VA WCHCS Bldg 8 Oneline Report 23.pdf
PDF 52 KB Posted
- Attached to
- H263--Fire Protection Services Federal contract opportunity
- Solicitation number
- 36C25925Q0190
About this file
This is a fire protection system inspection and testing report conducted by ALARMSpecialists, Inc. at VA Hospital WCHCS Building 8 in March 2023. The report documents required testing of various fire protection devices in accordance with EC.02.03.05 standards.
The testing covered multiple device types including: pull stations in various office locations, a smoke detector above the FACP, water flow switch (tested at 29 seconds), three tamper switches on control valves (tested at 1-2 turns), and numerous audio/visual devices including speaker/strobes, strobes, and strobe zone circuits throughout the building. All devices passed inspection and were documented with specific location information, device numbers, and test results. The testing appears to satisfy requirements for 12-month testing of manual fire alarm boxes and smoke detectors, 6-month testing of water flow devices and valve tamper switches, and 12-month testing of visual/audible fire alarms as specified in the EC standards referenced in the report.
View the file
Other files for this federal contract opportunity
Show all 27
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Prepared by ALARMSpecialists, Inc
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 1 of 5
Date Tested Device Location No de Lo op Device Status Comments March 21, 2023 Pull Station OFFICE 117 EXIT BUILDING 8 N 4 L 1 M 1 Pass March 21, 2023 Pull Station WORK SHOP 105 EXIT BUILDING 8 N 4 L 1 M 6 Pass March 21, 2023 Pull Station OFFICE 100 EXIT BUILDING 8 N 4 L 1 M 8 Pass March 21, 2023 Pull Station STORAGE 104 EXIT BUILDING 8 N 4 L 1 M 7 Pass
EC.02.03.05 EP 3 Every 12 months, the hospital tests duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors on the inventory. The results and completion dates are documented.
VA Hospital - WCHCS - Bldg 8 - Device List - March 23
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 2 of 5
Date Tested Device Location No de Lo op Device Status Comments March 21, 2023 Smoke Detector DETECTOR ABOVE FACP BUILDING 8 N 4 L 1 D 1 Pass
VA Hospital - WCHCS - Bldg 8 - Device List - March 23 EC.02.03.05 EP 3 Every 12 months, the hospital tests duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors on the inventory. The results and completion dates are documented.
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 3 of 5
Date Tested DEVICE LOCATION STATUS COMMENTS March 21, 2023 Water Flow Switch WATERFLOW BUILDING 8 N 4 L 1 M 2 Pass 29 SEC
VA WCHCS - Bldg 8 - Sprinkler - March 23 EC.02.03.05 EP 2 Every 6 months, the hospital tests vane-type and pressure-type water flow devices and valve tamper switches on the inventory. The results and completion dates are documented.
Note 2: Mechanical water-flow devices (including, but not limited to, water motor gongs) should be tested quarterly. The results and completion dates are documented.
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 4 of 5
Date Tested DEVICE LOCATION STATUS COMMENTS March 21, 2023 Tamper Switch TAMPER CONTROL VALVE BUILDING 8 N 4 L 1 M 3 Pass 1 TURN March 21, 2023 Tamper Switch TAMPER CONTROL VALVE BUILDING 8 N 4 L 1 M 4 Pass 1 TURN March 21, 2023 Tamper Switch TAMPER CONTROL VALVE BUILDING 8 N 4 L 1 M 5 Pass 2 TURNS
VA WCHCS - Bldg 8 - Sprinkler - March 23 EC.02.03.05 EP 2 Every 6 months, the hospital tests vane-type and pressure-type water flow devices and valve tamper switches on the inventory. The results and completion dates are documented.
Note: Mechanical water-flow devices (including, but not limited to, water motor gongs) should be tested quarterly.
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 5 of 5
Date Tested Device Floor Room # / Corridor Location No de Lo op Device Label Status Comments March 21, 2023 Speaker/Strobe By Main Entrance Building 8 N 4 L 1 x x 49798187 Pass March 21, 2023 Strobe By Rm 102 Building 8 N 4 L 1 x x 49798188 Pass March 21, 2023 Speaker/Strobe Rm 108 Mech shop Behind Shelves Building 8 N 4 L 1 x x 49798229 Pass March 21, 2023 Speaker/Strobe Rm 108 Break Rm Building 8 N 4 L 1 x x 49798232 Pass March 21, 2023 Strobe By Rm 108 Bathroom Building 8 N 4 L 1 x x 49798231 Pass March 21, 2023 Strobe Rm 113 Building 8 N 4 L 1 x x 49798185 Pass March 21, 2023 Speaker/Strobe By Rm 116 Building 8 N 4 L 1 x x 49798186 Pass March 21, 2023 Strobe Zone STROBE CIRCUIT P-1 IN FACP CAB Building 8 N 4 L 1 M 71 Pass March 21, 2023 Strobe Zone STROBE CIRCUIT P-2 IN FACP CAB Building 8 N 4 L 1 M 72 Pass March 21, 2023 Strobe Zone STROBE CIRCUIT P-3 IN FACP CAB Building 8 N 4 L 1 M 73 Pass March 21, 2023 Strobe Zone STROBE CIRCUIT P-4 IN FACP CAB Building 8 N 4 L 1 M 74 Pass
VA WCHCS - Bldg 8 - Audibles - Device List - March 23
EC.02.03.05 EP 4 Every 12 months, the hospital tests visual and audible fire alarms, including speakers and door-releasing devices on the inventory. The results and completion dates are documented.