This is an inspection report documenting the testing of fire safety devices at VA Hospital WCHCS Building 14 conducted by ALARMSpecialists, Inc on March 21, 2023. The report details the testing of multiple fire safety devices including pull stations, heat detectors, speaker/strobes, and strobe zones across different locations in Building 14, specifically in the lower level storage area and first floor incinerator area.
The inspection covered a total of 9 devices: 2 pull stations, 4 heat detectors, 2 speaker/strobes (labeled 49799211 and 49799215), and 1 strobe zone in the chiller room. All devices were tested in accordance with EC.02.03.05 EP 3 and EP 4 requirements for annual testing of fire alarm components. All devices passed their respective tests, with specific device locations and identification numbers documented. The testing was conducted in compliance with the requirement that hospitals must test duct detectors, heat detectors, manual fire alarm boxes, smoke detectors, visual and audible fire alarms, speakers, and door-releasing devices every 12 months.
View the file
Other files for this federal contract opportunity
Show all 27
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Prepared by ALARMSpecialists, Inc
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 1 of 3
Date Tested Device Location No de Lo op Device Status Comments March 21, 2023 Pull Station LOWER LEVEL STORAGE BLDG 14 N 3 L 2 M 2 Pass March 21, 2023 Pull Station 1ST FLR INCINERATOR BLDG 14 N 3 L 2 M 1 Pass
VA Hospital - WCHCS - Bldg 14 - Device List - March 23 EC.02.03.05 EP 3 Every 12 months, the hospital tests duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors on the inventory. The results and completion dates are documented.
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 2 of 3
Date Tested Device Location No de Lo op Device Status Comments March 21, 2023 Heat Detector LOWER LEVEL STORAGE BLDG 14 N 3 L 2 D 1 Pass March 21, 2023 Heat Detector LOWER LEVEL STORAGE BLDG 14 N 3 L 2 D 2 Pass March 21, 2023 Heat Detector 1ST FLR INCINERATOR BLDG 14 N 3 L 2 D 3 Pass March 21, 2023 Heat Detector 1ST FLR INCINERATOR BLDG 14 N 3 L 2 D 4 Pass
EC.02.03.05 EP 3 Every 12 months, the hospital tests duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors on the inventory. The results and completion dates are documented.
VA Hospital - WCHCS - Bldg 14 - Device List - March 23
6786 S Revere Pkwy Suite 110 Centennial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 3 of 3
Date Tested Device Room # / Corridor Location / Description No de Lo op Device Label Status Comments March 21, 2023 Speaker/Strobe Entrance Building 14 N 3 L 2 x x 49799211 Pass March 21, 2023 Strobe Zone BLDG 14 STROBES CHILLER ROOM Building 14 N 3 L 1 M 83 Pass March 21, 2023 Speaker/Strobe Entrance Building 14 N 3 L 2 x x 49799215 Pass
VA WCHCS - Bldg 14 - Audibles - Device List - March 23
EC.02.03.05 EP 4 Every 12 months, the hospital tests visual and audible fire alarms, including speakers and door-releasing devices on the inventory. The results and completion dates are documented.