Att. 7 - Set 5 of 8 Final Drawings By Building 590 22 700.pdf

PDF 34 MB Posted

Attached to
Y1DA--590-22-700 | Construct EHRM Infrastructure Upgrade | Hampton, VA | Federal contract opportunity
Solicitation number
36C77626R0041
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This is a set of final construction drawings for the EHRM Infrastructure Upgrades project at Hampton VA Medical Center in Hampton, Virginia. The drawings, designated as "Set 5 of 8," represent 100% construction documents dated May 9, 2025, and include detailed plans for Buildings 43, 44, 48, 66, 83, 110, and 110B across multiple levels.

The construction documents encompass comprehensive infrastructure work including technology systems, mechanical, plumbing, electrical, and structural components. Key design elements include new telecommunications rooms (TRs) with fiber optic distribution cabinets, variable refrigerant flow (VRF) cooling units, fire protection systems with sprinkler installations, and extensive data cabling infrastructure using CAT6A cables throughout multiple buildings. The drawings detail specific room layouts, equipment locations, conduit routing for optical fiber cables (24-strand OS2 fiber with both Core A and B pathways to Building 135), mechanical penetrations, electrical panelboards with A-side and B-side power feeds, and phased construction sequences coordinated with VA facility operations. The design includes ICRA (Infection Control Risk Assessment) barriers in specific areas and notes that work shall proceed in phases with contractor coordination regarding room closures and availability. The architect/engineer of record is StampConsultant with engineering discipline by SPEES Design Build located in Kent, Washington, and construction document approval is pending with a fully sprinklered occupancy classification noted throughout.

View the file

Other files for this federal contract opportunity

Other files attached to Y1DA--590-22-700 | Construct EHRM Infrastructure Upgrade | Hampton, VA |, newest first.
File Type Posted
Att. 3 - Brand Name Justification.pdf PDF
Att. 2 - Specifications - 4-23-2026.pdf PDF
Att. 1 - Tech Questions Tracker - 590-22-700.pdf PDF
36C77626R0041 0003.pdf PDF
36C77626R0041 0002.pdf PDF
Att. 1 - 52.222-90 ADDRESSING DEI DISCRIMINATION BY FEDERAL CONTRACTORS - APR 2026.pdf PDF
36C77626R0041 0001.pdf PDF
Attachment 01 - Site Visit Sign in Sheet.pdf PDF
Att. 12 - Set 2 of 8 Final Drawings By Discipline 590 22 700.pdf PDF
Att. 6 - Set 4 of 8 Final Drawings By Building 590 22 700.pdf PDF
Att. 24 - Key Personnel.pdf PDF
Att. 23 - KSI.pdf PDF
Att. 17 - Set 7 of 8 Final Drawings By Discipline 590 22 700.pdf PDF
Att. 15 - Set 5 of 8 Final Drawings By Discipline 590 22 700.pdf PDF
Att. 14 - Set 4 of 8 Final Drawings By Discipline 590 22 700.pdf PDF
Att. 8 - Set 6 of 8 Final Drawings By Building 590 22 700.pdf PDF
Att. 3 - Set 1 of 8 Final Drawings By Building 590 22 700.pdf PDF
Att. 2 - Specifications.pdf PDF
36C77626R0041.pdf PDF
Att. 22 - Limitations on Subcontracting.pdf PDF
Att. 18 - Set 8 of 8 Final Drawings By Discipline 590 22 700.pdf PDF
Att. 13 - Set 3 of 8 Final Drawings By Discipline 590 22 700.pdf PDF
Att. 10 - Set 8 of 8 Final Drawings By Building 590 22 700.pdf PDF
Att. 9 - Set 7 of 8 Final Drawings By Building 590 22 700.pdf PDF
Att. 5 - Set 3 of 8 Final Drawings By Building 590 22 700.pdf PDF
Att. 21 - HEFP SEP Design Alerts 1-9 and 11-16.pdf PDF
Att. 20 - Division Pricing Template.xlsx XLSX spreadsheet
Att. 19 - DBA Wage Determination.pdf PDF
Att. 16 - Set 6 of 8 Final Drawings By Discipline 590 22 700.pdf PDF
Att. 11 - Set 1 of 8 Final Drawings By Discipline 590 22 700.pdf PDF
Att. 4 - Set 2 of 8 Final Drawings By Building 590 22 700.pdf PDF
Att. 1 - Construction SOW.pdf PDF
Show all 32

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A B C D

E F G

H

I

C.2 C.3

I.5

J

K

L

M

N

20.5

8.5

IDES OFFICE

105B

LOBBY

HCHV OFFICE

ELEV MECH

ROOM

BATHROOM

TR

105H

STAIRWELL

HVAC MECH

ROOM

STAIRWELL

VESTIBULE

IDES WAITING

AREA

IDES CORRIDOR

STAIRWAY

WOMEN'S

BATHROOM

VA STATE VET

ASST OFFICE

ELEV 1

E-1

VESTIBULE

101A

HAC CLOSET

101C

CLOSET

101D

CCHT

101E

UNION OFFICE

105A

CCHT

105C

CCHT/AMBULATORY

CARE

105D RURAL HEALTH

105E

CLINICAL

APPLICATION

COORDINATORS

105F

CLINICAL

APPLICATION

COORDINATORS

105G

CORRIDOR

VA STATE VET

ASST OFFICE

114A

MECH ROOM

109A

IDES EXAM ROOM

111A

IDES PHYCH

OFFICE

111C

IDES PSYCH

OFFICE

111D

IDES EXAM ROOM

111E

BATHROOM

111F

IDES EXAM ROOM

111G

IDES OFFICE

111H

CLEAN STORAGE

111J

IDES EXAM ROOM

111K

DIRTY STORAGE

111L

IDES

CONFERENCE RM

111B.1

ELECTRICAL

ROOM

101B

IDES RECEPTION

111B

STORAGE

CLOSET

108A

HAC CLOSET

105K

43T-400

OUTLINE OF

TR #205H AT

FLOOR ABOVE

REFER TO TS001

FOR CONTINUATION

HH26

PW-PB-1

A

REFER TO TS001

FOR CONTINUATION

HH27

B PW-PB-1

B

A

(1) 4"C - (2) 24 STRAND OS2 FIBER CABLES (A)

43T-400

(1) 4"C - (2) 24-STRAND OS2 FIBER

CABLES (A) AND (1) 4"C - SPARE

(1) 4"C - (1) 24-STRAND

OS2 FIBER CABLE (B)

(1) 4"C - (1) 24-STRAND

OS2 FIBER CABLE (A)

(1) 4"C - (2) 24-STRAND OS2 FIBER

CABLES (B) AND (1) 4"C - SPARE

TR #105H

(1) 4"C - (2) 24 STRAND OS2 FIBER CABLES (B)

Eddie C. Willis, Jr.

REG. NO. 191562R

EXPIRES 12-31-2025

REGIS

TE

R

ED

CO

MMUNICA T IONS DISTRIBUT IO

N

DESIGNER

RCDD

225 W WASHINGTON STREET

SUITE 2700

CHICAGO, IL 60606

P: 312.294.0501 F: 312.294.0003 www.imegcorp.com

PROJECT #22010109.00

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

/1

/2

:2

:4

P

M

B

IM

/5

-2

-7

V A

H a m p to n E

H R

M /5

-7

.B

.T

R

.r v t

43T-201

BLDG.43 LEVEL 01 PLAN - TECHNOLOGY

EW IMEG

100% CONSTRUCTION

DOCUMENTS

05/09/2025

509-22-700EHRM INFRASTRUCTURE

UPGRADES - HAMPTON

HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA

N O R

HT

1/8" = 1'-0"

LEVEL 01 PLAN - TECHNOLOGY

SHEET NOTES:

1. REFER TO SITEPLAN TS001 FOR ADDITIONAL

INFORMATION.

2. REFER TO T500 AND T501 FOR CAMPUS OPTICAL

FIBER CABLE RISER DIAGRAMS.

3. REFER TO 2/T400 FOR HANDHOLE DETAIL.

4. NEW BACKBONE OPTICAL FIBER CABLES SHALL BE

INDOOR/OUTDOOR TYPE.

5. ALL BACKBONE OPTICAL FIBER CABLE PATHWAYS SHALL

BE NEW. DO NOT RE-USE EXISTING BACKBONE CABLE

PATHWAYS FOR NEW BACKBONE CABLES.

6. TRANSITION PVC CONDUITS TO GRC IN CRAWL SPACE OR

EXPOSED EXTERIOR LOCATIONS. TRANSITION TO EMT

CONDUITS AT INTERIOR OF BUILDING. SEAL ALL

PENETRATIONS TO MAINTAIN FIRE-RATINGS OF WALL,

CEILING AND FLOORS.

7. CONDUIT ROUTES THRU CRAWL SPACE ARE

"SUGGESTED" ROUTE. FIELD VERIFY EXACT ROUTE THRU

CRAWL SPACE.

KEY NOTES:

1. PROVIDE PENETRATION THRU WALL AND ROUTE

CONDUIT INTO CRAWL SPACE AND CONTINUE TO

LOCATION BELOW TR #105H.

2. PROVIDE PENETRATION TRHU CEILING DECK AND ROUTE

CONDUIT UP INTO TR #105H.

3. ROUTE CONDUIT UP TO HEIGHT ABOVE CABLE TRAY.

PROVIDE PULLBOX AND PENETRATION THRU CEILING TO

ROUTE CONDUIT UP INTO TR #205H.

Revisions: Date: 301 of 713

A B C D

E F G

H

I

C.2 C.3

I.5

J

K

L

M

N

20.5

8.5

CLASSROOM /

STORAGE

201A

BATHROOM

BATHROOM

BATHROOM

TR

205H

STAIRWELL

206 COFFEE ROOM

STAIRWAY

CORRIDOR

OFFICE

STAIRWELL

STORAGE

OFFICE

ELEVATOR 2

E-2

IRM OFFICE

205A

IRM OFFICE

205B

IRM OFFICE

205C

IRM OFFICE

205E

IRM OFFICE

205F

IRM OFFICE

205G

CORRIDOR

COMPUTER LAB

209A

HARDWARE

MAINTENANCE

209B

TRAINING ROOM

209C

IRM OFFICE

209D

STORAGE

209F

CORRIDOR

IRM OFFICE

205D

43T-400

TR-43-205H

A

B

43T-400

(1) 4"C - (1) 24-STRAND OS2 FIBER CABLE (A)

(1) 4"C - (1) 24-STRAND OS2 FIBER CABLE (B)

TR #205H

Eddie C. Willis, Jr.

REG. NO. 191562R

EXPIRES 12-31-2025

REGIS

TE

R

ED

CO

MMUNICA T IONS DISTRIBUT IO

N

DESIGNER

RCDD

225 W WASHINGTON STREET

SUITE 2700

CHICAGO, IL 60606

P: 312.294.0501 F: 312.294.0003 www.imegcorp.com

PROJECT #22010109.00

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

/1

/2

:2

:4

P

M

B

IM

/5

-2

-7

V A

H a m p to n E

H R

M /5

-7

.B

.T

R

.r v t

43T-202

BLDG.43 LEVEL 02 PLAN - TECHNOLOGY

EW IMEG

100% CONSTRUCTION

DOCUMENTS

05/09/2025

509-22-700EHRM INFRASTRUCTURE

UPGRADES - HAMPTON

HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA

N O R

HT

1/8" = 1'-0"

LEVEL 02 PLAN - TECHNOLOGY

SHEET NOTES:

1. REFER TO SITEPLAN TS001 FOR ADDITIONAL

INFORMATION.

2. REFER TO T500 AND T501 FOR CAMPUS OPTICAL

FIBER CABLE RISER DIAGRAMS.

3. REFER TO 2/T400 FOR HANDHOLE DETAIL.

4. NEW BACKBONE OPTICAL FIBER CABLES SHALL BE

INDOOR/OUTDOOR TYPE.

5. ALL BACKBONE OPTICAL FIBER CABLE PATHWAYS SHALL

BE NEW. DO NOT RE-USE EXISTING BACKBONE CABLE

PATHWAYS FOR NEW BACKBONE CABLES.

6. TRANSITION PVC CONDUITS TO GRC IN CRAWL SPACE OR

EXPOSED EXTERIOR LOCATIONS. TRANSITION TO EMT

CONDUITS AT INTERIOR OF BUILDING. SEAL ALL

PENETRATIONS TO MAINTAIN FIRE-RATINGS OF WALL,

CEILING AND FLOORS.

KEY NOTES:

1. ROUTE CONDUIT UP TO HEIGHT ABOVE CABLE TRAY.

2. PROVIDE (2) SETS OF 6-STRAND, OM4, OPTICAL FIBER

CABLES FROM CORE A AND CORE B IN FIBER

DISTRIBUTION CABINET TO (2) EXISTING NETWORK

SWITCHES IN COMPUTER LAB #209A. REFER TO

ENLARGED PLANS FOR ADDITIONAL WORK

REQUIREMENTS.

Revisions: Date: 302 of 713

FIBER

DISTRIBUTION

CABINET

FIBER

DISTRIBUTION

CABINET

E G H

TR

105H

MECH ROOM

109A

A

B

WORK IN ROOM

BY OTHER

(1) 4"C - (1) 24-STRAND OS2 FIBER CABLE (A)

(1) 4"C - (1) 24-STRAND OS2 FIBER CABLE (B)

E

H

TR

205H

B

A

WORK IN ROOM

BY OTHER

(1) 4"C - (1) 24-STRAND OS2 FIBER CABLE (A)

(1) 4"C - (1) 24-STRAND OS2 FIBER CABLE (B)

E G H

TR

105H

MECH ROOM

109A

A

B

(1) 4"C - (1) 24-STRAND OS2 FIBER CABLE (A)

E

H

TR

205H

B

A

(1) 4"C - (1) 24-STRAND OS2 FIBER CABLE (A)

(1) 4"C - (1) 24-STRAND OS2 FIBER CABLE (B)

NOTES:

1. THIS RISER IS DIAGRAMMATIC AND MAY NOT SHOW

ACTUAL ROUTING OR QUANTITIES OF MATERIALS

SHOWN. THIS RISER IS SHOWN FOR CLARIFICATION

OF CONNECTION(S), LOCATIONS AND CABLE TYPE.

ALL INFORMATION OUTLETS ARE TYPICAL OF THE

OUTLETS IN THE AREA SHOWN. REFER TO FLOOR

PLANS FOR MORE SPECIFIC ROUTING INFORMATION.

REFER TO SPECIFICATIONS FOR ADDITIONAL

REQUIREMENTS.

2. REFER TO ELECTRICAL DRAWINGS FOR CHANNEL

RACK AND FIBER OPTIC DISTRIBUTION CABINET

SPECIFICATIONS

TELECOMMUNICATIONS ROOM TR #105H

24 STRANDS OS2 FIBER OPTIC

CABLE, CORE "A" , TO BUILDING 135

24 STRANDS OS2 FIBER OPTIC

CABLE, CORE "B" , TO BUILDING 135

CHANNEL RACK

LEVEL 01

TELECOMMUNICATIONS ROOM TR #205H

24 STRANDS OS2 FIBER OPTIC

CABLE, CORE "A" , TO BUILDING 135

24 STRANDS OS2 FIBER OPTIC

CABLE, CORE "B" , TO BUILDING 135

CHANNEL RACK

LEVEL 02

Eddie C. Willis, Jr.

REG. NO. 191562R

EXPIRES 12-31-2025

REGIS

TE

R

ED

CO

MMUNICA T IONS DISTRIBUT IO

N

DESIGNER

RCDD

225 W WASHINGTON STREET

SUITE 2700

CHICAGO, IL 60606

P: 312.294.0501 F: 312.294.0003 www.imegcorp.com

PROJECT #22010109.00

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

/1

/2

:2

:5

P

M

B

IM

/5

-2

-7

V A

H a m p to n E

H R

M /5

-7

.B

.T

R

.r v t

43T-400

BLDG.43 TECHNOLOGY ENLARGEMENTS

EW IMEG

100% CONSTRUCTION

DOCUMENTS

05/09/2025

509-22-700EHRM INFRASTRUCTURE

UPGRADES - HAMPTON

HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA

N O R

HT

1/2" = 1'-0"

TELECOM ROOM ENLARGEMENT TR #105H

N O R

HT

1/2" = 1'-0"

TELECOM ROOM ENLARGEMENT TR #205H

NOTES:

1. REFER TO ELECTRICAL DRAWINGS FOR ROOM LAYOUT AND RACK ELEVATIONS.

2. ROUTE OPTICAL FIBER CABLE TO OVERHEAD CABLE TRAY AND TERMINATE IN FIBER DISTRIBUTION

CABINET.

KEY NOTES:

1. THROUGH FLOOR PENETRATION FOR BACKBONE CONDUIT. OPTICAL FIBER CABLE CONTINUES ON CABLE

TRAY TO RACKS.

NOTES:

1. REFER TO ELECTRICAL DRAWINGS FOR ROOM LAYOUT AND RACK ELEVATIONS.

2. ROUTE OPTICAL FIBER CABLE TO OVERHEAD CABLE TRAY AND TERMINATE IN FIBER DISTRIBUTION

CABINET.

KEY NOTES:

1. THROUGH FLOOR/CEILING PENETRATION FOR BACKBONE CONDUIT. CONDUIT SHALL CONTINUE UP

TO HEIGHT OF CABLE TRAY. OPTICAL FIBER CABLE CONTINUES ON CABLE TRAY TO RACKS.

2. PROVIDE NEW PATHWAY THRU WALL OF TELECOM ROOM TO ROUTE FIBER CABLES INTO COMPUTER

ROOM #209A.

3. PROVIDE (2) SETS OF 2-STRAND, OM4, OPTICAL FIBER CABLES FROM CORE A AND CORE B IN FIBER DISTRIBUTION CABINET IN NEW RACK TO EXISTING NETWORK SWITCHES IN COMPUTER LAB #209A VIA INNERDUCT AND CABLE SUPPORTS. TERMINATE BOTH ENDS OF EACH CABLE WITH LC CONNECTORS.

REFER TO SECOND FLOOR PLAN FOR LOCATION OF COPUTER LAB #209A.

N O R

HT

1/2" = 1'-0"

TELECOM ROOM PATHWAY TR #105H

N O R

HT

1/2" = 1'-0"

TELECOM ROOM PATHWAY TR #205H

NO SCALE

FIBER RISER DIAGRAM

Revisions: Date: 303 of 713

27B

27 31

27A

110A

110B

110D

13W

148-D

148-S

148-A

148T

146B

146A

138A 138136

137A

137C

137D

137B

137C

148B

148-C

170 150

110C

143 167

G R

A V

E L

R O

A D

FRANKLIN BOULEVARD

FRANKLIN BOULEVARD

AVERILL AVENUE

AVERILL AVENUE

A M

E S

S T

R E

E T

HARRIS AVENUE

JONES CREEK

K N

O X S

T R

E E

T

T H

O M

P S

O N

S T

R E

E T

F R A N

K

LI

N B

O U

LE

V A R

D

MALLORY STREET

M A

R T

IN

L. K

IN

G

JR

. B O

U L E

V A R

D

M A R

TIN

L. K

IN

G

JR

. B O U

LE

V

AR

D

E M

A N

C

IP

A T

IO

N D

R

SHORE ROAD

H A R R

IS

A V E N

U E

HARRIS AVENUE

M c C

L E

L L A

N

S E

W E

LL

A

V E

N U

E

A V

E N

U E

A B C D E F G H I J K L M

205 SF

STAIR 2

S-2

99 SF

OFFICE

97 SF

OFFICE

100 SF

OFFICE

105 SF

OFFICE

105 SF

OFFICE

104 SF

OFFICE

102 SF

OFFICE

101 SF

OFFICE

102 SF

OFFICE

290 SF

CONFERENCE

103 SF

OFFICE

99 SF

OFFICE

102 SF

OFFICE

2080 SF

WORKSTATIONS

1129 SF

LOBBY/ATRIUM

100435 SF

BREAK ROOM

112 SF

TELECOM

102 SF

ELEC.

105A

214 SF

SPRINKLER

MECH/PLUMBING

199 SF

MEN'S TOILET

199 SF

WOMEN'S TOILET

71 SF

HOUSE KEEPING

CLOSET

61 SF

ELEV 1

E-1

61 SF

ELEV 2

E-2 2650 SF

WORK STATIONS

93 SF

OFFICE

93 SF

OFFICE

122 SF

ELEV. MECH

281 SF

CONFERENCE

98 SF

OFFICE

100 SF

OFFICE

98 SF

OFFICE

100 SF

OFFICE

88 SF

COPY AREA

105 SF

OFFICE

105 SF

OFFICE

100 SF

OFFICE

97 SF

OFFICE

100 SF

OFFICE

205 SF

STAIR 3

S-3

172 SF

STAIR 1

S-1

SECTION 1A:

CONTRACTOR TO COORDINATE WITH VA

FOR ROOM CLOSURES AND AVAILABILITY

TO COMPLETE DATA WIRING IN THIS AREA.

ICRA CLASS IV

TR

TR

FEC FIRE EXTINGUISHER CABINET

ICRA PHASING LINE

BUILDING BOUNDARY LINE

FE FIRE EXTINGUISHER

ICRA CLASS II

ICRA CLASS III

KEY AREA SHOWN

TRUE

NORTH

BUILDING 044

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

/0

/2

:1

:1 a m

B

IM

/5

-2

-7

V A

H a m p to n E

H R

M /B

L D

G

.r v t

44AS101

BUILDING 044 - LEVEL 01 - PHASING PLAN

MA CO

100% CONSTRUCTION

DOCUMENTS

07/18/2025

590-22-700EHRM INFRASTRUCTURE

UPGRADES - HAMPTON

HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA

1/8" = 1'-0"

BUILDING 44 - LEVEL 01 - PHASING PLAN

LEGEND

KEY PLAN

PROJECT

NORTH

0' 4' 8' 16'

Revisions: Date: 304 of 713

27B

27 31

27A

110A

110B

110D

13W

148-D

148-S

148-A

148T

146B

146A

138A 138136

137A

137C

137D

137B

137C

148B

148-C

170 150

110C

143 167

G R

A V

E L

R O

A D

FRANKLIN BOULEVARD

FRANKLIN BOULEVARD

AVERILL AVENUE

AVERILL AVENUE

A M

E S

S T

R E

E T

HARRIS AVENUE

JONES CREEK

K N

O X S

T R

E E

T

T H

O M

P S

O N

S T

R E

E T

F R A N

K

LI

N B

O U

LE

V A R

D

MALLORY STREET

M A

R T

IN

L. K

IN

G

JR

. B O

U L E

V A R

D

M A R

TIN

L. K

IN

G

JR

. B O U

LE

V

AR

D

E M

A N

C

IP

A T

IO

N D

R

SHORE ROAD

H A R R

IS

A V E N

U E

HARRIS AVENUE

M c C

L E

L L A

N

S E

W E

LL

A

V E

N U

E

A V

E N

U E

A B C D E F G H I J K L M

435 SF

BREAK ROOM

112 SF

TELECOM

346 SF

MECH/PLUMB

202 SF

MEN

202 SF

WOMEN

71 SF

HOUSEKEEPING

CLOSET

2693 SF

WORKSTATIONS

100 SF

OFFICE

99 SF

OFFICE

105 SF

OFFICE

149 SF

CONFERENCE

120 SF

OFFICE

114 SF

OFFICE

113 SF

OFFICE

3347 SF

LIBRARY

335 SF

CONFERENCE

43 SF

COPY AREA

100 SF

OFFICE

96 SF

OFFICE

100 SF

OFFICE

98 SF

OFFICE

99 SF

OFFICE

52 SF

FILE STORAGE

233A

204 SF

STAIR 3

102 SF

ELEC

203A

205 SF

STAIR 2

61 SF

ELEV #2

61 SF

ELEV #1

626 SF

LOBBY/ATRIUM

675 SF

CORRIDOR

NRN

SECTION 1A:

CONTRACTOR TO COORDINATE WITH VA

FOR ROOM CLOSURES AND AVAILABILITY

TO COMPLETE DATA WIRING IN THIS AREA.

ICRA CLASS IV

TR

TR

FEC FIRE EXTINGUISHER CABINET

ICRA PHASING LINE

BUILDING BOUNDARY LINE

FE FIRE EXTINGUISHER

ICRA CLASS II

ICRA CLASS III

KEY AREA SHOWN

TRUE

NORTH

BUILDING 044

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

/0

/2

:1

:1 a m

B

IM

/5

-2

-7

V A

H a m p to n E

H R

M /B

L D

G

.r v t

44AS102

BUILDING 044 - LEVEL 02 - PHASING PLAN

MA CO

100% CONSTRUCTION

DOCUMENTS

07/18/2025

590-22-700EHRM INFRASTRUCTURE

UPGRADES - HAMPTON

HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA

LEGEND

KEY PLAN

1/8" = 1'-0"

BUILDING 44 - LEVEL 02 - PHASING PLAN

PROJECT

NORTH

Revisions: Date: 305 of 713

A B C D E F

OFFICE

STAIR 2

S-2

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

CONFERENCE

OFFICE

OFFICE

OFFICE

WORKSTATIONS

LOBBY/ATRIUM

BREAK ROOM

TELECOM

ELEC.

105A

SPRINKLER

MECH/PLUMBING

MEN'S TOILET

WOMEN'S TOILET

HOUSE KEEPING

CLOSET

ELEV 1

E-1

ELEV 2

E-2

WORK STATIONS

OFFICE

OFFICE

ELEV. MECH

CONFERENCE

OFFICE

OFFICE

OFFICE

OFFICE

COPY AREA

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

STAIR 3

S-3

STAIR 1

S-1

TR-44-105

44T-400

DASHED OUTLINE

OF TR #202 AT

FLOOR ABOVE

A B

B

A (1) 4"C - (2) 24 STRAND OS2 FIBER

CABLES (B) AND (1) 4"C - SPARE

HANDHOLE

PULLBOX, TYP.

44T-400

(1) 4"C - (2) 24

STRAND OS2 FIBER

CABLES (A) AND (1)

4"C - SPARE

(1) 4"C - (2) 24 STRAND

OS2 FIBER CABLES (B)

(1) 4"C - (2) 24 STRAND

OS2 FIBER CABLES (A)

Eddie C. Willis, Jr.

REG. NO. 191562R

EXPIRES 12-31-2025

REGIS

TE

R

ED

CO

MMUNICA T IONS DISTRIBUT IO

N

DESIGNER

RCDD

225 W WASHINGTON STREET

SUITE 2700

CHICAGO, IL 60606

P: 312.294.0501 F: 312.294.0003 www.imegcorp.com

PROJECT #22010109.00

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

/2

/2

:1

:5

P

M

B

IM

/5

-2

-7

V A

H a m p to n E

H R

M /5

-7

.B

.T

R

.r v t

44T-101

BLDG.44 LEVEL 01 PLAN - TECHNOLOGY

EW IMEG

100% CONSTRUCTION

DOCUMENTS

05/09/2025

509-22-700EHRM INFRASTRUCTURE

UPGRADES - HAMPTON

HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA

N O R

HT

1/8" = 1'-0"

LEVEL 01 PLAN - TECHNOLOGY

SHEET NOTES:

1. REFER TO SITEPLAN TS001 FOR ADDITIONAL

INFORMATION.

2. REFER TO T500 AND T501 FOR CAMPUS OPTICAL FIBER

CABLE RISER DIAGRAMS.

3. REFER TO 2/T400 FOR HANDHOLE DETAIL.

4. NEW BACKBONE OPTICAL FIBER CABLES SHALL BE

INDOOR/OUTDOOR TYPE.

5. ALL BACKBONE OPTICAL FIBER CABLE PATHWAYS

SHALL BE NEW. DO NOT RE-USE EXISTING BACKBONE

CABLE PATHWAYS FOR NEW BACKBONE CABLES.

6. TRANSITION PVC CONDUITS TO GRC IN CRAWL SPACE

OR EXPOSED EXTERIOR LOCATIONS. TRANSITION TO

EMT CONDUITS AT INTERIOR OF BUILDING. SEAL ALL

PENETRATIONS TO MAINTAIN FIRE-RATINGS OF WALL,

CEILING AND FLOORS.

KEYNOTES:

1. PROVIDE PULLBOX ON EXTERIOR WALL AT HEIGHT OF

FIRST FLOOR CEILING. ROUTE CONDUIT FROM HANDHOLE

UP WALL INTO PULLBOX. PROVIDE PENETRATIONS THRU

WALLS AND CONTINUE ROUTE ABOVE CORRIDOR

FINISHED CEILING OVER INTO TR #105.

2. ROUTE CONDUITS INTO TR #105 AT ABOVE HEIGHT OF

CABLE TRAY. PROVIDE PULLBOX AND ROUTE CONDUIT TO

LOCATION BELOW TR #202. PROVIDE PENETRATIONS THRU

CEILING DECK AND ROUTE CONDUITS UP INTO TR #202.

Revisions: Date: 306 of 713

A B C D E F

BREAK ROOM

TELECOM

MECH/PLUMB

203 MEN

WOMEN

HOUSEKEEPING

CLOSET

WORKSTATIONS

OFFICE

OFFICE

OFFICE

CONFERENCE

OFFICE

OFFICE

OFFICE

LIBRARY

CONFERENCE

COPY AREA

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

FILE STORAGE

233A

STAIR 3

ELEC

203A

STAIR 2

ELEV #2

ELEV #1

LOBBY/ATRIUM

CORRIDOR

NRN

44T-400

TR-44-202

B

A

44T-400

(1) 4"C - (2) 24 STRAND

OS2 FIBER CABLES (A)

(1) 4"C - (2) 24 STRAND

OS2 FIBER CABLES (B)

Eddie C. Willis, Jr.

REG. NO. 191562R

EXPIRES 12-31-2025

REGIS

TE

R

ED

CO

MMUNICA T IONS DISTRIBUT IO

N

DESIGNER

RCDD

225 W WASHINGTON STREET

SUITE 2700

CHICAGO, IL 60606

P: 312.294.0501 F: 312.294.0003 www.imegcorp.com

PROJECT #22010109.00

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

/2

/2

:1

:5

P

M

B

IM

/5

-2

-7

V A

H a m p to n E

H R

M /5

-7

.B

.T

R

.r v t

44T-102

BLDG.44 LEVEL 02 PLAN - TECHNOLOGY

EW IMEG

100% CONSTRUCTION

DOCUMENTS

05/09/2025

509-22-700EHRM INFRASTRUCTURE

UPGRADES - HAMPTON

HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA

N O R

HT

1/8" = 1'-0"

LEVEL 02 PLAN - TECHNOLOGY

SHEET NOTES:

1. REFER TO SITEPLAN TS001 FOR ADDITIONAL

INFORMATION.

2. REFER TO T500 AND T501 FOR CAMPUS OPTICAL FIBER

CABLE RISER DIAGRAMS.

3. REFER TO 2/T400 FOR HANDHOLE DETAIL.

4. NEW BACKBONE OPTICAL FIBER CABLES SHALL BE

INDOOR/OUTDOOR TYPE.

5. ALL BACKBONE OPTICAL FIBER CABLE PATHWAYS SHALL

BE NEW. DO NOT RE-USE EXISTING BACKBONE CABLE

PATHWAYS FOR NEW BACKBONE CABLES.

6. TRANSITION PVC CONDUITS TO GRC IN CRAWL SPACE OR

EXPOSED EXTERIOR LOCATIONS. TRANSITION TO EMT

CONDUITS AT INTERIOR OF BUILDING. SEAL ALL

PENETRATIONS TO MAINTAIN FIRE-RATINGS OF WALL,

CEILING AND FLOORS.

KEY NOTES:

1. ROUTE CONDUIT UP THRU FLOOR FROM TR #105 AT

FLOOR BELOW. CONTINUE ROUTE OF CONDUIT UP TO

ABOVE CABLE TRAY.

Revisions: Date: 307 of 713

CABINET

FIBER

DISTRIBUTION

CABINET

TELECOM

B

A

NOTES:

1. THIS RISER IS DIAGRAMMATIC AND MAY NOT SHOW ACTUAL ROUTING OR QUANTITIES

OF MATERIALS SHOWN. THIS RISER IS SHOWN FOR CLARIFICATION OF

CONNECTION(S), LOCATIONS AND CABLE TYPE. ALL INFORMATION OUTLETS ARE

TYPICAL OF THE OUTLETS IN THE AREA SHOWN. REFER TO FLOOR PLANS FOR MORE

SPECIFIC ROUTING INFORMATION. REFER TO SPECIFICATIONS FOR ADDITIONAL

REQUIREMENTS.

2. REFER TO ELECTRICAL DRAWINGS FOR CHANNEL RACK AND FIBER OPTIC

DISTRIBUTION CABINET SPECIFICATIONS

TELECOMMUNICATIONS ROOM TR-44-105

24 STRANDS OS2 FIBER OPTIC

CABLE, SIDE "A" , TO BUILDING 135

24 STRANDS OS2 FIBER OPTIC

CABLE, SIDE "B" , TO BUILDING 135

TELECOMMUNICATIONS ROOM TR-44-202

24 STRANDS OS2 FIBER OPTIC

CABLE, SIDE "A" , TO BUILDING 135

24 STRANDS OS2 FIBER OPTIC

CABLE, SIDE "B" , TO BUILDING 135

CHANNEL RACK

CHANNEL RACK

LEVEL 01

LEVEL 02

A B

TELECOM

B

A

TELECOM

A B

Eddie C. Willis, Jr.

REG. NO. 191562R

EXPIRES 12-31-2025

REGIS

TE

R

ED

CO

MMUNICA T IONS DISTRIBUT IO

N

DESIGNER

RCDD

225 W WASHINGTON STREET

SUITE 2700

CHICAGO, IL 60606

P: 312.294.0501 F: 312.294.0003 www.imegcorp.com

PROJECT #22010109.00

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

/2

/2

:1

:5

P

M

B

IM

/5

-2

-7

V A

H a m p to n E

H R

M /5

-7

.B

.T

R

.r v t

44T-400

BLDG.44 TECHNOLOGY ENLARGED PLANS

EW IMEG

100% CONSTRUCTION

DOCUMENTS

05/09/2025

509-22-700EHRM INFRASTRUCTURE

UPGRADES - HAMPTON

HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA

N O R

HT

1/2" = 1'-0"

TELECOM ROOM ENLARGEMENT PLAN - TR-44-202

NO SCALE

FIBER RISER DIAGRAM

N O R

HT

1/2" = 1'-0"

TELECOM ROOM ENLARGEMENT PLAN - TR-44-105

NOTES:

1. REFER TO ELECTRICAL DRAWINGS FOR ROOM LAYOUT AND RACK ELEVATIONS.

2. ROUTE OPTICAL FIBER CABLES TO OVERHEAD CABLE TRAYS AND TERMINATE IN FIBER

DISTRIBUTION CABINET

KEYNOTES:

1. THROUGH WALL PENETRATION FOR BACKBONE CONDUIT. OPTICAL FIBER CABLES

CONTINUE ON CABLE TRAY TO RACKS.

NOTES:

1. REFER TO ELECTRICAL DRAWINGS FOR ROOM LAYOUT AND RACK ELEVATIONS.

2. ROUTE OPTICAL FIBER CABLES TO OVERHEAD CABLE TRAYS AND TERMINATE IN FIBER

DISTRIBUTION CABINET

KEYNOTES:

1. THROUGH FLOOR/CEILING PENETRATION FOR BACKBONE CONDUIT. CONTINUE CONDUTI

UP TO ABOVE CABLE TRAY. OPTICAL FIBER CABLES CONTINUE ON CABLE TRAY TO RACKS.

N O R

HT

1/2" = 1'-0"

TELECOM ROOM PATHWAYS - TR-44-202

N O R

HT

1/2" = 1'-0"

TELECOM ROOM PATHWAYS - TR-44-105

Revisions: Date: 308 of 713

27B

27 31

27A

110A

110B

110D

13W

148-D

148-S

148-A

148T

146B

146A

138A 138136

137A

137C

137D

137B

137C

148B

173A

148-C

170 150

110C

143 167

G R

A V

E L

R O

A D

FRANKLIN BOULEVARD

FRANKLIN BOULEVARD

AVERILL AVENUE

AVERILL AVENUE

A M

E S

S T

R E

E T

HARRIS AVENUE

JONES CREEK

K N

O X S

T R

E E

T

T H

O M

P S

O N

S T

R E

E T

F R A N

K

LI

N B

O U

LE

V A R

D

MALLORY STREET

M A

R T

IN

L. K

IN

G

JR

. B O

U L E

V A R

D

M A R

TIN

L. K

IN

G

JR

. B O U

LE

V

AR

D

E M

A N

C

IP

A T

IO

N D

R

SHORE ROAD

H A R R

IS

A V E N

U E

HARRIS AVENUE

M c C

L E

L L A

N

S E

W E

LL

A

V E

N U

E

A V

E N

U E

TR

ICRA PHASING LINE

ICRA CLASS II

ICRA CLASS III

ICRA CLASS IV

FEC

FE

FIRE EXTINGUISHER CABINET

FIRE EXTINGUISHER

XFEC EXISTING FIRE EXTINGUISHER

CABINET

KEY AREA SHOWN

TRUE

NORTH

A B C D E F G H I J

K

L

M

O

P

Q

R

S

T

U

V

1 .5

N.5

N

105 SF

FOYER/TOILET

ROOMS

103A

3200 SF

PROTESTANT

AUDITORIUM

22 SF

CLOSET

102C

421 SF

FOYER

232 SF

JEWISH TAMBOL

102B

41 SF

MALE TOILET

102D

35 SF

FEMALE TOILET

102E

45 SF

VESTIBULE

102F

138 SF

FOYER

105C

170 SF

CONFESSIONAL

AREA

105B

3581 SF

CATHOLIC

AUDITORIUM

312 SF

CLOAK ROOM

105A

SECTION 1A:

CONTRACTOR TO COORDINATE WITH VA FOR ROOM

CLOSURES AND AVAILABILITY TO COMPLETE DATA

WIRING IN THIS AREA.

BUILDING 048

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

/0

/2

:1

:0 a m

B

IM

/5

-2

-7

V A

H a m p to n E

H R

M /B

L D

G

.r v t

48AS101

BUILDING 048 - LEVEL 01 - PHASING PLAN

MA CA

100% CONSTRUCTION

DOCUMENTS

07/18/2025

590-22-700EHRM INFRASTRUCTURE

UPGRADES - HAMPTON

HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA

LEGEND

KEY PLAN

1/8" = 1'-0"

BUILDING 48 - LEVEL 01 - PHASING PLAN

PROJECT

NORTH

Revisions: Date: 309 of 713

27B

27 31

27A

110A

110B

110D

13W

148-D

148-S

148-A

148T

146B

146A

138A 138136

137A

137C

137D

137B

137C

148B

173A

148-C

170 150

110C

143 167

G R

A V

E L

R O

A D

FRANKLIN BOULEVARD

FRANKLIN BOULEVARD

AVERILL AVENUE

AVERILL AVENUE

A M

E S

S T

R E

E T

HARRIS AVENUE

JONES CREEK

K N

O X S

T R

E E

T

T H

O M

P S

O N

S T

R E

E T

F R A N

K

LI

N B

O U

LE

V A R

D

MALLORY STREET

M A

R T

IN

L. K

IN

G

JR

. B O

U L E

V A R

D

M A R

TIN

L. K

IN

G

JR

. B O U

LE

V

AR

D

E M

A N

C

IP

A T

IO

N D

R

SHORE ROAD

H A R R

IS

A V E N

U E

HARRIS AVENUE

M c C

L E

L L A

N

S E

W E

LL

A

V E

N U

E

A V

E N

U E

TR

ICRA PHASING LINE

ICRA CLASS II

ICRA CLASS III

ICRA CLASS IV

FEC

FE

FIRE EXTINGUISHER CABINET

FIRE EXTINGUISHER

XFEC EXISTING FIRE EXTINGUISHER

CABINET

KEY AREA SHOWN

TRUE

NORTH

A B C D E F G H I J

K

L

M

O

P

Q

R

S

T

U

V

1 .5

N.5

N

335 SF

BALCONY

166 SF

STAIRWELL

76 SF

TE

108 SF

ISLAMIC PRAYER

ROOM

189 SF

CHOIR

145 SF

STORAGE ROOM

108C

PHASE 1:

CONTRACTOR TO COMPLETE THE WORK OF THIS

TE AND ASSOCIATED DATA DROPS. COMPLETE ONE

SECTION AT A TIME AS DIRECTED TO COR.

SECTION 1A:

CONTRACTOR TO COORDINATE WITH VA FOR ROOM

CLOSURES AND AVAILABILITY TO COMPLETE DATA

WIRING IN THIS AREA.

D

IA

M O

N D

L

IN

E

DIAMOND LINE

FEC

NEW SEMI-RECESSED FEC. NEW CLEAN

AGENT FIRE EXTINGUISHER. SEE DETAIL

3/A-603

BUILDING 048

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

/0

/2

:1

:0 a m

B

IM

/5

-2

-7

V A

H a m p to n E

H R

M /B

L D

G

.r v t

48AS102

BUILDING 048 - LEVEL 02 - PHASING PLAN

MA CA

100% CONSTRUCTION

DOCUMENTS

07/18/2025

590-22-700EHRM INFRASTRUCTURE

UPGRADES - HAMPTON

HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA

LEGEND

KEY PLAN

1/8" = 1'-0"

BUILDING 48 - LEVEL 02 - PHASING PLAN

PROJECT

NORTH

Revisions: Date: 310 of 713

TO DEMOLISH

EXISTING DOOR TO REMAIN

EXISTING DOOR TO DEMOLISH

EXISTING LIGHTS TO DEMOLISH

NEW DOOR

NEW LIGHTS (SEE ELECTRICAL DETAILS)

PENDENT SPRINKLER

UPRIGHT SPRINKLER WITH GUARD

H I J

ENTRY POINT

DN

H I J

EXPOSED

H I J

335 SF

BALCONY

166 SF

STAIRWELL

76 SF

TE

7 110

NEW

FLOORING

EXISTING

FLOORING

3'x8' TE FORM FACTOR

IN

-0

.0

-6

± 13' - 0" (EXIST.)

/2

(E X

IS

T

DN

IN

-0

.3

NEW SEMI-RECESSED FEC. NEW CLEAN

AGENT FIRE EXTINGUISHER. SEE DETAIL

3/A-603

H I J

335 SF

BALCONY

166 SF

STAIRWELL

76 SF

TE

EXPOSED

2' - 3"

1' - 4"

335 SF

BALCONY

166 SF

STAIRWELL

76 SF

STORAGE

335 SF

BALCONY

166 SF

STAIRWELL

76 SF

STORAGE

DEMOLISH EXISTING DOOR/FRAME. PREPARE FOR NEW

DOOR/FRAME.

DEMOLISH EXISTING FLOOR FINISH TO EXPOSE FLOOR

STRUCTURE UNDERNEATH. REMOVE EXISTING

SUBSTANCE/BONDING AGENT IF ANY. PREPARE FLOORING

FOR NEW WORK.

DEMOLISH EXISTING BASE REMOVE EXISTING ADHESIVE AND

PREPARE FOR NEW BASE.

INSTALL NEW DOOR/FRAME.

APPLY ANTI-STATIC COATING TO EXPOSED FLOOR. PROVIDE

VINYL REDUCER STRIP AT EXISTING FLOORING TRANSITION.

INSTALL NEW RESILIENT RUBBER BASE AT ROOM PERIMETER

WITH SEALANT AT THE BOTTOM.

THIS SPACE WILL BE UTILIZED FOR NEW

TELECOMMUNICATION ENCLOSURE. PROVIDE NEW FRT

PLYWOOD OVER WALLS PER DETAIL 3/AE421, TYPICAL.

ICRA KEYNOTES

INSTALL FIRE RETARDANT POLYETHYLENE SHEETING TO

ISOLATE CONSTRUCTION ZONE. TAPE AND SEAL ALONG

EDGES AND ANY AREAS WHERE POTENTIAL DUST MAY BE

EXPOSED OUTSIDE OF CONSTRUCTION AREA.

PLACE TACKY MATS AT ENTRANCE AND EXIT OF

CONSTRUCTION AREA, MINIMUM SIZE 24"X36", TYPICAL.

1. ALL PRODUCTS AND WALL FINISHES SHALL MATCH EXISTING

OR ADJACENT EXISTING UNLESS OTHERWISE NOTED.

2. PATCH AND REPAIR WALLS WHERE MECHANICAL, PLUMBING,

AND ELECTRICAL ITEMS ARE DEMOLISHED.

3. PROTECT FINISHES IN ROOMS ADJACENT TO NEW

TELECOMMUNICATION ROOMS AND AREAS NOT SCHEDULED

FOR NEW WORK.

4. CONTRACTOR SHALL LEAVE FIRE RATING STAMP

UNAPAINTED AND VISIBLE ON THE NEW INSTALLED FRT

PLYWOOD. SEE DETAILS 5/AE421.

5. REFER TO SHEET AS101 FOR ICRA REQUIREMENTS AND

DETAILS.

6. PATCH AND REPAIR CEILING, WALLS AND FLOORS AS

REQUIRED WHERE ICRA BARRIERS WILL BE CONSTRUCTED

AND REMOVED.

7. PATCH AND REPAIR GWB WHERE DOORS ARE DEMOLISHED

AND NEW DOORS ARE INSTALLED.

EXISTING WALL ACTING AS ICRA

BOUNDARY. SEAL ANY OPENINGS AND

PENETRATIONS AS REQUIRED.

POLYETHYLENE SHEETING

CONSTRUCTION TACKY MAT

HEPA EQUIPPED AIR FILTER

RM 110

KEY AREA SHOWN

PROJECT

NORTH

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

/0

/2

:1

:0 a m

B

IM

/5

-2

-7

V A

H a m p to n E

H R

M /B

L D

G

.r v t

48A-102

BUILDING 048 - LEVEL 02 - DEMO FLOOR PLAN,

DEMO RCP, FLOOR PLAN & RCP

MA MGA/CO

100% CONSTRUCTION

DOCUMENTS

07/18/2025

590-22-700EHRM INFRASTRUCTURE

UPGRADES - HAMPTON

HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA

GENERAL NOTES

KEY PLAN

KEY NOTES (THIS SHEET ONLY)

1/4" = 1'-0"

RM 110 - DEMO FLOOR PLAN

1/4" = 1'-0"

RM 110 - DEMO RCP

1/4" = 1'-0"

RM 110 - FLOOR PLAN

1/4" = 1'-0"

RM 110 - RCP

PROJECT

NORTH

PROJECT

NORTH

PROJECT

NORTH

PROJECT

NORTH

LEGEND

ICRA LEGEND - CLASS II

Revisions: Date: 311 of 713

H I

A B C D E F G J

K

L

M

O

P

Q

R

S

T

U

V

1 .5

N.5

N

BALCONY

ISLAMIC PRAYER

ROOM

CHOIR

STORAGE ROOM

108C

TE

STAIRWELL

048-M-401

048-M-401

BUILDING 048

AREA SHOWN

TRUE

NORTH

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT/DISCIPLINE

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/0

/2

:3

:0 a m

B

IM

/5

-2

-7

V A

H a m p to n E

H R

M /M

E C

H

B L D

G

.r v t

048-M-101

BLDG 048 - LVL 02 - OVERALL PLAN

MGH/JW AP/CY/JJ/MA/EA/RQ/BC

100% CONSTRUCTION

DOCUMENTS

07/18/2025

590-22-700EHRM INFRASTRUCTURE

UPGRADES - HAMPTON

HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA

1/8" = 1'-0"1

BLDG 048 - LVL 02 - OVERALL PLAN

PROJECT

NORTH

SITE PLAN

Revisions: Date:

7/18/25 312 of 713

SHOWN AREA

PROJECT

NORTH

H I

BALCONY

TE

STAIRWELL

J

1 3 048-TF-01-110

4048-TG-01-110

H I

BALCONY

TE

STAIRWELL

J

EXPOSED

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT/DISCIPLINE

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/0

/2

:3

:0 a m

B

IM

/5

-2

-7

V A

H a m p to n E

H R

M /M

E C

H

B L D

G

.r v t

048-M-401

BLDG 048 - LVL 02 - FLOOR PLAN & RCP

MGH/JW AP/CY/JJ/MA/EA/RQ/BC

100% CONSTRUCTION

DOCUMENTS

07/18/2025

590-22-700EHRM INFRASTRUCTURE

UPGRADES - HAMPTON

HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA

1/4" = 1'-0"1

RM 110 - FLOOR PLAN

PROJECT

NORTH

1/4" = 1'-0"2

RM 110 - RCP

PROJECT

NORTH

EXISTING DUCTWORK TO REMAIN.

EXISTING SIDEWALL SUPPLY DIFFUSER AND DUCTWORK TO

REMAIN.

INSTALL NEW WALL MOUNTED TRANSFER FAN. SEE

EQUIPMENT SCHEDULES ON SHEET M-602.

INSTALL 24"x16" WALL MOUNTED AIR GRILLE ON INTERIOR

AND EXTERIOR OF WALL. SEE EQUIPMENT SCHEDULES ON

SHEET M-602.

INSTALL NEW STANDARD RESPONSE SPRINKLER IN AN

UPRIGHT POSITION. INSTALL NEW BRANCH LINE, TIE-IN TO

NEAREST EXISTING MAIN.

KEYNOTES #

KEY PLAN

GENERAL NOTES

1. ALL PIPING IS SHOWN OFFSET AND DIAGRAMMATIC FOR

CLARITY. CONTRACTOR SHALL RACK PIPING AS CLOSE AS

POSSIBLE TO INSIDE WALL OF TELECOM ROOM.

2. NEW WORK SHOWN DARK, EXISTING WORK SHOWN

LIGHT.

3. A SINGLE LINE IS USED TO INDICATE ALL REFRIGERANT

PIPING ROUTED BETWEEN THE INDOOR AND OUTDOOR

UNIT(S). THIS SINGLE LINE REPRESENTS ALL PIPING

REQUIRED TO PROVIDE A COMPLETE AND FUNCTIONING

SYSTEM.

4. ROUTE ALL INTERIOR CONDENSATE AND REFRIGERANT

PIPING CONCEALED IN WALLS, CHASES OR CEILING

SPACES.

FIRE PROTECTION NOTES

1. FOR THE PURPOSES OF CLEARNESS AND LEGIBILITY,

DRAWINGS ARE DIAGRAMMATIC AND FOR DESIGN INTENT

ONLY. CONTRACTOR MUST VERIFY ALL DIMENSIONS BY

FIELD MEASUREMENT BEFORE BEGINNING ANY

FABRICATION OR CONSTRUCTION.

2. ALL WORK SHALL BE COMPLETED IN STRICT ACCORDANCE

WITH THE CURRENT VA GUIDES AND LOCAL FIRE

PROTECTION CODES AND ORDINANCES.

3. CONTRACTOR SHALL HAVE NICET III/IV TECHNICIAN DESIGN

DRAWINGS OR A LICENSED FIRE PROTECTION ENGINEER

STAMP ON ALL SHOP DRAWINGS.

4. COORDINATE EXACT LOCATION OF PIPING, SPRINKLERS,

EQUIPMENT AND MATERIALS WITH OTHER TRADES IN

ACCORDANCE WITH NFPA 13.

5. CONTRACTOR SHALL COORDINATE WITH GENERAL

CONTRACTOR AND VA COR PRIOR TO ANY CUTTING OF

WALLS AND ROOF.

6. THE CONTRACTOR SHALL PROVIDE FIRE CAULKING AT ALL

PIPING PENETRATIONS OF FIRE RATED ASSEMBLIES AS

REQUIRED.

7. TELECOM ROOMS SHALL HAVE FM APPROVED, UPRIGHT,

STANDARD RESPONSE SPRINKLERS WITH FUSIBLE LINKS.

PROVIDE LISTED MECHANICAL GUARDS. ALL EXPOSED

FIRE PROTECTION LINES SHALL BE PAINTED RED.

8. TELECOM ROOMS ARE CONSIDERED LIGHT HAZARD FOR

SPRINKLER HEAD DENSITY. ANY OTHER HAZARD

CLASSIFICATION AND SPRINKLER DENSITY ARE TO BE IN

ACCORDANCE WITH THE LATEST VERSIONS OF NFPA 13

AND VA FIRE PROTECTION DESIGN GUIDE.

9. DO NOT INSTALL SPRINKLER HEADS OR PIPING ABOVE

TELECOMMUNICATION RACKS WHERE FEASIBLE BUT STILL

IN ACCORDANCE WITH NFPA 13.

7/18/25 313 of 713

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

A A A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A A

B B

A A

B B

A B C D E F G H I J

K

L

M

O

P

Q

R

S

T

U

V

1 .5

N.5

N

MDP48

5000 KVA XFMR

ATS

5000 KVA XFMR

XFMR

SUBSTATION 151

(FEEDS BLDG 48)

DISC.

BUILDING 139

CATHOLIC AUDITORIUM

048-P-01

TO PANELBOARD "048-110A"

(REFERENCE SHEET 048EP402)

FOYER/TOILET ROOMS

103A

PROTESTANT AUDITORIUM

CLOSET

102C

FOYER

JEWISH TAMBOL

102B

MALE TOILET

102D

FEMALE TOILET

102E

VESTIBULE

102F

FOYER

105C

CONFESSIONAL AREA

105B

CLOAK ROOM

105A

048-P-02TO TE 110 SIDE B RECEPTACLE

(REFERENCE SHEET 048EP402)

PRIMARY BONDING

BUSBAR (PBB) E-504

TO SBB

(REFERENCE SHEET 048EP402)

AREA SHOWN

BLDG 048

'A' SIDE POWER, CONCEALED WHERE POSSIBLE

'B' SIDE POWER, CONCEALED WHERE POSSIBLE

'A' SIDE POWER, UNDERGROUND /UNDERFLOOR

'B' SIDE POWER, UNDERGROUND /UNDERFLOOR

PROVIDED TO INDICATE 'A' AND 'B' SIDE SOURCED POWER FEEDERS.

REFERENCE GENERAL SYMBOL LEGEND FOR ADDITIONAL INFORMATION.

LEGEND

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

/2

/2

:3

:0

A

M

B

IM

/5

-2

-7

V A

H a m p to n E

H R

M /E

E

B L D

G

.r v t

048EP101

BLDG 048 - LEVEL 01 - ELECTRICAL PLAN

JPB/WNM BCL/GPB

100% CONSTRUCTION

DOCUMENTS

07/18/2025

590-22-700EHRM INFRASTRUCTURE

UPGRADES - HAMPTON

HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA

- 1" = 10'-0"

1 BLDG 048 - LEVEL 01 - ELECTRICAL PLAN 0 10' 20'

PROJECT

NORTH

Revisions: Date:

KEY PLAN

TRUE

NORTH

GENERAL NOTES

EXISTING EQUIPMENT TO BE MODIFIED. REFERENCE ONE-LINE DIAGRAMS FOR

ADDITIONAL INFORMATION.

ROUTE CONDUIT THROUGH CRAWLSPACE. FIELD COORDINATE EXACT ROUTE.

PROVIDE TBC AS SHOWN. REFERENCE TELECOM BONDING RISER DIAGRAM ON SHEET

EG601 FOR ADDITIONAL INFORMATION.

PROVIDE TELECOMMUNICATIONS BONDING BACKBONE (TBB) TO CONNECT PBB TO

SBB(S). REFERENCE TELECOM BONDING RISER DIAGRAM ON SHEET EG601 FOR

ADDITIONAL INFORMATION.

APPROXIMATE FOOTPRINT OF TE 110 LOCATED ON ABOVE FLOOR. REFERENCE SHEET

048EP402 FOR ADDITIONAL INFORMATION.

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER, LIGHTING AND ASSOCIATED CIRCUITRY AS REQUIRED.

ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

2. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL EQUIPMENT, CONDUCTORS, AND

RACEWAYS ASSOCIATED WITH WALLS BEING REMOVED AND IN ALL LOCATIONS

WHERE JUNCTION BOXES WILL NOT REMAIN ACCESSIBLE AFTER INSTALLATION OF

MILLWORK, UNLESS OTHERWISE NOTED.

3. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE

REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

4. CONTRACTOR SHALL COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM

SHUTDOWNS AND PHASING WITH THE VA PRIOR TO PERFORMING REQUIRED

EQUIPMENT UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY POWER

AND DETERMINE TIE-IN/CONNECTION PLAN WITH EXISTING EQUIPMENT. POWER TO

ALL EXISTING ESSENTIAL EQUIPMENT CANNOT BE INTERRUPTED AND SHALL REMAIN

ACTIVE DURING CONSTRUCTION. BACKUP POWER AND TIE-IN SHALL CONFORM WITH

VA STANDARDS.

5. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

6. REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.

7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL DIRECTORIES FOR ALL

PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.

8. CONTRACTOR SHALL PROVIDE PULL BOXES FOR ALL FEEDERS WHERE FEEDER RUNS

EXCEED 250FT OR HAVE MORE THAN 270 DEGREES OF TOTAL BEND. PULL BOX

PLACEMENT AND SIZING BY CONTRACTOR. COORDINATE PULL BOX LOCATIONS WITH

ALL OBSTRUCTIONS, TRADES, AND VA AS REQUIRED.

9. ALL CONDUIT SHALL BE CONCEALED IN WALLS OR ABOVE ACCESSIBLE T-BAR

CEILINGS UNLESS OTHERWISE NOTED.

10. COORDINATE ALL CEILING REMOVAL AND REPLACEMENT WITH THE GENERAL

CONTRACTOR FOR COMPLETION OF WORK.

KEY NOTES

J

B

B

B

B

BBBB

A

A

A

A

A

AA

A A

B B

A A

B B

H I

H I

TELECOMMUNICATIONS

ENCLOSURE

E-502

E-504

048-TF-01-110TE

76 SF

TO PANELBOARD "MDP48"

(REFERENCE SHEET 048EP101)

ACCESS CONTROL PANEL

MDP 48-11

048-TR-02

048-P-01

EE

MDP 48-10

MDP 48-8

MDP 48-8

TO PRIMARY BONDING BUSBAR

(SEE SHEET 048EP101)

76 SF

STORAGE

AREA SHOWN

'A' SIDE POWER, CONCEALED WHERE POSSIBLE

'B' SIDE POWER, CONCEALED WHERE POSSIBLE

'A' SIDE POWER, UNDERGROUND /UNDERFLOOR

'B' SIDE POWER, UNDERGROUND /UNDERFLOOR

PROVIDED TO INDICATE 'A' AND 'B' SIDE SOURCED POWER FEEDERS.

REFERENCE GENERAL SYMBOL LEGEND FOR ADDITIONAL INFORMATION.

LEGEND

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

/2

/2

:3

:1

A

M

B

IM

/5

-2

-7

V A

H a m p to n E

H R

M /E

E

B L D

G

.r v t

048EP402

BLDG 048 - LEVEL 02 - ENLARGED ELECTRICAL

PLANS

JPB/WNM BCL/GPB

100% CONSTRUCTION

DOCUMENTS

07/18/2025

590-22-700EHRM INFRASTRUCTURE

UPGRADES - HAMPTON

HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA

KEY NOTES

GENERAL NOTES

1. DEMOLITION PLANS/NOTES ARE BASED ON SITE INVESTIGATIONS AND RECORD

DRAWINGS. IF DISCREPANCIES ARE FOUND THAT MAY IMPACT WORK, PROMPTLY

NOTIFY VA AND ENGINEER OF SAID DISCREPANCY.

2. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER, LIGHTING AND ASSOCIATED CIRCUITRY AS REQUIRED.

ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS

OTHERWISE NOTED.

3. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL EQUIPMENT, CONDUCTORS, AND

RACEWAYS ASSOCIATED WITH WALLS BEING REMOVED AND IN ALL LOCATIONS

WHERE JUNCTION BOXES WILL NOT REMAIN ACCESSIBLE AFTER INSTALLATION OF

MILLWORK, UNLESS OTHERWISE NOTED.

4. CONTRACTOR SHALL DISPOSE OF THE REMOVED DEVICES. DISPOSAL OF

DEVICES SHALL COMPLY WITH ALL APPROPRIATE CODES.

5. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE

REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

6. FIELD VERIFY ALL RACEWAY DEMOLITION AND INSTALLATIONS PRIOR TO

PERFORMING WORK.

7. CONTRACTOR SHALL COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM

SHUTDOWNS AND PHASING WITH THE VA PRIOR TO PERFORMING REQUIRED

EQUIPMENT UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY POWER

AND DETERMINE TIE-IN/CONNECTION PLAN WITH EXISTING EQUIPMENT. POWER TO

ALL EXISTING ESSENTIAL EQUIPMENT CANNOT BE INTERRUPTED AND SHALL

REMAIN ACTIVE DURING CONSTRUCTION. BACKUP POWER AND TIE-IN SHALL

CONFORM WITH VA STANDARDS.

8. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

9. REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.

FOR TR ROOM PANEL SCHEDULES REFERENCE THE TYPICAL A AND B POWER

SCHEDULE CLASSIFICATION FOR ADDITIONAL INFORMATION.

10. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL DIRECTORIES FOR ALL

PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.

11. ALL CONDUIT SHALL BE CONCEALED IN WALLS OR ABOVE ACCESSIBLE T-BAR

CEILINGS UNLESS OTHERWISE NOTED.

12. COORDINATE ALL CEILING REMOVAL AND REPLACEMENT WITH THE GENERAL

CONTRACTOR FOR COMPLETION OF WORK.

PROJECT

NORTH

- 1/2" = 1'-0"

1 RM 110 - DEMOLITION ELECTRICAL PLAN

- 1/2" = 1'-0"

2 RM 110 - ELECTRICAL PLAN1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

KEY PLAN

Revisions: Date:

PROVIDE MOTOR-RATED SNAP SWITCH.

PROVIDE SECONDARY BONDING BUSBAR. REFERENCE TELECOMMUNICATIONS

BONDING RISER DIAGRAM ON SHEET EG601 FOR ADDITIONAL INFORMATION.

TE POWER RECEPTACLE. 120V, 30A 1P L5-30 OUTLET.

FURNISH AND INSTALL POWER SUPPLY WITHIN JUNCTION BOX AS INDICATED ABOVE

ACCESSIBLE CEILINGS. VERIFY LOCATIONS WITH ARCHITECT. PROVIDE (1) POWER

SUPPLY FOR EACH DOOR OPENING. PROVIDE 120V POWER TO ADEQUATELY SERVE

DOORS WITH ELECTRIFIED DOOR HARDWARE AND MAKE CONNECTIONS AS REQUIRED.

SEE REQUIREMENTS IN 087100 - DOOR HARDWARE. COORDINATE WITH ARCHITECT

AND DOOR INSTALLER.

IN-LINE TRANSFER FAN WITH SPEED CONTROLLER. COORDINATE SPEED CONTROLLER

INSTALLATION LOCATION WITH MECHANICAL CONTRACTOR.

PROVIDE TELECOMMUNICATIONS BONDING BACKBONE (TBB) TO CONNECT PBB TO

SBB. REFERENCE TELECOM BONDING RISER DIAGRAM ON SHEET EG601 FOR

ADDITIONAL INFORMATION.

S

P XF2-151

Pri 4160 V Sec 240 V 300 kVA

4.00 % Z

PD-MCB-SUB151

SQUARE D

MA

1000 AF

1000 AT

BUS-151-SUB151

240 V 1200 A

PD-MDP-48

SQUARE D

MA

600 AF

600 AT

CBL-MDP-48

2 runs 350 kcmil 75 ft

PD-L

WESTINGHOUSE

JB

250 AF

225 AT

PD-AHU-1_1

CUTLER-HAMMER

ED

100 AF

100 AT

CBL-48-L

1 runs

1/0 AWG

50 ft

BUS-048-L

240 V 225 A

MTRI-AHU-1_1

20 hp

MTRI-AHU-2_1

20 hp

MTRI-AHU-3

20 hp

MTRI-AHU-4

20 hp

PD-AHU-2_1

CUTLER-HAMMER

ED

100 AF

100 AT

PD-AHU-3

CUTLER-HAMMER

FDB

100 AF

100 AT

PD-AHU-4

CUTLER-HAMMER

FDB

100 AF

100 AT

TO MEDIUM VOLTAGE EQUIPMENT

3P SPACE

(QTY=1)

WATER

HEATER

30A/2P 30A/2P

PANELBOARD "MDP 48" 600A, 240/120V, 3PH, 4W

30A/1P

WATER

HEATER

048-P-01

NEMA L5-30R

30A, 120V

LOCKING

30A/1P

048-P-02

2 2

TE 110

SIDE B

NEMA L5-30R

30A, 120V

LOCKING

TE 110

SIDE A

3P SPACE

(X25)

1P SPACE

(QTY=2)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

/2

/2

:4

:5

A

M

B

IM

/5

-2

-7

V A

H a m p to n E

H R

M /V

A H

A M

P T

O N

L e g e n d s

G e n e ra l N o te s

D ia g ra m s a n d

D e ta ils .r v t

048EP601

BLDG 048 - ONE-LINE DIAGRAM

JPB/WNM BCL/GPB

100% CONSTRUCTION

DOCUMENTS

07/18/2025

590-22-700EHRM INFRASTRUCTURE

UPGRADES - HAMPTON

HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA

- NTS

1 BLDG 048 - ONE-LINE DIAGRAM

GENERAL NOTES

1 REMOVE AND REPLACE EXISTING PANELBOARD PLACARD TO INDICATE CORRECT

VOLTAGE. PROVIDE PHENOLIC PLACARD THAT READS AS FOLLOWS:

LINE 1: "MDP48"

LINE 2: "240/120V, 3PH, 4W".

PROVIDE CIRCUIT BREAKER IN EXISTING SPACE.

REFERENCE ASSOCIATED PANEL SCHEDULE FOR ADDITIONAL INFORMATION.

1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY DISCREPANCIES

FOUND SHALL BE REPORTED TO THE ENGINEER.

2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS, TEMPORARY POWER PLANS,

AND PHASING PLANS FOR VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO

COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED FOR REVIEW 30-DAYS PRIOR

TO IMPLEMENTATION.

3. SHORT CIRCUIT CALCULATIONS BASED ON VA PROVIDED AS-BUILTS.

4. REFERENCE SHEET "048E-701" FOR ELECTRICAL EQUIPMENT LOAD SCHEDULES.

5. REFERENCE SHEET "048E-701" FOR ALL CONDUIT AND WIRING INFORMATION.

6. COMPLETE BUILDING ONE-LINE PROVIDED FOR INFORMATIONAL PURPOSES AND

AS-BUILDING PURPOSES.

KEY NOTES

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

/2

/2

:4

:3

A

M

B

IM

/5

-2

-7

V A

H a m p to n E

H R

M /V

A H

A M

P T

O N

L e g e n d s

G e n e ra l N o te s

D ia g ra m s a n d

D e ta ils .r v t

048E-701

BLDG 048 - ELECTRICAL PANELBOARD AND

CONDUIT AND WIRE SCHEDULES

JPB/WNM BCL/GPB

100% CONSTRUCTION

DOCUMENTS

07/18/2025

590-22-700EHRM INFRASTRUCTURE

UPGRADES - HAMPTON

HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA

1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE IN

ANY AND ALL CHANGES; ALL REVISED CIRCUIT DIRECTORIES SHALL BE

TYPEWRITTEN.

2. FOR ALL "REVISED" PANEL SCHEDULES REFERENCE "METERING AND LOAD

INFORMATION SCHEDULE" LOCATED ON SHEET E-703 FOR OVERALL PANEL

LOAD. "REVISED" PANEL SCHEDULES ON THIS SHEET ARE SHOWN FOR ADDED

BRANCH CIRCUIT SIZING ONLY.

3. ALL DIGITAL POWER METERS (DPM) AND SURGE PROTECTIVE DEVICES (SPD)

ARE INTEGRAL TO ELECTRICAL DISTRIBUTION EQUIPMENT, UNLESS

OTHERWISE NOTED.

GENERAL NOTES

KEY NOTES

1 UTILIZE EXISTING SPACES TO PROVIDE CIRCUIT BREAKERS AS INDICATED.

EXISTING PANELBOARD OR SWITCHBOARD TO BE MODIFIED AS INDICATED

BY BLACK TEXT. ALL GRAY TEXT SHOWS AS-BUILT EXISTING CONDITIONS.

WAP

WAP

WAP

WAP

WAP

WAP

WAP

A B C D E F G H I J

K

L

M

O

P

Q

R

T

U

V

1 .5

N.5

N

DATA OUTLETS AND DEVICES IN THIS AREA SHALL BE SERVED

FROM TELECOMMUNICATIONS ENCLOSURE 110 ON LEVEL 02.

FOYER/TOILET ROOMS

103A

PROTESTANT AUDITORIUM

CLOSET

102C

FOYER

JEWISH TAMBOL

102B

MALE TOILET

102D

FEMALE TOILET

102E

VESTIBULE

102F

FOYER

105C

CONFESSIONAL AREA

105B

CATHOLIC AUDITORIUM

CLOAK ROOM

105A

Y

D# N#

Y

D# N#

OUTLET, DATA OR VOIP TELEPHONE. THE FOLLOWING INFORMATION

INDICATED ON THE SYMBOL:

"#" = QUANTITY OF OUTLET PORTS.

"D" = EXISTING CABLES TO BE DEMOLISHED.

"N" = REPLACEMENT CABLES TO BE PROVIDED.

REFERENCE SHEET TNG002 FOR ADDITIONAL INFORMATION.

AREA SHOWN

BLDG 048

- 1/8" = 1'-0"

1 BLDG 048 - LEVEL 01 - TELECOMMUNICATIONS PLAN 4'0 8' 16'

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

/1

/2

:3

:4

A

M

B

IM

/5

-2

-7

V A

H a m p to n E

H R

M /E

E

B L D

G

.r v t

048TN101

BLDG 048 - LEVEL 01 - TELECOMMUNICATIONS

PLAN

KG BCL/GPB

100% CONSTRUCTION

DOCUMENTS

07/18/2025

590-22-700EHRM INFRASTRUCTURE

UPGRADES - HAMPTON

HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA

PROJECT

NORTH

Revisions: Date:

TRUE

NORTH

GENERAL NOTES

KEY PLAN

KEY NOTES

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE

REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO ASSOCIATED TR.

6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO

REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,

MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE

INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY

FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

7. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET

CURRENTLY DOES NOT EXIST, PROVIDE (1) 1" CONDUIT FROM NEW BACKBOX TO

ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO

TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM

OUTLET TO TR AS REQUIRED.

8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL

IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

11. THE CONTRACTOR SHALL BID AND INSTALL CAT6A CABLE WITH AN OD NOT GREATER

THAN 0.250 INCH (6.35mm) (4) CAT6A CABLES WITH AN 0.250 INCH (6.35mm) OD OR

SMALLER CAN BE INSTALLED IN A ¾” CONDUIT SUPPORTING A 40% FILL RATIO.

12. CONTRACTOR TO BID AN ADDITIONAL 10% OF THE TOTAL NUMBER OF WAO's PER

FLOOR. A WAO IS DEFINED AS TWO CAT6A OUTLETS.

EXISTING WIRELESS ACCESS POINT TO BE RE-FED WITH (2) CAT6A CABLES.

PROVIDE CONDUIT (4", MINIMUM) WITH APPROPRIATE FIRE-PROOFING AND CAULKING

AS REQUIRED TO EXTEND FROM LEVEL 01 ACCESSIBLE CEILING TO LEVEL 02

ACCESSIBLE CEILING. CONDUIT PROVIDED TO SERVE HORIZONTAL CABLING SERVING

WAOs FROM TR AS INDICATED ON PLANS.

A B C D E F G H I J

K

L

M

O

P

Q

R

T

U

V

1 .5

N.5

N

048TN402

DATA OUTLETS AND DEVICES IN THIS AREA SHALL BE

SERVED FROM TELECOMMUNICATIONS ENCLOSURE 110 .

048TN402

BALCONY

STAIRWELL

TE

ISLAMIC PRAYER ROOM

CHOIR

STORAGE ROOM

108C

048TN402

048TN402

Y

D# N#

Y

D# N#

OUTLET, DATA OR VOIP TELEPHONE. THE FOLLOWING INFORMATION

INDICATED ON THE SYMBOL:

"#" = QUANTITY OF OUTLET PORTS.

"D" = EXISTING CABLES TO BE DEMOLISHED.

"N" = REPLACEMENT CABLES TO BE PROVIDED.

REFERENCE SHEET TNG002 FOR ADDITIONAL INFORMATION.

AREA SHOWN

BLDG 048

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

/1

/2

:3

:4

A

M

B

IM

/5

-2

-7

V A

H a m p to n E

H R

M /E

E

B L D

G

.r v t

048TN102

BLDG 048 - LEVEL 02 - TELECOMMUNICATIONS

PLAN

KG BCL/GPB

100% CONSTRUCTION

DOCUMENTS

07/18/2025

590-22-700EHRM INFRASTRUCTURE

UPGRADES - HAMPTON

HAMPTON VA MEDICAL CENTER, HAMPTON, VIRGINIA

- 1/8" = 1'-0"

1 BLDG 048 - LEVEL 02 - TELECOMMUNICATIONS PLAN 4'0 8' 16'

PROJECT

NORTH

Revisions: Date:

TRUE

NORTH

GENERAL NOTES

KEY PLAN

KEY NOTES

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE

REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO ASSOCIATED TR.

6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO

REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,

MATERIALS, TOOLS,…