5c. 578-26-016 CLIN1 100 Percent Bid Drawings -Part 3.pdf
PDF 7 MB Posted
- Solicitation number
- 36C25226B0028
About this file
This file contains mechanical construction drawings and schedules for the Renovations to Building 217 at Edward J. Hines Jr. VA Medical Center (VAMC) under VA Contract No. 578-26-016. The drawings depict the complete mechanical systems design for the project, including detailed specifications for HVAC equipment, piping, ductwork, controls, and related infrastructure.
The mechanical systems include a primary air handling unit (AHU-1) rated at 7,000 CFM supply and return air with steam preheat and cooling capabilities, an air-cooled chiller system (ACCU-1) with 75-ton capacity and redundant glycol-water pumps, variable air volume (VAV) terminal boxes with hot water reheat coils throughout the building zones, centrifugal roof exhaust fans (EF-08, EF-09, EF-11), and a ductless split system (DFSS-108A) for supplemental cooling. The design incorporates energy recovery through heat pipe technology (ERC-1), direct digital controls (DDC) for all terminal units and primary equipment, glycol-based freeze protection down to -20°F, and full seismic bracing compliant with Risk Category IV standards. HVAC piping includes Schedule 80 steel for steam and copper for chilled/hot water with insulation, vibration isolation, and support requirements specified throughout. The project specifications emphasize coordination with architectural and structural elements, ADA compliance for all electrical controls and devices, VA-approved equipment equivalents, and adherence to the latest National Electrical Code, ASME standards, and SMACNA guidelines. All equipment is scheduled for new installation with full operational testing, commissioning of controls systems, and transfer to VA operations.
View the file
Other files
Show all 43
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
40 TONS & HIGHERTXV EQUALIZING LINE
VALVED BYPASS FOR FILTER DRYER 40 TONS & HIGHER
STRAINER 40 TONS & HIGHER
SIGHT GLASS/MOISTURE INDICATOR 25 TONS & HIGHER
SOLENOID VALVE 20 TONS & HIGHER
FILTER DRYER 5 TONS & HIGHER
THERMAL EXPANSION VALVE 5 TONS & HIGHER
CAPILLARY TUBE SYSTEM 4 TONS & LOWER
DEVICE APPLICATION
REFRIGERANT DEVICE APPLICATION SCHEDULE
2D
NTS
MAXIMUM PIPE/TUBING SUPPORT SPACING
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
NOM. SIZE
PIPE
TUBING
IN.
FT.
FT.
1" M
AX
1THRU 3/4
5 FT
1 1/21 1/4 2
2 1/2
TYPICAL WATER PIPING
NTS
NTS
D
SIDE VIEW TRAPEZE HANGER FOR UP
TO 1000 LB. UNIFORM LOAD
ADJUSTABLE CLEVIS HANGER
TYPE 1 - SEE SPECIFICATIONS
ADJUSTABLE CLEVIS HANGER
TYPE 43 - SEE SPECIFICATIONS
BUILT IN BIRD
SCREEN 1/2" MESH
CENTRIFUGAL ROOF
EXHAUSTER
ROOFING & FLASHING OF
CURB BY GENERAL CONTR.
BUILT-IN DISCONNECT
FURNISHED AND INSTALLED
TO SUIT ROOF PITCH
PRE-FAB ROOF CURB SLOPED
POWER WIRING
SEE DRAWINGS FOR SIZE.
EXHAUST DUCT UP THRU ROOF
SWITCH
CONDUIT
BY VENTILATION CONTR. GRAVITY
BACKDRAFT DAMPER
(SEE SCHEDULE)
N.C. MOTOR OPERATED
DAMPER (SEE FLOOR PLAN)
M
CU
DFSS
BAND
1-5/8" 12 GAUGE
CHANNEL OR 2"x2"x1/4"
ANGLE
1/2" DIA. HANGER RODS WITH 36"
MAX. SPACING ON EACH
CHANNEL
WELD
SADDLEINSULATION SHIELD
AT HANGER
PROVIDE HIGH
COMPRESSIVE STRENGTH
INSULATION (9 PSF MIN.
DENSITY) UNDER INSULATION
SHIELD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE)
HANGER ROD
PIPE HANGER DETAIL
NOTES:
SEE SPECIFER FOR DETAILED
HANGER REQUIREMENTS
PROVIDE INSULATION
SHIELD & INSERT FOR
ALL PIPING (8" MIN.)
PIPE HANGER
STEEL BEAM
HANGER ROD
CONCRETE INSERT
CONCRETE SLAB
INSERT NUT
HANGER ROD
LOCKING NUT
HANGER ROD
LAG SCREWS
SUPPORT NUT
WOOD JOIST OR BEAM
WELDS WEB MEMBERS O.W.S.J.
HANGER NUT
STEEL JOIST
PIPE HANGERS AND SUPPORTS
SUPPORT HORIZONTAL STEEL AND COPPER PIPING AS FOLLOWS:
NOMINAL PIPE SIZE
1/2"
3/4 TO 1-1/2"
2" TO 2-1/2"
3" AND 4"
6" TO 12"
14" TO 18"
DISTANCE BETWEEN SUPPORTS HANGER ROD DIAMETERS
3/8"
1/2"
1/2"
5/8"
7/8"
1"
6'
6'
10'
12'
14'
20'
HEAVY-DUTY
BEAM CLAMP
STRUCTURAL STEEL
BEAM
ADJUSTABLE
STEEL U-SUPPORT
WOOD JOIST OR
BEAM
HEAVY-DUTY CONCRETE STEEL
INSERT W/ELONGATED SLOT.
BENT STRAP 1 1/2" x 3/16" OVER VERTICAL
LEGS OF ANGLES.
ONE ANGLE EACH SIDE OF WEB MEMBERS. REST ON TOP OF
BOTTOM CHORD OF O.W.S.J. BETWEEN PANEL POINTS. SIZE
FOR LOAD.
HANGER ROD
BOTTOM CHORD OF
O.W.S.J.
PLACE HANGER WITHIN 1 FOOT OF EACH HORIZ. ELBOW. SUPPORT HORIZ. SOIL WASTE AND STORM PIPE NEAR EACH HUB, WITH 5 FEET MAXIMUM SPACING BETWEEN HANGERS. VERTICAL PIPING:
1. SUPPORT VERTICAL WATER PIPING AT EVERY FLOOR.
2. SUPPORT VERTICAL SOIL PIPE AT EACH FLOOR AT HUB.
WHERE SEVERAL PIPES CAN BE INSTALLED IN PARALLEL AND AT SAME ELEVATION PROVIDE MULTIPLE OR TRAPEZE HANGERS. WHERE PRACTICAL, SUPPORT RISER PIPING INDEPENDENTLY OF CONNECTED HORIZ. PIPING.
NTS
NTS
TYPICAL MANUAL AIR VENT
TYPICAL CHILLED AND HOT WATER
PIPING DRAIN VALVE CONNECTIONS
ELEVATION THREADED PIPING ELEVATION WELDED PIPING
REDUCER, IF REQUIRED
3/4" BALL VALVE
ADAPTER TO 3/4" HOSE
THREAD-PROVIDE HOSE CAP NUT
NOTES:
1. DRAIN ALL LOW POINTS AS INDICATED ABOVE.
2. WHERE SCALE POCKETS ARE SHOWN ON PIPE RISER DIAGRAMS
AND/OR PLANS LOCATE DRAIN AT BOTTOM OF SCALE POCKET.
AIR VENT
1/2"
BALL VALVE
1/4"
COPPER TUBING
1/2" x 4"
NIPPLE
CIRCULATING WATER PIPING
ELEVATION
NOTES:
1. VENT ALL HIGH POINTS INDICATED ABOVE.
2. IF AUTOMATIC AIR VENTS ARE USED, PIPE DISCHARGE TO DRAIN.
DRAIN VALVE AND AIR VENT CONNECTIONS (HYDRONIC
SYSTEMS)
MV
OR
AV
NTS
DUCTWORK FLEXIBLE CONNECTION DETAIL
ROUND FLEXIBLE CONNECTION
RECTANGULAR FLEXIBLE CONNECTION
FLANGED CONNECTION
ON FAN SIDE
1-1/2" MIN. TO 3"
MAX. INSTALLED. 6"
NOMINAL WITH MATERIAL TAUT
1"x1/8" DRAW BAND
DUCT
SHEET METAL SCREWS ON
12" CENTERS
RIVET ON 4"
CENTERS
SHEET METAL AS
SPECIFIED FOR
DUCTWORK.
DUCT
1/2" 1/2" 1 1/2"
WASHER
WASHER
NON CANVAS TYPE
FLEXIBLE MATERIAL
NTS
END OF STEAM LINE DRIP TRAP
CONDENSATE
STEAM PIPE
1 1/2" MIN. TO 3" MAX.
INSTALLED. 6"
NOMINAL WITH
MATERIAL TAUT
FLANGED
CONNECTION
ON FAN
SIDE
ALTERNATE
POSITION OF
BOLT
1" FLANGE & HEM
BOLT ON 4" CENTERS
1"x1/8" BAND IRON
NON CANVAS
TYPE FLEXIBLE
MATERIAL
SHEET METAL AS
SPECIFIED FOR
DUCTWORK.
1 1/2" POCKET SLIP
5/16" FLANGE
BOLT ON 4" CENTERS
1"x1/8" BAND IRON
CONCRETE EQUIPMENT BASES
NTS
SECTION A-A (BASE NOT POURED WITH SLAB)
SECTION A-A (BASE POURED WITH FLOOR SLAB)
PLAN SECTION B-B
FLOOR
L
W
A
A
D
16"
L /1
L
/1
5D
5D
5" M
IN
5" M
IN
PROVIDE #3 BARS 12" O.C.
EACH WAY IN THE BASE &
DOWEL BASE TO FLOOR
NOTE:
L & W DIMENSIONS
SHALL BE 6" GREATER
THAN THE EQUIPMENT
BASE PLATE.
WELD HEAD TO PLATE
OR BEND OVER END 5D
PIPE SLEEVE
(5D, 3" MIN.)
ANCHOR
BOLT (TYP)
CONCRETE BASE
TYPICAL ANCHOR
BOLT NUT & WASHER
EQUIPMENT BASE PLATE
PROVIDE DOUBLE SLAB
REINFORCING IN BASE AREA
TYPICAL ANCHOR
BOLT NUT & WASHER
EQUIPMENT BASE PLATE
B B
TO DRAIN
MV
MANUAL
AIR VENT
TO BUILDING
LOAD
INVERTED BUCKET
TRAP ASSEMBLY
WELDED
TEE
12"
6"
SCHEDULE 80 STEEL PIPE
1" GATE VALVE
9 7 56
CENTRIFUGAL ROOF EXHAUSTER DETAIL
NTS
EQUALIZING LINE
CONTROL WIRING IN CONDUIT
STRAINER
PITCH IN DIRECTION
OF FLOW.
NOTES:
REFRIGERANT PIPING AS SHOWN IS TO ILLUSTRATE GENERAL REQUIREMENTS.
PIPING SHALL BE SIZED, PITCHED, AND ARRANGED PER CONDENSING UNIT
MANUFACTURER'S RECOMMENDATIONS AND REQUIREMENTS.
1.
POWER WIRING IN CONDUIT
FLOOR DRAIN
PIPE TO INDIRECT
NOTE:
REFRIGERANT SPECIALTIES, TXVs, SIGHT GLASSES, EQUALIZING LINES, ETC. ARE SHOWN FOR INTENDED OPERATION OF TYPICAL DX SYSTEMS
REQUIREMENTS. LOCATIONS AND DEVICES MAY NOT BE APPLICABLE FOR
SMALL TONNAGE SPLIT SYSTEMS AND MANY MAY BE INTERNAL TO THE
SCHEDULED COMPONENTS. PROVIDE FULLY OPERATIONAL SYSTEMS WITH
REFIGERANT SPECIALTIES AND DEVICES REQUIRED. PROVIDE ADDITIONAL
SERVICE VALVES FOR SUCTION AND LIQUID LINES AT EVAPORATOR AND
ACCU SECTIONS.
OUTDOOR
CONDENSING
UNIT
VIBRATION ISOLATORS
ROOF MOUNTED
EQUIPMENT RAIL
SERVICE VALVES (TYPICAL)
ROOF
PIPING CURB
OIL TRAP (INSTALL PER
MANUFACTURER'S RECOMMENDATIONS)
LIQUID LINE
SUCTION LINE
OIL TRAP (INSTALL PER
MANUFACTURER'S RECOMMENDATIONS)
CHARGING VALVE
FILTER/DRYER
SIGHT GLASS/MOISTURE INDICATOR
SOLENOID VALVE
THERMAL EXPANSION VALVE
FACTORY CONDENSATE PUMP
WITH BUILT-IN AIR GAP
INDOOR
"DX" COOLING COIL
SERVICE VALVES (TYPICAL)7'-0" AFF WHERE
CONDITIONS
ALLOW (TYPICAL)
INSULATED
DRIP PAN
SENSING BULB
RUNNING TRAP W/CLEANOUTS
DFSS UNIT REFRIGERANT PIPING DETAIL (ROOF)
STEAM SAFETY VALVE
PROVIDE UNION UNLESS SAFETY
VALVE HAS FLANGED OUTLET
SAFETY VALVE
OPEN DRAIN (NOTE 3)
CONNECTION TO
PRESSURE VESSEL OR PIPE
VENT PIPE THROUGH ROOF SUPPORT AS
INDICATED ON DWGS. (NOTES 1, 2)
PIPE THREADED INTO ELBOW (SAME SIZE AS
ELBOW)
DRIP PAN ELBOW (SECTIONAL VIEW)
3/4" DRAIN TO FLOOR DRAIN OR OPEN SIGHT
DRAIN (NOTE 4)
1" M
IN
24" MAX
3"
ELEVATION
NOTES:
1. UNLESS OTHERWISE SHOWN ON THE DRAWINGS, SIZE THE VENT PIPE SO THAT STEAM IS NOT BLOWN OUT AT THE VENT PIPE ENTRANCE. UTILIZE THE CALCULATION METHOD CONTAINED IN ANSI B31.1.
POWER PIPING CODE, APPENDIX II. THE VENT PIPE SHOULD GO VERTICAL THRU THE ROOF WITH NO TURNS OR ANGLES. WHERE REQUIRED THERE SHALL BE NO MORE THEN A TOTAL OR 180 DEGREES IN
DIRECTIONAL CHANGES MADE WITH 45 DEG. ELBOWS.
2. VENT PIPE SHALL TERMINATE 6' MIN. ABOVE FINISHED ROOF OR GRADE.
3. DISCHARGE OF DRAIN SHALL BE DIRECTED AWAY FROM PLATFORMS OR OTHER AREAS WHERE
PERSONNEL MAY OCCUPY.
4. DO NOT CONNECT ANY OTHER DRAIN TO THE DRIP PAN ELBOW DRAIN PIPE.
5. SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
FLEXIBLE CONNECTOR
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
FULLY SPRINKLERED
Bancroft Project No. VA CONTRACT NO.
MECHANICAL DETAILS RENOVATIONS TO
BUILDING 217
EDWARD J. HINES JR. VAMC
06/10/2026 RH RBB
578-26-016
M503
100% CONSTRUCTION
DOCUMENTS
23-00936C25223C0071
Revisions: Date:
30% SCHEMATIC DESIGN 11/23/2023
60% DESIGN DEVELOPMENT 05/08/2024
90% CONSTRUCTION DOCUMENTS 08/23/2024
100% CONSTRUCTION DOCUMENTS 12/06/2024
ISSUE FOR CONSTRUCTION 11/25/2025
100% CONSTRUCTION DOCUMENTS 06/10/2026
T
AIRFLOW
STEAM
HUMIDIFER
NOTES:
1. TRANSITION WELDED STAINLESS STEEL 4' UPSTREAM OF HUMIDIFIER AND 8' DOWNSTREAM OF HUMIDIFIER.
2. DETAIL ONLY APPLICABLE TO AHU'S WITHOUT AFTER FILTER DOWNSTREAM OF THE SUPPLY AIR FAN.
3. INTEGRAL STAINLESS STEEL DRAIN PAN SLOPE FROM ALL DIRECTIONS TO DRAIN CONNECTION. SLOPE .125" PER 1'-0".
4. PROVIDE MIN. 18" WIDE ACCESS DOOR, DIRECTLY UPSTREAM AND DOWNSTREAM OF HUMIDIFIER.
AIR HANDLING UNIT
NOTE 1
4'-0" 8'-0"
LPS
ACCESS DOOR
NOTE 4 ACCESS DOOR
NOTE 4
ROUTE TO
FLOOR SINK
NOTE 3
LPR
42" MAX
NTS
DUCT MOUNTED HUMIDIFIER
HWS
HWR
HWS
HWR
HWS
HWR
HWS
HWR
D
FLOW
" M
IN
6" M
IN
4 D2 MIN.
20 D2 MIN.10 D1 MIN.
DU
CT
H
EI
G
HT
H1/
H 1/
H
SE
E
NO
TE
SEE NOTE 3
SEE NOTE 2
SEE NOTE 1
N.O. VAV BOX
BY CONTRACTOR
24V. N.O. MODULATING CONTROL VALVE FURNISHED
WIRED BY CONTRACTOR OF RESPONSIBLE TRADE (TYPICAL)
24V. POWER WIRING
VELOCITY SENSOR BY VAV BOX MANUFACTURER
VAV BOX INTEGRAL HOT WATER HEATING
COIL BY VAV MANUFACTURER
VAV BOX
CONTROLLER
BOX LOCATION NOTE: VAV BOXES SHALL BE
LOCATED NO HIGHER THAN 12" ABOVE
CEILING.
MAX. 3FT. OF 1" THICK
FACTORY INSULATED MED.
PRESS. FLEXIBLE DUCTWORK
W/ VAPOR BARRIER JACKET
3/4" DRAIN VALVE WITH HOSE THREAD
OUTLET
CEILING BY PRIME
CONTRACTOR
SUPPLY DIFFUSER (SEE
INSTALLATION DETAIL)
1" EXTERNALLY INSULATED
MEDIUM PRESS. SUPPLY
DUCTWORK MAIN
RIGID DUCT CONNECTION TO
BOX INLET. MIN 1.5 TIMES BOX
INLET DIAMETER BUT NOT LESS
THAN 12"
SPIRAL RIGID ROUND
DUCTWORK (WHERE
SHOWN ON FLOOR
PLANS)
SAME SIZE AS BOX INLET
DIA. SEE VAV BOX
SCHEDULE
CONICAL "SPIN-IN"
FITTING
BALL VALVE AT TAKE-OFF FROM MAIN
WHERE SHOWN ON PLANS
INTEGRAL HOT WATER REHEAT COIL
(WHERE SHOWN ON FLOOR PLANS)
LOW PRESS. RECTANGULAR SUPPLY AIR
DUCT WITH 1-1/2" THICK FLEXIBLE
FIBERGLASS WITH VAPOR BARRIER JACKET
DOWNSTREAM FROM DISCHARGE OF ALL
VAV BOXES
SPIN-IN COLLAR WITH
DAMPER
MANUAL AIR VENT(TYP.)
CIRCUIT BALANCING VALVE
UNION
REDUCER/INCREASER (TYP.)
NOTE:
PROVIDE STAINLESS STEEL BRAIDED LINES FOR CONNECTIONS TO
TERMINAL UNIT REHEAT COILS.
3-WAY MODULATING CONTROL VALVE
VAV BOX
CONTROLLER
BOX LOCATION NOTE: VAV BOXES SHALL BE
LOCATED NO HIGHER THAN 12" ABOVE
CEILING.
MAX. 3FT. OF 1" THICK
FACTORY INSULATED MED.
PRESS. FLEXIBLE DUCTWORK
W/ VAPOR BARRIER JACKET
3/4" DRAIN VALVE WITH HOSE THREAD
OUTLET
CEILING BY PRIME
CONTRACTOR
SUPPLY DIFFUSER (SEE
INSTALLATION DETAIL)
1" EXTERNALLY INSULATED
MEDIUM PRESS. SUPPLY
DUCTWORK MAIN
RIGID DUCT CONNECTION TO
BOX INLET. MIN 1.5 TIMES BOX
INLET DIAMETER BUT NOT LESS
THAN 12"
SPIRAL RIGID ROUND
DUCTWORK (WHERE
SHOWN ON FLOOR
PLANS)
SAME SIZE AS BOX INLET
DIA. SEE VAV BOX
SCHEDULE
CONICAL "SPIN-IN"
FITTING
BALL VALVE AT TAKE-OFF FROM MAIN
WHERE SHOWN ON PLANS
INTEGRAL HOT WATER REHEAT COIL
(WHERE SHOWN ON FLOOR PLANS)
LOW PRESS. RECTANGULAR SUPPLY AIR
DUCT WITH 1-1/2" THICK FLEXIBLE
FIBERGLASS WITH VAPOR BARRIER JACKET
DOWNSTREAM FROM DISCHARGE OF ALL
VAV BOXES
SPIN-IN COLLAR WITH
DAMPER
MANUAL AIR VENT(TYP.)
CIRCUIT BALANCING VALVE
UNION
REDUCER/INCREASER (TYP.)
NOTE:
PROVIDE STAINLESS STEEL BRAIDED LINES FOR CONNECTIONS TO
TERMINAL UNIT REHEAT COILS.
TI
STEAM PRESSURE REDUCING STATION VALVE SINGLE STAGE
1.
2.
2-WAY MODULATING CONTROL VALVE
F&T TRAP
NOTE: SEE MANUFACTURER'S PIPING RECOMMENDATIONS FOR FINAL LAYOUT
NTS
STEAM CONDENSATE
RETURN
TEMPERATURE SWITCH
SCALE POCKET
HUMIDIFIER
CONTROL VALVE
TO HUMIDISTAT
MANIFOLD PIPE ADAPTERS
STEAM SUPPLY
ON-OFF CONTROL VALVE AHU/DUCT CROSS
SECTION
6" M
IN
STEAM HUMIDIFIER - PIPING CONNECTIONS
NTS
NOTE:
1.
2.
3.
4.
5.
DUCT CONNECTIONS - AIR TERMINAL UNITS
RIGID STRAIGHT TERMINAL UNIT INLET LENGTH SHALL BE A MINIMUM OF 3 TIMES THE DIAMETER OF INLET
A FLEXIBLE AIR DUCT CONNECTOR IS NOT MANDATORY FOR INLET TO THIS BOX, BUT ALLOWED TO ACCOMMODATE MINOR OFFSETS. MAXIMUM
LENGTH 3'-0".
A BRANCH DUCT SERVING AN INDIVIDUAL BOX MAY BE THE SAME SIZE AS THE BOX INLET, PROVIDED THE EQUIVALENT LENGTH OF THE BRANCH DUCT, AS SHOWN, DOES NOT EXCEED 10 FEET . FOR LONGER LENGTHS, INCREASE THE DUCT SIZE AND PROVIDE A DUCT TRANSITION TO
MAINTAIN THE DUCT STATIC PRESSURE DROP AT OR BELOW 0.08"/100'.
FLEXIBLE AIR DUCT CONNECTORS, WHEN USED FROM TERMINAL UNIT SUPPLY AIR DUCT TO DIFFUSER, SHALL NOT EXCEED 3'-0". USE RIGID
ELBOWS FOR CHANGE OF DIRECTION GREATER THAN 45°.
COMPONENT ARRANGEMENT MAY VARY BY MANUFACTURER. PROVIDE
INSULATION W/VAPOR BARRIER FOR CONNECTING DUCT SECTIONS.
AIR TERMINAL UNIT (CV
OR VAV)
REHEAT COIL
FLEXIBLE AIR DUCT
CONNECTOR. SEE DETAIL
DIFFUSER (TYP.)
SEE SPECIFICATIONS FOR CLAMPS
AND SEALANT (TYP.)
SEE NOTE 5
V
NOTES:
ALL WORK SHOWN ABOVE SHALL BE BY THE TC CONTRACTOR UNLESS SPECIFICALLY NOTED OTHERWISE.
VAV BOX SHALL BE COMPLETE WITH BOX MANUFACTURER'S STANDARD AIRFLOW VELOCITY PRESSURE SENSOR.
1.
2.
VAV BOX CONTROL SCHEMATIC
NO SCALE
MULTI-POINT CENTER AVERAGING PNEUMATIC INLET
SECONDARY NETWORK CONTROL WIRING
ROOM THERMOSTAT
120V. POWER WIRING FROM AVAILABLE
24V. PLENUM RATED POWER WIRING
120/24 VAC CLASS II TRANSFORMER
CIRCUIT IN NEAREST POWER PANEL
TO OTHER VAV BOXES
AND CONTROL VALVES
DISCONNECT SWITCH, TERMINAL STRIP, AND NEMA
CONTROL PANEL BY VAV BOX MANUFACTURER
DDC VAV BOX CONTROLLER FURNISHED BY
TC CONTRACTOR TO HEATING CONTRACTOR FOR MOUNTING AT
THE FACTORY TO THE SIDE OF THE VAV BOX
24V. DAMPER ACTUATOR FURNISHED BY TC CONTRACTOR
TO HEATING CONTRACTOR FOR MOUNTING AT THE FACTORY INSIDE
THE VAV BOX CONTROL PANEL
DISCHARGE AIR TEMPERATURE SENSOR
NTS
VAV
NTS
TERMINAL UNIT PIPING DETAIL (3-WAY VALVE) (VAV-400)
SUPPORTED FROM STRUCTURE WITH
STRAPS PER SMACNA STANDARDS
(TYP.)
PROVIDE MINIMUM STRAIGHT LENGTH OF
RIGID DUCT AS RECOMMENDED BY MFG.
FOR PROPER AIR FLOW MEASUREMENT.
NOTES:
1. VERIFY RIGHT OR LEFT HAND CLEARANCE REQUIREMENTS WITH PLANS.
VAV
UNIT
VAV CONTROL PANEL
(MAINTAIN MIN. 36"
CLEARANCE
REQUIREMENTS)
FLEXIBLE SUPPLY DUCT
(ONLY WHERE CONCEALED
BY ACCESSIBLE CEILINGS)
VAV BOX INSTALLATION
NTS
SUPPLY, RETURN, OR
EXHAUST
REHEAT COIL SUPPLY VAV
BOXES ONLY
NTS
TERMINAL UNIT PIPING DETAIL (2-WAY VALVE)
FLOAT AND THERMOSTATIC STEAM TRAP ASSEMBLY
NTS
NOTE:
1. ALL DRIP POINTS ON STEAM MAINS SHALL BE PROVIDED WITH A 12" MINIMUM HIGH DRIP LEG
FROM BOTTOM OF STEAM MAIN TO TRAP INLET. DRIP LEG SHALL HAVE 6" SCALE POCKET
BELOW TRAP
INLET.
TO RETURN MAIN
PIPE SIZE SHALL BE SAME SIZE AS TRAP
FLOAT AND THERMOSTATIC TRAP.
SEE PLANS, AND SCHEDULES
DIELECTRIC FITTING WHERE
RETURN IS COPPER PIPE
SCHEDULE 80
STEEL PIPE
BYPASS-INSTALL IN HORIZONTAL PLANE LEVEL
WITH TRAP OR IN VERTICAL PLANE & BELOW TRAP
PROVIDE BYPASS PIPING FOR ALL TRAPS 1" AND
LARGER.
DRIP LEG OR EQUIPMENT CONNECTION.
MAKE THE SAME SIZE AS THE SUPPLY
MAIN OR EQUIPMENT CONNECTION. SEE
NOTE 1
SCHEDULE 80 STEEL PIPE
SEE DRAWINGS FOR PIPE SIZES
1" GATE
VALVE
CHILLED WATER COILS - PIPING CONNECTIONS
NTS
SINGLE COIL
WATER COIL
AIR VENT
WHEN COIL
IS NOT
SELF-VENTING
DRAIN WHEN
COIL IS NOT
SELF-DRAINING
TEST PLUG
(TYP.)
PIPE HANGER SHALL
SUPPORT
PIPING INDEPENDENT
OF COIL
REDUCER, IF REQUIRED
DRAIN
NOTES:
1. WHEN COIL IS INCLUDED IN CASING MOUNTED ON VIBRATION ISOLATORS THE FIRST 2
2. PIPING SHALL BE INSTALLED IN SUCH MANNER THAT IT WILL NOT BLOCK THE SWING OR
USE OF ACCESS DOORS OR PANELS; NEITHER SHALL IT BLOCK THE SERVICING OF FILTERS,
VALES, OR EQUIPMENT.
MV
MV
MV
TEMPERATURE
INDICATION TO
ECC SEE CONTROL DIAGRAM
CALIBRATED
BALANCING VALVE
(TYP.)
HANGERS FOR EACH PIPE SHALL BE SPRING & NEOPRENE TYPE. TYPE "H" FOR 4"∅ PIPE &
SMALLER. TYPE "H-P" FOR 5" PIPE & LARGER.
3. ALL VALVES TO BE INSTALLED IN MECHANICAL ROOM IN AN ACCESSIBLE LOCATION FOR MAINTANCE.
NTS
NOTE:
1.
2.
3.
4.
VENT TO ATMOSPHERE
SEE FLOOR PLANS FOR PIPE SIZES.
SEE EQUIPMENT SCHEDULES FOR VALVE DATA AND PIPE SIZES D1 AND D2.
INSTALL VALVES AS RECOMMENDED BY
MANUFACTURER.
MAKE BYPASS VALVE DISCHARGE PIPE THE SAME SIZE AS D2 FOR THE LARGEST
PRV.
PROVIDE NECESSARY UNIONS FOR THE REMOVAL OF VALVE WITH SCREWED
CONNECTIONS.
SIPHON (TYP.)
PILOT CONTROL LINE
REDUCER (TYP.) IF REQUIRED.
NOTE 1
D1
N.C.
D2
NOTE 1
NOTE 3
INVERTER
BUCKET TRAP
ASSEMBLY
TYP.
PSV
1/4" COPPER TUBE (TYP.)
DISCHARGE
TEMPERATURE SENSOR
PROVIDE PIPE HANGER
EACH SIDE OF PUMP
TRIPLE DUTY VALVE
PIPE INCREASER OR
BALL OR BUTTERFLY VALVE
STRAINER
IN-LINE CIRCULATING PUMP
WATER FLOW SWITCH HYDRONIC INDICATOR
W/TRUMPET VALVES
BLOW-DOWN PIPE & GATE VALVE WITH
SUCTION
PIPING CONTRACTOR SHALL FURNISH
AND INSTALL ALL PIPE WELLS
NOTES:
PIPING CONTRACTOR SHALL FURNISH/INSTALL WELL FOR TEMPERATURE SENSOR AND TAP FOR
BY T.C. CONTRACTOR
(WHEN REQUIRED)
BY T.C. CONTRACTOR
THREADED HOSE CONNECTION
REDUCER (TYPICAL)
REQUIRED BY T.C. CONTRACTOR.
SWITCH AS SHOWN FOR FUTURE USE EVEN IF SENSOR OR FLOW SWITCH ARE NOT PROVIDED
UNDER THIS PROJECT.
FOR PUMPS 1/2 HP OR SMALLER, CONTRACTOR MAY PROVIDE INDIVIDUAL PRESSURE/TEMPERATURE
PLUGS IN LIEU OF HYDRONIC INDICATOR AND TUBING SHOWN.
NTS
IN-LINE PUMP DETAIL
ISOLATION VALVE
VAV BOX CONTROL SCHEMATIC DIAGRAM
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
FULLY SPRINKLERED
Bancroft Project No. VA CONTRACT NO.
MECHANICAL DETAILS RENOVATIONS TO
BUILDING 217
EDWARD J. HINES JR. VAMC
06/10/2026 RH RBB
578-26-016
M504
100% CONSTRUCTION
DOCUMENTS
23-00936C25223C0071
Revisions: Date:
30% SCHEMATIC DESIGN 11/23/2023
60% DESIGN DEVELOPMENT 05/08/2024
90% CONSTRUCTION DOCUMENTS 08/23/2024
100% CONSTRUCTION DOCUMENTS 12/06/2024
~ AIR HANDLING UNIT
NTS1
POSITION # MODULE
RETURN FAN SECTION
FILTER SECTION
SERIES HEAT PIPE COIL
AIR MIXING SECTION
STEAM PREHEAT COIL SECTION
COOLING COIL SECTION7
STEAM REHEAT COIL SECTION
SERIES HEAT PIPE COIL
AIR COOLED CHILLER - PIPING CONNECTIONS
NTS
THERMOMETER
FLOW SWITCH
FLEXIBLE
CONNECTORS
IF REQUIRED
TEST PLUGS
CHS
EVAPORATOR
CHR
DDC
TEMPERATURE
SENSOR TO ECC
PRESSURE
GAUGE
UNDER CANOPY
FS
TT TT
DESIGNER NOTE:
1.
2.
3.
PROVIDE HEAT TRACING WHEN THE EXPOSED PIPING CARRYING CHILLED
WATER IS NOT MIXED WITH PROPYLENE CLYCOL. ALL VALVES, STRAINER,
FLOW SWITCH, FLEXIBLE CONNECTORS, ETC., SHALL BE WRAPPED WITH
ELECTRIC HEAT TRACE CABLE UNDER
INSULATION.
VERIFY NEED FOR FLEXIBLE CONNECTOR.
PROVIDE ALUMINUM JACKETING ON ALL EXPOSED, INSULATED PIPING.
1. PROVIDE QUANTITY OF DUCT SUPPORTS AS REQUIRED SUCH
THAT INSTALLED WEIGHT DOES NOT EXCEED 300 LBS. PER DUCT
SUPPORT OR 150 LBS. ON EACH
BASE.
2. SPACING NOT TO EXCEED 6'-0" CENTERS.
3. CROSSBRACE TWO PIPESTANDS EVERY FOURTH (4TH) PIPESTAND
FOR ELEVATIONS 24" AND
HIGHER.
4. IT IS NOT ACCEPTABLE FOR DUCT SUPPORT TO PENETRATE
VENTURE CLAD
JACKET.
3.0 PCF RIGID BOARD
INSULATION
SHEET METAL DUCTWORK
VENTURE CLAD 1577CW WHITE 5-PLY
LAMINATED FOIL/FILM JACKET
INSTALLED STRICTLY PER
MANUFACTURER'S INSTRUCTIONS.
CROWN TOP OF DUCT
FOR WATER DISPERSION
MIN 2'-0"
ROOF
ROOF GUARD PAD
1/2" THICK RUBBER ROOF GUARD PAD BY MIRO OR
HUMANE EQUIPMENT CO. (OR VA APPROVED
EQUAL) MINIMUM SIZE SHALL BE 4" LARGER THAN
DUCT SUPPORT BASE ASSEMBLY IN ALL
DIRECTIONS.
HOT-DIP GALVANIZED STEEL
BASE ASSEMBLY
ATTACH BASE ASSEMBLY
TO ROOF PAD USING 1/4"
DEEP LAYER OF MASTIC
BRACED STRUT
ASSEMBLY WITH
FIELD ADJUSTABLE
HEIGHT
12" WIDE SHEET ALUMINUM
BENEATH VENTURE CLAD
1577CW JACKET (OR VA
APPROVED EQUAL) AT ALL DUCT
SUPPORTS
MIRO 8-DS-HDG DUCT SUPPORT.
(OR VA APPROVED EQUAL)
NOTES:
NTS
EXTERIOR DUCT SUPPORT DETAIL
NTS
HOUSING FILTER
HOUSING FILTER
ACCESS DOOR
ENERGY RECOVERY COIL IN AIR HANDLING UNIT
ENERGY RECOVERY COIL - PASSIVE HEAT PIPE (REFRIGERANT)
CONTROLVALVE
(TYP. OF 3)
1. MAXIMUM 120 FT. PIPE LENGTH.
2. ELEVATE SUPPLY COIL (AHU) HEIGHT TO BE AT LEAST +25% OF EXHAUST COIL (DUCT
MOUNTED) HEIGHT. COORDINATE ROOF CURBS, RAILS AND AHU COIL STAND TO ACHIEVE
THE NECESSARY HEIGHT
REQUIREMENT.
NOTES:
ACCESS SECTION
CONTROL SECTION
SUPPLY FAN SECTION
ACCESS SECTION13
ACCESS SECTION
12345678
34567891011
RASA
SA
RA
RA
OA
ACCESS DOOR
(TYPICAL FOR 2)
STATIC PRESSURE TAPS
(TYPICAL FOR 2)
TOP VIEW
END VIEW
LIFTING LUGS
(TYPICAL FOR 2)
ACCESS DOOR
HINGES (TYPICAL 2
PER DOOR)
EASY GRIP KNOBS
(TYP. 2 PER DOOR)
SIDE VIEW
1. UNIT SHALL BE CONSTRUCTED OF 16 GA. GALVANIZED STEEL.
2. UNIT SHALL BE POP RIVITED, BOLTED, AND SEALED AIRTIGHT
WITH RTV
CAULKING.
3. RECOMMENDED STATIC PRESSURE FOR STANDARD HOUSING
IS -4" TO +3"
W.G.
4. ACCESS DOORS WITH NEOPRENE GASKET SHALL BE
PROVIDED ON BOTH SIDES OF
UNIT.
5. A MINIMUM OF 27 INCH CLEARANCE IS REQUIRED FOR FILTER
CHANGED
OUT.
6. ENTINER UNIT SHALL BE DOUBLE WALL INSULATED.
7. UNIT SHALL BE EQUIPPED WITH LIFTING LUGS.
4 NTS
OUTSIDE AIR ENERGY RECOVERY COIL FILTER HOUSING DETAIL
MERV 8 FILTERS
PROVIDE BASE TO ENSURE PROPER HEIGHT REQUIREMENTS
RETURN DUCTWORK
ENERGY RECOVERY COIL IN DUCTWORK
RETURN DUCTWORK
F-1
FABRICATE A FULL ENCLOUSRE TO SUPPOR THE
COIL AND A STAINLESS STEEL DRAIN PAN
ROUTE
CONDENSATE DRAIN
TO NEARBY ROOF
DRAIN
DRAIN PAN
RL
RS
DIRECTION OF RETURN AIR
RL
RS
RL
RS
ISOLATION VALVE (TYP.)
MANUAL AIR VENT (TYP.)
CALIBRATED BALANCE VALVE
STRUCTURAL STEEL
PRESSURE GAUGE (TYP.)
THEMOMETER (TYP.)
SPRING ISOLATORS
HOUSED/RESTRAINED
FLEXIBLE CONNECTION (TYP.)
AIR COOLED CHILLER
(TYPICAL)
NTS
AIR COOLED CHILLER DETAIL
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
FULLY SPRINKLERED
Bancroft Project No. VA CONTRACT NO.
MECHANICAL DETAILS RENOVATIONS TO
BUILDING 217
EDWARD J. HINES JR. VAMC
06/10/2026 RH RBB
578-26-016
M505
100% CONSTRUCTION
DOCUMENTS
23-00936C25223C0071
Revisions: Date:
30% SCHEMATIC DESIGN 11/23/2023
60% DESIGN DEVELOPMENT 05/08/2024
90% CONSTRUCTION DOCUMENTS 08/23/2024
100% CONSTRUCTION DOCUMENTS 12/06/2024
CW
PS
BUFFER
TANK
AV
PRESSURE
REDUCING VALVEN.C.
SET PRESSURE RELIEF AT 75 (FIELD
ADJ.) PSI
EXPANSION TANK
PUMP
PUMP (STANDBY)
3" GCR
PACKAGED GLYCOL AIR-COOLED
CHILLER
ON/OFF CONTROL VALVE (TYP.)
1" MU
3" GCR
AHU-1
GLYCOL FILL SYSTEM
ROUTE 3/4" PIPE TO
NEARBY FLOOR DRAIN
NTS
GLYCOL CHILLED WATER FLOW DIAGRAM FOR ACCU-1/AHU-1
ACCU-1
1" MU
1" M U
1" G
CR
1" G
CS
3" GCS
REFER TO SIDE STREAM FILTER
AND BY-PASS CHEMICAL FEEDER
DETAIL.
FROM DOMESTIC
COLD WATER
FROM DOMESTIC
COLD WATER
SIDE STREAM FILTER WITH
INLET AND OUTLET GAUGESFLOW METER
THREAD OUTLET
WITH HOSE
DRAIN VALVE
3/4" 3/4"
3/4"
UNION (TYP.)
GASKETED
1/4" MANUAL
CHECK VALVE (TYP.)
CHEMICAL POT
FEEDER WALL MOUNTED
DRAIN VALVE
WITH HOSE
THREAD OUTLET
BALL VALVE (TYP.)
PUMP
FROM
SYSTEM
TO SYSTEM
NOTE:
INSTALL FEEDER ACROSS POINTS OF ADEQUATE PRESSURE
DIFFERENTIAL TO OBTAIN FLOW THRU FEEDER.
AIR VENT
FILL CAP
NEAR PUMP.
3/4"
3/4"
SIDE STREAM FILTER AND BY-PASS CHEMICAL FEEDER DETAIL
NTS 2
NTS
NOTES:
1. PROVIDE LOW WATER LEVEL ALARM. PROVIDE A LOW WATER LEVEL AT
ECC. RELIEF VALVE DRAIN SHALL RETURN TO TANK AS SHOWN ON THIS
DETAIL.
2. SET REGULATING VALVE TO MAINTAIN MAKE-UP PRESSURE AT 15 PSIG
ABOVE HIGHEST SYSTEM PRV SETTING.
3. MAKE-UP PIPING SYSTEM DOES NOT REQUIRE INSULATION.
4. OPERATE PUMP MANUALLY AS REQUIRED TO FILL.
1"
INDIRECT GLYCOL MAKE-UP SYSTEM (PIPING AND CONTROLS)
3" THICK CONCRETE PAD
BACK PRESSURE REGULATING
VALVE SEE NOTE NO. 2
GLYCOL-WATER MAKE-UP
PUMP 5 GPM @ 30 PSIG
1"
55 GALLON GLYCOL-WATER
STORAGE TANK
WALL MOUNTED "ON-OFF"
MOTOR CONTROL-SEE
NOTE NO. 4
LOW WATER LEVEL
ALARM SEE NOTE NO. 1
PUMP SUCTION
BUFFER TANK
FLOOR
TO EXPANSION TANK
RESERVOIR TANK
INTEGRAL CONTROL PANEL
FACTORY LOW WATER LEVEL SENSOR
1 1/4" BY HVAC CONTRACTOR
EXPANSION TANK
SELF PRIMING PUMP
PRESSURE SWITCH
BALL VALVE (TYP.)
STRAINER
UNION (TYP.)
TRIPLE DUTY VALVE
PRESSURE GAUGE
DRAIN VALVE WITH HOSE CONNECTION
PRESSURE REDUCING VALVE
SEE FLOOR PLANS
1 1/4" BY PLUMBING CONTRACTOR
LOCAL BALL VALVE WITHIN 12" OF PIPE OUTLET
FOR MANUALLY FILLING TANK.
CODE AIR GAP HINGED COVER WITH 2"∅ HOLE FOR MAKE-UP
4" CONCRETE PAD
FLOOR
BY MANUFACTURER
BY HVAC CONTRACTOR
GLYCOL FILL SYSTEM DETAIL
NTS
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
FULLY SPRINKLERED
Bancroft Project No. VA CONTRACT NO.
MECHANICAL DETAILS RENOVATIONS TO
BUILDING 217
EDWARD J. HINES JR. VAMC
06/10/2026 RH RBB
578-26-016
M506
100% CONSTRUCTION
DOCUMENTS
23-00936C25223C0071
Revisions: Date:
30% SCHEMATIC DESIGN 11/23/2023
60% DESIGN DEVELOPMENT 05/08/2024
90% CONSTRUCTION DOCUMENTS 08/23/2024
100% CONSTRUCTION DOCUMENTS 12/06/2024
NTS
SEISMIC BRACING FOR PIPES AND ROUND AND RECTANGULAR DUCTS
3/16" (0.47 CM)
2 (MAX)
1 (MIN)
1/4" (0.63 CM) MIN
TYP.
SEE PLANS FOR
DUCT SIZE
2 (MAX)
1 (MIN)
1" (2.5 CM)
2 (MAX)
1 (MIN)
2 (MAX)
1 (MIN)
1 5/8" (4.1 CM)
6" (15.25 CM)
2 (MAX)
1 (MIN)
1 2
TRANSVERSE BRACING FOR PIPES
NO SCALE
LONGITUDINAL BRACING FOR PIPES
NO SCALE
BRACING FOR RECTANGULAR DUCTS
NO SCALE
BRACING FOR ROUND DUCTS
NO SCALE
SEISMIC BRACING NOTES
10'-0" (3 M) MAX TO STRUCTURAL
SUPPORTING MEMBER
1/2" (1.25 CM)
MIN
1/2" (1.25 CM)
MAX
8'-0" (2.4 M) MAX TO STRUCTURAL
SUPPORTING MEMBER
SEE PLANS FOR
DUCT SIZE
GENERAL
1. NO BRACING IS REQUIRED IF THE TOP OF THE DUCT OR PIPE IS SUSPENDED 12 INCHES OR LESS FROM THE SUPPORTING
STRUCTURAL MEMBER.
2. WALLS, INCLUDING DRYWALL PARTITIONS, MAY REPLACE REQUIRED TRANSVERSE OR VERTICAL
BRACING FOR DUCTWORK OR PIPING.
3. ALL SEISMIC RESTRAINTS SHALL MEET OR EXCEED REQUIREMENTS OF SMACNA PUBLICATION
"SEISMIC RESTRAINT MANUAL GUIDELINES FOR MECHANICAL SYSTEMS" 1991 EDITION.
DUCTWORK
4. BRACE ALL RECTANGULAR DUCTS OF 6 SQ. FT. CROSS SECTIONAL AREA AND LARGER.
BRACE ALL ROUND/OVAL DUCTS 28 INCHES IN DIAMETER AND LARGER.
5. TRANSVERSE AND VERTICAL BRACING SHALL OCCUR AT 30 FOOT INTERVALS, MAXIMUM. LONGITUDINAL BRACING SHALL OCCUR
AT 60 FOOT INTERVALS, MAXIMUM.
PIPING
6. BRACE ALL PIPES 2 1/2 INCHES IN DIAMETER AND LARGER. IN MECHANICAL ROOMS ALSO BRACE 1 1/4", 1 1/2" AND 2 INCH PIPING AS FOR 2 1/2" PIPING. BRACE ALL FUEL GAS AND COMPRESSED AIR PIPING 1" AND LARGER.
7. TRANSVERSE AND VERTICAL BRACING SHALL OCCUR AT 40 FOOT INTERVALS, MAXIMUM UNLESS NOTED OTHERWISE.
LONGITUDINAL BRACING SHALL OCCUR AT 80 FOOT INTERVALS, MAXIMUM. WHEN THERMAL EXPANSION OR CONTRACTION IS INVOLVED, PROVIDE LONGITUDINAL BRACING AT ANCHOR POINTS. THE LONGITUDINAL BRACES AND THE CONNECTIONS MUST
BE CAPABLE OF RESISTING THE FORCE INDUCED BY EXPANSION AND CONTRACTION.
8. AT PIPE RISERS, WHEREVER POSSIBLE, SUPPORT THE WEIGHT OF THE RISER AT A POINT OR POINTS ABOVE THE CENTER OF
GRAVITY OF THE RISER.
9. DO NOT FASTEN ONE RIGID PIPING SYSTEM TO DISSIMILAR PARTS OF THE BUILDING THAT MAY RESPOND IN A DIFFERENT MODE
DURING AN EARTHQUAKE; FOR EXAMPLE, A WALL AND A ROOF.
10. DO NOT USE BRANCH LINES TO BRACE MAIN LINES.
EQUIPMENT
11. FLOOR OR PAD MOUNTED EQUIPMENT, WITHOUT VIBRATION ISOLATORS, SHALL BE BOLTED TO THE OTHER SUPPORT.
12. FLOOR MOUNTED EQUIPMENT, WITH VIBRATION ISOLATORS, SHALL BE PROVIDED WITH LATERAL AND VERTICAL RESTRAINING
DEVICES ON ALL SIDES OF THE BASE TO RESTRICT DISPLACEMENT OF THE EQUIPMENT.
13. ON ALL SIDES OF SUSPENDED EQUIPMENT, PROVIDE BRACING FOR RIGID SUPPORTS AND PROVIDE RESTRAINTS FOR
RESILIENTLY SUPPORTED EQUIPMENT.
LONGITUDINAL BRACE AS
REQUIRED (ONE EACH SIDE)
12 GAUGE STRAP
WASHER
LONGITUDINAL BRACE
VERTICAL HANGER
TRANSVERSE BRACE
MACHINE BOLT
(TYP.)
L 3 x 3 x 1/4 0'-3"
12 GAUGE STRAP
VERTICAL HANGER
TRANSVERSE BRACE
TRANSVERSE BRACE
PIPE
PIPE HANGER
PIPE HANGER ROD
CLIP CONNECTION
ROD AND VERTICAL
HANGER
PIPE SLEEVE TO HAVE
INNER DIAMETER 1/4"
GREATER THAN DIAMETER
OF BOLT
PIPEPIPE HEAVY PIPE CLAMPHEAVY PIPE CLAMP
LONGITUDINAL BRACELONGITUDINAL
BRACE
LONGITUDINAL BRACE
(EACH ONE SIDE)
TRANSVERSE BRACE
VERTICAL HANGER
SELF-TAPPING SHEET METAL
SCREWS EQUALLY SPACED
VERTICAL HANGER
(WHERE REQUIRED)
WELDED BEAM ATTACHMENT
WASHER TO
CONCEAL WELD
HORIZONTAL
BRACE
REQUIRED (TYP.)
NTS
NOTE:
NOT REQUIRED FOR AIR
TERMINAL UNITS.
EQUIPMENT WEIGHT 250 LBS.
OR LESS
SEISMIC BRACING FOR LIGHT SUSPENDED
EQUIPMENT
FLOOR MOUNT EQUIPMENT RESTRAINED BY
RESILIENT PADS (TYPE DS)
FLOOR
EQUIPMENT
BASE ANCHOR BOLT
NEOPRENE WASHER &
SLEEVE
BONDED STEEL
PLATE
RESILIENT PAD
HANGER ROD
(TYP)
CROSS BRACING RODS ALL
FOUR SIDES
LOCK NUTS
(TYP)
CLAMP
SEISMIC BRACING FOR EQUIPMENT
NTS
TYPICAL SEISMIC PIPE BRACING (2 1/2" Ø AND LARGER PIPING)
REFER TO DETAILS SHEETS
DIAGONAL ANGLE
BOLT TO ANGLE
"EL CEN" HANGER ROD CLIP
ROD
LONGITUDINAL
DIAGONAL ANGLE
AS REQUIRED
(SHOWN DOTTED)
(SLOPE 1 TO 1)
ADD VERTICAL ANGLE WHEN "L"
IS GREATER THAN MAX.
LENGTH.
ADD PIPE SLEEVE THAT HAS AN
I.D. 4" +/- LARGER THAN O.D.
BOLT
WHEN THERMAL INSULATED
PIPING IS USED DO NOT
CONNECT PIPING OR HANGER
DIRECTLY TO PIPE
NON SPRINKLER PIPING
"L
6' -0
" M
AX
CONNECTION TO STRUCTURAL SUPPORTING MEMBER TO
BE SAME FOR VERTICAL DIAGONAL, AND LONGITUDINAL
EQUIPMENT
5/8"∅ ANCHOR BOLT
CONCRETE FLOOR
NEOPRENE PAD
STEEL SPRING VIBRATION
ISOLATOR FOR SEISMIC AREA
NEOPRENE PAD
NTS
VIBRATION ISOLATOR DETAIL
NOTE TO CONTRACTOR:
NTS
ALL DIRECTIONAL SEISMIC SNUBBER
STEEL BUSHING
ALL-DIRECTIONALL BRIDGE
BEARING QUALITY NEOPRENE
BUSHING
RESTRAINING ANGLE
SNUBBER BOLT AND WASHER
EQUIPMENT BASE ANCHOR BOLT
NTS
SEISMIC SWAY BRACE DETAIL (INSULATED NON SPRINKLER PIPIPNG)
TYPE 4 OR TYPE 8 PIPE CLAMP PIPE INSULATION UPPER HALF
OF PIPE
SEISMIC SWAY BRACING
HIGH DENSITY INSULATION
INSERT-LOWER HALF OF PIPE
TYPE 40 PROTECTION SHIELD HOT PIPE - ALL SIZES
COLD PIPE - ALL SIZES
NTS
ALL DIRECTIONAL SEISMIC SNUBBER
REPLACEABLE 0.75" THICK
ALL-DIRECTIONAL BRIDGE
BEARING QUALITY NEOPRENE
UPPER BRACKET TO EQUIPMENT
THRU-BOLT
LOCKNUT
AIRGAP
LOWER BRACKET TO
STRUCTURE
THESE DETAILS ARE DIAGRAMMATIC. ALL FINAL SEISMIC
RESTRAINTS SHALL BE IN ACCORDANCE WITH
SPECIFICATIONS SECTION 13 05 41 AND VA HANDBOOK
H-18-8. NON STRUCTURAL SEISMIC RESTRAINT SYSTEMS
SHALL BE DESIGNED BY A PROFESSIONAL STRUCTURAL
ENGINEER AS DELEGATED BY THE CONTRACTOR. ALL
SEISMIC RESTRAINTS SHALL MEET REQUIREMENTS OF RISK
CATEGORY IV SEISMIC DESIGN CATEGORY D.
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
FULLY SPRINKLERED
Bancroft Project No. VA CONTRACT NO.
MECHANICAL DETAILS RENOVATIONS TO
BUILDING 217
EDWARD J. HINES JR. VAMC
06/10/2026 RH RBB
578-26-016
M507
100% CONSTRUCTION
DOCUMENTS
23-00936C25223C0071
Revisions: Date:
30% SCHEMATIC DESIGN 11/23/2023
60% DESIGN DEVELOPMENT 05/08/2024
90% CONSTRUCTION DOCUMENTS 08/23/2024
100% CONSTRUCTION DOCUMENTS 12/06/2024
EF-08 GREENHECK G-140-VG ROOF-UNIT B
DEMENTIA
WING
CENTRIFUGAL
DOWN BLAST
DIRECT 63 2,400 0.75 15.1 1,558 0.77 1 1725 1 115 BAS 1,2,3,4,5,6
EF-09 GREENHECK G-160-VG ROOF-UNIT B
DEMENTIA
WING
CENTRIFUGAL
DOWN BLAST
DIRECT 63 1,750 0.63 10.3 963 0.33 1 1200 1 115 BAS 1,2,3,4,5,6
EF-11 GREENHECK G-120-VG ROOF-UNIT B
DEMENTIA
WING
CENTRIFUGAL
DOWN BLAST
DIRECT 49 1,250 0.62 11.2 1,358 0.24 1/2 1725 1 115 BAS 1,2,3,4,5,6
NOTES:
1. OTHER ACCEPTABLE MANUFACTURERS: VA APPROVED EQUALS
2. PROVIDE THE FOLLOWING OPTIONS: MOTORIZED DAMPER, NEMA 3R DISCONNECT SWITCH, AND SPEED CONTROLLER
3. PROVIDE ALUMINUM BIRDSCREEN.
4. PROVIDE PRE-FABRICATED 18" TALL INSULATED ROOF CURB.
5. FAN SHALL COME IN STANDARD ENAMEL GREY COLOR.
6. MOTORIZED DAMPER POWER SHALL BE FROM FAN CIRCUIT VIA INTEGRAL TRANSFORMER.
EQUIPMENT TAG
BASIS OF DESIGN
LOCATION
AREA
SERVED
TYPE DRIVE WEIGHT
(LBS)
CFM SP
(IN.)
MAXIMUM
SONES
FAN
RPM
BHP
MOTOR CONTROL
TYPE
NOTES
MANUFACTURER MODEL HP RPM PHASE VOLT
EXHAUST FAN SCHEDULE
ACCU-1 ROOF AHU-1 TRANE CGAM 52 6,423 4 18 R454B 57 42 81.12 48.06 PROPYLENE GLYCOL 30% DUAL HIGH HEAD 12.8 113 150 3 460 1 to 14
NOTES:
1. OTHER ACCEPTABLE MANUFACTURERS: VA APPROVED EQUAL 6. DUAL HIGH HEAD PUMPS, VFD, EXPANSION VESSELS, DRAINAGE VALVES, SHUT-OFF AT EW AND LW CONN; 140 GAL BUFFER TANK 11. FREEZE PROTECTION TO -20F AMBIENT; FACTORY HEAT TRACING
2. HOT GAS BYPASS. 7. SINGLE POINT POWER CONNECTION WITH 65KA HIGH FAULT CIRCUIT BREAKER 12. LEAD/LAG COMPONENT OPERATION AND PHASE REVERSAL PROTECTION
3. SPRING VIBRATION ISOLATORS. 8. INSTALL AIR COOLED CHILLER ON RAILS. 13. FACTORY PUMP PACKAGE
4.LOW AMBIENT CONTROL. 9. N+1 REDUNDANT PARALLEL PUMPS; LEAD LAG AND FAILURE RECOVERY FUNCTIONALITY 14. FACTORY INSTALLED REFRIGERANT ISOLATION VALVES
5. CRANKCASE HEATER. 10. BUFFER TANK WITH FACTORY INSULATION AND -20F FREEZE PROTECTION
EQUIPMENT
TAG
LOCATION
UNIT
SERVED
MANUFACTURER MODEL
HEAT
REJECTION
(TONS)
WEIGHT
(LBS)
COMPRESSORS WATERT SIDE ELECTRICAL DATA
NOTES
QUANTITY SIZE EACH
(TONS)
REF.
TYPE EWT (°F) LWT (°F) GPM COOLING
CAPACITY (TONS)
FLUID TYPE
FLUID
CONCENTRATION
PUMP TYPE PRESSURE DROP (FT) MCA MOCP PHASE VOLT
AIR COOLED CHILLER SCHEDULE
DFSS-108A TR-402 CARRIER 24,000 40MAHBQ24XA3
HIGH
WALL
15 45 11 720 75° 67° CLEANABLE CU-108A 38MARBQ24AA3 ROOF 2 R-410A 95 21.5 25 35 1 208 1,2,3
NOTES:
1. ACCEPTABLE MANUFACTURERS: VA APPROVED EQUALS
2. INDOOR UNIT SHALL BE INTERLOCKED TO OUTDOOR UNIT FOR POWER AND CONTROL WIRING.
3. WALL MOUNTED TEMPERATURE SENSOR.
EQUIPMENT
TAG
LOCATION
BASIS OF
DESIGN
COOLING
CAPACITY
(BTUH)
INDOOR UNIT OUTDOOR UNIT
NOTES
MODEL TYPE
DIMENSIONS
(IN.)
AIRFLOW FILTERS
EQUIPMENT
TAG
MODEL LOCATION
COMPRESSOR ELECTRICAL DATA
H W D
TOTAL
CFM
EAT. D.B.
(°F)
EAT. W.B.
(°F)
TYPE SIZE
(TONS)
REF.
TYPE
EAT
(°F)
SEER MCA MOCP PHASE VOLTS
DUCT FREE SPLIT SYSTEM SCHEDULE
ERC-1 ROOF
HEAT PIPE
TECHNOLOGY
HRM 7,000 R134A 47.25 54 22 13.89 3 / 2 6 / 12 474.0 47.25 54 22 13.89 3 / 2 6 / 12 474.0 504 32.4
91.5 / 76.4
87.3 / 75.3
0.86 70.0 / 58.43 74.2 / 60.0 0.83 19.3 0 7.1 504 214.4
0.2 / -1.2
28.5 / 20.5
0.76 70.0 / 52.9 41.9 / 39.7 0.81 40.6 0 31.8 1,2,3,4,5
NOTES:
1. OTHER ACCEPTABLE MANUFACTURERS: VA APPROVED EQUALS
2. PROVIDE NEMA 4 RATED 120V CONTROL PANEL. INSTALL CONTROL VALVE ON LIQUID PIPING.
3. REFER TO MANUFACTURERS MAXIMUM DISTANCES BETWEEN COILS.
4. PROVIDE A FULL ENCLOSURE FOR THE EXHAUST COIL TO INCLUDE DRAIN PAN. FIELD FABRICATE AS REQUIRED, ROUTE DRAIN PIPING TO NEARBY ROOF DRAIN.
5. COORIDNATE SUPPLY SIDE RECOVERY COIL SECTION WITH AHU MANUFACTURER.
EQUIPMENT
TAG
LOCATION
BASIS OF DESIGN CFM
(WHEN
RUNNING
100% OA)
REFRIGERANT
TYPE
SUPPLY SIDE (AHU)
APPROX. OVERALL
DIMENSIONS (IN.)
EXHAUST SIDE (DUCT MOUNTED)
APPROX. OVERALL
DIMENSIONS (IN.)
ENERGY RECOVERY (WHEN RUNNING 100% OA)
NOTES
SUMMER CONDITIONS WINTER CONDITIONS
AIR
VELOCITY
(FPM)
HEAT
TRANSFERED
(MBH)
SUPPLY SIDE (AHU) EXHAUST SIDE (DUCT MOUNTED) EFFECTIVENESS
AIR
VELOCITY
(FPM)
HEAT
TRANSFERED
(MBH)
SUPPLY SIDE (AHU) EXHAUST SIDE (DUCT MOUNTED) EFFECTIVENESS
MANUFACTURER MODEL H W L
FACE
AREA
(FT2)
# CIRCUITS /
ROWS PER
CIRCUIT
# ROWS /
FINS PER
INCH
WEIGHT
(LBS)
H W L
FACE
AREA
(FT2)
# CIRCUITS /
ROWS PER
CIRCUIT
# ROWS /
FINS PER
INCH
WEIGHT
(LBS)
EAT
DB /
WB (°F)
LAT
DB /
WB (°F)
PD
(IN.
WG)
EAT
DB / WB (°F)
LAT
DB / WB (°F)
PD
(IN. WG)
SENSIBLE
LATENT
TOTAL
EAT
DB /
WB (°F)
LAT
DB /
WB (°F)
PD
(IN.
WG)
EAT
DB / WB
(°F)
LAT
DB / WB
(°F)
PD
(IN. WG)
SENSIBLE
LATENT
TOTAL
ENERGY RECOVERY COILS SCHEDULE
PRV-1 BUILDING 217 HOFFMAN AHU-1 25 15 1,650 1,2
NOTES:
1. OTHER ACCEPTABLE MANUFACTURERS: VA APPROVED EQUAL
2. INSTALL CONTROL PRESSURE RANGE, AND PLATE.
EQUIPMENT
TAG
LOCATION MANUFACTURER SERVES
1ST STAGE
FLOW
(LBS / HR)
NOTESINLET PRESSURE
(PSI)
OUTLET PRESSURE
(PSI)
SINGLE STAGE STEAM PRESSURE REGULATOR VALVE SCHEDULE
AIR HANDLING UNIT SCHEDULE
STEAM RE-HEAT COIL RETURN FAN
PRE
FILTERS
TYPE
NOTES# OF
COILS
EAT
DB
(°F)
LAT
DB
(°F)
STEAM
PRESSURE
(PSI)
STEAM FLOW
(LBS/HR)
TOTAL
MBH
AIR
P.D.
(IN)
ROWS/
FPI
RETURN
CFM
TSP
(IN. WG)
ESP
(IN.)
TYPE FAN RPM
MOTOR
# OF
FANS
BHP HP FLA PH VOLT
2.0 80.0 107.8 15 219.9 208 0.07 1/6 7,000 1.8700 1.5 PLENUM 2,439 2.00 4.00 6.0 4.80 3 460
MERV 8 /
MERV 13
1-14
AIR HANDLING UNIT SCHEDULE
"EQUIPMENT
TAG"
BASIS OF DESIGN
LOCATION
DIMENSIONS
(IN.) WEIGHT
(LBS)
MIN.
O.A.
"100%
O.A."
SUPPLY FAN CHW COOLING COIL STEAM PRE-HEAT COIL
SUPPLY
CFM
TSP
(IN. WG)
ESP
(IN. WG)
TYPE
FAN
RPM
MOTOR
EAT
DB/WB (°F)
LAT
DB/WB
(°F)
EWT
(°F)
LWT
(°F)
AIR
P.D.
(IN)
AIR
VELOCITY
(FPM)
TOTAL
MBH
SENS.
MBH
ROWS/
FPI
# OF
COILS
FLUID
TYPE
FLUID
P.D.
(FT)
FLUID
VELOCITY
(FT/SEC)
GPM
EAT
DB
(°F)
LAT
DB
(°F)
STEAM
PRESSURE
(PSI)
STEAM FLOW
(LBS/HR)
TOTAL
MBH
AIR
P.D.
(IN)
ROWS/
FPIMANUFACTURER MODEL H W L
# OF
FANS
TOTAL
BHP
TOTAL
HP
FLA PH VOLT
AHU-1 TRANE CSAA017 ROOF 82 142 338 14,100 3,500 7,000 7,000 6.4 3.0 PLENUM 3,265 2 11 15 11 3 460 91.5/76.4 52/51.9 42 56 1.00 402 553 292 12 / 11 2.0
40% PROP.
GLYCOL
8.1 2.1 86.6 -10 80 15 718.6000 679.6000 0.45 2 / 14
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
FULLY SPRINKLERED
Bancroft Project No. VA CONTRACT NO.
MECHANICAL SCHEDULES RENOVATIONS TO
BUILDING 217
EDWARD J. HINES JR. VAMC
06/10/2026 RH RBB
578-26-016
M601
100% CONSTRUCTION
DOCUMENTS
23-00936C25223C0071
Revisions: Date:
30% SCHEMATIC DESIGN 11/23/2023
60% DESIGN DEVELOPMENT 05/08/2024
90% CONSTRUCTION DOCUMENTS 08/23/2024
100% CONSTRUCTION DOCUMENTS 12/06/2024
A TITUS OMNI SQUARE PANEL FACE 24"x24" STEEL 30 1,2,3
B TITUS 45F EGG CRATE VARIES ALUMINUM 30 1,2,3,4
C TITUS OMNI-AA SQUARE PANEL FACE 12"x12" ALUMINUM 30 1,2,3
D TITUS TBDI-80
LINEAR INSULATED
BOOT
VARIES STEEL 30 1,2,3,5,6
E TITUS 350F
35 DEG. DEFLECTION
REGISTER
VARIES ALUMINUM 30 1,2,3
COORDINATE FRAME TYPE WITH CEILING/WALL TYPE AND
ARCHITECT.
(2) -1" WIDE SLOTS
6. INSULATED PLENUM
EQUIPMENT
TAG
MANUFACTURER MODEL TYPE
NOMINAL
FACE SIZE
MATERIAL
MAX.
N.C.
NOTES
NOTES:
1. OTHER ACCEPTABLE MANUFACTURERS: VA APPROVED EQUALS.
2.
3. FINISH AS SELECTED BY ARCHITECT.
4. 1/2"x1/2"x1" GRID.
5.
DIFFUSER, GRILLE, AND REGISTER SCHEDULE
SEE PLANS TITUS DESV 260 260 06 12x8 8.0 15.5 12.0 260 5.6 55 75 180 0.7 2 16 24 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 170 170 08 12x10 10.0 15.5 12.0 170 3.2 55 72 180 0.8 1 - 24 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 165 165 06 12x8 8.0 15.5 12.0 165 5.6 55 86 180 0.5 1 11 19 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 170 170 06 12x8 8.0 15.5 12.0 170 6.5 55 90 180 0.6 1 11 19 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 155 155 06 12x8 8.0 15.5 12.0 155 5.5 55 88 180 0.5 1 11 18 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 165 165 08 12x10 10.0 15.5 12.0 165 5.7 55 87 180 0.7 1 - 23 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 165 165 08 12x10 10.0 15.5 12.0 165 3.8 55 76 180 0.7 1 - 23 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 115 115 06 12x8 8.0 15.5 12.0 115 2.5 55 75 180 0.5 1 - 15 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 1450 1450 14 20x17.5 17.5 15.5 20.0 1450 31.3 55 75 180 3.3 2 20 19 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 475 475 08 12x10 10.0 15.5 12.0 475 10.3 55 75 180 1.1 2 18 25 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 135 135 06 12x8 8.0 15.5 12.0 135 2.9 55 75 180 0.9 1 10 17 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 130 130 06 12x8 8.0 15.5 12.0 130 2.8 55 75 180 0.8 1 - 17 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 425 425 8 12x10 10.0 15.5 12.0 425 9.2 55 75 180 1.0 2 18 25 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 285 285 6 12x8 8.0 15.5 12.0 285 6.2 55 75 180 0.8 2 17 25 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 1025 1025 12 16x15 15.0 15.5 16.0 1025 22.2 55 75 180 2.6 2 19 23 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 1025 1025 12 16x15 15.0 15.5 16.0 1025 22.2 55 75 180 2.6 2 19 23 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 250 250 6 12x8 8.0 15.5 12.0 250 5.4 55 75 180 0.6 2 16 23 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 310 310 06 12x8 8.0 15.5 12.0 310 9.4 55 83 180 0.9 2 18 22 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 165 165 6 12x8 8.0 15.5 12.0 165 7.9 55 99 180 0.7 2 16 23 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 245 245 6 12x8 8.0 15.5 12.0 245 7.5 55 83 180 0.7 2 16 23 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 245 245 6 12x8 8.0 15.5 12.0 245 7.5 55 83 180 0.7 2 16 23 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 250 250 6 12x8 8.0 15.5 12.0 250 7.6 55 83 180 0.7 2 16 23 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 190 190 6 12x8 8.0 15.5 12.0 190 5.9 55 84 180 0.6 2 13 20 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 240 240 6 12x8 8.0 15.5 12.0 240 8.8 55 89 180 0.7 2 15 23 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 255 255 06 12x8 8.0 15.5 12.0 255 7.5 55 82 180 0.7 2 16 24 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 230 230 06 12x8 8.0 15.5 12.0 230 7.5 55 85 180 0.6 2 15 23 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 245 245 06 12x8 8.0 15.5 12.0 245 7.6 55 84 180 0.6 2 16 23 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 245 245 06 12x8 8.0 15.5 12.0 245 7.6 55 84 180 0.6 2 16 23 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 245 245 06 12x8 8.0 15.5 12.0 245 7.6 55 84 180 0.6 2 16 23 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 270 270 6 12x8 8.0 15.5 12.0 270 7.5 55 81 180 0.6 2 15 23 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 250 250 06 12x8 8.0 15.5 12.0 250 7.7 55 84 180 0.6 2 16 23 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 400 400 8 12x10 10.0 15.5 12.0 400 10.3 55 79 180 0.9 2 17 25 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 585 585 10 14x12.5 12.5 15.5 14.0 585 16.2 55 81 180 1.4 2 22 24 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 400 400 8 12x10 10.0 15.5 12.0 400 11.4 55 81 180 0.9 2 17 25 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 1200 1200 16 24x18 18.0 15.5 24.0 1200 52.3 55 95 180 1.9 2 12 11 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 420 420 08 12x10 10.0 15.5 12.0 420 12.2 55 82 180 1.0 2 18 25 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 500 500 08 12x10 10.0 15.5 12.0 500 10.8 55 75 180 1.4 2 30 36 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 945 945 14 20x17.5 17.5 15.5 20.0 945 20.4 55 75 180 1.6 2 17 18 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 305 305 6 12x8 8.0 15.5 12.0 305 9.3 55 83 180 0.9 2 18 22 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 595 595 10 14x12.5 12.5 15.5 14.0 595 11.5 55 73 180 1.4 2 20 24 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 810 810 12 16x15 15.0 15.5 16.0 810 17.5 55 75 180 1.6 2 18 22 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 440 440 8 12x10 10.0 15.5 12.0 440 12.6 55 82 180 1.0 2 18 25 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 420 420 8 12x10 10.0 15.5 12.0 420 12.2 55 82 180 1.0 2 18 25 NO 1,2,3,4,5,6,7,8
SEE PLANS TITUS DESV 430 430 8 12x10 10.0 15.5 12.0 430 12.4 55 82 180 1.0 2 18 25 NO 1,2,3,4,5,6,7,8
NOTES:
1. OTHER ACCEPTABLE MANUFACTURERS: VA APPROVED EQUAL 5. HOT WATER COIL WATER PRESSURE DROP SHALL NOT EXCEED 5' AND AIR PRESSURE DROP SHALL NOT EXCEED 0.3" WG.
2. PROVIDE WITH ACCESS DOORS FOR REHEAT COIL AND FACTORY MOUNTED DISCONNECT. 6. VAV MANUFACTURER TO MOUNT IN FACTORY THE DDC CARD/CONTROLLER AND DAMPER ACTUATOR
3. SOUND LEVELS (NC) AST FULL AIR FLOW WITH 0.75" INLET STATIC PRESSURE AND 0.5" FURNISHED BY THE T.C. CONTRACTOR. BOXES SHALL NOT BE RELEASED FOR PRODUCTION UNTIL BOX
4. DISCHARGE PRESSURE. NOISE CRITERIA (NC) SOUND INFORMATION IS BASED ON ARI-880-98. MANUFACTURER HAS COORDINATED WITH T.C. CONTRACTOR.
5. REGARDLESS OF HOT WATER COIL AIR PRESSURE DROP, AVAILABLE DISCHARGE STATIC 7. COORDINATE LEFT HANDED/RIGHT HANDED COIL CONNECTIONS WITH DESIGN DRAWINGS AND EXISTING FIELD CONDITIONS
PRESSURE SHALL NOT BE LESS THAN 0.25" AT AIR FLOW RATE SCHEDULED. 8. PROVIDE NECESSARY 120V / 24V POWER SUPPLY FOR CONTROLLER POWER. COORDINATE WITH ELECTRICAL DRAWINGS
FOR QUANTITY AND LOCATION.
EQUIPMENT
TAG
LOCATION MANUFACTURER MODEL
AIRFLOW (CFM) APPROX. DIMENSIONS (IN.) HOT WATER COIL NOISE LEVEL(NC) INTEGRAL
SOUND
ATTENUATOR
NOTES
MIN. MAX.
INLET
SIZE
OUTLET
SIZE
H L WHEATING CFMCAPACITY
(MBH)
EAT (°F) LAT (°F) EWT (°F) GPMROWSRADIATED DISCHARGE
VAV BOX WITH HOT WATER REHEAT SCHEDULE
VAV-1A104
VAV-1A104A
VAV-1A105
VAV-1A106
VAV-1A107
VAV-1A108
VAV-1A109
VAV-1A111
VAV-1A118
VAV-1A127A
VAV-1A141
VAV-1A142
VAV-2A12A
VAV-2A12B
VAV-2A18A
VAV-2A18B
VAV-1B142
VAV-1B149
VAV-1B153
VAV-1B155
VAV-1B156
VAV-1B159
VAV-1B160
VAV-1B162
VAV-1B164
VAV-1B167
VAV-1B168
VAV-1B171
VAV-1B172
VAV-1B175
VAV-1B176
VAV-1B178
VAV-1B100
VAV-2B78
VAV-1C100W
VAV-1C104
VAV-1C104B
VAV-1C104A
VAV-1C149
VAV-1C150N
VAV-1C150S
VAV-1C178
VAV-2C204
VAV-2C278
F-1 ERC-1
EASY
STREET
ROOF
FLANDERS 7,000
FILTER
ENCLOSURE,
PLEATED
FILTERS
35% / MERV-8 24 24 2 4 2 2 0.19 1.00 1 1,2,3,4,5,6,7,8
NOTES:
1. OTHER ACCEPTABLE MANUFACTURERS: VA APPROVED EQUAL.
2. PROVIDE STATIC PRESSURE TAPS AND WEATHER PROOF MAGNEHELIC GAGES TO READ ACROSS FILTER BANK.
3. PROVIDE ACCESS DOORS WITH NEOPRENE GASKET ON BOTH SIDES FOR FILTER REPLACEMENT. A MINIMUM OF 27" CLEARANCE IS REQUIRED FOR FILTER CHANGE OUT.
4. ENTIRE UNIT SHALL BE DOUBLE WALL INSULATED.
5. PROVIDE STATIC PRESSURE TAPS AND PROVIDE WEATHER COVER.
6. PROVIDE 2" CHANNEL BASE WELDED TO BOTTOM OF HOUSING. INSTALL ON ROOF RAIL, COORDINATE FINAL ELEVATIONS WITH DUCTWORK.
7. PROVIDE LIFTING LUGS.
8. SEE SPECIFICATIONS AND DETAILS FOR ADDITIONAL REQUIREMENTS
TAG SERVICE LOCATION MANUFACTURER
CFM
MAX
CAPACITY
TYPE
% Efficiency
ASHRAE
STANDARDS
52.1 / 52.2
FILTER MODULE
NOMINAL SIZE
FILTER MODULE ARRANGEMENT MAXIMUM PRESSURE
DROP (IN WG)
TOTAL
HOUSING
FINAL
PRESSURE
DROP
(IN WG)
REMARKS
H (IN) W (IN) D (IN)
TOTAL
NUMBER
OF UNITS
NUMBER
UNITS
HIGH
NUMBER
UNITS
WIDE
CLEAN DIRTY
FILTER HOUSING SCHEDULE
GFS-1 ROOF ACCU-1 50 GAL. SIMPLEX 1.8 GPM AT 70 PSI 1/3 120 1 WESSELS GMP-15050 1,2
NOTES:
1. OTHER ACCEPTABLE MANUFACTURERS: VA APPROVED EQUAL.
2. PACKAGED SYSTEM SHALL INCLUDE 1/2 HP PUMP, 50 GAL. GLYCOL DRUM, EXPANSION TANK, LOW WATER CUT OFF SWITCH, PRESSURE SWITCH/STARTER, Y-STRAINER, TRIPLE DUTY VALVE, PRESSURE GAUGE, AND THREADED OUTLET.
SYMBOL LOCATION CHILLER SERVED TYPE CAPACITY / SIZE
MOTOR BASIS OF DESIGN
NOTESHP VOLT PHASE MANUFACTURER MODEL
GLYCOL FILL STATION
SYMBOL
UH-101 AHU VESTIBULE 3 10.3 350 1600 1 / 100 14.5 208 1 16" x 14" x 8 1/2" 24.0000 QMARK HUHAA320 1 AND 2
UH-102 AHU VESTIBULE 3 10.3 350 1600 1 / 100 14.5 208 1 16" x 14" x 8 1/2" 24.0000 QMARK HUHAA320 1 AND 2
SERVICE
HEATING CAPACITY FAN / MOTOR DATA ELECTRICAL DIMENSIONS
( H x W x D)
UNIT
WEIGHT
(lbs)
MANUFACTURER MODEL REMARKS
KW MBH CFM RPM HP AMPS VOLT PHASE
HUM-1 AHU-1 7000 24 48 x 24 8 15 190 0.36 120 1 48 x 33 x 24.5 578 NEPTRONIC SKS4190SLPA 1, 2, 3, 4, 5, 6
NOTES:
1. PROVIDE NECESSARY STAND TO AHU MANIFOLD TO ACHIEVE DRAIN HEIGHT. FOLLOW ALL MANUFACTURER'S RECOMMENDATION.
2. PROVIDE ON/OFF DIGITAL DUCT HUMIDISTAT, AIR PROVING SWITCH, REMOTE WALL HUMIDITY SENSOR c/w DIGITAL DISPLAY,
3. PROVIDE HEADER, 304 STAINLESS STEEL STEAM TUBE, MOUNTING FRAME, AND INLET KIT.
4. PROVIDE FULLY MODULATING, BUILT-IN FLOAT & THERMOSTATIC STEAM TRAP, ELECTRIC ACTUATOR, AND BACnet COMPATIBLE.
5. PROVIDE WITH MANUFACTURER'S SUPPORT STAND.
6. REFER TO SPECIFICATION SECTION 23 22 13 STEAM AND CONDENSATE HEATING PIPING.
REMARKS:
1. PROVIDE DISCONNECT SWITCH, FAN DELAY SWITCH, AND BUILT-IN UNIT MOUNTED THERMOSTAT.
2. PROVIDE MOUNTING KIT TO MATCH MOUNTING REQUIREMENT.
SYMBOL SERVICE AIRFLOW
(CFM)
ABSORPTION
DISTANCE MAX.
(IN)
MANIFOLD
DIMENSIONS
(W x H)
NO. OF
DISPERSION
TUBES
STEAM
PRESSURE
(PSIG)
CAPACITY
(lbs/hr)
ELECTRICAL
DIMENSIONS
( H x W x D)
UNIT
WEIGHT
(lbs)
BASIS OF DESIGN
REMARKS
RATED POWER
(kW)
VOLT PHASE MANUFACTURER MODEL
UNIT HEATER SCHEDULE (ELECTRIC)
HUMIDIFIER SCHEDULE
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
FULLY SPRINKLERED
Bancroft Project No. VA CONTRACT NO.
MECHANICAL - SCHEDULES RENOVATIONS TO
BUILDING 217
EDWARD J. HINES JR. VAMC
06/10/2026 RH RBB
578-26-016
M602
100% CONSTRUCTION
DOCUMENTS
23-00936C25223C0071
Revisions: Date:
30% SCHEMATIC DESIGN 11/23/2023
60% DESIGN DEVELOPMENT 05/08/2024
90% CONSTRUCTION DOCUMENTS 08/23/2024
100% CONSTRUCTION DOCUMENTS 12/06/2024
AIR HANDLING UNIT POINT LIST (AHU-1)
HARDWARE POINTS SOFTWARE POINTS
POINT NAME AI AO BI BO AV BV SCHED TREND ALARM
SHOW ON
GRAPHIC
RETURN AIR HUMIDITY (H-1) X X X
SUPPLY AIR HUMDITY (H-2) X X X
OUTSIDE AIR DAMPER, POSITION (D-1) X X X
RETURN AIR DAMPER, POSITION (D-2) X X X
RELIEF AIR DAMPER, POSITION (D-3) X X X
MIXED AIR FILTER DIFFERENTIAL PRESSURE (MERV 8) X X X
MIXED AIR FILTER DIFFERENTIAL PRESSURE (MERV 13) X X X
RETURN AIR FILTER DIFFERENTIAL PRESSURE X X X
SUPPLY DUCT STATIC PRESSURE, SPS-1 X X X X
SUPPLY AIR TEMPERATURE, T-1 X X X X
ENERGY RECOVERY RETURN AIR TEMPERATURE, T-2 X X X X
MIXED AIR TEMPERATURE, T-3 X X X X
CHILLED AIR TEMPERATURE, T-4 X X X X
OUTSIDE AIR DEWPOINT TEMPERATURE, T-5 X X X X
HEATED AIR TEMPERATURE, T-6 X X X X
RETURN AIR TEMPERATURE, T-7 X X X X
SUPPLY FAN VFD SPEED CONTROL X X X
RETURN FAN VFD SPEED CONTROL X X X
OUTSIDE AIR DAMPER, ACTUATOR (D-1) X X X
RETURN AIR DAMPER, ACTUATOR (D-2) X X X
RELIEF AIR DAMPER, ACTUATOR (D-3) X X X
COOLING VALVE, V-2 X X X
SUPPLY DUCT HUMIDIFIER VALVE, V-3 X X X
SUPPLY FAN STATUS X X X
RETURN FAN STATUS X X X
STEAM HEATING VALVE STATUS, V-1 X X X
SUPPLY FAN VFD FAULT X X
RETURN FAN VFD FAULT X X
FREEZE PROTECTION, FZ X X
HIGH STATIC PRESSURE, SPS-2 X X X X
SUPPLY DUCT SMOKE DETECTOR, DSD-1 X X X X
STEAM HEATING VALVE, V-1 X X X
SUPPLY DUCT HUMIDIFIER VALVE ENABLE, V-3 X X X
SUPPLY FAN START/STOP X X X X X
RETURN FAN START/STOP X X X X X
ALARM
FREEZESTAT (FZ) X X X
HIGH SUPPLY AIR STATIC PRESSURE X
HIGH SUPPLY AIR TEMPERATURE (T-1) X
HIGH SUPPLY AIR HUMIDITY (H-2) X
HIGH MIXED AIR TEMPERATURE (T-3) X
HIGH RETURN AIR TEMPERATURE (T-7) X
HIGH RETURN AIR HUMIDITY (H-1) X
LOW SUPPLY AIR STATIC PRESSURE X
LOW SUPPLY AIR TEMPERATURE (T-1) X
LOW SUPPLY AIR HUMIDITY (H-2) X
LOW MIXED AIR TEMPERATURE (T-3) X
LOW RETURN AIR TEMPERATURE (T-7) X
LOW RETURN AIR HUMIDITY (H-1) X
SUPPLY FAN FAILURE X
RETURN FAN FAILURE X
SUPPLY FAN IN HAND X
RETURN FAN IN HAND X
PREFILTER CHANGE REQUIRED X
CONTROLS SYMBOLS
AI ANALOG INPUT
AO ANALOG OUTPUT
BI BINARY INPUT
BO BINARY OUTPUT
AV ANALOG VALUE
BV BINARY VALUE
SYMBOL DESCRIPTION
SYMBOL DESCRIPTION
CONTROL SYMBOL LIST
ADJ ADJUSTABLE
AFMS AIRFLOW MEASURING STATION
DP DIFFERENTIAL PRESSURE
DSD DUCT SMOKE DETECTOR
H HUMIDITY SENSOR
HOA HAND-OFF-AUTO
BAS BUILDING AUTOMATION SYSTEM
N.O. NORMALLY OPEN
N.C. NORMALLY CLOSED
SPS STATIC PRESSURE SENSOR
T TEMPERATURE SENSOR
VFD VARIABLE FREQUENCY DRIVE
EP POWER WIRING
CT CONTROLLER
SYMBOL DESCRIPTION
COOLING COIL
M
M
MOTORIZED DAMPER (SPRING RETURN)
MOTOR (FAN)
TRANSMITTER
TRANSMITTER, AVERAGING ELEMENT
PUMP
CONTROL VALVE
FZ FREEZESTAT
TSL TEMPERATURE SWITCH, LOW (FREEZESTAT)
STEAM HEATING COIL
M MOTORIZED DAMPER
DDC DIRECT DIGITAL CONTROL
RH RELATIVE HUMIDITY
ENERGY RECOVERY COIL
RELIEF
AIR
M
M
VFD
RETURN AIR
INDOORS OUTDOORS
DP
AI
M
OUTSIDE
AIR
M
T-3
AI
M
VFD
T-1
AI
SUPPLY AIR
H-1 AI
D-3
D-1
SPS-2
DSD-1
B1 TO FIRE ALARM
T-2
AI
T-5 AI
AO - RELIEF DAMPER
(OPEN/CLOSE)
AI - RELIEF DAMPER
(POSITION)
D-2
AO - OUTSIDE AIR DAMPER
(OPEN/CLOSE)
AI - OUTSIDE AIR DAMPER
(POSITION)
AI - FILTER STATUS
AI - FILTER STATUS
FZ
BI-TEMPERATURE TSL
T-4 AI
BI - FAN STATUS
C
X
AO - RETURN AIR DAMPER
(OPEN/CLOSE)
AI - RETURN AIR DAMPER
(POSITION)
LOCATED AT THE NORTH FACE OF BUILDING
WALL COORDINATE EXACT LOCATION WITH
COR/BUILDING ENGINEER.
LOCATED IN FIRST FLOOR
CORRIDOR. FIELD VERIFY EXACT
LOCATION
R
X
AO - ISOLATION VALVE
V-2
SEQUENCE OF OPERATION
CONSTANT AIR HANDLING UNIT
1. GENERAL
A. UNIT IS NORMALLY STARTED AND STOPPED REMOTELY AT THE DDC. H-O-A SWITCH SHALL BE KEPT IN THE "AUTO" POSITION.
"HAND" AND "OFF" POSITIONS SHALL BE USED ONLY FOR MAINTENANCE. WHEN THE UNIT IS "OFF" D-1, D-2, & D-3, SHALL BE FULLY CLOSED. WHEN THE UNIT IS "ON" D-1, D-2, & D-3 SHALL BE OPEN TO ITS MINIMUM POSITION. DAMPER SHALL
MODULATE IN ACCORDANCE WITH THE FOLLOWING…