805CM3048CNCColumBidSet_Bk_08.pdf
PDF 3 MB Posted
- Solicitation number
- 36C78625B0029
About this file
These architectural drawings are for Columbarium I Existing Conditions and Restoration Elevations at Calverton National Cemetery in Suffolk County, New York. The documents, part of a VA construction project (Project Number 805CM3048), detail restoration and improvement plans for multiple columbarium walls (Walls 4-7), including specific elevation views, existing condition assessments, and restoration notes. The drawings show detailed photographic and technical representations of concrete walls, highlighting areas requiring cleaning, joint restoration, and pavement protection, with each wall labeled and systematically documented across multiple sheets (CS127-CS129).
The drawings include restoration and existing condition notes that outline specific repair and preservation requirements, such as concrete surface preparation, joint treatment, and protection of surrounding infrastructure. The technical specifications are part of a larger bid document set for improvements to Columbarium H, I, J, K, L, M at the Calverton National Cemetery, with the work to be performed under Solicitation Number 36C78625B0029 by the Department of Veterans Affairs National Cemetery Administration.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
SUFFOLK COUNTY, NEW YORK
805CM3048
MARCH 25, 2025
U.S. Department of Veterans Affairs
STAMP
Revisions: Date:
Drawing Title
Approved:
Phase
Building Number
VA FORM 08 - 6231
321 4 5 6 7 8 9 10
CALVERTON NATIONAL CEMETERY
COLUMBARIUM IMPROVEMENTS
ARCHITECT / ENGINEER OF RECORD: Office of Construction and Facilities Management
BID DOCUMENTS
INTEGRITY FEDERAL SERVICES /
THE LA GROUP JOINT VENTURE
Integrity Federal Services 148 S. Queen Street, Suite 350 Martinsburg
WV 25401
(304)-725-8456
The LA Group 40 Long Alley Saratoga Springs
NY 12866
(518)-587-8100
COLUMBARIUM I EXISTING CONDITIONS
/ RESTORATION ELEVATIONS - SHEET 7
CS127
22 of 99LTM BMD
COLUMBARIUM I - WALL S4.1 ELEVATION2 COLUMBARIUM I - BACK OF WALL 43
COLUMBARIUM I - BACK OF WALL 55 COLUMBARIUM I - WALL 5A ELEVATION6Scale: 1" = 5'
COLUMBARIUM I KEY1
W
ALL 4
PERGOLA
CS127
CS127
CS127
CS127
COLUMBARIUM I - WALL S5 ELEVATION4
W
ALL 5
CS127
2 / D
2 / D
2 / D
A. REMOVE AND RESET PRECAST PANELS. SEE DETAIL 10/CS500 AND
SPECIFICATIONS. INSPECT ANCHORAGE AT TIME OF REMOVAL. ALL
PANELS TO BE CLEANED. SEE SPECIFICATIONS.
B. REMOVE AND REPLACE JOINT SEALANT IF PANELS REMAINING IN
PLACE, NEW SEALANT IF PANELS TO BE REPLACED. SEE
SPECIFICATIONS.
C. NOT APPLICABLE IN COLUMBARIUM I
D. REMOVE AND REPLACE JOINT SEALANT AT CRACKED CAP JOINTS.
SEE SPECIFICATIONS.
E. CLEANING: ALL WALLS TO BE CLEANED OF MOLD AND RUST. POWER
WASHING IS PROHIBITED AND CLEANING IS WITH MILD DETERGENT
PER SPECIFICATIONS.
F. REMOVE AND RESET CAP. SEE DETAIL 1/CS501
G. REMOVE CRACKED PANEL AND REPLACE WITH NEW PANEL. SEE
DETAIL 10/CS500
H. REMOVE AND REPLACE CONCRETE PAVEMENT. SEE DETAIL 3/CS500
I. REPAIR STONE VENEER
RESTORATION NOTES:
1. FAILING PANEL JOINT SEALANT, TYP.
2. FAILING COPING JOINT SEALANT, TYP.
3. CRACKED PRECAST CONCRETE CAP, TYP.
4. STAINED PRECAST CONCRETE PANELS, TYP.
5. CRACKED PRECAST CONCRETE WALL PANELS, TYP.
6. ENTRY WALL PANELS NOT FIRMLY ATTACHED, TYP.
7. FAILING STONE VENEER AND / OR STONE CAP
8. PITTED AND SPALLING CONCRETE FLATWORK
EXISTING CONDITIONS NOTES:
1 / B (ALL JOINTS
IN ELEVATION)
1 / B (ALL JOINTS
IN ELEVATION)
A
5 / G
1 / B (ALL JOINTS
IN ELEVATION)
1 / B (ALL JOINTS
IN ELEVATION)
NOTE: ALL WALLS ON THIS SHEET TO
RECEIVE CLEANING (E)
8 / H
PROTECT
EXISTING
PAVEMENT TO
REMAIN, TYP.
LEGEND:
REMOVE AND REPLACE CONCRETE FLATWORK 3
CS500
Project Title
Location
Issue Date Checked Drawn
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
SUFFOLK COUNTY, NEW YORK
805CM3048
MARCH 25, 2025
U.S. Department of Veterans Affairs
STAMP
Revisions: Date:
Drawing Title
Approved:
Phase
Building Number
VA FORM 08 - 6231
321 4 5 6 7 8 9 10
CALVERTON NATIONAL CEMETERY
COLUMBARIUM IMPROVEMENTS
ARCHITECT / ENGINEER OF RECORD: Office of Construction and Facilities Management
BID DOCUMENTS
INTEGRITY FEDERAL SERVICES /
THE LA GROUP JOINT VENTURE
Integrity Federal Services 148 S. Queen Street, Suite 350 Martinsburg
WV 25401
(304)-725-8456
The LA Group 40 Long Alley Saratoga Springs
NY 12866
(518)-587-8100
COLUMBARIUM I EXISTING CONDITIONS
/ RESTORATION ELEVATIONS - SHEET 8
CS128
23 of 99LTM BMD
COLUMBARIUM I - WALL 5B ELEVATION2 COLUMBARIUM I - WALL 5C ELEVATION3
COLUMBARIUM I - WALL S5.1 ELEVATION4 COLUMBARIUM I - WALL S6 ELEVATION5Scale: 1" = 5'
COLUMBARIUM I KEY1
W
ALL 5
WALL 9
W
ALL 10
CS128
CS128
CS128
CS128
W
ALL 6
W
ALL 8
WALL 7
WALL 8
COLUMBARIUM I - WALL 6A ELEVATION6
CS128
2 / D 2 / D
1 / B (ALL JOINTS
IN ELEVATION)
2 / D
2 / D
A. REMOVE AND RESET PRECAST PANELS. SEE DETAIL 10/CS500 AND
SPECIFICATIONS. INSPECT ANCHORAGE AT TIME OF REMOVAL. ALL
PANELS TO BE CLEANED. SEE SPECIFICATIONS.
B. REMOVE AND REPLACE JOINT SEALANT IF PANELS REMAINING IN
PLACE, NEW SEALANT IF PANELS TO BE REPLACED. SEE
SPECIFICATIONS.
C. NOT APPLICABLE IN COLUMBARIUM I
D. REMOVE AND REPLACE JOINT SEALANT AT CRACKED CAP JOINTS.
SEE SPECIFICATIONS.
E. CLEANING: ALL WALLS TO BE CLEANED OF MOLD AND RUST. POWER
WASHING IS PROHIBITED AND CLEANING IS WITH MILD DETERGENT
PER SPECIFICATIONS.
F. REMOVE AND RESET CAP. SEE DETAIL 1/CS501
G. REMOVE CRACKED PANEL AND REPLACE WITH NEW PANEL. SEE
DETAIL 10/CS500
H. REMOVE AND REPLACE CONCRETE PAVEMENT. SEE DETAIL 3/CS500
I. REPAIR STONE VENEER
RESTORATION NOTES:
1. FAILING PANEL JOINT SEALANT, TYP.
2. FAILING COPING JOINT SEALANT, TYP.
3. CRACKED PRECAST CONCRETE CAP, TYP.
4. STAINED PRECAST CONCRETE PANELS, TYP.
5. CRACKED PRECAST CONCRETE WALL PANELS, TYP.
6. ENTRY WALL PANELS NOT FIRMLY ATTACHED, TYP.
7. FAILING STONE VENEER AND / OR STONE CAP
8. PITTED AND SPALLING CONCRETE FLATWORK
EXISTING CONDITIONS NOTES:
1 / B (ALL JOINTS
IN ELEVATION)
1 / B (ALL JOINTS
IN ELEVATION)
GRAVEL
STRIP
CS500
A
5 / G 1 / B (ALL JOINTS
IN ELEVATION)
GRAVEL
STRIP
CS500
NOTE: ALL WALLS ON THIS SHEET TO
RECEIVE CLEANING (E)
LEGEND:
REMOVE EX. VEGETATION & MULCH. NEW GRAVEL
& DECORATIVE STONE PER SPECIFICATIONS
CS501
Project Title
Location
Issue Date Checked Drawn
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
SUFFOLK COUNTY, NEW YORK
805CM3048
MARCH 25, 2025
U.S. Department of Veterans Affairs
STAMP
Revisions: Date:
Drawing Title
Approved:
Phase
Building Number
VA FORM 08 - 6231
321 4 5 6 7 8 9 10
CALVERTON NATIONAL CEMETERY
COLUMBARIUM IMPROVEMENTS
ARCHITECT / ENGINEER OF RECORD: Office of Construction and Facilities Management
BID DOCUMENTS
INTEGRITY FEDERAL SERVICES /
THE LA GROUP JOINT VENTURE
Integrity Federal Services 148 S. Queen Street, Suite 350 Martinsburg
WV 25401
(304)-725-8456
The LA Group 40 Long Alley Saratoga Springs
NY 12866
(518)-587-8100
COLUMBARIUM I EXISTING CONDITIONS
/ RESTORATION ELEVATIONS - SHEET 9
CS129
24 of 99LTM BMD
COLUMBARIUM I - WALL 6B ELEVATION2 COLUMBARIUM I - CONCRETE SPALLING BETWEEN WALLS 7 & 93
COLUMBARIUM I - WALL 7A ELEVATION4 COLUMBARIUM I - WALL 7B ELEVATION5Scale: 1" = 5'
COLUMBARIUM I KEY1
WALL 7
W
ALL 8
W
ALL 6
CS129
CS129
WALL 8
WALL 9
CS129
CS129
2 / D
2 / D
5 / G
2 / D
A. REMOVE AND RESET PRECAST PANELS. SEE DETAIL 10/CS500 AND
SPECIFICATIONS. INSPECT ANCHORAGE AT TIME OF REMOVAL. ALL
PANELS TO BE CLEANED. SEE SPECIFICATIONS.
B. REMOVE AND REPLACE JOINT SEALANT IF PANELS REMAINING IN
PLACE, NEW SEALANT IF PANELS TO BE REPLACED. SEE
SPECIFICATIONS.
C. NOT APPLICABLE IN COLUMBARIUM I
D. REMOVE AND REPLACE JOINT SEALANT AT CRACKED CAP JOINTS.
SEE SPECIFICATIONS.
E. CLEANING: ALL WALLS TO BE CLEANED OF MOLD AND RUST. POWER
WASHING IS PROHIBITED AND CLEANING IS WITH MILD DETERGENT
PER SPECIFICATIONS.
F. REMOVE AND RESET CAP. SEE DETAIL 1/CS501
G. REMOVE CRACKED PANEL AND REPLACE WITH NEW PANEL. SEE
DETAIL 10/CS500
H. REMOVE AND REPLACE CONCRETE PAVEMENT. SEE DETAIL 3/CS500
I. REPAIR STONE VENEER
RESTORATION NOTES:
1. FAILING PANEL JOINT SEALANT, TYP.
2. FAILING COPING JOINT SEALANT, TYP.
3. CRACKED PRECAST CONCRETE CAP, TYP.
4. STAINED PRECAST CONCRETE PANELS, TYP.
5. CRACKED PRECAST CONCRETE WALL PANELS, TYP.
6. ENTRY WALL PANELS NOT FIRMLY ATTACHED, TYP.
7. FAILING STONE VENEER AND / OR STONE CAP
8. PITTED AND SPALLING CONCRETE FLATWORK
EXISTING CONDITIONS NOTES:
1 / B (ALL JOINTS
IN ELEVATION)
8 / H
1 / B (ALL JOINTS
IN ELEVATION)
2 / D
1 / B (ALL JOINTS
IN ELEVATION)
NOTE: ALL WALLS ON THIS SHEET TO
RECEIVE CLEANING (E)
PROTECT EXISTING
PAVEMENT TO REMAIN
LEGEND:
REMOVE AND REPLACE CONCRETE FLATWORK
REMOVE EX. VEGETATION & MULCH. NEW GRAVEL
& DECORATIVE STONE PER SPECIFICATIONS
CS500
CS501
| 22_CS127_COLUMBARIUM I RESTORATION-I-7 |