This file is a Basis of Design (BOD) document containing technical specifications and equipment details for HVAC systems, lighting controls, and electrical infrastructure for a VA facility renovation project (578-20-002 at Hines, Illinois).

The document includes mechanical load calculations for two air handling systems: an ATRIUM AHU serving 4,208 square feet with a peak cooling load of 25.6 tons (6,401 CFM) and a 23-009 HINES VA CLC system serving 20,425 square feet with a peak cooling load of 16.2 tons (8,761 CFM). The mechanical specifications detail zone sizing, terminal equipment requirements, and ventilation design parameters. HVAC distribution equipment specified includes Price Industries High Capacity Drum Louvers (HCD) and Linear Slot Diffusers (SDS/SDS4) with adjustable pattern controllers for architectural applications. Lighting control specifications call for Acuity Brands nLight-enabled occupancy sensors and wall controls, including models nCM xx RJB (ceiling-mount PIR sensors with 360-degree coverage options from 12 to 70 feet), nWSXA low-voltage wall switch sensors, nWV 16 wide-view corner-mount sensors, nPODMA wall-mounted control switches with dimming capabilities, and BLT 2x2 recessed LED luminaires with integrated nLight controls. Electrical infrastructure includes a 75 kVA Eaton transformer (480V primary to 208Y/120V secondary), a 500 VA Class 2 power supply with five 100VA outputs, and an Eaton HFD3200 200A molded case circuit breaker. All specified products include Buy American Act (BAA) compliance options. The document reflects 60% construction drawing phase specifications as of May 8, 2024.

View the file

Other files

File Type Posted
P09 - SOW BNOE_Nurse Call.docx DOCX document
S06 Amendment 0002 Solicitation 36C25226B0028.docx DOCX document
S06 Amendment 0001 Solicitation 36C25226B0028.docx DOCX document
FINAL RFI QUESTIONS AND ANSWERS FOR PROJECT 578-26-016.docx DOCX document
Pre-Bid Site Visit Sign-in.pdf PDF
57826016_Addendumnumber2_08202026.pdf PDF
7b. 578-20-002 Basis of Design -BOD Part 2_.pdf PDF
11. Building 217 _ Exterior Rooms.pdf PDF
8. 578-26-016 Building 217 Abatement Drawings.pdf PDF
5b. 578-26-016 CLIN1 100 Percent Bid Drawings -Part 2.pdf PDF
2. VHA PCRA-1.1 -May 21 2024- 578-26-016.pdf PDF
1.15 Hines COVID-19 Guidelines.pdf PDF
1.14 OIT Horizontal Cable Requirements.pdf PDF
1.12 Cutting Welding and Other Hot Work.pdf PDF
1.10 Fire Protection Code Reviews.pdf PDF
1.9 Above Ceiling Permits.pdf PDF
1.2 HINES VA SITE PLAN 5-1-2025.pdf PDF
P07 WAGE DETERMINATION IL20260009 05-18-2026.pdf PDF
13. Hines AC Shop HVAC Controls Requirements.docx DOCX document
10. Building 217 Colored Space Drawings.pdf PDF
7d. 578-20-002 Basis of Design -BOD Part 4.pdf PDF
7b. 578-20-002 Basis of Design -BOD Part 2.pdf PDF
7a. 578-20-002 Basis of Design -BOD Part 1.pdf PDF
5a. 578-26-016 CLIN1 100 Percent Bid Drawings -Part 1.pdf PDF
1.6 Pre-Construction Checklist Rev 07.27.2021.pdf PDF
1.4 Contractor Badging - Fingerprint Request Form 2025.pdf PDF
1.3 Parking Designations 08042025.pdf PDF
36C25226B0028.docx DOCX document
12. Hines VA Lock Hardware Standards.docx DOCX document
6. 578-26-016 CLIN1 Specifications Book R1.pdf PDF
1.16 VHA Supplemental COVID-19 Requirements.pdf PDF
1.13 Asbestos Survey Glossary.pdf PDF
1.8 Dig Permit SOP Form.pdf PDF
9. 578-26-016 Building 217 Abatement Specifications.pdf PDF
5c. 578-26-016 CLIN1 100 Percent Bid Drawings -Part 3.pdf PDF
4. VHA ICRA-1.3 -Dec 9 2024- 578-26-016.pdf PDF
3. Interim Life Safety Measures -ILSM 578-26-016.pdf PDF
1.17 Emergency Contact List - Template.pdf PDF
1.11 No Smoking Policy 10-1-19.pdf PDF
1.7 Infection Control Barrier Sample.pdf PDF
1.5 Safety and Health During Construction Activities.pdf PDF
1.1 Hines Underground Utility Plan.pdf PDF
P09 578-26-016 Donation Renovations Phase 2 Construction SOW 7-27-26.docx DOCX document
Show all 43

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

The High Capacity Drum Louvers (HCD) consist of extruded aluminum blades mounted inside a rotatable drum to produce long air throws with a high degree of directional control.

Individually adjustable vanes

Surface and spiral duct mounting available

Rotateable drum provides 60° vertical adjustment

Single blade

Spilt blade

2 For more information visit www.priceindustries.com | v100

HCD

High Capacity Drum Louver

SDS

LINEAR SLOT DIFFUSER

The SDS linear slot diffuser is designed to satisfy architectural applications that require continuous lengths without compromising air distribution performance. These linear slot diffusers feature fully adjustable, aerodynamic pattern controllers fabricated from extruded aluminum, and are available in a large selection of frame styles. The SDS provides the ideal combination of engineering excellence and architectural appeal.

Extensive frame style selection Aerodynamic ice-tong pattern controllers

Customizable slot quantity and width

Extruded aluminum construction

2 For more information visit www.priceindustries.com | v100

Linear Slot Diffuser

FULLY ADJUSTABLE

AIR PATTERN

The precisely shaped, aerodynamic ice-tong pattern controllers provide airflow rate control as well as a full 180° range of air pattern adjustment, anywhere from fully vertical to fully horizontal.

Pattern controllers come in discrete sections for multiple patterns on a single slot length.

DESIGN FLEXIBILITY

Ideal for highly architectural applications, the SDS features a one-piece extruded aluminum frame and is available with countless design options to provide ultimate flexibility. Options include:

+ Up to 10 slots for airflow pattern flexibility and additional capacity.

+ Four slot widths.

+ Available for discrete or continuous applications.

Continuous installations are supplied with alignment strips for high quality architectural installations.

+ Flexible position for supply plenums allowing active and return sections along the same diffuser. This is popular for continuous slot, perimeter applications.

+ Blank-off strips are used for inactive sections and maintain a continuous look.

+ Inside, outside or flat mitered corners.

+ Flat face curve sections.

+ Multiple finish options, including anodized

Mitered corners

TYPICAL

APPLICATIONS

Aerodynamically designed blades provide a tight horizontal pattern that maintains stability even at low airflow rates, making the SDS ideal for VAV applications.

Excellent for architectural applications, the SDS has many mounting styles and is available with multiple slot widths and quantities to meet a range of airflow requirements.

CONSTRUCTION OPTIONS

+ Models

- Supply (SDS)

- Return (SDR)

- Curved supply/return (SDC)

+ Slot widths

- 1/2 in.

- 3/4 in.

- 1 in.

- 1 1/2 in.

+ Slot quantity

- 1 to 10

+ Accessories

- Blank-off strips

- Mitered corner section (MC)

3v100 | For more information visit www.priceindustries.com

4-WAY LINEAR SLOT

DIFFUSER (SDS4)

Price SDS4 Series 4 way linear slot diffusers provide exceptional performance, superior design and crisp appearance for integration with ceiling tile. This unique design combines extruded aluminum construction with a ceiling tile that is field cut and placed into the face of the diffuser.

For design flexibility, the SDS4 is available in three ceiling module sizes, with one to 4 slots in three sizes to accommodate low, medium, and high airflow. Ideal for use in high performance VAV systems, the

SDS4 provides full 180° air pattern adjustment and a stable horizontal air pattern. Each slot is individually adjustable for air pattern and air volume using a precisely curved, aerodynamically shaped pattern controller.

A matching return unit is available and is supplied with a sight baffle instead of a plenum and pattern controllers.

CONSTRUCTION

+ Application

- Supply (SDS4)

- Return (SDR4)

+ Ceiling module size

- 20 in. x 20 in.

- 24 in. x 24 in.

- 30 in. x 30 in.

+ Slot width

- ½ in.

- ¾ in.

- 1 in.

+ Slot quantity

- 1, 2, 3*, 4*

*available on 24 in. and 30 in. only

+ Options

- Insulated plenum (SDSI4)

- No plenum

9v100 | For more information visit www.priceindustries.com

Mechanical Load Calculations

VA HINES, IL

RENOVATE SPACES Building 217

BAE Project # 23-009

STATION PROJECT # 578-20-002

CONTRACT # 36C25223C0071

Location: VA Hines

State: Illinois

Date: May 08, 2024

(60% Construction Drawings)

Air System Sizing Summary for ATRIUM AHU Project Name: 23-009 - Hines - Seperate Atrium 03/25/2024 Prepared by: Bancroft 01:40PM

Hourly Analysis Program 5.11 Page 1 of 5

Air System Information Air System Name ............................... ATRIUM AHU Equipment Class .................................. PKG ROOF Air System Type ............................................... VAV

Number of zones Floor Area .......................................................... 4208.0 ft² Location ....................................... Chicago IAP, Illinois

Sizing Calculation Information

Calculation Months ................................ Jan to Dec Sizing Data ............................................ Calculated

Zone CFM Sizing ................... Peak zone sensible load Space CFM Sizing .................. Coincident space loads

Central Cooling Coil Sizing Data

Total coil load ................................................... 25.6 Tons Total coil load ................................................. 306.9 MBH Sensible coil load ............................................ 199.8 MBH Coil CFM at Jul 1600 ....................................... 6401 CFM Max block CFM at Jul 1600 ............................. 6401 CFM Sum of peak zone CFM ................................... 6401 CFM Sensible heat ratio .......................................... 0.651 CFM/Ton ........................................................ 250.3 ft²/Ton ............................................................. 164.5 BTU/(hr·ft²) ....................................................... 72.9 Water flow @ 12.0 °F rise .................................. N/A

Load occurs at ................................................. Jul 1600

OA DB / WB .................................................. 91.0 / 74.0 °F

Entering DB / WB .......................................... 83.1 / 68.5 °F Leaving DB / WB ........................................... 53.5 / 52.4 °F Coil ADP ................................................................. 50.2 °F Bypass Factor ...................................................... 0.100 Resulting RH ............................................................. 48 % Design supply temp. ............................................... 57.0 °F Zone T-stat Check ................................................ 0 of 1 OK Max zone temperature deviation ............................... 0.0 °F

Preheat Coil Sizing Data

Max coil load ................................................... 138.7 MBH Coil CFM at Des Htg ........................................ 4756 CFM Max coil CFM ................................................... 6401 CFM Water flow @ 50.0 °F drop ................................ 5.55 gpm

Load occurs at .................................................. Des Htg Ent. DB / Lvg DB ........................................... 22.3 / 50.0 °F

Humidifier Sizing Data

Max steam flow at Des Htg ............................. 51.19 lb/hr Airflow Rate ..................................................... 4756 CFM

Air mass flow ................................................... 20886.50 lb/hr Moisture gain ...................................................... .00245 lb/lb

Supply Fan Sizing Data

Actual max CFM at Jul 1600 ............................ 6401 CFM Standard CFM ................................................. 6246 CFM Actual max CFM/ft² ........................................... 1.52 CFM/ft²

Fan motor BHP ......................................................... n/a Fan motor kW ......................................................... 6.94 kW

Return Fan Sizing Data

Actual max CFM at Jul 1600 ............................ 6401 CFM Standard CFM ................................................. 6246 CFM Actual max CFM/ft² ........................................... 1.52 CFM/ft²

Fan motor BHP ......................................................... n/a Fan motor kW ......................................................... 0.00 kW Fan static ................................................................ 0.00 in wg

Outdoor Ventilation Air Data Design airflow CFM ......................................... 2911 CFM CFM/ft² ............................................................. 0.69 CFM/ft²

CFM/person ......................................................... 19.41 CFM/person

Zone Sizing Summary for ATRIUM AHU

Prepared by: Bancroft 01:40PM

Hourly Analysis Program 5.11 Page 2 of 5

Air System Information Air System Name ............................... ATRIUM AHU Equipment Class .................................. PKG ROOF Air System Type ............................................... VAV

Number of zones Floor Area .......................................................... 4208.0 ft² Location ....................................... Chicago IAP, Illinois

Sizing Calculation Information

Calculation Months ................................ Jan to Dec Sizing Data ............................................ Calculated

Zone CFM Sizing ................... Peak zone sensible load Space CFM Sizing .................. Coincident space loads

Zone Terminal Sizing Data

Zone Name

Design Supply Airflow

(CFM)

Minimum Supply Airflow

(CFM)

Zone CFM/ft²

Reheat Coil Load

(MBH)

Reheat Coil

Water gpm

@ 50.0 °F

Zone Htg Unit

Coil Load

(MBH)

Zone Htg Unit Water gpm

@ 50.0 °F

Mixing Box Fan Airflow

(CFM)

Zone 1 6401 4756 1.52 190.5 7.62 0.0 - 0

Zone Peak Sensible Loads

Zone Zone Zone

Cooling Time of Heating Floor

Sensible Peak Sensible Load Area

Zone Name (MBH) Cooling Load (MBH) (ft²)

Zone 1 121.4 Jul 1600 125.3 4208.0

Space Loads and Airflows

Zone Name / Space Name Mult.

Cooling Sensible

(MBH)

Time of Peak

Sensible Load

Air Flow

(CFM)

Heating Load

(MBH)

Floor Area (ft²)

Space CFM/ft²

Zone 1

UPPER ATRIUM 1 78.1 Jul 1600 4118 125.3 2104.0 1.96

LOWER ATRIUM 1 43.3 Jul 1600 2282 0.0 2104.0 1.08

Air System Design Load Summary for ATRIUM AHU

Prepared by: Bancroft 01:40PM

Hourly Analysis Program 5.11 Page 3 of 5

DESIGN COOLING DESIGN HEATING

COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG

COOLING OA DB / WB 91.0 °F / 74.0 °F HEATING OA DB / WB -6.0 °F / -7.2 °F

Sensible Latent Sensible Latent

ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

Window & Skylight Solar Loads 2838 ft² 49237 - 2838 ft² - -

Wall Transmission 917 ft² 1339 - 917 ft² 7246 -

Roof Transmission 1479 ft² 4997 - 1479 ft² 10229 -

Window Transmission 2213 ft² 13819 - 2213 ft² 84094 -

Skylight Transmission 625 ft² 3903 - 625 ft² 23750 -

Door Loads 0 ft² 0 - 0 ft² 0 -

Floor Transmission 0 ft² 0 - 0 ft² 0 -

Partitions 0 ft² 0 - 0 ft² 0 -

Ceiling 0 ft² 0 - 0 ft² 0 -

Overhead Lighting 2630 W 8058 - 0 0 -

Task Lighting 0 W 0 - 0 0 -

Electric Equipment 1052 W 3426 - 0 0 -

People 150 36650 40500 0 0 0

Infiltration - 0 0 - 0 0

Miscellaneous - 0 0 - 0 0

Safety Factor 0% / 0% 0 0 0% 0 0

>> Total Zone Loads - 121429 40500 - 125319 0

Zone Conditioning - 131767 40500 - 119405 0

Plenum Wall Load 0% 0 - 0 0 -

Plenum Roof Load 0% 0 - 0 0 -

Plenum Lighting Load 0% 0 - 0 0 -

Return Fan Load 6401 CFM 0 - 4756 CFM 0 -

Ventilation Load 2911 CFM 44389 66576 2911 CFM 224019 53991

Supply Fan Load 6401 CFM 23665 - 4756 CFM -14206 -

Space Fan Coil Fans - 0 - - 0 -

Duct Heat Gain / Loss 0% 0 - 0% 0 -

>> Total System Loads - 199821 107076 - 329218 53991

Central Cooling Coil - 199821 107080 - 0 0

Preheat Coil - 0 - - 138733 -

Humidification Load - - 0 - - 53991

Terminal Reheat Coils - 0 - - 190485 -

>> Total Conditioning - 199821 107080 - 329218 53991

Key: Positive values are clg loads Positive values are htg loads

Negative values are htg loads Negative values are clg loads

Space Design Load Summary for ATRIUM AHU

Hourly Analysis Program 5.11 Page 4 of 5

TABLE 1.1.A. Component Loads For Space "UPPER ATRIUM" In Zone "Zone 1"

COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG

COOLING OA DB / WB 91.0 °F / 74.0 °F HEATING OA DB / WB -6.0 °F / -7.2 °F

OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F

Sensible Latent Sensible Latent

SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

Window & Skylight Solar Loads 2838 ft² 49237 - 2838 ft² - -

Wall Transmission 917 ft² 1339 - 917 ft² 7246 -

Roof Transmission 1479 ft² 4997 - 1479 ft² 10229 -

Window Transmission 2213 ft² 13819 - 2213 ft² 84094 -

Skylight Transmission 625 ft² 3903 - 625 ft² 23750 -

Door Loads 0 ft² 0 - 0 ft² 0 -

Floor Transmission 0 ft² 0 - 0 ft² 0 -

Partitions 0 ft² 0 - 0 ft² 0 -

Ceiling 0 ft² 0 - 0 ft² 0 -

Overhead Lighting 1578 W 4835 - 0 0 -

Task Lighting 0 W 0 - 0 0 -

Electric Equipment 0 W 0 - 0 0 -

People 0 0 0 0 0 0

Infiltration - 0 0 - 0 0

Miscellaneous - 0 0 - 0 0

Safety Factor 0% / 0% 0 0 0% 0 0

>> Total Zone Loads - 78130 0 - 125319 0

TABLE 1.1.B. Envelope Loads For Space "UPPER ATRIUM" In Zone "Zone 1"

COOLING COOLING HEATING

Area U-Value Shade TRANS SOLAR TRANS

(ft²) (BTU/(hr·ft²·°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)

N EXPOSURE

WALL 231 0.104 - 239 - 1823

WINDOW 1 1038 0.500 0.287 6482 7265 39444

E EXPOSURE

WALL 233 0.104 - 396 - 1839

WINDOW 1 396 0.500 0.287 2473 6504 15048

S EXPOSURE

WALL 221 0.104 - 373 - 1744

WINDOW 1 383 0.500 0.287 2392 5039 14554

W EXPOSURE

WALL 233 0.104 - 331 - 1839

WINDOW 1 396 0.500 0.287 2473 9410 15048

H EXPOSURE

ROOF 1479 0.091 - 4997 - 10229

SKYLIGHT 625 0.500 0.253 3903 21019 23750

Space Design Load Summary for ATRIUM AHU

Hourly Analysis Program 5.11 Page 5 of 5

TABLE 1.2.A. Component Loads For Space "LOWER ATRIUM" In Zone "Zone 1"

COOLING DATA AT Jan 2200 HEATING DATA AT DES HTG

COOLING OA DB / WB 32.7 °F / 32.7 °F HEATING OA DB / WB -6.0 °F / -7.2 °F

OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F

Sensible Latent Sensible Latent

SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -

Wall Transmission 0 ft² 0 - 0 ft² 0 -

Roof Transmission 0 ft² 0 - 0 ft² 0 -

Window Transmission 0 ft² 0 - 0 ft² 0 -

Skylight Transmission 0 ft² 0 - 0 ft² 0 -

Door Loads 0 ft² 0 - 0 ft² 0 -

Floor Transmission 0 ft² 0 - 0 ft² 0 -

Partitions 0 ft² 0 - 0 ft² 0 -

Ceiling 0 ft² 0 - 0 ft² 0 -

Overhead Lighting 1052 W 3346 - 0 0 -

Task Lighting 0 W 0 - 0 0 -

Electric Equipment 1052 W 3481 - 0 0 -

People 150 38442 40500 0 0 0

Infiltration - 0 0 - 0 0

Miscellaneous - 0 0 - 0 0

Safety Factor 0% / 0% 0 0 0% 0 0

>> Total Zone Loads - 45268 40500 - 0 0

TABLE 1.2.B. Envelope Loads For Space "LOWER ATRIUM" In Zone "Zone 1"

COOLING COOLING HEATING

Area U-Value Shade TRANS SOLAR TRANS

(ft²) (BTU/(hr·ft²·°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)

Air System Sizing Summary for 23-009 HINES VA CLC Project Name: 23-009 Hines VA CLC Hines Illinois 04/08/2024 Prepared by: Bancroft A+E 02:14PM

Air System Information Air System Name 23-009 HINES VA CLC Equipment Class UNDEF Air System Type VAV

Number of zones 4 Floor Area 20425.0 ft² Location Chicago IAP, Illinois

Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated

Zone CFM Sizing Peak zone sensible load Space CFM Sizing Individual peak space loads

Central Cooling Coil Sizing Data Total coil load 16.2 Tons Total coil load 194.6 MBH Sensible coil load 170.1 MBH Coil CFM at Jul 1800 7630 CFM Max block CFM at Jul 1800 8761 CFM Sum of peak zone CFM 8828 CFM Sensible heat ratio 0.874 CFM/Ton 470.6 ft²/Ton 1259.6 BTU/(hr·ft²) 9.5 Water flow @ 15.0 °F rise 25.96 gpm

Load occurs at Jul 1800

OA DB / WB 89.0 / 73.5 °F

Entering DB / WB 76.2 / 62.8 °F Leaving DB / WB 55.0 / 53.8 °F Coil ADP 52.6 °F Bypass Factor 0.100 Resulting RH 48 % Design supply temp. 55.0 °F Zone T-stat Check 4 of 4 OK Max zone temperature deviation 0.0 °F

Preheat Coil Sizing Data No heating coil loads occurred during this calculation.

Supply Fan Sizing Data Actual max CFM at Jul 1800 8761 CFM Standard CFM 8550 CFM Actual max CFM/ft² 0.43 CFM/ft²

Fan motor BHP 0.00 BHP Fan motor kW 0.00 kW Fan static 0.00 in wg

Outdoor Ventilation Air Data Design airflow CFM 0 CFM CFM/ft² 0.00 CFM/ft²

CFM/person 0.00 CFM/person

Hourly Analysis Program 5.11 Page 1 of 85

Zone Sizing Summary for 23-009 HINES VA CLC

Prepared by: Bancroft A+E 02:14PM

Air System Information Air System Name 23-009 HINES VA CLC Equipment Class UNDEF Air System Type VAV

Number of zones 4 Floor Area 20425.0 ft² Location Chicago IAP, Illinois

Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated

Zone CFM Sizing Peak zone sensible load Space CFM Sizing Individual peak space loads

Zone Terminal Sizing Data

Zone Name

Design Supply Airflow

(CFM)

Minimum Supply Airflow

(CFM)

Zone CFM/ft²

Reheat Coil Load

(MBH)

Reheat Coil

Water gpm

@ 20.0 °F

Zone Htg Unit

Coil Load

(MBH)

Zone Htg Unit Water gpm

@ 20.0 °F

Mixing Box Fan Airflow

(CFM)

Zone 1A114 4768 2292 0.42 96.6 9.67 0.0 0.00 0

Zone 1A121 1687 336 0.41 14.2 1.42 0.0 0.00 0

Zone 2A24 953 118 0.73 5.0 0.50 0.0 0.00 0

Zone 2A20 1420 338 0.38 14.2 1.42 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone

Cooling Time of Heating Floor

Sensible Peak Sensible Load Area

Zone Name (MBH) Cooling Load (MBH) (ft²)

Zone 1A114 100.5 Jul 1800 60.4 11333.0

Zone 1A121 35.6 Jul 1800 8.8 4093.0

Zone 2A24 20.1 Oct 1500 3.1 1305.0

Zone 2A20 29.9 Jul 1800 8.9 3694.0

Hourly Analysis Program 5.11 Page 2 of 85

Prepared by: Bancroft A+E 02:14PM

Space Loads and Airflows

Zone Name / Space Name Mult.

Cooling Sensible

(MBH)

Time of Peak

Sensible Load

Air Flow

(CFM)

Heating Load

(MBH)

Floor Area (ft²)

Space CFM/ft²

Zone 1A114

1A100 ENTRANCE 1 13.0 Jun 1800 619 11.6 652.0 0.95

1A100 ENTRANCE LOBBY 1 4.9 Jul 1800 233 3.6 720.0 0.32

1A100 ENTRANCE LOBBY INT 1 1.3 Jan 2200 60 0.0 400.0 0.15

1A104 WAITING / LIB 1 2.2 Jan 2100 105 0.0 253.0 0.41

1A104A RECEPTION 1 2.1 Jan 2100 98 0.0 210.0 0.47

1A105 CLINIC 1 3.0 Jun 1800 143 2.0 179.0 0.80

1A106 CLINIC 1 3.5 Jun 1800 167 2.8 182.0 0.92

1A107 CLINIC 1 3.0 Jun 1800 142 2.2 168.0 0.84

1A108 CLINIC 1 3.0 Jun 1800 142 2.1 177.0 0.80

1A109 CLINIC 1 2.2 Jan 2100 104 0.2 178.0 0.58

1A111 SOCIAL WORKER 1 2.0 Jan 2100 94 0.0 113.0 0.83

1A112 TOILET 1 0.2 Jan 2200 12 0.0 78.0 0.15

1A141 WORKROOM 1 1.8 Jan 2100 86 0.0 130.0 0.67

1A142 VITALS EXAM 1 1.8 Jan 2100 86 0.0 127.0 0.68

1B148 TOILET INT 1 0.2 Jan 2200 11 0.0 76.0 0.15

1B149 BARIATRIC ROOM 1 4.1 Jul 1500 197 2.7 312.0 0.63

1B154 TOILET EXT 1 0.5 Jul 1500 26 0.9 67.0 0.39

1B155 DEMENTIA ROOM 1 3.0 Jul 1600 142 1.3 241.0 0.59

1B156 DEMENTIA ROOM 1 3.0 Jul 1600 142 1.3 239.0 0.59

1B157 TOILET EXT 1 0.5 Jul 2000 26 0.9 65.0 0.40

1B158 TOILET EXT 1 0.5 Jul 1500 26 0.9 67.0 0.39

1B159 DEMENTIA ROOM 1 3.0 Jul 1600 142 1.3 246.0 0.58

1B160 MULTIPURPOSE ROOM 1 2.9 Jul 1600 136 1.8 153.0 0.89

1B161 TOILET INT 1 0.2 Jan 2200 9 0.0 60.0 0.15

1B162 DEMENTIA ROOM 1 3.3 Jul 1600 157 2.3 235.0 0.67

1B163 TOILET EXT 1 0.7 Aug 1500 33 1.2 78.0 0.43

1B164 DEMENTIA ROOM 1 3.8 Oct 1500 178 1.4 251.0 0.71

1B165 TOILET EXT 1 0.7 Aug 1900 34 0.9 72.0 0.47

1B166 TOILET EXT 1 0.7 Aug 1900 31 0.9 64.0 0.49

1B167 DEMENTIA ROOM 1 3.8 Oct 1500 180 1.4 221.0 0.81

1B168 DEMENTIA ROOM 1 3.9 Oct 1500 183 1.4 239.0 0.76

1B169 TOILET EXT 1 0.7 Aug 1900 32 0.9 67.0 0.47

1B170 TOILET EXT 1 0.7 Aug 1900 31 0.9 65.0 0.48

1B171 DEMENTIA ROOM 1 3.8 Oct 1500 182 1.4 236.0 0.77

1B172 DEMENTIA ROOM 1 3.9 Oct 1500 183 1.4 240.0 0.76

1B173 TOILET EXT 1 0.7 Aug 1900 32 0.9 67.0 0.47

1B174 TOILET EXT 1 0.7 Aug 1900 31 0.9 65.0 0.48

1B175 DEMENTIA ROOM 1 3.8 Oct 1500 182 1.4 235.0 0.77

1B176 DEMENTIA ROOM 1 3.9 Oct 1500 183 1.4 243.0 0.75

1B177 TOILET EXT 1 0.6 Aug 1700 31 0.9 75.0 0.41

CORRIDOR UNIT A NORTH 1 0.9 Jan 2200 41 0.0 550.0 0.07

CORRIDOR UNIT A SOUTH 1 1.5 Jan 2200 70 0.0 932.0 0.07

CORRIDOR UNIT B NORTH 1 1.0 Jan 2200 48 0.0 636.0 0.07

CORRIDOR UNIT B SOUTH 1 1.6 Jan 2200 75 0.0 997.0 0.07

1B151 CLEAN LINEN 1 0.1 Jan 2200 4 0.0 27.0 0.15

1B152 CLEAN UTILITY 1 1.3 Jun 0900 62 1.3 109.0 0.56

1B153 SOILED UTILITY 1 0.7 Jul 2000 33 0.9 110.0 0.30

1B178A EQUIP STORAGE 1 4.6 Oct 1500 217 3.2 260.0 0.83

1B178B WOUND CARE STOR 1 0.3 Jan 2200 16 0.0 108.0 0.15

1B179 TOILET INT 1 0.2 Jan 2200 9 0.0 58.0 0.15

Zone 1A121

1C104 HIGH FALL RISK RM 1 4.1 Jun 1800 197 3.1 455.0 0.43

1C105 TOILET INT 1 0.2 Jan 2200 11 0.0 72.0 0.15

1C148 TOILET INT 1 0.2 Jan 2200 11 0.0 76.0 0.15

Hourly Analysis Program 5.11 Page 3 of 85

Prepared by: Bancroft A+E 02:14PM

Zone Name / Space Name Mult.

Cooling Sensible

(MBH)

Time of Peak

Sensible Load

Air Flow

(CFM)

Heating Load

(MBH)

Floor Area (ft²)

Space CFM/ft²

1C149 BARIATRIC ROOM 1 5.3 Sep 1200 252 2.7 302.0 0.83

1C178 HIGH FALL RISK 1 6.6 Jul 1800 313 3.1 478.0 0.65

1C179 TOILET INT 1 0.2 Jan 2200 10 0.0 68.0 0.15

1A118 DINING ROOM 1 12.4 Jan 2100 589 0.0 1589.0 0.37

1A127A KITCHEN SUPPORT 1 4.2 Jan 2100 199 0.0 485.0 0.41

1B135 SHOWER ROOM 1 0.9 Jan 2100 41 0.0 210.0 0.20

1B135A TOILET INT 1 0.1 Jan 2200 7 0.0 45.0 0.15

1B142 STAFF WORK AREA 1 2.6 Jan 2100 124 0.0 313.0 0.40

Zone 2A24

2A212A CONFERENCE ROOM 1 5.4 Jan 2100 258 0.0 463.0 0.56

2A212B CONFERENCE ROOM 1 5.0 Jan 2100 235 0.0 309.0 0.76

2B041 NOURISHMENT 1 3.7 Jan 2100 175 0.0 61.0 2.87

2B278 FAMILY ROOM 1 6.6 Oct 1500 311 3.1 472.0 0.66

Zone 2A20

2A218 DINING ROOM 1 14.5 Jan 2100 687 0.0 2247.0 0.31

2C204 HIGH FALL RISK 1 4.1 Jun 1800 197 3.1 454.0 0.43

2C205 TOILET INT 1 0.2 Jan 2200 11 0.0 72.0 0.15

2C248 TOILET INT 1 0.2 Jan 2200 11 0.0 73.0 0.15

2C249 BARIATRIC ROOM 1 5.4 Sep 1200 254 2.7 314.0 0.81

2C278 HIGH FALL RISK 1 6.6 Jul 1800 311 3.1 466.0 0.67

2C279 TOILET INT 1 0.2 Jan 2200 10 0.0 68.0 0.15

Hourly Analysis Program 5.11 Page 4 of 85

Ventilation Sizing Summary for 23-009 HINES VA CLC

Prepared by: Bancroft A+E 02:14PM

1. Summary Ventilation Sizing Method Sum of Space OA Airflows Design Ventilation Airflow Rate 0 CFM

2. Space Ventilation Analysis

Zone Name / Space Name Mult.

Floor Area (ft²)

Maximum Occupants

Maximum Supply Air

(CFM)

Required Outdoor Air

(CFM/person)

Required Outdoor Air

(CFM/ft²)

Required Outdoor Air

(CFM)

Required Outdoor Air

(% of supply)

Uncorrected Outdoor Air

(CFM)

Zone 1A114

1A100 ENTRANCE 1 652.0 0.0 618.8 0.00 0.00 0.0 0.0 0.0

1A100 ENTRANCE LOBBY 1 720.0 6.0 232.5 0.00 0.00 0.0 0.0 0.0

1A100 ENTRANCE LOBBY INT 1 400.0 0.0 59.8 0.00 0.00 0.0 0.0 0.0

1A104 WAITING / LIB 1 253.0 2.0 104.8 0.00 0.00 0.0 0.0 0.0

1A104A RECEPTION 1 210.0 2.0 98.4 0.00 0.00 0.0 0.0 0.0

1A105 CLINIC 1 179.0 3.0 143.4 0.00 0.00 0.0 0.0 0.0

1A106 CLINIC 1 182.0 3.0 167.0 0.00 0.00 0.0 0.0 0.0

1A107 CLINIC 1 168.0 3.0 141.7 0.00 0.00 0.0 0.0 0.0

1A108 CLINIC 1 177.0 3.0 141.7 0.00 0.00 0.0 0.0 0.0

1A109 CLINIC 1 178.0 3.0 103.8 0.00 0.00 0.0 0.0 0.0

1A111 SOCIAL WORKER 1 113.0 3.0 94.2 0.00 0.00 0.0 0.0 0.0

1A112 TOILET 1 78.0 0.0 11.7 0.00 0.00 0.0 0.0 0.0

1A141 WORKROOM 1 130.0 2.0 86.5 0.00 0.00 0.0 0.0 0.0

1A142 VITALS EXAM 1 127.0 2.0 86.0 0.00 0.00 0.0 0.0 0.0

1B148 TOILET INT 1 76.0 0.0 11.4 0.00 0.00 0.0 0.0 0.0

1B149 BARIATRIC ROOM 1 312.0 2.0 196.7 0.00 0.00 0.0 0.0 0.0

1B154 TOILET EXT 1 67.0 0.0 26.0 0.00 0.00 0.0 0.0 0.0

1B155 DEMENTIA ROOM 1 241.0 2.0 141.9 0.00 0.00 0.0 0.0 0.0

1B156 DEMENTIA ROOM 1 239.0 2.0 141.6 0.00 0.00 0.0 0.0 0.0

1B157 TOILET EXT 1 65.0 0.0 26.0 0.00 0.00 0.0 0.0 0.0

1B158 TOILET EXT 1 67.0 0.0 26.0 0.00 0.00 0.0 0.0 0.0

1B159 DEMENTIA ROOM 1 246.0 2.0 142.1 0.00 0.00 0.0 0.0 0.0

1B160 MULTIPURPOSE ROOM 1 153.0 2.0 136.0 0.00 0.00 0.0 0.0 0.0

1B161 TOILET INT 1 60.0 0.0 9.0 0.00 0.00 0.0 0.0 0.0

1B162 DEMENTIA ROOM 1 235.0 2.0 156.6 0.00 0.00 0.0 0.0 0.0

1B163 TOILET EXT 1 78.0 0.0 33.5 0.00 0.00 0.0 0.0 0.0

1B164 DEMENTIA ROOM 1 251.0 2.0 178.0 0.00 0.00 0.0 0.0 0.0

1B165 TOILET EXT 1 72.0 0.0 33.8 0.00 0.00 0.0 0.0 0.0

1B166 TOILET EXT 1 64.0 0.0 31.2 0.00 0.00 0.0 0.0 0.0

1B167 DEMENTIA ROOM 1 221.0 2.0 180.1 0.00 0.00 0.0 0.0 0.0

1B168 DEMENTIA ROOM 1 239.0 2.0 182.6 0.00 0.00 0.0 0.0 0.0

1B169 TOILET EXT 1 67.0 0.0 31.6 0.00 0.00 0.0 0.0 0.0

1B170 TOILET EXT 1 65.0 0.0 31.3 0.00 0.00 0.0 0.0 0.0

1B171 DEMENTIA ROOM 1 236.0 2.0 182.2 0.00 0.00 0.0 0.0 0.0

1B172 DEMENTIA ROOM 1 240.0 2.0 182.8 0.00 0.00 0.0 0.0 0.0

1B173 TOILET EXT 1 67.0 0.0 31.6 0.00 0.00 0.0 0.0 0.0

Hourly Analysis Program 5.11 Page 5 of 85

Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitybrands.com/nLight © 2014-2024 Acuity Brands Lighting, Inc. All rights reserved. Rev. 03/13/24 nCM xx RJB — TN-139-001

OVERVIEW

The nCM xx RJB family of nLight ceiling/surface mount occupancy sensors provide a range of networked sensor solutions for applications with finished ceilings (e.g. ceiling tiles, sheetrock, plaster). nCM xx RJB family sensors utilize 100% digital Passive Infrared (PIR) detection and are available with several lens options, providing flexibility for multiple mounting height and coverage pattern requirements. Dual technology occupancy detection can also be added as an option for applications where occupants are stationary for long periods of time. nCM xx RJB family sensors are also available with an optional auxiliary low voltage relay for simple integration with a BMS system or other building system.

nCM xx RJB family sensors are powered via the nLight network bus and typically communicate with one or more nLight enabled luminaires (e.g. Lithonia VTLED Series) or nLight relay/dimming packs to enable control of fixtures individually or in groups. These configurations work standalone and do not require a connection to a larger nLight network.

FEATURES

•100% digital PIR detection
•Optional dimming photocell (ADCX option)
•Optional auxiliary low voltage relay (AR option) for dry contact output – relay only tracks occupancy by

default, ignoring switch and photocell commands

•LED status indicator
•Adjustable settings (e.g. occupancy time delays, photocell set-points) via push-button or SensorView

software application

•Broadcasts occupancy and photocell information over a local nLight channel
•Remotely upgradeable firmware

Catalog Number: Date: Project:

nCM xx RJB nCM PDT xx RJB nCM 9 RJB nCM PDT 9 RJB nCM 10 RJB nCM PDT 10 RJB nCM 6 RJB

Buy American Act Product with the BAA option is assembled in the USA and meets the Buy America(n) government procurement requirements under FAR, DFARS and DOT regulations.

Build America Buy America Product with the BAA option also qualifies as produced in the United States under the definitions of the Build America, Buy America Act.

Please refer to www.acuitybrands.com/buy-american for additional information.

Warranty Five-year limited warranty. This is the only warranty provided and no other statements in this specification sheet create any warranty of any kind. All other express and implied warranties are disclaimed. Complete warranty terms located at: www.acuitybrands.com/support/warranty/terms-and-conditions

Note: Actual performance may differ as a result of end-user environment and application.

Specifications subject to change without notice.

Items marked by a shaded background qualify for the Design Select program and ship in 15 days or less. To learn more about Design Select, visit www.acuitybrands.com/designselect.

*See ordering tree for details

Capable This item is an A+ capable component, which has been designed and tested to provide out-of-the-box luminaire compatibility with simple commissioning, when included as part of an A+ Certified™ Solution.

To learn more about A+, visit www.acuitybrands.com/aplus.

https://www.acuitybrands.com/buy-american https://www.acuitybrands.com/support/warranty/terms-and-conditions https://www.acuitybrands.com/designselect

Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitybrands.com/nLight nCM xx RJB — TN-139-001 nCM xx RJB Example: nCM PDT 9 ADCX RJB

Series / Detection Coverage Type Options (See Below) RJ45 Port Location Buy America(n)2 nCM PIR Detection nCM PDT Dual Tech

(PIR/ Microphonics)

9 Small Motion 360° 10 Large Motion 360 ° 6 High Mount 360° (not available with PDT version)

RJB Rear RJ45 (CAT5e patch cable & RJ45 splitter included) blank Standard BAA Buy America(n) Act and/or

Build America Buy America Qualified

ORDERING INFORMATION

nCM xx RJB Options

Photocell Auxiliary Relay Preset Type 1 Time Delay Temp/ Humidity

[blank] Standard (No photocell) ADCX Automatic Dimming Control

(of remote dimming output)

[blank] None AR Low Voltage Aux. Relay

[blank] Single Time Delay 2P Dual Time Delay

[blank] Standard 15M 15 Minutes 20M 20 Minutes 30M 30 Minutes

[blank] Standard LT Low Temp / High

Humidity

NOTES:

1.Not available with AR or ADCX options.
2.Not available with AR, 2P, Time Delay, or LT options

COVERAGE PATTERNS*

HIGH MOUNT 360º (Model # nCM 6)

• Best choice for 15 to 45 ft (4.57 to 13.72 m) mounting heights

• 15 to 20 ft (4.57 to 6.10 m) radial coverage overlaps area lit by a typical high bay fixture

• Excellent detection of large motion (e.g.

walking) up to 35 ft (10.76 m)

• Excellent detection of extra large motion (e.g.

forklifts) up to a 45 ft (13.72 m)

30 20 10 0 ft 10 20 30

9.1 6 3 0 m 3 6 9.1

0 ft

0 m

4.6

9.1

13.7

LOW VIEW HIGH VIEW

0 ft

0 m

4.6

20 10 0 ft 10 20

6 3 0 m 3 6

30 20 10 0 ft 10 20 30

9.1 6 3 0 m 3 6 9.1

0 ft

0 m

4.6

9.1

13.7

LOW VIEW HIGH VIEW

0 ft

0 m

4.6

20 10 0 ft 10 20

6 3 0 m 3 6

• Best choice for large motion detection (e.g.

walking)

•360º conical shaped pattern
•Provides ~24 ft (7.32 m) radial coverage

(~2000 ft2) when mounted at 9 ft (2.74 m)

• 7 to 15 ft (2.13 to 4.57 m) mounting heights provide 16 to 36 ft (4.88 to 10.97 m) radial coverage

• Detection range improves when walking across beams compared to into beams

LARGE MOTION 360º (Model # nCM 10/nCM PDT 101)

0 ft

0 m

2.7

28 21 14 7 0 ft 7 14 21 28

8.5 6.4 4.3 2.1 0 m 2.1 4.3 6.4 8.5

SIDE VIEW TOP VIEW

0 ft

8.5

4.3

0 m

4.3

8.5

1 Sensors with Microphonics™ provides overlapping detection of human activity over the complete PIR coverage area. Advanced filtering is also utilized to prevent non-occupant noises from keeping the lights on.

• Best choice for small motion (e.g. hand movements) detection

•360º conical shaped pattern
•Provides 12 ft (3.66 m) radial coverage (~500

ft2) when mounted to standard 9 ft (2.74 m) ceiling

• 8 to 15 ft (2.44 to 4.57 m) mounting heights provide 10 to 20 ft (3.05 to 6.10 m) radial coverage

SMALL MOTION 360º (Model # nCM 9/nCM PDT 91)

12 6 0 ft 6 12

3.7 1.8 0 m 1.8 3.7

SIDE VIEW

0 ft

0 m

2.7

TOP VIEW

0 ft

3.7

1.8

0 m

1.8

3.7

1 Sensors with Microphonics™ provides overlapping detection of human activity over the complete PIR coverage area. Advanced filtering is also utilized to prevent non-occupant noises from keeping the lights on.

* Coverage pattern shown is derived from NEMA WD7 testing

Design Select options indicated by this color background.

jcruz Highlight nCM PIR Detection nCM PDT Dual Tech (PIR/ Microphonics) jcruz Highlight 9 Small Motion 360° 10 Large Motion 360 ° jcruz Highlight RJB Rear RJ45 (CAT5e patch cable & RJ45 splitter included) jcruz Highlight BAA Buy America(n) Act and/or Build America Buy America Qualified

Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitybrands.com/nLight nCM xx RJB — TN-139-001

Wiring an nCM xx ADCX RJB to an nLight Dimming Pack

Wiring to an nLight Enabled Luminaire

Wiring to an nLight Relay Pack

TYPICAL APPLICATIONS

The following instructions are for mounting sensor directly to a ceiling tile or sheetrock surface.1 Sensor’s mounting holes also align with standard round fixture or single gang handy box (screws not provided).

1. Using template included with unit, mark spots on ceiling tile/sheetrock for cable hole and mounting anchors/screws

2.Drill 1/2” hole through ceiling surface at location indicated on template
3.Insert provided anchors into ceiling surface at locations indicated on template
4.Remove provided RJ-45 splitter from sensor’s attached CAT5e cable and then thread

cable (and low voltage wires if -AR option included) through hole from underside

5.Mount sensor to anchors using two screws provided
6.Attach provided RJ45 splitter device (model CAT5 Y) above ceiling to cable from sensor

(see diagram on right)

7. Interconnect CAT-5e cables to/from rest of nLight zone to RJ45 splitter 2

8. Once power is received via CAT-5e connection, all devices in zone will automatically begin functioning together according to each device’s defaults

9.Install decorative sensor lid by rotating clockwise
10.Refer to included instruction card for default settings and directions on push-button

programming.

CAT-5e

BRN

BRN

CAT-5e Splitter

CAT-5e CAT-5e

- AR option (contact closure) to/from nLight Zone

TYPICAL APPLICATIONS

nPP16

WHT (neutral)

BLU (line in)

BLU (line out)

CAT-5e

120 VAC

OR

277 VAC1

BLK1 (line in)

ORN1 (line in)

LOAD

To other nLight devices (optional)

CAT-5e CAT-5e Splitter

(included)

CAT-5e CAT-5e

To other nLight devices (optional) nCM xx RJB

WHT(neutral)

BLU (line in)

BLU (line out)

VIO (low voltage dim out)

GRY (low voltage common)

GRN

CAT-5e nPP16 D or nPP16 DS

0-10 VDC

Ballast or

LED Driver

120 VAC

OR

277 VAC1 ORN1 (line in)

BLK1 (line in)

To other nLight devices (optional)

CAT-5e Splitter (included)

CAT-5e CAT-5e

To other nLight devices (optional) nCM xx ADCX RJB

CAT-5e To other nLight devices (optional) nLight Enabled Luminaire

CAT-5e Splitter (included)

CAT-5e CAT-5e To other nLight devices (optional) nCM xx RJB or nCM xx ADCX RJB

Note:

1.Recommended mounting 4’ or more away from HVAC vents.
2.T568B pin/pair assignment is recommended for all CAT-5e cables. Sensor power is

provided via a CAT-5e connection to an nLight power pack/supply, nLight enabled digital luminaire, or nLight Bridge.

Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitybrands.com/nLight nCM xx RJB — TN-139-001

Electrical Input Ratings 15-24VDC, 3mA, Class 2 (nLight network power)

Output Ratings 24 VAC/VDC, 1A - Resistive (AR option)

Relay Type Latching (AR option)

Standards/ Ratings Energy Management Equipment, UL916 (E167435)

Mechanical Dimensions 4.55”W x 1.55”D (116mm x 40mm)

Mounting Single-Gang or Octagonal Box, Surface Mount

Color White

Finish Matte Connection Type RJ-45 nLight Network Ports (2 ports via included RJ-45 splitter)

Low-Voltage Leads (AR option)

Environmental Warrantied Operating Temperature Standard: 14°F to 185°F (-10°C to 85°C) PDT option: 14°F to 140°F (-10°C to 60°C) LT option: -4°F to 185°F (-20°C to 85°C) PDT LT options: -4°F to 140°F (-20°C to 60°C)

Relative Humidity Up to 90%, Non-Condensing Standards/ Ratings RoHS

General Standards/ Ratings System Component to aid in compliance with Title 24, ASHRAE 90.1, IECC

SPECIFICATIONS

Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitybrands.com/nLight © 2019-2024 Acuity Brands Lighting, Inc. All rights reserved. Rev. 04/16/24 nPODMA

OVERVIEW

The nPODMA Series WallPods are single gang nLight-enabled decorator wall switches that enable toggle/ raise/lower/scene control of lighting zones. Equipped with soft-click push-buttons, and a green LED indicator for each button, these devices allow field replaceable and custom engraved button options.

nPODMA WallPods communicate with other nLight devices, via CAT-5e cable, through RJ-45 connectors and can be daisy-chained to work with nLight power packs and/or nLight-enabled fixtures to provide switch control operations.

The scene control option presents a convenient method of selecting a custom lighting control scene for spaces in which installed, or requesting a global profile scene be run across several remote zones. By default, scene control wall switches are configured as on/off toggle switches and are to be customized programmatically through the SensorView software.

*In order to utilize a blink warning, system gateway and additional programming is required.

FEATURES

•Communicates with nLight network
•Remotely configurable/upgradeable
•Soft-click push-button control
•Sets lights to one of two or four preset levels with single button push (nPODMA xL versions only)
•Scene controllers run locally stored scenes or global scenes (stored on gateway)
•Capable of Programming 4 Different Scene Types
•Local “Profile” Scene — Modifies the operational configuration of up to 80 devices in the local

zone. Stopping scene will revert devices to default settings.

• Local “Preset” Scene — Modifies on/off/dim levels for up to 16 local switch groups. Exit scene through additional “preset” scene or WallPod control.

• Global “Profile” Scene — Modifies the operational configuration of any devices on the system.

Stopping scene will revert devices to default settings. Scene is stored on the system Gateway.

• Global “Preset” Scene — Modifies on/off/dim levels for up to 128 global switch groups. Exit scene through additional “preset” scene or WallPod control.

• Easy-to-install screwless wall plate design offers a clean, uninterrupted aesthetic for a more refined look in the space.

• A full range of color options provides a variety of choices for your building designs with the assurance that the housing and the wall plate match.

•1, 2, or 4 channel on/off
•1, 2, or 4 channel raise/lower
•“Dynamic” options for custom button names when pairing with Acuity Brands nTUNE fixtures

CUSTOM BUTTON ENGRAVING

•Standard Button labeling is shown on back
•Custom lettering for units can be specified and ordered at: nGrave Form
•To ensure color uniformity, ordering templates facilitate specifying all buttons on a unit as custom

lettered. Replacing single buttons not recommended

• Buttons may ship separately and require field installations nPODMA Wallpod: On/Off & On/ Off+Raise/Lower

Catalog Number: Date: Project:

Government Procurement BAA – Buy America(n) Act: Product with the BAA option qualifies as a domestic end product under the Buy American Act as implemented in the FAR and DFARS. Product with the BAA option also qualifies as manufactured in the United States under DOT Buy America regulations.

BABA – Build America Buy America: Product with the BAA option also qualifies as produced in the United States under the definitions of the Build America, Buy America Act.

Please refer to www.acuitybrands.com/buy-american for additional information.

Warranty Five-year limited warranty. This is the only warranty provided and no other statements in this specification sheet create any warranty of any kind. All other express and implied warranties are disclaimed. Complete warranty terms located at: www.acuitybrands.com/support/ warranty/terms-and-conditions Note: Actual performance may differ as a result of end-user environment and application.

Specifications subject to change without notice.

Items marked by a shaded background qualify for the Design Select program and ship in 15 days or less. To learn more about Design Select, visit www.acuitybrands.com/designselect.

*See ordering tree for details

Capable This item is an A+ capable component, which has been designed and tested to provide out-of-the-box luminaire compatibility with simple commissioning, when included as part of an A+ Certified™ Solution.

To learn more about A+, visit www.acuitybrands.com/aplus.

https://img.acuitybrands.com/public-assets/catalog/1137611/ngrave-request-form.pdf?abl_version=03%2f03%2f2023+13%3a33%3a45&DOC_Type=Technical_Bulletins http://www.acuitybrands.com/buy-american http://www.acuitybrands.com/support/warranty/terms-and-conditions http://www.acuitybrands.com/support/warranty/terms-and-conditions https://www.acuitybrands.com/designselect http://www.acuitybrands.com/aplus

Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitybrands.com/nLight nPODMA nPODMA Example: nPODMA DX WH

Series Poles & Scenes Dimming Control Dynamic Color Temp/Humidity Buy America(n)67 nPODMA [blank] None 2P Two channels 4P Four channels 2L 1 Two levels 2L AB 1 High/low step control 4L 2 Four levels with raise/lower 1SB 1 1 Scene control (2 buttons) 2S 2 Scene control (2 buttons) 2SB 1 2 Scene control (4 buttons) 4S 4 Scene control (4 buttons) 4SB 1 4 Scene control (8 buttons)

[blank] Standard DX On/off + raise/lower control

[blank] Standard CCT 3 Correlated color temperature GRSC 5 Grayscale COLOR 5 Color control EDUTW4 Tuneable White

WH White IV Ivory GY Gray AL Lt Almond BK Black RD Red

[blank] Normal LT Low temp

[blank] Standard BAA Buy America(n)

Act and/or Build America Buy America Qualified

ORDERING INFORMATION

WIRING

TYPICAL WIRING

WallPods and/or nLight wall switch sensors can be configured together to create zones with multiple switching locations.

nPP16 EFP

CAT-5

LOAD

CAT-5

120 V 277 V

BLK

ORN

Power to WallPod device is provided via the CAT-5e connection to an nLight enabled fixture, nLight power pack (e.g. nPP16), power supply (nPS80), or Bridge (nBRG 8).

nPP16 EFP

CAT-5

LOAD

CAT-5CAT-5

120 V 277 V

BLK

ORN

ON/OFF

3-WAY CONFIGURATION WIRING

Notes

1.Not available with DX option.
2.Only available with DX option.
3.Only available with 2P DX version.
4.Only available with 4S and 4S DX versions.
5.Only available with 2P DX and 4S DX versions.
6.Only available in WH, IV, or GY.
7.Not available with LT option.
8.Only available for Variety Packs.
9.Not available for SSW Series.
10.Ships with custom screwless wall plate.
11.Single units only available with SSW series.

ACCESSORIES

Series # of Gangs Mounting Color Packaging

WS xPODA Wall Plates (Standard)

SSW 10 Sealed Cover

1 GNG Single Gang

[blank] Standard WH White IV Ivory GY 9 Gray AL 9 Lt Almond

BK 9 Black RD Red VP 9 Variety Pack

[blank] Single Unit 11

M5 9 5 Pack M6 8,9 6 Pack

All nPODMA switches are shipped with wall plates and mounting flanges (WS XPODA), and mounting flanges (WS XPODA), however, the following order information is available to acquire replacement wall plates. Also compatible with the WALLP Series.

WALL SWITCH CLEANING

It will occasionally be necessary to clean the wall switches. All nPODMA switches may be wiped down with a soft cloth or paper towel dampened with glass cleaner, vinegar and water, hydrogen peroxide, or a mild abrasive. Spray a limited amount on the cloth or paper towel prior to applying. Do not spray cleaner on the switches directly, and do not wipe the switches down with a towel saturated (drips when wrung out) with cleaner.

If the ability to clean the switches using chemical spray disinfectants is desired, we recommend the use of the Sealed Screwless Wall Plate (SSW). The Sealed Screwless Wall Plate is a cover for the standard wall plate, designed with an IP54 rating. It consists of a transparent silicone rubber layer that covers the wall switch to prevent liquids from entering the wall switch while maintaining a tactile button feel. The Sealed Screwless Wall Plate is the ideal solution to help protect a wall switch from fluid entering the device while enabling the use of disinfectants recommended by the EPA for use against SARS-CoV-2, the coronavirus that causes COVID-19, which often require spraying or saturating the surface.

For more information on the Sealed Covers

ON/OFF + DIMMMING (nPODMA DX)

[D] Dimming Control

CAT-5

LOAD

CAT-5

120 V 277 V

BLK

ORN

VIO

nPP16 EFP

PN

K

Design Select options indicated by this color background.

https://img.acuitybrands.com/public-assets/catalog/1715568/wallp-series.pdf?abl_version=11%2f18%2f2021+21:06:49&DOC_Type=SPEC_SHEET) https://sensorswitch.acuitybrands.com/products/detail/1715566/sensorswitch/ssw-series/sealed-screwless-wall-plate jcruz Highlight nPODMA jcruz Highlight [blank] Standard DX On/off + raise/lower control jcruz Highlight WH White jcruz Highlight [blank] Normal jcruz Highlight BAA Buy America(n) Act and/or Build America Buy America

Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitybrands.com/nLight nPODMA

DEFAULT LABELING

ODMA 2SB nPODMA 4SnPODMA 2S DX nPODMA 4SB nPODMA 4S DXMA 2S nPODMA 2SB nPODMA 4SnPODMA 2S DX nPODMA 4SB nPODMA 4S DXDMA 2S nPODMA 2SB nPODMA 4SnPODMA 2S DX nPODMA 4SB nPODMA 4S DX nPODMA 1SB nPODMA 2S nPODMA 2SB nPODMA 4SnPODMA 2S DX nPODMA 4SB nPODMA 4S DXnPODMA 1SB nPODMA 2S nPODMA 2SB nPODMA 4SnPODMA 2S DX

SB nPODMA 2S nPODMA 2SB nPODMA 4SnPODMA 2S DX nPODMA 4SB nPODMA 4S DX nPODMA 1SB nPODMA 2S nPODMA 2SB nPODMA 2S DX

Dynamic wallpods below are paired with Acuity Brands nTUNE fixtures for out-of-box operation. Reference fixture cut sheets for additional details.

nPODMA 4S EDUTW nPODMA 4S DX GRSCnPODMA 4S DX COLORnPODMA 4S DX EDUTW

ON/OFF

COLOR

nPODMA 2P DX COLOR

ON/OFF

CCT

nPODMA 2P DX CCT

ON/OFF

GRAYSCALE

nPODMA 2P DX GRSC

ON

OFF

nPODMA

ON/OFF

nPODMA DX

ON

OFF

ON

OFF

nPODMA 2P

ON/OFF

ON/OFF

nPODMA 2P DX

ON OFF

ON OFF

ON OFF

ON OFF

nPODMA 4P

ON

OFF

nPODMA 4P DX

LEVEL 1

100% nPODMA 2L

LEVEL 2

50%

ON/OFF

LEVEL 1

LEVEL 2

nPODMA 4L DX

LEVEL 1

100%

LEVEL 3

50%

LEVEL 2

75%

LEVEL 4

25%

On

Off

LEVEL

LEVEL

LEVEL

LEVEL

Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitybrands.com/nLight nPODMA

Electrical Input Ratings 15-24VDC, 5mA, Class 2 (nLight network power)

Standards/Ratings Energy Management Equipment, UL916 (E167435)

Mechanical Dimensions 2.74”H x 1.68”W x 1.63”D (70mm x 43mm x 41mm) - does not include ground strap

Mounting Single-Gang Box or Low Voltage Ring Connection Type RJ-45 nLight Network Ports (2)

Environmental Warrantied Operating Temperature 32°F to 140°F (0°C to 60°C) LT Option: -4°F to 140°F (-20°C to 60°C)

Relative Humidity Up to 90%, Non-Condensing Standards/ Ratings RoHS

Security Complies with California Civil Code Title 1.81.26, Security of Connected Devices, approved under Senate Bill No. 327 (2018)

SPECIFICATIONS

•Ensure CAT-5e cable(s) an effectively fed through the gang box
•Push the CAT5e cables through the back of the gang box

• Remove the wall plate from the device by pulling the sides out to expand the wall plate and release it from the mounting flanges.

•Access RJ-45 port(s) on the WallPod by sliding the plastic guard up
•Insert the CAT-5e cable(s) to the RJ-45 port(s)
•Slide the guard back onto metal strap
•Connect the unit to the gang box
•The unit will connect to the gang box by screws, one at the top and one at the bottom
•To ensure correct wall plate installation, drive the screws until the mounting flanges

contact the wall surface. If the screws are overdriven, the mounting flanges will disengage, preventing wall plate installation. If this happens, reattach the mounting flange(s) and install to correct position. (The flanges may be reattached by inserting the two tabs in the side of the unit and pushing the part inward to engage the three snaps.)

•Reattach the wall plate
•Expand the wall plate horizontally
•Place the wall plate onto the unit
•Contract the horizontally expanded wall plate onto the unit such that the side flange

features seat inside the wall plate

SLID

E

TO RJ-45 PORT

TO RJ-45 PORT

CAT-5

CAT-5

PROGRAMMING

• Refer to instruction card IN-11.3 for directions on programming the switch via the upper-most left push-button. All buttons are factory set to the matching switch channel (button 1 - channel 1, button 2 - channel 2, etc). For nPODMA 4P DX, channels to be controlled are selected first, then the control button (on/off or raise/lower).

• For 2L and 4L variants, the preset dim level of a button can be changed by first adjusting the light level with either the unit’s raise/lower buttons (nPODM 4L DX) or via another raise/lower WallPod broadcasting on the same switch channel (necessary with a nPODM 2L). Once lights are at desired level, hold a LEVEL button for 8 seconds until the LED flashes. Levels can also be set via SensorView.

INSTALLATION

Attention! Only use non-booted CAT5e cables.

Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitybrands.com/nLight © 2020-2024 Acuity Brands Lighting, Inc. All rights reserved. Rev. 02/29/24

NWSXA

OVERVIEW

The nWSXA series nLight wall switch occupancy sensor provides a simple control solution for a small room, in particular one utilizing nLight enabled digital luminaires. Capable of detecting small motion up to 20 ft (6.10 m), this sensor is perfect for private offices, private rest rooms, copy rooms, closets or any small enclosed space. Available as Passive Infrared (PIR), or PIR/Microphonics Dual Technology (PDT), this stylish sensor can be programmed locally, via the front push button(s), or remotely via the nLight software solutions. The nWSXA includes an integrated photocell (inhibit only — disabled by default).

FEATURES

•100% digital PIR detection, vandal resistant lens standard, includes screwless wall plate
•Push-button programmable, adjustable time delays, multiple operating modes
•Multiple nWSXA sensors or WallPods can be used in 3 way(or greater) configurations w/o traveler wires
•Photocell standard (inhibit only — disabled by default)
•Broadcasts occupancy, photocell, and switch information over a local and/or global nLight channel
•Remotely firmware upgradeable

CONTROL MODES

A control zone with an nWSXA can operate in several modes:

1.Auto On / Auto Off (i.e. Fully Automatic)
2.Manual On (initial state) to Override On (with expiration timer)
3.Auto On (initial state) to Override On (with expiration timer)
4.Manual On / Automatic Off (i.e. Semi-Automatic)
5.Manual On (initial state) to Fully Automatic
6.Predictive Off Switch (returns zone to auto-on unless person remained in room after an off switch press)

*See MLO operation chart on page 2.

Catalog Number: Date: Project:

nWSXA Low Voltage Wall Switch Sensor nWSXA DX

Buy American Act Product with the BAA option is assembled in the USA and meets the Buy America(n) government procurement requirements under FAR, DFARS and DOT regulations.

Build America Buy America Product with the BAA option also qualifies as produced in the United States under the definitions of the Build America, Buy America Act.

Please refer to www.acuitybrands.com/buy-american for additional information.

Warranty Five-year limited warranty. This is the only warranty provided and no other statements in this specification sheet create any warranty of any kind. All other express and implied warranties are disclaimed. Complete warranty terms located at: www.acuitybrands.com/support/warranty/terms-and-conditions Note: Actual performance may differ as a result of end-user environment and application.

Specifications subject to change without notice.

nWSXA Example: nWSXA LV DX WH

Series Occupancy Detection Voltage Dimming Color Temp/Humidity Buy America(n)1 2 nWSXA Passive Infrared

[blank] PIR Detection PDT Dual Tech - PIR/

Microphonics

LV Low Voltage [blank] None DX Raise/Lower dim control

WH White IV Ivory GY Gray

AL Lt. Almond BK Black RD Red

[blank] Standard LT Low temp

[blank] Standard BAA Buy America(n)

Act and/or Build America Buy America Qualified

ACCESSORIES

Series # of Gangs Mounting Color Packaging

WS xPODA Wall Plates (Standard)

SSW 5 Sealed Covers

1 GNG Single Gang

[blank] Standard OCC 6 Occ. Wall

Switch

WH White IV Ivory GY 4 Gray AL 4…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .