VA WCHCS Bldg 13 Oneline Report 23.pdf
PDF 55 KB Posted
- Attached to
- H263--Fire Protection Services Federal contract opportunity
- Solicitation number
- 36C25925Q0190
About this file
This is a fire protection system inspection report from March 21, 2023, documenting testing of various safety devices in Building 13 of a VA Hospital (WCHCS). The report, prepared by ALARMSpecialists Inc., details the inspection and testing results of multiple fire safety components including pull stations, smoke detectors, tamper switches, water flow switches, strobe zones, and speaker zones.
The inspection covered four pull stations (at dryer exit, loading dock exit, basement exit, and washers exit), one smoke detector above the FACP, two tamper switches (control valve and breakroom), two water flow switches (main building and breakroom), four strobe circuits, and two speaker zones - all located in Building 13. All devices passed inspection, with specific performance notes including tamper switch turns (3 turns and 1 turn) and water flow response times (33 seconds and 5 seconds). The testing complied with EC.02.03.05 requirements for 12-month testing of fire alarm devices and 6-month testing of water flow devices and valve tamper switches.
View the file
Other files for this federal contract opportunity
Show all 27
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Prepared by ALARMSpecialists, Inc
6786 S Revere Pkwy Suite 110 Centennnial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 1 of 5
Date Tested Device Location No de Lo op Device Status Comments March 21, 2023 Pull Station DRYER EXIT BUILDING 13 N 8 L 1 M 3 Pass March 21, 2023 Pull Station LOADING DOCK EXIT BUILDING 13 N 8 L 1 M 4 Pass March 21, 2023 Pull Station BASEMENT EXIT BUILDING 13 N 8 L 1 M 5 Pass March 21, 2023 Pull Station WASHERS EXIT BUILDING 13 N 8 L 1 M 6 Pass
VA Hospital - WCHCS - Bldg 13 - Device List - March 23 EC.02.03.05 EP 3 Every 12 months, the hospital tests duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors on the inventory. The results and completion dates are documented.
6786 S Revere Pkwy Suite 110 Centennnial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 2 of 5
Date Tested Device Location No de Lo op Device Status Comments March 21, 2023 Smoke Detector SMOKE ABOVE FACP BUILDING 13 N 8 L 1 D 1 Pass
EC.02.03.05 EP 3 Every 12 months, the hospital tests duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors on the inventory. The results and completion dates are documented.
VA Hospital - WCHCS - Bldg 13 - Device List - March 23
6786 S Revere Pkwy Suite 110 Centennnial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 3 of 5
Date Tested DEVICE LOCATION STATUS COMMENTS March 21, 2023 Tamper Switch TAMPER CONTROL VALVE BUILDING 13 N 8 L 1 M 2 Pass 3 Turns March 21, 2023 Tamper Switch TAAMPER BY BREAKROOM BUILDING 13 N 8 L 1 M 22 Pass 1 Turn
VA WCHCS - Bldg 13 - Sprinkler - March 23 EC.02.03.05 EP 2 Every 6 months, the hospital tests vane-type and pressure-type water flow devices and valve tamper switches on the inventory. The results and completion dates are documented.
Note: Mechanical water-flow devices (including, but not limited to, water motor gongs) should be tested quarterly. The results and completion dates are documented.
6786 S Revere Pkwy Suite 110 Centennnial CO 80112 Phone: 303 986-5900 Fax: 866 974-9299 Page 4 of 5
Date Tested DEVICE LOCATION STATUS COMMENTS March 21, 2023 Water Flow Switch WATERFLOW BUILDING 13 N 8 L 1 M 1 Pass 33 SEC March 21, 2023 Water Flow Switch WATERFLOW BY BREAKROOM BLDG 13 N 8 L 1 M 23 Pass 5 SEC
VA WCHCS - Bldg 13 - Sprinkler - March 23 EC.02.03.05 EP 2 Every 6 months, the hospital tests vane-type and pressure-type water flow devices and valve tamper switches on the inventory. The results and completion dates are documented.
Note: Mechanical water-flow devices (including, but not limited to, water motor gongs) should be tested quarterly. The results and completion dates are documented.
8081 E Orchard Road Ste 175 Greenwood Village, CO 80111 Phone: 303 986-5900 Fax: 866 974-9299 Page 5 of 5
Date Tested Device Room # / Corridor Location / Description No de Lo op Device Label Status Comments
March 21, 2023 Strobe Zone STROBE CIRCUIT M-1
IN FACP CAB N 8 L 1 M #
Pass
March 21, 2023 Strobe Zone STROBE CIRCUIT M-2
IN FACP CAB N 8 L 1 M #
Pass
March 21, 2023 Strobe Zone STROBE CIRCUIT M-3
IN FACP CAB N 8 L 1 M #
Pass
March 21, 2023 Strobe Zone STROBE CIRCUIT M-4
IN FACP CAB N 8 L 1 M #
Pass
March 21, 2023 Speaker Zone BLDG 13 SPEAKERS
IN FACP CAB N 8 L 1 M #
Pass
March 21, 2023 Speaker Zone BLDG 13 SPEAKERS
IN FACP CAB N 8 L 1 M #
Pass
VA WCHCS - Bldg 13 - Audibles - Device List - March 23
EC.02.03.05 EP 4 Every 12 months, the hospital tests visual and audible fire alarms, including speakers and door-releasing devices on the inventory. The results and completion dates are documented.
File details come from the government source that posted it. Updated .