Att. 18 - Set 8 of 8 Final Drawings By Discipline 590 22 700.pdf
PDF 16 MB Posted
- Attached to
- Y1DA--590-22-700 | Construct EHRM Infrastructure Upgrade | Hampton, VA | Federal contract opportunity
- Solicitation number
- 36C77626R0041
About this file
This document is a comprehensive set of final construction drawings for telecommunications infrastructure upgrades at Hampton VA Medical Center in Hampton, Virginia, covering project 590-22-700 (EHRM Infrastructure Upgrades). The drawings depict detailed telecommunications system designs across multiple buildings at the medical center campus, including telecommunications rooms (TR), telecom enclosures (TE), fiber optic backbone routing, cable tray installations, and connectivity upgrades to support healthcare operations.
The project involves extensive fiber optic backbone infrastructure installation with Core A and Core B diverse routing loops connecting to the existing main computer room (MCR) in Building 135. Key deliverables include new telecommunications rooms in Buildings 146, 148, 148T, and 168; upgrades to existing telecom infrastructure across the campus; Category 6A (CAT6A) cabling for horizontal distribution with replacement of legacy Category 6 and below cabling; installation of new data racks with fiber distribution cabinets and network switches; underground conduit ductbanks with innerducts for fiber cable routing; telecommunications handholes and manholes positioned at maximum 400-foot intervals; fire-rated conduit sleeves and penetration sealing throughout; and access control and physical security panel installations. The design specifies two diverse pathways (A-Loop and B-Loop) for redundancy, uses indoor/outdoor rated fiber optic cables, and mandates compliance with VA Infrastructure Standard for Telecommunications Spaces (ISTS) V4.0 and the Physical Security and Resiliency Design Manual. Construction is organized in three phasing sequences to maintain existing system operability during transition to new infrastructure, with provisions for coordinating with the VA to keep live systems operational during migration.
View the file
Other files for this federal contract opportunity
Show all 32
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
W W
AREA SHOWN
PROJECT
NORTH
Q
FIBER OPTIC PANEL
TELEPHONE
TERMINAL BOARD
ACCESS CONTROLLER
PANEL
TELECOMMUNICATIONS
ENCLOSURE
BONDING
BUSBAR
DATA CLOSET
T2
8 SF
Q
FIBER OPTIC PANEL
ACCESS CONTROLLER
PANEL
TELEPHONE
TERMINAL BOARD
BONDING
BUSBAR DATA CLOSET
T2
8 SF
Q
P
DATA CLOSET
T2
8 SF
T2
Q
DATA CLOSET
T2
8 SF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/0
/2
:3
:3 a m
B
IM
/5
-2
-7
V
A H a m p to n E
H R
M /E
E
B L
D G
.r v t
146TN401d
BLDG 146 - LEVEL 01 - ENLARGED
TELECOMMUNICATIONS PLANS
KG BCL/GPB
100% CONSTRUCTION
DOCUMENTS
07/18/2025
590-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
1/2" = 1'-0"146TN101A
1 RM T2 - DEMOLITION FLOOR PLAN
1/2" = 1'-0"146TN101A
2 RM T2 - TELECOMMUNICATIONS PLAN
1/2" = 1'-0"146TN101A
3 RM T2 - DEMOLITION OVERHEAD PLAN
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1/2" = 1'-0"146TN101A
4 RM T2 - OVERHEAD PLAN 1'0 2' 4'
PROJECT
NORTH
Revisions: Date:
EXISTING DATA RACK TO BE DECOMMISIONED BY VA. CONTRACTOR SHALL
COORDINATE WITH VA AS REQUIRED.
EXISTING VERTICAL CABLING SLEEVES TO BE PRESERVED. EXISTING FIBER OPTIC
AND/OR EXISTING VERTICAL CABLING RELATED TO EXISTING TR RACKS TO
BE DEMOLISHED.
EXISTING PENETRATIONS WITH CABLING TO BE REMOVED. CONTRACTOR SHALL
PATCH AND FIREPROOF OPENINGS. COORDINATE WITH ARCHITECTURAL DRAWINGS
AND SPECIFICATIONS.
GENERAL NOTES
KEY PLAN
KEY NOTES
1. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO ASSOCIATED TR.
5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO
REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,
MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE
INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY
FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
6. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 1" CONDUIT FROM NEW BACKBOX TO
ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO
TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM
OUTLET TO TR AS REQUIRED.
7. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION OF
HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL IN
AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
8. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD
BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS
REQUIRED.
9. ANY LIVE SYSTEMS IN DEMO'D TR'S MUST REMAIN LIVE. CONTRACTOR TO
COORDINATE WITH THE STATION TO IDENTIFY SYSTEMS THAT ARE LIVE. IF SYSTEMS
ARE LIVE; INSTALL NEW CABLE FROM DEMO’D TR TO NEW TR. REFER TO DETAIL '3' ON
TN506.
W
P
W
P P PPP
P
AREA SHOWN
PROJECT
NORTH
E
TELEPHONE
TERMINAL
BOARD
FIBER OPTIC
PANELS
SIGNAL
DEVICE
TELECOMMUNICATIONS
ENCLOSURE
COMPUTER
BOX
ACCESS DOOR
CONTROLLER PANEL
PUBLIC ADDRESS
SYSTEM EQUIPMENTS
EXISTING BONDING BUSBAR
DATA CLOSET
T3
47 SF
E
TELEPHONE
TERMINAL
BOARD
FIBER OPTIC
PANELS
SIGNAL
DEVICE
COMPUTER
BOX
ACCESS DOOR
CONTROLLER PANEL
PUBLIC ADDRESS
SYSTEM EQUIPMENTS
EXISTING BONDING BUSBAR
DATA CLOSET
T3
47 SF
T3
E
EXISTING AC UNIT
E
DATA CLOSET
T3
47 SF
DATA CLOSET
T3
47 SF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/0
/2
:3
:5 a m
B
IM
/5
-2
-7
V
A H a m p to n E
H R
M /E
E
B L
D G
.r v t
146TN401e
BLDG 146 - LEVEL 01 - ENLARGED
TELECOMMUNICATIONS PLANS
KG BCL/GPB
100% CONSTRUCTION
DOCUMENTS
07/18/2025
590-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
1/2" = 1'-0"146TN101A
1 RM T3 - DEMOLITION FLOOR PLAN
1/2" = 1'-0"146TN101A
2 RM T3 - TELECOMMUNICATIONS PLAN1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1/2" = 1'-0"146TN101A
3 RM T3 - DEMOLITION OVERHEAD PLAN
1/2" = 1'-0"146TN101A
4 RM T3 - OVERHEAD PLAN1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
Revisions: Date:
EXISTING DATA RACK TO BE DECOMMISIONED BY VA. CONTRACTOR SHALL
COORDINATE WITH VA AS REQUIRED.
EXISTING VERTICAL CABLING SLEEVES TO BE PRESERVED. EXISTING FIBER OPTIC
AND/OR EXISTING VERTICAL CABLING RELATED TO EXISTING TR RACKS TO BE
DEMOLISHED.
EXISTING PENETRATIONS WITH CABLING TO BE REMOVED. CONTRACTOR SHALL PATCH
AND FIREPROFF OPENINGS. COORDINATE WITH ARCHITECTURAL DRAWINGS AND
SPECIFICATIONS.
GENERAL NOTES
KEY PLAN
KEY NOTES
1. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO ASSOCIATED TR.
5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO
REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,
MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE
INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY
FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
6. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 1" CONDUIT FROM NEW BACKBOX TO
ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO
TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM
OUTLET TO TR AS REQUIRED.
7. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION OF
HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL IN
AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
8. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD
BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS
REQUIRED.
9. ANY LIVE SYSTEMS IN DEMO'D TR'S MUST REMAIN LIVE. CONTRACTOR TO
COORDINATE WITH THE STATION TO IDENTIFY SYSTEMS THAT ARE LIVE. IF SYSTEMS
ARE LIVE; INSTALL NEW CABLE FROM DEMO’D TR TO NEW TR. REFER TO DETAIL '3' ON
PROJECT
NORTH
E
TELEPHONE
TERMINAL
BOARD
TEMPERATURE
MONITORING
DEVICES
FIBER OPTIC
PANEL
FIRE ALARM
PANELS
FIRE ALARM
EQUIPMENT
DATA RACK
ACCESS DOOR
CONTROLLER PANEL
BONDING BUSBAR
DATA
CLOSET
T4
48 SF
E
TELEPHONE
TERMINAL
BOARD
TEMPERATURE
MONITORING
DEVICES
FIBER OPTIC
PANEL
FIRE ALARM
PANELS
FIRE ALARM
EQUIPMENT
ACCESS DOOR
CONTROLLER PANEL
BONDING BUSBAR
DATA
CLOSET
T4
48 SF
T4
EE
P
P
EXISTING AC UNIT
PPP
DATA
CLOSET
T4
48 SF
E
EXISTING AC UNIT
DATA
CLOSET
T4
48 SF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/0
/2
:3
:4 a m
B
IM
/5
-2
-7
V
A H a m p to n E
H R
M /E
E
B L
D G
.r v t
146TN401f
BLDG 146 - LEVEL 01 - ENLARGED
TELECOMMUNICATIONS PLANS
KG BCL/GPB
100% CONSTRUCTION
DOCUMENTS
07/18/2025
590-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
11/2" = 1'-0"146TN101A
1 RM T4 - DEMOLITION FLOOR PLAN
1/2" = 1'-0"146TN101A
2 RM T4 - TELECOMMUNICATIONS PLAN1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1/2" = 1'-0"146TN101A
3 RM T4 - DEMOLITION OVERHEAD PLAN 1'0 2' 4'
PROJECT
NORTH
1/2" = 1'-0"146TN101A
4 RM T4 - OVERHEAD PLAN 1'0 2' 4'
PROJECT
NORTH
Revisions: Date:
EXISTING DATA RACK TO BE DECOMMISIONED BY VA. CONTRACTOR SHALL
COORDINATE WITH VA AS REQUIRED.
EXISTING VERTICAL CABLING SLEEVES TO BE PRESERVED. EXISTING FIBER OPTIC
AND/OR EXISTING VERTICAL CABLING RELATED TO EXISTING TR RACKS TO BE
DEMOLISHED.
EXISTING PENETRATIONS WITH CABLING TO BE REMOVED. CONTRACTOR SHALL PATCH
AND FIREPROFF OPENINGS. COORDINATE WITH ARCHITECTURAL DRAWINGS AND
SPECIFICATIONS.
GENERAL NOTES
KEY PLAN
KEY NOTES
1. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO ASSOCIATED TR.
5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO
REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,
MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE
INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY
FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
6. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 1" CONDUIT FROM NEW BACKBOX TO
ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO
TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM
OUTLET TO TR AS REQUIRED.
7. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION OF
HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL IN
AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
8. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD
BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS
REQUIRED.
9. ANY LIVE SYSTEMS IN DEMO'D TR'S MUST REMAIN LIVE. CONTRACTOR TO
COORDINATE WITH THE STATION TO IDENTIFY SYSTEMS THAT ARE LIVE. IF SYSTEMS
ARE LIVE; INSTALL NEW CABLE FROM DEMO’D TR TO NEW TR. REFER TO DETAIL '3' ON
PROJECT
NORTH
Q
3 ACCESS CONTROLLER
PANEL
TELECOMMUNICATIONS
ENCLOSURE
TELEPHONE
TERMINAL
BOARD
FIBER OPTIC
PANEL
ELECT
CLOSET
E8
9 SF
Q
3 ACCESS
CONTROLLER PANEL
TELEPHONE
TERMINAL
BOARD
FIBER OPTIC
PANEL
ELECT
CLOSET
E8
9 SF
Q
P
ELECT
CLOSET
E8
9 SF E8
Q
ELECT
CLOSET
E8
9 SF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/0
/2
:3
:4 a m
B
IM
/5
-2
-7
V
A H a m p to n E
H R
M /E
E
B L
D G
.r v t
146TN401g
BLDG 146 - LEVEL 01 - ENLARGED
TELECOMMUNICATIONS PLANS
KG BCL/GPB
100% CONSTRUCTION
DOCUMENTS
07/18/2025
590-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
11/2" = 1'-0"146TN101A
1 RM E8 - DEMOLITION FLOOR PLAN
1/2" = 1'-0"146TN101A
2 RM E8 - TELECOMMUNICATIONS PLAN
1/2" = 1'-0"146TN101A
3 RM E8 - DEMOLITION OVERHEAD PLAN
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1/2" = 1'-0"146TN101A
4 RM E8 - OVERHEAD PLAN 1'0 2' 4'
PROJECT
NORTH
Revisions: Date:
EXISTING DATA RACK TO BE DECOMMISIONED BY VA. CONTRACTOR SHALL
COORDINATE WITH VA AS REQUIRED.
EXISTING VERTICAL CABLING SLEEVE TO BE PRESERVED. EXISTING FIBER OPTIC
AND/OR EXISTING VERTICAL CABLING RELATED TO EXISTING TR RACKS TO BE
DEMOLISHED.
EXISTING PENETRATIONS WITH CABLING TO BE REMOVED. CONTRACTOR SHALL PATCH
AND FIREPROOF OPENINGS. COORDINATE WITH ARCHITECTURAL DRAWINGS AND
SPECIFICATIONS.
GENERAL NOTES
KEY PLAN
KEY NOTES
1. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO ASSOCIATED TR.
5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO
REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,
MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE
INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY
FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
6. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 1" CONDUIT FROM NEW BACKBOX TO
ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO
TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM
OUTLET TO TR AS REQUIRED.
7. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION OF
HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL IN
AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
8. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD
BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS
REQUIRED.
9. ANY LIVE SYSTEMS IN DEMO'D TR'S MUST REMAIN LIVE. CONTRACTOR TO
COORDINATE WITH THE STATION TO IDENTIFY SYSTEMS THAT ARE LIVE. IF SYSTEMS
ARE LIVE; INSTALL NEW CABLE FROM DEMO’D TR TO NEW TR. REFER TO DETAIL '3' ON
WAP
W
360°
CD
C
XW
WAP
AREA SHOWN
PROJECT
NORTH
Ia
Ja
Ka
5a
TYP.
Ia
Ja
Ka
5a
PHYSICIAN
OFFICE
A185
186 SF
PHYSICIAN
OFFICE
A185
186 SF
Ia
Ja
Ka
5a
C
ACCESS CONTROL PANEL 5
148-A185A
SECONDARY
BONDING
BUSBAR
TR
A185
186 SF
TN502
TN503
DATA RACK,
TYP.
148-VRF-05-A185
148-VRF-06-A185
Ia
Ja
Ka
5a
TR
A185
186 SF
TN501
TN501
DATA RACK,
TYP.
A185
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/0 /2
:1
:1 a m
B
IM
/5
-2
-7
V A
H a m p to n E
H R
M /E
E
B L D
G
.r v t
148TN401a
BLDG 148 - LEVEL 01 - ENLARGED
TELECOMMUNICATIONS PLANS
KG BCL/GPB
100% CONSTRUCTION
DOCUMENTS
07/18/2025
590-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
GENERAL NOTES
KEY NOTES
EXISTING EQUIPMENT TO BE DEMOLISHED. ASSOCIATED RACEWAYS AND CABLING
SHALL BE DEMOLISHED BACK TO SOURCE.
EXISTING WIRELESS ACCESS POINT TO BE RE-FED WITH (2) CAT6A CABLES.
PROVIDE RIGID CONDUIT SLEEVES WITH FIRE PROOFING AS REQUIRED. SIDE 'A' AND
SIDE 'B' SLEEVES SHALL BE SEPARATED BY AT LEAST 10-FT.
WIRE BASKET CABLE TRAY.
PROVIDE (2)-DOOR ACCESS CONTROL PANEL TO SERVE ALL PACS DOOR SECURITY
EQUIPMENT FOR THIS TR ROOM. PROVIDE ALL REQUIRED CONNECTIONS,
PROGRAMMING, POWER SUPPLIES, AND COMPONENTS TO PROVIDE A COMPLETE
AND FULLY FUNCTIONAL SYSTEM. REFERENCE SPECIFICATION "28 13 00 - PHYSICAL
ACCESS CONTROL SYSTEM" FOR ADDITIONAL INFORMATION.
3/8" = 1'-0"148TN101A
1 RM A185 - DEMOLITION FLOOR PLAN
3/8" = 1'-0"148TN101A
3 RM A185 - DEMOLITION OVERHEAD PLAN
3/8" = 1'-0"148TN101A
2 RM A185 - TELECOMMUNICATIONS PLAN
3/8" = 1'-0"148TN101A
4 RM A185 - OVERHEAD PLAN
2'0 4' 6'
PROJECT
NORTH
2'0 4' 6'
PROJECT
NORTH
2'0 4' 6'
PROJECT
NORTH
2'0 4' 6'
PROJECT
NORTH
KEY PLAN
1. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO ASSOCIATED TR.
5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO
REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,
MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE
INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY
FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
6. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 1" CONDUIT FROM NEW BACKBOX TO
ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO
TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM
OUTLET TO TR AS REQUIRED.
7. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION OF
HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL IN
AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
8. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD
BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS
REQUIRED.
9. ANY LIVE SYSTEMS IN DEMO'D TR'S MUST REMAIN LIVE. CONTRACTOR TO
COORDINATE WITH THE STATION TO IDENTIFY SYSTEMS THAT ARE LIVE. IF SYSTEMS
ARE LIVE; INSTALL NEW CABLE FROM DEMO’D TR TO NEW TR. REFER TO DETAIL '3' ON
TN506.
10. RAIL KITS ARE PROVIDED BY THE GC FOR EQUIPMENT MOUNTED IN THE TR CHANNEL
RACKS.
11. LADDER RACK IN ALL TR'S WILL BE MOUNTED 6" OFF THE WALLS TO ACCOMMODATE
ELECTRICAL AND MECHNICAL EQUIPMENT.
Revisions: Date: 605 of 713
2 2
X W
X W C
360°
Jb
11b 12b
TYP.
Jb
11b 12b
DATA RACK,
TYP.
ACCESS CONTROL PANEL
TR
B185
184 SF
SECONDARY
BONDING BUSBAR
148-B185A
C
TN503
TN502
148-VRF-02-B185
148-VRF-01-B185
Jb
11b 12b
Jb
11b 12b
DATA RACK,
TYP.
TR
B185
184 SF
TYP.
TN501
TYP.
TN501
184 SF
DAP OFFICE
B185
184 SF
DAP OFFICE
B185
AREA SHOWN
PROJECT
NORTH
B185
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/0 /2
:1
:3 a m
B
IM
/5
-2
-7
V A
H a m p to n E
H R
M /E
E
B L D
G
.r v t
148TN401b
BLDG 148 - LEVEL 01 - ENLARGED
TELECOMMUNICATIONS PLANS
KG BCL/GPB
100% CONSTRUCTION
DOCUMENTS
07/18/2025
590-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
1/2" = 1'-0"148TN101A
1 RM B185 - DEMOLITION FLOOR PLAN
1/2" = 1'-0"148TN101A
2 RM B185 - TELECOMMUNICATIONS PLAN
1/2" = 1'-0"148TN101A
3 RM B185 - DEMOLITION OVERHEAD PLAN
1/2" = 1'-0"148TN101A
4 RM B185 - OVERHEAD PLAN
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4' 1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
PROJECT
NORTH
PROJECT
NORTH
PROJECT
NORTH
GENERAL NOTES
KEY PLAN
EXISTING EQUIPMENT TO BE DEMOLISHED. ASSOCIATED RACEWAYS AND CABLING
SHALL BE DEMOLISHED BACK TO SOURCE.
PROVIDE RIGID CONDUIT SLEEVES WITH FIRE PROOFING AS REQUIRED. SIDE 'A' AND
SIDE 'B' SLEEVES SHALL BE SEPARATED BY AT LEAST 10-FT.
WIRE BASKET CABLE TRAY.
PROVIDE (2)-DOOR ACCESS CONTROL PANEL TO SERVE ALL PACS DOOR SECURITY
EQUIPMENT FOR THIS TR ROOM. PROVIDE ALL REQUIRED CONNECTIONS,
PROGRAMMING, POWER SUPPLIES, AND COMPONENTS TO PROVIDE A COMPLETE
AND FULLY FUNCTIONAL SYSTEM. REFERENCE SPECIFICATION "28 13 00 - PHYSICAL
ACCESS CONTROL SYSTEM" FOR ADDITIONAL INFORMATION.
1. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO ASSOCIATED TR.
5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO
REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,
MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE
INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY
FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
6. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 1" CONDUIT FROM NEW BACKBOX TO
ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO
TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM
OUTLET TO TR AS REQUIRED.
7. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION OF
HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL IN
AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
8. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD
BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS
REQUIRED.
9. ANY LIVE SYSTEMS IN DEMO'D TR'S MUST REMAIN LIVE. CONTRACTOR TO
COORDINATE WITH THE STATION TO IDENTIFY SYSTEMS THAT ARE LIVE. IF SYSTEMS
ARE LIVE; INSTALL NEW CABLE FROM DEMO’D TR TO NEW TR. REFER TO DETAIL '3' ON
TN506.
10. RAIL KITS ARE PROVIDED BY THE GC FOR EQUIPMENT MOUNTED IN THE TR CHANNEL
RACKS.
11. LADDER RACK IN ALL TR'S WILL BE MOUNTED 6" OFF THE WALLS TO ACCOMMODATE
ELECTRICAL AND MECHNICAL EQUIPMENT.
Revisions: Date:
KEY NOTES
360°
CD
W
W
X X
S
WAP
WAPWAP
AREA SHOWN
PROJECT
NORTH
Bc
Cc
10c
TYP.
Bc
Cc
10c
SECONDARY
BONDING BUSBAR
C
DATA RACK,
TYP.
TR
C185
184 SF
ACCESS CONTROL PANEL4
148-C185A
TN502
TN503
148-VRF-04-C185
148-VRF-03-C185
Bc
Cc
10c
TR
C185
184 SF
DATA RACK,
TYP.
TYP.
TN501
TYP.
TN501
C185
184 SF
PHYSICIAN
OFFICE
C185
Bc
Cc
10c
184 SF
PHYSICIAN
OFFICE
C185
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/0 /2
:1
:4 a m
B
IM
/5
-2
-7
V A
H a m p to n E
H R
M /E
E
B L D
G
.r v t
148TN401c
BLDG 148 - LEVEL 01 - ENLARGED
TELECOMMUNICATIONS PLANS
KG BCL/GPB
100% CONSTRUCTION
DOCUMENTS
07/18/2025
590-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
GENERAL NOTES
KEY PLAN
1/2" = 1'-0"148TN101A
1 RM C185 - DEMOLITION FLOOR PLAN
1/2" = 1'-0"148TN101A
2 RM C185 - TELECOMMUINCATIONS PLAN
1/2" = 1'-0"148TN101A
4 RM C185 - OVERHEAD PLAN
EXISTING EQUIPMENT TO BE DEMOLISHED. ASSOCIATED RACEWAYS AND CABLING
SHALL BE DEMOLISHED BACK TO SOURCE.
PROVIDE RIGID CONDUIT SLEEVES WITH FIRE PROOFING AS REQUIRED. SIDE 'A' AND
SIDE 'B' SLEEVES SHALL BE SEPARATED BY AT LEAST 10-FT.
WIRE BASKET CABLE TRAY.
PROVIDE (2)-DOOR ACCESS CONTROL PANEL TO SERVE ALL PACS DOOR SECURITY
EQUIPMENT FOR THIS TR ROOM. PROVIDE ALL REQUIRED CONNECTIONS,
PROGRAMMING, POWER SUPPLIES, AND COMPONENTS TO PROVIDE A COMPLETE
AND FULLY FUNCTIONAL SYSTEM. REFERENCE SPECIFICATION "28 13 00 - PHYSICAL
ACCESS CONTROL SYSTEM" FOR ADDITIONAL INFORMATION.
EXISTING WIRELESS ACCESS POINT TO BE RE-FED WITH (2) CAT6A CABLES.
1/2" = 1'-0"148TN101A
3 RM C185 - DEMOLITION OVERHEAD PLAN
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO ASSOCIATED TR.
5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO
REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,
MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE
INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY
FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
6. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 1" CONDUIT FROM NEW BACKBOX TO
ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO
TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM
OUTLET TO TR AS REQUIRED.
7. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION OF
HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL IN
AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
8. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD
BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS
REQUIRED.
9. ANY LIVE SYSTEMS IN DEMO'D TR'S MUST REMAIN LIVE. CONTRACTOR TO
COORDINATE WITH THE STATION TO IDENTIFY SYSTEMS THAT ARE LIVE. IF SYSTEMS
ARE LIVE; INSTALL NEW CABLE FROM DEMO’D TR TO NEW TR. REFER TO DETAIL '3' ON
TN506.
10. RAIL KITS ARE PROVIDED BY THE GC FOR EQUIPMENT MOUNTED IN THE TR CHANNEL
RACKS.
11. LADDER RACK IN ALL TR'S WILL BE MOUNTED 6" OFF THE WALLS TO ACCOMMODATE
ELECTRICAL AND MECHNICAL EQUIPMENT.
Revisions: Date:
W
WX
WX
D
C
Gd
Hd
2d 3d
184 SF
VISN GR& EC -
D185
Gd
Hd
2d 3d
148-D185A
C
SECONDARY BONDING
BUSBAR
TR
D185
184 SF
TN503
TN502
3DATA RACK,
TYP.
148-VRF-08-D-185
148-VRF-07-D185
Gd
Hd
2d 3d
Gd
Hd
2d 3d
DATA RACK,
TYP.
TR
D185
184 SF
TYP.
TN501
TYP.
TN501
D185
184 SF
VISN GR& EC -
D185
AREA SHOWN
PROJECT
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/1
/2
:1
:2
P
M
B
IM
/5
-2
-7
V A
H a m p to n E
H R
M /E
E
B L D
G
.r v t
148TN401d
BLDG 148 - LEVEL 01 - ENLARGED
TELECOMMUNICATIONS PLANS
KG BCL/GPB
100% CONSTRUCTION
DOCUMENTS
07/18/2025
590-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
1" = 25'-0"148TN101B
1 RM D185 - DEMOLITION FLOOR PLAN
1" = 25'-0"148TN101B
2 RM D185 - TELECOMMUNICATIONS PLAN
3/8" = 1'-0"148TN101A
3 RM D185 - DEMOLITION OVERHEAD PLAN
3/8" = 1'-0"148TN101A
4 RM D185 - OVERHEAD PLAN
GENERAL NOTES
KEY PLAN
2'0 4' 6' 2'0 4' 6'
2'0 4' 6'2'0 4' 6'
PROJECT
NORTH
PROJECT
NORTH
PROJECT
NORTH
PROJECT
NORTH
PROVIDE RIGID CONDUIT SLEEVES WITH FIRE PROOFING AS REQUIRED. SIDE 'A' AND
SIDE 'B' SLEEVES SHALL BE SEPARATED BY AT LEAST 10-FT.
WIRE BASKET CABLE TRAY.2
1. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO ASSOCIATED TR.
5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO
REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,
MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE
INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY
FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
6. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 1" CONDUIT FROM NEW BACKBOX TO
ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO
TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM
OUTLET TO TR AS REQUIRED.
7. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION OF
HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL IN
AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
8. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD
BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS
REQUIRED.
9. ANY LIVE SYSTEMS IN DEMO'D TR'S MUST REMAIN LIVE. CONTRACTOR TO
COORDINATE WITH THE STATION TO IDENTIFY SYSTEMS THAT ARE LIVE. IF SYSTEMS
ARE LIVE; INSTALL NEW CABLE FROM DEMO’D TR TO NEW TR. REFER TO DETAIL '3' ON
TN506.
10. RAIL KITS ARE PROVIDED BY THE GC FOR EQUIPMENT MOUNTED IN THE TR CHANNEL
RACKS.
11. LADDER RACK IN ALL TR'S WILL BE MOUNTED 6" OFF THE WALLS TO ACCOMMODATE
ELECTRICAL AND MECHNICAL EQUIPMENT.
Revisions: Date:
PROJECT
NORTH
10s
DATA RACK
TEL. TERMINAL
BLOCK
TELECOM PANEL
EXISTING GROUNDING
BUSBAR
ELECTRICAL
CLOSET
S113
18 SF
10s
ELECTRICAL
CLOSET
S113
18 SF
TEL. TERMINAL
BLOCK
TELECOM PANEL
EXISTING GROUNDING
BUSBAR
10s
ELECTRICAL
CLOSET
S113
18 SF
S113
10s
P
ELECTRICAL
CLOSET
S113
18 SF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/0 /2
:1
:5 a m
B
IM
/5
-2
-7
V A
H a m p to n E
H R
M /E
E
B L D
G
.r v t
148TN401e
BLDG 148 - LEVEL 01 - ENLARGED
TELECOMMUNICATIONS PLANS
KG BCL/GPB
100% CONSTRUCTION
DOCUMENTS
07/18/2025
590-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
GENERAL NOTES
KEY PLAN
KEY NOTES
1/2" = 1'-0"148TN101A
1 RM S113 - DEMOLITION FLOOR PLAN
1/2" = 1'-0"148TN101A
2 RM S113 - TELECOMMUNICATIONS PLAN
1/2" = 1'-0"148TN101A
4 RM S113 - OVERHEAD PLAN
2'0 4' 6'
PROJECT
NORTH
EXISTING DATA RACK TO BE DECOMMISIONED BY VA. CONTRACTOR SHALL
COORDINATE WITH VA AS REQUIRED.
EXISTING VERTICAL CABLING SLEEVES (QTY = 18) TO BE PRESERVED. EXISTING FIBER
OPTIC AND/OR EXISTING VERTICAL CABLING RELATED TO EXISTING TR RACKS TO BE
DEMOLISHED.
EXISTING PENETRATIONS WITH CABLING TO BE REMOVED. CONTRACTOR SHALL
PATCH AND FIREPROOF OPENINGS. COORDINATE WITH ARCHITECTURAL DRAWINGS
AND SPECIFICATIONS.
1/2" = 1'-0"148TN101A
3 RM S113 - DEMOLITION OVERHEAD PLAN 2'0 4' 6'
PROJECT
NORTH
2'0 4' 6'
PROJECT
NORTH
2'0 4' 6'
PROJECT
NORTH
1. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO ASSOCIATED TR.
5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO
REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,
MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE
INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY
FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
6. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 1" CONDUIT FROM NEW BACKBOX TO
ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO
TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM
OUTLET TO TR AS REQUIRED.
7. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION OF
HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL IN
AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
8. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD
BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS
REQUIRED.
9. ANY LIVE SYSTEMS IN DEMO'D TR'S MUST REMAIN LIVE. CONTRACTOR TO
COORDINATE WITH THE STATION TO IDENTIFY SYSTEMS THAT ARE LIVE. IF SYSTEMS
ARE LIVE; INSTALL NEW CABLE FROM DEMO’D TR TO NEW TR. REFER TO DETAIL '3' ON
Revisions: Date: 609 of 713
Mb
8b 9b
FACP
TELEPHONE
TERMINAL BOARDS
FIBER OPTIC
PATCH PANEL
POWER PANEL
ACCESS
CONTROL PANEL
DATA RACK
BONDING BUSBAR
COMMUNICATION
CLOSET
B175
36 SF
Mb
8b 9b
FACP
TELEPHONE
TERMINAL BOARDS
FIBER OPTIC
PATCH PANEL
POWER PANEL
ACCESS
CONTROL PANEL
BONDING BUSBAR
COMMUNICATION
CLOSET
B175
36 SF
Mb
8b 9b
COMMUNICATION
CLOSET
B175
36 SF
Mb
8b 9b
COMMUNICATION
CLOSET
B175
36 SF
B175
AREA SHOWN
PROJECT
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/0 /2
:1
:0 a m
B
IM
/5
-2
-7
V A
H a m p to n E
H R
M /E
E
B L D
G
.r v t
148TN401f
BLDG 148 - LEVEL 01 - ENLARGED
TELECOMMUNICATIONS PLANS
KG BCL/GPB
100% CONSTRUCTION
DOCUMENTS
07/18/2025
590-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
GENERAL NOTES
KEY PLAN
KEY NOTES
EXISTING DATA RACK TO BE DECOMMISIONED BY VA. CONTRACTOR SHALL
COORDINATE WITH VA AS REQUIRED.
EXISTING VERTICAL CABLING SLEEVE TO BE PRESERVED. EXISTING FIBER OPTIC
AND/OR EXISTING VERTICAL CABLING RELATED TO EXISTING TR RACKS TO BE
DEMOLISHED.
21/2" = 1'-0"148TN101B
1 RM B175 - DEMOLITION FLOOR PLAN
1/2" = 1'-0"148TN101B
2 RM B175 - TELECOMMUNICATIONS PLAN
1/2" = 1'-0"148TN101A
3 RM B175 - DEMOLITION OVERHEAD PLAN
1/2" = 1'-0"148TN101A
4 RM B175 - OVERHEAD PLAN
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO ASSOCIATED TR.
5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO
REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,
MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE
INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY
FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
6. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 1" CONDUIT FROM NEW BACKBOX TO
ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO
TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM
OUTLET TO TR AS REQUIRED.
7. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION OF
HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL IN
AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
8. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD
BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS
REQUIRED.
9. ANY LIVE SYSTEMS IN DEMO'D TR'S MUST REMAIN LIVE. CONTRACTOR TO
COORDINATE WITH THE STATION TO IDENTIFY SYSTEMS THAT ARE LIVE. IF SYSTEMS
ARE LIVE; INSTALL NEW CABLE FROM DEMO’D TR TO NEW TR. REFER TO DETAIL '3' ON
Revisions: Date: 610 of 713
C175
Ec
FACP
TELEPHONE
TERMINAL BOARDS
ACCESS POWER
CONTROLLER PANEL
FIBER OPTIC
PATCH PANEL
DATA RACK
BONDING BUS
D2
D2
TYP.
COMMUNICATION
CLOSET
C175
33 SF
Ec
N2
N2
TYP.
FACP
TELEPHONE
TERMINAL BOARDS
ACCESS POWER
CONTROLLER PANEL
FIBER OPTIC
PATCH PANEL
BONDING BUS
COMMUNICATION
CLOSET
C175
33 SF
AREA SHOWN
PROJECT
NORTH
Ec
COMMUNICATION
CLOSET
C175
33 SF
Ec
COMMUNICATION
CLOSET
C175
33 SF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/0 /2
:1
:1 a m
B
IM
/5
-2
-7
V A
H a m p to n E
H R
M /E
E
B L D
G
.r v t
148TN401g
BLDG 148 - LEVEL 01 - ENLARGED
TELECOMMUNICATIONS PLANS
KG BCL/GPB
100% CONSTRUCTION
DOCUMENTS
07/18/2025
590-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
GENERAL NOTES
KEY PLAN
KEY NOTES
1'0 2' 4'
PROJECT
NORTH
1/2" = 1'-0"148TN101A
1 RM C175 - DEMOLITION FLOOR PLAN
1/2" = 1'-0"148TN101A
2 RM C175 - TELECOMMUNICATIONS PLAN EXISTING DATA RACK TO BE DECOMMISIONED BY VA. CONTRACTOR SHALL
COORDINATE WITH VA AS REQUIRED.
EXISTING VERTICAL CABLING SLEEVE TO BE PRESERVED. EXISTING FIBER OPTIC
AND/OR EXISTING VERTICAL CABLING RELATED TO EXISTING TR RACKS TO BE
DEMOLISHED.
EXISTING EQUIPMENT TO BE DEMOLISHED. ASSOCIATED CABLING SHALL BE
DEMOLISHED BACK TO SOURCE.
PROVIDE TELECOMMUNICATIONS OUTLET WITH PORT QUANTITY SHOWN TO
REPLACE EXISTING TELECOMMUNICATIONS OUTLET; EXISTING OUTLET CONDUIT
SHALL REMAIN AND BE UTILIZED TO FEED NEW CABLING; REFERENCE SHEET DETAIL
'1' ON SHEET TN501 AND THE GENERAL NOTES ON THIS SHEET FOR ADDITIONAL
INFORMATION. COORDINATE WITH VA FOR EXACT OUTLET PLACEMENT.
1/2" = 1'-0"148TN101A
3 RM C175 - DEMOLITION OVERHEAD PLAN 1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1/2" = 1'-0"148TN101A
4 RM C175 - OVERHEAD PLAN 1'0 2' 4'
PROJECT
NORTH
1. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO ASSOCIATED TR.
5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO
REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,
MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE
INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY
FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
6. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 1" CONDUIT FROM NEW BACKBOX TO
ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO
TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM
OUTLET TO TR AS REQUIRED.
7. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION OF
HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL IN
AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
8. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD
BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS
REQUIRED.
9. ANY LIVE SYSTEMS IN DEMO'D TR'S MUST REMAIN LIVE. CONTRACTOR TO
COORDINATE WITH THE STATION TO IDENTIFY SYSTEMS THAT ARE LIVE. IF SYSTEMS
ARE LIVE; INSTALL NEW CABLE FROM DEMO’D TR TO NEW TR. REFER TO DETAIL '3' ON
Revisions: Date: 611 of 713
PROJECT
NORTH
D175
Ed
5d
FACP
TELEPHONE
TERMINAL BOARDS
ACCESS CONTROL
PANEL
FIBER OPTIC
PATCH PANEL
EXISTING BONDING
BUSBAR
DATA RACK
COMMUNICATION
CLOSET
D175
34 SF
Ed
5d
FACP
TELEPHONE
TERMINAL BOARDS
ACCESS CONTROL
PANEL
FIBER OPTIC
PATCH PANEL
EXISTING BONDING
BUSBAR
COMMUNICATION
CLOSET
D175
34 SF
Ed
5d
COMMUNICATION
CLOSET
D175
34 SF
Ed
5d
COMMUNICATION
CLOSET
D175
34 SF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/0 /2
:1
:2 a m
B
IM
/5
-2
-7
V A
H a m p to n E
H R
M /E
E
B L D
G
.r v t
148TN401h
BLDG 148 - LEVEL 01 - ENLARGED
TELECOMMUNICATIONS PLANS
KG BCL/GPB
100% CONSTRUCTION
DOCUMENTS
07/18/2025
590-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
GENERAL NOTES
KEY PLAN
KEY NOTES
EXISTING DATA RACK TO BE DECOMMISIONED BY VA. CONTRACTOR SHALL
COORDINATE WITH VA AS REQUIRED.
EXISTING VERTICAL CABLING SLEEVE TO BE PRESERVED. EXISTING FIBER OPTIC
AND/OR EXISTING VERTICAL CABLING RELATED TO EXISTING TR RACKS TO BE
DEMOLISHED.
21/2" = 1'-0"148TN101A
1 RM D175 - DEMOLITION FLOOR PLAN
1/2" = 1'-0"148TN101A
2 RM D175 - TELECOMMUNICATIONS PLAN
1/2" = 1'-0"148TN101A
3 RM D175 - DEMOLITION OVERHEAD PLAN
1/2" = 1'-0"148TN101A
4 RM D175 - OVERHEAD PLAN
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO ASSOCIATED TR.
5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO
REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,
MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE
INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY
FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
6. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 1" CONDUIT FROM NEW BACKBOX TO
ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO
TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM
OUTLET TO TR AS REQUIRED.
7. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION OF
HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL IN
AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
8. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD
BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS
REQUIRED.
9. ANY LIVE SYSTEMS IN DEMO'D TR'S MUST REMAIN LIVE. CONTRACTOR TO
COORDINATE WITH THE STATION TO IDENTIFY SYSTEMS THAT ARE LIVE. IF SYSTEMS
ARE LIVE; INSTALL NEW CABLE FROM DEMO’D TR TO NEW TR. REFER TO DETAIL '3' ON
Revisions: Date: 612 of 713
WAP WAP
PROJECT
NORTH
Es
4s 5s
DATA CABINET
FIRE ALARM
EQUIPMENT
UNLABELED
PANEL (ABOVE)
UNLABELED
PANEL
AHU METERING
PANEL (BELOW)
MAIN
COMMUNICATION
CLOSET
S128
70 SF
Es
4s 5s
FIRE ALARM
EQUIPMENT
UNLABELED
PANEL (ABOVE)
UNLABELED
PANEL
AHU METERING
PANEL (BELOW)
MAIN
COMMUNICATION
CLOSET
S128
70 SF
TELEPHONE TERMINAL PANEL
TELEPHONE TERMINAL BOARDS
FIBER OPTIC PANEL
S
Es
4s 5s
P
P
PPPP
MAIN
COMMUNICATION
CLOSET
S128
70 SF
Es
4s 5s
MAIN
COMMUNICATION
CLOSET
S128
70 SF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/0 /2
:1
:3 a m
B
IM
/5
-2
-7
V A
H a m p to n E
H R
M /E
E
B L D
G
.r v t
148TN401i
BLDG 148 - LEVEL 01 - ENLARGED
TELECOMMUNICATIONS PLANS
KG BCL/GPB
100% CONSTRUCTION
DOCUMENTS
07/18/2025
590-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
GENERAL NOTES
KEY PLAN
KEY NOTES
EXISTING DATA RACK TO BE DECOMMISIONED BY VA. CONTRACTOR SHALL
COORDINATE WITH VA AS REQUIRED.
EXISTING VERTICAL CABLING SLEEVE TO BE PRESERVED. EXISTING FIBER OPTIC
AND/OR EXISTING VERTICAL CABLING RELATED TO EXISTING TR RACKS TO BE
DEMOLISHED.
EXISTING WIRELESS ACCESS POINT TO BE RE-FED WITH (2) CAT6A CABLES.
EXISTING PENETRATIONS WITH CABLING TO BE REMOVED. CONTRACTOR SHALL
PATHC AND FIREPROOF OPENINGS. COORDINATE WITH ARCHITECTURAL DRAWINGS
AND SPECIFICATIONS.
1/2" = 1'-0"148TN101A
1 RM S128 - DEMOLITION FLOOR PLAN
1/2" = 1'-0"148TN101A
2 RM S128 - TELECOMMUNICATIONS PLAN1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1/2" = 1'-0"148TN101A
3 RM S128 - DEMOLITION OVERHEAD PLAN
1/2" = 1'-0"148TN101A
4 RM S128 - OVERHEAD PLAN 1'0 2' 4'
PROJECT
NORTH
1. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO ASSOCIATED TR.
5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO
REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,
MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE
INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY
FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
6. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET
CURRENTLY DOES NOT EXIST, PROVIDE (1) 1" CONDUIT FROM NEW BACKBOX TO
ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO
TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM
OUTLET TO TR AS REQUIRED.
7. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION OF
HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL IN
AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
8. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD
BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS
REQUIRED.
9. ANY LIVE SYSTEMS IN DEMO'D TR'S MUST REMAIN LIVE. CONTRACTOR TO
COORDINATE WITH THE STATION TO IDENTIFY SYSTEMS THAT ARE LIVE. IF SYSTEMS
ARE LIVE; INSTALL NEW CABLE FROM DEMO’D TR TO NEW TR. REFER TO DETAIL '3' ON
Revisions: Date: 613 of 713
Ga
3a
FACPPOWER PANEL
SECURITY ACCESS PANEL
TELEPHONE
TERMINAL BOARDS
ACCESS CONTROL
PANEL
ACCESS
CONTROLLER PANELDATA RACK
BONDING BUS
Ga
3a
FACPPOWER PANEL
SECURITY ACCESS PANEL
TELEPHONE
TERMINAL BOARDS
ACCESS
CONTROLLER PANEL
BONDING BUS
A175
AREA SHOWN
PROJECT
NORTH
Ga
3a
Ga
3a
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/0 /2
:1
:4 a m
B
IM
/5
-2
-7
V A
H a m p to n E
H R
M /E
E
B L D
G
.r v t
148TN401j
BLDG 148 - LEVEL 01 - ENLARGED
TELECOMMUNICATIONS PLANS
KG BCL/GPB
100% CONSTRUCTION
DOCUMENTS
07/18/2025
590-22-700EHRM INFRASTRUCTURE
UPGRADES - HAMPTON
HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA
GENERAL NOTES
KEY PLAN
KEY NOTES
1/2" = 1'-0"148TN101A
1 RM A175 - DEMOLITION FLOOR…