovation of multiple building levels with primary focus on creating new telecommunications rooms (TRs), upgrading data and voice infrastructure to CAT6A standards, installing new ductless HVAC units or VRF/VRV cooling systems, implementing fire protection upgrades, and providing dual-sourced electrical distribution (A-side and B-side power feeds). Key technical requirements include: replacement of existing telecommunications cabling with CAT6A ports and cables, installation of fiber optic backbone cabling (24-strand OS2) to Building 135, provision of secondary bonding busbars and telecommunications bonding backbones per ANSI/TIA standards, installation of surge protective devices (SPDs) and digital power meters (DPMs), implementation of ICRA (Infection Control Risk Assessment) barriers for Class II clinical construction work, and coordination of phased construction to maintain essential medical systems throughout work periods. The drawings specify that the contractor must field-verify all existing conditions, provide detailed shutdown and phasing plans for VA review 30 days prior to implementation, preserve existing branch circuits for retermination where applicable, and coordinate with VA for exact equipment placement and system integration. Multiple specialized rooms are identified including data/telecom closets, equipment rooms, and mechanical spaces requiring fire-rated construction, specific electrical panel configurations, and precise HVAC distribution systems.
View the file
Other files for this federal contract opportunity
Show all 32
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GEN-27
200 kVA 208 V
TO BUS-129-SWBD-129
(SHEET 028EP601)
PD-GEN-27
SQUARE D
LE
600 AF
400 AT
BUS-027-ATS27-E
208 V
CBL-ATS27-N
1 runs 500 kcmil 150 ft
TO BUS-129-SWBD-129
(SHEET 028EP601)
CBL-MDP27
1 runs 500 kcmil 250 ft
BUS-027-ATS27-N
208 V
BUS-027-MDP27
208 V 400 A
E N
AUTO-ATS27
400A
CBL-AX
1 runs
4/0 AWG
50 ft
CBL-BX_1
1 runs
4/0 AWG
50 ft
CBL-F
1 runs
2 AWG
200 ft
BUS-027-AX
208 V 225 A
BUS-027-BX
208 V 225 A
PD-MCB-F
SQUARE D
QD
70 AF
70 AT
BUS-027-F
208 V 100 A
PD-LA_1
SQUARE D
QO
100 AF
100 AT
PD-ELEV2
SQUARE D
QO
100 AF
100 AT
CBL-L
1 runs 500 kcmil 5 ft
PD-AX
SQUARE D
QD
200 AF
200 AT
PD-BX_1
SQUARE D
QB
225 AF
225 AT
PD-F
SQUARE D
QD
125 AF
125 AT
PD-L_1
SQUARE D
LA
400 AF
400 AT
BUS-027-L
208 V 400 A
PD-1C
SQUARE D
QO
100 AF
100 AT
PD-MCB-27AA
GE
SGDA
400 AF
400 AT
CBL-LA
1 runs
2 AWG
20 ft
MTRI-ELEV2
25 hp
CBL-1C
1 runs
2 AWG
20 ft
BUS-027-LA
208 V 100 A
BUS-027-1C
208 V 225 A
PD-L27AB
GE
SELA
100 AF
100 AT
PD-L27C2
GE
SFLA
250 AF
125 AT
PD-G27A
GE
SELA
60 AF
60 AT
PD-ELEV1
GE
SFLA
250 AF
200 AT
PD-L27A
GE
SELA
60 AF
60 AT
PD-L27C
GE
SFLA
250 AF
150 AT
CBL-L27AB
1 runs
2 AWG
5 ft
CBL-L27C2
1 runs
2 AWG
100 ft
CBL-G27A
1 runs
2 AWG
100 ft MTRI-ELEV1
25 hp
BUS-027-L27AB
208 V 100 A
PD-MCB-L27C2
SQUARE D
Q2
100 AF
100 AT
BUS-027-L27C2
208 V 100 A
BUS-027-G27A
208 V 100 A
CBL-L27A
1 runs
2 AWG
100 ft
CBL-L27C
1 runs
2/0 AWG
100 ft
BUS-027-L27A
208 V 100 A
PD-MCB-L27C
GE
TQD
225 AF
200 AT
BUS-027-L27C
208 V 225 A
PD-L27C1
GE
TED
100 AF
100 AT
CBL-L27C1
1 runs
2 AWG
145 ft
PD-MCB-L27C1
SQUARE D
QO
100 AF
100 AT
BUS-027-L27C1
208 V 100 A
CBL-L27-EZ
1 runs 500 kcmil 150 ft
BUS-027-L27-EZ1
208V 100A
CBL-L27-EZ1
1 runs
1 AWG
50 ft
TO BUS-129-SWBD-129
(SHEET 028EP601)
PANELBOARD "27AA" 400A, 208/120V, 3PH, 4W
TRASH
COMP
UNKNOWN
LOAD
UNKNOWN
LOAD
1P SPACE
(QTY=14) 40A/3P20A/1P20A/2P 150A/3P
PANELBOARD "L27 EZ" 400A, 208/120V, 3PH, 4W
30A/3P 30A/3P
027-P-05 027-P-06
100A/3P
PANELBOARD
"027-204DA"
100A 208/120V
3PH
027-P-04
100A/3P
PANELBOARD
"027-109AA"
100A 208/120V
3PH
027-P-03
400A/3P 20A/3P
SPDDPM
PANELBOARD "027-DP-TRA" 600A, 208/120V, 3PH, 4W
600AF
400AT
3P
LSI
027-P-01
027-P-02
3 3
SPD SPD
NEMA L21-30R
30A, 208V
LOCKING
TR 109A
SIDE B
NEMA L21-30R
30A, 208V
LOCKING
TR 204D
SIDE B
1 1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/2
/2
:4
:1
A
M
B
IM
/5
-2
-7
V A
H a m p to n E
H R
M /V
A H
A M
P T
O N
L e g e n d s
G e n e ra l N o te s
D ia g ra m s a n d
D e ta ils .r v t
027EP611
BLDG 027 - PARTIAL ONE-LINE DIAGRAM -
REVISED
JPB/WNM BCL/GPB
100% CONSTRUCTION
DOCUMENTS
07/18/2025
590-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
- NTS
1 BLDG 027 - PARTIAL ONE-LINE DIAGRAM - REVISED
REFERENCE ASSOCIATED PANEL SCHEDULE FOR ADDITIONAL CIRCUITING
INFORMATION.
MODIFIED EQUIPMENT. REFERENCE ASSOCIATED PANEL SCHEDULE FOR
ADDITIONAL INFORMATION.
UTILIZE EXISTING PANELBOARD SPACE TO PROVIDE CIRCUIT BREAKER AND
FEEDER AS INDICATED.
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY
DISCREPANCIES FOUND SHALL BE REPORTED TO THE ENGINEER.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS, TEMPORARY POWER
PLANS,AND PHASING PLANS FOR VA AND ENGINEER REVIEW AND APPROVAL
PRIOR TO COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED FOR REVIEW
30 DAYS PRIOR TO IMPLEMENTATION.
3. SHORT CIRCUIT CALCULATIONS BASED ON VA PROVIDED AS-BUILTS.
4. REFERENCE SHEET(S) "027E-701" THROUGH "027E-703" FOR ELECTRICAL
EQUIPMENT LOAD SCHEDULES.
5. REFERENCE SHEET "027E-701" FOR ALL CONDUIT AND WIRING INFORMATION.
6. COMPLETE BUILDING ONE-LINE PROVIDED FOR INFORMATIONAL PURPOSES
AND AS-BUILDING PURPOSES.
GENERAL NOTES
KEY NOTES
Revisions: Date:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/2
/2
:4
:5
A
M
B
IM
/5
-2
-7
V A
H a m p to n E
H R
M /V
A H
A M
P T
O N
L e g e n d s
G e n e ra l N o te s
D ia g ra m s a n d
D e ta ils .r v t
027E-701
BLDG 027 - ELECTRICAL PANELBOARD AND
CONDUIT AND WIRE SCHEDULES
JPB/WNM BCL/GPB
100% CONSTRUCTION
DOCUMENTS
07/18/2025
590-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE IN
ANY AND ALL CHANGES; ALL REVISED CIRCUIT DIRECTORIES SHALL BE
TYPEWRITTEN.
2. FOR ALL "REVISED" PANEL SCHEDULES REFERENCE "METERING AND LOAD
INFORMATION SCHEDULE" LOCATED ON SHEET E-703 FOR OVERALL PANEL
LOAD. "REVISED" PANEL SCHEDULES ON THIS SHEET ARE SHOWN FOR ADDED
BRANCH CIRCUIT SIZING ONLY.
3. ALL DIGITAL POWER METERS (DPM) AND SURGE PROTECTIVE DEVICES (SPD)
ARE INTEGRAL TO ELECTRICAL DISTRIBUTION EQUIPMENT, UNLESS
OTHERWISE NOTED.
GENERAL NOTES
KEY NOTES
UTILIZE EXISTING SPACE TO PROVIDE CIRCUIT BREAKER AS INDICATED.
EXISTING PANELBOARD OR SWITCHBOARD TO BE MODIFIED AS INDICATED BY
BLACK TEXT. ALL GRAY TEXT SHOWS AS-BUILT EXISTING CONDITIONS.
WAP
WAP WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
360°
0°
A B C D E F G O P Q R S T U V
H I J K L NM
ELECTRICAL
SHOP STORAGE
STORAGE
1D.1
STORAGE
1D
STORAGE
1D.2
PERSONAL
EFFECT
STORAGE
1C
ELEVATOR
1A
ELEV. MECH.
ROOM
BULK STORAGE
STAIRWELL
1B
SECURITY AREA
VAULT
2A
ELEVATOR
2B
BULK STORAGE
MECHANICAL
STORAGE
3A
BLDG REPAIR
STORAGE
STAIRWELL
3B
CRAWL SPACE
UNEXCAVATED
3C
UNEXCAVATED
3D
DATA OUTLETS AND DEVICES IN THIS AREA SHALL BE SERVED
FROM TELECOMMUNICATIONS ROOM 109A ON LEVEL 01.
EXTEND FROM FLOOR TO
ACCESSIBLE CEILING BELOW
DDC
CONTROL
PANEL
DV1
N2
DV1
N2
TYP.
DD2
N2
EMERGENCY
WALL PHONE
EMERGENCY
WALL PHONE
4 4
AREA SHOWN
Y
D# N#
Y
D# N#
OUTLET, DATA OR VOIP TELEPHONE. THE FOLLOWING INFORMATION
INDICATED ON THE SYMBOL:
"#" = QUANTITY OF OUTLET PORTS.
"D" = EXISTING CABLES TO BE DEMOLISHED.
"N" = REPLACEMENT CABLES TO BE PROVIDED.
REFERENCE SHEET TNG002 FOR ADDITIONAL INFORMATION.
BLDG 027
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/1
/2
:4
:5
A
M
B
IM
/5
-2
-7
V A
H a m p to n E
H R
M /E
E
B L D
G
A
B
.r v t
027TN100
BLDG 027 - LEVEL 00 - TELECOMMUNICATIONS
PLAN
KG BCL/GPB
100% CONSTRUCTION
DOCUMENTS
07/18/2025
590-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
- 3/32" = 1'-0"
1 BLDG 027 - LEVEL 00 - TELECOMMUNICATIONS PLAN 8'0 16' 24'
PROJECT
NORTH
TRUE
NORTH
GENERAL NOTES
KEY PLAN
KEY NOTES
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS
REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE
DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE
NOTED.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO ASSOCIATED TR.
6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO
REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,
MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE
INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY
FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
7. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 1" CONDUIT FROM NEW BACKBOX TO
ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO
TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM
OUTLET TO TR AS REQUIRED.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES.
9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION
OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL
IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;
DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.
11. THE CONTRACTOR SHALL BID AND INSTALL CAT6A CABLE WITH AN OD NOT GREATER
THAN 0.250 INCH (6.35mm) (4) CAT6A CABLES WITH AN 0.250 INCH (6.35mm) OD OR
SMALLER CAN BE INSTALLED IN A ¾” CONDUIT SUPPORTING A 40% FILL RATIO.
12. CONTRACTOR TO BID AN ADDITIONAL 10% OF THE TOTAL NUMBER OF WAO's PER
FLOOR. A WAO IS DEFINED AS TWO CAT6A OUTLETS.
PROVIDE VERTICLE FIRE STOP SLEEVES WITH QUANTITY AND SIZE AS INDICATED ON
"TELECOMMUNICATIONS WAO AND CABLE TRAY SCHEDULE" ON SHEET TN701. SLEEVE
PROVIDED TO SERVE HORIZONTAL CABLING FOR WAOs ROUTED FROM TR AS
INDICATED ON PLANS.
EXISTING DDC CONTROL PANEL TO BE RECABLED WITH (1) CAT6A CABLE AS
REQUIRED. COORDINATE WITH VA FOR EXACT LOCATION.
PROVIDE TELECOMMUNICATIONS OUTLET WITH PORT QUANTITY SHOWN TO
REPLACE EXISTING TELECOMMUNICATIONS OUTLET; EXISTING OUTLET CONDUIT
SHALL REMAIN AND BE UTILIZED TO FEED NEW CABLING; REFERENCE DETAIL '1' ON
SHEET TN501 AND THE GENERAL NOTES ON THIS SHEET FOR ADDITIONAL
INFORMATION. COORDINATE WITH VA FOR EXACT OUTLET PLACEMENT.
EXISTING WIRELESS ACCESS POINT TO BE RE-FED WITH (2) CAT6A CABLES.
Revisions: Date: 203 of 713
WAP
WAP
360°
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
360°
WAP WAP
WAP
WAP
WAP
WAP
WAP
360°
WAP WAP
360°360°
ALERTUS
WAP
A B C D E F G O P Q R S T U V
H I J K L NM
027TN401
027TN401
027TN401
027TN401
DATA OUTLETS AND DEVICES IN THIS AREA SHALL BE
SERVED FROM TELECOMMUNICATIONS ROOM 109A.
TYP.
DD2
DD2
DD2
DD2
DD2
DD2
DD2
DD4
DD2 DD2
DD2 DD2
DD2 DD2
DD2 DD2
DD2 DD2
DD2 DD2
DD2
DD2
DD2
DD2
DD2
DD2
DD4
DD2
DD2
DD2
DD2
DD2 DD2
DD2 DD2
DD2 DD2
DD2 DD2
DD2
DD2
DD2
DD2
DD2
DD4 DD4
DD4
DD2DD2
DD2
DD2
DD2
DD2 DD3
DD4
DD2
DD2 DD2
DD2
DD2
DD4
DD4
DD4DD4
DD2
DD2 DD2 DD2
DD2DD2DD2
TYP.
SECURITY DEVICES
DD2
ACCESS
CONTROL
PANEL
DD2
DD2
DD2
DD2
DD2
DD2
DD2
DD2 DD2
DD2 DD2
DD2
DD2
DD2
DD2
DD2
DD2
DD2 DD2 2
DD2
DD2 DD2
DDC
CONTROL
PANEL
DD2
DD2
N2
N2
N2
N2 N2
N2 N2
N2 N2
N2 N2
N2 N2
N2 N2
N2
N2
N2
N2
N2
N2
N2 N2
N2 N2
N2 N2
N2 N2 N2
N2
N2
N2
N2 N2 N2
N2
N2
N2 N2
N2
N2
N2 N2
N2 N2
N2 N2
N2 N2
N2 N2
N2 N2
N2 N2
N2
N2
N2
N2
N2
N2
N2
N2
N2 N2 N2
N2
N2
N2
N2
N2 N2 N2
N2
N2
N2
N2
N2 N2 N2
N2
N2N2
N2
N2 N2 N2
N2N2N2
DD3
N2
N2
DD4
ALERTUS
DEVICE 5
DD2
N2
ALERTUS TTS
N2
N2
N2
N2
N2
DD2
N2
N2
DD2
N2
DD2
DD2
N2
DD2
N2
N2
DD2
N2
DD2
N2
DD2
N2
DD2
DD2
N2
N2
DD2
N2
DV1
N2
DV1 N2
DD2
N2
DD2
N2
DD2
DD2
N2
DD2
N2
DD2
N2
DD2
N2
DD2
N2
EMERGENCY
WALL PHONE
DD2
N2
2 2
STAIR
STORAGE ROOM
109B
TR
109A
CONFERENCE ROOM / WORK
AREA
101A
OFFICE
OPEN WORK SPACE
OFFICE
101E
OFFICE
101B
OFFICE
101A
OFFICE
OFFICE
OFFICE
109C
OFFICE
OFFICE
OFFICE
LOBBY
104A
RECEPTION
CONFERENCE ROOM
FEMALE TOILET
104CMALE TOILET
MECH. ROOM
104E
CORRIDOR
C1
CORRIDOR
C2
KITCHEN
103C
STAIRWELL
103B
ELEVATOR
103A
TRAINING ROOM
KITCHEN
103D
WAREHOUSE
HAC
OFFICE
101C
ELEVATOR
101D
WAREHOUSE
STAIRWELL
101F
TOILET
STORAGE ROOM
SUPPLY
FURNITURE STORAGE
101H
FURNITURE STORAGE
TOILET/SHOWER
116B
MECHANICAL ROOM
FURNITURE STORAGE
116C
CLOSET
STORAGE
107A
STORAGE
107B
OFFICE
101B
OFFICE
101C
OFFICE
101D
N4
N4
DD3
N2
N2
DD3
N4
DD4
AREA SHOWN
Y
D# N#
Y
D# N#
OUTLET, DATA OR VOIP TELEPHONE. THE FOLLOWING INFORMATION
INDICATED ON THE SYMBOL:
"#" = QUANTITY OF OUTLET PORTS.
"D" = EXISTING CABLES TO BE DEMOLISHED.
"N" = REPLACEMENT CABLES TO BE PROVIDED.
REFERENCE SHEET TNG002 FOR ADDITIONAL INFORMATION.
BLDG 027
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/1
/2
:4
:1
A
M
B
IM
/5
-2
-7
V A
H a m p to n E
H R
M /E
E
B L D
G
A
B
.r v t
027TN101
BLDG 027 - LEVEL 01 - TELECOMMUNICATIONS
PLAN
KG BCL/GPB
100% CONSTRUCTION
DOCUMENTS
07/18/2025
590-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
- 3/32" = 1'-0"
1 BLDG 027 - LEVEL 01 - TELECOMMUNICATIONS PLAN 8'0 16' 24'
PROJECT
NORTH
TRUE
NORTH
GENERAL NOTES
KEY PLAN
KEY NOTES
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS
REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE
DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE
NOTED.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO ASSOCIATED TR.
6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO
REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,
MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE
INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY
FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
7. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 1" CONDUIT FROM NEW BACKBOX TO
ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO
TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM
OUTLET TO TR AS REQUIRED.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES.
9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION
OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL
IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;
DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.
11. THE CONTRACTOR SHALL BID AND INSTALL CAT6A CABLE WITH AN OD NOT GREATER
THAN 0.250 INCH (6.35mm) (4) CAT6A CABLES WITH AN 0.250 INCH (6.35mm) OD OR
SMALLER CAN BE INSTALLED IN A ¾” CONDUIT SUPPORTING A 40% FILL RATIO.
12. CONTRACTOR TO BID AN ADDITIONAL 10% OF THE TOTAL NUMBER OF WAO's PER
FLOOR. A WAO IS DEFINED AS TWO CAT6A OUTLETS.
PROVIDE TELECOMMUNICATIONS OUTLET WITH PORT QUANTITY SHOWN TO REPLACE
EXISTING TELECOMMUNICATIONS OUTLET; EXISTING OUTLET CONDUIT SHALL REMAIN
AND BE UTILIZED TO FEED NEW CABLING; REFERENCE DETAIL '1' ON SHEET TN501 AND
THE GENERAL NOTES ON THIS SHEET FOR ADDITIONAL INFORMATION. COORDINATE
WITH VA FOR EXACT OUTLET PLACEMENT.
EXISTING WIRELESS ACCESS POINT TO BE RE-FED WITH (2) CAT6A CABLES.
PROVIDE CABLE TRAY AS INDICATED. REFERENCE DETAIL "6" ON SHEET TN501 AND
TELECOMMUNICATIONS WAO AND CABLE TRAY SCHEDULE ON SHEET TN701. WHERE
WALL EXTENDS TO CEILING, CABLE TRAY SHALL STOP AND TRANSITION TO
HORIZONTAL FIRE STOP SLEEVES [(2) 4", MINIMUM]. WHERE EXISTING CABLE TRAY IS
PRESENT, IT SHALL BE DEMOLISHED AND REPLACED AS INDICATED. EXISTING
SLEEVES MAY BE UTILIZED IF SUITABLE FOR REUSE, BUT NOT IN PLACE OF FIRE STOP
SLEEVES AS MENTIONED ABOVE. WHERE CLEARANCES OR OBSTRUCTIONS DO NOT
PERMIT INSTALLATION OF CABLE TRAY, PROVIDE J-HOOKS AS REQUIRED FOR CABLE
DISTRIBUTION.
EXISTING ACCESS CONTROL PANEL TO BE RE-FED WITH (1) CAT6A CABLE.
EXISTING ALERTUS DEVICE TO BE RECABLED WITH (1) CAT6A CABLE AS REQUIRED.
COORDINATE WITH VA FOR EXACT LOCATION.
EXISTING DDC CONTROL PANEL TO BE RECABLED WITH (1) CAT6A CABLE ASREQUIRED.
COORDINATE WITH VA FOR EXACT LOCATION.
Revisions: Date: 204 of 713
1A
WAP
WAP
WAP
WAP
360° 360°
360°
360°
WAP
WAP
360°
360°
360°
360°
WAP
WAP
WAPWAP
WAP
WAP
WAP
A B C D E F G O P Q R S T U V
H I J K L NM
FIRST FLOOR ROOFFIRST FLOOR ROOF
027TN402a
TR
204D
027TN402b
027TN402b
027TN402a
ANTI-ROOM
ELEVATOR
201C
SPD STORAGE
201B
CHCHE DRUG STORAGE
201B.1
STAIRWELL
201B.2
DRUG STORAGE
201A
BULK STORAGE
ELEVATOR
202A
STAIRWELL
202C
COM. CLOSET
202B
OFFICE CUBICLES
MALE TOILET
204B
MECH. ROOM
204C
MALE TOILET
204A
PURCHASING AGENTS
MECH. ROOM
203C
MALE TOILET
203D
FEMALE TOILET
203E
ELEC./MECH.
203F
CHIEF PURCHASING
109B
STAIRS
203G
OFFICE
203A
DATA OUTLETS AND DEVICES IN THIS AREA SHALL BE
SERVED FROM TELECOMMUNICATIONS ROOM 204D.
TYP.
DD2
DD2
DD2
DD2
DD2
DD2
DD2
DD2
DD2
DD2
DD2
DD2
DD2
DD2
DD2DD2
DD2
DD2
DD2
DD2
DD2
DD2
DD2
DD2
DD2
DD2
DD2DD2
DD2
DD2
DD2
DD2
DD2
DD2 DD2
DD2
DD2
DD4
DD2 DD2
DD2
DD2
DD2
DD2 DD2 DD2 DD2
DD4 DD2
TYP.
DD2
DD2
DD2
DD2
DD2
DD2
DDC
CONTROL
PANEL
DD2
N2 N2
DD4
N4
DV1
N2N2N2 N2
N2
N2
N2
N2
N2
N2
N2
N2
N2
N2
N2
N2 N2
N2
N2 N2
N2 N2
N2 N2
N2 N2
N2
N2
N2
N2
N2
N2
N2
N2
N2N2
N2
N2
N2
N2 N2
N2 N2
N2 N2
N2
N2
N2N2
N2 N2 N2 N2 N2
N2N2
DD2
N2
N2
DD2
DD2
N2
DD2
N2
DD2
DD2
N2
N2
DD2
027TN402a
027TN402a
027TN402b
027TN402b
N4
DD4
AREA SHOWN
Y
D# N#
Y
D# N#
OUTLET, DATA OR VOIP TELEPHONE. THE FOLLOWING INFORMATION
INDICATED ON THE SYMBOL:
"#" = QUANTITY OF OUTLET PORTS.
"D" = EXISTING CABLES TO BE DEMOLISHED.
"N" = REPLACEMENT CABLES TO BE PROVIDED.
REFERENCE SHEET TNG002 FOR ADDITIONAL INFORMATION.
BLDG 027
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/1
/2
:4
:1
A
M
B
IM
/5
-2
-7
V A
H a m p to n E
H R
M /E
E
B L D
G
A
B
.r v t
027TN102
BLDG 027 - LEVEL 02 - TELECOMMUNICATIONS
PLAN
KG BCL/GPB
100% CONSTRUCTION
DOCUMENTS
07/18/2025
590-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
- 3/32" = 1'-0"
1 BLDG 027 - LEVEL 02 - TELECOMMUNICATIONS PLAN 8'0 16' 24'
PROJECT
NORTH
TRUE
NORTH
GENERAL NOTES
KEY PLAN
KEY NOTES
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS
REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE
DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE
NOTED.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO ASSOCIATED TR.
6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO
REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,
MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE
INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY
FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
7. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 1" CONDUIT FROM NEW BACKBOX TO
ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO
TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM
OUTLET TO TR AS REQUIRED.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES.
9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION
OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL
IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;
DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.
11. THE CONTRACTOR SHALL BID AND INSTALL CAT6A CABLE WITH AN OD NOT GREATER
THAN 0.250 INCH (6.35mm) (4) CAT6A CABLES WITH AN 0.250 INCH (6.35mm) OD OR
SMALLER CAN BE INSTALLED IN A ¾” CONDUIT SUPPORTING A 40% FILL RATIO.
12. CONTRACTOR TO BID AN ADDITIONAL 10% OF THE TOTAL NUMBER OF WAO's PER
FLOOR. A WAO IS DEFINED AS TWO CAT6A OUTLETS.
PROVIDE TELECOMMUNICATIONS OUTLET WITH PORT QUANTITY SHOWN TO REPLACE
EXISTING TELECOMMUNICATIONS OUTLET; EXISTING OUTLET CONDUIT SHALL REMAIN
AND BE UTILIZED TO FEED NEW CABLING; REFERENCE DETAIL '1' ON SHEET TN501 AND
THE GENERAL NOTES ON THIS SHEET FOR ADDITIONAL INFORMATION. COORDINATE
WITH VA FOR EXACT OUTLET PLACEMENT.
EXISTING WIRELESS ACCESS POINT TO BE RE-FED WITH (2) CAT6A CABLES.
PROVIDE CABLE TRAY AS INDICATED. REFERENCE DETAIL "6" ON SHEET TN501 AND
TELECOMMUNICATIONS WAO AND CABLE TRAY SCHEDULE ON SHEET TN701. WHERE
WALL EXTENDS TO CEILING, CABLE TRAY SHALL STOP AND TRANSITION TO
HORIZONTAL FIRE STOP SLEEVES [(2) 4", MINIMUM]. WHERE EXISTING CABLE TRAY IS
PRESENT, IT SHALL BE DEMOLISHED AND REPLACED AS INDICATED. EXISTING
SLEEVES MAY BE UTILIZED IF SUITABLE FOR REUSE, BUT NOT IN PLACE OF FIRE STOP
SLEEVES AS MENTIONED ABOVE. WHERE CLEARANCES OR OBSTRUCTIONS DO NOT
PERMIT INSTALLATION OF CABLE TRAY, PROVIDE J-HOOKS AS REQUIRED FOR CABLE
DISTRIBUTION.
EXISTING DDC CONTROL PANEL TO BE RECABLED WITH (1) CAT6A CABLE ASREQUIRED.
COORDINATE WITH VA FOR EXACT LOCATION.
Revisions: Date: 205 of 713
WAP
WAP
WAP
1A
360°
360°
360°
WAP
WAP
WAP
WAP
270°
D E F G O P Q R S
H I J K L NM
STAIRWELL
303A
WAREHOUSE
STORAGE
ELEVATOR
302A
STAIRWELL
ELEVATOR
ROOM
WAREHOUSE
STORAGE
WAREHOUSE
STORAGE
STAIRWELL
301B
DATA OUTLETS AND DEVICES IN THIS AREA SHALL BE SERVED
FROM TELECOMMUNICATIONS ROOM 204D ON LEVEL 02.
N2
DV1
AREA SHOWN
Y
D# N#
Y
D# N#
OUTLET, DATA OR VOIP TELEPHONE. THE FOLLOWING INFORMATION
INDICATED ON THE SYMBOL:
"#" = QUANTITY OF OUTLET PORTS.
"D" = EXISTING CABLES TO BE DEMOLISHED.
"N" = REPLACEMENT CABLES TO BE PROVIDED.
REFERENCE SHEET TNG002 FOR ADDITIONAL INFORMATION.
BLDG 027
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/1
/2
:4
:2
A
M
B
IM
/5
-2
-7
V A
H a m p to n E
H R
M /E
E
B L D
G
A
B
.r v t
027TN103
BLDG 027 - LEVEL 03 - TELECOMMUNICATIONS
PLAN
KG BCL/GPB
100% CONSTRUCTION
DOCUMENTS
07/18/2025
590-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
- 1/8" = 1'-0"
1 BLDG 027 - LEVEL 03 - TELECOMMUNICATIONS PLAN 4'0 8' 16'
PROJECT
NORTH
TRUE
NORTH
GENERAL NOTES
KEY PLAN
KEY NOTES
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS
REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE
DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE
NOTED.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO ASSOCIATED TR.
6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO
REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,
MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE
INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY
FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
7. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 1" CONDUIT FROM NEW BACKBOX TO
ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO
TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM
OUTLET TO TR AS REQUIRED.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES.
9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION
OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL
IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;
DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.
11. THE CONTRACTOR SHALL BID AND INSTALL CAT6A CABLE WITH AN OD NOT GREATER
THAN 0.250 INCH (6.35mm) (4) CAT6A CABLES WITH AN 0.250 INCH (6.35mm) OD OR
SMALLER CAN BE INSTALLED IN A ¾” CONDUIT SUPPORTING A 40% FILL RATIO.
12. CONTRACTOR TO BID AN ADDITIONAL 10% OF THE TOTAL NUMBER OF WAO's PER
FLOOR. A WAO IS DEFINED AS TWO CAT6A OUTLETS.
EXISTING WIRELESS ACCESS POINT TO BE RE-FED WITH (2) CAT6A CABLES.
PROVIDE CONDUIT (4", MINIMUM) WITH APPROPRIATE FIRE-PROOFING AND CAULKING
AS REQUIRED TO EXTEND FROM LEVEL 02 ACCESSIBLE CEILING TO LEVEL 03
ACCESSIBLE CEILING. CONDUIT PROVIDED TO SERVE HORIZONTAL CABLING SERVING
WAOs FROM TR AS INDICATED ON PLANS.
PROVIDE (1) CAT6A CABLE FOR TELEPHONE SERVICE TO ELEVATOR. COORDINATE
WITH VA FOR EXACT LOCATION.
PROVIDE TELECOMMUNICATIONS OUTLET WITH PORT QUANTITY SHOWN TO REPLACE
EXISTING TELECOMMUNICATIONS OUTLET; EXISTING OUTLET CONDUIT SHALL REMAIN
AND BE UTILIZED TO FEED NEW CABLING; REFERENCE DETAIL '1' ON SHEET TN501 AND
THE GENERAL NOTES ON THIS SHEET FOR ADDITIONAL INFORMATION. COORDINATE
WITH VA FOR EXACT OUTLET PLACEMENT.
Revisions: Date: 206 of 713
W
W
360°
X
W
X
W
C
D
WAPWAP
AREA SHOWN
D
TYP.
CLOSET
13 SF
UNLABELED
PANEL
DATA RACK
D
DATA RACK,
TYP. TN502
027-109AA
SECONDARY
BONDING BUSBAR
CLOSET
13 SF
UNLABELED
PANEL
TN503
027-VRF-02-109A
C
TR
109A
119 SF
EXTEND FROM FLOOR TO
ACCESSIBLE CEILING BELOW6
ACCESS CONTROL PANEL7
027-VRF-01-109A
D
TYP.
TN501
DATA RACK,
TYP.
CLOSET
13 SF
TR
109A
119 SF
TYP.
TN501
109A
119 SF
OFFICE
109A
D
CLOSET
13 SF
119 SF
OFFICE
109A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/1
/2
:4
:3
A
M
B
IM
/5
-2
-7
V A
H a m p to n E
H R
M /E
E
B L D
G
A
B
.r v t
027TN401
BLDG 027 - LEVEL 01 - ENLARGED
TELECOMMUNICATIONS PLANS
KG BCL/GPB
100% CONSTRUCTION
DOCUMENTS
07/18/2025
590-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
KEY PLAN
GENERAL NOTES
PROJECT
NORTH
3/8" = 1'-0"027TN101
1 RM 109&109A - DEMOLITION FLOOR PLAN
3/8" = 1'-0"027TN101
2 RM 109&109A - TELECOMMUNICATIONS PLAN
3/8" = 1'-0"027TN101
4 RM 109&109A - OVERHEAD PLAN
2'0 4' 6'
PROJECT
NORTH
EXISTING EQUIPMENT TO BE DEMOLISHED. ASSOCIATED RACEWAYS AND CABLING
SHALL BE DEMOLISHED BACK TO SOURCE.
PROVIDE RIGID CONDUIT SLEEVES WITH FIRE PROOFING AS REQUIRED. SIDE 'A' AND
SIDE 'B' SLEEVES SHALL BE SEPARATED BY AT LEAST 10-FT.
WIRE BASKET CABLE TRAY.
EXISTING DATA RACK TO BE DECOMMISIONED BY VA. CONTRACTOR SHALL
COORDINATE WITH VA AS REQUIRED.
EXISTING WIRELESS ACCESS POINT TO BE RE-FED WITH (2) CAT6A CABLES.
PROVIDE VERTICAL FIRE STOP SLEEVES WITH QUANTITY AND SIZE AS INDICATED ON
"TELECOMMUNICATIONS WAO AND CABLE TRAY SCHEDULE" ON SHEET TN701.
SLEEVE PROVIDED TO SERVE HORIZONTAL CABLING FOR WAOs ROUTED FROM TR
AS INDICATED ON PLANS.
PROVIDE (2)-DOOR ACCESS CONTROL PANEL TO SERVE ALL PACS DOOR SECURITY
EQUIPMENT FOR THIS TR ROOM. PROVIDE ALL REQUIRED CONNECTIONS,
PROGRAMMING, POWER SUPPLIES, AND COMPONENTS TO PROVIDE A COMPLETE
AND FULLY FUNCTIONAL SYSTEM. REFERENCE SPECIFICATION "28 13 00 - PHYSICAL
ACCESS CONTROL SYSTEM" FOR ADDITIONAL INFORMATION.
3/8" = 1'-0"027TN101
3 RM 109&109A - DEMOLITION OVERHEAD PLAN
2'0 4' 6'
PROJECT
NORTH
2'0 4' 6'
PROJECT
NORTH
2'0 4' 6'
PROJECT
NORTH
KEY NOTES
Revisions: Date:
1. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO ASSOCIATED TR.
5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO
REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,
MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE
INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY
FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
6. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 1" CONDUIT FROM NEW BACKBOX TO
ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO
TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM
OUTLET TO TR AS REQUIRED.
7. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION OF
HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL IN
AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
8. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD
BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS
REQUIRED.
9. ANY LIVE SYSTEMS IN DEMO'D TR'S MUST REMAIN LIVE. CONTRACTOR TO
COORDINATE WITH THE STATION TO IDENTIFY SYSTEMS THAT ARE LIVE. IF SYSTEMS
ARE LIVE; INSTALL NEW CABLE FROM DEMO’D TR TO NEW TR. REFER TO DETAIL '3' ON
TN506.
10. RAIL KITS ARE PROVIDED BY THE GC FOR EQUIPMENT MOUNTED IN THE TR CHANNEL
RACKS.
11. LADDER RACK IN ALL TR'S WILL BE MOUNTED 6" OFF THE WALLS TO ACCOMMODATE
ELECTRICAL AND MECHNICAL EQUIPMENT.
360°
W
X
W
W
X
D
C
AREA SHOWN
204D
G
H
TYP.
G
H
TR
204D
84 SF
TN502
027-204DA
SECONDARY
BONDING
BUSBAR
TN503
C
ACCESS CONTROL PANEL
DATA RACK, TYP.
027-VRF-04-204D
027-VRF-03-204D
G
TR
204D
84 SF
TYP.
TN501
TYP.
TN501
DATA RACK, TYP.
1248 SF
OFFICE
CUBICLES
G
H
1248 SF
OFFICE
CUBICLES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/1
/2
:1
:4
P
M
B
IM
/5
-2
-7
V A
H a m p to n E
H R
M /E
E
B L D
G
A
B
.r v t
027TN402a
BLDG 027 - LEVEL 02 - ENLARGED
TELECOMMUNICATIONS PLANS
KG BCL/GPB
100% CONSTRUCTION
DOCUMENTS
07/18/2025
590-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
KEY PLAN
GENERAL NOTES
PROJECT
NORTH
1/2" = 1'-0"027TN102
1 RM 204 - DEMOLITION FLOOR PLAN
1/2" = 1'-0"027TN102
2 RM 204D - TELECOMMUNICATIONS PLAN
1/2" = 1'-0"027TN102
4 RM 204D - OVERHEAD PLAN
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
EXISTING EQUIPMENT TO BE DEMOLISHED. ASSOCIATED RACEWAYS AND CABLING
SHALL BE DEMOLISHED BACK TO SOURCE.
PROVIDE RIGID CONDUIT SLEEVES WITH FIRE PROOFING AS REQUIRED. SIDE 'A' AND
SIDE 'B' SLEEVES SHALL BE SEPARATED BY AT LEAST 10-FT.
WIRE BASKET CABLE TRAY.
PROVIDE CONDUIT (4", MINIMUM) WITH APPROPRIATE FIRE-PROOFING AND CAULKING
AS REQUIRED TO EXTEND FROM LEVEL 02 ACCESSIBLE CEILING TO LEVEL 03
ACCESSIBLE CEILING. CONDUIT PROVIDED TO SERVE HORIZONTAL CABLING
SERVING WAOs FROM TR AS INDICATED ON PLANS.
PROVIDE (2)-DOOR ACCESS CONTROL PANEL TO SERVE ALL PACS DOOR SECURITY
EQUIPMENT FOR THIS TR ROOM. PROVIDE ALL REQUIRED CONNECTIONS,
PROGRAMMING, POWER SUPPLIES, AND COMPONENTS TO PROVIDE A COMPLETE
AND FULLY FUNCTIONAL SYSTEM. REFERENCE SPECIFICATION "28 13 00 - PHYSICAL
ACCESS CONTROL SYSTEM" FOR ADDITIONAL INFORMATION.
1/2" = 1'-0"027TN102
3 RM 204D - DEMOLITION OVERHEAD PLAN 1'0 2' 4'
PROJECT
NORTH
KEY NOTES
Revisions: Date:
1. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO ASSOCIATED TR.
5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO
REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,
MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE
INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY
FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
6. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 1" CONDUIT FROM NEW BACKBOX TO
ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO
TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM
OUTLET TO TR AS REQUIRED.
7. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION OF
HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL IN
AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
8. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD
BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS
REQUIRED.
9. ANY LIVE SYSTEMS IN DEMO'D TR'S MUST REMAIN LIVE. CONTRACTOR TO
COORDINATE WITH THE STATION TO IDENTIFY SYSTEMS THAT ARE LIVE. IF SYSTEMS
ARE LIVE; INSTALL NEW CABLE FROM DEMO’D TR TO NEW TR. REFER TO DETAIL '3' ON
TN506.
10. RAIL KITS ARE PROVIDED BY THE GC FOR EQUIPMENT MOUNTED IN THE TR CHANNEL
RACKS.
11. LADDER RACK IN ALL TR'S WILL BE MOUNTED 6" OFF THE WALLS TO ACCOMMODATE
ELECTRICAL AND MECHNICAL EQUIPMENT.
AREA SHOWN
N
30 SF
COM. CLOSET
202B
UNLABELED PANEL
TELEPHONE
TERMINAL BOARD
DATA RACK
EXISTING AC UNIT
N
30 SF
COM. CLOSET
202B
UNLABELED PANEL
TELEPHONE
TERMINAL BOARD
EXISTING AC UNIT
202B
N
30 SF
COM. CLOSET
202B
N
30 SF
COM. CLOSET
202B
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/1
/2
:4
:4
A
M
B
IM
/5
-2
-7
V A
H a m p to n E
H R
M /E
E
B L D
G
A
B
.r v t
027TN402b
BLDG 027 - LEVEL 02 - ENLARGED
TELECOMMUNICATIONS PLANS
KG BCL/GPB
100% CONSTRUCTION
DOCUMENTS
07/18/2025
590-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
KEY PLAN
GENERAL NOTES
PROJECT
NORTH
1/2" = 1'-0"027TN102
1 RM 202B - DEMOLITION FLOOR PLAN 1'0 2' 4'
PROJECT
NORTH
1/2" = 1'-0"027TN102
2 RM 202B - TELECOMMUNICATIONS PLAN 1'0 2' 4'
PROJECT
NORTH
EXISTING DATA RACK TO BE DECOMMISIONED BY VA. CONTRACTOR SHALL
COORDINATE WITH VA AS REQUIRED.
EXISTING CABLE TRAY TO BE DEMOLISHED.
EXISTING HORIZONTAL CABLING SLEEVE TO BE PRESERVED. EXISTING FIBER OPTIC
AND/OR EXISTING HORIZONTAL CABLING RELATED TO EXISTING TR RACKS TO BE
DEMOLISHED.
1/2" = 1'-0"027TN102
3 RM 202B - DEMOLITION OVERHEAD PLAN 1'0 2' 4'
PROJECT
NORTH
1/2" = 1'-0"027TN102
4 RM 202B - OVERHEAD PLAN 1'0 2' 4'
PROJECT
NORTH
KEY NOTES
1. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO ASSOCIATED TR.
5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO
REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,
MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE
INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY
FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
6. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 1" CONDUIT FROM NEW BACKBOX TO
ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO
TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM
OUTLET TO TR AS REQUIRED.
7. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION OF
HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL IN
AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
8. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD
BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS
REQUIRED.
9. ANY LIVE SYSTEMS IN DEMO'D TR'S MUST REMAIN LIVE. CONTRACTOR TO
COORDINATE WITH THE STATION TO IDENTIFY SYSTEMS THAT ARE LIVE. IF SYSTEMS
ARE LIVE; INSTALL NEW CABLE FROM DEMO’D TR TO NEW TR. REFER TO DETAIL '3' ON
TN506.
Revisions: Date: 209 of 713
A B C D
E F G H I J K L M N O P Q R S T
U V
CRAWL
SPACE
ELECTRICAL
SHOP
STORAGE
STORAGE
1D.1
STORAGE
1D
STORAGE
1D.2
PERSONAL
EFFECT
STORAGE
1C
ELEVATOR
1A
ELEV. MECH.
ROOM
BULK
STORAGE
STAIRWELL
1B
SECURITY
AREA
VAULT
2AELEVATOR
2B
BULK
STORAGE
MECHANICAL
STORAGE
3A
BLDG
REPAIR
STORAGE
STAIRWELL
3B
UNEXCAVATED
3C
UNEXCAVATED
3D
STAIRWELL
OUTLINE OF TR #109A AT
FLOOR ABOVE
REFER TO TS001
FOR CONTINUATION
A
HH03
REFER TO TS001
FOR CONTINUATION
HH04
B
PW-PB-1
PW-PB-1
PW-PB-1
PW-PB-1
A
B
(1) 4"C - (2) 24-STRAND OS2
FIBER CABLES (B)
(1) 4"C - (2) 24-STRAND
OS2 FIBER CABLES (A)
(1) 4"C - (2) 24-STRAND OS2 FIBER
CABLES (B) AND (1) 4"C - SPARE
(1) 4"C - (2) 24-STRAND OS2 FIBER
CABLES (A) AND (1) 4"C - SPARE
(1) 4"C - (2) 24-STRAND OS2 FIBER
CABLES (B)
(1) 4"C - (2) 24 STRAND
OS2 FIBER CABLES (B)
Eddie C. Willis, Jr.
REG. NO. 191562R
EXPIRES 12-31-2025
REGIS
TE
R
ED
CO
MMUNICA T IONS DISTRIBUT IO
N
DESIGNER
RCDD
225 W WASHINGTON STREET
SUITE 2700
CHICAGO, IL 60606
P: 312.294.0501 F: 312.294.0003 www.imegcorp.com
PROJECT #22010109.00
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/1
/2
:0
:0
P
M
B
IM
/5
-2
-7
V A
H a m p to n E
H R
M /5
-7
.B
.T
R
.r v t
27T-200
BLDG.27 BASEMENT PLAN - TECHNOLOGY
EW IMEG
100% CONSTRUCTION
DOCUMENTS
05/09/2025
509-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
N O R
HT
1/8" = 1'-0"
BASEMENT PLAN - TECHNOLOGY
SHEET NOTES:
1. REFER TO SITEPLAN TS001 FOR ADDITIONAL
INFORMATION.
2. REFER TO T500 AND T501 FOR CAMPUS OPTICAL
FIBER CABLE RISER DIAGRAMS.
3. REFER TO 2/T400 FOR HANDHOLE DETAIL.
4. NEW BACKBONE OPTICAL FIBER CABLES SHALL BE
INDOOR/OUTDOOR TYPE.
5. ALL BACKBONE OPTICAL FIBER CABLE PATHWAYS SHALL
BE NEW. DO NOT RE-USE EXISTING BACKBONE CABLE
PATHWAYS FOR NEW BACKBONE CABLES.
6. TRANSITION PVC CONDUITS TO GRC IN CRAWL SPACE OR
EXPOSED EXTERIOR LOCATIONS. TRANSITION TO EMT
CONDUITS AT INTERIOR OF BUILDING. SEAL ALL
PENETRATIONS TO MAINTAIN FIRE-RATINGS OF WALL,
CEILING AND FLOORS.
KEY NOTES:
1. PROVIDE PULLBOX ON EXTERIOR WALL AT HEIGHT
ABOVE BASEMENT CEILING. ROUTE CONDUIT UP WALL
INTO PULLBOX. PROVIDE PENETRATION THRU WALL AND
ROUTE CONDUIT THRU WALL ABOVE CEILING AND OVER
TO LOCATION BELOW TR #109A.
2. PROVIDE PULLBOX ON EXTERIOR WALL AT HEIGHT
ABOVE CRAWL SPACE CEILING. ROUTE CONDUIT UP
WALL INTO PULLBOX. PROVIDE PENETRATION THRU WALL
AND ROUTE CONDUIT THRU WALL INTO CRAWL SPACE
AND OVER TO LOCATION BELOW TR #109A.
3. PROVIDE PENETRATION THRU CEILING AND ROUTE
CONDUITS UP INTO TR #109A.
Revisions: Date: 210 of 713
E F G H I J K L M N O P Q R S T
U V
STAIR
110STORAGE
ROOM
109B
TR
109A
CONFERENCE
ROOM /
WORK AREA
101A
OFFICE
OPEN WORK
SPACE
OFFICE
101E
OFFICE
101B
OFFICE
101A
OFFICE
OFFICE
OFFICE
109C
OFFICE
OFFICE
OFFICE
LOBBY
104A
RECEPTION
CONFERENCE
ROOM
FEMALE
TOILET
104C
MALE TOILET
MECH. ROOM
104E
CORRIDOR
C1
CORRIDOR
C2
KITCHEN
103C
STAIRWELL
103B
ELEVATOR
103A
TRAINING
ROOM
KITCHEN
103D
WAREHOUSE
HAC
OFFICE
101C
ELEVATOR
101D
WAREHOUSE
STAIRWELL
101F
TOILET
STORAGE
ROOM
SUPPLY
FURNITURE
STORAGE
101H
FURNITURE
STORAGE
TOILET/SHOWER
116B
MECHANICAL
ROOM
FURNITURE
STORAGE
116C
CLOSET
STORAGE
107A
STORAGE
107B
OFFICE
101B
OFFICE
101C
OFFICE
101D
27T-400
TR #109A
OUTLINE OF TR #204D
AT FLOOR ABOVE
A
B
PW-PB-1
PW-PB-1
PW-PB-1
PW-PB-1
B
A
27T-400
(1) 4"C - (1) 24-STRAND
OS2 FIBER CABLE (B)
(1) 4"C - (1) 24-STRAND
OS2 FIBER CABLE (A)
(1) 4"C - (1) 24-STRAND
OS2 FIBER CABLE (A)
(1) 4"C - (1) 24-STRAND
OS2 FIBER CABLE (B)
Eddie C. Willis, Jr.
REG. NO. 191562R
EXPIRES 12-31-2025
REGIS
TE
R
ED
CO
MMUNICA T IONS DISTRIBUT IO
N
DESIGNER
RCDD
225 W WASHINGTON STREET
SUITE 2700
CHICAGO, IL 60606
P: 312.294.0501 F: 312.294.0003 www.imegcorp.com
PROJECT #22010109.00
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/1
/2
:0
:0
P
M
B
IM
/5
-2
-7
V A
H a m p to n E
H R
M /5
-7
.B
.T
R
.r v t
27T-201
BLDG.27 LEVEL 01 PLAN - TECHNOLOGY
EW IMEG
100% CONSTRUCTION
DOCUMENTS
05/09/2025
509-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
N O R
HT
1/8" = 1'-0"
LEVEL 01 PLAN - TECHNOLOGY
KEY NOTES:
1. ROUTE CONDUIT UP TO HEIGHT ABOVE CABLE TRAY.
PROVIDE PULLBOX AND ROUTE CONDUIT ABOVE CEILING
AND OVER TO LOCATION BELOW TR #204D.
2. PROVIDE PENETRATION TRHU CEILING DECK AND ROUTE
CONDUIT UP INTO TR #204D.
SHEET NOTES:
1. REFER TO SITEPLAN TS001 FOR ADDITIONAL
INFORMATION.
2. REFER TO T500 AND T501 FOR CAMPUS OPTICAL
FIBER CABLE RISER DIAGRAMS.
3. REFER TO 2/T400 FOR HANDHOLE DETAIL.
4. NEW BACKBONE OPTICAL FIBER CABLES SHALL BE
INDOOR/OUTDOOR TYPE.
5. ALL BACKBONE OPTICAL FIBER CABLE PATHWAYS SHALL
BE NEW. DO NOT RE-USE EXISTING BACKBONE CABLE
PATHWAYS FOR NEW BACKBONE CABLES.
6. TRANSITION PVC CONDUITS TO GRC IN CRAWL SPACE OR
EXPOSED EXTERIOR LOCATIONS. TRANSITION TO EMT
CONDUITS AT INTERIOR OF BUILDING. SEAL ALL
PENETRATIONS TO MAINTAIN FIRE-RATINGS OF WALL,
CEILING AND FLOORS.
Revisions: Date: 211 of 713
E F G H I J K L M N O P Q R S T
U V
ANTI-ROOM
ELEVATOR
201C
SPD
STORAGE
201B
CHCHE DRUG
STORAGE
201B.1
STAIRWELL
201B.2
DRUG
STORAGE
201A
BULK
STORAGE
ELEVATOR
202A
STAIRWELL
202C
COM.
CLOSET
202B
OFFICE
CUBICLES
MALE TOILET
204B
MECH. ROOM
204C
MALE TOILET
204A
PURCHASING
AGENTS
MECH. ROOM
203C
MALE TOILET
203D
FEMALE
TOILET
203E
ELEC./MECH.
203F
CHIEF
PURCHASING
109B
STAIRS
203G
OFFICE
203A
TR
204D
27T-400
TR #204D B
A
27T-400
(1) 4"C - (1) 24-
STRAND OS2 FIBER
CABLE (A)
(1) 4"C - (1) 24-
STRAND OS2 FIBER
CABLE (B)
Eddie C. Willis, Jr.
REG. NO. 191562R
EXPIRES 12-31-2025
REGIS
TE
R
ED
CO
MMUNICA T IONS DISTRIBUT IO
N
DESIGNER
RCDD
225 W WASHINGTON STREET
SUITE 2700
CHICAGO, IL 60606
P: 312.294.0501 F: 312.294.0003 www.imegcorp.com
PROJECT #22010109.00
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/1
/2
:0
:0
P
M
B
IM
/5
-2
-7
V A
H a m p to n E
H R
M /5
-7
.B
.T
R
.r v t
27T-202
BLDG.27 LEVEL 02 PLAN - TECHNOLOGY
EW IMEG
100% CONSTRUCTION
DOCUMENTS
05/09/2025
509-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
N O R
HT
1/8" = 1'-0"
LEVEL 02 PLAN - TECHNOLOGY
KEY NOTES:
1. ROUTE CONDUIT UP TO HEIGHT ABOVE CABLE TRAY.
SHEET NOTES:
1. REFER TO SITEPLAN TS001 FOR ADDITIONAL
INFORMATION.
2. REFER TO T500 AND T501 FOR CAMPUS OPTICAL
FIBER CABLE RISER DIAGRAMS.
3. REFER TO 2/T400 FOR HANDHOLE DETAIL.
4. NEW BACKBONE OPTICAL FIBER CABLES SHALL BE
INDOOR/OUTDOOR TYPE.
5. ALL BACKBONE OPTICAL FIBER CABLE PATHWAYS SHALL
BE NEW. DO NOT RE-USE EXISTING BACKBONE CABLE
PATHWAYS FOR NEW BACKBONE CABLES.
6. TRANSITION PVC CONDUITS TO GRC IN CRAWL SPACE OR
EXPOSED EXTERIOR LOCATIONS. TRANSITION TO EMT
CONDUITS AT INTERIOR OF BUILDING. SEAL ALL
PENETRATIONS TO MAINTAIN FIRE-RATINGS OF WALL,
CEILING AND FLOORS.
Revisions: Date: 212 of 713
FIBER
DISTRIBUTION
CABINET
FIBER
DISTRIBUTION
CABINET
D
TR
109A
CLOSET
A
B
WORK IN ROOM
BY OTHER
(1) 4"C - (1) 24-STRAND
OS2 FIBER CABLE (B)
(1) 4"C - (1) 24-STRAND
OS2 FIBER CABLE (A)
G
TR
204D
WORK IN ROOM
BY OTHER
A
B
(1) 4"C - (1) 24-STRAND
OS2 FIBER CABLE (A)
G
TR
204D
A
B
(1) 4"C - (1) 24-STRAND
OS2 FIBER CABLE (A)
D
TR
109A
CLOSET
A
B
(1) 4"C - (1) 24-STRAND
OS2 FIBER CABLE (B)
(1) 4"C - (1) 24-STRAND
OS2 FIBER CABLE (A)
NOTES:
1. THIS RISER IS DIAGRAMMATIC AND MAY NOT SHOW ACTUAL ROUTING OR QUANTITIES
OF MATERIALS SHOWN. THIS RISER IS SHOWN FOR CLARIFICATION OF
CONNECTION(S), LOCATIONS AND CABLE TYPE. ALL INFORMATION OUTLETS ARE
TYPICAL OF THE OUTLETS IN THE AREA SHOWN. REFER TO FLOOR PLANS FOR MORE
SPECIFIC ROUTING INFORMATION. REFER TO SPECIFICATIONS FOR ADDITIONAL
REQUIREMENTS.
2. REFER TO ELECTRICAL DRAWINGS FOR CHANNEL RACK AND FIBER OPTIC
DISTRIBUTION CABINET SPECIFICATIONS
TELECOMMUNICATIONS ROOM TR #109A
24 STRANDS OS2 FIBER OPTIC
CABLE, CORE "A" , TO BUILDING 135
24 STRANDS OS2 FIBER OPTIC
CABLE, CORE "B" , TO BUILDING 135
CHANNEL RACK
LEVEL 01
TELECOMMUNICATIONS ROOM TR #204D
24 STRANDS OS2 FIBER OPTIC
CABLE, CORE "A" , TO BUILDING 135
24 STRANDS OS2 FIBER OPTIC
CABLE, CORE "B" , TO BUILDING 135
CHANNEL RACK
LEVEL 02
Eddie C. Willis, Jr.
REG. NO. 191562R
EXPIRES 12-31-2025
REGIS
TE
R
ED
CO
MMUNICA T IONS DISTRIBUT IO
N
DESIGNER
RCDD
225 W WASHINGTON STREET
SUITE 2700
CHICAGO, IL 60606
P: 312.294.0501 F: 312.294.0003 www.imegcorp.com
PROJECT #22010109.00
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/1
/2
:0
:1
P
M
B
IM
/5
-2
-7
V A
H a m p to n E
H R
M /5
-7
.B
.T
R
.r v t
27T-400
BLDG.27 TECHNOLOGY DETAILS AND
DIAGRAMS
EW IMEG
100% CONSTRUCTION
DOCUMENTS
05/09/2025
509-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
N O R
HT
1/2" = 1'-0"
TELECOM ROOM ENLARGEMENT TR #109A
N O R
HT
1/2" = 1'-0"
TELECOM ROOM ENLARGEMENT TR #204D
NOTES:
1. REFER TO ELECTRICAL DRAWINGS FOR ROOM LAYOUT AND RACK ELEVATIONS.
2. ROUTE OPTICAL FIBER CABLE TO OVERHEAD CABLE TRAY AND TERMINATE IN
FIBER DISTRIBUTION CABINET.
KEY NOTES:
1. THROUGH FLOOR/CEILING PENETRATION FOR BACKBONE CONDUIT. CONDUIT
SHALL CONTINUE UP TO HEIGHT OF CABLE TRAY. OPTICAL FIBER CABLE CONTINUES
ON CABLE TRAY TO RACKS.
N O R
HT
1/2" = 1'-0"
TELECOM ROOM PATHWAY TR #204D
N O R
HT
1/2" = 1'-0"
TELECOM ROOM PATHWAY TR #109A
NOTES:
1. REFER TO ELECTRICAL DRAWINGS FOR ROOM LAYOUT AND RACK ELEVATIONS.
2. ROUTE OPTICAL FIBER CABLE TO OVERHEAD CABLE TRAY AND TERMINATE IN
FIBER DISTRIBUTION CABINET.
KEY NOTES:
1. THROUGH FLOOR/CEILING PENETRATION FOR BACKBONE CONDUIT. CONDUIT
SHALL CONTINUE UP TO HEIGHT OF CABLE TRAY. OPTICAL FIBER CABLE CONTINUES
ON CABLE TRAY TO RACKS.
NO SCALE
FIBER RISER DIAGRAM
(1) 4"C - (1) 24-STRAND
OS2 FIBER CABLE (B)
(1) 4"C - (1) 24-STRAND
OS2 FIBER CABLE (B)
Revisions: Date: 213 of 713
27B
27 31
27A
110A
110B
110D
13W
148-D
148-S
148-A
148T
146B
146A
138A 138136
137A
137C
137D
137B
137C
148B
173A
148-C
170 150
110C
143 167
G R
A V
E L
R O
A D
FRANKLIN BOULEVARD
FRANKLIN BOULEVARD
AVERILL AVENUE
AVERILL AVENUE
A M
E S
S T
R E
E T
HARRIS AVENUE
JONES CREEK
K N
O X S
T R
E E
T
T H
O M
P S
O N
S T
R E
E T
F R A N
K
LI
N B
O U
LE
V A R
D
MALLORY STREET
M A
R T
IN
L. K
IN
G
JR
. B O
U L E
V A R
D
M A R
TIN
L. K
IN
G
JR
. B O U
LE
V
AR
D
E M
A N
C
IP
A T
IO
N D
R
SHORE ROAD
H A R R
IS
A V E N
U E
HARRIS AVENUE
M c C
L E
L L A
N
S E
W E
LL
A
V E
N U
E
A V
E N
U E
A B C D E F G H I J K
236 SF
OFFICE
61 SF
COMM. CLOSET
102B
29 SF
TOILET ROOM
102A
136 SF
OFFICE
103B
286 SF
OFFICE
275 SF
ELECTRONIC
TECHS OFFICE
103B.1
92 SF
TR
103B.1a
251 SF
BREAK ROOM
57 SF
BATHROOM
105A
1173 SF
MECH SHOP
105B
890 SF
GROUNDS
KEEPING
EQUIPMENT
300 SF
CONFERENCE
RM/LOCKERS
105C
67 SF
STAIRS
27 SF
TOILET
101A
OVERHEAD DOOR
PHASE 1:
CONTRACTOR TO COMPLETE THE WORK OF THIS TR
AND ASSOCIATED DATA DROPS. COMPLETE ONE
SECTION AT A TIME AS DIRECTED TO COR.
SECTION 1A:
CONTRACTOR TO COORDINATE…